E N G I N E E R I N G D A T A CB30M ELITE ® SERIES R−22 Ready − Multi−Position A I R H A N D L E R S Bulletin No. 210106 December 2007 Supersedes July 2007 Nominal Capacity − 1.5 to 5 Tons Optional Electric Heat − 2.5 to 30 kW MODEL NUMBER IDENTIFICATION CB 30 41 - 1 Unit Type CB = Blower / Evaporator Coil Series Nominal Cooling Capacity 21/26 = 1.5 to 2 tons 31 = 2.5 tons 41 = 3 tons 46 = 3.5 tons 51 = 4 tons 65 = 5 tons Minor Revision Number M Configuration M = Multi−Position - Voltage P = 208/230V−60hz−1ph G = 460V−60hz−3ph J = 575V−60hz−3ph P

ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in

Embed Size (px)

Citation preview

Page 1: ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in

E N G I N E E R I N G D A T A

CB30MELITE® SERIES

R−22 Ready − Multi−Position

A I R H A N D L E R S

Bulletin No. 210106

December 2007

Supersedes July 2007

Nominal Capacity − 1.5 to 5 TonsOptional Electric Heat − 2.5 to 30 kW

MODEL NUMBER IDENTIFICATION

CB 30 41− 1

Unit Type

CB = Blower / Evaporator Coil

Series

Nominal Cooling Capacity

21/26 = 1.5 to 2 tons

31 = 2.5 tons

41 = 3 tons

46 = 3.5 tons

51 = 4 tons

65 = 5 tons

Minor Revision Number

M

Configuration

M = Multi−Position

Voltage

P = 208/230V−60hz−1ph

G = 460V−60hz−3ph

J = 575V−60hz−3ph

P

Page 2: ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in

CB30M / Page 2

FEATURES

CONTENTS

Blower Data Pages 6−7. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Dimensions Pages 12−14. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Electric Heat Data Pages 8−11. . . . . . . . . . . . . . . . . . . . . . .

Features Pages 2−4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Installation Clearances Page 4. . . . . . . . . . . . . . . . . . . . . . .

Model Number Identification Page 1. . . . . . . . . . . . . . . . . .

Specifications Page 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Warranty

All covered components − five years in residentialapplications, one year in non-residential applications.Refer to Lennox Limited Warranty Certificate includedwith each unit for additional details.

Approvals

Tested with matching air conditioners and heat pump unitsin the Lennox Research Laboratory environmental testroom in accordance with ARI Standard 210/240.Optional electric heaters are rated in accordance with USDepartment of Energy (DOE) test procedures andFederal Trade Commission (FTC) labeling regulations.Blower performance data according to unit testsconducted in Lennox air test chamber.Air handlers are UL Listed to US and Canadian safetystandards and components within are bonded forgrounding to meet safety standards for servicing requiredby CEC and NEC.ISO 9001 Registered Manufacturing Quality System.

Applications

1.5 to 5 ton nominal sizes.Multi-position (up-flow, down-flow or horizontal)applications. Optional Down−Flow Conversion Kit isavailable for field installation.Applicable to expansion valve systems in coolingapplications and check and expansion valve systems inheat pump applicationsWide range check and expansion valve factory installed.See bulletins in section, Air Conditioners for coolingcapacities.See bulletins in section, Heat Pump Outdoor Units forcooling and heating capacities.

REFRIGERANT SYSTEM

Refrigerant Line ConnectionsSuction (vapor) and liquid lines have sweat connectionsthat extended outside of the cabinet for ease ofconnection.See dimension drawings for locations.

Check and Expansion Valve FurnishedWide range valve with Chatleff style fitting.Factory installed on all models, internal to cabinet.

B

H

F

D

E

C

G

Copper Tube/Enhanced Fin Indoor CoilLennox designed and fabricated twin coils.Assembled in �A" configurationProvides extra large surface and contact area, excellentheat transfer and low air resistance for maximumefficiency.Precise circuiting for uniform refrigerant distribution.Precisely spaced ripple-edged aluminum fins fitted todurable seamless copper tubes.Fins are strengthened to resist bending and are equippedwith collars that grip tubing for maximum contact area.Lanced fins provide maximum exposure of fin surface toair stream.Long life copper tubing easy to service.Rifled tubing provides superior heat transfer.Flared shoulder tubing joints and silver soldering providetight, leakproof joints.Coil thoroughly factory tested under high pressure toinsure leakproof construction.

B

C

D

Page 3: ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in

CB30M / Page 3

FEATURES

Filter

Tool-less access to filter area for quick and easy servicing.Disposable frame type filter furnished and factoryinstalled in rails in cabinet.See Specifications tables for sizes.

BLOWER

Lennox designed and built direct−drive blower.Statically and dynamically balanced before installation inunit.Resiliently mounted multi-speed leadless motor withplug-in connections.Choice of blower speeds. See blower performancetables.Speed changes easily accomplished by a simple wiringchange.Blower slides out of cabinet for servicing.

CONTROLS

Transformer and Blower Cooling Relay24 volt transformer with in−line fuse and blower coolingrelay furnished as standard.Factory installed in the unit control box.Terminal strip furnished.

OPTIONS

ThermostatSee Thermostat bulletins in Controls section and LennoxPrice Book for a complete list of thermostats.

Step−down Transformer (575V Applications)460V−3 phase units can be used in 575V applications.575V electric heaters are shipped with a 575V to 460Vstep−down transformer.If no electric heat is used, order a 575V Step−downTransformer Kit.

Cabinet

Constructed of heavy gauge galvanized steel.Completely insulated with thick fiberglass insulation.Pre-painted steel cabinets have mildly textured enamelfinish with primer coat on unpainted side of all panels.Units are shipped in one piece but may be disassembledinto two separate sections for ease of installation in tightapplications. See dimension drawings.Thick rubber gasket between sections provides air tight seal.No external screw heads on sides of cabinet for tightinstallations without damage to walls or woodwork.Removable panels provide complete service access.Electrical inlets provided in sides and top of cabinet. Seedimension drawings for locations.

Multi-Position CapabilityShipped for up-flow and horizontal right−hand discharge.Quickly converted to down-flow or left−hand, horizontal airdischarge.Optional Kit required for conversion to down−flow.

Drain PansDrain pans designed for up-flow, down-flow or horizontalapplications.Deep, corrosion resistant plastic drain pans have dual pipedrains.See dimension drawings.

OPTIONS

Down-Flow Additive Base (Down−Flow Only)Additive base required for models with electric heatinstalled in down-flow position on combustible floors.

Down−Flow Conversion KitRequired for field conversion to down−flow position. Kitconsists of drip shields and 2 brackets for repositioningcoil and drain pan. See Specifications table.

Horizontal Support Frame KitProvides support of unit in horizontal applications.Consists of (2) 1 x 1-1/2 x 32-5/8 in. and (2) 1 x 3 x 53-7/8in. painted heavy gauge cold rolled steel support channelswith assembly and suspending holes.Bolts and nuts furnished for field assembly.Suspending rods must be field provided.

Side Return Unit Stand (Up-Flow Only)Raises unit 16 in. above floor for side return air ductconnection.Eliminates need for wooden platform construction.All aluminum construction.Two adjustable frames fit all sizes.

Wall Hanging Bracket Kit (Up-Flow Only)Allows unit to be hung on wall at any height.Consists of heavy−gauge steel support brackets (one forair handler, one for wall mount).Screws furnished for fastening one bracket to unit.Bolts for fastening one bracket to wall are field provided.

E

F

G

Page 4: ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in

CB30M / Page 4

FEATURES

OPTIONAL Electric Heat

Field install internal to unit cabinet.Available in several voltages and kw sizes. See Electric Heattables.Helix wound nichrome heating elements exposed directlyin air stream resulting in instant heat transfer, low elementtemperatures and long service life.Each element equipped with accurately located limitcontrol with fixed temperature off setting and automaticreset.Supplemental thermal cutoff limit control, providespositive protection in case of excessive temperatures.Thermal sequencer relay brings elements on and off line,in sequence and equal increments, with time delaybetween each. Initiates and terminates blower operation.Heating control relay(s) furnished as standard.Control box and access cover constructed of heavy gaugegalvanized steel.Factory assembled with controls installed and wired.Electric heat low voltage controls plug-in to blower coilunit.

Circuit Breaker ModelsECB29-5CB, −6CB, -8CB, −9CB, -10CB, -12.5CB, -15CB,-20CB, -25CB and -30CB (208/240v-1ph) andECB29-15CB, -20CB and -25CB (208/240v-3ph) heatersare equipped with circuit breakers for overload and shortcircuit protection.Factory wired and mounted on electric heat unit.Current sensitive and temperature actuated.Manual reset.Circuit breakers qualify as disconnect means at unit inmany areas, eliminate the need for field provideddisconnect.Consult local electrical code in your area.

EvenHeater� ModelsElectric heat is staged to provide supplemental heat tomeet desired comfort levels.EHC control board stages the heat on and off based on thedemand of the provided (field installed) supply plenumthermistor.Temperature set point (85, 100, 115 or 130°F) is selected byuse of a jumper pin on the EHC control board.ECB29EH-9CB, -12.5CB, -15CB and -20CB heaters areequipped with circuit breakers for overload and short circuitprotection.Factory provided and field mounted in electric heat unit.Current sensitive and temperature actuated.Manual reset.Circuit breakers qualify as disconnect means at unit inmany areas, eliminate the need for field provideddisconnect.Consult local electrical code in your area.

OPTIONS

Circuit Breaker Cover KitFlexible plastic cover protects circuit breaker.Recommended in areas with high humidity to preventnuisance tripping.

Single-Point Power Source Control BoxControl Box may be used with optional electric heat whensingle power supply is connected to multi−circuit electricheat.Field installs external to the unit cabinet on either side or top.Constructed of heavy gauge steel, baked enamel finish,prepunched mounting holes, electrical inlet knockouts, andterminal strip.Removeable cover provides easy access.Dimensions (H x W x D) − 7 x 7 x 4 in.

INSTALLATION CLEARANCES

Cabinet 0 inch (0 mm)

Plenum and Outlet duct on blower/coil units 1 inch (25 mm)

Plenum and Warm air duct within 3 feet (914mm) of cabinet 1 inch (25 mm)

Floor 1 Combustible1 When unit is installed in the down-flow position with electric heat on a combustible floor, an optional down−flow base is required.

H

Page 5: ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in

CB30M / Page 5

SPECIFICATIONS

GeneralD t

Model Number CB30M-21/26 CB30M-31 CB30M-41 CB30M-46 CB30M-51 CB30M-65Data

Nominal tonnage 1.5 − 2 2.5 3 3.5 4 5

Refrigerant R−22 R−22 R−22 R−22 R−22 R−22

Connectionsin

Suction (vapor) line (o.d.) − sweat 5/8 3/4 3/4 7/8 7/8 1-1/8in.

Liquid line (o.d.) − sweat 3/8 3/8 3/8 3/8 3/8 3/8

Condensate − fpt (2) 3/4 (2) 3/4 (2) 3/4 (2) 3/4 (2) 3/4 (2) 3/4

EvaporatorCoil

Net face area − ft.2 3.56 4.44 5.0 5.0 7.22 7.22Coil

Tube outside diameter − in. 3/8 3/8 3/8 3/8 3/8 3/8

Number of rows 3 3 3 3 3 3

Fins per inch 12 12 12 12 12 12

Blower Wheel nom. diameter x width − in. 10 x 7 10 x 8 11 x 8 11 x 8 11-1/2 x 9 12 x 9

Blower motor output − hp 1/5 1/3 1/3 1/3 1/3 1/2

1 Filters Size of filter − in. 15 �x �20 �x� 1 20 x 20 x 1 20 x 20 x 1 20 x 20 x 1 20 x 24 x 1 20 x 24 x 1

Shipping Data −1 package − lbs. 136 157 177 181 206 206

ELECTRICAL DATA

Voltage − 1phase − 60hz 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V

Voltage − 3phase − 60hz − − − − − − 2 460V − − − 2 460V 2 460V

3 Maximum overcurrent protection (unit only)all voltages

15 15 15 15 15 15

Minimum circuit ampacity (unit only) − 208/230V 2 2 2 3 3 5

460V − − − − − − 2 − − − 2 3

Optional Accessories − Must Be Ordered Extra

Circuit Breaker Cover Kit 93M85 93M85 93M85 93M85 93M85 93M85

Down-Flow Combustible Base 34J72 34J73 34J73 34J73 34J73 34J73

Down-Flow Conversion Kit 83M57 83M57 83M57 83M57 83M57 83M57

Electric Heat − See Electric Heat Data tables 2.5 to 20 kW 5 to 30 kW

Horizontal Support Frame Kit 56J18 56J18 56J18 56J18 56J18 56J18

Side Return Unit Stand (Up-Flow) 45K31 45K32 45K32 45K32 45K32 45K32

Single Point Power Source Control Box 21H39 21H39 21H39 21H39 21H39 21H39

Step−Down Transformer Kit (575V applications) − − − − − − 66K90 − − − 66K90 66K90

Wall Hanging Bracket Kit (Up−Flow Only) 45K30 45K30 45K30 45K30 45K30 45K301 Disposable frame type filter.2 Blower motor is 460V − 1 phase. Optional electric heat is 460V − 3 phase.3 HACR type circuit breaker or fuse.

Page 6: ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in

CB30M / Page 6

BLOWER DATA

CB30M-21/26 BLOWER PERFORMANCE (208/230V)

ExternalSt ti

Air Volume & Motor Watts at Specific Blower TapsExternalStatic

Pressure High Medium LowPressure− in. w.g. cfm Watts cfm Watts cfm Watts

.00 1030 365 895 300 700 245

.05 1015 360 890 295 695 245

.10 1000 355 875 290 690 240

.15 980 345 860 285 680 235

.20 960 340 845 280 665 230

.25 935 335 825 275 650 220

.30 910 325 800 265 635 215

.40 850 310 745 250 590 205

.50 780 295 685 235 535 190

.60 705 280 605 220 470 175

.70 615 265 520 200 395 165

.75 565 255 475 195 350 155

CB30M-31 BLOWER PERFORMANCE (208/230V)

ExternalSt ti

Air Volume & Motor Watts at Specific Blower TapsExternalStatic

Pressure High Medium LowPressure− in. w.g. cfm Watts cfm Watts cfm Watts

.00 1290 385 1175 335 1045 315

.05 1295 380 1190 330 1075 310

.10 1290 375 1190 325 1085 300

.15 1265 370 1175 320 1085 295

.20 1230 360 1145 310 1065 285

.25 1180 350 1105 295 1030 270

.30 1115 335 1045 280 980 255

.40 945 305 890 250 830 220

.50 720 275 675 215 615 190

.60 440 240 405 185 335 160

NOTE − All air data is measured external to unit with air filter in place with bottom return air.Electric heaters have no appreciable air resistance.

CB30M-41 BLOWER PERFORMANCE (208/230V)

ExternalSt ti

Air Volume & Motor Watts at Specific Blower TapsExternalStatic

Pressure High Medium LowPressure− in. w.g. cfm Watts cfm Watts cfm Watts

.00 1525 505 1120 390 915 335

.05 1520 495 1150 385 965 330

.10 1510 480 1170 380 1005 325

.15 1495 470 1180 375 1035 320

.20 1475 455 1190 370 1055 320

.25 1450 440 1185 360 1060 310

.30 1415 430 1175 350 1050 300

.40 1335 400 1135 325 1005 290

.50 1230 375 1060 300 915 255

.60 1100 345 960 280 775 230

.70 950 320 830 255 590 205

.75 870 305 750 245 485 195

CB30M-41 BLOWER PERFORMANCE (460V−1ph)

ExternalSt ti

Air Volume & Motor Watts at Specific Blower TapsExternalStatic

Pressure High LowPressure− in. w.g. cfm Watts cfm Watts

.00 1525 505 1120 390

.05 1520 495 1150 385

.10 1510 480 1170 380

.15 1495 470 1180 375

.20 1475 455 1190 370

.25 1450 440 1185 360

.30 1415 430 1175 350

.40 1335 400 1135 325

.50 1230 375 1060 300

.60 1100 345 960 280

.70 950 320 830 255

.75 870 305 750 245

NOTE − All air data is measured external to unit with air filter in place with bottom return air.Electric heaters have no appreciable air resistance.

CB30M-46 BLOWER PERFORMANCE (208/230V)

ExternalSt ti

Air Volume & Motor Watts at Specific Blower TapsExternalStatic

Pressure High Medium LowPressure− in. w.g. cfm Watts cfm Watts cfm Watts

.00 1825 565 1600 455 1325 370

.05 1790 555 1585 455 1335 370

.10 1750 540 1565 450 1335 370

.15 1710 530 1540 440 1330 365

.20 1660 520 1505 435 1320 360

.25 1610 505 1470 425 1300 355

.30 1555 495 1425 415 1270 350

.40 1430 465 1320 390 1195 330

.50 1290 440 1195 365 1090 310

.60 1135 415 1050 335 955 285

.70 965 385 875 310 795 260

.75 875 370 780 295 700 250

NOTE − All air data is measured external to unit with air filter in place with bottom return air.Electric heaters have no appreciable air resistance.

Page 7: ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in

CB30M / Page 7

BLOWER DATA

CB30M-51 BLOWER PERFORMANCE (208/230V)

ExternalSt ti

Air Volume & Motor Watts at Specific Blower TapsExternalStatic

Pressure High Medium LowPressure− in. w.g. cfm Watts cfm Watts cfm Watts

.00 1910 590 1785 520 1475 430

.05 1895 585 1770 515 1480 430

.10 1870 580 1750 510 1475 425

.15 1840 570 1720 500 1465 420

.20 1800 565 1685 490 1445 410

.25 1755 550 1645 480 1415 405

.30 1700 540 1600 465 1380 395

.40 1580 515 1485 440 1290 370

.50 1425 485 1350 410 1170 345

.60 1250 450 1190 380 1020 320

.70 1045 415 1000 350 840 295

.75 930 400 900 335 740 280

CB30M-51 BLOWER PERFORMANCE (460V − 1 ph)

ExternalSt ti

Air Volume & Motor Watts at Specific Blower TapsExternalStatic

Pressure High LowPressurein. w.g. cfm Watts cfm Watts

.00 1870 610 1775 530

.05 1875 610 1775 530

.10 1870 590 1765 515

.15 1850 585 1750 510

.20 1825 575 1720 500

.25 1790 560 1685 490

.30 1745 545 1645 480

.40 1625 505 1530 450

.50 1465 470 1380 420

.60 1270 425 1195 385

.70 1030 385 975 350

.80 755 340 720 320

NOTE − All air data is measured external to unit with air filter in place with bottom return air.Electric heaters have no appreciable air resistance.

CB30M-65 BLOWER PERFORMANCE (208/230V)

ExternalSt ti

Air Volume & Motor Watts at Specific Blower TapsExternalStatic

Pressure High Medium LowPressure− in. w.g. cfm Watts cfm Watts cfm Watts

.00 2115 780 2025 670 1775 585

.05 2100 770 2010 665 1775 590

.10 2085 765 1995 655 1770 580

.15 2060 750 1975 645 1760 570

.20 2030 740 1950 635 1745 560

.25 2000 730 1915 625 1725 550

.30 1960 715 1880 610 1695 535

.40 1870 685 1795 580 1630 505

.50 1755 655 1690 545 1540 475

.60 1620 625 1560 515 1425 440

.70 1465 590 1415 480 1295 410

.80 1290 560 1250 445 1140 375

.85 1195 545 1160 425 1050 360

CB30M-65 BLOWER PERFORMANCE (460V − 1 ph)

ExternalSt ti

Air Volume & Motor Watts at Specific Blower TapsExternalStatic

Pressure High LowPressurein. w.g. cfm Watts cfm Watts

.00 2140 795 1965 710

.05 2110 780 1950 700

.10 2080 765 1930 685

.15 2045 755 1910 675

.20 2005 740 1880 660

.25 1965 725 1850 645

.30 1920 710 1815 630

.40 1820 680 1735 600

.50 1710 650 1635 570

.60 1585 615 1520 540

.70 1450 585 1390 505

.80 1305 550 1245 475

.85 1225 535 1165 460

NOTE − All air data is measured external to unit with air filter in place with bottom return air.Electric heaters have no appreciable air resistance.

Page 8: ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in

CB30M / Page 8

CB30M−21/26 AND cb30m−31 − ELECTRIC HEAT DATA

SINGLE PHASE ELECTRIC HEAT CB30M−21/26 CB30M−31

Input

2 BlowerMotorFull

3 MinimumCircuit

5 MaximumOvercurrent

2 BlowerMotorFull

Load

3 MinimumCircuit

Ampacity

5 MaximumOvercurrentProtection

No.of Volts kW 1 Btuh

FullLoadA

CircuitAmpacity

OvercurrentProtection

LoadAmps Circuit Circuit

Model Numberof

StagesVolts kW 1 Btuh Amps

p y Amps1 2 1 2

2.5 kW4 lbs

ECB29-2.5 (28K30) 1 208 1.9 6,400 1.5 13 154 lbs.

220 2.1 7,200 1.5 15 15Not Available

230 2.3 7,800 1.5 15 15Not Available

240 2.5 8,500 1.5 15 15

5 kW4 lbs

ECB29-5 (28K31)Terminal Block

1 208 3.8 12,800 1.5 24 4 25 1.73 25 − − − 4 25 − − −4 lbs. Terminal Block

ECB29-5CB (28K32)30A Circuit breaker

220 4.2 14,300 1.5 28 30 1.73 28 − − − 30 − − −( )30A Circuit breaker

230 4.6 15,700 1.5 28 30 1.73 28 − − − 30 − − −

240 5.0 17,100 1.5 28 30 1.73 28 − − − 30 − − −

6 kW4 lbs

ECB29-6 (47L22)Terminal Block

1 208 4.5 15,400 1.5 29 4 30 1.73 30 − − − 4 30 − − −4 lbs. Terminal Block

ECB29-6CB (47L23)35A Circuit breaker

220 5.0 17,100 1.5 33 35 1.73 33 − − − 35 − − −( )35A Circuit breaker

230 5.5 18,800 1.5 33 35 1.73 33 − − − 35 − − −

240 6.0 20,500 1.5 33 35 1.73 33 − − − 35 − − −

8 kW5 lbs

ECB29-8 (28K33)Terminal Block

1 208 6.0 20,500 1.5 38 4 40 1.73 38 − − − 4 40 − − −5 lbs. Terminal Block

ECB29-8CB (28K34)45A Circuit breaker

220 6.7 22,900 1.5 44 45 1.73 44 − − − 45 − − −( )45A Circuit breaker

230 7.3 25,100 1.5 44 45 1.73 44 − − − 45 − − −

240 8.0 27,300 1.5 44 45 1.73 44 − − − 45 − − −

9 kW5 lbs

ECB29-9CB (10L11)50A Circuit breaker

2 208 6.8 23,100 1.5 42 4 45 1.73 43 − − − 4 45 − − −5 lbs. 50A Circuit breaker

ECB29EH-9CB (91K67)50A Circuit breaker

220 7.6 25,800 1.5 49 50 1.73 49 − − − 50 − − −( )50A Circuit breaker

230 8.3 28,200 1.5 49 50 1.73 49 − − − 50 − − −

240 9.0 30,700 1.5 49 50 1.73 49 − − − 50 − − −

10 kW6 lbs

ECB29-10 (28K35)Terminal Block

2 208 7.5 25,600 1.5 47 4 50 1.73 47 − − − 4 50 − − −6 lbs. Terminal Block

ECB29-10CB (28K36)60A Circuit breaker

220 8.4 28,700 1.5 54 60 1.73 54 − − − 60 − − −( )60A Circuit breaker

230 9.2 31,400 1.5 54 60 1.73 54 − − − 60 − − −

240 10.0 34,100 1.5 54 60 1.73 54 − − − 60 − − −

12.5 kW10 lbs

ECB29-12.5CB (28K37)(1) 25A & (1) 50A Circuit breaker

2 208 7.5 25,600 1.73 21 31 25 4 4510 lbs. (1) 25A & (1) 50A Circuit breaker

ECB29EH-12.5CB (91K68)(1) 25A & (1) 50A Circuit breaker

220 8.4 28,700Not Available

1.73 24 35 25 50( )(1) 25A & (1) 50A Circuit breaker

230 9.2 31,400Not Available

1.73 24 35 25 50

240 10.0 34,100 1.73 24 35 25 50

15 kW12 lbs

ECB29-15CB (28K38)(1) 30A & (1) 60A Circuit breaker

2 208 11.3 38,400 1.73 24 37 4 25 4 5012 lbs. (1) 30A & (1) 60A Circuit breaker

ECB29EH-15CB (91K69)(1) 30A & (1) 60A Circuit breaker

220 12.6 43,000Not Available

1.73 28 42 30 60( )(1) 30A & (1) 60A Circuit breaker

230 13.8 47,000Not Available

1.73 28 42 30 60

240 15.0 51,200 1.73 28 42 30 60

NOTE − Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.1 Electric heater capacity only � does not include additional blower motor heat capacity.2 Amps shown are for blower motor only.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F (75�C).4 Bold text indicates that the circuit breaker on �CB" circuit breaker models must be replaced with size noted.5 HACR type circuit breaker or fuse.

Page 9: ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in

CB30M / Page 9

CB30M−41 AND CB30M−46 ELECTRIC HEAT DATA

SINGLE PHASE ELECTRIC HEAT CB30M−41 CB30M−46

Input

2 BlowerMotorFull

3 MinimumCircuit

Ampacity

5 MaximumOvercurrentProtection

2 BlowerMotorFull

Load

3 MinimumCircuit

Ampacity

5 MaximumOvercurrentProtection

No.of Volts kW 1 Btuh

FullLoadA

Circuit CircuitLoadAmps Circuit Circuit

Model Numberof

StagesVolts kW 1 Btuh Amps

1 2 1 2Amps

1 2 1 2

5 kW4 lbs

ECB29-5 (28K31)T i l Bl k

1 208 3.8 12,800 1.72 25 − − − 4 25 − − − 2.4 26 − − − 30 − − −4 lbs.

( )Terminal Block

ECB29 5CB (28K32)220 4.2 14,300 1.72 28 − − − 30 − − − 2.4 29 − − − 30 − − −

ECB29-5CB (28K32)30A Circuit breaker

230 4.6 15,700 1.72 28 − − − 30 − − − 2.4 29 − − − 30 − − −30A Circuit breaker

240 5.0 17,100 1.72 28 − − − 30 − − − 2.4 29 − − − 30 − − −

6 kW4 lbs

ECB29-6 (47L22)T i l Bl k

1 208 4.5 15,400 1.72 30 − − − 4 30 − − − 2.4 30 − − − 4 30 − − −4 lbs.

( )Terminal Block

ECB29 6CB (47L23)220 5.0 17,100 1.72 33 − − − 35 − − − 2.4 34 − − − 35 − − −

ECB29-6CB (47L23)35A Circuit breaker

230 5.5 18,800 1.72 33 − − − 35 − − − 2.4 34 − − − 35 − − −35A Circuit breaker

240 6.0 20,500 1.72 33 − − − 35 − − − 2.4 34 − − − 35 − − −

8 kW5 lbs

ECB29-8 (28K33)T i l Bl k

1 208 6.0 20,500 1.72 38 − − − 4 40 − − − 2.4 40 − − − 4 40 − − −5 lbs.

( )Terminal Block

ECB29 8CB (28K34)220 6.7 22,900 1.72 44 − − − 45 − − − 2.4 45 − − − 45 − − −

ECB29-8CB (28K34)45A Circuit breaker

230 7.3 25,100 1.72 44 − − − 45 − − − 2.4 45 − − − 45 − − −45A Circuit breaker

240 8.0 27,300 1.72 44 − − − 45 − − − 2.4 45 − − − 45 − − −

9 kW5 lbs

ECB29-9CB (10L11)50A Ci it b k

2 208 6.8 25,600 1.72 43 − − − 4 45 − − − 2.4 44 − − − 4 45 − − −5 lbs.

( )50A Circuit breaker

ECB29EH 9CB (91K67)220 7.6 28,700 1.72 49 − − − 50 − − − 2.4 50 − − − 50 − − −

ECB29EH-9CB (91K67)50A Circuit breaker

230 8.3 31,400 1.72 49 − − − 50 − − − 2.4 50 − − − 50 − − −50A Circuit breaker

240 9.0 34,100 1.72 49 − − − 50 − − − 2.4 50 − − − 50 − − −

10 kW6 lbs

ECB29-10 (28K35)T i l Bl k

2 208 7.5 25,600 1.72 47 − − − 4 50 − − − 2.4 48 − − − 4 50 − − −6 lbs.

( )Terminal Block

ECB29 10CB (28K36)220 8.4 28,700 1.72 54 − − − 60 − − − 2.4 55 − − − 60 − − −

ECB29-10CB (28K36)60A Circuit breaker

230 9.2 31,400 1.72 54 − − − 60 − − − 2.4 55 − − − 60 − − −60A Circuit breaker

240 10.0 34,100 1.72 54 − − − 60 − − − 2.4 55 − − − 60 − − −

12.5 kW10 lbs

ECB29-12.5CB (28K37)(1) 25A & (1) 50A Ci it b k

2 208 9.4 32,000 1.72 21 31 25 4 45 2.4 22 31 25 4 4510 lbs.

( )(1) 25A & (1) 50A Circuit breaker

ECB29EH 12 5CB (91K68)220 10.5 35,800 1.72 24 35 25 50 2.4 25 35 25 50

ECB29EH-12.5CB (91K68)(1) 25A & (1) 50A Circuit breaker

230 11.5 39,200 1.72 24 35 25 50 2.4 25 35 25 50(1) 25A & (1) 50A Circuit breaker

240 12.5 42,600 1.72 24 35 25 50 2.4 25 35 25 50

15 kW12 lbs

ECB29-15CB (28K38)(1) 30A & (1) 60A Ci it B k

2 208 11.3 38,400 1.72 24 37 4 25 4 50 2.4 26 37 30 4 5012 lbs.

( )(1) 30A & (1) 60A Circuit Breaker

ECB29EH 15CB (91K69)220 12.6 43,000 1.72 28 42 30 60 2.4 29 42 30 60

ECB29EH-15CB (91K69)(1) 30A & (1) 60A Circuit Breaker

230 13.8 47,000 1.72 28 42 30 60 2.4 29 42 30 60(1) 30A & (1) 60A Circuit Breaker

240 15.0 51,200 1.72 28 42 30 60 2.4 29 42 30 60

20 kW19 lbs

ECB29-20CB (11L31)(1) 50A & (1) 60A Ci it B k

2 208 15.0 51,200 1.72 44 41 4 45 60 2.4 45 41 4 45 6019 lbs.

( )(1) 50A & (1) 60A Circuit Breaker

ECB29EH 20CB (91K70)220 16.8 57,300 1.72 49 46 50 60 2.4 50 46 50 60

ECB29EH-20CB (91K70)(1) 50A & (1) 60A Circuit Breaker

230 18.4 62,700 1.72 49 46 50 60 2.4 50 46 50 60(1) 50A & (1) 60A Circuit Breaker

240 20.0 68,200 1.72 49 46 50 60 2.4 50 46 50 60

THREE PHASE ELECTRIC HEAT CB30M−41 CB30M−468 kW5 lbs

ECB29-8 (28K42)T i l Bl k

1 208 6.0 20,500 1.72 23 − − − 25 − − − 2.4 24 − − − 25 − − −5 lbs.

( )Terminal Block 220 6.7 22,900 1.72 26 − − − 30 − − − 2.4 27 − − − 30 − − −

230 7.3 25,100 1.72 26 − − − 30 − − − 2.4 27 − − − 30 − − −

240 8.0 27,300 1.72 26 − − − 30 − − − 2.4 27 − − − 30 − − −

10 kW6 lbs

ECB29-10 (28K43)T i l Bl k

1 208 7.5 25,600 1.72 28 − − − 30 − − − 2.4 29 − − − 30 − − −6 lbs.

( )Terminal Block 220 8.4 28,700 1.72 32 − − − 35 − − − 2.4 33 − − − 35 − − −

230 9.2 31,400 1.72 32 − − − 35 − − − 2.4 33 − − − 35 − − −

240 10.0 34,100 1.72 32 − − − 35 − − − 2.4 33 − − − 35 − − −

ECB29-10 (28K47)(3) 20A F

1 440 8.4 28,700 1.1 16 − − − 20 − − −( )(3) 20A Fuses 460 9.2 31,400 1.1 16 − − − 20 − − − Not Available

480 10.0 34,100 1.1 16 − − − 20 − − −

Not Available

15 kW12 lbs

ECB29-15CB (28K44)(1) 50A Ci it b k

1 208 11.3 38,400 1.72 41 − − − 4 45 − − − 2.4 42 − − − 4 45 − − −12 lbs.

( )(1) 50A Circuit breaker 220 12.6 43,000 1.72 47 − − − 50 − − − 2.4 48 − − − 50 − − −

230 13.5 47,000 1.72 47 − − − 50 − − − 2.4 48 − − − 50 − − −

240 15.0 51,200 1.72 47 − − − 50 − − − 2.4 48 − − − 50 − − −

ECB29-15 (28K48)(3) 25A F

1 440 12.6 43,000 1.1 24 − − − 30 − − −( )(3) 25A Fuses 460 13.8 47,000 1.1 24 − − − 30 − − − Not Available

480 15.0 51,200 1.1 24 − − − 30 − − −

Not Available

20 kW19 lb

ECB29-20CB (28K45)(2) 35A Circuit breaker

2 208 15.0 51,200 1.72 28 21 4 30 4 30 2.4 29 21 4 30 4 3019 lbs.

( )(2) 35A Circuit breaker 220 16.8 57,300 1.72 32 24 35 35 2.4 33 24 35 35

230 18.4 62,700 1.72 32 24 35 35 2.4 33 24 35 35

240 20.0 68,200 1.72 32 24 35 35 2.4 33 24 35 35

NOTE − Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.1 Electric heater capacity only � does not include additional blower motor heat capacity.2 Amps shown are for blower motor only.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F (75�C).4 Bold text indicates that the circuit breaker on �CB" circuit breaker models must be replaced with size noted.5 HACR type circuit breaker or fuse.

Page 10: ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in

CB30M / Page 10

CB30M−51 AND CB30M−65 ELECTRIC HEAT DATA

SINGLE PHASE ELECTRIC HEAT CB30M−51 CB30M−65

No. ofSt

2 BlowerMotorFull

3 MinimumCircuit

Ampacity

5 MaximumOvercurrentProtection

2 BlowerMotorFull

3 MinimumCircuit

Ampacity

5 MaximumOvercurrentProtection

StagesInput

FullLoadA

Circuit CircuitFull

LoadAmps

Circuit Circuit

Model Number Volts kW 1 BtuhAmps

1 2 3 1 2 3Amps

1 2 3 1 2 3

5 kW4 lb

ECB29-5 (28K31)T i l Bl k

1 208 3.8 12,800 2.4 26 − − − − − − 30 − − − − − − 3.9 27 − − − − − − 30 − − − − − −4 lbs.

( )Terminal Block

ECB29-5CB (28K32) 220 4.2 14,300 2.4 29 − − − − − − 30 − − − − − − 3.9 31 − − − − − − 35 − − − − − −ECB29-5CB (28K32)30A Circuit breaker 230 4.6 15,700 2.4 29 − − − − − − 30 − − − − − − 3.9 31 − − − − − − 35 − − − − − −

240 5.0 17,100 2.4 29 − − − − − − 30 − − − − − − 3.9 31 − − − − − − 35 − − − − − −

6 kW4 lb

ECB29-6 (47L22)T i l Bl k

1 208 4.5 15,400 2.4 30 − − − − − − 4 30 − − − − − − 3.9 31 − − − − − − 35 − − − − − −4 lbs.

( )Terminal Block

ECB29-6CB (47L23) 220 5.0 17,100 2.4 34 − − − − − − 35 − − − − − − 3.9 36 − − − − − − 40 − − − − − −ECB29-6CB (47L23)35A Circuit breaker 230 5.5 18,800 2.4 34 − − − − − − 35 − − − − − − 3.9 36 − − − − − − 40 − − − − − −

240 6.0 20,500 2.4 34 − − − − − − 35 − − − − − − 3.9 36 − − − − − − 40 − − − − − −

8 kW5 lb

ECB29-8 (28K33)T i l Bl k

1 208 6.0 20,500 2.4 40 − − − − − − 4 40 − − − − − − 3.9 40 − − − − − − 4 40 − − − − − −5 lbs.

( )Terminal Block

ECB29-8CB (28K34) 220 6.7 22,900 2.4 45 − − − − − − 45 − − − − − − 3.9 47 − − − − − − 50 − − − − − −ECB29-8CB (28K34)45A Circuit breaker 230 7.3 25,100 2.4 45 − − − − − − 45 − − − − − − 3.9 47 − − − − − − 50 − − − − − −

240 8.0 27,300 2.4 45 − − − − − − 45 − − − − − − 3.9 47 − − − − − − 50 − − − − − −

9 kW5 lb

ECB29-9CB (10L11)50A Ci it b k

2 208 6.8 25,600 2.4 44 − − − − − − 4 45 − − − − − − 3.9 45 − − − − − − 4 45 − − − − − −5 lbs.

( )50A Circuit breaker

ECB29EH-9CB (91K67) 220 7.6 28,700 2.4 50 − − − − − − 50 − − − − − − 3.9 52 − − − − − − 60 − − − − − −ECB29EH-9CB (91K67)50A Circuit breaker 230 8.3 31,400 2.4 50 − − − − − − 50 − − − − − − 3.9 52 − − − − − − 60 − − − − − −

240 9.0 34,100 2.4 50 − − − − − − 50 − − − − − − 3.9 52 − − − − − − 60 − − − − − −

10 kW6 lb

ECB29-10 (28K35)T i l Bl k

2 208 7.5 25,600 2.4 48 − − − − − − 4 50 − − − − − − 3.9 51 − − − − − − 60 − − − − − −6 lbs.

( )Terminal Block

ECB29-10CB (28K36) 220 8.4 28,700 2.4 55 − − − − − − 60 − − − − − − 3.9 57 − − − − − − 60 − − − − − −ECB29-10CB (28K36)60A Circuit breaker 230 9.2 31,400 2.4 55 − − − − − − 60 − − − − − − 3.9 57 − − − − − − 60 − − − − − −

240 10.0 34,100 2.4 55 − − − − − − 60 − − − − − − 3.9 57 − − − − − − 60 − − − − − −

12.5 kW10 lb

ECB29-12.5CB (28K37)(1) 25A & (1) 50A Ci it b k

2 208 9.4 32,000 2.4 22 31 − − − 25 4 45 − − − 3.9 23 31 − − − 25 4 45 − − −10 lbs.

( )(1) 25A & (1) 50A Circuit breaker

ECB29EH-12.5CB (91K68) 220 10.5 35,800 2.4 25 35 − − − 25 50 − − − 3.9 27 35 − − − 30 50 − − −ECB29EH-12.5CB (91K68)(1) 25A & (1) 50A Circuit breaker 230 11.5 39,200 2.4 25 35 − − − 25 50 − − − 3.9 27 35 − − − 30 50 − − −

240 12.5 42,600 2.4 25 35 − − − 25 50 − − − 3.9 27 35 − − − 30 50 − − −

15 kW12 lb

ECB29-15CB (28K38)(1) 30A & (1) 60A Ci it b k

2 208 11.3 38,400 2.4 26 37 − − − 30 4 50 − − − 3.9 27 37 − − − 30 4 50 − − −12 lbs.

( )(1) 30A & (1) 60A Circuit breaker

ECB29EH-15CB (91K69) 220 12.6 43,000 2.4 29 42 − − − 30 60 − − − 3.9 31 42 − − − 35 60 − − −ECB29EH-15CB (91K69)(1) 30A & (1) 60A Circuit breaker 230 13.5 47,000 2.4 29 42 − − − 30 60 − − − 3.9 31 42 − − − 35 60 − − −

240 15.0 51,200 2.4 29 42 − − − 30 60 − − − 3.9 31 42 − − − 35 60 − − −

20 kW19 lb

ECB29-20CB (11L31)(1) 50A & (1) 60A Ci it b k

2 208 15.0 51,200 2.4 45 41 − − − 4 45 60 − − − 3.9 46 41 − − − 50 60 − − −19 lbs.

( )(1) 50A & (1) 60A Circuit breaker

ECB29EH-20CB (91K70) 220 16.8 57,300 2.4 50 46 − − − 50 60 − − − 3.9 52 46 − − − 60 60 − − −ECB29EH-20CB (91K70)(1) 50A & (1) 60A Circuit breaker 230 18.4 62,700 2.4 50 46 − − − 50 60 − − − 3.9 52 46 − − − 60 60 − − −

240 20.0 68,200 2.4 50 46 − − − 50 60 − − − 3.9 52 46 − − − 60 60 − − −

25 kW19 lb

ECB29-25CB (28K40)(3) 50A Ci it b k

3 208 18.8 64,100 2.4 40 31 31 4 40 4 45 4 45 3.9 42 31 31 4 45 4 45 4 4519 lbs.

( )(3) 50A Circuit breakers

220 21.0 71,700 2.4 47 35 35 50 50 50 3.9 48 35 35 50 50 50

230 23.0 78,300 2.4 47 35 35 50 50 50 3.9 48 35 35 50 50 50

240 25.0 85,300 2.4 47 35 35 50 50 50 3.9 48 35 35 50 50 50

30 kW19 lb

ECB29-30CB (28K41)(3) 60A Ci it b k

3 208 22.5 76,900 3.9 51 37 37 60 4 50 4 5019 lbs.

( )(3) 60A Circuit breakers

220 25.2 86,000Not Available

3.9 56 42 42 60 60 60

230 27.5 94,000Not Available

3.9 56 42 42 60 60 60

240 30.0 102,400 3.9 56 42 42 60 60 60

NOTE − Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.1 Electric heater capacity only � does not include additional blower motor heat capacity.2 Amps shown are for blower motor only.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F (75�C).4 Bold text indicates that the circuit breaker on �CB" circuit breaker models must be replaced with size noted.5 HACR type circuit breaker or fuse.

Page 11: ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in

CB30M / Page 11

CB30M−51 AND CB30M−65 ELECTRIC HEAT DATA

THREE PHASE ELECTRIC HEAT CB30M−51 CB30M−65

No. ofStages

Input2 Blower

MotorFull

3 MinimumCircuit

Ampacity

7 MaximumOvercurrentProtection

2 BlowerMotor

Full Load

3 MinimumCircuit

Ampacity

7 MaximumOvercurrentProtection

StagesVolts kW 1 Btuh

FullLoadA

Circuit CircuitFull Load

Amps Circuit Circuit

Model NumberVolts kW 1 Btuh Amps 1 2 1 2

Amps1 2 1 2

8 kW5 lbs

ECB29-8 (28K42)Terminal block

1 208 6.0 20,500 2.4 24 − − − 25 − − − 3.9 25 − − − 25 − − −5 lbs. Terminal block

220 6.7 22,900 2.4 27 − − − 30 − − − 3.9 29 − − − 30 − − −

230 7.3 25,100 2.4 27 − − − 30 − − − 3.9 29 − − − 30 − − −

240 8.0 27,300 2.4 27 − − − 30 − − − 3.9 29 − − − 30 − − −

10 kW6 lbs

ECB29-10 (28K43)Terminal Block

1 208 7.5 25,600 2.4 29 − − − 30 − − − 3.9 30 − − − 30 − − −6 lbs. Terminal Block

220 8.4 28,700 2.4 33 − − − 35 − − − 3.9 35 − − − 35 − − −

230 9.2 31,400 2.4 33 − − − 35 − − − 3.9 35 − − − 35 − − −

240 10.0 34,100 2.4 33 − − − 35 − − − 3.9 35 − − − 35 − − −

ECB29-10 (28K47)(3) 20A Fuses

1 440 8.4 28,700 1.3 17 − − − 20 − − − 1.9 17 − − − 20 − − −(3) 20A Fuses

460 9.2 31,400 1.3 17 − − − 20 − − − 1.9 17 − − − 20 − − −

480 10.0 34,100 1.3 17 − − − 20 − − − 1.9 17 − − − 20 − − −

15 kW12 lbs

ECB29-15CB (28K44)50A Circuit breaker

1 208 11.3 38,400 2.4 42 − − − 4 45 − − − 3.9 43 − − − 4 45 − − −12 lbs. 50A Circuit breaker

220 12.6 43,000 2.4 48 − − − 50 − − − 3.9 50 − − − 50 − − −

230 13.5 47,000 2.4 48 − − − 50 − − − 3.9 50 − − − 50 − − −

240 15.0 51,200 2.4 48 − − − 50 − − − 3.9 50 − − − 50 − − −

ECB29-15 (28K48)(3) 25A Fuses

1 440 12.6 43,000 1.3 24 − − − 30 − − − 1.9 25 − − − 25 − − −(3) 25A Fuses

460 13.8 47,000 1.3 24 − − − 30 − − − 1.9 25 − − − 25 − − −

480 15.0 51,200 1.3 24 − − − 30 − − − 1.9 25 − − − 25 − − −

20 kW19 lbs

ECB29-20CB (28K45)(2) 35A Circuit breaker

2 208 15.0 51,200 2.4 29 21 4 30 4 30 3.9 30 21 4 30 4 3019 lbs. (2) 35A Circuit breaker

220 16.8 57,300 2.4 33 24 35 35 3.9 35 24 35 35

230 18.4 62,700 2.4 33 24 35 35 3.9 35 24 35 35

240 20.0 68,200 2.4 33 24 35 35 3.9 35 24 35 35

ECB29-20 (28K49)(3) 35A Fuses

1 440 16.8 57,300 1.3 32 − − − 35 − − − 1.9 32 − − − 35 − − −(3) 35A Fuses

460 18.4 62,700 1.3 32 − − − 35 − − − 1.9 32 − − − 35 − − −

480 20.0 68,200 1.3 32 − − − 35 − − − 1.9 32 − − − 35 − − −

5 ECB29-20 (28K51)(3) 25A Fuses

1 550 16.8 57,300 6 1.3 26 − − − 30 − − − 6 1.9 26 − − − 30 − − −(3) 25A Fuses

575 18.4 62,700 6 1.3 26 − − − 30 − − − 6 1.9 26 − − − 30 − − −

600 20.0 68,200 6 1.3 26 − − − 30 − − − 6 1.9 26 − − − 30 − − −

25 kW19 lbs

ECB29-25CB (28K46)(2) 45A Circuit breaker

2 208 18.8 64,100 2.4 35 27 4 40 4 40 3.9 37 27 4 40 4 4019 lbs. (2) 45A Circuit breaker

220 21.0 71,700 2.4 41 30 45 45 3.9 43 30 45 45

230 23.0 78,300 2.4 41 30 45 45 3.9 43 30 45 45

240 25.0 85,300 2.4 41 30 45 45 3.9 43 30 45 45

ECB29-25 (28K50)(3) 40A Fuses

2 440 21.0 71,700 1.3 39 − − − 45 − − − 1.9 40 − − − 45 − − −(3) 40A Fuses

460 23.0 78,300 1.3 39 − − − 45 − − − 1.9 40 − − − 45 − − −

480 25.0 85,300 1.3 39 − − − 45 − − − 1.9 40 − − − 45 − − −

5 ECB29-25 (28K52)(3) 35A Fuses

2 550 21.0 71,700 6 1.3 32 − − − 35 − − − 6 1.9 32 − − − 35 − − −(3) 35A Fuses

575 23.0 78,300 6 1.3 32 − − − 35 − − − 6 1.9 32 − − − 35 − − −

600 25.0 85,300 6 1.3 32 − − − 35 − − − 6 1.9 32 − − − 35 − − −

NOTE − Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.1 Electric heater capacity only � does not include additional blower motor heat capacity.2 Amps shown are for blower motor only.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F (75°C).4 Bold text indicates that the circuit breaker on �CB" circuit breaker models must be replaced with size noted.5 All 575v electric heaters are used with 460V blower coil units. A 575V to 460V Step-down transformer for the blower coil unit is furnished with all 575V electric heaters.6 Blower motor is rated at 460V.7 HACR type circuit breaker or fuse.

Page 12: ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in

OPTIONALELECTRIC

HEAT(Field

Installed)

AIR FLOW

LIQUIDLINE

SUCTIONLINE

SUPPLYAIR

OPENING

Return AirFILTER

LOW VOLTAGEINLETS(Top and

Right Side)

LINE VOLTAGEINLETS

(Top and Left Side)

Return Air

TOP VIEW

FRONT VIEW SIDE VIEW

BLOWER

DETAIL OF PIPING PLATE

A

B C

11-1/16 (281)

D

F E

LIQUIDLINE

SUCTION LINE CONDENSATEDRAINS (2)(Horizontal)

COILPIPINGPLATE

3/4(19)

3/4(19)

3/4(19)

5/8(16)

5/8(16)

1(25)

5/8(16)

5/8(16)

1-3/4(44)

2(51)

1-1/8 (29)4-3/8(111)

2-3/4(70)

5-3/8(137)

3-1/2 (89)

OPTIONALELECTRIC

HEAT(Field

Installed)

AIR FLOW

LIQUIDLINE

SUCTIONLINE

RETURNAIR

OPENING

Supply Air

FILTER

Supply Air

TOP VIEW

FRONT VIEW SIDE VIEW

BLOWER

DETAIL OF PIPING PLATE

A

B C

11-1/16(281)

F

D

E

LIQUIDLINE

SUCTION LINE

CONDENSATEDRAINS (2)

(Up-Flow andDown-flow)

CONDENSATEDRAINS (2)(Horizontal)

COILPIPINGPLATE

5/8(16)

5/8(16)

5/8(16)

3/4(19)

3/4(19) 5/8

(16)

5/8(16)

1-3/4(44)

2(51)

1-1/8 (29)4-3/8(111)

1 (25)

3−5/8(92)

3-1/2 (89)

LOW VOLTAGE(Right Side)

LINE VOLTAGE(Left Side)

CB30M DOWN-FLOW POSITION

1(25)

CB30M UP-FLOW POSITION

CONDENSATEDRAINS (2)

(Up-Flow andDown-flow)

FILTERACCESS

FILTERACCESS

H

G

H

G

CB30M / Page 12

DIMENSIONS − INCHES (MM)

Model No. A B C D E F G H

CB30M−21/26 in. 45−1/4 16−1/4 20−5/8 14−3/4 19 15 24−5/8 20−5/8

mm 1149 413 524 375 483 381 625 524

CB30M−31 in. 49−1/4 21−1/4 20−5/8 19−3/4 19 20 24−5/8 24−5/8

mm 1251 540 524 502 483 508 625 625

CB30M−41 in. 51 21−1/4 22−5/8 19−3/4 21 20 26−3/8 24−5/8

mm 1295 540 575 502 533 508 670 625

CB30M−46 in. 52−1/2 21−1/4 22−5/8 19−3/4 21 20 27−7/8 24−5/8

mm 1334 540 575 502 533 508 708 625

CB30M−51CB30M 65

in. 58−1/2 21−1/4 24−5/8 19−3/4 23 20 27−7/8 30−5/8CB30M−65

mm 1486 540 625 502 584 508 708 778

Model No. A B C D E F G H

CB30M−21/26 in. 45−1/4 16−1/4 20−5/8 14−3/4 19 15 24−5/8 20−5/8

mm 1149 413 524 375 483 381 625 524

CB30M−31 in. 49−1/4 21−1/4 20−5/8 19−3/4 19 20 24−5/8 24−5/8

mm 1251 540 524 502 483 508 625 625

CB30M−41 in. 51 21−1/4 22−5/8 19−3/4 21 20 26−3/8 24−5/8

mm 1295 540 575 502 533 508 670 625

CB30M−46 in. 52−1/2 21−1/4 22−5/8 19−3/4 21 20 27−7/8 24−5/8

mm 1334 540 575 502 533 508 708 625

CB30M−51CB30M 65

in. 58−1/2 21−1/4 24−5/8 19−3/4 23 20 27−7/8 30−5/8CB30M−65

mm 1486 540 625 502 584 508 708 778

Page 13: ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in

CB30M / Page 13

DIMENSIONS − INCHES (MM)

Model A B C D E F G HModelNo. inch mm inch mm inch mm inch mm inch mm inch mm inch mm inch mm

CB30M-21/26 45-1/4 1149 16-1/4 413 20-5/8 524 14-3/4 375 19 483 15 381 24-5/8 625 20-5/8 524

CB30M-31 49-1/4 1251 21-1/4 540 20-5/8 524 19-3/4 502 19 483 20 508 24-5/8 625 24-5/8 625

CB30M-41 51 1295 21-1/4 540 22-5/8 575 19-3/4 502 21 533 20 508 26-3/8 670 24-5/8 625

CB30M-46 52-1/2 1334 21-1/4 540 22-5/8 575 19-3/4 502 21 533 20 508 27-7/8 708 24-5/8 625

CB30M-51CB30M-65

58-1/2 1486 21-1/4 540 24-5/8 625 19-3/4 502 23 584 20 508 27-7/8 708 30-5/8 778

LIQUIDLINE

SUCTION LINE

SUPPLYAIR

OPENING

FILTER

LOW VOLTAGE INLETS(Bottom and Right Side)

TOP VIEW

FRONT VIEW END VIEW

BLOWER

DETAIL OF PIPING PLATE

H

B

C

D

LIQUIDLINE

SUCTIONLINE

CONDENSATEDRAINS (2)

(Up-Flow and Down-flow)

CONDENSATEDRAINS (2)(Horizontal)

COIL

PIPINGPLATE

3/4(19)

3/4(19)

3/4(19)

1-1/2(38)

1-3/4(44)

5-3/4(146)

2(51)

1-1/8 (29)

RETURNAIR

OPENING

F

E

5/8(16)

5/8(16)

5/8(16)

END VIEW

AIRFLOW

OPTIONAL ELECTRIC HEAT(Field Installed)

11-1/16(281)LINE VOLTAGE

INLETS(Top and Right Side)

5-3/8(137)

4-3/8(111)

LIQUIDLINE

SUCTION LINE

SUPPLYAIR

OPENING

FILTER

LOW VOLTAGEINLETS(Top andLeft Side)

TOP VIEW

FRONT VIEWEND VIEW

BLOWER

DETAIL OF PIPING PLATE

B

C

D

LIQUIDLINE

SUCTIONLINE

COIL

PIPINGPLATE

3/4(19)

3/4(19)

3/4(19)

2(51)

1-1/8 (29)

RETURNAIR

OPENING

F

E

5/8(16)

5/8(16)

5/8(16)

END VIEW

AIRFLOW

OPTIONAL ELECTRIC HEAT(Field Installed)

11-1/16(281)

LINE VOLTAGE INLETS(Bottom and Left Side)

5-3/8(137)

4-3/8(111)

HORIZONTAL POSITION (LEFT-HAND AIR DISCHARGE)

HORIZONTAL POSITION (RIGHT-HAND AIR DISCHARGE)

FILTERACCESS

FILTERACCESS

5-3/4(146)

1-1/2(38)

1-3/4(44)

CONDENSATEDRAINS (2)(Horizontal)

A 5/8(16)

G

H

A5/8(16)

G

1(25)

1(25)

Page 14: ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in

TOP VIEW

Opening

1-5/8(41)

SIDE VIEW

DOWN-FLOW COMBUSTIBLE FLOOR BASE

BLOWERCOILUNIT

1-5/8(41)

11-3/8(289)

2 (51)

1-5/8(41)

22-1/8(562)5/8

(16) 13-3/8 (340)

DOWN-FLOWCOMBUSTIBLEFLOOR BASE

AIR FLOWA

B

PIPINGPLATE

5/8(16)

AIR FLOW

PIPINGPLATE

B

A

5/8(16)

AIR FLOW

BPIPINGPLATE

A 5/8(16)

AIR FLOWB

PIPINGPLATE

A5/8(16)

RIGHT HAND AIR FLOW LEFT HAND AIR FLOW

UP-FLOW DOWN-FLOW

AIR FLOW

ADJUSTABLE20 (508) to

25 (635)ALL UNITS

16(406)

6(152)

SIDE RETURN UNIT STAND(Up-Flow Only)

CB30M-018/024 − 16-1/4 (413)CB30M-030 thru -060 − 21-1/4 (540)

SUPPLYAIR

OPENING

CB30M-018/024 − 15 (381)CB30M-030 thru 060 − 20 (508)

CB30M−21/26 & −31 −16−1/4 (464)

CB30M−41 thru −65 −23−1/4 (591)

CB30M / Page 14

DIMENSIONS − INCHES (MM)

Model NoA B

Model No.in. mm in. mm

CB30M-21/26 45-1/4 1149 16-1/4 413

CB30M-31 49-1/4 1251 21-1/4 540

CB30M-41 51 1295 21-1/4 540

CB30M-46 52-1/2 1334 21-1/4 540

CB30M-51CB30M-65

58-1/2 1486 21-1/4 540

Page 15: ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in
Page 16: ehb cb30 0712 - INNOVATION GROUPinnovation-group.com.ua/downloads/eh/60/ah/cb30m.pdfElectric Heat Data Pages 8−11 ... Tested with matching air conditioners and heat pump units in

REVISIONS

Section Description of Change

All CB30U models discontinued.

Visit us at www.lennox.com

For the latest technical information, www.lennoxdavenet.com

Contact us at 1−800−4−LENNOX

NOTE − Due to Lennox’ ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.Installation and service must be performed by a qualified installer and servicing agency. ©2007 Lennox Industries Inc.