Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer Tertiary connected shunt reactors in preventing failures - Field measurements and comparison with Transient study results Pratap Mysore Venugopal Tondupally Adi Mulawarman Pratap Consulting Services HDR Xcel Energy

Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Presented by: Pratap MysoreMinnesota Power Systems Conference

November 6, 2018

Effectiveness of Surge Capacitors on Transformer Tertiary connected shunt reactors in preventing failures

- Field measurements and comparison with Transient study results

Pratap Mysore Venugopal Tondupally Adi MulawarmanPratap Consulting Services HDR Xcel Energy

Page 2: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Shunt Reactor Additions in Xcel EnergyWind Generation Addition 825 MW wind power generation in Southern MNCAPX 2020Joint Initiative of eleven transmission owning utilities in four states in upper Midwest.800 miles of transmission at 345 kV and 230 kVLargest transmission project in 40 years to improve reliability of the grid in upper Midwest. Last line of the project expected to be energized in December 2018.

2

Page 3: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Applicable documents for Operating Voltage RangeSystem voltage needs to be within the allowable range to prevent connected equipment failures.

ANSI C84.1-2016 “American National Standard for Electric Power Systems and Equipment—Voltage Ratings (60 Hz)”. This standard establishes nominal voltage ratings and operating tolerances for 60 Hz electric power systems above 100V. The latest version includes preferred voltage ratings up to 1200kV which was covered earlier in IEEE 1312-1993.

3

Page 4: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Shunt ReactorsInstalled to keep system voltage below maximum limit

Installed on Transmission lines

Either at both ends or at only one end.

Middle of the line.

Grounded “Wye” with or without Neutral Reactor

Tertiaries of transmission transformers

4

Page 5: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Transformer Tertiary connected Reactors Economical Installation at lower voltage

Air core Construction – voltages up to 34.5 kV

Up to 50 MVAR

Ungrounded “Wye” configuration

Frequency of switching – Daily or more frequent

5

Page 6: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Reactor connections and Physical Layout

6

Page 7: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Reactor and Switching Device ratings34.5 kV, 50 MVAR Reactor; Rated Current 836A

13.8 kV, 50 MVAR Reactor; Rated Current 2091A

72.5 kV, 3000 A, 40 kA SF6 Gas circuit breaker with gas pressure

at 65 PSI34.5 kV Reactor Load current is 2% of the short circuit current

interruption rating

13.8 kV reactor current is 5% of the short circuit current interruption rating.Breaker load current interruption is less than 5% of maximum

short circuit rating.

7

Page 8: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Circuit Breaker CharacteristicsCircuit breakers are designed to interrupt high short circuit current

-40kAHave no problem interrupting low load currents but, the current is

forced to zero before the natural current zero occurs –Phenomenon referred to as current chopping.C37.015-2017,”IEEE Guide for the Application of Shunt Reactor

Switching” assumes low current region to be less than 300A.Xcel energy 34.5 kV reactors (load current 836A) have failed due

to suspected current chopping.One circuit breaker failure and few 34.5kV reactor failures were

attributed to transient voltages due to current chopping

8

Page 9: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Bus Capacitance and Shunt Reactor Inductance

9

Page 10: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Effect of Current ChoppingIf Chopped Current is iCH, the stored energy in the inductor is ½*L*iCH

2

There is an energy exchange between the bus capacitance (1/2*C*V2)Total energy exchange is 1/2CV2 -1/2CV0

2= LiCH2

Where, V0 is the voltage at which current is chopped. Voltage developed, V = √[V0

2 +(L/C) * iCH2 ]

√(L/C) is the surge impedance

10

Page 11: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Surge Impedance Transient volta

Surge Impedance: Assuming 250 pf capacitance, 13.8 kV Reactor bus: Z = 106√(0.0101/250) = 6.36 kΩ34.5 kV Reactor bus; Z = 106√(0.063/250) = 15.89 kΩTransient voltage Peak: √[V0

2 + (6.36*iCH)2] kV at 13.8 kV √[V0

2 +(15.89*iCH)2] kV at 34.5 kVV0 is the voltage at which contacts interrupted the current.

11

Page 12: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Transient Voltage The value of current chopped is dependent on:

Capacitance on both sides of the breaker

Chopping number λ, a characteristic value of the circuit

breaker

SF6 Puffer type λ = 4x104 to 19x104

Total current chopped = λ√C; With 250 pf on both sides of the

breaker and λ=10x104 , C=250pf/2, iCH = 1.1A; This can vary

up to 4A depending on λ and capacitance.

Chopping current is higher at load currents.12

Page 13: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Transient Voltage rate of rise

13

Page 14: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Addition of Surge CapacitanceSurge Capacitance Csurge = 0.25 µF

Surge Impedance

13.8 kV Reactor bus: Z = 103√(0.0101/0.25) = 200 Ω

34.5 kV Reactor bus; Z = 103√(0.063/0.25) = 502 Ω

Transient Voltage magnitude and Frequency: 10A chopped

13.8 kV bus: 200*10 =2kV; Frequency:3.167 kHz RRRV=25 V/µs

34.5 kV bus: 502*10 =5kV; Frequency:1.26 kHz RRRV=25 V/µs

14

Page 15: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Surge CapacitorReduces Peak Transient Voltage

Reduces the frequency of oscillation

Reduces the Rate of rise of transient voltage on the

Reactor bus

Reduces the transient recovery voltage rate of rise across

the breaker.

Minimizes Breaker reignition

15

Page 16: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Transient Studies • Used Alternate Transient Program (ATP) , a version of Electro-magnetic

transient Program(EMTP) • Breaker re-ignition modeled using ‘MODELS’ blocks• High Frequency model of shunt reactor • Hybrid Transformer model-includes Wdg Capacitance

16

A AXFMR

V

TR_HV EQ-S

TR_LV EQ-S

V

V

Rp

R

LCg1 Cg2

CS

15.3kVMCOVMOV

PS V

Rp

R

LCg1 Cg2

CS

MOV

Rp

R

LCg1 Cg2

CS

MOV

C-Surge-0.25

UI VP

S

V

MO

VU

I

MO

V

V V

PS

PS

PS

PS

PS

+v-+v-

V

Page 17: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Breaker Dielectric Recovery Characteristics• Cold dielectric recovery Characteristic at Low current Interruption• Inherent to the specific breaker (Initial Rate of rise -1.8kV/µs)• Modeled in EMTP_ATP using ‘MODELS’ as an exponential function

• Cold Dielectric recovery VRecovery = 1600 (1-e-(t-18.03E-3)/(3.55E-3)) kV17

(f ile ADM_ich_10_Bef ore_v 2.pl4; x-v ar t) m:XX0006 18 20 22 24 26 28 30*10-3

0.0000

0.1999

0.3999

0.5998

0.7998

0.9997

1.1997

1.3996

1.5996*106

Page 18: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Dielectric Recovery at Load Current Interruption

•Arc re-ignites if the voltage across the contacts exceeds• Dielectric Recovery voltage after current interruption.

18

M

Cstray Cstray

1S3_ACB2A_1 CB2A_2

UI

MODELreigniti

I

ARC_sw

UI

Reignition Switch Model

Page 19: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Results with 10A Chopping Current

19

(f ile ADM_TR.pl4; x-v ar t) c:X0001A-X0013A c:X0001B-X0013B c:X0001C-X0013C 0 10 20 30 40 50*10-3

-3000

-2000

-1000

0

1000

2000

3000

(f ile ADM_ich_10_Bef ore_v 2.pl4; x-v ar t) v :X0001A- 17.98 18.04 18.09 18.15 18.21 18.26 18.32*10-3

-40

-30

-20

-10

0

10

20

30

*103

(f ile ADM_ich_10_Bef ore_v 2.pl4; x-v ar t) v :CB2A_1-CB2A_2 18.02 18.03 18.04 18.05 18.06 18.07 18.08*10-3

-40

-30

-20

-10

0

10

20

30

*103

Reactor Current

Page 20: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Bus Voltage -Switching with Surge Capacitor

20

(f ile ADM_ich_10_Bef ore_v 2.pl4; x-v ar t) v :X0001A- 0 10 20 30 40 50*10-3

-10.0

-7.5

-5.0

-2.5

0.0

2.5

5.0

7.5

10.0*103

(f ile ADM_ich_10_Bef ore_v 2.pl4; x-v ar t) v :CB2A_1-CB2A_2 16.0 16.5 17.0 17.5 18.0 18.5 19.0 19.5*10-3

-40

-30

-20

-10

0

10

*103

Bus Voltage Breaker TRV (Voltage Across Breaker)

Page 21: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Comparison of ATP simulations with Field Records

21

(f ile ADM01.pl4; x-v ar t) c:X0001A-X0002A c:X0001B-X0002B c:X0001C-X0002C 0.495 0.506 0.517 0.528 0.539 0.550

-3000

-2000

-1000

0

1000

2000

3000

Shunt Reactor phase CurrentsField Recorded ATP Simulation

Page 22: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Bus Voltage –After Breaker First Pole Opens

22

(f ile ADM01.pl4; x-v ar t) v :X0002C 0.49 0.51 0.53 0.55 0.57 0.59

-12

-8

-4

0

4

8

12

*103

Relay Captured –VC voltageFrequency- 3.03 kHz, RRRV-67V/µs

ATP Simulation–VC voltageFrequency: 3.11 kHz

Page 23: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Reactor Bus Voltage – After next Poles Open

23

(f ile ADM01.pl4; x-v ar t) v :X0002B 0.50 0.51 0.52 0.53 0.54 0.55 0.56 0.57 0.58

-15

-10

-5

0

5

10

15

*103

Relay Captured –VB voltageFrequency- 3.03 kHz, Changes to 3.07kHzAfter all poles open

ATP Simulation–VB voltageFrequency 3.11 kHz

Calculated Frequency:3.167 kHz C37.015 calculations assume grounded Source with Ungrounded Reactor Configuration -Frequency after first pole opens is lower than the frequency of oscillations after all poles open. This is not true if the source is ungrounded.

Page 24: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

ConclusionsAddition of Surge Capacitors at the terminals of the reactor

mitigates re-ignitions.

At 13.8 kV, 50 MVAR reactor Load current is high enough not to

cause current Chopping as seen at 34.5 kV.

34.5 kV installation to be commissioned in the near future will

provide the proof of effectiveness of Surge capacitors for lower

reactor currents.

Need to have a High sample recording device with Two Voltage

inputs to record Breaker TRV24

Page 25: Effectiveness of Surge Capacitors on Transformer …...Presented by: Pratap Mysore Minnesota Power Systems Conference November 6, 2018 Effectiveness of Surge Capacitors on Transformer

Questions?

25