58
SRI LANKA INSTITUTE of ADVANCED TECHNOLOGICAL EDUCATION Training Unit Protective Measures against Excessive Contact Voltage Theory No: EE 017 INDUSTRIETECHNIK INDUSTRIETECHNIK ELECTRICAL and ELECTRONIC ENGINEERING Instructor Manual

EE017-Protective Measures...-Th-Inst.pdf

  • Upload
    -

  • View
    220

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EE017-Protective Measures...-Th-Inst.pdf

SRI LANKA INSTITUTE of ADVANCED TECHNOLOGICAL EDUCATION

Training Unit

Protective Measures against Excessive Contact

Voltage Theory

No: EE 017

INDUSTRIETECHNIKINDUSTRIETECHNIK

ELECTRICAL and ELECTRONIC ENGINEERING

Instructor Manual

Page 2: EE017-Protective Measures...-Th-Inst.pdf

1

Training Unit

Protective Measures against Excessive Contact Voltage

Theoretical Part

No.: EE 017

Edition: 2008 All Rights Reserved Editor: MCE Industrietechnik Linz GmbH & Co Education and Training Systems, DM-1 Lunzerstrasse 64 P.O.Box 36, A 4031 Linz / Austria Tel. (+ 43 / 732) 6987 – 3475 Fax (+ 43 / 732) 6980 – 4271 Website: www.mcelinz.com

Page 3: EE017-Protective Measures...-Th-Inst.pdf

2

PROTECTIVE MEASURES AGAINST EXCESSIVE CONTACT VOLTAGE

CONTENTS Page

LEARNING OBJECTIVES...................................................................................................5

1 GENERAL ....................................................................................................................7

1.1 The protection of humans and animals against direct and indirect contact .........7

1.1.1 Direct contact ...................................................................................................7

1.1.2 Indirect contact.................................................................................................7

1.2 Legal regulations..................................................................................................7

2 DEFINITIONS...............................................................................................................9

2.1 Active components...............................................................................................9

2.2 Inactive components ............................................................................................9

2.3 Types of fault .......................................................................................................9

2.3.1 Housing contact .............................................................................................10

2.3.2 Short circuit ....................................................................................................10

2.3.3 Earth fault.......................................................................................................10

2.4 Electrical equipment...........................................................................................10

2.5 Causes of excessive contact voltage on the housing of electrical equipment ...11

2.6 Operational insulation ........................................................................................11

2.7 Fault voltage ......................................................................................................11

2.8 Contact voltage ..................................................................................................11

2.9 Area of risk (Resistance area) ...........................................................................12

2.10 Earth voltage......................................................................................................13

2.11 Surface voltage gradient US ...............................................................................13

2.12 Specific earth resistance....................................................................................14

2.13 Reaching distance (arms reach) ........................................................................14

2.14 PEN conductor (combined protective conductor and neutral conductor)...........15

2.15 PE-conductor or protective conductors or earth continuity conductor................16

2.16 The term "nominal".............................................................................................16

3 TYPES AND APPLICATIONS OF PROTECTIVE MEASURES.................................17

3.1 Summary of protective measures ......................................................................17

3.2 The requirements when putting an Installation into operation...........................17

3.3 Protective insulation (double insulation) ............................................................18

3.3.1 Double insulation of electrical equipment.......................................................18

3.3.2 The Symbol for double insulated equipment..................................................19

Page 4: EE017-Protective Measures...-Th-Inst.pdf

3

3.3.3 Double insulation............................................................................................19

3.3.4 Types of AC plug............................................................................................19

3.3.5 Protective insulation of the working area .......................................................21

3.4 Protective low voltage (safety extra-low voltage or SELV)...............................22

3.4.1 Diagram symbols for safety transformers ......................................................22

3.4.2 Permissible voltage supplies for SELV ..........................................................23

3.4.3 Non permissible supplies for SELV................................................................23

3.4.4 Regulations for extra-low voltages .................................................................24

3.5 Protective isolation (protection by electrical separation) ....................................24

3.5.1 Regulations for protective Isolation ................................................................25

3.6 Protective earthing .............................................................................................26

3.7 Neutralisation or protective multiple earthing.....................................................29

3.7.1 Regulations for protective multiple earthing ...................................................30

3.7.2 Dimensions of connectors in protective multiple earthing systems................31

3.7.3 Neutralisation in complete electrical installations...........................................31

3.8 Protective conductor systems ............................................................................31

3.8.1 Regulations for protective conductor systems ...............................................32

3.9 Voltage-operated earth-leakage circuit breaker .................................................33

3.9.1 Auxiliary earth ................................................................................................34

3.10 Current-operated earth-leakage circuit breaker .................................................35

3.10.1 How the current-operated circuit breaker functions ...................................35

3.10.2 Calculation of the earth electrode resistance .............................................36

3.10.3 The regulations for connecting current-operated circuit breakers..............37

3.11 Combined current-voltage-operated circuit breaker...........................................38

3.11.1 The regulations for connecting combined current-voltage-operated circuit

breaker 38

3.12 Controlling the earth potential ............................................................................39

4 EARTHS.....................................................................................................................40

4.1 General ..............................................................................................................40

4.2 Earth electrode resistance (Reel) ........................................................................40

4.2.1 The approximate value for specific earth resistance (ρe)[Ωm] ......................40

4.3 Types of earth ....................................................................................................41

4.3.1 Strip earth (horizontal earth) ..........................................................................41

4.3.2 Foundation earths ..........................................................................................42

4.3.3 Earth rods (deep earths - vertical earths).......................................................44

4.3.4 Earth plates ....................................................................................................45

4.4 General information for insulating earths ...........................................................45

Page 5: EE017-Protective Measures...-Th-Inst.pdf

4

4.4.1 Water pipes....................................................................................................45

4.4.2 Other pipe systems ........................................................................................46

5 TESTING THE PROTECTIVE MEASURES...............................................................47

6 EXPLANATION OF FORMULA SYMBOLS AND FORMULARE ...............................48

6.1 Explanation of symbols ......................................................................................48

6.2 Formulary...........................................................................................................49

Page 6: EE017-Protective Measures...-Th-Inst.pdf

5

PROTECTIVE MEASURES AGAINST EXCESSIVE CONTACT VOLTAGE

LEARNING OBJECTIVES

The student should...

state the purpose of protective measures

state the highest allowable contact voltage for humans and animals

state what is meant by the following three types of fault: insulation fault, short circuit

and accidental earthing and describe. the difference between them

define the terms active components, inactive components, electrical equipment, area

of risk and reaching distance

state the difference between a neutral conductor and a protective conductor

classify active and inactive protective measures

understand the difference between insulation of electrical equipment and insulation of

the working area

state the highest allowable values of low voltage

name the permissible and non permissible voltage supplies for safety extra low

voltage

explain how protective Isolation functions

state the rules for Installation of protective Isolation

explain how protective earthing functions

calculate the protective earthing resistance

explain how neutralisation functions

name the rules for Installing neutralisation

name the rules for Installing protective conductor systems

state what is meant by a voltage operated earth leakage circuit breaker

describe the Operation and make a drawing of a current operated earth leakage circuit

breaker

calculate the earth electrode resistance

Page 7: EE017-Protective Measures...-Th-Inst.pdf

6

state the rules for the installation of a current-operated circuit breaker

state the use of a protective switch, neutralization

explain the rules for the installation of a voltage-operated circuit breaker

state the purpose of controlling earth potential

define the term "earthing"

state the way in which earth resistance varies with distance from the earthing

electrode

describe different methods of earthing

know the rules for Installing earthing systems

Page 8: EE017-Protective Measures...-Th-Inst.pdf

7

PROTECTIVE MEASURES AGAINST EXCESSIVE CONTACT VOLTAGE

1 GENERAL

1.1 The protection of humans and animals against direct and indirect contact

1.1.1 Direct contact

This means contact with the active conductors in electrical circuits. Protection is provided

by all equipment for normal sale. In most cases appliance and equipment will be marked

with a safety symbol.

1.1.2 Indirect contact

This refers to contact with inactive components of electrical equipment which are at a high

voltage due to a defect (i.e. insulation fault). The laws regarding Electrical Engineering

specify protective measures in which the maximum permissible contact voltage may not

exceed:

50 V for humans and 24 V for animals.

(Various protective measures are listed in paragraph 3, page 17).

1.2 Legal regulations

The material design of all high-voltage installations must meet the latest standards of

electrical engineering technology.

In all industrialized countries, laws and regulations have been established to protect

persons working with electrical equipment and appliances.

Page 9: EE017-Protective Measures...-Th-Inst.pdf

8

It has been assumed that, in the countries where this text book will be used, laws and

regulations exist which are the same or similar to the regulations outlined and the

instructors will be able to point out the differences without difficulty.

The laws for Electrical Engineering make the observation of certain regulations

compulsory. Failure to comply with these regulations is often punishable (by fine).

The law shows little leniency towards trained people, such as electricians, who should be

aware of such dangers.

The specialist must protect the layman!

The following regulations must always be observed when installing and operating

electrical installations:

- Life must not be endangered.

- Electrical Installations may not cause any damage (fires).

- Safety standards must be as high as possible in order to ensure trouble-free operation

of the plant.

Page 10: EE017-Protective Measures...-Th-Inst.pdf

9

2 DEFINITIONS

2.1 Active components

Active components are all those components (parts) or conductors (wires) which have a

current-carrying capability and which make up the electrical circuit.

Direct contact with active conductors is prevented by operational insulation (insulated

conductors in cables), protective covering (covered terminals), or installations which are

out of reach.

The following are examples of active conductors:

Electric lines, switches, fuses, neutral conductors, plugs and terminals.

2.2 Inactive components

Inactive components are conducting components which are not a part of the working

circuit, e g a motor housing.

2.3 Types of fault

Page 11: EE017-Protective Measures...-Th-Inst.pdf

10

2.3.1 Housing contact

This is a connection, caused by an insulation fault, between an active conductor with an

inactive component or housing of electrical equipment.

2.3.2 Short circuit

This is a connection between active conductors having different potentials.

2.3.3 Earth fault

This is a conducting connection, caused by an insulation fault, between a live conductor

and earth or earthed components.

2.4 Electrical equipment

Electrical equipment includes items which, as a whole or in part, are intended for

generating, transmitting or using electrical energy.

NOTE:

Electrical equipment must be protected against mechanical damage to from high

temperature, which could cause damage to the insulation. lf, as the result of an insulation

fault, connection is made between an active conductor and an inactive component in an

item of electrical equipment, then there will be a potential difference between the housing

of the equipment and earth.

Page 12: EE017-Protective Measures...-Th-Inst.pdf

11

2.5 Causes of excessive contact voltage on the housing of electrical equipment

Overloading, failure to allow for expansion, dust and dampness, incorrect handling and

repair by unqualified persons can cause excessive voltage on the housing of equipment.

2.6 Operational insulation

This is achieved by covering conductors along their full length with insulating material

(Varnish, enamel or oxide coatings are not permissible. Such conductors may only be

used on the Inside of electrical equipment or behind a protective covering).

2.7 Fault voltage

This is the voltage which occurs when contact is possible

2.8 Contact voltage

This is the part of the fault voltage which can be bridged by a human.

Page 13: EE017-Protective Measures...-Th-Inst.pdf

12

Re = consumers earth electrode Ro = power supplier's earth

resistance electrode resistance

Rf = fault resistance Rtoc = location contact resistance

Rh = human resistance Uc = contact voltage

Uf = fault voltage

Ut = line voltage

2.9 Area of risk (Resistance area)

It is that part of the general mass of earth where, in case of a short circuit to earth, a

noticeable voltage exists between any point in this area and a reference point of the earth

(a sufficient distance away from earth electrode).

Page 14: EE017-Protective Measures...-Th-Inst.pdf

13

2.10 Earth voltage

This is the voltage which appears between a current-carrying earth (earth Installation) and

a reference point of the Earth which is a sufficient distance away from earth electrode.

2.11 Surface voltage gradient US

This is that part of the earth voltage between two points 1 m apart (an average stride).

Page 15: EE017-Protective Measures...-Th-Inst.pdf

14

2.12 Specific earth resistance

This is the resistance between opposite faces of a cube of earth with 1 m edges. The

specific earth resistance ( ) is calculated by using the formula for conductor resistance.

2.13 Reaching distance (arms reach)

This is the area which a person can reach with his hands from the point or place where he

is standing.

Page 16: EE017-Protective Measures...-Th-Inst.pdf

15

NOTE:

A distance of 2500 mm must exist between the standing area (floor) and a live conductor

or conducting element.

2.14 PEN conductor (combined protective conductor and neutral conductor)

This is the neutral conductor of an electrical network, which is connected to the earth

continuity conductor on the customer's premises and also to the earth electrode. Should

an earth fault occur, the fault current flows back to the source of supply through the PEN

conductor in parallel with earth. Since the path resistance is very low, the fault current is

large enough to blow the fuse on switch off a protective circuit breaks.

Page 17: EE017-Protective Measures...-Th-Inst.pdf

16

2.15 PE-conductor or protective conductors or earth continuity conductor

The protective conductor serves to prevent the housing of electrical equipment against

excessive contact voltage and must, therefore, be installed and clamped with the greatest

of care.

Symbol for the terminal for the protective conductor:

The colour of the insulation (covering) on the protective conductor is yellow and green

(from the manufacturer). In older installations it can be red or for English cables, brown.

The protective conductor must never carry operational current; it only carries leakage

current (fault current) in case of a fault. The protective conductor for portable electrical

equipment must be included in the connecting cable for the equipment.

NOTE:

The protective conductor must never be switched with the live or neutral conductors. This

could endanger life!

2.16 The term "nominal"

The term "nominal" identifies the values used in the design of electrical equipment and

installations. Operational characteristics and limit test values are related to these values.

Page 18: EE017-Protective Measures...-Th-Inst.pdf

17

3 TYPES AND APPLICATIONS OF PROTECTIVE MEASURES

3.1 Summary of protective measures

The following are examples of active protective measures, apart from the connection of

the protective conductor to the equipment, which will excessive contact voltage:

- Protective insulation (double insulation).

- Protective low voltage (safety Extra Low Voltage, SELV).

- Protective Isolation for one item of equipment.

The following are examples of inactive protective measures, when a protective conductor

is connected to the equipment, which prevents excessive contact voltage from remaining:

- Protective isolation for several items of equipment.

- Safety earthing.

- Neutralization (Protective Multiple Earthing, PME).

- Protective conductor system.

- Voltage-operated earth leakage circuit breaker.

- Current-operated earth leakage circuit breaker.

- Combined current-voltage-operated earth leakage circuit breaker.

- Controlling the earth potential.

3.2 The requirements when putting an Installation into operation

- Before every electrical installation is put into operation, the fault- free Operation of the

protective measures used must be thoroughly tested.

- It is entirely forbidden to simulate protective measures or to render them inoperative.

- The following practices are forbidden:

Installing an earthed AC plug without a protective conductor (exception: when the

equipment is double-insulated) .

Altering a normal AC plug so that it will fit into an earthed AC socket.

Page 19: EE017-Protective Measures...-Th-Inst.pdf

18

Bypassing protective switches.

Using unauthorized adapter plugs which interrupt the protective conductor.

3.3 Protective insulation (double insulation)

The function of protective insulation is to protect all inactive components in the equipment

by additional insulation when a fault (housing contact) occurs which would result in

excessive contact voltage.

3.3.1 Double insulation of electrical equipment

This additional insulation is produced by enclosing components in insulation and by

incorporating insulating, intermediate sections in the gears at the factory.

Page 20: EE017-Protective Measures...-Th-Inst.pdf

19

3.3.2 The Symbol for double insulated equipment

3.3.3 Double insulation

Double insulated equipment need not have a protective conductor connection. However,

the AC plug on the connecting cable of a piece of double insulated equipment must fit into

an earthed AC socket.

3.3.4 Types of AC plug

Contour AC plugs or flat AC plugs (with partially insulated pins) must be inseparably

connected with the AC cable. When such plugs or the cable are to be replaced, earthed

plugs should be used with the protective contact not connected.

Page 21: EE017-Protective Measures...-Th-Inst.pdf

20

Protective insulation is only recognised as a protective measure if the item of equipment is

marked with the appropriate

NOTE:

Electrical hand tools, electric razors and household appliances etc.; are items which are

commonly constructed with double insulation.

Page 22: EE017-Protective Measures...-Th-Inst.pdf

21

3.3.5 Protective insulation of the working area

This is sometimes known as "Protection by non-conducting location". This is allowed for

fixed electrical installations only. In addition to the standing area, all components which

are current-conducting and situated within reaching distances of ground must have

insulating covers, (i.e. floors, water-pipes and radiators etc.).

The covering must be sufficiently large so that the electrical equipment can only be

reached from an insulated area. The covers must also be robust and firmly fixed to the

base. If several fixed, electrical items can be reached from one location, then all of their

inactive components must be connected with an equalizing conductor (earth free local

equipotent bonding).

Page 23: EE017-Protective Measures...-Th-Inst.pdf

22

3.4 Protective low voltage (safety extra-low voltage or SELV)

The protective low voltage may not be more than 42 volts; in children's toys it may not

exceed 24 volts nominal rate. This voltage is not high enough to allow a dangerous

amount of current to flow through the human body.

3.4.1 Diagram symbols for safety transformers

- enclosed safety transformer

- safety transformer non-enclosed (built in)

- transformer for toys

- transformer for bells

- transformer for hand-light

- transformer for de-frosting

Page 24: EE017-Protective Measures...-Th-Inst.pdf

23

3.4.2 Permissible voltage supplies for SELV

- Protective transformers with separate windings

- Rotary converters with separate windings (motor and generator are separate)

- Primary cells

3.4.3 Non permissible supplies for SELV

Page 25: EE017-Protective Measures...-Th-Inst.pdf

24

Prohibited: because of electrical connection between the primary and secondary sides.

A potential source of danger exists.

- Autotransformers

- Series-resistors (voltage droppers)

- Voltage dividers (potential dividers)

- Rotary converters with common windings

3.4.4 Regulations for extra-low voltages

- Safety extra-low voltage electrical circuits must not be earthed.

- Plugs for low-voltage equipment must not be capable of being fitted into sockets for

higher voltage.

- Extra-low voltage circuits and conductors must be insulated for a nominal 250 V.

- For children's toys, driven by electric motors, the supply must be 24 V or lower

- Extra-low voltage equipment for treating and keeping animals must have a rated

voltage of 24 V or lower.

- Protective conductors may not be connected to low-voltage equipment (danger of

voltage from other faulty electrical equipment passing over the protective conductor to

the low voltage equipment).

The use of safety extra-low voltage:

Children's toys, hand lamps, electrical hand tools, under-water lights and wet grinding

machines etc. all use safety extra-low voltage

3.5 Protective isolation (protection by electrical separation)

The purpose of protective Isolation is to isolate the electrical circuit completely from the

electrical mains and earth, through an Isolation transformer with a maximum 660 V

nominal rating for the primary and a secondary with from 42 V to a maximum 380 V

nominal rating.

Page 26: EE017-Protective Measures...-Th-Inst.pdf

25

Diagram symbol for isolation transformer

Connection of electrical equipment to an Isolation transformer

3.5.1 Regulations for protective Isolation

- The movable connecting cable on the secondary must have a minimum performance

equal to GMM or YMM cables.

- Any portable isolation transformer must be double-insulated.

- The housing of electrical equipment (non isolated electrical hand drills) silvated in

electrically conducting areas must be connected in an easily visible manner to this

area with a minimum of 4 mm² copper cable.

Page 27: EE017-Protective Measures...-Th-Inst.pdf

26

- The connection to the secondary electrical circuit must not be too long. The maximum

conductor length is 250 m at 250 V.

- Should several items of equipment be driven with an isolation transformer, then their

housings must be connected with a potential equalizing conductor.

Connection of several items of electrical equipment to one isolation transformer

The use of protective isolation:

Protective isolation is used in razor sockets (AC), electrical hand tools and in boilers.

It is also used when repairing open electrical equipment in a repair shop.

3.6 Protective earthing

All inactive components of electrical equipment which might receive excessive contact

voltage in case of a housing contact are connected through a protective conductor to an

earth electrode installed in the earth.

Page 28: EE017-Protective Measures...-Th-Inst.pdf

27

Example of protective earthing

Rs = safety earthing resistance

The fault current flows through the protective earth electrode to earth. The resistance of

the safety earthing Rs must be sufficiently low, so if a fault voltage of 50 V (24 V for

animals) is reached, the preceding protective component operates and shuts off the

supply.

Rs = Safety earthing electrode resistance.

Ib = Fault current through the over-current

protection component which will cause

it to operate.

In = Nominal rating of the over-current protection

component.

k = Short circuit factor (the factor by which In must

be multiplied in order to obtain the smallest

lb in case of a short circuit).

Page 29: EE017-Protective Measures...-Th-Inst.pdf

28

Operation of over-current protection components

Over-current protection

component

Fault current Ib in

consumer plant In x k

Fuse, quick-acting In x 3.5

Fuse, rating up to

50 A (slow-acting) over

63 A (slow-acting)

In x 3 5

In x 5

Circuit breaker

Type L

Type G

In x 5

In x 10

Calculate the highest permissible earthing electrode resistance, using a quick-acting 20

amp fuse.

For a house Uc = 50 V.

For a farm Uc = 24 V.

Calculate the highest permissible earthing electrode resistance in a mains circuit. An

automatic circuit breaker, type L10 A, is installed as an over-current protection

component.

Page 30: EE017-Protective Measures...-Th-Inst.pdf

29

As the calculations have shown, the earth electrode resistances must be very low.

It is very expensive to lay safety earthing and almost impossible to keep the regulations in

earth which conducts poorly.

NOTE:

With the safety earthing, there must be a very low resistance to earth. It is forbidden to

replace an over-current protection component with one of a higher nominal rating.

3.7 Neutralisation or protective multiple earthing

All inactive components of an electrical Installation which might reach an excessive

contact voltage in the event of a fault (housing contact) are connected to the neutral

conductor.

The fault current flows through the neutral conductor.

Page 31: EE017-Protective Measures...-Th-Inst.pdf

30

3.7.1 Regulations for protective multiple earthing

- When the conductor cross section is under 10 mm² the PEN-conductor must be

separated into a neutral conductor and protective conductor. These may not be

reconnected later on.

- The PEN-conductor must never be fused or interrupted.

- The PEN-conductor must be connected to the water pipes and must also bridge the

water meter in every household.

Page 32: EE017-Protective Measures...-Th-Inst.pdf

31

3.7.2 Dimensions of connectors in protective multiple earthing systems

- Steel strip: 90 mm² cross section, galvanized, minimum 3 mm thick.

- Steel rod: 10 diameter, galvanized.

- Copper: same cross section the PEN-conductor, for conductor sizes up to 16 mm².

All of the conducting components (foundation earth, central heating and oil tank etc.) are

also connected to the potential equalizing strip.

3.7.3 Neutralisation in complete electrical installations

Neutralisation must only be used in the complete installations when the following four

neutralisation conditions can be met:

- The cross section of the conductor between power supply and consumers must be of

a sufficient size, so that in case of short circuit between the live and PEN-conductors,

a current, larger that the operating current of the preceding over-current protection

circuit breaker, flows.

- The PEN-conductor must be earthed near the power source (transformer) and near

the terminal of the mains branch.

- The PEN-conductor may not be interrupted (switched) and must also be laid to the

same regulations as the live wire.

- All available earths in the area of the installation are to be connected to the PEN-

conductor.

3.8 Protective conductor systems

These protective measures may only be used in factories or workshops which have a

power generator or a transformer with the windings isolated from earth (neutral point of a

star connection must not be connected to earth!).

Page 33: EE017-Protective Measures...-Th-Inst.pdf

32

3.8.1 Regulations for protective conductor systems

- All exposed metalwork in buildings and construction sites and all inactive components

of electrical equipment must be connected to the protective conductor.

- A supervisory device must be installed to monitor the insulation condition between live

conductors and earth.

- The total earth electrode resistance of the protective conductor system must not

exceed 20Ω.

Electrical equipment remains operative in the event of an insulation fault in one phase.

There is no contact voltage on the inactive components. The fault, however, will be

indicated on the insulation supervisory equipment. Only when there is a second housing

contact in an electrical component in another phase will the over-current protection device

be activated.

Page 34: EE017-Protective Measures...-Th-Inst.pdf

33

3.9 Voltage-operated earth-leakage circuit breaker

Should there be a high fault voltage on inactive components of electrical equipment,

current flows through the coil of the voltage-operated earth leakage circuit breaker, which

is earthed to an auxiliary earth and the voltage-operated circuit breaker switches off

automatically.

Page 35: EE017-Protective Measures...-Th-Inst.pdf

34

With the test button one can only determine whether the breaker is operating or if the

auxiliary earth conductor and the auxiliary earth are good. The condition of the protective

conductor and its proper connection is not tested by the Operation of the test button.

3.9.1 Auxiliary earth

Earthing rods driven 1.5 m into the earth may serve as auxiliary earth, or an earthing band

3 m long laid below the frost line can be used. The connecting cable from the auxiliary

earth to the voltage-operated circuit breaker must be insulated when laid

With a contact voltage of 50 V, the auxiliary earth resistance may be up to a maximum of

800 Ω and the circuit will operate correctly.

NOTE:

The voltage-operated circuit breaker will not function when there is a direct connection

between the protective conductor and the auxiliary earth. In new installations the voltage-

operated circuit breaker is no longer authorized for use.

Page 36: EE017-Protective Measures...-Th-Inst.pdf

35

3.10 Current-operated earth-leakage circuit breaker

All conductors which serve the purpose of supplying current for the electrical equipment to

be protected are controlled through the balanced current transformer of the current-

operated circuit breaker.

3.10.1 How the current-operated circuit breaker functions

If the insulation resistance of the electrical installation is good, the sum of the current

flowing through the balanced current transformer will be equal to zero (Kirchhoff's First

Law).

Should a housing contact exist in an item of electrical equipment which is connected after

the current-operated circuit breaker, then fault current flows from protective earth to

supply transformer earth. As a result, the sum of the currents flowing through the current

transformer is no longer zero.

Page 37: EE017-Protective Measures...-Th-Inst.pdf

36

Depending on the amount of fault current in the primary, a current will be induced in the

secondary. This current reduces the strength of a permanent magnet in the switch, the

switch will operate and turn off the supply.

3.10.2 Calculation of the earth electrode resistance

For the protection of humans

For the protection of domestic animals

Re = earth electrode

I∆f = Fault release current of the current-operated circuit breaker

Calculate the following earth electrode resistance Re for the protection of humans and

domestic animals using a current-operated circuit breaker.

Fault release

current I∆f [A]

0.015 003 0.1 0.3 0.2 2

Max. Re [Ω]

with Uc ≤ 150 V

4333

Max. Re [Ω]

with Uc ≤ 24 V

1600

Page 38: EE017-Protective Measures...-Th-Inst.pdf

37

3.10.3 The regulations for connecting current-operated circuit breakers

- All metal installation components are to be protected and must be earthed according

to regulations. The minimum cross section of the protective conductor is 1.5 mm².

- Fuses must be installed in front of the current-operated circuit breaker.

- All of the conductors after the current-operated circuit breaker must be well insulated

from earth.

- All energy-carrying conductors, including the neutral conductor, must be connected

through the current-operated circuit breaker.

- The current-operated circuit breaker must be tested monthly. The following information

is to be posted with good visibility.

NOTE:

This test cannot determine whether the electrical equipment is properly connected and

earthed. A current-operated circuit breaker with a fault release current up to 100 mA will

also protect one against earthing in case of contact with active components (live parts).

Page 39: EE017-Protective Measures...-Th-Inst.pdf

38

3.11 Combined current-voltage-operated circuit breaker

This type of protective breaker is intended for use in installations where the neutralizing

requirements are not fully satisfied.

The combined current-voltage-operated circuit breaker contains a current operating and a

voltage operating unit.

3.11.1 The regulations for connecting combined current-voltage-operated circuit breaker

- All live conductors and the neutral conductor must be wired through the circuit

breaker.

- The neutral conductor after the switch must be insulated from earth.

Page 40: EE017-Protective Measures...-Th-Inst.pdf

39

- All of the electrical equipment to be protected must be connected through a protective

conductor to terminal "K" of the protective circuit breaker.

- The auxiliary earth conductor will be connected to terminal "H" of the protective circuit

breaker. The auxiliary earth conductor is to be insulated from earth.

3.12 Controlling the earth potential

This is used mostly in combination with other protective measures. All metal parts and an

earth, must be electrically connected.

Example

- Foundation earth

- Water pipes (metal)

- Drain pipes (metal)

- Pipe systems from central heating

- Gas pipes

- Protective conductors etc

Potential equalizing strip

Page 41: EE017-Protective Measures...-Th-Inst.pdf

40

4 EARTHS

4.1 General

Earthing means creating an electrical, conducting connection between earth and the

earthing system. The earth electrode resistance near the earthing system is very high.

The greater the distance from the earthing electrode, the larger the earth's cross section

available for current flow.

After a distance of approximately 20 m from the earthing system, the earth can be rated

as an excellent current conductor because of the large cross section.

4.2 Earth electrode resistance (Reel)

This is dependent on the specific earth resistance (see paragraph 2.11, page 13) and on

the cross section and length of the grounding item.

4.2.1 The approximate value for specific earth resistance (ρe)[Ωm]

Wet, marshy soil 30 Ωm

Damp clay and humus 100 Ωm

Damp sand 300 Ωm

Damp gravel with sand 500 Ωm

Dry sand 1000 Ωm

Dry gravel 3000 Ωm

Rock 10000 Ωm

Area of risk:

See paragraph 2.9, page 12.

Page 42: EE017-Protective Measures...-Th-Inst.pdf

41

4.3 Types of earth

The type of earth which will be used depends on the composition of the earth and on the

actual requirements (protective measures) in each case.

4.3.1 Strip earth (horizontal earth)

Made of galvanized steel band, the minimum cross section is 90 mm²; dimensions 3 x 30

mm.

Made of galvanized steel cable, the minimum cross section is 95 mm²; diameter of each

wire minimum 2.5 mm.

Made of copper cable the minimum cross section is 35 mm².

The earthing strip should be buried a minimum of 0.5 - 1 m deep, depending on the

properties of the soil.

The strip earth may be laid as a ray, ring or mesh.

With a ray earth, the spacing should be even.

The angles between the rays should not exceed 60°.

Page 43: EE017-Protective Measures...-Th-Inst.pdf

42

The connection to the earthing electrode must be wrapped with a corrosion-protective

band, alternatively the connecting point must be covered with cable-insulating compound

to protect against corrosion.

Approximate values for earth electrode resistance Reel for strip earth (horizontal earth)

when the specific earth resistance equals 100 Ωm.

Band length

[m]

10 25 50 100

earth electrode

resistance Reel [Ω]

16 7.5 4.5 2.5

4.3.2 Foundation earths

These are very economical as later digging is not required Foundation earths are laid as a

ring under the outer foundation walls of a building (when necessary under middle walls as

well).

Page 44: EE017-Protective Measures...-Th-Inst.pdf

43

No point in the ground level plan of the building may be more than 5 m from the earth.

Strip steel must be laid an edge and there must be a minimum of 5 cm of concrete

beneath the strip.

Concrete-cased steel components and reinforcing steel can be connected to the

foundation earth by welding, screws or clamps.

Page 45: EE017-Protective Measures...-Th-Inst.pdf

44

Specified dimensions for connecting a foundation earth

4.3.3 Earth rods (deep earths - vertical earths)

These are used when it is impossible to lay a horizontal earth or when good conducting

earth is found at a deep level. The material used is galvanized rod or sectional steel which

is vertically driven into the earth. Earth rods may also be connected in parallel. However,

the distance between the rods in the earth must be twice the length of the original rods.

Approximate values of the earth electrode resistance for earth rods when the specific

earth resistance equals 100 Ωm.

Effective rod length [m] 2 3 5

Earth electrode resistance

Reel [Ω]

40 30 20

Page 46: EE017-Protective Measures...-Th-Inst.pdf

45

4.3.4 Earth plates

These are sheet plates at least 3 mm thick and buried vertically 1 m deep in the earth.

They are rarely used as a main earthing electrode due to the high earth electrode

resistance but may be used as an auxiliary earth.

Approximate value of the earth electrode resistance Reel for earth plates when specific

resistance equals 100 Ωm.

Plate size [m] 0.5 x 1 1 x 1

Earth electrode

resistance Reel [Ω]

45

35

4.4 General information for insulating earths

The contact surface of the connecting points must be cleaned. A connecting strip must be

laid between the earthing terminal and the water pipes. All connections open to be

protected from corrosion. Earthing connectors should not be laid under driveways or

paths. The earth electrode resistance can vary during the course of the year by a ratio of

approximately 1 : 2.

4.4.1 Water pipes

Metal water pipes may only be used as a sole earth when their components are

electrically well connected with each other and the earth electrode resistance must be as

low as normal earth electrode resistance. It must also be ensured that a change from

metal to plastic pipes will not be made at a later date.

Page 47: EE017-Protective Measures...-Th-Inst.pdf

46

4.4.2 Other pipe systems

Central heating pipes, pipes from distant heating plants, pipes from the gas system and

drain pipes must not be used as sole earths. They must be connected to the protective

earth.

Page 48: EE017-Protective Measures...-Th-Inst.pdf

47

5 TESTING THE PROTECTIVE MEASURES

The applied protective measures are to be tested by the installer before the Installation is

made operative.

The test must include all measurements and a complete visual inspection of all of the

protective circuit components.

If line voltage is used during the test, attention should be paid to the danger arising

through contact voltage, i.e. surface voltage gradient. If the test with a low test current

already shows that the protective measures are not in order, then the current must not be

increased. The test is to be interrupted.

The installer must advise the consumer to have the protective measures tested at suitable

intervals.

Page 49: EE017-Protective Measures...-Th-Inst.pdf

48

6 EXPLANATION OF FORMULA SYMBOLS AND FORMULARE

6.1 Explanation of symbols

Formula Symbol Name Unit Abbreviation

Ib Breaking current Ampere A

In Nominal current Ampere A

I∆t Fault release current of the

current-operated circuit

breaker

Ampere A

k Short circuit factor

Reel Earth electrode resistance Ohm Ω

Re Earth electrode resistance of

customers

Ohm Ω

Rt Resistance at point of fault Ohm Ω

Rh Human resistance Ohm Ω

Ro Power supplier's earth

electrode resistance

Ohm Ω

Rs Safety earthing resistance Ohm Ω

Rloc Location contact resistance Ohm Ω

Q Specific earth resistance Ohm metre Ωm

Uc Contact voltage Volt V

Ue Earth voltage Volt V

Uf Fault voltage Volt V

Ul Line voltage Volt V

Us Surface voltage gradient Volt V

Page 50: EE017-Protective Measures...-Th-Inst.pdf

49

6.2 Formulary

Calculation of the protective earth electrode resistance

Calculation of the earth electrode resistance for current-operated circuit breaker

Page 51: EE017-Protective Measures...-Th-Inst.pdf

50

EE 017

Protective Measures against Excessive

Contact Voltage

Theoretical Test

Page 52: EE017-Protective Measures...-Th-Inst.pdf

51

EE 017

PROTECTIVE MEASURES AGAINST CONTACT WITH EXCESSIVE VOLTAGE

TEST 1

1. Name three possible ways in which humans may be protected from making contact

with active conductors.

2. What is meant by "short circuit"?

3. State three safety principles which must be observed when installing and operating

electrical installations?

4. What is an active component?

5. What is meant by "earth fault"?

6. Which insulating materials may only be used on the inside of electrical equipment?

7. What is contact voltage?

8. State the formula for calculating specific earth resistance.

9. What distance must there be between a live conductor and the standing area, to

ensure safety?

10. What is the purpose of the PE-protective conductor?

Page 53: EE017-Protective Measures...-Th-Inst.pdf

52

EE 017

PROTECTIVE MEASURES AGAINST CONTACT WITH EXCESSIVE VOLTAGE

TEST 2

1. State the colour of the insulation on a protective conductor.

2. Name three examples of active protection measures apart from connection of the

protective conductor to the equipment to prevent excessive contact voltage.

3. State eight examples of inactive protective measures, using a protective conductor,

which prevents excessive contact voltage from remaining, when the equipment is

connected.

4. What is the function of double insulation?

5. What measures should be carried out before putting an installation into operation?

6. How can double-insulated equipment be recognised?

7. What is the maximum permissible voltage of a safety extra-low voltage system?

8. Name three permissible types of voltage supply for safety extra-low voltage systems.

9. Name three non permissible types of voltage supply for safety extra-low voltage

systems.

10. Why should protective conductors not be connected to low-voltage equipment?

Page 54: EE017-Protective Measures...-Th-Inst.pdf

53

EE 017

PROTECTIVE MEASURES AGAINST CONTACT WITH EXCESSIVE VOLTAGE

TEST 3

1. What is the purpose of double insulation?

2. What is the maximum fault voltage allowed on the neutral or protective conductor

before a component is shut off?

3. What are the minimum dimensions of neutralisation conductors made from steel strip;

steel rod; copper?

4. What is the maximum total earth electrode resistance permissible in a protective

conductor system?

5. With a contact voltage of 50 V, what is the maximum permissible auxiliary earth

electrode resistance using a voltage-operated earth-leakage circuit breaker?

6. What are the approximate values of specific earth resistance of the following

conditions: wet, marshy soil; damp sand; dry sand; rock?

7. What factors govern the type of earth used?

8. How deep should the earthing strip be buried?

9. Name three types of horizontal earthing strip.

10. What is the relationship between the length of vertical earth rods, and the distance

between the rods?

Page 55: EE017-Protective Measures...-Th-Inst.pdf

54

EE 017

PROTECTIVE MEASURES AGAINST CONTACT WITH EXCESSIVE VOLTAGE

TEST 1

(Solution)

1. By insulation of the conductor, protective covering of conductors and machinery, by

placing the conductors out of reach.

2. A conducting connection between active conductors with different potentials.

3. The safety to life may not be endangered.

Electrical installation must not cause any damage (e.g. fire).

Safety standards must be as high as possible.

4. Any component or wire used to carry current.

5. A conducting connection between a live conductor and earth or earthed (grounded)

component.

6. Varnish, enamel or oxide coatings.

7. The part of the fault voltage which can be bridged by a human.

8.

9. 2500 mm.

10. The PE-conductor is installed to protect the equipment housing from excessive

voltage.

Page 56: EE017-Protective Measures...-Th-Inst.pdf

55

EE 017

PROTECTIVE MEASURES AGAINSTCONTACT WITH EXCESSIVE VOLTAGE

TEST 2

(Solution)

1. Yellow and green.

2. Protective insulation; protective low voltage; protective isolation of one item of

equipment.

3. Protective isolation for several items of equipment; safety earthing; neutralisation;

protective conductor system; voltage-operated circuit breaker; current-operated

circuit breaker; combined current-voltage-operated circuit breaker; controlling the

earth potential.

4. To protect all inactive components from excessive contact voltage.

5. The Operation of all protective measures must be inspected and tested.

6. By the standard symbol (a square within a square) which all such equipment must

carry.

7. Maximum 42 volts.

8. Protective transformers with separated windings; rotary converter with separate

windings; storage batteries; dry batteries.

9. Autotransformers; series resistors; voltage dividers; rotary converters with

connections between windings.

10. Because of the danger of voltage from other faulty equipment passing over the

conductor to the low-voltage equipment.

Page 57: EE017-Protective Measures...-Th-Inst.pdf

56

EE 017

PROTECTIVE MEASURES AGAINSTCONTACT WITH EXCESSIVE VOLTAGE

TEST 3

(Solution)

1. To provide complete Isolation from the mains and earth.

2. 50 V

3. 90 mm² cross section

10 mm diameter

16 mm² cross section

4. 20 ohms.

5. 800 ohms.

6. 30 Ωm; 300 Ωm; 1000 Ωm; 10000 Ωm.

7. The composition of the soil (earth) and the requirements of the installation.

8. Between 0.5 and 1 m, depending on soil conditions.

9. Ring earth; ray earth; mesh earth.

10. The distance between them must be equal to twice their length.

Page 58: EE017-Protective Measures...-Th-Inst.pdf

57

KEY TO EVALUATION

PER CENT

MARK

88 – 100

1

75 – 87

2

62 – 74

3

50 – 61

4

0 – 49

5