4
Data Sheet ES001-2004 Issue 1 Not to be used for installation purposes. Page 1 of 4 Edwards 116 Class Genesis mass notification strobes are designed for use in Class 1, Division 1 and 2 explosionproof and hazardous location (non fire alarm) applications where electrical supervision is required. The units feature two lenses, an outer clear globe, and an inner colored lens available in amber, red, green, blue or magenta. This diode-polarized unit is UL 1638 and cUL listed for outdoor use as a NEMA Type 3R and 4X enclosure. The strobe has been evaluated to UL 1971 polar plot requirements with on axis light output values. The 116 Class features an enhanced synchronization circuit to comply with the latest requirements of UL 1971, signaling devices for the hearing impaired, and the Canadian standard CAN/ULC S526. Synchronized operation requires a separately installed synchronization control module, compatible Edwards control panel or booster power supply. See table on page 2 for a list of compatible synchronization modules. Mounting options are available (ordered separately) for wall, ceiling and pendant mounts. The unit is supplied with a guard installed over the clear outer globe for additional protection against impact. 116 Class Genesis Features Clear globe with dome guard Can be synchronized when connected to a compatible Five inner lens colors available: Amber, Red, Edwards control panel, booster power supply or Green, Blue, or Magenta synchronization module Three mounting options: wall, ceiling, or pendant Available in 16-33V DC/FWR Negligible in-rush current UL 1638 and cUL Listed NEMA Type 3R and 4X enclosures 116 Class Genesis Mass Notification Strobe Explosionproof LED BRIGHTEST EX-PROOF ENCLOSURE 3R 4X DC

Edwards Signaling 116DEGEXA-FJ Data Sheet

Embed Size (px)

DESCRIPTION

Buy the Edwards Signaling 116DEGEXA-FJ at JMAC Supply.https://www.jmac.com/Edwards_Signaling_116DEGEXA_FJ_p/edwards-signaling-116degexa-fj.htm

Citation preview

  • Data Sheet ES001-2004 Issue 1Not to be used for installation purposes.

    Page 1 of 4

    Edwards 116 Class Genesis mass notification strobes are designed for use in Class 1, Division 1 and 2 explosionproof and hazardous location (non fire alarm) applications where electrical supervision is required. The units feature two lenses, an outer clear globe, and an inner colored lens available in amber, red, green, blue or magenta.

    This diode-polarized unit is UL 1638 and cUL listed for outdoor use as a NEMA Type 3R and 4X enclosure. The strobe has been evaluated to UL 1971 polar plot requirements with on axis light output values.

    The 116 Class features an enhanced synchronization circuit to comply with the latest requirements of UL 1971, signaling devices for the hearing impaired, and the Canadian standard CAN/ULC S526. Synchronized operation requires a separately installed synchronization control module, compatible Edwards control panel or booster power supply. See table on page 2 for a list of compatible synchronization modules.

    Mounting options are available (ordered separately) for wall, ceiling and pendant mounts. The unit is supplied with a guard installed over the clear outer globe for additional protection against impact.

    116 Class Genesis Features

    Clear globe with dome guard Can be synchronized when connected to a compatible Five inner lens colors available: Amber, Red, Edwards control panel, booster power supply or

    Green, Blue, or Magenta synchronization module Three mounting options: wall, ceiling, or pendant Available in 16-33V DC/FWR Negligible in-rush current UL 1638 and cUL Listed

    NEMA Type 3R and 4X enclosures

    116 Class Genesis Mass Notification StrobeExplosionproof

    LED BRIGHTEST EX-PROOF ENCLOSURE

    3R 4XDC

  • Data Sheet ES001-2004 Issue 1Not to be used for installation purposes.

    Page 2 of 4

    116 Class Genesis

    Description Cat. No.Operating

    Voltage CurrentLens

    ColorsFlash Rate

    Light Output UL 1971

    Replacement

    Dome Guard

    Explosionproof Mass Notification Strobe

    116DEGEXA-FJ 16-33V DC/FWR0.505A, DC, RMS

    0.683A, FWR, RMSAmber 65 fpm 36 cd 116-Globe 116-GRD

    116DEGEXB-FJ 16-33V DC/FWR0.505A, DC, RMS

    0.683A, FWR, RMSBlue 65 fpm 14 cd 116-Globe 116-GRD

    116DEGEXG-FJ 16-33V DC/FWR0.505A, DC, RMS

    0.683A, FWR, RMSGreen 65 fpm 19 cd 116-Globe 116-GRD

    116DEGEXM-FJ 16-33V DC/FWR0.505A, DC, RMS

    0.683A, FWR, RMSMagenta 65 fpm 9 cd 116-Globe 116-GRD

    116DEGEXR-FJ 16-33V DC/FWR0.505A, DC, RMS

    0.683A, FWR, RMSRed 65 fpm 6 cd 116-Globe 116-GRD

    Hazardous Location Ratings

    116 Class Genesis

    Operating Temperature

    AmbientTemp.

    Supply Wire Temp. Marking

    Class I, Div. 2Groups A, B

    Class I, Div. 1 & 2Groups C, D

    Class II & III, Div. 1Groups E, F, G

    Class II & III, Div. 2Groups F, G

    40C 75C T2B (260C) T6 (85C) T4A (120C) T4A (120C)55C 90C T2B (260C) T6 (85C) T4 (135C) T4 (135C)65C 105C T2B (260C) T6 (85C) T3C (160C) T3C (160C)

    AccessoriesDescription Cat. No. Conduit Size

    Wall Bracket Mounting Elbow 116EX-B* N/ACeiling/Wall Mounting Module 116EX-C 3/4" NPTPendant Mounting Module 116EX-P 3/4" NPT

    *Note: Wall mount requires both 116EX-B and 116EX-C.

    Compatible Synchronization ModulesDescription Cat. No.

    Auto-sync Output Module

    SIGA-CC1SSIGA-CC1S-LGSIGA-MCC1SSIGA-MCC1S-LG

    Genesis Signal Master - Remote Mount

    ADTG1M-RMEG1M-RMG1M-RMG1M-RM-LGMG1M-RMXLSG1M-RMZG1M-RM

  • Data Sheet ES001-2004 Issue 1Not to be used for installation purposes.

    Page 3 of 4

    Family Tree

    Dimensional Drawings

    116 Class Housing and Globe Assembly with Guard

    dr_vs_explodeproof_pendantMt_01.eps

    dr_vs_explodeproof_wallMt_01.eps

    Ceiling Mount 116EX-C

    Wall Mount 116EX-B

    Pendant Mount 116EX-P

    12 9/16"(319mm)

    9 7/16"(240mm)

    6 3/4"(171mm)

    4"(102mm)

    4"(102mm)

    1"(25mm)

    5/16"(8mm)

    16 1/16"(408mm)

    16 13/16"(427mm)

    12"305mm)

    12 3/4"(324mm)

    dr_vs_explodeproof_ceilingMt_01.eps

    6 3/4"(171mm)

    13 3/4"(349mm)

    13"(330mm)

    4"(102mm)

    4"(102mm)

    1"(25mm)

    7 1/4"(184mm)

    7 1/4"(184mm)

    NOTE: 116EX-C must be used when application requires 116EX-B

    Pendant 116EX-P

    3/4" Conduit Entry

    Ceiling/Wall 116EX-C

    3/4" Conduit Entries

    Ceiling/Wall 116EX-C

    3/4" Conduit Entries

    Wall Bracket Elbow

    116EX-B 3" Hub

    dr_vs_explodeproof_tree_01.eps

  • Data Sheet ES001-2004 Issue 1Not to be used for installation purposes.

    Page 4 of 4

    9 Farm Springs Road Farmington, CT 060321.800.336.4206www.edwardssignaling.com

    Copyright 2012 Edwards Signaling