776
EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating, and Maintaining the EDR-5000 IM02602007E Rev. New

EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

Embed Size (px)

Citation preview

Page 1: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 EATON DISTRIBUTION RELAYInstruction Manual for Installing, Operating, and Maintaining the EDR-5000

IM02602007E Rev. New

Page 2: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

EDR-5000 Application Overview

2 www.eaton.com

Trend recorder

Event recorder

Current and Volt.:unbalance

%THD and THDFund. and RMSmin./max./avg.phasors and

angles

Power:Fund. and RMS

MVA, Mwatt, Mvar,PF

Metering, Statistics and

Demand

standard

3

1

3

EDR-5000

74TC

*

Zone InterlockingIRIG-B00X Breaker Wear Programmable Logic

50BF51R50R46 67P 67R50P

CTS

25

51P

27A

SOTF CLPU

59A

59N

47 55A/D

27M 59M 81R81 U/O 51V78V

LOP

32 32V50X 51X

1

67X

79

Fault recorder

Disturb. recorder

Page 3: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Key Features, Functions and Benefits..........................................................................................8General Description.........................................................................................................................................8Features...........................................................................................................................................................9

Comments on the Manual.............................................................................................................14What Is Included with the Device...................................................................................................................17Storage..........................................................................................................................................................17Important Information.....................................................................................................................................17Symbols.........................................................................................................................................................18General Conventions.....................................................................................................................................23

Device.............................................................................................................................................24Device Planning.............................................................................................................................................24Device Planning Parameters of the Device....................................................................................................24

Installation and Wiring..................................................................................................................27Three-Side-View............................................................................................................................................27Overview of Slots - Assembly Groups............................................................................................................28Typical Connection Diagrams........................................................................................................................30Slot X1: Power Supply Card with Digital Inputs..............................................................................................34Slot X2: Relay Output Card - Zone Interlock..................................................................................................37Slot X3: Current Transformer Measuring Inputs.............................................................................................39Slot X4: Voltage Transformer Measuring Inputs.............................................................................................47Slot X5: Relay Output Card............................................................................................................................52Slot X100: Ethernet Interface.........................................................................................................................55Slot X103: Data Communication....................................................................................................................56Slot X104: IRIG-B00X and Supervision Contact............................................................................................60X120 - PC Interface.......................................................................................................................................61Control Wiring Diagram.................................................................................................................................62

Input, Output, and LED Settings..................................................................................................63Digital Input Configuration..............................................................................................................................63DI-8P X..........................................................................................................................................................64Wired Inputs (Aliases)....................................................................................................................................67Relay Output Configuration............................................................................................................................74RO-4ZI X - Settings........................................................................................................................................77RO-6 X Settings.............................................................................................................................................95LED Configuration........................................................................................................................................120The »System OK« LED ...............................................................................................................................123LED Settings................................................................................................................................................123

Front Panel..................................................................................................................................144Basic Menu Control......................................................................................................................................148PowerPort-E Keyboard Commands.............................................................................................................149

PowerPort-E.................................................................................................................................151Installation of PowerPort-E...........................................................................................................................151Uninstalling PowerPort-E.............................................................................................................................151Setting up the Serial Connection PC - Device..............................................................................................152Loading of Device Data When Using PowerPort-E......................................................................................162Restoring Device Data When Using PowerPort-E........................................................................................163Backup and Documentation When Using PowerPort-E...............................................................................164Off-line Device Planning Via PowerPort-E...................................................................................................165

Measuring Values........................................................................................................................165Read Out Measured Values.........................................................................................................................165Current - Measured Values..........................................................................................................................166Voltage - Measured Values..........................................................................................................................169Power - Measured Values............................................................................................................................174

Energy Counter...........................................................................................................................175Direct Commands of the Energy Counter Module .......................................................................................175Signals of the Energy Counter Module (States of the Outputs)....................................................................175

Statistics......................................................................................................................................177Read Out Statistics......................................................................................................................................177Statistics (Configuration)..............................................................................................................................177Direct Commands........................................................................................................................................178Global Protection Parameters of the Statistics Module................................................................................178States of the Inputs of the Statistics Module................................................................................................182

www.eaton.com 3

Page 4: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Signals of the Statistics Module...................................................................................................................183Counters of the Module Statistics.................................................................................................................183

System Alarms.............................................................................................................................193Demand Management.................................................................................................................................193Peak Demand..............................................................................................................................................195Min. and Max. Values...................................................................................................................................195THD Protection............................................................................................................................................195Device Planning Parameters of the Demand Management.........................................................................195Signals of the Demand Management (States of the Outputs)......................................................................196Global Protection Parameter of the Demand Management..........................................................................196States of the Inputs of the Demand Management........................................................................................200System Alarm Signals (States of the Outputs).............................................................................................200

Resets..........................................................................................................................................201Manual Acknowledgment.............................................................................................................................202Manual Acknowledgment Via PowerPort-E..................................................................................................202External Acknowledgments..........................................................................................................................202External Acknowledge Via PowerPort-E.......................................................................................................203External LED - Acknowledgment Signals.....................................................................................................203Manual Resets.............................................................................................................................................204Manual Resets Via PowerPort-E..................................................................................................................204

Status Display..............................................................................................................................205Status Display via PowerPort E....................................................................................................................205

Operating Panel (HMI).................................................................................................................206Special Parameters of the Panel..................................................................................................................206Direct Commands of the Panel....................................................................................................................206Global Protection Parameters of the Panel..................................................................................................206

Recorders....................................................................................................................................207Disturbance Recorder..................................................................................................................................207Fault Recorder.............................................................................................................................................215Event Recorder............................................................................................................................................220Trend Recorder............................................................................................................................................221

Communication Protocols..........................................................................................................226Modbus®.....................................................................................................................................................226IEC 61850....................................................................................................................................................232IRIG-B00X...................................................................................................................................................239

Parameters...................................................................................................................................244Parameter Definitions..................................................................................................................................244Adaptive Parameters via HMI......................................................................................................................247Operational Modes (Access Authorization)..................................................................................................259Password.....................................................................................................................................................260Changing of Parameters - Example.............................................................................................................261Changing of Parameters When Using the PowerPort-E - Example.............................................................262Protection Parameters ................................................................................................................................264Setting Groups.............................................................................................................................................264Comparing Parameter Files Via PowerPort-E..............................................................................................266Converting Parameter Files Via PowerPort-E..............................................................................................266

Device Parameters......................................................................................................................268Date and Time.............................................................................................................................................268Version.........................................................................................................................................................268Version Via PowerPort-E..............................................................................................................................268TCP/IP Settings...........................................................................................................................................269Direct Commands of the System Module.....................................................................................................269Global Protection Parameters of the System...............................................................................................270System Module Input States........................................................................................................................272System Module Signals................................................................................................................................273Special Values of the System Module..........................................................................................................274

System Parameters.....................................................................................................................275General System Parameters........................................................................................................................275Voltage Depending System Parameters......................................................................................................275Current Depending System Parameters......................................................................................................276

Blocking.......................................................................................................................................278

4 www.eaton.com

Page 5: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Permanent Blocking.....................................................................................................................................278Temporary Blocking.....................................................................................................................................278To Activate or Deactivate the Tripping Command of a Protection Module....................................................280Activate, Deactivate Respectively to Block Temporary Protection Functions...............................................281

Protection (Prot) Module............................................................................................................283How to Block All Protective and Supervisory Functions................................................................................283Direct Commands of the Protection Module.................................................................................................290Global Protection Parameters of the Protection Module...............................................................................290Protection Module Input States....................................................................................................................290Protection Module Signals (Output States)..................................................................................................290Protection Module Values.............................................................................................................................291

Switchgear/Breaker - Manager...................................................................................................292Breaker Configuration..................................................................................................................................292Switching the Breaker at the Panel..............................................................................................................318

Protective Elements....................................................................................................................327Directional Feature – Phase Current............................................................................................................32750P/67P- DEFT Overcurrent Protection.......................................................................................................33051P/67P - INV Overcurrent-Protection.........................................................................................................337Directional Features for Measured (IX) Ground Fault Elements 50X/51X....................................................35450X/67X DEFT Measured Ground Fault Protection.....................................................................................35751X/67X INV Measured Ground Fault Protection.........................................................................................364Directional Features for Calculated (IR) Ground Fault Elements 50R/51R..................................................37250R/67R DEFT Calculated Ground Fault Protection....................................................................................37551R/67R INV Calculated Ground Fault Protection.......................................................................................382ZI - Zone Interlocking...................................................................................................................................38979 - Automatic Reclosure.............................................................................................................................40146 - Current Unbalance Protection...............................................................................................................431LOP – Loss of Potential...............................................................................................................................438SOTF - Switch Onto Fault Protection...........................................................................................................443CLPU - Supervision Module Cold Load Pickup............................................................................................44927M - Undervoltage Protection.....................................................................................................................45659M - Overvoltage Protection.......................................................................................................................46527A - Auxiliary Undervoltage Protection.......................................................................................................47459A - Auxiliary Overvoltage Protection.........................................................................................................47959N - Neutral Overvoltage...........................................................................................................................48425 - Sync-check...........................................................................................................................................48947 - Voltage Unbalance Protection...............................................................................................................51981O/U, 81R, 78V Frequency Protection.......................................................................................................52632 - Power Protection...................................................................................................................................54932V - Reactive Power Protection.................................................................................................................56055A and 55D - PF Protection.......................................................................................................................571ExP - External Protection.............................................................................................................................578

Supervision..................................................................................................................................58450BF – Breaker Failure Supervision............................................................................................................584CTS – Current Transformer Supervision......................................................................................................60174TC - Trip Circuit Monitoring......................................................................................................................606Self Supervision...........................................................................................................................................612

Programmable Logic...................................................................................................................614General Description.....................................................................................................................................614Programmable Logic at the Panel................................................................................................................618Programmable Logic Via PowerPort-E.........................................................................................................618

Commissioning...........................................................................................................................641Commissioning/Protection Test....................................................................................................................641Decommissioning – Removing the Plug from the Relay..............................................................................642

Service and Commissioning Support........................................................................................644Maintenance Mode......................................................................................................................................644Principle – General Use...............................................................................................................................644Before Use...................................................................................................................................................645How to Use the Maintenance Mode.............................................................................................................645Forcing the Relay Output Contacts..............................................................................................................647Disarming the Relay Output Contacts..........................................................................................................648Failure Simulator (Sequencer)*....................................................................................................................649

www.eaton.com 5

Page 6: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Technical Data.............................................................................................................................666Climatic Environmental Conditions...............................................................................................................666Degree of Protection EN 60529...................................................................................................................666Routine Test.................................................................................................................................................666Housing........................................................................................................................................................666Current and Ground Current Measurement.................................................................................................667Voltage and Residual Voltage Measurement................................................................................................667Frequency Measurement.............................................................................................................................668Voltage Supply.............................................................................................................................................668Power Consumption.....................................................................................................................................668Display.........................................................................................................................................................668Front Interface RS232..................................................................................................................................668Real Time Clock...........................................................................................................................................668Digital Inputs................................................................................................................................................668Relay Outputs..............................................................................................................................................669Supervision Contact (SC).............................................................................................................................669Time Synchronization IRIG-B00X.................................................................................................................669Zone Interlocking.........................................................................................................................................670RS485*........................................................................................................................................................670Fiber Optic*..................................................................................................................................................670URTD-Interface*..........................................................................................................................................670Boot Phase..................................................................................................................................................670

Standards.....................................................................................................................................671Approvals.....................................................................................................................................................671Design Standards........................................................................................................................................671High Voltage Tests (IEC 60255-6)................................................................................................................671EMC Immunity Tests....................................................................................................................................671EMC Emission Tests....................................................................................................................................672Environmental Tests.....................................................................................................................................672Mechanical Tests.........................................................................................................................................673

Specifications..............................................................................................................................674Specifications of the Real Time Clock..........................................................................................................674Specifications of the Measured Value Acquisition........................................................................................674Protection Elements Accuracy.....................................................................................................................675

Appendix......................................................................................................................................681Instantaneous Current Curves (Phase)........................................................................................................687Time Current Curves (PHASE)....................................................................................................................688Instantaneous Current Curves (Ground Current Calculated).......................................................................700Instantaneous Current Curves (Ground Current Measured)........................................................................701Time Current Curves (Ground Current)........................................................................................................702

Assignment List..........................................................................................................................714

6 www.eaton.com

Page 7: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

ff29cf4c2846dafcd774575c3a3fc66e7e00f5bb7cdd4f821e6f72b400fc1985

RMS Handoff: 0File: C:\p4_data\deliver_EDR-5000_KWelchering\generated\EDR-5000_user_manual_eaton_en.odtThis manual applies to devices (version):

Version 1.0.b

Build: 12288

www.eaton.com 7

Page 8: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Key Features, Functions and Benefits• Microprocessor-based protection with monitoring and control for medium voltage main and feeder

applications.• Current, voltage, and frequency protection for electrical power distribution systems.• Complete metering of voltage, currents, power, energy, minimum/maximum, and demand functions.• Complete metering, protection, and control in a single compact case to reduce panel space, wiring, and

costs.• Integral test function reduces maintenance time and expense.• Zone selective interlocking improves coordination and tripping time, and saves money compared to a

traditional bus differential scheme.• Programmable logic control functions for main-tie-main transfer schemes.• Reduce trouble shooting time and maintenance costs - Trip and event recording in non-volatile memory

provides detailed information for analysis and system restoration. Waveform capture aids in post fault analysis (viewable using PowerPort-E software).

• Minimum replacement time - Removable terminal blocks ideal in industrial environments.• Front RS-232 port and PowerPort-E software provides local computer access and User-friendly windows

based interface for relay settings, configuration, and data retrieval.• Breaker open/close from relay faceplate or remotely via communications.• Fast an easy troubleshooting, improved maintenance procedures, and increased device security.

Provides detailed traceability for system configuration changes• Relays self-diagnostics and reporting improves up-time and troubleshooting.• Breaker trip circuit monitoring improves the reliability of the breaker operation.

General DescriptionEaton’s EDR-5000 distribution protection relay is a multi-functional, microprocessor-based relay for feeder circuits of all voltage levels. It may be used as the primary protection on feeders, mains, and tie breaker applications; or as backup protection for transformers, high voltage lines, and differential protection. The relay is most commonly used on medium voltage switchgear applications.

The EDR-5000 feeder protection relay provides complete current, voltage, and frequency protection and metering in a single, compact case. The relay has four current inputs rated for either 5 amperes or 1 ampere and four voltage inputs. Three of the voltage inputs are to be connected to the 3-phase power voltage for voltage protection and for metering. They can be connected in wye-ground or open delta configuration. The fourth voltage is for independent single-phase undervoltage/overvoltage protection, or ground protection for an ungrounded system.

The maintenance mode, password protected soft key can be used for arc flash mitigation to change to an alternate settings group or set to have instantaneous elements only. The multiple setting groups can also be changed,via communications or a digital input.

An integral keypad and display is provided for direct User programming and retrieval of data without the need of a computer. 14 programmable LEDs provide quick indication of relay status.

A front port is provided for direct computer connection. An RS-485 communication port on the back is standard for local area networking using Modbus-RTU. An optional Ethernet port and protocols are available.

The EDR-5000 distribution protection relay includes programmable logic functions. Logic gates and timers may be defined and arranged for customized applications. Programmable logic control functions make the EDR-5000 relay ideally suited for main-tie-main and main 1/main 2 transfer schemes. The relay allows for four preprogrammed setting groups which can be activated through software or contact input.

Flash memory is used for the programming and all settings are stored in nonvolatile memory. The relay allows for four preprogrammed setting groups which can be activated through software, the display, or a contact input.

The EDR-5000 distribution protection relay has mass memory for data storage and a real-time clock with 1 ms

8 www.eaton.com

Page 9: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

time resolution. The relay will log 300 sequence of event records, 20 detailed trip logs, minimum/maximum values, load profiles, breaker wear information, and oscillography data.

The EDR-5000 has programmable binary inputs, two normally opened and eight Form C heavy duty outputs and one form C signal alarm relay. It can be powered from 19 Vdc to 300 Vdc or 40 Vac to 250 Vac auxiliary power.

Features

Protection Features

Phase overcurrent elements• Three instantaneous elements with timers ( 50P[1], 50P[2], and 50P[3])• Three inverse time overcurrent elements (51P[1], 51P[2], and 51P[3])• 11 standard curves• Instantaneous or time delay reset• Voltage Restraint (51P[2] and 51P[3])• Directional Control (All Elements)

Ground overcurrent elements• Two instantaneous measured elements with timers (50X[1] and 50X[2])• Two instantaneous calculated elements with timers (50R[1] and 50R[2])• Two inverse time overcurrent measured elements (51X[1],and 51X[2])• Two inverse time overcurrent calculated elements (51R[1] and 51R[2])• 11 standard curves• Directional Control (All Elements)• Instantaneous or time delay reset

Breaker failure (50BF)

Phase unbalance negative sequence overcurrent (46[1], 46[2]))

Phase voltage unbalance and sequence protection (47[1], 47[2])

Main 3-phase under/overvoltage (27M[1], 27M[2], 59M[1], 59M[2])

Auxiliary single-phase under/overvoltage (27A[1], 27A[2], 59A[1], 59A[2])

Ground fault overvoltage relay (59N[1], 59N[2])

Six Frequency elements that can be assigned to: over frequency, under frequency, rate of change, or vector surge (81[1], 81[2], 81[3], 81[4], 81[5], 81[6])

Apparent and displacement power factor (55A[1], 55A[2], 55D[1], 55D[2])

Forward and Reverse Watts (32[1], 32[2], 32[3])

Forward and Reverse Vars (32V[1], 32V[2], 32V[3])

Sync-check (25)

Zone interlocking for bus protection (87B)

Switch onto fault protection

Cold load pickup

www.eaton.com 9

Page 10: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Metering Features

• Amperes: Positive, negative, and zero sequence• Ampere demand• Volts: Positive, negative, and zero sequence• Phase angles• Volt-amperes and VA demand• Watts and kW demand• kWh (forward, reverse, net)• Vars and kvar demand• kvarh (lead, leg and net)• Power factor• Frequency• % THD V and I• Magnitude THD V and I• Minimum/maximum recording• Trending (load profile over time)

Monitoring Features

• Trip coil monitor• Breaker wear primary and secondary (accumulated interrupted current)• Oscillography (6000 cycles total)• Fault data logs (up to 20 events)• Sequence of events report (up to 300 events)• Clock (1 ms time stamping)

Control Functions

• Breaker open/close• Remote open/close• Programmable I/O• Programmable Logic• Programmable LEDs• Multiple setting groups• Cold load pickup• CT supervision

Communication Features• Local HMI• Password protected• Addressable• IRIG-B• Local communication port• Remote communication port:

- RS-232; and- RS-485

• Protocols:

10 www.eaton.com

Page 11: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

- Modbus-RTU;- Modbus-TCP (Optional); and- IEC61850 (Optional)

• Configuration software

Protection and Control Functions

The Eaton’s EDR-5000 distribution protection relay has been designed for maximum User flexibility and simplicity. The base relay includes all the standard current and voltage protection and metering functions.

Directional Overcurrent Protection

The EDR-5000 distribution protection relay provides complete 3-phase and ground directional overcurrent protection. There are 8 independent ground overcurrent elements. The ground elements “X” use the independently measured ground (or neutral) current from a separate current-sensing input. The ground elements “R” uses a calculated 3Io residual current obtained from the sum of the 3-phase currents. This calculated current could be used for either the neutral or ground current in a 3-phase, 4-wire system. Each of the phase and ground overcurrent elements can be selected to operate based on fundamental or RMS current. Phase direction is a function used to supervise all phase current elements (50, 51). A quadrature voltage is compared to a corresponding phase current to establish the direction of the fault. This function is selectable to operate in the forward, reverse or both directions. Ground direction is used to supervise ground current elements and is accomplished by using ground, negative sequence or residual currents supervised by zero, negative, or positive sequence voltages or ground current. This function s selectable to operate in forward, reverse or both directions.

Voltage Restrained Overcurrent

Voltage restraint reduces the overcurrent pickup level (51P[3]). This modification of the pickup overcurrent level is compared to the corresponding phase input voltage. The EDR-5000 uses the simple linear model below to determine the effective pickup value.

Sync-check

The sync-check function is provided for double-ended power source applications. The sync-check monitors voltage magnitude, phase angle and slip frequency between the bus and line. It also incorporates breaker close time, dead bus dead line, dead bus live line, and live bus live line features

Reverse Power

Reverse power provides control for power flowing through a feeder. There are three elements to be configured:

• Operate in forward;• Reverse; or• Under or over power conditions.

Reverse power is typically applied to generator or motor applications while under power is generally applied to load or generation loss

Reverse Vars

Reverse vars can be used to detect loss of excitation in synchronous machines. There are three elements to be configured:

• Operate in forward;• Reverse; or• Under or over vars conditions.

www.eaton.com 11

Page 12: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Inverse-Time Characteristics

There are 11 User-selectable inverse-time overcurrent curve characteristics. The User can select from the ANSI, IEC, or thermal curve families and can select instantaneous or time delay reset characteristics.

Breaker Failure

The EDR-5000 distribution protection relay includes a breaker failure (50BF, 62BF) function that can be initiated from either an internal or external trip signal. This is an independent element that can be used to operate a lockout relay or trip an upstream breaker. The timer must be longer than the breaker operating time and the protective function reset times.

Voltage Protection

The EDR-5000 distribution protection relay has four voltage-input circuits. There is a 3-phase set designated as Main Voltage (M) and a single-phase voltage circuit designated as Auxiliary Voltage (A). Both include undervoltage (27) and overvoltage (59) protection. The 3-phase voltage protection can be set to operate on a single-phase, 2 out of 3 phases, or all 3-phase logic. The Main VTs also provide phase voltage unbalance/reversal (47 negative sequence) protection. Each element has an independent threshold set point and adjustable time delay.

Ground Voltage Protection

In high impedance grounded systems, ground fault protection is provided by the detection of zero sequence voltage (3Vo) voltage in the neutral of the transformer by an overvoltage element (59N) connected to the secondary of the distribution grounding transformer, or in the secondary of a Wye- Broken Delta transformer used when the neutral is not accessible or in Delta system. In the EDR-5000, the User can measure this zero sequence voltage through the 4th voltage input; the 59N element has to be desensitized for 3rd harmonic voltages that can be present in the system under normal operation.

Flexible Phase Rotation

The EDR-5000 distribution protection relay can be applied on either an A-B-C or A-C-B phase rotation. A User setting permits correct operation and indication of the actual system configuration.

Frequency Protection

The EDR-5000 relay provides six frequency elements than can be used to detect under/over frequency, rate of change, and a vector surge (decoupling of two systems) protection on the Main VT inputs. Each element has an independent threshold set point and adjustable time delay.

Autoreclosing LogicThe EDR-5000 provides a six shot-recloser scheme. Autoreclosing is normally used by the utilities in their distribution and transmission lines, but it can be used in commercial and industrial applications with long overhead lines. Nearly 85% of the faults that occur on overhead lines are transient in nature. Tripping of a breaker normally clears a transient fault and reclosing of the breaker restores power back to the circuit.

Maintenance ModeThe Maintenance Mode can improve safety by providing a simple and reliable method to reduce fault clearing time and lower incident energy levels at energized panels. The Maintenance Mode allows the User to switch to more sensitive settings via a password protected soft key, communication, or via a digital Input while maintenance work is being performed at an energized panel or device. The more sensitive settings provide greater security for maintenance personnel and helps reduce the possibility of injury.

12 www.eaton.com

Page 13: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Monitoring and Metering

Sequence of Events RecordsThe EDR-5000 protection relay records a maximum of 300 events associated with the relay. An event is classified as a change of state as detected by the relay. These include relay pickups, dropouts, trips, contact closure, alarms, setting changes, and self-diagnostic failures. Each event is date and time stamped to a 1 ms resolution. The events are stored in a FIFO in chronological order.

Trip LogThe EDR-5000 protection relay will store a maximum of 20 trip records in a FIFO trip log. Each trip record will be date and time stamped to a 1 ms resolution. The trip log record will include information on the type of fault, protection elements that operated, fault location, and currents and voltages at the time of the fault.

Waveform CaptureThe EDR-5000 distribution protection relay provides oscillography-recording capabilities. The relay will record all measured signals along with the binary signals of pickup, trip, logic, and contact closures. The EDR-5000 relay can record up to 6000 cycles of data. The number of records is proportional to the size of each record; the maximum size per record is 600 cycles. The waveform capture is initiated by up to eight different triggers; it can also be generated manually through the display or via communications.

Integral User InterfaceThe front panel User interface has a 128 x 64 pixel LCD display with background illumination for wide angle viewing in all light conditions. 17 programmable LEDs provide quick and easy visual display of power on, mode of operation, alarm, and trip indication. Soft keys are provided for operation mode selection, scrolling through data, and settings. In addition, the relay settings and test functions are password protected.

Load Profiling/TrendingThe EDR-5000 relay automatically records selected quantities into non-volatile memory every 5, 10, 15, 30, or 60 minutes, depending on the trending report setting.

Programmable I/O The EDR-5000 distribution protection relay provides heavy-duty, trip rated, two normally open and eight Form C contacts. Two isolated inputs can be used for monitoring the trip circuit. One Form C contact is dedicated to the relay failure alarm function and is operated in a normally energized (fail-safe) mode. There are eight User-configurable discrete inputs that accept a wet contact and can operate through a wide range of power. Each input and output is User-programmable for maximum application flexibility.

Programmable LogicThe EDR-5000 distribution protection relay provides logic gates and timers that the User can customize for special or unique applications. Each gate can be assigned a logic function of either AND, OR, NAND or NOR. Each gate can have a maximum of four input signals and each input signal can be required to be a NOT. Input signals can be external inputs received via the binary inputs or internal values associated with the protection, alarm or metering set points. Each gate has a unique output assignment and designation that can be used as the input to another gate. There are 24 independent timers that have adjustable pickup and dropout delay settings.

www.eaton.com 13

Page 14: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Comments on the ManualThis manual gives a general explanation of the tasks of device planning, parameter setting, installation, commissioning, operation, and maintenance of the Eaton devices.

The manual serves as reference document for:

• Engineers in the protection field;• Commissioning engineers;• Personnel dealing with the setting, testing, and maintenance of protection and control devices; and• Well trained personnel involved in electrical installations and power stations.

All functions concerning the type code will be defined. Should there be a description of any functions, parameters, or inputs/outputs that do not apply to the device in use, please ignore that information.

All details and references are explained to the best of our knowledge and are based on our experience and observations.

This manual describes the full featured versions of the devices, including all options.

All technical information and data included in this manual reflect their state at the time this document was issued. Eaton Corporation reserves the right to carry out technical modifications in line with further development without changing this manual and without previous notice. Therefore no claim can be brought based on the information and descriptions included in this manual.

Text, graphics, and formulas do not always apply to the actual delivery scope. The drawings and graphics are not true to scale. Eaton Corporation does not accept any liability for damage and operational failures caused by operating errors or disregarding the directions of this manual.

No part of this manual is allowed to be reproduced or passed on to others in any form, unless Eaton Corporation has issued advanced approval in writing.

This User manual is part of the delivery scope when purchasing the device. In case the device is passed on (sold) to a third party, the manual has to be passed on as well.

Any repair work carried out on the device requires skilled and competent personnel with verifiable knowledge and experienced with local safety regulations and have the necessary experience with working on electronic protection devices and power installations.

IMPORTANT DEFINITIONS

The symbol/word combinations detailed below are designed to call the User's attention to issues that could affect User safety and well being as well as the operating life of the device.

DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.

WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION, used with the safety alert symbol, indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

14 www.eaton.com

Page 15: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

CAUTION, without the safety alert symbol, is used to address practices not related to personal injury.

NOTICE is used to address information and practices not related to personal injury.

FOLLOW INSTRUCTIONS

Read this entire manual and all other publications pertaining to the work to be performed before installing, operating, or servicing this equipment. Practice all plant and safety instructions and precautions. Failure to follow the instructions can cause personal injury and/or property damage.

PROPER USE

Any unauthorized modifications to or use of this equipment outside its specified mechanical, electrical, or other operating limits may cause personal injury and/or property damage, including damage to the equipment. Any such unauthorized modifications: (1) constitute "misuse" and/or "negligence" within the meaning of the product warranty, thereby excluding warranty coverage for any resulting damage; and (2) invalidate product certifications or listings.

The programmable devices subject to this manual are designed for protection and also control of power installations and operational devices. The devices are further designed for installation in low voltage (LV) compartments of medium voltage (MV) switchgear panels or in de-centralized protection panels. The programming and settings have to meet all requirements of the protection concept (of the equipment that is to be protected). The User must ensure that the device will properly recognize and manage (e.g.: switch off the breaker) on the basis of User selected programming and settings all operational conditions (failures). Before starting any operation and after any modification of the programming/settings, make a documented proof that the programming and settings meet the requirements of the protection concept.

Typical applications for this product family/device line are for example:

• Feeder protection;

• Mains protection;

• Transformer Protection and

• Machine protection.

This device is not designed for any usage beyond these applications. The manufacturer cannot be held liable for any resulting damage. The User alone bears the risk if this device is used for any application for which it was not designed. As to the appropriate use of the device: the technical data specified by Eaton Corporation has to be met.

www.eaton.com 15

Page 16: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

OUT-OF-DATE PUBLICATION

This publication may have been revised or updated since this copy was produced. To verify that you have the latest revision, be sure to check the Eaton Corporation website:

www. e aton.com

The latest versions of most publications are available at this site.

If the User's publication is not found on the web site, please contact Eaton Customer Support to get the latest copy.

ELECTROSTATIC DISCHARGE AWARENESS

All electronic equipment is sensitive to electrostatic discharge, some components more than others. To protect these components from electrostatic damage, the User must take special precautions to minimize or eliminate electrostatic discharges.

Follow these precautions when working with or near the device.

1. Before performing maintenance on the electronic device, discharge the static electricity on your body to ground by touching and holding a grounded metal object (pipes, cabinets, equipment, etc.).

2. Avoid the build-up of static electricity on your body by not wearing clothing made of synthetic materials. Wear cotton or cotton-blend materials as much as possible because these do not store static electric charges as much as synthetics.

3. Keep plastic, vinyl, and Styrofoam materials (such as plastic or Styrofoam cups, cup holders, cigarette packages, cellophane wrappers, vinyl books or folders, plastic bottles, and plastic ash trays) away from the device, the modules, and the work area as much as possible.

4. Do not remove any printed circuit board (PCB) from the device cabinet unless absolutely necessary. If you must remove the PCB from the device cabinet, follow these precautions:

• Do not touch any part of the PCB except the edges.

• Do not touch the electrical conductors, the connectors, or the components with conductive devices or with your hands.

• When replacing a PCB, keep the new PCB in the plastic, anti-static protective bag it comes in until you are ready to install the PCB. Immediately after removing the old PCB from the device cabinet, place it in the anti-static protective bag.

16 www.eaton.com

Page 17: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Eaton Corporation reserves the right to update any portion of this publication at any time. Information provided by Eaton Corporation is believed to be correct and reliable. However, no responsibility is assumed by Eaton Corporation unless otherwise expressly undertaken.

© Eaton Corporation, 2010. All Rights Reserved.

What Is Included with the DeviceThe device package includes all connection terminals, except communication connectors, but does not include the fastening material. Please check the package for completeness upon delivery.

Device Package Contents:

• 1 – Protective Relay;• 1 – Mount (Standard or Projection);• 1 – Quick Start Guide; and• 2 – CDs

Disk 1 - Contains the User's Manual, Modbus Datapoint List, Wiring Diagram, and Device Template for Off-line Parameter Setting;

Disk 2 - Contains PowerPort-E and Quality Manager software applications.

Disk1 contains the device templates. The device templates MUST BE installed to allow PowerPort-E to configure a device off-line.

Please make sure the product label, wiring diagram, type code, and materials and description pertain to this device. If you have any doubts, please contact Eaton Corporation's Customer Service Department.

StorageThe devices must not be stored outdoors. If stored, it must be stored in an area with temperature and humidity control (see the Technical Data section contained in this manual).

Important Information

In line with the customer’s requirement, the devices are combined in a modular way (in compliance with the order code). The terminal assignment of the device can be found on the top of the device (wiring diagram). In addition, it can be found within the Appendix of this manual (see Wiring Diagrams).

www.eaton.com 17

Page 18: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Symbols

18 www.eaton.com

Inac

tive

Activ

e

IG.n

ondi

r Trip

at

VG=0

1 2

Setti

ng V

alue

:<N

ame>

.I

Dev

ice

Plan

ning

:<N

ame>

Sign

al:

IGM

easu

red

Valu

es:

<Nam

e>.*i

nt A

lm L

1In

tern

al m

essa

ge

Func

tiona

l des

crip

tion:

If th

e se

tting

va

lue

"IG.B

lock

at V

G=0

" is

set t

o "in

activ

e", t

he o

utpu

t 1 is

act

ive

and

outp

ut 2

is in

activ

e. If

the

setti

ng v

alue

"IG

.Blo

ck a

t VE=

0" is

set

to "a

ctiv

e",

the

outp

ut 2

is a

ctiv

e an

d th

e ou

tput

1

is in

activ

e.

Prot

.I di

r fw

d

AR.t-

D

0t-D

φ

"φ"=

Elem

ents

with

com

plex

func

tions

"g

ray-

box"

.

Inac

tive

Activ

e

Bkr.L

atch

edO

ptio

n/fe

atur

es to

be

real

ised

in th

e fu

ture

.

Para

met

er o

f a M

odul

e-In

put w

ith a

Se

lect

ionL

ist/D

ropD

own.

An

(1..n

) si

gnal

/out

put f

rom

the

list o

r a p

re-

defin

ed v

alue

can

be

sele

cted

.1.

.n, A

ssig

nmen

t Lis

t

<Nam

e>

1..n

, VeE

nabl

e

No

assi

gnm

ent,1

..n

No

assi

gnm

ent

1

<Nam

e>

1..n

, Ass

ignm

ent L

ist

Para

met

er o

f a M

odul

e-In

put (

with

sp

ecia

l val

ues)

: An

(1..n

) out

put f

rom

the

list w

ill be

ass

igne

d to

the

inpu

t "<

nam

e>.id

entif

ier".

If th

e pa

ram

eter

is

set t

o "It

emN

ull",

an

"act

ive"

-sig

nal w

ill be

gi

ven

out.

Lim

it va

lue

mon

itorin

g w

ith th

ree

anal

og in

put v

alue

s. C

ompa

res

3 an

alog

val

ues

with

the

set l

imit;

out

put

valu

es a

re th

ree

diffe

rent

bin

ary

valu

es a

s a

resu

lt of

the

com

paris

ion.

If

the

anal

og s

igna

l exc

eeds

the

limit

I/In

, the

cor

resp

ondi

ng o

utpu

t sig

nal

beco

mes

"1".

I/ In

IA IB IC

<20%

VnV

Lim

it va

lue

mon

itorin

g (C

ompa

red

to

a fix

ed v

alue

). C

ompa

res

a va

lue

with

th

e fix

ed s

et li

mit;

out

put v

alue

is

bina

ry a

s a

resu

lt of

the

com

paris

ion.

If

the

sign

al e

xcee

ds th

e lim

it, th

e co

rresp

ondi

ng o

utpu

t sig

nal b

ecom

es

"1".

Adap

tive

Par

amet

er

Sele

ctio

n Li

st

<Nam

e>

Dire

ct C

omm

and

Page 19: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 19

And

Or

Neg

ated

Inpu

t

Neg

ated

Out

put

Band

-pas

s (fi

lter)

IH1

Band

-pas

s (fi

lter)

IH2

Quo

tient

of A

nalo

g Va

lues

t1

Del

ay T

imer

1

Bkr.t

-Trip

Cm

d

t

Anal

og V

alue

s

AND

S

Q

R1

Q

a b

c dR

S fli

p-flo

pa

b c

d0

0 U

ncha

nged

0 1

0 1

1 0

1 0

1 1

0 1

Tim

e st

age:

A "1

" at t

he

inpu

t sta

rts th

e el

emen

t. If

the

time

<nam

e>.t

is

expi

red,

the

outp

ut b

ecom

es

"1" t

oo. T

he ti

me

stag

e w

ill be

rese

t by

"0" a

t the

inpu

t. Th

us th

e ou

tput

will

be s

et to

"0

" at t

he s

ame

time.

Tim

e st

age

min

imum

pul

se

wid

th: T

he p

ulse

wid

th

<nam

e>.t

will

be s

tarte

d if

a "1

" is

feed

to th

e in

put.

By

star

ting

<nam

e>.t,

the

outp

ut b

ecom

es "1

". If

the

time

is e

xpire

d, th

e ou

tput

be

com

es "0

" ind

epen

dent

fro

m th

e in

put s

igna

l.

IH1

IH2

Excl

usiv

e-XR

Anal

og V

alue

C

ompa

rato

r

+ R+

Incr

emen

tR

Res

et

Edge

trig

gere

d co

unte

r

IH2

IH1OR

XO

R

Inve

rting

t2

t1: S

witc

h O

n D

elay

t2: S

witc

h O

ff D

elay

Del

ay T

imer

t1t2

t1t2 C

ount

er

Page 20: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

20 www.eaton.com

22

Inpu

t Sig

nal

Out

put S

igna

l

2N

ame.

Activ

e

3N

ame.

Blo

Trip

Cm

d

4N

ame.

Activ

e

5IH

2.Bl

o Ph

ase

A

6IH

2.Bl

o Ph

ase

B

7IH

2.Bl

o Ph

ase

C

8IH

2.Bl

o IG

9N

ame.

Fau

lt in

Pro

ject

ed D

irect

ion

10N

ame.

Fau

lt in

Pro

ject

ed D

irect

ion

10a

Prot

-50

R -

Dire

ctio

n D

etec

tion

10b

Prot

-50

X -D

irect

ion

Det

ectio

n

14 15N

ame.

Trip

Cm

d

1Pr

ot.A

vaila

ble

Plea

se R

efer

to D

iagr

am: B

lock

ings

Plea

se R

efer

to D

iagr

am: B

lock

ings

**

Plea

se R

efer

to D

iagr

am: P

rot

Plea

se R

efer

to D

iagr

am: T

rip B

lock

ings

Plea

se R

efer

to D

iagr

am: I

H2

Plea

se R

efer

to D

iagr

am: I

H2

Plea

se R

efer

to D

iagr

am: I

H2

Plea

se R

efer

to D

iagr

am: I

H2

Plea

se R

efer

to D

iagr

am: D

irect

ion

Dec

isio

n Ph

ase

over

curre

nt

Plea

se R

efer

to D

iagr

am: D

irect

ion

Dec

isio

n G

roun

d Fa

ult

Plea

se R

efer

to D

iagr

am: D

irect

ion

Dec

isio

n G

roun

d Fa

ult

Plea

se R

efer

to D

iagr

am: D

irect

ion

Dec

isio

n G

roun

d Fa

ult

Nam

e.Pi

ckup

Each

pic

kup

of a

mod

ule

(exc

ept f

rom

su

perv

isio

n m

odul

es b

ut in

clud

ing

BF) w

ill

lead

to a

gen

eral

pic

kup

(col

lect

ive

pick

up).

Each

trip

of a

n ac

tive,

trip

aut

horiz

ed

prot

ectio

n m

odul

e w

ill le

ad to

a g

ener

al tr

ip.

17b

Nam

e.Tr

ip P

hase

B

18

Nam

e.Tr

ip P

hase

C

19

Nam

e.Tr

ipC

md

16

Nam

e.Tr

ip P

hase

A

Eac

h tri

p of

an

activ

e, tr

ip a

utho

rized

pro

tect

ion

mod

ule

will

lead

to a

gen

eral

trip

.

Eac

h tri

p of

an

activ

e, tr

ip a

utho

rized

pro

tect

ion

mod

ule

will

lead

to a

gen

eral

trip

.

Eac

h tri

p of

an

activ

e, tr

ip a

utho

rized

pro

tect

ion

mod

ule

will

lead

to a

gen

eral

trip

.

Eac

h tri

p of

an

activ

e, tr

ip a

utho

rized

pro

tect

ion

mod

ule

will

lead

to a

gen

eral

trip

.

16a

Nam

e.Tr

ip P

hase

A

Eac

h tri

p of

an

activ

e, tr

ip a

utho

rized

pro

tect

ion

mod

ule

will

lead

to a

gen

eral

trip

.

16b

Nam

e.Tr

ip P

hase

A

Eac

h tri

p of

an

activ

e, tr

ip a

utho

rized

pro

tect

ion

mod

ule

will

lead

to a

gen

eral

trip

.

17

Nam

e.Tr

ip P

hase

B

Eac

h tri

p of

an

activ

e, tr

ip a

utho

rized

pro

tect

ion

mod

ule

will

lead

to a

gen

eral

trip

.

17a

Nam

e.Tr

ip P

hase

B

Eac

h tri

p of

an

activ

e, tr

ip a

utho

rized

pro

tect

ion

mod

ule

will

lead

to a

gen

eral

trip

.

19a

Nam

e.Tr

ipC

md

Eac

h tri

p of

an

activ

e, tr

ip a

utho

rized

pro

tect

ion

mod

ule

will

lead

to a

gen

eral

trip

.

19b

Nam

e.Tr

ipC

md

Eac

h tri

p of

an

activ

e, tr

ip a

utho

rized

pro

tect

ion

mod

ule

will

lead

to a

gen

eral

trip

.

19c

Nam

e.Tr

ipC

md

Eac

h tri

p of

an

activ

e, tr

ip a

utho

rized

pro

tect

ion

mod

ule

will

lead

to a

gen

eral

trip

.

19d

Nam

e.Tr

ipC

md

Eac

h tri

p of

an

activ

e, tr

ip a

utho

rized

pro

tect

ion

mod

ule

will

lead

to a

gen

eral

trip

.

18a

Nam

e.Tr

ip P

hase

C

Eac

h tri

p of

an

activ

e, tr

ip a

utho

rized

pro

tect

ion

mod

ule

will

lead

to a

gen

eral

trip

.

18b

Nam

e.Tr

ip P

hase

C

Eac

h tri

p of

an

activ

e, tr

ip a

utho

rized

pro

tect

ion

mod

ule

will

lead

to a

gen

eral

trip

.

11 12VT

S.Pi

ckup

Ple

ase

Ref

er to

Dia

gram

: VTS

VTS.

Pick

upP

leas

e R

efer

to D

iagr

am: V

TS

Page 21: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 21

34Bk

r.Pos

CLO

SE

35Bk

r.Pos

OPE

N

33Bk

r.Sta

te

Ple

ase

Ref

er to

Dia

gram

: Bkr

.Bkr

Man

ager

Ple

ase

Ref

er to

Dia

gram

: Bkr

.Bkr

Man

ager

Ple

ase

Ref

er to

Dia

gram

: Bkr

.Bkr

Man

ager

36Bk

r.Pos

Inde

term

37Bk

r.Pos

Dis

turb

Plea

se R

efer

to D

iagr

am: B

kr.B

kr M

anag

er

Plea

se R

efer

to D

iagr

am: B

kr.B

kr M

anag

er

20N

ame.

Trip

Pha

se A

21N

ame.

Trip

Pha

se B

Each

trip

of a

n ac

tive,

trip

aut

horiz

ed p

rote

ctio

n m

odul

e w

ill le

ad to

a g

ener

al tr

ip.

Each

trip

of a

n ac

tive,

trip

aut

horiz

ed p

rote

ctio

n m

odul

e w

ill le

ad to

a g

ener

al tr

ip.

22N

ame.

Trip

Pha

se C

23N

ame.

Trip

Each

trip

of a

n ac

tive,

trip

aut

horiz

ed p

rote

ctio

n m

odul

e w

ill le

ad to

a g

ener

al tr

ip.

Each

trip

of a

n ac

tive,

trip

aut

horiz

ed p

rote

ctio

n m

odul

e w

ill le

ad to

a g

ener

al tr

ip.

25N

ame.

Pick

up IB

26b

Nam

e.Pi

ckup

IC

27N

ame.

Pick

up

28N

ame.

Pick

up P

hase

A

29N

ame.

Pick

up P

hase

B

24N

ame.

Pick

up IA

Each

pha

se s

elec

tive

pick

up o

f a m

odul

e (I,

IG, V

, VX

de

pend

ing

on th

e de

vice

type

) will

lead

to a

pha

se

sele

ctiv

e ge

nera

l pic

kup

(col

lect

ive

pick

up).

Each

pha

se s

elec

tive

pick

up o

f a m

odul

e (I,

IG, V

, VX

de

pend

ing

on th

e de

vice

type

) will

lead

to a

pha

se

sele

ctiv

e ge

nera

l pic

kup

(col

lect

ive

pick

up).

Each

pha

se s

elec

tive

pick

up o

f a m

odul

e (I,

IG, V

, VX

de

pend

ing

on th

e de

vice

type

) will

lead

to a

pha

se

sele

ctiv

e ge

nera

l pic

kup

(col

lect

ive

pick

up).

Each

pha

se s

elec

tive

pick

up o

f a m

odul

e (I,

IG, V

, VX

de

pend

ing

on th

e de

vice

type

) will

lead

to a

pha

se

sele

ctiv

e ge

nera

l pic

kup

(col

lect

ive

pick

up).

Each

pha

se s

elec

tive

pick

up o

f a m

odul

e (I,

IG, V

, VX

depe

ndin

g on

the

devi

ce ty

pe) w

ill le

ad to

a p

hase

se

lect

ive

gene

ral p

icku

p (c

olle

ctiv

e pi

ckup

).

Each

pha

se s

elec

tive

pick

up o

f a m

odul

e (I,

IG, V

, VX

depe

ndin

g on

the

devi

ce ty

pe) w

ill le

ad to

a p

hase

se

lect

ive

gene

ral p

icku

p (c

olle

ctiv

e pi

ckup

).

30N

ame.

Pick

up P

hase

C

31N

ame.

Pick

up

Each

pha

se s

elec

tive

pick

up o

f a m

odul

e (I,

IG, V

, VX

depe

ndin

g on

the

devi

ce ty

pe) w

ill le

ad to

a p

hase

se

lect

ive

gene

ral p

icku

p (c

olle

ctiv

e pi

ckup

).

Each

pha

se s

elec

tive

pick

up o

f a m

odul

e (I,

IG, V

, VX

depe

ndin

g on

the

devi

ce ty

pe) w

ill le

ad to

a p

hase

se

lect

ive

gene

ral p

icku

p (c

olle

ctiv

e pi

ckup

).

32Pr

ot.B

lo T

ripC

md

24a

Nam

e.Pi

ckup

IA

Each

pha

se s

elec

tive

pick

up o

f a m

odul

e (I,

IG, V

, VX

depe

ndin

g on

the

devi

ce ty

pe) w

ill le

ad to

a p

hase

se

lect

ive

gene

ral p

icku

p (c

olle

ctiv

e pi

ckup

).

24b

Nam

e.Pi

ckup

IA

Each

pha

se s

elec

tive

pick

up o

f a m

odul

e (I,

IG, V

, VX

de

pend

ing

on th

e de

vice

type

) will

lead

to a

pha

se

sele

ctiv

e ge

nera

l pic

kup

(col

lect

ive

pick

up).

25a

Nam

e.Pi

ckup

IB

Each

pha

se s

elec

tive

pick

up o

f a m

odul

e (I,

IG, V

, VX

depe

ndin

g on

the

devi

ce ty

pe) w

ill le

ad to

a p

hase

se

lect

ive

gene

ral p

icku

p (c

olle

ctiv

e pi

ckup

).

25b

Nam

e.Pi

ckup

IB

Each

pha

se s

elec

tive

pick

up o

f a m

odul

e (I,

IG, V

, VX

de

pend

ing

on th

e de

vice

type

) will

lead

to a

pha

se

sele

ctiv

e ge

nera

l pic

kup

(col

lect

ive

pick

up).

26N

ame.

Pick

up IC

Each

pha

se s

elec

tive

pick

up o

f a m

odul

e (I,

IG, V

, VX

de

pend

ing

on th

e de

vice

type

) will

lead

to a

pha

se

sele

ctiv

e ge

nera

l pic

kup

(col

lect

ive

pick

up).

26a

Nam

e.Pi

ckup

IC

Each

pha

se s

elec

tive

pick

up o

f a m

odul

e (I,

IG, V

, VX

de

pend

ing

on th

e de

vice

type

) will

lead

to a

pha

se

sele

ctiv

e ge

nera

l pic

kup

(col

lect

ive

pick

up).

27a

Nam

e.Pi

ckup

Eac

h ph

ase

sele

ctiv

e pi

ckup

of a

mod

ule

(I, IG

, V, V

X de

pend

ing

on th

e de

vice

type

) will

lead

to a

pha

se

sele

ctiv

e ge

nera

l pic

kup

(col

lect

ive

pick

up).

27b

Nam

e.Pi

ckup

Each

pha

se s

elec

tive

pick

up o

f a m

odul

e (I,

IG, V

, VX

depe

ndin

g on

the

devi

ce ty

pe) w

ill le

ad to

a p

hase

se

lect

ive

gene

ral p

icku

p (c

olle

ctiv

e pi

ckup

).

27c

Nam

e.Pi

ckup

Eac

h ph

ase

sele

ctiv

e pi

ckup

of a

mod

ule

(I, IG

, V, V

X de

pend

ing

on th

e de

vice

type

) will

lead

to a

pha

se

sele

ctiv

e ge

nera

l pic

kup

(col

lect

ive

pick

up).

27d

Nam

e.Pi

ckup

Eac

h ph

ase

sele

ctiv

e pi

ckup

of a

mod

ule

(I, IG

, V, V

X de

pend

ing

on th

e de

vice

type

) will

lead

to a

pha

se

sele

ctiv

e ge

nera

l pic

kup

(col

lect

ive

pick

up).

38Pl

ease

Ref

er to

Dia

gram

: LO

P.LO

P Bl

o LO

P.LO

P Bl

o

39P

leas

e R

efer

to D

iagr

am: Q

->&V

<.D

ecou

plin

g En

ergy

Res

ourc

eQ

->&V

<.D

ecou

plin

g En

ergy

Res

ourc

e

40P

leas

e R

efer

to D

iagr

am: C

TS.P

icku

pC

TS.P

icku

p

Page 22: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

22 www.eaton.com

41Br

eake

r.Pro

t CLO

SE

42Br

eake

r.CLO

SE C

md

Brea

ker.P

rot C

LOSE

Brea

ker.C

LOS

E C

md

Page 23: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

General Conventions

www.eaton.com 23

»Parameters are indicated by right and left double arrow heads and written in italic.«

»SIGNALS are indicated by right and left double arrow heads and small caps.«

[Paths are indicated by brackets.]

Software and Device names are written in italic.

Module and Instance (Element) names are displayed italic and underlined.

»Pushbuttons, Modes, and Menu entries are indicated by right and left double arrow heads.«

1 2 3 Image References (Squares)

.

Page 24: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

DeviceEDR-5000

Device PlanningPlanning of a device means to reduce the functional range to a degree that suits the protection task to be fulfilled (i.e.: the device shows only those functions needed or desired). If the User, for example, deactivates the voltage protection function, all parameter branches related to this function will not appear in the parameter. All corresponding events, signals, etc. will also be deactivated. Due to this change, the parameter trees become very transparent.

Planning also involves adjustment of all basic system data (frequency etc.).

It MUST be taken into account that by deactivating, for instance, protective functions, the User also changes the functionality of the device. If the User cancels the directional feature of the overcurrent protections, then the device no longer trips in a directional way but merely in a non-directional way.

The manufacturer does not accept liability for any personal or material damage as a result of incorrect planning.

Contact your Eaton Customer Service representative for more information.

Beware of the inadvertent deactivating of protective functions/modules.

If the User is deactivating modules within the device planning, all parameters of those modules will be set on default.

If the User is activating one of these modules, again, all parameters of those reactivated modules will be set on default.

If the protective device is equipped with Zone Interlocking, overcurrent and earth current elements are needed to trigger the Zone Interlocking function. Therefore, some overcurrent and earth current elements cannot be deactivated if the device is equipped with Zone Interlocking.

Device Planning Parameters of the Device

Parameter Description Options Default Menu Path

Hardware Variant 1

Optional Hardware Extension »A« 8 DI, 2 Form A, 8+1 Form C, ZI

8 DI, 2 Form A, 8+1 Form C, ZI

[EDR-5000]

Hardware Variant 2

Optional Hardware Extension »0« Without,

»1« Sensitive Ground Current

»0« Without

[EDR-5000]

24 www.eaton.com

Page 25: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Options Default Menu Path

Communication

Communication »B« Modbus RTU: RS485 / Terminals,

»H« Ethernet: RJ45,

»I« RS485 term / Ethernet

Modbus RTU: RS485 / Terminals

[EDR-5000]

Printed Circuit Board

Printed Circuit Board »A« Standard,

»B« Conformal Coating

»A« Standard

[EDR-5000]

There are two mounts available for the EDR-5000: a Standard Mount and a Projection Mount. To order the EDR-5000 with a Standard Mount, append the device code with a zero (0). To order the EDR-5000 with a Pro-jection Mount, append the device code with a one (1). Refer to the table below for details of the available device options.

A retrofit kit for Eaton IQ cutouts is available (Style No. 66D2217G01 – Catalog No. ER-IQEDRKIT). This kit is required when replacing a DT-3000 with the EDR-5000.

EDR-5000 Eaton Distribution Relay Removable Terminals

EDR-5000 A 0 B A 1

Choose from the following options.

Hardware Option 1

8 DI, 11 Outputs, Removable Terminals, Zone Interlocking.

A

8 DI, 11 Outputs, Removable Terminals, Zone Interlocking, and Larger Display*.

B

Hardware Option 2

Phase Current 5A/1A, Ground Current 5A/1A, Power Supply Range: 19-300 Vdc, 40-250 Vac.

0 (Zero)

Phase Current 5A/1A, Sensitive Ground Current 0.5A/0.1A, Power Supply Range: 19-300 Vdc, 40-250 Vac.*

1

Communication Options

Modbus-RTU (RS-485) B

IEC-61850 (Goose) H

Modbus-RTU + Modbus-TCP I

www.eaton.com 25

Page 26: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Conformal Coating Options

None A

Conformal Coated Circuit Boards B

Mounting Options

Standard Mount 0 (Zero)

Projection Panel Mount 1

* Consult the factory for the availability of sensitive ground and larger display.

The catalog number identification table defines the electrical characteristics and operation features included in the EDR-5000. For example, if the catalog number were EDR-5000A0BA1, the device would have the following:

EDR-5000

(A) - 8 DI, 11 Outputs Relays, Removable Terminals, Zone Interlocking

(0) - 5A/1A Phase and Ground CTs, Power Supply Range: 19-300 Vdc, 40-250 Vac.

(B) - Modbus-RTU (RS-485)

(A) - Without Conformal Coating

(1) - Projection Panel Mount

26 www.eaton.com

Page 27: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Installation and Wiring

Three-Side-View

Depending on the connection method of the communication system used, the needed space (depth) differs. If, for instance, a D-Sub-Plug is used, it has to be added to the depth dimension.

Even when the auxiliary voltage is switched-off, unsafe voltages remain at the device connections.

Outline Projection Mount - Door Cut-out

The housing must be carefully grounded. Connect a ground cable (AWG 12-10 [4 to 6 mm2] / 15 In-lb [1.7 Nm]) to the housing, using the screw that is marked with the ground symbol (at the rear side of the device).

The power supply card needs a separate ground connection (AWG 14 [2.5 mm2] / 5-7 In-lb [0.56-0.79 Nm]) at terminal X1.

DO NOT over-tighten the mounting nuts of the relay (0.164 X32 ). Check the torque by means of a torque wrench (1.7 Nm [15 In-lb]). Over-tightening the mounting nuts could cause personal injury or damage the relay.

www.eaton.com 27

Page 28: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Outline Standard Mount - Door Cut-out

The housing must be carefully grounded. Connect a ground cable (AWG 12-10 [4 to 6 mm2] / 15 In-lb [1.7 Nm]) to the housing, using the screw that is marked with the ground symbol (at the rear side of the device).

The power supply card needs a separate ground connection (AWG 14 [2.5 mm2] / 5-7 In-lb [0.56-0.79 Nm]) at terminal X1.

Overview of Slots - Assembly Groups

In line with the customers' requirement, the devices are combined in a modular way (in compliance with the order code). In each of the slots, an assembly/group may be integrated. In the following diagram, the terminal assignment of the individual assembly/groups are shown. The exact installation/placement of the individual modules can be determined from the connection diagram attached to the top of your device.

28 www.eaton.com

Page 29: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Overview of Slots

Housing B2

Schematic Diagram

The housing must be carefully grounded. Connect a ground cable (AWG 12-10 [4 to 6 mm2] / 15 In-lb [1.7 Nm]) to the housing, using the screw that is marked with the ground symbol (at the rear side of the device).

The power supply card needs a separate ground connection (AWG 14 [2.5 mm2] / 5-7 In-lb [0.56-0.79 Nm]) at terminal X1.

Grounding

The housing must be carefully grounded. Connect a ground cable (AWG 12-10 [4 to 6 mm2] / 15 In-lb [1.7 Nm]) to the housing, using the screw that is marked with the ground symbol (at the rear side of the device).

The power supply card needs a separate ground connection (AWG 14 [2.5 mm2] / 5-7 In-lb [0.56-0.79 Nm]) at terminal X1.

The devices are very sensitive to electrostatic discharges.

www.eaton.com 29

X1 X2 X3

X100 X102

X5 X6

X104

X4

X103

Slot3 Slot4 Slot5 Slot6Slot1 Slot2

X101

Page 30: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Typical Connection Diagrams

Wye VTs and 5 A CTs in Residual Connection

30 www.eaton.com

1X4.

2345678

A B C

C

B

A

A B C1

X3.

23456789

101112IX'

IA

1A

5A

N

IB

1A

5A

N

IC

1A

5A

N

IX

1A

5A

N

VX

VC/VCA

VB/VBC

VA/VAB

IA IB IC

IB'

IC'

IA'

LOAD

Page 31: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Wye Input Wiring with Aux VX Input Connected to the Load Side of the Breaker and 1A CTs in Residual Connection

www.eaton.com 31

1X4.

2345678

A B C

C

B

A

A B C1

X3.

23456789101112IX'

IA

1A

5A

N

IB

1A

5A

N

IC

1A

5A

N

IX

1A

5A

N

VX

VC/VCA

VB/VBC

VA/VAB

IA IB IC

IB'

IC'

IA'

LOAD

Page 32: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Open Delta VTs Input Wiring and 1 A CTs in Residual Connection

32 www.eaton.com

C

B

A

A B C1

X3.

23456789

101112IX'

IA

1A

5A

N

IB

1A

5A

N

IC

1A

5A

N

IX

1A

5A

N

IA IB IC

IB'

IC'

IA'

A B C 1X4.

2345678

VX

VC/VCA

VB/VBC

VA/VAB

LOAD

Page 33: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Open Delta VTs Input Wiring with Aux VTs Connected to the Load Side of the Breaker and 1A CTs in Residual Connection

www.eaton.com 33

A B C 1X4.

2345678

VX

VC/VCA

VB/VBC

VA/VAB

C

B

A

A B C1

X3.

23456789

101112IX'

IA

1A

5A

N

IB

1A

5A

N

IC

1A

5A

N

IX

1A

5A

N

IA IB IC

IB'

IC'

IA'

LOAD

Page 34: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Slot X1: Power Supply Card with Digital Inputs

Rear Side of the Device (Slots)

The type of power supply card and the number of digital inputs on it used in this slot is dependent on the ordered device type. The different variants have a different scope of functions.

Available assembly groups in this slot:

• (DI8-X1): This assembly group comprises a wide-range power supply unit; and two non-grouped digital inputs and six (6) digital inputs (grouped).

The available combinations can be gathered from the ordering code.

DI-8 X - Power Supply and Digital Inputs

Make sure that the tightening torque is 5-7 In-lb [0.56-0.79 Nm].

This assembly group comprises:

• A wide-range power supply unit;• Two non-grouped digital inputs; and• Six (6) digital inputs, grouped.

34 www.eaton.com

X1 X2 X3

X100 X102

X5 X6

X104

X4

X103

Slot3 Slot4 Slot5 Slot6Slot1 Slot2

X101

Page 35: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Auxiliary Voltage Supply

• The auxiliary voltage inputs (wide-range power supply unit) are non-polarized. The device can be powered with an AC or DC control voltage.

Digital Inputs

For each digital input group, the related voltage input range has to be configured. Wrong switching thresholds can result in malfunctions/wrong signal transfer times.

The digital inputs are provided with different switching thresholds (that are configurable) (two AC and five DC in-put ranges). The following switching levels can be defined:

• 24 Vdc;• 48 Vdc • 60 Vdc;• 110/120 Vac/dc; and• 230/240 Vac/dc.

If a voltage >80% of the set switching threshold is applied at the digital input, the state change is recognized (logically “1”). If the voltage is below 40% of the set switching threshold, the device detects logically “0”.

When using DC supply, the negative potential has to be connected to the common terminal (COM1, COM2, COM3 - please see the terminal marking).

www.eaton.com 35

Page 36: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Terminal Marking

Pin Assignment

36 www.eaton.com

V+

V-

PE

COM1

DI1

COM2

DI2

DI3

DI4

DI5

DI6

DI7

DI8

COM3

Do not use

0+HTL-NT

COM3

N.C.

Do not use

13

24

56

78

910

1112

1314

1516

1718

Power Supply

12345678

PE

9101112

COM1

131415161718

V+ Power Supply

DI1COM2DI2COM3

DI3DI4DI5DI6DI7DI8

COM

Do not useDo not use

V-

X?.

N.C.

Page 37: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Slot X2: Relay Output Card - Zone Interlock

Rear Side of the Device (Slots)

The type of card in this slot is dependent on the ordered device type. The different variants have a different scope of functions.

Available assembly groups in this slot:

• (RO-4Z X2): Assembly Group with four Relay Outputs (two Form A and two Form C) and Zone Interlocking.

The available combinations can be gathered from the ordering code.

RO-ZI X - Relay Outputs and Zone Interlock

The Relay Outputs are potential-free contacts. In the Assignment/Relay Outputs section, the assignment of the Relay Outputs is specified. The changeable signals are listed in the Assignment List section.

Make sure that the tightening torque is 5-7 In-lb [0.56-0.79 Nm].

Please carefully consider the current carrying capacity of the Relay Outputs. Please refer to the Technical Data.

www.eaton.com 37

X1 X2 X3

X100 X102

X5 X6

X104

X4

X103

Slot3 Slot4 Slot5 Slot6Slot1 Slot2

X101

Page 38: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Terminal Marking

Pin Assignment

38 www.eaton.com

Do not use

Do not use

RO3 CMN

RO3 N.O.

RO3 N.C.

13

24

56

78

910

1112

1314

1516

1718

RO-4Z X

RO1 N.O.

RO2 N.O.

COM

OUT

IN

COM

RO4 CMN

RO4 N.O.

RO4 N.C.

123456789

101112131415161718

RO3

X?.Do not use

Do not use

COM

OUT

IN

COM

RO4

RO1

RO2

Page 39: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Slot X3: Current Transformer Measuring Inputs

Rear Side of the Device (Slots)

This slot contains the current transformer measuring inputs. Depending on the order code, this might be a standard current measuring card or a sensitive ground current measuring card.

Available assembly groups in this slot:

• (TI-4 X3): Standard ground current measuring card.

• (TIS-4 X3): Sensitive Ground current measuring card.

The available combinations can be gathered from the ordering code.

TI X- Standard Phase and Ground Current Measuring Input Card

A current measuring card is provided with four (4) current measuring inputs: three for measuring the phase currents and one for measuring of the ground current. Each of the current measuring inputs has a measuring input for 1 A and 5 A.

The input for ground current measuring either can be connected to a zero sequence current transformer or, alternatively, it is possible to connect the summation current path of the phase current transformer to this input (residual connection).

Current transformers have to be earth grounded on their secondary side.

www.eaton.com 39

X1 X2 X3

X100 X102

X5 X6

X104

X4

X103

Slot3 Slot4 Slot5 Slot6Slot1 Slot2

X101

Page 40: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Interrupting the secondary circuits of current transformers causes hazardous voltages.

The secondary side of the current transformers have to be short circuited before the current circuit to the device is opened.

The current measuring inputs may exclusively be connected to current measuring transformers (with galvanic separation).

• Do not mix the inputs (1 A/5 A).

• Make sure the transformer ratios and the power of the CTs are correctly rated. If the rating of the CTs is not correct (overrated), then the normal operational conditions may not be recognized. The pickup value of the measuring unit amounts to approximately 3% of the rated current of the device. Also, the CTs need a current greater than approximately 3% of the rated current to ensure sufficient accuracy.

Example: For a 600 A CT (primary current), any currents below 18 A cannot be detected.

• Overloading can result in destruction of the measuring inputs or faulty signals. Overloading means that, in case of a short circuit, the current carrying capacity of the measuring inputs could be exceeded.

Make sure that the tightening torque is 17.7 In-lb [2 Nm].

40 www.eaton.com

Page 41: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Terminal Markings

Pin Assignment

www.eaton.com 41

0+HTL-TI-x

IA-1A

IA-N

IA-5A

IB-1A

IB-N

IC-1A

IC-N

IC-5A

IX-1A

IX-N

IX-5A

IB-5A

1

2

3

4

5

6

7

8

10

11

9

12

123456789

101112

IA

1A

5A

N

IB

1A

5A

N

IC

1A

5A

N

IX

1A

5A

N

X?.

Page 42: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

TIS X – Phase and Sensitive Ground Current Measuring Card

The sensitive ground current measuring card is provided with four (4) current measuring inputs: three for measuring the phase currents and one for measuring of the sensitive ground current. Each of the phase current measuring inputs has a measuring input for 1 A and 5 A.

The sensitive ground current measuring inputs has a measuring input for 0.1 A and 0.5 A.

The input for ground current measuring either can be connected to a zero sequence current transformer or, alternatively, it is possible to connect the summation current path of the phase current transformer to this input (residual connection).

Current transformers have to be earth grounded on their secondary side.

Interrupting the secondary circuits of current transformers causes hazardous voltages.

The secondary side of the current transformers have to be short circuited before the current circuit to the device is opened.

The current measuring inputs may exclusively be connected to current measuring transformers (with galvanic separation).

Make sure that the tightening torque is 17.7 In-lb [2 Nm].

42 www.eaton.com

Page 43: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Terminal Markings

Pin Assignment

Common CT Wiring Configurations

Check the installation direction.

It is imperative that the secondary sides of measuring transformers be grounded.

www.eaton.com 43

IA-1A

IA-N

IA-5A

IB-1A

IB-N

IC-1A

IC-N

IC-5A

IX-0.1A

IX-N

IX-0.5A

IB-5A

1

2

3

4

5

6

7

8

10

11

9

12

123456789

101112

IA

1A

5A

N

IB

1A

5A

N

IC

1A

5A

N

IX

0.1A

0.5A

N

X?.

Page 44: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

The current measuring inputs may exclusively be connected to current measuring transformers (with galvanic separation).

CT secondary circuits must always to be low-burdened or short-circuited during operation.

For current and voltage sensing function external wired and appropriate current and voltage transformer shall be used, based on the required input measurement ratings. Those devices provide the necessary insulation functionality.

All current measuring inputs can be provided with 1 A or 5 A nominal. Make sure that the wiring is correct.

CT Connection Options

The current transformers may be connected in several ways, and the specified configuration affects the way system measurements are made and results computed. The computation of the residual current IR, is dependent on the system configuration setting for the CT connection. The configurations resulting from the setting options are shown as well as the calculated IR residual current.

3-phase, 3-wire IG Calculated

44 www.eaton.com

A B C

IA

IB

IC

1X3.

23456789

101112

Three-phase Current Measurement; Inom Secondary = 5 A.

IA

1A

5A

N

IB

1A

5A

N

IC

1A

5A

N

IX

1A

5A

N

IB'

IC'

IA'

IR calc = IA + IB + IC = IG

Page 45: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

3-phase, 3-wire IG Measured

www.eaton.com 45

A B C

IB'

IA

IC'

IB

IC

IA'1

X3.

23456789

101112

Three-phase Current Measurement; Inom Secondary = 1 A.Ground Current Measuring via Zero Sequence CT ; IGnom Secondary = 1 A.

IX'

IA

1A

5A

N

IB

1A

5A

N

IC

1A

5A

N

IX

1A

5A

N

Warning!The shielding at the dismantled end of the line has to be put through the zero sequence current transformer and has to be grounded at the cable side.

Zero Sequence Current Transformer: Measures the ground current (sum of the three phase currents). Can be used for measuring the ground current in isolated and compensated networks. The shield is to be returned through the zero sequence current transformer.

IX meas = IG

IR calc = IA + IB + IC

Page 46: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

4-wire system, 4th CT on Neutral

46 www.eaton.com

A B C

IA

IB

IC

1X3.

23456789

101112

4-wire system, 4th CT on Neutral; In secondary = 5 A.

IA

1A

5A

N

IB

1A

5A

N

IC

1A

5A

N

IX

1A

5A

N

IB'

IC'

IA'

N

IN

IN'

IX meas=IN

IR calc = IG = IA + IB + IC - IN

IR calc´

Page 47: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

4-wire System Ground Current CT Involving Neutral

Slot X4: Voltage Transformer Measuring Inputs

Rear Side of the Device (Slots)

www.eaton.com 47

X1 X2 X3

X100 X102

X5 X6

X104

X4

X103

Slot3 Slot4 Slot5 Slot6Slot1 Slot2

X101

A B C

IA

IB

IC

1X3.

23456789101112

4-wire system with ground current CT (Torodial) involving Neutral; In secondary = 5 A.

IA

1A

5A

N

IB

1A

5A

N

IC

1A

5A

N

IX

1A

5A

N

IB'

IC'

IA'

N

INIX meas = IG

IR calc = IA + IB + IC = IG + IN

IR calc´

IG = IA + IB + IC + IN

Page 48: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

This slot contains the voltage transformer measuring inputs.

Voltage Measuring Inputs

The device is provided with 4 voltage measuring inputs. Three for measuring the mains voltages (»VAB«, »VBC« , »VCA« - in case of Open Delta) or phase-to-neutral voltages (»VA«, »VB«, »VC« in case of Wye). The fourth measuring input is to be used for »VX«.

Make sure that the tightening torque is 1.2-1-6 Nm [11-15 In-lb].

The rotating field of your power supply system has to be taken in to account. Make sure that the voltage transformers are wired correctly.

For the Open Delta connection the system parameter »Main VT con« has to be set to »Open Delta«.

For the Wye connection the system parameter »Main VT con« has to be set to »Wye«.

Please refer to the Technical Data.

48 www.eaton.com

Page 49: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Terminal Marking

Pin assignment

www.eaton.com 49

0+HTL-TU-x

VL1.112

63

78

54

VL1.2

VL2.1

VL2.2

VL3.1

VL3.2

VX1.1

VX1.2

12345678

VX

VL3/VL31

VL2/VL23

VL1/VL12

X?.

Page 50: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Common VT Wirings

Check the installation direction of the VTs.

It is imperative that the secondary sides of measuring transformers be grounded.

For current and voltage sensing function, externally wired and appropriate current and voltage transformer must be used, based on the required input measurement ratings. Those devices provide the necessary insulation functionality.

VT Check Measuring Values

Connect a three-phase measuring voltage equal to the rated voltage to the relay.

Take the connection of the measuring transformers (open delta/Wye connection) into account.

Now adjust the voltage values in the nominal voltage range with the corresponding nominal frequencies that are not likely to cause over-voltage or under-voltage trips.

Compare the values shown in the device display with the readings of the measuring instruments. The deviation must be according to the specifications in the Technical Data section.

50 www.eaton.com

Page 51: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

VT Wye

www.eaton.com 51

A B C

VAB

VBC

VCA

VA

VB

VC

VA'

A

C

B

NVB' VC'

VAB'

VBC'

VCA'1

X?.

2345678

Three-phase voltage measurement - wiring of the measurement inputs: "Wye"

VX

VC/VCA

VB/VBC

VA/VAB

Page 52: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

VT Open Delta

Slot X5: Relay Output Card

Rear Side of the Device (Slots)

52 www.eaton.com

X1 X2 X3

X100 X102

X5 X6

X104

X4

X103

Slot3 Slot4 Slot5 Slot6Slot1 Slot2

X101

A B C

VABVBC

VCA

A

C

BVAB'

VBC'

VCA'1

X?.

2345678

Two-phase voltage measurement - wiring of the measuring inputs: "Open Delta"

VX

VC/VCA

VB/VBC

VA/VAB

Page 53: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

The type of card in this slot is dependent on the ordered device type. The different variants have a different scope of functions.

Available assembly groups in this slot:

• (RO-6 X5): Assembly Group with 6 Relay Outputs (Form C).

The available combinations can be gathered from the ordering code.

RO-6 X - Relay Outputs

The Relay Outputs are potential-free contacts. In the Assignment/Relay Outputs section, the assignment of the Relay Outputs is specified. The changeable signals are listed in the Assignment List section.

Make sure that the tightening torque is 5-7 In-lb [0.56-0.79 Nm].

Please carefully consider the current carrying capacity of the Relay Outputs. Please refer to the Technical Data.

www.eaton.com 53

Page 54: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Terminal Marking

Pin Assignment

54 www.eaton.com

RO1 CMN

RO1 N.O.

RO1 N.C.

RO2 CMN

RO2 N.O.

RO2 N.C.

RO3 CMN

RO3 N.O.

RO3 N.C.

RO4 CMN

RO4 N.O.

RO4 N.C.

RO5 CMN

RO5 N.O.

RO5 N.C.

RO6 CMN

RO6 N.O.

RO6 N.C.

0+HTL-MK

13

24

56

78

910

1112

1314

1516

1718

123456789101112131415161718

RO3

RO1

RO2

RO4

RO5

RO6

X?.

Page 55: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Slot X100: Ethernet Interface

Rear Side of the Device (Slots)

An Ethernet interface may be available depending on the device type ordered.

The available combinations can be gathered from the ordering code.

Ethernet - RJ45

Terminal Marking

www.eaton.com 55

X1 X2 X3

X100 X102

X5 X6

X104

X4

X103

Slot3 Slot4 Slot5 Slot6Slot1 Slot2

X101

1 8

TxD

+

TxD

RxD

+

N.C

.

N.C

.

RxD

N.C

.

N.C

.

Page 56: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Slot X103: Data Communication

Rear Side of the Device (Slots)

The data communication interface in the X103 slot is dependent on the ordered device type. The scope of functions is dependent on the type of data communication interface.

Available assembly groups in this slot:

• RS485 Terminals

The available combinations can be gathered from the ordering code.

56 www.eaton.com

X1 X2 X3

X100 X102

X5 X6

X104

X4

X103

Slot3 Slot4 Slot5 Slot6Slot1 Slot2

X101

Page 57: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

RS485 - Modbus® RTU

Make sure that the tightening torque is 2-4 In-lb [0.22-0.45 Nm].

Terminal Marking

Pin Assignment

The Modbus® connection cable must be shielded. The shielding has to be fixed at the screw that is marked with the ground symbol at the rear side of the device.

The communication is Half Duplex.

www.eaton.com 57

64 5321

R1R2

R1

+5V GND

R1 = 560 ΩR2 = 120 Ω

B(+

)

A(-

)

Protective Relay

HF

Shi

eld

1X

103

2 3 4 5 6

B(+

)

A(-

)

+5V GND

560

Ω

560Ω120Ω

Protective Relay

HF

Shi

eld

Page 58: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Wiring Example: Device in the Middle of the Bus

Wiring Example: Device at the End of the BUS (Using the Integrated Terminal Resistor)

58 www.eaton.com

64 5321

+5V GND

R1 = 560 ΩR2 = 120 Ω

Protective Relay

B(+)

A(-)

R1R2

R1

HF

Shi

eld

64 5321

+5V GND

R1 = 560 ΩR2 = 120 Ω

Protective Relay

B(+)

B(+)*

A(-)

A(-)*

R1R2

R1

HF

Shi

eld

Page 59: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Shielding Options (2-wire + Shield)

Shielding Options (3-wire + Shield)

www.eaton.com 59

1 32 4 5 6

TR-P

2.2nF(internal)

1 32 4 5 6

TR-P

2.2nF(internal)

1 32 4 5 6

TR-P

2.2nF(internal)

1 32 4 5 6TR

-P

2.2nF(internal)

Shield at bus master side connected to earth termination

resistors used

Shield at bus device side connected to earth termination

resistors used

Shield at bus master side connected to earth termination

resistors not used

Shield at bus device side connected to earth termination

resistors not used

B(+

)

A(-

)

B(+

)

A(-

)

B(+

)

A(-

)

B(+

)

A(-

)

TR-N

TR-N

TR-N

TR-N

Com

mon

Com

mon

Com

mon

Com

mon

HF

Shi

eld

HF

Shi

eld

HF

Shi

eld

HF

Shi

eld

Shield at bus master side connected to earth termination

resistors used

Shield at bus device side connected to earth termination

resistors used

Shield at bus master side connected to earth termination

resistors not used

Shield at bus device side connected to earth termination

resistors not used

1 32 4 5 6

TR-P

2.2nF(internal)

1 32 4 5 6

TR-P

2.2nF(internal)

1 32 4 5 6

TR-P

2.2nF(internal)

1 32 4 5 6

TR-P

2.2nF(internal)

B(+)

A(-)

B(+

)

A(-)

B(+

)

A(-)

B(+

)

A(-

)

TR-N

TR-N

TR-N

TR-N

Com

mon

Com

mon

Com

mon

Com

mon

HF

Shi

eld

HF

Shie

ld

HF

Shi

eld

HF

Shi

eld

Page 60: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Slot X104: IRIG-B00X and Supervision Contact

Rear Side of the Device (Slots)

This comprises the IRIG-B00X and the System contact (Supervision Contact).

System Contact and IRIG-B00X

Make sure that the tightening torque is 5-7 In-lb [0.56-0.79 Nm].

Terminals

60 www.eaton.com

X1 X2 X3

X100 X102

X5 X6

X104

X4

X103

Slot3 Slot4 Slot5 Slot6Slot1 Slot2

X101

1X1

04 2 3 4 5SC

IRIG

-B+

IRIG

-B-

Page 61: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Pin Assignment for Device

The Supervision Contact (SC) closes after the boot phase of the device if the protection is working. This Super-vision Contact (SC) will open if an internal device error has occurred (please refer to the Self Supervision sec-tion).

The System-OK contact (SC relay) cannot be configured. The system contact is a Form “C” contact that picks up when the device is free from internal faults. While the device is booting up, the System OK relay (SC) re-mains dropped-off (unenergized). As soon as the system is properly started, the System Contact picks up and the assigned LED is activated accordingly (please refer to the Self Supervision section).

X120 - PC InterfaceThe interface is a 9-pole D-Sub at all device fronts.

Pin Assignment

www.eaton.com 61

0+HTL-uP-6 / 0+HTL-uP-14

X1041 32 4 5

SC N

.C.

SC

N.O

.

SC

CM

N

IRIG

-B+

IRIG

-B-

1 DCD

2 RxD

3 TxD

4 DTR

5 GND

6 DSR

7 RTS

8 CTS

Housing shielded

9 RI

51

6 9

Page 62: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Assignment of the Null Modem Cable

Assignment of the fully wired, null modem cable.

Dsub -9 (Female) Signal Dsub -9 (Female) Signal2 RxD 3 TxD3 TxD 2 RxD4 DTR 6,1 DSR, DCD6,1 DSR, DCD 4 DTR7 RTS 8 CTS8 CTS 7 RTS5 GND (Ground) 5 GND (Ground)9 Ring Signal 9 Ring Signal

The connection cable must be shielded.

Control Wiring Diagram

Below is the recommended control wiring schematic for the EDR-5000.

Wiring Diagrams

Please refer to the file “edr-5000_wiring_diagrams.pdf” on your manual CD.

62 www.eaton.com

Page 63: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Input, Output, and LED SettingsDigital Input Configuration

The State of the Digital Inputs can be checked within menu:

[Operations/Status Display/Name of the assembly group (e.g. DI-8X)]

The Digital Inputs can be configured within menu:

[Device Para/Digital Inputs/Name of the assembly group (e.g. DI-8X)/Group X]

Set the following parameters for each of the digital inputs:

• »Nominal voltage«;

• »Debouncing time«: A state change will only be adopted by the digital input after the debouncing time has expired; and

• »Inverting« (where necessary).

The debouncing time will be started each time the state of the input signal alternates.

In addition to the debouncing time that can be set via software, there is always a hardware debouncing time (approx 12 ms) that cannot be turned of.

www.eaton.com 63

State of the Digital Input.

Inverting

Input Signal

Nom Voltage

DI Slot X.DI x XOR

Debouncing Time

t

0

Page 64: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

DI-8P XName of the Assembly group:DI-8P X1

Device Parameters of the Digital Inputs on DI-8P X

Parameter Description Setting Range Default Menu Path

Nom Voltage Nominal voltage of the digital inputs 24 V dc,

48 V dc,

60 V dc,

110/120 V dc,

230/240 V dc,

110/120 V ac,

230/240 V ac

110/120 V dc [Device Para

/Digital Inputs

/DI-8P X1

/Group 1]

Inverting 1 Inverting the input signals. Inactive,

Active

Inactive [Device Para

/Digital Inputs

/DI-8P X1

/Group 1]Debouncing Time 1

A change of the state of a digital input will only be recognized after the debouncing time has expired (become effective). Thus, transient signals will not be misinterpreted.

No Debouncing Time,

20 ms,

50 ms,

100 ms

20 ms [Device Para

/Digital Inputs

/DI-8P X1

/Group 1]Nom Voltage Nominal voltage of the digital inputs 24 V dc,

48 V dc,

60 V dc,

110/120 V dc,

230/240 V dc,

110/120 V ac,

230/240 V ac

110/120 V dc [Device Para

/Digital Inputs

/DI-8P X1

/Group 2]

Inverting 2 Inverting the input signals. Inactive,

Active

Inactive [Device Para

/Digital Inputs

/DI-8P X1

/Group 2]

64 www.eaton.com

Page 65: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Debouncing Time 2

A change of the state of a digital input will only be recognized after the debouncing time has expired (become effective). Thus, transient signals will not be misinterpreted.

No Debouncing Time,

20 ms,

50 ms,

100 ms

20 ms [Device Para

/Digital Inputs

/DI-8P X1

/Group 2]Nom Voltage Nominal voltage of the digital inputs 24 V dc,

48 V dc,

60 V dc,

110/120 V dc,

230/240 V dc,

110/120 V ac,

230/240 V ac

110/120 V dc [Device Para

/Digital Inputs

/DI-8P X1

/Group 3]

Inverting 3 Inverting the input signals. Inactive,

Active

Inactive [Device Para

/Digital Inputs

/DI-8P X1

/Group 3]Debouncing Time 3

A change of the state of a digital input will only be recognized after the debouncing time has expired (become effective). Thus, transient signals will not be misinterpreted.

No Debouncing Time,

20 ms,

50 ms,

100 ms

20 ms [Device Para

/Digital Inputs

/DI-8P X1

/Group 3]Inverting 4 Inverting the input signals. Inactive,

Active

Inactive [Device Para

/Digital Inputs

/DI-8P X1

/Group 3]Debouncing Time 4

A change of the state of a digital input will only be recognized after the debouncing time has expired (become effective). Thus, transient signals will not be misinterpreted.

No Debouncing Time,

20 ms,

50 ms,

100 ms

20 ms [Device Para

/Digital Inputs

/DI-8P X1

/Group 3]Inverting 5 Inverting the input signals. Inactive,

Active

Inactive [Device Para

/Digital Inputs

/DI-8P X1

/Group 3]

www.eaton.com 65

Page 66: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Debouncing Time 5

A change of the state of a digital input will only be recognized after the debouncing time has expired (become effective). Thus, transient signals will not be misinterpreted.

No Debouncing Time,

20 ms,

50 ms,

100 ms

20 ms [Device Para

/Digital Inputs

/DI-8P X1

/Group 3]Inverting 6 Inverting the input signals. Inactive,

Active

Inactive [Device Para

/Digital Inputs

/DI-8P X1

/Group 3]Debouncing Time 6

A change of the state of a digital input will only be recognized after the debouncing time has expired (become effective). Thus, transient signals will not be misinterpreted.

No Debouncing Time,

20 ms,

50 ms,

100 ms

20 ms [Device Para

/Digital Inputs

/DI-8P X1

/Group 3]Inverting 7 Inverting the input signals. Inactive,

Active

Inactive [Device Para

/Digital Inputs

/DI-8P X1

/Group 3]Debouncing Time 7

A change of the state of a digital input will only be recognized after the debouncing time has expired (become effective). Thus, transient signals will not be misinterpreted.

No Debouncing Time,

20 ms,

50 ms,

100 ms

20 ms [Device Para

/Digital Inputs

/DI-8P X1

/Group 3]Inverting 8 Inverting the input signals. Inactive,

Active

Inactive [Device Para

/Digital Inputs

/DI-8P X1

/Group 3]Debouncing Time 8

A change of the state of a digital input will only be recognized after the debouncing time has expired (become effective). Thus, transient signals will not be misinterpreted.

No Debouncing Time,

20 ms,

50 ms,

100 ms

20 ms [Device Para

/Digital Inputs

/DI-8P X1

/Group 3]

66 www.eaton.com

Page 67: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Digital Inputs Output Signals on DI-8P X

Name Description

DI 1 Signal: Digital InputDI 2 Signal: Digital InputDI 3 Signal: Digital InputDI 4 Signal: Digital InputDI 5 Signal: Digital InputDI 6 Signal: Digital InputDI 7 Signal: Digital InputDI 8 Signal: Digital Input

Wired Inputs (Aliases)Available Elements:WiredInputs

The module WiredInputs allows aliasing Digital Inputs. By means of the menu [Device Para/WiredInputs] the User can assign specific functions on digital inputs.

Alias Example: The 52a contact will be assigned/connected to Digital input1 (DI1). Once the 52a is aliased (linked) on the DI1, the signal »WiredInput.52A« can be used instead of the DI1 signal for further processing within the protective relay. That means, from now on any state changes of the Digital Input1 will we represented by the »WiredInput.52A« signal.

Global Protection Parameter of the Wired Inputs Wired

Parameter Description Setting Range Default Menu Path

52a M1 Main 1 Breaker Closed -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

www.eaton.com 67

Page 68: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

52b M1 Main 1 Breaker Open -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

TOCa M1 Main 1 Breaker Connected -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

43/10 M1 Main 1 Breaker Selected To Trip -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

68 www.eaton.com

Page 69: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

52a M2 Main 2 Breaker Closed -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

52b M2 Main 2 Breaker Open -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

TOCa M2 Main 2 Breaker Connected -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

www.eaton.com 69

Page 70: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

43/10 M2 Main 2 Breaker Selected To Trip -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

52a T Tie Breaker Closed -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

52b T Tie Breaker Open -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

70 www.eaton.com

Page 71: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

TOCa T Tie Breaker Connected -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

43/10 T Tie Breaker Selected To Trip -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

43 M System In Manual -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

www.eaton.com 71

Page 72: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

43 A System in Auto -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

43 P1 Preferred Source 1 -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

43 P2 Preferred Source 2 -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

72 www.eaton.com

Page 73: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Bkr Trouble Breaker Trouble -.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Device Para

/WiredInputs]

States of the Inputs of the Wired Inputs Module

Name Description Assignment Via

52a M1-I State of the module input: Main 1 Breaker Closed

[Device Para

/WiredInputs]52b M1-I State of the module input: Main 1 Breaker

Open[Device Para

/WiredInputs]TOCa M1-I State of the module input: Main 1 Breaker

Connected [Device Para

/WiredInputs]43/10 M1-I State of the module input: Main 1 Breaker

Selected To Trip [Device Para

/WiredInputs]52a M2-I State of the module input: Main 2 Breaker

Closed[Device Para

/WiredInputs]52b M2-I State of the module input: Main 2 Breaker

Open[Device Para

/WiredInputs]TOCa M2-I State of the module input: Main 2 Breaker

Connected [Device Para

/WiredInputs]43/10 M2-I State of the module input: Main 2 Breaker

Selected To Trip[Device Para

/WiredInputs]52a T -I State of the module input: Tie Breaker

Closed[Device Para

/WiredInputs]52b T-I State of the module input: Tie Breaker

Open[Device Para

/WiredInputs]

www.eaton.com 73

Page 74: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

TOCa T-I State of the module input: Tie Breaker Connected

[Device Para

/WiredInputs]43/10 T-I State of the module input: Tie Breaker

Selected To Trip[Device Para

/WiredInputs]43 M-I State of the module input: System In

Manual[Device Para

/WiredInputs]43 A-I State of the module input: System in Auto [Device Para

/WiredInputs]43 P1-I State of the module input: Preferred Source

1[Device Para

/WiredInputs]43 P2-I State of the module input: Preferred Source

2[Device Para

/WiredInputs]Bkr Trouble-I Breaker Trouble [Device Para

/WiredInputs]

Relay Output Configuration

The State of the Relay Outputs can be checked within menu:

[Operations/Status Display/Name of the assembly group (e.g. RO-XX)]

The Relay Outputs can be configured within menu:

[Device Para/Relay Outputs/Name of the assembly group (e.g. RO-XX)]

Set the following parameters for each of the relay output contacts.

• Up to seven (7) signals from the »assignment list« (OR-connected).

The states of the module outputs and the signals (e.g. states of protective functions) can be assigned to the relay output contacts. The relay output contacts are “dry-type“ contacts.

• Each of the assigned signals can be inverted.

• The (collective) state of the relay output contacts can be inverted.

• Each relay output contact can be set as »Latched« (Latched = active or inactive). A latched relay output contact will return to it's latched position after a loss of power to the protective device. A latched relay output contact will keep it´s position as long as it has not been reset and as long as the power supply feeds the protective relay. In the case of a loss of power to the protective device, the relays will return to the latched position once the power is restored to the protective device (latched = relay output contacts have a memory). A latched state of a relay output contact always needs to be reset after a power loss even if the assignments are taken away (if the assignments are reprogrammed).

74 www.eaton.com

Page 75: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

• Latched = inactive«:If the latching function is »inactive«, the relay output and, respectively, the relay output contact will adopt the state of those pickups that were assigned.

• »Latched = active«:If the latching function is »active«, the state of the relay output and, respectively, the relay output contact that was set by the pickups will be stored (they have a memory that needs to be reset).

The relay output contact can only be acknowledged after reset of those signals that hadinitiated the setting of the relay and after expiration of the »t-OFF delay«.

• At signal changes, the minimal latching time (»t-OFF delay«) ensures that the relay will be maintained as picked-up or released for at least this period.

If the relay output contacts are configured as »Latched=active«, they will keep their position even if there is a power outage within the power supply of the protective device.

If the relay output contacts are configured as »Latched=active«, they will also retain their position even if they are reprogrammed in another way. This also applies if the relay output contacts are set to »Latched is set to inactive«. Resetting a relay output contact that has latched a signal will always require an acknowledgement.

The »System OK Relay« (watchdog) cannot be configured.

Acknowledgment Options

Relay output contacts can be acknowledged:

• Via the push-button »C« at the operating panel;

• If »Latched is active«, each relay output contact can be acknowledged by a signal (for example: It could be reset by the state of a digital input);

• Via the module »Ex Acknowledge« where all relay output contacts can be acknowledged at once if the signal for external acknowledgment that was selected from the »Assignment list« becomes true (e.g.: the state of a digital input); and

• Via Communication (Comm), all relay output contacts can be acknowledged at once.

Relay output contacts can be set by force or disarmed (for commisioning support, please refer to the “Service/Disarming the Relay Output Contacts“ and “Service/Forcing the Relay Output Contacts“ sections).

www.eaton.com 75

Page 76: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

76 www.eaton.com

Assi

gnm

ent 1

Inve

rting

1

Assi

gnm

ent 2

Inve

rting

2

Assi

gnm

ent 3

Inve

rting

3

Assi

gnm

ent 4

Inve

rting

4

Assi

gnm

ent 5

Inve

rting

5

OR

Inac

tive

Act

ive

Latc

hedAs

sign

men

t 6

Inve

rting

6

Assi

gnm

ent 7

Inve

rting

7

Inve

rting

OR

OR

AND

Sta

te o

f the

Rel

ay

Out

put

Ack

now

ledg

e -H

MI

Ackn

owle

dge-

1..n

, Ass

ignm

ent L

ist

Ackn

owle

dge-

Com

m

XOR

XOR

XOR

XOR

XOR

XOR

XOR

XOR

OR

Switc

h O

ff D

elay

0

t-Off

Del

ay

S

Q

R1

Q

Page 77: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

RO-4ZI X - Settings

RO-4Z X2

Direct Commands of RO-4ZI X

Parameter Description Setting Range Default Menu Path

DISARMED This is the second step, after the "DISARMED Ctrl" has been activated, that is required to DISARM the relay output contacts. This will DISARM those relay output contacts that are currently not latched and that are not timing out. CAUTION! RELAYS DISARMED in order to safely perform maintenance while eliminating the risk of taking an entire process off-line. (Note: Zone Interlocking and Supervision Contact cannot be disarmed). The User MUST ENSURE that the relays are ARMED AGAIN after maintenance.

Only available if: DISARMED Ctrl = Active

Inactive,

Active

Inactive [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/DISARMED

/RO-4Z X2]

Force all Outs By means of this function the normal Relay Output State can be overwritten (forced). The relay can be set from normal operation (relay works according to the assigned signals) to "force energized" or "force de-energized" state. Forcing all relay output contacts of an entire assembly group has precedence to forcing a single relay output.

Normal,

De-Energized,

Energized

Normal [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-4Z X2]Force ZI RO Signal: Forced Zone Interlocking OUT Normal,

De-Energized,

Energized

Normal [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-4Z X2]Force RO1 By means of this function the normal Relay

Output State can be overwritten (forced). The relay can be set from normal operation (relay works according to the assigned signals) to "force energized" or "force de-energized" state.

Normal,

De-Energized,

Energized

Normal [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-4Z X2]

www.eaton.com 77

Page 78: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Force RO2 By means of this function the normal Relay Output State can be overwritten (forced). The relay can be set from normal operation (relay works according to the assigned signals) to "force energized" or "force de-energized" state.

Normal,

De-Energized,

Energized

Normal [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-4Z X2]Force RO3 By means of this function the normal Relay

Output State can be overwritten (forced). The relay can be set from normal operation (relay works according to the assigned signals) to "force energized" or "force de-energized" state.

Normal,

De-Energized,

Energized

Normal [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-4Z X2]Force RO4 By means of this function the normal Relay

Output State can be overwritten (forced). The relay can be set from normal operation (relay works according to the assigned signals) to "force energized" or "force de-energized" state.

Normal,

De-Energized,

Energized

Normal [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-4Z X2]

Global Protection Parameters of RO-4ZI X

Parameter Description Setting Range Default Menu Path

t-Off Delay Switch Off Delay 0.00 – 300.00 s 0.1 s [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]Latched Defines whether the Relay Output will be

latched when it picks up.Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]

78 www.eaton.com

Page 79: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Acknowledgment

Acknowledgment Signal - An acknowledgment signal (that acknowledges the corresponding Relay Output) can be assigned to each Relay Output. The acknowledgment-signal is only effective if the parameter "Latched" is set to active.

Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]

Inverting Inverting of the Relay Output. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]Assignment 1 Assignment 1..n, Assignment List Breaker

TripCmd[Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]Assignment 2 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]Assignment 3 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]

www.eaton.com 79

Page 80: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]Assignment 6 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]Inverting 6 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]

80 www.eaton.com

Page 81: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Assignment 7 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]Inverting 7 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]t-Off Delay Switch Off Delay 0.00 – 300.00 s 0.00 s [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]Latched Defines whether the Relay Output will be

latched when it picks up.Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]Acknowledgment

Acknowledgment Signal - An acknowledgment signal (that acknowledges the corresponding Relay Output) can be assigned to each Relay Output. The acknowledgment-signal is only effective if the parameter "Latched" is set to active.

Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]

Inverting Inverting of the Relay Output. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]Assignment 1 Assignment 1..n, Assignment List Prot.Pickup [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]

www.eaton.com 81

Page 82: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]Assignment 2 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]Assignment 3 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]

82 www.eaton.com

Page 83: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]Assignment 6 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]Inverting 6 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]Assignment 7 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]Inverting 7 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]t-Off Delay Switch Off Delay 0.00 – 300.00 s 0.00 s [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]

www.eaton.com 83

Page 84: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Latched Defines whether the Relay Output will be latched when it picks up.

Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]Acknowledgment

Acknowledgment Signal - An acknowledgment signal (that acknowledges the corresponding Relay Output) can be assigned to each Relay Output. The acknowledgment-signal is only effective if the parameter "Latched" is set to active.

Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]

Inverting Inverting of the Relay Output. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]Assignment 1 Assignment 1..n, Assignment List BF.Trip [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]Assignment 2 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]

84 www.eaton.com

Page 85: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Assignment 3 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]Assignment 6 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]

www.eaton.com 85

Page 86: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Inverting 6 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]Assignment 7 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]Inverting 7 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]t-Off Delay Switch Off Delay 0.00 – 300.00 s 0.00 s [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]Latched Defines whether the Relay Output will be

latched when it picks up.Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]Acknowledgment

Acknowledgment Signal - An acknowledgment signal (that acknowledges the corresponding Relay Output) can be assigned to each Relay Output. The acknowledgment-signal is only effective if the parameter "Latched" is set to active.

Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]

Inverting Inverting of the Relay Output. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]

86 www.eaton.com

Page 87: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Assignment 1 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]Assignment 2 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]Assignment 3 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]

www.eaton.com 87

Page 88: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]Assignment 6 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]Inverting 6 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]Assignment 7 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]Inverting 7 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]

88 www.eaton.com

Page 89: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

DISARMED Ctrl

Enables and disables the disarming of the relay output contacts. This is the first step of a two step process, to inhibit the operation or the relay output contacts. Please refer to "DISARMED" for the second step.

Inactive,

Active

Inactive [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/DISARMED

/RO-4Z X2]Disarm Mode CAUTION! RELAYS DISARMED in order to

safely perform maintenance while eliminating the risk of taking an entire process off-line. (Note: Zone Interlocking and Supervision Contact cannot be disarmed). The User MUST ENSURE that the relays are ARMED AGAIN after maintenance.

Permanent,

Timeout

Permanent [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/DISARMED

/RO-4Z X2]t-Timeout DISARM

The relays will be armed again after expiring of this time.

Only available if: Mode = Timeout DISARM

0.00 – 300.00 s 0.03 s [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/DISARMED

/RO-4Z X2]Force Mode By means of this function the normal Relay

Output States can be overwritten (forced) in case that the Relay Output is not in a disarmed state. The relays can be set from normal operation (relay works according to the assigned signals) to "force energized" or "force de-energized" state.

Permanent,

Timeout

Permanent [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-4Z X2]t-Timeout Force

The Output State will be set by force for the duration of this time. That means, for the duration of this time, the Relay Output does not show the state of the signals that are assigned on it.

Only available if: Mode = Timeout DISARM

0.00 – 300.00 s 0.03 s [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-4Z X2]

www.eaton.com 89

Page 90: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Input States of RO-4ZI X

Name Description Assignment Via

RO1.1 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]RO1.2 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]RO1.3 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]RO1.4 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]RO1.5 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]RO1.6 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]RO1.7 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]

90 www.eaton.com

Page 91: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

Ack signal RO 1 Module Input State: Acknowledgment signal for the Relay Output. If latching is set to active, the Relay Output can only be acknowledged if those signals that initiated the setting are fallen back and the hold time is expired.

[Device Para

/Relay Outputs

/RO-4Z X2

/RO 1]RO2.1 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]RO2.2 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]RO2.3 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]RO2.4 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]RO2.5 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]RO2.6 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]

www.eaton.com 91

Page 92: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

RO2.7 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]Ack signal RO 2 Module Input State: Acknowledgment signal

for the Relay Output. If latching is set to active, the Relay Output can only be acknowledged if those signals that initiated the setting are fallen back and the hold time is expired.

[Device Para

/Relay Outputs

/RO-4Z X2

/RO 2]RO3.1 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]RO3.2 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]RO3.3 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]RO3.4 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]RO3.5 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]

92 www.eaton.com

Page 93: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

RO3.6 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]RO3.7 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]Ack signal RO 3 Module Input State: Acknowledgment signal

for the Relay Output. If latching is set to active, the Relay Output can only be acknowledged if those signals that initiated the setting are fallen back and the hold time is expired.

[Device Para

/Relay Outputs

/RO-4Z X2

/RO 3]RO4.1 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]RO4.2 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]RO4.3 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]RO4.4 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]

www.eaton.com 93

Page 94: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

RO4.5 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]RO4.6 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]RO4.7 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]Ack signal RO 4 Module Input State: Acknowledgment signal

for the Relay Output. If latching is set to active, the Relay Output can only be acknowledged if those signals that initiated the setting are fallen back and the hold time is expired.

[Device Para

/Relay Outputs

/RO-4Z X2

/RO 4]

Signals of RO-4ZI X

Name Description

ZI OUT Signal: Zone Interlocking OUTRO 1 Signal: Relay OutputRO 2 Signal: Relay OutputRO 3 Signal: Relay OutputRO 4 Signal: Relay OutputDISARMED! Signal: CAUTION! RELAYS DISARMED in order to safely perform

maintenance while eliminating the risk of taking an entire process off-line. (Note: Zone Interlocking and Supervision Contact cannot be disarmed). The User MUST ENSURE that the relays are ARMED AGAIN after maintenance

Outs forced Signal: The State of at least one Relay Output has been set by force. That means that the state of at least one Relay is forced and hence does not show the state of the assigned signals.

94 www.eaton.com

Page 95: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

RO-6 X Settings

RO-6 X5

Direct Commands of RO-6 X

Parameter Description Setting Range Default Menu Path

DISARMED This is the second step, after the "DISARMED Ctrl" has been activated, that is required to DISARM the relay output contacts. This will DISARM those relay output contacts that are currently not latched and that are not timing out. CAUTION! RELAYS DISARMED in order to safely perform maintenance while eliminating the risk of taking an entire process off-line. (Note: Zone Interlocking and Supervision Contact cannot be disarmed). The User MUST ENSURE that the relays are ARMED AGAIN after maintenance.

Only available if: DISARMED Ctrl = Active

Inactive,

Active

Inactive [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/DISARMED

/RO-6 X5]

Force all Outs By means of this function the normal Relay Output State can be overwritten (forced). The relay can be set from normal operation (relay works according to the assigned signals) to "force energized" or "force de-energized" state. Forcing all relay output contacts of an entire assembly group has precedence to forcing a single relay output.

Normal,

De-Energized,

Energized

Normal [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-6 X5]Force RO1 By means of this function the normal Relay

Output State can be overwritten (forced). The relay can be set from normal operation (relay works according to the assigned signals) to "force energized" or "force de-energized" state.

Normal,

De-Energized,

Energized

Normal [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-6 X5]Force RO2 By means of this function the normal Relay

Output State can be overwritten (forced). The relay can be set from normal operation (relay works according to the assigned signals) to "force energized" or "force de-energized" state.

Normal,

De-Energized,

Energized

Normal [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-6 X5]

www.eaton.com 95

Page 96: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Force RO3 By means of this function the normal Relay Output State can be overwritten (forced). The relay can be set from normal operation (relay works according to the assigned signals) to "force energized" or "force de-energized" state.

Normal,

De-Energized,

Energized

Normal [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-6 X5]Force RO4 By means of this function the normal Relay

Output State can be overwritten (forced). The relay can be set from normal operation (relay works according to the assigned signals) to "force energized" or "force de-energized" state.

Normal,

De-Energized,

Energized

Normal [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-6 X5]Force RO5 By means of this function the normal Relay

Output State can be overwritten (forced). The relay can be set from normal operation (relay works according to the assigned signals) to "force energized" or "force de-energized" state.

Normal,

De-Energized,

Energized

Normal [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-6 X5]Force RO6 By means of this function the normal Relay

Output State can be overwritten (forced). The relay can be set from normal operation (relay works according to the assigned signals) to "force energized" or "force de-energized" state.

Normal,

De-Energized,

Energized

Normal [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-6 X5]

96 www.eaton.com

Page 97: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Device Parameters of RO-6 X

Parameter Description Setting Range Default Menu Path

t-Off Delay Switch Off Delay 0.00 – 300.00 s 0.00 s [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]Latched Defines whether the Relay Output will be

latched when it picks up.Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]Acknowledgment

Acknowledgment Signal - An acknowledgment signal (that acknowledges the corresponding Relay Output) can be assigned to each Relay Output. The acknowledgment-signal is only effective if the parameter "Latched" is set to active.

Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]

Inverting Inverting of the Relay Output. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]Assignment 1 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]Assignment 2 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]

www.eaton.com 97

Page 98: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]Assignment 3 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]

98 www.eaton.com

Page 99: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Assignment 6 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]Inverting 6 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]Assignment 7 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]Inverting 7 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]t-Off Delay Switch Off Delay 0.00 – 300.00 s 0.00 s [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]Latched Defines whether the Relay Output will be

latched when it picks up.Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]Acknowledgment

Acknowledgment Signal - An acknowledgment signal (that acknowledges the corresponding Relay Output) can be assigned to each Relay Output. The acknowledgment-signal is only effective if the parameter "Latched" is set to active.

Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]

www.eaton.com 99

Page 100: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Inverting Inverting of the Relay Output. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]Assignment 1 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]Assignment 2 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]Assignment 3 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]

100 www.eaton.com

Page 101: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]Assignment 6 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]Inverting 6 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]Assignment 7 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]

www.eaton.com 101

Page 102: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Inverting 7 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]t-Off Delay Switch Off Delay 0.00 – 300.00 s 0.00 s [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]Latched Defines whether the Relay Output will be

latched when it picks up.Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]Acknowledgment

Acknowledgment Signal - An acknowledgment signal (that acknowledges the corresponding Relay Output) can be assigned to each Relay Output. The acknowledgment-signal is only effective if the parameter "Latched" is set to active.

Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]

Inverting Inverting of the Relay Output. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]Assignment 1 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]

102 www.eaton.com

Page 103: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Assignment 2 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]Assignment 3 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]

www.eaton.com 103

Page 104: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]Assignment 6 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]Inverting 6 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]Assignment 7 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]Inverting 7 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]t-Off Delay Switch Off Delay 0.00 – 300.00 s 0.00 s [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]Latched Defines whether the Relay Output will be

latched when it picks up.Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]

104 www.eaton.com

Page 105: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Acknowledgment

Acknowledgment Signal - An acknowledgment signal (that acknowledges the corresponding Relay Output) can be assigned to each Relay Output. The acknowledgment-signal is only effective if the parameter "Latched" is set to active.

Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]

Inverting Inverting of the Relay Output. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]Assignment 1 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]Assignment 2 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]Assignment 3 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]

www.eaton.com 105

Page 106: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]Assignment 6 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]Inverting 6 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]

106 www.eaton.com

Page 107: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Assignment 7 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]Inverting 7 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]t-Off Delay Switch Off Delay 0.00 – 300.00 s 0.00 s [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]Latched Defines whether the Relay Output will be

latched when it picks up.Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]Acknowledgment

Acknowledgment Signal - An acknowledgment signal (that acknowledges the corresponding Relay Output) can be assigned to each Relay Output. The acknowledgment-signal is only effective if the parameter "Latched" is set to active.

Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]

Inverting Inverting of the Relay Output. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]Assignment 1 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]

www.eaton.com 107

Page 108: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]Assignment 2 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]Assignment 3 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]

108 www.eaton.com

Page 109: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]Assignment 6 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]Inverting 6 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]Assignment 7 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]Inverting 7 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]t-Off Delay Switch Off Delay 0.00 – 300.00 s 0.00 s [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]

www.eaton.com 109

Page 110: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Latched Defines whether the Relay Output will be latched when it picks up.

Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]Acknowledgment

Acknowledgment Signal - An acknowledgment signal (that acknowledges the corresponding Relay Output) can be assigned to each Relay Output. The acknowledgment-signal is only effective if the parameter "Latched" is set to active.

Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]

Inverting Inverting of the Relay Output. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]Assignment 1 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]Assignment 2 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]

110 www.eaton.com

Page 111: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Assignment 3 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]Assignment 6 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]

www.eaton.com 111

Page 112: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Inverting 6 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]Assignment 7 Assignment 1..n, Assignment List -.- [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]Inverting 7 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]DISARMED Ctrl

Enables and disables the disarming of the relay output contacts. This is the first step of a two step process, to inhibit the operation or the relay output contacts. Please refer to "DISARMED" for the second step.

Inactive,

Active

Inactive [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/DISARMED

/RO-6 X5]Disarm Mode CAUTION! RELAYS DISARMED in order to

safely perform maintenance while eliminating the risk of taking an entire process off-line. (Note: Zone Interlocking and Supervision Contact cannot be disarmed). The User MUST ENSURE that the relays are ARMED AGAIN after maintenance.

Permanent,

Timeout

Permanent [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/DISARMED

/RO-6 X5]t-Timeout DISARM

The relays will be armed again after expiring of this time.

Only available if: Mode = Timeout DISARM

0.00 – 300.00 s 0.03 s [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/DISARMED

/RO-6 X5]

112 www.eaton.com

Page 113: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Force Mode By means of this function the normal Relay Output States can be overwritten (forced) in case that the Relay Output is not in a disarmed state. The relays can be set from normal operation (relay works according to the assigned signals) to "force energized" or "force de-energized" state.

Permanent,

Timeout

Permanent [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-6 X5]t-Timeout Force

The Output State will be set by force for the duration of this time. That means, for the duration of this time, the Relay Output does not show the state of the signals that are assigned on it.

Only available if: Mode = Timeout DISARM

0.00 – 300.00 s 0.03 s [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Force RO

/RO-6 X5]

Input States of RO-6 X

Name Description Assignment Via

RO1.1 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]RO1.2 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]RO1.3 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]RO1.4 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]

www.eaton.com 113

Page 114: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

RO1.5 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]RO1.6 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]RO1.7 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 1]Ack signal RO 1 Module Input State: Acknowledgment signal

for the Relay Output. If latching is set to active, the Relay Output can only be acknowledged if those signals that initiated the setting are fallen back and the hold time is expired.

[Device Para

/Relay Outputs

/RO-6 X5

/RO 1]RO2.1 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]RO2.2 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]RO2.3 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]

114 www.eaton.com

Page 115: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

RO2.4 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]RO2.5 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]RO2.6 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]RO2.7 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 2]Ack signal RO 2 Module Input State: Acknowledgment signal

for the Relay Output. If latching is set to active, the Relay Output can only be acknowledged if those signals that initiated the setting are fallen back and the hold time is expired.

[Device Para

/Relay Outputs

/RO-6 X5

/RO 2]RO3.1 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]RO3.2 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]

www.eaton.com 115

Page 116: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

RO3.3 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]RO3.4 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]RO3.5 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]RO3.6 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]RO3.7 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 3]Ack signal RO 3 Module Input State: Acknowledgment signal

for the Relay Output. If latching is set to active, the Relay Output can only be acknowledged if those signals that initiated the setting are fallen back and the hold time is expired.

[Device Para

/Relay Outputs

/RO-6 X5

/RO 3]RO4.1 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]

116 www.eaton.com

Page 117: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

RO4.2 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]RO4.3 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]RO4.4 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]RO4.5 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]RO4.6 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]RO4.7 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 4]Ack signal RO 4 Module Input State: Acknowledgment signal

for the Relay Output. If latching is set to active, the Relay Output can only be acknowledged if those signals that initiated the setting are fallen back and the hold time is expired.

[Device Para

/Relay Outputs

/RO-6 X5

/RO 4]

www.eaton.com 117

Page 118: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

RO5.1 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]RO5.2 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]RO5.3 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]RO5.4 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]RO5.5 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]RO5.6 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]RO5.7 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 5]

118 www.eaton.com

Page 119: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

Ack signal RO 5 Module Input State: Acknowledgment signal for the Relay Output. If latching is set to active, the Relay Output can only be acknowledged if those signals that initiated the setting are fallen back and the hold time is expired.

[Device Para

/Relay Outputs

/RO-6 X5

/RO 5]RO6.1 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]RO6.2 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]RO6.3 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]RO6.4 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]RO6.5 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]RO6.6 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]

www.eaton.com 119

Page 120: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

RO6.7 Module Input State: Assignment [Device Para

/Relay Outputs

/RO-6 X5

/RO 6]Ack signal RO 6 Module Input State: Acknowledgment signal

for the Relay Output. If latching is set to active, the Relay Output can only be acknowledged if those signals that initiated the setting are fallen back and the hold time is expired.

[Device Para

/Relay Outputs

/RO-6 X5

/RO 6]

Signals of RO-6 X

Name Description

RO 1 Signal: Relay OutputRO 2 Signal: Relay OutputRO 3 Signal: Relay OutputRO 4 Signal: Relay OutputRO 5 Signal: Relay OutputRO 6 Signal: Relay OutputDISARMED! Signal: CAUTION! RELAYS DISARMED in order to safely perform

maintenance while eliminating the risk of taking an entire process off-line. (Note: Zone Interlocking and Supervision Contact cannot be disarmed). The User MUST ENSURE that the relays are ARMED AGAIN after maintenance

Outs forced Signal: The State of at least one Relay Output has been set by force. That means that the state of at least one Relay is forced and hence does not show the state of the assigned signals.

LED ConfigurationThe LEDs can be configured within menu:

[Device Para/LEDs/Group X]

Attention must be paid to insure that there are no overlapping functions due to double or multiple LED assignment of colors and flashing codes.

If LEDs are configured as »Latched=active«, they will keep (return to) their blink code and color even if there is a power outage within the power supply of the protective device.

If the LEDs are configured as »Latched=active«, they will also retain their blink code and color even if the LEDs are reprogrammed in another way. This also applies if the LEDs are set to »Latched = inactive«. Resetting a LED that has latched a signal will always require an acknowledgement.

120 www.eaton.com

Page 121: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

This chapter contains information on the LEDs that are placed on the left hand side of the display (Group A).

If your device is also equipped with LEDs on the right hand side of the display (Group B), the analog information in this chapter is valid. The only difference between “Group A” and “Group B” is within the menu paths.

Via the »INFO« push-button, it is always possible to display the current pickups and alarm texts that are assigned to an LED. Please refer to the Navigation section for a description of the »INFO« push-button functionality.

Set the following parameters for each LED.

• »Latching (self holding function)«: If »Latching« is set to »Active«, the state that is set by the pickups will be stored until it is reset. If »Latching« is set to »Inactive«, the LED always adopts the state of those pickups that were assigned.

• »Acknowledgement«: Signal that will reset the LED.

• »LED active color«: LED lights up in this color when at least one of the allocated functions is valid (red, red-flashing, green, green flashing, off).

• »LED inactive color«: LED lights up in this color when none of the allocated functions is valid (red, red-flashing, green, green flashing, off).

• »Assignment 1...n« Apart from the LED for System OK, each LED can be assigned up to five functions (e.g. pickups) out of the »Assignment list«.

• »Inverting an Assignment 1...n«: This will invert the input signal.

Acknowledgment Options

LEDs can be acknowledged by:

• The push-button »C« at the operating panel;

• A signal from the »LED Reset list« (e.g. digital inputs or communication signals) (If »Latched = active«);

• The »Ex Acknowledge« module - all LEDs can be acknowledged at once, if the signal for external acknowledgment becomes true (e.g.: the state of a digital input); and

• Communication (Comm) - all LEDs can be acknowledged at once.

www.eaton.com 121

Page 122: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

122 www.eaton.com

Inac

tive

Act

ive

Latc

hed

Assi

gnm

ent 1

Inve

rting

1

Assi

gnm

ent 2

Inve

rting

2

Assi

gnm

ent 3

Inve

rting

3

Assi

gnm

ent 4

Inve

rting

4

Assi

gnm

ent 5

Inve

rting

5

LED

Act

ive

Col

or

LED

Inac

tive

Col

or

OR

OR

AND

Ackn

owle

dge

-HM

IAc

know

ledg

e-1.

.n, A

ssig

nmen

t Lis

tAc

know

ledg

e-C

omm

XO

R

XOR

XOR

XOR

XOR

OR

S

Q

R1

Q

Page 123: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

The »System OK« LED This LED flashes green while the device is booting. After booting is complete, the LED for System OK lights up in green signaling that the protection (function) is »activated«. If, however, in spite of successful booting, or after the third unsuccessful reboot caused by the self supervision module, the System OK – LED flashes in red or is solidly illuminated in red, please contact your Eaton Corporation Customer Service Representative (also see the Self Supervision section).

The System OK LED cannot be configured.

LED SettingsLEDs group A ,LEDs group B

Device Parameters of the LEDs

Parameter Description Setting Range Default Menu Path

Latched Defines whether the LED will be latched when it picks up.

Inactive,

Active

LEDs group A: Active

LEDs group B: Inactive

[Device Para

/LEDs

/LEDs group A

/LED 1]Ack signal Acknowledgment signal for the LED. If

latching is set to active the LED can only be acknowledged if all signals that initiated the setting of the LED are no longer present.

Dependency Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 1]LED Active Color

The LED lights up in this color if the state of the OR-assignment of the signals is true.

Green,

Red,

Red flash,

Green flash,

-

LEDs group A: Red

LEDs group B: Green

[Device Para

/LEDs

/LEDs group A

/LED 1]

LED Inactive Color

The LED lights up in this color if the state of the OR-assignment of the signals is false.

Green,

Red,

Red flash,

Green flash,

-

- [Device Para

/LEDs

/LEDs group A

/LED 1]

www.eaton.com 123

Page 124: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Assignment 1 Assignment 1..n, Assignment List LEDs group A: 51P[1].TripCmd

LEDs group B: Breaker.Pos OPEN

[Device Para

/LEDs

/LEDs group A

/LED 1]Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 1]Assignment 2 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 1]Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 1]Assignment 3 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 1]Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 1]Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 1]

124 www.eaton.com

Page 125: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 1]Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 1]Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 1]Latched Defines whether the LED will be latched

when it picks up.Inactive,

Active

LEDs group A: Active

LEDs group B: Inactive

[Device Para

/LEDs

/LEDs group A

/LED 2]Ack signal Acknowledgment signal for the LED. If

latching is set to active the LED can only be acknowledged if all signals that initiated the setting of the LED are no longer present.

Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 2]LED Active Color

The LED lights up in this color if the state of the OR-assignment of the signals is true.

Green,

Red,

Red flash,

Green flash,

-

Red [Device Para

/LEDs

/LEDs group A

/LED 2]

LED Inactive Color

The LED lights up in this color if the state of the OR-assignment of the signals is false.

Green,

Red,

Red flash,

Green flash,

-

- [Device Para

/LEDs

/LEDs group A

/LED 2]

www.eaton.com 125

Page 126: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Assignment 1 Assignment 1..n, Assignment List LEDs group A: 51X[1].TripCmd

LEDs group B: Breaker.Pos CLOSE

[Device Para

/LEDs

/LEDs group A

/LED 2]Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 2]Assignment 2 Assignment 1..n, Assignment List LEDs group A:

51R[1].TripCmd

LEDs group B: -.-

[Device Para

/LEDs

/LEDs group A

/LED 2]Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 2]Assignment 3 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 2]Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 2]Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 2]

126 www.eaton.com

Page 127: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 2]Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 2]Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 2]Latched Defines whether the LED will be latched

when it picks up.Inactive,

Active

Active [Device Para

/LEDs

/LEDs group A

/LED 3]Ack signal Acknowledgment signal for the LED. If

latching is set to active the LED can only be acknowledged if all signals that initiated the setting of the LED are no longer present.

Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 3]LED Active Color

The LED lights up in this color if the state of the OR-assignment of the signals is true.

Green,

Red,

Red flash,

Green flash,

-

Red [Device Para

/LEDs

/LEDs group A

/LED 3]

LED Inactive Color

The LED lights up in this color if the state of the OR-assignment of the signals is false.

Green,

Red,

Red flash,

Green flash,

-

- [Device Para

/LEDs

/LEDs group A

/LED 3]

www.eaton.com 127

Page 128: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Assignment 1 Assignment 1..n, Assignment List LEDs group A: 50P[1].TripCmd

LEDs group B: 27M[1].TripCmd

[Device Para

/LEDs

/LEDs group A

/LED 3]Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 3]Assignment 2 Assignment 1..n, Assignment List LEDs group A:

-.-

LEDs group B: 59M[1].TripCmd

[Device Para

/LEDs

/LEDs group A

/LED 3]Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 3]Assignment 3 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 3]Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 3]Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 3]

128 www.eaton.com

Page 129: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 3]Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 3]Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 3]Latched Defines whether the LED will be latched

when it picks up.Inactive,

Active

Active [Device Para

/LEDs

/LEDs group A

/LED 4]Ack signal Acknowledgment signal for the LED. If

latching is set to active the LED can only be acknowledged if all signals that initiated the setting of the LED are no longer present.

Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 4]LED Active Color

The LED lights up in this color if the state of the OR-assignment of the signals is true.

Green,

Red,

Red flash,

Green flash,

-

Red [Device Para

/LEDs

/LEDs group A

/LED 4]

LED Inactive Color

The LED lights up in this color if the state of the OR-assignment of the signals is false.

Green,

Red,

Red flash,

Green flash,

-

- [Device Para

/LEDs

/LEDs group A

/LED 4]

www.eaton.com 129

Page 130: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Assignment 1 Assignment 1..n, Assignment List LEDs group A: 50X[1].TripCmd

LEDs group B: 81[1].TripCmd

[Device Para

/LEDs

/LEDs group A

/LED 4]Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 4]Assignment 2 Assignment 1..n, Assignment List LEDs group A:

50R[1].TripCmd

LEDs group B: 81[3].TripCmd

[Device Para

/LEDs

/LEDs group A

/LED 4]Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 4]Assignment 3 Assignment 1..n, Assignment List LEDs group A:

-.-

LEDs group B: 81[5].TripCmd

[Device Para

/LEDs

/LEDs group A

/LED 4]Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 4]Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 4]

130 www.eaton.com

Page 131: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 4]Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 4]Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 4]Latched Defines whether the LED will be latched

when it picks up.Inactive,

Active

LEDs group A: Inactive

LEDs group B: Active

[Device Para

/LEDs

/LEDs group A

/LED 5]Ack signal Acknowledgment signal for the LED. If

latching is set to active the LED can only be acknowledged if all signals that initiated the setting of the LED are no longer present.

Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 5]LED Active Color

The LED lights up in this color if the state of the OR-assignment of the signals is true.

Green,

Red,

Red flash,

Green flash,

-

LEDs group A: Red flash

LEDs group B: Red

[Device Para

/LEDs

/LEDs group A

/LED 5]

LED Inactive Color

The LED lights up in this color if the state of the OR-assignment of the signals is false.

Green,

Red,

Red flash,

Green flash,

-

- [Device Para

/LEDs

/LEDs group A

/LED 5]

www.eaton.com 131

Page 132: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Assignment 1 Assignment 1..n, Assignment List LEDs group A: Prot.Pickup

LEDs group B: ZI.TripCmd

[Device Para

/LEDs

/LEDs group A

/LED 5]Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 5]Assignment 2 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 5]Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 5]Assignment 3 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 5]Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 5]Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 5]

132 www.eaton.com

Page 133: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 5]Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 5]Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 5]Latched Defines whether the LED will be latched

when it picks up.Inactive,

Active

Active [Device Para

/LEDs

/LEDs group A

/LED 6]Ack signal Acknowledgment signal for the LED. If

latching is set to active the LED can only be acknowledged if all signals that initiated the setting of the LED are no longer present.

Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 6]LED Active Color

The LED lights up in this color if the state of the OR-assignment of the signals is true.

Green,

Red,

Red flash,

Green flash,

-

Red [Device Para

/LEDs

/LEDs group A

/LED 6]

LED Inactive Color

The LED lights up in this color if the state of the OR-assignment of the signals is false.

Green,

Red,

Red flash,

Green flash,

-

- [Device Para

/LEDs

/LEDs group A

/LED 6]

www.eaton.com 133

Page 134: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Assignment 1 Assignment 1..n, Assignment List LEDs group A: BF.Trip

LEDs group B: LOP.LOP Blo

[Device Para

/LEDs

/LEDs group A

/LED 6]Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 6]Assignment 2 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 6]Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 6]Assignment 3 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 6]Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 6]Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 6]

134 www.eaton.com

Page 135: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 6]Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 6]Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 6]Latched Defines whether the LED will be latched

when it picks up.Inactive,

Active

LEDs group A: Inactive

LEDs group B: Active

[Device Para

/LEDs

/LEDs group A

/LED 7]Ack signal Acknowledgment signal for the LED. If

latching is set to active the LED can only be acknowledged if all signals that initiated the setting of the LED are no longer present.

Only available if: Latched = Active

1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 7]LED Active Color

The LED lights up in this color if the state of the OR-assignment of the signals is true.

Green,

Red,

Red flash,

Green flash,

-

LEDs group A: Green flash

LEDs group B: Red

[Device Para

/LEDs

/LEDs group A

/LED 7]

LED Inactive Color

The LED lights up in this color if the state of the OR-assignment of the signals is false.

Green,

Red,

Red flash,

Green flash,

-

- [Device Para

/LEDs

/LEDs group A

/LED 7]

www.eaton.com 135

Page 136: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Assignment 1 Assignment 1..n, Assignment List LEDs group A: Sys.Maint Mode Active

LEDs group B: Prot.Trip

[Device Para

/LEDs

/LEDs group A

/LED 7]Inverting 1 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 7]Assignment 2 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 7]Inverting 2 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 7]Assignment 3 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 7]Inverting 3 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 7]Assignment 4 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 7]

136 www.eaton.com

Page 137: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Inverting 4 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 7]Assignment 5 Assignment 1..n, Assignment List -.- [Device Para

/LEDs

/LEDs group A

/LED 7]Inverting 5 Inverting of the state of the assigned signal. Inactive,

Active

Inactive [Device Para

/LEDs

/LEDs group A

/LED 7]

LED Input States

Name Description Assignment Via

LED1.1 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 1]LED1.2 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 1]LED1.3 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 1]LED1.4 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 1]

www.eaton.com 137

Page 138: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

LED1.5 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 1]Acknow Sig 1 Module Input State: Acknowledgment

Signal (only for automatic acknowledgment).

[Device Para

/LEDs

/LEDs group A

/LED 1]LED2.1 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 2]LED2.2 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 2]LED2.3 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 2]LED2.4 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 2]LED2.5 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 2]

138 www.eaton.com

Page 139: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

Acknow Sig 2 Module Input State: Acknowledgment Signal (only for automatic acknowledgment).

[Device Para

/LEDs

/LEDs group A

/LED 2]LED3.1 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 3]LED3.2 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 3]LED3.3 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 3]LED3.4 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 3]LED3.5 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 3]Acknow Sig 3 Module Input State: Acknowledgment

Signal (only for automatic acknowledgment).

[Device Para

/LEDs

/LEDs group A

/LED 3]

www.eaton.com 139

Page 140: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

LED4.1 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 4]LED4.2 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 4]LED4.3 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 4]LED4.4 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 4]LED4.5 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 4]Acknow Sig 4 Module Input State: Acknowledgment

Signal (only for automatic acknowledgment).

[Device Para

/LEDs

/LEDs group A

/LED 4]LED5.1 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 5]

140 www.eaton.com

Page 141: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

LED5.2 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 5]LED5.3 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 5]LED5.4 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 5]LED5.5 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 5]Acknow Sig 5 Module Input State: Acknowledgment

Signal (only for automatic acknowledgment).

[Device Para

/LEDs

/LEDs group A

/LED 5]LED6.1 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 6]LED6.2 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 6]

www.eaton.com 141

Page 142: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

LED6.3 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 6]LED6.4 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 6]LED6.5 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 6]Acknow Sig 6 Module Input State: Acknowledgment

Signal (only for automatic acknowledgment).

[Device Para

/LEDs

/LEDs group A

/LED 6]LED7.1 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 7]LED7.2 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 7]LED7.3 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 7]

142 www.eaton.com

Page 143: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

LED7.4 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 7]LED7.5 Module Input State: LED [Device Para

/LEDs

/LEDs group A

/LED 7]Acknow Sig 7 Module Input State: Acknowledgment

Signal (only for automatic acknowledgment).

[Device Para

/LEDs

/LEDs group A

/LED 7]

www.eaton.com 143

Page 144: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Front Panel

144 www.eaton.com

1 2 3

5

76 8 10

RS232 Interface (PowerPort-E Connection)

ACK/RST-keyINFO Key (Signals/Messages)

Control

Softkeys

DisplayLED »System OK« Programmable LEDs

9

OK-key

4

Programmable LEDs

ProtectiveDevice

Page 145: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Item Graphic Name Description

1

(Example for an insert)

Group A: Programmable LEDs

Basically, there are 14 programmable LEDs (7 on the left, 7 on the right side) provided for User to configure. The choice for each programmable LED can be any signal from the global assignment list, which includes all internal operation states of each function activated. Based on the application need, up to 14 (but not necessarily all) programmable LEDs can be activated. By properly configuring some or all 14 LEDs, the User will be able to view the relay's overall operation and some critical information immediately and intuitively without having to access any menu.

2 LED »System OK«

Should the LED »System OK« flash red during operation, contact Customer Support immediately.

3 Display Via the display, the User can view operational data and edit the parameters.

www.eaton.com 145

Page 146: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Item Graphic Name Description

4

(Example for an insert)

Group B: Programmable LEDs

Basically, there are 14 programmable LEDs (7 on the left, 7 on the right side) provided for User to configure. The choice for each programmable LED can be any signal from the global assignment list, which includes all internal operation states of each function activated. Based on the application need, up to 14 (but not necessarily all) programmable LEDs can be activated. By properly configuring some or all 14 LEDs, the User will be able to view the relay's overall operation and some critical information immediately and intuitively without having to access any menu.

5 Softkeys The function of the »SOFTKEYS« changes. Their active functions appear on the bottom line of the display.

Possible functions are:

• Navigation;

• Parameter decrement/increment;

• Scrolling up/down a menu page;

• Moving to a digit; and

• Change into the parameter setting mode »Wrench Symbol«.

146 www.eaton.com

Page 147: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Item Graphic Name Description

6 INFO Key (Signals/Messages)

Looking through the present LED assignment. The Direct Select key can be activated at any time. If the INFO key is actuated again, the User will leave the LED menu.

Here only the first assignments of the LEDs will be shown. Every three seconds the »SOFTKEYs« will be shown (flashing).

Displaying the Multiple Assignments

If the INFO key is pressed, only the first assignments of any LED is shown. Every three seconds the »SOFTKEYs« will be shown (flashing).

If there is more than one signal assigned to an LED (indicated by three dots), the User can check the state of the multiple assignments by proceeding as follows.

In order to show all (multiple) assignments, select an LED by means of the »SOFTKEYs« »up« and »down«.

Via the »Softkey« »right«, call up a sub-menu of this LED that gives the User detailed information on the state of all signals assigned to this LED. An arrow symbol points to the LED whose assignments are currently displayed.

Via the »SOFTKEYs« »up« and »down«, the User can call up the next / previous LED.

In order to leave the LED menu, press the »SOFTKEY« »left« multiple times.

www.eaton.com 147

Page 148: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Item Graphic Name Description

7 »ACK/RST- Key« Used to abort changes and to acknowledge messages as well as resetting counters.

In order to reset, press the Softkey »Wrench« and enter the password.

The User can exit the reset menu by pressing the Softkey »Arrow-left«

8 RS232 Interface (PowerPort-E Connection)

Connection to the computer/software PowerPort-E is done via the RS232 interface.

9 »OK Key« When using the »OK« key, parameter changes are temporarily stored. If the »OK« key is pressed again, those changes are stored indefinitely.

10 »CTRL Key« Access to the Control menu (not available in all devices)

Basic Menu ControlThe graphic User interface is equivalent to a hierarchical structured menu tree. For access to the individual sub-menus, the »SOFTKEYS«/Navigation Keys are used. The function of the »SOFTKEYS« can be found near the bottom of the display.

Softkey Description• Via »SOFTKEY« »Up«, the User will be taken to the prior menu point/one parameter up by

scrolling upwards.• Via »SOFTKEY« »Left«, the User will be taken one step back.

• Via »SOFTKEY« »Down«, the User will be taken to the next menu point/one parameter down by scrolling downwards.

• Via »SOFTKEY« »Right«, the User will be taken to a sub-menu.

• Via »SOFTKEY« »Top of List«, the User will be taken directly to the top of a list.

• Via »SOFTKEY« »Bottom of List«, the User will be taken directly to the end of a list.

148 www.eaton.com

Page 149: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Softkey Description• Via »SOFTKEY« »+«, the related digit will be incremented. (Continuous pressure -> fast).

• Via »SOFTKEY« »-«, the related digit will be decremented. (Continuous pressure -> fast)

• Via »SOFTKEY« »Left«, the User will be taken one digit to the left.

• Via »SOFTKEY« »Right«, the User will be taken one digit to the right.

• Via »SOFTKEY« »Parameter Setting«, the User will call up the parameter setting mode.

• Via »SOFTKEY« »Delete«, data will be deleted.

In order to return to the main menu, just keep pressing the Softkey »Arrow-Left« until you arrive at the »Main Menu».

PowerPort-E Keyboard CommandsThe User can control PowerPort-E alternatively by means of keyboard commands (instead of the mouse).

Key Description

á Move up within the navigation tree or parameter list.

â

Move down within the navigation tree or parameter list.

ß

Collapse the tree item or select a folder on a higher level.

à Expands the tree item or selects a sub-folder.

Numpad + Expands the tree item.

Numpad - Collapses the tree item.

Home Moves to the top of the active window.

End Moves to the bottom of the active window.

Ctrl+O Opens the file opening dialog. Allows browsing through the file system for an existing device file.

Ctrl+N Creates a new parameter file by means of a template.

Ctrl+S Saves the actual loaded parameter file.

F1 Displays the on-line help information.

www.eaton.com 149

Page 150: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Key Description

F2 Loads device data.

F5 Reloads the displayed data of a device.

Ctrl+F5 Enables the automatic refresh.

Ctrl+Shift+T Moves back to the navigation window.

Ctrl+F6 Walks through the tabular forms (detail windows).

Page á Moves to the previous value (parameter setting).

Page â Moves to the next value (parameter setting).

150 www.eaton.com

Page 151: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

PowerPort-EPowerPort-E is software that is used to configure a device and read data from a device. PowerPort-E provides the following:

• Menu controlled parameter setting including validity checks;• Off-line configuration of all relay types;• Reading and evaluation of statistical data and measuring values;• Commissioning Support (Forcing Relays, Disarming Relays);• Display of the device status; and• Fault analysis via event and fault recorder.

Installation of PowerPort-EPort 52152 must not be blocked by a Firewall. If it is, the connection will be blocked.

If the Windows Vista User Access Control pops up while installing PowerPort-E, please “Allow” all installation requirements concerning PowerPort-E.

System Requirements: Windows 2000, Windows XP, Windows Vista, or Windows 7).

To install PowerPort-E:

• Double-click on the installation file with the left mouse button.

• Confirm by pressing the »Continue« button in the INFO frame.

• Select an installation path or confirm the standard installation path by mouse click on the »Continue« button.

• Confirm the entry for the suggested installation folder by mouse click on the »Continue« button.

• Start the installation process by mouse click on the »Install« button.

• Finish the installation procedure by mouse click on the »Complete« button.

If the suggested installation folder was chosen in the procedure above, the User can now call up the program via

[Start > Programs > Eaton Relays> PowerPort-E].

Uninstalling PowerPort-EVia the [Start>System Control >Software] menu, the PowerPort-E application can be uninstalled from the com-puter.

www.eaton.com 151

Page 152: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Setting up the Serial Connection PC - Device

Set Up a Connection Via Serial Interface Under Windows 2000

After installation of the software, the »Connection PC/Notebook to the Device« has to be initially configured so that the User is able to read device data or re-write them into the device by means of the PowerPort-E application.

To connect the device to the User's PC/notebook, a special null modem cable is needed (no serial cable!- -please refer to the section »Null Modem Cable«).

If the PC/notebook does not have a serial interface, the User will need a special USB-to-serial-adapter. If the USB-to-serial-adapter is correctly installed, communication with the device can be established using the CD provided (see the next section).

The connection of the PC/notebook to the device MUST NOT be protected/encrypted via a smartcard.

If the network connection wizard asks to encrypt the connection via a smartcard or not, please choose »Do not use the smartcard«.

Setting Up/Configuring the Connection

• Connect the PC/notebook with the device via a null modem cable.

• Start the PowerPort-E application.•

• Select the menu point »Device Connection« in the »Settings« menu.

• Click on »Serial Connection«.

• Click the »Settings« button.

• When initially setting up the connection, a dialog window appears with the information that, so far, a direct connection with your protection device has not been established. Click on »Yes«.

• If, to this point, a location has not been set up on your PC, your location information has to be put in. Confirm the pop-up window »Telephone and Modem Options« with »OK«.

• The Windows network connection assistant appears after the location information is set up. Select the connection type »Establish direct connection to another computer«.

• Select the serial interface (COM-Port) where the device shall be connected.

• Select »To be used for all Users« in the »Availability of the connection« window.

• Do not change the connection name appearing in window »Name of the connection« and click the button »Complete«.

• Finally, you arrive again in the window »Device Installation« from where you started establishing the connection. Confirm the adjustments by clicking the »OK« button.

152 www.eaton.com

Page 153: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Due to a problem in Windows 2000, it is possible that the automatically made communication settings are not correctly adopted. In order to overcome this problem, proceed as follows after setting up the serial connection.

• Select the menu point »Device Connection« in the »Settings« menu.

• Select »Serial Connection«.

• Click on the »Settings« button.

• Change the register card to »General«.

• Ensure that »Communication cable between two computers Com X« is selected in the »Drop Down Menu«. X = the interface number where the User has connected the null modem cable.

• Click the »Configure« button.

• Ensure that the »Hardware Flowing Control« is activated.

• Ensure that a baud rate »115200« is selected.

Set Up a Serial Connection Via Serial Interface Under Windows XP

After installation of the software, the »Connection PC/Notebook to the Device« has to be initially configured so that the User is able to read device data or re-write them into the device by means of the PowerPort-E application.

To connect the device to the User's PC/notebook, a special null modem cable is needed (no serial cable!- -please refer to the section »Null Modem Cable«).

If the PC/notebook does not have a serial interface, the User will need a special USB-to-serial-adapter. If the USB-to-serial-adapter is correctly installed, communication with the device can be established using the CD provided (see the next section).

Setting Up/Configuring the Connection

• Connect your PC/notebook with the device via a null modem cable.

• Start the PowerPort-E application.

• Select the menu point »Device Connection« in the »Settings« menu.

• Click on »Serial Connection«.

• Click the »Settings« button.

• When initially setting up the connection, a dialog window appears with the information that, so far, a direct connection with your protection device has not been established. Click on »Yes«.

www.eaton.com 153

Page 154: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

• If, to this point, a location has not been set up on your PC, your location information has to be put in. Confirm the following pop-up window »Telephone and Modem Options« by selecting »OK«.

• The Windows network connection assistant appears after the location information is set up. Select the connection type »Establish direct connection to another computer«.

• Select the serial interface (COM-Port) where the device will be connected.

• Select »To be used for all Users« in the »Availability of the connection« window.

• Do not change the connection name appearing in the »Name of the connection« window and click the »Complete« button.

• Finally, you arrive again in the »Device Installation« window where you started establishing the connection. Confirm the adjustments by clicking the »OK« button.

Set up a Connection Via Serial Interface Under Windows Vista or Windows 7

Establishing the connection between PowerPort-E and the device is a three step procedure.

1.Installing PowerPort-E (the application itself)

2.Installing a (virtual) modem (that is a precondition for TCP/IP communication via a null modem cable)/(to be done within the Windows Phone and Modem dialog).

154 www.eaton.com

RS232

Parameter Setting and Evaluation via Serial/RS232

PowerPort-E

Protective Relay

Device Example

Page 155: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

3.Establishing a network connection between PowerPort-E and the device (to be done within PowerPort-E).

1. Installation of PowerPort-E (the application itself).

• Refer to the “Installation of PowerPort-E” (earlier in this section).

2. Installation of the (virtual) modem.

• Open the Windows Start menu and type “Phone and Modem” and RETURN.• This opens the “Phone and Modem” Dialog.• Go to the »Modem« tab.• Click on the »Add« button.• The Hardware Wizard window “Install New Modem” pops up.• Set the check box “Don´t detect my modem; I will select it from a list”.• Click on the »Next« button.• Select Communications cable between two computers.• Click on the »Next« button.• Choose the correct COM-Port.• Click on the »Next« button.• Click on the »Finish« button.• Select the new added modem and click on the »Properties« button.• Go to the »General« tab.• Click on the »Change settings« button.• Go to the »Modem« tab.• Within the Drop-Down Menu, set the correct baud rate = 115200.• Close this dialog with the »OK« button.• Close the Phone and Modem dialog with the »OK« button.• You have to reboot your computer now!

3. Establishing a network connection between PowerPort-E and the device.

• Connect the device to the PC/notebook via a correct null modem cable.• Run PowerPort-E.• Call up »Device Connection« within the menu »Device Connection«.• Click on the »Settings« button.• A connection wizard will pop up asking you How do you want to connect.• Choose »Dial-up«.• The telephone number must not be empty. Please enter any number (e.g. 1).• The User name and password can be ignored.• Click on the »OK« button.

Calling Up Web Site While Connected to a Device

In principle, it is possible to call up web sites while there is an active connection to the device.

If your computer has no direct connection to the Internet, that means that it is placed behind a proxy server. In certain circumstances, the device connection has to be modified. The device connection has to be provided with

www.eaton.com 155

Page 156: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

the proxy settings.

Internet Explorer

For each connection, the proxy settings have to be set manually. Please proceed as follows.

• Start your Internet Explorer.

• Call up the »Tools« menu.

• Call up the »Internet options« menu.

• Call up the »Connections« tab.

• Left click on the »Settings« button on the right of the »Device-Connection«.

• Set the check box »Use Proxy Server for this connection«.

• Enter the proxy settings that are available from your network administrator.

• Confirm the settings by pressing »OK«.

Firefox

The proxy settings are centrally managed, so there is no need to modify any settings.

Establishing the Serial Connection Via a USB-/RS232-Adapter

If your PC/notebook does not have an RS-232 interface, an USB-/RS232-Adapter+Null Modem Cable can be used.

Only an adapter approved by Eaton Corporation may be used. First install the adapter (with the related driver that you can find on the CD) and then establish the connection (PowerPort-E => Device). The adapters must support very high speed data transfer.

Set-up a Connection Via Ethernet - TCP/IP

Warning: Mixing up IP Addresses

(In case there is more than one protective device within the TCP/IP network or establishing an unintentional wrong connection to a protective device based on a wrong entered IP address.

Transferring parameters into the wrong protective device might lead to death, personal injury, or damage of electrical equipment.

In order to prevent faulty connections, the User MUST document and maintain a list with the IP addresses of any switchboard/protective devices.

The User MUST double check the IP addresses of the connection that is to be established. That means, the User MUST first read out the IP address at the HMI of the device (within menu [Device para/TCP IP]) then compare the IP address with the list. If the addresses are identical, establish the connection. If they are not, DO NOT establish the connection.

156 www.eaton.com

Page 157: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Establishing a connection via TCP/IP to the device is only possible if your device is equipped with an Ethernet Interface (RJ45).

Contact your IT administrator in order to establish the network connection.

Part 1: Set the TCP/IP Parameters at the panel (Device).

Call up the »Device parameter/TCP/IP« menu at the HMI (panel) and set the following parameters:

• TCP/IP address

• Subnet mask

• Gateway

Part 2: Setting the IP address within PowerPort-E.

• Call up the menu Settings/Device Connection within PowerPort-E.

• Set the radio button Network Connection.

• Enter the IP-Address of the device that should be connected.

www.eaton.com 157

TCP/IP

Parameter Setting and Evaluation via TCP/IP

PowerPort-E

IP-A

ddre

ss

Device Example

Page 158: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Or:

Set-up a Connection Via Modbus Tunnel

Establishing a connection via a Gateway (TCP/IP)/Modbus RTU to the device is only possible if your device is equipped with an Ethernet Interface (RJ45).

Contact your IT administrator in order to establish the network connection.

Part 1: If you do not know the Slave ID of the device that should be connected via Modbus Tunnel, it can be read out at the device.

158 www.eaton.com

Protective Relay

Protective Relay...

TCP/IP

TCP/IP

TCP/IP

Parameter Setting and Evaluation via TCP/IP

PowerPort-E

IP-A

ddre

ss

IP-A

ddre

ss

IP-A

ddre

ss

TCP/IP

Ethernet

Device Example

Device Example

Device Example

Page 159: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

• Call up the menu »Device parameter/Modbus« at the HMI (panel) and read out the Slave ID.

Part 2: Setting the IP address of the gateway and the Slave ID of the device that is to be connected via Modbus tunnel using PowerPort-E.

• Call up the menu Settings/Device Connection within PowerPort-E.

• Set the radio button Modbus TCP Gateway.

• Enter the IP-Address of the device that should be connected.

• Enter the Slave ID of the device.

www.eaton.com 159

Page 160: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

PowerPort-E Troubleshooting

• Make sure that the Windows service Telephony is started. In [Start>System Control >Administration >Services] the service »Telephony« must be visible and must have been started. If not, the service has to be started.

• For establishing the connection, the User needs to have sufficient rights (administration rights).

• If a firewall is installed on your computer, TCP/IP port 52152 must have been released.

160 www.eaton.com

Protective Relay

Protective Relay ...

TCP/IP

Modbus RTU

Modbus RTU

Parameter Setting and Evaluation via Modbus Tunnel

PowerPort-E

Power Xpert Gateway

SLA

VE

ID 2

SLA

VE

ID 3

SLA

VE

ID n

IP-Address

Modbus RTU

Device Example

Device Example

Device Example

Page 161: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

• If your computer does not have a serial interface, the User needs a USB-to-serial-adapter, approved by Eaton Corporation. This adapter has to be properly installed.

• Ensure that a null modem cable is used (a standard serial cable without control wires does not enable communication).

If a serial interface connection can not be established, and the User is running a Windows XP Operating System, the following may be the cause.

If a serial interface was selected in the connection assistant, it may be that this is not entered correctly in the dial-up network due to a bug in the Windows operating system. Your attention is drawn to this problem by the operational software and the error message »Warning, invalid connection setting« will be shown.

To solve this problem, you need administration rights.

Please proceed as follows.

• Select the menu item »Device Connection« in the »Settings« menu.

• Select »Serial Connection«.

• Click the »Settings« button.

• Change the register card to »General«.

• Ensure that »Communication cable between two computers (Com X)« is selected in the Drop Down menu. »X« = the interface number where the null modem cable is connected.

If the message »Warning, invalid connection settings« appears during establishment of the connection, it indicates that the connection adjustments chosen are not correct.

If this warning is displayed, the User may respond as follows.

»Yes«: (to set up a completely new connection).By selecting »Yes«, all adjustments are canceled and the connection assistant is opened again for renewed adjustment of the connection to the device.

This procedure is advisable in case basic adjustments cannot be modified via the characteristics dialog (e.g.: if a new additional serial interface has been installed on the system).

»No«: (to modify the existing dial-up network entry).Selecting »No« opens the dialog for characteristics of the connection settings. During the dialog, it is possible to correct invalid settings (e.g.: the recommended baud rate).

»Cancel«:The warning is ignored and the connection adjustments remain as they are set. This procedure is accepted for a limited time, but the User is required to establish a correct connection at a later time.

www.eaton.com 161

Page 162: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

PowerPort-E Persistent Connection Problems

In the case of persistent connection problems, the User should remove all connection settings and establish them again. In order to remove all connection settings, please proceed as follows.

1. Remove the Settings for the Dial-up Network.

• Close PowerPort-E.

• Call up the »Control Panel«.

• Choose »Network & Internet«.

• On the left side, click on »Manage Network Connections«.

• Right click on »"Protective Device Name" Direct Connection«.

• Choose »Delete« from the shortcut menu.

• Click on the »OK« button.

2. Remove the (Virtual) Modem.

• Call up the »Control Panel«.

• Choose »Hardware & Sound«.

• Choose »Phone & Modem Options«.

• Go to the »Modem« tab.

• Click on the correct (in case there is more than one) entry »Connection cable between two computers«.

• Click on the »Remove« button.

Loading of Device Data When Using PowerPort-E• Start the PowerPort-E application.

• Make sure the connection has been established properly.

• Connect your PC with the device via a null modem cable.

• Select »Receiving Data From The Device« in the »Device« menu.

162 www.eaton.com

Page 163: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Restoring Device Data When Using PowerPort-EBy selecting the »Transfer only modified parameters into the device« button, only modified parameters are transmitted into the device.

Parameter modifications are indicated by a red “star symbol” in front of the parameter.

The star symbol (in the device tree window) indicates that parameters in the opened file (within PowerPort-E) differ from parameters stored on your local hard disk.

By selecting the »Transfer only modified parameters into the device« button, the User can transmit all parameters that are marked by this symbol.

If a parameter file is saved on the local hard drive, these parameters are no longer classified to be modified and cannot be transmitted via the »Transfer only modified parameters into the device« button.

In case the User has loaded and modified a parameter file from the device and saved it to the local hard drive without transferring the parameters into the device before hand, the User cannot use the »Transfer only modified parameters into the device« button. In this case, use the »Transfer all parameters into the device« button.

The »Transfer only modified parameters into the device« button only works if modified parameters are available in the PowerPort-E application.

In contrast, all parameters of the device are transferred when the »Transfer all parameters into the device« button is pressed (provided all device parameters are valid).

• In order to (re-)transfer changed parameters into the device, select »Transfer all parameters into the device« in the »Device« menu.

• Confirm the safety inquiry »Shall the parameters be overwritten into the device?«.

• Enter the password for setting parameters in the pop-up window.

• The changed data is transferred to the device and adopted.

• Confirm the inquiry »Parameters successfully updated?«. It is recommended to save the parameters into a local file on your hard drive. Confirm »Shall The Data Be Saved Locally?“« with »Yes« (recommended). Select a suitable folder on the hard disk.

• Confirm the chosen folder by clicking »Save«.

• The changed parameter data are now saved in the chosen folder.

www.eaton.com 163

Page 164: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Backup and Documentation When Using PowerPort-EHow to Save Device Data on a PC

Click on »Save as ...« in the »File« menu. Specify a name, choose a folder on the hard disk, and save the device data accordingly.

Printing of Device Data When Using PowerPort-E (Setting List)

The »Printing« menu offers the following options:

• Printer settings;• Page preview;• Printing; and • Exporting the selected print range into a "txt" file.

The printing menu of the PowerPort-E software offers different types of printing ranges.

• Printing of the complete parameter tree:All values and parameters of the present parameter file are printed.

• Printing of the displayed working window: Only the data shown on the relevant working window are printed (i.e.: this applies, if at least one window is opened).

• Printing of all opened working windows:The data shown on all windows are printed (i.e.: this applies only if more than one window is opened).

• Printing of the device parameter tree as from a shown position on:All data and parameters of the device parameter tree are printed as from the position/marking in the navigation window. Below this selection, the complete name of the marking is additionally displayed.

Exporting Data as a “txt” File Via PowerPort-E

Within the print menu [File>Print], the User can choose »Export into File« in order to export the device data into a “txt” file.

When exporting data, only the actual selected printing range will be exported into a “txt” file. That means that if the User has chosen the “Complete device parameter tree” printing range, then the “Complete device parameter tree” will be exported. But, if the User has chosen the “Actual working window” printing range, only that range of data will be exported.

This is the only method available to export data via PowerPort-E.

If the User exports a “txt” file, the content of this file is encoded as Unicode. That means that, if the User wants to edit this file, the application must support Unicode encoded files (e.g.: Microsoft Office 2003 or higher).

164 www.eaton.com

Page 165: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Off-line Device Planning Via PowerPort-E

In order to be able to transmit a parameter file (e.g.: created off-line) into the device, the following information must be located:

• Type code (written on the top of the device/type label); and

• Version of the device model (can be found in menu [Device Parameters\Version].

The PowerPort-E application also enables the User to create a configuration/parameter file off-line using a “Device Model”. The advantage of using a device model is that the User can pre-configure a device by setting parameters in advance.

The User can also read the parameter file out of the device, further process it off-line (e.g.: from the office) and finally re-transfer it to the device.

The User can either:

• Load an existing parameter file from a device (please refer to the Section “Loading Device Data When Using PowerPort-E");

• Create a new parameter file (see below); or• Open a locally saved parameter file (backup).

In order to create a new device/parameter file by way of a device template off-line.

• In order to create a new off-line parameter file, select »Create new parameter file« within the »File« menu.

• A working window pops- up. Please make sure that you select the right device type with the correct version and configuration.

• Finally click on »Apply«.

• In order to save the device configuration, select »Save« out of the »File« menu.

• Within the »Modify Device Configuration (Typecode)« menu, the User can modify the device configuration or simply find out the type code of the current selection.

If the User wants to transfer the parameter file into a device, please refer to Section “Restoring Device Data When using PowerPort-E”.

Measuring Values

Read Out Measured ValuesIn the »Operation/Measured Values« menu, both measured and calculated values can be viewed. The measured values are ordered by »Standard values« and »Special values« (depending on the type of device).

www.eaton.com 165

Page 166: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Read Out of Measured Values Via PowerPort-E

• If PowerPort-E is not running, please start the application.

• If the device data have not been loaded, select »Receive Data From The Device« from the »Device« menu.

• Double click on the »Operation« icon in the navigation tree.

• Double click on the »Measured Values« icon within the »Operation« navigation tree.

• Double click the »Standard Values« or »Special values« within the »Measured values« tree.

• The measured and calculated values are now shown in tabular form in the window.

To have the measuring data read in a cyclic manner, select »Auto refresh« in the »View« menu. The measured values are read out about every two seconds.

Current - Measured Values

If the device is not equipped with an voltage measuring card the first measuring input on the first current measuring card (slot with the lowest number) will be used as the reference angle (»IA«).

Value Description Menu Path

IA Fund. Measured value: Phase current (Fundamental)

[Operation

/Measured Values

/Current Fund.]IB Fund. Measured value: Phase current

(Fundamental)[Operation

/Measured Values

/Current Fund.]IC Fund. Measured value: Phase current

(Fundamental)[Operation

/Measured Values

/Current Fund.]IX meas Fund. Measured value (measured): IX

(Fundamental)[Operation

/Measured Values

/Current Fund.]IR calc Fund. Measured value (calculated): IR

(Fundamental)[Operation

/Measured Values

/Current Fund.]

166 www.eaton.com

Page 167: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Value Description Menu Path

I0 Fund. Measured value (calculated): Zero current (Fundamental)

[Operation

/Measured Values

/Current Fund.]I1 Fund. Measured value (calculated): Positive

phase sequence current (Fundamental)[Operation

/Measured Values

/Current Fund.]I2 Fund. Measured value (calculated): Unbalanced

load current (Fundamental)[Operation

/Measured Values

/Current Fund.]Angle IA Measured Value (Calculated): Angle of

Phasor IA[Operation

/Measured Values

/Current Fund.]Angle IB Measured Value (Calculated): Angle of

Phasor IB[Operation

/Measured Values

/Current Fund.]Angle IC Measured Value (Calculated): Angle of

Phasor IC[Operation

/Measured Values

/Current Fund.]Angle IX meas Measured Value: Angle of Phasor IX meas [Operation

/Measured Values

/Current Fund.]Angle IR calc Measured Value (Calculated): Angle of

Phasor IR calc[Operation

/Measured Values

/Current Fund.]Angle I0 Measured Value (calculated): Angle of Zero

Sequence System[Operation

/Measured Values

/Current Fund.]Angle I1 Measured Value (calculated): Angle of

Positive Sequence System[Operation

/Measured Values

/Current Fund.]

www.eaton.com 167

Page 168: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Value Description Menu Path

Angle I2 Measured value (calculated): Angle of Negative Sequence System

[Operation

/Measured Values

/Current Fund.]IA RMS Measured value: Phase current (RMS) [Operation

/Measured Values

/Current RMS]IB RMS Measured value: Phase current (RMS) [Operation

/Measured Values

/Current RMS]IC RMS Measured value: Phase current (RMS) [Operation

/Measured Values

/Current RMS]IX meas RMS Measured value (measured): IX (RMS) [Operation

/Measured Values

/Current RMS]IR calc RMS Measured value (calculated): IR (RMS) [Operation

/Measured Values

/Current RMS]%IA THD Measured Value (Calculated): IA Total

Harmonic Distortion[Operation

/Measured Values

/Current RMS]%IB THD Measured Value (Calculated): IB Total

Harmonic Distortion[Operation

/Measured Values

/Current RMS]%IC THD Measured Value (Calculated): IC Total

Harmonic Distortion[Operation

/Measured Values

/Current RMS]IA THD Measured Value (Calculated): IA Total

Harmonic Current [Operation

/Measured Values

/Current RMS]

168 www.eaton.com

Page 169: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Value Description Menu Path

IB THD Measured Value (Calculated): IB Total Harmonic Current

[Operation

/Measured Values

/Current RMS]IC THD Measured Value (Calculated): IC Total

Harmonic Current [Operation

/Measured Values

/Current RMS]%(I2/I1) Measured value (calculated): I2/I1 if ABC,

I1/I2 if CBA[Operation

/Measured Values

/Current Fund.]

Voltage - Measured ValuesThe first measuring input on the first measuring card (slot with the lowest number) is used as the reference angle.

E.g. »VA« respectively »VAB«.

Value Description Menu Path

f Measured Value: Frequency [Operation

/Measured Values

/Voltage RMS]VAB Fund. Measured value: Phase-to-phase voltage

(Fundamental)[Operation

/Measured Values

/Voltage Fund.]VBC Fund. Measured value: Phase-to-phase voltage

(Fundamental)[Operation

/Measured Values

/Voltage Fund.]VCA Fund. Measured value: Phase-to-phase voltage

(Fundamental)[Operation

/Measured Values

/Voltage Fund.]VA Fund. Measured value: Phase-to-neutral voltage

(Fundamental)[Operation

/Measured Values

/Voltage Fund.]

www.eaton.com 169

Page 170: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Value Description Menu Path

VB Fund. Measured value: Phase-to-neutral voltage (Fundamental)

[Operation

/Measured Values

/Voltage Fund.]VC Fund. Measured value: Phase-to-neutral voltage

(Fundamental)[Operation

/Measured Values

/Voltage Fund.]VX meas Fund. Measured value (measured): VG measured

(Fundamental)[Operation

/Measured Values

/Voltage Fund.]VR calc Fund. Measured value (calculated): VR

(Fundamental)[Operation

/Measured Values

/Voltage Fund.]V0 Fund. Measured value (calculated): Symmetrical

components Zero voltage(Fundamental)[Operation

/Measured Values

/Voltage Fund.]V1 Fund. Measured value (calculated): Symmetrical

components positive phase sequence voltage(Fundamental)

[Operation

/Measured Values

/Voltage Fund.]V2 Fund. Measured value (calculated): Symmetrical

components negative phase sequence voltage(Fundamental)

[Operation

/Measured Values

/Voltage Fund.]VAB RMS Measured value: Phase-to-phase voltage

(RMS)[Operation

/Measured Values

/Voltage RMS]VBC RMS Measured value: Phase-to-phase voltage

(RMS)[Operation

/Measured Values

/Voltage RMS]VCA RMS Measured value: Phase-to-phase voltage

(RMS)[Operation

/Measured Values

/Voltage RMS]

170 www.eaton.com

Page 171: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Value Description Menu Path

VA RMS Measured value: Phase-to-neutral voltage (RMS)

[Operation

/Measured Values

/Voltage RMS]VB RMS Measured value: Phase-to-neutral voltage

(RMS)[Operation

/Measured Values

/Voltage RMS]VC RMS Measured value: Phase-to-neutral voltage

(RMS)[Operation

/Measured Values

/Voltage RMS]VX meas RMS Measured value (measured): VG measured

(RMS)[Operation

/Measured Values

/Voltage RMS]VR calc RMS Measured value (calculated): VR (RMS) [Operation

/Measured Values

/Voltage RMS]Angle VAB Measured Value (Calculated): Angle of

Phasor VAB[Operation

/Measured Values

/Voltage Fund.]Angle VBC Measured Value (Calculated): Angle of

Phasor VBC[Operation

/Measured Values

/Voltage Fund.]Angle VCA Measured Value (Calculated): Angle of

Phasor VCA[Operation

/Measured Values

/Voltage Fund.]Angle VA Measured Value (Calculated): Angle of

Phasor VA[Operation

/Measured Values

/Voltage Fund.]Angle VB Measured Value (Calculated): Angle of

Phasor VB[Operation

/Measured Values

/Voltage Fund.]

www.eaton.com 171

Page 172: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Value Description Menu Path

Angle VC Measured Value (Calculated): Angle of Phasor VC

[Operation

/Measured Values

/Voltage Fund.]Angle VX meas Measured Value: Angle of Phasor VX meas [Operation

/Measured Values

/Voltage Fund.]Angle VR calc Measured Value (Calculated): Angle of

Phasor VR calc[Operation

/Measured Values

/Voltage Fund.]Angle V0 Measured Value (calculated): Angle of Zero

Sequence System[Operation

/Measured Values

/Voltage Fund.]Angle V1 Measured Value (calculated): Angle of

Positive Sequence System[Operation

/Measured Values

/Voltage Fund.]Angle V2 Measured value (calculated): Angle of

Negative Sequence System[Operation

/Measured Values

/Voltage Fund.]%(V2/V1) Measured value (calculated): %V2/V1 if

ABC, %V1/V2 if CBA[Operation

/Measured Values

/Voltage Fund.]% VAB THD Measured value (calculated): VAB Total

Harmonic Distortion / fundamental[Operation

/Measured Values

/Voltage RMS]% VBC THD Measured value (calculated): VBC Total

Harmonic Distortion / fundamental[Operation

/Measured Values

/Voltage RMS]% VCA THD Measured value (calculated): VCA Total

Harmonic Distortion / fundamental[Operation

/Measured Values

/Voltage RMS]

172 www.eaton.com

Page 173: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Value Description Menu Path

% VA THD Measured value (calculated): VA Total Harmonic Distortion / fundamental

[Operation

/Measured Values

/Voltage RMS]% VB THD Measured value (calculated): VB Total

Harmonic Distortion / fundamental[Operation

/Measured Values

/Voltage RMS]% VC THD Measured value (calculated): VC Total

Harmonic Distortion / fundamental[Operation

/Measured Values

/Voltage RMS] VAB THD Measured value (calculated): VAB Total

Harmonic Distortion [Operation

/Measured Values

/Voltage RMS] VBC THD Measured value (calculated): VBC Total

Harmonic Distortion [Operation

/Measured Values

/Voltage RMS] VCA THD Measured value (calculated): VCA Total

Harmonic Distortion [Operation

/Measured Values

/Voltage RMS] VA THD Measured value (calculated): VA Total

Harmonic Distortion [Operation

/Measured Values

/Voltage RMS] VB THD VB THD [Operation

/Measured Values

/Voltage RMS] VC THD VC THD [Operation

/Measured Values

/Voltage RMS]

www.eaton.com 173

Page 174: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Power - Measured Values

Value Description Menu Path

Disp PF Measured Value (Calculated): 55D - Displacement Power Factor Power factor

[Operation

/Measured Values

/Power]Wh Fwd Positive Active Power is consumed active

energy [Operation

/Measured Values

/Energy]Wh Rev Negative Active Power (Fed Energy) [Operation

/Measured Values

/Energy]VArh Lag Positive Reactive Power is consumed

Reactive Energy[Operation

/Measured Values

/Energy]VArh Lead Negative Reactive Power (Fed Energy) [Operation

/Measured Values

/Energy]VAh Net Net VA Hours [Operation

/Measured Values

/Energy]Wh Net Net Watt Hours [Operation

/Measured Values

/Energy]VArh Net Net VAr Hours [Operation

/Measured Values

/Energy]Start Date/Time Energy counters run since ... (Date and

time of last reset)[Operation

/Measured Values

/Energy]Syst VA RMS Measured VAs (RMS) [Operation

/Measured Values

/Power]

174 www.eaton.com

Page 175: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Value Description Menu Path

Syst W RMS Measured Watts. Active power (P- = Fed Active Power, P+ = Consumpted Active Power) (RMS)

[Operation

/Measured Values

/Power]Syst VAr RMS Measured VARs. Reactive power (Q- = Fed

Reactive Power, Q+ = Consumpted Reactive Power) (RMS)

[Operation

/Measured Values

/Power]Apt PF Measured Value (Calculated): 55A -

Apparent Power Factor[Operation

/Measured Values

/Power]

Energy Counter

EnergyCr

Direct Commands of the Energy Counter Module

Parameter Description Setting Range Default Menu Path

Res all Energy Cr

Reset of all Energy Counters Inactive,

Active

Inactive [Operation

/Reset]

Signals of the Energy Counter Module (States of the Outputs)

Name Description

Cr Overflow VAh Net Signal: Counter Overflow VAh NetCr Overflow Wh Net Signal: Counter Overflow Wh NetCr Overflow Wh Fwd Signal: Counter Overflow Wh FwdCr Overflow Wh Rev Signal: Counter Overflow Wh RevCr Overflow VArh Net Signal: Counter Overflow VArh NetCr Overflow VArh Lag Signal: Counter Overflow VArh LagCr Overflow VArh Lead Signal: Counter Overflow VArh LeadVAh Net Res Cr Signal: VAh Net Reset CounterWh Net Res Cr Signal: Wh Net Reset CounterWh Fwd Res Cr Signal: Wh Fwd Reset CounterWh Rev Res Cr Signal: Wh Rev Reset CounterVArh Net Res Cr Signal: VArh Net Reset CounterVArh Lag Res Cr Signal: VArh Lag Reset Counter

www.eaton.com 175

Page 176: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

VArh Lead Res Cr Signal: VArh Lead Reset CounterRes all Energy Cr Signal: Reset of all Energy CountersCr OverflwWarn VAh Net Signal: Counter VAh Net will overflow soonCr OverflwWarn Wh Net Signal: Counter Wh Net will overflow soonCr OverflwWarn Wh Fwd Signal: Counter Wh Fwd will overflow soonCr OverflwWarn Wh Rev Signal: Counter Wh Rev will overflow soonCr OverflwWarn VArh Net Signal: Counter VArh Net will overflow soonCr OverflwWarn VArh Lag Signal: Counter VArh Lag will overflow soonCr OverflwWarn VArh Lead Signal: Counter VArh Lead will overflow soon

176 www.eaton.com

Page 177: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

StatisticsStatistics

In the »Operation/Statistics« menu, the minimum, maximum, and mean values of the measured and calculated quantities can be found. The statistics are ordered by »Standard values« and »Special values« (depending on the type of device and the device planning).

In the »Device Parameter/Statistics« menu, the User can either set a fixed synchronization time and a calculation interval or start and stop the statistics via a function (e.g.: digital input).

Read Out Statistics• Call up the main menu.

• Call up the »Operation/Statistics« sub-menu.

• Call up either the »Standard values« or »Special values«.

Statistics to Be Read Out Via PowerPort-E

• If PowerPort-E is not running, please start the application.

• If device data have not been downloaded recently, click »Receive Data From The Device« in the »Device« menu.

• Double click on the »Operation« icon in the navigation tree.

• Double click on the »Statistics« icon within the »Operation« navigation tree.

• Double click on the »Standard values« or »Special values« icon.

• In the window, the statistical data are shown in tabular form.

The values can be read out cyclically. For this purpose, please select »Auto Refresh« out of the »View« menu.

Statistics (Configuration)The Statistics module can be configured within the »Device Parameter/Statistics« menu.

The time interval, that is taken into account for the calculation of the statistics, can either be limited by a fixed duration or it can be limited by a start function (freely assignable signal from the »assignment list« menu).

Fixed Duration:

If the statistics module is set to a fixed duration/time interval, the minimum, maximum, and average values will be calculated and displayed continuously on the basis of this duration/time interval.

Start Function (Flexible Duration):

If the statistics module is to be initiated by a start function, the statistics will not be updated until the start function becomes true (rising edge). At the same time, a new time interval will be started.

www.eaton.com 177

Page 178: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Statistics (Configuration) Via PowerPort-E

• If PowerPort-E is not running, please start the application.

• If device data have not been downloaded recently, click »Receive Data From The Device« in the»Device« menu.

• Double click on the »Device Parameter« icon in the navigation tree.

• Double click on the »Statistics« icon within the »Device Parameter« navagation tree.

• Configure the Statistics module.

Direct Commands

Parameter Description Setting Range Default Menu Path

ResFc all Resetting of all Statistic values (Current Demand, Power Demand, Min, Max)

Inactive,

Active

Inactive [Operation

/Reset]ResFc I Demand

Resetting of Statistics - Current Demand (avg, peak avg)

Inactive,

Active

Inactive [Operation

/Reset]ResFc P Demand

Resetting of Statistics - Power Demand (avg, peak avg)

Inactive,

Active

Inactive [Operation

/Reset]ResFc Min Resetting of all Minimum values Inactive,

Active

Inactive [Operation

/Reset]ResFc Max Resetting of all Maximum values Inactive,

Active

Inactive [Operation

/Reset]

Global Protection Parameters of the Statistics Module

Parameter Description Setting Range Default Menu Path

ResFc Max Resetting of all Maximum values 1..n, Assignment List -.- [Device Para

/Statistics

/Min / Max]ResFc Min Resetting of all Minimum values 1..n, Assignment List -.- [Device Para

/Statistics

/Min / Max]

178 www.eaton.com

Page 179: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Start I Demand via:

Start Current demand by: Duration,

StartFct

Duration [Device Para

/Statistics

/Demand

/Current Demand]Start I Demand Fc

Start of the calculation, if the assigned signal becomes true.

Only available if: Start I Demand via: = StartFct

1..n, Assignment List -.- [Device Para

/Statistics

/Demand

/Current Demand]ResFc I Demand

Resetting of Statistics - Current Demand (avg, peak avg)

1..n, Assignment List -.- [Device Para

/Statistics

/Demand

/Current Demand]

www.eaton.com 179

Page 180: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Duration I Demand

Recording time

Only available if: Start I Demand via: = Duration

2 s,

5 s,

10 s,

15 s,

30 s,

1 min,

5 min,

10 min,

15 min,

30 min,

1 h,

2 h,

6 h,

12 h,

1 d,

2 d,

5 d,

7 d,

10 d,

30 d

15 s [Device Para

/Statistics

/Demand

/Current Demand]

Window I Demand

Window configuration Sliding,

Fixed

Fixed [Device Para

/Statistics

/Demand

/Current Demand]Start P Demand via:

Start Active Power demand by: Duration,

StartFct

Duration [Device Para

/Statistics

/Demand

/Power Demand]

180 www.eaton.com

Page 181: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Start P Demand Fc

Start of the calculation, if the assigned signal becomes true.

Only available if: Start P Demand via: = StartFct

1..n, Assignment List -.- [Device Para

/Statistics

/Demand

/Power Demand]ResFc P Demand

Resetting of Statistics - Power Demand (avg, peak avg)

1..n, Assignment List -.- [Device Para

/Statistics

/Demand

/Power Demand]Duration P Demand

Recording time

Only available if: Start P Demand via: = Duration

2 s,

5 s,

10 s,

15 s,

30 s,

1 min,

5 min,

10 min,

15 min,

30 min,

1 h,

2 h,

6 h,

12 h,

1 d,

2 d,

5 d,

7 d,

10 d,

30 d

15 s [Device Para

/Statistics

/Demand

/Power Demand]

www.eaton.com 181

Page 182: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Window P Demand

Window configuration Sliding,

Fixed

Sliding [Device Para

/Statistics

/Demand

/Power Demand]

States of the Inputs of the Statistics Module

Name Description Assignment Via

StartFc 1-I State of the module input: Start of Statistics 1 (Update the displayed Demand )

[Device Para

/Statistics

/Demand

/Current Demand]StartFc 2-I State of the module input: Start of Statistics

2 (Update the displayed Demand )[Device Para

/Statistics

/Demand

/Power Demand]ResFc I Demand-I State of the module input: Resetting of

Statistics - Current Demand (avg, peak avg)[Device Para

/Statistics

/Demand

/Current Demand]ResFc P Demand-I State of the module input: Resetting of

Statistics - Power Demand (avg, peak avg)[Device Para

/Statistics

/Demand

/Power Demand]ResFc Max-I State of the module input: Resetting of all

Maximum values [Device Para

/Statistics

/Min / Max]ResFc Min-I State of the module input: Resetting of all

Minimum values [Device Para

/Statistics

/Min / Max]

182 www.eaton.com

Page 183: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Signals of the Statistics Module

Name Description

ResFc all Signal: Resetting of all Statistic values (Current Demand, Power Demand, Min, Max)

ResFc I Demand Signal: Resetting of Statistics - Current Demand (avg., peak avg.)ResFc P Demand Signal: Resetting of Statistics - Power Demand (avg., peak avg.)ResFc Max Signal: Resetting of all Maximum values ResFc Min Signal: Resetting of all Minimum values

Counters of the Module Statistics

Value Description Menu Path

MeasPointNo Each measuring point that is taken over by the statistics increments this counter. By means of this counter, the User can check whether the statistics are alive and if data are being acquired.

[Operation

/Count and RevData

/Statistics]MeasPointNo2 Each measuring point that is taken over by

the statistics increments this counter. By means of this counter, the User can check whether the statistics are alive and if data are being acquired.

[Operation

/Count and RevData

/Statistics]Res Cr I Demand Number of resets since last booting. The

time stamp shows date and time of the last reset.

[Operation

/Statistics

/Demand

/Current Demand]Res Cr P Demand Number of resets since last booting. The

time stamp shows date and time of the last reset.

[Operation

/Statistics

/Demand

/Power Demand]Res Cr Min values Number of resets since last booting. The

time stamp shows date and time of the last reset.

[Operation

/Statistics

/Min

/Power]Res Cr Max values Number of resets since last booting. The

time stamp shows date and time of the last reset.

[Operation

/Statistics

/Max

/Power]

www.eaton.com 183

Page 184: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Current - Statistic Values

Value Description Menu Path

I1 max Fund. Maximum value positive phase sequence current (Fundamental)

[Operation

/Statistics

/Max

/Current]I1 min Fund. Minimum value positive phase sequence

current (Fundamental)[Operation

/Statistics

/Min

/Current]I2 max Fund. Maximum value unbalanced load current

(Fundamental)[Operation

/Statistics

/Max

/Current]I2 min Fund. Minimum value unbalanced load current

(Fundamental)[Operation

/Statistics

/Min

/Current]IA max RMS IA maximum value (RMS) [Operation

/Statistics

/Max

/Current]IA avg RMS IA average value (RMS) [Operation

/Statistics

/Demand

/Current Demand]IA min RMS IA minimum value (RMS) [Operation

/Statistics

/Min

/Current]

184 www.eaton.com

Page 185: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Value Description Menu Path

IB max RMS IB maximum value (RMS) [Operation

/Statistics

/Max

/Current]IB avg RMS IB average value (RMS) [Operation

/Statistics

/Demand

/Current Demand]IB min RMS IB minimum value (RMS) [Operation

/Statistics

/Min

/Current]IC max RMS IC maximum value (RMS) [Operation

/Statistics

/Max

/Current]IC avg RMS IC average value (RMS) [Operation

/Statistics

/Demand

/Current Demand]IC min RMS IC minimum value (RMS) [Operation

/Statistics

/Min

/Current]IX meas max RMS Measured value: IX maximum value (RMS) [Operation

/Statistics

/Max

/Current]

www.eaton.com 185

Page 186: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Value Description Menu Path

IX meas min RMS Measured value: IX minimum value (RMS) [Operation

/Statistics

/Min

/Current]IR calc max RMS Measured value (calculated): IR maximum

value (RMS)[Operation

/Statistics

/Max

/Current]IR calc min RMS Measured value (calculated): IR minimum

value (RMS)[Operation

/Statistics

/Min

/Current]%(I2/I1) max Measured value (calculated): I2/I1

maximum value if ABC, I1/I2 if CBA[Operation

/Statistics

/Max

/Current]%(I2/I1) min %(I2/I1) min [Operation

/Statistics

/Min

/Current]IA Peak demand IA Peak value, RMS value [Operation

/Statistics

/Demand

/Current Demand]IB Peak demand IB Peak value, RMS value [Operation

/Statistics

/Demand

/Current Demand]

186 www.eaton.com

Page 187: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Value Description Menu Path

IC Peak demand IC Peak value, RMS value [Operation

/Statistics

/Demand

/Current Demand]

Voltage - Statistic Values

Value Description Menu Path

f max Max. frequency value [Operation

/Statistics

/Max

/Voltage]f min Min. frequency value [Operation

/Statistics

/Min

/Voltage]V1 max Fund. Maximum value: Symmetrical components

positive phase sequence voltage (Fundamental)

[Operation

/Statistics

/Max

/Voltage]V1 min Fund. Minimum value: Symmetrical components

positive phase sequence voltage (Fundamental)

[Operation

/Statistics

/Min

/Voltage]V2 max Fund. Maximum value: Symmetrical components

negative phase sequence voltage (Fundamental)

[Operation

/Statistics

/Max

/Voltage]V2 min Fund. Minimum value: Symmetrical components

negative phase sequence voltage (Fundamental)

[Operation

/Statistics

/Min

/Voltage]

www.eaton.com 187

Page 188: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Value Description Menu Path

VAB max RMS VAB maximum value (RMS) [Operation

/Statistics

/Max

/Voltage]VAB min RMS VAB minimum value (RMS) [Operation

/Statistics

/Min

/Voltage]VBC max RMS VBC maximum value (RMS) [Operation

/Statistics

/Max

/Voltage]VBC min RMS VBC minimum value (RMS) [Operation

/Statistics

/Min

/Voltage]VCA max RMS VCA maximum value (RMS) [Operation

/Statistics

/Max

/Voltage]VCA min RMS VCA minimum value (RMS) [Operation

/Statistics

/Min

/Voltage]VA max RMS VA maximum value (RMS) [Operation

/Statistics

/Max

/Voltage]

188 www.eaton.com

Page 189: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Value Description Menu Path

VA min RMS VA minimum value (RMS) [Operation

/Statistics

/Min

/Voltage]VB max RMS VB maximum value (RMS) [Operation

/Statistics

/Max

/Voltage]VB min RMS VB minimum value (RMS) [Operation

/Statistics

/Min

/Voltage]VC max RMS VC maximum value (RMS) [Operation

/Statistics

/Max

/Voltage]VC min RMS VC minimum value (RMS) [Operation

/Statistics

/Min

/Voltage]VX meas max RMS Measured value: VX maximum value (RMS) [Operation

/Statistics

/Max

/Voltage]VX meas min RMS Measured value: VX minimum value (RMS) [Operation

/Statistics

/Min

/Voltage]

www.eaton.com 189

Page 190: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Value Description Menu Path

VR calc max RMS Measured value (calculated): VR maximum value (RMS)

[Operation

/Statistics

/Max

/Voltage]VR calc min RMS Measured value (calculated): VR minimum

value (RMS)[Operation

/Statistics

/Min

/Voltage]%(V2/V1) max Measured value (calculated): %V2/V1

maximum value[Operation

/Statistics

/Max

/Voltage]%(V2/V1) min Measured value (calculated): %V2/V1

minimum value [Operation

/Statistics

/Min

/Voltage]

Power - Statistic Values

Value Description Menu Path

Disp PF max Maximum value of the 55D - Displacement Power Factor power factor

[Operation

/Statistics

/Max

/Power]Disp PF min Minimum value of the 55D - Displacement

Power Factor power factor[Operation

/Statistics

/Min

/Power]Syst VA max Maximum value of the apparent power [Operation

/Statistics

/Max

/Power]

190 www.eaton.com

Page 191: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Value Description Menu Path

Syst VA avg Average of the apparent power [Operation

/Statistics

/Demand

/Power Demand]Syst VA min Minimum value of the apparent power [Operation

/Statistics

/Min

/Power]Syst W max Maximum value of the active power [Operation

/Statistics

/Max

/Power]Syst W avg Average of the active power [Operation

/Statistics

/Demand

/Power Demand]Syst W min Minimum value of the active power [Operation

/Statistics

/Min

/Power]Syst VAr max Maximum value of the reactive power [Operation

/Statistics

/Max

/Power]Syst VAr avg Average of the reactive power [Operation

/Statistics

/Demand

/Power Demand]

www.eaton.com 191

Page 192: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Value Description Menu Path

Syst VAr min Minimum value of the reactive power [Operation

/Statistics

/Min

/Power]Apt PF max Maximum value of the 55A - Apparent

Power Factor[Operation

/Statistics

/Max

/Power]Apt PF min Minimum value of the 55A - Apparent

Power Factor[Operation

/Statistics

/Min

/Power]VA Peak demand VA Peak value, RMS value [Operation

/Statistics

/Demand

/Power Demand]Watt Peak demand WATTS Peak value, RMS value [Operation

/Statistics

/Demand

/Power Demand]VAr Peak demand VARs Peak value, RMS value [Operation

/Statistics

/Demand

/Power Demand]

192 www.eaton.com

Page 193: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

System Alarms

Available Elements:System Alarms

Within the System Alarms menu [System Para/System Alarms], the User can configure:

• General Settings (activate/inactivate the Demand Management, optional assign a signal, that will block the Demand Management);

• Power Protection (please refer to section 32, 32V, 32VA);

• Demand Management (Power and Current); and

• THD Protection.

Demand ManagementDemand is the average of system current or power over a time interval (window). Demand management supports the User to keep energy demand below target values bound by contract (with the energy supplier). If the contractual target values are exceeded, extra charges are to be paid to the energy supplier.

Therefore, demand management helps the User detect and avoid averaged peak loads that are taken into account for the billing. In order to reduce the demand charge respective to demand rate, peak loads, if possible, should be diversified. That means, if possible, avoiding large loads at the same time. In order to assist the User in analyzing the demand, demand management might inform the User by an alarm. The User might also use demand alarms and assign them on relays in order to perform load shedding (where applicable).

Demand management comprises:

• Watt Demand (Active Power);• VAr Demand (Reactive Power);• VA Demand (Apparent Power); and• Current Demand.

Configuring the Demand

Configuring the demand is a two step procedure. Proceed as follows.

Step1. Configure the general settings within the [Device Para/Demand] menu:

• Set the trigger source to »Duration«.• Select a time base for the »window«.• Determine if the window is »fixed« or »sliding«.

The interval time (window) can be set to fixed or sliding.

Example for a fixed window: If the range is set for 15 minutes, the protective device calculates the average current or power over the past 15 minutes and updates the value every 15 minutes.

Example for a sliding window: If the sliding window is selected and the interval is set to 15 minutes, the protective device calculates and updates the average current or power continuously, for the past 15 minutes (the newest measuring value replaces the oldest measuring value continuously).

www.eaton.com 193

Page 194: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

194 www.eaton.com

5 6 7 8 9 10 11 12 13 14 15 16 17 181 2 3 4

5 6 7 8 9 10 11 12 13 14 15 16 17 181 2 3 4

5 6 7 8 9 10 11 12 13 14 15 16 17 181 2 3 4

5 6 7 8 9 10 11 12 13 14 15 16 17 181 2 3 4

Window configuration = Sliding

Window configuration = Fixed

Sliding

Sliding

t-Delay0

Duration

Average Calculation Pickup

t-Delay0

Average Calculation Pickup

t-Delay0

Average Calculation Pickup

t-Delay0

Average Calculation Pickup

Average Calculation Average Calculation Average Calculation Average Calculation

Average Calculation Average Calculation Average Calculation Average Calculation

Duration Duration Duration

Page 195: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Step 2. In addition, the Demand specific settings have to be configured in the [System Para/System Alarms/Demand] menu:

• Determine if the demand should generate an alarm or if it should run in the silent mode (Alarm active/inactive);

• Set the threshold; and• Where applicable, set a delay time for the alarm.

Peak DemandThe protective device also saves the peak demand values for current and power. The quantities represent the largest demand value since the demand values were last reset. Peak demands for current and system power are date and time stamped.

Within the [Operation/Demand] menu, the current Demand and Peak demand values can be seen.

Min. and Max. Values.Within the Operation menu the minimum (min.) and maximum (max.) values can be seen.

Minimum values since last reset: The minimum values are continuously compared to the last minimum value for that measuring value. If the new value is less than the last minimum, the value is updated. Within the [Device Para/Statistics] menu, a reset signal can be assigned.

Maximum values since last reset: The maximum values are continuously compared to the last maximum value for that measuring value. If the new value is greater than the last maximum, the value is updated. Within the [Device Para/Statistics] menu, a reset signal can be assigned.

THD ProtectionIn order to supervise power quality, the protective device can monitor the voltage (phase-to-phase) and current THDs.

Within the [System Para/System Alarms/THD] menu:

• Determine if an alarm is to be issued or not (Alarm active/inactive);• Set the threshold; and• Where applicable, set a delay time for the alarm.

Device Planning Parameters of the Demand Management

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Use [Device Plan-ning]

www.eaton.com 195

Page 196: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Signals of the Demand Management (States of the Outputs)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingAlarm Watt Power Signal: Alarm WATTS peakAlarm VAr Power Signal: Alarm VArs peakAlarm VA Power Signal: Alarm VAs peakAlarm Watt Demand Signal: Alarm WATTS demand valueAlarm VAr Demand Signal: Alarm VARs demand valueAlarm VA Demand Signal: Alarm VAs demand valueAlarm Current Demand Signal: Alarm Current demand valueAlarm I THD Signal: Alarm Total Harmonic Distortion CurrentAlarm V THD Signal: Alarm Total Harmonic Distortion VoltageTrip Watt Power Signal: Trip WATTS peakTrip VAr Power Signal: Trip VArs peakTrip VA Power Signal: Trip VAs peakTrip Watt Demand Signal: Trip WATTS demand valueTrip VAr Demand Signal: Trip VARs demand valueTrip VA Demand Signal: Trip VAs demand valueTrip Current Demand Signal: Trip Current demand valueTrip I THD Signal: Trip Total Harmonic Distortion CurrentTrip V THD Signal: Trip Total Harmonic Distortion Voltage

Global Protection Parameter of the Demand Management

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [System Alarms

/General Settings]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

1..n, Assignment List -.- [System Alarms

/General Settings]

Alarm Threshold Inactive,

Active

Inactive [System Alarms

/Power

/Watt]

196 www.eaton.com

Page 197: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Threshold Alarm 1 – 40000000 kW 10000 kW [System Alarms

/Power

/Watt]t-Delay Tripping Delay 0 – 60 min 0 min [System Alarms

/Power

/Watt]Alarm Threshold Inactive,

Active

Inactive [System Alarms

/Power

/VAr]Threshold Alarm 1 – 40000000 kVAr 10000 kVAr [System Alarms

/Power

/VAr]t-Delay Tripping Delay 0 – 60 min 0 min [System Alarms

/Power

/VAr]Alarm Threshold Inactive,

Active

Inactive [System Alarms

/Power

/VA]Threshold Alarm 1 – 40000000 kVA 10000 kVA [System Alarms

/Power

/VA]t-Delay Tripping Delay 0 – 60 min 0 min [System Alarms

/Power

/VA]Alarm Threshold Inactive,

Active

Inactive [System Alarms

/Demand

/Power Demand

/Watt Demand]

www.eaton.com 197

Page 198: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Threshold Alarm 1 – 40000000 kW 10000 kW [System Alarms

/Demand

/Power Demand

/Watt Demand]t-Delay Tripping Delay 0 – 60 min 0 min [System Alarms

/Demand

/Power Demand

/Watt Demand]Alarm Threshold Inactive,

Active

Inactive [System Alarms

/Demand

/Power Demand

/VAr Demand]Threshold Alarm 1 – 40000000 kVAr 20000 kVAr [System Alarms

/Demand

/Power Demand

/VAr Demand]t-Delay Tripping Delay 0 – 60 min 0 min [System Alarms

/Demand

/Power Demand

/VAr Demand]Alarm Threshold Inactive,

Active

Inactive [System Alarms

/Demand

/Power Demand

/VA Demand]Threshold Alarm 1 – 40000000 kVA 20000 kVA [System Alarms

/Demand

/Power Demand

/VA Demand]

198 www.eaton.com

Page 199: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

t-Delay Tripping Delay 0 – 60 min 0 min [System Alarms

/Demand

/Power Demand

/VA Demand]Alarm Threshold Inactive,

Active

Inactive [System Alarms

/Demand

/Current Demand]Threshold Alarm 10 – 500000 A 500 A [System Alarms

/Demand

/Current Demand]t-Delay Tripping Delay 0 – 60 min 0 min [System Alarms

/Demand

/Current Demand]Alarm Threshold Inactive,

Active

Inactive [System Alarms

/THD

/I THD]Threshold Alarm 1 – 500000 A 500 A [System Alarms

/THD

/I THD]t-Delay Tripping Delay 0 – 3600 s 0 s [System Alarms

/THD

/I THD]Alarm Threshold Inactive,

Active

Inactive [System Alarms

/THD

/U THD]Threshold Alarm 1 – 500000 V 10000 V [System Alarms

/THD

/U THD]t-Delay Tripping Delay 0 – 3600 s 0 s [System Alarms

/THD

/U THD]

www.eaton.com 199

Page 200: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

States of the Inputs of the Demand Management

Name Description Assignment Via

ExBlo-I Module Input State: External Blocking [System Alarms

/General Settings]

System Alarm Signals (States of the Outputs)

Name Description

-.- No assignmentSystem Alarms.Active Signal: ActiveSystem Alarms.ExBlo Signal: External BlockingSystem Alarms.Alarm Watt Power Signal: Alarm WATTS peakSystem Alarms.Alarm VAr Power Signal: Alarm VArs peakSystem Alarms.Alarm VA Power Signal: Alarm VAs peakSystem Alarms.Alarm Watt Demand Signal: Alarm WATTS demand valueSystem Alarms.Alarm VAr Demand Signal: Alarm VARs demand valueSystem Alarms.Alarm VA Demand Signal: Alarm VAs demand valueSystem Alarms.Alarm Current Demand Signal: Alarm Current demand valueSystem Alarms.Alarm I THD Signal: Alarm Total Harmonic Distortion CurrentSystem Alarms.Alarm V THD Signal: Alarm Total Harmonic Distortion VoltageSystem Alarms.Trip Watt Power Signal: Trip WATTS peakSystem Alarms.Trip VAr Power Signal: Trip VArs peakSystem Alarms.Trip VA Power Signal: Trip VAs peakSystem Alarms.Trip Watt Demand Signal: Trip WATTS demand valueSystem Alarms.Trip VAr Demand Signal: Trip VARs demand valueSystem Alarms.Trip VA Demand Signal: Trip VAs demand valueSystem Alarms.Trip Current Demand Signal: Trip Current demand valueSystem Alarms.Trip I THD Signal: Trip Total Harmonic Distortion CurrentSystem Alarms.Trip V THD Signal: Trip Total Harmonic Distortion Voltage

200 www.eaton.com

Page 201: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

ResetsCollective Acknowledgments for Latched Signals:

Collective Acknowledgments

LEDs Relay Outputs SCADA Pending Trip Command

LEDs+Relay Outputs+

SCADA+Pending

Trip Command

Via PowerPort-E or at the panel all...can be acknowledged.

At the panel, the [Operation\

Acknowledge] menu can directly be

accessed via the »C« key.

All LEDs at once:

Where? [Operation\

Acknowledge]

All Relay Outputs at once:

Where? [Operation\

Acknowledge]

All SCADA signals at once:

Where? [Operation\

Acknowledge]

All pending trip commands at

once:

Where? [Operation\

Acknowledge]

All at once:

Where? [Operation\

Acknowledge]

External Acknowledg-ment: Via a signal from the assignment list (e.g.: a digital Input) all... can be acknowledged.

All LEDs at once:

Where?Within the

Ex Acknowledge menu.

All Relay Outputs at once:

Where?Within the

Ex Acknowledge menu.

All SCADA signals at once:

Where?Within the

Ex Acknowledge menu.

All Pending Trip commands at once:

Where?Within the

Ex Acknowledge menu.

All at once:

Where?Within the

Ex Acknowledge menu.

Options for Individual Acknowledgments for Latched Signals:

Individual Acknowledgment

LEDs Relay Output Pending Trip Command

Via a signal from the assignment list (e.g.: a digital Input), a single... can be acknowledged.

Single LED:

Where? Within the Configuration menu

of this single LED.

Relay Output:

Where? Within the Configuration menu

of this single Relay Output.

Pending Trip Command.

Where?Within the module

TripControl

If the User is within the parameter setting mode, the User cannot acknowledge.

In case of a fault during parameter setting via the operating panel, the User must first leave the parameter mode by pressing either the push-buttons »C« or »OK« before accessing the »Acknowledgements« menu via the push-button.

www.eaton.com 201

Page 202: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Manual Acknowledgment

• Press the »C« button on the panel.• Select the item to be acknowledged via the softkeys:

• Relay Outputs;• LEDs;• SCADA;• A trip command; or• All the above mentioned items at once.

• Press the Softkey with the »Wrench-Symbol«.• Enter the password.

Manual Acknowledgment Via PowerPort-E

• If PowerPort-E is not running, please start the application.

• If device data have not been downloaded recently, select »Receive Data From The Device« from the »Device« menu.

• Double click on the »Operation« icon in the navigation tree.

• Double click on the »Acknowledgment« icon within the operation menu.

• Double click the entry within the pop-up that is to be acknowledged.

• Press the »Execute immediately« button.

• Enter the password.

External AcknowledgmentsWithin the [Ex Acknowledge] menu, the User can assign a signal (e.g.: the state of a digital input) from the assignment list that:

• Acknowledges all (acknowledgeable) LEDs at once;• Acknowledges all (acknowledgeable) Output Relays at once; or• Acknowledges all (acknowledgeable) SCADA signals at once.

Within the [Protection Para\Global Prot Para\TripControl] menu, the User can assign a signal that acknowledges a pending trip command.

202 www.eaton.com

1..n, Assignment List

Ack LED

1..n, Assignment List

Ack RO

1..n, Assignment List

Ack Comm

Ex Acknowledge.Ack LED

Ex Acknowledge.Ack RO

Ex Acknowledge.Ack Comm

Page 203: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

For details, please refer to the Trip Control section.

External Acknowledge Via PowerPort-E• If PowerPort-E is not running, please start the application.

• If device data have not been downloaded recently, select »Receive Data From The Device« from the »Device« menu.

• Double click on the »Device Parameter« icon in the navigation tree.

• Double click on the »Ex Acknowledge« icon within the operation menu.

• In the working window, the User can now assign each signal that resets all acknowledgeable LEDs, a signal that resets all Relay Outputs, a signal that resets the SCADA signals respectively, and a signal that acknowledges a pending trip command.

External LED - Acknowledgment SignalsThe following signals can be used for external acknowledgment of latched LEDs.

Name Description

-.- No assignmentDI-8P X1.DI 1 Signal: Digital InputDI-8P X1.DI 2 Signal: Digital InputDI-8P X1.DI 3 Signal: Digital InputDI-8P X1.DI 4 Signal: Digital InputDI-8P X1.DI 5 Signal: Digital InputDI-8P X1.DI 6 Signal: Digital InputDI-8P X1.DI 7 Signal: Digital InputDI-8P X1.DI 8 Signal: Digital InputModbus.Comm Cmd 1 Communication CommandModbus.Comm Cmd 2 Communication CommandModbus.Comm Cmd 3 Communication CommandModbus.Comm Cmd 4 Communication CommandModbus.Comm Cmd 5 Communication CommandModbus.Comm Cmd 6 Communication CommandModbus.Comm Cmd 7 Communication CommandModbus.Comm Cmd 8 Communication CommandModbus.Comm Cmd 9 Communication CommandModbus.Comm Cmd 10 Communication CommandModbus.Comm Cmd 11 Communication CommandModbus.Comm Cmd 12 Communication Command

www.eaton.com 203

Page 204: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Modbus.Comm Cmd 13 Communication CommandModbus.Comm Cmd 14 Communication CommandModbus.Comm Cmd 15 Communication CommandModbus.Comm Cmd 16 Communication Command

Manual ResetsIn the »Operation/Reset« menu, the User can:

• Reset counters;• Delete records (e.g.: disturbance records); and• Reset special things (like statistics, thermal replica, etc.).

The description of the reset commands can be found within the corresponding modules.

Manual Resets Via PowerPort-E

• If PowerPort-E is not running, please start the application.

• If device data have not been downloaded recently, click »Receive Data From The Device« in the »Device« menu.

• Double click the »Operation« icon in the navigation tree.

• Double click the »Reset icon« within the operation menu.

• Double click the entry within the pop-up that is to be reset or deleted.

The description of the reset commands can be found within the corresponding modules.

204 www.eaton.com

Page 205: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Status DisplayIn the status display within the »Operation« menu, the present state of all signals can be viewed. This means the User is able to see if the individual signals are active or inactive at that moment. The User can see all signals sorted by protective elements/modules.

State of the Module Input / Signal Is ... Is Shown at the Panel as ...

false / »0«

true / »1«

Status Display via PowerPort E• If PowerPort E is not running, please start the application.

• If the device data have not been downloaded recently, select »Receive Data From The Device« from »Device« menu.

• Double click on the »Operation« icon in the navigation tree.

• Double click on the »Status Display« icon within the operational data.

• Double click on a subfolder (e.g. Prot) in order to see e.g. the states of the general alarms.

To have the status display updated in a cyclic manner, select »Automatic Up-Date« in the »VIEW« menu.

State of the Module Input / Signal Is ... Is Shown in PowerPort-E as ...

false / »0« 0true / »1« 1

No connection to the device ?

www.eaton.com 205

Page 206: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Operating Panel (HMI)HMI

Special Parameters of the PanelThe »Device Parameter/HMI« menu is used to define the contrast of the display, the maximum admissible edit time, and the menu language (after expiration, all unsaved parameter changes will be rejected).

Direct Commands of the Panel

Parameter Description Setting Range Default Menu Path

Contrast Contrast 30 - 60 50 [Device Para

/HMI]

Global Protection Parameters of the Panel

Parameter Description Setting Range Default Menu Path

t-max Edit If no other key(s) is pressed at the panel, after expiration of this time, all cached (changed) parameters are canceled

20 – 3600 s 180 s [Device Para

/HMI]

206 www.eaton.com

Page 207: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

RecordersDisturbance Recorder

Disturb rec

The disturbance recorder works with 32 samples per cycle. It can be started by one of eight start events (selection from the »Assignment list«/OR-Logic).

The disturbance record contains the measuring values including the pre-trigger time. By means of PowerPort-E/Quality Manager (option), the oscillographic curves of the analog (current, voltage) and digital channels/traces can be shown and evaluated in a graphical form.

The disturbance recorder has a storage capacity of 120 s (duration). The amount of records depends on the file size of each record.

The disturbance recorder can be configured in the»Device Parameter/Recorder/Disturb rec« menu.

Determine the maximum recording time to register a disturbance event. The maximum total length of a recording is 10 s (including pre-trigger and post-trigger time).

To trigger the disturbance recorder, up to eight signals can be selected from the »Assignment list«. The trigger events are OR-linked. If a disturbance record is written, a new disturbance record cannot be triggered until all trigger signals, which have triggered the previous disturbance record, are gone.

Recording is only done for the time the assigned event exists (event controlled), plus the time for the pre- and post-trigger, but not longer than 10 s. The time for the pre- and post-trigger is to be entered as percent of the maximum file size.

The post-trigger time will be up to the "Post-trigger time" depending on the duration of the trigger signal. The post-trigger will be the remaining time of the "Max file size" but, at maximum, the "Post-trigger time".

Example

The disturbance recorder is started by the general activation facility. After the fault has been cleared (plus follow-up time), the recording process is stopped (but after 10 s at the latest).

The parameter »Auto Delete« defines how the device will react if a location to which to save the disturbance record is not available. In case »Auto Delete« is »Active«, the first recorded disturbance will be overwritten according to the FIFO principle. If the parameter is set to »Inactive«, recording of the disturbance events will be stopped until the storage location is manually released.

www.eaton.com 207

Page 208: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

208 www.eaton.com

Start: 1Trigger

Start: 2Trigger

Start: 3Trigger

Start: 4Trigger

Start: 5Trigger

Start: 6Trigger

Start: 7Trigger

Start: 8Trigger

Man. Trigger

RecordingOR

OR

Page 209: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 209

Start 1

t

t

0

1

0

1

300 ms

1335 ms

Pre-trigger time

t

0

1365 ms

Post-trigger time

t

0

12000 ms

t-rec

t

0

12000 ms

Max file size

Start 1 = Prot.Pickup

Start 2 = -.-

Start 3 = -.-

Start 4 = -.-

Start 5 = -.-

Start 6 = -.-

Start 7 = -.-

Start 8 = -.-

Post-trigger time = 25%

Pre-trigger time = 15%

Max file size = 2s

Auto overwriting = Active

t-rec = Max file size

Page 210: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

210 www.eaton.com

Start 1

t

t

0

1

0

1

300 ms

200 ms

Pre-trigger time

t

0

1500 ms

Post-trigger time

t

0

11000 ms

t-rec

t-rec < Max file size

t

0

12000 ms

Max file size

Start 1 = Prot.Trip

Start 2 = -.-

Start 3 = -.-

Start 4 = -.-

Start 5 = -.-

Start 6 = -.-

Start 7 = -.-

Start 8 = -.-

Post-trigger time = 25%

Pre-trigger time = 15%

Max file size = 2s

Auto overwriting = Active

Page 211: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Read Out of Disturbance Records

Within the »Operation/Disturb rec« menu, the User can:

• Detect the accumulated disturbance records.

Within the »Operation/Recorders/Man Trigger« menu, the User can trigger the disturbance recorder manually.

To Read Out the Disturbance Recorder with PowerPort-E

• If PowerPort-E is not running, please start the application.

• If the device data have not been loaded, click »Receive Data From The Device« in the »Device« menu.

• Double click the »Operation« icon in the navigation tree.

• Double click the »Recorders« icon in the navigation tree.

• Double click the »Disturb rec« icon.

• In the window, the disturbance records are shown in tabular form.

• A pop-up will appear by double clicking on a disturbance record. Choose a folder where the disturbance record is to be saved.

• The User can analyze the disturbance records by means of the optionally available Quality Manager by clicking on »Yes« when asked “Shall the received disturbance record be opened by the Quality Manager?"

Deleting Disturbance Records

Within the »Operation/Disturb rec« menu, the User can:

• Delete disturbance records;

• Choose the disturbance record that is to be deleted via »SOFTKEY« »up« and »SOFTKEY« »down«;

• Call up the detailed view of the disturbance record via »SOFTKEY« »right«;

• Confirm by pressing »SOFTKEY« »delete«;

• Enter the User password followed by pressing the »OK« key;

• Choose whether only the current or all disturbance records should be deleted; and

• Confirm by pressing »SOFTKEY« »OK«.

www.eaton.com 211

Page 212: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Deleting Disturbance Records Via PowerPort-E

• If PowerPort-E is not running, please start the application.

• If the device data have not been loaded, click »Receive Data From The Device« in the »Device« menu.

• Double click the »Operation« icon in the navigation tree.

• Double click the »Recorders« icon in the navigation tree.

• Double click the »Disturb rec« icon.

• In the window, the disturbance records are shown in tabular form.

• In order to delete a disturbance record, double click on

(the red x) in front of the disturbance record and confirm.

Direct Commands of the Disturbance Recorder Module

Parameter Description Setting Range Default Menu Path

Man. Trigger Manual Trigger False,

True

False [Operation

/Recorders

/Man. Trigger]Res all rec Reset all records Inactive,

Active

Inactive [Operation

/Reset]

Global Protection Parameters of the Disturbance Recorder Module

Parameter Description Setting Range Default Menu Path

Start: 1 Start recording if the assigned signal is true. 1..n, Assignment List Prot.Pickup [Device Para

/Recorders

/Disturb rec]Start: 2 Start recording if the assigned signal is true. 1..n, Assignment List -.- [Device Para

/Recorders

/Disturb rec]Start: 3 Start recording if the assigned signal is true. 1..n, Assignment List -.- [Device Para

/Recorders

/Disturb rec]

212 www.eaton.com

Page 213: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Start: 4 Start recording if the assigned signal is true. 1..n, Assignment List -.- [Device Para

/Recorders

/Disturb rec]Start: 5 Start recording if the assigned signal is true. 1..n, Assignment List -.- [Device Para

/Recorders

/Disturb rec]Start: 6 Start recording if the assigned signal is true. 1..n, Assignment List -.- [Device Para

/Recorders

/Disturb rec]Start: 7 Start recording if the assigned signal is true. 1..n, Assignment List -.- [Device Para

/Recorders

/Disturb rec]Start: 8 Start recording if the assigned signal is true. 1..n, Assignment List -.- [Device Para

/Recorders

/Disturb rec]Auto overwriting

If there is no more free memory capacity left, the oldest file will be overwritten.

Inactive,

Active

Active [Device Para

/Recorders

/Disturb rec]Post-trigger time

The post trigger time is settable up to a maximum of 50% of the Maximum file size setting. The post-trigger will be the remaining time of the "Max file size" but at maximum "Post-trigger time"

0 - 50% 20% [Device Para

/Recorders

/Disturb rec]Pre-trigger time The pre trigger time is settable up to a

maximum of 50% of the maximum file size setting.

0 - 50% 20% [Device Para

/Recorders

/Disturb rec]Max file size The maximum storage capacity per record

is 10 seconds, including pre-trigger and post-trigger time. The disturbance recorder has a total storage capacity of 120 seconds.

0.1 – 10.0 s 2 s [Device Para

/Recorders

/Disturb rec]

www.eaton.com 213

Page 214: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Disturbance Recorder Module Input States

Name Description Assignment Via

Start1-I State of the module input: Trigger event / start recording if:

[Device Para

/Recorders

/Disturb rec]Start2-I State of the module input: Trigger event /

start recording if:[Device Para

/Recorders

/Disturb rec]Start3-I State of the module input: Trigger event /

start recording if:[Device Para

/Recorders

/Disturb rec]Start4-I State of the module input: Trigger event /

start recording if:[Device Para

/Recorders

/Disturb rec]Start5-I State of the module input: Trigger event /

start recording if:[Device Para

/Recorders

/Disturb rec]Start6-I State of the module input: Trigger event /

start recording if:[Device Para

/Recorders

/Disturb rec]Start7-I State of the module input: Trigger event /

start recording if:[Device Para

/Recorders

/Disturb rec]Start8-I State of the module input: Trigger event /

start recording if:[Device Para

/Recorders

/Disturb rec]

Disturbance Recorder Module Signals

Name Description

Recording Signal: RecordingMemory full Signal: Memory FullClear fail Signal: Clear Failure in MemoryRes all rec Signal: All records deleted

214 www.eaton.com

Page 215: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Res record Signal: Delete Record Man. Trigger Signal: Manual Trigger

Special Parameters of the Disturbance Recorder

Value Description Default Size Menu Path

Rec state Recording state Ready Ready,

Recording,

Writing file,

Trigger Blo

[Operation

/Status display

/Disturb rec]

Error code Error code OK OK,

Write err,

Clear fail,

Calculation err,

File not found,

Auto overwriting off

[Operation

/Status display

/Disturb rec]

Fault RecorderFault rec

The fault recorder can be started by one of eight start events (selection from the »Assignment list«/OR-Logic). It can register up to 20 faults. The last of the recorded faults is stored in a fail-safe manner.

If one of the assigned trigger events becomes true, the fault recorder will be started. When a trigger event happens, each fault is saved including the module and name, fault number, number of grid faults and record number at that time. For each of the faults, the measuring values (at the time when the trigger event became true) can be viewed.

Up to eight signals to trigger the fault recorder can be selected from the »Assignment list«. The trigger events are OR-linked.

The parameter »Auto Delete« defines how the device will react if there is no saving place available. In case »Auto Delete« is »Active«, the first recorded fault will be overwritten according to the FIFO principle. If the parameter is set to »Inactive«, recording of the fault events will be stopped until the storage location is released manually.

www.eaton.com 215

Page 216: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Read Out the Fault Recorder

The measured values at the time of tripping are saved (fail-safe) within the fault recorder. If there is no more memory free, the oldest record will be overwritten (FIFO).

In order to read out a failure record:

• Call up the main menu;

• Call up the sub-menu »Operation/Recorders/Fault rec.«;

• Select a fault record; and

• Analyze the corresponding measured values.

To Read Out the Fault Recorder Via PowerPort-E

• If PowerPort-E is not running, please start the application.

• If the device data have not been loaded, click »Receive Data From The Device« in the »Device« menu.

• Double click the »Operation« icon in the navigation tree.

216 www.eaton.com

Start: 1Trigger

Start: 2Trigger

Start: 3Trigger

Start: 4Trigger

Start: 5Trigger

Start: 6Trigger

Start: 7Trigger

Start: 8Trigger

Man. Trigger

RecordingOR

OR

Page 217: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

• Double click the »Fault Rec« icon within the »Operation/Recorders« tree.

• In the window, the fault recordings are shown in tabular form.

• In order to receive more detailed information on a fault, click the »Plus Sign« in front of the fault number.

Via the print menu, the User can export the data into a file. Please proceed as follows.

• Call up the data as described above.

• Call up the »File/Print« menu.

• Choose »Print Actual Working Window« within the pop-up.

• Press the »Print« button.

• Press the »Export to File« button.

• Enter a file name.

• Choose a location where to save the file.

• Confirm the »Save« button.

Direct Commands of the Fault Recorder Module

Parameter Description Setting Range Default Menu Path

Res all rec Reset all records Inactive,

Active

Inactive [Operation

/Reset]Man. Trigger Manual Trigger False,

True

False [Operation

/Recorders

/Man. Trigger]

Global Protection Parameters of the Fault Recorder Module

Parameter Description Setting Range Default Menu Path

Start: 1 Start recording if the assigned signal is true. 1..n, Assignment List Prot.Trip [Device Para

/Recorders

/Fault rec]

www.eaton.com 217

Page 218: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Start: 2 Start recording if the assigned signal is true. 1..n, Assignment List -.- [Device Para

/Recorders

/Fault rec]Start: 3 Start recording if the assigned signal is true. 1..n, Assignment List -.- [Device Para

/Recorders

/Fault rec]Start: 4 Start recording if the assigned signal is true. 1..n, Assignment List -.- [Device Para

/Recorders

/Fault rec]Start: 5 Start recording if the assigned signal is true. 1..n, Assignment List -.- [Device Para

/Recorders

/Fault rec]Start: 6 Start recording if the assigned signal is true. 1..n, Assignment List -.- [Device Para

/Recorders

/Fault rec]Start: 7 Start recording if the assigned signal is true. 1..n, Assignment List -.- [Device Para

/Recorders

/Fault rec]Start: 8 Start recording if the assigned signal is true. 1..n, Assignment List -.- [Device Para

/Recorders

/Fault rec]Auto overwriting

If there is no more free memory capacity left, the oldest file will be overwritten.

Inactive,

Active

Active [Device Para

/Recorders

/Fault rec]

Fault Recorder Module Input States

Name Description Assignment Via

Start1-I State of the module input: Trigger event / start recording if:

[Device Para

/Recorders

/Fault rec]

218 www.eaton.com

Page 219: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

Start2-I State of the module input: Trigger event / start recording if:

[Device Para

/Recorders

/Fault rec]Start3-I State of the module input: Trigger event /

start recording if:[Device Para

/Recorders

/Fault rec]Start4-I State of the module input: Trigger event /

start recording if:[Device Para

/Recorders

/Fault rec]Start5-I State of the module input: Trigger event /

start recording if:[Device Para

/Recorders

/Fault rec]Start6-I State of the module input: Trigger event /

start recording if:[Device Para

/Recorders

/Fault rec]Start7-I State of the module input: Trigger event /

start recording if:[Device Para

/Recorders

/Fault rec]Start8-I State of the module input: Trigger event /

start recording if:[Device Para

/Recorders

/Fault rec]

Fault Recorder Module Signals

Name Description

Res record Signal: Delete Record Man. Trigger Signal: Manual Trigger

Fault Recorder Trigger Functions

These events (Pickups, Trips, Digital Inputs, Relay Output states) will start the fault recorder.

www.eaton.com 219

Page 220: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Event RecorderEvent rec

The event recorder can register up to 300 events and the last 50 (minimum) saved events are stored in non-volatile memory, and therefore retailed when power is lost to the unit. The following information is provided for any of the events.

Events are logged as follows:

Record No. Fault No. No of grid faults Date of Record Module Name State

Sequential Number Number of the ongoing fault.

This counter will be incremented by each General Pickup (Prot.Pickup).

A grid fault No. can have several Fault Nos.

This counter will be incremented by each General Pickup.(Exception AR: this applies only to devices that offer auto reclosing).

Time stamp What has changed? Changed Value

There are three different classes of events.

• Alternation of binary states are shown as:• 0->1 if the signal changes physically from »0« to »1«.• 1->0 if the signal changes physically from »1« to »0«.

• Counters increment is shown as:• Old Counter state -> New Counter state (e.g.: 3->4)

• Alternation of multiple states are shown as:• Old state -> New state (e.g.: 0->2)

Read Out the Event Recorder

• Call up the »main menu«.•

• Call up the sub-menu »Operation/Recorders/Event rec«.

• Select an event.

To Read Out the Event Recorder via PowerPort-E

• If PowerPort-E is not running, please start the application.

• If the device data have not been loaded, click »Receive Data From The Device« in the »Device menu.

• Double click the »Operation« icon in the navigation tree.

• Double click the »Event Rec« icon within the »Operation/Recorders« menu.

220 www.eaton.com

Page 221: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

• In the window, the events are shown in tabular form.

To have the event recorder updated in a cyclic manner, select »Automatic Up-Date« in the »View« menu.

PowerPort-E is able to record more events than the device itself, if the window of the event recorder is opened and »Automatic Up-Date« is set to active.

Via the print menu, the User can export the data into a file. Please proceed as follows.

• Call up the data as described above.

• Call up the »File/Print« menu.

• Choose »Print Actual Working Window« within the pop-up.

• Press the »Print« button.

• Press the »Export to File« button.

• Enter a file name.

• Choose a location where to save the file.

• Confirm the »Save« button.

Direct Commands of the Event Recorder Module

Parameter Description Setting Range Default Menu Path

Res all rec Reset all records Inactive,

Active

Inactive [Operation

/Reset]

Event Recorder Module Signals

Name Description

Res all rec Signal: All records deleted

Trend RecorderAvailable Elements:Trend rec

Functional Description

The Trend Data are data points stored by the Trend Recorder on the relay device over fixed intervals of time, and can be downloaded from the device using PowerPort-E. A Trend Record is viewable using the Quality

www.eaton.com 221

Page 222: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Monitor software by selecting files saved by PowerPort-E with a file extension of “.ErTr”. The list of available trend recorder data is viewable by selecting [Operation/ Recorders/Trend Recorder] on the front panel of the relay.

When viewed within the Quality Manager, the trend record will show the observed values (up to 10) that the User has specified. The available values are dependent on the ordered protective device.

Managing Trend Records

To download information from the Trend Recorder, select [Operation/Recorder/Trend Rec] from the menu tree. The User will find three options within the Trend Recorder window that will allow the User to:

• Receive Trend Records,• Refresh the Trend Recorder, and • Delete Trend Records.

Selecting the »Receive Trend Record« button will download data from the relay to the User's PC. By selecting the »Refresh Trend Recorder«”, PowerPort-E updates the list of the Trend Recorder. The »Delete Trend Recorder« function will clear all trend data from the relay, leaving the data files on the User's PC.

To view data using the Quality Manager, first the User must open the desired “.ErTr” file to be viewed from a folder location previously designated by the User. Once the “.ErTr” file is open, the User will see the “Analog Channels” that are monitored by the Trend Recorder. By clicking on the “Analog Channels”, all monitored parameters are listed. To view a channel, the User must click on the left mouse key, then drag and drop the channel onto the right side of the Quality Manager screen. The channel is then listed under the »Displayed Channels«.

To remove a channel from view, the User must select the Trend Data to be removed in the »Displayed Channels« menu tree, then click on the right mouse button to bring up the menu options. Here, the User will find the »Remove« menu option that, when selected, will remove the trend data.

Configuring the Trend Recorder

The Trend Recorder is to be configured within [Device Para/Recorders/Trend Recorder] menu.

The User has to set the time interval. This defines the distance between two measuring points.

The User can select up to ten values that will be recorded.

Selection List for Trending

Name Description

- No assignmentIA RMS Measured value: Phase current (RMS)IB RMS Measured value: Phase current (RMS)IC RMS Measured value: Phase current (RMS)IX meas RMS Measured value (measured): IX (RMS)IR calc RMS Measured value (calculated): IR (RMS)I0 Fund. Measured value (calculated): Zero current (Fundamental)I1 Fund. Measured value (calculated): Positive phase sequence current

(Fundamental)

222 www.eaton.com

Page 223: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

I2 Fund. Measured value (calculated): Unbalanced load current (Fundamental)

IA avg RMS IA average value (RMS)IB avg RMS IB average value (RMS)IC avg RMS IC average value (RMS)VA RMS Measured value: Phase-to-neutral voltage (RMS)VB RMS Measured value: Phase-to-neutral voltage (RMS)VC RMS Measured value: Phase-to-neutral voltage (RMS)VX meas RMS Measured value (measured): VG measured (RMS)VAB RMS Measured value: Phase-to-phase voltage (RMS)VBC RMS Measured value: Phase-to-phase voltage (RMS)VCA RMS Measured value: Phase-to-phase voltage (RMS)V0 Fund. Measured value (calculated): Symmetrical components Zero

voltage(Fundamental)V1 Fund. Measured value (calculated): Symmetrical components positive

phase sequence voltage(Fundamental)V2 Fund. Measured value (calculated): Symmetrical components negative

phase sequence voltage(Fundamental)VA avg RMS VA average value (RMS)VB avg RMS VB average value (RMS)VC avg RMS VC average value (RMS)VAB avg RMS VAB average value (RMS)VBC avg RMS VBC average value (RMS)VCA avg RMS VCA average value (RMS)f Measured Value: FrequencyDisp PF Measured Value (Calculated): 55D - Displacement Power Factor

Power factorApt PF Measured Value (Calculated): 55A - Apparent Power FactorIA THD Measured Value (Calculated): IA Total Harmonic Current IB THD Measured Value (Calculated): IB Total Harmonic Current IC THD Measured Value (Calculated): IC Total Harmonic Current VA THD Measured value (calculated): VA Total Harmonic Distortion VB THD VB THD VC THD VC THD VAB THD Measured value (calculated): VAB Total Harmonic Distortion VBC THD Measured value (calculated): VBC Total Harmonic Distortion VCA THD Measured value (calculated): VCA Total Harmonic Distortion

www.eaton.com 223

Page 224: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Global Protection Parameters of the Trend Recorder

Parameter Description Setting Range Default Menu Path

Resolution Resolution (recording frequency) 60 min,

30 min,

15 min,

10 min,

5 min

15 min [Device Para

/Recorders

/Trend rec]

Observed Value1

Observed Value1 1..n, TrendRecList IA RMS [Device Para

/Recorders

/Trend rec]Observed Value2

Observed Value2 1..n, TrendRecList IB RMS [Device Para

/Recorders

/Trend rec]Observed Value3

Observed Value3 1..n, TrendRecList IC RMS [Device Para

/Recorders

/Trend rec]Observed Value4

Observed Value4 1..n, TrendRecList IX meas RMS [Device Para

/Recorders

/Trend rec]Observed Value5

Observed Value5 1..n, TrendRecList VA RMS [Device Para

/Recorders

/Trend rec]Observed Value6

Observed Value6 1..n, TrendRecList VB RMS [Device Para

/Recorders

/Trend rec]Observed Value7

Observed Value7 1..n, TrendRecList VC RMS [Device Para

/Recorders

/Trend rec]Observed Value8

Observed Value8 1..n, TrendRecList VX meas RMS [Device Para

/Recorders

/Trend rec]

224 www.eaton.com

Page 225: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Observed Value9

Observed Value9 1..n, TrendRecList - [Device Para

/Recorders

/Trend rec]Observed Value10

Observed Value10 1..n, TrendRecList - [Device Para

/Recorders

/Trend rec]

Trend Recorder Module Signals (Output States)

Name Description

Hand Reset Hand Reset

Direct Commands of the Trend Recorder

Parameter Description Setting Range Default Menu Path

Reset Delete all entries Inactive,

Active

Inactive [Operation

/Reset]

www.eaton.com 225

Page 226: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Communication ProtocolsModbus®

Modbus

Modbus® Protocol Configuration

The time-controlled Modbus® protocol is based on the master-slave working principle. This means that the substation control and protection system sends an inquiry or instruction to a certain device (slave address) that will then be answered or carried out accordingly. If the inquiry/instruction cannot be answered/carried out (e.g.: because of an invalid slave address), a failure message is returned to the master.

The master (substation control and protection system) can query information from the device, such as:

• Type of unit version;• Measuring values/statistical measured values;• Switch operating position (in preparation);• State of device;• Time and date;• State of the device’s digital inputs; and• Protection-/state pickups.

The master (control system) can give commands/instructions to the device, such as:

• Control of switchgear (where applicable, i.e.: each according to the applied device version);• Change-over of parameter set;• Reset and acknowledgment of pickups/signals;• Adjustment of the date and time; and• Control of pickup relays.

For detailed information on data point lists and error handling, please refer to the Modbus® documentation.

To allow configuration of the devices for Modbus® connection, some default values of the control system must be available.

Device Planning Parameters of the Modbus

Parameter Description Options Default Menu Path

Mode Mode RTU,

TCP

RTU [Device Plan-ning]

Modbus RTU

Part 1: Configuration of the Devices

Call up »Device parameter/Modbus« and set the following communication parameters:

• Slave address, to allow clear identification of the device; and

• Baud rate.

226 www.eaton.com

Page 227: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Also, select the RS485 interface-related parameters such as:

• Number of data bits;

• One of the following supported communication variants:• Number of data bits,• Even,• Odd,• Parity or no parity, or• Number of stop bits;

• »t-timeout«: communication errors are only identified after expiration of a supervision time »t-timeout«; and

• Response time (defining the period within which an inquiry from the master has to be answered).

Part 2: Hardware Connection

• For hardware connection to the control system, there is an RS485 interface at the rear side of the device (RS485, fiber optic or terminals).

• Connect the bus and the device (wiring).

• Up to 32 devices can be connected to the bus (point to point connection/spurs).

• Connect a terminating resistor to the bus.

Error Handling - Hardware Errors

Information on physical communication errors, such as:

• Baud rate error and• Parity error;

can be obtained from the event recorder.

Error Handling – Errors on Protocol Level

If, for example, an invalid memory address is inquired, error codes will be returned by the device that need to be interpreted.

Modbus TCP

Establishing a connection via TCP/IP to the device is only possible if the device is equipped with an Ethernet Interface (RJ45).

Contact your IT administrator in order to establish the network connection.

Part 1: Setting the TCP/IP Parameters

www.eaton.com 227

Page 228: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Call up »Device parameter/TCP/IP« at the HMI (panel) and set the following parameters:

• TCP/IP address;

• Subnetmask; and

• Gateway.

Part 2: Configuration of the Devices

Call up »Device parameter/Modbus« and set the following communication parameters.

• Setting a unit identifier is only necessary if a TCP network should be coupled to a RTU network.

• If a different port than the default port 502 should be used, please proceed as follows:

• Choose “Private” within the TCP-Port-Configuration.

• Set the port number.

• Set the maximum acceptable time out for “no communication”. If this time has expired without any communication, the device concludes a failure has occurred within the master system.

• Allow or disallow the blocking of SCADA commands.

Part 3: Hardware Connection

• There is a RJ45 interface at the rear side of the device for the hardware connection to the control system.

• Establish the connection to the device by means of a proper Ethernet cable.

Direct Commands of the Modbus®

Parameter Description Setting Range Default Menu Path

Res Diagn Cr All Modbus Diagnosis Counters will be reset.

Inactive,

Active

Inactive [Operation

/Reset]

Global Protection Parameters of the Modbus®

Parameter Description Setting Range Default Menu Path

Slave ID Device address (Slave ID) within the bus system. Each device address has to be unique within a bus system.

Only available if:Device Planning = RTU

1 - 247 1 [Device Para

/Modbus]

228 www.eaton.com

Page 229: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Unit ID The Unit Identifier is used for routing. This parameter is to be set, if a Modbus RTU and a Modbus TCP network should be coupled.

Only available if:Device Planning = TCP

1 - 255 255 [Device Para

/Modbus]

TCP Port Config

TCP Port Configuration. This parameter is to be set only if the default Modbus TCP Port should not be used.

Only available if:Device Planning = TCP

Default,

Private

Default [Device Para

/Modbus]

Port Port number

Only available if:Device Planning = TCP And Only available if: TCP Port Config = Private

502 - 65535 502 [Device Para

/Modbus]

t-timeout Within this time the answer has to be received by the Communication system, otherwise the request will be disregarded. In that case, the Communication system detects a communication failure and the Communication System has to send a new request.

Only available if:Device Planning = RTU

0.01 – 10.00 s 1 s [Device Para

/Modbus]

Baud rate Baud rate

Only available if:Device Planning = RTU

1200,

2400,

4800,

9600,

19200,

38400

19200 [Device Para

/Modbus]

Physical Settings

Digit 1: Number of bits. Digit 2: E=even parity, O=odd parity, N=no parity. Digit 3: Number of stop bits. More information on the parity: It is possible that the last data bit is followed by a parity bit which is used for recognition of communication errors. The parity bit ensures that with even parity ("EVEN") always an even number of bits with valence "1" or with odd parity ("ODD") an odd number of "1" valence bits are transmitted. But it is also possible to transmit no parity bits (here the setting is "Parity = None"). More information on the stop-bits: The end of a data byte is terminated by the stop-bits.

Only available if:Device Planning = RTU

8E1,

8O1,

8N1,

8N2

8E1 [Device Para

/Modbus]

www.eaton.com 229

Page 230: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

t-call If there is no request message sent from Communication to the device after expiry of this time, the device concludes a communication failure within the Communication system.

1 – 3600 s 10 s [Device Para

/Modbus]

Comm CmdBlo Activating (allowing)/ Deactivating (disallowing) the blocking of the Communication Commands

Inactive,

Active

Inactive [Device Para

/Modbus]Disable Latching

Disable Latching: If this parameter is active (true), none of the Modbus states will be latched. That means that trip signals wont be latched by Modbus.

Inactive,

Active

Inactive [Device Para

/Modbus]

AllowGap If this parameter is active (True), the User can request a set of modbus register without getting an exception, because of invalid address in the requested array. The invalid addresses have a special value 0xFAFA, but the User is responsible for ignoring invalid addresses. Attention: This special value can be valid, if address is valid.

Inactive,

Active

Inactive [Device Para

/Modbus]

Modbus® Module Signals (Output States)

Some signals (that are active for a short time only) have to be acknowledged separately (e.g.: trip signals) by the communication system.

Name Description

Transmission Signal: Communication ActiveComm Cmd 1 Communication CommandComm Cmd 2 Communication CommandComm Cmd 3 Communication CommandComm Cmd 4 Communication CommandComm Cmd 5 Communication CommandComm Cmd 6 Communication CommandComm Cmd 7 Communication CommandComm Cmd 8 Communication CommandComm Cmd 9 Communication CommandComm Cmd 10 Communication CommandComm Cmd 11 Communication CommandComm Cmd 12 Communication CommandComm Cmd 13 Communication CommandComm Cmd 14 Communication Command

230 www.eaton.com

Page 231: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Comm Cmd 15 Communication CommandComm Cmd 16 Communication Command

Modbus® Module Values

Value Description Default Size Menu Path

NoOfRequestsTotal Total number of requests. Includes requests for other slaves.

0 0 - 9999999999

[Operation

/Count and RevData

/Modbus]NoOfRequestsForMe

Total Number of requests for this slave.

0 0 - 9999999999

[Operation

/Count and RevData

/Modbus]NoOfResponse Total number of requests having

been responded.0 0 -

9999999999[Operation

/Count and RevData

/Modbus]NoOfResponsTimeOverruns

Total number of requests with exceeded response time. Physically corrupted Frame.

0 0 - 9999999999

[Operation

/Count and RevData

/Modbus]NoOfOverrunErros Total Number of Overrun Failures.

Physically corrupted Frame.0 0 -

9999999999[Operation

/Count and RevData

/Modbus]NoOfParityErrors Total number of parity errors.

Physically corrupted Frame.0 0 -

9999999999[Operation

/Count and RevData

/Modbus]NoOfFrameErrors Total Number of Frame Errors.

Physically corrupted Frame.0 0 -

9999999999[Operation

/Count and RevData

/Modbus]NoOfBreaks Number of detected communication

aborts0 0 -

9999999999[Operation

/Count and RevData

/Modbus]NoOfQueryInvalid Total Number of Request errors.

Request could not be interpreted0 0 -

9999999999[Operation

/Count and RevData

/Modbus]

www.eaton.com 231

Page 232: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Value Description Default Size Menu Path

NoOfInternalError Total Number of Internal errors while interpreting the request.

0 0 - 9999999999

[Operation

/Count and RevData

/Modbus]

IEC 61850IEC61850

Introduction

To understand the functioning and mode of operation of a substation in an IEC 61850 automation environment, it is useful to compare the commissioning steps with those of a conventional substation in a Modbus TCP environment. In a conventional substation, the individual Intelligent Electronic Devices (IEDs) communicate in a vertical direction with the higher level control center via Communication. The horizontal communication is exclusively realized by wiring relay output contacts (RO) and digital inputs (DI) together.

In an IEC 61850 environment, communication between the IEDs takes place digitally (via Ethernet) by a service called Generic Object Oriented Substation Event (GOOSE). By means of this service, information about events is submitted between each IED. Therefore each IED has to know about the functional capability of all other connected IEDs.

Each IEC 61850 capable device includes a description of its own functionality and communications skills (IED Capability Description, *.ICD). By means of a Substation Configuration Tool to describe the structure of the substation, assignment of the devices to the primary technique, etc., virtual wiring of the IEDs between each other and with other switch gear of the substation can be achieved. A description of the substation configuration will be generated in the form of a *.SCD file. Finally, this file has to be submitted to each device. Now the IEDs are able to communicate with each other, react to interlockings, and operate switch gear.

232 www.eaton.com

Page 233: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Commissioning steps for a conventional substation with modbus TCP environment:

• Parameter setting of the IEDs;• Ethernet installation;• TCP/IP settings for the IEDs; and• Wiring according to wiring scheme.

Commissioning steps for a substation with IEC 61850 environment:

1. Parameter setting of the IEDsEthernet installationTCP/IP settings for the IEDs

2. IEC 61850 configuration (software wiring)a) Exporting an ICD file from each deviceb) Configuration of the substation

(generating a SCD file)c) Transmit SCD file to each device.

Generation/Export of a Device Specific ICD File

Each Eaton IEC 61850 capable device includes a description of its own functionality and communications skills in the form of an IED Capability Description (*.ICD) file. This file can be exported as follows and be used for the configuration of the substation.

• A change of the devices parameters has an influence on the content of the ICD file.

1. Connect the device with your PC/Notebook.2. Start PowerPort E.3. Click on »Receive data from Device« in the »Device« menu.4. Click on »IEC 61850« in the »Device Para« menu.5. Click on the ICD icon in the IEC 61850 window.6. Select a drive and file name for the ICD file and click "save".7. Repeat the steps 1 to 6 for all connected devices in this IEC 61850 environment.

Substation Configuration,Generation of a Station Configuration Description (SCD) File

The substation configuration (i. e. connection of all logical nodes of protection and control devices) as well as switch gear usually is done with a ”Substation Configuration Tool“. Therefore the ICD files of all connected IEDs in the IEC 61850 environment have to be available. The result of the station wide “software wiring” can be exported in the form of a Station Configuration Description (SCD) file.

www.eaton.com 233

IED1 IED2 IED3

IEC61850Master

Ethernet

Com

mIE

C61

850

GOOSE IEC61850 soft wiring

IED1 IED2 IED3

Modbus-TCPMaster

Ethernet

Com

mM

odbu

sTC

P

Conventional hard wiring

DI RO DI RO DI RO

Page 234: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Suitable Substation Configuration Tools (SCT) are available by the following Companies:

• H&S, Hard- & Software Technologie GmbH & Co. KG, Dortmund (Germany) (www.hstech.de).• Applied Systems Engineering Inc. (www.ase-systems.com)• Kalki Communication Technologies Limited (www.kalkitech.com)

Import of the *.SCD File into the Device

When the substation configuration is completed, the *.SCD file has to be transmitted to all connected devices. This is has to be done as follows.

1. Connect the device with your PC/notebook.2. Start PowerPort E.3. Click on »Receive data from Device« in the »Device« menu.4. Click on »IEC 61850« in the »Device Para« menu.5. Switch the parameter »IEC 61850 Communication« to »OFF« and submit the changed parameter set

into the device.6. Click on the SCD icon in the IEC 61850 window.7. Select the folder where the *.SCD file is stored. Select the *.SCD file and click "Open".8. A password is requested. Enter the same password, which you use for parameter setting of the device.9. Following Step 5, again switch on the IEC Communication and submit the changed parameter set into

the device.10. Repeat Steps 1 through 9 for all devices connected to this IEC 61850 environment.11. If no error message occurs, the configuration has been completed successfully.

• When changing the substation configuration, usually a new *.SCD file has to be generated. This *.SCD file must be transmitted to all devices by means of PowerPort E. If the file is not transmitted to all devices, IEC 61850 malfunctions will be the result.

• If the parameters of the devices are changed after the completion of the substation configuration, changes in the corresponding *.ICD file may result. This, in turn, may make an update of the *.SCD file necessary.

IEC 61850 Virtual Outputs

In addition to the standardized logical node status information, up to 16 free configurable status information items can be assigned to the 16 Virtual Outputs. This can be done in the [Device Para/IEC61850] menu.

Device Planning Parameters of the IEC 61850

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Use [Device Plan-ning]

234 www.eaton.com

Page 235: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Direct Commands of the IEC 61850

Parameter Description Setting Range Default Menu Path

ResetStatistic Reset of all IEC61850 diagnostic counters Inactive,

Active

Inactive [Operation

/Count and RevData

/IEC61850]

Global Protection Parameters of the IEC 61850

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Active,

Inactive

Inactive [Device Para

/IEC61850]VirtualOutput1 Virtual Output. This signal can be assigned

or visualized via the SCD file to other devices within the IEC61850 substation.

1..n, Assignment List -.- [Device Para

/IEC61850]VirtualOutput2 Virtual Output. This signal can be assigned

or visualized via the SCD file to other devices within the IEC61850 substation.

1..n, Assignment List -.- [Device Para

/IEC61850]VirtualOutput3 Virtual Output. This signal can be assigned

or visualized via the SCD file to other devices within the IEC61850 substation.

1..n, Assignment List -.- [Device Para

/IEC61850]VirtualOutput4 Virtual Output. This signal can be assigned

or visualized via the SCD file to other devices within the IEC61850 substation.

1..n, Assignment List -.- [Device Para

/IEC61850]VirtualOutput5 Virtual Output. This signal can be assigned

or visualized via the SCD file to other devices within the IEC61850 substation.

1..n, Assignment List -.- [Device Para

/IEC61850]VirtualOutput6 Virtual Output. This signal can be assigned

or visualized via the SCD file to other devices within the IEC61850 substation.

1..n, Assignment List -.- [Device Para

/IEC61850]VirtualOutput7 Virtual Output. This signal can be assigned

or visualized via the SCD file to other devices within the IEC61850 substation.

1..n, Assignment List -.- [Device Para

/IEC61850]VirtualOutput8 Virtual Output. This signal can be assigned

or visualized via the SCD file to other devices within the IEC61850 substation.

1..n, Assignment List -.- [Device Para

/IEC61850]VirtualOutput9 Virtual Output. This signal can be assigned

or visualized via the SCD file to other devices within the IEC61850 substation.

1..n, Assignment List -.- [Device Para

/IEC61850]VirtualOutput10 Virtual Output. This signal can be assigned

or visualized via the SCD file to other devices within the IEC61850 substation.

1..n, Assignment List -.- [Device Para

/IEC61850]VirtualOutput11 Virtual Output. This signal can be assigned

or visualized via the SCD file to other devices within the IEC61850 substation.

1..n, Assignment List -.- [Device Para

/IEC61850]VirtualOutput12 Virtual Output. This signal can be assigned

or visualized via the SCD file to other devices within the IEC61850 substation.

1..n, Assignment List -.- [Device Para

/IEC61850]

www.eaton.com 235

Page 236: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

VirtualOutput13 Virtual Output. This signal can be assigned or visualized via the SCD file to other devices within the IEC61850 substation.

1..n, Assignment List -.- [Device Para

/IEC61850]VirtualOutput14 Virtual Output. This signal can be assigned

or visualized via the SCD file to other devices within the IEC61850 substation.

1..n, Assignment List -.- [Device Para

/IEC61850]VirtualOutput15 Virtual Output. This signal can be assigned

or visualized via the SCD file to other devices within the IEC61850 substation.

1..n, Assignment List -.- [Device Para

/IEC61850]VirtualOutput16 Virtual Output. This signal can be assigned

or visualized via the SCD file to other devices within the IEC61850 substation.

1..n, Assignment List -.- [Device Para

/IEC61850]

States of the Inputs of the IEC 61850

Name Description Assignment Via

VirtualOutput1-I Module input state: Binary state of the Virtual Output (GGIO)

[Device Para

/IEC61850]VirtualOutput2-I Module input state: Binary state of the

Virtual Output (GGIO)[Device Para

/IEC61850]VirtualOutput3-I Module input state: Binary state of the

Virtual Output (GGIO)[Device Para

/IEC61850]VirtualOutput4-I Module input state: Binary state of the

Virtual Output (GGIO)[Device Para

/IEC61850]VirtualOutput5-I Module input state: Binary state of the

Virtual Output (GGIO)[Device Para

/IEC61850]VirtualOutput6-I Module input state: Binary state of the

Virtual Output (GGIO)[Device Para

/IEC61850]VirtualOutput7-I Module input state: Binary state of the

Virtual Output (GGIO)[Device Para

/IEC61850]VirtualOutput8-I Module input state: Binary state of the

Virtual Output (GGIO)[Device Para

/IEC61850]VirtualOutput9-I Module input state: Binary state of the

Virtual Output (GGIO)[Device Para

/IEC61850]VirtualOutput10-I Module input state: Binary state of the

Virtual Output (GGIO)[Device Para

/IEC61850]VirtualOutput11-I Module input state: Binary state of the

Virtual Output (GGIO)[Device Para

/IEC61850]

236 www.eaton.com

Page 237: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

VirtualOutput12-I Module input state: Binary state of the Virtual Output (GGIO)

[Device Para

/IEC61850]VirtualOutput13-I Module input state: Binary state of the

Virtual Output (GGIO)[Device Para

/IEC61850]VirtualOutput14-I Module input state: Binary state of the

Virtual Output (GGIO)[Device Para

/IEC61850]VirtualOutput15-I Module input state: Binary state of the

Virtual Output (GGIO)[Device Para

/IEC61850]VirtualOutput16-I Module input state: Binary state of the

Virtual Output (GGIO)[Device Para

/IEC61850]

IEC 61850 Module Signals (Output States)

Name Description

VirtualInput1 Signal: Virtual Input (IEC61850 GGIO Ind)VirtualInput2 Signal: Virtual Input (IEC61850 GGIO Ind)VirtualInput3 Signal: Virtual Input (IEC61850 GGIO Ind)VirtualInput4 Signal: Virtual Input (IEC61850 GGIO Ind)VirtualInput5 Signal: Virtual Input (IEC61850 GGIO Ind)VirtualInput6 Signal: Virtual Input (IEC61850 GGIO Ind)VirtualInput7 Signal: Virtual Input (IEC61850 GGIO Ind)VirtualInput8 Signal: Virtual Input (IEC61850 GGIO Ind)VirtualInput9 Signal: Virtual Input (IEC61850 GGIO Ind)VirtualInput10 Signal: Virtual Input (IEC61850 GGIO Ind)VirtualInput11 Signal: Virtual Input (IEC61850 GGIO Ind)VirtualInput12 Signal: Virtual Input (IEC61850 GGIO Ind)VirtualInput13 Signal: Virtual Input (IEC61850 GGIO Ind)VirtualInput14 Signal: Virtual Input (IEC61850 GGIO Ind)VirtualInput15 Signal: Virtual Input (IEC61850 GGIO Ind)VirtualInput16 Signal: Virtual Input (IEC61850 GGIO Ind)

IEC 61850 Module Values

Value Description Default Size Menu Path

NoOfGooseRxAll Total number of received GOOSE messages including messages for other devices (subscribed and not subscribed messages).

0 0 - 9999999999

[Operation

/Count and RevData

/IEC61850]

www.eaton.com 237

Page 238: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Value Description Default Size Menu Path

NoOfGooseRxSubscribed

Total Number of subscribed GOOSE messages including messages with incorrect content.

0 0 - 9999999999

[Operation

/Count and RevData

/IEC61850]NoOfGooseRxCorrect

Total Number of subscribed and correctly received GOOSE messages.

0 0 - 9999999999

[Operation

/Count and RevData

/IEC61850]NoOfGooseRxNew Number of subscribed and correctly

received GOOSE messages with new content.

0 0 - 9999999999

[Operation

/Count and RevData

/IEC61850]NoOfGooseTxAll Total Number of GOOSE messages

that have been published by this device.

0 0 - 9999999999

[Operation

/Count and RevData

/IEC61850]NoOfGooseTxNew Total Number of new GOOSE

messages (modified content) that have been published by this device.

0 0 - 9999999999

[Operation

/Count and RevData

/IEC61850]NoOfServerRequestsAll

Total number of MMS Server requests including incorrect requests.

0 0 - 9999999999

[Operation

/Count and RevData

/IEC61850]NoOfDataReadAll Total Number of values read from

this device including incorrect requests.

0 0 - 9999999999

[Operation

/Count and RevData

/IEC61850]NoOfDataReadCorrect

Total Number of correctly read values from this device.

0 0 - 9999999999

[Operation

/Count and RevData

/IEC61850]NoOfDataWrittenAll Total Number of values written by

this device including incorrect ones.0 0 -

9999999999[Operation

/Count and RevData

/IEC61850]NoOfDataWrittenCorrect

Total Number of correctly written values by this device.

0 0 - 9999999999

[Operation

/Count and RevData

/IEC61850]

238 www.eaton.com

Page 239: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Value Description Default Size Menu Path

NoOfDataChangeNotification

Number of detected changes within the data sets that are published with GOOSE messages.

0 0 - 9999999999

[Operation

/Count and RevData

/IEC61850]

Values of the IEC 61850

Value Description Default Size Menu Path

GoosePublisherState

State of the GOOSE Publisher (on or off)

Off Off,

On,

Error

[Operation

/Status display

/IEC61850]GooseSubscriberState

State of the GOOSE Subscriber (on or off)

Off Off,

On,

Error

[Operation

/Status display

/IEC61850]MmsServerState State of MMS Server (on or off) Off Off,

On,

Error

[Operation

/Status display

/IEC61850]

IRIG-B00XIRIG-B

Requirement: A IRIG-B00X time code receiver is needed. IRIG-B004 and higher will support/transmit the “year” information.

If you are using an IRIG time code that does not support the “year” information (IRIG-B000, IRIG-B001, IRIG-B002, IRIG-B003), you have to set the “year” manually within the device. In these cases the correct year information is a precondition for a properly working IRIG-B.

Principle - General Use

This standard is the most used standard to synchronize the time of protection devices in medium voltage applications.

www.eaton.com 239

Page 240: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Based on the IRIG STANDARD 200-04, the device interface and software provides all time synchronization formats IRIG-B00X (IRIG-B000 / B001 / B002 / B003 / B004 / B005 / B006 / B007) as described in the standard. IRIG-B004 and higher will support/transmit the “year” information.

Time code B has a time frame of 1 second with an index count of 10 milliseconds and contains time-of-year and year information in a binary code decimal (BCD) format, and seconds-of-day in straight binary seconds (SBS) format.

Time accuracy of ±1ms is a requirement to synchronize the different protection devices.

The location of the IRIG-B interface depends to the device type. Please see the wiring diagram supplied with the protective device.

Function

The following IRIG-B parameters can be set within the Device Parameters menu.

• Set the IRIG-B type (choose B000 through B007).

• Set the time synchronization via IRIG-B to Active or Inactive.

• Set the time zone parameter (choose one of the 36 UTC Time Zones).

• Activate or deactivate the “Daylight Savings Time” function.

Parameter for Daylight Savings Time (summer-winter time) has to be set manually.

240 www.eaton.com

IRIG-BTime Code Generator

Protective Relay

GPS Satellite Signal (optional)

GPS Conncection (optional)

+

Twisted Pair Cable

To Other Devices

-

Page 241: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Check the wiring (wiring error) if no IRIG signal can be detected.

A signal will be issued if no IRIG-B time code is received for longer than 60 s.

IRIG-B Control Commands

In addition to the date and time information, the IRIB-B code offers the option to transmit up to 18 control commands that can be processed by the protective device. They have to be set and issued by the Time Code Generator.

The protective devices offer up to 18 IRIG-B assignment options for those control commands in order to carry out the assigned action. That means if the IRIG-B time code is fed with the corresponding state of those control commands, than they can be used for further processing within the devices (e.g.: in order to start statistics, switch on or off street lighting).

Device Planning Parameters of the IRIG-B00X

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Use [Device Plan-ning]

Direct Commands of the IRIG-B00X

Parameter Description Setting Range Default Menu Path

Res IRIG-B Cr Resetting of the Diagnosis Counters: IRIG-B

Inactive,

Active

Inactive [Operation

/Reset]

Global Protection Parameters of the IRIG-B00X

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Device Para

/IRIG-B]IRIG-B00X Determination of the Type: IRIG-B00X.

IRIG-B types differ in types of included “Coded Expressions” (year, control-functions, straight-binary-seconds).

IRIB-000,

IRIB-001,

IRIB-002,

IRIB-003,

IRIB-004,

IRIB-005,

IRIB-006,

IRIB-007

IRIB-000 [Device Para

/IRIG-B]

www.eaton.com 241

Page 242: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Time Zones Time Zones UTC+14 Kiritimati, UTC+13 Rawaki, UTC+12.75 Chatham Island, UTC+12 Wellington, UTC+11.5 Kingston, UTC+11 Port Vila, UTC+10.5 Lord Howe Island, UTC+10 Sydney, UTC+9.5 Adelaide, UTC+9 Tokyo, UTC+8 Hong Kong, UTC+7 Bangkok, UTC+6.5 Rangoon, UTC+6 Colombo, UTC+5.75 Kathmandu, UTC+5.5 New Delhi, UTC+5 Islamabad, UTC+4.5 Kabul, UTC+4 Abu Dhabi, UTC+3.5 Tehran, UTC+3 Moscow, UTC+2 Athens, UTC+1 Berlin, UTC+0 London, UTC-1 Azores, UTC-2 Fern. d. Noronha, UTC-3 Buenos Aires, UTC-3.5 St. John’s, UTC-4 Santiago, UTC-5 New York, UTC-6 Chicago, UTC-7 Salt Lake City, UTC-8 Los Angeles, UTC-9 Anchorage, UTC-9.5 Taiohae, UTC-10 Honolulu, UTC-11 Midway Islands

UTC+0 London [Device Para

/IRIG-B]

Daylight Saving Time

Daylight Saving Time Inactive,

Active

Inactive [Device Para

/IRIG-B]

Signals of the IRIG-B00X (Output States)

Name Description

Active Signal: ActiveInverted Signal: IRIG-B invertedControl Signal1 Signal: IRIG-B Control SignalControl Signal2 Signal: IRIG-B Control SignalControl Signal4 Signal: IRIG-B Control SignalControl Signal5 Signal: IRIG-B Control SignalControl Signal6 Signal: IRIG-B Control Signal

242 www.eaton.com

Page 243: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Control Signal7 Signal: IRIG-B Control SignalControl Signal8 Signal: IRIG-B Control SignalControl Signal9 Signal: IRIG-B Control SignalControl Signal10 Signal: IRIG-B Control SignalControl Signal11 Signal: IRIG-B Control SignalControl Signal12 Signal: IRIG-B Control SignalControl Signal13 Signal: IRIG-B Control SignalControl Signal14 Signal: IRIG-B Control SignalControl Signal15 Signal: IRIG-B Control SignalControl Signal16 Signal: IRIG-B Control SignalControl Signal17 Signal: IRIG-B Control SignalControl Signal18 Signal: IRIG-B Control Signal

IRIG-B00X Values

Value Description Default Size Menu Path

NoOfFramesOK Total number valid Frames. 0 0 - 65535 [Operation

/Count and RevData

/IRIG-B]NoOfFrameErrors Total Number of Frame Errors.

Physically corrupted Frame.0 0 - 65535 [Operation

/Count and RevData

/IRIG-B]Edges Edges 0 0 - 65535 [Operation

/Count and RevData

/IRIG-B]

www.eaton.com 243

Page 244: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

ParametersParameter setting and planning can be done:

• Directly at the device; or

• By way of the PowerPort-E software application.

Parameter Definitions

Device Parameters

Device Parameters are part of the Device Parameter tree. By modifying the Device Parameters, the User may (depending on the type of device):

• Set cutoff levels;• Configure digital inputs, Assign LEDs;• Configure Relay Outputs;• Assign acknowledgment signals;• Configure statistics;• Configure general Protocol Settings;• Adapt HMI settings;• Configure recorders (reports);• Set date and time;• Change passwords; and/or• Check the version (build) of the device.

System Parameters

System Parameters are part of the Device Parameter tree. System Parameters comprise the essential, basic settings of your switchboard such as rated frequency and transformer ratios.

Protection Parameters

Protection Parameters are part of the Device Parameter tree. This Protection Parameters include the following.

• Global Protection Parameters are part of the Protection Parameters: All settings and assignments that are done within the Global Parameter tree are valid independent of the Setting Groups. They have to be set only once. In addition, Global Protection Parameters include the parameters used for Breaker Management.

• The Parameter Setting Switch is part of the Protection Parameters: The User may either directly switch to a certain parameter setting group or determine the conditions for switching to another parameter setting group.

• Setting Group Parameters are part of the Protection Parameters: By means of the Setting Group Parameters, the User may individually adapt the protective device to the current conditions or grid conditions. The Setting Group Parameters may be individually set in each Settings group.

244 www.eaton.com

Page 245: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Device Planning Parameters

Device Planning Parameters are part of the Device Parameter tree.

• Improving the Usability (Clarity): All protection modules that are currently unused can be hidden (switched to invisible) through Device Planning. In the Device Planning menu, the User can adapt the scope of functionality of the protective device exactly as needed. The User can improve the usability by hiding all modules that are not currently needed.

• Adapting the device to the application: For those modules that are needed, determine how they should be set up (e.g.: directional, non-directional, <, >...).

Direct Commands

Direct Commands are part of the Device Parameter tree but NOT part of the parameter file. They will be executed directly (e.g.: Resetting of a Counter).

State of the Module Inputs

Module Inputs are part of the Device Parameter tree. The State of the Module Input is context-dependent.

By means of the Module Inputs, information can be passed to and acted upon by the modules. The User can assign signals to Module Inputs. The state of the signals that are assigned to an input can be viewed from the Status Display. Module Inputs can be identified by an ”-I” at the end of the name.

Signals

Signals are part of the Device Parameter tree. The state of the signal is context-dependent.

• Signals represent the state of the installation/equipment (e.g.: position indicators of the breaker).

• Signals are assessments of the state of the grid and the equipment (System OK, Transformer failure detected, ...).

• Signals represent decisions that are taken by the device (e.g.: Trip Command) based on the User parameter settings.

www.eaton.com 245

Page 246: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Adaptive Parameter Sets

246 www.eaton.com

PSet-SwitchAdap

tSet

Prot

ectio

n Pa

ra

Para

met

er S

et 4

Act

ive/

Inac

tive

Act

ive/

Inac

tive

Activ

e/In

activ

eA

ctiv

e/In

activ

eA

ctiv

e/In

activ

e

Para

met

er S

et 3

Act

ive/

Inac

tive

Act

ive/

Inac

tive

Activ

e/In

activ

eA

ctiv

e/In

activ

eA

ctiv

e/In

activ

e

Para

met

er S

et 2

Act

ive/

Inac

tive

Act

ive/

Inac

tive

Activ

e/In

activ

eA

ctiv

e/In

activ

eA

ctiv

e/In

activ

e

Para

met

er S

et 1

Act

ive/

Inac

tive

Act

ive/

Inac

tive

Activ

e/In

activ

eA

ctiv

e/In

activ

eA

ctiv

e/In

activ

e

PS1

PS2

PS3

PS4

PSS

via

Inp

fct

PSS

via

Com

m

PSet

-Sw

itch.

Mod

e

Func

tion

ExB

lo F

cR

vs B

lo F

cB

lo T

ripC

md

ExB

lo T

ripC

md

FcAda

ptS

et 4

[0…

*In]

[1...

n][0

…s]

[0.0

5...n

][1

...n]

[0…

s]A

ctiv

e/In

activ

eA

ctiv

e/In

activ

e

[0…

*In]

[1...

n][0

…s]

[0.0

5...n

][1

...n]

[0…

s]A

ctiv

e/In

activ

eA

ctiv

e/In

activ

e

[0…

*In]

[1...

n][0

…s]

[0.0

5...n

][1

...n]

[0…

s]A

ctiv

e/In

activ

eA

ctiv

e/In

activ

e

[0…

*In]

[1...

n][0

…s]

[0.0

5...n

][1

...n]

[0…

s]A

ctiv

e/In

activ

eA

ctiv

e/In

activ

e

[0…

*In]

[1...

n][0

…s]

[0.0

5...n

][1

...n]

[0…

s]A

ctiv

e/In

activ

eA

ctiv

e/In

activ

e

Ada

ptS

et 3

[0…

*In]

[1...

n][0

…s]

[0.0

5...n

][1

...n]

[0…

s]A

ctiv

e/In

activ

eA

ctiv

e/In

activ

e

Ada

ptS

et 2

[0…

*In]

[1...

n][0

…s]

[0.0

5...n

][1

...n]

[0…

s]A

ctiv

e/In

activ

eA

ctiv

e/In

activ

e[0

…*In

][1

...n]

[0…

s][0

.05.

..n]

[1...

n][0

…s]

Act

ive/

Inac

tive

Act

ive/

Inac

tive

Stan

dard

Pic

kup

Sta

ndar

d

Cur

ve S

hape

Stan

dard

t

Stan

dard

t-mul

tiplie

r

Sta

ndar

d

Res

et M

ode

Sta

ndar

d

t-res

et

Sta

ndar

d

IH2

Blo

Sta

ndar

d

Non

dir T

rip a

t V=0

Pro

tect

ion

Par

a/G

loba

l Pro

t Par

a / I

-Pro

t / I[

1]...

[n] /

Ada

ptSe

t...

& AND

& AND

& AND

1..n

, Ass

ignm

ent L

ist

Adap

tSet

4

1..n

, Ass

ignm

ent L

ist

Adap

tSet

3

1..n

, Ass

ignm

ent L

ist

Adap

tSet

2

1..n

, Ass

ignm

ent L

ist

Adap

tSet

1

Ada

ptS

et 1

& AND

Stan

dard

Page 247: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Adaptive Parameter Sets are part of the Device Parameter tree.

By means of Adaptive Parameter Sets, the User can temporarily modify single parameters within the Parameter Setting groups.

Adaptive Parameters drop-out automatically if the acknowledged signal that has activated them has dropped-out. Please take into account that Adaptive Set 1 is dominant to Adaptive Set 2. Adaptive Set 2 is dominant to Adaptive Set 3. Adaptive Set 3 is dominant to Adaptive Set 4.

In order to increase the usability (clarity), Adaptive Parameter Sets become visible if a corresponding activation signal has been assigned (PowerPort-E V. 1.2 and higher).

Example: In order to use Adaptive Parameters within Protective Element I [1], please proceed as follows.

• Assign within the Global Parameter tree, within Protective Element I[1], an activation signal for Adaptive Parameter Set 1.

• Adaptive Parameter Set 1 becomes now visible within the Protection Parameter Sets for element I[1].

By means of additional activation signals, further Adaptive Parameter Sets can be used.

The functionality of the IED (relay) can be enhanced / adapted, by means of Adaptive Parameters in order to meet the requirements of modified states of the grid or the power supply system respectively, to manage unpredictable events.

Moreover, the adaptive parameter can also be used to realize various special protective functions or to expand the existing function modules in a simple way, without costly redesign the existing hardware or software platform.

The Adaptive Parameter feature allows, besides a standard parameter set, one of the four parameter sets labeled from 1 to 4, to be used, for example, in a time overcurrent element under the control of the configurable Set Control Logic. The dynamic switch-over of the adaptive parameter set is only active for a particular element when its adaptive set control logic is configured and only as long as the activation signal is true.

For some protection elements, such as time overcurrent and instantaneous overcurrent ( 50P, 51P, 50G, 51G, …), besides the “default” setting there exists another four “alternative” settings for pickup value, curve type, time dial, and reset mode set values that can dynamically be switched-over by means of the configurable adaptive setting control logic in the single set parameter.

If the Adaptive Parameter feature is not used, the adaptive set control logic will not be selected (assigned). The protective elements work, in this case, just like a normal protection using the “Default” settings. If one of the Adaptive Set Control logic is assigned to a logic function, the protective element will be “switched-over” to the corresponding adaptive settings if the assigned logic function is asserted and will drop-out to the “Default” setting if the assigned signal that has activated the Adaptive Set has dropped-out.

Adaptive Parameters via HMI

The use of Adaptive Parameters via the HMI (panel) differs a bit to the use via PowerPort-E.

www.eaton.com 247

Page 248: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Adaptive Parameters can be also used via the HMI (instead of using the recommended PowerPort-E). The principle method of using them via the HMI is as follows.

1. Assign an activation signal for an Adaptive Parameter Set within the Global Parameters »Global Para« for a protective element (available for current functions only).

2. Call up this protective element within a Setting Group.

3. Go to the parameter that should be modified adaptively and call it up for editing (arrow-right-key).

4. Choose the corresponding Adaptive Set.

5. Set the modified parameter for the selected Adaptive Set.

Application Example

The tripping time »t« for the 50[1] element of »Parameter Set 1« should be desensitized (reduced) in case Digital Input 2 becomes active.

1. Call up the menu [Protection Para/Global Protection Para/I-Prot/50[1]/Adaptive Para1] and assign Digital Input 2 as activation signal.

2. Call up the 50[1] element within the menu [Protection Para/Set[1]/I-Port/50[1].

3. Go to the tripping time parameter »t« by means of the softkey (arrow-down) and call up the submenu by means of the softkey (arrow-right).

4. Call up the corresponding parameter set (Adaptive Set 1 in this example).

5. Set the reduced tripping time for »Adaptive Set 1«.

Check and confirm that the functionality is in compliance with your protection plan via a commissioning test.

Application Example

During a “Switch-OnTo-Fault” condition, the User is usually requested to make the embedded protective function tripping of the faulted line faster, instantaneous, or sometimes non-directional.

Such a “Switch-OnTo-Fault” application can easily be realized using the Adaptive Parameter features mentioned previously. The standard time overcurrent protection element (e.g.: 51P) should trip instantaneously in case of SOTF condition,. If the SOTF logic function »SOTF ENABLED« is detecting a manual breaker close condition, the relay switches to Adaptive Set 1 if the signal »SOTF.ENABLED« is assigned to Adaptive Set 1. The corresponding Adaptive Set 1 will become active and than »t = 0« sec.

248 www.eaton.com

Page 249: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

The screen shot above shows the adaptive setting configurations following applications based on only one simple overcurrent protection element:

1.Standard Set: Default settings;2.Adaptive Set 1: SOTF application (Switch-OnTo-Fault);3.Adaptive Set 2: CLPU application (Cold Load Pickup);

Application Examples

• The output signal of the Switch OnTo Fault module can be used to activate an Adaptive Parameter Set that sensitizes the overcurrent protection.

• The output signal of the Cold Load Pickup module can be used to activate an Adaptive Parameter Set that desensitizes the overcurrent protection.

• By means of Adaptive Parameter Sets, an Adaptive Auto Reclosure can be realized. After a reclosure attempt, the tripping thresholds or tripping curves of the overcurrent protection can be adapted.

• Depending on undervoltage, the overcurrent protection can be modified (voltage controlled). This applies to devices that offer voltage protection only.

• The ground overcurrent protection can be modified by the residual voltage. This applies to devices that offer voltage protection only.

www.eaton.com 249

Page 250: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

• Dynamic and automatic adaption of the ground current settings in order to adapt the settings to different loads (single-phase load diversity).

Adaptive Parameter Sets are only available for devices with current protection modules.

Adaptive Parameter Set Activation Signals

Name Description

-.- No assignment27M[1].Pickup Signal: Pickup Voltage Element27M[2].Pickup Signal: Pickup Voltage Element59M[1].Pickup Signal: Pickup Voltage Element59M[2].Pickup Signal: Pickup Voltage Element47[1].Pickup Signal: Pickup Voltage Asymmetry47[2].Pickup Signal: Pickup Voltage AsymmetrySOTF.enabled Signal: Switch Onto Fault enabled. This Signal can be used to

modify Overcurrent Protection Settings.CLPU.enabled Signal: Cold Load enabledAR.Running Signal: Auto Reclosing RunningAR.Pre Shot Pre Shot ControlAR.Shot 1 Shot ControlAR.Shot 2 Shot ControlAR.Shot 3 Shot ControlAR.Shot 4 Shot ControlAR.Shot 5 Shot ControlAR.Shot 6 Shot ControlDI-8P X1.DI 1 Signal: Digital InputDI-8P X1.DI 2 Signal: Digital InputDI-8P X1.DI 3 Signal: Digital InputDI-8P X1.DI 4 Signal: Digital InputDI-8P X1.DI 5 Signal: Digital InputDI-8P X1.DI 6 Signal: Digital InputDI-8P X1.DI 7 Signal: Digital InputDI-8P X1.DI 8 Signal: Digital InputLogic.LE1.Gate Out Signal: Output of the logic gateLogic.LE1.Timer Out Signal: Timer OutputLogic.LE1.Out Signal: Latched Output (Q)Logic.LE1.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE2.Gate Out Signal: Output of the logic gateLogic.LE2.Timer Out Signal: Timer Output

250 www.eaton.com

Page 251: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE2.Out Signal: Latched Output (Q)Logic.LE2.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE3.Gate Out Signal: Output of the logic gateLogic.LE3.Timer Out Signal: Timer OutputLogic.LE3.Out Signal: Latched Output (Q)Logic.LE3.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE4.Gate Out Signal: Output of the logic gateLogic.LE4.Timer Out Signal: Timer OutputLogic.LE4.Out Signal: Latched Output (Q)Logic.LE4.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE5.Gate Out Signal: Output of the logic gateLogic.LE5.Timer Out Signal: Timer OutputLogic.LE5.Out Signal: Latched Output (Q)Logic.LE5.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE6.Gate Out Signal: Output of the logic gateLogic.LE6.Timer Out Signal: Timer OutputLogic.LE6.Out Signal: Latched Output (Q)Logic.LE6.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE7.Gate Out Signal: Output of the logic gateLogic.LE7.Timer Out Signal: Timer OutputLogic.LE7.Out Signal: Latched Output (Q)Logic.LE7.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE8.Gate Out Signal: Output of the logic gateLogic.LE8.Timer Out Signal: Timer OutputLogic.LE8.Out Signal: Latched Output (Q)Logic.LE8.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE9.Gate Out Signal: Output of the logic gateLogic.LE9.Timer Out Signal: Timer OutputLogic.LE9.Out Signal: Latched Output (Q)Logic.LE9.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE10.Gate Out Signal: Output of the logic gateLogic.LE10.Timer Out Signal: Timer OutputLogic.LE10.Out Signal: Latched Output (Q)Logic.LE10.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE11.Gate Out Signal: Output of the logic gateLogic.LE11.Timer Out Signal: Timer OutputLogic.LE11.Out Signal: Latched Output (Q)Logic.LE11.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE12.Gate Out Signal: Output of the logic gate

www.eaton.com 251

Page 252: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE12.Timer Out Signal: Timer OutputLogic.LE12.Out Signal: Latched Output (Q)Logic.LE12.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE13.Gate Out Signal: Output of the logic gateLogic.LE13.Timer Out Signal: Timer OutputLogic.LE13.Out Signal: Latched Output (Q)Logic.LE13.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE14.Gate Out Signal: Output of the logic gateLogic.LE14.Timer Out Signal: Timer OutputLogic.LE14.Out Signal: Latched Output (Q)Logic.LE14.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE15.Gate Out Signal: Output of the logic gateLogic.LE15.Timer Out Signal: Timer OutputLogic.LE15.Out Signal: Latched Output (Q)Logic.LE15.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE16.Gate Out Signal: Output of the logic gateLogic.LE16.Timer Out Signal: Timer OutputLogic.LE16.Out Signal: Latched Output (Q)Logic.LE16.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE17.Gate Out Signal: Output of the logic gateLogic.LE17.Timer Out Signal: Timer OutputLogic.LE17.Out Signal: Latched Output (Q)Logic.LE17.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE18.Gate Out Signal: Output of the logic gateLogic.LE18.Timer Out Signal: Timer OutputLogic.LE18.Out Signal: Latched Output (Q)Logic.LE18.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE19.Gate Out Signal: Output of the logic gateLogic.LE19.Timer Out Signal: Timer OutputLogic.LE19.Out Signal: Latched Output (Q)Logic.LE19.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE20.Gate Out Signal: Output of the logic gateLogic.LE20.Timer Out Signal: Timer OutputLogic.LE20.Out Signal: Latched Output (Q)Logic.LE20.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE21.Gate Out Signal: Output of the logic gateLogic.LE21.Timer Out Signal: Timer OutputLogic.LE21.Out Signal: Latched Output (Q)Logic.LE21.Out inverted Signal: Negated Latched Output (Q NOT)

252 www.eaton.com

Page 253: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE22.Gate Out Signal: Output of the logic gateLogic.LE22.Timer Out Signal: Timer OutputLogic.LE22.Out Signal: Latched Output (Q)Logic.LE22.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE23.Gate Out Signal: Output of the logic gateLogic.LE23.Timer Out Signal: Timer OutputLogic.LE23.Out Signal: Latched Output (Q)Logic.LE23.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE24.Gate Out Signal: Output of the logic gateLogic.LE24.Timer Out Signal: Timer OutputLogic.LE24.Out Signal: Latched Output (Q)Logic.LE24.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE25.Gate Out Signal: Output of the logic gateLogic.LE25.Timer Out Signal: Timer OutputLogic.LE25.Out Signal: Latched Output (Q)Logic.LE25.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE26.Gate Out Signal: Output of the logic gateLogic.LE26.Timer Out Signal: Timer OutputLogic.LE26.Out Signal: Latched Output (Q)Logic.LE26.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE27.Gate Out Signal: Output of the logic gateLogic.LE27.Timer Out Signal: Timer OutputLogic.LE27.Out Signal: Latched Output (Q)Logic.LE27.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE28.Gate Out Signal: Output of the logic gateLogic.LE28.Timer Out Signal: Timer OutputLogic.LE28.Out Signal: Latched Output (Q)Logic.LE28.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE29.Gate Out Signal: Output of the logic gateLogic.LE29.Timer Out Signal: Timer OutputLogic.LE29.Out Signal: Latched Output (Q)Logic.LE29.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE30.Gate Out Signal: Output of the logic gateLogic.LE30.Timer Out Signal: Timer OutputLogic.LE30.Out Signal: Latched Output (Q)Logic.LE30.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE31.Gate Out Signal: Output of the logic gateLogic.LE31.Timer Out Signal: Timer OutputLogic.LE31.Out Signal: Latched Output (Q)

www.eaton.com 253

Page 254: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE31.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE32.Gate Out Signal: Output of the logic gateLogic.LE32.Timer Out Signal: Timer OutputLogic.LE32.Out Signal: Latched Output (Q)Logic.LE32.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE33.Gate Out Signal: Output of the logic gateLogic.LE33.Timer Out Signal: Timer OutputLogic.LE33.Out Signal: Latched Output (Q)Logic.LE33.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE34.Gate Out Signal: Output of the logic gateLogic.LE34.Timer Out Signal: Timer OutputLogic.LE34.Out Signal: Latched Output (Q)Logic.LE34.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE35.Gate Out Signal: Output of the logic gateLogic.LE35.Timer Out Signal: Timer OutputLogic.LE35.Out Signal: Latched Output (Q)Logic.LE35.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE36.Gate Out Signal: Output of the logic gateLogic.LE36.Timer Out Signal: Timer OutputLogic.LE36.Out Signal: Latched Output (Q)Logic.LE36.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE37.Gate Out Signal: Output of the logic gateLogic.LE37.Timer Out Signal: Timer OutputLogic.LE37.Out Signal: Latched Output (Q)Logic.LE37.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE38.Gate Out Signal: Output of the logic gateLogic.LE38.Timer Out Signal: Timer OutputLogic.LE38.Out Signal: Latched Output (Q)Logic.LE38.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE39.Gate Out Signal: Output of the logic gateLogic.LE39.Timer Out Signal: Timer OutputLogic.LE39.Out Signal: Latched Output (Q)Logic.LE39.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE40.Gate Out Signal: Output of the logic gateLogic.LE40.Timer Out Signal: Timer OutputLogic.LE40.Out Signal: Latched Output (Q)Logic.LE40.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE41.Gate Out Signal: Output of the logic gateLogic.LE41.Timer Out Signal: Timer Output

254 www.eaton.com

Page 255: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE41.Out Signal: Latched Output (Q)Logic.LE41.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE42.Gate Out Signal: Output of the logic gateLogic.LE42.Timer Out Signal: Timer OutputLogic.LE42.Out Signal: Latched Output (Q)Logic.LE42.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE43.Gate Out Signal: Output of the logic gateLogic.LE43.Timer Out Signal: Timer OutputLogic.LE43.Out Signal: Latched Output (Q)Logic.LE43.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE44.Gate Out Signal: Output of the logic gateLogic.LE44.Timer Out Signal: Timer OutputLogic.LE44.Out Signal: Latched Output (Q)Logic.LE44.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE45.Gate Out Signal: Output of the logic gateLogic.LE45.Timer Out Signal: Timer OutputLogic.LE45.Out Signal: Latched Output (Q)Logic.LE45.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE46.Gate Out Signal: Output of the logic gateLogic.LE46.Timer Out Signal: Timer OutputLogic.LE46.Out Signal: Latched Output (Q)Logic.LE46.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE47.Gate Out Signal: Output of the logic gateLogic.LE47.Timer Out Signal: Timer OutputLogic.LE47.Out Signal: Latched Output (Q)Logic.LE47.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE48.Gate Out Signal: Output of the logic gateLogic.LE48.Timer Out Signal: Timer OutputLogic.LE48.Out Signal: Latched Output (Q)Logic.LE48.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE49.Gate Out Signal: Output of the logic gateLogic.LE49.Timer Out Signal: Timer OutputLogic.LE49.Out Signal: Latched Output (Q)Logic.LE49.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE50.Gate Out Signal: Output of the logic gateLogic.LE50.Timer Out Signal: Timer OutputLogic.LE50.Out Signal: Latched Output (Q)Logic.LE50.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE51.Gate Out Signal: Output of the logic gate

www.eaton.com 255

Page 256: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE51.Timer Out Signal: Timer OutputLogic.LE51.Out Signal: Latched Output (Q)Logic.LE51.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE52.Gate Out Signal: Output of the logic gateLogic.LE52.Timer Out Signal: Timer OutputLogic.LE52.Out Signal: Latched Output (Q)Logic.LE52.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE53.Gate Out Signal: Output of the logic gateLogic.LE53.Timer Out Signal: Timer OutputLogic.LE53.Out Signal: Latched Output (Q)Logic.LE53.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE54.Gate Out Signal: Output of the logic gateLogic.LE54.Timer Out Signal: Timer OutputLogic.LE54.Out Signal: Latched Output (Q)Logic.LE54.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE55.Gate Out Signal: Output of the logic gateLogic.LE55.Timer Out Signal: Timer OutputLogic.LE55.Out Signal: Latched Output (Q)Logic.LE55.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE56.Gate Out Signal: Output of the logic gateLogic.LE56.Timer Out Signal: Timer OutputLogic.LE56.Out Signal: Latched Output (Q)Logic.LE56.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE57.Gate Out Signal: Output of the logic gateLogic.LE57.Timer Out Signal: Timer OutputLogic.LE57.Out Signal: Latched Output (Q)Logic.LE57.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE58.Gate Out Signal: Output of the logic gateLogic.LE58.Timer Out Signal: Timer OutputLogic.LE58.Out Signal: Latched Output (Q)Logic.LE58.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE59.Gate Out Signal: Output of the logic gateLogic.LE59.Timer Out Signal: Timer OutputLogic.LE59.Out Signal: Latched Output (Q)Logic.LE59.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE60.Gate Out Signal: Output of the logic gateLogic.LE60.Timer Out Signal: Timer OutputLogic.LE60.Out Signal: Latched Output (Q)Logic.LE60.Out inverted Signal: Negated Latched Output (Q NOT)

256 www.eaton.com

Page 257: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE61.Gate Out Signal: Output of the logic gateLogic.LE61.Timer Out Signal: Timer OutputLogic.LE61.Out Signal: Latched Output (Q)Logic.LE61.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE62.Gate Out Signal: Output of the logic gateLogic.LE62.Timer Out Signal: Timer OutputLogic.LE62.Out Signal: Latched Output (Q)Logic.LE62.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE63.Gate Out Signal: Output of the logic gateLogic.LE63.Timer Out Signal: Timer OutputLogic.LE63.Out Signal: Latched Output (Q)Logic.LE63.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE64.Gate Out Signal: Output of the logic gateLogic.LE64.Timer Out Signal: Timer OutputLogic.LE64.Out Signal: Latched Output (Q)Logic.LE64.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE65.Gate Out Signal: Output of the logic gateLogic.LE65.Timer Out Signal: Timer OutputLogic.LE65.Out Signal: Latched Output (Q)Logic.LE65.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE66.Gate Out Signal: Output of the logic gateLogic.LE66.Timer Out Signal: Timer OutputLogic.LE66.Out Signal: Latched Output (Q)Logic.LE66.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE67.Gate Out Signal: Output of the logic gateLogic.LE67.Timer Out Signal: Timer OutputLogic.LE67.Out Signal: Latched Output (Q)Logic.LE67.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE68.Gate Out Signal: Output of the logic gateLogic.LE68.Timer Out Signal: Timer OutputLogic.LE68.Out Signal: Latched Output (Q)Logic.LE68.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE69.Gate Out Signal: Output of the logic gateLogic.LE69.Timer Out Signal: Timer OutputLogic.LE69.Out Signal: Latched Output (Q)Logic.LE69.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE70.Gate Out Signal: Output of the logic gateLogic.LE70.Timer Out Signal: Timer OutputLogic.LE70.Out Signal: Latched Output (Q)

www.eaton.com 257

Page 258: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE70.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE71.Gate Out Signal: Output of the logic gateLogic.LE71.Timer Out Signal: Timer OutputLogic.LE71.Out Signal: Latched Output (Q)Logic.LE71.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE72.Gate Out Signal: Output of the logic gateLogic.LE72.Timer Out Signal: Timer OutputLogic.LE72.Out Signal: Latched Output (Q)Logic.LE72.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE73.Gate Out Signal: Output of the logic gateLogic.LE73.Timer Out Signal: Timer OutputLogic.LE73.Out Signal: Latched Output (Q)Logic.LE73.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE74.Gate Out Signal: Output of the logic gateLogic.LE74.Timer Out Signal: Timer OutputLogic.LE74.Out Signal: Latched Output (Q)Logic.LE74.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE75.Gate Out Signal: Output of the logic gateLogic.LE75.Timer Out Signal: Timer OutputLogic.LE75.Out Signal: Latched Output (Q)Logic.LE75.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE76.Gate Out Signal: Output of the logic gateLogic.LE76.Timer Out Signal: Timer OutputLogic.LE76.Out Signal: Latched Output (Q)Logic.LE76.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE77.Gate Out Signal: Output of the logic gateLogic.LE77.Timer Out Signal: Timer OutputLogic.LE77.Out Signal: Latched Output (Q)Logic.LE77.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE78.Gate Out Signal: Output of the logic gateLogic.LE78.Timer Out Signal: Timer OutputLogic.LE78.Out Signal: Latched Output (Q)Logic.LE78.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE79.Gate Out Signal: Output of the logic gateLogic.LE79.Timer Out Signal: Timer OutputLogic.LE79.Out Signal: Latched Output (Q)Logic.LE79.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE80.Gate Out Signal: Output of the logic gateLogic.LE80.Timer Out Signal: Timer Output

258 www.eaton.com

Page 259: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE80.Out Signal: Latched Output (Q)Logic.LE80.Out inverted Signal: Negated Latched Output (Q NOT)Sys.Maint Mode Active Signal: Arc Flash Reduction Maintenance ActiveSys.Maint Mode Inactive Signal: Arc Flash Reduction Maintenance Inactive

Operational Modes (Access Authorization)

Operational Mode – »Display Only«

• The protection is activated.

• All data, measuring values, records, and counters/meters can be viewed.

Operation Mode – »Parameter Setting and Planning«

In this mode, the User is able to:

• Edit and set parameters;

• Change device planning details; and

• Configure and reset operational data (event recorder/fault recorder/power meter/switching cycles).

If the device was not active within the parameter setting mode for a longer time (can be set between 20 – 3600 seconds), the device will automatically reset to »Display Only« mode (Please refer to the Appendix Module Panel).

As long as the User is within the parameter setting mode, the device cannot acknowledge.

In order to change into the operation mode (»Parameter Setting«) please proceed as follows.

1.Mark the parameter to be changed in the device display.

2.Press the »Wrench« soft key to temporarily change into the Parameter Setting mode.

3.Enter the parameter password.

4.Change the parameter.

5.Change any additional parameters that are needed.

As long as the User is within the parameter setting mode, a wrench icon will be shown in the upper right corner of the display.

6. For saving the altered parameter(s):

www.eaton.com 259

Page 260: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

• Press the »OK« key; and• Confirm by pressing the »Yes« soft key.

7.Then the device changes into the »Display Only« mode.

Password

Password Entry at the Panel

Passwords can be entered by way of the soft keys

1 2 3 4

Example: For password (3244) press successively:

• Soft key 3;• Soft key 2;• Soft key 4; and• Soft key 4.

Password Changes

Passwords can be changed at the device in the »Device Para/Password« menu or by means of the PowerPort-E software.

A password must be a User-defined combination of the numbers 1, 2, 3, 4.

All other characters and keys WILL NOT be accepted.

The password for the operation mode »Parameter setting and planning« enables the User to transfer parameters from the PowerPort-E software into the device.

When the User wants to change a password, the existing one has to be entered first. The new password (up to 8 digits) is then to be confirmed twice. Please proceed as follows.

• In order to change the password, please enter the old password followed by pressing the »OK« key.• Next, enter the new password and press the »OK« key.• Finally, confirm your new password and press the »OK« key.

Password Forgotten

All passwords can be reset to the fail-safe adjustment (1234) by pressing the »Ack/Rst« key during cold booting. For this procedure, confirm the inquiry »Reset Passwords?« with »Yes«.

260 www.eaton.com

Page 261: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Changing of Parameters - Example

• Move to the parameter to be change by using the soft keys.

• Press the »Wrench« soft key.

• Enter the password for parameter setting.

• Edit/change the parameter.

Now the User can:

• Save the change made and have it adopted by the system; or

• Change additional parameters and save all the altered parameters and have them adopted by the system.

To Save Parameter Changes Immediately

• Press the »OK« key to save the changed parameters directly and to have them adopted by the device. Confirm the parameter changes by pressing the »Yes« soft key or dismiss by pressing »No« soft key.

To Change Additional Parameters and Save Afterwards

• Move to other parameters and change them.

A star symbol in front of the changed parameters indicates that the modifications have only temporarily been saved. They are not yet stored and adopted by the device.

In order to make things easier to follow, especially where complex parameter changes are involved, on every superior/higher-ranking menu level, the intended change of the parameter is indicated by the star symbol (star trace). This makes it possible to control or follow from the main menu level at any time where parameter changes have been made and have not been saved.

In addition to the star trace to the temporarily saved parameter changes, a general parameter changing symbol is faded in at the left corner of the display. It is possible from each point of the menu tree to see that there are parameter changes still not adopted by the device.

Press the »OK« key to initiate the final storage of all parameter changes. Confirm the parameter changes by pressing the »Yes« soft key or dismiss by pressing the »No« soft key.

www.eaton.com 261

Page 262: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Plausibility Check

In order to prevent obvious incorrect settings, the device constantly monitors all temporarily saved parameter changes. If the device detects a conflict, it is indicated by a question mark in front of the respective parameter.

In order to make things easier to follow, especially where complex parameter changes are involved, a question mark appears above the temporarily saved parameters (on every superior /higher - ranking menu level). This makes it possible to control or follow, from the main menu level, where conflicts are intended to be saved. This can be done at any time.

In addition to the question mark trace to the temporarily saved conflict parameter changes, a general conflict symbol/question mark is faded-in at the left corner of the display, and so it is possible to see from each point of the menu tree that conflicts have been detected by the device.

A star/parameter change indication is always overwritten by the question mark/conflict symbol.

If a device detects a conflict, it rejects saving and adopting of the parameters.

Example: If the residual voltage has been configured as »calculated« (»EVTcon = calculated«), then the device recognizes a conflict in case voltage measuring is configured as »Phase to Phase« (»VTcon = Phase to Phase«). The calculation of the residual voltage is physically not possible by means of phase-to-phase voltages.

Changing of Parameters When Using the PowerPort-E - ExampleExample: Changing of a protective parameter (to alter the characteristic for the overcurrent protection function I[1] in Parameter Set 1).

• If PowerPort-E is not in operation, please start the application.

• If the device data have not been loaded, select »Data To Be Received From The Device« in the »Device« menu.

• Double-click the »Protection Para Icon« in the navigation tree.

• Double-click the »Protection Para Set Icon« in the navigation tree.

• Double-click the »Set 1 Icon« in the navigation tree.

• Double-click the »protection stage I[1]« in the navigation tree.

• In the working window, a tabulated overview appears showing the parameters assigned to this protective function.

• In this table, double-click the value/parameter to be changed (in this example: »Char«).

• Another window (pop-up) is opened where the User can select the required characteristic.

262 www.eaton.com

Page 263: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

• Close this window by clicking the »OK« key.

A star symbol in front of the changed parameters indicates that the alterations have only temporarily been saved. They are not yet stored and adopted by the software/device.

In order to make things easier to follow, especially where complex parameter changes are involved, on every superior/higher menu level, the intended change of the parameter is indicated by the star symbol (star trace). This makes it possible to control or follow, from the main menu level, where parameter changes have been made and have not been saved. This can be done at any time.

Plausibility Check

In order to prevent obvious incorrect settings, the application constantly monitors all temporarily saved parameter changes. If the device detects a conflict, it is indicated by a question mark in front of the respective parameter.

In order to make things easier to follow, especially where complex parameter changes are involved, on every superior/higher menu level above of the temporarily saved parameters, a conflict is indicated by a question mark (plausibility trace). This makes it possible to control or follow, from the main menu level, where conflicts exist. This can be done at any time.

So it is possible to see from each point of the menu tree that conflicts have been detected by the application.

A star/parameter change indication is always overwritten by the question mark/conflict symbol.

If the software detects a conflict, it rejects the saving and adopting of the parameters.

Example: If the residual voltage has been configured as »Calculated« (»EVTcon = calculated«), then the application recognizes a conflict in case voltage measuring is configured as »Phase to Phase« (»VTcon = Phase to Phase«). The calculation of the residual voltage is physically not possible by means of phase-to-phase voltages.

• Additional parameters can be changed if required.

• In order to transfer changed parameters into the device, please select »Transfer all parameters into the device« in the »Device« menu.

• Confirm the safety inquiry »Shall The Parameters Be Overwritten?«.

• Enter the password for setting parameters in the pop-up window.

• Confirm the inquiry »Shall The Data Be Saved Locally?« with »Yes« (recommended). Select a suitable storing location on your hard disk.

www.eaton.com 263

Page 264: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

• Confirm the selected storage location by clicking »Save«.

• The changed parameter data is now saved in the data file chosen. Thereafter, the changed data is transferred to the device and adopted.

Once the User has entered the parameter setting password, PowerPort-E will not ask the User again for the password for at least 10 minutes. This time interval will start again each time parameters are transmitted into the device. If, for more than 10 minutes, no parameters are transmitted into the device, PowerPort-E will again ask for the password when the User tries to transmit parameters into the device.

Protection Parameters

Please note that by deactivating, for example protective functions, the User also changes the functionality of the device.

The manufacturer does not accept liability for any personal or material damage as a result of incorrect planning.

Contact your Eaton Customer Service representative for more information.

The protection parameters include the following protection parameter trees.

• Global Protection Parameters »Global Prot Para«: Here the User can find all protection parameters that are universally valid. That means they are valid independent of the protection parameter sets.

• Setting Group Parameters »Set1..4«: The protection parameters that the User set within a parameter set are only valid if the parameter set selected is switched to active.

Setting Groups

Setting Group Switch

Within the »Protection Para/P-Set Switch« menu, the User has the following possibilities:

• To manually set one of the four setting groups active;• To assign a signal to each setting group that sets this group to active; and• Scada switches the setting groups.

Setting Group Switch

Manual Selection Via Input Function (e.g.: Digital Input)

Via Scada

Switching Options Switch over, if another setting group is chosen manually within the »Protection Para/P-Set

Switch« menu.

Switch over not until the request is clear.

That means if there is more or less than one request signal active, no switch over will be

executed.

Switch over if there is a clear Scada request.

Otherwise no switch over will be executed.

264 www.eaton.com

Page 265: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

The description of the parameters can be found within the “System Parameters” section.

Setting Group Switch Via PowerPort-E

• If PowerPort-E is not running, please start the application.

• If the device data have not been loaded, click »Receive Data From The Device« in the »Device« menu.

• Double click the »Protection Para« icon in the navigation tree.

• Double click the »P-Set Switch« within the protection parameters.

• To configure the Setting Group Switch respectively, manually choose an active set.

The description of the parameters can be found within the “System Parameters” section.

Copying Setting Groups (Parameter Sets) Via PowerPort-E

Setting groups can only be copied if there are no conflicts (no red question marks).

For applications using multiple settings groups, one can use the configuration file from the first group to create the second group. With the help of PowerPort-E, the User can simply copy an existing setting group to another (not yet configured) one. The User only needs to change those parameters where the two setting groups are different.

To efficiently establish a second parameter set where only few parameters are different, proceed as follows.

• If PowerPort-E is not running, please start the application.

• Open a (off-line) parameter file of a device or load data of a connected device.

• Carefully save the relevant device parameters by selecting [File\Save as].

• Select »Copy Parameter Sets« out of the “Edit” menu.

• Then define both source and destination of the parameter sets to be copied (source = copy from; destination: copy to).

• Click on »OK« to start the copy procedure.

• The copied parameter set is now cached (not yet saved!).

• Then, modify the copied parameter set(s), if applicable.

• Assign a new file name to the revised device parameter file and save it on your hard disk (backup copy).

www.eaton.com 265

Page 266: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

• To transfer the modified parameters back to the device, click on the »Device« menu item and select »Transfer All Parameters into the Device«.

Comparing Setting Groups Via PowerPort-E

• If PowerPort-E is not running, please start the application.

• Click on menu item »Edit« and select »Compare Parameter Sets«.

• Select the two parameter sets from the two drop down menus that are to be compared with each other.

• Press the »Compare« button.

• The values that are different from the set parameters will be listed in tabular form.

Comparing Parameter Files Via PowerPort-EWith the help of PowerPort-E, the User can simply compare/differentiate the currently open parameter/device file against a file on the hard disk. The precondition is that the versions and type of devices match. To compare the parameter files, please proceed as follows.

• Click on »Compare with a Parameter File« within the »Device« menu.

• Click on the Folder icon in order to select a file on your hard disk.

• The differences will be shown in tabular form.

Converting Parameter Files Via PowerPort-EParameter files of the same type can be up- or down-graded (converted). During this process, the new parameter file will keep all active settings from the source parameter file and, at the same time, remove all inactive settings. As many parameters as possible will be converted.

• Parameters that are newly added will be set to default.

• Parameters that are not included in the target file version will be deleted.

• In order to convert a parameter file please proceed as follows.

• If PowerPort-E is not in operation, please start the application.

• Open a parameter file or load the parameters from a device that should be converted.

• Make a backup of this file in a fail-safe place.

• Choose »Save as« from the »File« menu.

• Enter a new file name (in order to prevent overwriting the original file).

266 www.eaton.com

Page 267: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

• Choose the new file type from drop down menu »File Type«.

• Confirm the security check by clicking on »Yes« only if the User is sure that the file conversion should be

executed.

• In tabular form the modifications will be shown as follows.

Added parameter:

Deleted parameter:

www.eaton.com 267

Page 268: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Device ParametersSys

Date and TimeIn the »Device parameters/Date/Time« menu, the User can set the date and time.

Synchronize Date and Time Via PowerPort-E

• If PowerPort-E is not running, please start the application.

• If device data have not been downloaded recently, click »Receive Data From The Device« in the »Device« menu.

• Double click the »Device parameters« icon in the navigation tree.

• Double click the »Date/time« icon within the operational data.

• From the working window, the User can now synchronize the date and time of the device with the PC (i.e.: that means that the device accepts the date and time from the PC).

VersionWithin the»Device parameters/Version« menu, the User can obtain information on the software and hardware versions.

Version Via PowerPort-EWithin the »File/Properties« menu, the User can obtain detailed information on the currently opened file (e.g.: software and hardware version).

In order to be able to transmit a parameter file (e.g.: created off line) into the device, the following parameters must agree:

• Type Code (written on the top of the device/type label); and

• Version of the device model (can be found in the »Device Parameters\Version« menu).

268 www.eaton.com

Page 269: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

TCP/IP Settings

Warning: Mixing up IP Addresses

(In case there is more than one protective device within the TCP/IP network or establishing an unintentional wrong connection to a protective device based on a wrong entered IP address.

Transferring parameters into the wrong protective device might lead to death, personal injury, or damage of electrical equipment.

In order to prevent faulty connections, the User MUST document and maintain a list with the IP addresses of any switchboard/protective devices.

The User MUST double check the IP addresses of the connection that is to be established. That means, the User MUST first read out the IP address at the HMI of the device (within menu [Device para/TCP IP]) then compare the IP address with the list. If the addresses are identical, establish the connection. If they are not, DO NOT establish the connection.

Within »Device Para / TCP/IP« menu, the TCP/IP settings have to be set.

The first-time setting of the TCP/IP Parameters can be done at the panel (HMI) only.

Establishing a connection via TCP/IP to the device is only possible if the device is equipped with an Ethernet interface (RJ45).

Contact your IT administrator in order to establish the network connection.

Set the TCP/IP Parameters:

Call up »Device parameter/TCP/IP« at the HMI (panel) and set the following parameters:

• TCP/IP address;

• Subnetmask; and

• Gateway.

Direct Commands of the System Module

Parameter Description Setting Range Default Menu Path

Ack LED All acknowledgeable LEDs will be acknowledged.

Inactive,

Active

Inactive [Operation

/Reset]

Ack RO All acknowledgeable Relay Outputs will be acknowledged.

Inactive,

Active

Inactive [Operation

/Reset]

www.eaton.com 269

Page 270: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Ack Comm Communication will be acknowledged. Inactive,

Active

Inactive [Operation

/Reset]Ack RO LED Comm TCmd

Reset the Relay Outputs, LEDs, Communication, and the Trip Command.

Inactive,

Active

Inactive [Operation

/Reset]

Reboot Rebooting the device. No,

Yes

No [Service

/General]MaintMode Manually

Arc Flash Reduction Maintenance Switch Mode: Manual Activation of the Arc Flash Reduction Mode

Only available if: Maint Mode = Activation Manually

Maint Mode inactive,

Activation via Comm,

Activation via DI,

Inactive,

Active

Inactive [Service

/MaintMode Manually]

CAUTION: Manually rebooting the device will release the Supervision Contact.

Global Protection Parameters of the System

Parameter Description Setting Range Default Menu Path

PSet-Switch Switching Parameter Set PS1,

PS2,

PS3,

PS4,

PSS via Inp fct,

PSS via Comm

PSS via Inp fct [Protection Para

/PSet-Switch]

PS1: Activated by

This Setting Group will be the active one if: The Parameter Setting Group Switch is set to "Switch via Input" and the other three input functions are inactive at the same time. In case there is more than one input function active, no Parameter Setting Group Switch will be executed. In case all input functions are inactive, the device will keep working with the Setting Group that was activated lastly.

Only available if: PSet-Switch = PSS via Inp fct

1..n, PSS Sys.Maint Mode Inactive

[Protection Para

/PSet-Switch]

270 www.eaton.com

Page 271: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

PS2: Activated by

This Setting Group will be the active one if: The Parameter Setting Group Switch is set to "Switch via Input" and the other three input functions are inactive at the same time. In case there is more than one input function active, no Parameter Setting Group Switch will be executed. In case all input functions are inactive, the device will keep working with the Setting Group that was activated lastly.

Only available if: PSet-Switch = PSS via Inp fct

1..n, PSS Sys.Maint Mode Active

[Protection Para

/PSet-Switch]

PS3: Activated by

This Setting Group will be the active one if: The Parameter Setting Group Switch is set to "Switch via Input" and the other three input functions are inactive at the same time. In case there is more than one input function active, no Parameter Setting Group Switch will be executed. In case all input functions are inactive, the device will keep working with the Setting Group that was activated lastly.

Only available if: PSet-Switch = PSS via Inp fct

1..n, PSS -.- [Protection Para

/PSet-Switch]

PS4: Activated by

This Setting Group will be the active one if: The Parameter Setting Group Switch is set to "Switch via Input" and the other three input functions are inactive at the same time. In case there is more than one input function active, no Parameter Setting Group Switch will be executed. In case all input functions are inactive, the device will keep working with the Setting Group that was activated lastly.

Only available if: PSet-Switch = PSS via Inp fct

1..n, PSS -.- [Protection Para

/PSet-Switch]

Ack LED All acknowledgeable LEDs will be acknowledged if the state of the assigned signal becomes true.

1..n, Assignment List -.- [Device Para

/Ex Acknowledge]Ack RO All acknowledgeable Relay Outputs will be

acknowledged if the state of the assigned signal becomes true.

1..n, Assignment List -.- [Device Para

/Ex Acknowledge]Ack Comm Communication will be acknowledged if the

state of the assigned signal becomes true.1..n, Assignment List -.- [Device Para

/Ex Acknowledge]Scaling Display of the measured values as primary,

secondary, or per unit values.Per unit values,

Primary values,

Secondary values

Primary values [Operation

/General Settings]

www.eaton.com 271

Page 272: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Maint Mode Activation Mode of the Arc Flash Reduction. Switching into another mode is only possible when no Activation Signal is active (pending).

Inactive,

Activation Manually,

Activation via Comm,

Activation via DI

Inactive [Service

/Maint Mode]

Maint Mode Activated by

Activation Signal for the Arc Flash Reduction Maintenance Switch.

Only available if: Maint Mode Activated by = Activation via DI

-.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

DI-8P X1.DI 7 [Service

/Maint Mode]

System Module Input States

Name Description Assignment Via

Ack LED-I Module Input State: LEDs Acknowledgment by Digital Input.

[Device Para

/Ex Acknowledge]Ack RO-I Module Input State: Acknowledgment of the

Relay Outputs.[Device Para

/Ex Acknowledge]Ack Comm-I Module Input State: Acknowledge

Communication via Digital Input. The replica that Communication has received from the device is to be reset.

[Device Para

/Ex Acknowledge]

PS1-I State of the module input, respectively of the signal, that should activate this Parameter Setting Group.

[Protection Para

/PSet-Switch]PS2-I State of the module input, respectively of

the signal, that should activate this Parameter Setting Group.

[Protection Para

/PSet-Switch]PS3-I State of the module input, respectively of

the signal, that should activate this Parameter Setting Group.

[Protection Para

/PSet-Switch]PS4-I State of the module input, respectively of

the signal, that should activate this Parameter Setting Group.

[Protection Para

/PSet-Switch]

272 www.eaton.com

Page 273: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

Maint Mode-I Module Input State: Arc Flash Reduction Maintenance Switch

[Service

/Maint Mode]

System Module Signals

Name Description

Reboot Signal: Rebooting the device: 1=Restart initiated by power supply; 2=Restart initiated by the User; 3=Set on defaults (Super Reset); 4=Restart by the debugger; 5=Restart because of configuration change; 6=General failure; 7=Restart initiated by System Abort (host side); 8=Restart initiated by watchdog timeout (host side); 9=Restart initiated by System Abort (dsp side); 10=Restart initiated by watchdog timeout (dsp side); 11=Power supply failure (short term interruption) or power supply voltage to low; 12=illegal memory access.

Act Set Signal: Active Parameter SetPS 1 Signal: Parameter Set 1PS 2 Signal: Parameter Set 2PS 3 Signal: Parameter Set 3PS 4 Signal: Parameter Set 4PSS manual Signal: Manual switch over of a Parameter SetPSS via Comm Signal: Parameter Set Switch via CommunicationPSS via Inp fct Signal: Parameter Set Switch via Input FunctionMin. 1 param changed Signal: At least one parameter has been changedMaint Mode Active Signal: Arc Flash Reduction Maintenance ActiveMaint Mode Inactive Signal: Arc Flash Reduction Maintenance InactiveMaintMode Manually Signal: Arc Flash Reduction Maintenance Manual ModeMaint Mode Comm Signal: Arc Flash Reduction Maintenance Comm ModeMaint Mode DI Signal: Arc Flash Reduction Maintenance Digital Input ModeParam to be saved Number of parameters to be saved. 0 means that all parameter

changes are overtaken.Ack LED Signal: LEDs AcknowledgmentAck RO Signal: Acknowledgment of the Relay OutputsAck Counter Signal: Reset of all CountersAck Comm Signal: Acknowledge CommunicationAck TripCmd Signal: Reset Trip CommandAck LED-HMI Signal: LEDs Acknowledgment :HMIAck RO-HMI Signal: Acknowledgment of the Relay Outputs :HMIAck Counter-HMI Signal: Reset of all Counters :HMIAck Comm-HMI Signal: Acknowledge Communication :HMIAck TripCmd-HMI Signal: Reset Trip Command :HMIAck LED-Comm Signal: LEDs Acknowledgment :Communication

www.eaton.com 273

Page 274: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Ack RO-Comm Signal: Acknowledgment of the Relay Outputs :CommunicationAck Counter-Comm Signal: Reset of all Counters :CommunicationAck Comm-Comm Signal: Acknowledge Communication :CommunicationAck TripCmd-Comm Signal: Reset Trip Command :CommunicationRes OperationsCr Signal: Res OperationsCrRes AlarmCr Signal: Res AlarmCrRes TripCr Signal: Res TripCrRes TotalCr Signal: Res TotalCr

Special Values of the System Module

Value Description Menu Path

Build Build [Device Para

/Version]Version Version [Device Para

/Version]Operating hours Cr Operating hours counter of the protective

device[Operation

/Count and RevData

/Sys]

274 www.eaton.com

Page 275: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

System ParametersSystem Para

Within the system parameters, the User can set all parameters that are relevant for the primary side and the mains operational method like frequency, primary and secondary values, and the star point treatment.

General System Parameters

Parameter Description Setting Range Default Menu Path

Phase Sequence

Phase Sequence direction ABC,

ACB

ABC [System Para

/General Settings]

f Nominal frequency 50Hz,

60Hz

60Hz [System Para

/General Settings]

Voltage Depending System Parameters

Parameter Description Setting Range Default Menu Path

Main VT pri Primary Voltage of Main VTs. The phase to phase voltage is to be entered even if the load is in delta connection.

60 – 500000 V 12000 V [System Para

/General Settings]Main VT sec Secondary Voltage of Main VTs. The phase

to phase voltage is to be entered even if the load is in delta connection.

60.00 – 600.00 V 120 V [System Para

/General Settings]Main VT con Main VTs connection Wye,

Phase-to-Phase, Open-Delta

Wye [System Para

/General Settings]Aux VT pri Primary voltage of Aux VTs 60 – 500000 V 12000 V [System Para

/General Settings]Aux VT sec Secondary voltage of Aux VTs 35.00 – 600.00 V 120 V [System Para

/General Settings]V Sync The fourth measuring input of the voltage

measuring card measures the voltage that is to be synchronized.

A,

B,

C,

AB,

BC,

CA

A [System Para

/General Settings]

www.eaton.com 275

Page 276: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Phase MTA Maximum Torque Angle: Angle between phase current and reference voltage in case of a short circuit. This angle is needed to determine the fault direction in case of short circuits.

0 - 360° 30° [System Para

/Direction]

IR Dir Cntrl IOptions for direction detection IR 3V0,

IR IPol,

IR Dual,

IR Neg

IR 3V0 [System Para

/Direction]

IX Dir Cntrl Options for direction detection IX 3V0,

IX Neg,

IX Dual

IX 3V0 [System Para

/Direction]

3V0 Source Earth overcurrent protection elements take into account this parameter for direction decisions. The User has to ensure, that this parameter is set to "Measured" only if the ground current is fed to the fourth measuring input of the current measuring card.

Measured,

Calculated

Calculated [System Para

/Direction]

Ground MTA Ground MTA

Only available if: Star point treatment = Solidly (Effectively) or Low-Resistance Grounded

0 - 360° 110° [System Para

/Direction]

Current Depending System Parameters

Parameter Description Setting Range Default Menu Path

CT con Current transformer connection 3-wire,

4th CT IN,

4th CT IG

3-wire [System Para

/General Settings]

CT pri Nominal current of the primary side of the current transformers.

1 – 50000 A 500 A [System Para

/General Settings]CT sec Nominal current of the secondary side of

the current transformers.1 A,

5 A

5 A [System Para

/General Settings]

276 www.eaton.com

Page 277: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

CT dir Protection functions with directional feature can only work properly if the connection of the current transformers is free of wiring errors. If all current transformers are connected to the device with an incorrect polarity, the wiring error can be compensated by this parameter. This parameter turns the current vectors by 180 degrees.

0°,

180°

0° [System Para

/General Settings]

XCT pri This parameter defines the primary nominal current of the connected ground current transformer. If the ground current is measured via the Residual connection, the primary value of the phase current transformer must be entered here.

1 – 50000 A 50 A [System Para

/General Settings]

XCT sec This parameter defines the secondary nominal current of the connected ground current transformer. If the ground current is done via the Residual connection, the primary value of the phase current transformer must be entered here.

1 A,

5 A

5 A [System Para

/General Settings]

XCT dir Ground fault protection with directional feature depends also on the correct wiring of the ground current transformer. An incorrect polarity/wiring can be corrected by means of the settings "0°" or "180°". The operator has the possibility of turning the current vector by "180°" (change of sign) without modification of the wiring. This means, that – in terms of figures - the determined current indicator was turned by "180°" by the device.

0°,

180°

0° [System Para

/General Settings]

www.eaton.com 277

Page 278: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

BlockingThe device provides a function for temporary blocking of the complete protection functionality or of single protections.

Make absolutely sure that no illogical or even life-threatening blockings are allocated.

Make sure not to carelessly deactivate protection functions that have to be available according to the protection concept.

Permanent BlockingSwitching “On” or “Off” the Complete Protection Functionality

In the »Protection« module, the complete protection of the device can be switched “On” or “Off”. Set the Function parameter to »Active« or »Inactive« in the »Prot« module .

Protection is activated only if in the »Prot« module the parameter Function is = »Active« (i.e.: with »Function« = »Inactive«, no protection function are operating). If »Function« = »Inactive«, then the device cannot protect any components.

Switching Modules “On” or “Off”

Each of the modules can be switched “On” or “Off” (permanently). This is achieved when the »Function« parameter is set to »Active« or »Inactive« in the respective module.

Activating or Deactivating the Tripping Command of a Protection Permanently

In each of the protections, the tripping command to the breaker can be permanently blocked. For this purpose, the »TripCmd Blo« parameter has to be set to »Active«.

Temporary BlockingTo Block the Complete Protection of the Device Temporarily by a Signal

In the »Prot« module, the complete protection of the device can be blocked temporarily by a signal. On the condition that a module-external blocking is permitted (»ExBlo Fc=active«). In addition to this, a related blocking signal from the »Assignment list« must have been assigned. For the time the allocated blocking signal is active, the module is blocked.

If the »Prot« module is blocked, the complete protection function does not work. As long as the blocking signal is active, the device cannot protect any components.

To Block a Complete Protection Module Temporarily by an Active Assignment

• In order to establish a temporary blockage of a protection module, the parameter »ExBlo Fc« of the module has to be set to »Active«. This gives the permission: »This module can be blocked«.

278 www.eaton.com

Page 279: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

• Within the general protection parameters, a signal has to be additionally chosen from the »Assignment list«. The blocking only becomes active when the assigned signal is active.

To Block the Tripping Command of a Protection Element Temporarily by an Active Assignment

The tripping command of any of the protection modules can be blocked from an external signal. In this case, external does not only mean from outside the device, but also from outside the module. Not only real external signals are permitted to be used as blocking signals (for example: the state of a digital input), but the User can also choose any other signal from the »Assignment list«.

• In order to establish a temporary blockage of a protection element, the parameter »ExBlo TripCmd Fc« of the module has to be set to »Active«. This gives the permission: »The tripping command of this element can be blocked«.

• Within the general protection parameters, an additional signal has to be chosen and assigned to the »ExBlo« parameter from the »Assignment list«. If the selected signal is activated, the temporary blockage becomes effective.

www.eaton.com 279

Page 280: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

To Activate or Deactivate the Tripping Command of a Protection Module

280 www.eaton.com

Inac

tive

Activ

e

Nam

e.Bl

o Tr

ipC

md

Inac

tive

Activ

e

Nam

e.Ex

Blo

Trip

Cm

d Fc

1..n

, Ass

ignm

ent L

ist

Nam

e.Ex

Blo

Trip

Cm

d

Nam

e.Ex

Blo

Trip

Cm

d

Trip

Blo

ckin

gs

Nam

e =

All M

odul

es T

hat A

re B

lock

able

Nam

e.Ex

Blo

Trip

Cm

d-I

Nam

e.Bl

o Tr

ipC

md

3O

R

AND

Page 281: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Activate, Deactivate Respectively to Block Temporary Protection Functions

For the Sync-check module the signal Sync.Active will not be deactivated by an external blocking signal.

www.eaton.com 281

AND

Inac

tive

Activ

e

Nam

e.Fu

nctio

n

Inac

tive

Activ

e

Nam

e.Ex

Blo

Fc

Nam

e.Ac

tive

Prot

. Act

ive

1..n

, Ass

ignm

ent L

ist

Nam

e.Ex

Blo

1

Nam

e.Ex

Blo

Bloc

king

s (The

Gen

eral

Pro

tect

ion

mod

ule

is no

t dea

ctiv

ated

or b

lock

ed)

Nam

e.Ex

Blo1

-I

1..n

, Ass

ignm

ent L

ist

Nam

e.Ex

Blo

2

Nam

e.Ex

Blo2

-I

Nam

e =A

ll M

odul

es T

hat A

re B

lock

able

1

2

Plea

se R

efer

to D

iagr

am: P

rot

OR

AND

Page 282: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Current protective functions cannot only be blocked permanently (»Function = Inactive«) or temporarily by any blocking signal from the »Assignment list«, but also by »Reverse Interlocking«.

All other protection functions can be activated, deactivated, or blocked in the same manner.

282 www.eaton.com

AND

Inac

tive

Activ

e

Nam

e.R

vs B

lo F

c

AND

Inac

tive

Activ

e

Nam

e.Fu

nctio

n

Inac

tive

Activ

e

Nam

e.Ex

Blo

Fc

Nam

e.Ac

tive

Prot

. Act

ive

1..n

, Ass

ignm

ent L

ist

Nam

e.Ex

Blo

1

1..n

, Ass

ignm

ent L

ist

Nam

e.R

vs B

lo

Nam

e.Ex

Blo

Nam

e.R

vs B

lo

Bloc

king

s **

(The

Gen

eral

Pro

tect

ion

mod

ule

is n

ot d

eact

ivat

ed o

r blo

cked

)

Nam

e =

I[1]..

.[n],

IG[1

]...[n

]

Nam

e.Ex

Blo1

-I

Nam

e.Rv

s Bl

o-I

1..n

, Ass

ignm

ent L

ist

Nam

e.Ex

Blo

2Na

me.

ExBl

o2-I

1

4

Plea

se R

efer

to D

iagr

am: P

rot

OR

AND

Page 283: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Protection (Prot) ModuleProt

The »Protection« module serves as the outer frame for all other protection modules (i.e.: they are all enclosed by the »Protection« Module).

In the case where the »Protection« module is blocked, the complete protective function of the device is disabled.

Module Prot Blocked - Protection Inactive:

If the master »Protection« module is allowed to be temporarily blocked and the allocated blocking signals are active, then all protection functions will be disabled. In such a case, the protective function is »Inactive«.

Protection Active:

If the master »Protection« module was activated and a blockade for this module was not activated respectively, the assigned blocking signals are inactive at that moment, then the »Protection« is »Active«.

How to Block All Protective and Supervisory FunctionsIn order to block all protective and supervisory functions, call up the menu [Protection/Para/Global Prot Para/Prot]:

• Set the parameter »ExBlo Fc = active«;

• Choose an assignment for »ExBlo1«; and

• Optionally choose an assignment for »ExBlo2«.

If the signal becomes true, then all protective and supervisory functions will be blocked as long as one of these signals are true.

www.eaton.com 283

Page 284: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

284 www.eaton.com

AND

Inac

tive

Activ

e

Prot

.ExB

lo F

c

Prot

.Act

ive

1..n

, Ass

ignm

ent L

ist

Prot

.ExB

lo 1

Prot

.ExB

lo

Prot

-Ac

tive 1.

.n, A

ssig

nmen

t Lis

t

Prot

.ExB

lo 2

Prot

.ExB

lo1-

I

Prot

.ExB

lo2-

I

AND

Prot

.Ava

ilabl

e M

easu

red

Valu

es: O

K

At th

e m

omen

t, no

par

amet

er is

bei

ng c

hang

ed (e

xcep

t par

amet

er s

et p

aram

eter

s).

1

OR

AND

Sele

ctio

n Li

st

Prot

.ExB

lo 3

**Pr

ot.E

xBlo

3-I

**=A

vaila

bilit

y of

third

blo

ckin

g in

put d

epen

ds o

n de

vice

and

mod

ule

Page 285: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Each protection element generates its own pickup and trip signals, which are automatically passed onto the »Prot« module where the phase based and general (collective) pickup and trip signals are generated. The »Prot« module serves as a top level and a common place to group all pickups and trips from each individual protection element.

For instance, »PROT.PICKUP PHASE A« is the phase A pickup signal OR-ed from all protection elements; »PROT.TRIP PHASE A« is the phase A trip signal OR-ed from all protection elements; »PROT.PICKUP« is the collective pickup signal OR-ed from all protection elements; Prot.Trip is the collective Trip signal OR-ed from all protection elements, and etc. The Tripping commands of the protection elements have to be fed to the »Bkr Manager« module for further trip request processing.

The tripping commands are executed by the »Bkr Manager« module. Tripping commands have to be assigned to a breaker. The Breaker Manager will issue the trip command to the breaker.

If a protection element is activated and respectively decides to trip, two pickup signals will be created.

1. The module or the protection element issues an pickup/alarm (e.g.: »50P[1].PICKUP or »50P[1].TRIP«).

2. The master »Prot« module collects/summarizes the signals and issues a pickup/alarm or a trip signal»PROT.PICKUP« »PROT.TRIP«.

www.eaton.com 285

Page 286: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

286 www.eaton.com

Prot

.Trip

Nam

e.Tr

ip

Nam

e =

Each

trip

of a

n ac

tive,

trip

aut

horiz

ed p

rote

ctio

n m

odul

e w

ill le

ad to

a g

ener

al tr

ip.

Nam

e.Tr

ip

Prot

.Trip Nam

e[n]

.Trip

...15 15 15

OR

Page 287: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 287

Prot

.Pic

kup

Prot

.Pic

kup

Nam

e.Pi

ckup

Nam

e.Pi

ckup

Nam

e.Pi

ckup

Nam

e =

Each

pic

kup

of a

mod

ule

(exc

ept f

rom

sup

ervi

sion

mod

ules

but

incl

udin

g BF

) will

lead

to a

gen

eral

pic

kup

(col

lect

ive

pick

up).

...14 1414

OR

Page 288: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

288 www.eaton.com

50R[

1]...

[n].T

rip*

59[n

].Trip

Cm

d*

Prot

.Trip

IX o

r IR

51R[

1]...

[n].T

rip*

Prot

.Trip

Each

pha

se s

elec

tive

trip

of a

trip

aut

horiz

ed m

odul

e (I,

IG, V

, VX

depe

ndin

g on

the

devi

ce ty

pe) w

ill le

ad to

a p

hase

se

lect

ive

gene

ral t

rip.

19c

19d 23

OR

Prot

.Trip

Pha

se A

50P[

1]...

[n].T

rip P

hase

A*

51P[

1]...

[n].T

rip P

hase

A*

V[n]

.Trip

Pha

se A

*

16a

16b

20

OR

Prot

.Trip

Pha

se B

50P[

1]...

[n].T

rip P

hase

B*

51P[

1]...

[n].T

rip P

hase

B*

V[n]

.Trip

Pha

se B

*

17a

17b 21

OR

Prot

.Trip

Pha

se C

50P[

1]...

[n].T

rip P

hase

C*

51P[

1]...

[n].T

rip P

hase

C*

V[n]

.Trip

Pha

se C

*

18a

18b

22

OR

50X[

1]...

[n].T

rip*

51X[

1]...

[n].T

rip*

19a

19b

*=Depending on the type of device

Page 289: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 289

50R

[1]..

.[n].P

icku

p*

59[n

].Pic

kup*

Prot

.Pic

kup

IX o

r IR

51R

[1]..

.[n].P

icku

p*

Prot

.Pic

kup

Each

pha

se s

elec

tive

pick

up o

f a m

odul

e (I,

IG, V

, VX

dep

endi

ng o

n th

e de

vice

type

) will

lead

to a

pha

se s

elec

tive

gene

ral p

icku

p (c

olle

ctiv

e pi

ckup

).

27c

27d 31

OR

Prot

.Pic

kup

Phas

e B

50P[

1]...

[n].P

icku

p IB

*

V[n]

.Pic

kup

Phas

e B*

25a 29

OR

51P[

1]...

[n].P

icku

p IB

*25

b

Prot

.Pic

kup

Phas

e C

50P[

1]...

[n].P

icku

p IC

*

V[n]

.Pic

kup

Phas

e C

*

26a

30

OR

26b

51P[

1]...

[n].P

icku

p IC

*

Prot

.Pic

kup

Phas

e A

51P[

1]...

[n].P

icku

p IA

*

V[n]

.Pic

kup

Phas

e A*

24b

28

OR

50P[

1]...

[n].P

icku

p IA

*24

a

50X[

1]...

[n].P

icku

p*

51X[

1]...

[n].P

icku

p*

27a

27b

*=Depending on the type of device

Page 290: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Direct Commands of the Protection Module

Parameter Description Setting Range Default Menu Path

Res Fault a Mains No

Resetting of fault number and number of grid faults.

Inactive,

Active

Inactive [Operation

/Reset]

Global Protection Parameters of the Protection Module

Parameter Description Setting Range Default Menu Path

ExBlo Fc Activate (allow) the external blocking of the global protection functionality of the device.

Inactive,

Active

Inactive [Protection Para

/Global Prot Para

/Prot]ExBlo1 If external blocking of this module is

activated (allowed), the global protection functionality of the device will be blocked if the state of the assigned signal becomes true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Prot]ExBlo2 If external blocking of this module is

activated (allowed), the global protection functionality of the device will be blocked if the state of the assigned signal becomes true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Prot]

Protection Module Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking1 [Protection Para

/Global Prot Para

/Prot]ExBlo2-I Module Input State: External Blocking2 [Protection Para

/Global Prot Para

/Prot]

Protection Module Signals (Output States)

Name Description

Available Signal: Protection is available.Active Signal: ActiveExBlo Signal: External BlockingPickup Phase A Signal: General Pickup Phase A

290 www.eaton.com

Page 291: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Pickup Phase B Signal: General Pickup Phase BPickup Phase C Signal: General Pickup Phase CPickup IX or IR Signal: General Pickup - Ground FaultPickup Signal: General PickupTrip Phase A Signal: General Trip Phase ATrip Phase B Signal: General Trip Phase BTrip Phase C Signal: General Trip Phase CTrip IX or IR Signal: General Trip Ground FaultTrip Signal: General TripRes Fault a Mains No Signal: Resetting of fault number and number of grid faults.I dir fwd Signal: Phase current failure forward directionI dir rev Signal: Phase current failure reverse directionI dir n poss Signal: Phase fault - missing reference voltageIR dir fwd Signal: IR Ground fault (calculated) forwardIR dir rev Signal: IR Ground fault (calculated) reverse directionIR dir n poss Signal: IR Ground fault (calculated) direction detection not possibleIX dir fwd Signal: IX Ground fault (measured) forwardIX dir rev Signal: IX Ground fault (measured) reverse directionIX dir n poss Signal: IX Ground fault (measured) direction detection not possible

Protection Module Values

Value Description Menu Path

FaultNo Disturbance No. [Operation

/Count and RevData

/Prot]No of grid faults Number of grid faults: A grid fault, e.g. a

short circuit, might cause several faults with trip and autoreclosing, each fault being identified by an increased fault number. In this case, the grid fault number remains the same.

[Operation

/Count and RevData

/Prot]

www.eaton.com 291

Page 292: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Switchgear/Breaker - ManagerBreaker

WARNING: Misconfiguration of the Breaker could result in death or serious injury.

Breaker ConfigurationFor the configuration of the breaker, great attention has to be payed to the following steps:

• Wiring;• Switching Authority;• POS Indicators wiring;• General Settings;• Trip Manager;• Interlockings;• Ex OPEN/CLOSE (Option); and• Synchronous Switching.

It is recommended to use the status display in order to verify and analyze each of the steps.

Wiring

The User has to establish the wiring of the Position Indicators of the Breaker to the Digital Inputs of the protective device (52a or 52b or (both recommended)).

The User has to wire a Relay Output for the Trip command.

In case the protective device is used for control purposes, two additional relay outputs have to be wired for the control commands (issue the OPEN and CLOSE commands). That means the Relay Output for the Breaker Open and the Relay Output for the Breaker Close command.

Switching Authority

For the Switching Authority [Control\General Settings], the following general settings are possible:

None: No switching authority (switching not allowed);Local: Switching only via push buttons at the panel;Remote: Switching only via SCADA, digital inputs, or internal signals; andLocal and Remote: Switching via push buttons, SCADA, digital inputs, or internal signals.

POS Indicators wiring

In the menu [Control/Breaker/Pos Indicators wiring], the signals for the switchgear status indication (position and ready) are to be assigned.

Position Indication with two contacts - 52a and 52b (recommended)

To identify the current position of the switchgear, the switchgear contact outputs have to be used (called 52a/52b

292 www.eaton.com

Page 293: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

at a breaker). The Position Indication can work on either one or both of these inputs. Nevertheless, it is recommended that both are used.

The protective device monitors and evaluates continuously the Status of the Input Signals CinBkr52a-I and CinBkr52b-I. These signals are validated based on the supervision timers »t-Move CLOSE« and »t-Move OPEN« validation functions. As a result, the breaker position will be detected by the following signals:

• Pos CLOSE;• Pos OPEN;• Pos Indeterm;• Pos Disturb; and• Pos State (0, 1, 2 or 3).

CLOSE initiated (Supervision)

When a CLOSE command is initiated, the »t-Move CLOSE« timer will be started. While the timer is running, the »POS INDETERM« State will become true. If the command is executed and the breaker has reached the end position before the timer has elapsed, »POS CLOSE« will become true. Otherwise, if the timer has elapsed »POS DISTURB« will become true.

OPEN initiated (Supervision)

When an OPEN command is initiated, the »t-Move OPEN« timer will be started. While the timer is running, the »POS INDETERM« State will become true. If the command is executed and the breaker has reached the end position before the timer has elapsed, »POS OPEN« will become true. Otherwise, if the timer has elapsed »POS DISTURB« will become true.

The following table shows how breaker positions are validated based on 52a and 52b.

States of the Digital Inputs Validated Breaker PositionsCinBkr52a-I CinBkr52b-I Pos CLOSE Pos OPEN Pos Indeterm Pos Disturb Breaker

State

0 0 0 0 1(While a Moving timer is running)

0(While a Moving timer is running)

0Intermediate

1 1 0 0 1(While a Moving timer is running)

0(While a Moving timer is running)

0Intermediate

0 1 0 1 0 0 1OFF

1 0 1 0 0 0 2ON

0 0 0 0 0(Moving timer

elapsed)

1(Moving timer

elapsed)

3Disturbed

1 1 0 0 0(Moving timer

elapsed)

1(Moving timer

elapsed)

3Disturbed

If for any reason only one breaker contact (52a or 52b) is wired, the Single Contact Indication can be used.

Single Contact Indication

The moving time supervision works only in one direction. If the 52a signal is connected to the device, only the “CLOSE command” can be supervised and if the 52b signal is connected to the device, only the “OPEN command” can be supervised.

www.eaton.com 293

Page 294: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

If the single contact indication is used, the »SI SINGLECONTACTIND« will become true.

NOTICE: In case of single contact indication, the protective device can monitor either the 52a or the 52b contact only. In case of the 52a, the device will monitor / supervise the CLOSE command. In case of the 52b, the device will monitor / supervise the OPEN command.

Single Contact Indication – 52a only

If only the 52a signal is used for the Status Indication of an “CLOSE command”, the switch command will also start the moving time, the position indication indicates an INTERMEDIATE position during this time interval. When the switchgear reaches the end position indicated by the Pos CLOSE signal, the moving time will be terminated. If the moving time elapsed before the switchgear has reached the end position, the switching operation was not successful and the Position Indication will change to Pos DISTURB.

An OPEN command also starts the moving time. Because the device does not receive an open signal by the breaker, it assumes that the breaker is in open position after the moving time has elapsed.

The following table shows how breaker positions are validated based on 52a only.

States of the Digital Input Validated Breaker PositionsCinBkr52a-I CinBkr52b-I Pos CLOSE Pos OPEN Pos Indeterm Pos Disturb Breaker

State

0 Not wired 0 0 1(While t-Move

CLOSE is running)

0(While t-Move

CLOSE is running)

0Intermediate

0 Not wired 0 1 0 0 1OFF

1 Not wired 1 0 0 0 2ON

1 Not wired 0 0 0(After t-Move

CLOSE is elapsed)

1(After t-Move

CLOSE is elapsed)

3Disturbed

Single Contact Indication – 52b only

If only the 52b signal is used for the monitoring of the “OPEN command”, the switch command will start the moving timer. The Position Indication will indicate an INTERMEDIATE position. If the moving time elapsed before the switchgear has reached the OPEN position, the switching operation was not successful and the Position Indication will change to Pos DISTURB.

A CLOSE command also starts the moving time. Because the device does not receive a close signal by the breaker, it assumes that the breaker is in close position after the moving time has elapsed.

The following table shows how breaker positions are validated based on 52b only.

294 www.eaton.com

Page 295: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

States of the Digital Input Validated Breaker PositionsCinBkr52a-I CinBkr52b-I Pos CLOSE Pos OPEN Pos Indeterm Pos Disturb Breaker

StateNot wired 0 0 0 1

(While t-Move OPEN is running)

0(While t-Move

OPEN is running)

0Intermediate

Not wired 0 0 1 0 0 1OFF

Not wired 1 1 0 0 0 2ON

Not wired 1 0 0 0(After t-Move OPEN

is elapsed)

1(After t-Move OPEN

is elapsed)

3Disturbed

General Settings

In the menu [Control/Breaker/General Settings], the moving times for opening and closing of the breaker can be set.

Trip Manager

The command for tripping will be triggered by each of the assigned protection modules. The tripping commands of all protection modules are combined by an “OR” logic.

In addition to that, the User can set the minimum hold time of the tripping command within this module and define whether the tripping command is latched or not.

www.eaton.com 295

Page 296: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

296 www.eaton.com

Signal Breaker CLOSE

Signal Breaker OPEN

Signal Breaker Ready

Trigger [x]

Trigger [x]

Trigger [x]

Bre

aker

Breaker OPEN Command

Breaker CLOSE Command

Protection Trip Command

Position Indication:OPEN, CLOSE,

Indeterminated, Disturbed

Trip Command 50P[x]

Trip Command 51P[x]

Trip Command XX[x]

I Pro

tect

ion

Mod

ule

Trip Command 27[x]

Trip Command 59[x]

Trip Command XX[x]

V Pr

otec

tion

Mod

ule

HMI

Autoreclosure CLOSE

SCADA

Page 297: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 297

Bkr.T

rip B

kr

Bkr.T

rip B

kr

Nam

e.Tr

ipC

md

1

Bkr.t

-Trip

Cmd

t

. . . .

Activ

e

Inac

tive

Bkr.L

atch

ed

+ R

Trip

Cm

d C

r

Bkr.R

es T

ripC

mdC

r

Nam

e.Tr

ipC

md

Nam

e.Tr

ipC

md

Nam

e.Tr

ipC

md

Nam

e.Tr

ipC

md

Ackn

owle

dge

-HM

I

Ackn

owle

dge-

1..n

, Ass

ignm

ent L

ist

Ackn

owle

dge-

Com

m

Nam

e =E

ach

trip

of a

n ac

tive,

trip

aut

horiz

ed p

rote

ctio

n m

odul

e w

ill le

ad to

a g

ener

al tr

ip.

11

15 15 15 15 15

OR

OR

OR

OR

AND

S

Q

R1

Q

Cou

nter

Page 298: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Interlockings

There are three interlocking inputs for each switching direction (OPEN/CLOSE) available. Switching into the corresponding switching direction can be inhibited via these inputs. Please note: The Protection Trip commands and the reclosure command of the auto reclosure module will be issued without interlocking. In cases when the breaker must not be opened, the protection trip command has to be inhibited by a separate blocking signal.

298 www.eaton.com

AND

Switc

h co

mm

and

requ

est v

ia

Dig

ital I

nput

:(M

anua

l Sw

itch

Com

man

d)

Com

mun

icat

ion

issu

es th

e fo

llow

ing

com

man

ds:

(Man

ual S

witc

h C

omm

and)

HM

I iss

ues

the

follo

win

g co

mm

ands

:(M

anua

l Sw

itch

Com

man

d)

Auto

recl

osur

e is

sues

the

follo

win

g co

mm

ands

:(A

utom

atic

Sw

itch

Com

man

d)

Prot

ectio

n is

sues

Trip

C

omm

and

(e.g

. 50P

)

Interlockings

AND

Trip command assigned and

configured within the Trip manager

Brea

ker.O

PEN

Cm

d

Brea

ker.T

ripC

md

Bkr O

PEN

Cm

d

Bkr

CLO

SE C

md

Bkr

CLO

SE C

md

Bkr

CLO

SE C

md

Bkr

CLO

SE C

md

Bkr

OP

EN C

md

Bkr

OP

EN C

md

15 15 15

41 42

Brea

ker.P

rot C

LOSE

Brea

ker.C

LOSE

Cm

d

Rel

ease

by

sync

hron

izin

g un

it

Page 299: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Ex OPEN/CLOSE

If the breaker should be opened or closed by an external signal, the User can assign one signal that will trigger the CLOSE and one signal that will trigger the OPEN command (e.g.: digital inputs or output signals of the Logic).

An applied CLOSE command will be overwritten by an upcoming OPEN command. An applied OPEN command will not be overwritten by an upcoming CLOSE command, that means, the OPEN command is dominantly.

Synchronous Switching

If a signal is assigned to the »Synchronism« input, the closing of the switchgear will be performed only when this signal gets active during the maximum allowed waiting time »t-MaxSyncSuperv«.

If no signal is assigned to the »Synchronism« input, the synchronism release is permanent.

www.eaton.com 299

Signal Breaker CLOSE

Signal Breaker OPEN

Signal Breaker Ready

Trigger [x]

Trigger [x]

Synchronism

Brea

ker

Breaker OPEN Command

Breaker CLOSE Command

Trip Command

CLOSE Request

Position Indication:OPEN, CLOSE,

Indeterminated, Disturbed

HMI

Autoreclosure CLOSE

SCADA

Ready to CLOSE

Sync

Che

ck

Breaker CLOSE Initiative

Page 300: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Direct Commands of the Switchgear/Breaker

Parameter Description Setting Range Default Menu Path

Res Bwear Slow Breaker

Resetting the slow breaker alarm Inactive,

Active

Inactive [Operation

/Reset]

Ack TripCmd Acknowledge Trip Command Inactive,

Active

Inactive [Operation

/Reset]

Global Protection Parameters of the Switchgear/Breaker

Parameter Description Setting Range Default Menu Path

CinBkr-52a The breaker is in CLOSE-position if the state of the assigned signal is true (52a).

-.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

DI-8P X1.DI 5 [Control

/Breaker

/Pos Indicators wiring]

CinBkr-52b The breaker is in OPEN-position if the state of the assigned signal is true (52b).

-.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

DI-8P X1.DI 6 [Control

/Breaker

/Pos Indicators wiring]

Ready Breaker is ready for operation if the state of the assigned signal is true. This digital input can be used by some protective elements (if they are available within the device) like Auto Reclosure (AR), e.g.: as a trigger signal.

1..n, DI-LogicList -.- [Control

/Breaker

/Pos Indicators wiring]

300 www.eaton.com

Page 301: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Interl CLOSE1 Interlocking of the CLOSE command 1..n, Assignment List WiredInputs.Bkr. Trouble-I

[Control

/Breaker

/Interlockings]Interl CLOSE2 Interlocking of the CLOSE command 1..n, Assignment List -.- [Control

/Breaker

/Interlockings]Interl CLOSE3 Interlocking of the CLOSE command 1..n, Assignment List -.- [Control

/Breaker

/Interlockings]Interl OPEN1 Interlocking of the OPEN command 1..n, Assignment List -.- [Control

/Breaker

/Interlockings]Interl OPEN2 Interlocking of the OPEN command 1..n, Assignment List -.- [Control

/Breaker

/Interlockings]Interl OPEN3 Interlocking of the OPEN command 1..n, Assignment List -.- [Control

/Breaker

/Interlockings]SC CLOSE Switching CLOSE Command, e.g.: the

state of the Logic or the state of the digital input

1..n, DI-LogicList -.- [Control

/Breaker

/Ex OPEN/CLOSE Cmd]

SC OPEN Switching OPEN Command, e.g.: the state of the Logic or the state of the digital input

1..n, DI-LogicList -.- [Control

/Breaker

/Ex OPEN/CLOSE Cmd]

t-TripCmd Minimum hold time of the OPEN-command (Breaker, load break switch)

0 – 300.00 s 0.2 s [Control

/Breaker

/Trip Manager]Latched Defines whether the Relay Output will be

Latched when it picks up.Inactive,

Active

Inactive [Control

/Breaker

/Trip Manager]

www.eaton.com 301

Page 302: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Ack TripCmd Ack TripCmd 1..n, Assignment List -.- [Control

/Breaker

/Trip Manager]Trigger1 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 50P[1].TripCmd [Control

/Breaker

/Trip Manager]Trigger2 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 50P[2].TripCmd [Control

/Breaker

/Trip Manager]Trigger3 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 50P[3].TripCmd [Control

/Breaker

/Trip Manager]Trigger4 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 51P[1].TripCmd [Control

/Breaker

/Trip Manager]Trigger5 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 51P[2].TripCmd [Control

/Breaker

/Trip Manager]Trigger6 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 51P[3].TripCmd [Control

/Breaker

/Trip Manager]Trigger7 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 50X[1].TripCmd [Control

/Breaker

/Trip Manager]Trigger8 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 50X[2].TripCmd [Control

/Breaker

/Trip Manager]Trigger9 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 51X[1].TripCmd [Control

/Breaker

/Trip Manager]

302 www.eaton.com

Page 303: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Trigger10 Open Command to the breaker if the state of the assigned signal becomes true.

1..n, Trip Cmds 51X[2].TripCmd [Control

/Breaker

/Trip Manager]Trigger11 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 50R[1].TripCmd [Control

/Breaker

/Trip Manager]Trigger12 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 50R[2].TripCmd [Control

/Breaker

/Trip Manager]Trigger13 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 51R[1].TripCmd [Control

/Breaker

/Trip Manager]Trigger14 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 51R[2].TripCmd [Control

/Breaker

/Trip Manager]Trigger15 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 27M[1].TripCmd [Control

/Breaker

/Trip Manager]Trigger16 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 27M[2].TripCmd [Control

/Breaker

/Trip Manager]Trigger17 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 59M[1].TripCmd [Control

/Breaker

/Trip Manager]Trigger18 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 59M[2].TripCmd [Control

/Breaker

/Trip Manager]Trigger19 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 27A[1].TripCmd [Control

/Breaker

/Trip Manager]

www.eaton.com 303

Page 304: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Trigger20 Open Command to the breaker if the state of the assigned signal becomes true.

1..n, Trip Cmds 27A[2].TripCmd [Control

/Breaker

/Trip Manager]Trigger21 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 59A[1].TripCmd [Control

/Breaker

/Trip Manager]Trigger22 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 59A[2].TripCmd [Control

/Breaker

/Trip Manager]Trigger23 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 59N[1].TripCmd [Control

/Breaker

/Trip Manager]Trigger24 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 59N[2].TripCmd [Control

/Breaker

/Trip Manager]Trigger25 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 46[1].TripCmd [Control

/Breaker

/Trip Manager]Trigger26 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 46[2].TripCmd [Control

/Breaker

/Trip Manager]Trigger27 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 47[1].TripCmd [Control

/Breaker

/Trip Manager]Trigger28 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 47[2].TripCmd [Control

/Breaker

/Trip Manager]Trigger29 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 81[1].TripCmd [Control

/Breaker

/Trip Manager]

304 www.eaton.com

Page 305: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Trigger30 Open Command to the breaker if the state of the assigned signal becomes true.

1..n, Trip Cmds 81[3].TripCmd [Control

/Breaker

/Trip Manager]Trigger31 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 32[1].TripCmd [Control

/Breaker

/Trip Manager]Trigger32 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 32[2].TripCmd [Control

/Breaker

/Trip Manager]Trigger33 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 32V[1].TripCmd [Control

/Breaker

/Trip Manager]Trigger34 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 32V[2].TripCmd [Control

/Breaker

/Trip Manager]Trigger35 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds PF-55D[1].TripC

md[Control

/Breaker

/Trip Manager]Trigger36 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds PF-55D[2].TripC

md[Control

/Breaker

/Trip Manager]Trigger37 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds PF-55A[1].TripC

md[Control

/Breaker

/Trip Manager]Trigger38 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds PF-55A[2].TripC

md[Control

/Breaker

/Trip Manager]Trigger39 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds 81[5].TripCmd [Control

/Breaker

/Trip Manager]

www.eaton.com 305

Page 306: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Trigger40 Open Command to the breaker if the state of the assigned signal becomes true.

1..n, Trip Cmds -.- [Control

/Breaker

/Trip Manager]Trigger41 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds -.- [Control

/Breaker

/Trip Manager]Trigger42 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds -.- [Control

/Breaker

/Trip Manager]Trigger43 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds -.- [Control

/Breaker

/Trip Manager]Trigger44 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds -.- [Control

/Breaker

/Trip Manager]Trigger45 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds -.- [Control

/Breaker

/Trip Manager]Trigger46 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds -.- [Control

/Breaker

/Trip Manager]Trigger47 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds -.- [Control

/Breaker

/Trip Manager]Trigger48 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds -.- [Control

/Breaker

/Trip Manager]Trigger49 Open Command to the breaker if the state

of the assigned signal becomes true.1..n, Trip Cmds -.- [Control

/Breaker

/Trip Manager]

306 www.eaton.com

Page 307: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Trigger50 Open Command to the breaker if the state of the assigned signal becomes true.

1..n, Trip Cmds -.- [Control

/Breaker

/Trip Manager]Synchronism Synchronism 1..n, In-SyncList -.- [Control

/Breaker

/Synchronous Switching]

t-MaxSyncSuperv

Synchron-Run timer: Max. time allowed for synchronizing process after a close initiate. Only used for GENERATOR2SYSTEM working mode.

0 – 3000.00 s 0.2 s [Control

/Breaker

/Synchronous Switching]

t-Move CLOSE Time to move to the CLOSE Position. 0.01 – 100.00 s 0.1 s [Control

/Breaker

/General Settings]t-Move OPEN Time to move to the OPEN Position. 0.01 – 100.00 s 0.1 s [Control

/Breaker

/General Settings]

Synchronism release signals

Name Description

-.- No assignmentBreaker.CLOSE request Signal: Synchronous CLOSE requestDI-8P X1.DI 1 Signal: Digital InputDI-8P X1.DI 2 Signal: Digital InputDI-8P X1.DI 3 Signal: Digital InputDI-8P X1.DI 4 Signal: Digital InputDI-8P X1.DI 5 Signal: Digital InputDI-8P X1.DI 6 Signal: Digital InputDI-8P X1.DI 7 Signal: Digital InputDI-8P X1.DI 8 Signal: Digital InputLogic.LE1.Gate Out Signal: Output of the logic gateLogic.LE1.Timer Out Signal: Timer OutputLogic.LE1.Out Signal: Latched Output (Q)Logic.LE1.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE2.Gate Out Signal: Output of the logic gate

www.eaton.com 307

Page 308: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE2.Timer Out Signal: Timer OutputLogic.LE2.Out Signal: Latched Output (Q)Logic.LE2.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE3.Gate Out Signal: Output of the logic gateLogic.LE3.Timer Out Signal: Timer OutputLogic.LE3.Out Signal: Latched Output (Q)Logic.LE3.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE4.Gate Out Signal: Output of the logic gateLogic.LE4.Timer Out Signal: Timer OutputLogic.LE4.Out Signal: Latched Output (Q)Logic.LE4.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE5.Gate Out Signal: Output of the logic gateLogic.LE5.Timer Out Signal: Timer OutputLogic.LE5.Out Signal: Latched Output (Q)Logic.LE5.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE6.Gate Out Signal: Output of the logic gateLogic.LE6.Timer Out Signal: Timer OutputLogic.LE6.Out Signal: Latched Output (Q)Logic.LE6.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE7.Gate Out Signal: Output of the logic gateLogic.LE7.Timer Out Signal: Timer OutputLogic.LE7.Out Signal: Latched Output (Q)Logic.LE7.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE8.Gate Out Signal: Output of the logic gateLogic.LE8.Timer Out Signal: Timer OutputLogic.LE8.Out Signal: Latched Output (Q)Logic.LE8.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE9.Gate Out Signal: Output of the logic gateLogic.LE9.Timer Out Signal: Timer OutputLogic.LE9.Out Signal: Latched Output (Q)Logic.LE9.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE10.Gate Out Signal: Output of the logic gateLogic.LE10.Timer Out Signal: Timer OutputLogic.LE10.Out Signal: Latched Output (Q)Logic.LE10.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE11.Gate Out Signal: Output of the logic gateLogic.LE11.Timer Out Signal: Timer OutputLogic.LE11.Out Signal: Latched Output (Q)Logic.LE11.Out inverted Signal: Negated Latched Output (Q NOT)

308 www.eaton.com

Page 309: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE12.Gate Out Signal: Output of the logic gateLogic.LE12.Timer Out Signal: Timer OutputLogic.LE12.Out Signal: Latched Output (Q)Logic.LE12.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE13.Gate Out Signal: Output of the logic gateLogic.LE13.Timer Out Signal: Timer OutputLogic.LE13.Out Signal: Latched Output (Q)Logic.LE13.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE14.Gate Out Signal: Output of the logic gateLogic.LE14.Timer Out Signal: Timer OutputLogic.LE14.Out Signal: Latched Output (Q)Logic.LE14.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE15.Gate Out Signal: Output of the logic gateLogic.LE15.Timer Out Signal: Timer OutputLogic.LE15.Out Signal: Latched Output (Q)Logic.LE15.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE16.Gate Out Signal: Output of the logic gateLogic.LE16.Timer Out Signal: Timer OutputLogic.LE16.Out Signal: Latched Output (Q)Logic.LE16.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE17.Gate Out Signal: Output of the logic gateLogic.LE17.Timer Out Signal: Timer OutputLogic.LE17.Out Signal: Latched Output (Q)Logic.LE17.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE18.Gate Out Signal: Output of the logic gateLogic.LE18.Timer Out Signal: Timer OutputLogic.LE18.Out Signal: Latched Output (Q)Logic.LE18.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE19.Gate Out Signal: Output of the logic gateLogic.LE19.Timer Out Signal: Timer OutputLogic.LE19.Out Signal: Latched Output (Q)Logic.LE19.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE20.Gate Out Signal: Output of the logic gateLogic.LE20.Timer Out Signal: Timer OutputLogic.LE20.Out Signal: Latched Output (Q)Logic.LE20.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE21.Gate Out Signal: Output of the logic gateLogic.LE21.Timer Out Signal: Timer OutputLogic.LE21.Out Signal: Latched Output (Q)

www.eaton.com 309

Page 310: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE21.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE22.Gate Out Signal: Output of the logic gateLogic.LE22.Timer Out Signal: Timer OutputLogic.LE22.Out Signal: Latched Output (Q)Logic.LE22.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE23.Gate Out Signal: Output of the logic gateLogic.LE23.Timer Out Signal: Timer OutputLogic.LE23.Out Signal: Latched Output (Q)Logic.LE23.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE24.Gate Out Signal: Output of the logic gateLogic.LE24.Timer Out Signal: Timer OutputLogic.LE24.Out Signal: Latched Output (Q)Logic.LE24.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE25.Gate Out Signal: Output of the logic gateLogic.LE25.Timer Out Signal: Timer OutputLogic.LE25.Out Signal: Latched Output (Q)Logic.LE25.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE26.Gate Out Signal: Output of the logic gateLogic.LE26.Timer Out Signal: Timer OutputLogic.LE26.Out Signal: Latched Output (Q)Logic.LE26.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE27.Gate Out Signal: Output of the logic gateLogic.LE27.Timer Out Signal: Timer OutputLogic.LE27.Out Signal: Latched Output (Q)Logic.LE27.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE28.Gate Out Signal: Output of the logic gateLogic.LE28.Timer Out Signal: Timer OutputLogic.LE28.Out Signal: Latched Output (Q)Logic.LE28.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE29.Gate Out Signal: Output of the logic gateLogic.LE29.Timer Out Signal: Timer OutputLogic.LE29.Out Signal: Latched Output (Q)Logic.LE29.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE30.Gate Out Signal: Output of the logic gateLogic.LE30.Timer Out Signal: Timer OutputLogic.LE30.Out Signal: Latched Output (Q)Logic.LE30.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE31.Gate Out Signal: Output of the logic gateLogic.LE31.Timer Out Signal: Timer Output

310 www.eaton.com

Page 311: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE31.Out Signal: Latched Output (Q)Logic.LE31.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE32.Gate Out Signal: Output of the logic gateLogic.LE32.Timer Out Signal: Timer OutputLogic.LE32.Out Signal: Latched Output (Q)Logic.LE32.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE33.Gate Out Signal: Output of the logic gateLogic.LE33.Timer Out Signal: Timer OutputLogic.LE33.Out Signal: Latched Output (Q)Logic.LE33.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE34.Gate Out Signal: Output of the logic gateLogic.LE34.Timer Out Signal: Timer OutputLogic.LE34.Out Signal: Latched Output (Q)Logic.LE34.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE35.Gate Out Signal: Output of the logic gateLogic.LE35.Timer Out Signal: Timer OutputLogic.LE35.Out Signal: Latched Output (Q)Logic.LE35.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE36.Gate Out Signal: Output of the logic gateLogic.LE36.Timer Out Signal: Timer OutputLogic.LE36.Out Signal: Latched Output (Q)Logic.LE36.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE37.Gate Out Signal: Output of the logic gateLogic.LE37.Timer Out Signal: Timer OutputLogic.LE37.Out Signal: Latched Output (Q)Logic.LE37.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE38.Gate Out Signal: Output of the logic gateLogic.LE38.Timer Out Signal: Timer OutputLogic.LE38.Out Signal: Latched Output (Q)Logic.LE38.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE39.Gate Out Signal: Output of the logic gateLogic.LE39.Timer Out Signal: Timer OutputLogic.LE39.Out Signal: Latched Output (Q)Logic.LE39.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE40.Gate Out Signal: Output of the logic gateLogic.LE40.Timer Out Signal: Timer OutputLogic.LE40.Out Signal: Latched Output (Q)Logic.LE40.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE41.Gate Out Signal: Output of the logic gate

www.eaton.com 311

Page 312: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE41.Timer Out Signal: Timer OutputLogic.LE41.Out Signal: Latched Output (Q)Logic.LE41.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE42.Gate Out Signal: Output of the logic gateLogic.LE42.Timer Out Signal: Timer OutputLogic.LE42.Out Signal: Latched Output (Q)Logic.LE42.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE43.Gate Out Signal: Output of the logic gateLogic.LE43.Timer Out Signal: Timer OutputLogic.LE43.Out Signal: Latched Output (Q)Logic.LE43.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE44.Gate Out Signal: Output of the logic gateLogic.LE44.Timer Out Signal: Timer OutputLogic.LE44.Out Signal: Latched Output (Q)Logic.LE44.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE45.Gate Out Signal: Output of the logic gateLogic.LE45.Timer Out Signal: Timer OutputLogic.LE45.Out Signal: Latched Output (Q)Logic.LE45.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE46.Gate Out Signal: Output of the logic gateLogic.LE46.Timer Out Signal: Timer OutputLogic.LE46.Out Signal: Latched Output (Q)Logic.LE46.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE47.Gate Out Signal: Output of the logic gateLogic.LE47.Timer Out Signal: Timer OutputLogic.LE47.Out Signal: Latched Output (Q)Logic.LE47.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE48.Gate Out Signal: Output of the logic gateLogic.LE48.Timer Out Signal: Timer OutputLogic.LE48.Out Signal: Latched Output (Q)Logic.LE48.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE49.Gate Out Signal: Output of the logic gateLogic.LE49.Timer Out Signal: Timer OutputLogic.LE49.Out Signal: Latched Output (Q)Logic.LE49.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE50.Gate Out Signal: Output of the logic gateLogic.LE50.Timer Out Signal: Timer OutputLogic.LE50.Out Signal: Latched Output (Q)Logic.LE50.Out inverted Signal: Negated Latched Output (Q NOT)

312 www.eaton.com

Page 313: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE51.Gate Out Signal: Output of the logic gateLogic.LE51.Timer Out Signal: Timer OutputLogic.LE51.Out Signal: Latched Output (Q)Logic.LE51.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE52.Gate Out Signal: Output of the logic gateLogic.LE52.Timer Out Signal: Timer OutputLogic.LE52.Out Signal: Latched Output (Q)Logic.LE52.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE53.Gate Out Signal: Output of the logic gateLogic.LE53.Timer Out Signal: Timer OutputLogic.LE53.Out Signal: Latched Output (Q)Logic.LE53.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE54.Gate Out Signal: Output of the logic gateLogic.LE54.Timer Out Signal: Timer OutputLogic.LE54.Out Signal: Latched Output (Q)Logic.LE54.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE55.Gate Out Signal: Output of the logic gateLogic.LE55.Timer Out Signal: Timer OutputLogic.LE55.Out Signal: Latched Output (Q)Logic.LE55.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE56.Gate Out Signal: Output of the logic gateLogic.LE56.Timer Out Signal: Timer OutputLogic.LE56.Out Signal: Latched Output (Q)Logic.LE56.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE57.Gate Out Signal: Output of the logic gateLogic.LE57.Timer Out Signal: Timer OutputLogic.LE57.Out Signal: Latched Output (Q)Logic.LE57.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE58.Gate Out Signal: Output of the logic gateLogic.LE58.Timer Out Signal: Timer OutputLogic.LE58.Out Signal: Latched Output (Q)Logic.LE58.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE59.Gate Out Signal: Output of the logic gateLogic.LE59.Timer Out Signal: Timer OutputLogic.LE59.Out Signal: Latched Output (Q)Logic.LE59.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE60.Gate Out Signal: Output of the logic gateLogic.LE60.Timer Out Signal: Timer OutputLogic.LE60.Out Signal: Latched Output (Q)

www.eaton.com 313

Page 314: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE60.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE61.Gate Out Signal: Output of the logic gateLogic.LE61.Timer Out Signal: Timer OutputLogic.LE61.Out Signal: Latched Output (Q)Logic.LE61.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE62.Gate Out Signal: Output of the logic gateLogic.LE62.Timer Out Signal: Timer OutputLogic.LE62.Out Signal: Latched Output (Q)Logic.LE62.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE63.Gate Out Signal: Output of the logic gateLogic.LE63.Timer Out Signal: Timer OutputLogic.LE63.Out Signal: Latched Output (Q)Logic.LE63.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE64.Gate Out Signal: Output of the logic gateLogic.LE64.Timer Out Signal: Timer OutputLogic.LE64.Out Signal: Latched Output (Q)Logic.LE64.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE65.Gate Out Signal: Output of the logic gateLogic.LE65.Timer Out Signal: Timer OutputLogic.LE65.Out Signal: Latched Output (Q)Logic.LE65.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE66.Gate Out Signal: Output of the logic gateLogic.LE66.Timer Out Signal: Timer OutputLogic.LE66.Out Signal: Latched Output (Q)Logic.LE66.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE67.Gate Out Signal: Output of the logic gateLogic.LE67.Timer Out Signal: Timer OutputLogic.LE67.Out Signal: Latched Output (Q)Logic.LE67.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE68.Gate Out Signal: Output of the logic gateLogic.LE68.Timer Out Signal: Timer OutputLogic.LE68.Out Signal: Latched Output (Q)Logic.LE68.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE69.Gate Out Signal: Output of the logic gateLogic.LE69.Timer Out Signal: Timer OutputLogic.LE69.Out Signal: Latched Output (Q)Logic.LE69.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE70.Gate Out Signal: Output of the logic gateLogic.LE70.Timer Out Signal: Timer Output

314 www.eaton.com

Page 315: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE70.Out Signal: Latched Output (Q)Logic.LE70.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE71.Gate Out Signal: Output of the logic gateLogic.LE71.Timer Out Signal: Timer OutputLogic.LE71.Out Signal: Latched Output (Q)Logic.LE71.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE72.Gate Out Signal: Output of the logic gateLogic.LE72.Timer Out Signal: Timer OutputLogic.LE72.Out Signal: Latched Output (Q)Logic.LE72.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE73.Gate Out Signal: Output of the logic gateLogic.LE73.Timer Out Signal: Timer OutputLogic.LE73.Out Signal: Latched Output (Q)Logic.LE73.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE74.Gate Out Signal: Output of the logic gateLogic.LE74.Timer Out Signal: Timer OutputLogic.LE74.Out Signal: Latched Output (Q)Logic.LE74.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE75.Gate Out Signal: Output of the logic gateLogic.LE75.Timer Out Signal: Timer OutputLogic.LE75.Out Signal: Latched Output (Q)Logic.LE75.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE76.Gate Out Signal: Output of the logic gateLogic.LE76.Timer Out Signal: Timer OutputLogic.LE76.Out Signal: Latched Output (Q)Logic.LE76.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE77.Gate Out Signal: Output of the logic gateLogic.LE77.Timer Out Signal: Timer OutputLogic.LE77.Out Signal: Latched Output (Q)Logic.LE77.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE78.Gate Out Signal: Output of the logic gateLogic.LE78.Timer Out Signal: Timer OutputLogic.LE78.Out Signal: Latched Output (Q)Logic.LE78.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE79.Gate Out Signal: Output of the logic gateLogic.LE79.Timer Out Signal: Timer OutputLogic.LE79.Out Signal: Latched Output (Q)Logic.LE79.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE80.Gate Out Signal: Output of the logic gate

www.eaton.com 315

Page 316: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE80.Timer Out Signal: Timer OutputLogic.LE80.Out Signal: Latched Output (Q)Logic.LE80.Out inverted Signal: Negated Latched Output (Q NOT)

Switchgear/Breaker Input States

Name Description Assignment Via

CinBkr-52a-I Feed-back signal of the Bkr. (52a) [Control

/Breaker

/Pos Indicators wiring]CinBkr-52b-I Module Input State: Feed-back signal of the

Bkr.. (52b)[Control

/Breaker

/Pos Indicators wiring]Ready-I Module Input State: Breaker Ready [Control

/Breaker

/Pos Indicators wiring]Sys-in-Sync-I State of the module input: This signals has

to become true within the synchronization time. If not, switching is unsuccessful.

[Control

/Breaker

/Synchronous Switching]Ack TripCmd-I State of the module input: Acknowledgment

Signal (only for automatic acknowledgment). Module input signal

[Control

/Breaker

/Trip Manager]Interl CLOSE1-I State of the module input: Interlocking of

the CLOSE command[Control

/Breaker

/Interlockings]Interl CLOSE2-I State of the module input: Interlocking of

the CLOSE command[Control

/Breaker

/Interlockings]Interl CLOSE3-I State of the module input: Interlocking of

the CLOSE command[Control

/Breaker

/Interlockings]

316 www.eaton.com

Page 317: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

Interl OPEN1-I State of the module input: Interlocking of the OPEN command

[Control

/Breaker

/Interlockings]Interl OPEN2-I State of the module input: Interlocking of

the OPEN command[Control

/Breaker

/Interlockings]Interl OPEN3-I State of the module input: Interlocking of

the OPEN command[Control

/Breaker

/Interlockings]SC CLOSE-I State of the module input: Switching

CLOSE Command, e.g.: the state of the Logic or the state of the digital input.

[Control

/Breaker

/Ex OPEN/CLOSE Cmd]SC OPEN-I State of the module input: Switching OPEN

Command, e.g.: the state of the Logic or the state of the digital input.

[Control

/Breaker

/Ex OPEN/CLOSE Cmd]

Switchgear/Breaker Signals (Outputs States)

Name Description

SI SingleContactInd Signal: The Position of the Switchgear is detected by one auxiliary contact (pole) only. Thus indeterminate and disturbed Positions cannot be detected.

Pos not CLOSE Signal: Pos not CLOSEPos CLOSE Signal: Breaker is in CLOSE-PositionPos OPEN Signal: Breaker is in OPEN-PositionPos Indeterm Signal: Breaker is in Indeterminate PositionPos Disturb Signal: Breaker Disturbed - Undefined Breaker Position. The feed-

back signals (Position Indicators) contradict themselves. After expiring of a supervision timer this signal becomes true.

State Signal: Breaker Position (0 = Indeterminate, 1 = OPEN, 2 = CLOSE, 3 = Disturbed)

Ready Signal: Breaker is ready for operation.CES succesf Command Execution Supervision: Switching command executed

successfully.CES Disturbed Command Execution Supervision: Switching Command

unsuccessful. Switchgear in disturbed position.CES SAuthority Command Execution Supervision: Switching Command not

executed. No switching authority.

www.eaton.com 317

Page 318: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

CES SwitchgDir Command Execution Supervision: Switching Direction Control. A switchgear that is already OPEN should be switched OPEN again (doubly).

CES DoubleOperating Command Execution Supervision: A second switch command is in conflict with a pending one.

CES CLOSE durg OPEN Cmd Command Execution Supervision: CLOSE Command during a pending OPEN Command.

CES SG not ready Command Execution Supervision: Switchgear not ready.CES Field Interl Command Execution Supervision: Switching Command not

executed because of field interlocking.CES SyncTimeout Command Execution Supervision: Switching Command not

executed No Synchronization signal while t-sync was running.Prot CLOSE Signal: CLOSE command issued by the Prot module.TripCmd Signal: Trip CommandAck TripCmd Signal: Acknowledge Trip Command.Bwear Slow Breaker Signal: Slow Breaker Alarm.Res Bwear Slow Breaker Signal: Resetting the slow breaker alarm.CLOSE Cmd Signal: CLOSE command issued to the switchgear. Depending on

the setting the signal may include the CLOSE command of the Prot module.

OPEN Cmd Signal: OPEN command issued to the switchgear. Depending on the setting the signal may include the OPEN command of the Prot module.

CLOSE Cmd manual Signal: CLOSE Cmd manualOPEN Cmd manual Signal: OPEN Cmd manualCLOSE request Signal: Synchronous CLOSE request

Switching the Breaker at the PanelControl

Manually switching a switchgear at the device panel is possible at the following switching authorities:

• Local; and • Local and Remote.

Assumed the device displays the main screen:

1. Press the »Menu« softkey.

2. Select the »Control« menu by using the »up« or »down« softkeys and press the »right« arrow softkey button.

3. Select the »Control« menu by using the »up« or »down« softkeys and press the »right« arrow softkey button.

4. A symbol for the switchgear and its status (ON, OFF, intermediate or disturbed) is displayed.

5.

318 www.eaton.com

Page 319: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

6. Dependent on the status (ON/OFF), the switchgear can be switched ON or OFF by the corresponding softkey.

The current position of the switchgear will be visualized by different symbols:

Breaker State Symbol0

(Intermediate)

1(Off)

2(ON)

3(Disturbed)

Direct Commands of the Switching Authority

Parameter Description Setting Range Default Menu Path

Switching Authority

Switching Authority None,

Local,

Remote,

Local and Remote

Local [Control

/General Settings]

Signals of the Switching Authority

Name Description

Local Switching Authority: LocalRemote Switching Authority: Remote

Breaker Wear Features

The protective relay offers the following Breaker Wear features.

• Monitoring of the accumulated interrupted currents.• Slow breaker alarm.• Calculation of the Breaker Open Capacity »Bkr OPEN capacity«. 100% means that breaker

maintenance is mandatory now.

www.eaton.com 319

Page 320: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

• Breaker Wear Curve.• Monitoring of total CLOSE/OPEN cycles and alarm for max allowed CLOSE/OPEN cycles per hour.

Slow Breaker Alarm

An increase of the closing or opening time of the breaker is an indication for the maintenance need of this switchgear. If the measured time exceeds the time »t-Move OPEN« or »t-Move CLOSE«, the signal »BWEAR SLOW BREAKER« will be activated. This signal will be active until it is reset manually.

Breaker Wear Curve

In order to keep the breaker in good working condition, the breaker needs to be monitored. The breaker health (operation life) depends above all on:

• The number of CLOSE/OPEN cycles;• The amplitudes of the interrupting currents; and• The frequency that the breaker operates (operations per hour).

The User has to maintain the breaker accordingly to the maintenance schedule that is to be provided by the manufacturer (breaker operation statistics). By means of up to ten points that the User can replicate the breaker wear curve within menu [Control/Breaker/BWear]. Each point has two settings: the interrupt current in kilo amperes and the allowed operation counts. No matter how many points are used, the operation counts the last point as zero. The protective relay will interpolate the allowed operations based on the breaker wear curve. When the interrupted current is greater than the interrupt current at the last point, the protective relay will assume zero operation counts.

320 www.eaton.com

Page 321: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Global Protection Parameters of the Breaker Wear Module

Parameter Description Setting Range Default Menu Path

Operations Alarm

Service Alarm, too many Operations 1 - 100000 9999 [Control

/Breaker

/BWear]Isum Intr Alarm Alarm, the Sum (Limit) of interrupting

currents has been exceeded.0.00 – 2000.00 kA 100.00 kA [Control

/Breaker

/BWear]

www.eaton.com 321

0.1 1 10 1001

10

100

1 103×

1 104×0.0

100001.2

10000

8.0150

20.012

20.00

Breaker Maintenance Curve for a typical 25kV Breaker

Num

ber o

f Ope

ratio

ns

Interrupted Current in kA per operation

Page 322: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Isum Intr per hour Alarm

Alarm, the per hour Sum (Limit) of interrupting currents has been exceeded.

0.00 – 2000.00 kA 100.00 kA [Control

/Breaker

/BWear]Bwear Curve Fc

The Breaker Wear Curve defines the maximum allowed CLOSE/OPEN cycles depending on the brake currents. If the breaker maintenance curve is exceeded, an alarm will be issued. The breaker maintenance curve is to be taken from the technical data sheet of the breaker manufacturer. By means of the available points this curve is to be replicated.

Inactive,

Active

Inactive [Control

/Breaker

/BWear]

WearLevel Alarm

Breaker Wear curve Alarm Level in %

Only available if:Bwear Curve Fc = Active

0.00 - 100.00% 80.00% [Control

/Breaker

/BWear]WearLevel Lockout

Breaker Wear Curve Lockout Level in %

Only available if:Bwear Curve Fc = Active

0.00 - 100.00% 95.00% [Control

/Breaker

/BWear]Current1 Interrupted Current Level #1

Only available if:Bwear Curve Fc = Active

0.00 – 2000.00 kA 0.00 kA [Control

/Breaker

/BWear]Count1 Open Counts Allowed #1

Only available if:Bwear Curve Fc = Active

0 - 100000 10000 [Control

/Breaker

/BWear]Current2 Interrupted Current Level #2

Only available if:Bwear Curve Fc = Active

0.00 – 2000.00 kA 1.20 kA [Control

/Breaker

/BWear]Count2 Open Counts Allowed #2

Only available if:Bwear Curve Fc = Active

0 - 100000 10000 [Control

/Breaker

/BWear]Current3 Interrupted Current Level #3

Only available if:Bwear Curve Fc = Active

0.00 – 2000.00 kA 8.00 kA [Control

/Breaker

/BWear]

322 www.eaton.com

Page 323: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Count3 Open Counts Allowed #3

Only available if:Bwear Curve Fc = Active

0 - 100000 150 [Control

/Breaker

/BWear]Current4 Interrupted Current Level #4

Only available if:Bwear Curve Fc = Active

0.00 – 2000.00 kA 20.00 kA [Control

/Breaker

/BWear]Count4 Open Counts Allowed #4

Only available if:Bwear Curve Fc = Active

0 - 100000 12 [Control

/Breaker

/BWear]Current5 Interrupted Current Level #5

Only available if:Bwear Curve Fc = Active

0.00 – 2000.00 kA 20.00 kA [Control

/Breaker

/BWear]Count5 Open Counts Allowed #5

Only available if:Bwear Curve Fc = Active

0 - 100000 0 [Control

/Breaker

/BWear]Current6 Interrupted Current Level #6

Only available if:Bwear Curve Fc = Active

0.00 – 2000.00 kA 20.00 kA [Control

/Breaker

/BWear]Count6 Open Counts Allowed #6

Only available if:Bwear Curve Fc = Active

0 - 100000 0 [Control

/Breaker

/BWear]Current7 Interrupted Current Level #7

Only available if:Bwear Curve Fc = Active

0.00 – 2000.00 kA 20.00 kA [Control

/Breaker

/BWear]Count7 Open Counts Allowed #7

Only available if:Bwear Curve Fc = Active

0 - 100000 0 [Control

/Breaker

/BWear]Current8 Interrupted Current Level #8

Only available if:Bwear Curve Fc = Active

0.00 – 2000.00 kA 20.00 kA [Control

/Breaker

/BWear]

www.eaton.com 323

Page 324: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Count8 Open Counts Allowed #8

Only available if:Bwear Curve Fc = Active

0 - 100000 0 [Control

/Breaker

/BWear]Current9 Interrupted Current Level #9

Only available if:Bwear Curve Fc = Active

0.00 – 2000.00 kA 20.00 kA [Control

/Breaker

/BWear]Count9 Open Counts Allowed #9

Only available if:Bwear Curve Fc = Active

0 - 100000 0 [Control

/Breaker

/BWear]Current10 Interrupted Current Level #10

Only available if:Bwear Curve Fc = Active

0.00 – 2000.00 kA 20.00 kA [Control

/Breaker

/BWear]Count10 Open Counts Allowed #10

Only available if:Bwear Curve Fc = Active

0 - 100000 0 [Control

/Breaker

/BWear]

Breaker Wear Signals (Output States)

Name Description

Operations Alarm Signal: Service Alarm, too many OperationsIsum Intr trip: IA Signal: Maximum permissible Summation of the interrupting

(tripping) currents exceeded: IAIsum Intr trip: IB Signal: Maximum permissible Summation of the interrupting

(tripping) currents exceeded: IBIsum Intr trip: IC Signal: Maximum permissible Summation of the interrupting

(tripping) currents exceeded: ICIsum Intr trip Signal: Maximum permissible Summation of the interrupting

(tripping) currents exceeded in at least one phase.Res TripCmdCr Signal: Resetting of the Counter: total number of trip commandsRes Isum trip Signal: Reset summation of the tripping currentsWearLevel Alarm Signal: Breaker Wear curve Alarm Level in %WearLevel Lockout Signal: Breaker Wear Curve Lockout Level in %Res Bwear Curve Signal: Res Bwear CurveIsum Intr per hour Alarm Signal: Isum Intr per hour AlarmRes Isum Intr per hour Alarm Signal: Res Isum Intr per hour Alarm

324 www.eaton.com

Page 325: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Breaker Wear Counter Values

Value Description Menu Path

TripCmd Cr Counter: Total number of trips of the switchgear (breaker, load break switch … ). Resettable with Total or All.

[Operation

/Count and RevData

/Breaker]

Breaker Wear Values

Value Description Default Size Menu Path

Isum trip IA Summation of the tripping currents phase

0.00 A 0.00 – 1000.00 A

[Operation

/Count and RevData

/Breaker]Isum trip IB Summation of the tripping currents

phase0.00 A 0.00 –

1000.00 A[Operation

/Count and RevData

/Breaker]Isum trip IC Summation of the tripping currents

phase0.00 A 0.00 –

1000.00 A[Operation

/Count and RevData

/Breaker]Isum Intr per hour Sum per hour of interrupting

currents.0.00 kA 0.00 –

1000.00 kA[Operation

/Count and RevData

/Breaker]Bkr OPEN capacity Bkr. OPEN capacity. 100% means,

that the breaker is to be maintenanced.

0.0% 0.0 - 100.0% [Operation

/Count and RevData

/Breaker]

Direct Commands of the Breaker Wear Module

Parameter Description Setting Range Default Menu Path

Res TripCmdCr Resetting of the Counter: total number of trip commands

Inactive,

Active

Inactive [Operation

/Reset]Res Isum trip Reset summation of the tripping currents Inactive,

Active

Inactive [Operation

/Reset]Res Isum Intr per hour

Sum per hour of interrupting currents. Inactive,

Active

Inactive [Operation

/Reset]

www.eaton.com 325

Page 326: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Res Bkr OPEN capacity

Resetting of the Bkr. OPEN capacity. 100% means, that the breaker is to be maintenanced.

Inactive,

Active

Inactive [Operation

/Reset]

326 www.eaton.com

Page 327: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Protective Elements

Directional Feature – Phase Current

All elements can be selected as »Non-directional/Forward/Reverse« operated. This has to be done in the »Device Planning« menu.

For the direction detection it is mandatory, that the required voltages exceed 0.35 V and the required currents exceed 10 mA.

For the case, that the voltage drops below 0.35 V, the last angle between the operating and polarizing quantity will be used for the directional detection.

Overcurrent protection elements, time inverse or instantaneous or time delay, etc., can trip in a specified fault current direction. When the trip direction is set to »Non-directional«, the direction detection takes no effect. When it is set to »Forward«, a trip is only permitted in the forward direction where fault current lies within ± 90° around the maximum torque angle »Phase MTA«. When it is set to »Reverse«, a trip is only permitted in reverse direction where fault current lies within ± 90° around the opposite of the maximum torque angle.

In the case of a 3-phase nearly zero voltage fault, the memorized voltage, or prefault voltages, is used to establish the correct fault direction.

www.eaton.com 327

Page 328: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

328 www.eaton.com

Prot

.I di

r n p

oss

Prot

.I di

r rev

Prot

.I di

r fw

d

VA IA IB ICVCVB

Prot

.I Ph

ase

MTA

φ VAB

VA

VBC

VBVC

A

VC

VBC

I1

Phas

e M

TA

Rev

erse

Forw

ard

Volta

ge m

emor

y

(For

war

d)

(Rev

erse

)

(Not

pos

sibl

e)

Prot

-Ph

ase

failu

re D

irect

ion

Det

ectio

n

AND

AND

AND

Prot

.Pha

se S

eque

nce

Prot

.Pic

kup

Page 329: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Phase Directional Supervision Logic

www.eaton.com 329

Non

-dire

ctio

nal

Rev

erse

Forw

ard

Nam

e.M

ode

AND

AND

Prot

.I di

r fw

d

Prot

.I di

r rev

Nam

e. F

ault

in P

roje

cted

Dire

ctio

n

(For

war

d)

(Rev

erse

)

Dire

ctio

n D

ecis

ion

Phas

e ov

ercu

rrent

AND

Prot

.I di

r n p

oss

(Not

pos

sibl

e)

Inac

tive

Activ

e

Nam

e.N

ondi

r Trip

at V

=0

Nam

e =

I[1]..

.[n]

Dev

ice

Plan

ning

9O

R

Page 330: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

50P/67P- DEFT Overcurrent ProtectionAvailable Elements50P[1] ,50P[2] ,50P[3]

If using inrush blockings, the tripping delay of the current protection functions must be at least 30 ms or more in order to prevent faulty trippings (applies only to devices which are equipped with Inrush protection)..

All overcurrent protective elements are identically structured.

All ANSI 67 elements (directional overcurrent protection), will be displayed as ANSI 50 elements. That means, that the name of an ANSI 50 element wont change, if it is set within the device planning from “non-directional” to “directional”.

For each element the following characteristic is available:

• DEFT (definite time).

Explanation

This element offers a criterion setting. The criterion setting tells if the threshold is based on the fundamental (Phasor) or RMS.

For Tripping curves, please refer to the “Appendix/Instantaneous Current Curves (Phase)” section.

330 www.eaton.com

t = Tripping delay

I = Fault current

Pickup = If the pickup value is exceeded, the module/element starts to time out to trip.

Page 331: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 331

50P/

67P[

1]...

[n]

Nam

e =

50P[

1]...

[n]

Fund

.

RM

S

Nam

e.C

riter

ion

φ

Nam

e.Tr

ipC

md

Nam

e.Pi

ckup

IA

Nam

e.Pi

ckup

IB

Nam

e.Pi

ckup

IC Nam

e.Tr

ip

IH2.

Blo

Phas

e A

IH2.

Blo

Phas

e B

IH2.

Blo

Phas

e C

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs**

Nam

e.Pi

ckup

IA IB IC

AND

AND

AND

Nam

e.Tr

ip P

hase

A

Nam

e.Tr

ip P

hase

B

Nam

e.Tr

ip P

hase

C

Nam

e.Pi

ckup

Ple

ase

Ref

er to

Dia

gram

: Trip

Blo

ckin

gs

Inac

tive

Activ

e

Nam

e.IH

2 Bl

o

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

AND

AND

AND

Nam

e.IH

2 Bl

o*

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

5 6 74 3

Ple

ase

Ref

er to

Dia

gram

: IH

2*

Ple

ase

Ref

er to

Dia

gram

: IH

2*

Ple

ase

Ref

er to

Dia

gram

: IH

2*

1516a

17a

18a

24a

25a

26a

14

OR

OR

AND

AND

AND

AND

AND

φD

EFT

Nam

e.Pi

ckup

Nam

e.t

Base

d on

abo

ve p

aram

eter

s,

tripp

ing

times

and

rese

t mod

es w

ill

be c

alcu

late

d by

the

devi

ce.

*=Applies only to devices that offer Inrush Protection

t 0

Nam

e.* I

[1]..

.[n] F

ault

in P

roje

cted

Dire

ctio

n9

Ple

ase

Ref

er to

Dia

gram

: Dire

ctio

n D

ecis

ion

Pha

se o

verc

urre

nt

Page 332: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Device Planning Parameters of the 50P/67P Module

Parameter Description Options Default Menu Path

Mode Mode 50P[1]: Non-directional,

Forward,

Reverse

50P[2]: Non-directional,

Forward,

Reverse

50P[3]: Do not use,

Non-directional,

Forward,

Reverse

Non-directional

[Device Plan-ning]

Global Protection Parameters of the 50P/67P Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/50P[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/50P[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/50P[1]]Rvs Blo Reverse Blocking, if Reverse Blocking is

activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/50P[1]]

332 www.eaton.com

Page 333: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

AdaptSet 1 Assignment Adaptive Parameter 1 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/50P[1]]AdaptSet 2 Assignment Adaptive Parameter 2 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/50P[1]]AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/50P[1]]AdaptSet 4 Assignment Adaptive Parameter 4 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/50P[1]]

Setting Group Parameters of the 50P/67P Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

50P[1]: Active

50P[2]: Active

50P[3]: Inactive

[Protection Para

/<n>

/I-Prot

/50P[1]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/50P[1]]Rvs Blo Fc Activate (allow) or inactivate (disallow)

reverse blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/element are blocked that are configured "Rvs Blo Fc = active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/50P[1]]

www.eaton.com 333

Page 334: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Blo TripCmd Permanent blocking of the Trip Command of the module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/50P[1]]ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/50P[1]]

Criterion Measuring method: fundamental or Reset Fundamental,

True RMS,

I2

True RMS [Protection Para

/<n>

/I-Prot

/50P[1]]Pickup

If the pickup value is exceeded, the module/element starts to time out to trip.

Only available if: Characteristic = DEFT Or Characteristic = INV Minimum of the setting range If: VRestraint = Active Minimum of the setting range If: VRestraint = Inactive

0.02 – 40.00 In 50P[1]: 2 In

50P[2]: 2.5 In

50P[3]: 3.0 In

[Protection Para

/<n>

/I-Prot

/50P[1]]

t

Tripping delay

Only available if: Characteristic = DEFT

0.00 – 300.00 s 50P[1]: 0 s

50P[2]: 0.25 s

50P[3]: 0.25 s

[Protection Para

/<n>

/I-Prot

/50P[1]]

50P/67P Module Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking 1 [Protection Para

/Global Prot Para

/I-Prot

/50P[1]]

334 www.eaton.com

Page 335: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

ExBlo2-I Module Input State: External Blocking 2 [Protection Para

/Global Prot Para

/I-Prot

/50P[1]]ExBlo TripCmd-I Module Input State: External Blocking of the

Trip Command[Protection Para

/Global Prot Para

/I-Prot

/50P[1]]Rvs Blo-I Module Input State: Reverse Blocking [Protection Para

/Global Prot Para

/I-Prot

/50P[1]]AdaptSet1-I Module Input State: Adaptive Parameter 1 [Protection Para

/Global Prot Para

/I-Prot

/50P[1]]AdaptSet2-I Module Input State: Adaptive Parameter 2 [Protection Para

/Global Prot Para

/I-Prot

/50P[1]]AdaptSet3-I Module Input State: Adaptive Parameter 3 [Protection Para

/Global Prot Para

/I-Prot

/50P[1]]AdaptSet4-I Module Input State: Adaptive Parameter 4 [Protection Para

/Global Prot Para

/I-Prot

/50P[1]]

www.eaton.com 335

Page 336: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

50P/67P Module Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingRvs Blo Signal: Reverse BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup IA Signal: Pickup IAPickup IB Signal: Pickup IBPickup IC Signal: Pickup ICPickup Signal: PickupTrip Phase A Signal: General Trip Phase ATrip Phase B Signal: General Trip Phase BTrip Phase C Signal: General Trip Phase CTrip Signal: TripTripCmd Signal: Trip CommandActive AdaptSet Active Adaptive ParameterDefaultSet Signal: Default Parameter SetAdaptSet 1 Signal: Adaptive Parameter 1AdaptSet 2 Signal: Adaptive Parameter 2AdaptSet 3 Signal: Adaptive Parameter 3AdaptSet 4 Signal: Adaptive Parameter 4

Commissioning: Overcurrent Protection, directional [ANSI 50P/67P]

Object to be tested:

• For each directional overcurrent element is to be measured: the total tripping time (recommendation) or alternatively tripping delays and the drop-out ratios; each time 3 x single-phase and 1 x three-phase.

Especially in Holmgreen connections, wiring errors can happen easily and these are then detected safely. By measuring the total tripping time, it can be ensured that the secondary wiring is OK (from the terminal on, up to the trip coil of the Breaker).

Eaton recommends measuring the total tripping time instead of the tripping delay. The tripping delay should be specified by the User. The total tripping time is measured at the position signaling contact of the breaker (not at the relay output contacts!).

Total tripping time = tripping delay (please refer to the tolerances of the protection elements) + breaker operating time (about 50 ms)

Please take the breaker operating times from the technical data specified in the relevant documentation provided by the breaker manufacturer.

336 www.eaton.com

Page 337: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Necessary means

• Synchronizable current and voltage sources• Optional: ampere meters • Timer

Procedure

Synchronize the 3-phase current and voltage sources with each other. Then simulate the tripping directions to be tested by the angle between current and voltage.

Testing the threshold values (3 x single-phase and 1 x three-phase)

Each time feed a current which is about 3-5% above the threshold value for activation/tripping. Then check the threshold values.

Testing the total tripping delay (recommendation)

Measure the total tripping times at the auxiliary contacts of the Brk. (Brk. tripping).

Testing the trip delay (measured at the relay output)

Measure the tripping times at the relay output.

Testing the drop-out ratio

Reduce the current to 97% below the trip value and check the dropout ratio.

Successful test result

The measured total tripping delays or individual tripping delays, threshold values and drop-out ratios correspond with those values, specified in the adjustment list. Permissible deviations/tolerances can be found under Technical Data.

51P/67P - INV Overcurrent-ProtectionAvailable Elements51P[1]

If using inrush blockings, the tripping delay of the current protection functions must be at least 30 ms or more in order to prevent faulty trippings (applies only to devices which are equipped with Inrush protection).

All overcurrent protective elements are identically structured.

All ANSI 67 elements (directional overcurrent protection), will be displayed as ANSI 51 elements. That means, that the name of an ANSI 51 element wont change, if it is set within the device planning from “non-directional” to “directional”.

www.eaton.com 337

Page 338: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

For each element, the following characteristics are available:

• NINV (IEC/XInv);• VINV (IEC/XInv);• LINV (IEC/XInv);• EINV (IEC/XInv);• MINV (ANSI/XInv);• VINV (ANSI/XInv);• EINV (ANSI/XInv);• Thermal Flat;• Therm Flat IT;• Therm Flat I2T; and• Therm Flat I4T.

For tripping curves please refer to the “Appendix/Time Current Curves (PHASE)” section.

338 www.eaton.com

Page 339: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 339

Fund

.

RM

S

Nam

e.C

riter

ion

φ

Nam

e.Tr

ipC

md

Nam

e.Pi

ckup

IA

Nam

e.Pi

ckup

IB

Nam

e.Pi

ckup

IC Nam

e.Tr

ip

IH2.

Blo

Phas

e A

IH2.

Blo

Phas

e B

IH2.

Blo

Phas

e C

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs**

Nam

e.Pi

ckup

IA IB IC

AND

AND

AND

Nam

e.Tr

ip P

hase

A

Nam

e.Tr

ip P

hase

B

Nam

e.Tr

ip P

hase

C

Nam

e.Pi

ckup

Ple

ase

Ref

er to

Dia

gram

: Trip

Blo

ckin

gs

Inac

tive

Activ

e

Nam

e.IH

2 Bl

o

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals) AN

D

AND

AND

Nam

e.IH

2 Bl

o*

Imax

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

5 6 74 3

Plea

se R

efer

to D

iagr

am: I

H2*

Ple

ase

Ref

er to

Dia

gram

: IH

2*

Ple

ase

Ref

er to

Dia

gram

: IH

2*

1516b

17b

18b

24b

25b

26b

14

OR

OR

AND

AND

AND

AND

AND

φ INV

Imax

Nam

e.t-r

eset

Nam

e.t-m

ultip

lier

Nam

e.C

urve

Sha

pe

Nam

e.R

eset

Mod

e

Base

d on

abo

ve p

aram

eter

s,

tripp

ing

times

and

rese

t mod

es w

ill

be c

alcu

late

d by

the

devi

ce.

51P/

67P[

1]...

[n]

Nam

e =

51P/

67P[

1]...

[n]

*=Applies only to devices that offer Inrush Protection

Nam

e.* I

[1]..

.[n] F

ault

in P

roje

cted

Dire

ctio

n9

Plea

se R

efer

to D

iagr

am: D

irect

ion

Dec

isio

n Ph

ase

over

curre

nt

Page 340: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Device Planning Parameters of the 51P/67P Module

Parameter Description Options Default Menu Path

Mode Mode Non-directional,

Forward,

Reverse

Non-directional

[Device Plan-ning]

Global Protection Parameters of the 51P/67P Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/51P[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/51P[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/51P[1]]Rvs Blo Reverse Blocking, if Reverse Blocking is

activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/51P[1]]AdaptSet 1 Assignment Adaptive Parameter 1 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/51P[1]]

340 www.eaton.com

Page 341: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

AdaptSet 2 Assignment Adaptive Parameter 2 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/51P[1]]AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/51P[1]]AdaptSet 4 Assignment Adaptive Parameter 4 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/51P[1]]

Setting Group Parameters of the 51P/67P Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Active [Protection Para

/<n>

/I-Prot

/51P[1]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51P[1]]Rvs Blo Fc Activate (allow) or inactivate (disallow)

reverse blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/element are blocked that are configured "Rvs Blo Fc = active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51P[1]]Blo TripCmd Permanent blocking of the Trip Command

of the module/element.Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51P[1]]

www.eaton.com 341

Page 342: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51P[1]]

Criterion Measuring method: fundamental or Reset Fundamental,

True RMS,

I2

True RMS [Protection Para

/<n>

/I-Prot

/51P[1]]Pickup

If the pickup value is exceeded, the module/element starts to time out to trip.

Minimum of the setting range If: VRestraint = Active Minimum of the setting range If: VRestraint = Inactive

0.02 – 40.00 In 1.00 In [Protection Para

/<n>

/I-Prot

/51P[1]]Curve Shape

Characteristic IEC NINV,

IEC VINV,

IEC EINV,

IEC LINV,

ANSI MINV,

ANSI VINV,

ANSI EINV,

Therm Flat,

IT,

I2T,

I4T

ANSI MINV [Protection Para

/<n>

/I-Prot

/51P[1]]

t-multiplier

Time multiplier/tripping characteristic factor. The setting range depends on the selected tripping curve.

0.02 - 20.00 1 [Protection Para

/<n>

/I-Prot

/51P[1]]

342 www.eaton.com

Page 343: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Reset Mode

Reset Mode Instantaneous,

t-delay,

Calculated

Calculated [Protection Para

/<n>

/I-Prot

/51P[1]]t-reset

Reset time for intermittent phase failures (INV characteristics only)

Available if:Reset Mode = t-delay

0.00 – 60.00 s 0 s [Protection Para

/<n>

/I-Prot

/51P[1]]

51P/67P Module Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking1 [Protection Para

/Global Prot Para

/I-Prot

/51P[1]]ExBlo2-I Module Input State: External Blocking2 [Protection Para

/Global Prot Para

/I-Prot

/51P[1]]ExBlo TripCmd-I Module Input State: External Blocking of the

Trip Command[Protection Para

/Global Prot Para

/I-Prot

/51P[1]]Rvs Blo-I Module Input State: Reverse Blocking [Protection Para

/Global Prot Para

/I-Prot

/51P[1]]AdaptSet1-I Module Input State: Adaptive Parameter1 [Protection Para

/Global Prot Para

/I-Prot

/51P[1]]

www.eaton.com 343

Page 344: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

AdaptSet2-I Module Input State: Adaptive Parameter2 [Protection Para

/Global Prot Para

/I-Prot

/51P[1]]AdaptSet3-I Module Input State: Adaptive Parameter3 [Protection Para

/Global Prot Para

/I-Prot

/51P[1]]AdaptSet4-I Module Input State: Adaptive Parameter4 [Protection Para

/Global Prot Para

/I-Prot

/51P[1]]

51P/67P Module Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingRvs Blo Signal: Reverse BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup IA Signal: Pickup IAPickup IB Signal: Pickup IBPickup IC Signal: Pickup ICPickup Signal: PickupTrip Phase A Signal: General Trip Phase ATrip Phase B Signal: General Trip Phase BTrip Phase C Signal: General Trip Phase CTrip Signal: TripTripCmd Signal: Trip CommandActive AdaptSet Active Adaptive ParameterDefaultSet Signal: Default Parameter SetAdaptSet 1 Signal: Adaptive Parameter 1AdaptSet 2 Signal: Adaptive Parameter 2AdaptSet 3 Signal: Adaptive Parameter 3AdaptSet 4 Signal: Adaptive Parameter 4

344 www.eaton.com

Page 345: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Commissioning: Overcurrent Protection, Non-directional [ANSI 51P/67P]

Object to be tested:

• For each directional overcurrent element is to be measured: the total tripping time (recommendation) or alternatively tripping delays and the drop-out ratios; each time 3 x single-phase and 1 x three-phase.

Especially in Holmgreen connections, wiring errors can happen easily and these are then detected safely. By measuring the total tripping time, it can be ensured that the secondary wiring is OK (from the terminal on, up to the trip coil of the Breaker).

Eaton recommends measuring the total tripping time instead of the tripping delay. The tripping delay should be specified by the User. The total tripping time is measured at the position signaling contact of the breaker (not at the relay output contacts!).

Total tripping time = tripping delay (please refer to the tolerances of the protection elements) + breaker operating time (about 50 ms)

Please take the breaker operating times from the technical data specified in the relevant documentation provided by the breaker manufacturer.

Necessary means

• Synchronizable current and voltage sources;• Optional: ampere meters; and• Timer.

Procedure

Synchronize the 3-phase current and voltage sources with each other. Then simulate the tripping directions to be tested by the angle between current and voltage.

Testing the threshold values (3 x single-phase and 1 x three-phase)

Each time feed a current which is about 3-5% above the threshold value for activation/tripping. Then check the threshold values.

Testing the total tripping delay (recommendation)

Measure the total tripping times at the auxiliary contacts of the Brk. (Brk. tripping).

Testing the trip delay (measured at the relay output)

Measure the tripping times at the relay output.

Testing the drop-out ratio

Reduce the current to 97% below the trip value and check the dropout ratio.

Successful test result

The measured total tripping delays or individual tripping delays, threshold values and drop-out ratios correspond with those values, specified in the adjustment list. Permissible deviations/tolerances can be found under Technical Data.

www.eaton.com 345

Page 346: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

51V – Voltage Restraint Overcurrent-Protection

The 51P[2] and 51P[3] elements can be used for Voltage Restraint if the Parameter »VRestraint« is set to »active« within the Parameter Set.

51P[2] ,51P[3]

All voltage restraint overcurrent protective elements are identically structured.

All ANSI 67 elements (directional overcurrent protection), will be displayed as ANSI 51 elements. That means, that the name of an ANSI 51 element wont change, if it is set within the device planning from “non-directional” to “directional”.

The 51V element restrains operation which reduces pickup levels. This allows the User to lower the pickup value of the 51V elements with the corresponding phase input voltage (phase-to-phase or phase-to-ground, depending on the setting of »Main VT con« within the System Parameters). When the minimum fault phase current is close to the load current, it may make the phase time overcurrent protection coordination difficult. In this case, an undervoltage function may be used to alleviate this situation. When the voltage (RMS) is low, the phase time overcurrent pickup threshold may be set low accordingly, so that the phase time overcurrent protection may achieve adequate sensitivity and better coordination. The device uses a simple linear model to determine the effective pickup by characterizing the relationship between the voltage and the phase time overcurrent pickup threshold.

Once the voltage restraint is activated, the effective phase time overcurrent pickup threshold will be the calculated Pickup% times the phase time overcurrent pickup setting. The effective pickup threshold must be within the setting range allowed and, if it is less, the minimum pickup value will be used.

That means:Vmin = 0.25*Vmax;• Pickup%min = 25%;• Pickup% = 25%, if V <= Vmin;• Pickup% = 1/Vmax*(V - Vmin) + 25%, if Vmin < V < Vmax;• Pickup% = 100%, if V >= Vmax;

346 www.eaton.com

Pickup%

VRestraint max25% VRestraint max

25%

100%

V

Page 347: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

For tripping curves, please refer to the“Appendix/Instantaneous Current Curves (Phase)” section.

If this element should be blocked in case of a Loss Of Potential, »LOP BLO« has to be set to »active«.

Definition of Vn: Vn is dependent on the System Parameter setting of "Main VT con".

In case that within the System Parameters "Main VT con" is set to "Open-Delta":

Vn=Main VT sec .

In case that "Main VT con" is set to "Wye":

Vn= MainVT sec3

www.eaton.com 347

Name.TripCmd

Name.Pickup IA

Name.Pickup IB

Name.Pickup IC

Name.Trip

IH2.Blo Phase A

IH2.Blo Phase B

IH2.Blo Phase C

Please Refer to Diagram: Blockings**

51V Pickup = %Pickup * 51P

Pickup

IA

IB

IC

AND

AND

AND

Name.Trip Phase A

Name.Trip Phase B

Name.Trip Phase C

Name.Pickup

Please Refer to Diagram: Trip Blockings

Inactive

Active

Name.IH2 Blo

(Element is not deactivated and no active blocking signals)

AND

AND

AND

Name.IH2 Blo*

Imax

(Tripping command not deactivated or blocked. )

5

6

7

4

3

Please Refer to Diagram: IH2*

Please Refer to Diagram: IH2*

Please Refer to Diagram: IH2*

15

16b

17b

18b

24b

25b

26b

14

OROR

AND

AND

AND

AND

AND

φINV

Imax

Name.t-reset

Name.t-multiplier

Name.Curve Shape

Name.Reset Mode

Based on above parameters, tripping times and reset modes will be calculated by the device.

51V[1]...[n]

Name = 51V[1]...[n]

*=Applies only to devices that offer Inrush P

rotection

VA

VB

VC

φ

Pickup%

25%

100%

V

25%

VRestraint max

%Pickup

RMS

RMS

RMS

RMS

RMS

RMS

Page 348: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Device Planning Parameters of the 51V Module

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Non-directional,

Forward,

Reverse

Non-directional

[Device Plan-ning]

Global Protection Parameters of the 51V Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/51P[2]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/51P[2]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/51P[2]]Rvs Blo Reverse Blocking, if Reverse Blocking is

activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/51P[2]]AdaptSet 1 Assignment Adaptive Parameter 1 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/51P[2]]

348 www.eaton.com

Page 349: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

AdaptSet 2 Assignment Adaptive Parameter 2 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/51P[2]]AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/51P[2]]AdaptSet 4 Assignment Adaptive Parameter 4 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/51P[2]]

Setting Group Parameters of the 51V Module

In the case that Voltage Restraint is active (Vrestraint=active), the minimum pickup that can be set is 0.1 In.

In the case that Voltage Restraint is inactive (Vrestraint=inactive), the minimum pickup that can be set is 0.01 In.

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

51P[2]: Active

51P[3]: Inactive

[Protection Para

/<n>

/I-Prot

/51P[2]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51P[2]]Rvs Blo Fc Activate (allow) or inactivate (disallow)

reverse blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/element are blocked that are configured "Rvs Blo Fc = active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51P[2]]

www.eaton.com 349

Page 350: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Blo TripCmd Permanent blocking of the Trip Command of the module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51P[2]]ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51P[2]]

Criterion Measuring method: fundamental or Reset Fundamental,

True RMS,

I2

True RMS [Protection Para

/<n>

/I-Prot

/51P[2]]Pickup If the pickup value is exceeded, the module/

element starts to time out to trip.

Minimum of the setting range If: VRestraint = Active Minimum of the setting range If: VRestraint = Inactive

0.02 – 40.00 In 1.00 In [Protection Para

/<n>

/I-Prot

/51P[2]]Curve Shape

Characteristic IEC NINV,

IEC VINV,

IEC EINV,

IEC LINV,

ANSI MINV,

ANSI VINV,

ANSI EINV,

Therm Flat,

IT,

I2T,

I4T

ANSI MINV [Protection Para

/<n>

/I-Prot

/51P[2]]

350 www.eaton.com

Page 351: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

t-multiplier

Time multiplier/tripping characteristic factor. The setting range depends on the selected tripping curve.

0.02 - 20.00 51P[2]: 2

51P[3]: 3

[Protection Para

/<n>

/I-Prot

/51P[2]]Reset Mode

Reset Mode Instantaneous,

t-delay,

Calculated

Calculated [Protection Para

/<n>

/I-Prot

/51P[2]]t-reset

Reset time for intermittent phase failures (INV characteristics only).

Available if:Reset Mode = t-delay

0.00 – 60.00 s 0 s [Protection Para

/<n>

/I-Prot

/51P[2]]VRestraint

Voltage Restraint Protection Inactive,

Active

Active [Protection Para

/<n>

/I-Prot

/51P[2]]VRestraint max

Maximum voltage restraint level. Definition of Vn: Vn is dependent on the System Parameter setting of "Main VT con". When the System Parameters "Main VT con" is set to "Open-Delta" , "Vn = Main VT sec ". When the System Parameters "Main VT con" is set to "Wye", "Vn = Main VT sec/SQRT(3)".

Only available if: VRestraint = Active

0.04 – 1.30 Vn 1.00 Vn [Protection Para

/<n>

/I-Prot

/51P[2]]

LOP Blo

Blocking if voltage transformer failure detected. LOP (Loss of Potential)

Only available if: VRestraint = Active

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51P[2]]

www.eaton.com 351

Page 352: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

51V Module Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking 1 [Protection Para

/Global Prot Para

/I-Prot

/51P[2]]ExBlo2-I Module Input State: External Blocking 2 [Protection Para

/Global Prot Para

/I-Prot

/51P[2]]ExBlo TripCmd-I Module Input State: External Blocking of the

Trip Command[Protection Para

/Global Prot Para

/I-Prot

/51P[2]]Rvs Blo-I Module Input State: Reverse Blocking [Protection Para

/Global Prot Para

/I-Prot

/51P[2]]AdaptSet1-I Module Input State: Adaptive Parameter 1 [Protection Para

/Global Prot Para

/I-Prot

/51P[2]]AdaptSet2-I Module Input State: Adaptive Parameter 2 [Protection Para

/Global Prot Para

/I-Prot

/51P[2]]AdaptSet3-I Module Input State: Adaptive Parameter 3 [Protection Para

/Global Prot Para

/I-Prot

/51P[2]]

352 www.eaton.com

Page 353: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

AdaptSet4-I Module Input State: Adaptive Parameter 4 [Protection Para

/Global Prot Para

/I-Prot

/51P[2]]

51V Module Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingRvs Blo Signal: Reverse BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup IA Signal: Pickup IAPickup IB Signal: Pickup IBPickup IC Signal: Pickup ICPickup Signal: PickupTrip Phase A Signal: General Trip Phase ATrip Phase B Signal: General Trip Phase BTrip Phase C Signal: General Trip Phase CTrip Signal: TripTripCmd Signal: Trip CommandActive AdaptSet Active Adaptive ParameterDefaultSet Signal: Default Parameter SetAdaptSet 1 Signal: Adaptive Parameter 1AdaptSet 2 Signal: Adaptive Parameter 2AdaptSet 3 Signal: Adaptive Parameter 3AdaptSet 4 Signal: Adaptive Parameter 4

Commissioning: Voltage Restraint [ANSI 51V]

Object to be tested:

Signals to be measured for Voltage Restraint element: the threshold values, total tripping time (recommended), or alternatively tripping delays and the dropout ratios; each time 3 x single-phase and 1 x three-phase.

www.eaton.com 353

Page 354: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Eaton recommends measuring the total tripping time instead of the tripping delay. The tripping delay should be specified by the customer. The total tripping time is measured at the position signaling contact of the breaker (not at the relay output contacts!).

Total tripping time = tripping delay (please refer to the tolerances of the protection stages)+ breaker operating time (about 50 ms)

Please take the breaker operating times from the technical data specified in the relevant documentation provided by the breaker manufacturer.

Necessary means:

• Current source;• Voltage Source;• Current and Voltage meters; and• Timer.

Procedure:

Testing the threshold values (3 x single-phase and 1 x three-phase)Feed %Pickup voltage. For each test performed, feed a current that is about 3-5% above the threshold value for activation/tripping. Then check if the pickup values are %Pickup of the value according to 51P protection.

Testing the total tripping delay (recommendation)Measure the total tripping times at the auxiliary contacts of the breakers (breaker tripping).

Testing the tripping delay (measuring at the relay output contact)Measure the tripping times at the relay output contact.

Testing the dropout ratioReduce the current to 97% below the trip value and check the dropout ratio.

Successful test resultThe measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond with those values specified in the adjustment list. Permissible deviations/tolerances can be found under Technical Data.

Directional Features for Measured (IX) Ground Fault Elements 50X/51XAll ground fault elements can be selected as »Non-directional/Forward/Reverse« operated. This has to be done in the »Device Planning« menu.

For the direction detection, it is mandatory that the required voltages exceed 0.35 V and the required currents exceed 10 mA. An exception is the measured sensitive ground current which has to exceed 1 mA.

For the case that the voltage drops below 0.35 V, the last angle between the operating and polarizing quantity will be used for the directional detection.

354 www.eaton.com

Page 355: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Important Definitions

Polarizing Quantity: This is the quantity that is used as a reference value. The polarizing quantity can be selected by the parameter »IX Direction Control« in the [System Para/Direction] menu as follows:

• »IX 3V0«: The neutral voltage selected by the parameter »3V0 Source« will be used as the polarizing quantity. The traditional way to polarize a ground fault element is to use neutral voltage (3V0). The neutral voltage can, however, be either »measured« or »calculated«. This can be selected by the parameter »3V0 Source« in the [System Para/Direction] menu.

• »IX Neg«: With this selection, the negative phase sequence voltage and current (Polarizing: V2/Operating: I2) will be used to detect direction. The monitored current is still the measured residual current IX.

• »IX Dual«: For this method, the negative phase sequence voltage »V2« will be used as polarizing quantity if »V2« and »I2« are available, otherwise 3V0 will be used. The operating quantity is either I2 if »V2« and »I2« are available, else IX.

The following table gives the User a quick overview of the all possible directional settings.

50X/51X Direction Decision by Angle Between:

[System Para/ Direction]

The Following Angle Has to Be Set:

[System Para/Direction]:

IX Dir Cntrl =

[System Para/Direction]:

3V0 Source =

Measured ground current and neutral voltage:IX, 3V0 (measured)

Ground MTA IX 3V0 Measured

Measured ground current and neutral voltage:IX, 3V0 (calculated)

Ground MTA IX 3V0 Calculated

Negative sequence voltage and currentI2, V2

90° + Phase MTA IX Neg N.A.

Negative phase sequence current and voltage (preferred), measured ground current and neutral voltage (alternatively):I2, V2 (if available)or else:IX, 3V0 (measured)

If V2 and I2 are available: 90° + Phase MTA

else:

Ground MTA

IX Dual Measured

Negative phase sequence current and voltage (preferred), measured ground current and neutral voltage (alternatively):I2, V2 (if available)or else:IX, 3V0 (calculated)

If V2 and I2 are available: 90° + Phase MTA

else:

Ground MTA

IX Dual Calculated

www.eaton.com 355

Page 356: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

356 www.eaton.com

50X/

51X

-Dire

ctio

n D

etec

tion

Prot

.IX d

ir n

poss

Prot

.IX d

ir re

v

Prot

.IX d

ir fw

d(F

orw

ard)

(Rev

erse

)

(Not

pos

sibl

e)

10b

10b

Prot

-50

X/51

X -D

irect

ion

Det

ectio

n

10b

Mea

sure

d

3V0

Sour

ce

Syst

em P

ara

Calc

ulat

ed

VR c

alc

VX m

eas

IX 3

V0

IX N

eg

IX D

ir C

ntrl

IX D

ual

3V0

3V0

If V2

and

I2 a

re a

vaila

ble,

I2 is

the

oper

atin

g qu

antit

y, e

lse

IX is

the

oper

atin

g qu

antit

y

V2

IG =

IX m

eas 90

° +

Phas

e M

TA

Gro

und

MTA

Syst

em P

ara

Syst

em P

ara

If V2

and

I2 a

re a

vaila

ble,

MTA

= 9

0° +

Ph

ase

MTA

, oth

erw

ise

MTA

= G

roun

d M

TA

Rev

erse

Forw

ard

pola

rizin

g

MTA

pola

rizin

gop

erat

ing

oper

ating

V2

I2

Page 357: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

50X/67X DEFT Measured Ground Fault ProtectionElements50X[1] ,50X[2]

If using inrush blockings, the tripping delay of the ground current protection functions must be at least 30 ms or more in order to prevent faulty trippings.

All ground current elements are identically structured.

The following table shows the application options of the earth overcurrent protection element

Applications of the IG-Protection Module Setting in OptionANSI 50X – Ground overcurrent protection, non-directional

Device Planning menuSetting: Non-directional

Measuring Mode: Fundamental/TrueRMS

ANSI 67X – Ground overcurrent protection, directional

Device Planning menuSetting: Forward/Reverse

Measuring Mode: Fundamental/TrueRMSVX Selection: measured/calculated

CriterionFor all protection elements it can be determined, whether the measurement is done on basis of the »Fundamental« or if »TrueRMS« measurement is used.

VX SelectionWithin the parameter menu, this parameter determines, whether the earth current and the residual voltage is »measured« or »calculated«.

Calculation is only possible, when phase to neutral voltage is applied to the voltage inputs.

At setting »measured« the quantities to be measured, i. e.: residual voltage and the measured ground current have to be applied to the corresponding 4th measuring input.

All ground current protective elements can be planned User defined as non-directional or as directional stages. This means, for instance, all elements can be projected in forward/reverse direction.

For each element the following characteristics are available:

• DEFT (definite time).

For tripping curves, please refer to the “Appendix/Instantaneous Current Curves (Ground Current Measured)” section.

The ground current can be measured either directly via a zero sequence transformer or detected by a residual connection. The ground current can alternatively be calculated from the phase currents. However, this is only possible if the current transformers are Wye-connected.

www.eaton.com 357

Page 358: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

358 www.eaton.com

50X[

1]...

[n]

Nam

e =

50X[

1]...

[n]

Nam

e.Tr

ipC

md

Nam

e.Tr

ip

Plea

se R

efer

to D

iagr

am: B

lock

ings

**

Nam

e.Pi

ckup

Plea

se R

efer

to D

iagr

am: T

rip B

lock

ings

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

IH2.

Blo

IG

Inac

tive

Activ

e

Nam

e.IG

H2

Blo

AND

Nam

e.Pi

ckup

Nam

e.IG

H2

Blo*

84 3

Plea

se R

efer

to D

iagr

am: I

H2*

151427

a

19a

AND AN

D

AND

φD

EFT

Nam

e.t

Nam

e.Pi

ckup

IX M

easu

red

Fund

.

RM

S

Nam

e.C

riter

ion

φ

Base

d on

abo

ve p

aram

eter

s,

tripp

ing

times

and

rese

t mod

es

will

be c

alcu

late

d by

the

devi

ce.

*=Applies only to devices that offer Inrush Protection

t 0

Nam

e.* F

ault

in P

roje

cted

Dire

ctio

n10

Plea

se R

efer

to D

iagr

am: D

irect

ion

Dec

isio

n G

roun

d Fa

ult

Page 359: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Device Planning Parameters of the 50X/67X Ground Fault Protection

Parameter Description Options Default Menu Path

Mode Mode Non-directional,

Forward,

Reverse

Non-directional

[Device Plan-ning]

Global Protection Parameters of the 50X/67X Ground Fault Protection

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/50X[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/50X[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/50X[1]]Rvs Blo Reverse Blocking, if Reverse Blocking is

activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/50X[1]]AdaptSet 1 Assignment Adaptive Parameter 1 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/50X[1]]AdaptSet 2 Assignment Adaptive Parameter 2 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/50X[1]]

www.eaton.com 359

Page 360: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/50X[1]]AdaptSet 4 Assignment Adaptive Parameter 4 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/50X[1]]

Setting Group Parameters of the 50X/67X Ground Fault Protection

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Active [Protection Para

/<n>

/I-Prot

/50X[1]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/50X[1]]Rvs Blo Fc Activate (allow) or inactivate (disallow)

reverse blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/element are blocked that are configured "Rvs Blo Fc = active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/50X[1]]Blo TripCmd Permanent blocking of the Trip Command

of the module/element.Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/50X[1]]

360 www.eaton.com

Page 361: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/50X[1]]

Criterion Measuring method: fundamental or Reset Fundamental,

True RMS

True RMS [Protection Para

/<n>

/I-Prot

/50X[1]]Pickup

If the pickup value is exceeded, the module/element will be started.

0.02 – 20.00 In 50X[1]: 1 In

50X[2]: 2 In

[Protection Para

/<n>

/I-Prot

/50X[1]]Pickup

If the pickup value is exceeded, the module/element will be started.

0.002 – 2.000 In 0.02 In [Protection Para

/<n>

/I-Prot

/50X[1]]t

Tripping delay

Only available if: Characteristic = DEFT

0.00 – 300.00 s 0.5 s [Protection Para

/<n>

/I-Prot

/50X[1]]

50X/67X Ground Fault Protection Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking1 [Protection Para

/Global Prot Para

/I-Prot

/50X[1]]

www.eaton.com 361

Page 362: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

ExBlo2-I Module Input State: External Blocking2 [Protection Para

/Global Prot Para

/I-Prot

/50X[1]]ExBlo TripCmd-I Module Input State: External Blocking of the

Trip Command[Protection Para

/Global Prot Para

/I-Prot

/50X[1]]Rvs Blo-I Module Input State: Reverse Blocking [Protection Para

/Global Prot Para

/I-Prot

/50X[1]]AdaptSet1-I Module Input State: Adaptive Parameter 1 [Protection Para

/Global Prot Para

/I-Prot

/50X[1]]AdaptSet2-I Module Input State: Adaptive Parameter 2 [Protection Para

/Global Prot Para

/I-Prot

/50X[1]]AdaptSet3-I Module Input State: Adaptive Parameter 3 [Protection Para

/Global Prot Para

/I-Prot

/50X[1]]AdaptSet4-I Module Input State: Adaptive Parameter 4 [Protection Para

/Global Prot Para

/I-Prot

/50X[1]]

362 www.eaton.com

Page 363: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

50X/67X Ground Fault Protection Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingRvs Blo Signal: Reverse BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup Signal: Pickup IX or IRTrip Signal: TripTripCmd Signal: Trip CommandActive AdaptSet Active Adaptive ParameterDefaultSet Signal: Default Parameter SetAdaptSet 1 Signal: Adaptive Parameter 1AdaptSet 2 Signal: Adaptive Parameter 2AdaptSet 3 Signal: Adaptive Parameter 3AdaptSet 4 Signal: Adaptive Parameter 4

Commissioning: Ground Fault Protection – Non-directional [ANSI 50X/67X]

Please test the non-directional ground overcurrent analog to the non-directional phase overcurrent protection.

www.eaton.com 363

Page 364: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

51X/67X INV Measured Ground Fault ProtectionElements51X[1] ,51X[2]

All ground current elements are identically structured.

The following table shows the application options of the earth overcurrent protection element

Applications of the IG-Protection Module Setting in OptionANSI 51X – Ground overcurrent protection, non-directional

Device Planning menuSetting: Non-directional

Measuring Mode: Fundamental/TrueRMS

ANSI 67X – Ground overcurrent protection, directional

Device Planning menuSetting: Forward/Reverse

Measuring Mode: Fundamental/TrueRMSVX Selection: measured/calculated

CriterionFor all protection elements it can be determined, whether the measurement is done on basis of the »Fundamental« or if »TrueRMS« measurement is used.

VX SelectionWithin the parameter menu, this parameter determines, whether the earth current and the residual voltage is »measured« or »calculated«.

Calculation is only possible, when phase to neutral voltage is applied to the voltage inputs.

At setting »measured« the quantities to be measured, i. e. Residual voltage and the measured ground current have to be applied to the corresponding 4th measuring input.

All ground current protective elements can be planned User defined as non-directional or as directional stages. This means, for instance, all elements can be projected in forward/reverse direction.

For each element the following characteristics are available:

• NINV (IEC/XInv);• VINV (IEC/XInv);• LINV (IEC/XInv);• EINV (IEC/XInv);• MINV (ANSI/XInv);• VINV (ANSI/XInv);• EINV (ANSI/XInv);• Thermal Flat;• Therm Flat IT;• Therm Flat I2T; and• Therm Flat I4T.

For tripping curves please refer to the “Appendix/Time Current Curves (Ground Current)” section.

The ground current can be measured either directly via a zero sequence transformer or detected by a residual connection. The ground current can alternatively be calculated from the phase currents. However, this is only possible if the current transformers are Wye-connected.

364 www.eaton.com

Page 365: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 365

Nam

e.Tr

ipC

md

Nam

e.Tr

ip

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs**

Nam

e.Pi

ckup

Ple

ase

Ref

er to

Dia

gram

: Trip

Blo

ckin

gs

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

IH2.

Blo

IG

Inac

tive

Activ

e

Nam

e.IG

H2

Blo

AND

Nam

e.Pi

ckup

Nam

e.IG

H2

Blo*

84 3

Ple

ase

Ref

er to

Dia

gram

: IH

2*

151427

b

19b

AND AN

D

AND

IX M

easu

red

Fund

.

RM

S

Nam

e.C

riter

ion

φ

51X[

1]...

[n]

Nam

e =

51X[

1]...

[n]

φ INV

Nam

e.t-r

eset

Nam

e.t-m

ultip

lier

Nam

e.C

urve

Sha

pe

Nam

e.R

eset

Mod

e

Base

d on

abo

ve p

aram

eter

s, tr

ippi

ng

times

and

rese

t mod

es w

ill be

cal

cula

ted

by th

e de

vice

.

*=Applies only to devices that offer Inrush Protection

Nam

e.* F

ault

in P

roje

cted

Dire

ctio

n10

Ple

ase

Ref

er to

Dia

gram

: Dire

ctio

n D

ecis

ion

Gro

und

Faul

t

Page 366: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Device Planning Parameters of the 51X/67X Ground Fault Protection

Parameter Description Options Default Menu Path

Mode Mode 51X[1]: Non-directional,

Forward,

Reverse

51X[2]: Do not use,

Non-directional,

Forward,

Reverse

Non-directional

[Device Plan-ning]

Global Protection Parameters of the 51X/67X Ground Fault Protection

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/51X[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/51X[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/51X[1]]Rvs Blo Reverse Blocking, if Reverse Blocking is

activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/51X[1]]AdaptSet 1 Assignment Adaptive Parameter 1 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/51X[1]]

366 www.eaton.com

Page 367: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

AdaptSet 2 Assignment Adaptive Parameter 2 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/51X[1]]AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/51X[1]]AdaptSet 4 Assignment Adaptive Parameter 4 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/51X[1]]

Setting Group Parameters of the 51X/67X Ground Fault Protection

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Active [Protection Para

/<n>

/I-Prot

/51X[1]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51X[1]]Rvs Blo Fc Activate (allow) or inactivate (disallow)

reverse blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/element are blocked that are configured "Rvs Blo Fc = active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51X[1]]Blo TripCmd Permanent blocking of the Trip Command

of the module/element.Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51X[1]]

www.eaton.com 367

Page 368: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51X[1]]

Criterion Measuring method: fundamental or Reset Fundamental,

True RMS

True RMS [Protection Para

/<n>

/I-Prot

/51X[1]]Pickup

If the pickup value is exceeded, the module/element will be started.

0.02 – 20.00 In 0.5 In [Protection Para

/<n>

/I-Prot

/51X[1]]Pickup

If the pickup value is exceeded, the module/element will be started.

0.002 – 2.000 In 0.02 In [Protection Para

/<n>

/I-Prot

/51X[1]]Curve Shape

Characteristic IEC NINV,

IEC VINV,

IEC EINV,

IEC LINV,

ANSI MINV,

ANSI VINV,

ANSI EINV,

Therm Flat,

IT,

I2T,

I4T

ANSI MINV [Protection Para

/<n>

/I-Prot

/51X[1]]

368 www.eaton.com

Page 369: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

t-multiplier

Time multiplier/tripping characteristic factor. The setting range depends on the selected tripping curve.

0.02 - 20.00 51X[1]: 1

51X[2]: 2

[Protection Para

/<n>

/I-Prot

/51X[1]]Reset Mode

Reset Mode Instantaneous,

t-delay,

Calculated

Calculated [Protection Para

/<n>

/I-Prot

/51X[1]]t-reset

Reset time for intermittent phase failures (INV characteristics only)

Only available if:Reset Mode = t-delay

0.00 – 60.00 s 0.00 s [Protection Para

/<n>

/I-Prot

/51X[1]]

51X/67X Ground Fault Protection Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking 1 [Protection Para

/Global Prot Para

/I-Prot

/51X[1]]ExBlo2-I Module Input State: External Blocking 2 [Protection Para

/Global Prot Para

/I-Prot

/51X[1]]ExBlo TripCmd-I Module Input State: External Blocking of the

Trip Command[Protection Para

/Global Prot Para

/I-Prot

/51X[1]]Rvs Blo-I Module Input State: Reverse Blocking [Protection Para

/Global Prot Para

/I-Prot

/51X[1]]

www.eaton.com 369

Page 370: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

AdaptSet1-I Module Input State: Adaptive Parameter 1 [Protection Para

/Global Prot Para

/I-Prot

/51X[1]]AdaptSet2-I Module Input State: Adaptive Parameter 2 [Protection Para

/Global Prot Para

/I-Prot

/51X[1]]AdaptSet3-I Module Input State: Adaptive Parameter 3 [Protection Para

/Global Prot Para

/I-Prot

/51X[1]]AdaptSet4-I Module Input State: Adaptive Parameter 4 [Protection Para

/Global Prot Para

/I-Prot

/51X[1]]

51X/67X Ground Fault Protection Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingRvs Blo Signal: Reverse BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup Signal: Pickup IX or IRTrip Signal: TripTripCmd Signal: Trip CommandActive AdaptSet Active Adaptive ParameterDefaultSet Signal: Default Parameter SetAdaptSet 1 Signal: Adaptive Parameter 1AdaptSet 2 Signal: Adaptive Parameter 2AdaptSet 3 Signal: Adaptive Parameter 3AdaptSet 4 Signal: Adaptive Parameter 4

370 www.eaton.com

Page 371: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Commissioning: Ground Fault Protection – Non-directional [ANSI 51X/67X]

Please test the non-directional ground overcurrent analog to the non-directional phase overcurrent protection.

www.eaton.com 371

Page 372: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Directional Features for Calculated (IR) Ground Fault Elements 50R/51RAll ground fault elements can be selected as »Non-directional/Forward/Reverse« operated. This has to be done in the »Device Planning« menu.

For the direction detection, it is mandatory that the required voltages exceed 0.35 V and the required currents exceed 10 mA. An exception is the measured sensitive ground current which has to exceed 1 mA.For the case that the voltage drops below 0.35 V, the last angle between the operating and polarizing quantity will be used for the directional detection.

Important Definitions

Polarizing Quantity: This is the quantity that is used as a reference value. The polarizing quantity can be selected by the parameter »IR Direction Control« in the [System Para/Direction] menu as follows:

• »IR 3V0«: The neutral voltage selected by the parameter »3V0 Source« will be used as the polarizing quantity. The traditional way to polarize a ground fault element is to use neutral voltage (3V0). The neutral voltage can, however, be either »measured« or »calculated«. This can be selected by the parameter »3V0 Source« in the [System Para/Direction] menu.

• »IR IPol«: The measured neutral current (usually = IX) will be used as polarizing quantity.

• »IR Dual«: For this method, the measured neutral current IPol=IX will be used as polarizing quantity, if available, otherwise 3V0 will be used.

• »IR Neg«: With this selection, the negative phase sequence voltage and current will be used to detect the direction. The monitored current is still the calculated residual current IR.

Operating Quantity: For the directional IR elements, the operating quantity is in general the calculated neutral current IR (except from »IR Neg« mode, where »I2« is the operating quantity).

The ground maximum torque angles (MTA) can be adjusted from 0° to 360°, except, if »IR IPol« is selected. In this case, it is set to 0° (fixed).

The following table gives the User a quick overview of the all possible directional settings.

50R/51R Direction Decision by Angle Between:

[System Para/ Direction]

The Following Angle Has to Be Set:

[System Para/Direction]:

IR Dir Cntrl =

[System Para/Direction]:

3V0 Source =

Residual current and neutral voltage:IR, 3V0 (measured)

Ground MTA IR 3V0 Measured

Residual current and neutral voltage:IR, 3V0 (calculated)

Ground MTA IR 3V0 Calculated

Residual current and neutral/ground currentIR, IX

0° (fixed) IR IPol N.A.

372 www.eaton.com

Page 373: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

50R/51R Direction Decision by Angle Between:

[System Para/ Direction]

The Following Angle Has to Be Set:

[System Para/Direction]:

IR Dir Cntrl =

[System Para/Direction]:

3V0 Source =

Residual current and neutral/ground current (preferred), residual current and neutral voltage (alternatively):IR, IX (if available)or else:IR, 3V0 (measured)

If Ipol (=IX) is available, MTA = 0° (fixed); else MTA=Ground MTA

IR Dual Measured

Residual current and neutral/ground current (preferred), residual current and neutral voltage (alternatively):IR, IX (if available)or else:IR, 3V0 (calculated)

If Ipol (=IX) is available, MTA = 0° (fixed); else MTA=Ground MTA

IR Dual Calculated

Negative sequence voltage and currentI2, V2

90° + Phase MTA IR Neg N.A.

www.eaton.com 373

Page 374: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

374 www.eaton.com

Rev

erse

Forw

ard

pola

rizin

g

50R

/51R

-D

irect

ion

Det

ectio

n

MTA

Mea

sure

d

3V0

Sour

ce

Syst

em P

ara

Cal

cula

ted

VR

cal

c

VX

mea

s

IR 3

V0

IR IP

ol

IR D

ir C

ntrl

IR D

ual

IR N

eg

3V0

3V0

IX m

eas

IX m

eas

I2

V2

I0 =

IR c

alc

Prot

.IR d

ir n

poss

Prot

.IR d

ir re

v

Prot

.IR d

ir fw

d(F

orw

ard)

(Rev

erse

)

(Not

pos

sibl

e)

10a

10a

pola

rizin

gop

erat

ing

Prot

-50

R/5

1R -

Dire

ctio

n D

etec

tion

oper

ating

0° (f

ixed

)

Gro

und

MTA

Syst

em P

ara

Syst

em P

ara

10a

Prot

.IR N

eg d

ir n

poss

Prot

.IR N

eg re

v di

r

Prot

.IR N

eg d

ir fw

d(F

orw

ard)

(Rev

erse

)

(Not

pos

sibl

e)

10a

10a

10a

If IP

ol is

ava

ilabl

e, M

TA =

0°;

els

e M

TA=G

roun

d M

TA

90°

+ P

hase

MTA

Page 375: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

50R/67R DEFT Calculated Ground Fault ProtectionElements50R[1] ,50R[2]

If using inrush blockings, the tripping delay of the ground current protection functions must be at least 30 ms or more in order to prevent faulty trippings.

All ground current elements are identically structured.

The following table shows the application options of the earth overcurrent protection element

Applications of the IG-Protection Module Setting in OptionANSI 50R – Ground overcurrent protection, non-directional

Device Planning menuSetting: Non-directional

Measuring Mode: Fundamental/TrueRMS

ANSI 67R – Ground overcurrent protection, directional

Device Planning menuSetting: Forward/Reverse

Measuring Mode: Fundamental/TrueRMSVX Selection: measured/calculated

CriterionFor all protection elements it can be determined, whether the measurement is done on basis of the »Fundamental« or if »TrueRMS« measurement is used.

VX SelectionWithin the parameter menu, this parameter determines, whether the earth current and the residual voltage is »measured« or »calculated«.

• Calculation is only possible, when phase to neutral voltage is applied to the voltage inputs.

At setting »measured« the quantities to be measured, i. e.: residual voltage and the measured ground current have to be applied to the corresponding 4th measuring input.

All ground current protective elements can be planned User defined as non-directional or as directional stages. This means, for instance, all elements can be projected in forward/reverse direction.

For each element the following characteristics are available:

• DEFT (definite time).

For tripping curves please refer to the “Appendix/Instantaneous Current Curves (Ground Current Calculated)” section.

The ground current can be measured either directly via a zero sequence transformer or detected by a residual connection. The ground current can alternatively be calculated from the phase currents. However, this is only possible if the current transformers are Wye-connected.

www.eaton.com 375

Page 376: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

376 www.eaton.com

Nam

e.Tr

ipC

md

Nam

e.Tr

ip

Plea

se R

efer

to D

iagr

am: B

lock

ings

**

Nam

e.Pi

ckup

Plea

se R

efer

to D

iagr

am: T

rip B

lock

ings

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

IH2.

Blo

IG

Inac

tive

Activ

e

Nam

e.IG

H2

Blo

AND

Nam

e.Pi

ckup

Nam

e.IG

H2

Blo*

84 3

Ple

ase

Ref

er to

Dia

gram

: IH

2*

151427

c

19c

AND AN

D

AND

Fund

.

RM

S

Nam

e.C

riter

ion

φ

50R

[1]..

.[n]

Nam

e =

50R

[1]..

.[n]

IX C

alcu

late

d

Nam

e.t

Nam

e.Pi

ckup

t0

φD

EFT

Base

d on

abo

ve p

aram

eter

s, tr

ippi

ng

times

and

rese

t mod

es w

ill be

cal

cula

ted

by th

e de

vice

.

*=Applies only to devices that offer Inrush Protection

t 0

Nam

e.* F

ault

in P

roje

cted

Dire

ctio

n10

Plea

se R

efer

to D

iagr

am: D

irect

ion

Dec

isio

n G

roun

d Fa

ult

Page 377: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Device Planning Parameters of the 50R/67R Ground Fault Protection

Parameter Description Options Default Menu Path

Mode Mode Non-directional,

Forward,

Reverse

Non-directional

[Device Plan-ning]

Global Protection Parameters of the 50R/67R Ground Fault Protection

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/50R[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/50R[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/50R[1]]Rvs Blo Reverse Blocking, if Reverse Blocking is

activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/50R[1]]AdaptSet 1 Assignment Adaptive Parameter 1 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/50R[1]]AdaptSet 2 Assignment Adaptive Parameter 2 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/50R[1]]

www.eaton.com 377

Page 378: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/50R[1]]AdaptSet 4 Assignment Adaptive Parameter 4 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/50R[1]]

Setting Group Parameters of the 50R/67R Ground Fault Protection

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Active [Protection Para

/<n>

/I-Prot

/50R[1]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/50R[1]]Rvs Blo Fc Activate (allow) or inactivate (disallow)

reverse blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/element are blocked that are configured "Rvs Blo Fc = active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/50R[1]]Blo TripCmd Permanent blocking of the Trip Command

of the module/element.Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/50R[1]]

378 www.eaton.com

Page 379: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/50R[1]]

Criterion Measuring method: fundamental or Reset Fundamental,

True RMS

True RMS [Protection Para

/<n>

/I-Prot

/50R[1]]Pickup

If the pickup value is exceeded, the module/element will be started.

0.02 – 20.00 In 50R[1]: 1 In

50R[2]: 2 In

[Protection Para

/<n>

/I-Prot

/50R[1]]t

Tripping delay

Only available if: Characteristic = DEFT

0.00 – 300.00 s 0.5 s [Protection Para

/<n>

/I-Prot

/50R[1]]

50R/67R Ground Fault Protection Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking1 [Protection Para

/Global Prot Para

/I-Prot

/50R[1]]ExBlo2-I Module Input State: External Blocking2 [Protection Para

/Global Prot Para

/I-Prot

/50R[1]]

www.eaton.com 379

Page 380: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command

[Protection Para

/Global Prot Para

/I-Prot

/50R[1]]Rvs Blo-I Module Input State: Reverse Blocking [Protection Para

/Global Prot Para

/I-Prot

/50R[1]]AdaptSet1-I Module Input State: Adaptive Parameter1 [Protection Para

/Global Prot Para

/I-Prot

/50R[1]]AdaptSet2-I Module Input State: Adaptive Parameter2 [Protection Para

/Global Prot Para

/I-Prot

/50R[1]]AdaptSet3-I Module Input State: Adaptive Parameter3 [Protection Para

/Global Prot Para

/I-Prot

/50R[1]]AdaptSet4-I Module Input State: Adaptive Parameter4 [Protection Para

/Global Prot Para

/I-Prot

/50R[1]]

50R/67R Ground Fault Protection Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingRvs Blo Signal: Reverse BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip Command

380 www.eaton.com

Page 381: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Pickup Signal: Pickup IX or IRTrip Signal: TripTripCmd Signal: Trip CommandActive AdaptSet Active Adaptive ParameterDefaultSet Signal: Default Parameter SetAdaptSet 1 Signal: Adaptive Parameter 1AdaptSet 2 Signal: Adaptive Parameter 2AdaptSet 3 Signal: Adaptive Parameter 3AdaptSet 4 Signal: Adaptive Parameter 4

Commissioning: Ground Fault Protection – Non-directional [ANSI 50R/67R]

Please test the non-directional ground overcurrent using the procedure for non-directional phase overcurrent protection.

www.eaton.com 381

Page 382: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

51R/67R INV Calculated Ground Fault ProtectionElements51R[1] ,51R[2]

All ground current elements are identically structured.

The following table shows the application options of the earth overcurrent protection element

Applications of the IG-Protection Module Setting in OptionANSI 51R – Ground overcurrent protection, non-directional

Device Planning menuSetting: Non-directional

Measuring Mode: Fundamental/TrueRMS

ANSI 67R – Ground overcurrent protection, directional

Device Planning menuSetting: Forward/Reverse

Measuring Mode: Fundamental/TrueRMSVX Selection: measured/calculated

CriterionFor all protection elements it can be determined, whether the measurement is done on basis of the »Fundamental« or if »TrueRMS« measurement is used.

VX SelectionWithin the parameter menu, this parameter determines, whether the earth current and the residual voltage is »measured« or »calculated«.

• Calculation is only possible, when phase to neutral voltage is applied to the voltage inputs.

At setting »measured« the quantities to be measured, i. e.: residual voltage and the measured ground current have to be applied to the corresponding 4th measuring input.

All ground current protective elements can be planned User defined as non-directional or as directional stages. This means, for instance, all elements can be projected in forward/reverse direction.

For each element the following characteristics are available:

• NINV (IEC/XInv);• VINV (IEC/XInv);• LINV (IEC/XInv);• EINV (IEC/XInv);• MINV (ANSI/XInv);• VINV (ANSI/XInv);• EINV (ANSI/XInv);• Thermal Flat;• Therm Flat IT;• Therm Flat I2T; and• Therm Flat I4T.

For tripping curves please refer to the “Appendix/Time Current Curves (Ground Current)” section.

The ground current can be measured either directly via a zero sequence transformer or detected by a residual connection. The ground current can alternatively be calculated from the phase currents. However, this is only possible if the current transformers are Wye-connected.

382 www.eaton.com

Page 383: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 383

Nam

e.Tr

ipC

md

Nam

e.Tr

ip

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs**

Nam

e.Pi

ckup

Ple

ase

Ref

er to

Dia

gram

: Trip

Blo

ckin

gs

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

IH2.

Blo

IG

Inac

tive

Activ

e

Nam

e.IG

H2

Blo

AND

Nam

e.Pi

ckup

Nam

e.IG

H2

Blo*

84 3

Ple

ase

Ref

er to

Dia

gram

: IH

2*

151427

d

19d

AND AN

D

AND

Fund

.

RM

S

Nam

e.C

riter

ion

φ

φ INV

Nam

e.t-r

eset

Nam

e.t-m

ultip

lier

Nam

e.C

urve

Sha

pe

Nam

e.R

eset

Mod

e

Base

d on

abo

ve p

aram

eter

s, tr

ippi

ng

times

and

rese

t mod

es w

ill be

cal

cula

ted

by th

e de

vice

.

IX C

alcu

late

d

51R

[1]..

.[n]

Nam

e =

51R

[1]..

.[n]

*=Applies only to devices that offer Inrush Protection

Nam

e.* F

ault

in P

roje

cted

Dire

ctio

n10

Ple

ase

Ref

er to

Dia

gram

: Dire

ctio

n D

ecis

ion

Gro

und

Faul

t

Page 384: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Device Planning Parameters of the 51R/67R Ground Fault Protection

Parameter Description Options Default Menu Path

Mode Mode 51R[1]: Non-directional,

Forward,

Reverse

51R[2]: Do not use,

Non-directional,

Forward,

Reverse

Non-directional

[Device Plan-ning]

Global Protection Parameters of the 51R/67R Ground Fault Protection

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/51R[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/51R[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/51R[1]]Rvs Blo Reverse Blocking, if Reverse Blocking is

activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/I-Prot

/51R[1]]AdaptSet 1 Assignment Adaptive Parameter 1 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/51R[1]]

384 www.eaton.com

Page 385: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

AdaptSet 2 Assignment Adaptive Parameter 2 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/51R[1]]AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/51R[1]]AdaptSet 4 Assignment Adaptive Parameter 4 AdaptSet -.- [Protection Para

/Global Prot Para

/I-Prot

/51R[1]]

Setting Group Parameters of the 51R/67R Ground Fault Protection

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Active [Protection Para

/<n>

/I-Prot

/51R[1]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51R[1]]Rvs Blo Fc Activate (allow) or inactivate (disallow)

reverse blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/element are blocked that are configured "Rvs Blo Fc = active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51R[1]]Blo TripCmd Permanent blocking of the Trip Command

of the module/element.Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51R[1]]

www.eaton.com 385

Page 386: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/I-Prot

/51R[1]]

Criterion Measuring method: fundamental or Reset Fundamental,

True RMS

True RMS [Protection Para

/<n>

/I-Prot

/51R[1]]Pickup

If the pickup value is exceeded, the module/element will be started.

0.02 – 20.00 In 51R[1]: 0.1 In

51R[2]: 0.5 In

[Protection Para

/<n>

/I-Prot

/51R[1]]Curve Shape

Characteristic IEC NINV,

IEC VINV,

IEC EINV,

IEC LINV,

ANSI MINV,

ANSI VINV,

ANSI EINV,

Therm Flat,

IT,

I2T,

I4T

ANSI MINV [Protection Para

/<n>

/I-Prot

/51R[1]]

t-multiplier

Time multiplier/tripping characteristic factor. The setting range depends on the selected tripping curve.

0.02 - 20.00 51R[1]: 1

51R[2]: 2

[Protection Para

/<n>

/I-Prot

/51R[1]]

386 www.eaton.com

Page 387: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Reset Mode

Reset Mode Instantaneous,

t-delay,

Calculated

Calculated [Protection Para

/<n>

/I-Prot

/51R[1]]t-reset

Reset time for intermittent phase failures (INV characteristics only)

Only available if:Reset Mode = t-delay

0.00 – 60.00 s 0.00 s [Protection Para

/<n>

/I-Prot

/51R[1]]

51R/67R Ground Fault Protection Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking 1 [Protection Para

/Global Prot Para

/I-Prot

/51R[1]]ExBlo2-I Module Input State: External Blocking 2 [Protection Para

/Global Prot Para

/I-Prot

/51R[1]]ExBlo TripCmd-I Module Input State: External Blocking of the

Trip Command[Protection Para

/Global Prot Para

/I-Prot

/51R[1]]Rvs Blo-I Module Input State: Reverse Blocking [Protection Para

/Global Prot Para

/I-Prot

/51R[1]]AdaptSet1-I Module Input State: Adaptive Parameter 1 [Protection Para

/Global Prot Para

/I-Prot

/51R[1]]

www.eaton.com 387

Page 388: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

AdaptSet2-I Module Input State: Adaptive Parameter 2 [Protection Para

/Global Prot Para

/I-Prot

/51R[1]]AdaptSet3-I Module Input State: Adaptive Parameter 3 [Protection Para

/Global Prot Para

/I-Prot

/51R[1]]AdaptSet4-I Module Input State: Adaptive Parameter 4 [Protection Para

/Global Prot Para

/I-Prot

/51R[1]]

51R/67R Ground Fault Protection Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingRvs Blo Signal: Reverse BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup Signal: Pickup IX or IRTrip Signal: TripTripCmd Signal: Trip CommandActive AdaptSet Active Adaptive ParameterDefaultSet Signal: Default Parameter SetAdaptSet 1 Signal: Adaptive Parameter 1AdaptSet 2 Signal: Adaptive Parameter 2AdaptSet 3 Signal: Adaptive Parameter 3AdaptSet 4 Signal: Adaptive Parameter 4

Commissioning: Ground Fault Protection – Non-directional [ANSI 51R/67R]

Please test the non-directional ground overcurrent analog to the non-directional phase overcurrent protection.

388 www.eaton.com

Page 389: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

ZI - Zone InterlockingElementsZI

Principle – General Use

The purpose of zone interlocking is to speed up tripping for some faults without sacrificing the coordination of the system and interjecting nuisance trips into the system. Zone interlocking devices can communicate across distribution zones to determine whether or not a device sees a fault condition.

Zone interlocking is a communication scheme used with breakers and protective relays to improve the level of protection in a power distribution system. This is achieved through communication between the downstream and upstream devices in a power system. The zones are classified by their location downstream of the main circuit protective device which is generally defined as Zone 1.

By definition, a selectively coordinated system is one where by adjusting the trip unit pickup and time delay settings, the breaker closest to the fault trips first. The upstream breaker serves two functions: (1) back-up protection to the downstream breaker and (2) protection of the conductors between the upstream and downstream breakers.

For faults which occur on the conductors between the upstream and downstream breakers, it is ideal for the upstream breaker to trip with no time delay. This is the feature provided by Zone Selective Interlocking.

The zone interlocking information can be transferred to or received from other compatible zone interlocking devices by means of suitable communication cables. The single zone interlock terminal block, with its 3-wire scheme, can be used for either phase zone interlocking, ground zone interlocking, or a combination of the two. If phase and ground zone interlocking are combined, the potential consequences must be understood before implementation.

Systems containing multiple sources, or where the direction of power flow varies, require special considerations, or may not be suitable for this feature.

The breaker failure pickup signal »BF.PICKUP« is implicitly connected to zone interlocking, so that NO zone interlock output signal can be sent to the upstream device if a breaker failure on a downstream device is detected.

Description of the Functions and Features

• Configurable protection functions to initiate the zone interlocking OUTPUT signal (start functions).

• Remove zone interlocking OUTPUT signal immediately after detection of a breaker failure.

• Reset time (about ten cycles - settable) to interrupt OUTPUT signal for durable trip signal.

• Small trip delay (about three cycles – settable) to wait for downstream devices interlocking signals.

• Zone interlocking trip signal only possible by absence of zone interlocking INPUT signals.

• Configurable zone interlocking trip functions (protective functions serve as zone interlocking trip functions).

• Zone interlocking trip function pickup and tripping characteristic adaption using adaptive settings controlled by the zone interlocking input signals.

www.eaton.com 389

Page 390: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Device Planning Parameters of the Zone Interlocking

Parameter Description Options Default Menu Path

Mode Mode Use Use [Device Plan-ning]

Global Protection Parameters of the Zone Interlocking

In the global parameter menu for zone interlocking, two external blocking inputs (»Ex Block1/Ex Block2«), as with other protection modules, can be assigned to the input of the zone interlocking function so that the zone interlock function can be blocked by an assigned functions

Via an external input signal, the zone interlocking can also be blocked if the parameter »ExtBlockTripCMD« is assigned.

Breaker Failure Pickup flag BF.Pickup is implicitly connected to zone interlocking, so that NO zone interlock output signal can be sent to the upstream device if a breaker failure on downstream device is detected.

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/ZI]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/ZI]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/ZI]

Setting Group Parameters of the Zone Interlocking

The zone interlocking Setting Group Parameters consists of three groups of setting to configure the zone interlocking module to adapt to various application philosophies accordingly:

• General: This group comprises the settings used to control the general usage of the zone interlocking module.

• OUTPUT: What should be assigned to the Zone Out?- Phase,- Ground, or

• - Both.

The OUTPUT group comprises the settings to configure the zone interlocking output logic. If the zone interlocking application is used to a downstream device, the settings in OUTPUT group should be programmed accordingly. If the zone interlocking application is only used for an upstream device (main

390 www.eaton.com

Page 391: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

breaker or Zone 1), the setting ZoneInterlockOut within the OUTPUT group should be disabled.

• TRIP: Activate the Zone Trip.

The TRIP group comprises the settings used to configure the zone interlocking TRIP logic. If the zone interlocking application is applied to an upstream device, (main breaker or Zone 1), the settings in the TRIP group should be programmed accordingly. If the zone interlocking application is only used for a downstream device (feeder breaker or Zone 2), the setting ZoneInterlockTrip in TRIP group should be disabled.

Setting the above mentioned setting groups accordingly the zone interlocking module can be configured as:

• Downstream device application (using only OUTPUT logic);,

• Upstream device application (using only TRIP logic); or

• Midstream device application (using both OUTPUT and TRIP logic together).

The following menu and tables show the detailed information about the settings.

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/ZI

/General Settings]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/ZI

/General Settings]Blo TripCmd Permanent blocking of the Trip Command

of the module/element.Inactive,

Active

Inactive [Protection Para

/<n>

/ZI

/General Settings]ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/ZI

/General Settings]

www.eaton.com 391

Page 392: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

ZI OUT Fc Zone Interlocking Out activate (allow) / inactivate (disallow)

Inactive,

Active

Active [Protection Para

/<n>

/ZI

/Zone Out]Fault Type Fault Type Phase,

Ground,

Both

Both [Protection Para

/<n>

/ZI

/Zone Out]Trip Signal: Zone Interlocking Trip Inactive,

Active

Active [Protection Para

/<n>

/ZI

/Zone Trip]Fault Type Fault Type Phase,

Ground,

Both

Both [Protection Para

/<n>

/ZI

/Zone Trip]

Zone Interlocking Output Logic [X2]

The following current protective function elements serve as the Phase Zone Interlock OUTPUT start functions:

• 51P[1];• 50P[1]; and• 50P[2].

The following current protective function serves as the Ground Zone Interlock OUTPUT start functions:

• 51X[1];• 50X[1];• 51R[1]; and• 50R[1].

392 www.eaton.com

Page 393: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 393

ZI.OUT

Zone Interlocking OUTPUT Logic Timing

STARTEDSTANDBY TRIPPED RESET STANDBYSTATETRANSFER

51P[1].Trip

51P[1].Pickup

ZI.Bkr Blo

t

t

0

1

0

1

t

0

1

t

0

1

t

0

1

Reset Timer

10 Cycles

Page 394: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

394 www.eaton.com

OR OR OR

OR

OR

OR

OR

AND

AND

AND

AND

AND

AND

Phas

e

Gro

und

Faul

t Typ

e

Both

50P[

1].P

icku

p

51P[

1].P

icku

p

50P[

2].P

icku

p

50P[

1].T

ripC

md

51P[

1].T

ripC

md

50P[

2].T

ripC

md

50X[

1].P

icku

p

51X[

1].P

icku

p

50R

[1].P

icku

p

51R

[1].P

icku

p

50X[

1].T

ripC

md

51X[

1].T

ripC

md

50R

[1].T

ripC

md

51R

[1].T

ripC

md

Activ

e

ZI O

UT

Fc

Inac

tive

BF[1

].Trip

ZI[1

].Bkr

Blo

ZI[1

].Gro

und

OU

T

ZI[1

].Pha

se O

UT

ZI[1

].OU

T

166 m

st

166 m

st

X2: Z

I.Zon

e O

ut

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs2

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

Page 395: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Zone Interlocking Trip Logic [X2]

The following overcurrent protection elements trigger Phase Zone-Interlock trip functions:

• 1.5 * 51P[1];• 50P[1]; and• 50P[2].

The following overcurrent protection elements trigger Ground Zone Interlock trip functions:

• 51X[1];• 50X[1];• 51R[1]; and• 50R[1].

www.eaton.com 395

Zone Interlocking TRIP Logic Timing

STARTEDSTANDBY TRIPPED STANDBY INTERLOCKED STANDBY

ZI.Trip

STATETRANSFER

51P[1].Pickup

ZI.Pickup

t

t

0

1

0

1

t

0

1

t

0

1

t0

1

Trip Delay Timer

3 Cycles

ZI.IN

Page 396: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

396 www.eaton.com

AND

AND

OR

50 m

st

50 m

st

OR OR OR

OR

AND

AND

Phas

e

Gro

und

Faul

t Typ

e

Both

50P[

1].P

icku

p

1.5*

51P[

1].P

icku

p

50P[

2].P

icku

p

50X[

1].P

icku

p

51X[

1].P

icku

p

50R

[1].P

ickup

51R

[1].P

ickup

Activ

e

Trip

Inac

tive

ZI[1

].Gro

und

Pick

up

ZI[1

].Pha

se P

icku

p

ZI[1

].Pha

se T

rip

ZI[1

].Gro

und

Trip

ZI[1

].Trip

ZI.IN

X2: Z

I.Zon

e Tr

ip

Plea

se R

efer

to D

iagr

am: B

lock

ings

2(E

lem

ent i

s no

t dea

ctiv

ated

and

no

activ

e bl

ocki

ng s

igna

ls)

ZI[1

].Trip

Cm

d

Ple

ase

Ref

er to

Dia

gram

: Trip

Blo

ckin

gs

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

3

15AN

D

14O

R

1414

ZI[1

].Pic

kup

Page 397: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Zone Interlocking Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking1 [Protection Para

/Global Prot Para

/ZI]ExBlo2-I Module Input State: External Blocking2 [Protection Para

/Global Prot Para

/ZI]ExBlo TripCmd-I Module Input State: External Blocking of the

Trip Command[Protection Para

/Global Prot Para

/ZI]Bkr Blo-I Signal: Blocked by Breaker Failure []

Zone Interlocking Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandBkr Blo Signal: Blocked by Breaker FailurePhase Pickup Signal: Zone Interlocking Phase PickupPhase Trip Signal: Zone Interlocking Phase Trip Ground Pickup Signal: Zone Interlocking Ground PickupGround Trip Signal: Zone Interlocking Ground Trip Pickup Signal: Pickup Zone InterlockingTrip Signal: Zone Interlocking TripTripCmd Signal: Zone Interlocking Trip CommandPhase OUT Signal: Zone Interlocking Phase OUTGround OUT Signal: Zone Interlocking Ground OUTOUT Signal: Zone Interlocking OUTIN Signal: Zone Interlocking IN

Zone Interlocking Wiring

The ZI Outputs are for use with connection to electronic inputs only.

The zone interlocking connection between relays is done by means of a twisted shielded cable. Downstream

www.eaton.com 397

Page 398: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

zone interlock outputs may be paralleled from up to ten devices (FP-5000 or DT-3000 or a combination of both) for connection to upstream zone interlocked relays.

Hardware Terminals for Zone Interlocking

By means of the zone interlocking terminals, the device can be connected to other Eaton protective devices such as an FP5000, DT3000, etc.

As an upstream device, the terminals - Phase/Ground IN should be connected to the OUT terminals of up to ten downstream device(s) by means of a dedicated cable wired in parallel. As a downstream device, the terminals - Phase/Ground OUT should be connected to the IN terminals of an upstream device by means of a dedicated cable.

398 www.eaton.com

Zone 1

J3

FP-X000

1

4

2

Out

In

Com

X2

13

14

15

Shield

Out

Com

Zone 2

16

17

18

Shield

In

Com

EDR-X000

Zone 3

J3

FP-X000

1

4

2

Out

In

Com

DT-3000

13

14

15

Out

In

Out

16

18

In

Com

Ground

Phase

J3

FP-X000

1

4

2

Out

In

Com

X2

13

14

15

Shield

Out

Com

16

17

18

Shield

In

Com

EDR-X000

Page 399: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Terminal Marking X2 for Device: EDR-3000

www.eaton.com 399

123456789

101112131415161718

RO3

X?.

SC

IRIG-B+

IRIG-B-

COM

OUT

IN

COM

Page 400: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Terminal Marking X2 for Device: EDR-4000 and EDR-5000

400 www.eaton.com

123456789

101112131415161718

RO3

X?.Do not use

Do not use

COM

OUT

IN

COM

RO4

RO1

RO2

Page 401: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

79 - Automatic ReclosureAR

The autoreclosure is used to minimize outages on overhead lines. The majority1 (>60% in medium voltage and >85% in high voltage) of faults (arc flash over) on overhead lines are temporary and can be cleared by means of the autoreclosure element.

De-select the autoclosure element within the device planning menu if the protective device is used in order to protect cables, generators, ortransformers.

Features

The autoreclose function is designed with diverse, very comprehensive yet flexible features which meet all requirements of different utility concepts and technical applications.

The available features of the autoreclose function can be summarized as follows.

• Flexible assignment of initiate functions for individual shots.

• Maximum of six autoreclose shots.

• Dynamic adjustment of protection setting values (e.g.: pickup, time delay tripping curve, etc.) during autoreclose process via adaptive set concept.

• Reclose shots per hour limit.

• Autorecloser wear monitor with maintenance alarm.

• Programmable reclosing blocking feature.

• Auto zone coordination with downstream reclosers.

• Automatic manual-breaker-close blocking feature.

• Manual/Auto reset lockout (panel, contact input, communications, etc.).

• Autoreclose with Sync-check (Only in conjunction with internal Sync-check and Control modules).

• External AR shot counter increment is possible.

• Automatic autoreclose result evaluation (successful/unsuccessful).

• Separate counters to register total, successful/unsuccessful reclosing numbers.

1: Protective Relaying: Principles and Applications, ISBN 978-0824799182

www.eaton.com 401

Page 402: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Via the pre shot (fast trip), the AR-module is able to trip the breaker ahead of the protection stage that has activated the AR-module. As a general rule, a fast trip is either issued before the first reclosure attempt or after the last permitted reclosure attempt.

1. At the beginning of the sequence, a “Pre shot” (Fast trip) is executed before the time overcurrent protection element of any device on the line completely times out. Purpose: to clear the fault before any of the circuit protection trips or blows open. A short time after the pre-shot occurs, the breaker can be re-closed into the line and all circuits connected on the line will still be energized. 80%-90% of the faults are not permanent. After a period from 0.5 up to 1 sec., the line is probably no longer faulty and the complete line can be re-energized. If the line is still faulty, segments of the line will be switched off selectively by the time overcurrent protection module as a result of the system coordination.

2. A Pre shot (Fast trip) at the end of the reclosure sequence occurs after the last permitted reclosure shot. Purpose: To prevent unnecessary damage from the electrical equipment in case of permanent faults. If the last reclosure attempt is executed and the fault is still present, then the breaker can be tripped quickly before the time overcurrent protection module has completely timed out.

The following table gives a folder (structure) overview.

AR Menu Folder Purpose

AR

Path:[Protection Para\Global Prot Para\AR]

Within this menu, external blockings, external lockings, external shot increments and external resets can be assigned. Those external events can only become effective, if they have been activated (allowed) within the General Settings. Please see table row below.

General Settings

Path: [Protection Para\Set[x]\AR\General Settings]

Within this menu several general settings can be activated: the function itself, external blocking, zone coordination, external locking, and external shot increment can be set to active. The corresponding trigger events (e.g.: digital inputs) have to be assigned within the corresponding global protection parameters. Please see table row above.

Furthermore, this menu contains some timers, the number of permitted reclosure attempts, the alarm mode (trip/alarm), and the reset mode can be set.

Shot Manager

Path: [Protection Para\Set[x]\AR\Shot Manager]

In Shot manager setting menu, the control logic between individual shots and protective functions will be specified. For each shot (inclusive the pre shot), the trigger (start) events can be assigned.

For each shot, a maximum of four initiate functions (protective functions which are dedicated to start this shot) can be selected from a list of available protective functions.

When the autoreclosure process is running in the shot X stage, the corresponding protection and control settings will be used to control the operation during this stage.In addition, the dead times have to be set. For each shot, its dead time will be set individually, except for the shot 0, for which no dead timer setting is necessary. The shot 0 is just a virtual state to define the time before the first shot is to issue. Each dead timer specifies the time duration which has to be expired before the reclosure command for this shot can be issued.

402 www.eaton.com

Page 403: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

AR Wear Supervision

Path: [Protection Para\Set[x]\AR\AR Wear Superv]

In this setting menu two Service Alarms can be set as well as the number of permissible reclosure attempts per hour.

BlockFct

Path: [Protection Para\Set[x]\AR\BlockFct]

This group of settings specifies the protection functions by which the autoreclosure function must be blocked even if the autoreclosure function is already initiated.

Note the difference between the protection function which can be blocked by autorecloser and the function(s) here to block the autorecloser.

AR States

The following diagram shows the state transitions between the various states of the autoreclosure function. This diagram visualizes the run time logic and timing sequence according to the state transition direction and the events which trigger the transitions.

www.eaton.com 403

Page 404: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

State transition diagram.

In general, the autoreclosure function is only active (will be initiated) when all of the following conditions are met:

• Autoreclosure function is enabled (In AR General Setting: Function =active);

404 www.eaton.com

Standby

1

Ready

3

Lockout

6

t-ManualCloseBlock

2

t-Reset Lockout

7Blocked

5

AR Cycle

Start

t-dead

t-Run2Ready

4

Lock=True

Initiate AR

Initi

ateF

c=Tr

ue

succ

essf

ul

Bkr=

Pos

CLO

SE Lock=True

Bkr=

Pos

CLO

SE&

t-Man

ualC

lose

Bloc

k=tim

er e

laps

ed

Reset Lockout=True

t-Res

et L

ocko

ut=t

imer

ela

psed

Blo=

Fals

e

Bkr=

Pos

OPE

N&

t-Man

ualC

lose

Bloc

k=tim

er e

laps

ed

Blo=

True

Blo=True

AR.B

lo=T

rue

Lock=True

Bkr=Pos OPEN

Page 405: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

• Breaker contact(s) (52a or/and 52b) is (are) installed and has (have) been programmed; and

• Autoreclosure is not blocked by the blocking inputs (ExBlo1/2).

1 Standby

The autoreclosure is in this state when the following conditions are met:

• The breaker is in the open position;• The autoreclose function is not initiated from any initiate (start) functions; and• No external or internal AR blocking signals are present.

No autoreclose shot operation is possible if the autoreclose function is within Standby state.

2 t-manual close block

Suppose that the breaker is open and the AR state is in Standby state. Then the breaker is closed manually. The event “CB Pos On” starts a Manual-Close-Blocking timer and results in a state transition from »STANDBY« to a transit state - »T-BLO AFTER CB MAN ON«. The autoreclosure function changes into the »READY« state only as the Manual-Close-Blocking timer elapses and the breaker is closed. By means of the manual close blocking timer, a faulty starting of the autoreclose function in case of a Switch-OnTo-Fault condition is prevented.

3 Ready

An activated autoreclose function is considered to be in »READY« state when all of the following conditions are true:

• The breaker is in closed position;

• The Manual-Close-Block-timer elapses after a breaker manual/remote close operation;

• The autoreclose function is not initiated from any initiate (start) functions; and

• No external or internal AR blocking signals are present.

An autoreclose start is only possible if the autoreclose function is in Ready state.

4 Run (Cycle)

The »RUN« state can only be reached if the following conditions are fulfilled:

www.eaton.com 405

Page 406: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

• The autoreclose was in »READY« state before;

• The breaker was in closed position before;

• No external or internal AR Blocking signals exist; and

• At least one of the assigned initiate functions is true (triggers the Autoreclosure).

A complete autoreclose process with multi-shot reclosing will be accomplished inside the Run state.

If the autoreclose gets into the »RUN« state, the autoreclose function transfers its control to a »RUN« state control automatically with several subordinate states which will be described in detail in the next section (AR Cycle).

5 Blocked

An activated autoreclose function goes into the »BLOCKED« state when one of the assigned blocking functions is true.

The autoreclose function exits the »BLOCKED« state if the assigned blocking signal is no longer present.

6 Lockout

An activated autoreclose function goes into the »LOCKOUT« state when one of the following conditions is true:

• An unsuccessful autoreclose is detected after all programmed autoreclose shots. The fault is of permanent nature;

• Reclose failure (incomplete sequence);

• Autoreclose rate per hour exceeds the limit;

• Breaker failure during AR starting;

• Manual breaker close operation during autoreclose process;

• At least one protective function is still tripping before the reclose command is issued; or

The autoreclose function exits the »LOCKOUT« state if the programmed lockout reset signal asserts and programmed Lockout Reset timer elapses.

A Service Alarm (Service Alarm 1 or Service Alarm 2) will not lead to a lockout of the AR function.

406 www.eaton.com

Page 407: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

AR Cycle (Shot)

4 Run (Cycle)

The following drawing shows the state transitions in detail inside an AR run cycle.

www.eaton.com 407

tR2R=OUT&&Bkr=Pos CLOSE

--------------------------AR.successful

tD=OUT&CB=OFF&

CB_READY=TRUE&Trip

=False---------------------------------------------

Shot=Shot+1 & tCI start & Shot=Shot+1 &

tCI start & CB_CLOSE=True

t-Run2Ready

16

t-dead

14

Waiting Bkr Open

13

Ready

11

Ready

11

AR.Lock=TrueAR.Blo=True

AR.Lock=True

AR.Lock=TrueAR.Blo=True

AR.Blo=True

AR.Blo=TrueAR.Lock=True

Initi

ate

AR: I

nitia

teFc

=Trip

&&(S

hotC

ount

er<s

et)

------

------

------

------

------

------

t-CB

open

sta

rt

Bkr=Pos OPEN------------------

t-D: timer started

Initiate AR: InitiateFc=Trip-----------------------------------

tCB-Open start

Bkr=Pos CLOSE-----------------------------------------

tR2R start&CB_CLOSE=False

Reclosing

15

Page 408: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

11 Ready

An activated autoreclose function is considered to be in »READY« state when all of the following conditions are true:

• The breaker is in closed position;

• The Manual-Close-Block-timer elapses after a breaker manual/remote close operation;

• The autoreclose function is not initiated from any initiate (start) functions; and

• No external or internal AR blocking signals are present.

13 Waiting Bkr Open

While in the »WAITING BKR OPEN« state, the autoreclosure supervises if the breaker is really tripped (open) after receiving the trip flag of the initiate protection function within a pre-set breaker supervision time (200 ms). If this is the case, the autoreclosure starts the programmed dead timer and goes to the dead timing state »t-dead«.

14 t-dead

While in the dead timing state »t-dead«, the pre-set dead timer for current AR shot is timing and cannot be interrupted unless there are any blocking or lockout conditions coming.

After dead timer elapses, the autoreclosure issues the breaker reclosing command and goes into the next state: »RECLOSING«, only if the following conditions are met:

• The breaker is in open position;• The breaker is ready for next reclosing operation (if the Bkr. Ready logic input is used);• No pickup from current (assigned) AR initiate function(s);• No trip from current (assigned) AR initiate function(s); and• No general tipping command.

Before issuing the breaker reclosing command, the current shot counter will be incremented. This is very important for the shot-controlled initiate and blocking functions. Before entering into the »RECLOSING« state, the pre-set breaker reclosing supervision timer (»t-Brk-ON-cmd«) will also be started.

15 Reclosing

If there is no other blocking or lockout conditions and the breaker is closed while the breaker reclosing supervision timer is timing, the autoreclosure starts the »t-Run2Ready« timer and goes into the state: »T-RUN2READY«.

408 www.eaton.com

Page 409: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

16 t-Run2Ready

Successful Autoreclosure:While in »T-RUN2READY« state, if there is no other blocking or lockout conditions and no more faults detected within the »t-Run2Ready« timer, the autoreclosure logic will leave the »RUN« state and goes back to the »READY« state. The flag “successful” is set.

Unsuccessful Autoreclose:If a fault is detected again (the shot-controlled initiate function is triggering) while »t-Run2Ready« timer is still timing, the autoreclosure control again transfers to the »RUNNING« state. For a permanent fault, the process described before will be repeated until all programmed shots were operated and the autoreclose process changes into the »LOCKOUT« state. The flag “failed” is set.

Timing Diagrams

Auto Reclosing timing diagram for unsuccessful 2-shot auto reclosing scheme with acceleration at pre-shot.

www.eaton.com 409

Pre Shot

Shot

AR.Running

Shot 1 Shot 2

AR - Module statest

0

1

Ready Running Lockout

Reclosing

t

0

1

Bkr State

t

0

1

Protection

t

0

1

Protection

t

0

1

Fault

t

0

1

t-D1 t-D2 t-Run2Ready

Pos OPEN

Pos CLOSE

Reset

Trip

Reset

Pickup

Clearance

Inception

50P[1].Fasttrip 50P[1].Trip 51P[1].Trip

51P[1] 50P[1]. AdaptSet1 50P[1].DefaultSet

Page 410: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Auto Reclosing timing diagram for successful 2-shot auto reclosing scheme with acceleration at pre-shot.

Auto Reclosing States during manual breaker closing.

Protection Trip while Manual Close Blocking time is Timing

What happens if while the timer manual close block time is timing down the protective device gets a trip signal?

While the timer manual close block time is timing, any trip during this time period trips the breaker. The manual

410 www.eaton.com

Pre Shot

Shot

AR.Running

Shot 1 Shot 2

AR - Module statest

0

1

Ready Running Ready

Reclosing

t0

1

Bkr State

t0

1

Protection

t0

1

Protection

t0

1

Fault

t0

1

t-D1 t-D2 t-Run2Ready

Pos OPEN

Pos CLOSE

Reset

Trip

Reset

Pickup

50P[1].Fasttrip 50P[1].Trip

50P[1]. AdaptSet1 50P[1].DefaultSet

Clearance

Inception

Manual Breaker Close

AR - Module statest

0

1

t-Man Close Blo

t0

1

t-ManualCloseBlock

Pos OPEN

Pos CLOSE

Standby Ready

Bkr State

Page 411: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

close block timer does not care about that and timing continues until it times out.

After it times out, the AR-module looks at the breaker status again and sees that the breaker is open. The AR goes to the »STANDBY« state, no autoreclosure is possible. Note: The AR Does Not go to »LOCKOUT« state!)

AR Lockout Reset Logic in case lockout Reset coming before manual breaker closed.

www.eaton.com 411

Protection Trip

AR - Module statest

0

1

t-Man Close Blo

Manual Breaker Close

t0

1

Bkr State

t0

1

t-ManualCloseBlock

Standby

Pos OPEN

Pos CLOSE

Standby

Lockout Reset

AR - Module statest

0

1

Lockout t-Man Close Blo Ready

Manual Breaker Close

t0

1

t0

1

Lockout Reset Time

t-ManualCloseBlock

t-Reset Lockout Standby

Bkr State

Pos OPEN

Pos CLOSE

Page 412: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

AR Lockout Reset Logic in case lockout Reset coming after manual breaker closed.

Zone Coordination

General Description

What does Zone Coordination mean?

Zone Coordination means that the upstream protection device is doing a virtual autoreclosure while the downstream protective device is doing a “real” autoreclosure. By means of the zone coordination, selectivity can be kept even if a downstream protective device changes its tripping characteristic after a reclosure cycle. The virtual autoreclosure of the upstream device follows the downstream autoreclosure.

What application can be realized by means of Zone Coordination?

A radial distribution system is protected by an upstream protective device (with a breaker) and a downstream protective device with a reclosure and fuse. By means of the zone coordination, a “fuse saving scheme” might be realized. In order to “save fuses”, the downstream protective device might trip for the first reclosure attempt at low tripping values (under-grade the fuse, trying to avoid a damaging of the fuse). If the reclosure attempt fails, the tripping values might be raised (over-grade the fuse) for the second reclosure attempt (using higher tripping values/characteristics).

What is essential?

The triggering thresholds of the upstream and the downstream devices have to be the same but the tripping times have to be selectively.

How is Zone Coordination activated?

The zone coordination function is part of the autoreclosure element and it can be enabled by setting the parameter »Zone coordination« as »active« within the [Protection Para/AR/General Settings] menu for an upstream feeder protection device.

How does the Zone Coordination work (within the upstream protection device)?

When the zone coordination function is enabled, it works similar to a normal autoreclose function with the same setting parameters: maximum reclosure attempts, dead timer for each shot, initiate functions for each shot, and other timers for autoreclose process, but with the following zone coordination features to coordinate with the downstream reclosers.

• The corresponding dead timer for each shot will be started even if the breaker of the upstream feeder relay is NOT tripped from the assigned initiate protective functions.

412 www.eaton.com

Lockout Reset

AR - Module statest

0

1

Lockout t-Man Close Blo Ready

Manual Breaker Close

t0

1

t0

1

t-Lock2Ready t-ManualCloseBlock

t-Reset Lockout

Bkr State

Pos OPEN

Pos CLOSE

Page 413: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

• The dead timer begins timing once the autoreclose senses a drawback of the assigned overcurrent protection pickup signal. This exhibits that the fault current was tripped by the downstream recloser opening.

• The shot counter of an enabled zone coordination will be incremented after the dead timer elapses, even there is no breaker reclosing command issued. Meanwhile, the »T-RUN2READY« timer is started.

• If a permanent fault exists after the downstream recloser is reclosed, the fault current makes the upstream overcurrent protection pick up again, but with the pickup thresholds or operating curves controlled by the incremented shot number. In this way, the upstream feeder will “follow” the protective settings of downstream recloser shot by shot.

• For a transient fault, the autoreclose with zone coordination will not be initiated again because of absence of the fault current and will be reset normally after the expiration of the reset timer »t-Run2Ready«.

www.eaton.com 413

Page 414: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

414 www.eaton.com

Protective Device

Recloser

Shot 1(triggered by: I [1])

Tripping Curve of the Fuse

Shot 2 (triggered by: I [2])

Shot 1(triggered by: I [1])

Shot 2(triggered by: I [2])

I

t

I

t

I

t

Page 415: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Direct Commands of the Automatic Reclosure Module

Parameter Description Setting Range Default Menu Path

Res TotNo suc unsuc

Reset all statistic AR counters: Total number of AR, successful and unsuccessful no of AR.

Inactive,

Active

Inactive [Operation

/Reset]Res ServiceCr Reset the Service Counters Inactive,

Active

Inactive [Operation

/Reset]Reset Lock via HMI

Reset the AR Lockout via the panel. Inactive,

Active

Inactive [Operation

/Reset]Res Max Shots / h Cr

Resetting the Counter for the maximum allowed shots per hour.

Inactive,

Active

Inactive [Operation

/Reset]

Device Planning Parameters of the Module Automatic Reclosure

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Use [Device Plan-ning]

Global Protection Parameters of the Module Automatic Reclosure

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/AR]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/AR]Ex Shot Inc The AR Shot counter will be incremented by

this external Signal. This can be used for Zone Coordination (of upstream Auto Reclosure devices).

1..n, DI-LogicList -.- [Protection Para

/Global Prot Para

/AR]Ex Lock The auto reclosure will locked out by this

external Signal (set into the lockout state).1..n, DI-LogicList -.- [Protection Para

/Global Prot Para

/AR]

www.eaton.com 415

Page 416: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

DI Reset Ex Lock

The Lockout State of the AR can be reset by a digital input.

1..n, DI-LogicList -.- [Protection Para

/Global Prot Para

/AR]Comm Reset Ex Lock

The Lockout State of the AR can be reset by Communication.

-.-,

Modbus.Comm Cmd 1,

Modbus.Comm Cmd 2,

Modbus.Comm Cmd 3,

Modbus.Comm Cmd 4,

Modbus.Comm Cmd 5,

Modbus.Comm Cmd 6,

Modbus.Comm Cmd 7,

Modbus.Comm Cmd 8,

Modbus.Comm Cmd 9,

Modbus.Comm Cmd 10,

Modbus.Comm Cmd 11,

Modbus.Comm Cmd 12,

Modbus.Comm Cmd 13,

Modbus.Comm Cmd 14,

Modbus.Comm Cmd 15,

Modbus.Comm Cmd 16

-.- [Protection Para

/Global Prot Para

/AR]

Setting Group Parameters of the Module Automatic Reclosure

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/AR

/General Settings]

416 www.eaton.com

Page 417: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/AR

/General Settings]Zone coordination

Zone coordination: Sequence coordination is to keep upstream reclosers in step with the downstream ones for fast and delay curve operation, thus avoiding over-tripping

Inactive,

Active

Inactive [Protection Para

/<n>

/AR

/General Settings]Ex Shot Inc Fc The AR Shot counter will be incremented by

this external Signal. This can be used for Zone Coordination (of upstream Auto Reclosure devices). Note: This parameter enables the functionality only. The assignment has to be set within the global parameters.

Inactive,

Active

Inactive [Protection Para

/<n>

/AR

/General Settings]

Ex Lock Fc The auto reclosure will locked out by this external Signal. Note: This parameter enables the functionality only. The assignment has to be set within the global parameters.

Inactive,

Active

Inactive [Protection Para

/<n>

/AR

/General Settings]Reset Mode Reset Mode Auto,

HMI,

DI,

Comm,

HMI And Comm,

HMI And DI,

Comm And DI,

HMI And DI

Auto [Protection Para

/<n>

/AR

/General Settings]

Attempts Maximum number of permitted reclosure attempts.

1 - 6 1 [Protection Para

/<n>

/AR

/General Settings]

www.eaton.com 417

Page 418: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

t-D1 Dead time between trip and reclosure attempt. Can be initiated either by a phase or a ground fault.

Only available if: Attempts = 1-6

0.01 – 9999.00 s 1 s [Protection Para

/<n>

/AR

/Shot Manager

/Shot 1]t-D2 Dead time between trip and reclosure

attempt. Can be initiated either by a phase or a ground fault.

Only available if: Attempts = 2-6

0.01 – 9999.00 s 1 s [Protection Para

/<n>

/AR

/Shot Manager

/Shot 2]t-D3 Dead time between trip and reclosure

attempt. Can be initiated either by a phase or a ground fault.

Only available if: Attempts = 3-6

0.01 – 9999.00 s 1 s [Protection Para

/<n>

/AR

/Shot Manager

/Shot 3]t-D4 Dead time between trip and reclosure

attempt. Can be initiated either by a phase or a ground fault.

Only available if: Attempts = 4-6

0.1 – 9999.00 s 1 s [Protection Para

/<n>

/AR

/Shot Manager

/Shot 4]t-D5 Dead time between trip and reclosure

attempt. Can be initiated either by a phase or a ground fault.

Only available if: Attempts = 5-6

0.01 – 9999.00 s 1 s [Protection Para

/<n>

/AR

/Shot Manager

/Shot 5]t-D6 Dead time between trip and reclosure

attempt. Can be initiated either by a phase or a ground fault.

Only available if: Attempts = 6

0.01 – 9999.00 s 1 s [Protection Para

/<n>

/AR

/Shot Manager

/Shot 6]

418 www.eaton.com

Page 419: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

t-ManualCloseBlock

This timer will be started if the Breaker was switched on manually. While this timer is running, AR cannot be started.

0.01 – 9999.00 s 10.0 s [Protection Para

/<n>

/AR

/General Settings]t-Lock2Ready This timer is started by the lockout reset

signal, and before the timer expire the AR cannot go to any other state.

0.01 – 9999.00 s 10.0 s [Protection Para

/<n>

/AR

/General Settings]t-Run2Ready Examination Time: If the Breaker remains

after an reclosure attempt (shot) for the duration of this timer in the Closed position, the AR has been successful and the AR module returns into the ready state.

0.01 – 9999.00 s 10.0 s [Protection Para

/<n>

/AR

/General Settings]t-Block2Ready The release (de-blocking) of the AR will be

delayed for this time, if there is no blocking signal anymore.

0.01 – 9999.00 s 10.0 s [Protection Para

/<n>

/AR

/General Settings]t-AR Supervision

AR Overall supervision time (> sum of all the timers used by AR)

1.00 – 9999.00 s 100.0 s [Protection Para

/<n>

/AR

/General Settings]Service Alarm 1

As soon as the AR-Counter exceeds this number of reclosure attempts, an alarm will be given out (overhauling of the Bkr.)

1 - 65535 1000 [Protection Para

/<n>

/AR

/AR Wear Superv]Service Alarm 2

Too many auto reclosure attempts. If the configured number of AR cycles is reached, an alarm will be given out.

1 - 65535 65535 [Protection Para

/<n>

/AR

/AR Wear Superv]

www.eaton.com 419

Page 420: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Max AR/h Maximum Number of permitted Autoreclosure Cycles per hour.

1 - 20 10 [Protection Para

/<n>

/AR

/AR Wear Superv]Initiate AR: InitiateFc1

Initiate Auto Reclosure : Initiate Function Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Initiate AR]Initiate AR: InitiateFc2

Initiate Auto Reclosure : Initiate Function Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Initiate AR]Initiate AR: InitiateFc3

Initiate Auto Reclosure : Initiate Function Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Initiate AR]Initiate AR: InitiateFc4

Initiate Auto Reclosure : Initiate Function Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Initiate AR]Shot 1: InitiateFc1

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 1-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 1]

420 www.eaton.com

Page 421: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Shot 1: InitiateFc2

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 1-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 1]Shot 1: InitiateFc3

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 1-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 1]Shot 1: InitiateFc4

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 1-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 1]Shot 2: InitiateFc1

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 2-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 2]Shot 2: InitiateFc2

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 2-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 2]Shot 2: InitiateFc3

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 2-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 2]

www.eaton.com 421

Page 422: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Shot 2: InitiateFc4

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 2-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 2]Shot 3: InitiateFc1

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 3-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 3]Shot 3: InitiateFc2

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 3-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 3]Shot 3: InitiateFc3

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 3-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 3]Shot 3: InitiateFc4

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 3-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 3]Shot 4: InitiateFc1

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 4-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 4]

422 www.eaton.com

Page 423: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Shot 4: InitiateFc2

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 4-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 4]Shot 4: InitiateFc3

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 4-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 4]Shot 4: InitiateFc4

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 4-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 4]Shot 5: InitiateFc1

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 5-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 5]Shot 5: InitiateFc2

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 5-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 5]Shot 5: InitiateFc3

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 5-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 5]

www.eaton.com 423

Page 424: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Shot 5: InitiateFc4

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 5-6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 5]Shot 6: InitiateFc1

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 6]Shot 6: InitiateFc2

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 6]Shot 6: InitiateFc3

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 6]Shot 6: InitiateFc4

Automatic Reclosure Attempt : Initiate Function

Only available if: Attempts = 6

Start fct -.- [Protection Para

/<n>

/AR

/Shot Manager

/Shot 6]

Module Automatic Reclosure Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking1 [Protection Para

/Global Prot Para

/AR]

424 www.eaton.com

Page 425: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

ExBlo2-I Module Input State: External Blocking2 [Protection Para

/Global Prot Para

/AR]Ex Shot Inc-I Module input state: The AR Shot counter

will be incremented by this external Signal. This can be used for Zone Coordination (of upstream Auto Reclosure devices). Note: This parameter enables the functionality only. The assignment has to be set within the global parameters.

[Protection Para

/Global Prot Para

/AR]

Ex Lock-I Module input state: External AR lockout. [Protection Para

/Global Prot Para

/AR]DI Reset Ex Lock-I Module input state: Resetting the lockout

state of the AR (if the resetting via digital inputs has been selected).

[Protection Para

/Global Prot Para

/AR]Comm Reset Ex Lock-I Module input state: Resetting the Lockout

State of the AR by Communication.[Protection Para

/Global Prot Para

/AR]

Module Automatic Reclosure Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingStandby Signal: Standbyt-Man Close Blo Signal: AR blocked after breaker was switched on manually. This

timer will be started if the breaker was switched on manually. While this timer is running, AR cannot be started.

Ready Signal: Ready to shootRunning Signal: Auto Reclosing Runningt-dead Signal: Dead time between trip and reclosure attemptBkr CLOSE Cmd Signal: Bkr. Switch ON (CLOSE) Commandt-Run2Ready Signal: Examination Time: If the Breaker remains after a reclosure

attempt (shot) for the duration of this timer in the Closed position, the AR has been successful and the AR module returns into the ready state.

Lock Signal: Auto Reclosure is locked outt-Reset Lockout Signal: Delay Timer for resetting the AR lockout. The reset of the

AR lockout state will be delayed for this time after the reset signal (e.g digital input or Scada) has been detected.

www.eaton.com 425

Page 426: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Blo Signal: Auto Reclosure is blockedt-Blo Reset Signal: Delay Timer for resetting the AR blocking. The release

(de-blocking) of the AR will be delayed for this time, if there is no blocking signal anymore.

successful Signal: Auto Reclosing successfulfailed Signal: Auto Reclosing Failuret-AR Supervision Signal: AR SupervisionPre Shot Pre Shot ControlShot 1 Shot ControlShot 2 Shot ControlShot 3 Shot ControlShot 4 Shot ControlShot 5 Shot ControlShot 6 Shot ControlService Alarm 1 Signal: AR - Service Alarm 1, too many switching operationsService Alarm 2 Signal: AR - Service Alarm 2, too many switching operationsMax Shots / h exceeded Signal: The maximum allowed number of shots per hour has been

exceeded.Res Statistics Cr Signal: Reset all statistic AR counters: Total number of AR,

successful and unsuccessful no of AR. Res Service Cr Signal: Reset the Service Counters for pickup and blocking.Reset Lockout Signal: The AR Lockout has been reset via the panel.Res Max Shots / h Signal: The Counter for the maximum allowed shots per hour has

been reset.ARRecCState Signal: AutoReclosing states defined by IEC61850:1=Ready/2=In

Progress/3=Successful

Automatic Reclosure Module Values

Value Description Default Size Menu Path

AR Shot No. Counter - Auto Reclosure Attempts 0 0 - 6 [Operation

/Count and RevData

/AR]Total number Cr Total number of all executed

Automatic Reclosures Attempts0 0 - 65536 [Operation

/Count and RevData

/AR]Cr successfl Total number of successfully

executed Automatic Reclosures0 0 - 65536 [Operation

/Count and RevData

/AR]

426 www.eaton.com

Page 427: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Value Description Default Size Menu Path

Cr failed Total number of unsuccessfully executed automatic reclosure attempts

0 0 - 65536 [Operation

/Count and RevData

/AR]Cr Service Alarm1 Remaining numbers of ARs until

Service Alarm 11000 0 - 1000 [Operation

/Count and RevData

/AR]Cr Service Alarm2 Remaining numbers of ARs until

Service Alarm 265536 0 - 65536 [Operation

/Count and RevData

/AR]Max Shots / h Cr Counter for the maximum allowed

shots per hour.0 0 - 65536 [Operation

/Count and RevData

/AR]

Setting Group Parameters of the AR Abort Functions

Parameter Description Setting Range Default Menu Path

Assignment: 1 Abort the AR-cycle, if the state of the assigned signal is true. If the state of this function is true the AR will be aborted.

BlockFct -.- [Protection Para

/<n>

/AR

/BlockFct]Assignment: 2 Abort the AR-cycle, if the state of the

assigned signal is true. If the state of this function is true the AR will be aborted.

BlockFct -.- [Protection Para

/<n>

/AR

/BlockFct]Assignment: 3 Abort the AR-cycle, if the state of the

assigned signal is true. If the state of this function is true the AR will be aborted.

BlockFct -.- [Protection Para

/<n>

/AR

/BlockFct]Assignment: 4 Abort the AR-cycle, if the state of the

assigned signal is true. If the state of this function is true the AR will be aborted.

BlockFct -.- [Protection Para

/<n>

/AR

/BlockFct]

www.eaton.com 427

Page 428: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Assignment: 5 Abort the AR-cycle, if the state of the assigned signal is true. If the state of this function is true the AR will be aborted.

BlockFct -.- [Protection Para

/<n>

/AR

/BlockFct]Assignment: 6 Abort the AR-cycle, if the state of the

assigned signal is true. If the state of this function is true the AR will be aborted.

BlockFct -.- [Protection Para

/<n>

/AR

/BlockFct]

AR Abort Functions

Name Description

-.- No assignment50P[1].TripCmd Signal: Trip Command50P[2].TripCmd Signal: Trip Command50P[3].TripCmd Signal: Trip Command51P[1].TripCmd Signal: Trip Command51P[2].TripCmd Signal: Trip Command51P[3].TripCmd Signal: Trip Command50X[1].TripCmd Signal: Trip Command50X[2].TripCmd Signal: Trip Command51X[1].TripCmd Signal: Trip Command51X[2].TripCmd Signal: Trip Command50R[1].TripCmd Signal: Trip Command50R[2].TripCmd Signal: Trip Command51R[1].TripCmd Signal: Trip Command51R[2].TripCmd Signal: Trip Command27M[1].TripCmd Signal: Trip Command27M[2].TripCmd Signal: Trip Command59M[1].TripCmd Signal: Trip Command59M[2].TripCmd Signal: Trip Command27A[1].TripCmd Signal: Trip Command27A[2].TripCmd Signal: Trip Command59A[1].TripCmd Signal: Trip Command59A[2].TripCmd Signal: Trip Command59N[1].TripCmd Signal: Trip Command59N[2].TripCmd Signal: Trip Command

428 www.eaton.com

Page 429: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

46[1].TripCmd Signal: Trip Command46[2].TripCmd Signal: Trip Command47[1].TripCmd Signal: Trip Command47[2].TripCmd Signal: Trip Command81[1].TripCmd Signal: Trip Command81[2].TripCmd Signal: Trip Command81[3].TripCmd Signal: Trip Command81[4].TripCmd Signal: Trip Command81[5].TripCmd Signal: Trip Command81[6].TripCmd Signal: Trip Command32[1].TripCmd Signal: Trip Command32[2].TripCmd Signal: Trip Command32[3].TripCmd Signal: Trip Command32V[1].TripCmd Signal: Trip Command32V[2].TripCmd Signal: Trip Command32V[3].TripCmd Signal: Trip CommandPF-55D[1].TripCmd Signal: Trip CommandPF-55D[2].TripCmd Signal: Trip CommandPF-55A[1].TripCmd Signal: Trip CommandPF-55A[2].TripCmd Signal: Trip CommandExP[1].TripCmd Signal: Trip CommandExP[2].TripCmd Signal: Trip CommandExP[3].TripCmd Signal: Trip CommandExP[4].TripCmd Signal: Trip Command

AR Start Functions

Name Description

-.- No assignment50P[1].TripCmd Signal: Trip Command50P[2].TripCmd Signal: Trip Command50P[3].TripCmd Signal: Trip Command51P[1].TripCmd Signal: Trip Command51P[2].TripCmd Signal: Trip Command51P[3].TripCmd Signal: Trip Command50X[1].TripCmd Signal: Trip Command50X[2].TripCmd Signal: Trip Command51X[1].TripCmd Signal: Trip Command51X[2].TripCmd Signal: Trip Command

www.eaton.com 429

Page 430: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

50R[1].TripCmd Signal: Trip Command50R[2].TripCmd Signal: Trip Command51R[1].TripCmd Signal: Trip Command51R[2].TripCmd Signal: Trip Command46[1].TripCmd Signal: Trip Command46[2].TripCmd Signal: Trip CommandExP[1].TripCmd Signal: Trip CommandExP[2].TripCmd Signal: Trip CommandExP[3].TripCmd Signal: Trip CommandExP[4].TripCmd Signal: Trip Command

430 www.eaton.com

Page 431: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

46 - Current Unbalance ProtectionElements:46[1] ,46[2]

This is the 46 device Current Unbalance setting, which works similar to the 47 device Voltage Unbalance setting. The positive and negative sequence currents are calculated from the 3-phase currents. The Threshold setting defines a minimum operating current magnitude of either I1 or I2 for the 46 function to operate, which insures that the relay has a solid basis for initiating a current unbalance trip. The »%(I2/I1)« setting is the unbalance trip pickup setting. It is defined by the ratio of negative sequence current to positive sequence current »%(I2/I1)« for ABC rotation and »%(I1/I2)« for ACB rotation. The device will automatically select the correct ratio based on the Phase Sequence setting in the System Configuration group described above.

This function requires positive or negative sequence current magnitude above the threshold setting and the percentage current unbalance above the »%(I2/I1)« setting before allowing a current unbalance trip. Therefore, both the threshold and percent settings must be met for the specified Delay time setting before the relay initiates a trip for current unbalance.

All elements are identically structured.

www.eaton.com 431

Page 432: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

432 www.eaton.com

Nam

e.Tr

ipC

md

Nam

e.Tr

ip

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs

IA

Nam

e.Pi

ckup

Ple

ase

Ref

er to

Dia

gram

: Trip

Blo

ckin

gs

46[1

]...[n

]

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

ICIBNam

e =

46[1

]...[n

]

2 3

1514

AND

AND

PPS

NPS

Filte

r

Nam

e.%(I2

/I1)

Nam

e.Thr

esho

ld

AND

I2

%(I2

/I1)

Nam

e.t t 0

Page 433: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Device Planning Parameters of the Current Unbalance Module

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Use [Device Plan-ning]

Global Protection Parameters of the Current Unbalance Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Unbalance-Prot

/46[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Unbalance-Prot

/46[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Unbalance-Prot

/46[1]]

Setting Group Parameters of the Current Unbalance Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Unbalance-Prot

/46[1]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Unbalance-Prot

/46[1]]

www.eaton.com 433

Page 434: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Blo TripCmd Permanent blocking of the Trip Command of the module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Unbalance-Prot

/46[1]]ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Unbalance-Prot

/46[1]]

Threshold The Threshold setting defines a minimum operating current magnitude of I2 for the 46 function to operate, which ensures that the relay has a solid basis for initiating a current unbalance trip. This is a supervisory function and not a trip level.

0.01 – 4.00 In 0.1 In [Protection Para

/<n>

/Unbalance-Prot

/46[1]]%(I2/I1) The %(I2/I1) setting is the unbalance trip

pickup setting. It is defined by the ratio of negative sequence current to positive sequence current (% Unbalance=I2/I1), or %(I2/I1) for ABC rotation and %(I1/I2) for ACB rotation.

Only available if: %(I2/I1) = Use

2 - 40% 46[1]: 40%

46[2]: 20%

[Protection Para

/<n>

/Unbalance-Prot

/46[1]]

t Tripping delay

Only available if: Characteristic = DEFT

0.00 – 300.00 s 46[1]: 10 s

46[2]: 20 s

[Protection Para

/<n>

/Unbalance-Prot

/46[1]]

Current Unbalance Module Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking 1 [Protection Para

/Global Prot Para

/Unbalance-Prot

/46[1]]

434 www.eaton.com

Page 435: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

ExBlo2-I Module Input State: External Blocking 2 [Protection Para

/Global Prot Para

/Unbalance-Prot

/46[1]]ExBlo TripCmd-I Module Input State: External Blocking of the

Trip Command[Protection Para

/Global Prot Para

/Unbalance-Prot

/46[1]]

Current Unbalance Module Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup Signal: Pickup Negative SequenceTrip Signal: TripTripCmd Signal: Trip Command

Commissioning: Current Unbalance Module

Object to be tested:Test of the unbalanced load protection function.

Necessary means:• Three-phase current source with adjustable current unbalance; and• Timer.

Procedure:

Check the phase sequence:

• Ensure that the phase sequence is the same as that set in the system parameters.

• Feed-in a three-phase nominal current.

• Change to the »Measuring Values« menu.

• Check the measuring value for the unbalanced current »I2 Fund.«. The measuring value displayed for »I2 Fund.« should be zero (within the physical measuring accuracy).

www.eaton.com 435

Page 436: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

If the displayed magnitude for I2 Fund. is the same as that for the balanced nominal currents fed to the relay, it implies that the phase sequence of the currents seen by the relay is reversed.

• Now turn-off phase A.

• Again check the measuring value of the unbalanced current »I2 Fund.« in the »Measuring Values« menu.The measuring value of the unbalanced current »I2 Fund.« should now be 33%.

• Turn-on phase A, but turn-off phase B.

• Once again check the measuring value of the unbalanced current I2 Fund. in the »Measuring Values« menu. The measuring value of the asymmetrical current »I2 Fund.« should be again 33%.

• Turn-on phase B, but turn-off phase C.

• Again check the measuring value of unbalanced current »I2 Fund.« in the »Measuring Values« menu. The measuring value of the unbalanced current »I2 Fund.« should still be 33%.

Testing the trip delay:

• Apply a balanced three-phase current system (nominal currents).

• Switch off IA (the threshold value »Threshold« for »I2 Fund.« must be below 33%).

• Measure the tripping time.

The present current unbalance »I2 Fund.« corresponds with 1/3 of the existing phase current displayed.

Testing the threshold values

• Configure minimum »%(I2/I1)« setting (2%) and an arbitrary threshold value »Threshold« (I2 Fund.).

• For testing the threshold value, a current has to be fed to phase A which is lower than three times the adjusted threshold value »Threshold« (I2 Fund.).

• Feeding only phase A results in »%(I2/I1) = 100%«, so the first condition »%(I2/I1) >= 2%« is always fulfilled.

• Now increase the phase A current until the relay is activated.

Testing the drop-out ratio of the threshold values

Having tripped the relay in the previous test, now decrease the phase A current. The drop-out ratio must not be higher than 0.97 times the threshold value.

Testing %(I2/I1)

• Configure minimum threshold value »Threshold« (I2 Fund.) (0.01 x In) and set »%(I2/I1)« greater or equal to 10%.

436 www.eaton.com

Page 437: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

• Apply a balanced three-phase current system (nominal currents). The measuring value of »%(I2/I1)« should be 0%.

• Now increase the phase A current. With this configuration, the threshold value »Threshold« (I2 Fund.) should be reached before the value »%(I2/I1)« reaches the set »%(I2/I1)« ratio threshold.

• Continue increasing the phase 1 current until the relay is activated.

Testing the drop-out ratio of %(I2/I1)

Having tripped the relay in the previous test, now decrease the phase A current. The drop-out of »%(I2/I1)« has to be 1% below the »%(I2/I1)«setting.

Successful test result:

The measured trip delays, threshold values, and drop-out ratios are within the permitted deviations/tolerances, specified under Technical Data.

www.eaton.com 437

Page 438: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

LOP – Loss of PotentialAvailable elements:LOP

LOP function detects the loss of voltage in any of the voltage input measuring circuits and uses the following measured values and information to detect an LOP condition:

• Three-phase voltages;

• Ratio of negative-to-positive sequence voltages;

• Zero sequence voltage;

• Three-phase currents;

• Residual current (I0);

• Pickup flags from all overcurrent elements; and

• Breaker status.

Once an LOP condition is detected and it lasts longer than an adjustable minimum pickup time, the LOP Pickup will be set. The LOP Block will only be set if the LOP-Block control setting is set to enabled (activated). The LOP Pickup and LOP Block signals can both be used as logical signal to block the protective functions which use the voltage information such as voltage restraint. The minimum pickup timer is used to prevent short time incorrect operation of the LOP function during breaker switching-on operation.

438 www.eaton.com

Page 439: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 439

SQ

R

Inac

tive

LOP

Blo

Enab

le

Activ

e

VA/V

AB

VB/V

BC

VC/V

CA

%(V

2/V1

)

V0 IA IB IC 3*I0

No

IOC

Pic

kup

Bkr s

tate

= c

lose

d

V <

1.0

V

%(V

2/V1

) > 4

0%

V0 <

1.0

V

I < 2

x In

3*I0

< 0

.1 x

In

0.0

999

9 s

t-Pic

kup

0N

ame.

LOP

Blo

Nam

e.Pi

ckup

AND

AND

AND

ANDOR

OR

LOP[

1]...

[n]

Nam

e =

LOP

50 m

s

t-Min

Hol

d Ti

me

0

100

ms

0

t-Res

etD

elay

38

Plea

se R

efer

to D

iagr

am: B

lock

ings

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)2

IOC

= In

stan

tane

ous

Ove

rcur

rent

Page 440: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Device Planning Parameters of the LOP Module

Parameter Description Options Default Menu Path

Mode Mode Use Use [Device Plan-ning]

Global Protection Parameters of the LOP Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Supervision

/LOP]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Supervision

/LOP]

Setting Group Parameters of the LOP Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Supervision

/LOP]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Supervision

/LOP]LOP Blo Enable

Activate (allow) or inactivate (disallow) blocking by the module LOP.

Inactive,

Active

Inactive [Protection Para

/<n>

/Supervision

/LOP]

440 www.eaton.com

Page 441: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

t-Pickup Pickup Delay 0 – 9999.0 s 0.1 s [Protection Para

/<n>

/Supervision

/LOP]

LOP Module Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking1 [Protection Para

/Global Prot Para

/Supervision

/LOP]ExBlo2-I Module Input State: External Blocking2 [Protection Para

/Global Prot Para

/Supervision

/LOP]State Module input state: Breaker Position (0 =

Indeterminate, 1 = OPEN, 2 = CLOSE, 3 = Disturbed)

[]

LOP Module Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingPickup Signal: Pickup Loss of PotentialLOP Blo Signal: Loss of Potential blocks other elements

Commissioning: Loss of Potential

Object to be tested:

Testing the LOP.

Necessary means:

• Three-phase current source and

• Three-phase voltage source.

www.eaton.com 441

Page 442: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Procedure part 1:

Examine if the output signals »LOP BLO « (200ms delay) and »LOP« only become true if:

• Any of the three-phase voltages becomes less 1 Volt;and

• The residual voltage is less than 1 Volt or the %V2/V1 ratio is greater 40%and

• All three-phase currents are less than 2 * Ipu (rated current);and

• The residual current is less than 0.1 Ipu (rated current);and

• No pickup of an IOC element;and

• The breaker is closed.

Successful test result part 1:

The output signals only become true if all the above mentioned conditions are fulfilled.

Procedure part 2:

Assign the »LOP« or »LOP BLO« output signals to all protection element that should be blocked by LOP (e.g.: Undervoltage Protection, Voltage Restraint … ).

Test if those elements are blocked if the LOP modules issue a blocking signal.

Successful test result part 2:

All elements that should be blocked in case of LOP are blocked if the conditions (Procedure part 1) are fulfilled.

442 www.eaton.com

Page 443: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

SOTF - Switch Onto Fault ProtectionSOTF

In case a faulty line is energized (e.g.: when an grounding switch is in the CLOSE position), an instantaneous trip is required. The SOTF module is provided to generate a permissive signal for other protection functions such as overcurrents to accelerate their trips. The SOTF condition is recognized according to the User’s operation mode that can be based on:

• The breaker state;• No current flowing;• Breaker state and no current flowing;• Breaker switched on manually; and/or• An external trigger.

This protection module can initiate a high speed trip of the overcurrent protection modules. The module can be started via a digital input that indicates that the breaker is manually closed.

This module issues a signal only (the module is not armed and does not issue a trip command).

In order to influence the trip settings of the overcurrent protection in case of switching onto a fault, the User has to assign the signal “SOTF.ENABLED“ to an Adaptive Parameter Set. Please refer to Parameter / Adaptive Parameter Sets sections. Within the Adaptive Parameter Set, the User has to modify the trip characteristic of the overcurrent protection according to the User's needs.

www.eaton.com 443

Page 444: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

444 www.eaton.com

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

Nam

e =

SOTF

2

SOTF

.ena

bled

SOTF

.I<

IA IB IC

SOTF

.I<

SOTF

.AR

Blo

*AR

.Run

ning

*

SO

TF.

t-en

able

t0

Ext S

OTF

SOTF

AND

AND

AND

I<

Bkr

Stat

e An

d I<

SOTF

.Mod

e

Bkr

Stat

e

Bkr m

anua

l CLO

SEEx

t SO

TF

OR

OR

*App

lies

only

for d

evic

es w

ith A

uto

Rec

losu

re

Bkr[x

].Ex

Man

CLO

SE C

md

T

41Br

eake

r.Pro

t CLO

SE

Page 445: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Device Planning Parameters of the Switch Onto Fault Module

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Use [Device Plan-ning]

Global Protection Parameters of the Switch Onto Fault Module

Parameter Description Setting Range Default Menu Path

Mode Mode Bkr State,

I<,

Bkr State And I<,

Bkr manual CLOSE,

Ext SOTF

Bkr manual CLOSE

[Protection Para

/Global Prot Para

/SOTF]

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/SOTF]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/SOTF]Rvs Blo Reverse Blocking, if Reverse Blocking is

activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/SOTF]Ext SOTF External Switch Onto Fault

Only available if: Mode = Ext SOTF

1..n, DI-LogicList -.- [Protection Para

/Global Prot Para

/SOTF]

Setting Group Parameters of the Switch Onto Fault Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/SOTF]

www.eaton.com 445

Page 446: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/SOTF]

Rvs Blo Fc Activate (allow) or inactivate (disallow) reverse blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/element are blocked that are configured "Rvs Blo Fc = active".

Inactive,

Active

Inactive [Protection Para

/<n>

/SOTF]

I< The breaker is in the OPEN Position, if the measured current is less than this parameter.

0.01 – 1.00 In 0.01 In [Protection Para

/<n>

/SOTF]t-enable While this timer is running, and while the

module is not blocked, the Switch Onto Fault Module is effective (SOTF is armed).

0.10 – 10.00 s 2 s [Protection Para

/<n>

/SOTF]

Switch Onto Fault Module Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking [Protection Para

/Global Prot Para

/SOTF]ExBlo2-I Module Input State: External Blocking [Protection Para

/Global Prot Para

/SOTF]Rvs Blo-I Module Input State: Reverse Blocking [Protection Para

/Global Prot Para

/SOTF]Ex Man CLOSE Cmd-I Module Input State: External manual

breaker CLOSE command (NOT for AR!)[]

Bkr Pos-I Module input state: Breaker Position by now (switching position)

[]

Ext SOTF-I Module Input State: External Switch Onto Fault Alarm

[Protection Para

/Global Prot Para

/SOTF]

446 www.eaton.com

Page 447: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Signals of the Switch Onto Fault Module (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingRvs Blo Signal: Reverse Blockingenabled Signal: Switch Onto Fault enabled. This Signal can be used to

modify Overcurrent Protection Settings.I< Signal: No Load Current.

Commissioning: Switch Onto Fault [ANSI 50HS]

Object to be tested:

Testing the module Switch Onto Fault according to the configured operating mode:

• I< (No current);• Bkr. state (Breaker position);• I< (No current) and Bkr. state (Breaker position); and• Bkr. manual CLOSE.

Necessary means:

• Three-phase current source (if the Enable Mode depends on current);• Ampere meters (may be needed if the Enable Mode depends on current); and• Timer.

Test Example for Mode Bkr. Manual CLOSE

Mode I< (In order to test the effectiveness): Initially, do not feed any current. Start the timer and feed with an abruptly changing current that is distinctly greater than the I<-threshold to the measuring inputs of the relay.

Mode I< and Bkr. state: Simultaneously, manually switch on the breaker and feed with an abrupt change current that is distinctly greater than the I<-threshold.

Mode Bkr. state: The breaker has to be in the OFF position. The signal „SOTF.ENABLED“=0 is false. If the breaker is switched on, the signal „SOTF.ENABLED“=1 becomes true as long as the timer t-effective is running.

• The breaker has to be in the OPEN position. There must be no load current.

• The status display of the device shows the signal "SOTF.ENABLED“=1.

Testing:

• Manually switch the breaker to the CLOSE position and start the timer at the same time.

www.eaton.com 447

Page 448: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

• After the hold time t-enable is expired, the state of the signal has to change to "SOTF.enabled“=0.

• Write down the measured time.

Successful test result:

The measured total tripping delays or individual tripping delays, threshold values, and drop-out ratios correspond with those values, specified in the adjustment list. Permissible deviations/tolerances can be found in the Tech-nical Data section.

448 www.eaton.com

Page 449: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

CLPU - Supervision Module Cold Load PickupAvailable Elements:CLPU

When manually or automatically closing a breaker after it has been open for a prolonged time, a greater than normal load current may be experienced due to the load inrush . This high starting current causes some overcurrent elements to unnecessarily trip the breaker. The cold load pickup (CLPU) function prevents this from happening.

The cold load pickup function detects a warm-to-cold load transition according to the four selectable cold load detection modes:

• Breaker state;• Undercurrent (I<);• Breaker state AND undercurrent; and• Breaker state OR undercurrent.

After a warm-to-cold load transition has been detected, a specified load-off timer will be started. This User-settable load-off timer is used in some cases to make sure that the load is really “cold” enough. After the load-off timer times out, the CLPU function issues an “enable” signal »CLPU.ENABLED« that can be used to block User-selected, sensitive protection elements such as instantaneous overcurrent elements, current unbalance, or power protection elements. Using this enable signal, some User-selected time inverse overcurrent elements may also be desensitized by means of activating adaptive settings of the corresponding overcurrent elements.

When a cold load condition is finished (a cold-to-warm load condition is detected) due to, for example, breaker closing or load current injection, a load inrush detector will be initiated that supervises the coming and going of the load inrush current process. A load inrush is detected if the coming load current exceeds a User-specified inrush current threshold. This load inrush is considered as finished if the load current is decreased to 90% of the inrush current threshold.

After the inrush current is diminished, a settle timer starts. The cold load pickup enable signal can only be reset after the settle timer times out. Another max-Block timer, which is started parallel with the load inrush detector after a cold load condition is finished, may also terminate the CLPU enable signal if a load inrush condition is prolonged abnormally.

The cold load pickup function can be blocked manually by external or internal signal at the User´s choice. For the devices with the Auto-Reclosing function, the CLPU function will be blocked automatically if auto-reclosure is initiated (AR is running).

This module issues a signal only (it is not armed).

In order to influence the tripping settings of the overcurrent protection, the User has to assign the signal “CLPU.ENABLED“ to an adaptive parameter set. Please refer to the Parameter / Adaptive Parameter Sets section. Within the adaptive parameter set, the User has to modify the tripping characteristic of the overcurrent protection according to the needs.

www.eaton.com 449

Page 450: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Please be aware of the meaning of the two delay timers.

t load Off (Pickup Delay): After this time expires, the load is no longer diversified.

t Max Block (Release Delay): After the starting condition is fulfilled (e.g.: breaker switched on manually), the “CLPU.enabled” signal will be issued for this time. That means for the duration of this time, the tripping thresholds of the overcurrent protection can be desensitized by means of adaptive parameters (please refer to the Parameters section). This timer will be stopped if the current falls below 0.9 times of the threshold of the load inrush detector and remains below 0.9 times of the threshold for the duration of the settle time.

450 www.eaton.com

Page 451: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Example Mode: Breaker Position

www.eaton.com 451

Nam

e =

CLP

U

CLP

U

Cin

Bkr-5

2a

0101

CLP

U.d

etec

ted

t-Loa

d O

fft-M

ax B

lock

Col

d Lo

ad01P

leas

e R

efer

to D

iagr

am: B

lock

ings

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals)

Nam

e =

CLP

U

2

CLP

U.e

nabl

ed

CLP

U.I<

IA IB IC

CLP

U.I<

AR.R

unni

ng*

CLP

U

AND

AND

AND

I<

Bkr

Stat

e An

d I<

CLP

U.M

ode

Bkr

Stat

e

Bkr

Stat

e O

r I<

OR

OR

Bkr[x

].Pos

OPE

N

*App

lies

only

for d

evic

es w

ith A

uto

Rec

losu

re

AND

CLP

U.L

oad

Inru

sh

CLP

U.S

ettle

Tim

e

Imax

1.0

* Thr

esho

ld

0.9

* Thr

esho

ld

Settl

e Ti

me

0

0

Settl

e Ti

me+

e

OR

0

t-Max

Blo

ck

t-Loa

d O

ff

0

CLP

U.d

etec

ted

1.0

* Thr

esho

ld

0.9

* Thr

esho

ld

Load

Inru

sh D

etec

tor

S

Q

R1

Q

Page 452: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Device Planning Parameters of the Cold Load Pickup Module

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Use [Device Plan-ning]

Global Protection Parameter of the Cold Load Pickup Module

Parameter Description Setting Range Default Menu Path

Mode Mode Bkr State,

I<,

Bkr State Or I<,

Bkr State And I<

Bkr State [Protection Para

/Global Prot Para

/CLPU]

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/CLPU]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/CLPU]Rvs Blo Reverse Blocking, if Reverse Blocking is

activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/CLPU]

Set Parameters of the Cold Load Pickup Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/CLPU]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/CLPU]

452 www.eaton.com

Page 453: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Rvs Blo Fc Activate (allow) or inactivate (disallow) reverse blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/element are blocked that are configured "Rvs Blo Fc = active".

Inactive,

Active

Inactive [Protection Para

/<n>

/CLPU]

t-Load Off Select the outage time required for a load to be considered cold. If the Pickup Timer (Delay) has run out, a Cold Load Signal will be issued.

0.00 – 7200.00 s 10 s [Protection Para

/<n>

/CLPU]t-Max Block Select the maximum amount of time

allowed for cold load pickup to be active; if the time has elapsed a warm load signal will be issued.

0.00 – 300.00 s 10 s [Protection Para

/<n>

/CLPU]I< The breaker is in the OPEN Position, if the

measured current is less than this parameter.

0.01 – 1.00 In 0.01 In [Protection Para

/<n>

/CLPU]Threshold Set the load current inrush threshold. 0.10 – 4.00 In 1.2 In [Protection Para

/<n>

/CLPU]Settle Time Select the time for the cold load inrush. 0.00 – 300.00 s 1.00 s [Protection Para

/<n>

/CLPU]

States of the Inputs of the Cold Load Pickup Module

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking [Protection Para

/Global Prot Para

/CLPU]ExBlo2-I Module Input State: External Blocking [Protection Para

/Global Prot Para

/CLPU]Rvs Blo-I Module Input State: Reverse Blocking [Protection Para

/Global Prot Para

/CLPU]

www.eaton.com 453

Page 454: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

Bkr Pos-I Module input state: Breaker Position by now (switching position).

[]

Signals of the Cold Load Pickup Module (States of the Outputs)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingRvs Blo Signal: Reverse Blockingenabled Signal: Cold Load enableddetected Signal: Cold Load detectedI< Signal: No Load Current.Load Inrush Signal: Load InrushSettle Time Signal: Settle Time

Commissioning of the Cold Load Pickup Module

Object to be tested:

Testing the Cold Load Pickup module according to the configured operating mode:

• I< (No current);• Bkr. state (Breaker position);• I< (No Current) and Bkr. state (Breaker position); and• I< (No Current) or Bkr. state (Breaker position).

Necessary means:

• Three-phase current source (if the Enable Mode depends on current);Ampere meters (may be needed if the Enable Mode depends on current); and• Timer.

Test Example for Mode Bkr. State (Breaker Position)

Mode I<: In order to test the tripping delay, start the timer then feed with an abruptly changing current that is distinctly less than the I<-threshold. Measure the tripping delay. In order to measure the drop-out ratio, feed an abruptly changing current that is distinctly above the I<-threshold.

Mode I< and Bkr state: Combine the abruptly changing current(switching the current ON and OFF) with the manual switching ON and OFF of the breaker.

Mode I< or Bkr state: Initially carry out the test with an abruptly changing current that is switched ON and OFF (above and below the I<-threshold). Measure the tripping times. Finally, carry out the test by manually switching the breaker ON and OFF.

454 www.eaton.com

Page 455: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

• The breaker has to be in the OFF position. There must not be any load current.

• The Status Display of the device shows the signal "CLPU.ENABLED“=1.

• The Status Display of the device shows the signal ”CLPU.I<“=1.

Testing the tripping delay and the resetting ratio:

• Manually switch the breaker ON and simultaneously start the timer.•

• After the the »t Max Block (Release Delay)« timer has expired, the signal "CPLU.Enabled “=0 has to be false.

• Write down the measured time.•

• Manually switch the breaker OFF and simultaneously start the timer.•

• After the »t load Off« timer has expired, the signal ”CPLU.ENABLED “=1 has to become true.

• Write down the measured time.

Successful test result:

The measured total tripping delays or individual tripping delays, threshold values, and drop-out ratios correspond with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Tech-nical Data section.

www.eaton.com 455

Page 456: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

27M - Undervoltage ProtectionAvailable elements:27M[1] ,27M[2]

M is for “Main” referring to protection metered by the Main Voltage transformer in the System Configuration.

All undervoltage elements are identically structured.

Definition of Vn: Vn is dependent on the System Parameter setting of "Main VT con".

In case that within the System Parameters "Main VT con" is set to "Open-Delta":

Vn=Main VT sec .

In case that "Main VT con" is set to "Wye":

Vn= MainVT sec3

This is the 27 device undervoltage setting for the main three phase VT. This function consists of a Phase, a Pickup, a Delay setting. The Phase setting allows the User to select at which phase (any one, any two, or all) the undervoltage function operates. The Pickup setting is the magnitude at which the undervoltage element operates. The Delay setting is the time period an undervoltage must occur before the device initiates a trip. Depending on the settings within the System Parameters, the element works based on phase-to-phase (»Open-Delta«) or phase-to-ground (»wye«) voltages. This element will operate depending on the phase setting: if any one, any two, or all of the voltage(s) that is/are selected by the Phase setting drop(s) below the set point. This element works based on RMS values.

An undervoltage pickup occurs when the measured voltage drops below the UV Threshold setting. The undervoltage trip is set when the voltage stays below the threshold setting for the delay time specified (within the number of phases specified by the phase setting). The undervoltage pickup and trip is reset when the voltage rises above the drop-out ratio specified in Specifications section for the undervoltage protection.

If the element should be blocked in the event of a “Loss of Potential”, the »LOP BLO« parameter must be set to »active«.

If the VT measurement location is not at the bus bar side but at the output side, the following has to be taken into account.

When disconnecting the line, it has to be ensured by an »External Blocking« that undervoltage tripping cannot happen. In order to block the 27M element in case that the breaker is open:

• Assign the »Bkr.POS OPEN« signal to a blocking input (»ExBlo1« or »ExBlo2« within the Global Parameters) of the 27M element,and

• »ExBlo Fc« has to be set to “active” within the parameter sets of the the 27M element.

When the auxiliary voltage is switched on and the measuring voltage has not yet been applied, undervoltage tripping has to be prevented by an »External

456 www.eaton.com

Page 457: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Blocking«. Otherwise a continuous tripping would occur, disabling the ability to energize again.

If phase voltages are applied to the measuring inputs of the device and system parameter »VT con« is set to »Phase-to-ground«, the messages issued by the voltage protection module in case of actuation or trip should be interpreted as follows:

»27M[1].PICKUP A« or »27M[1].TRIP A« => pickup or trip caused by phase voltage »VA«.»27M[1].PICKUP B« or »27M[1].TRIP B« => pickup or trip caused by phase voltage »VB«.»27M[1].PICKUP C« or »27M[1].TRIP B« => pickup or trip caused by phase voltage »VC«.

However, if line-to-line voltages are applied to the measuring inputs and system parameter »VT con« is set to »Phase to Phase«, then the messages should be interpreted as follows:

»27M[1].PICKUP A« or »27M[1].TRIP A« => pickup or trip caused by phase-to-phase voltage »VAB«.»27M[1]. PICKUP B« or »27M[1].TRIP B« => pickup or trip caused by phase-to-phase voltage »VBC«.»27M[1]. PICKUP C« or »27M[1].TRIP C« => pickup or trip caused by phase-to-phase voltage »VCA«

www.eaton.com 457

Page 458: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

458 www.eaton.com

Nam

e.Pi

ckup

Pha

se C

Nam

e.Tr

ipC

md

Nam

e.Tr

ip

Nam

e.Pi

ckup

Nam

e.Pi

ckup

Pha

se A

Nam

e.Pi

ckup

Pha

se B

VA VB VC

Plea

se R

efer

to D

iagr

am: B

lock

ings

AND

AND

AND

Nam

e.Tr

ip P

hase

A

Nam

e.Tr

ip P

hase

B

Nam

e.Tr

ip P

hase

C

Ple

ase

Ref

er to

Dia

gram

: Trip

Blo

ckin

gs

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

27M

[1]..

.[n]

V<

AND

AND

Inac

tive

Nam

e.LO

P Bl

o

Activ

e

Nam

e =

27M

[1]..

.[n]

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

2 31514 20 21 2228 29 30

OR

AND

OR

AND

AND

AND

AND

AND

Nam

e.t

t 0

38LO

P.LO

P Bl

o

any

one

Nam

e.M

ode

any

two

all

RM

S

RM

S

RM

S

Page 459: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Device Planning Parameters of the Undervoltage Protection Module

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Use [Device Plan-ning]

Global Protection Parameters of the Undervoltage Protection Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Main-V-Prot

/27M[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Main-V-Prot

/27M[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Main-V-Prot

/27M[1]]

Setting Group Parameters of the Undervoltage Protection Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Main-V-Prot

/27M[1]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Main-V-Prot

/27M[1]]

www.eaton.com 459

Page 460: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Blo TripCmd Permanent blocking of the Trip Command of the module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Main-V-Prot

/27M[1]]ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Main-V-Prot

/27M[1]]

Phases Indicates if one, two of three or all phases are required for operation

Any one,

Any two,

All

Any one [Protection Para

/<n>

/Main-V-Prot

/27M[1]]Pickup If the pickup value is exceeded, the module/

element will be started. Definition of Vn: Vn is dependent on the System Parameter setting of "Main VT con". In case that within the System Parameters "Main VT con" is set to "Open-Delta" , "Vn = Main VT sec ". In case that "Main VT con" is set to "Wye", "Vn = Main VT sec/SQRT(3)".

Only available if: Device Planning: V.Mode = V<

0.01 – 1.30 Vn 27M[1]: 0.80 Vn

27M[2]: 0.90 Vn

[Protection Para

/<n>

/Main-V-Prot

/27M[1]]

t Tripping delay 0.00 – 300.00 s 27M[1]: 10 s

27M[2]: 2.00 s

[Protection Para

/<n>

/Main-V-Prot

/27M[1]]LOP Blo Blocking if voltage transformer failure

detected. LOP (Loss of Potential)Inactive,

Active

Active [Protection Para

/<n>

/Main-V-Prot

/27M[1]]Vstart< If the voltage falls below this voltage, the

Time Depending Voltage Protection will be started.

Only available if: Device Planning: V.Mode = Vstart<

0.01 – 1.30 Vn 0.90 Vn [Protection Para

/<n>

/Main-V-Prot

/27M[1]]

460 www.eaton.com

Page 461: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

V(t)<1 Pickup value

Only available if: Device Planning: V.Mode = V(t)<

0.01 – 1.30 Vn 0.01 Vn [Protection Para

/<n>

/Main-V-Prot

/27M[1]]t1 Tripping delay

Only available if: Device Planning: V.Mode = V(t)<

0.00 – 10.00 s 0.00 s [Protection Para

/<n>

/Main-V-Prot

/27M[1]]V(t)<2 Pickup value

Only available if: Device Planning: V.Mode = V(t)<

0.01 – 1.30 Vn 0.01 Vn [Protection Para

/<n>

/Main-V-Prot

/27M[1]]t2 Tripping delay

Only available if: Device Planning: V.Mode = V(t)<

0.00 – 10.00 s 0.15 s [Protection Para

/<n>

/Main-V-Prot

/27M[1]]V(t)<3 Pickup value

Only available if: Device Planning: V.Mode = V(t)<

0.01 – 1.30 Vn 0.70 Vn [Protection Para

/<n>

/Main-V-Prot

/27M[1]]t3 Tripping delay

Only available if: Device Planning: V.Mode = V(t)<

0.00 – 10.00 s 0.15 s [Protection Para

/<n>

/Main-V-Prot

/27M[1]]V(t)<4 Pickup value

Only available if: Device Planning: V.Mode = V(t)<

0.01 – 1.30 Vn 0.70 Vn [Protection Para

/<n>

/Main-V-Prot

/27M[1]]

www.eaton.com 461

Page 462: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

t4 Tripping delay

Only available if: Device Planning: V.Mode = V(t)<

0.00 – 10.00 s 0.70 s [Protection Para

/<n>

/Main-V-Prot

/27M[1]]V(t)<5 Pickup value

Only available if: Device Planning: V.Mode = V(t)<

0.01 – 1.30 Vn 0.90 Vn [Protection Para

/<n>

/Main-V-Prot

/27M[1]]t5 Tripping delay

Only available if: Device Planning: V.Mode = V(t)<

0.00 – 10.00 s 1.50 s [Protection Para

/<n>

/Main-V-Prot

/27M[1]]V(t)<6 Pickup value

Only available if: Device Planning: V.Mode = V(t)<

0.01 – 1.30 Vn 0.90 Vn [Protection Para

/<n>

/Main-V-Prot

/27M[1]]t6 Tripping delay

Only available if: Device Planning: V.Mode = V(t)<

0.00 – 10.00 s 3.00 s [Protection Para

/<n>

/Main-V-Prot

/27M[1]]V(t)<7 Pickup value

Only available if: Device Planning: V.Mode = V(t)<

0.01 – 1.30 Vn 0.90 Vn [Protection Para

/<n>

/Main-V-Prot

/27M[1]]t7 Tripping delay

Only available if: Device Planning: V.Mode = V(t)<

0.00 – 10.00 s 3.00 s [Protection Para

/<n>

/Main-V-Prot

/27M[1]]

462 www.eaton.com

Page 463: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

V(t)<8 Pickup value

Only available if: Device Planning: V.Mode = V(t)<

0.01 – 1.30 Vn 0.90 Vn [Protection Para

/<n>

/Main-V-Prot

/27M[1]]t8 Tripping delay

Only available if: Device Planning: V.Mode = V(t)<

0.00 – 10.00 s 3.00 s [Protection Para

/<n>

/Main-V-Prot

/27M[1]]V(t)<9 Pickup value

Only available if: Device Planning: V.Mode = V(t)<

0.01 – 1.30 Vn 0.90 Vn [Protection Para

/<n>

/Main-V-Prot

/27M[1]]t9 Tripping delay

Only available if: Device Planning: V.Mode = V(t)<

0.00 – 10.00 s 3.00 s [Protection Para

/<n>

/Main-V-Prot

/27M[1]]V(t)<10 Pickup value

Only available if: Device Planning: V.Mode = V(t)<

0.01 – 1.30 Vn 0.90 Vn [Protection Para

/<n>

/Main-V-Prot

/27M[1]]t10 Tripping delay

Only available if: Device Planning: V.Mode = V(t)<

0.00 – 10.00 s 3.00 s [Protection Para

/<n>

/Main-V-Prot

/27M[1]]

Undervoltage Protection Module Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking 1 [Protection Para

/Global Prot Para

/Main-V-Prot

/27M[1]]

www.eaton.com 463

Page 464: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

ExBlo2-I Module Input State: External Blocking 2 [Protection Para

/Global Prot Para

/Main-V-Prot

/27M[1]]ExBlo TripCmd-I Module Input State: External Blocking of the

Trip Command[Protection Para

/Global Prot Para

/Main-V-Prot

/27M[1]]

Undervoltage Protection Module Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup Phase A Signal: Pickup Phase APickup Phase B Signal: Pickup Phase BPickup Phase C Signal: Pickup Phase CPickup Signal: Pickup Voltage ElementTrip Phase A Signal: General Trip Phase ATrip Phase B Signal: General Trip Phase BTrip Phase C Signal: General Trip Phase CTrip Signal: TripTripCmd Signal: Trip Command

Commissioning: Undervoltage Protection [27M]

This test can be carried out similar to the test for overvoltage protection 59M (by using the related undervoltage values).

Please consider the following deviations:

• For testing the threshold values, the test voltage has to be decreased until the relay is activated.

• For detection of the dropout ratio, the measuring quantity has to be increased to achieve more than 103% of the trip value. At 103% of the trip value, the relay is to dropout at the earliest moment.

464 www.eaton.com

Page 465: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

59M - Overvoltage ProtectionAvailable elements:59M[1] ,59M[2]

M is for “Main” referring to protection metered by the Main Voltage transformer in the System Configuration.

All elements are identically structured.

Definition of Vn: Vn is dependent on the System Parameter setting of "Main VT con".

In case that within the System Parameters "Main VT con" is set to "Open-Delta":

Vn=Main VT sec .

In case that "Main VT con" is set to "Wye":

Vn= MainVT sec3

This is the 59 device Overvoltage setting for the Main VT. This element consists of a Phase, a Pickup, and a Delay setting. The Phase setting allows the User to select which phase (any one, any two, or all) the Overvoltage function operates. Depending on the settings within the System Parameters, the element works based on phase-to-phase (»Open-Delta«) or phase-to-ground (»wye«) voltages. This element will operate depending on the phase setting: if any one, any two, or all of the voltage(s) that is/are selected by the Phase setting rise(s) above the set point. This element works based on RMS values.

An overvoltage pickup occurs when the measured voltage rises above the overvoltage threshold setting. The overvoltage trip is set when the voltage stays above the threshold setting for the delay time specified (within the number of phases specified by the phase setting).. The overvoltage pickup and trip is reset when the voltage falls below the drop-out ratio specified in Specifications section for the overvoltage protection.

If phase voltages are applied to the measuring inputs of the device and system parameter »VT con« is set to »Phase-to-ground«, the messages issued by the voltage protection module in case of actuation or trip should be interpreted as follows:

»59M[1].PICKUP A« or »59M[1].TRIP A« => pickup or trip caused by phase voltage »VA«.»59M[1].PICKUP B« or »59M[1].TRIP B« => pickup or trip caused by phase voltage »VB«.»59M[1].PICKUPC« or »59M[1].TRIP B« => pickup or trip caused by phase voltage »VC«.

However,if line-to-line voltages are applied to the measuring inputs and system parameter »VT con« is set to »Phase to Phase«, then the messages should be interpreted as follows:

»59M[1].PICKUP A« or »59M[1].TRIP A« => pickup or trip caused by line-to-line voltage »VAB«.»59M[1]. PICKUP B« or »59M[1].TRIP B« => pickup or trip caused by line-to-line voltage »VBC«.»59M[1]. PICKUP C« or »59M[1].TRIP C« => pickup or trip caused by line-to-line voltage »VCA«

www.eaton.com 465

Page 466: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

466 www.eaton.com

Nam

e.Pi

ckup

Pha

se C

Nam

e.Tr

ipC

md

any

one

Nam

e.M

ode

any

two

Nam

e.Tr

ip

Nam

e.Pi

ckup

Nam

e.Pi

ckup

Pha

se A

Nam

e.Pi

ckup

Pha

se B

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs

AND

AND

AND

Nam

e.Tr

ip P

hase

A

Nam

e.Tr

ip P

hase

B

Nam

e.Tr

ip P

hase

C

Plea

se R

efer

to D

iagr

am: T

rip B

lock

ings

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

59M

[1]..

.[n]

AND

AND

Nam

e =

59M

[1]..

.[n]

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

2 31514 20 21 2228 29 30

OR

AND

OR

AND

AND

AND

AND

VA VB VC

V>

Nam

e.t t 0

all

RM

S

RM

S

RM

S

Page 467: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Device Planning Parameters of the Overvoltage Protection Module

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Use [Device Plan-ning]

Global Protection Parameters of the Overvoltage Protection Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Main-V-Prot

/59M[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Main-V-Prot

/59M[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Main-V-Prot

/59M[1]]

Setting Group Parameters of the Overvoltage Protection Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Main-V-Prot

/59M[1]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Main-V-Prot

/59M[1]]

www.eaton.com 467

Page 468: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Blo TripCmd Permanent blocking of the Trip Command of the module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Main-V-Prot

/59M[1]]ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Main-V-Prot

/59M[1]]

Phases Indicates if one, two of three or all phases are required for operation

Any one,

Any two,

All

Any one [Protection Para

/<n>

/Main-V-Prot

/59M[1]]Pickup If the pickup value is exceeded, the module/

element will be started. Definition of Vn: Vn is dependent on the System Parameter setting of "Main VT con". In case that within the System Parameters "Main VT con" is set to "Open-Delta" , "Vn = Main VT sec ". In case that "Main VT con" is set to "Wye", "Vn = Main VT sec/SQRT(3)".

Only available if: Device Planning: V.Mode = V>

0.01 – 1.30 Vn 59M[1]: 1.2 Vn

59M[2]: 1.1 Vn

[Protection Para

/<n>

/Main-V-Prot

/59M[1]]

t Tripping delay

Only available if: Device Planning: V.Mode = V> Or V<

0.00 – 300.00 s 59M[1]: 10 s

59M[2]: 2.00 s

[Protection Para

/<n>

/Main-V-Prot

/59M[1]]Vstart< If the voltage falls below this voltage, the

Time Depending Voltage Protection will be started.

0.01 – 1.30 Vn 0.90 Vn [Protection Para

/<n>

/Main-V-Prot

/59M[1]]V(t)<1 Pickup value 0.01 – 1.30 Vn 0.01 Vn [Protection Para

/<n>

/Main-V-Prot

/59M[1]]

468 www.eaton.com

Page 469: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

t1 Tripping delay 0.00 – 10.00 s 0.00 s [Protection Para

/<n>

/Main-V-Prot

/59M[1]]V(t)<2 Pickup value 0.01 – 1.30 Vn 0.01 Vn [Protection Para

/<n>

/Main-V-Prot

/59M[1]]t2 Tripping delay 0.00 – 10.00 s 0.15 s [Protection Para

/<n>

/Main-V-Prot

/59M[1]]V(t)<3 Pickup value 0.01 – 1.30 Vn 0.70 Vn [Protection Para

/<n>

/Main-V-Prot

/59M[1]]t3 Tripping delay 0.00 – 10.00 s 0.15 s [Protection Para

/<n>

/Main-V-Prot

/59M[1]]V(t)<4 Pickup value 0.01 – 1.30 Vn 0.70 Vn [Protection Para

/<n>

/Main-V-Prot

/59M[1]]t4 Tripping delay 0.00 – 10.00 s 0.70 s [Protection Para

/<n>

/Main-V-Prot

/59M[1]]

www.eaton.com 469

Page 470: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

V(t)<5 Pickup value 0.01 – 1.30 Vn 0.90 Vn [Protection Para

/<n>

/Main-V-Prot

/59M[1]]t5 Tripping delay 0.00 – 10.00 s 1.50 s [Protection Para

/<n>

/Main-V-Prot

/59M[1]]V(t)<6 Pickup value 0.01 – 1.30 Vn 0.90 Vn [Protection Para

/<n>

/Main-V-Prot

/59M[1]]t6 Tripping delay 0.00 – 10.00 s 3.00 s [Protection Para

/<n>

/Main-V-Prot

/59M[1]]V(t)<7 Pickup value 0.01 – 1.30 Vn 0.90 Vn [Protection Para

/<n>

/Main-V-Prot

/59M[1]]t7 Tripping delay 0.00 – 10.00 s 3.00 s [Protection Para

/<n>

/Main-V-Prot

/59M[1]]V(t)<8 Pickup value 0.01 – 1.30 Vn 0.90 Vn [Protection Para

/<n>

/Main-V-Prot

/59M[1]]

470 www.eaton.com

Page 471: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

t8 Tripping delay 0.00 – 10.00 s 3.00 s [Protection Para

/<n>

/Main-V-Prot

/59M[1]]V(t)<9 Pickup value 0.01 – 1.30 Vn 0.90 Vn [Protection Para

/<n>

/Main-V-Prot

/59M[1]]t9 Tripping delay 0.00 – 10.00 s 3.00 s [Protection Para

/<n>

/Main-V-Prot

/59M[1]]V(t)<10 Pickup value 0.01 – 1.30 Vn 0.90 Vn [Protection Para

/<n>

/Main-V-Prot

/59M[1]]t10 Tripping delay 0.00 – 10.00 s 3.00 s [Protection Para

/<n>

/Main-V-Prot

/59M[1]]

Overvoltage Protection Module Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking 1 [Protection Para

/Global Prot Para

/Main-V-Prot

/59M[1]]ExBlo2-I Module Input State: External Blocking 2 [Protection Para

/Global Prot Para

/Main-V-Prot

/59M[1]]

www.eaton.com 471

Page 472: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command

[Protection Para

/Global Prot Para

/Main-V-Prot

/59M[1]]

Overvoltage Protection Module Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup Phase A Signal: Pickup Phase APickup Phase B Signal: Pickup Phase BPickup Phase C Signal: Pickup Phase CPickup Signal: Pickup Voltage ElementTrip Phase A Signal: General Trip Phase ATrip Phase B Signal: General Trip Phase BTrip Phase C Signal: General Trip Phase CTrip Signal: TripTripCmd Signal: Trip Command

Commissioning: Overvoltage Protection [59M]

Object to be tested:Test of the overvoltage protection elements, 3 x single-phase and 1 x three-phase (for each element).

Necessary means:• Three phase AC voltage source;• Timer for measuring of the tripping time; and• Voltmeter.

Procedure (3 x single-phase, 1 x three-phase, for each element)

Testing the threshold values:For testing the threshold values and drop-out values, the test voltage has to be increased until the relay is activ-ated. When comparing the displayed values with those of the voltmeter, the deviation must be within the per-missible tolerances.

Testing the trip delay:For testing the trip delay, a timer is to be connected to the contact of the associated trip relay. The timer is started when the limiting value of the tripping voltage is exceeded and it is stopped when the relay trips.

472 www.eaton.com

Page 473: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Testing the drop-out ratio:Reduce the measuring quantity to less than 97% of the trip value. The relay must only drop-out at a minimum of 97% of the trip value.

Successful test result:The measured threshold values, trip delays, and drop-out ratios comply with those specified in the adjustment list. Permissible deviations/tolerances can be taken from the Technical Data.

www.eaton.com 473

Page 474: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

27A - Auxiliary Undervoltage ProtectionAvailable elements:27A[1] ,27A[2]

All elements are identically structured.

This is the 27A device Undervoltage setting for the Auxiliary VT. This device setting works exactly the same as the 27M except it is a single-phase element only operating from the Auxiliary VT input. The Alarm Delay is the time period a LOP must occur before the device initiates a »LOP BLO« signal that can be used to block other elements like 51V (Voltage Restraint).

474 www.eaton.com

Page 475: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 475

Nam

e.V<

AND

Plea

se R

efer

to D

iagr

am: B

lock

ings

Nam

e.Pi

ckup

Nam

e.Tr

ip

Nam

e.Tr

ipC

md

V

Plea

se R

efer

to D

iagr

am: T

rip B

lock

ings

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

Nam

e =

27A[

1]...

[n]

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

2 31514

31 23AN

D

27A[

1]...

[n]

Nam

e.t

t 0

RM

S

Page 476: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Device Planning Parameters of the Aux. Undervoltage Module

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Use [Device Plan-ning]

Global Protection Parameters of the Aux. Undervoltage Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Aux-V-Prot

/27A[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Aux-V-Prot

/27A[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Aux-V-Prot

/27A[1]]

Setting Group Parameters of the Aux. Undervoltage Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Aux-V-Prot

/27A[1]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Aux-V-Prot

/27A[1]]

476 www.eaton.com

Page 477: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Blo TripCmd Permanent blocking of the Trip Command of the module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Aux-V-Prot

/27A[1]]ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Aux-V-Prot

/27A[1]]

Pickup Vn refers to either the primary or secondary voltage of the aux VT.

Only available if: Device Planning: 59.Mode = V<

0.01 – 1.30 Vn 27A[1]: 0.8 Vn

27A[2]: 0.9 Vn

[Protection Para

/<n>

/Aux-V-Prot

/27A[1]]t Tripping delay 0.00 – 300.00 s 27A[1]: 10 s

27A[2]: 2.00 s

[Protection Para

/<n>

/Aux-V-Prot

/27A[1]]

Aux. Undervoltage Module Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking 1 [Protection Para

/Global Prot Para

/Aux-V-Prot

/27A[1]]ExBlo2-I Module Input State: External Blocking 2 [Protection Para

/Global Prot Para

/Aux-V-Prot

/27A[1]]

www.eaton.com 477

Page 478: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command

[Protection Para

/Global Prot Para

/Aux-V-Prot

/27A[1]]

Aux. Undervoltage Module Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup Signal: Pickup Residual Voltage Supervision-ElementTrip Signal: TripTripCmd Signal: Trip Command

Commissioning: Aux. Undervoltage

Object to be tested:Aux. undervoltage protection elements.

Necessary components:• One-phase AC voltage source;• Timer for measuring of the tripping time; and• Voltmeter.

Procedure (for each element):

Testing the threshold valuesFor testing the threshold and dropout values, the test voltage at the measuring input for the residual voltage has to be decreased until the relay is activated. When comparing the displayed values with those of the voltmeter, the deviation must be within the permissible tolerances.

Testing the trip delayFor testing the trip delay, a timer is to be connected to the contact of the associated trip relay. The timer is started when the limiting value of the tripping voltage is reached and it is stopped when the relay trips.

Testing the dropout ratio Increase the measuring quantity to more than 103% of the trip value. The relay must only dropout at a maximum of 103% of the trip value.

Successful test result The measured threshold values, trip delays, and dropout ratios comply with those specified in the adjustment list. Permissible deviations/tolerances can be taken from the Technical Data.

478 www.eaton.com

Page 479: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

59A - Auxiliary Overvoltage ProtectionAvailable elements:59A[1] ,59A[2]

All elements are identically structured.

This is the 59 device Overvoltage setting for the Auxiliary VT. This device setting works exactly the same as the 59M, except it is a single-phase element only operating from the Auxiliary VT input.

www.eaton.com 479

Page 480: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

480 www.eaton.com

Nam

e.Pic

kup

AND

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs

Nam

e.Pi

ckup

Nam

e.Tr

ip

Nam

e.Tr

ipC

md

V

Ple

ase

Ref

er to

Dia

gram

: Trip

Blo

ckin

gs

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

59A[

1]...

[n]

Nam

e =

59A[

1]...

[n]

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

2 31514

31 23AN

D

Nam

e.t t 0

RM

S

Page 481: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Device Planning Parameters of the Aux. Overvoltage Module

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Use [Device Plan-ning]

Global Protection Parameters of the Aux. Overvoltage Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Aux-V-Prot

/59A[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Aux-V-Prot

/59A[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Aux-V-Prot

/59A[1]]

Setting Group Parameters of the Aux. Overvoltage Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Aux-V-Prot

/59A[1]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Aux-V-Prot

/59A[1]]

www.eaton.com 481

Page 482: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Blo TripCmd Permanent blocking of the Trip Command of the module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Aux-V-Prot

/59A[1]]ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Aux-V-Prot

/59A[1]]

Pickup Vn refers to either the primary or secondary voltage of the aux VT.

Only available if: Device Planning: 59.Mode = V>

0.01 – 1.30 Vn 59A[1]: 1.2 Vn

59A[2]: 1.1 Vn

[Protection Para

/<n>

/Aux-V-Prot

/59A[1]]t Tripping delay 0.00 – 300.00 s 59A[1]: 10 s

59A[2]: 2.00 s

[Protection Para

/<n>

/Aux-V-Prot

/59A[1]]

Aux. Overvoltage Module Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking 1 [Protection Para

/Global Prot Para

/Aux-V-Prot

/59A[1]]ExBlo2-I Module Input State: External Blocking 2 [Protection Para

/Global Prot Para

/Aux-V-Prot

/59A[1]]

482 www.eaton.com

Page 483: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command

[Protection Para

/Global Prot Para

/Aux-V-Prot

/59A[1]]

Aux. Overvoltage Module Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup Signal: Pickup Residual Voltage Supervision-ElementTrip Signal: TripTripCmd Signal: Trip Command

Commissioning: Aux. Overvoltage

Object to be tested:Aux. Overvoltage protection elements.

Necessary components:• One-phase AC voltage source;• Timer for measuring of the tripping time; and• Voltmeter.

Procedure (for each element):

Testing the threshold valuesFor testing the threshold and dropout values, the test voltage at the measuring input for the voltage has to be in-creased until the relay is activated. When comparing the displayed values with those of the voltmeter, the devia-tion must be within the permissible tolerances.

Testing the trip delayFor testing the trip delay a timer is to be connected to the contact of the associated trip relay. The timer is started when the limiting value of the tripping voltage is exceeded and it is stopped when the relay trips.

Testing the dropout ratioReduce the measuring quantity to less than 97% of the trip value. The relay must only dropout at a minimum of 97% of the trip value.

Successful test resultThe measured threshold values, trip delays, and dropout ratios comply with those specified in the adjustment list. Permissible deviations/tolerances can be taken from the Technical Data.

www.eaton.com 483

Page 484: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

59N - Neutral OvervoltageAvailable elements:59N[1] ,59N[2]

All elements are identically structured.

This is the 59 device for the Neutral Overvoltage settings. This element offers a criterion setting. The criterion setting tells if the threshold is based on the fundamental (Phasor) or RMS.

484 www.eaton.com

Page 485: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 485

Fund

.

Nam

e.Pic

kup

AND

Plea

se R

efer

to D

iagr

am: B

lock

ings

Nam

e.Pi

ckup

Nam

e.Tr

ip

Nam

e.Tr

ipC

md

VX

Plea

se R

efer

to D

iagr

am: T

rip B

lock

ings

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

59N

[1]..

.[n]

Nam

e =

59N

[1]..

.[n]

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

2 31514

31 23AN

D

Nam

e.t t 0

Page 486: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Device Planning Parameters of the Neutral Overvoltage Module

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Use [Device Plan-ning]

Global Protection Parameters of the Neutral Overvoltage Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Neutral-V-Prot

/59N[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Neutral-V-Prot

/59N[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Neutral-V-Prot

/59N[1]]

Setting Group Parameters of the Neutral Overvoltage Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Neutral-V-Prot

/59N[1]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Neutral-V-Prot

/59N[1]]

486 www.eaton.com

Page 487: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Blo TripCmd Permanent blocking of the Trip Command of the module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Neutral-V-Prot

/59N[1]]ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Neutral-V-Prot

/59N[1]]

Pickup Vn refers to either the primary or secondary voltage of the aux VT.

Only available if: Device Planning: 59.Mode = V>

0.01 – 1.30 Vn 59N[1]: 0.4 Vn

59N[2]: 0.3 Vn

[Protection Para

/<n>

/Neutral-V-Prot

/59N[1]]t Tripping delay 0.00 – 300.00 s 59N[1]: 5.00 s

59N[2]: 2.00 s

[Protection Para

/<n>

/Neutral-V-Prot

/59N[1]]

Neutral Overvoltage Module Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking1 [Protection Para

/Global Prot Para

/Neutral-V-Prot

/59N[1]]ExBlo2-I Module Input State: External Blocking2 [Protection Para

/Global Prot Para

/Neutral-V-Prot

/59N[1]]

www.eaton.com 487

Page 488: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command

[Protection Para

/Global Prot Para

/Neutral-V-Prot

/59N[1]]

Neutral Overvoltage Module Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup Signal: Pickup Residual Voltage Supervision-ElementTrip Signal: TripTripCmd Signal: Trip Command

Commissioning: Neutral Overvoltage Protection

Object to be tested:Neutral overvoltage protection elements.

Necessary components:• One-phase AC voltage source;• Timer for measuring of the tripping time; and• Voltmeter.

Procedure (for each element):

Testing the threshold values For testing the threshold and dropout values, the test voltage at the measuring input for the voltage has to be in-creased until the relay is activated. When comparing the displayed values with those of the voltmeter, the devia-tion must be within the permissible tolerances.

Testing the trip delayFor testing the trip delay, a timer is to be connected to the contact of the associated trip relay. The timer is started when the limiting value of the tripping voltage is exceeded and it is stopped when the relay trips.

Testing the dropout ratioReduce the measuring quantity to less than 97% of the trip value. The relay must only dropout at a minimum of 97% of the trip value.

Successful test resultThe measured threshold values, trip delays, and dropout ratios comply with those specified in the adjustment list. Permissible deviations/tolerances can be taken from the Technical Data.

488 www.eaton.com

Page 489: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

25 - Sync-checkAvailable Elements:Sync

The sync-check function can be bypassed by external sources. In this case, synchronization has to be secured by other synchronizing systems before breaker closing!

The Bus voltages are to be measured by the first three measuring inputs of the voltage measuring card (VA/VAB, VB/VBC, VC/VCA). The line voltage is to be measured by the fourth measuring input of the voltage measuring card (VX). In the menu [System Para/General Settings/V Sync] the User has to define to which phase the fourth measuring input is compared.

Sync-check

The sync-check function is provided for the applications where a line has two-ended power sources. The sync-check function has the abilities to check voltage magnitude, angle differences, and frequency difference (slip frequency) between the bus and the line. If enabled, the sync-check may supervise the closing operation manually, automatically, or both.. This function can be overridden by certain bus-line operation conditions and can be bypassed with an external source.

Voltage Difference ΔV

The first condition for paralleling two electrical systems is that their voltage phasors have the same magnitude. This can be controlled by the generator's AVR.

Frequency Difference (Slip Frequency) ΔF

The second condition for paralleling two electrical systems is that their frequencies are nearly equal. This can be controlled by the generator's speed governor.

www.eaton.com 489

Line VA

Bus VB

Line VCLine VB

Bus VA

Bus VC

Page 490: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

If the generator frequency fBus is not equal to the mains frequency fLine, it results in a slip frequency ΔF = |fBus -fLine| between the two system frequencies.

Voltage Curve with Enlarged Resolution.

490 www.eaton.com

Line VA

Bus VB

Line VCLine VB

Bus VA

Bus VC

Bus f

Line f

t

v(t)

v(t)Linev(t)Line

v(t)Busbarv(t)Busbar

∆ v(t)∆ v(t)

t

∆ v(t)

Page 491: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Angular or Phase Difference.

Even if the frequency of both systems is exactly identical, usually an angular difference of the voltage phasors is the case.

At the instant of synchronization, the angular difference of the two systems should be nearly zero because, otherwise, unwanted load inrushes occur. Theoretically, the angular difference can be regulated to zero by giving short pulses to the speed governors. When paralleling generators with the grid, in practice, synchronization is requested as quick as possible and so usually a slight frequency difference is accepted. In such cases, the angular difference is not constant but changes with the slip frequency ΔF.

By taking the breaker closing time into consideration, a lead of the closing release impulse can be calculated in a way that breaker closing takes place at exactly the time when both systems are in angular conformity.

Basically the following applies:

• Where large rotating masses are concerned, the frequency difference (slip frequency) of the two systems should possibly be nearly zero, because of the very high load inrushes at the instant of breaker closing. For smaller rotating masses, the frequency difference of the systems can be higher.

Synchronization Modes

The sync-check module is able to check the synchronization of two electrical systems (system-to-system) or between a generator and an electrical system (generator-to-system). For paralleling two electrical systems, the station frequency, voltage, and phase angle should be exactly the same as the utility grid. Whereas the synchronization of a generator to a system can be done with a certain slip-frequency, depending on the size of the generator used. Therefore the maximum breaker closing time has to be taken into consideration. With the set breaker closing time, the sync-check module is able to calculate the moment of synchronization and gives the paralleling release.

When paralleling two systems, it has to be verified that the system-to-system mode is selected. Paralleling two systems in generator-to-system mode can cause severe damage!

Working Principle Sync-check (Generator-to-System)

(Please refer to the block diagram following this section.)

The sync-check element measures the three phase-to-neutral voltages »VA«, »VB«, and »VC« or the three phase-to-phase voltages »VAB«, »VBC«, and »VCA« of the generator busbar. The line voltage Vx is measured

www.eaton.com 491

Line VA

Bus VB

Line VCLine VB

Bus VA

Bus VC

Angle Diff

Bus f = Line f

Page 492: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

by the fourth voltage input. If all synchronous conditions are fulfilled (i. e.: ΔV [VoltageDiff], ΔF [SlipFrequency], and Δφ [AngleDiff]) are within the limits, a signal will be issued that both systems are synchronous. An advanced Close Angle Evaluator function takes the breaker closing time into consideration.

492 www.eaton.com

Page 493: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 493

OR

AND

t-Vol

tDea

d0

Min

Live

BusV

olta

ge

Max

Dea

dBus

Volta

ge

Min

Live

Line

Volta

ge

Max

Dea

dLin

eVol

tage

Max

Volta

geD

iff

Max

Slip

Freq

uenc

y

Max

Angl

eDiff

AND

Bus

VA

Bus

VAB

Bus

VC

Bus

VCA

Bus

VB

Bus

VBC

AND

BkrC

lose

Initi

ate

Sync

Mod

e=

Gen

erat

or2S

yste

m

AND

AND

AND

t-Vol

tDea

d0

AND

Bypa

ss-I

Bypa

ss=

Activ

e

AND

AND

AND

AND

OR

AND

AND

AND

AND

t-Max

Sync

Supe

rv0

Line

VX

Adva

nced

Clo

se

Angl

e C

alcu

lato

rBk

r=O

pen

LBD

L=Ac

tive

DBL

L =

Activ

e

Mai

n VT

con

Ext.

Bloc

ked

DBD

L=Ac

tive

Bkr=

Ope

n

LBD

L

DBL

L

DBD

L

Bypa

ss o

verri

de

Sync

ove

rride

LB DB

LBLL

LL

DL

Sync

hron

Run

Tim

ing

Sync

hron

Faile

d

Sync

Ove

rridd

en

VDiff

TooH

igh

In-S

ync

Allo

wed

Slip

TooH

igh

Sys-

in-S

ync

Angl

eDiff

TooH

igh

Syn

c=: S

yncM

ode=

Gen

erat

or2S

yste

mP

leas

e R

efer

to D

iagr

am: B

lock

ings

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)2

Ope

n-D

elta

Wye

Vol

tage

diff

eren

ce: L

ine

to B

us

Freq

uenc

y di

ffere

nce:

Lin

e to

B

us

Ang

le d

iffer

ence

: Lin

e to

Bus

t-Max

BkrC

lose

Del

ay

t

Live

Bus

Live

Line

AND

Page 494: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Working Principle Sync-check (System-to-System)

(Please refer to the block diagram on next page.)

The sync-check function for two systems is very similar to the sync-check function for generator-to-system except there is no need to take the breaker closing time into account. The sync-check element measures the three phase-to-neutral voltages »VA«, »VB«, and »VC« or the three phase-to-phase voltages »VAB«, »VBC«, and »VCA« of the station voltage bus bar. The line voltage Vx is measured by the fourth voltage input. If all synchronous conditions are fulfilled (i. e.: ΔV [VoltageDiff], ΔF [SlipFrequency], and Δφ [AngleDiff]) are within the limits, a signal will be issued that both systems are synchronous.

494 www.eaton.com

Page 495: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 495

OR

AND

t-Vol

tDea

d0

Min

Live

BusV

olta

ge

Max

Dea

dBus

Volta

ge

Min

Live

Line

Volta

ge

Max

Dea

dLin

eVol

tage

Max

Volta

geD

iff

Max

Slip

Freq

uenc

y

Max

Angl

eDiff

AND

Bus

VA

Bus

VAB

Bus

VC

Bus

VCA

Bus

VB

Bus

VBC

AND

AND

AND

t-Vol

tDea

d0

AND

Bypa

ss-I

Bypa

ss=

Activ

e

AND

AND

AND

AND

OR

AND

AND

Line

VX

LBD

L=Ac

tive

DBL

L =

Activ

e

Mai

n VT

con

Ext.

Bloc

ked

DBD

L=Ac

tive

LBD

L

DBL

L

DBD

L

Bypa

ss o

verri

de

Sync

ove

rride

LB DB

LBLL

LL

DL

Sync

Ove

rridd

en

VDiff

TooH

igh

In-S

ync

Allo

wed

Slip

TooH

igh

Sys-

in-S

ync

Angl

eDiff

TooH

igh

Syn

c=: S

yncM

ode=

Sys

tem

2Sys

tem

Ope

n-D

elta

Wye

Volta

ge d

iffer

ence

: Lin

e to

Bus

Freq

uenc

y di

ffere

nce:

Lin

e to

Bu

s

Angl

e di

ffere

nce:

Lin

e to

Bus

Plea

se R

efer

to D

iagr

am: B

lock

ings

(Ele

men

t is

not d

eact

ivate

d an

d no

act

ive

bloc

king

sig

nals

)2

Live

Bus

Live

Line

Page 496: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Sync-check Override Conditions

If enabled the following conditions can override the sync-check function:

• LBDL = Live Bus – Dead Line• DBLL = Dead Bus – Live Line• DBDL = Dead Bus – Dead Line

Also the sync-check function can be bypassed by an external source.

When the sync-check function is overridden or bypassed, synchronization has to be secured by other synchronizing systems before breaker closing!

Device Planning Parameters of the Sync-check Module

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Use [Device Plan-ning]

Trigger Signals for Sync-check

Name Description

-.- No assignmentDI-8P X1.DI 1 Signal: Digital InputDI-8P X1.DI 2 Signal: Digital InputDI-8P X1.DI 3 Signal: Digital InputDI-8P X1.DI 4 Signal: Digital InputDI-8P X1.DI 5 Signal: Digital InputDI-8P X1.DI 6 Signal: Digital InputDI-8P X1.DI 7 Signal: Digital InputDI-8P X1.DI 8 Signal: Digital InputLogic.LE1.Gate Out Signal: Output of the logic gateLogic.LE1.Timer Out Signal: Timer OutputLogic.LE1.Out Signal: Latched Output (Q)Logic.LE1.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE2.Gate Out Signal: Output of the logic gateLogic.LE2.Timer Out Signal: Timer OutputLogic.LE2.Out Signal: Latched Output (Q)Logic.LE2.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE3.Gate Out Signal: Output of the logic gateLogic.LE3.Timer Out Signal: Timer OutputLogic.LE3.Out Signal: Latched Output (Q)Logic.LE3.Out inverted Signal: Negated Latched Output (Q NOT)

496 www.eaton.com

Page 497: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE4.Gate Out Signal: Output of the logic gateLogic.LE4.Timer Out Signal: Timer OutputLogic.LE4.Out Signal: Latched Output (Q)Logic.LE4.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE5.Gate Out Signal: Output of the logic gateLogic.LE5.Timer Out Signal: Timer OutputLogic.LE5.Out Signal: Latched Output (Q)Logic.LE5.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE6.Gate Out Signal: Output of the logic gateLogic.LE6.Timer Out Signal: Timer OutputLogic.LE6.Out Signal: Latched Output (Q)Logic.LE6.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE7.Gate Out Signal: Output of the logic gateLogic.LE7.Timer Out Signal: Timer OutputLogic.LE7.Out Signal: Latched Output (Q)Logic.LE7.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE8.Gate Out Signal: Output of the logic gateLogic.LE8.Timer Out Signal: Timer OutputLogic.LE8.Out Signal: Latched Output (Q)Logic.LE8.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE9.Gate Out Signal: Output of the logic gateLogic.LE9.Timer Out Signal: Timer OutputLogic.LE9.Out Signal: Latched Output (Q)Logic.LE9.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE10.Gate Out Signal: Output of the logic gateLogic.LE10.Timer Out Signal: Timer OutputLogic.LE10.Out Signal: Latched Output (Q)Logic.LE10.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE11.Gate Out Signal: Output of the logic gateLogic.LE11.Timer Out Signal: Timer OutputLogic.LE11.Out Signal: Latched Output (Q)Logic.LE11.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE12.Gate Out Signal: Output of the logic gateLogic.LE12.Timer Out Signal: Timer OutputLogic.LE12.Out Signal: Latched Output (Q)Logic.LE12.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE13.Gate Out Signal: Output of the logic gateLogic.LE13.Timer Out Signal: Timer OutputLogic.LE13.Out Signal: Latched Output (Q)

www.eaton.com 497

Page 498: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE13.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE14.Gate Out Signal: Output of the logic gateLogic.LE14.Timer Out Signal: Timer OutputLogic.LE14.Out Signal: Latched Output (Q)Logic.LE14.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE15.Gate Out Signal: Output of the logic gateLogic.LE15.Timer Out Signal: Timer OutputLogic.LE15.Out Signal: Latched Output (Q)Logic.LE15.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE16.Gate Out Signal: Output of the logic gateLogic.LE16.Timer Out Signal: Timer OutputLogic.LE16.Out Signal: Latched Output (Q)Logic.LE16.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE17.Gate Out Signal: Output of the logic gateLogic.LE17.Timer Out Signal: Timer OutputLogic.LE17.Out Signal: Latched Output (Q)Logic.LE17.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE18.Gate Out Signal: Output of the logic gateLogic.LE18.Timer Out Signal: Timer OutputLogic.LE18.Out Signal: Latched Output (Q)Logic.LE18.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE19.Gate Out Signal: Output of the logic gateLogic.LE19.Timer Out Signal: Timer OutputLogic.LE19.Out Signal: Latched Output (Q)Logic.LE19.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE20.Gate Out Signal: Output of the logic gateLogic.LE20.Timer Out Signal: Timer OutputLogic.LE20.Out Signal: Latched Output (Q)Logic.LE20.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE21.Gate Out Signal: Output of the logic gateLogic.LE21.Timer Out Signal: Timer OutputLogic.LE21.Out Signal: Latched Output (Q)Logic.LE21.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE22.Gate Out Signal: Output of the logic gateLogic.LE22.Timer Out Signal: Timer OutputLogic.LE22.Out Signal: Latched Output (Q)Logic.LE22.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE23.Gate Out Signal: Output of the logic gateLogic.LE23.Timer Out Signal: Timer Output

498 www.eaton.com

Page 499: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE23.Out Signal: Latched Output (Q)Logic.LE23.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE24.Gate Out Signal: Output of the logic gateLogic.LE24.Timer Out Signal: Timer OutputLogic.LE24.Out Signal: Latched Output (Q)Logic.LE24.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE25.Gate Out Signal: Output of the logic gateLogic.LE25.Timer Out Signal: Timer OutputLogic.LE25.Out Signal: Latched Output (Q)Logic.LE25.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE26.Gate Out Signal: Output of the logic gateLogic.LE26.Timer Out Signal: Timer OutputLogic.LE26.Out Signal: Latched Output (Q)Logic.LE26.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE27.Gate Out Signal: Output of the logic gateLogic.LE27.Timer Out Signal: Timer OutputLogic.LE27.Out Signal: Latched Output (Q)Logic.LE27.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE28.Gate Out Signal: Output of the logic gateLogic.LE28.Timer Out Signal: Timer OutputLogic.LE28.Out Signal: Latched Output (Q)Logic.LE28.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE29.Gate Out Signal: Output of the logic gateLogic.LE29.Timer Out Signal: Timer OutputLogic.LE29.Out Signal: Latched Output (Q)Logic.LE29.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE30.Gate Out Signal: Output of the logic gateLogic.LE30.Timer Out Signal: Timer OutputLogic.LE30.Out Signal: Latched Output (Q)Logic.LE30.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE31.Gate Out Signal: Output of the logic gateLogic.LE31.Timer Out Signal: Timer OutputLogic.LE31.Out Signal: Latched Output (Q)Logic.LE31.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE32.Gate Out Signal: Output of the logic gateLogic.LE32.Timer Out Signal: Timer OutputLogic.LE32.Out Signal: Latched Output (Q)Logic.LE32.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE33.Gate Out Signal: Output of the logic gate

www.eaton.com 499

Page 500: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE33.Timer Out Signal: Timer OutputLogic.LE33.Out Signal: Latched Output (Q)Logic.LE33.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE34.Gate Out Signal: Output of the logic gateLogic.LE34.Timer Out Signal: Timer OutputLogic.LE34.Out Signal: Latched Output (Q)Logic.LE34.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE35.Gate Out Signal: Output of the logic gateLogic.LE35.Timer Out Signal: Timer OutputLogic.LE35.Out Signal: Latched Output (Q)Logic.LE35.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE36.Gate Out Signal: Output of the logic gateLogic.LE36.Timer Out Signal: Timer OutputLogic.LE36.Out Signal: Latched Output (Q)Logic.LE36.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE37.Gate Out Signal: Output of the logic gateLogic.LE37.Timer Out Signal: Timer OutputLogic.LE37.Out Signal: Latched Output (Q)Logic.LE37.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE38.Gate Out Signal: Output of the logic gateLogic.LE38.Timer Out Signal: Timer OutputLogic.LE38.Out Signal: Latched Output (Q)Logic.LE38.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE39.Gate Out Signal: Output of the logic gateLogic.LE39.Timer Out Signal: Timer OutputLogic.LE39.Out Signal: Latched Output (Q)Logic.LE39.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE40.Gate Out Signal: Output of the logic gateLogic.LE40.Timer Out Signal: Timer OutputLogic.LE40.Out Signal: Latched Output (Q)Logic.LE40.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE41.Gate Out Signal: Output of the logic gateLogic.LE41.Timer Out Signal: Timer OutputLogic.LE41.Out Signal: Latched Output (Q)Logic.LE41.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE42.Gate Out Signal: Output of the logic gateLogic.LE42.Timer Out Signal: Timer OutputLogic.LE42.Out Signal: Latched Output (Q)Logic.LE42.Out inverted Signal: Negated Latched Output (Q NOT)

500 www.eaton.com

Page 501: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE43.Gate Out Signal: Output of the logic gateLogic.LE43.Timer Out Signal: Timer OutputLogic.LE43.Out Signal: Latched Output (Q)Logic.LE43.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE44.Gate Out Signal: Output of the logic gateLogic.LE44.Timer Out Signal: Timer OutputLogic.LE44.Out Signal: Latched Output (Q)Logic.LE44.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE45.Gate Out Signal: Output of the logic gateLogic.LE45.Timer Out Signal: Timer OutputLogic.LE45.Out Signal: Latched Output (Q)Logic.LE45.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE46.Gate Out Signal: Output of the logic gateLogic.LE46.Timer Out Signal: Timer OutputLogic.LE46.Out Signal: Latched Output (Q)Logic.LE46.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE47.Gate Out Signal: Output of the logic gateLogic.LE47.Timer Out Signal: Timer OutputLogic.LE47.Out Signal: Latched Output (Q)Logic.LE47.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE48.Gate Out Signal: Output of the logic gateLogic.LE48.Timer Out Signal: Timer OutputLogic.LE48.Out Signal: Latched Output (Q)Logic.LE48.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE49.Gate Out Signal: Output of the logic gateLogic.LE49.Timer Out Signal: Timer OutputLogic.LE49.Out Signal: Latched Output (Q)Logic.LE49.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE50.Gate Out Signal: Output of the logic gateLogic.LE50.Timer Out Signal: Timer OutputLogic.LE50.Out Signal: Latched Output (Q)Logic.LE50.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE51.Gate Out Signal: Output of the logic gateLogic.LE51.Timer Out Signal: Timer OutputLogic.LE51.Out Signal: Latched Output (Q)Logic.LE51.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE52.Gate Out Signal: Output of the logic gateLogic.LE52.Timer Out Signal: Timer OutputLogic.LE52.Out Signal: Latched Output (Q)

www.eaton.com 501

Page 502: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE52.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE53.Gate Out Signal: Output of the logic gateLogic.LE53.Timer Out Signal: Timer OutputLogic.LE53.Out Signal: Latched Output (Q)Logic.LE53.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE54.Gate Out Signal: Output of the logic gateLogic.LE54.Timer Out Signal: Timer OutputLogic.LE54.Out Signal: Latched Output (Q)Logic.LE54.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE55.Gate Out Signal: Output of the logic gateLogic.LE55.Timer Out Signal: Timer OutputLogic.LE55.Out Signal: Latched Output (Q)Logic.LE55.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE56.Gate Out Signal: Output of the logic gateLogic.LE56.Timer Out Signal: Timer OutputLogic.LE56.Out Signal: Latched Output (Q)Logic.LE56.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE57.Gate Out Signal: Output of the logic gateLogic.LE57.Timer Out Signal: Timer OutputLogic.LE57.Out Signal: Latched Output (Q)Logic.LE57.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE58.Gate Out Signal: Output of the logic gateLogic.LE58.Timer Out Signal: Timer OutputLogic.LE58.Out Signal: Latched Output (Q)Logic.LE58.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE59.Gate Out Signal: Output of the logic gateLogic.LE59.Timer Out Signal: Timer OutputLogic.LE59.Out Signal: Latched Output (Q)Logic.LE59.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE60.Gate Out Signal: Output of the logic gateLogic.LE60.Timer Out Signal: Timer OutputLogic.LE60.Out Signal: Latched Output (Q)Logic.LE60.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE61.Gate Out Signal: Output of the logic gateLogic.LE61.Timer Out Signal: Timer OutputLogic.LE61.Out Signal: Latched Output (Q)Logic.LE61.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE62.Gate Out Signal: Output of the logic gateLogic.LE62.Timer Out Signal: Timer Output

502 www.eaton.com

Page 503: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE62.Out Signal: Latched Output (Q)Logic.LE62.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE63.Gate Out Signal: Output of the logic gateLogic.LE63.Timer Out Signal: Timer OutputLogic.LE63.Out Signal: Latched Output (Q)Logic.LE63.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE64.Gate Out Signal: Output of the logic gateLogic.LE64.Timer Out Signal: Timer OutputLogic.LE64.Out Signal: Latched Output (Q)Logic.LE64.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE65.Gate Out Signal: Output of the logic gateLogic.LE65.Timer Out Signal: Timer OutputLogic.LE65.Out Signal: Latched Output (Q)Logic.LE65.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE66.Gate Out Signal: Output of the logic gateLogic.LE66.Timer Out Signal: Timer OutputLogic.LE66.Out Signal: Latched Output (Q)Logic.LE66.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE67.Gate Out Signal: Output of the logic gateLogic.LE67.Timer Out Signal: Timer OutputLogic.LE67.Out Signal: Latched Output (Q)Logic.LE67.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE68.Gate Out Signal: Output of the logic gateLogic.LE68.Timer Out Signal: Timer OutputLogic.LE68.Out Signal: Latched Output (Q)Logic.LE68.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE69.Gate Out Signal: Output of the logic gateLogic.LE69.Timer Out Signal: Timer OutputLogic.LE69.Out Signal: Latched Output (Q)Logic.LE69.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE70.Gate Out Signal: Output of the logic gateLogic.LE70.Timer Out Signal: Timer OutputLogic.LE70.Out Signal: Latched Output (Q)Logic.LE70.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE71.Gate Out Signal: Output of the logic gateLogic.LE71.Timer Out Signal: Timer OutputLogic.LE71.Out Signal: Latched Output (Q)Logic.LE71.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE72.Gate Out Signal: Output of the logic gate

www.eaton.com 503

Page 504: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE72.Timer Out Signal: Timer OutputLogic.LE72.Out Signal: Latched Output (Q)Logic.LE72.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE73.Gate Out Signal: Output of the logic gateLogic.LE73.Timer Out Signal: Timer OutputLogic.LE73.Out Signal: Latched Output (Q)Logic.LE73.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE74.Gate Out Signal: Output of the logic gateLogic.LE74.Timer Out Signal: Timer OutputLogic.LE74.Out Signal: Latched Output (Q)Logic.LE74.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE75.Gate Out Signal: Output of the logic gateLogic.LE75.Timer Out Signal: Timer OutputLogic.LE75.Out Signal: Latched Output (Q)Logic.LE75.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE76.Gate Out Signal: Output of the logic gateLogic.LE76.Timer Out Signal: Timer OutputLogic.LE76.Out Signal: Latched Output (Q)Logic.LE76.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE77.Gate Out Signal: Output of the logic gateLogic.LE77.Timer Out Signal: Timer OutputLogic.LE77.Out Signal: Latched Output (Q)Logic.LE77.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE78.Gate Out Signal: Output of the logic gateLogic.LE78.Timer Out Signal: Timer OutputLogic.LE78.Out Signal: Latched Output (Q)Logic.LE78.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE79.Gate Out Signal: Output of the logic gateLogic.LE79.Timer Out Signal: Timer OutputLogic.LE79.Out Signal: Latched Output (Q)Logic.LE79.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE80.Gate Out Signal: Output of the logic gateLogic.LE80.Timer Out Signal: Timer OutputLogic.LE80.Out Signal: Latched Output (Q)Logic.LE80.Out inverted Signal: Negated Latched Output (Q NOT)Sys.Maint Mode Active Signal: Arc Flash Reduction Maintenance ActiveSys.Maint Mode Inactive Signal: Arc Flash Reduction Maintenance Inactive

504 www.eaton.com

Page 505: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Sync-check Release Signals

Name Description

-.- No assignmentSync.In-Sync Allowed Signal: In-Sync AllowedDI-8P X1.DI 1 Signal: Digital InputDI-8P X1.DI 2 Signal: Digital InputDI-8P X1.DI 3 Signal: Digital InputDI-8P X1.DI 4 Signal: Digital InputDI-8P X1.DI 5 Signal: Digital InputDI-8P X1.DI 6 Signal: Digital InputDI-8P X1.DI 7 Signal: Digital InputDI-8P X1.DI 8 Signal: Digital InputLogic.LE1.Gate Out Signal: Output of the logic gateLogic.LE1.Timer Out Signal: Timer OutputLogic.LE1.Out Signal: Latched Output (Q)Logic.LE1.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE2.Gate Out Signal: Output of the logic gateLogic.LE2.Timer Out Signal: Timer OutputLogic.LE2.Out Signal: Latched Output (Q)Logic.LE2.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE3.Gate Out Signal: Output of the logic gateLogic.LE3.Timer Out Signal: Timer OutputLogic.LE3.Out Signal: Latched Output (Q)Logic.LE3.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE4.Gate Out Signal: Output of the logic gateLogic.LE4.Timer Out Signal: Timer OutputLogic.LE4.Out Signal: Latched Output (Q)Logic.LE4.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE5.Gate Out Signal: Output of the logic gateLogic.LE5.Timer Out Signal: Timer OutputLogic.LE5.Out Signal: Latched Output (Q)Logic.LE5.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE6.Gate Out Signal: Output of the logic gateLogic.LE6.Timer Out Signal: Timer OutputLogic.LE6.Out Signal: Latched Output (Q)Logic.LE6.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE7.Gate Out Signal: Output of the logic gateLogic.LE7.Timer Out Signal: Timer OutputLogic.LE7.Out Signal: Latched Output (Q)Logic.LE7.Out inverted Signal: Negated Latched Output (Q NOT)

www.eaton.com 505

Page 506: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE8.Gate Out Signal: Output of the logic gateLogic.LE8.Timer Out Signal: Timer OutputLogic.LE8.Out Signal: Latched Output (Q)Logic.LE8.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE9.Gate Out Signal: Output of the logic gateLogic.LE9.Timer Out Signal: Timer OutputLogic.LE9.Out Signal: Latched Output (Q)Logic.LE9.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE10.Gate Out Signal: Output of the logic gateLogic.LE10.Timer Out Signal: Timer OutputLogic.LE10.Out Signal: Latched Output (Q)Logic.LE10.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE11.Gate Out Signal: Output of the logic gateLogic.LE11.Timer Out Signal: Timer OutputLogic.LE11.Out Signal: Latched Output (Q)Logic.LE11.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE12.Gate Out Signal: Output of the logic gateLogic.LE12.Timer Out Signal: Timer OutputLogic.LE12.Out Signal: Latched Output (Q)Logic.LE12.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE13.Gate Out Signal: Output of the logic gateLogic.LE13.Timer Out Signal: Timer OutputLogic.LE13.Out Signal: Latched Output (Q)Logic.LE13.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE14.Gate Out Signal: Output of the logic gateLogic.LE14.Timer Out Signal: Timer OutputLogic.LE14.Out Signal: Latched Output (Q)Logic.LE14.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE15.Gate Out Signal: Output of the logic gateLogic.LE15.Timer Out Signal: Timer OutputLogic.LE15.Out Signal: Latched Output (Q)Logic.LE15.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE16.Gate Out Signal: Output of the logic gateLogic.LE16.Timer Out Signal: Timer OutputLogic.LE16.Out Signal: Latched Output (Q)Logic.LE16.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE17.Gate Out Signal: Output of the logic gateLogic.LE17.Timer Out Signal: Timer OutputLogic.LE17.Out Signal: Latched Output (Q)

506 www.eaton.com

Page 507: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE17.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE18.Gate Out Signal: Output of the logic gateLogic.LE18.Timer Out Signal: Timer OutputLogic.LE18.Out Signal: Latched Output (Q)Logic.LE18.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE19.Gate Out Signal: Output of the logic gateLogic.LE19.Timer Out Signal: Timer OutputLogic.LE19.Out Signal: Latched Output (Q)Logic.LE19.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE20.Gate Out Signal: Output of the logic gateLogic.LE20.Timer Out Signal: Timer OutputLogic.LE20.Out Signal: Latched Output (Q)Logic.LE20.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE21.Gate Out Signal: Output of the logic gateLogic.LE21.Timer Out Signal: Timer OutputLogic.LE21.Out Signal: Latched Output (Q)Logic.LE21.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE22.Gate Out Signal: Output of the logic gateLogic.LE22.Timer Out Signal: Timer OutputLogic.LE22.Out Signal: Latched Output (Q)Logic.LE22.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE23.Gate Out Signal: Output of the logic gateLogic.LE23.Timer Out Signal: Timer OutputLogic.LE23.Out Signal: Latched Output (Q)Logic.LE23.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE24.Gate Out Signal: Output of the logic gateLogic.LE24.Timer Out Signal: Timer OutputLogic.LE24.Out Signal: Latched Output (Q)Logic.LE24.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE25.Gate Out Signal: Output of the logic gateLogic.LE25.Timer Out Signal: Timer OutputLogic.LE25.Out Signal: Latched Output (Q)Logic.LE25.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE26.Gate Out Signal: Output of the logic gateLogic.LE26.Timer Out Signal: Timer OutputLogic.LE26.Out Signal: Latched Output (Q)Logic.LE26.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE27.Gate Out Signal: Output of the logic gateLogic.LE27.Timer Out Signal: Timer Output

www.eaton.com 507

Page 508: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE27.Out Signal: Latched Output (Q)Logic.LE27.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE28.Gate Out Signal: Output of the logic gateLogic.LE28.Timer Out Signal: Timer OutputLogic.LE28.Out Signal: Latched Output (Q)Logic.LE28.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE29.Gate Out Signal: Output of the logic gateLogic.LE29.Timer Out Signal: Timer OutputLogic.LE29.Out Signal: Latched Output (Q)Logic.LE29.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE30.Gate Out Signal: Output of the logic gateLogic.LE30.Timer Out Signal: Timer OutputLogic.LE30.Out Signal: Latched Output (Q)Logic.LE30.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE31.Gate Out Signal: Output of the logic gateLogic.LE31.Timer Out Signal: Timer OutputLogic.LE31.Out Signal: Latched Output (Q)Logic.LE31.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE32.Gate Out Signal: Output of the logic gateLogic.LE32.Timer Out Signal: Timer OutputLogic.LE32.Out Signal: Latched Output (Q)Logic.LE32.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE33.Gate Out Signal: Output of the logic gateLogic.LE33.Timer Out Signal: Timer OutputLogic.LE33.Out Signal: Latched Output (Q)Logic.LE33.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE34.Gate Out Signal: Output of the logic gateLogic.LE34.Timer Out Signal: Timer OutputLogic.LE34.Out Signal: Latched Output (Q)Logic.LE34.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE35.Gate Out Signal: Output of the logic gateLogic.LE35.Timer Out Signal: Timer OutputLogic.LE35.Out Signal: Latched Output (Q)Logic.LE35.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE36.Gate Out Signal: Output of the logic gateLogic.LE36.Timer Out Signal: Timer OutputLogic.LE36.Out Signal: Latched Output (Q)Logic.LE36.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE37.Gate Out Signal: Output of the logic gate

508 www.eaton.com

Page 509: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE37.Timer Out Signal: Timer OutputLogic.LE37.Out Signal: Latched Output (Q)Logic.LE37.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE38.Gate Out Signal: Output of the logic gateLogic.LE38.Timer Out Signal: Timer OutputLogic.LE38.Out Signal: Latched Output (Q)Logic.LE38.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE39.Gate Out Signal: Output of the logic gateLogic.LE39.Timer Out Signal: Timer OutputLogic.LE39.Out Signal: Latched Output (Q)Logic.LE39.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE40.Gate Out Signal: Output of the logic gateLogic.LE40.Timer Out Signal: Timer OutputLogic.LE40.Out Signal: Latched Output (Q)Logic.LE40.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE41.Gate Out Signal: Output of the logic gateLogic.LE41.Timer Out Signal: Timer OutputLogic.LE41.Out Signal: Latched Output (Q)Logic.LE41.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE42.Gate Out Signal: Output of the logic gateLogic.LE42.Timer Out Signal: Timer OutputLogic.LE42.Out Signal: Latched Output (Q)Logic.LE42.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE43.Gate Out Signal: Output of the logic gateLogic.LE43.Timer Out Signal: Timer OutputLogic.LE43.Out Signal: Latched Output (Q)Logic.LE43.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE44.Gate Out Signal: Output of the logic gateLogic.LE44.Timer Out Signal: Timer OutputLogic.LE44.Out Signal: Latched Output (Q)Logic.LE44.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE45.Gate Out Signal: Output of the logic gateLogic.LE45.Timer Out Signal: Timer OutputLogic.LE45.Out Signal: Latched Output (Q)Logic.LE45.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE46.Gate Out Signal: Output of the logic gateLogic.LE46.Timer Out Signal: Timer OutputLogic.LE46.Out Signal: Latched Output (Q)Logic.LE46.Out inverted Signal: Negated Latched Output (Q NOT)

www.eaton.com 509

Page 510: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE47.Gate Out Signal: Output of the logic gateLogic.LE47.Timer Out Signal: Timer OutputLogic.LE47.Out Signal: Latched Output (Q)Logic.LE47.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE48.Gate Out Signal: Output of the logic gateLogic.LE48.Timer Out Signal: Timer OutputLogic.LE48.Out Signal: Latched Output (Q)Logic.LE48.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE49.Gate Out Signal: Output of the logic gateLogic.LE49.Timer Out Signal: Timer OutputLogic.LE49.Out Signal: Latched Output (Q)Logic.LE49.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE50.Gate Out Signal: Output of the logic gateLogic.LE50.Timer Out Signal: Timer OutputLogic.LE50.Out Signal: Latched Output (Q)Logic.LE50.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE51.Gate Out Signal: Output of the logic gateLogic.LE51.Timer Out Signal: Timer OutputLogic.LE51.Out Signal: Latched Output (Q)Logic.LE51.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE52.Gate Out Signal: Output of the logic gateLogic.LE52.Timer Out Signal: Timer OutputLogic.LE52.Out Signal: Latched Output (Q)Logic.LE52.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE53.Gate Out Signal: Output of the logic gateLogic.LE53.Timer Out Signal: Timer OutputLogic.LE53.Out Signal: Latched Output (Q)Logic.LE53.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE54.Gate Out Signal: Output of the logic gateLogic.LE54.Timer Out Signal: Timer OutputLogic.LE54.Out Signal: Latched Output (Q)Logic.LE54.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE55.Gate Out Signal: Output of the logic gateLogic.LE55.Timer Out Signal: Timer OutputLogic.LE55.Out Signal: Latched Output (Q)Logic.LE55.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE56.Gate Out Signal: Output of the logic gateLogic.LE56.Timer Out Signal: Timer OutputLogic.LE56.Out Signal: Latched Output (Q)

510 www.eaton.com

Page 511: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE56.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE57.Gate Out Signal: Output of the logic gateLogic.LE57.Timer Out Signal: Timer OutputLogic.LE57.Out Signal: Latched Output (Q)Logic.LE57.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE58.Gate Out Signal: Output of the logic gateLogic.LE58.Timer Out Signal: Timer OutputLogic.LE58.Out Signal: Latched Output (Q)Logic.LE58.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE59.Gate Out Signal: Output of the logic gateLogic.LE59.Timer Out Signal: Timer OutputLogic.LE59.Out Signal: Latched Output (Q)Logic.LE59.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE60.Gate Out Signal: Output of the logic gateLogic.LE60.Timer Out Signal: Timer OutputLogic.LE60.Out Signal: Latched Output (Q)Logic.LE60.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE61.Gate Out Signal: Output of the logic gateLogic.LE61.Timer Out Signal: Timer OutputLogic.LE61.Out Signal: Latched Output (Q)Logic.LE61.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE62.Gate Out Signal: Output of the logic gateLogic.LE62.Timer Out Signal: Timer OutputLogic.LE62.Out Signal: Latched Output (Q)Logic.LE62.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE63.Gate Out Signal: Output of the logic gateLogic.LE63.Timer Out Signal: Timer OutputLogic.LE63.Out Signal: Latched Output (Q)Logic.LE63.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE64.Gate Out Signal: Output of the logic gateLogic.LE64.Timer Out Signal: Timer OutputLogic.LE64.Out Signal: Latched Output (Q)Logic.LE64.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE65.Gate Out Signal: Output of the logic gateLogic.LE65.Timer Out Signal: Timer OutputLogic.LE65.Out Signal: Latched Output (Q)Logic.LE65.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE66.Gate Out Signal: Output of the logic gateLogic.LE66.Timer Out Signal: Timer Output

www.eaton.com 511

Page 512: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE66.Out Signal: Latched Output (Q)Logic.LE66.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE67.Gate Out Signal: Output of the logic gateLogic.LE67.Timer Out Signal: Timer OutputLogic.LE67.Out Signal: Latched Output (Q)Logic.LE67.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE68.Gate Out Signal: Output of the logic gateLogic.LE68.Timer Out Signal: Timer OutputLogic.LE68.Out Signal: Latched Output (Q)Logic.LE68.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE69.Gate Out Signal: Output of the logic gateLogic.LE69.Timer Out Signal: Timer OutputLogic.LE69.Out Signal: Latched Output (Q)Logic.LE69.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE70.Gate Out Signal: Output of the logic gateLogic.LE70.Timer Out Signal: Timer OutputLogic.LE70.Out Signal: Latched Output (Q)Logic.LE70.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE71.Gate Out Signal: Output of the logic gateLogic.LE71.Timer Out Signal: Timer OutputLogic.LE71.Out Signal: Latched Output (Q)Logic.LE71.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE72.Gate Out Signal: Output of the logic gateLogic.LE72.Timer Out Signal: Timer OutputLogic.LE72.Out Signal: Latched Output (Q)Logic.LE72.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE73.Gate Out Signal: Output of the logic gateLogic.LE73.Timer Out Signal: Timer OutputLogic.LE73.Out Signal: Latched Output (Q)Logic.LE73.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE74.Gate Out Signal: Output of the logic gateLogic.LE74.Timer Out Signal: Timer OutputLogic.LE74.Out Signal: Latched Output (Q)Logic.LE74.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE75.Gate Out Signal: Output of the logic gateLogic.LE75.Timer Out Signal: Timer OutputLogic.LE75.Out Signal: Latched Output (Q)Logic.LE75.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE76.Gate Out Signal: Output of the logic gate

512 www.eaton.com

Page 513: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE76.Timer Out Signal: Timer OutputLogic.LE76.Out Signal: Latched Output (Q)Logic.LE76.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE77.Gate Out Signal: Output of the logic gateLogic.LE77.Timer Out Signal: Timer OutputLogic.LE77.Out Signal: Latched Output (Q)Logic.LE77.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE78.Gate Out Signal: Output of the logic gateLogic.LE78.Timer Out Signal: Timer OutputLogic.LE78.Out Signal: Latched Output (Q)Logic.LE78.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE79.Gate Out Signal: Output of the logic gateLogic.LE79.Timer Out Signal: Timer OutputLogic.LE79.Out Signal: Latched Output (Q)Logic.LE79.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE80.Gate Out Signal: Output of the logic gateLogic.LE80.Timer Out Signal: Timer OutputLogic.LE80.Out Signal: Latched Output (Q)Logic.LE80.Out inverted Signal: Negated Latched Output (Q NOT)

Global Protection Parameter of the Sync-check Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Sync]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Sync]Bypass The Sync-check will be bypassed if the

state of the assigned signal (logic input) becomes true.

1..n, DI-LogicList -.- [Protection Para

/Global Prot Para

/Sync]BkrCloseInitiate Breaker Close Initiate with sync-check from

any control sources (e.g.: HMI / SCADA). If the state of the assigned signal becomes true, a Breaker Close will be initiated (Trigger Source).

1..n, SyncRequestList -.- [Protection Para

/Global Prot Para

/Sync]

www.eaton.com 513

Page 514: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Set Parameters of the Sync-check Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Sync

/General Settings]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Sync

/General Settings]Bypass Fc Allowing to bypass the Sync-check, if the

state signal that is assigned to the parameter with the same name within the Global Parameters (logic input) becomes true.

Inactive,

Active

Inactive [Protection Para

/<n>

/Sync

/General Settings]SyncMode Sync-check mode: GENERATOR2SYSTEM

= Synchronizing generator to system (breaker close initiate needed). SYSTEM2SYSTEM = Sync-check between two systems (Stand-Alone, no breaker info needed).

System2System,

Generator2System

System2System [Protection Para

/<n>

/Sync

/Mode / Times]t-MaxBkrCloseDelay

Maximum breaker close time delay (Only used for GENERATOR-SYSTEM working mode and is critical for a correct synchronized switching) .

Only available if: SyncMode = System2System

0.00 – 300.00 s 0.05 s [Protection Para

/<n>

/Sync

/Mode / Times]t-MaxSyncSuperv

Synchron-Run timer: Max. time allowed for synchronizing process after a close initiate. Only used for GENERATOR2SYSTEM working mode.

Only available if: SyncMode = System2System

0.00 – 3000.00 s 30.00 s [Protection Para

/<n>

/Sync

/Mode / Times]MinLiveBusVoltage

Minimum Live Bus voltage (Live bus detected, when all three phase bus voltages are above this limit).

0.10 – 1.30 Vn 0.65 Vn [Protection Para

/<n>

/Sync

/DeadLiveVLevels]

514 www.eaton.com

Page 515: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

MaxDeadBusVoltage

Maximum Dead Bus voltage (Dead bus detected, when all three phase bus voltages are below this limit).

0.01 – 1.00 Vn 0.03 Vn [Protection Para

/<n>

/Sync

/DeadLiveVLevels]MinLiveLineVoltage

Minimum Live Line voltage (Live line detected, when line voltage above this limit).

0.10 – 1.30 Vn 0.65 Vn [Protection Para

/<n>

/Sync

/DeadLiveVLevels]MaxDeadLineVoltage

Maximum Dead Line voltage (Dead Line detected, when line voltage below this limit).

0.01 – 1.00 Vn 0.03 Vn [Protection Para

/<n>

/Sync

/DeadLiveVLevels]t-VoltDead Voltage dead time (A Dead Bus/Line

condition will be accepted only if the voltage falls below the set dead voltage levels longer than this time setting).

0.000 – 300.000 s 0.167 s [Protection Para

/<n>

/Sync

/DeadLiveVLevels]MaxVoltageDiff Maximum voltage difference between bus

and line voltage phasors (Delta V) for synchronism (Related to bus voltage secondary rating).

0.01 – 1.00 Vn 0.24 Vn [Protection Para

/<n>

/Sync

/Conditions]MaxSlipFrequency

Maximum frequency difference (Slip: Delta f) between bus and line voltage allowed for synchronism

0.01 – 2.00 Hz 0.20 Hz [Protection Para

/<n>

/Sync

/Conditions]MaxAngleDiff Maximum phase angle difference (Delta-Phi

in degree) between bus and line voltages allowed for synchronism.

1 - 60° 20° [Protection Para

/<n>

/Sync

/Conditions]

www.eaton.com 515

Page 516: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

DBDL Enable/disable Dead-Bus AND Dead-Line synchronism overriding.

Inactive,

Active

Inactive [Protection Para

/<n>

/Sync

/Override]DBLL Enable/disable Dead-Bus AND Live-Line

synchronism overriding.Inactive,

Active

Inactive [Protection Para

/<n>

/Sync

/Override]LBDL Enable/disable Live-Bus AND Dead-Line

synchronism overriding.Inactive,

Active

Inactive [Protection Para

/<n>

/Sync

/Override]

States of the Inputs of the Sync-check Module

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking1 [Protection Para

/Global Prot Para

/Sync]ExBlo2-I Module Input State: External Blocking2 [Protection Para

/Global Prot Para

/Sync]Bypass-I State of the module input: Bypass [Protection Para

/Global Prot Para

/Sync]BkrCloseInitiate-I State of the module input: Breaker Close

Initiate with synchronism check from any control sources (e.g. HMI / SCADA). If the state of the assigned signal becomes true, a Breaker Close will be initiated (Trigger Source).

[Protection Para

/Global Prot Para

/Sync]

516 www.eaton.com

Page 517: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Signals of the Sync-check Module (States of the Outputs)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingLiveBus Signal: Live-Bus or Dead-Bus flag: 1=Live-Bus, 0=Dead-BusLiveLine Signal: Live-Line or Dead-Line flag: 1=Live-Line, 0=Dead-LineSync-check RunTiming Signal: Sync-check RunTimingSync-checkFailed Signal: This signal indicates a failed synchronization. It is set for

5s when the breaker is still open after the Sync-check Run-timer has timed out.

SyncOverridden Signal:Sync-check is overridden because one of the Sync-check overriding conditions (DB/DL or ExtBypass) is met.

VDiffTooHigh Signal: Voltage difference between bus and line too high.SlipTooHigh Signal: Frequency difference (slip frequency) between bus and line

voltages too high.AngleDiffTooHigh Signal: Phase Angle difference between bus and line voltages too

high.Sys-in-Sync Signal: Bus and line voltages are in synchronism according to the

system synchronism criteria.In-Sync Allowed Signal: In-Sync Allowed.

Sync-check Statistic Values

Value Description Menu Path

Slip Freq Slip frequency [Operation

/Measured Values

/Synchronism]Volt Diff Voltage difference [Operation

/Measured Values

/Synchronism]Angle Diff Angle difference [Operation

/Measured Values

/Synchronism]f Bus Bus frequency [Operation

/Measured Values

/Synchronism]

www.eaton.com 517

Page 518: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Value Description Menu Path

f Line Line frequency [Operation

/Measured Values

/Synchronism]V Bus Bus Voltage [Operation

/Measured Values

/Synchronism]V Line Line Voltage [Operation

/Measured Values

/Synchronism]Angle Bus Bus Angle (Reference) [Operation

/Measured Values

/Synchronism]Angle Line Line Angle [Operation

/Measured Values

/Synchronism]

518 www.eaton.com

Page 519: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

47 - Voltage Unbalance ProtectionAvailable elements:47[1] ,47[2]

This is the 47 device Voltage Unbalance setting, which consists of the threshold, %(V2/V1), and delay settings. The voltage unbalance function is based on the Main VT system 3-phase voltages.

The positive and negative sequence voltages are calculated from the 3-phase voltages. The threshold setting defines a minimum operating voltage magnitude of either V1 or V2 for the 47 function to operate, which ensures that the relay has a solid basis for initiating a voltage unbalance trip. This is a supervisory function and not a trip level.

The %(V2/V1) setting is the unbalance trip pickup setting. It is defined by the ratio of negative sequence voltage to positive sequence voltage (% Unbalance=V2/V1), or %(V2/V1) for ABC rotation and %(V1/V2) for ACB rotation. The device will automatically select the correct ratio based on the phase sequence setting in the System Configuration group described above.

This function requires positive or negative sequence voltage magnitude above the threshold setting and the percentage voltage unbalance above the %(V2/V1) setting before allowing a voltage unbalance trip. Therefore, both the threshold and percent settings must be met for the specified Delay time setting before the relay initiates a trip for voltage unbalance.

The voltage unbalance pickup and trip functions are reset when the positive and negative sequence voltages V1 and V2 drop below the threshold setting or (V2/V1) drops below the %(V2/V1) setting minus 1%.

www.eaton.com 519

Page 520: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

520 www.eaton.com

Nam

e.Tr

ip

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs

NPS

Filte

r

VA

Nam

e.Pi

ckup

Ple

ase

Ref

er to

Dia

gram

: Trip

Blo

ckin

gs

47[1

]...[n

]

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

VCVB

V2

PPS

Filte

rV1

V1>

Nam

e =

47[1

]...[n

]

2 3

Nam

e.Tr

ipC

md

1514

Nam

e.M

ode

V1<

Thre

shol

d

Dev

ice

Plan

ning

AND

AND

Nam

e.%(V

2/V1

)

AND

Nam

e.Thr

esho

ld

Nam

e.t t 0

Page 521: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Device Planning Parameters of the Voltage Unbalance Module

Parameter Description Options Default Menu Path

Mode Unbalance Protection: Supervision of the Voltage System Do not use,

Use

Use [Device Plan-ning]

Global Protection Parameters of the Voltage Unbalance Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.1

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Unbalance-Prot

/47[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.2

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Unbalance-Prot

/47[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Unbalance-Prot

/47[1]]

Parameter Set Parameters of the Voltage Unbalance Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Unbalance-Prot

/47[1]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Unbalance-Prot

/47[1]]

www.eaton.com 521

Page 522: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Blo TripCmd Permanent blocking of the Trip Command of the module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Unbalance-Prot

/47[1]]ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Unbalance-Prot

/47[1]]

Threshold The threshold defines a minimum operating voltage magnitude of either V1 or V2 for the 47 function to operate, which ensures that the relay has a solid basis for initiating a voltage unbalance trip. This is a supervisory function and not a trip level. The meaning of Vn: Phase to Phase: Vn = Main VT sec. Phase to Ground: Vn = Main VT / SQRT(3).

Only available if: Device Planning: 47.Mode = Threshold

0.01 – 1.30 Vn 0.2 Vn [Protection Para

/<n>

/Unbalance-Prot

/47[1]]

%(V2/V1) The %(V2/V1) setting is the unbalance trip pickup setting. It is defined by the ratio of negative sequence voltage to positive sequence voltage (% Unbalance=V2/V1), or %(V2/V1) for ABC rotation and %(V1/V2) for ACB rotation.

Only available if: %(V2/V1) = Use

2 - 40% 47[1]: 40%

47[2]: 20%

[Protection Para

/<n>

/Unbalance-Prot

/47[1]]

t Tripping delay 0.00 – 300.00 s 47[1]: 10.0 s

47[2]: 20 s

[Protection Para

/<n>

/Unbalance-Prot

/47[1]]LOP Blo Blocking if voltage transformer failure

detected. LOP (Loss of Potential)

Only available if: Device Planning: 47.Mode = Threshold

Inactive,

Active

Inactive [Protection Para

/<n>

/Unbalance-Prot

/47[1]]

522 www.eaton.com

Page 523: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

States of the Inputs of the Voltage Unbalance Module

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking 1 [Protection Para

/Global Prot Para

/Unbalance-Prot

/47[1]]ExBlo2-I Module Input State: External Blocking 2 [Protection Para

/Global Prot Para

/Unbalance-Prot

/47[1]]ExBlo TripCmd-I Module Input State: External Blocking of the

Trip Command[Protection Para

/Global Prot Para

/Unbalance-Prot

/47[1]]

Signals of the Voltage Unbalance Module (States of the Outputs)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup Signal: Pickup Voltage AsymmetryTrip Signal: TripTripCmd Signal: Trip Command

Commissioning: Voltage Unbalance Module

Object to be tested:Test of the unbalanced load protection function.

Necessary means:• Three-phase AC voltage source with adjustable voltage unbalance; and• Timer.

Procedure:

Check the phase sequence:

www.eaton.com 523

Page 524: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

• Ensure that the phase sequence is the same as that set in the system parameters.

• Feed-in a three-phase nominal voltage.

• Change to the [Measured Values/Voltage] menu.

• Check the measuring value for the unbalanced voltage »V2 Fund.«. The measuring value displayed for »V2 Fund.« should be zero (within the physical measuring accuracy).

If the displayed magnitude for V2 Fund. is the same as that for the balanced nominal voltages fed to the relay, it implies that the phase sequence of the voltages seen by the relay is reversed.

• Now turn-off phase A.

• Again check the measuring value of the unbalanced voltage »V2 Fund.« in the [Measured Values/Voltage] menu.The measuring value of the unbalanced voltage »V2 Fund.« should now be 33% of the nominal voltage.

• Turn-on phase A, but turn-off phase B.

• Once again check the measuring value of the unbalanced voltage »V2 Fund.« in the [Measured Values/Voltage] menu. The measuring value of the unbalanced voltage »V2 Fund.« should be again 33%.

• Turn-on phase B, but turn-off phase C.

• Again check the measuring value of unbalanced voltage »V2 Fund.« in the [Measured Values/Voltage] menu. The measuring value of the unbalanced voltage »V2 Fund.« should still be 33%.

Testing the trip delay:

• Apply a balanced three-phase voltage system (nominal voltages).

• Switch off VA (the threshold value »Threshold« for »V2 Fund.« must be below 33% of the nominal voltage Vn).

• Measure the tripping time.

The present voltage unbalance »V2 Fund.« corresponds with 1/3 of the existing phase voltage displayed.

Testing the threshold values

• Configure minimum »%(V2/V1)« setting (2%) and an arbitrary threshold value »Threshold« (V2 Fund.).

• For testing the threshold value, a voltage has to be fed to phase A which is lower than three times the adjusted threshold value »Threshold« (V2 Fund.).

• Feeding only phase A results in »%(V2/V1) = 100%«, so the first condition »%(V2/V1) >= 2%« is always fulfilled.

• Now increase the phase A voltage until the relay is activated.

524 www.eaton.com

Page 525: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Testing the drop-out ratio of the threshold values

Having tripped the relay in the previous test, now decrease the phase A voltage. The drop-out ratio must not be higher than 0.97 times the threshold value.

Testing %(V2/V1)

• Configure minimum threshold value »Threshold« (V2 Fund.) (0.01 x Vn) and set »%(V2/V1)« greater or equal to 10%.

• Apply a balanced three-phase voltage system (nominal voltages). The measuring value of »%(V2/V1)« should be approximately 0%.

• Now increase the phase A voltage. With this configuration, the threshold value »Threshold« (V2 Fund.) should be reached before the value »%(V2/V1)« reaches the set »%(V2/V1)« ratio threshold.

• Continue increasing the phase 1 voltage until the relay is activated.

Testing the drop-out ratio of %(V2/V1)

Having tripped the relay in the previous test, now decrease the phase A voltage. The drop-out of »%(V2/V1)« has to be 1% below the »%(V2/V1)«setting.

Successful test result:

The measured trip delays, threshold values, and drop-out ratios are within the permitted deviations/tolerances, specified under Technical Data.

www.eaton.com 525

Page 526: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

81O/U, 81R, 78V Frequency ProtectionAvailable elements: 81[1] ,81[2] ,81[3] ,81[4] ,81[5] ,81[6]

All frequency protective elements are identically structured.

Frequency - Measuring Principle

The frequency is calculated as the average of the measured values of the three phase frequencies. Only valid measured frequency values are taken into account. If a phase voltage is no longer measurable, this phase will be excluded from the calculation of the average value.

The measuring principle of the frequency supervision is based in general on the time measurement of complete cycles, whereby a new measurement is started at each zero passage. The influence of harmonics on the measuring result is thus minimized.

Frequency tripping is sometimes not desired by low measured voltages which, for instance. occur during alternator acceleration. All frequency supervision functions are blocked if the voltage is lower 0.15 times Vn.

Frequency Functions

Due to its various frequency functions, the device is very flexible. That makes it suitable for a wide range of applications where frequency supervision is an important criterion.

In the Device Planning menu, the User can decide how to use each of the six frequency elements.

f[1] to f[6] can be assigned as:

• 81U – Under-frequency;• 81O – Over-frequency;• 81R – Rate of Change of Frequency (df/dt);• 81UR – Under-frequency and Rate of Change of Frequency (df/dt);• 81OR – Over-frequency and Rate of Change of Frequency (df/dt);• 81UΔR – Under-frequency and DF/DT (absolute frequency change per definite time interval);• 81OΔR – Over-frequency and DF/DT (absolute frequency change per definite time interval); and• 78V – Vector Surge.

526 www.eaton.com

V(t)

t

T

T

Page 527: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

81U – Under-frequency

This protection element provides a pickup threshold and a tripping delay. If the frequency falls below the set pickup threshold, an alarm will be issued instantaneously. If the frequency remains under the set pickup threshold until the tripping delay has elapsed, a tripping command will be issued.

With this setting, the frequency element protects electrical generators, loads, or electrical operating equipment in general against under-frequency.

81O – Over-frequency

This protection element provides a pickup threshold and a tripping delay. If the frequency exceeds the set pickup threshold, an alarm will be issued instantaneously. If the frequency remains above the set pickup threshold until the tripping delay has elapsed, a tripping command will be issued.

With this setting, the frequency element protects electrical generators, loads, or electrical operating equipment in general against over-frequency.

Working Principle

(Please refer to the block diagram on next page.)

The frequency element supervises the three phase voltages »VA«, »VB« and »VC«. If any of the three phase voltages is below 15% Vn, the frequency calculation is blocked. According to the frequency supervision mode set in the Device Planning (81U or 81O), the phase voltages are compared to the set pickup threshold for over- or under-frequency. If in any of the phases, the frequency exceeds or falls below the set pickup threshold and if there are no blocking commands for the frequency element, an alarm is issued instantaneously and the tripping delay timer is started. When the frequency still exceeds or is below the set pickup threshold after the tripping delay timer has elapsed, a tripping command will be issued.

www.eaton.com 527

Page 528: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

528 www.eaton.com

Nam

e.Tr

ipC

md

Nam

e.Tr

ip 8

1

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs

VA

Nam

e.Pi

ckup

81

Plea

se R

efer

to D

iagr

am: T

rip B

lock

ings

81[1

]...[n

]:81U

-Und

er

Or

81O

-Ove

r

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

VCVBNam

e =

81[1

]...[n

]

Nam

e.Bl

o by

V<

Nam

e.f

(81O

-Ove

r|81U

-U

nder

)

81U

-Und

er: 8

1O-O

ver

Nam

e.M

ode

81O

-Ove

r: 81

U-U

nder

Dev

ice

Plan

ning

Freq

uenc

y C

alcu

latio

nf

Nam

e.Tr

ip

Nam

e.Pi

ckup

2 3

1514

AND

AND

AND

<15%

Vn

<15%

Vn

<15%

Vn

Nam

e.t

t 0

Page 529: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

81R Rate of Change of Frequency (df/dt)

Electrical generators running in parallel with the mains (e. g.: industrial internal power supply plants) should be separated from the mains when failure in the intra-system occurs for the following reasons:

• Damage to electrical generators must be prevented when mains voltage is recovering asynchronously (e. g.: after a short interruption).

• The industrial internal power supply must be maintained.

A reliable criterion of detecting mains failure is the measurement of the rate of change of frequency 81R (df/dt). The precondition for this is a load flow via the mains coupling point. At mains failure, the load flow change spontaneously leads to an increasing or decreasing frequency. At active power deficit of the internal power station, a linear drop of the frequency occurs and a linear increase occurs at power excess. Typical frequency gradients during application of "mains decoupling" are in the range of 0.5 Hz/s up to over 2 Hz/s.

The protective device detects the instantaneous frequency gradient 81R (df/dt) of each mains voltage period. Through multiple evaluations of the frequency gradient in sequence, the continuity of the directional change (sign of the frequency gradient) is determined. Because of this special measuring procedure, a high safety in tripping and thus a high stability against transient processes (e. g.: switching procedure) are achieved.

The frequency gradient (rate of change of frequency [df/dt]) may have a negative or positive sign, depending on frequency increase (positive sign) or decrease (negative sign).

In the frequency parameter sets, the User can define the kind of df/dt mode:

• Positive df/dt = the frequency element detects an increase in frequency;• Negative df/dt = the frequency element detects a decrease in frequency; and• Absolute df/dt (positive and negative) = the frequency element detects both, increase and decrease in

frequency.

This protection element provides a tripping threshold and a tripping delay. If the frequency gradient df/dt exceeds or falls below the set tripping threshold, an alarm will be issued instantaneously. If the frequency gradient remains still above/below the set tripping threshold until the tripping delay has elapsed, a tripping command will be issued.

Working Principle

(Please refer to block diagram on next page.)

The frequency element supervises the three phase voltages »VA«, »VB« and »VC«. If any of the three phase voltages is below 15% Vn, the frequency calculation is blocked. According to the frequency supervision mode set in the Device Planning (81R), the phase voltages are compared to the set frequency gradient (df/dt) threshold. If in any of the phases, the frequency gradient exceeds or falls below the set pickup threshold (acc. to the set df/dt mode) and if there are no blocking commands for the frequency element, an alarm is issued instantaneously and the tripping delay timer is started. When the frequency gradient still exceeds or is below the set pickup threshold after the tripping delay timer has elapsed, a tripping command will be issued.

www.eaton.com 529

Page 530: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

530 www.eaton.com

VA VCVBdf

/dt C

alcu

latio

n

81R

-Rat

e of

Cha

nge

df/d

t Mod

e

+df/d

t

Idf/d

tI

-df/d

t

81[1

]...[n

]: 81

R-R

ate

of C

hang

e

Nam

e =

81[1

]...[n

]

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs

Ple

ase

Ref

er to

Dia

gram

: Trip

Blo

ckin

gs

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

Posi

tive

df/d

t

Neg

ativ

e df

/dt

Abso

lute

df/d

t

Nam

e.Pi

ckup

df/d

t | D

F/D

T

81R

-Rat

e of

Cha

nge

Dev

ice

Plan

ning

Nam

e.M

ode

Nam

e.Bl

o by

V<

Nam

e.Pi

ckup Nam

e.Tr

ip

Nam

e.Tr

ip d

f/dt |

DF/

DT

2 3

Nam

e.Tr

ipC

md

1514

AND

AND

AND

<15%

Vn

<15%

Vn

<15%

Vn

Nam

e.t

t 0

Page 531: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

81UR – Under-frequency and Rate of Change of Frequency (df/dt)

With this setting, the frequency element supervises if the frequency falls below a set pickup threshold and if the frequency gradient exceeds a set threshold at the same time.

In the selected frequency parameter set 81[X], an under-frequency pickup threshold f<, a frequency gradient df/dt, and a tripping delay can be set.

Whereby:

• Positive df/dt = the frequency element detects an increase in frequency;• Negative df/dt = the frequency element detects a decrease in frequency; and • Absolute df/dt (positive and negative) = the frequency element detects both, increase and decrease in

frequency.

81OR – Over-frequency and Rate of Change of Frequency (df/dt)

With this setting, the frequency element supervises if the frequency exceeds a set pickup threshold and if the frequency gradient exceeds a set threshold at the same time.

In the selected frequency parameter set 81[X], an over-frequency pickup threshold f>, a frequency gradient df/dt, and a tripping delay can be set.

Whereby:

• Positive df/dt = the frequency element detects an increase in frequency;• Negative df/dt = the frequency element detects a decrease in frequency; and• Absolute df/dt (positive and negative) = the frequency element detects both, increase and decrease in

frequency.

Working Principle

(Please refer to block diagram on next page.)

The frequency element supervises the three phase voltages »VA«, »VB« and »VC«. If any of the three phase voltages is below 15% Vn, the frequency calculation is blocked. According to the frequency supervision mode set in the Device Planning (81UR & df/dt or 81OR & dt/dt), the phase voltages are compared to the set frequency pickup threshold and the set frequency gradient (df/dt) threshold. If in any of the phases, both the frequency and the frequency gradient exceed or falls below the set thresholds and if there are no blocking commands for the frequency element, an alarm is issued instantaneously and the tripping delay timer is started. When the frequency and the frequency gradient still exceed or are below the set threshold after the tripping delay timer has elapsed, a tripping command will be issued.

www.eaton.com 531

Page 532: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

532 www.eaton.com

Freq

uenc

y C

alcu

latio

nf

VA VCVBf

df/d

t Cal

cula

tion

Nam

e.Pi

ckup

81

81R

-Rat

e of

Cha

nge

df/d

t Mod

e

+df/d

t

Idf/d

tI

-df/d

t

81[1

]...[n

]: 81

UR

-Und

er &

df/d

t O

r 8

1OR

-Ove

r & d

f/dt

Nam

e =

81[1

]...[n

]

Plea

se R

efer

to D

iagr

am: B

lock

ings

Plea

se R

efer

to D

iagr

am: T

rip B

lock

ings

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

f

Posit

ive

df/d

t

Nega

tive

df/d

t

Abso

lute

df/d

t

Nam

e.Pi

ckup

Nam

e.Tr

ip 8

1

Nam

e.Bl

o by

V<

Nam

e.Tr

ip

Nam

e.Tr

ip d

f/dt |

DF/

DT

Nam

e.Pi

ckup

df/d

t | D

F/D

T2 3

Nam

e.Tr

ipC

md

151481

OR

-Ove

r & d

f/dt

Nam

e.M

ode

Dev

ice

Plan

ning

81U

R-Un

der &

df/d

t

81O

-Ove

r

81U

-Und

er

AND

AND

AND

<15%

Vn

<15%

Vn

<15%

Vn

Nam

e.t

t 0

Page 533: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

81UΔR – Under-frequency and DF/DT

With this setting, the frequency element supervises the frequency and the absolute frequency difference during a definite time interval.

In the selected frequency parameter set 81[X], an under-frequency pickup threshold f<, a threshold for the absolute frequency difference (frequency decrease) DF and supervision interval DT can be set.

81OΔR – Over-frequency and DF/DT

With this setting, the frequency element supervises the frequency and the absolute frequency difference during a definite time interval.

In the selected frequency parameter set 81[X], an over-frequency pickup threshold f>, a threshold for the absolute frequency difference (frequency increase) DF and supervision interval DT can be set.

Working Principle

(Please refer to block diagram on next page.)

The frequency element supervises the three phase voltages »VA«, »VB« and »VC«. If any of the three phase voltages is below 15% Vn, the frequency calculation is blocked. According to the frequency supervision mode set in the Device Planning (81UR & DF/DT or 81OR & DF/DT), the phase voltages are compared to the set frequency pickup threshold and the set frequency decrease or increase threshold DF.

If in any of the phases, the frequency exceeds or falls below the set pickup threshold and if there are no blocking commands for the frequency element, an alarm is issued instantaneously. At the same time the timer for the supervision interval DT is started. When, during the supervision interval DT, the frequency still exceeds or is below the set pickup threshold and the frequency decrease/increase reaches the set threshold DF, a tripping command will be issued.

Working Principle of DF/DT Function

(Please refer to f(t) diagram after the block diagram.)

Case 1:When the frequency falls below a set f< threshold (81U) at t1, the DF/DT element energizes. If the frequency difference (decrease) does not reach the set value DF before the time interval DT has expired, no trip will occur. The frequency element remains blocked until the frequency falls below the under-frequency threshold f< (81U) again.

Case 2:When the frequency falls below a set f< threshold (81U) at t4, the DF/DT element energizes. If the frequency difference (decrease) reaches the set value DF before the time interval DT has expired (t5), a trip command is issued.

www.eaton.com 533

Page 534: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

534 www.eaton.com

1

DT

t <nam

e>.8

1+

DF

Freq

uenc

y C

alcu

latio

nf

81O

DR

-Ove

r & D

F/D

T

Dev

ice

Plan

ning

81U

DR

-Und

er &

DF/

DT

81O

-Ove

r

81U

-Und

er

Plea

se R

efer

to D

iagr

am: T

rip B

lock

ings

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

Plea

se R

efer

to D

iagr

am: B

lock

ings

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

81[1

]...[n

]: 81

UD

R-U

nder

& D

F/D

T O

r 8

1OD

R-O

ver &

DF/

DT

Nam

e =

81[1

]...[n

]

Nam

e.Bl

o by

V<

VA VCVBf

Nam

e.M

ode

Nam

e.Pi

ckup

81

Nam

e.Pi

ckup

Nam

e.Pi

ckup

df/d

t | D

F/D

T

Nam

e.Tr

ip 8

1

Nam

e.Tr

ip

Nam

e.Tr

ip d

f/dt |

DF/

DT

2 4

Nam

e.Tr

ipC

md

1514

AND

AND

AND

AND

<15%

Vn

<15%

Vn

<15%

Vn

Page 535: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 535

fNf

81U

-Und

er

DT

DT

Res

et

DF

DF

DF

Tem

pora

rily

Bloc

king

t

t1t2

t3t4

t6

Trip

81[1

]...[n

]: 81

UD

R-U

nder

& D

F/D

T N

ame

= 81

[1]..

.[n]

t5

Page 536: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

78V Vector Surge

The vector surge supervision protects synchronous generators in mains parallel operation due to very fast decoupling in case of mains failure. Very dangerous are mains auto reclosings for synchronous generators. The mains voltage returning typically after 300 ms can hit the generator in asynchronous position. A very fast decoupling is also necessary in case of long time mains failures.

Generally there are two different applications.

• Only mains parallel operation - no single operation:In this application, the vector surge supervision protects the generator by tripping the generator breaker in case of mains failure.

• Mains parallel operation and single operation:For this application, the vector surge supervision trips the mains breaker. Here it is insured that the gen.-set is not blocked when it is required as an emergency set.

A very fast decoupling in case of mains failures for synchronous generators is very difficult. Voltage supervision units cannot be used because the synchronous alternator, as well as the load impedance, support the decreasing voltage.

In this situation, the mains voltage drops only after some 100 ms below the pickup threshold of the voltage supervision and, therefore, a safe detection of mains auto reclosings is not possible with voltage supervision only.

Frequency supervision is partially unsuitable because only a highly loaded generator decreases its speed within 100 ms. Current relays detect a fault only when short-circuit type currents exist, but cannot avoid their development. Power relays are able to pickup within 200 ms, but they also cannot prevent the power from rising to short-circuit values. Since power changes are also caused by sudden loaded alternators, the use of power relays can be problematic.

Whereas the vector surge supervision of the device detects mains failures within 60 ms without the restrictions described above because it is specially designed for applications where very fast decoupling from the mains is required. Adding the typical operating time of a breaker or contactor, the total disconnection time remains below 150 ms.

Basic requirement for tripping of the generator/mains monitor is a change in load of more than 15 - 20% of the rated load. Slow changes of the system frequency, for instance at regulating processes (adjustment of speed regulator), do not cause the relay to trip.

Trippings can also be caused by short-circuits within the grid, because a voltage vector surge higher than the preset value can occur. The magnitude of the voltage vector surge depends on the distance between the short-circuit and the generator. This function is also of advantage to the Power Utility Company because the mains short-circuit capacity and, consequently, the energy feeding the short-circuit is limited.

To prevent a possible false tripping, the vector surge measuring is blocked at a low input voltage <15% Vn. The undervoltage lockout acts faster then the vector surge measurement.

Vector surge tripping is blocked by a phase loss so that a VT fault (e. g.: faulty VTs fuse) does not cause false tripping.

536 www.eaton.com

Page 537: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Measuring Principle of Vector Surge Supervision

Equivalent circuit at synchronous generator in parallel with the mains.

Voltage vectors at mains parallel operation.

The rotor displacement angle between stator and rotor is dependent on the mechanical moving torque of the generator shaft. The mechanical shaft power is balanced with the electrical fed mains power and, therefore, the synchronous speed keeps constant.

www.eaton.com 537

Grid/Load

Generator

VPV1

V = I1* j Xd

Grid

V = I1* j Xd

VP V1

I1 I2

Page 538: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Equivalent circuit at mains failure.

In case of mains failure or auto-reclosing, the generator suddenly feeds a very high load. The rotor displacement angle is decreased repeatedly and the voltage vector V1 changes its direction (V1').

Voltage vectors at mains failure.

538 www.eaton.com

Generator Load

VPV1 V´1

V´ = I´1* j Xd

Grid

V´ = I´1* j Xd

VP V´1

I1

Page 539: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Voltage vector surge.

As shown in the voltage/time diagram, the instantaneous value of the voltage jumps to another value and the phase position changes. This is called phase or vector surge.

The relay measures the cycle duration. A new measuring is started at each zero passage. The measured cycle duration is internally compared with a reference time and from this the deviation of the cycle duration of the voltage signal is ascertained. In case of a vector surge as shown in the above graphic, the zero passage occurs either earlier or later. The established deviation of the cycle duration is in compliance with the vector surge angle. If the vector surge angle exceeds the set value, the relay trips immediately.

Tripping of the vector surge is blocked in case of loss of one or more phases of the measuring voltage.

Working Principle

(Please refer to block diagram on next page.)

The vector surge element supervises the three phase voltages »VA«, »VB« and »VC«. If any of the three phase voltages is below 15% Vn, the vector surge calculation is blocked. According to the frequency supervision mode set in the Device Planning (78V), the phase voltages are compared to the set vector surge threshold. If in any of the phases, the vector surge exceeds the set threshold and if there are no blocking commands for the frequency element, an alarm and a trip command is issued instantaneously.

www.eaton.com 539

V(t) V(t) V(t)`

Trip

tt=0

78V vector surge

Voltage Vector Surge

Page 540: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

540 www.eaton.com

VA VCVBD

elta

phi

Cal

cula

tion

Nam

e.78

V ve

ctor

su

rge

81[1

]...[n

]: 78

V ve

ctor

sur

ge

Nam

e =

81[1

]...[n

]

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs

Ple

ase

Ref

er to

Dia

gram

: Trip

Blo

ckin

gs

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals)

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

Nam

e.Pi

ckup

Nam

e.Tr

ip

78V

vect

or s

urge

Dev

ice

Plan

ning

Nam

e.M

ode

78V

vect

or

surg

e

Nam

e.Bl

o by

V<

Nam

e.Tr

ip V

ecto

r Sur

ge

Nam

e.Pi

ckup

Vec

tor S

urge

2 3

Nam

e.Tr

ipC

md

1514

AND

AND

AND

<15%

Vn

<15%

Vn

<15%

Vn

Page 541: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Device Planning Parameters of the Frequency Protection Module

Parameter Description Options Default Menu Path

Mode Mode Do not use,

81U-Under,

81O-Over,

81UR- Under & df/dt,

81OR- Over & df/dt,

81UDR- Under & DF/DT,

81ODR- Over & DF/DT,

81R-Rate of Change,

78V vector surge

81[1]: 81O-Over

81[2]: 81O-Over

81[3]: 81U-Under

81[4]: 81U-Under

81[5]: 81R-Rate of Change

81[6]: 81R-Rate of Change

[Device Plan-ning]

Global Protection Parameters of the Frequency Protection Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Freq-Prot

/81[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Freq-Prot

/81[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Freq-Prot

/81[1]]

www.eaton.com 541

Page 542: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Setting Group Parameters of the Frequency Protection Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Freq-Prot

/81[1]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Freq-Prot

/81[1]]Blo TripCmd Permanent blocking of the Trip Command

of the module/element.Inactive,

Active

Inactive [Protection Para

/<n>

/Freq-Prot

/81[1]]ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Freq-Prot

/81[1]]

81O-Over Pickup value for over-frequency.

Only available if: Device Planning: 81.Mode = 81O-Over Or 81OR- Over & df/dt Or 81ODR- Over & DF/DT

40.00 – 69.95 Hz 81[1]: 61.00 Hz

81[2]: 61.0 Hz

81[3]: 51.00 Hz

81[4]: 51.00 Hz

81[5]: 51.00 Hz

81[6]: 51.00 Hz

[Protection Para

/<n>

/Freq-Prot

/81[1]]

81U-Under Pickup value for under-frequency.

Only available if: Device Planning: 81.Mode = 81U-Under Or 81UR- Under & df/dt Or 81UDR- Under & DF/DT

40.00 – 69.95 Hz 81[1]: 59.0 Hz

81[2]: 49.00 Hz

81[3]: 59.0 Hz

81[4]: 59.0 Hz

81[5]: 59.0 Hz

81[6]: 59.0 Hz

[Protection Para

/<n>

/Freq-Prot

/81[1]]

542 www.eaton.com

Page 543: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

t Tripping delay

Only available if: Device Planning: 81.Mode = 81U-Under Or 81O-OverOr 81OR- Over & df/dt Or 81UR- Under & df/dt

0.00 – 3600.00 s 1.00 s [Protection Para

/<n>

/Freq-Prot

/81[1]]81R-Rate of Change

Measured value (calculated): Rate-of-frequency-change.

Only available if: Device Planning: 81.Mode = 81R-Rate of Change Or 81UR- Under & df/dt Or 81OR- Over & df/dt

0.1 – 10.0 Hz/s 1.0 Hz/s [Protection Para

/<n>

/Freq-Prot

/81[1]]t-df/dt Trip delay df/dt 0.00 – 300.00 s 1.00 s [Protection Para

/<n>

/Freq-Prot

/81[1]]DF Frequency difference for the maximum

admissible variation of the mean of the rate of frequency-change. This function is inactive if DF=0.

Only available if: Device Planning: 81.Mode = 81UDR- Under & DF/DT Or 81ODR- Over & DF/DT

0.0 – 10.0 Hz 1.00 Hz [Protection Para

/<n>

/Freq-Prot

/81[1]]

DT Time interval of the maximum admissible rate-of-frequency-change.

Only available if: Device Planning: 81.Mode = 81UDR- Under & DF/DT Or 81ODR- Over & DF/DT

0.1 – 10.0 s 1.00 s [Protection Para

/<n>

/Freq-Prot

/81[1]]df/dt Mode df/dt Mode

Only available if: Device Planning: 81.Mode = 81R-Rate of Change Or 81UR- Under & df/dt Or 81OR- Over & df/dt Only available if: Device Planning: 81.Mode = 81R-Rate of Change Or 81UR- Under & df/dt Or 81OR- Over & df/dt Only available if: Device Planning: 81.Mode = 81R-Rate of Change

Absolute df/dt,

Positive df/dt,

Negative df/dt

Absolute df/dt [Protection Para

/<n>

/Freq-Prot

/81[1]]

78V vector surge

Measured Value (Calculated): Vector Surge

Only available if: Device Planning: 81.Mode = 78V vector surge

1 - 30° 10° [Protection Para

/<n>

/Freq-Prot

/81[1]]

www.eaton.com 543

Page 544: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Frequency Protection Module Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking 1 [Protection Para

/Global Prot Para

/Freq-Prot

/81[1]]ExBlo2-I Module Input State: External Blocking 2 [Protection Para

/Global Prot Para

/Freq-Prot

/81[1]]ExBlo TripCmd-I Module Input State: External Blocking of the

Trip Command[Protection Para

/Global Prot Para

/Freq-Prot

/81[1]]

Frequency Protection Module Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingBlo by V< Signal: Module is blocked by undervoltage.Blo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup 81 Signal: Pickup Frequency ProtectionPickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-

change Pickup Vector Surge Signal: Pickup Vector SurgePickup Signal: Pickup Frequency Protection (collective signal)Trip 81 Signal: Frequency has exceeded the limit.Trip df/dt | DF/DT Signal: Trip df/dt or DF/DTTrip Vector Surge Signal: Trip delta phiTrip Signal: Trip Frequency Protection (collective signal)TripCmd Signal: Trip Command

Commissioning: Over-frequency [ANSI 81O]

Object to be tested:All configured over-frequency protection stages.

544 www.eaton.com

Page 545: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Necessary means:• Three-phase voltage source with variable frequency; and• Timer.

Procedure:

Testing the threshold values• Keep on increasing the frequency until the respective frequency element is activated;• Note the frequency value; and• Disconnect the test voltage.

Testing the trip delay• Set the test voltage to nominal frequency and• Now connect a frequency jump (activation value) and then start a timer. Measure the tripping time at the

relay output.

Testing the drop-out ratio:Reduce the measuring quantity to less than 99.95% of the trip value (or 0.05% fn). The relay must only fall back at 99.95% of the trip value at the earliest (or 0.05% fn).

Successful test result:Permissible deviations/tolerances can be taken from the Technical Data.

Commissioning: Under-frequency [ANSI 81U]

For all configured under-frequency elements, this test can be carried out similar to the test for over-frequency protection (by using the related under-frequency values).

Please consider the following deviations:

• For testing the threshold values, the frequency has to be decreased until the protection element is activated.

• For detection of the drop-out ratio, the measuring quantity has to be increased to more than 100.05% of the trip value (or 0.05% fn). At 100.05% of the trip value the relay is to fall back at the earliest (or 0.05% fn).

Commissioning: 81R Rate of Change (df/dt)

Object to be tested:All frequency protection stages that are projected as df/dt.

Necessary means:• Three-phase voltage source and• Frequency generator that can generate and measure a linear, defined rate of change of frequency.

Procedure:

Testing the threshold values• Keep on increasing the rate of change of frequency until the respective element is activated and• Note the value.

www.eaton.com 545

Page 546: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Testing the trip delay • Set the test voltage to nominal frequency:• Now apply a step change (sudden change) that is 1.5 times the setting value (example: apply 3 Hz per

second if the setting value is 2 Hz per second); and• Measure the tripping time at the relay output. Compare the measured tripping time to the configured

tripping time.

Successful test result:Permissible deviations/tolerances and dropout ratios can be taken from the Technical Data.

Commissioning: 81U and Rate of Change (f< and -df/dt)

Object to be tested:All frequency protection stages that are projected as f< and -df/dt.

Necessary means:• Three-phase voltage source and• Frequency generator that can generate and measure a linear, defined rate of change of frequency.

Procedure:

Testing the threshold values• Feed nominal voltage and nominal frequency to the device:• Decrease the frequency below the f< threshold: and• Apply a rate of change of frequency (step change) that is below the setting value (example: apply -1 Hz

per second if the setting value is -0.8 Hz per second). After the tripping delay is expired the relay has to trip.

Successful test result:Permissible deviations/tolerances and dropout ratios can be taken from the Technical Data.

Commissioning: 81O and Rate of Change (f> and df/dt)

Object to be tested:All frequency protection stages that are projected as f> and df/dt.

Necessary means:• Three-phase voltage source and• Frequency generator that can generate and measure a linear, defined rate of change of frequency.

Procedure:

Testing the threshold values• Feed nominal voltage and nominal frequency to the device;• Increase the frequency above the f> threshold; and• Apply a rate of change of frequency (step change) that is above the setting value (example: apply 1 Hz

per second if the setting value is 0.8 Hz per second). After the tripping delay is expired the relay has to trip.

546 www.eaton.com

Page 547: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Successful test result:Permissible deviations/tolerances and dropout ratios can be taken from the Technical Data.

Commissioning: 81UΔR – Under-frequency and DF/DT

Object to be tested:All frequency protection stages that are projected as f< and Df/Dt.

Necessary means:• Three-phase voltage source and• Frequency generator that can generate and measure a defined frequency change.

Procedure:

Testing the threshold values• Feed nominal voltage and nominal frequency to the device;• Decrease the frequency below the f< threshold; and• Apply a defined frequency change (step change) that is above the setting value (example: apply a

frequency change of 1 Hz during the set time interval DT if the setting value DF is 0.8 Hz ). The relay has to trip immediately.

Successful test result:Permissible deviations/tolerances and dropout ratios can be taken from the Technical Data.

Commissioning: 81OΔR – Over-frequency and DF/DT

Object to be tested:All frequency protection stages that are projected as f> and Df/Dt.

Necessary means:• Three-phase voltage source and• Frequency generator that can generate and measure a defined frequency change.

Procedure:

Testing the threshold values• Feed nominal voltage and nominal frequency to the device;• Increase the frequency above the f> threshold; and• Apply a defined frequency change (step change) that is above the setting value (example: apply a

frequency change of 1 Hz during the set time interval DT if the setting value DF is 0.8 Hz ). The relay has to trip immediately.

Successful test result:Permissible deviations/tolerances and dropout ratios can be taken from the Technical Data.

www.eaton.com 547

Page 548: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Commissioning: Vector Surge 78V

Object to be tested:All frequency protection stages that are projected as vector surge (78V).

Necessary means:• Three-phase voltage source that can generate a definite step (sudden change) of the voltage pointers

(phase shift).

Procedure:

Testing the threshold values • Apply a vector surge (sudden change) that is 1.5 times the setting value (example: if the setting value is

10° apply 15°).

Successful test result:Permissible deviations/tolerances and dropout ratio can be taken from the Technical Data.

548 www.eaton.com

Page 549: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

32 - Power ProtectionAvailable Elements:32[1] ,32[2] ,32[3]

This is the 32 device Power Protection setting. Each element can be set to one of five settings:

• Do Not Use;• Over Forward Power (P>);• Under Forward Power (P<);• Over Reverse Power (Pr>); and• Under Reverse Power (Pr<).

Each element consists of a Pickup and a Delay setting. These elements are based on rated apparent power VAn.

Definition for VAn is as follows:

• VAn = SQRT(3) * VT secondary rating * CT secondary rating (I=1/5A) for wye or• VAn = 3 * VT secondary rating/SQRT(3) * CT secondary rating (I=1/5A) for delta connections.

The following graphics show the areas that are protected by the corresponding modes.

www.eaton.com 549

Page 550: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

32 - Forward Power - Over and Under

550 www.eaton.com

Q

P

Trip Region

Pickup P>

Q

P

Trip Region

Pickup P<

No Trip

No Trip

Page 551: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

32 - Reverse Power - Over and Under

www.eaton.com 551

Q

P

Trip Region

Pickup Pr>

Q

P

Trip Region

Pickup Pr<

No Trip

No Trip

Page 552: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

552 www.eaton.com

Plea

se R

efer

to D

iagr

am: B

lock

ings

Plea

se R

efer

to D

iagr

am: T

rip B

lock

ings

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

Nam

e =

32[1

]...[n

]

Nam

e.Pi

ckup Nam

e.Tr

ip

2 3

Nam

e.Tr

ipC

md 1514

Pick

up P

>

Pick

up P

<

Dev

ice

Plan

ning

Pick

up P

r>

Pick

up P

r<

Nam

e.M

ode

Pick

up P

>, P

icku

p P<

, Pic

kup

Pr>,

Pic

kup

Pr<

PQS.

Mod

e

32[1

]...[n

]

AND

AND

Nam

e.t

t 0

Syst

W R

MS

activ

e

Loss

of P

oten

tial B

lo

AND

OR

OR

38 40Pl

ease

Ref

er to

Dia

gram

:.CTS

Plea

se R

efer

to D

iagr

am:.L

OP

Page 553: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Device Planning Parameters of the Power Protection Module

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Over forward,

Under forward,

Over reverse,

Under reverse

32[1]: Over forward

32[2]: Under forward

32[3]: Over reverse

[Device Plan-ning]

Global Protection Parameters of the Power Protection Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Power-Prot

/32[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Power-Prot

/32[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Power-Prot

/32[1]]

Parameter Set Parameters of the Power Protection Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Power-Prot

/32[1]]

www.eaton.com 553

Page 554: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Power-Prot

/32[1]]Blo TripCmd Permanent blocking of the Trip Command

of the module/element.Inactive,

Active

Inactive [Protection Para

/<n>

/Power-Prot

/32[1]]ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Power-Prot

/32[1]]

Loss of Potential Blo

Blocking of the protective element in case that of lacking measuring input quantities (Loss of Potential)

Inactive,

Active

Active [Protection Para

/<n>

/Power-Prot

/32[1]]Pickup P> Over(load) Active Power Pickup Value. Can

be used for monitoring the maximum allowed forward power limits of transformers or overhead lines.

Only available if: Device Planning: PQS.Mode = Pickup P>

0.02 – 10.00 VAn 1.20 VAn [Protection Para

/<n>

/Power-Prot

/32[1]]Pickup P< Under(load) Active Power Pickup Value

(e.g.: caused by idling motors).

Only available if: Device Planning: PQS.Mode = Pickup P<

0.02 – 10.00 VAn 0.80 VAn [Protection Para

/<n>

/Power-Prot

/32[1]]Pickup Pr> Over Reverse

Only available if: Device Planning: PQS.Mode = Pickup Pr>

0.02 – 10.00 VAn 1.20 VAn [Protection Para

/<n>

/Power-Prot

/32[1]]

554 www.eaton.com

Page 555: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Pickup Pr< Under Reverse

Only available if: Device Planning: PQS.Mode = Pickup Pr<

0.02 – 10.00 VAn 0.80 VAn [Protection Para

/<n>

/Power-Prot

/32[1]]t Tripping delay 0.00 – 1100.00 s 0.01 s [Protection Para

/<n>

/Power-Prot

/32[1]]

States of the Inputs of the Power Protection Module

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking [Protection Para

/Global Prot Para

/Power-Prot

/32[1]]ExBlo2-I Module Input State: External Blocking [Protection Para

/Global Prot Para

/Power-Prot

/32[1]]ExBlo TripCmd-I Module Input State: External Blocking of the

Trip Command[Protection Para

/Global Prot Para

/Power-Prot

/32[1]]

Signals of the Power Protection Module (States of the Outputs)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup Signal: Pickup Power ProtectionTrip Signal: Trip Power Protection

www.eaton.com 555

Page 556: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

TripCmd Signal: Trip Command

Commissioning Examples for the Power Protection Module

Object to be tested:

Testing the projected Power Protection Modules:

• P>;• P<;• Pr>; and• Pr<.

Necessary means:

• 3-phase AC voltage source ;• 3-phase AC current source; and• Timer.

Procedure – Testing the wiring:

• Feed rated voltage and rated current to the measuring inputs of the relay.

• Adjust the current pointers 30 degrees lagging to the voltage pointers.

• The following measuring values have to be shown:• P=0.86 Pn;• Q=0.5 Qn; and• S=1 Sn.

If the measured values are shown with a negative (algebraic) sign, check the wiring.

The examples shown within this chapter have to be carried out with the tripping values and tripping delays that apply to the User's switchboard.

If the User is testing „greater than thresholds“ (e.g.: P>), start at 80% of the tripping value and increase the object to be tested until the relay picks up.

In case the User is testing „less than thresholds“ (e.g.: P<), start at 120% of the tripping value and reduce the object to be tested until the relay picks up.

If the User is testing tripping delays of „greater than“ modules (e.g.: P>), start a timer simultaneously with an abrupt change of the object to be tested from 80% of the tripping value to 120% of the tripping value.

If the User is testing tripping delays of „less than“ modules (e.g.: P<), start a timer simultaneously with an abrupt change of the object to be tested from 120% of the tripping value to 80% of the tripping value.

556 www.eaton.com

Page 557: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

P>

Testing the threshold values (Example, Threshold 1.1 Pn)

• Feed rated voltage and 0.9 times rated current in phase to the measuring inputs of the relay (PF=1).

• The measured values for the active power „P“ must show a positive algebraic sign.

• Set the pickup threshold (e.g.: 1.1 Pn).

• In order to test the pickup thresholds, feed 0.9 times rated current to the measuring inputs of the relay. Increase the current slowly until the relay picks up. Ensure that the angle between current and voltage remains constant. Compare the measured pickup value to the configured value.

Testing the tripping delay (Example, Threshold 1.1 Pn)

• Feed rated voltage and 0.9 times rated current in phase to the measuring inputs of the relay (PF=1).

• The measured values for the active power „P“ must show a positive algebraic sign.

• Set the pickup threshold (e.g.: 1.1 Pn).

• In order to test the tripping delay, feed 0.9 times rated current to the measuring inputs of the relay. Increase the current with an abrupt change to 1.2 In. Ensure that the angle between current and voltage remains constant. Measure the tripping delay at the output of the relay.

Successful test result:

The measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Techni-cal Data section.

P<

Testing the threshold values (Example, Threshold 0.3 Pn)

• Feed rated voltage and 0.5 times rated current in phase to the measuring inputs of the relay (PF=1).

• The measured values for the active power „P“ must show a positive algebraic sign.

• Set the pickup threshold (e.g.: 0.3 Pn).

• In order to test the pickup thresholds, feed 0.5 times rated current to the measuring inputs of the relay. Decrease the current slowly until the relay picks up. Ensure that the angle between current and voltage remains constant. Compare the measured pickup value to the configured.

Testing the tripping delay (Example, Threshold 0.3 Pn)

• Feed rated voltage and 0.5 times rated current in phase to the measuring inputs of the relay (PF=1).

• The measured values for the active power „P“ must show a positive algebraic sign.

www.eaton.com 557

Page 558: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

• Set the pickup threshold (e.g.: 0.3 Pn).

• In order to test the tripping delay feed, 0.5 times rated current to the measuring inputs of the relay. Decrease the current with an abrupt change to 0.2 In. Ensure that the angle between current and voltage remains constant. Measure the tripping delay at the output of the relay.

Successful test result:

The measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Techni-cal Data section.

Pr>

Testing the threshold values (Example, Threshold 1.1 Pn)

• Feed rated voltage and 0.9 times rated current with 180 degree phase angle between voltage and current pointers to the measuring inputs of the relay.

• The measured values for the active power „P“ must show a negative algebraic sign.

• Set the pickup threshold (e. g.: 1.1 Pn).

• In order to test the pickup thresholds, feed 0.9 times rated current to the measuring inputs of the relay. Increase the current slowly until the relay picks up. Ensure that the angle between current and voltage remains constant. Compare the measured pickup value to the configured value.

Testing the tripping delay (Example, Threshold 1.1 Pn)

• Feed rated voltage and 0.9 times rated current with 180 degree phase shift between voltage and current pointers to the measuring inputs of the relay.

• The measured values for the active power „P“ must show a negative algebraic sign.

• Set the pickup threshold (e.g.: 1.1 Pn).

• In order to test the tripping delay, feed 0.9 times rated current to the measuring inputs of the relay. Increase the current with an abrupt change to 1.2 In. Ensure that the angle between current and voltage remains constant. Measure the tripping delay at the output of the relay.

Successful test result:

The measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Techni-cal Data section.

558 www.eaton.com

Page 559: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Pr<

Testing the threshold values (Example, Threshold 0.3 Pn)

• Feed rated voltage and 0.5 times rated current with 180 degree phase shift between voltage and current pointers to the measuring inputs of the relay.

• The measured values for the active power „P“ must show a negative algebraic sign.

• Set the pickup threshold (e. g.: 0.3 Pn).

• In order to test the pickup thresholds, feed 0.5 times rated current to the measuring inputs of the relay. Decrease the current slowly until the relay picks up. Ensure that the angle between current and voltage remains constant. Compare the measured pickup value to the configured value.

Testing the tripping delay (Example, Threshold 0.3 Pn)

• Feed rated voltage and 0.5 times rated current with 180 degree phase shift between voltage and current pointers to the measuring inputs of the relay.

• The measured values for the active power „P“ must show a negative algebraic sign.

• Set the pickup threshold (e.g.: 0.3 Pn).

• In order to test the tripping delay, feed 0.5 times rated current to the measuring inputs of the relay. Decrease the current with an abrupt change to 0.2 In. Ensure that the angle between current and voltage remains constant. Measure the tripping delay at the output of the relay.

Successful test result:

The measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Techni-cal Data section.

www.eaton.com 559

Page 560: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

32V - Reactive Power ProtectionAvailable Elements:32V[1] ,32V[2] ,32V[3]

This is the 32V device Reactive Power Protection setting. Each element can be set to one of five settings:

• Do Not Use;• Over Forward Reactive Power (Q>);• Under Forward Reactive Power (Q<);• Over Reverse Reactive Power (Qr>); and• Under Reverse Reactive Power (Qr<).

Each element consists of a Pickup and a Delay setting. These elements are based on rated apparent power Van.

Definition for VAn is as follows:•

VAn = SQRT(3) * VT secondary rating * CT secondary rating (I=1/5A) for wye or• VAn = 3 * VT secondary rating/SQRT(3) * CT secondary rating (I=1/5A) for delta connections.

The following graphics show the areas that are protected by the corresponding modes.

560 www.eaton.com

Page 561: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

32V Forward Reactive Power - Over and Under

www.eaton.com 561

Q

P

P

Q

Trip Region

No Trip

Trip Region

No Trip

Pickup Q>

Pickup Q<

.

Page 562: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

32V Reverse Reactive Power - Over and Under

562 www.eaton.com

Q

P

Trip Region

No Trip

Pickup Qr>

Q

P

Trip Region

No Trip

Pickup Qr<

Page 563: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 563

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs

Ple

ase

Ref

er to

Dia

gram

: Trip

Blo

ckin

gs

(Ele

men

t is

not d

eact

ivate

d an

d no

act

ive

bloc

king

sig

nals

)

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

Nam

e =

32V[

1]...

[n]

Nam

e.Pi

ckup Nam

e.Tr

ip

2 3

Nam

e.Tr

ipC

md 1514

Pick

up Q

>

Pick

up Q

<

Dev

ice

Plan

ning

Pick

up Q

r>

Pick

up Q

r<

Nam

e.M

ode

Pick

up Q

>, P

icku

p Q

<, P

icku

p Q

r>, P

icku

p Q

r<

PQS.

Mod

e

32V[

1]...

[n]

AND

AND

Nam

e.t

t 0

Sys

t VA

r RM

S

activ

e

Loss

of P

oten

tial B

lo

AND

OR OR

38 40Pl

ease

Ref

er to

Dia

gram

:.CTS

Plea

se R

efer

to D

iagr

am:.L

OP

Page 564: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Device Planning Parameters of the Reactive Power Protection Module

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Over forward,

Under forward,

Over reverse,

Under reverse

32V[1]: Over forward

32V[2]: Under forward

32V[3]: Over reverse

[Device Plan-ning]

Global Protection Parameters of the Reactive Power Protection Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Power-Prot

/32V[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Power-Prot

/32V[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Power-Prot

/32V[1]]

Parameter Set Parameters of the Reactive Power Protection Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Power-Prot

/32V[1]]

564 www.eaton.com

Page 565: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Power-Prot

/32V[1]]Blo TripCmd Permanent blocking of the Trip Command

of the module/element.Inactive,

Active

Inactive [Protection Para

/<n>

/Power-Prot

/32V[1]]ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Power-Prot

/32V[1]]

Loss of Potential Blo

Blocking of the protective element in case that of lacking measuring input quantities (Loss of Potential)

Inactive,

Active

Active [Protection Para

/<n>

/Power-Prot

/32V[1]]Pickup Q> Over(load) Reactive Power Pickup Value.

Monitoring the maximum allowed reactive power of the electrical equipment like transformers or overhead lines). If the maximum value is exceeded, a condensator bank could be switched off.

Only available if: Device Planning: PQS.Mode = Pickup Q>

0.02 – 10.00 VAn 1.20 VAn [Protection Para

/<n>

/Power-Prot

/32V[1]]

Pickup Q< Under(load) Reactive Power Pickup Value. Monitoring the minimum value of the reactive power. If it falls below the set value, a condensator bank could be switched on.

Only available if: Device Planning: PQS.Mode = Pickup Q<

0.02 – 10.00 VAn 0.80 VAn [Protection Para

/<n>

/Power-Prot

/32V[1]]

Pickup Qr> Over Reverse

Only available if: Device Planning: PQS.Mode = Pickup Qr>

0.02 – 10.00 VAn 1.20 VAn [Protection Para

/<n>

/Power-Prot

/32V[1]]

www.eaton.com 565

Page 566: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Pickup Qr< Under Reverse

Only available if: Device Planning: PQS.Mode = Pickup Qr<

0.02 – 10.00 VAn 0.80 VAn [Protection Para

/<n>

/Power-Prot

/32V[1]]t Tripping delay 0.00 – 1100.00 s 0.01 s [Protection Para

/<n>

/Power-Prot

/32V[1]]

States of the Inputs of the Reactive Power Protection Module

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking [Protection Para

/Global Prot Para

/Power-Prot

/32V[1]]ExBlo2-I Module Input State: External Blocking [Protection Para

/Global Prot Para

/Power-Prot

/32V[1]]ExBlo TripCmd-I Module Input State: External Blocking of the

Trip Command[Protection Para

/Global Prot Para

/Power-Prot

/32V[1]]

Signals of the Reactive Power Protection Module (States of the Outputs)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup Signal: Pickup Power ProtectionTrip Signal: Trip Power Protection

566 www.eaton.com

Page 567: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

TripCmd Signal: Trip Command

Commissioning Examples for the Reactive Power Protection Module

Object to be tested:

Testing the projected Power Protection Modules.

• Q>;• Q<;• Qr>; and• Qr<.

Necessary means:

• 3-phase AC voltage source;• 3-phase AC current source; and• Timer.

Procedure – Testing the wiring:

• Feed rated voltage and rated current to the measuring inputs of the relay.

• Adjust the current pointers 30° lagging to the voltage pointers.

• The following measuring values have to be shown:• P=0.86 Pn;• Q=0.5 Qn; and• S=1 Sn.

If the measured values are shown with a negative (algebraic) sign, check the wiring.

The examples shown within this chapter have to be carried out with the tripping values and tripping delays that apply to the User's switchboard.

If the User is testing „greater than thresholds“ (e.g.: Q>), start at 80% of the tripping value and increase the object to be tested until the relay picks up.

In case the User is testing „less than thresholds“ (e.g.: Q<), start at 120% of the tripping value and reduce the object to be tested until the relay picks up.

If the User is testing tripping delays of „greater than“ modules (e.g.: Q>), start a timer simultaneously with an abrupt change of the object to be tested from 80% of the tripping value to 120% of the tripping value.

If the User is testing tripping delays of „less than“ modules (e.g.: Q<), start a timer simultaneously with an abrupt change of the object to be tested from 120% of the tripping value to 80% of the tripping value.

www.eaton.com 567

Page 568: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Q>

Testing the threshold values (Example, Threshold 1,1 Qn)

• Feed rated voltage and 0.9 times rated current (90 degrees phase shift) to the measuring inputs of the relay (PF=0).

• The measured values for the active power „Q“ must show a positive algebraic sign.

• Set the pickup threshold (e.g.: 1.1. Qn).

• In order to test the pickup thresholds, feed 0.9 times rated current to the measuring inputs of the relay. Increase the current slowly until the relay picks up. Ensure that the angle between current and voltage remains constant. Compare the measured pickup value to the configured value.

Testing the tripping delay (Example, Threshold 1.1 Qn)

• Feed rated voltage and 0.9 times rated current (90 degree phase shift) to the measuring inputs of the relay (PF=0).

• The measured values for the active power „Q“ must show a positive algebraic sign.

• Set the pickup threshold (e.g. 1.1. Qn).

• In order to test the tripping delay, feed 0.9 times rated current to the measuring inputs of the relay. Increase the current with an abrupt change to 1.2 In. Ensure that the angle between current and voltage remains constant. Measure the tripping delay at the output of the relay.

Successful test result:

The measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Techni-cal Data section.

Q<

Testing the threshold values (Example, Threshold 0.3 Qn)

• Feed rated voltage and 0.5 times rated current (90 degree phase shift) to the measuring inputs of the relay (PF=0).

• The measured values for the active power „Q“ must show a positive algebraic sign.

• Set the pickup threshold (e.g.: 0.3 Qn).

• In order to test the pickup thresholds, feed 0.5 times rated current to the measuring inputs of the relay. Decrease the current slowly until the relay picks up. Ensure that the angle between current and voltage remains constant. Compare the measured pickup value to the configured value.

568 www.eaton.com

Page 569: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Testing the tripping delay (Example, Threshold 0.3 Qn)

• Feed rated voltage and 0.5 times rated current (90 degree phase shift) to the measuring inputs of the relay (PF=0).

• The measured values for the active power „Q“ must show a positive algebraic sign.

• Set the pickup threshold (e.g.: 0.3 Qn).

• In order to test the tripping delay, feed 0.5 times rated current to the measuring inputs of the relay. Decrease the current with an abrupt change to 0.2 In. Ensure that the angle between current and voltage remains constant. Measure the tripping delay at the output of the relay.

Successful test result:

The measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Techni-cal Data section.

Qr>

Testing the threshold values (Example, Threshold 1.1 Qn)

• Feed rated voltage and 0.9 times rated current with -90 degree phase shift between voltage and current pointers to the measuring inputs of the relay.

• The measured values for the active power „Q“ must show a negative algebraic sign.

• Set the pickup threshold (e. g.: 1.1 Qn).

• In order to test the pickup thresholds, feed 0.9 times rated current to the measuring inputs of the relay. Increase the current slowly until the relay picks up. Ensure that the angle between current and voltage remains constant. Compare the measured pickup value to the configured value.

Testing the tripping delay (Example, Threshold 1.1 Qn)

• Feed rated voltage and 0.9 times rated current with -90 degree phase shift between voltage and current pointers to the measuring inputs of the relay.

• The measured values for the active power „Q“ must show a negative algebraic sign.

• Set the pickup threshold (e. g. 1.1 Qn).

• In order to test the tripping delay, feed 0.9 times rated current to the measuring inputs of the relay. Increase the current with an abrupt change to 1.2 In. Ensure that the angle between current and voltage remains constant. Measure the tripping delay at the output of the relay.

Successful test result:

The measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Techni-cal Data section.

www.eaton.com 569

Page 570: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Qr<

Testing the threshold values (Example, Threshold 0.3 Qn)

• Feed rated voltage and 0.5 times rated current with -90 degree phase shift between voltage and current pointers to the measuring inputs of the relay.

• The measured values for the active power „Q“ must show a negative algebraic sign.

• Set the pickup threshold (e. g.: 0.3 Qn).

• In order to test the pickup thresholds, feed 0.5 times rated current to the measuring inputs of the relay. Decrease the current slowly until the relay picks up. Ensure that the angle between current and voltage remains constant. Compare the measured pickup value to the configured value.

Testing the tripping delay (Example, Threshold 0.3 Qn)

• Feed rated voltage and 0.5 times rated current with -90 degree phase shift between voltage and current pointers to the measuring inputs of the relay.

• The measured values for the active power „Q“ must show a negative algebraic sign.

• Set the pickup threshold (e. g. 0.3 Qn).

• In order to test the tripping delay, feed 0.5 times rated current to the measuring inputs of the relay. Decrease the current with an abrupt change to 0.2 In. Ensure that the angle between current and voltage remains constant. Measure the tripping delay at the output of the relay.

Successful test result:

The measured total tripping delays or individual tripping delays, threshold values, and dropout ratios correspond with those values specified in the adjustment list. Permissible deviations/tolerances can be found in the Techni-cal Data section.

570 www.eaton.com

Page 571: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

55A and 55D - PF ProtectionAvailable elements:PF-55D[1] ,PF-55D[2] ,PF-55A[1] ,PF-55A[2]

Definition Apparent Power Factor 55A (RMS - Includes Harmonics):

The Apparent Power Factor is computed by dividing real power (watts) by volt-amperes. The apparent power factor computation includes harmonics.

PF apparent=WattVA

Definition Displacement Power Factor 55D (Fundamental):

The Displacement Power Factor is computed by dividing the fundamental watts by the fundamental volt-amperes as shown below. This definition is only valid at the system fundamental operating frequency. The Displacement Power Factor isolates the fundamental portion of the Power Factor from the effects of harmonics.

PF displacement=Watt

Watt 2var2

These elements supervise the Power Factor within a defined area (limits).

The area is defined by four parameters:

• The Trigger Quadrant (lead or lag);•

• The Threshold (Power Factor value);•

• The Reset Quadrant (lead or lag); and•

• The Reset Value (Power Factor value).

www.eaton.com 571

Q

P

leading

leading

lagging

lagging

PF>0

PF>0 PF<0

PF<0

0°<phi<90°

270°<phi<360°

90°<phi<180°

180°<phi<270°

Page 572: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

572 www.eaton.com

Nam

e.Tr

ip

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs

Plea

se R

efer

to D

iagr

am: T

rip B

lock

ings

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sign

als)

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

Nam

e =

PF[1

]...[n

]

Nam

e.Pi

ckup

2 3

Nam

e.Tr

ipC

md 1514

<20%

Vn

<0.5

%In

ImaxV

Post

-trig

ger t

ime

Pre-

trigg

er ti

me

Nam

e.t-P

icku

p C

omp

Nam

e.t-R

eset

Com

p

PF

Nam

e.Im

poss

ible

Nam

e.C

ompe

nsat

or

Pick

up D

elay

And

Rel

ease

Del

ay

PF[1

]...[n

]

OR

ORAN

D

AND

Fund

.

RM

S

Nam

e.C

riter

ion

φN

ame.

PFN

ame.

t

t 0

Page 573: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Device Planning Parameters of the Power Factor Module

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Use [Device Plan-ning]

Global Protection Parameter of the Power Factor Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Power Factor-Prot

/PF-55D[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Power Factor-Prot

/PF-55D[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Power Factor-Prot

/PF-55D[1]]

Set Parameters of the Power Factor Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Power Factor-Prot

/PF-55D[1]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Power Factor-Prot

/PF-55D[1]]

www.eaton.com 573

Page 574: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Blo TripCmd Permanent blocking of the Trip Command of the module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Power Factor-Prot

/PF-55D[1]]ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Power Factor-Prot

/PF-55D[1]]

Trig Mode Trigger Mode. Should the Module be triggered if the Current Phasor is leading to the Voltage Phasor = Lead? Or should the Module be triggered if the Current Phasor is lagging to the Voltage Phasor = Lag?

Leading,

Lagging

Lagging [Protection Para

/<n>

/Power Factor-Prot

/PF-55D[1]]Trigger-PF This is the power factor where the relay will

pick up0.5 - 0.99 0.7 [Protection Para

/<n>

/Power Factor-Prot

/PF-55D[1]]Res Mode Trigger Mode. Should the Module be

triggered if the Current Phasor is leading to the Voltage Phasor = Lead? Or should the Module be triggered if the Current Phasor is lagging to the Voltage Phasor = Lag?

Leading,

Lagging

Lagging [Protection Para

/<n>

/Power Factor-Prot

/PF-55D[1]]Reset-PF This setting is the power factor, at which the

relay will reset the power factor trip. It is like setting a hysteresis for the Trigger setting.

0.5 - 0.99 0.9 [Protection Para

/<n>

/Power Factor-Prot

/PF-55D[1]]t-trip Tripping delay 0.00 – 300.00 s 0.00 s [Protection Para

/<n>

/Power Factor-Prot

/PF-55D[1]]

574 www.eaton.com

Page 575: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

t-Pickup Comp Pre-trigger time for the Compensation Signal. When this timer is elapsed the compensation signal will be activated.

0.00 – 300.00 s 5.00 s [Protection Para

/<n>

/Power Factor-Prot

/PF-55D[1]]t-Reset Comp Reset (Post-trigger) time of the

Compensation Signal. When this timer is elapsed the compensation signal will be deactivated.

0.00 – 300.00 s 5.00 s [Protection Para

/<n>

/Power Factor-Prot

/PF-55D[1]]

States of the Inputs of the Power Factor Module

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking [Protection Para

/Global Prot Para

/Power Factor-Prot

/PF-55D[1]]ExBlo2-I Module Input State: External Blocking [Protection Para

/Global Prot Para

/Power Factor-Prot

/PF-55D[1]]ExBlo TripCmd-I Module Input State: External Blocking of the

Trip Command[Protection Para

/Global Prot Para

/Power Factor-Prot

/PF-55D[1]]

Signals of the Power Factor Module (States of the Outputs)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandPickup Signal: Pickup Power FactorTrip Signal: Trip Power Factor

www.eaton.com 575

Page 576: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

TripCmd Signal: Trip CommandCompensator Signal: Compensation SignalImpossible Signal: Pickup Power Factor Impossible

Commissioning: Power Factor

Object to be tested:

• Testing the projected Power Factor Modules.

Necessary means:

• Three-phase AC voltage source;• Three-phase AC current source; and• Timer.

Procedure – Testing the wiring:

• Feed the rated voltage and rated current to the measuring inputs of the relay.

• Adjust the current pointers 30° lagging to the voltage pointers.

• The following measuring values have to be shown:• P = 0.86 Pn• Q = 0.5 Qn• S = 1 Sn

If the measured values are shown with a negative (algebraic) sign, check the wiring.

In this example, the PF-Trigger is set to 0.86 = 30° (lagging) and the PF-Reset is set to 0.86 = 30° (leading).

Carry out the test with the settings (trigger and reset) that fit the switchboard.

Testing the threshold values (Trigger) (PF Trigger: Example = 0.86 lagging):

• Feed the rated voltage and rated current in phase to the measuring inputs of the relay (PF=1).

• Adjust the angle between the voltage and current (current pointer lagging) until the relay picks up.

• Write down the pickup value.

Testing the Reset (PF Reset: Example = 0.86 leading):

• Reduce the angle between voltage and current beyond PF = 1 (current pointer leading) until the alarm drops off.

576 www.eaton.com

Page 577: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

• Write down the reset value.

Testing the trip delay (PF Trigger: Example = 0.86 lagging):

• Feed the rated voltage and rated current in phase to the measuring inputs of the relay (PF=1).

• Adjust the angle between voltage and current (current pointer lagging) with an abrupt change to PF = 0.707 (45°) lagging.

• Measure the tripping delay at the output of the relay. Compare the measured tripping time to the selected trip time.

Successful test result:

The measured total tripping delays, threshold, and reset values correspond with those values specified in the ad-justment list. Permissible deviations/tolerances can be found the Technical Data section.

www.eaton.com 577

Page 578: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

ExP - External ProtectionAvailable elements:ExP[1] ,ExP[2] ,ExP[3] ,ExP[4]

All elements of the external protection ExP[1]...[4] are identically structured.

By means of these elements, the protective device can detect and execute pickups and trips that are issued by other external devices. This can be helpful, for logging purposes, if the other device is not equipped with an event or disturbance recorder. This might also be helpful if the other device has no communication (SCADA) interface.

578 www.eaton.com

Page 579: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 579

1..n

, Ass

ignm

ent L

ist

Nam

e.Al

arm

Nam

e.Tr

ipC

md

1..n

, Ass

ignm

ent L

ist

Nam

e.Tr

ip

AND

AND

Nam

e.Tr

ip

Nam

e.Al

arm

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs

Ple

ase

Ref

er to

Dia

gram

: Trip

Blo

ckin

gs

(Ele

men

t is

not d

eact

ivat

ed

and

no a

ctiv

e bl

ocki

ng

sign

als)

(Trip

ping

com

man

d no

t dea

ctiv

ated

or b

lock

ed. )

ExP[

1]...

[n]

Nam

e =

ExP[

1]...

[n]

Nam

e.Tr

ip-I

Nam

e.Al

arm

-I2 3

14 15AN

D

Page 580: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Device Planning Parameters of the External Protection Module

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Do not use [Device Plan-ning]

Global Protection Parameters of the External Protection Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/ExP

/ExP[1]]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/ExP

/ExP[1]]ExBlo TripCmd External blocking of the Trip Command of

the module/the element, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/ExP

/ExP[1]]Alarm Assignment for External Alarm 1..n, Assignment List -.- [Protection Para

/Global Prot Para

/ExP

/ExP[1]]Trip External trip of the Bkr. if the state of the

assigned signal is true.1..n, Assignment List -.- [Protection Para

/Global Prot Para

/ExP

/ExP[1]]

580 www.eaton.com

Page 581: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Setting Group Parameters of the External Protection Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/ExP

/ExP[1]]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/ExP

/ExP[1]]Blo TripCmd Permanent blocking of the Trip Command

of the module/element.Inactive,

Active

Inactive [Protection Para

/<n>

/ExP

/ExP[1]]ExBlo TripCmd Fc

Activate (allow) or inactivate (disallow) blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo TripCmd Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/ExP

/ExP[1]]

External Protection Module Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking 1 [Protection Para

/Global Prot Para

/ExP

/ExP[1]]ExBlo2-I Module Input State: External Blocking 2 [Protection Para

/Global Prot Para

/ExP

/ExP[1]]

www.eaton.com 581

Page 582: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command

[Protection Para

/Global Prot Para

/ExP

/ExP[1]]Alarm-I Module Input State: Alarm [Protection Para

/Global Prot Para

/ExP

/ExP[1]]Trip-I Module Input State: Trip [Protection Para

/Global Prot Para

/ExP

/ExP[1]]

External Protection Module Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingBlo TripCmd Signal: Trip Command blockedExBlo TripCmd Signal: External Blocking of the Trip CommandAlarm Signal: AlarmTrip Signal: TripTripCmd Signal: Trip Command

Commissioning: External Protection

Object to be tested:

• Test of the External Protection Module.

Necessary means:

• Dependent on the application.

Procedure:

• Simulate the functionality of the External Protection (pickup, trip, and blockings) by (de-)energizing the digital inputs.

582 www.eaton.com

Page 583: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Successful test result:

All external pickups, external trips, and external blockings are correctly recognized and processed by the device.

www.eaton.com 583

Page 584: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Supervision50BF – Breaker Failure Supervision

BF

Principle – General Use

The breaker failure (BF) protection is used to provide backup protection in the event that a breaker fails to oper-ate properly during fault clearing. A breaker failure condition is recognized if current is still flowing through the breaker after tripping or opening breaker commands have been issued for a specified time. The User can select different trigger modes. In addition, up to three additional trigger events (trip commands) can be assigned from all the protection modules.

Trigger Modes

There are three trigger modes for the breaker failure available. In addition, there are three assignable trigger inputs available.

• All Trips: All trip signals that are assigned to this breaker (within the breaker manager) will start the BF module.

• Current Trips: All current trips that are assigned to this breaker (within the breaker manager) will start the BF module.

• External Trips: All external trips that are assigned to this breaker (within the breaker manager) will start the BF module.

In addition, the User can also select none (e.g.: if the User intends to use one of the three additional assignable trigger inputs).

Those trips can exclusively start the breaker failures that are assigned within the breaker manager to the breaker that is to be supervised.

Select the winding side from which the measured currents should be taken in case this protective device is a transformer differential protection.

584 www.eaton.com

Page 585: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 585

Cur

rent

Trip

s

Det

erm

inin

g th

e tri

gger

mod

e fo

r th

e Br

eake

r Fai

lure

.

All T

rips

Exte

rnal

Trip

s

Nam

e.I-B

F >

IA IB IC

AND

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs

BF.T

rip

BF.P

icku

p

BF

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

si

gnal

s)

Nam

e =

BF

2

14

AND

All T

rips

Exte

rnal

Trip

s

Cur

rent

Trip

s

1515 15

15

15 15

OR

BF.T

rigge

r1

BF.T

rigge

r2

BF.T

rigge

r3

BF.T

rigge

r1-I

BF.T

rigge

r2-I

BF.T

rigge

r3-I

none

Nam

e.t-B

F

t-BF

0S

Q

R1

Q

S

1

R1

1

BF.L

ocko

ut

Res

Loc

kout

Page 586: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Direct Commands

Parameter Description Setting Range Default Menu Path

Res Lockout Reset Lockout Inactive,

Active

Inactive [Operation

/Reset]

Device Planning Parameters of the BF Module

Parameter Description Options Default Menu Path

Mode Mode Use Use [Device Plan-ning]

Global Protection Parameters of the BF Module

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Supervision

/BF]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Supervision

/BF]Trigger Determining the trigger mode for the

Breaker Failure.- . -,

All Trips,

Current Trips,

ExP Fc

All Trips [Protection Para

/Global Prot Para

/Supervision

/BF]Trigger1 Trigger that will start the BF Trigger -.- [Protection Para

/Global Prot Para

/Supervision

/BF]Trigger2 Trigger that will start the BF Trigger -.- [Protection Para

/Global Prot Para

/Supervision

/BF]

586 www.eaton.com

Page 587: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Trigger3 Trigger that will start the BF Trigger -.- [Protection Para

/Global Prot Para

/Supervision

/BF]

Setting Group Parameters of the BF Module

In order to prevent a faulty activation of the BF Module, the pickup (alarm) time must be greater than the sum of:

• The close-open time of the breaker (please refer to the technical data of the manufacturer of the breaker);

• + The tripping delay of the device (please refer to the Technical Data section);

• + The security margin; and

• + The operating time.

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Supervision

/BF]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Supervision

/BF]I-BF > Current level that needs to exist after Trip

Command has been given.0.00 – 0.10 In 0.00 In [Protection Para

/<n>

/Supervision

/BF]t-BF If the delay time is expired, an BF alarm is

given out.0.00 – 10.00 s 0.20 s [Protection Para

/<n>

/Supervision

/BF]

www.eaton.com 587

Page 588: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

BF Module Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking1 [Protection Para

/Global Prot Para

/Supervision

/BF]ExBlo2-I Module Input State: External Blocking2 [Protection Para

/Global Prot Para

/Supervision

/BF]Trigger1 Module Input: Trigger that will start the BF [Protection Para

/Global Prot Para

/Supervision

/BF]Trigger2 Module Input: Trigger that will start the BF [Protection Para

/Global Prot Para

/Supervision

/BF]Trigger3 Module Input: Trigger that will start the BF [Protection Para

/Global Prot Para

/Supervision

/BF]

BF Module Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingPickup Signal: BF-Module Started (Pickup)Trip Signal: Breaker Failure TripLockout Signal: LockoutRes Lockout Signal: Reset Lockout

588 www.eaton.com

Page 589: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

BF Module Trigger Functions

In case that the protective device is equipped with directional overcurrent protection. All ANSI 67 elements (directional overcurrent protection), will be displayed as ANSI 50/51 elements. That means, that the name of an ANSI 50/51 element wont change, if it is set within the device planning from “non-directional” to “directional”.

These trips will start the BF module if all trips have been selected as the trigger event.

Name Description

-.- No assignment50P[1].TripCmd Signal: Trip Command50P[2].TripCmd Signal: Trip Command50P[3].TripCmd Signal: Trip Command51P[1].TripCmd Signal: Trip Command51P[2].TripCmd Signal: Trip Command51P[3].TripCmd Signal: Trip Command50X[1].TripCmd Signal: Trip Command50X[2].TripCmd Signal: Trip Command51X[1].TripCmd Signal: Trip Command51X[2].TripCmd Signal: Trip Command50R[1].TripCmd Signal: Trip Command50R[2].TripCmd Signal: Trip Command51R[1].TripCmd Signal: Trip Command51R[2].TripCmd Signal: Trip Command27M[1].TripCmd Signal: Trip Command27M[2].TripCmd Signal: Trip Command59M[1].TripCmd Signal: Trip Command59M[2].TripCmd Signal: Trip Command27A[1].TripCmd Signal: Trip Command27A[2].TripCmd Signal: Trip Command59A[1].TripCmd Signal: Trip Command59A[2].TripCmd Signal: Trip Command59N[1].TripCmd Signal: Trip Command59N[2].TripCmd Signal: Trip Command46[1].TripCmd Signal: Trip Command46[2].TripCmd Signal: Trip Command47[1].TripCmd Signal: Trip Command47[2].TripCmd Signal: Trip Command81[1].TripCmd Signal: Trip Command81[2].TripCmd Signal: Trip Command81[3].TripCmd Signal: Trip Command

www.eaton.com 589

Page 590: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

81[4].TripCmd Signal: Trip Command81[5].TripCmd Signal: Trip Command81[6].TripCmd Signal: Trip CommandPF-55D[1].TripCmd Signal: Trip CommandPF-55D[2].TripCmd Signal: Trip CommandPF-55A[1].TripCmd Signal: Trip CommandPF-55A[2].TripCmd Signal: Trip CommandZI.TripCmd Signal: Zone Interlocking Trip CommandExP[1].TripCmd Signal: Trip CommandExP[2].TripCmd Signal: Trip CommandExP[3].TripCmd Signal: Trip CommandExP[4].TripCmd Signal: Trip CommandDI-8P X1.DI 1 Signal: Digital InputDI-8P X1.DI 2 Signal: Digital InputDI-8P X1.DI 3 Signal: Digital InputDI-8P X1.DI 4 Signal: Digital InputDI-8P X1.DI 5 Signal: Digital InputDI-8P X1.DI 6 Signal: Digital InputDI-8P X1.DI 7 Signal: Digital InputDI-8P X1.DI 8 Signal: Digital InputLogic.LE1.Gate Out Signal: Output of the logic gateLogic.LE1.Timer Out Signal: Timer OutputLogic.LE1.Out Signal: Latched Output (Q)Logic.LE1.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE2.Gate Out Signal: Output of the logic gateLogic.LE2.Timer Out Signal: Timer OutputLogic.LE2.Out Signal: Latched Output (Q)Logic.LE2.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE3.Gate Out Signal: Output of the logic gateLogic.LE3.Timer Out Signal: Timer OutputLogic.LE3.Out Signal: Latched Output (Q)Logic.LE3.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE4.Gate Out Signal: Output of the logic gateLogic.LE4.Timer Out Signal: Timer OutputLogic.LE4.Out Signal: Latched Output (Q)Logic.LE4.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE5.Gate Out Signal: Output of the logic gateLogic.LE5.Timer Out Signal: Timer OutputLogic.LE5.Out Signal: Latched Output (Q)

590 www.eaton.com

Page 591: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE5.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE6.Gate Out Signal: Output of the logic gateLogic.LE6.Timer Out Signal: Timer OutputLogic.LE6.Out Signal: Latched Output (Q)Logic.LE6.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE7.Gate Out Signal: Output of the logic gateLogic.LE7.Timer Out Signal: Timer OutputLogic.LE7.Out Signal: Latched Output (Q)Logic.LE7.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE8.Gate Out Signal: Output of the logic gateLogic.LE8.Timer Out Signal: Timer OutputLogic.LE8.Out Signal: Latched Output (Q)Logic.LE8.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE9.Gate Out Signal: Output of the logic gateLogic.LE9.Timer Out Signal: Timer OutputLogic.LE9.Out Signal: Latched Output (Q)Logic.LE9.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE10.Gate Out Signal: Output of the logic gateLogic.LE10.Timer Out Signal: Timer OutputLogic.LE10.Out Signal: Latched Output (Q)Logic.LE10.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE11.Gate Out Signal: Output of the logic gateLogic.LE11.Timer Out Signal: Timer OutputLogic.LE11.Out Signal: Latched Output (Q)Logic.LE11.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE12.Gate Out Signal: Output of the logic gateLogic.LE12.Timer Out Signal: Timer OutputLogic.LE12.Out Signal: Latched Output (Q)Logic.LE12.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE13.Gate Out Signal: Output of the logic gateLogic.LE13.Timer Out Signal: Timer OutputLogic.LE13.Out Signal: Latched Output (Q)Logic.LE13.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE14.Gate Out Signal: Output of the logic gateLogic.LE14.Timer Out Signal: Timer OutputLogic.LE14.Out Signal: Latched Output (Q)Logic.LE14.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE15.Gate Out Signal: Output of the logic gateLogic.LE15.Timer Out Signal: Timer Output

www.eaton.com 591

Page 592: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE15.Out Signal: Latched Output (Q)Logic.LE15.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE16.Gate Out Signal: Output of the logic gateLogic.LE16.Timer Out Signal: Timer OutputLogic.LE16.Out Signal: Latched Output (Q)Logic.LE16.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE17.Gate Out Signal: Output of the logic gateLogic.LE17.Timer Out Signal: Timer OutputLogic.LE17.Out Signal: Latched Output (Q)Logic.LE17.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE18.Gate Out Signal: Output of the logic gateLogic.LE18.Timer Out Signal: Timer OutputLogic.LE18.Out Signal: Latched Output (Q)Logic.LE18.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE19.Gate Out Signal: Output of the logic gateLogic.LE19.Timer Out Signal: Timer OutputLogic.LE19.Out Signal: Latched Output (Q)Logic.LE19.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE20.Gate Out Signal: Output of the logic gateLogic.LE20.Timer Out Signal: Timer OutputLogic.LE20.Out Signal: Latched Output (Q)Logic.LE20.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE21.Gate Out Signal: Output of the logic gateLogic.LE21.Timer Out Signal: Timer OutputLogic.LE21.Out Signal: Latched Output (Q)Logic.LE21.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE22.Gate Out Signal: Output of the logic gateLogic.LE22.Timer Out Signal: Timer OutputLogic.LE22.Out Signal: Latched Output (Q)Logic.LE22.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE23.Gate Out Signal: Output of the logic gateLogic.LE23.Timer Out Signal: Timer OutputLogic.LE23.Out Signal: Latched Output (Q)Logic.LE23.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE24.Gate Out Signal: Output of the logic gateLogic.LE24.Timer Out Signal: Timer OutputLogic.LE24.Out Signal: Latched Output (Q)Logic.LE24.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE25.Gate Out Signal: Output of the logic gate

592 www.eaton.com

Page 593: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE25.Timer Out Signal: Timer OutputLogic.LE25.Out Signal: Latched Output (Q)Logic.LE25.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE26.Gate Out Signal: Output of the logic gateLogic.LE26.Timer Out Signal: Timer OutputLogic.LE26.Out Signal: Latched Output (Q)Logic.LE26.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE27.Gate Out Signal: Output of the logic gateLogic.LE27.Timer Out Signal: Timer OutputLogic.LE27.Out Signal: Latched Output (Q)Logic.LE27.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE28.Gate Out Signal: Output of the logic gateLogic.LE28.Timer Out Signal: Timer OutputLogic.LE28.Out Signal: Latched Output (Q)Logic.LE28.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE29.Gate Out Signal: Output of the logic gateLogic.LE29.Timer Out Signal: Timer OutputLogic.LE29.Out Signal: Latched Output (Q)Logic.LE29.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE30.Gate Out Signal: Output of the logic gateLogic.LE30.Timer Out Signal: Timer OutputLogic.LE30.Out Signal: Latched Output (Q)Logic.LE30.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE31.Gate Out Signal: Output of the logic gateLogic.LE31.Timer Out Signal: Timer OutputLogic.LE31.Out Signal: Latched Output (Q)Logic.LE31.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE32.Gate Out Signal: Output of the logic gateLogic.LE32.Timer Out Signal: Timer OutputLogic.LE32.Out Signal: Latched Output (Q)Logic.LE32.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE33.Gate Out Signal: Output of the logic gateLogic.LE33.Timer Out Signal: Timer OutputLogic.LE33.Out Signal: Latched Output (Q)Logic.LE33.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE34.Gate Out Signal: Output of the logic gateLogic.LE34.Timer Out Signal: Timer OutputLogic.LE34.Out Signal: Latched Output (Q)Logic.LE34.Out inverted Signal: Negated Latched Output (Q NOT)

www.eaton.com 593

Page 594: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE35.Gate Out Signal: Output of the logic gateLogic.LE35.Timer Out Signal: Timer OutputLogic.LE35.Out Signal: Latched Output (Q)Logic.LE35.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE36.Gate Out Signal: Output of the logic gateLogic.LE36.Timer Out Signal: Timer OutputLogic.LE36.Out Signal: Latched Output (Q)Logic.LE36.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE37.Gate Out Signal: Output of the logic gateLogic.LE37.Timer Out Signal: Timer OutputLogic.LE37.Out Signal: Latched Output (Q)Logic.LE37.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE38.Gate Out Signal: Output of the logic gateLogic.LE38.Timer Out Signal: Timer OutputLogic.LE38.Out Signal: Latched Output (Q)Logic.LE38.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE39.Gate Out Signal: Output of the logic gateLogic.LE39.Timer Out Signal: Timer OutputLogic.LE39.Out Signal: Latched Output (Q)Logic.LE39.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE40.Gate Out Signal: Output of the logic gateLogic.LE40.Timer Out Signal: Timer OutputLogic.LE40.Out Signal: Latched Output (Q)Logic.LE40.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE41.Gate Out Signal: Output of the logic gateLogic.LE41.Timer Out Signal: Timer OutputLogic.LE41.Out Signal: Latched Output (Q)Logic.LE41.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE42.Gate Out Signal: Output of the logic gateLogic.LE42.Timer Out Signal: Timer OutputLogic.LE42.Out Signal: Latched Output (Q)Logic.LE42.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE43.Gate Out Signal: Output of the logic gateLogic.LE43.Timer Out Signal: Timer OutputLogic.LE43.Out Signal: Latched Output (Q)Logic.LE43.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE44.Gate Out Signal: Output of the logic gateLogic.LE44.Timer Out Signal: Timer OutputLogic.LE44.Out Signal: Latched Output (Q)

594 www.eaton.com

Page 595: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE44.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE45.Gate Out Signal: Output of the logic gateLogic.LE45.Timer Out Signal: Timer OutputLogic.LE45.Out Signal: Latched Output (Q)Logic.LE45.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE46.Gate Out Signal: Output of the logic gateLogic.LE46.Timer Out Signal: Timer OutputLogic.LE46.Out Signal: Latched Output (Q)Logic.LE46.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE47.Gate Out Signal: Output of the logic gateLogic.LE47.Timer Out Signal: Timer OutputLogic.LE47.Out Signal: Latched Output (Q)Logic.LE47.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE48.Gate Out Signal: Output of the logic gateLogic.LE48.Timer Out Signal: Timer OutputLogic.LE48.Out Signal: Latched Output (Q)Logic.LE48.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE49.Gate Out Signal: Output of the logic gateLogic.LE49.Timer Out Signal: Timer OutputLogic.LE49.Out Signal: Latched Output (Q)Logic.LE49.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE50.Gate Out Signal: Output of the logic gateLogic.LE50.Timer Out Signal: Timer OutputLogic.LE50.Out Signal: Latched Output (Q)Logic.LE50.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE51.Gate Out Signal: Output of the logic gateLogic.LE51.Timer Out Signal: Timer OutputLogic.LE51.Out Signal: Latched Output (Q)Logic.LE51.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE52.Gate Out Signal: Output of the logic gateLogic.LE52.Timer Out Signal: Timer OutputLogic.LE52.Out Signal: Latched Output (Q)Logic.LE52.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE53.Gate Out Signal: Output of the logic gateLogic.LE53.Timer Out Signal: Timer OutputLogic.LE53.Out Signal: Latched Output (Q)Logic.LE53.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE54.Gate Out Signal: Output of the logic gateLogic.LE54.Timer Out Signal: Timer Output

www.eaton.com 595

Page 596: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE54.Out Signal: Latched Output (Q)Logic.LE54.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE55.Gate Out Signal: Output of the logic gateLogic.LE55.Timer Out Signal: Timer OutputLogic.LE55.Out Signal: Latched Output (Q)Logic.LE55.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE56.Gate Out Signal: Output of the logic gateLogic.LE56.Timer Out Signal: Timer OutputLogic.LE56.Out Signal: Latched Output (Q)Logic.LE56.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE57.Gate Out Signal: Output of the logic gateLogic.LE57.Timer Out Signal: Timer OutputLogic.LE57.Out Signal: Latched Output (Q)Logic.LE57.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE58.Gate Out Signal: Output of the logic gateLogic.LE58.Timer Out Signal: Timer OutputLogic.LE58.Out Signal: Latched Output (Q)Logic.LE58.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE59.Gate Out Signal: Output of the logic gateLogic.LE59.Timer Out Signal: Timer OutputLogic.LE59.Out Signal: Latched Output (Q)Logic.LE59.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE60.Gate Out Signal: Output of the logic gateLogic.LE60.Timer Out Signal: Timer OutputLogic.LE60.Out Signal: Latched Output (Q)Logic.LE60.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE61.Gate Out Signal: Output of the logic gateLogic.LE61.Timer Out Signal: Timer OutputLogic.LE61.Out Signal: Latched Output (Q)Logic.LE61.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE62.Gate Out Signal: Output of the logic gateLogic.LE62.Timer Out Signal: Timer OutputLogic.LE62.Out Signal: Latched Output (Q)Logic.LE62.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE63.Gate Out Signal: Output of the logic gateLogic.LE63.Timer Out Signal: Timer OutputLogic.LE63.Out Signal: Latched Output (Q)Logic.LE63.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE64.Gate Out Signal: Output of the logic gate

596 www.eaton.com

Page 597: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE64.Timer Out Signal: Timer OutputLogic.LE64.Out Signal: Latched Output (Q)Logic.LE64.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE65.Gate Out Signal: Output of the logic gateLogic.LE65.Timer Out Signal: Timer OutputLogic.LE65.Out Signal: Latched Output (Q)Logic.LE65.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE66.Gate Out Signal: Output of the logic gateLogic.LE66.Timer Out Signal: Timer OutputLogic.LE66.Out Signal: Latched Output (Q)Logic.LE66.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE67.Gate Out Signal: Output of the logic gateLogic.LE67.Timer Out Signal: Timer OutputLogic.LE67.Out Signal: Latched Output (Q)Logic.LE67.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE68.Gate Out Signal: Output of the logic gateLogic.LE68.Timer Out Signal: Timer OutputLogic.LE68.Out Signal: Latched Output (Q)Logic.LE68.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE69.Gate Out Signal: Output of the logic gateLogic.LE69.Timer Out Signal: Timer OutputLogic.LE69.Out Signal: Latched Output (Q)Logic.LE69.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE70.Gate Out Signal: Output of the logic gateLogic.LE70.Timer Out Signal: Timer OutputLogic.LE70.Out Signal: Latched Output (Q)Logic.LE70.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE71.Gate Out Signal: Output of the logic gateLogic.LE71.Timer Out Signal: Timer OutputLogic.LE71.Out Signal: Latched Output (Q)Logic.LE71.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE72.Gate Out Signal: Output of the logic gateLogic.LE72.Timer Out Signal: Timer OutputLogic.LE72.Out Signal: Latched Output (Q)Logic.LE72.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE73.Gate Out Signal: Output of the logic gateLogic.LE73.Timer Out Signal: Timer OutputLogic.LE73.Out Signal: Latched Output (Q)Logic.LE73.Out inverted Signal: Negated Latched Output (Q NOT)

www.eaton.com 597

Page 598: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE74.Gate Out Signal: Output of the logic gateLogic.LE74.Timer Out Signal: Timer OutputLogic.LE74.Out Signal: Latched Output (Q)Logic.LE74.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE75.Gate Out Signal: Output of the logic gateLogic.LE75.Timer Out Signal: Timer OutputLogic.LE75.Out Signal: Latched Output (Q)Logic.LE75.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE76.Gate Out Signal: Output of the logic gateLogic.LE76.Timer Out Signal: Timer OutputLogic.LE76.Out Signal: Latched Output (Q)Logic.LE76.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE77.Gate Out Signal: Output of the logic gateLogic.LE77.Timer Out Signal: Timer OutputLogic.LE77.Out Signal: Latched Output (Q)Logic.LE77.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE78.Gate Out Signal: Output of the logic gateLogic.LE78.Timer Out Signal: Timer OutputLogic.LE78.Out Signal: Latched Output (Q)Logic.LE78.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE79.Gate Out Signal: Output of the logic gateLogic.LE79.Timer Out Signal: Timer OutputLogic.LE79.Out Signal: Latched Output (Q)Logic.LE79.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE80.Gate Out Signal: Output of the logic gateLogic.LE80.Timer Out Signal: Timer OutputLogic.LE80.Out Signal: Latched Output (Q)Logic.LE80.Out inverted Signal: Negated Latched Output (Q NOT)

These trips will start the BF module if all current functions have been selected as the trigger event.

In case that the protective device is equipped with directional overcurrent protection. All ANSI 67 elements (directional overcurrent protection), will be displayed as ANSI 50/51 elements. That means, that the name of an ANSI 50/51 element wont change, if it is set within the device planning from “non-directional” to “directional”.

Name Description

-.- No assignment50P[1].TripCmd Signal: Trip Command50P[2].TripCmd Signal: Trip Command

598 www.eaton.com

Page 599: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

50P[3].TripCmd Signal: Trip Command51P[1].TripCmd Signal: Trip Command51P[2].TripCmd Signal: Trip Command51P[3].TripCmd Signal: Trip Command50X[1].TripCmd Signal: Trip Command50X[2].TripCmd Signal: Trip Command51X[1].TripCmd Signal: Trip Command51X[2].TripCmd Signal: Trip Command50R[1].TripCmd Signal: Trip Command50R[2].TripCmd Signal: Trip Command51R[1].TripCmd Signal: Trip Command51R[2].TripCmd Signal: Trip Command46[1].TripCmd Signal: Trip Command46[2].TripCmd Signal: Trip CommandZI.TripCmd Signal: Zone Interlocking Trip Command

These trips will start the BF module if external trips have been selected as the trigger event.

Name Description

-.- No assignmentExP[1].TripCmd Signal: Trip CommandExP[2].TripCmd Signal: Trip CommandExP[3].TripCmd Signal: Trip CommandExP[4].TripCmd Signal: Trip Command

Commissioning: Breaker Failure Protection

The time that is configured for the BF MUST NOT be below the breaker control time, otherwise an unwanted operation of the BF is caused by any protective trip.

Object to Be Tested:

• Test of the breaker failure protection.

Necessary Means:

• Current source;• Current meter; and• Timer.

www.eaton.com 599

Page 600: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

When testing, the applied test current must always be higher than the tripping threshold »I-BF«. If the test current falls below the threshold while the breaker is in the “Off” position, no pickup will be generated.

Procedure (Single-Phase):

For testing the tripping time of the BF protection, a test current has to be higher than the threshold value of one of the current protection modules that are assigned to trigger the BF protection. The BF trip delay can be measured from the time when one of the triggering inputs becomes active to the time when the BF protection trip is asserted.

To avoid wiring errors, checked to make sure the breaker in the upstream system switches off.

The time, measured by the timer, should be in line with the specified tolerances.

Re-connect the control cable to the breaker!

Successful Test Result:

The actual times measured comply with the setpoint times. The breaker in the higher-level section switches off.

600 www.eaton.com

Page 601: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

CTS – Current Transformer SupervisionCTS

Most functions of metering, protection, and control in the relay rely on correct current measurements. It is important to make sure the CT connections and their operations are correct. The failures (including CT secondary wire broken, insulation broken down, broken wiring between CT and relay, and mismatched polarities) will cause the incorrect current measurements. The other CT errors (due to the magnetizing current that is proportional to the primary current, CT saturation, and measuring circuit and quantization error) can also cause inaccurate current measurements.

The CTS utilizes the Kirchhoff’s current law to detect a CT failure and can differentiate the wiring errors from the measurement errors by adding biases to offset the measurement related errors. The biases include two terms, one of which is related to the static error that accounts for CT magnetizing characteristic differences and current measurement circuit calibration errors and other is the dynamic error that is proportional to the measured maximum current due to CT transformation characteristics. The CTs are assumed to be used in the wye-grounded winding sides. Under normal conditions, the mismatch between the calculated and the measured zero sequence current should be less than the bias value. However, if there is a CT wiring error, such relationship will not hold true. If the mismatch exceeds the bias for a specified time, an alarm will be generated.

The operating principle can be expressed in terms of CT secondary currents as follow:

IL1IL2IL3KI∗IG=3∗I 0KI ∗ IG∆IKd∗Imax

KI is the ratio of the ground CT ratio over the phase CT ratio, and it is automatically calculated from the rated system parameters.

∆I = The static error, a minimum mismatch allowed between the calculated and measured zero sequence current.

Kd = The dynamic error factor, a restrain slope that defines a percentage error generated by a high current.

Imax = maximum phase current.Total bias value = ∆I + Kd x Imax.

The current transformer supervision operation can be graphically represented as follows.

If the current is measured in two phases only (for example only IA/IB) or if there is no separate ground current measuring (e.g.: normally via a zero sequence CT), the supervision function should be deactivated.

www.eaton.com 601

Limit Value

Imax

I

Kd*Imax

Page 602: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

602 www.eaton.com

Ple

ase

Ref

er to

Dia

gram

: Blo

ckin

gs

IX

Cal

cula

ted

IA

CTS

.Pic

kup

CTS

(Ele

men

t is

not d

eact

ivat

ed a

nd n

o ac

tive

bloc

king

sig

nals

)

ICIB IX

Σ

+ -

KdCTS

.¬I

2

AND

CTS

.t

t 0

40

Page 603: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Device Planning Parameters of the Current Transformer Supervision

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Do not use [Device Plan-ning]

Global Protection Parameter of the Current Transformer Supervision

Parameter Description Setting Range Default Menu Path

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Supervision

/CTS]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Supervision

/CTS]

Setting Group Parameters of the Current Transformer Supervision

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Supervision

/CTS]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Supervision

/CTS]ΔI In order to prevent faulty tripping of phase

selective protection functions that use the current as tripping criterion. If the difference of the measured ground current and the calculated value I0 is higher than the pick up value ΔI, an pickup event is generated after expiring of the excitation time. In such a case, a fuse failure, a broken wire or a faulty measuring circuit can be assumed.

0.10 – 1.00 In 0.50 In [Protection Para

/<n>

/Supervision

/CTS]

www.eaton.com 603

Page 604: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Pickup delay Pickup delay 0.1 – 9999.0 s 1.0 s [Protection Para

/<n>

/Supervision

/CTS]Kd Dynamic correction factor for the evaluation

of the difference between calculated and measured ground current. This correction factor allows transformer faults, caused by higher currents, to be compensated.

0.00 - 0.99 0.00 [Protection Para

/<n>

/Supervision

/CTS]

Current Transformer Supervision Input States

Name Description Assignment Via

ExBlo1-I Module Input State: External Blocking 1 [Protection Para

/Global Prot Para

/Supervision

/CTS]ExBlo2-I Module Input State: External Blocking 2 [Protection Para

/Global Prot Para

/Supervision

/CTS]

Current Transformer Supervision Signals (Outputs States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingPickup Signal: Pickup Current Transformer Measuring Circuit Supervision

Commissioning: Current Transformer Failure Supervision

Preconditions:1.Measurement of all three-phase currents (are applied to the measuring inputs of the device).2.The ground current is detected via a zero sequence transformer (not in residual connection).

604 www.eaton.com

Page 605: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Object to Be Tested:

Check of the CT Supervision (by comparing the calculated with the measured ground current).

Necessary Means:

Three-phase current source.

Procedure, Part 1:

• Set the limiting value of the CTs to »delta I=0.1*In«.• Feed a three-phase, symmetrical current system (approx. nominal current) to the secondary side.• Disconnect the current of one phase from one of the measuring inputs (the symmetrical feeding at the

secondary side has to be maintained).• Make sure that the »CTS.ALARM« signal is generated.

Successful Test Result, Part 1:

The »CTS.ALARM« signal is generated.

Procedure, Part 2:

• Feed a three-phase, symmetrical current system (approx. nominal current) to the secondary side.• Feed a current that is higher than the threshold value for the measuring circuit supervision to the ground

current measuring input.• Make sure that the »CTS.ALARM« signal is generated.

Successful Test Result, Part 2:

The »CTS.ALARM« signal is generated.

www.eaton.com 605

Page 606: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

74TC - Trip Circuit MonitoringTCM

The trip circuit monitoring is used for monitoring if the trip circuit is ready for opening operations. The monitoring can be fulfilled by two ways. The one way assumes only 52a is used in the trip circuit and other assumes besides 52a, 52b is also used for the circuit monitoring. Two options either 52a only (or breaker closed) or both (52a and 52b) are provided for the User to select based on use of the breaker status in the trip circuit. With 52a only in the trip circuit, the monitoring is only effective when the breaker is closed while if both 52a and 52b are used, the trip circuit will be monitored all time as long as the control power is on.

The trip circuit continuity is monitored through the digital inputs DI1 and DI2, and the breaker status 52a or 52b or both must be monitored through the other digital inputs. Note that the digital inputs used for this purpose must be configured properly based on the trip circuit control voltage and also that the de-bouncing times must be set to minimum. If the trip circuit is detected broken, an alarm will be issued with a specified delay, which must be greater than a period from the time when a trip contact is closed to the time when the breaker status is clearly recognized by the relay.

In Slot 1 has two digital inputs, each of which has a separate root (contact separation) for the trip circuit supervision.

In this case, the trip circuit supply voltage serves also as supply voltage for the digital inputs and so the supply voltage failure of a trip circuit can be detected directly.

In order to identify a conductor failure in the trip circuit on the supply line or in the trip coil, the off-coil has to be looped-in to the supervision circuit.

The time delay is to be set in a way that switching actions cannot cause false trips in this module.

606 www.eaton.com

Page 607: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

One Breaker Application Examples

Trip Circuit Monitoring for one Breaker: Auxiliary Contacts (52a and 52b) in trip circuit.

www.eaton.com 607

Breaker 1 (Bkr[1]) Control Voltage

12345678

PE

9101112

COM1

131415161718

V+

DI1COM2

DI2

V-

X1TC

W1-52a

W1-52b

+DC

- DC

52a 52b

Trip

Relay Control Voltage

AND

t-TCM

0

tTCM.Pickup

56

X1

AND78

X1

OR

DI-Threshold

52a and 52b in Trip Circuit

DI-Threshold

V+V-

Page 608: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Trip Circuit Monitoring for One Breaker: Auxiliary Contacts (52a Only) in Trip Circuit.

Device Planning Parameters of the Trip Circuit Monitoring Module

Parameter Description Options Default Menu Path

Mode Mode Do not use,

Use

Use [Device Plan-ning]

Global Protection Parameters of the Trip Circuit Monitoring Module

Parameter Description Setting Range Default Menu Path

Mode Select if trip circuit is going to be monitored when the breaker is closed or when the breaker is either open or close.

Closed,

Either

Closed [Protection Para

/Global Prot Para

/Supervision

/TCM]

608 www.eaton.com

Breaker 1 (Bkr[1]) Control Voltage

12345678

PE

9101112

COM1

131415161718

V+

DI1

V-

X1TC

W1-52a

W1-52b

+DC

- DC

52a 52b

Trip

Relay Control Voltage

AND

Bkr.Pos CLOSE

t-TCM

0

t TCM.Pickup56

X1

52a only in Trip Circuit

DI-Threshold

V+V-

Page 609: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

Input 1 Select the input configured to monitor the trip coil when the breaker is closed.

-.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

DI-8P X1.DI 1 [Protection Para

/Global Prot Para

/Supervision

/TCM]

Input 2 Select the input configured to monitor the trip coil when the breaker is open. Only available if Mode set to “Either”.

Only available if: Mode = Either

-.-,

DI-8P X1.DI 1,

DI-8P X1.DI 2,

DI-8P X1.DI 3,

DI-8P X1.DI 4,

DI-8P X1.DI 5,

DI-8P X1.DI 6,

DI-8P X1.DI 7,

DI-8P X1.DI 8

-.- [Protection Para

/Global Prot Para

/Supervision

/TCM]

ExBlo1 External blocking of the module, if blocking is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Supervision

/TCM]ExBlo2 External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List -.- [Protection Para

/Global Prot Para

/Supervision

/TCM]

www.eaton.com 609

Page 610: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Setting Group Parameters of the Trip Circuit Monitoring Module

Parameter Description Setting Range Default Menu Path

Function Permanent activation or deactivation of module/element.

Inactive,

Active

Inactive [Protection Para

/<n>

/Supervision

/TCM]ExBlo Fc Activate (allow) or inactivate (disallow)

blocking of the module/element. This parameter is only effective if a signal is assigned to the corresponding global protection parameter. If the signal becomes true, those modules/elements are blocked that are configured "ExBlo Fc=active".

Inactive,

Active

Inactive [Protection Para

/<n>

/Supervision

/TCM]t-TCM Tripping delay time of the Trip Circuit

Supervision0.10 – 10.00 s 0.2 s [Protection Para

/<n>

/Supervision

/TCM]

Trip Circuit Monitoring Module Input States

Name Description Assignment Via

CinBkr-52a-I Feed-back signal of the Bkr. (52a) [Protection Para

/Global Prot Para

/Supervision

/TCM]CinBkr-52b-I Module Input State: Feed-back signal of the

Bkr. (52b)[Protection Para

/Global Prot Para

/Supervision

/TCM]ExBlo1-I Module Input State: External Blocking 1 [Protection Para

/Global Prot Para

/Supervision

/TCM]

610 www.eaton.com

Page 611: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description Assignment Via

ExBlo2-I Module Input State: External Blocking 2 [Protection Para

/Global Prot Para

/Supervision

/TCM]Bkr Pos Detect-I Module Input State: Criterion by which the

Breaker Switch Position is to be detected.[]

Trip Circuit Monitoring Module Signals (Output States)

Name Description

Active Signal: ActiveExBlo Signal: External BlockingPickup Signal: Pickup Trip Circuit SupervisionNot Possible Not possible because no state indicator assigned to the breaker.

Commissioning: Trip Circuit Monitoring for Breakers

For breakers that trip by means of little energy (e.g.: via an optocoupler), it has to be ensured that the current applied by the digital inputs will not cause false tripping of the breaker.

Object to Be Tested:Test of the trip circuit monitoring (with 52a and 52b contact).

Procedure, Part 1:Simulate failure of the control voltage in the power circuits.

Successful Test Result, Part 1:After expiration of »t-TCM« the trip circuit supervision, TCM of the device should signal an alarm.

Procedure, Part 2:Simulate a broken cable in the breaker control circuit.

Successful Test Result, Part 2:After expiration of »t-TCM«, the trip circuit supervision TCM of the device should signal an alarm.

www.eaton.com 611

Page 612: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Self SupervisionThe System-OK contact (SC relay, life-contact) cannot be configured. The system contact is a Form “C” contact that picks up when the device is free from internal faults. While the device is booting up, the System OK relay (SC) remains dropped-off (unenergized). As soon as the system is properly started (and protection is active), the System Contact picks up and the System LED is activated accordingly.

The devices are continuously monitored and supervised by different methods during normal operation as well as during the start-up phase.

Results of this supervision may be:

• Messages appearing within the event recorder;• Indications within the display or PowerPort-E;• Corrective measures;• Restart of the device; or• Any combination of the above results.

In case of failures that cannot be corrected immediately, 3 restarts within 20 minutes are accepted before the device will be deactivated. In such a case, the device should be removed for service to ensure continuous correct operation. The Eaton Customer Service contact information and address can be found at the front of this manual.

In case of any failures, the recorders of the device should be left untouched to ensure an easy diagnosis and proper repair at the factory. Besides the records and visible indications to the customer, there is internal information about failures. These allow Eaton service personnel at the repair facility to make a detailed analysis of files with failure reports.

Self supervision is applied by different functions at different cyclic or non-cyclic timings to the following parts and functions of the device:

• Faultless cyclic execution of the software;• Functional capability of memory boards;• Consistency of data;• Functional capability of hardware sub-assemblies; and• Faultless operation of the measuring unit.

Faultless cyclic operation of the software is supervised by timing analysis and checking results of different functions. Errors of the software (watchdog function) lead to restarting the device and switching off the System-OK contact (life contact). In addition, the “System-OK” LED will blink red after 3 unsuccessful attempts to restart the device within a time period of 20 minutes.

The main processor cyclically monitors the operation of the signal processor and initiates corrective actions or restart of the device in case of faulty operation. Data and files are generally secured against unintended overwriting or faulty changes by check-sums.

The measuring unit continuously checks the measured data by comparing received data with data from a second channel sampled in parallel.

The auxiliary voltage is monitored continuously. If the voltage of one of the different supply circuits falls below a certain threshold, a restart of the device is initiated. If the voltage staggers around the threshold, the device also starts again after several seconds. Additionally the level of all internal supply voltage groups are continuously monitored.

Independent of these separate monitoring functions, the intermediate voltage circuit is buffered until all important and relevant operational and fault-data have been saved and the device initiates a restart.

612 www.eaton.com

Page 613: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Error Messages / Codes

After a reboot of the device, the reason for rebooting will be displayed under [Operation/Status Display/Sys/Reboot]. For more information about the reboot reason, please refer to the information in this section.

The reboot will also be logged within the event recorder. Rebooting causes an event named “Sys.Reboot”.

Numeric Reboot Codes

Error Messages/Codes

1. Reboot after clean switching off of the device - Normal reboot after clean shut-down of the device.

2. Reboot by User command - User-initiated reboot through panel command.

3. Super reset - Reset to factory settings.

4. Restart by debugger - Eaton internally for system-analysis purposes.

5. Restart because of configuration changes.

6. General failure - Reboot without definite reason.

7. Reboot by “SW-system abort” (HOST-side) - Summary of several reboot reasons detected by the software (i.e.: wrong pointer, corrupted files, etc.).

8. Reboot by watchdog timeout (HOST-side) - Signaling if the protection-class-task hangs.

9. Reboot by system abort (DSP-side) - Summary of several reboot reasons detected by software (i.e.: wrong pointer, DSP-side).

10. Reboot by watchdog timeout (DSP-side) - Appears when DSP sequence needs too long for one cycle.

11. Loss of auxiliary voltage or low voltage reboot after loss of auxiliary voltage or voltage dropping below reboot level but not becoming zero.

12. Faulty memory access - Message of MMU (memory mapping unit) that prohibited memory access has occurred.

www.eaton.com 613

Page 614: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Programmable LogicAvailable Elements (Equations):Logic

General DescriptionThe protective device includes programmable logic equations for programming inputs, outputs, blocking of protective functions, and custom logic functions in the relay.

The logic provides control of the relay output contacts based on the state of the inputs that can be chosen from the assignment list (protective function pickups, protective function states, breaker states, system alarms, and module inputs). The User can use the output signals of a logic equation as inputs in higher equations (e.g.: the output signal of logic equation 10 might be used as an input of logic equation 11).

Principle Overview

614 www.eaton.com

IN1

IN2

IN3

IN4

Reset Latched

Inverting settable

Inverting settable

Inverting settable

Inverting settable

AND

OR

NAND

NOR

Inverting settable

Inverting settable

t-On Delay

t-Off Delay

Gate Out

Timer Out

Out

Out inverted

Set

Reset

Type of logic gate selectable

Delay Timer

S

R

Q

Q

Page 615: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Detailed Overview – Overall Logic Diagram.

www.eaton.com 615

φ

AN

DO

RN

AN

DN

OR

t-On

Del

ay

t-Off

Del

ay

Gat

e O

ut

Tim

er O

ut Out

Out

inve

rted

Del

ay T

imer

1..n

, Ass

ignm

ent L

ist

LE[x

].IN

1

Activ

e

Inac

tive

Inve

rting

1XO

R

1..n

, Ass

ignm

ent L

ist

LE[x

].IN

2

Activ

e

Inac

tive

Inve

rting

2XO

R

1..n

, Ass

ignm

ent L

ist

LE[x

].IN

3

Activ

e

Inac

tive

Inve

rting

3XO

R

1..n

, Ass

ignm

ent L

ist

LE[x

].IN

4

Activ

e

Inac

tive

Inve

rting

4XO

R

1..n

, Ass

ignm

ent L

ist

LE[x

].Res

et L

atch

ed

Activ

e

Inac

tive

Inve

rting

Res

etX

OR

Gat

e

AND

OR

NA

ND

NO

R

Activ

e

Inac

tive

Inve

rting

Set

XO

RS

Q

R

Q

LE[1

]...[n

]

Page 616: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Available Gates (Operators)

Within the Logic Equation, the following Gates can be used.

Input Signals

The User can assign up to four Input signals (from the assignment list) to the inputs of the gate.

As an option, each of the four input signals can be inverted (negated).

Timer Gate (On Delay and Off Delay)

The output of the gate can be delayed. The User has the option to set an On and an Off delay.

Latching

The timer issues two signals: an unlatched and a latched signal. The latched output can optionally be inverted.

In order to reset the latched signal, the User has to assign a reset signal from the assignment list. Optionally, the reset signal can also be inverted.

If no »Reset Latched« signal is assigned, then the »LATCH OUT «signal will be identical with the »TIMER OUT « signal.

Cascading Logical Outputs

The device will evaluate output states of the logic equations starting from “Logic Equation 1” up to the logic equation with the highest number. This evaluation cycle will be continuously repeated.

Cascading Logic Equations in an ascending sequence.

Cascading in an ascending sequence means that the User utilizes the output signal of “Logic Equation n” as input of “Logic Equation n+1”. If the state of “Logic Equation n” changes, the state of the output of “Logic Equation n+1” will be updated within the same cycle.

Cascading Logic Equations in a descending sequence.

Cascading in a descending sequence means that the User utilizes the output signal of “Logic Equation n+1” as input of “Logic Equation n”. If the output of “Logic Equation n+1” changes, this change of the feed back signal at the input of “Logic Equation n” will be delayed for one cycle.

616 www.eaton.com

AND ORAND OR

AND NAND OR NOR

Gate

Page 617: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 617

Logic Equation1

LE1.IN1

LE1.IN2

LE1.IN3

LE1.IN4

Output of Logic Equation 1

Logic Equation2

LE2.IN2

LE2.IN3

LE2.IN4

Output of Logic Equation 2

Update within the same evaluation cycle

Update within the next evaluation cycle (1 cycle delay)

Logic Equation2

LE2.IN1

LE2.IN2

LE2.IN3

LE2.IN4

Output of Logic Equation 2

Logic Equation1

LE1.IN2

LE1.IN3

LE1.IN4

Output of Logic Equation1

Update within the next evaluation cycle (1 cycle delay)

Logic Equation2

LE2.IN2

LE2.IN3

LE2.IN4

Output of Logic Equation 2

Logic Equation1

LE1.IN2

LE1.IN3

LE1.IN4

Output of Logic Equation 1

Logic Equation3

LE3.IN1

LE3.IN2

LE3.IN3

LE3.IN4

Logic Equation2

Output of Logic Equation 1

LE2.IN2

LE2.IN3

LE2.IN4

Output of Logic Equation 2

Logic Equation3

LE3.IN2

LE3.IN3

LE3.IN4

Output of Logic Equation 3

Logic Equation1

LE1.IN1

LE1.IN2

LE1.IN3

LE1.IN4

Update within the same evaluation cycle

Update within the same evaluation cycle

Update within the next but one evaluation cycle (2 cycles delay)

Update within the same evaluation cycle

Output of Logic Equation 3

Cascading in Ascending Order

Cascading in Descending Order

Page 618: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Programmable Logic at the Panel

WARNING improper use of logic equations might result in personal injury or damage the electrical equipment.

Do not use logic equations unless the User can ensure the safe functionality.

How to configure a logic equation?

• Within the Device Planning, set the number of required Logic Equations.

• Call up the [Logic] menu.

• Select a Logic Equation that is to be set.

• Set the Input Signals (where necessary, invert them).

• If required, configure the timer (»On delay« and »Off delay«).

• If the latched output signal is used, assign a reset signal to the reset input.

• Within the »status display«, the User can check the status of the logical inputs and outputs of the logic equation.

In case the logic equations should be cascaded, the User has to be aware of timing delays (cycles) in case of descending sequences (Please refer to the Cascading Logical Outputs section).

By means of the Status Display [Operation/Status Display], the logical states can be verified.

Programmable Logic Via PowerPort-E

WARNING improper use of logic equations might result in personal injury or damage the electrical equipment.

Do not use logic equations unless the User can ensure the safe functionality.

It is recommended to configure the logic via the PowerPort-E application.

How to configure a logic equation?

• Within the Device Planning, set the number of required Logic Equations.

• Call up the [Logic] menu.

• Set the Input Signals (where necessary, invert them).

618 www.eaton.com

Page 619: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

• If required, configure the timer (»On delay« and »Off delay«).

• If the latched output signal is used, assign a reset signal to the reset input.

• Within the »status display«, the User can check the status of the logical inputs and outputs of the logic equation.

In case the logic equations should be cascaded, the User has to be aware of timing delays (cycles) in case of descending sequences (Please refer to section: Cascading Logical Outputs).

By means of the Status Display [Operation/Status Display], the logical states can be verified.

Device Planning Parameters of the Programmable Logic

Parameter Description Options Default Menu Path

No of Equations:

Number of required Logic Equations: 0,

5,

10,

20,

40,

80

20 [Device Plan-ning]

Selection List for Logic Input Signals

Name Description

-.- No assignmentProt.Active Signal: ActiveProt.Available Signal: Protection is availableProt.I dir fwd Signal: Phase current failure forward directionProt.I dir n poss Signal: Phase fault - missing reference voltageProt.I dir rev Signal: Phase current failure reverse directionProt.IR dir fwd Signal: IR Ground fault (calculated) forwardProt.IR dir n poss Signal: IR Ground fault (calculated) direction detection not possibleProt.IR dir rev Signal: IR Ground fault (calculated) reverse directionProt.IX dir fwd Signal: IX Ground fault (measured) forwardProt.IX dir n poss Signal: IX Ground fault (measured) direction detection not possibleProt.IX dir rev Signal: IX Ground fault (measured) reverse directionProt.Pickup Signal: General PickupProt.Trip Signal: General TripBreaker.Interl CLOSE1-I State of the module input: Interlocking of the CLOSE commandBreaker.Interl CLOSE2-I State of the module input: Interlocking of the CLOSE command

www.eaton.com 619

Page 620: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Breaker.Interl CLOSE3-I State of the module input: Interlocking of the CLOSE commandBreaker.Interl OPEN1-I State of the module input: Interlocking of the OPEN commandBreaker.Interl OPEN2-I State of the module input: Interlocking of the OPEN commandBreaker.Interl OPEN3-I State of the module input: Interlocking of the OPEN commandBreaker.Ack unsucc SwitchCmd-I State of the module input: Acknowledge an error signal the

signalizes an unsuccessful switching attemptBreaker.SC CLOSE-I State of the module input: Switching CLOSE Command, e.g.: the

state of the Logic or the state of the digital inputBreaker.SC OPEN-I State of the module input: Switching OPEN Command, e.g.: the

state of the Logic or the state of the digital inputBreaker.CinBkr-52a-I Feed-back signal of the Bkr. (52a)Breaker.CinBkr-52b-I Module Input State: Feed-back signal of the Bkr. (52b)Breaker.Ready-I Module Input State: Breaker ReadyBreaker.Sys-in-Sync-I State of the module input: This signals has to become true within

the synchronization time. If not, switching is unsuccessful.Breaker.Operate Position-I State of the module input: The withdrawable Breaker is in the

Operate PositionBreaker.Test Position-I State of the module input: The withdrawable Breaker is in the Test

PositionBreaker.Removed-I State of the module input: The withdrawable Breaker is RemovedBreaker.Ack TripCmd-I State of the module input: Acknowledgment Signal (only for

automatic acknowledgment). Module input signalBreaker.SI SingleContactInd Signal: The Position of the Switchgear is detected by one auxiliary

contact (pole) only. Thus indeterminate and disturbed Positions cannot be detected.

Breaker.Pos not CLOSE Signal: Pos not CLOSEBreaker.Pos CLOSE Signal: Breaker is in CLOSE-PositionBreaker.Pos OPEN Signal: Breaker is in OPEN-PositionBreaker.Pos Indeterm Signal: Breaker is in Indeterminate PositionBreaker.Pos Disturb Signal: Breaker Disturbed - Undefined Breaker Position. The feed-

back signals (Position Indicators) contradict themselves. After expiring of a supervision timer this signal becomes true.

Breaker.Ready Signal: Breaker is ready for operation.Breaker.t-Dwell Signal: Dwell timeBreaker.Operate Position Signal: The withdrawable Breaker is in the Operate PositionBreaker.Test Position Signal: The withdrawable Breaker is in the Test PositionBreaker.Removed Signal: The withdrawable Breaker is RemovedBreaker.CES succesf Command Execution Supervision: Switching command executed

successfully.Breaker.CES Disturbed Command Execution Supervision: Switching Command

unsuccessful. Switchgear in disturbed position.Breaker.CES SAuthority Command Execution Supervision: Switching Command not

executed. No switching authority.

620 www.eaton.com

Page 621: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Breaker.CES SwitchgDir Command Execution Supervision: Switching Direction Control. A switchgear that is already OPEN should be switched OPEN again (doubly).

Breaker.CES DoubleOperating Command Execution Supervision: A second switch command is in conflict with a pending one.

Breaker.CES CLOSE durg OPEN Cmd Command Execution Supervision: CLOSE Command during a pending OPEN Command.

Breaker.CES SG not ready Command Execution Supervision: Switchgear not readyBreaker.CES Field Interl Command Execution Supervision: Switching Command not

executed because of field interlocking.Breaker.CES Station Interl Command Execution Supervision: Switching Command not

executed because of station interlocking.Breaker.CES SyncTimeout Command Execution Supervision: Switching Command not

executed No Synchronization signal while t-sync was running.Breaker.Prot CLOSE Signal: CLOSE command issued by the Prot module.Breaker.TripCmd Signal: Trip CommandBreaker.Ack TripCmd Signal: Acknowledge Trip CommandBreaker.CLOSE incl Prot CLOSE Signal: The CLOSE Command includes the CLOSE Command

issued by the Protection module.Breaker.OPEN incl TripCmd Signal: The OPEN Command includes the OPEN Command

issued by the Protection module.Breaker.Position Ind manipulated Signal: Position Ind manipulatedBreaker.Bwear Slow Breaker Signal: Slow Breaker AlarmBreaker.Res Bwear Slow Breaker Signal: Resetting the slow breaker alarm.Breaker.CLOSE Cmd Signal: CLOSE command issued to the switchgear. Depending on

the setting the signal may include the CLOSE command of the Prot module.

Breaker.OPEN Cmd Signal: OPEN command issued to the switchgear. Depending on the setting the signal may include the OPEN command of the Prot module.

Breaker.CLOSE Cmd manual Signal: CLOSE Cmd manualBreaker.OPEN Cmd manual Signal: OPEN Cmd manualBreaker.CLOSE request Signal: Synchronous CLOSE request50P[1].Pickup Signal: Pickup50P[1].Trip Signal: Trip50P[1].TripCmd Signal: Trip Command50P[2].Pickup Signal: Pickup50P[2].Trip Signal: Trip50P[2].TripCmd Signal: Trip Command50P[3].Pickup Signal: Pickup50P[3].Trip Signal: Trip50P[3].TripCmd Signal: Trip Command51P[1].Pickup Signal: Pickup

www.eaton.com 621

Page 622: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

51P[1].Trip Signal: Trip51P[1].TripCmd Signal: Trip Command51P[2].Pickup Signal: Pickup51P[2].Trip Signal: Trip51P[2].TripCmd Signal: Trip Command51P[3].Pickup Signal: Pickup51P[3].Trip Signal: Trip51P[3].TripCmd Signal: Trip Command50X[1].Pickup Signal: Pickup IX or IR50X[1].Trip Signal: Trip50X[1].TripCmd Signal: Trip Command50X[2].Pickup Signal: Pickup IX or IR50X[2].Trip Signal: Trip50X[2].TripCmd Signal: Trip Command51X[1].Pickup Signal: Pickup IX or IR51X[1].Trip Signal: Trip51X[1].TripCmd Signal: Trip Command51X[2].Pickup Signal: Pickup IX or IR51X[2].Trip Signal: Trip51X[2].TripCmd Signal: Trip Command50R[1].Pickup Signal: Pickup IX or IR50R[1].Trip Signal: Trip50R[1].TripCmd Signal: Trip Command50R[2].Pickup Signal: Pickup IX or IR50R[2].Trip Signal: Trip50R[2].TripCmd Signal: Trip Command51R[1].Pickup Signal: Pickup IX or IR51R[1].Trip Signal: Trip51R[1].TripCmd Signal: Trip Command51R[2].Pickup Signal: Pickup IX or IR51R[2].Trip Signal: Trip51R[2].TripCmd Signal: Trip Command27M[1].Pickup Signal: Pickup Voltage Element27M[1].Trip Signal: Trip27M[1].TripCmd Signal: Trip Command27M[2].Pickup Signal: Pickup Voltage Element27M[2].Trip Signal: Trip27M[2].TripCmd Signal: Trip Command59M[1].Pickup Signal: Pickup Voltage Element

622 www.eaton.com

Page 623: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

59M[1].Trip Signal: Trip59M[1].TripCmd Signal: Trip Command59M[2].Pickup Signal: Pickup Voltage Element59M[2].Trip Signal: Trip59M[2].TripCmd Signal: Trip Command27A[1].Pickup Signal: Pickup Residual Voltage Supervision-Element27A[1].Trip Signal: Trip27A[1].TripCmd Signal: Trip Command27A[2].Pickup Signal: Pickup Residual Voltage Supervision-Element27A[2].Trip Signal: Trip27A[2].TripCmd Signal: Trip Command59A[1].Pickup Signal: Pickup Residual Voltage Supervision-Element59A[1].Trip Signal: Trip59A[1].TripCmd Signal: Trip Command59A[2].Pickup Signal: Pickup Residual Voltage Supervision-Element59A[2].Trip Signal: Trip59A[2].TripCmd Signal: Trip Command59N[1].Pickup Signal: Pickup Residual Voltage Supervision-Element59N[1].Trip Signal: Trip59N[1].TripCmd Signal: Trip Command59N[2].Pickup Signal: Pickup Residual Voltage Supervision-Element59N[2].Trip Signal: Trip59N[2].TripCmd Signal: Trip Command46[1].Pickup Signal: Pickup Negative Sequence46[1].Trip Signal: Trip46[1].TripCmd Signal: Trip Command46[2].Pickup Signal: Pickup Negative Sequence46[2].Trip Signal: Trip46[2].TripCmd Signal: Trip Command47[1].Pickup Signal: Pickup Voltage Asymmetry47[1].Trip Signal: Trip47[1].TripCmd Signal: Trip Command47[2].Pickup Signal: Pickup Voltage Asymmetry47[2].Trip Signal: Trip47[2].TripCmd Signal: Trip Command81[1].Pickup Signal: Pickup Frequency Protection (collective signal)81[1].Pickup 81 Signal: Pickup Frequency Protection81[1].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-

change.

www.eaton.com 623

Page 624: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

81[1].Pickup Vector Surge Signal: Pickup Vector Surge81[1].Trip Signal: Trip Frequency Protection (collective signal)81[1].TripCmd Signal: Trip Command81[1].Trip 81 Signal: Frequency has exceeded the limit.81[1].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT81[1].Trip Vector Surge Signal: Trip delta phi81[2].Pickup Signal: Pickup Frequency Protection (collective signal)81[2].Pickup 81 Signal: Pickup Frequency Protection81[2].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-

change. 81[2].Pickup Vector Surge Signal: Pickup Vector Surge81[2].Trip Signal: Trip Frequency Protection (collective signal)81[2].TripCmd Signal: Trip Command81[2].Trip 81 Signal: Frequency has exceeded the limit.81[2].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT81[2].Trip Vector Surge Signal: Trip delta phi81[3].Pickup Signal: Pickup Frequency Protection (collective signal)81[3].Pickup 81 Signal: Pickup Frequency Protection81[3].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-

change. 81[3].Pickup Vector Surge Signal: Pickup Vector Surge81[3].Trip Signal: Trip Frequency Protection (collective signal)81[3].TripCmd Signal: Trip Command81[3].Trip 81 Signal: Frequency has exceeded the limit.81[3].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT81[3].Trip Vector Surge Signal: Trip delta phi81[4].Pickup Signal: Pickup Frequency Protection (collective signal)81[4].Pickup 81 Signal: Pickup Frequency Protection81[4].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-

change. 81[4].Pickup Vector Surge Signal: Pickup Vector Surge81[4].Trip Signal: Trip Frequency Protection (collective signal)81[4].TripCmd Signal: Trip Command81[4].Trip 81 Signal: Frequency has exceeded the limit.81[4].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT81[4].Trip Vector Surge Signal: Trip delta phi81[5].Pickup Signal: Pickup Frequency Protection (collective signal)81[5].Pickup 81 Signal: Pickup Frequency Protection81[5].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-

change.

624 www.eaton.com

Page 625: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

81[5].Pickup Vector Surge Signal: Pickup Vector Surge81[5].Trip Signal: Trip Frequency Protection (collective signal)81[5].TripCmd Signal: Trip Command81[5].Trip 81 Signal: Frequency has exceeded the limit.81[5].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT81[5].Trip Vector Surge Signal: Trip delta phi81[6].Pickup Signal: Pickup Frequency Protection (collective signal)81[6].Pickup 81 Signal: Pickup Frequency Protection81[6].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-

change. 81[6].Pickup Vector Surge Signal: Pickup Vector Surge81[6].Trip Signal: Trip Frequency Protection (collective signal)81[6].TripCmd Signal: Trip Command81[6].Trip 81 Signal: Frequency has exceeded the limit.81[6].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT81[6].Trip Vector Surge Signal: Trip delta phi32[1].Pickup Signal: Pickup Power Protection32[1].Trip Signal: Trip Power Protection32[1].TripCmd Signal: Trip Command32[2].Pickup Signal: Pickup Power Protection32[2].Trip Signal: Trip Power Protection32[2].TripCmd Signal: Trip Command32[3].Pickup Signal: Pickup Power Protection32[3].Trip Signal: Trip Power Protection32[3].TripCmd Signal: Trip Command32V[1].Pickup Signal: Pickup Power Protection32V[1].Trip Signal: Trip Power Protection32V[1].TripCmd Signal: Trip Command32V[2].Pickup Signal: Pickup Power Protection32V[2].Trip Signal: Trip Power Protection32V[2].TripCmd Signal: Trip Command32V[3].Pickup Signal: Pickup Power Protection32V[3].Trip Signal: Trip Power Protection32V[3].TripCmd Signal: Trip CommandPF-55D[1].Pickup Signal: Pickup Power FactorPF-55D[1].Trip Signal: Trip Power FactorPF-55D[1].TripCmd Signal: Trip CommandPF-55D[2].Pickup Signal: Pickup Power FactorPF-55D[2].Trip Signal: Trip Power Factor

www.eaton.com 625

Page 626: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

PF-55D[2].TripCmd Signal: Trip CommandPF-55A[1].Pickup Signal: Pickup Power FactorPF-55A[1].Trip Signal: Trip Power FactorPF-55A[1].TripCmd Signal: Trip CommandPF-55A[2].Pickup Signal: Pickup Power FactorPF-55A[2].Trip Signal: Trip Power FactorPF-55A[2].TripCmd Signal: Trip CommandZI.Ground OUT Signal: Zone Interlocking Ground OUTZI.Ground Pickup Signal: Zone Interlocking Ground PickupZI.Ground Trip Signal: Zone Interlocking Ground Trip ZI.IN Signal: Zone Interlocking INZI.OUT Signal: Zone Interlocking OUTZI.Phase OUT Signal: Zone Interlocking Phase OUTZI.Phase Pickup Signal: Zone Interlocking Phase PickupZI.Phase Trip Signal: Zone Interlocking Phase Trip ZI.Pickup Signal: Pickup Zone InterlockingZI.Trip Signal: Zone Interlocking TripZI.TripCmd Signal: Zone Interlocking Trip CommandSOTF.Active Signal: ActiveSOTF.enabled Signal: Switch Onto Fault enabled. This Signal can be used to

modify Overcurrent Protection Settings.SOTF.Ex Man CLOSE Cmd-I Module Input State: External manual breaker CLOSE command

(NOT for AR!)SOTF.I< Signal: No Load Current.CLPU.detected Signal: Cold Load detectedCLPU.enabled Signal: Cold Load enabledCLPU.ExBlo Signal: External BlockingCLPU.ExBlo1-I Module Input State: External BlockingCLPU.ExBlo2-I Module Input State: External BlockingCLPU.I< Signal: No Load Current.CLPU.Load Inrush Signal: Load InrushCLPU.Settle Time Signal: Settle TimeBF.Lockout Signal: LockoutBF.Pickup Signal: BF-Module Started (Pickup)BF.Trip Signal: Breaker Failure TripTCM.Not Possible Not possible because no state indicator assigned to the breaker.TCM.Pickup Signal: Pickup Trip Circuit SupervisionCTS.Pickup Signal: Pickup Current Transformer Measuring Circuit SupervisionLOP.Pickup Signal: Pickup Loss of PotentialAR.Blo Signal: Auto Reclosure is blocked

626 www.eaton.com

Page 627: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

AR.failed Signal: Auto Reclosing FailureAR.Lock Signal: Auto Reclosure is locked outAR.Pre Shot Pre Shot ControlAR.Ready Signal: Ready to shootAR.Running Signal: Auto Reclosing RunningAR.Standby Signal: StandbyAR.successful Signal: Auto Reclosing successfulSync.In-Sync Allowed Signal: In-Sync AllowedSync.Sys-in-Sync Signal: Bus and line voltages are in synchronism according to the

system synchronism criteria.Sync.LiveBus Signal: Live-Bus or Dead-Bus flag: 1=Live-Bus, 0=Dead-BusSync.LiveLine Signal: Live-Line or Dead-Line flag: 1=Live-Line, 0=Dead-LineSync.SlipTooHigh Signal: Frequency difference (slip frequency) between bus and line

voltages too high.Sync.SynchronFailed Signal: This signal indicates a failed synchronization. It is set for

5 s when the breaker is still open after the Sync-check Run-timer has timed out.

Sync.Sync-checkRunTiming Signal: Sync-check RunTimingSync.SyncOverridden Signal: Sync-check is overridden because one of the Synchronism

overriding conditions (DB/DL or ExtBypass) is met.Sync.VDiffTooHigh Signal: Voltage difference between bus and line too high.WiredInputs.52a M1-I State of the module input: Main 1 Breaker ClosedWiredInputs.52b M1-I State of the module input: Main 1 Breaker OpenWiredInputs.TOCa M1-I State of the module input: Main 1 Breaker Connected WiredInputs.43/10 M1-I State of the module input: Main 1 Breaker Selected To Trip WiredInputs.52a M2-I State of the module input: Main 2 Breaker ClosedWiredInputs.52b M2-I State of the module input: Main 2 Breaker OpenWiredInputs.TOCa M2-I State of the module input: Main 2 Breaker Connected WiredInputs.43/10 M2-I State of the module input: Main 2 Breaker Selected To TripWiredInputs.52a T -I State of the module input: Tie Breaker ClosedWiredInputs.52b T-I State of the module input: Tie Breaker OpenWiredInputs.TOCa T-I State of the module input: Tie Breaker Connected WiredInputs.43/10 T-I State of the module input: Tie Breaker Selected To TripWiredInputs.43 M-I State of the module input: System In ManualWiredInputs.43 A-I State of the module input: System in AutoWiredInputs.43 P1-I State of the module input: Preferred Source 1WiredInputs.43 P2-I State of the module input: Preferred Source 2WiredInputs.Bkr Trouble-I Breaker TroubleDI-8P X1.DI 1 Signal: Digital InputDI-8P X1.DI 2 Signal: Digital InputDI-8P X1.DI 3 Signal: Digital Input

www.eaton.com 627

Page 628: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

DI-8P X1.DI 4 Signal: Digital InputDI-8P X1.DI 5 Signal: Digital InputDI-8P X1.DI 6 Signal: Digital InputDI-8P X1.DI 7 Signal: Digital InputDI-8P X1.DI 8 Signal: Digital InputRO-6 X5.RO 1 Signal: Relay OutputRO-6 X5.RO 2 Signal: Relay OutputRO-6 X5.RO 3 Signal: Relay OutputRO-6 X5.RO 4 Signal: Relay OutputRO-6 X5.RO 5 Signal: Relay OutputRO-6 X5.RO 6 Signal: Relay OutputRO-4Z X2.ZI OUT Signal: Zone Interlocking OUTRO-4Z X2.RO 1 Signal: Relay OutputRO-4Z X2.RO 2 Signal: Relay OutputRO-4Z X2.RO 3 Signal: Relay OutputRO-4Z X2.RO 4 Signal: Relay OutputIEC61850.VirtualOutput1-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput2-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput3-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput4-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput5-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput6-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput7-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput8-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput9-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput10-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput11-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput12-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput13-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput14-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput15-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput16-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualInput1 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput2 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput3 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput4 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput5 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput6 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput7 Signal: Virtual Input (IEC61850 GGIO Ind)

628 www.eaton.com

Page 629: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

IEC61850.VirtualInput8 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput9 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput10 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput11 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput12 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput13 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput14 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput15 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput16 Signal: Virtual Input (IEC61850 GGIO Ind)Logic.LE1.Gate Out Signal: Output of the logic gateLogic.LE1.Timer Out Signal: Timer OutputLogic.LE1.Out Signal: Latched Output (Q)Logic.LE1.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE2.Gate Out Signal: Output of the logic gateLogic.LE2.Timer Out Signal: Timer OutputLogic.LE2.Out Signal: Latched Output (Q)Logic.LE2.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE3.Gate Out Signal: Output of the logic gateLogic.LE3.Timer Out Signal: Timer OutputLogic.LE3.Out Signal: Latched Output (Q)Logic.LE3.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE4.Gate Out Signal: Output of the logic gateLogic.LE4.Timer Out Signal: Timer OutputLogic.LE4.Out Signal: Latched Output (Q)Logic.LE4.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE5.Gate Out Signal: Output of the logic gateLogic.LE5.Timer Out Signal: Timer OutputLogic.LE5.Out Signal: Latched Output (Q)Logic.LE5.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE6.Gate Out Signal: Output of the logic gateLogic.LE6.Timer Out Signal: Timer OutputLogic.LE6.Out Signal: Latched Output (Q)Logic.LE6.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE7.Gate Out Signal: Output of the logic gateLogic.LE7.Timer Out Signal: Timer OutputLogic.LE7.Out Signal: Latched Output (Q)Logic.LE7.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE8.Gate Out Signal: Output of the logic gateLogic.LE8.Timer Out Signal: Timer Output

www.eaton.com 629

Page 630: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE8.Out Signal: Latched Output (Q)Logic.LE8.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE9.Gate Out Signal: Output of the logic gateLogic.LE9.Timer Out Signal: Timer OutputLogic.LE9.Out Signal: Latched Output (Q)Logic.LE9.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE10.Gate Out Signal: Output of the logic gateLogic.LE10.Timer Out Signal: Timer OutputLogic.LE10.Out Signal: Latched Output (Q)Logic.LE10.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE11.Gate Out Signal: Output of the logic gateLogic.LE11.Timer Out Signal: Timer OutputLogic.LE11.Out Signal: Latched Output (Q)Logic.LE11.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE12.Gate Out Signal: Output of the logic gateLogic.LE12.Timer Out Signal: Timer OutputLogic.LE12.Out Signal: Latched Output (Q)Logic.LE12.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE13.Gate Out Signal: Output of the logic gateLogic.LE13.Timer Out Signal: Timer OutputLogic.LE13.Out Signal: Latched Output (Q)Logic.LE13.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE14.Gate Out Signal: Output of the logic gateLogic.LE14.Timer Out Signal: Timer OutputLogic.LE14.Out Signal: Latched Output (Q)Logic.LE14.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE15.Gate Out Signal: Output of the logic gateLogic.LE15.Timer Out Signal: Timer OutputLogic.LE15.Out Signal: Latched Output (Q)Logic.LE15.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE16.Gate Out Signal: Output of the logic gateLogic.LE16.Timer Out Signal: Timer OutputLogic.LE16.Out Signal: Latched Output (Q)Logic.LE16.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE17.Gate Out Signal: Output of the logic gateLogic.LE17.Timer Out Signal: Timer OutputLogic.LE17.Out Signal: Latched Output (Q)Logic.LE17.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE18.Gate Out Signal: Output of the logic gate

630 www.eaton.com

Page 631: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE18.Timer Out Signal: Timer OutputLogic.LE18.Out Signal: Latched Output (Q)Logic.LE18.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE19.Gate Out Signal: Output of the logic gateLogic.LE19.Timer Out Signal: Timer OutputLogic.LE19.Out Signal: Latched Output (Q)Logic.LE19.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE20.Gate Out Signal: Output of the logic gateLogic.LE20.Timer Out Signal: Timer OutputLogic.LE20.Out Signal: Latched Output (Q)Logic.LE20.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE21.Gate Out Signal: Output of the logic gateLogic.LE21.Timer Out Signal: Timer OutputLogic.LE21.Out Signal: Latched Output (Q)Logic.LE21.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE22.Gate Out Signal: Output of the logic gateLogic.LE22.Timer Out Signal: Timer OutputLogic.LE22.Out Signal: Latched Output (Q)Logic.LE22.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE23.Gate Out Signal: Output of the logic gateLogic.LE23.Timer Out Signal: Timer OutputLogic.LE23.Out Signal: Latched Output (Q)Logic.LE23.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE24.Gate Out Signal: Output of the logic gateLogic.LE24.Timer Out Signal: Timer OutputLogic.LE24.Out Signal: Latched Output (Q)Logic.LE24.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE25.Gate Out Signal: Output of the logic gateLogic.LE25.Timer Out Signal: Timer OutputLogic.LE25.Out Signal: Latched Output (Q)Logic.LE25.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE26.Gate Out Signal: Output of the logic gateLogic.LE26.Timer Out Signal: Timer OutputLogic.LE26.Out Signal: Latched Output (Q)Logic.LE26.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE27.Gate Out Signal: Output of the logic gateLogic.LE27.Timer Out Signal: Timer OutputLogic.LE27.Out Signal: Latched Output (Q)Logic.LE27.Out inverted Signal: Negated Latched Output (Q NOT)

www.eaton.com 631

Page 632: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE28.Gate Out Signal: Output of the logic gateLogic.LE28.Timer Out Signal: Timer OutputLogic.LE28.Out Signal: Latched Output (Q)Logic.LE28.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE29.Gate Out Signal: Output of the logic gateLogic.LE29.Timer Out Signal: Timer OutputLogic.LE29.Out Signal: Latched Output (Q)Logic.LE29.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE30.Gate Out Signal: Output of the logic gateLogic.LE30.Timer Out Signal: Timer OutputLogic.LE30.Out Signal: Latched Output (Q)Logic.LE30.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE31.Gate Out Signal: Output of the logic gateLogic.LE31.Timer Out Signal: Timer OutputLogic.LE31.Out Signal: Latched Output (Q)Logic.LE31.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE32.Gate Out Signal: Output of the logic gateLogic.LE32.Timer Out Signal: Timer OutputLogic.LE32.Out Signal: Latched Output (Q)Logic.LE32.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE33.Gate Out Signal: Output of the logic gateLogic.LE33.Timer Out Signal: Timer OutputLogic.LE33.Out Signal: Latched Output (Q)Logic.LE33.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE34.Gate Out Signal: Output of the logic gateLogic.LE34.Timer Out Signal: Timer OutputLogic.LE34.Out Signal: Latched Output (Q)Logic.LE34.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE35.Gate Out Signal: Output of the logic gateLogic.LE35.Timer Out Signal: Timer OutputLogic.LE35.Out Signal: Latched Output (Q)Logic.LE35.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE36.Gate Out Signal: Output of the logic gateLogic.LE36.Timer Out Signal: Timer OutputLogic.LE36.Out Signal: Latched Output (Q)Logic.LE36.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE37.Gate Out Signal: Output of the logic gateLogic.LE37.Timer Out Signal: Timer OutputLogic.LE37.Out Signal: Latched Output (Q)

632 www.eaton.com

Page 633: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE37.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE38.Gate Out Signal: Output of the logic gateLogic.LE38.Timer Out Signal: Timer OutputLogic.LE38.Out Signal: Latched Output (Q)Logic.LE38.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE39.Gate Out Signal: Output of the logic gateLogic.LE39.Timer Out Signal: Timer OutputLogic.LE39.Out Signal: Latched Output (Q)Logic.LE39.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE40.Gate Out Signal: Output of the logic gateLogic.LE40.Timer Out Signal: Timer OutputLogic.LE40.Out Signal: Latched Output (Q)Logic.LE40.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE41.Gate Out Signal: Output of the logic gateLogic.LE41.Timer Out Signal: Timer OutputLogic.LE41.Out Signal: Latched Output (Q)Logic.LE41.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE42.Gate Out Signal: Output of the logic gateLogic.LE42.Timer Out Signal: Timer OutputLogic.LE42.Out Signal: Latched Output (Q)Logic.LE42.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE43.Gate Out Signal: Output of the logic gateLogic.LE43.Timer Out Signal: Timer OutputLogic.LE43.Out Signal: Latched Output (Q)Logic.LE43.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE44.Gate Out Signal: Output of the logic gateLogic.LE44.Timer Out Signal: Timer OutputLogic.LE44.Out Signal: Latched Output (Q)Logic.LE44.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE45.Gate Out Signal: Output of the logic gateLogic.LE45.Timer Out Signal: Timer OutputLogic.LE45.Out Signal: Latched Output (Q)Logic.LE45.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE46.Gate Out Signal: Output of the logic gateLogic.LE46.Timer Out Signal: Timer OutputLogic.LE46.Out Signal: Latched Output (Q)Logic.LE46.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE47.Gate Out Signal: Output of the logic gateLogic.LE47.Timer Out Signal: Timer Output

www.eaton.com 633

Page 634: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE47.Out Signal: Latched Output (Q)Logic.LE47.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE48.Gate Out Signal: Output of the logic gateLogic.LE48.Timer Out Signal: Timer OutputLogic.LE48.Out Signal: Latched Output (Q)Logic.LE48.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE49.Gate Out Signal: Output of the logic gateLogic.LE49.Timer Out Signal: Timer OutputLogic.LE49.Out Signal: Latched Output (Q)Logic.LE49.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE50.Gate Out Signal: Output of the logic gateLogic.LE50.Timer Out Signal: Timer OutputLogic.LE50.Out Signal: Latched Output (Q)Logic.LE50.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE51.Gate Out Signal: Output of the logic gateLogic.LE51.Timer Out Signal: Timer OutputLogic.LE51.Out Signal: Latched Output (Q)Logic.LE51.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE52.Gate Out Signal: Output of the logic gateLogic.LE52.Timer Out Signal: Timer OutputLogic.LE52.Out Signal: Latched Output (Q)Logic.LE52.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE53.Gate Out Signal: Output of the logic gateLogic.LE53.Timer Out Signal: Timer OutputLogic.LE53.Out Signal: Latched Output (Q)Logic.LE53.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE54.Gate Out Signal: Output of the logic gateLogic.LE54.Timer Out Signal: Timer OutputLogic.LE54.Out Signal: Latched Output (Q)Logic.LE54.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE55.Gate Out Signal: Output of the logic gateLogic.LE55.Timer Out Signal: Timer OutputLogic.LE55.Out Signal: Latched Output (Q)Logic.LE55.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE56.Gate Out Signal: Output of the logic gateLogic.LE56.Timer Out Signal: Timer OutputLogic.LE56.Out Signal: Latched Output (Q)Logic.LE56.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE57.Gate Out Signal: Output of the logic gate

634 www.eaton.com

Page 635: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE57.Timer Out Signal: Timer OutputLogic.LE57.Out Signal: Latched Output (Q)Logic.LE57.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE58.Gate Out Signal: Output of the logic gateLogic.LE58.Timer Out Signal: Timer OutputLogic.LE58.Out Signal: Latched Output (Q)Logic.LE58.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE59.Gate Out Signal: Output of the logic gateLogic.LE59.Timer Out Signal: Timer OutputLogic.LE59.Out Signal: Latched Output (Q)Logic.LE59.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE60.Gate Out Signal: Output of the logic gateLogic.LE60.Timer Out Signal: Timer OutputLogic.LE60.Out Signal: Latched Output (Q)Logic.LE60.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE61.Gate Out Signal: Output of the logic gateLogic.LE61.Timer Out Signal: Timer OutputLogic.LE61.Out Signal: Latched Output (Q)Logic.LE61.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE62.Gate Out Signal: Output of the logic gateLogic.LE62.Timer Out Signal: Timer OutputLogic.LE62.Out Signal: Latched Output (Q)Logic.LE62.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE63.Gate Out Signal: Output of the logic gateLogic.LE63.Timer Out Signal: Timer OutputLogic.LE63.Out Signal: Latched Output (Q)Logic.LE63.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE64.Gate Out Signal: Output of the logic gateLogic.LE64.Timer Out Signal: Timer OutputLogic.LE64.Out Signal: Latched Output (Q)Logic.LE64.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE65.Gate Out Signal: Output of the logic gateLogic.LE65.Timer Out Signal: Timer OutputLogic.LE65.Out Signal: Latched Output (Q)Logic.LE65.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE66.Gate Out Signal: Output of the logic gateLogic.LE66.Timer Out Signal: Timer OutputLogic.LE66.Out Signal: Latched Output (Q)Logic.LE66.Out inverted Signal: Negated Latched Output (Q NOT)

www.eaton.com 635

Page 636: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE67.Gate Out Signal: Output of the logic gateLogic.LE67.Timer Out Signal: Timer OutputLogic.LE67.Out Signal: Latched Output (Q)Logic.LE67.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE68.Gate Out Signal: Output of the logic gateLogic.LE68.Timer Out Signal: Timer OutputLogic.LE68.Out Signal: Latched Output (Q)Logic.LE68.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE69.Gate Out Signal: Output of the logic gateLogic.LE69.Timer Out Signal: Timer OutputLogic.LE69.Out Signal: Latched Output (Q)Logic.LE69.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE70.Gate Out Signal: Output of the logic gateLogic.LE70.Timer Out Signal: Timer OutputLogic.LE70.Out Signal: Latched Output (Q)Logic.LE70.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE71.Gate Out Signal: Output of the logic gateLogic.LE71.Timer Out Signal: Timer OutputLogic.LE71.Out Signal: Latched Output (Q)Logic.LE71.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE72.Gate Out Signal: Output of the logic gateLogic.LE72.Timer Out Signal: Timer OutputLogic.LE72.Out Signal: Latched Output (Q)Logic.LE72.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE73.Gate Out Signal: Output of the logic gateLogic.LE73.Timer Out Signal: Timer OutputLogic.LE73.Out Signal: Latched Output (Q)Logic.LE73.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE74.Gate Out Signal: Output of the logic gateLogic.LE74.Timer Out Signal: Timer OutputLogic.LE74.Out Signal: Latched Output (Q)Logic.LE74.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE75.Gate Out Signal: Output of the logic gateLogic.LE75.Timer Out Signal: Timer OutputLogic.LE75.Out Signal: Latched Output (Q)Logic.LE75.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE76.Gate Out Signal: Output of the logic gateLogic.LE76.Timer Out Signal: Timer OutputLogic.LE76.Out Signal: Latched Output (Q)

636 www.eaton.com

Page 637: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE76.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE77.Gate Out Signal: Output of the logic gateLogic.LE77.Timer Out Signal: Timer OutputLogic.LE77.Out Signal: Latched Output (Q)Logic.LE77.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE78.Gate Out Signal: Output of the logic gateLogic.LE78.Timer Out Signal: Timer OutputLogic.LE78.Out Signal: Latched Output (Q)Logic.LE78.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE79.Gate Out Signal: Output of the logic gateLogic.LE79.Timer Out Signal: Timer OutputLogic.LE79.Out Signal: Latched Output (Q)Logic.LE79.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE80.Gate Out Signal: Output of the logic gateLogic.LE80.Timer Out Signal: Timer OutputLogic.LE80.Out Signal: Latched Output (Q)Logic.LE80.Out inverted Signal: Negated Latched Output (Q NOT)System Alarms.Alarm Current Demand Signal: Alarm Current demand valueSystem Alarms.Alarm I THD Signal: Alarm Total Harmonic Distortion CurrentSystem Alarms.Alarm V THD Signal: Alarm Total Harmonic Distortion VoltageSystem Alarms.Alarm VA Demand Signal: Alarm VAs demand valueSystem Alarms.Alarm VA Power Signal: Alarm VAs peakSystem Alarms.Alarm VAr Demand Signal: Alarm VARs demand valueSystem Alarms.Alarm VAr Power Signal: Alarm VArs peakSystem Alarms.Alarm Watt Demand Signal: Alarm WATTS demand valueSystem Alarms.Alarm Watt Power Signal: Alarm WATTS peakSystem Alarms.Trip Current Demand Signal: Trip Current demand valueSystem Alarms.Trip I THD Signal: Trip Total Harmonic Distortion CurrentSystem Alarms.Trip V THD Signal: Trip Total Harmonic Distortion VoltageSystem Alarms.Trip VA Demand Signal: Trip VAs demand valueSystem Alarms.Trip VA Power Signal: Trip VAs peakSystem Alarms.Trip VAr Demand Signal: Trip VARs demand valueSystem Alarms.Trip VAr Power Signal: Trip VArs peakSystem Alarms.Trip Watt Demand Signal: Trip WATTS demand valueSystem Alarms.Trip Watt Power Signal: Trip WATTS peakSys.Maint Mode Active Signal: Arc Flash Reduction Maintenance ActiveSys.Maint Mode Comm Signal: Arc Flash Reduction Maintenance Comm. ModeSys.Maint Mode DI Signal: Arc Flash Reduction Maintenance Digital Input ModeSys.Maint Mode Inactive Signal: Arc Flash Reduction Maintenance Inactive

www.eaton.com 637

Page 638: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Sys.MaintMode Manually Signal: Arc Flash Reduction Maintenance Manual ModeSys.Maint Mode-I Module Input State: Arc Flash Reduction Maintenance SwitchSys.Min. 1 param changed Signal: At least one parameter has been changed.Sys.PS 1 Signal: Parameter Set 1Sys.PS 2 Signal: Parameter Set 2Sys.PS 3 Signal: Parameter Set 3Sys.PS 4 Signal: Parameter Set 4Sys.PS1-I State of the module input, respectively of the signal, that should

activate this Parameter Setting Group.Sys.PS2-I State of the module input, respectively of the signal, that should

activate this Parameter Setting Group.Sys.PS3-I State of the module input, respectively of the signal, that should

activate this Parameter Setting Group.Sys.PS4-I State of the module input, respectively of the signal, that should

activate this Parameter Setting Group.Sys.PSS manual Signal: Manual switch over of a Parameter SetSys.PSS via Comm Signal: Parameter Set Switch via CommunicationSys.PSS via Inp fct Signal: Parameter Set Switch via Input FunctionSys.Res AlarmCr Signal: Res AlarmCrSys.Res OperationsCr Signal: Res OperationsCrSys.Res TotalCr Signal: Res TotalCrSys.Res TripCr Signal: Res TripCr

Global Protection Parameter of the Programmable Logic

Parameter Description Setting Range Default Menu Path

LE1.Gate Logic gate AND,

OR,

NAND,

NOR

AND [Logic

/LE 1]

LE1.IN1 Assignment of the Input Signal 1..n, LogicList -.- [Logic

/LE 1]LE1.Inverting1 Inverting the input signals.

Only available if an input signal has been assigned.

Inactive,

Active

Inactive [Logic

/LE 1]

LE1.IN2 Assignment of the Input Signal 1..n, LogicList -.- [Logic

/LE 1]

638 www.eaton.com

Page 639: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

LE1.Inverting2 Inverting the input signals.

Only available if an input signal has been assigned.

Inactive,

Active

Inactive [Logic

/LE 1]

LE1.IN3 Assignment of the Input Signal 1..n, LogicList -.- [Logic

/LE 1]LE1.Inverting3 Inverting the input signals.

Only available if an input signal has been assigned.

Inactive,

Active

Inactive [Logic

/LE 1]

LE1.IN4 Assignment of the Input Signal 1..n, LogicList -.- [Logic

/LE 1]LE1.Inverting4 Inverting the input signals.

Only available if an input signal has been assigned.

Inactive,

Active

Inactive [Logic

/LE 1]

LE1.t-On Delay Switch On Delay 0.00 – 36000.00 s 0.00 s [Logic

/LE 1]LE1.t-Off Delay Switch Off Delay 0.00 – 36000.00 s 0.00 s [Logic

/LE 1]LE1.Reset Latched

Reset Signal for the Latching 1..n, LogicList -.- [Logic

/LE 1]LE1.Inverting Reset

Inverting Reset Signal for the Latching Inactive,

Active

Inactive [Logic

/LE 1]LE1.Inverting Set

Inverting the Setting Signal for the Latching Inactive,

Active

Inactive [Logic

/LE 1]

Programmable Logic Inputs

Name Description Assignment Via

LE1.Gate In1-I State of the module input: Assignment of the Input Signal

[Logic

/LE 1]LE1.Gate In2-I State of the module input: Assignment of

the Input Signal[Logic

/LE 1]LE1.Gate In3-I State of the module input: Assignment of

the Input Signal[Logic

/LE 1]LE1.Gate In4-I State of the module input: Assignment of

the Input Signal[Logic

/LE 1]

www.eaton.com 639

Page 640: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description Assignment Via

LE1.Reset Latch-I State of the module input: Reset Signal for the Latching

[Logic

/LE 1]

Programmable Logic Outputs

Name Description

LE1.Gate Out Signal: Output of the logic gateLE1.Timer Out Signal: Timer OutputLE1.Out Signal: Latched Output (Q)LE1.Out inverted Signal: Negated Latched Output (Q NOT)

640 www.eaton.com

Page 641: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

CommissioningBefore starting work on an open switchboard, it is required that the switchboard is de-energized and the following five safety regulations have been met.

Safety precautions:• Disconnect the power supply;• Secure against reconnection;• Verify that the equipment is de-energized;• Connect to ground and short-circuit all phases; and• Cover or safeguard all live adjacent parts.

The secondary circuit of a current transformer must never be opened during operation. The prevailing high voltages can cause severe injury or death.

Even when the auxiliary voltage is switched off, it is likely that there are still hazardous voltages at the component connections.

All locally applicable national and international installation and safety regulations for working at electrical power installations MUST always to be followed.

Prior to the initial voltage connection, the following must be guaranteed:

• Correct grounding of the device;• That all signal circuits are tested;• That all control circuits are tested;• Transformer wiring is checked;• Correct rating of the CTs;• Correct burden of the CTs;• That the operational conditions are in line with the Technical Data;• Correct rating of the transformer protection;• Function of the transformer fuses;• Correct wiring of all digital inputs;• Polarity and capacity of the supply voltage; and• Correct wiring of the analog inputs and outputs.

The permissible deviations of measuring values and device adjustment are dependent on the Technical Data/Tolerances.

Commissioning/Protection Test

Commissioning/protection test must be carried out by authorized and qualified personnel. Before the device is put into operation, the related documentation MUST be read and understood.

www.eaton.com 641

Page 642: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

With any test of the protection functions, the following has to be checked:

• Is activation/tripping saved in the event recorder?• Is tripping saved in the fault recorder?• Is tripping saved in the disturbance recorder?• Are all signals/messages correctly generated?• Do all generally configured blocking functions work properly?• Do all temporarily configured (via DI) blocking functions work

properly?• To enable checks on all LEDs and relay functions, these have to

be provided with the relevant pickup (alarm) and tripping functions of the respective protection functions/elements. This MUST be tested in practical operation.

Check of all temporary blockings (via digital inputs).

• In order to avoid malfunctions, all blockings related to tripping/non-tripping of protection function MUST be tested. The test can be very complex and should therefore be performed by the same personnel who set up the protection concept.

Check all general trip blockings. All general trip blockings MUST be tested.

Prior to the initial operation of the protection device, all tripping times and values shown in the adjustment list MUST be confirmed by a secondary test.

Any description of functions, parameters, inputs, or outputs that does not match the device in hand can be ignored.

Decommissioning – Removing the Plug from the RelayDismounting the relay will lead to a loss of the protection functionality. Ensure that there is a back-up protection. If you are not aware of the consequences of decommissioning the device – STOP! DO NOT start.

Inform SCADA before you start.

Switch-off the power supply.

Ensure that the cabinet is de-energized and that there are no voltages that could lead to injury of personnel.

Disconnect the terminals at the rear-side of the device. DO NOT pull any cable – pull on the plug! If it is stuck, use a screw driver.

Fasten the cables and terminals in the cabinet by means of cable clips to ensure that no accidental electrical connections are caused.

Hold the device at the front-side while removing the mounting nuts.

642 www.eaton.com

Page 643: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Remove the device carefully from the cabinet.

In case no other device is to be mounted or replaced, cover/close the cut-out in the front-door.

Close the cabinet.

www.eaton.com 643

Page 644: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Service and Commissioning SupportWithin the service menu, various functions support maintenance and commissioning of the device.

General

Within the [Service/General] menu, the User can initiate a reboot of the device.

Maintenance Mode

Principle – General UseThe Maintenance Mode can be used to reduce arc flash levels. Refer to Std. NFPA70E.

DO NOT attempt to install or perform maintenance on equipment while it is energized. Severe personal injury or death can result from contact with energized equipment. Verify that no voltage is present before opening doors of the switchboard.

If maintenance will be performed on a device, special protective clothing and equipment MUST BE USED and all industry standard procedures MUST BE FOLLOWED. Failure to do so can result in severe personal injury or death.

The Maintenance Mode can improve safety by providing a simple and reliable method to reduce fault clearing time and lower incident energy levels at energized panels. The Maintenance Mode allows the User to switch to more sensitive settings via the HMI/panel, Communication, or via a Digital Input while maintenance work is being performed at an energized panel or device. The more sensitive settings provide greater security for maintenance personnel and helps reduce the possibility of injury.

The status of the Maintenance Mode (active/inactive) is stored power fail-safe.

Manual activation is only possible via the HMI/panel (not via PowerPort-E).

The Maintenance Mode can be activated:

• Manually (only at the HMI/panel);• Via communication; or• Via a digital input.

Changing to another mode is only possible if there is no active Activation Signal (e.g.: if the device is in the “Via Digital Input Mode” and while the assigned Digital Input is “true”, the User cannot switch to the “Manual Mode”).

644 www.eaton.com

Page 645: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Before UseThe sensitivity settings for the Maintenance Mode have to be calculated and programmed into the device (according to Std. NFPA70E). They are not part of the device by default.

When the Maintenance Mode is enabled and fault current causes its operation, the fault clearing time of the associated breaker has to be very fast. Calculate the sensitivity setting on the basis of Std. NFPA70E.

Program those sensitivity settings either into a setting group or into Adaptive Parameters.

How to Use the Maintenance ModeCalculate the sensitivity setting on the basis of Std. NFPA70E. Program those sensitivity settings either into a setting group or into Adaptive Parameters.

The Maintenance Mode offers two output signals: “Maint Mode activated” and “Maint Mode not activated”.

The »Maint Mode.ACTIVATED« signal should be used to:

• Switch to another setting group (in case the sensitivity settings are saved within this setting group);• Activate “Adaptive Parameters” (in case the sensitivity settings are saved within these adaptive

parameters); and/or• Block or activate dedicated functions.

Please see the Adaptive Parameters section for more details.

The »Maint Mode.NOT ACTIVATED« signal should be used to:

• Switch back to the standard setting group when Maintenance Mode should not be used.

For fast access, the Maintenance Mode can be accessed by means of the »Softkey« Maint on the start screen (root) of the device.

www.eaton.com 645

Page 646: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

646 www.eaton.com

1..n

, Dig

Inpu

ts

Sys.

Mai

nt M

ode

Activ

ated

by

Inac

tive

Sys.

Mai

nt M

ode

Mod

e

Activ

atio

n M

anua

lly

Activ

atio

n vi

a C

omm

Activ

atio

n vi

a D

I

Inac

tive

Sys.

Mai

ntM

ode

Man

ually

Activ

e

Com

m C

md

Sys.

Mai

nt M

ode

Activ

e

Sys.

Mai

nt M

ode

Inac

tive

Sys.

Mai

ntM

ode

Man

ually

Sys.

Mai

nt M

ode

Com

m

Sys.

Mai

nt M

ode

DI

Mai

nt M

ode

Sys.

Mai

nt M

ode-

I

AND

AND

AND

OR

Sys

Page 647: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Forcing the Relay Output Contacts

The parameters, their defaults, and setting ranges have to be taken from Relay Output Contacts section.

Principle – General Use

The User MUST ENSURE that the relay output contacts operate normally after maintenance is completed. If the relay output contacts do not operate normally, the protective device WILL NOT provide protection.

For commissioning purposes or for maintenance, relay output contacts can be set by force.

Within this mode [Service/Test Mode (Prot inhibit)/WARNING! Cont?/Force RO], relay output contacts can be set by force:

• Permanent; or• Via timeout.

If they are set with a timeout, they will keep their “Force Position” only as long as this timer runs. If the timer expires, the relay will operate normally. If they are set as Permanent, they will keep the “Force Position” continuously.

There are two options available:

• Forcing a single relay »Force Rox«; and• Forcing an entire group of relay output contacts »Force all Outs«.

Forcing an entire group takes precedence over forcing a single relay output contact!

A relay output contact WILL NOT follow a force command as long as it is disarmed at the same time.

A relay output contact WILL follow a force command:

• If it is not disarmed; and • If the Direct Command is applied to the relay(s).

Keep in mind, that forcing all relay output contacts (of the same assembly group) takes precedence over the force command of a single relay output contact.

www.eaton.com 647

Page 648: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Disarming the Relay Output ContactsThe parameters, their defaults, and setting ranges have to be taken from the Relay Output Contacts section.

Principle – General Use

Within this mode [Service/Test Mode (Prot inhibit)/WARNING! Cont?/DISARMED], entire groups of relay output contacts can be disabled. By means of this test mode, contact outputs switching actions of the relay output contacts are prevented. If the relay output contacts are disarmed, maintenance actions can be carried out without the risk of taking entire processes off-line.

The User MUST ENSURE that the relay output contacts are ARMED AGAIN after maintenance is complete. If they are not armed, the protective device WILL NOT provide protection.

Zone Interlocking Output and the Supervision Contact cannot be disarmed.

Within this mode [Service/Test Mode (Prot inhibit)/WARNING! Cont?/DISARMED] entire groups of relay output contacts can be disarmed:

• Permanent; or• Via timeout.

If they are set with a timeout, they will keep their “Disarm Position” only as long as this timer runs. If the timer expires, the relay output contacts will operate normally. If they are set Permanent, they will keep the “Disarm State” continuously.

A relay output contact WILL NOT be disarmed as long as:

• A relay output contact WILL NOT be disarmed if it is latched (and not yet reset).

• A relay output contact WILL NOT be disarmed as long as a running t-OFF-delay timer is not yet expired (hold time of a relay output contact).

• If the Disarm Control is not set to active.

• If the Direct Command is not applied.

A relay output contact WILL be disarmed if it is not latched and:

• If there is no running t-OFF-delay timer (hold time of a relay output contact); and

• If the DISARM Control is set to active; and

• If the Direct Command Disarm is applied.

648 www.eaton.com

Page 649: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Failure Simulator (Sequencer)*Available Elements:Sine wave gen

* = Availability depends on ordered device.

For commissioning support and in order to analyze failures, the protective device offers the option to simulate measuring quantities. The simulation menu can be found within the [Service/Test Mode (Prot inhibit)/WARNING! Cont?/Sine wave gen] menu. The simulation cycle consists of three states:

• Pre-failure;• Failure; and• Post-failure State (Phase).

Within the [Service/Test Mode (Prot inhibit)/WARNING! Cont?/Sine wave gen/Configuration] sub-menu, the duration of each phase can be set. In addition; the measuring quantities to be simulated can be determined (e.g.: voltages, currents, and the corresponding angles) for each phase (and ground).

Setting the device into the simulation mode means taking the protective device out of operation for the duration of the simulation. Do not use this feature during operation of the device if the User cannot guarantee that there is a running and properly working backup protection.

The energy counters will be stopped while the failure simulator is running.

The simulation voltages are always phase to neutral voltages, irrespectively of the mains voltage transformers' connection method (Phase-to-phase / Wye / Open Delta).

www.eaton.com 649

pre postFailure Simulation

t-PreFault t-FaultSimulation t-PostFault

Sine wave gen

Page 650: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Application Options of the Fault Simulator**:

Stop Options Cold Simulation (Option 1) Hot Simulation (Option 2)

Do not stop

Run complete: Pre Failure, Failure, Post Failure.

How To?: Call up [Service/Test Mode (Prot inhibit)/WARNING! Cont?/Sine wave gen/Process] Ex Force Post = no assignment and

Press/Call up Start Simulation.

Simulation without tripping the breaker:Blocking protective Trips to the Breaker. That means verifying if the protective device generates a trip without energizing the trip coil of the breaker (similar to disarm the relay output contact).

How To?: Call up [Service/Test Mode (Prot inhibit)/WARNING! Cont?/Sine wave gen/Process]

Trip Cmd Mode = No Trip

Simulation is authorized to trip the breaker:How To?: Call up [Service/Test Mode (Prot inhibit)/WARNING! Cont?/Sine wave gen/Process]

Trip Cmd Mode = Trip

Stop by external signal

Force Post: As soon as this signal becomes true, the Fault Simulation will be forced to switch into the Post Failure mode. How To?: Call up [Service/Test Mode (Prot inhibit)/WARNING! Cont?/Sine wave gen/Process]

Ex Force Post = Assigned SignalManual stop

As soon as this signal becomes true, the Fault Simulation will be terminated and the device changes back to normal operation. How To?: Call up [Service/Test Mode (Prot inhibit)/WARNING! Cont?/Sine wave gen/Process]

Press/Call up Stop Simulation.

**Please note: Due to internal dependencies, the frequency of the simulation module is 0.16% greater than the rated one.

Global Protection Parameter of the Failure Simulator

Parameter Description Setting Range Default Menu Path

t-PreFault Pre Fault Duration 0.00 – 300.00 s 0.0 s [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/Times]

650 www.eaton.com

Page 651: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

t-FaultSimulation

Duration of Fault Simulation 0.00 – 10800.00 s 0.0 s [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/Times]t-PostFault t-PostFault 0.00 – 300.00 s 0.0 s [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/Times]TripCmd Mode Trip Command Mode No TripCmd,

With TripCmd

No TripCmd [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Process]ExBlo External blocking of the module, if blocking

is activated (allowed) within a parameter set and if the state of the assigned signal is true.

1..n, Assignment List Breaker.Pos CLOSE

[Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Process]Ex ForcePost Force Post state. Abort simulation. 1..n, Assignment List -.- [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Process]

www.eaton.com 651

Page 652: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Voltage Parameter of the Failure Simulator

Parameter Description Setting Range Default Menu Path

VA Fund. Voltage Fundamental Magnitude in Pre State: Phase A

0.00 – 2.00 Vn 1.0 Vn [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PreFault

/Voltage]VB Fund. Voltage Fundamental Magnitude in Pre

State: Phase B0.00 – 2.00 Vn 1.0 Vn [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PreFault

/Voltage]VC Fund. Voltage Fundamental Magnitude in Pre

State: Phase C0.00 – 2.00 Vn 1.0 Vn [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PreFault

/Voltage]

652 www.eaton.com

Page 653: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

VX Fund. Voltage Fundamental Magnitude in Pre State: VX

0.00 – 2.00 Vn 0.0 Vn [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PreFault

/Voltage]Angle VA Fund. Start Position respectively Start Angle of the

Voltage Phasor during Pre Phase:Phase A-360 - 360° 0° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PreFault

/Voltage]Angle VB Fund. Start Position respectively Start Angle of the

Voltage Phasor during Pre Phase:Phase B-360 - 360° 240° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PreFault

/Voltage]Angle VC Fund.

Start Position respectively Start Angle of the Voltage Phasor during Pre Phase:Phase C

-360 - 360° 120° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PreFault

/Voltage]

www.eaton.com 653

Page 654: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Angle VX meas Fund.

Start Position respectively Start Angle of the Voltage Phasor during Pre Phase: VX

-360 - 360° 0° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PreFault

/Voltage]VA Fund. Voltage Fundamental Magnitude in Fault

State: Phase A0.00 – 2.00 Vn 0.5 Vn [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-FaultSimulation

/Voltage]VB Fund. Voltage Fundamental Magnitude in Fault

State: Phase B0.00 – 2.00 Vn 0.5 Vn [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-FaultSimulation

/Voltage]VC Fund. Voltage Fundamental Magnitude in Fault

State: Phase C0.00 – 2.00 Vn 0.5 Vn [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-FaultSimulation

/Voltage]

654 www.eaton.com

Page 655: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

VX Fund. Voltage Fundamental Magnitude in Fault State: Phase VX

0.00 – 2.00 Vn 0. 5Vn [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-FaultSimulation

/Voltage]Angle VA Fund. Start Position respectively Start Angle of the

Voltage Phasor during Fault Phase:Phase A

-360 - 360° 0° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-FaultSimulation

/Voltage]Angle VB Fund. Start Position respectively Start Angle of the

Voltage Phasor during Fault Phase:Phase B

-360 - 360° 240° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-FaultSimulation

/Voltage]Angle VC Fund.

Start Position respectively Start Angle of the Voltage Phasor during Fault Phase:Phase C

-360 - 360° 120° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-FaultSimulation

/Voltage]

www.eaton.com 655

Page 656: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Angle VX meas Fund.

Start Position respectively Start Angle of the Voltage Phasor during Fault Phase: VX

-360 - 360° 0° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-FaultSimulation

/Voltage]VA Fund. Voltage Fundamental Magnitude during

Post phase: Phase A0.00 – 2.00 Vn 1.0 Vn [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PostFault

/Voltage]VB Fund. Voltage Fundamental Magnitude during

Post phase: Phase B0.00 – 2.00 Vn 1.0 Vn [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PostFault

/Voltage]VC Fund. Voltage Fundamental Magnitude during

Post phase: Phase C0.00 – 2.00 Vn 1.0 Vn [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PostFault

/Voltage]

656 www.eaton.com

Page 657: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

VX Fund. Voltage Fundamental Magnitude during Post phase: Phase VX

0.00 – 2.00 Vn 0.0 Vn [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PostFault

/Voltage]Angle VA Fund. Start Position respectively Start Angle of the

Voltage Phasor during Post phase: Phase A-360 - 360° 0° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PostFault

/Voltage]Angle VB Fund. Start Position respectively Start Angle of the

Voltage Phasor during Post phase: Phase B-360 - 360° 240° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PostFault

/Voltage]Angle VC Fund.

Start Position respectively Start Angle of the Voltage Phasor during Post phase: Phase C

-360 - 360° 120° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PostFault

/Voltage]

www.eaton.com 657

Page 658: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Angle VX meas Fund.

Start Position respectively Start Angle of the Voltage Phasor during Post phase: Phase VX

-360 - 360° 0° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PostFault

/Voltage]

Current Parameter of the Failure Simulator

Parameter Description Setting Range Default Menu Path

IA Fund. Current Fundamental Magnitude in Pre State: Phase A

0.00 – 40.00 In 0.0 In [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PreFault

/Current]IB Fund. Current Fundamental Magnitude in Pre

State: Phase B0.00 – 40.00 In 0.0 In [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PreFault

/Current]

658 www.eaton.com

Page 659: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

IC Fund. Current Fundamental Magnitude in Pre State: Phase C

0.00 – 40.00 In 0.0 In [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PreFault

/Current]IX meas Fund. Current Fundamental Magnitude in Pre

State: IX0.00 – 25.00 In 0.0 In [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PreFault

/Current]Angle IA Fund. Start Position respectively Start Angle of the

Current Phasor during Pre Phase:Phase A-360 - 360° 0° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PreFault

/Current]Angle IB Fund. Start Position respectively Start Angle of the

Current Phasor during Pre Phase:Phase B-360 - 360° 240° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PreFault

/Current]

www.eaton.com 659

Page 660: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Angle IC Fund. Start Position respectively Start Angle of the Current Phasor during Pre Phase:Phase C

-360 - 360° 120° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PreFault

/Current]Angle IX meas Fund.

Start Position respectively Start Angle of the Current Phasor during Pre Phase: IX

-360 - 360° 0° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PreFault

/Current]IA Fund. Current Fundamental Magnitude in Fault

State: Phase A0.00 – 40.00 In 0.0 In [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-FaultSimulation

/Current]IB Fund. Current Fundamental Magnitude in Fault

State: Phase B0.00 – 40.00 In 0.0 In [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-FaultSimulation

/Current]

660 www.eaton.com

Page 661: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

IC Fund. Current Fundamental Magnitude in Fault State: Phase C

0.00 – 40.00 In 0.0 In [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-FaultSimulation

/Current]IX meas Fund. Current Fundamental Magnitude in Fault

State: IX0.00 – 25.00 In 0.0 In [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-FaultSimulation

/Current]Angle IA Fund. Start Position respectively Start Angle of the

Current Phasor during Fault Phase:Phase A-360 - 360° 0° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-FaultSimulation

/Current]Angle IB Fund. Start Position respectively Start Angle of the

Current Phasor during Fault Phase:Phase B-360 - 360° 240° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-FaultSimulation

/Current]

www.eaton.com 661

Page 662: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Angle IC Fund. Start Position respectively Start Angle of the Current Phasor during Fault Phase:Phase C

-360 - 360° 120° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-FaultSimulation

/Current]Angle IX meas Fund.

Start Position respectively Start Angle of the Current Phasor during Fault Phase: IX

-360 - 360° 0° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-FaultSimulation

/Current]IA Fund. Current Fundamental Magnitude during

Post phase: Phase A0.00 – 40.00 In 0.0 In [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PostFault

/Current]IB Fund. Current Fundamental Magnitude during

Post phase: Phase B0.00 – 40.00 In 0.0 In [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PostFault

/Current]

662 www.eaton.com

Page 663: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Parameter Description Setting Range Default Menu Path

IC Fund. Current Fundamental Magnitude during Post phase: Phase C

0.00 – 40.00 In 0.0 In [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PostFault

/Current]IX meas Fund. Current Fundamental Magnitude during

Post phase: IX0.00 – 25.00 In 0.0 In [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PostFault

/Current]Angle IA Fund. Start Position respectively Start Angle of the

Current Phasor during Post phase: Phase A-360 - 360° 0° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PostFault

/Current]Angle IB Fund. Start Position respectively Start Angle of the

Current Phasor during Post phase: Phase B-360 - 360° 240° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PostFault

/Current]

www.eaton.com 663

Page 664: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Parameter Description Setting Range Default Menu Path

Angle IC Fund. Start Position respectively Start Angle of the Current Phasor during Post phase: Phase C

-360 - 360° 120° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PostFault

/Current]Angle IX meas Fund.

Start Position respectively Start Angle of the Current Phasor during Post phase: IX

-360 - 360° 0° [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Configuration

/t-PostFault

/Current]

States of the Inputs of the Failure Simulator

Name Description Assignment Via

ExBlo Module Input State: External Blocking [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Process]Ex ForcePost-I State of the module input:Force Post state.

Abort simulation.[Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Process]

664 www.eaton.com

Page 665: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Signals of the Failure Simulator (States of the Outputs)

Name Description

Running Signal: Measuring value simulation is running.State Signal: Wave generation states: 0=AdcNormal, 1=PreFault,

2=Fault, 3=Post, 4=InitReset.

Direct Commands of the Failure Simulator

Parameter Description Setting Range Default Menu Path

Start Simulation

Start Fault Simulation (Using the test parameters)

Inactive,

Active

Inactive [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Process]Stop Simulation Stop Fault Simulation (Using the test

parameters)Inactive,

Active

Inactive [Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/Process]

Failure Simulator Values

Value Description Default Size Menu Path

State Wave generation states: 0=AdcNormal, 1=PreFault, 2=Fault, 3=Post, 4=InitReset

L1 L2 L3 Normal L1 L2 L3 Normal,

t-PreFault,

t-FaultSimulation,

t-PostFault,

Init Res

[Service

/Test Mode (Prot inhibit)

/WARNING! Cont?

/Sine wave gen

/State]

www.eaton.com 665

Page 666: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Technical DataUse Copper conductors only, 75°C (167°F).Conductor size AWG 14 [2.5 mm].

Climatic Environmental ConditionsStorage Temperature: -30°C to +70°C (-22°F to 158°F)Operating Temperature: -20°C to +60°C (-4°F to 140°F)Permissible Humidity at Ann. Average: <75% rel. (on 56d up to 95% rel.)Permissible Installation Altitude: <2,000 m (6,561.67 ft) above sea level

If 4,000 m (13,123.35 ft) altitude applies, a changed classification of the operating and test voltages may be necessary.

Degree of Protection EN 60529

HMI Front Panel with Seal: IP54Rear Side Terminals: IP20

Routine TestInsulation Test Acc. to IEC60255-5: All tests to be carried out against ground and other input and output circuits.Aux. Voltage Supply, Digital Inputs, Current Measuring Inputs, Signal Relay Outputs:

2.5 kV (eff.) / 50 Hz

Voltage Measuring Inputs: 3.0 kV (eff.) / 50 HzAll Wire-Bound Communication Interfaces: 1.5 kV DC

HousingHousing B2: Height / Width 183 mm (7.205 in.) / 212.7 mm (8.374 in.)Housing Depth (Incl. Terminals): 208 mm (8.189 in.)Material, Housing: Aluminum extruded sectionMaterial, Front Panel: Aluminum/Foil frontMounting Position: Horizontal (±45° around the X-axis must be permitted)Weight: Approx. 4.2 kg (9.259 lb)

666 www.eaton.com

Page 667: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Current and Ground Current Measurement

Plug-in Connector with Integrated Short-Circuiter (Conventional Current Inputs)

Phase and Ground Current Inputs:

Nominal Currents: 1 A / 5 AMax. Measuring Range: Up to 40 x In (phase currents)

Up to 25 x In (ground current standard)Capacity:Overcurrent Proof:

4 x In/continuously30 x In / 10 s100 x In / 1 s250 x In / 10 ms (1 half-wave)

Power Consumption: Phase current inputs At In = 1 A S = 0.15 mVAAt In = 5 A S = 0.15 mVA

Ground current inputAt In = 1 A S = 0.35 mVA At In = 5 A S = 0.35 mVA

Sensitive Ground Current Inputs:

Nominal Currents: 1 A / 5 A with a special 50:0.025 core balance CTMax. Measuring Range: Up to 2.5 x InCapacity:Overcurrent Proof:

1.5 x In / continuously3.0 x In / 10 s10 x In / 1 s25 x In / 10 ms (1 half-wave)

Power Consumption: At In = 1 A S = 0.35 mVA At In = 5 A S = 0.35 mVA

Frequency Range: 50 Hz / 60 Hz ±10%Terminals:

Screws

Screw-type terminals with integrated short-circuiters (contacts)

M4, captive type acc. to VDEWConnection Cross Sections: 1 x or 2 x 2.5 mm² (2 x AWG 14) with wire end ferrule

1 x or 2 x 4.0 mm² (2 x AWG 12) with ring cable sleeve or cable sleeve1 x or 2 x 6 mm² (2 x AWG 10) with ring cable sleeve or cable sleeve

The current measuring board´s terminal blocks may be used as with 2 (double) conductors AWG 10,12,14 otherwise with single conductors only.

Voltage and Residual Voltage MeasurementNominal Voltages: 100 V/ 110 V/ 230 V/ 400 V (can be configured)Max. Measuring Range: 2 x nominal voltageContinuous Loading Capacity: 2 x nominal voltage (800 Vac) Power Consumption: at Vn = 100 V S = 0.1 mVA

at Vn = 110 V S = 0.1 mVAat Vn = 230 V S = 0.4 mVAat Vn = 400 V S = 1.0 mVA

Frequency Range: 50 Hz or 60 Hz ±10%Terminals: Screw-type terminals

www.eaton.com 667

Page 668: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Frequency MeasurementNominal Frequencies: 50 Hz / 60 Hz

Voltage SupplyAux. Voltage: 24 - 270 Vdc / 48 - 230 Vac (-20/+10%)Buffer Time in Case of Supply Failure: >= 50 ms at minimal aux. voltage

Interrupted communication is permitted.Max. Permissible Making Current: 18 A peak value for <0.25 ms

12 A peak value for <1 ms

The voltage supply must be protected by a fuse of:• 2,5 A time-lag miniature fuse 5 x 20 mm (approx. 0.2 x 0.8 in.) according to IEC 60127• 3,5 A time-lag miniature fuse 6,3 x 32 mm (approx. 0.25 x 1.25 in.) according to UL 248-14

Power ConsumptionPower Supply Range: Power consumption

in Idle ModeMax. Power Consumption

24 - 270 Vdc: Approx. 7 W Approx.13 W48 - 230 Vac(For Frequencies of 50-60 Hz):

Approx. 7 VA Approx.13 VA

DisplayDisplay Type: LCD with LED background illuminationResolution - Graphics Display: 128 x 64 pixel

LED - Type: Two colored: red / greenNumber of LEDs, Housing B2: 15

Front Interface RS232Baud Rates: 115,200 BaudHandshake: RTS and CTSConnection: 9-pole D-Sub plug

Real Time ClockRunning Reserve of the Real Time Clock:

1 year min.

Digital InputsMax. Input Voltage: 300 Vdc / 259 VacInput Current: <4 mAReaction Time: <20 msDrop-out Time: <30 ms

668 www.eaton.com

Page 669: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

(Safe State of the Digital Inputs)

Switching Thresholds: Un =24 Vdc, 48 Vdc, 60 Vdc,110 Vac / dc, 230 Vac / dc

Un = 24 VdcSwitching Threshold 1 ON:Switching Threshold 1 OFF:

Min. 19.2 VdcMax. 9.6 Vdc

Un = 48 V / 60VdcSwitching Threshold 2 ON:Switching Threshold 2 OFF:

Min. 42.6 VdcMax. 21.3 Vdc

Un = 110 / 120 Vac / dcSwitching Threshold 3 ON:Switching Threshold 3 OFF:

Min. 88.0 Vdc / 88.0 VacMax. 44.0 Vdc / 44.0 Vac

Un = 230 / 240 Vac / dcSwitching Threshold 4 ON:Switching Threshold 4 OFF:

Min. 184 Vdc / 184 VacMax. 92 Vdc / 92 Vac

Terminals: Screw-type terminal

Relay OutputsContinuous Current: 5 A ac / dcMax. Make Current: 25 A ac / 25 A dc for 4 s

30 A / 230Vac according to ANSI IEEE Std C37.90-200530 A / 250Vdc according to ANSI IEEE Std C37.90-2005

Max. Breaking Current: 5 A ac up to 240 Vac5 A dc up to 30 V (resistive)0.3 A dc at 250 V (resistive)

Max. Switching Voltage: 250 V ac / 250 VdcSwitching Capacity: 1,250 VAContact Type: Form C or normally open contactTerminals: Screw-type terminals

Supervision Contact (SC)Continuous Current: 5 A ac / dcMax. Switch-on Current: 15 A ac / 15 A dc for 4 s Max. Breaking Current: 5 A ac up to 250 Vac

5 A dc up to 30 Vdc (resistive)0,25 A at 250 Vdc (resistive)

Max. Switching Voltage: 250 V ac / 250 VdcSwitching Capacity: 1,250 VAContact Type: Form C or normally open contactTerminals: Screw-type terminals

Time Synchronization IRIG-B00XNominal input voltage: 5 VConnection: Screw-type terminals (twisted pair)

www.eaton.com 669

Page 670: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Zone InterlockingOnly for Zone Interlock Tripping Outputs (Zone Interlock, semiconductor output): 5 Vdc, <2mA for connection to electronic inputs only.

Zone Out:Output voltage (High) 4.75 to 5.25 VdcOutput voltage (Low) 0.0 to +0.5 Vdc

Zone In:Nominal input voltage +5 VdcMax. input voltage +5.5 VdcSwitching threshold ON min. 4.0 VdcSwitching threshold OFF max. 1.5 Vdc

Galvanic isolation 2.5 kV ac (to ground and other IO)Connection: Screw-type terminals (twisted pair)

RS485*Master/Slave: SlaveConnection: 6 screw-clamping terminals RM 3.5 mm (138 MIL)

(terminating resistors internal)

The RS485 interface is realized via terminals. The communication cable has to be shielded. The shielding has to be fixed at the screw that is marked with the ground symbol (rear side of the device).

Fiber Optic*Master/Slave: SlaveConnection: ST-Plug

URTD-Interface*Connection: Versatile Link

*availability depends on device

Boot PhaseAfter switching on the power supply, the protection will be available in approximately 16 seconds. After approximately 97 seconds, the boot phase is completed (HMI and Communication initialized).

670 www.eaton.com

Page 671: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Standards

Approvals• UL-listed file: e217753

Design StandardsGeneric Standard EN 61000-6-2

EN 61000-6-3Product Standard IEC 60255-6

EN 50178 UL 508 (Industrial Control Equipment)CSA C22.2 No. 14-95 (Industrial Control Equipment)ANSI C37.90

High Voltage Tests (IEC 60255-6)High Frequency Interference TestIEC 60255-22-1Class 3

Within one circuit

Circuit to ground

Circuit to circuit

1 kV/2 s

2.5 kV/2 s

2.5 kV/2 s

Insulation Voltage TestIEC 60255-5EN 50178

All circuits to other circuits and exposed conductive parts

Except interfaces

Voltage measuring input

2.5 kV (eff.)/50Hz, 1 min.

1.5 kV DC, 1 min.

3 kV (eff.)/50 Hz, 1 min.

Impulse Voltage TestIEC 60255-5 5 kV/0.5J, 1.2/50 µs

EMC Immunity Tests

Fast Transient Disturbance Immunity Test (Burst)IEC 60255-22-4IEC 61000-4-4Class 4ANSI C37.90.1

Power supply, mains inputs

Other in- and outputs

±4 kV, 2.5 kHz

±2 kV, 5 kHz (coupling network)±4 kV, 2.5 kHz (coupling clamp)

Surge Immunity TestIEC 61000-4-5Class 4

Within one circuit

Circuit to ground

2 kV

4 kV

Class 3 Communication cables to ground 2 kV

www.eaton.com 671

Page 672: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Electrical Discharge Immunity TestIEC 60255-22-2IEC 61000-4-2Class 3

Air discharge

Contact discharge

8 kV

6 kVRadiated Radio Frequency Electromagnetic Field Immunity TestIEC 61000-4-3Class XANSI C37.90.2

26 MHz – 80 MHz80 MHz – 1 GHz1 GHz – 3 GHz

10 V/m35 V/m10 V/m

Immunity to Conducted Disturbances Induced by Radio Frequency FieldsIEC 61000-4-6Class 3

10 V

Power Frequency Magnetic Field Immunity TestIEC 61000-4-8Class 4

Continuous

3 sec

30 A/m

300 A/m

EMC Emission Tests

Radio Interference Suppression TestIEC/CISPR11 Limit value class B

Radio Interference Radiation TestIEC/CISPR11 Limit value class B

Environmental Tests

Classification:IEC 60068-1 Climatic

Classification

20/060/56

IEC 60721-3-1 Classification of ambient conditions (Storage)

1K5/1B1/1C1L/1S1/1M2but min. -30°C (-22°F)

IEC 60721-3-2 Classification of ambient conditions (Transportation)

2K4/2B1/2C1/2S1/2M2but min. -30°C (-22°F)

IEC 60721-3-3 Classification of ambient conditions (Stationary use at weather protected locations)

3K6/3B1/3C1/3S1/3M2 but min. -20°C (-4°F) /max 60°C (140°F)

Test Ad: ColdIEC 60068-2-1 Temperature

Test duration-20°C (-4°F)16 h

Test Bd: Dry HeatIEC 60068-2-2 Temperature

Relative humidityTest duration

60°C (140°F)<50%72 h

Test Cab: Damp Heat (Steady State)IEC 60068-2-78 Temperature

Relative humidityTest duration

40°C (104°F)93%56 d

672 www.eaton.com

Page 673: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Test Db: Damp Heat (Cyclic)IEC 60068-2-30 Temperature

Relative humidityCycles (12 + 12-hour)

60°C (140°F)95%2

Mechanical TestsTest Fc: Vibration Response TestIEC 60068-2-6IEC 60255-21-1Class 1

(10 Hz – 59 Hz)Displacement

(59Hz – 150Hz)Acceleration

Number of cycles in each axis

0.0014 in. (0.035 mm)

0.5 gn

1

Test Fc: Vibration Endurance TestIEC 60068-2-6IEC 60255-21-1Class 1

(10 Hz – 150 Hz)Acceleration

Number of cycles in each axis

1.0 gn

20

Test Ea: Shock TestIEC 60068-2-27IEC 60255-21-2Class 1

Shock response test 5 gn, 11 ms, 3 impulses in each direction

Shock resistance test 15 gn, 11 ms, 3 impulses in each direction

Test Eb: Shock Endurance TestIEC 60068-2-29IEC 60255-21-2Class 1

Shock endurance test 10 gn, 16 ms, 1,000 impulses in each direction

Test Fe: Earthquake TestIEC 60068-3-3KTA 3503IEC 60255-21-3

Single axis earthquake vibration test 3 – 7 Hz: Horizontal 0.394 in. (10 mm), 1 cycle each axis

Class 2 7 – 35 Hz Horizontal: 2 gn, 1 cycle each axis

www.eaton.com 673

Page 674: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Specifications

Specifications of the Real Time Clock

Resolution: 1 msTolerance: <1 minute / month (+20°C [68°F])

Specifications of the Measured Value Acquisition

Phase and Ground Current Measuring

Frequency Range: 50 Hz / 60 Hz ± 10%Accuracy: Class 0.5Amplitude Error if I < In: ±0.5% of the rated valueAmplitude Error if I > In: ±0.5% of the measured valueAmplitude Error if I > 2 In: ±1.0% of the measured valueResolution: 0.01 AHarmonics: Up to 20% 3rd harmonic ±2%

Up to 20% 5th harmonic ±2%Frequency Influence: <±2% / Hz in the range of ±5 Hz of the configured nominal frequencyTemperature Influence: <±1% within the range of 0°C to +60°C (+32°F to +140°F)

Phase-to-ground and Residual Voltage Measurement

Nominal voltage (Vn): 60 ... 600 V in 1 V stepsMax measuring range: 2 x nominal value (Vn)Frequency range: 50 Hz or 60 Hz ±10%Precision: Class 0,5Amplitude error for V<Vn (measured): ±0.5% of the rated valueAmplitude error for V<Vn (calculated): ±1.0% of the rated valueAmplitude error for V>Vn (measured): ±0.5% of the measured valueAmplitude error for V>Vn (calculated): ±1.0% of the calculated valueResolution: 0.1 VHarmonics: up to 20% 3rd harmonic ±1%, up to 20% 5th harmonic ±1%Frequency influence: <±2% / Hz in the range of ±5 Hz of the configured nominal frequencyTemperature influence: <±1% within the range of 0°C up to +55°C

Frequency Measurement

Nominal frequency: 50 Hz / 60 HzPrecision: ±0.05% of fn within the range of 40-70 Hz at voltages >50 VVoltage dependency: frequency acquisition of 5 V – 800 V

674 www.eaton.com

Page 675: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Protection Elements Accuracy

The tripping delay relates to the time between alarm and trip. The accuracy of the operating time relates to the time between when the measured value has exceeded the threshold until the protection element is picked-up.

Overcurrent Protection Elements 50P[x], 51P/[x]and directional Overcurrent Protection 67P[x]

Accuracy

Pickup ±1.5% of the setting value resp. 1% x In.Dropout Ratio 97% or 0.5% x Int DEFT

±1% resp. ±10 msOperating Time

Starting from I higher than 1.1 x I>

<35 ms

Disengaging Time <45 mst-Multiplier ±5%

IEC NINV

IEC VINV

IEC EINV

IEC LINV

ANSI MINV

ANSI VINV

ANSI EINV

Flat

It

I2t

I4t Reset Mode ±1% resp. ±10 ms

IEC NINV

IEC VINV

IEC EINV

IEC LINV 5%

ANSI MINV

ANSI VINV

ANSI EINV

Flat

It

I2t

I4t

www.eaton.com 675

Page 676: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Voltage restraint 51V[x] AccuracyPickup ±1.5% of the setting value resp. 1% x In.Dropout Ratio 97% or 0.5% x InOperating Time

Starting from I higher than 1.1 x I>

<35 ms

Disengaging Time <45 mst-Multiplier ±5%

IEC NINV

IEC VINV

IEC EINV

IEC LINV

ANSI MINV

ANSI VINV

ANSI EINV

Flat

It

I2t

I4t Reset Mode ±1% resp. ±10 ms

IEC NINV

IEC VINV

IEC EINV

IEC LINV 5%

ANSI MINV

ANSI VINV

ANSI EINV

Flat

It

I2t

I4t

Ground Current Elements: 50X[x], 50R[x], 51X[x], 51R[x] and directional Ground Current Protection 67X[x], 67R[x]

Accuracy

Pickup (measured ground current)

Pickup (calculated ground current)

±1.5% of the setting value, Resp. 1% x In

±2.0% of the setting value, Resp. 1.5% x InDropout Ratio 97% or 0.5% x Int DEFT

±1% resp. ±10 ms

676 www.eaton.com

Page 677: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Operating Time

Starting from IE higher than 1.1 x IE>

<35 ms

Disengaging Time <45 mst-Multiplier ±5%

IEC NINV

IEC VINV

IEC EINV

IEC LINV

ANSI MINV

ANSI VINV

ANSI EINV

Flat

It

I2t

I4t Reset Mode ±1% resp. ±10 ms

IEC characteristics

IEC NINV

IEC VINV

IEC EINV

IEC LINV5%

Reset curves if ANSI characteristics

ANSI MINV

ANSI VINV

ANSI EINV

Flat

It

I2t

I4t

Phase under- and phase overvoltage 27M[x]/59M[x] AccuracyPickup ±1.5% of the setting value

Resp. 1% x VnDropout Ratio 97% or 0.5% x Vnt DEFT

±1% resp. ±10 msOperating Time

Starting from V higher/lower than 1.1 x V> or V<

<35 ms

Disengaging Time <45 ms

www.eaton.com 677

Page 678: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Aux. under- and phase overvoltage and neutral overvoltage 27A[x]/59A[x]/59N[x]

Accuracy

Pickup ±1.5% of the setting value

Resp. 1% x VnDropout Ratio 97% or 0.5% x Vnt DEFT

±1% resp. ±10 msOperating Time

Starting from VG or VX higher than 1.1 x VG> or VX>

<35 ms

Disengaging Time <45 ms

Current unbalance: 46[x] AccuracyThreshold ±2% of the setting value resp.1% InI2/I1 ≥ 0.1 x In ±1%t DEFT

±1% resp. ±10 msOperating Time

Starting from I2/I1 ≥ 1.1 x In

<60 ms

Disengaging Time <40 ms

Voltage unbalance: 47[x] AccuracyThreshold ±2% of the setting value resp.1% VnV2/V1 ≥ 0.1 x Vn ±1%t DEFT

±1% resp. ±10 msOperating Time

Starting from V2/V1 ≥ 1.1 x Vn

<60 ms

Disengaging Time <40 ms

Frequency Protection 81O[x] AccuracyThreshold 10 mHz at fnDropout ratio 99.95%

or 0.05% x fnt ±1% resp. ±10 msOperating time

Starting from f higher than f>+0.02 Hz

40-50Hz <60 ms50-70Hz <50 ms

Disengaging time 40-50Hz <85 ms 50-70Hz <75 ms

Frequency Protection 81U[x] AccuracyThreshold 10 mHz at fnt ±1% resp. ±10 msDropout ratio 100.05% or 0.05% x fnOperating time

Starting from f lower than f<-0.02 Hz

40-50Hz <60 ms50-70Hz <50 ms

Release time 40-50Hz <85 ms50-70Hz <75 ms

V Block f ±1.5% of the setting value resp. 1% x VnDropout ratio 103%

or 0.5% x Vn

678 www.eaton.com

Page 679: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Rate of Change of Frequency df/dt AccuracyThreshold 100 mHz per Secondt ±1% resp. ±10 msOperating time <40 ms

Disengaging time <40 ms

Rate of Change of Frequency Df/Dt AccuracyThreshold 100 mHz per Secondt ±1% resp. ±10 msOperating time <40 ms

Disengaging time <40 ms

Vector surge 87V AccuracyThreshold ±0,5° [1-30°] at Vn and fnOperating time <40 ms

PQ-protection 32[x]/32V[x] AccuracyThreshold ±3% or ±1.5% Snt ±1% resp. ±10 msOperating time 75 msDisengaging time 75 msDropout Ratio 97% for P>/Q> and 103% for P</Q<

PF-55D/PF-55A - Power Factor AccuracyThreshold ± 0.01 (absolute)Operating time <120 ms

AR – Auto Reclosing Accuracyt-ManualCloseBlock ±1% resp. ±10 mst-Lock2Ready ±1% resp. ±10 mst-Run2Ready ±1% resp. ±10 mst-Block2Ready ±1% resp. ±10 mst-Brk CLOSE Cmd ±1% resp. ±10 mst-sync_AR ±1% resp. ±10 mst-AR Supervision ±1% resp. ±10 ms

Sync - Sync-Check AccuracyOperating time Max. 300 mst-MaxBrkCloseDelay ±1% resp. ±10 mst-MaxSyncSuperv ±1% resp. ±10 msMinLiveBusVoltage ±1.5% of the setting value Resp. 1% x VnMaxDeadBusVoltage ±1.5% of the setting value Resp. 1% x VnMinLiveLineVoltage ±1.5% of the setting value Resp. 1% x VnMaxDeadLineVoltage ±1.5% of the setting value Resp. 1% x Vnt-VoltDead ±1% resp. ±10 msMaxVoltageDiff ±1.5% of the setting value Resp. 1% x Vn, may be

exceeded when open delta is configuredMaxSlipFrequency 10 mHz at fnMaxAngleDiff ±1°

SOTF – Switch onto fault AccuracyOperating time <35 msI< ±1.5% of the setting value resp.1% x Int-enable ±1% resp. ±10 ms

www.eaton.com 679

Page 680: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

CLPU – Cold load pickup AccuracyOperating time <35 mst-Load OFF ±1% resp. ±10 mst-Max Block ±1% resp. ±10 msI< ±1.5% of the setting value resp.1% x In

Breaker Failure Protection 50BF Accuracy I-BF> ±1.5% of the setting value resp.1% x Int-BF ±1% resp. ±10 ms

Operating Time

Starting from I Higher than 1.3 x I-BF>

<40 ms

Disengaging Time <40 ms

Trip Circuit Monitoring TCM Accuracyt-TCM ±1% resp. ±10 ms

LOP - loss of potential Accuracyt-Pickup ±1% resp. ±10 ms

Current Transformer Supervision CTS AccuracyΔI ±2% of the setting value resp. 1.5% InDropout Ratio 94%Pickup delay ±1% resp. ± 10 ms

680 www.eaton.com

Page 681: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Appendix

The following terms, abbreviations, and acronyms are used in this manual. Please refer to this section for their meanings / definitions.

A Ampere(s), Amp(s)AC Alternating currentA/D Analog to digitalAck. AcknowledgeAMP Ampere(s), Amp(s)AND Logical gate (The output becomes true if all Input signals are true.)ANG AngleANSI American National Standards InstituteAR Automatic reclosureAUX AuxiliaryAVG, avg AverageAWG American wire gaugeBF Breaker failureBFI Breaker failure initiateBKR, bkr BreakerBlo Blocking(s)°C Degrees Celsiuscalc CalculatedCB Circuit breaker, BreakerCD Compact diskChar Curve shapeCHK CheckCHNL ChannelCmd. CommandCMND CommandCMN Common inputCOM Common inputComm CommunicationCOMP Compensated, comparisonCONN ConnectionCONT Continuous, contactCPU Central processing unitCr. Counter(s)CRT, CRNT CurrentCSA Canadian Standards AssociationCT Control transformerCtrl. ControlCTS Current transformer supervisiond DayD/A Digital to analogD-Sub-Plug Communication interfaceDC, dc Direct currentDEFT Definite time characteristic (Tripping time does not depend on the height of the current.)DFLT DefaultDGNST DiagnosticsDI Digital InputDiagn. Diagnosis

www.eaton.com 681

Page 682: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Diagn Cr Diagnosis counter(s)DIFF DifferentialDIN Deutsche Industrie NormDIR, dir DirectionalDMD DemandDPO DropoutDSP Digital signal processordt Rate of changeEINV Extremely inverse tripping characteristicEMC Electromagnetic compatibilityEN Europäische Normerr. / Err. ErrorEVTcon Parameter determines if the residual voltage is measured or calculated.Ex ExternalExBlo External blocking(s)ExP External protectionEXT Extension, external°F Degrees FahrenheitF FieldFc Function (Enable or disable functionality = allow or disallow.)FIFO First in first outFIFO Principal First in first outFLA Full load currentFO Fiber opticFTP File transfer protocolfund Fundamental (ground wave)FWD ForwardG, g Generatorgn Acceleration of the earth in vertical direction (9.81 m/s2)GND GroundGPS Global positioning systemh HourHARM Harmonic / harmonicsHMI Human machine interface (Front of the protective relay)HTL Manufacturer internal product designationHTTP Hyper text transfer protocolHz HertzI Fault currentI CurrentI0 Zero current (symmetrical components), Zero sequence currentI1 Positive sequence current (symmetrical components)I2 Negative sequence current (symmetrical components)IA Phase A currentIAB Phase A minus B currentIB Phase B currentIBC Phase B minus C currentI-BF Tripping thresholdIC Phase C currentIC's Manufacturer internal product designationICA Phase C minus A currentID IdentificationIEC International Electrotechnical CommissionIED Intelligent electronic device

682 www.eaton.com

Page 683: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

IEEE Institute of Electrical and Electronics EngineersIG Ground current (not residual)IG Fault currentIgd Differential ground currentIGnom Nominal ground currentIH1 Fundamental harmonic (1st harmonic)IH2 2nd harmonicIINV Inversein. Inchincl. Include, includingInfo. InformationInterl. InterlockingINV Inverse characteristic (The tripping time will be calculated depending on the height of the

current)I/O Input / outputIOC Instantaneous overcurrentIOV Instantaneous overvoltageIR Calculated ground currentIRIG Input for time synchronization (Clock), Inter-range instrumentation groupISO International Standards OrganizationIT Thermal CharacteristicI2T Thermal CharacteristicI4T Thermal CharacteristicIUV Instantaneous undervoltageIX 4th measuring input of the current measuring assembly group (either ground or neutral current)J JoulekA Kiloamperekg KilogramkHz KilohertzkV Kilovolt(s)kVdc or kVDC Kilovolt(s) direct currentL1 Phase AL2 Phase BL3 Phase Cl/ln Ratio of current to nominal current.LED Light emitting diodelb-in Pound-inchLINV Long time inverse tripping characteristicLV Low voltagem MeterM MachinemA Milliampere(s), Milliamp(s)MAG MagnitudeMAN, man. Manual / manuallyMAX, max. Maximummeas MeasuredMIN, min. Minimummin. MinuteMINV Moderately Inverse Tripping CharacteristicMK Manufacturer Internal Product Designation Codemm MillimeterMMU Memory mapping unitMRT Minimum response time

www.eaton.com 683

Page 684: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

ms Milli-second(s)MTA Maximum torque angleMTR MotorMV Medium voltagemVA Milli volt amperes (Power)MVA Mega volt-ampere (total 3-phase)MVA A Mega volt-ampere (phase A)MVA B Mega volt-ampere (phase B)MVA C Mega volt-ampere (phase C)MVAR Mega Var (total 3-phase)MVAR A Mega Var (phase A)MVAR B Mega Var (phase B)MVAR C Mega Var (phase C)MVARH Mega Var-HourMW Megawatt(s) (total 3-phase)MW A Megawatt(s) (phase A)MW B Megawatt(s) (phase B)MW C Megawatt(s) (phase C)MWH Megawatt-Hour(s)N NeutralN/A, n/a Not applicableN.C. Not connectedNEG NegativeNINV Normal inverse tripping characteristicNm Newton-meterNo NumberN.O. Normal open (Contact)NOM, Nom. NominalNT Manufacturer internal product designation codeO OverOC, O/C OvercurrentO/P, Op, OUT OutputOV OvervoltageOVERFREQ Over-frequencyOVLD OverloadP PhasePara. ParameterPC Personal computerPCB Printed circuit boardPE Protected EarthPF Power factor (total 3-phase)PF A Power factor (phase A)PF B Power factor (phase B)PF C Power factor (phase C)Ph PhasePOS PositivePRESS PressurePRI, pri PrimaryPROT, Prot Protection Module (Master Module), protectionPS1 Parameter set 1PS2 Parameter set 2PS3 Parameter set 3PS4 Parameter set 4

684 www.eaton.com

Page 685: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

PSet Parameter setPSS Parameter set switch (Switching from one parameter set to another)pu Per unitPWM Pulse width modulatedPWR PowerR Resetrec. RecordREF Referencerel RelativeREM Remoteres ResetResetFct Reset functionREV ReverseRevData Review dataRMS Root mean squareRO Relay OutputRO1 1st Relay OutputRO2 2nd Relay OutputRO3 3rd Relay OutputRst ResetRTD Resistance-temperature detectorRX (Rx) Receive, receivers SecondS SensitiveSAT CT saturationSC Supervision contactSca SCADASCADA Communication module, supervisory control and data acquisitionsec Second(s)SEC, sec SecondarySENS SensitiveSEQ SequenceSig. SignalSNTP Simple network time protocolSRC SourceStartFct Start functionSTATS StatisticsSum SummationSUPERV SupervisionSW SoftwareSYNC Sync-check, SynchrocheckSYNCHCHK Sync-check, SynchrocheckSys. Systemt or t. Timet Tripping delayT Time, transformerTcmd Trip commandTCP Transmission control protocolTCP/IP Communication protocolTEMP, temp TemperatureTHD Total harmonic distortionTI Manufacturer internal product designation codeTOC Time overcurrent

www.eaton.com 685

Page 686: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

TOV Time overvoltageTRANS TransientTripCmd Trip commandTX (Tx) Transmit, transmittertxt TextUC UndercurrentUL Underwriters LaboratoriesUMZ DEFT (definite time tripping characteristic)URTD Universal resistance-temperature detectorUSB Universal serial busV VoltsV0 Zero sequence voltageV1 Positive sequence voltageV2 Negative sequence voltageVA Phase A voltageVAB Phase A to B voltageVac / V ac Volts alternating currentVAG Phase A to ground voltageVARH Var-hour voltageVB Phase B voltageVBA Phase B to A voltageVBG Phase B to ground voltageVC Phase C voltageVCA Phase C to A voltageVCG Phase C to ground voltageVdc / V dc Volts direct currentVDE Verband Deutscher ElektrotechnikVDEW Verband der ElektrizitätswirtschaftVE Residual voltageV/Hz Volts per HertzVINV Very inverse tripping characteristicVT Voltage transformerVTS Voltage transformer supervisionW Watt(s)WDC Watch dog contact (supervision contact)WDG WindingWH Watthourwww World wide webX ReactanceXCT 4th current measuring input (ground or neutral current)XInv Inverse characteristicZ Impedance, zone

686 www.eaton.com

Page 687: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Instantaneous Current Curves (Phase)Explanation:

www.eaton.com 687

t [s]

PickupI

1 100.01

0.1

1

10

100

1 100.01

0.1

1

10

100

tt

4040

300 s300 s

0.0 s0.0 s

0.010.01PickupI

DEFT

t = Tripping delay

I = Fault current

Pickup = If the pickup value is exceeded, the module/element starts to time out to trip.

Page 688: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Time Current Curves (PHASE)The following characteristics are available:

• NINV (IEC/XInv);• VINV (IEC/XInv);• LINV (IEC/XInv);• EINV (IEC/XInv);• MINV (ANSI/XInv);• VINV (ANSI/XInv);• EINV (ANSI/XInv);• Thermal Flat;• Therm Flat IT;• Therm Flat I2T; and• Therm Flat I4T.

Explanation:

688 www.eaton.com

t = Tripping delay

t-multiplier = Time multiplier/tripping characteristic factor

I = Fault current

Pickup = If the pickup value is exceeded, the module/element starts to time out to trip.

Page 689: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 689

t-multiplier

x * Pickup (Multiples of Pickup)

TripReset

t = 0.14 *t-multiplier [s]

Pickup -1I( )2 t = 0.14 *t-multiplier [s]

Pickup -1I( )0.02

t [s]

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

IEC NINV

Page 690: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

690 www.eaton.com

t [s]t-multiplier

t = 13.5 *t-multiplier [s]

Pickup -1I( )t = 13.5 *t-multiplier [s]

Pickup -1I( )2

TripReset

x * Pickup (Multiples of Pickup)

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

IEC VINV

Page 691: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 691

t [s] t-multiplier

t = 120 *t-multiplier [s]

Pickup -1I( )2

t = 120 *t-multiplier [s]

Pickup -1I( )

TripReset

x * Pickup (Multiples of Pickup)

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

IEC LINV

Page 692: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

692 www.eaton.com

t [s] t-multiplier

t = 80 *t-multiplier [s]

Pickup -1I( )2t = 80 *t-multiplier [s]

Pickup -1I( )2

TripReset

x * Pickup (Multiples of Pickup)

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

IEC EINV

Page 693: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 693

t [s] t-multiplier

t = 4.85 *t-multiplier [s]

Pickup -1I( )2 t = 0.0515 *t-multiplier [s]

Pickup -1I( )0.02 + 0.1140( )

TripReset

x * Pickup (Multiples of Pickup)

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

ANSI MINV

Page 694: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

694 www.eaton.com

t [s] t-multiplier

TripReset

x * Pickup (Multiples of Pickup)

t = 19.61 *t-multiplier [s]

Pickup -1I( )2 + 0.491( )t = 21.6 *t-multiplier [s]

Pickup -1I( )2

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

ANSI VINV

Page 695: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 695

t [s] t-multiplier

t = 29.1 *t-multiplier [s]

Pickup -1I( )2

TripReset

x * Pickup (Multiples of Pickup)

t = 28.2 *t-multiplier [s]

Pickup -1I( )2 + 0.1217( )

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

ANSI EINV

Page 696: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

696 www.eaton.com

t [s] t-multiplier

x * Pickup (Multiples of Pickup)

TripReset

t = 5*3 *t-multiplier [s]2

InI( )

0t = 5*1 *t-multiplier [s]

InI( )

0

2

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

Therm Flat

t = 45 *t-multiplier [s]

0.01 0.1 1 10 1000.01

0.1

1

10

100

1 103×

1 104×

TM[s]=

10

5

2

1.0

0.5

0.05

Page 697: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 697

t [s] t-multiplier

x * Pickup (Multiples of Pickup)

TripReset

t = 5*3 *t-multiplier [s]2

InI( )

0

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

IT

t = 5*3 *t-multiplier [s]1

InI( )

1

0.01 0.1 1 10 1000.01

0.1

1

10

100

1 103×

1 104×

TM[s]=

10

5

2

1.0

0.5

0.05

Page 698: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

698 www.eaton.com

0.01 0.1 1 10 1000.01

0.1

1

10

100

1 103×

1 104×

TM[s]=

10

5

2

1.0

0.50.05

t [s] t-multiplier

x * Pickup (Multiples of Pickup)

TripReset

t = 5*3 *t-multiplier [s]2

InI( )

0

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

I2T

t = 5*3 *t-multiplier [s]

InI( )

2

2

Page 699: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 699

t [s] t-multiplier

x * Pickup (Multiples of Pickup)

TripReset

t = 5*3 *t-multiplier [s]2

InI( )

0

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

I4T

t = 5*3 *t-multiplier [s]

InI( )

4

4

0.01 0.1 1 10 1000.01

0.1

1

10

100

1 103×

1 104×

TM[s]=

10

52

1.00.5

0.05

Page 700: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Instantaneous Current Curves (Ground Current Calculated)The following characteristics is available:

• DEFT (definite time).

Explanation:

The ground current can be measured either directly via a zero sequence transformer or detected by a residual connection. The ground current can alternatively be calculated from the phase currents; but this is only possible if the current transformers are Wye-connected.

700 www.eaton.com

t [s]

1 100.01

0.1

1

10

100

1 100.01

0.1

1

10

100

I/I>

tt

4020

300 s300 s

0.0 s0.0 s

0.010.01

PickupIR calc

PickupIR calc

DEFT

t = Tripping delay

IG = Fault current

Pickup = If the pickup value is exceeded, the module/element starts to time out to trip.

Page 701: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Instantaneous Current Curves (Ground Current Measured)

The following characteristics is available:

• DEFT (definite time).

Explanation:

The ground current can be measured either directly via a zero sequence transformer or detected by a residual connection. The ground current can alternatively be calculated from the phase currents; but this is only possible if the current transformers are Wye-connected.

www.eaton.com 701

t [s]

1 100.01

0.1

1

10

100

1 100.01

0.1

1

10

100

I/I>

tt

4020

300 s300 s

0.0 s0.0 s

0.010.01

PickupIX

PickupIX

DEFT

t = Tripping delay

IX = Fault current

Pickup = If the pickup value is exceeded, the module/element starts to time out to trip.

Page 702: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Time Current Curves (Ground Current)

The following characteristics are available:

• NINV (IEC/XInv);• VINV (IEC/XInv);• LINV (IEC/XInv);• EINV (IEC/XInv);• MINV (ANSI/XInv);• VINV (ANSI/XInv);• EINV (ANSI/XInv);• Thermal Flat;• Therm Flat IT;• Therm Flat I2T; and• Therm Flat I4T.

Explanation:

The ground current can be measured either directly via a zero sequence transformer or detected by a residual connection. The ground current can alternatively be calculated from the phase currents; but this is only possible if the current transformers are Wye-connected.

702 www.eaton.com

t = Tripping delay

t-multiplier = Time multiplier/tripping characteristic factor

IG = Fault current

Pickup = If the pickup value is exceeded, the module/element starts to time out to trip.

Page 703: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 703

t-multiplier

t = 0.14 *t-multiplier [s]

Pickup -1IG( )0.02

TripReset

t = 0.14 *t-multiplier [s]

Pickup -1IG( )2

x * Pickup (Multiples of Pickup)

t [s]

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

IEC NINV

Page 704: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

704 www.eaton.com

t [s]t-multiplier

TripReset

x * Pickup (Multiples of Pickup)

t = 13.5 *t-multiplier [s]

Pickup -1IG( )2

t = 13.5 *t-multiplier [s]

Pickup -1IG( )

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

IEC VINV

Page 705: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 705

t [s] t-multiplier

x * Pickup (Multiples of Pickup)

TripReset

t = 120 *t-multiplier [s]

Pickup -1IG( )t = 120 *t-multiplier [s]

-1IG( )2

Pickup

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

IEC LINV

Page 706: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

706 www.eaton.com

t [s] t-multiplier

x * Pickup (Multiples of Pickup)

TripReset

t = 80 *t-multiplier [s]

Pickup -1IG( )2 t = 80 *t-multiplier [s]

Pickup -1IG( )2

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

IEC EINV

Page 707: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 707

t [s] t-multiplier

x * Pickup (Multiples of Pickup)

t = 0.0515 *t-multiplier [s]

Pickup -1IG( )0.02 + 0.1140( )t = 4.85 *t-multiplier [s]

-1IG( )2

Pickup

TripReset

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

ANSI MINV

Page 708: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

708 www.eaton.com

t [s] t-multiplier

x * Pickup (Multiples of Pickup)

TripReset

t = 21.6 *t-multiplier [s]-1IG( )

2

Pickup

t = 19.61 *t-multiplier [s]

Pickup -1IG( )2 + 0.491( )

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

ANSI VINV

Page 709: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 709

t [s] t-multiplier

x * Pickup (Multiples of Pickup)

TripReset

t = 28.2 *t-multiplier [s]

Pickup -1IG( )2 + 0.1217( )t = 29.1 *t-multiplier [s]

-1IG( )2

Pickup

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

ANSI EINV

Page 710: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

710 www.eaton.com

t [s] t-multiplier

TripReset

t = 5*1 *t-multiplier [s]2

IG( )0

IGnom

x * Pickup (Multiples of Pickup)

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

Therm Flat

t = 5 *t-multiplier [s]

IGnomIG( )

0

t = 5 *t-multiplier [s]

0.01 0.1 1 10 1000.01

0.1

1

10

100

1 103×

1 104×

TM[s]=

10

5

2

1.0

0.5

0.05

Page 711: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 711

t [s] t-multiplier

TripReset

x * Pickup (Multiples of Pickup)

t = 5*1 *t-multiplier [s]2

IG( )0

IGnom

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

IT

t = 5*1 *t-multiplier [s]

IGnomIG( )

1

1

0.01 0.1 1 10 1000.01

0.1

1

10

100

1 103×

1 10×

TM[s]=

510

5 2

2

1.0

0.5

0.05

4

Page 712: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

712 www.eaton.com

t [s] t-multiplier

TripReset

x * Pickup (Multiples of Pickup)

t = 5*1 *t-multiplier [s]2

IG( )0

IGnom

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

I2T

t = 5*1 *t-multiplier [s]

IGnomIG( )

2

2

0.01 0.1 1 10 1000.01

0.1

1

10

100

1 103×

1 104×

TM[s]=

10

5

2

1.00.50.05

Page 713: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

www.eaton.com 713

t [s] t-multiplier

TripReset

x * Pickup (Multiples of Pickup)

t =

Notice!Various Reset Modes are available. Resetting via characteristic, delayed, and instantaneous.

I4T

t = 5*1 *t-multiplier [s]

IGnomIG( )

4

45*1 *t-multiplier [s]2

IGnomIG( )

0

0.01 0.1 1 10 1000.01

0.1

1

10

100

1 103×

1 104×

TM[s]=

10

5

2

1.0

0.50.05

Page 714: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Assignment ListThe »ASSIGNMENT LIST« below summarizes all module outputs (signals) and inputs (e.g.: states of the assignments).

Name Description

-.- No assignmentProt.Available Signal: Protection is available.Prot.Active Signal: ActiveProt.ExBlo Signal: External BlockingProt.Pickup Phase A Signal: General Pickup Phase AProt.Pickup Phase B Signal: General Pickup Phase BProt.Pickup Phase C Signal: General Pickup Phase CProt.Pickup IX or IR Signal: General Pickup - Ground FaultProt.Pickup Signal: General PickupProt.Trip Phase A Signal: General Trip Phase AProt.Trip Phase B Signal: General Trip Phase BProt.Trip Phase C Signal: General Trip Phase CProt.Trip IX or IR Signal: General Trip Ground FaultProt.Trip Signal: General TripProt.Res Fault a Mains No Signal: Resetting of fault number and number of grid faults.Prot.I dir fwd Signal: Phase current failure forward directionProt.I dir rev Signal: Phase current failure reverse directionProt.I dir n poss Signal: Phase fault - missing reference voltageProt.IR dir fwd Signal: IR Ground fault (calculated) forwardProt.IR dir rev Signal: IR Ground fault (calculated) reverse directionProt.IR dir n poss Signal: IR Ground fault (calculated) direction detection not

possible.Prot.IX dir fwd Signal: IX Ground fault (measured) forwardProt.IX dir rev Signal: IX Ground fault (measured) reverse directionProt.IX dir n poss Signal: IX Ground fault (measured) direction detection not

possible.Prot.ExBlo1-I Module Input State: External Blocking 1Prot.ExBlo2-I Module Input State: External Blocking 2Control.Local Switching Authority: LocalControl.Remote Switching Authority: RemoteBreaker.SI SingleContactInd Signal: The Position of the Switchgear is detected by one auxiliary

contact (pole) only. Thus indeterminate and disturbed Positions cannot be detected.

Breaker.Pos not CLOSE Signal: Pos not CLOSEBreaker.Pos CLOSE Signal: Breaker is in CLOSE-PositionBreaker.Pos OPEN Signal: Breaker is in OPEN-Position

714 www.eaton.com

Page 715: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Breaker.Pos Indeterm Signal: Breaker is in Indeterminate PositionBreaker.Pos Disturb Signal: Breaker Disturbed - Undefined Breaker Position. The feed-

back signals (Position Indicators) contradict themselves. After expiring of a supervision timer this signal becomes true.

Breaker.Ready Signal: Breaker is ready for operation.Breaker.CES succesf Command Execution Supervision: Switching command executed

successfully.Breaker.CES Disturbed Command Execution Supervision: Switching Command

unsuccessful. Switchgear in disturbed position.Breaker.CES SAuthority Command Execution Supervision: Switching Command not

executed. No switching authority.Breaker.CES SwitchgDir Command Execution Supervision: Switching Direction Control. A

switchgear that is already OPEN should be switched OPEN again (doubly).

Breaker.CES DoubleOperating Command Execution Supervision: A second switch command is in conflict with a pending one.

Breaker.CES CLOSE durg OPEN Cmd Command Execution Supervision: CLOSE Command during a pending OPEN Command.

Breaker.CES SG not ready Command Execution Supervision: Switchgear not ready.Breaker.CES Field Interl Command Execution Supervision: Switching Command not

executed because of field interlocking.Breaker.CES SyncTimeout Command Execution Supervision: Switching Command not

executed No Synchronization signal while t-sync was running.Breaker.Prot CLOSE Signal: CLOSE command issued by the Prot module.Breaker.TripCmd Signal: Trip CommandBreaker.Ack TripCmd Signal: Acknowledge Trip CommandBreaker.Bwear Slow Breaker Signal: Slow Breaker AlarmBreaker.Res Bwear Slow Breaker Signal: Resetting the slow breaker alarm.Breaker.CLOSE Cmd Signal: CLOSE command issued to the switchgear. Depending on

the setting the signal may include the CLOSE command of the Prot module.

Breaker.OPEN Cmd Signal: OPEN command issued to the switchgear. Depending on the setting the signal may include the OPEN command of the Prot module.

Breaker.CLOSE Cmd manual Signal: CLOSE Cmd manualBreaker.OPEN Cmd manual Signal: OPEN Cmd manualBreaker.CLOSE request Signal: Synchronous CLOSE requestBreaker.CinBkr-52a-I Feed-back signal of the Bkr. (52a)Breaker.CinBkr-52b-I Module Input State: Feed-back signal of the Bkr. (52b)Breaker.Ready-I Module Input State: Breaker ReadyBreaker.Sys-in-Sync-I State of the module input: This signals has to become true within

the synchronization time. If not, switching is unsuccessful.Breaker.Ack TripCmd-I State of the module input: Acknowledgment Signal (only for

automatic acknowledgment). Module input signal.Breaker.Interl CLOSE1-I State of the module input: Interlocking of the CLOSE command

www.eaton.com 715

Page 716: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Breaker.Interl CLOSE2-I State of the module input: Interlocking of the CLOSE commandBreaker.Interl CLOSE3-I State of the module input: Interlocking of the CLOSE commandBreaker.Interl OPEN1-I State of the module input: Interlocking of the OPEN commandBreaker.Interl OPEN2-I State of the module input: Interlocking of the OPEN commandBreaker.Interl OPEN3-I State of the module input: Interlocking of the OPEN commandBreaker.SC CLOSE-I State of the module input: Switching CLOSE Command, e.g.: the

state of the Logic or the state of the digital input.Breaker.SC OPEN-I State of the module input: Switching OPEN Command, e.g.: the

state of the Logic or the state of the digital input.Breaker.Operations Alarm Signal: Service Alarm, too many OperationsBreaker.Isum Intr trip: IA Signal: Maximum permissible Summation of the interrupting

(tripping) currents exceeded: IA.Breaker.Isum Intr trip: IB Signal: Maximum permissible Summation of the interrupting

(tripping) currents exceeded: IB.Breaker.Isum Intr trip: IC Signal: Maximum permissible Summation of the interrupting

(tripping) currents exceeded: IC.Breaker.Isum Intr trip Signal: Maximum permissible Summation of the interrupting

(tripping) currents exceeded in at least one phase.Breaker.Res TripCmdCr Signal: Resetting of the Counter: total number of trip commands.Breaker.Res Isum trip Signal: Reset summation of the tripping currents.Breaker.WearLevel Alarm Signal: Breaker Wear curve Alarm Level in %.Breaker.WearLevel Lockout Signal: Breaker Wear Curve Lockout Level in %.Breaker.Res Bwear Curve Signal: Res Bwear CurveBreaker.Isum Intr per hour Alarm Signal: Isum Intr per hour AlarmBreaker.Res Isum Intr per hour Alarm Signal: Res Isum Intr per hour Alarm50P[1].Active Signal: Active50P[1].ExBlo Signal: External Blocking50P[1].Rvs Blo Signal: Reverse Blocking50P[1].Blo TripCmd Signal: Trip Command blocked50P[1].ExBlo TripCmd Signal: External Blocking of the Trip Command50P[1].Pickup IA Signal: Pickup IA50P[1].Pickup IB Signal: Pickup IB50P[1].Pickup IC Signal: Pickup IC50P[1].Pickup Signal: Pickup50P[1].Trip Phase A Signal: General Trip Phase A50P[1].Trip Phase B Signal: General Trip Phase B50P[1].Trip Phase C Signal: General Trip Phase C50P[1].Trip Signal: Trip50P[1].TripCmd Signal: Trip Command50P[1].DefaultSet Signal: Default Parameter Set50P[1].AdaptSet 1 Signal: Adaptive Parameter 1

716 www.eaton.com

Page 717: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

50P[1].AdaptSet 2 Signal: Adaptive Parameter 250P[1].AdaptSet 3 Signal: Adaptive Parameter 350P[1].AdaptSet 4 Signal: Adaptive Parameter 450P[1].ExBlo1-I Module Input State: External Blocking 150P[1].ExBlo2-I Module Input State: External Blocking 250P[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command50P[1].Rvs Blo-I Module Input State: Reverse Blocking50P[1].AdaptSet1-I Module Input State: Adaptive Parameter150P[1].AdaptSet2-I Module Input State: Adaptive Parameter250P[1].AdaptSet3-I Module Input State: Adaptive Parameter350P[1].AdaptSet4-I Module Input State: Adaptive Parameter450P[2].Active Signal: Active50P[2].ExBlo Signal: External Blocking50P[2].Rvs Blo Signal: Reverse Blocking50P[2].Blo TripCmd Signal: Trip Command blocked50P[2].ExBlo TripCmd Signal: External Blocking of the Trip Command50P[2].Pickup IA Signal: Pickup IA50P[2].Pickup IB Signal: Pickup IB50P[2].Pickup IC Signal: Pickup IC50P[2].Pickup Signal: Pickup50P[2].Trip Phase A Signal: General Trip Phase A50P[2].Trip Phase B Signal: General Trip Phase B50P[2].Trip Phase C Signal: General Trip Phase C50P[2].Trip Signal: Trip50P[2].TripCmd Signal: Trip Command50P[2].DefaultSet Signal: Default Parameter Set50P[2].AdaptSet 1 Signal: Adaptive Parameter 150P[2].AdaptSet 2 Signal: Adaptive Parameter 250P[2].AdaptSet 3 Signal: Adaptive Parameter 350P[2].AdaptSet 4 Signal: Adaptive Parameter 450P[2].ExBlo1-I Module Input State: External Blocking 150P[2].ExBlo2-I Module Input State: External Blocking 250P[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command50P[2].Rvs Blo-I Module Input State: Reverse Blocking50P[2].AdaptSet1-I Module Input State: Adaptive Parameter 150P[2].AdaptSet2-I Module Input State: Adaptive Parameter 250P[2].AdaptSet3-I Module Input State: Adaptive Parameter 350P[2].AdaptSet4-I Module Input State: Adaptive Parameter 450P[3].Active Signal: Active

www.eaton.com 717

Page 718: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

50P[3].ExBlo Signal: External Blocking50P[3].Rvs Blo Signal: Reverse Blocking50P[3].Blo TripCmd Signal: Trip Command blocked50P[3].ExBlo TripCmd Signal: External Blocking of the Trip Command50P[3].Pickup IA Signal: Pickup IA50P[3].Pickup IB Signal: Pickup IB50P[3].Pickup IC Signal: Pickup IC50P[3].Pickup Signal: Pickup50P[3].Trip Phase A Signal: General Trip Phase A50P[3].Trip Phase B Signal: General Trip Phase B50P[3].Trip Phase C Signal: General Trip Phase C50P[3].Trip Signal: Trip50P[3].TripCmd Signal: Trip Command50P[3].DefaultSet Signal: Default Parameter Set50P[3].AdaptSet 1 Signal: Adaptive Parameter 150P[3].AdaptSet 2 Signal: Adaptive Parameter 250P[3].AdaptSet 3 Signal: Adaptive Parameter 350P[3].AdaptSet 4 Signal: Adaptive Parameter 450P[3].ExBlo1-I Module Input State: External Blocking 150P[3].ExBlo2-I Module Input State: External Blocking 250P[3].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command50P[3].Rvs Blo-I Module Input State: Reverse Blocking50P[3].AdaptSet1-I Module Input State: Adaptive Parameter 150P[3].AdaptSet2-I Module Input State: Adaptive Parameter 250P[3].AdaptSet3-I Module Input State: Adaptive Parameter 350P[3].AdaptSet4-I Module Input State: Adaptive Parameter 451P[1].Active Signal: Active51P[1].ExBlo Signal: External Blocking51P[1].Rvs Blo Signal: Reverse Blocking51P[1].Blo TripCmd Signal: Trip Command blocked51P[1].ExBlo TripCmd Signal: External Blocking of the Trip Command51P[1].Pickup IA Signal: Pickup IA51P[1].Pickup IB Signal: Pickup IB51P[1].Pickup IC Signal: Pickup IC51P[1].Pickup Signal: Pickup51P[1].Trip Phase A Signal: General Trip Phase A51P[1].Trip Phase B Signal: General Trip Phase B51P[1].Trip Phase C Signal: General Trip Phase C51P[1].Trip Signal: Trip

718 www.eaton.com

Page 719: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

51P[1].TripCmd Signal: Trip Command51P[1].DefaultSet Signal: Default Parameter Set51P[1].AdaptSet 1 Signal: Adaptive Parameter 151P[1].AdaptSet 2 Signal: Adaptive Parameter 251P[1].AdaptSet 3 Signal: Adaptive Parameter 351P[1].AdaptSet 4 Signal: Adaptive Parameter 451P[1].ExBlo1-I Module Input State: External Blocking 151P[1].ExBlo2-I Module Input State: External Blocking 251P[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command51P[1].Rvs Blo-I Module Input State: Reverse Blocking51P[1].AdaptSet1-I Module Input State: Adaptive Parameter 151P[1].AdaptSet2-I Module Input State: Adaptive Parameter 251P[1].AdaptSet3-I Module Input State: Adaptive Parameter 351P[1].AdaptSet4-I Module Input State: Adaptive Parameter 451P[2].Active Signal: Active51P[2].ExBlo Signal: External Blocking51P[2].Rvs Blo Signal: Reverse Blocking51P[2].Blo TripCmd Signal: Trip Command blocked51P[2].ExBlo TripCmd Signal: External Blocking of the Trip Command51P[2].Pickup IA Signal: Pickup IA51P[2].Pickup IB Signal: Pickup IB51P[2].Pickup IC Signal: Pickup IC51P[2].Pickup Signal: Pickup51P[2].Trip Phase A Signal: General Trip Phase A51P[2].Trip Phase B Signal: General Trip Phase B51P[2].Trip Phase C Signal: General Trip Phase C51P[2].Trip Signal: Trip51P[2].TripCmd Signal: Trip Command51P[2].DefaultSet Signal: Default Parameter Set51P[2].AdaptSet 1 Signal: Adaptive Parameter 151P[2].AdaptSet 2 Signal: Adaptive Parameter 251P[2].AdaptSet 3 Signal: Adaptive Parameter 351P[2].AdaptSet 4 Signal: Adaptive Parameter 451P[2].ExBlo1-I Module Input State: External Blocking 151P[2].ExBlo2-I Module Input State: External Blocking 251P[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command51P[2].Rvs Blo-I Module Input State: Reverse Blocking51P[2].AdaptSet1-I Module Input State: Adaptive Parameter 151P[2].AdaptSet2-I Module Input State: Adaptive Parameter 2

www.eaton.com 719

Page 720: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

51P[2].AdaptSet3-I Module Input State: Adaptive Parameter 351P[2].AdaptSet4-I Module Input State: Adaptive Parameter 451P[3].Active Signal: Active51P[3].ExBlo Signal: External Blocking51P[3].Rvs Blo Signal: Reverse Blocking51P[3].Blo TripCmd Signal: Trip Command blocked51P[3].ExBlo TripCmd Signal: External Blocking of the Trip Command51P[3].Pickup IA Signal: Pickup IA51P[3].Pickup IB Signal: Pickup IB51P[3].Pickup IC Signal: Pickup IC51P[3].Pickup Signal: Pickup51P[3].Trip Phase A Signal: General Trip Phase A51P[3].Trip Phase B Signal: General Trip Phase B51P[3].Trip Phase C Signal: General Trip Phase C51P[3].Trip Signal: Trip51P[3].TripCmd Signal: Trip Command51P[3].DefaultSet Signal: Default Parameter Set51P[3].AdaptSet 1 Signal: Adaptive Parameter 151P[3].AdaptSet 2 Signal: Adaptive Parameter 251P[3].AdaptSet 3 Signal: Adaptive Parameter 351P[3].AdaptSet 4 Signal: Adaptive Parameter 451P[3].ExBlo1-I Module Input State: External Blocking 151P[3].ExBlo2-I Module Input State: External Blocking 251P[3].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command51P[3].Rvs Blo-I Module Input State: Reverse Blocking51P[3].AdaptSet1-I Module Input State: Adaptive Parameter 151P[3].AdaptSet2-I Module Input State: Adaptive Parameter 251P[3].AdaptSet3-I Module Input State: Adaptive Parameter 351P[3].AdaptSet4-I Module Input State: Adaptive Parameter 450X[1].Active Signal: Active50X[1].ExBlo Signal: External Blocking50X[1].Rvs Blo Signal: Reverse Blocking50X[1].Blo TripCmd Signal: Trip Command blocked50X[1].ExBlo TripCmd Signal: External Blocking of the Trip Command50X[1].Pickup Signal: Pickup IX or IR50X[1].Trip Signal: Trip50X[1].TripCmd Signal: Trip Command50X[1].DefaultSet Signal: Default Parameter Set50X[1].AdaptSet 1 Signal: Adaptive Parameter 1

720 www.eaton.com

Page 721: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

50X[1].AdaptSet 2 Signal: Adaptive Parameter 250X[1].AdaptSet 3 Signal: Adaptive Parameter 350X[1].AdaptSet 4 Signal: Adaptive Parameter 450X[1].ExBlo1-I Module Input State: External Blocking 150X[1].ExBlo2-I Module Input State: External Blocking 250X[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command50X[1].Rvs Blo-I Module Input State: Reverse Blocking50X[1].AdaptSet1-I Module Input State: Adaptive Parameter 150X[1].AdaptSet2-I Module Input State: Adaptive Parameter 250X[1].AdaptSet3-I Module Input State: Adaptive Parameter 350X[1].AdaptSet4-I Module Input State: Adaptive Parameter 450X[2].Active Signal: Active50X[2].ExBlo Signal: External Blocking50X[2].Rvs Blo Signal: Reverse Blocking50X[2].Blo TripCmd Signal: Trip Command blocked50X[2].ExBlo TripCmd Signal: External Blocking of the Trip Command50X[2].Pickup Signal: Pickup IX or IR50X[2].Trip Signal: Trip50X[2].TripCmd Signal: Trip Command50X[2].DefaultSet Signal: Default Parameter Set50X[2].AdaptSet 1 Signal: Adaptive Parameter 150X[2].AdaptSet 2 Signal: Adaptive Parameter 250X[2].AdaptSet 3 Signal: Adaptive Parameter 350X[2].AdaptSet 4 Signal: Adaptive Parameter 450X[2].ExBlo1-I Module Input State: External Blocking 150X[2].ExBlo2-I Module Input State: External Blocking 250X[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command50X[2].Rvs Blo-I Module Input State: Reverse Blocking50X[2].AdaptSet1-I Module Input State: Adaptive Parameter 150X[2].AdaptSet2-I Module Input State: Adaptive Parameter 250X[2].AdaptSet3-I Module Input State: Adaptive Parameter 350X[2].AdaptSet4-I Module Input State: Adaptive Parameter 451X[1].Active Signal: Active51X[1].ExBlo Signal: External Blocking51X[1].Rvs Blo Signal: Reverse Blocking51X[1].Blo TripCmd Signal: Trip Command blocked51X[1].ExBlo TripCmd Signal: External Blocking of the Trip Command51X[1].Pickup Signal: Pickup IX or IR51X[1].Trip Signal: Trip

www.eaton.com 721

Page 722: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

51X[1].TripCmd Signal: Trip Command51X[1].DefaultSet Signal: Default Parameter Set51X[1].AdaptSet 1 Signal: Adaptive Parameter 151X[1].AdaptSet 2 Signal: Adaptive Parameter 251X[1].AdaptSet 3 Signal: Adaptive Parameter 351X[1].AdaptSet 4 Signal: Adaptive Parameter 451X[1].ExBlo1-I Module Input State: External Blocking 151X[1].ExBlo2-I Module Input State: External Blocking 251X[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command51X[1].Rvs Blo-I Module Input State: Reverse Blocking51X[1].AdaptSet1-I Module Input State: Adaptive Parameter 151X[1].AdaptSet2-I Module Input State: Adaptive Parameter 251X[1].AdaptSet3-I Module Input State: Adaptive Parameter 351X[1].AdaptSet4-I Module Input State: Adaptive Parameter 451X[2].Active Signal: Active51X[2].ExBlo Signal: External Blocking51X[2].Rvs Blo Signal: Reverse Blocking51X[2].Blo TripCmd Signal: Trip Command blocked51X[2].ExBlo TripCmd Signal: External Blocking of the Trip Command51X[2].Pickup Signal: Pickup IX or IR51X[2].Trip Signal: Trip51X[2].TripCmd Signal: Trip Command51X[2].DefaultSet Signal: Default Parameter Set51X[2].AdaptSet 1 Signal: Adaptive Parameter 151X[2].AdaptSet 2 Signal: Adaptive Parameter 251X[2].AdaptSet 3 Signal: Adaptive Parameter 351X[2].AdaptSet 4 Signal: Adaptive Parameter 451X[2].ExBlo1-I Module Input State: External Blocking 151X[2].ExBlo2-I Module Input State: External Blocking 251X[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command51X[2].Rvs Blo-I Module Input State: Reverse Blocking51X[2].AdaptSet1-I Module Input State: Adaptive Parameter 151X[2].AdaptSet2-I Module Input State: Adaptive Parameter 251X[2].AdaptSet3-I Module Input State: Adaptive Parameter 351X[2].AdaptSet4-I Module Input State: Adaptive Parameter 450R[1].Active Signal: Active50R[1].ExBlo Signal: External Blocking50R[1].Rvs Blo Signal: Reverse Blocking50R[1].Blo TripCmd Signal: Trip Command blocked

722 www.eaton.com

Page 723: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

50R[1].ExBlo TripCmd Signal: External Blocking of the Trip Command50R[1].Pickup Signal: Pickup IX or IR50R[1].Trip Signal: Trip50R[1].TripCmd Signal: Trip Command50R[1].DefaultSet Signal: Default Parameter Set50R[1].AdaptSet 1 Signal: Adaptive Parameter 150R[1].AdaptSet 2 Signal: Adaptive Parameter 250R[1].AdaptSet 3 Signal: Adaptive Parameter 350R[1].AdaptSet 4 Signal: Adaptive Parameter 450R[1].ExBlo1-I Module Input State: External Blocking 150R[1].ExBlo2-I Module Input State: External Blocking 250R[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command50R[1].Rvs Blo-I Module Input State: Reverse Blocking50R[1].AdaptSet1-I Module Input State: Adaptive Parameter 150R[1].AdaptSet2-I Module Input State: Adaptive Parameter 250R[1].AdaptSet3-I Module Input State: Adaptive Parameter 350R[1].AdaptSet4-I Module Input State: Adaptive Parameter 450R[2].Active Signal: Active50R[2].ExBlo Signal: External Blocking50R[2].Rvs Blo Signal: Reverse Blocking50R[2].Blo TripCmd Signal: Trip Command blocked50R[2].ExBlo TripCmd Signal: External Blocking of the Trip Command50R[2].Pickup Signal: Pickup IX or IR50R[2].Trip Signal: Trip50R[2].TripCmd Signal: Trip Command50R[2].DefaultSet Signal: Default Parameter Set50R[2].AdaptSet 1 Signal: Adaptive Parameter 150R[2].AdaptSet 2 Signal: Adaptive Parameter 250R[2].AdaptSet 3 Signal: Adaptive Parameter 350R[2].AdaptSet 4 Signal: Adaptive Parameter 450R[2].ExBlo1-I Module Input State: External Blocking 150R[2].ExBlo2-I Module Input State: External Blocking 250R[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command50R[2].Rvs Blo-I Module Input State: Reverse Blocking50R[2].AdaptSet1-I Module Input State: Adaptive Parameter 150R[2].AdaptSet2-I Module Input State: Adaptive Parameter 250R[2].AdaptSet3-I Module Input State: Adaptive Parameter 350R[2].AdaptSet4-I Module Input State: Adaptive Parameter 451R[1].Active Signal: Active

www.eaton.com 723

Page 724: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

51R[1].ExBlo Signal: External Blocking51R[1].Rvs Blo Signal: Reverse Blocking51R[1].Blo TripCmd Signal: Trip Command blocked51R[1].ExBlo TripCmd Signal: External Blocking of the Trip Command51R[1].Pickup Signal: Pickup IX or IR51R[1].Trip Signal: Trip51R[1].TripCmd Signal: Trip Command51R[1].DefaultSet Signal: Default Parameter Set51R[1].AdaptSet 1 Signal: Adaptive Parameter 151R[1].AdaptSet 2 Signal: Adaptive Parameter 251R[1].AdaptSet 3 Signal: Adaptive Parameter 351R[1].AdaptSet 4 Signal: Adaptive Parameter 451R[1].ExBlo1-I Module Input State: External Blocking 151R[1].ExBlo2-I Module Input State: External Blocking 251R[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command51R[1].Rvs Blo-I Module Input State: Reverse Blocking51R[1].AdaptSet1-I Module Input State: Adaptive Parameter 151R[1].AdaptSet2-I Module Input State: Adaptive Parameter 251R[1].AdaptSet3-I Module Input State: Adaptive Parameter 351R[1].AdaptSet4-I Module Input State: Adaptive Parameter 451R[2].Active Signal: Active51R[2].ExBlo Signal: External Blocking51R[2].Rvs Blo Signal: Reverse Blocking51R[2].Blo TripCmd Signal: Trip Command blocked51R[2].ExBlo TripCmd Signal: External Blocking of the Trip Command51R[2].Pickup Signal: Pickup IX or IR51R[2].Trip Signal: Trip51R[2].TripCmd Signal: Trip Command51R[2].DefaultSet Signal: Default Parameter Set51R[2].AdaptSet 1 Signal: Adaptive Parameter 151R[2].AdaptSet 2 Signal: Adaptive Parameter 251R[2].AdaptSet 3 Signal: Adaptive Parameter 351R[2].AdaptSet 4 Signal: Adaptive Parameter 451R[2].ExBlo1-I Module Input State: External Blocking 151R[2].ExBlo2-I Module Input State: External Blocking 251R[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command51R[2].Rvs Blo-I Module Input State: Reverse Blocking51R[2].AdaptSet1-I Module Input State: Adaptive Parameter 151R[2].AdaptSet2-I Module Input State: Adaptive Parameter 2

724 www.eaton.com

Page 725: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

51R[2].AdaptSet3-I Module Input State: Adaptive Parameter 351R[2].AdaptSet4-I Module Input State: Adaptive Parameter 427M[1].Active Signal: Active27M[1].ExBlo Signal: External Blocking27M[1].Blo TripCmd Signal: Trip Command blocked27M[1].ExBlo TripCmd Signal: External Blocking of the Trip Command27M[1].Pickup Phase A Signal: Pickup Phase A27M[1].Pickup Phase B Signal: Pickup Phase B27M[1].Pickup Phase C Signal: Pickup Phase C27M[1].Pickup Signal: Pickup Voltage Element27M[1].Trip Phase A Signal: General Trip Phase A27M[1].Trip Phase B Signal: General Trip Phase B27M[1].Trip Phase C Signal: General Trip Phase C27M[1].Trip Signal: Trip27M[1].TripCmd Signal: Trip Command27M[1].ExBlo1-I Module Input State: External Blocking 127M[1].ExBlo2-I Module Input State: External Blocking 227M[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command27M[2].Active Signal: Active27M[2].ExBlo Signal: External Blocking27M[2].Blo TripCmd Signal: Trip Command blocked27M[2].ExBlo TripCmd Signal: External Blocking of the Trip Command27M[2].Pickup Phase A Signal: Pickup Phase A27M[2].Pickup Phase B Signal: Pickup Phase B27M[2].Pickup Phase C Signal: Pickup Phase C27M[2].Pickup Signal: Pickup Voltage Element27M[2].Trip Phase A Signal: General Trip Phase A27M[2].Trip Phase B Signal: General Trip Phase B27M[2].Trip Phase C Signal: General Trip Phase C27M[2].Trip Signal: Trip27M[2].TripCmd Signal: Trip Command27M[2].ExBlo1-I Module Input State: External Blocking 127M[2].ExBlo2-I Module Input State: External Blocking 227M[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command59M[1].Active Signal: Active59M[1].ExBlo Signal: External Blocking59M[1].Blo TripCmd Signal: Trip Command blocked59M[1].ExBlo TripCmd Signal: External Blocking of the Trip Command59M[1].Pickup Phase A Signal: Pickup Phase A

www.eaton.com 725

Page 726: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

59M[1].Pickup Phase B Signal: Pickup Phase B59M[1].Pickup Phase C Signal: Pickup Phase C59M[1].Pickup Signal: Pickup Voltage Element59M[1].Trip Phase A Signal: General Trip Phase A59M[1].Trip Phase B Signal: General Trip Phase B59M[1].Trip Phase C Signal: General Trip Phase C59M[1].Trip Signal: Trip59M[1].TripCmd Signal: Trip Command59M[1].ExBlo1-I Module Input State: External Blocking 159M[1].ExBlo2-I Module Input State: External Blocking 259M[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command59M[2].Active Signal: Active59M[2].ExBlo Signal: External Blocking59M[2].Blo TripCmd Signal: Trip Command blocked59M[2].ExBlo TripCmd Signal: External Blocking of the Trip Command59M[2].Pickup Phase A Signal: Pickup Phase A59M[2].Pickup Phase B Signal: Pickup Phase B59M[2].Pickup Phase C Signal: Pickup Phase C59M[2].Pickup Signal: Pickup Voltage Element59M[2].Trip Phase A Signal: General Trip Phase A59M[2].Trip Phase B Signal: General Trip Phase B59M[2].Trip Phase C Signal: General Trip Phase C59M[2].Trip Signal: Trip59M[2].TripCmd Signal: Trip Command59M[2].ExBlo1-I Module Input State: External Blocking 159M[2].ExBlo2-I Module Input State: External Blocking 259M[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command27A[1].Active Signal: Active27A[1].ExBlo Signal: External Blocking27A[1].Blo TripCmd Signal: Trip Command blocked27A[1].ExBlo TripCmd Signal: External Blocking of the Trip Command27A[1].Pickup Signal: Pickup Residual Voltage Supervision-Element27A[1].Trip Signal: Trip27A[1].TripCmd Signal: Trip Command27A[1].ExBlo1-I Module Input State: External Blocking 127A[1].ExBlo2-I Module Input State: External Blocking 227A[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command27A[2].Active Signal: Active27A[2].ExBlo Signal: External Blocking

726 www.eaton.com

Page 727: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

27A[2].Blo TripCmd Signal: Trip Command blocked27A[2].ExBlo TripCmd Signal: External Blocking of the Trip Command27A[2].Pickup Signal: Pickup Residual Voltage Supervision-Element27A[2].Trip Signal: Trip27A[2].TripCmd Signal: Trip Command27A[2].ExBlo1-I Module Input State: External Blocking 127A[2].ExBlo2-I Module Input State: External Blocking 227A[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command59A[1].Active Signal: Active59A[1].ExBlo Signal: External Blocking59A[1].Blo TripCmd Signal: Trip Command blocked59A[1].ExBlo TripCmd Signal: External Blocking of the Trip Command59A[1].Pickup Signal: Pickup Residual Voltage Supervision-Element59A[1].Trip Signal: Trip59A[1].TripCmd Signal: Trip Command59A[1].ExBlo1-I Module Input State: External Blocking 159A[1].ExBlo2-I Module Input State: External Blocking 259A[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command59A[2].Active Signal: Active59A[2].ExBlo Signal: External Blocking59A[2].Blo TripCmd Signal: Trip Command blocked59A[2].ExBlo TripCmd Signal: External Blocking of the Trip Command59A[2].Pickup Signal: Pickup Residual Voltage Supervision-Element59A[2].Trip Signal: Trip59A[2].TripCmd Signal: Trip Command59A[2].ExBlo1-I Module Input State: External Blocking 159A[2].ExBlo2-I Module Input State: External Blocking 259A[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command59N[1].Active Signal: Active59N[1].ExBlo Signal: External Blocking59N[1].Blo TripCmd Signal: Trip Command blocked59N[1].ExBlo TripCmd Signal: External Blocking of the Trip Command59N[1].Pickup Signal: Pickup Residual Voltage Supervision-Element59N[1].Trip Signal: Trip59N[1].TripCmd Signal: Trip Command59N[1].ExBlo1-I Module Input State: External Blocking 159N[1].ExBlo2-I Module Input State: External Blocking 259N[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command59N[2].Active Signal: Active

www.eaton.com 727

Page 728: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

59N[2].ExBlo Signal: External Blocking59N[2].Blo TripCmd Signal: Trip Command blocked59N[2].ExBlo TripCmd Signal: External Blocking of the Trip Command59N[2].Pickup Signal: Pickup Residual Voltage Supervision-Element59N[2].Trip Signal: Trip59N[2].TripCmd Signal: Trip Command59N[2].ExBlo1-I Module Input State: External Blocking 159N[2].ExBlo2-I Module Input State: External Blocking 259N[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command46[1].Active Signal: Active46[1].ExBlo Signal: External Blocking46[1].Blo TripCmd Signal: Trip Command blocked46[1].ExBlo TripCmd Signal: External Blocking of the Trip Command46[1].Pickup Signal: Pickup Negative Sequence46[1].Trip Signal: Trip46[1].TripCmd Signal: Trip Command46[1].ExBlo1-I Module Input State: External Blocking 146[1].ExBlo2-I Module Input State: External Blocking 246[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command46[2].Active Signal: Active46[2].ExBlo Signal: External Blocking46[2].Blo TripCmd Signal: Trip Command blocked46[2].ExBlo TripCmd Signal: External Blocking of the Trip Command46[2].Pickup Signal: Pickup Negative Sequence46[2].Trip Signal: Trip46[2].TripCmd Signal: Trip Command46[2].ExBlo1-I Module Input State: External Blocking 146[2].ExBlo2-I Module Input State: External Blocking 246[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command47[1].Active Signal: Active47[1].ExBlo Signal: External Blocking47[1].Blo TripCmd Signal: Trip Command blocked47[1].ExBlo TripCmd Signal: External Blocking of the Trip Command47[1].Pickup Signal: Pickup Voltage Asymmetry47[1].Trip Signal: Trip47[1].TripCmd Signal: Trip Command47[1].ExBlo1-I Module Input State: External Blocking 147[1].ExBlo2-I Module Input State: External Blocking 247[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command

728 www.eaton.com

Page 729: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

47[2].Active Signal: Active47[2].ExBlo Signal: External Blocking47[2].Blo TripCmd Signal: Trip Command blocked47[2].ExBlo TripCmd Signal: External Blocking of the Trip Command47[2].Pickup Signal: Pickup Voltage Asymmetry47[2].Trip Signal: Trip47[2].TripCmd Signal: Trip Command47[2].ExBlo1-I Module Input State: External Blocking 147[2].ExBlo2-I Module Input State: External Blocking 247[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command81[1].Active Signal: Active81[1].ExBlo Signal: External Blocking81[1].Blo by V< Signal: Module is blocked by undervoltage.81[1].Blo TripCmd Signal: Trip Command blocked81[1].ExBlo TripCmd Signal: External Blocking of the Trip Command81[1].Pickup 81 Signal: Pickup Frequency Protection81[1].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-

change.81[1].Pickup Vector Surge Signal: Pickup Vector Surge81[1].Pickup Signal: Pickup Frequency Protection (collective signal)81[1].Trip 81 Signal: Frequency has exceeded the limit.81[1].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT81[1].Trip Vector Surge Signal: Trip delta phi81[1].Trip Signal: Trip Frequency Protection (collective signal)81[1].TripCmd Signal: Trip Command81[1].ExBlo1-I Module Input State: External Blocking 181[1].ExBlo2-I Module Input State: External Blocking 281[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command81[2].Active Signal: Active81[2].ExBlo Signal: External Blocking81[2].Blo by V< Signal: Module is blocked by undervoltage.81[2].Blo TripCmd Signal: Trip Command blocked81[2].ExBlo TripCmd Signal: External Blocking of the Trip Command81[2].Pickup 81 Signal: Pickup Frequency Protection81[2].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-

change.81[2].Pickup Vector Surge Signal: Pickup Vector Surge81[2].Pickup Signal: Pickup Frequency Protection (collective signal)81[2].Trip 81 Signal: Frequency has exceeded the limit.81[2].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT

www.eaton.com 729

Page 730: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

81[2].Trip Vector Surge Signal: Trip delta phi81[2].Trip Signal: Trip Frequency Protection (collective signal)81[2].TripCmd Signal: Trip Command81[2].ExBlo1-I Module Input State: External Blocking 181[2].ExBlo2-I Module Input State: External Blocking 281[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command81[3].Active Signal: Active81[3].ExBlo Signal: External Blocking81[3].Blo by V< Signal: Module is blocked by undervoltage.81[3].Blo TripCmd Signal: Trip Command blocked81[3].ExBlo TripCmd Signal: External Blocking of the Trip Command81[3].Pickup 81 Signal: Pickup Frequency Protection81[3].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-

change.81[3].Pickup Vector Surge Signal: Pickup Vector Surge81[3].Pickup Signal: Pickup Frequency Protection (collective signal)81[3].Trip 81 Signal: Frequency has exceeded the limit.81[3].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT81[3].Trip Vector Surge Signal: Trip delta phi81[3].Trip Signal: Trip Frequency Protection (collective signal)81[3].TripCmd Signal: Trip Command81[3].ExBlo1-I Module Input State: External Blocking 181[3].ExBlo2-I Module Input State: External Blocking 281[3].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command81[4].Active Signal: Active81[4].ExBlo Signal: External Blocking81[4].Blo by V< Signal: Module is blocked by undervoltage.81[4].Blo TripCmd Signal: Trip Command blocked81[4].ExBlo TripCmd Signal: External Blocking of the Trip Command81[4].Pickup 81 Signal: Pickup Frequency Protection81[4].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-

change.81[4].Pickup Vector Surge Signal: Pickup Vector Surge81[4].Pickup Signal: Pickup Frequency Protection (collective signal)81[4].Trip 81 Signal: Frequency has exceeded the limit.81[4].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT81[4].Trip Vector Surge Signal: Trip delta phi81[4].Trip Signal: Trip Frequency Protection (collective signal)81[4].TripCmd Signal: Trip Command81[4].ExBlo1-I Module Input State: External Blocking 1

730 www.eaton.com

Page 731: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

81[4].ExBlo2-I Module Input State: External Blocking 281[4].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command81[5].Active Signal: Active81[5].ExBlo Signal: External Blocking81[5].Blo by V< Signal: Module is blocked by undervoltage.81[5].Blo TripCmd Signal: Trip Command blocked81[5].ExBlo TripCmd Signal: External Blocking of the Trip Command81[5].Pickup 81 Signal: Pickup Frequency Protection81[5].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-

change.81[5].Pickup Vector Surge Signal: Pickup Vector Surge81[5].Pickup Signal: Pickup Frequency Protection (collective signal)81[5].Trip 81 Signal: Frequency has exceeded the limit.81[5].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT81[5].Trip Vector Surge Signal: Trip delta phi81[5].Trip Signal: Trip Frequency Protection (collective signal)81[5].TripCmd Signal: Trip Command81[5].ExBlo1-I Module Input State: External Blocking 181[5].ExBlo2-I Module Input State: External Blocking 281[5].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command81[6].Active Signal: Active81[6].ExBlo Signal: External Blocking81[6].Blo by V< Signal: Module is blocked by undervoltage.81[6].Blo TripCmd Signal: Trip Command blocked81[6].ExBlo TripCmd Signal: External Blocking of the Trip Command81[6].Pickup 81 Signal: Pickup Frequency Protection81[6].Pickup df/dt | DF/DT Pickup instantaneous or average value of the rate-of-frequency-

change.81[6].Pickup Vector Surge Signal: Pickup Vector Surge81[6].Pickup Signal: Pickup Frequency Protection (collective signal)81[6].Trip 81 Signal: Frequency has exceeded the limit.81[6].Trip df/dt | DF/DT Signal: Trip df/dt or DF/DT81[6].Trip Vector Surge Signal: Trip delta phi81[6].Trip Signal: Trip Frequency Protection (collective signal)81[6].TripCmd Signal: Trip Command81[6].ExBlo1-I Module Input State: External Blocking 181[6].ExBlo2-I Module Input State: External Blocking 281[6].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command32[1].Active Signal: Active32[1].ExBlo Signal: External Blocking

www.eaton.com 731

Page 732: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

32[1].Blo TripCmd Signal: Trip Command blocked32[1].ExBlo TripCmd Signal: External Blocking of the Trip Command32[1].Pickup Signal: Pickup Power Protection32[1].Trip Signal: Trip Power Protection32[1].TripCmd Signal: Trip Command32[1].ExBlo1-I Module Input State: External Blocking32[1].ExBlo2-I Module Input State: External Blocking32[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command32[2].Active Signal: Active32[2].ExBlo Signal: External Blocking32[2].Blo TripCmd Signal: Trip Command blocked32[2].ExBlo TripCmd Signal: External Blocking of the Trip Command32[2].Pickup Signal: Pickup Power Protection32[2].Trip Signal: Trip Power Protection32[2].TripCmd Signal: Trip Command32[2].ExBlo1-I Module Input State: External Blocking32[2].ExBlo2-I Module Input State: External Blocking32[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command32[3].Active Signal: Active32[3].ExBlo Signal: External Blocking32[3].Blo TripCmd Signal: Trip Command blocked32[3].ExBlo TripCmd Signal: External Blocking of the Trip Command32[3].Pickup Signal: Pickup Power Protection32[3].Trip Signal: Trip Power Protection32[3].TripCmd Signal: Trip Command32[3].ExBlo1-I Module Input State: External Blocking32[3].ExBlo2-I Module Input State: External Blocking32[3].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command32V[1].Active Signal: Active32V[1].ExBlo Signal: External Blocking32V[1].Blo TripCmd Signal: Trip Command blocked32V[1].ExBlo TripCmd Signal: External Blocking of the Trip Command32V[1].Pickup Signal: Pickup Power Protection32V[1].Trip Signal: Trip Power Protection32V[1].TripCmd Signal: Trip Command32V[1].ExBlo1-I Module Input State: External Blocking32V[1].ExBlo2-I Module Input State: External Blocking32V[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command32V[2].Active Signal: Active

732 www.eaton.com

Page 733: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

32V[2].ExBlo Signal: External Blocking32V[2].Blo TripCmd Signal: Trip Command blocked32V[2].ExBlo TripCmd Signal: External Blocking of the Trip Command32V[2].Pickup Signal: Pickup Power Protection32V[2].Trip Signal: Trip Power Protection32V[2].TripCmd Signal: Trip Command32V[2].ExBlo1-I Module Input State: External Blocking32V[2].ExBlo2-I Module Input State: External Blocking32V[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip Command32V[3].Active Signal: Active32V[3].ExBlo Signal: External Blocking32V[3].Blo TripCmd Signal: Trip Command blocked32V[3].ExBlo TripCmd Signal: External Blocking of the Trip Command32V[3].Pickup Signal: Pickup Power Protection32V[3].Trip Signal: Trip Power Protection32V[3].TripCmd Signal: Trip Command32V[3].ExBlo1-I Module Input State: External Blocking32V[3].ExBlo2-I Module Input State: External Blocking32V[3].ExBlo TripCmd-I Module Input State: External Blocking of the Trip CommandPF-55D[1].Active Signal: ActivePF-55D[1].ExBlo Signal: External BlockingPF-55D[1].Blo TripCmd Signal: Trip Command blockedPF-55D[1].ExBlo TripCmd Signal: External Blocking of the Trip CommandPF-55D[1].Pickup Signal: Pickup Power FactorPF-55D[1].Trip Signal: Trip Power FactorPF-55D[1].TripCmd Signal: Trip CommandPF-55D[1].Compensator Signal: Compensation SignalPF-55D[1].Impossible Signal: Pickup Power Factor ImpossiblePF-55D[1].ExBlo1-I Module Input State: External BlockingPF-55D[1].ExBlo2-I Module Input State: External BlockingPF-55D[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip CommandPF-55D[2].Active Signal: ActivePF-55D[2].ExBlo Signal: External BlockingPF-55D[2].Blo TripCmd Signal: Trip Command blockedPF-55D[2].ExBlo TripCmd Signal: External Blocking of the Trip CommandPF-55D[2].Pickup Signal: Pickup Power FactorPF-55D[2].Trip Signal: Trip Power FactorPF-55D[2].TripCmd Signal: Trip CommandPF-55D[2].Compensator Signal: Compensation Signal

www.eaton.com 733

Page 734: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

PF-55D[2].Impossible Signal: Pickup Power Factor ImpossiblePF-55D[2].ExBlo1-I Module Input State: External BlockingPF-55D[2].ExBlo2-I Module Input State: External BlockingPF-55D[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip CommandPF-55A[1].Active Signal: ActivePF-55A[1].ExBlo Signal: External BlockingPF-55A[1].Blo TripCmd Signal: Trip Command blockedPF-55A[1].ExBlo TripCmd Signal: External Blocking of the Trip CommandPF-55A[1].Pickup Signal: Pickup Power FactorPF-55A[1].Trip Signal: Trip Power FactorPF-55A[1].TripCmd Signal: Trip CommandPF-55A[1].Compensator Signal: Compensation SignalPF-55A[1].Impossible Signal: Pickup Power Factor ImpossiblePF-55A[1].ExBlo1-I Module Input State: External BlockingPF-55A[1].ExBlo2-I Module Input State: External BlockingPF-55A[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip CommandPF-55A[2].Active Signal: ActivePF-55A[2].ExBlo Signal: External BlockingPF-55A[2].Blo TripCmd Signal: Trip Command blockedPF-55A[2].ExBlo TripCmd Signal: External Blocking of the Trip CommandPF-55A[2].Pickup Signal: Pickup Power FactorPF-55A[2].Trip Signal: Trip Power FactorPF-55A[2].TripCmd Signal: Trip CommandPF-55A[2].Compensator Signal: Compensation SignalPF-55A[2].Impossible Signal: Pickup Power Factor ImpossiblePF-55A[2].ExBlo1-I Module Input State: External BlockingPF-55A[2].ExBlo2-I Module Input State: External BlockingPF-55A[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip CommandZI.Active Signal: ActiveZI.ExBlo Signal: External BlockingZI.Blo TripCmd Signal: Trip Command blockedZI.ExBlo TripCmd Signal: External Blocking of the Trip CommandZI.Bkr Blo Signal: Blocked by Breaker FailureZI.Phase Pickup Signal: Zone Interlocking Phase PickupZI.Phase Trip Signal: Zone Interlocking Phase Trip ZI.Ground Pickup Signal: Zone Interlocking Ground PickupZI.Ground Trip Signal: Zone Interlocking Ground Trip ZI.Pickup Signal: Pickup Zone InterlockingZI.Trip Signal: Zone Interlocking Trip

734 www.eaton.com

Page 735: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

ZI.TripCmd Signal: Zone Interlocking Trip CommandZI.Phase OUT Signal: Zone Interlocking Phase OUTZI.Ground OUT Signal: Zone Interlocking Ground OUTZI.OUT Signal: Zone Interlocking OUTZI.IN Signal: Zone Interlocking INZI.ExBlo1-I Module Input State: External Blocking1ZI.ExBlo2-I Module Input State: External Blocking2ZI.ExBlo TripCmd-I Module Input State: External Blocking of the Trip CommandZI.Bkr Blo-I Signal: Blocked by Breaker FailureSOTF.Active Signal: ActiveSOTF.ExBlo Signal: External BlockingSOTF.Rvs Blo Signal: Reverse BlockingSOTF.enabled Signal: Switch Onto Fault enabled. This Signal can be used to

modify Overcurrent Protection Settings.SOTF.I< Signal: No Load Current.SOTF.ExBlo1-I Module Input State: External BlockingSOTF.ExBlo2-I Module Input State: External BlockingSOTF.Rvs Blo-I Module Input State: Reverse BlockingSOTF.Ex Man CLOSE Cmd-I Module Input State: External manual breaker CLOSE command

(NOT for AR!)SOTF.Ext SOTF-I Module Input State: External Switch Onto Fault AlarmCLPU.Active Signal: ActiveCLPU.ExBlo Signal: External BlockingCLPU.Rvs Blo Signal: Reverse BlockingCLPU.enabled Signal: Cold Load enabledCLPU.detected Signal: Cold Load detectedCLPU.I< Signal: No Load Current.CLPU.Load Inrush Signal: Load InrushCLPU.Settle Time Signal: Settle TimeCLPU.ExBlo1-I Module Input State: External BlockingCLPU.ExBlo2-I Module Input State: External BlockingCLPU.Rvs Blo-I Module Input State: Reverse BlockingExP[1].Active Signal: ActiveExP[1].ExBlo Signal: External BlockingExP[1].Blo TripCmd Signal: Trip Command blockedExP[1].ExBlo TripCmd Signal: External Blocking of the Trip CommandExP[1].Alarm Signal: AlarmExP[1].Trip Signal: TripExP[1].TripCmd Signal: Trip CommandExP[1].ExBlo1-I Module Input State: External Blocking1

www.eaton.com 735

Page 736: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

ExP[1].ExBlo2-I Module Input State: External Blocking2ExP[1].ExBlo TripCmd-I Module Input State: External Blocking of the Trip CommandExP[1].Alarm-I Module Input State: AlarmExP[1].Trip-I Module Input State: TripExP[2].Active Signal: ActiveExP[2].ExBlo Signal: External BlockingExP[2].Blo TripCmd Signal: Trip Command blockedExP[2].ExBlo TripCmd Signal: External Blocking of the Trip CommandExP[2].Alarm Signal: AlarmExP[2].Trip Signal: TripExP[2].TripCmd Signal: Trip CommandExP[2].ExBlo1-I Module Input State: External Blocking1ExP[2].ExBlo2-I Module Input State: External Blocking2ExP[2].ExBlo TripCmd-I Module Input State: External Blocking of the Trip CommandExP[2].Alarm-I Module Input State: AlarmExP[2].Trip-I Module Input State: TripExP[3].Active Signal: ActiveExP[3].ExBlo Signal: External BlockingExP[3].Blo TripCmd Signal: Trip Command blockedExP[3].ExBlo TripCmd Signal: External Blocking of the Trip CommandExP[3].Alarm Signal: AlarmExP[3].Trip Signal: TripExP[3].TripCmd Signal: Trip CommandExP[3].ExBlo1-I Module Input State: External Blocking 1ExP[3].ExBlo2-I Module Input State: External Blocking 2ExP[3].ExBlo TripCmd-I Module Input State: External Blocking of the Trip CommandExP[3].Alarm-I Module Input State: AlarmExP[3].Trip-I Module Input State: TripExP[4].Active Signal: ActiveExP[4].ExBlo Signal: External BlockingExP[4].Blo TripCmd Signal: Trip Command blockedExP[4].ExBlo TripCmd Signal: External Blocking of the Trip CommandExP[4].Alarm Signal: AlarmExP[4].Trip Signal: TripExP[4].TripCmd Signal: Trip CommandExP[4].ExBlo1-I Module Input State: External Blocking 1ExP[4].ExBlo2-I Module Input State: External Blocking 2ExP[4].ExBlo TripCmd-I Module Input State: External Blocking of the Trip CommandExP[4].Alarm-I Module Input State: Alarm

736 www.eaton.com

Page 737: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

ExP[4].Trip-I Module Input State: TripBF.Active Signal: ActiveBF.ExBlo Signal: External BlockingBF.Pickup Signal: BF-Module Started (Pickup)BF.Trip Signal: Breaker Failure TripBF.Lockout Signal: LockoutBF.Res Lockout Signal: Reset LockoutBF.ExBlo1-I Module Input State: External Blocking 1BF.ExBlo2-I Module Input State: External Blocking 2BF.Trigger1 Module Input: Trigger that will start the BFBF.Trigger2 Module Input: Trigger that will start the BFBF.Trigger3 Module Input: Trigger that will start the BFTCM.Active Signal: ActiveTCM.ExBlo Signal: External BlockingTCM.Pickup Signal: Pickup Trip Circuit SupervisionTCM.Not Possible Not possible because no state indicator assigned to the breaker.TCM.CinBkr-52a-I Feed-back signal of the Bkr. (52a)TCM.CinBkr-52b-I Module Input State: Feed-back signal of the Bkr. (52b)TCM.ExBlo1-I Module Input State: External Blocking 1TCM.ExBlo2-I Module Input State: External Blocking 2CTS.Active Signal: ActiveCTS.ExBlo Signal: External BlockingCTS.Pickup Signal: Pickup Current Transformer Measuring Circuit SupervisionCTS.ExBlo1-I Module Input State: External Blocking 1CTS.ExBlo2-I Module Input State: External Blocking 2LOP.Active Signal: ActiveLOP.ExBlo Signal: External BlockingLOP.Pickup Signal: Pickup Loss of PotentialLOP.LOP Blo Signal: Loss of Potential blocks other elementsLOP.ExBlo1-I Module Input State: External Blocking 1LOP.ExBlo2-I Module Input State: External Blocking 2AR.Active Signal: ActiveAR.ExBlo Signal: External BlockingAR.Standby Signal: StandbyAR.t-Man Close Blo Signal: AR blocked after breaker was switched on manually. This

timer will be started if the breaker was switched on manually. While this timer is running, AR cannot be started.

AR.Ready Signal: Ready to shootAR.Running Signal: Auto Reclosing RunningAR.t-dead Signal: Dead time between trip and reclosure attempt

www.eaton.com 737

Page 738: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

AR.Bkr CLOSE Cmd Signal: Bkr. Switch ON (CLOSE) CommandAR.t-Run2Ready Signal: Examination Time: If the Breaker remains after a reclosure

attempt (shot) for the duration of this timer in the Closed position, the AR has been successful and the AR module returns into the ready state.

AR.Lock Signal: Auto Reclosure is locked outAR.t-Reset Lockout Signal: Delay Timer for resetting the AR lockout. The reset of the

AR lockout state will be delayed for this time after the reset signal (e.g digital input or Scada) has been detected.

AR.Blo Signal: Auto Reclosure is blockedAR.t-Blo Reset Signal: Delay Timer for resetting the AR blocking. The release

(de-blocking) of the AR will be delayed for this time, if there is no blocking signal anymore.

AR.successful Signal: Auto Reclosing successfulAR.failed Signal: Auto Reclosing FailureAR.t-AR Supervision Signal: AR SupervisionAR.Pre Shot Pre Shot ControlAR.Shot 1 Shot ControlAR.Shot 2 Shot ControlAR.Shot 3 Shot ControlAR.Shot 4 Shot ControlAR.Shot 5 Shot ControlAR.Shot 6 Shot ControlAR.Service Alarm 1 Signal: AR - Service Alarm 1, too many switching operationsAR.Service Alarm 2 Signal: AR - Service Alarm 2, too many switching operationsAR.Max Shots / h exceeded Signal: The maximum allowed number of shots per hour has been

exceeded.AR.Res Statistics Cr Signal: Reset all statistic AR counters: Total number of AR,

successful and unsuccessful no of AR. AR.Res Service Cr Signal: Reset the Service Counters for pickup and blocking.AR.Reset Lockout Signal: The AR Lockout has been reset via the panel.AR.Res Max Shots / h Signal: The Counter for the maximum allowed shots per hour has

been reset.AR.ExBlo1-I Module Input State: External Blocking 1AR.ExBlo2-I Module Input State: External Blocking 2AR.Ex Shot Inc-I Module input state: The AR Shot counter will be incremented by

this external Signal. This can be used for Zone Coordination (of upstream Auto Reclosure devices). Note: This parameter enables the functionality only. The assignment has to be set within the global parameters.

AR.Ex Lock-I Module input state: External AR lockout.AR.DI Reset Ex Lock-I Module input state: Resetting the lockout state of the AR (if the

resetting via digital inputs has been selected).

738 www.eaton.com

Page 739: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

AR.Comm Reset Ex Lock-I Module input state: Resetting the Lockout State of the AR by Communication.

Sync.Active Signal: ActiveSync.ExBlo Signal: External BlockingSync.LiveBus Signal: Live-Bus or Dead-Bus flag: 1=Live-Bus, 0=Dead-BusSync.LiveLine Signal: Live-Line or Dead-Line flag: 1=Live-Line, 0=Dead-LineSync.SynchronRunTiming Signal: Sync-checkRunTimingSync.SynchronFailed Signal: This signal indicates a failed synchronization. It is set for

5s when the breaker is still open after the Sync-check Run-timer has timed out.

Sync.SyncOverridden Signal:Sync-check is overridden because one of the Synchronism overriding conditions (DB/DL or ExtBypass) is met.

Sync.VDiffTooHigh Signal: Voltage difference between bus and line too high.Sync.SlipTooHigh Signal: Frequency difference (slip frequency) between bus and line

voltages too high.Sync.AngleDiffTooHigh Signal: Phase Angle difference between bus and line voltages too

high.Sync.Sys-in-Sync Signal: Bus and line voltages are in synchronism according to the

system synchronism criteria.Sync.In-Sync Allowed Signal: In-Sync AllowedSync.ExBlo1-I Module Input State: External Blocking 1Sync.ExBlo2-I Module Input State: External Blocking 2Sync.Bypass-I State of the module input: BypassSync.BkrCloseInitiate-I State of the module input: Breaker Close Initiate with synchronism

check from any control sources (e.g. HMI / SCADA). If the state of the assigned signal becomes true, a Breaker Close will be initiated (Trigger Source).

WiredInputs.52a M1-I State of the module input: Main 1 Breaker ClosedWiredInputs.52b M1-I State of the module input: Main 1 Breaker OpenWiredInputs.TOCa M1-I State of the module input: Main 1 Breaker Connected WiredInputs.43/10 M1-I State of the module input: Main 1 Breaker Selected To Trip WiredInputs.52a M2-I State of the module input: Main 2 Breaker ClosedWiredInputs.52b M2-I State of the module input: Main 2 Breaker OpenWiredInputs.TOCa M2-I State of the module input: Main 2 Breaker Connected WiredInputs.43/10 M2-I State of the module input: Main 2 Breaker Selected To TripWiredInputs.52a T -I State of the module input: Tie Breaker ClosedWiredInputs.52b T-I State of the module input: Tie Breaker OpenWiredInputs.TOCa T-I State of the module input: Tie Breaker Connected WiredInputs.43/10 T-I State of the module input: Tie Breaker Selected To TripWiredInputs.43 M-I State of the module input: System In ManualWiredInputs.43 A-I State of the module input: System in AutoWiredInputs.43 P1-I State of the module input: Preferred Source 1

www.eaton.com 739

Page 740: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

WiredInputs.43 P2-I State of the module input: Preferred Source 2WiredInputs.Bkr Trouble-I Breaker TroubleDI-8P X1.DI 1 Signal: Digital InputDI-8P X1.DI 2 Signal: Digital InputDI-8P X1.DI 3 Signal: Digital InputDI-8P X1.DI 4 Signal: Digital InputDI-8P X1.DI 5 Signal: Digital InputDI-8P X1.DI 6 Signal: Digital InputDI-8P X1.DI 7 Signal: Digital InputDI-8P X1.DI 8 Signal: Digital InputRO-6 X5.RO 1 Signal: Relay OutputRO-6 X5.RO 2 Signal: Relay OutputRO-6 X5.RO 3 Signal: Relay OutputRO-6 X5.RO 4 Signal: Relay OutputRO-6 X5.RO 5 Signal: Relay OutputRO-6 X5.RO 6 Signal: Relay OutputRO-6 X5.DISARMED! Signal: CAUTION! RELAYS DISARMED in order to safely perform

maintenance while eliminating the risk of taking an entire process off-line. (Note: Zone Interlocking and Supervision Contact cannot be disarmed). The User MUST ENSURE that the relays are ARMED AGAIN after maintenance.

RO-6 X5.Outs forced Signal: The State of at least one Relay Output has been set by force. That means that the state of at least one Relay is forced and hence does not show the state of the assigned signals.

RO-4Z X2.ZI OUT Signal: Zone Interlocking OUTRO-4Z X2.RO 1 Signal: Relay OutputRO-4Z X2.RO 2 Signal: Relay OutputRO-4Z X2.RO 3 Signal: Relay OutputRO-4Z X2.RO 4 Signal: Relay OutputRO-4Z X2.DISARMED! Signal: CAUTION! RELAYS DISARMED in order to safely perform

maintenance while eliminating the risk of taking an entire process off-line. (Note: Zone Interlocking and Supervision Contact cannot be disarmed). The User MUST ENSURE that the relays are ARMED AGAIN after maintenance.

RO-4Z X2.Outs forced Signal: The State of at least one Relay Output has been set by force. That means that the state of at least one Relay is forced and hence does not show the state of the assigned signals.

Event rec.Res all rec Signal: All records deletedDisturb rec.Recording Signal: RecordingDisturb rec.Memory full Signal: Memory FullDisturb rec.Clear fail Signal: Clear Failure in MemoryDisturb rec.Res all rec Signal: All records deletedDisturb rec.Res record Signal: Delete Record

740 www.eaton.com

Page 741: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Disturb rec.Man. Trigger Signal: Manual TriggerDisturb rec.Start1-I State of the module input: Trigger event / start recording if:Disturb rec.Start2-I State of the module input: Trigger event / start recording if:Disturb rec.Start3-I State of the module input: Trigger event / start recording if:Disturb rec.Start4-I State of the module input: Trigger event / start recording if:Disturb rec.Start5-I State of the module input: Trigger event / start recording if:Disturb rec.Start6-I State of the module input: Trigger event / start recording if:Disturb rec.Start7-I State of the module input: Trigger event / start recording if:Disturb rec.Start8-I State of the module input: Trigger event / start recording if:Fault rec.Res record Signal: Delete Record Fault rec.Man. Trigger Signal: Manual TriggerFault rec.Start1-I State of the module input: Trigger event / start recording if:Fault rec.Start2-I State of the module input: Trigger event / start recording if:Fault rec.Start3-I State of the module input: Trigger event / start recording if:Fault rec.Start4-I State of the module input: Trigger event / start recording if:Fault rec.Start5-I State of the module input: Trigger event / start recording if:Fault rec.Start6-I State of the module input: Trigger event / start recording if:Fault rec.Start7-I State of the module input: Trigger event / start recording if:Fault rec.Start8-I State of the module input: Trigger event / start recording if:Trend rec.Hand Reset Hand ResetEnergyCr.Cr Overflow VAh Net Signal: Counter Overflow VAh NetEnergyCr.Cr Overflow Wh Net Signal: Counter Overflow Wh NetEnergyCr.Cr Overflow Wh Fwd Signal: Counter Overflow Wh FwdEnergyCr.Cr Overflow Wh Rev Signal: Counter Overflow Wh RevEnergyCr.Cr Overflow VArh Net Signal: Counter Overflow VArh NetEnergyCr.Cr Overflow VArh Lag Signal: Counter Overflow VArh LagEnergyCr.Cr Overflow VArh Lead Signal: Counter Overflow VArh LeadEnergyCr.VAh Net Res Cr Signal: VAh Net Reset CounterEnergyCr.Wh Net Res Cr Signal: Wh Net Reset CounterEnergyCr.Wh Fwd Res Cr Signal: Wh Fwd Reset CounterEnergyCr.Wh Rev Res Cr Signal: Wh Rev Reset CounterEnergyCr.VArh Net Res Cr Signal: VArh Net Reset CounterEnergyCr.VArh Lag Res Cr Signal: VArh Lag Reset CounterEnergyCr.VArh Lead Res Cr Signal: VArh Lead Reset CounterEnergyCr.Res all Energy Cr Signal: Reset of all Energy CountersEnergyCr.Cr OverflwWarn VAh Net Signal: Counter VAh Net will overflow soon.EnergyCr.Cr OverflwWarn Wh Net Signal: Counter Wh Net will overflow soon.EnergyCr.Cr OverflwWarn Wh Fwd Signal: Counter Wh Fwd will overflow soon.EnergyCr.Cr OverflwWarn Wh Rev Signal: Counter Wh Rev will overflow soon.

www.eaton.com 741

Page 742: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

EnergyCr.Cr OverflwWarn VArh Net Signal: Counter VArh Net will overflow soon.EnergyCr.Cr OverflwWarn VArh Lag Signal: Counter VArh Lag will overflow soon.EnergyCr.Cr OverflwWarn VArh Lead Signal: Counter VArh Lead will overflow soon.Modbus.Transmission Signal: Communication ActiveModbus.Comm Cmd 1 Communication CommandModbus.Comm Cmd 2 Communication CommandModbus.Comm Cmd 3 Communication CommandModbus.Comm Cmd 4 Communication CommandModbus.Comm Cmd 5 Communication CommandModbus.Comm Cmd 6 Communication CommandModbus.Comm Cmd 7 Communication CommandModbus.Comm Cmd 8 Communication CommandModbus.Comm Cmd 9 Communication CommandModbus.Comm Cmd 10 Communication CommandModbus.Comm Cmd 11 Communication CommandModbus.Comm Cmd 12 Communication CommandModbus.Comm Cmd 13 Communication CommandModbus.Comm Cmd 14 Communication CommandModbus.Comm Cmd 15 Communication CommandModbus.Comm Cmd 16 Communication CommandIEC61850.VirtualInput1 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput2 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput3 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput4 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput5 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput6 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput7 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput8 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput9 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput10 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput11 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput12 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput13 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput14 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput15 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualInput16 Signal: Virtual Input (IEC61850 GGIO Ind)IEC61850.VirtualOutput1-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput2-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput3-I Module input state: Binary state of the Virtual Output (GGIO)

742 www.eaton.com

Page 743: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

IEC61850.VirtualOutput4-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput5-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput6-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput7-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput8-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput9-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput10-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput11-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput12-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput13-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput14-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput15-I Module input state: Binary state of the Virtual Output (GGIO)IEC61850.VirtualOutput16-I Module input state: Binary state of the Virtual Output (GGIO)IRIG-B.Active Signal: ActiveIRIG-B.Inverted Signal: IRIG-B invertedIRIG-B.Control Signal1 Signal: IRIG-B Control SignalIRIG-B.Control Signal2 Signal: IRIG-B Control SignalIRIG-B.Control Signal4 Signal: IRIG-B Control SignalIRIG-B.Control Signal5 Signal: IRIG-B Control SignalIRIG-B.Control Signal6 Signal: IRIG-B Control SignalIRIG-B.Control Signal7 Signal: IRIG-B Control SignalIRIG-B.Control Signal8 Signal: IRIG-B Control SignalIRIG-B.Control Signal9 Signal: IRIG-B Control SignalIRIG-B.Control Signal10 Signal: IRIG-B Control SignalIRIG-B.Control Signal11 Signal: IRIG-B Control SignalIRIG-B.Control Signal12 Signal: IRIG-B Control SignalIRIG-B.Control Signal13 Signal: IRIG-B Control SignalIRIG-B.Control Signal14 Signal: IRIG-B Control SignalIRIG-B.Control Signal15 Signal: IRIG-B Control SignalIRIG-B.Control Signal16 Signal: IRIG-B Control SignalIRIG-B.Control Signal17 Signal: IRIG-B Control SignalIRIG-B.Control Signal18 Signal: IRIG-B Control SignalStatistics.ResFc all Signal: Resetting of all Statistic values (Current Demand, Power

Demand, Min, Max)Statistics.ResFc I Demand Signal: Resetting of Statistics - Current Demand (avg, peak avg)Statistics.ResFc P Demand Signal: Resetting of Statistics - Power Demand (avg, peak avg)Statistics.ResFc Max Signal: Resetting of all Maximum values Statistics.ResFc Min Signal: Resetting of all Minimum values Statistics.StartFc 1-I State of the module input: Start of Statistics 1 (Update the

displayed Demand)

www.eaton.com 743

Page 744: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Statistics.StartFc 2-I State of the module input: Start of Statistics 2 (Update the displayed Demand)

Logic.LE1.Gate Out Signal: Output of the logic gateLogic.LE1.Timer Out Signal: Timer OutputLogic.LE1.Out Signal: Latched Output (Q)Logic.LE1.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE1.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE1.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE1.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE1.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE1.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE2.Gate Out Signal: Output of the logic gateLogic.LE2.Timer Out Signal: Timer OutputLogic.LE2.Out Signal: Latched Output (Q)Logic.LE2.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE2.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE2.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE2.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE2.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE2.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE3.Gate Out Signal: Output of the logic gateLogic.LE3.Timer Out Signal: Timer OutputLogic.LE3.Out Signal: Latched Output (Q)Logic.LE3.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE3.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE3.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE3.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE3.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE3.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE4.Gate Out Signal: Output of the logic gateLogic.LE4.Timer Out Signal: Timer OutputLogic.LE4.Out Signal: Latched Output (Q)Logic.LE4.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE4.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE4.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE4.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE4.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE4.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE5.Gate Out Signal: Output of the logic gate

744 www.eaton.com

Page 745: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE5.Timer Out Signal: Timer OutputLogic.LE5.Out Signal: Latched Output (Q)Logic.LE5.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE5.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE5.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE5.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE5.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE5.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE6.Gate Out Signal: Output of the logic gateLogic.LE6.Timer Out Signal: Timer OutputLogic.LE6.Out Signal: Latched Output (Q)Logic.LE6.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE6.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE6.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE6.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE6.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE6.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE7.Gate Out Signal: Output of the logic gateLogic.LE7.Timer Out Signal: Timer OutputLogic.LE7.Out Signal: Latched Output (Q)Logic.LE7.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE7.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE7.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE7.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE7.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE7.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE8.Gate Out Signal: Output of the logic gateLogic.LE8.Timer Out Signal: Timer OutputLogic.LE8.Out Signal: Latched Output (Q)Logic.LE8.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE8.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE8.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE8.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE8.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE8.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE9.Gate Out Signal: Output of the logic gateLogic.LE9.Timer Out Signal: Timer OutputLogic.LE9.Out Signal: Latched Output (Q)Logic.LE9.Out inverted Signal: Negated Latched Output (Q NOT)

www.eaton.com 745

Page 746: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE9.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE9.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE9.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE9.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE9.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE10.Gate Out Signal: Output of the logic gateLogic.LE10.Timer Out Signal: Timer OutputLogic.LE10.Out Signal: Latched Output (Q)Logic.LE10.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE10.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE10.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE10.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE10.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE10.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE11.Gate Out Signal: Output of the logic gateLogic.LE11.Timer Out Signal: Timer OutputLogic.LE11.Out Signal: Latched Output (Q)Logic.LE11.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE11.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE11.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE11.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE11.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE11.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE12.Gate Out Signal: Output of the logic gateLogic.LE12.Timer Out Signal: Timer OutputLogic.LE12.Out Signal: Latched Output (Q)Logic.LE12.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE12.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE12.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE12.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE12.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE12.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE13.Gate Out Signal: Output of the logic gateLogic.LE13.Timer Out Signal: Timer OutputLogic.LE13.Out Signal: Latched Output (Q)Logic.LE13.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE13.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE13.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE13.Gate In3-I State of the module input: Assignment of the Input Signal

746 www.eaton.com

Page 747: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE13.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE13.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE14.Gate Out Signal: Output of the logic gateLogic.LE14.Timer Out Signal: Timer OutputLogic.LE14.Out Signal: Latched Output (Q)Logic.LE14.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE14.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE14.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE14.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE14.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE14.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE15.Gate Out Signal: Output of the logic gateLogic.LE15.Timer Out Signal: Timer OutputLogic.LE15.Out Signal: Latched Output (Q)Logic.LE15.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE15.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE15.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE15.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE15.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE15.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE16.Gate Out Signal: Output of the logic gateLogic.LE16.Timer Out Signal: Timer OutputLogic.LE16.Out Signal: Latched Output (Q)Logic.LE16.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE16.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE16.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE16.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE16.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE16.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE17.Gate Out Signal: Output of the logic gateLogic.LE17.Timer Out Signal: Timer OutputLogic.LE17.Out Signal: Latched Output (Q)Logic.LE17.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE17.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE17.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE17.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE17.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE17.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE18.Gate Out Signal: Output of the logic gate

www.eaton.com 747

Page 748: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE18.Timer Out Signal: Timer OutputLogic.LE18.Out Signal: Latched Output (Q)Logic.LE18.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE18.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE18.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE18.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE18.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE18.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE19.Gate Out Signal: Output of the logic gateLogic.LE19.Timer Out Signal: Timer OutputLogic.LE19.Out Signal: Latched Output (Q)Logic.LE19.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE19.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE19.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE19.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE19.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE19.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE20.Gate Out Signal: Output of the logic gateLogic.LE20.Timer Out Signal: Timer OutputLogic.LE20.Out Signal: Latched Output (Q)Logic.LE20.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE20.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE20.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE20.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE20.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE20.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE21.Gate Out Signal: Output of the logic gateLogic.LE21.Timer Out Signal: Timer OutputLogic.LE21.Out Signal: Latched Output (Q)Logic.LE21.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE21.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE21.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE21.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE21.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE21.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE22.Gate Out Signal: Output of the logic gateLogic.LE22.Timer Out Signal: Timer OutputLogic.LE22.Out Signal: Latched Output (Q)Logic.LE22.Out inverted Signal: Negated Latched Output (Q NOT)

748 www.eaton.com

Page 749: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE22.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE22.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE22.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE22.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE22.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE23.Gate Out Signal: Output of the logic gateLogic.LE23.Timer Out Signal: Timer OutputLogic.LE23.Out Signal: Latched Output (Q)Logic.LE23.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE23.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE23.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE23.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE23.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE23.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE24.Gate Out Signal: Output of the logic gateLogic.LE24.Timer Out Signal: Timer OutputLogic.LE24.Out Signal: Latched Output (Q)Logic.LE24.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE24.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE24.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE24.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE24.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE24.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE25.Gate Out Signal: Output of the logic gateLogic.LE25.Timer Out Signal: Timer OutputLogic.LE25.Out Signal: Latched Output (Q)Logic.LE25.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE25.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE25.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE25.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE25.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE25.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE26.Gate Out Signal: Output of the logic gateLogic.LE26.Timer Out Signal: Timer OutputLogic.LE26.Out Signal: Latched Output (Q)Logic.LE26.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE26.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE26.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE26.Gate In3-I State of the module input: Assignment of the Input Signal

www.eaton.com 749

Page 750: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE26.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE26.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE27.Gate Out Signal: Output of the logic gateLogic.LE27.Timer Out Signal: Timer OutputLogic.LE27.Out Signal: Latched Output (Q)Logic.LE27.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE27.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE27.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE27.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE27.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE27.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE28.Gate Out Signal: Output of the logic gateLogic.LE28.Timer Out Signal: Timer OutputLogic.LE28.Out Signal: Latched Output (Q)Logic.LE28.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE28.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE28.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE28.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE28.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE28.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE29.Gate Out Signal: Output of the logic gateLogic.LE29.Timer Out Signal: Timer OutputLogic.LE29.Out Signal: Latched Output (Q)Logic.LE29.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE29.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE29.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE29.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE29.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE29.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE30.Gate Out Signal: Output of the logic gateLogic.LE30.Timer Out Signal: Timer OutputLogic.LE30.Out Signal: Latched Output (Q)Logic.LE30.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE30.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE30.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE30.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE30.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE30.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE31.Gate Out Signal: Output of the logic gate

750 www.eaton.com

Page 751: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE31.Timer Out Signal: Timer OutputLogic.LE31.Out Signal: Latched Output (Q)Logic.LE31.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE31.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE31.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE31.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE31.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE31.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE32.Gate Out Signal: Output of the logic gateLogic.LE32.Timer Out Signal: Timer OutputLogic.LE32.Out Signal: Latched Output (Q)Logic.LE32.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE32.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE32.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE32.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE32.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE32.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE33.Gate Out Signal: Output of the logic gateLogic.LE33.Timer Out Signal: Timer OutputLogic.LE33.Out Signal: Latched Output (Q)Logic.LE33.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE33.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE33.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE33.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE33.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE33.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE34.Gate Out Signal: Output of the logic gateLogic.LE34.Timer Out Signal: Timer OutputLogic.LE34.Out Signal: Latched Output (Q)Logic.LE34.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE34.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE34.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE34.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE34.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE34.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE35.Gate Out Signal: Output of the logic gateLogic.LE35.Timer Out Signal: Timer OutputLogic.LE35.Out Signal: Latched Output (Q)Logic.LE35.Out inverted Signal: Negated Latched Output (Q NOT)

www.eaton.com 751

Page 752: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE35.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE35.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE35.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE35.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE35.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE36.Gate Out Signal: Output of the logic gateLogic.LE36.Timer Out Signal: Timer OutputLogic.LE36.Out Signal: Latched Output (Q)Logic.LE36.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE36.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE36.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE36.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE36.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE36.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE37.Gate Out Signal: Output of the logic gateLogic.LE37.Timer Out Signal: Timer OutputLogic.LE37.Out Signal: Latched Output (Q)Logic.LE37.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE37.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE37.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE37.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE37.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE37.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE38.Gate Out Signal: Output of the logic gateLogic.LE38.Timer Out Signal: Timer OutputLogic.LE38.Out Signal: Latched Output (Q)Logic.LE38.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE38.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE38.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE38.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE38.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE38.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE39.Gate Out Signal: Output of the logic gateLogic.LE39.Timer Out Signal: Timer OutputLogic.LE39.Out Signal: Latched Output (Q)Logic.LE39.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE39.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE39.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE39.Gate In3-I State of the module input: Assignment of the Input Signal

752 www.eaton.com

Page 753: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE39.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE39.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE40.Gate Out Signal: Output of the logic gateLogic.LE40.Timer Out Signal: Timer OutputLogic.LE40.Out Signal: Latched Output (Q)Logic.LE40.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE40.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE40.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE40.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE40.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE40.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE41.Gate Out Signal: Output of the logic gateLogic.LE41.Timer Out Signal: Timer OutputLogic.LE41.Out Signal: Latched Output (Q)Logic.LE41.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE41.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE41.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE41.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE41.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE41.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE42.Gate Out Signal: Output of the logic gateLogic.LE42.Timer Out Signal: Timer OutputLogic.LE42.Out Signal: Latched Output (Q)Logic.LE42.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE42.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE42.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE42.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE42.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE42.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE43.Gate Out Signal: Output of the logic gateLogic.LE43.Timer Out Signal: Timer OutputLogic.LE43.Out Signal: Latched Output (Q)Logic.LE43.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE43.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE43.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE43.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE43.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE43.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE44.Gate Out Signal: Output of the logic gate

www.eaton.com 753

Page 754: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE44.Timer Out Signal: Timer OutputLogic.LE44.Out Signal: Latched Output (Q)Logic.LE44.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE44.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE44.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE44.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE44.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE44.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE45.Gate Out Signal: Output of the logic gateLogic.LE45.Timer Out Signal: Timer OutputLogic.LE45.Out Signal: Latched Output (Q)Logic.LE45.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE45.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE45.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE45.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE45.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE45.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE46.Gate Out Signal: Output of the logic gateLogic.LE46.Timer Out Signal: Timer OutputLogic.LE46.Out Signal: Latched Output (Q)Logic.LE46.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE46.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE46.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE46.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE46.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE46.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE47.Gate Out Signal: Output of the logic gateLogic.LE47.Timer Out Signal: Timer OutputLogic.LE47.Out Signal: Latched Output (Q)Logic.LE47.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE47.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE47.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE47.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE47.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE47.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE48.Gate Out Signal: Output of the logic gateLogic.LE48.Timer Out Signal: Timer OutputLogic.LE48.Out Signal: Latched Output (Q)Logic.LE48.Out inverted Signal: Negated Latched Output (Q NOT)

754 www.eaton.com

Page 755: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE48.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE48.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE48.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE48.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE48.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE49.Gate Out Signal: Output of the logic gateLogic.LE49.Timer Out Signal: Timer OutputLogic.LE49.Out Signal: Latched Output (Q)Logic.LE49.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE49.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE49.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE49.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE49.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE49.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE50.Gate Out Signal: Output of the logic gateLogic.LE50.Timer Out Signal: Timer OutputLogic.LE50.Out Signal: Latched Output (Q)Logic.LE50.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE50.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE50.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE50.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE50.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE50.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE51.Gate Out Signal: Output of the logic gateLogic.LE51.Timer Out Signal: Timer OutputLogic.LE51.Out Signal: Latched Output (Q)Logic.LE51.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE51.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE51.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE51.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE51.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE51.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE52.Gate Out Signal: Output of the logic gateLogic.LE52.Timer Out Signal: Timer OutputLogic.LE52.Out Signal: Latched Output (Q)Logic.LE52.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE52.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE52.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE52.Gate In3-I State of the module input: Assignment of the Input Signal

www.eaton.com 755

Page 756: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE52.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE52.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE53.Gate Out Signal: Output of the logic gateLogic.LE53.Timer Out Signal: Timer OutputLogic.LE53.Out Signal: Latched Output (Q)Logic.LE53.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE53.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE53.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE53.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE53.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE53.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE54.Gate Out Signal: Output of the logic gateLogic.LE54.Timer Out Signal: Timer OutputLogic.LE54.Out Signal: Latched Output (Q)Logic.LE54.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE54.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE54.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE54.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE54.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE54.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE55.Gate Out Signal: Output of the logic gateLogic.LE55.Timer Out Signal: Timer OutputLogic.LE55.Out Signal: Latched Output (Q)Logic.LE55.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE55.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE55.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE55.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE55.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE55.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE56.Gate Out Signal: Output of the logic gateLogic.LE56.Timer Out Signal: Timer OutputLogic.LE56.Out Signal: Latched Output (Q)Logic.LE56.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE56.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE56.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE56.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE56.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE56.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE57.Gate Out Signal: Output of the logic gate

756 www.eaton.com

Page 757: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE57.Timer Out Signal: Timer OutputLogic.LE57.Out Signal: Latched Output (Q)Logic.LE57.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE57.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE57.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE57.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE57.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE57.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE58.Gate Out Signal: Output of the logic gateLogic.LE58.Timer Out Signal: Timer OutputLogic.LE58.Out Signal: Latched Output (Q)Logic.LE58.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE58.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE58.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE58.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE58.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE58.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE59.Gate Out Signal: Output of the logic gateLogic.LE59.Timer Out Signal: Timer OutputLogic.LE59.Out Signal: Latched Output (Q)Logic.LE59.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE59.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE59.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE59.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE59.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE59.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE60.Gate Out Signal: Output of the logic gateLogic.LE60.Timer Out Signal: Timer OutputLogic.LE60.Out Signal: Latched Output (Q)Logic.LE60.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE60.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE60.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE60.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE60.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE60.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE61.Gate Out Signal: Output of the logic gateLogic.LE61.Timer Out Signal: Timer OutputLogic.LE61.Out Signal: Latched Output (Q)Logic.LE61.Out inverted Signal: Negated Latched Output (Q NOT)

www.eaton.com 757

Page 758: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE61.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE61.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE61.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE61.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE61.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE62.Gate Out Signal: Output of the logic gateLogic.LE62.Timer Out Signal: Timer OutputLogic.LE62.Out Signal: Latched Output (Q)Logic.LE62.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE62.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE62.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE62.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE62.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE62.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE63.Gate Out Signal: Output of the logic gateLogic.LE63.Timer Out Signal: Timer OutputLogic.LE63.Out Signal: Latched Output (Q)Logic.LE63.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE63.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE63.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE63.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE63.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE63.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE64.Gate Out Signal: Output of the logic gateLogic.LE64.Timer Out Signal: Timer OutputLogic.LE64.Out Signal: Latched Output (Q)Logic.LE64.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE64.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE64.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE64.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE64.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE64.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE65.Gate Out Signal: Output of the logic gateLogic.LE65.Timer Out Signal: Timer OutputLogic.LE65.Out Signal: Latched Output (Q)Logic.LE65.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE65.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE65.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE65.Gate In3-I State of the module input: Assignment of the Input Signal

758 www.eaton.com

Page 759: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE65.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE65.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE66.Gate Out Signal: Output of the logic gateLogic.LE66.Timer Out Signal: Timer OutputLogic.LE66.Out Signal: Latched Output (Q)Logic.LE66.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE66.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE66.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE66.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE66.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE66.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE67.Gate Out Signal: Output of the logic gateLogic.LE67.Timer Out Signal: Timer OutputLogic.LE67.Out Signal: Latched Output (Q)Logic.LE67.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE67.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE67.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE67.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE67.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE67.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE68.Gate Out Signal: Output of the logic gateLogic.LE68.Timer Out Signal: Timer OutputLogic.LE68.Out Signal: Latched Output (Q)Logic.LE68.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE68.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE68.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE68.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE68.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE68.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE69.Gate Out Signal: Output of the logic gateLogic.LE69.Timer Out Signal: Timer OutputLogic.LE69.Out Signal: Latched Output (Q)Logic.LE69.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE69.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE69.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE69.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE69.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE69.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE70.Gate Out Signal: Output of the logic gate

www.eaton.com 759

Page 760: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE70.Timer Out Signal: Timer OutputLogic.LE70.Out Signal: Latched Output (Q)Logic.LE70.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE70.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE70.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE70.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE70.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE70.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE71.Gate Out Signal: Output of the logic gateLogic.LE71.Timer Out Signal: Timer OutputLogic.LE71.Out Signal: Latched Output (Q)Logic.LE71.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE71.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE71.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE71.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE71.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE71.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE72.Gate Out Signal: Output of the logic gateLogic.LE72.Timer Out Signal: Timer OutputLogic.LE72.Out Signal: Latched Output (Q)Logic.LE72.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE72.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE72.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE72.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE72.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE72.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE73.Gate Out Signal: Output of the logic gateLogic.LE73.Timer Out Signal: Timer OutputLogic.LE73.Out Signal: Latched Output (Q)Logic.LE73.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE73.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE73.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE73.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE73.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE73.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE74.Gate Out Signal: Output of the logic gateLogic.LE74.Timer Out Signal: Timer OutputLogic.LE74.Out Signal: Latched Output (Q)Logic.LE74.Out inverted Signal: Negated Latched Output (Q NOT)

760 www.eaton.com

Page 761: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE74.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE74.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE74.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE74.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE74.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE75.Gate Out Signal: Output of the logic gateLogic.LE75.Timer Out Signal: Timer OutputLogic.LE75.Out Signal: Latched Output (Q)Logic.LE75.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE75.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE75.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE75.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE75.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE75.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE76.Gate Out Signal: Output of the logic gateLogic.LE76.Timer Out Signal: Timer OutputLogic.LE76.Out Signal: Latched Output (Q)Logic.LE76.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE76.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE76.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE76.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE76.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE76.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE77.Gate Out Signal: Output of the logic gateLogic.LE77.Timer Out Signal: Timer OutputLogic.LE77.Out Signal: Latched Output (Q)Logic.LE77.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE77.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE77.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE77.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE77.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE77.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE78.Gate Out Signal: Output of the logic gateLogic.LE78.Timer Out Signal: Timer OutputLogic.LE78.Out Signal: Latched Output (Q)Logic.LE78.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE78.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE78.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE78.Gate In3-I State of the module input: Assignment of the Input Signal

www.eaton.com 761

Page 762: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE78.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE78.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE79.Gate Out Signal: Output of the logic gateLogic.LE79.Timer Out Signal: Timer OutputLogic.LE79.Out Signal: Latched Output (Q)Logic.LE79.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE79.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE79.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE79.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE79.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE79.Reset Latch-I State of the module input: Reset Signal for the LatchingLogic.LE80.Gate Out Signal: Output of the logic gateLogic.LE80.Timer Out Signal: Timer OutputLogic.LE80.Out Signal: Latched Output (Q)Logic.LE80.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE80.Gate In1-I State of the module input: Assignment of the Input SignalLogic.LE80.Gate In2-I State of the module input: Assignment of the Input SignalLogic.LE80.Gate In3-I State of the module input: Assignment of the Input SignalLogic.LE80.Gate In4-I State of the module input: Assignment of the Input SignalLogic.LE80.Reset Latch-I State of the module input: Reset Signal for the LatchingSystem Alarms.Active Signal: ActiveSystem Alarms.ExBlo Signal: External BlockingSystem Alarms.Alarm Watt Power Signal: Alarm WATTS peakSystem Alarms.Alarm VAr Power Signal: Alarm VArs peakSystem Alarms.Alarm VA Power Signal: Alarm VAs peakSystem Alarms.Alarm Watt Demand Signal: Alarm WATTS demand valueSystem Alarms.Alarm VAr Demand Signal: Alarm VARs demand valueSystem Alarms.Alarm VA Demand Signal: Alarm VAs demand valueSystem Alarms.Alarm Current Demand Signal: Alarm Current demand valueSystem Alarms.Alarm I THD Signal: Alarm Total Harmonic Distortion CurrentSystem Alarms.Alarm V THD Signal: Alarm Total Harmonic Distortion VoltageSystem Alarms.Trip Watt Power Signal: Trip WATTS peakSystem Alarms.Trip VAr Power Signal: Trip VArs peakSystem Alarms.Trip VA Power Signal: Trip VAs peakSystem Alarms.Trip Watt Demand Signal: Trip WATTS demand valueSystem Alarms.Trip VAr Demand Signal: Trip VARs demand valueSystem Alarms.Trip VA Demand Signal: Trip VAs demand valueSystem Alarms.Trip Current Demand Signal: Trip Current demand valueSystem Alarms.Trip I THD Signal: Trip Total Harmonic Distortion Current

762 www.eaton.com

Page 763: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

System Alarms.Trip V THD Signal: Trip Total Harmonic Distortion VoltageSystem Alarms.ExBlo-I Module Input State: External BlockingSine wave gen.running Signal: Measuring value simulation is runningSine wave gen.ExBlo Module Input State: External BlockingSine wave gen.Ex ForcePost-I State of the module input:Force Post state. Abort simulation.Sys.PS 1 Signal: Parameter Set 1Sys.PS 2 Signal: Parameter Set 2Sys.PS 3 Signal: Parameter Set 3Sys.PS 4 Signal: Parameter Set 4Sys.PSS manual Signal: Manual switch over of a Parameter SetSys.PSS via Comm Signal: Parameter Set Switch via CommunicationSys.PSS via Inp fct Signal: Parameter Set Switch via Input FunctionSys.Min. 1 param changed Signal: At least one parameter has been changedSys.Maint Mode Active Signal: Arc Flash Reduction Maintenance ActiveSys.Maint Mode Inactive Signal: Arc Flash Reduction Maintenance InactiveSys.MaintMode Manually Signal: Arc Flash Reduction Maintenance Manual ModeSys.Maint Mode Comm Signal: Arc Flash Reduction Maintenance Comm ModeSys.Maint Mode DI Signal: Arc Flash Reduction Maintenance Digital Input ModeSys.Ack LED Signal: LEDs AcknowledgmentSys.Ack RO Signal: Acknowledgment of the Relay OutputsSys.Ack Comm Signal: Acknowledge CommunicationSys.Ack TripCmd Signal: Reset Trip CommandSys.Ack LED-HMI Signal: LEDs Acknowledgment :HMISys.Ack RO-HMI Signal: Acknowledgment of the Relay Outputs :HMISys.Ack Comm-HMI Signal: Acknowledge Communication :HMISys.Ack TripCmd-HMI Signal: Reset Trip Command :HMISys.Ack LED-Comm Signal: LEDs Acknowledgment :CommunicationSys.Ack RO-Comm Signal: Acknowledgment of the Relay Outputs :CommunicationSys.Ack Counter-Comm Signal: Reset of all Counters :CommunicationSys.Ack Comm-Comm Signal: Acknowledge Communication :CommunicationSys.Ack TripCmd-Comm Signal: Reset Trip Command :CommunicationSys.Res OperationsCr Signal: Res OperationsCrSys.Res AlarmCr Signal: Res AlarmCrSys.Res TripCr Signal: Res TripCrSys.Res TotalCr Signal: Res TotalCrSys.Ack LED-I Module Input State: LEDs Acknowledgment by Digital Input.Sys.Ack RO-I Module Input State: Acknowledgment of the Relay Outputs.Sys.Ack Comm-I Module Input State: Acknowledge Communication via Digital Input.

The replica that Communication has received from the device is to be reset.

www.eaton.com 763

Page 764: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Sys.PS1-I State of the module input, respectively of the signal, that should activate this Parameter Setting Group.

Sys.PS2-I State of the module input, respectively of the signal, that should activate this Parameter Setting Group.

Sys.PS3-I State of the module input, respectively of the signal, that should activate this Parameter Setting Group.

Sys.PS4-I State of the module input, respectively of the signal, that should activate this Parameter Setting Group.

Sys.Maint Mode-I Module Input State: Arc Flash Reduction Maintenance Switch

Special Assignment List for All Digital Input Signals and All Logic Outputs

Name Description

-.- No assignmentDI-8P X1.DI 1 Signal: Digital InputDI-8P X1.DI 2 Signal: Digital InputDI-8P X1.DI 3 Signal: Digital InputDI-8P X1.DI 4 Signal: Digital InputDI-8P X1.DI 5 Signal: Digital InputDI-8P X1.DI 6 Signal: Digital InputDI-8P X1.DI 7 Signal: Digital InputDI-8P X1.DI 8 Signal: Digital InputLogic.LE1.Gate Out Signal: Output of the logic gateLogic.LE1.Timer Out Signal: Timer OutputLogic.LE1.Out Signal: Latched Output (Q)Logic.LE1.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE2.Gate Out Signal: Output of the logic gateLogic.LE2.Timer Out Signal: Timer OutputLogic.LE2.Out Signal: Latched Output (Q)Logic.LE2.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE3.Gate Out Signal: Output of the logic gateLogic.LE3.Timer Out Signal: Timer OutputLogic.LE3.Out Signal: Latched Output (Q)Logic.LE3.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE4.Gate Out Signal: Output of the logic gateLogic.LE4.Timer Out Signal: Timer OutputLogic.LE4.Out Signal: Latched Output (Q)Logic.LE4.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE5.Gate Out Signal: Output of the logic gateLogic.LE5.Timer Out Signal: Timer OutputLogic.LE5.Out Signal: Latched Output (Q)

764 www.eaton.com

Page 765: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE5.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE6.Gate Out Signal: Output of the logic gateLogic.LE6.Timer Out Signal: Timer OutputLogic.LE6.Out Signal: Latched Output (Q)Logic.LE6.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE7.Gate Out Signal: Output of the logic gateLogic.LE7.Timer Out Signal: Timer OutputLogic.LE7.Out Signal: Latched Output (Q)Logic.LE7.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE8.Gate Out Signal: Output of the logic gateLogic.LE8.Timer Out Signal: Timer OutputLogic.LE8.Out Signal: Latched Output (Q)Logic.LE8.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE9.Gate Out Signal: Output of the logic gateLogic.LE9.Timer Out Signal: Timer OutputLogic.LE9.Out Signal: Latched Output (Q)Logic.LE9.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE10.Gate Out Signal: Output of the logic gateLogic.LE10.Timer Out Signal: Timer OutputLogic.LE10.Out Signal: Latched Output (Q)Logic.LE10.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE11.Gate Out Signal: Output of the logic gateLogic.LE11.Timer Out Signal: Timer OutputLogic.LE11.Out Signal: Latched Output (Q)Logic.LE11.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE12.Gate Out Signal: Output of the logic gateLogic.LE12.Timer Out Signal: Timer OutputLogic.LE12.Out Signal: Latched Output (Q)Logic.LE12.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE13.Gate Out Signal: Output of the logic gateLogic.LE13.Timer Out Signal: Timer OutputLogic.LE13.Out Signal: Latched Output (Q)Logic.LE13.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE14.Gate Out Signal: Output of the logic gateLogic.LE14.Timer Out Signal: Timer OutputLogic.LE14.Out Signal: Latched Output (Q)Logic.LE14.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE15.Gate Out Signal: Output of the logic gateLogic.LE15.Timer Out Signal: Timer Output

www.eaton.com 765

Page 766: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE15.Out Signal: Latched Output (Q)Logic.LE15.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE16.Gate Out Signal: Output of the logic gateLogic.LE16.Timer Out Signal: Timer OutputLogic.LE16.Out Signal: Latched Output (Q)Logic.LE16.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE17.Gate Out Signal: Output of the logic gateLogic.LE17.Timer Out Signal: Timer OutputLogic.LE17.Out Signal: Latched Output (Q)Logic.LE17.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE18.Gate Out Signal: Output of the logic gateLogic.LE18.Timer Out Signal: Timer OutputLogic.LE18.Out Signal: Latched Output (Q)Logic.LE18.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE19.Gate Out Signal: Output of the logic gateLogic.LE19.Timer Out Signal: Timer OutputLogic.LE19.Out Signal: Latched Output (Q)Logic.LE19.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE20.Gate Out Signal: Output of the logic gateLogic.LE20.Timer Out Signal: Timer OutputLogic.LE20.Out Signal: Latched Output (Q)Logic.LE20.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE21.Gate Out Signal: Output of the logic gateLogic.LE21.Timer Out Signal: Timer OutputLogic.LE21.Out Signal: Latched Output (Q)Logic.LE21.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE22.Gate Out Signal: Output of the logic gateLogic.LE22.Timer Out Signal: Timer OutputLogic.LE22.Out Signal: Latched Output (Q)Logic.LE22.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE23.Gate Out Signal: Output of the logic gateLogic.LE23.Timer Out Signal: Timer OutputLogic.LE23.Out Signal: Latched Output (Q)Logic.LE23.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE24.Gate Out Signal: Output of the logic gateLogic.LE24.Timer Out Signal: Timer OutputLogic.LE24.Out Signal: Latched Output (Q)Logic.LE24.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE25.Gate Out Signal: Output of the logic gate

766 www.eaton.com

Page 767: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE25.Timer Out Signal: Timer OutputLogic.LE25.Out Signal: Latched Output (Q)Logic.LE25.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE26.Gate Out Signal: Output of the logic gateLogic.LE26.Timer Out Signal: Timer OutputLogic.LE26.Out Signal: Latched Output (Q)Logic.LE26.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE27.Gate Out Signal: Output of the logic gateLogic.LE27.Timer Out Signal: Timer OutputLogic.LE27.Out Signal: Latched Output (Q)Logic.LE27.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE28.Gate Out Signal: Output of the logic gateLogic.LE28.Timer Out Signal: Timer OutputLogic.LE28.Out Signal: Latched Output (Q)Logic.LE28.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE29.Gate Out Signal: Output of the logic gateLogic.LE29.Timer Out Signal: Timer OutputLogic.LE29.Out Signal: Latched Output (Q)Logic.LE29.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE30.Gate Out Signal: Output of the logic gateLogic.LE30.Timer Out Signal: Timer OutputLogic.LE30.Out Signal: Latched Output (Q)Logic.LE30.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE31.Gate Out Signal: Output of the logic gateLogic.LE31.Timer Out Signal: Timer OutputLogic.LE31.Out Signal: Latched Output (Q)Logic.LE31.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE32.Gate Out Signal: Output of the logic gateLogic.LE32.Timer Out Signal: Timer OutputLogic.LE32.Out Signal: Latched Output (Q)Logic.LE32.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE33.Gate Out Signal: Output of the logic gateLogic.LE33.Timer Out Signal: Timer OutputLogic.LE33.Out Signal: Latched Output (Q)Logic.LE33.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE34.Gate Out Signal: Output of the logic gateLogic.LE34.Timer Out Signal: Timer OutputLogic.LE34.Out Signal: Latched Output (Q)Logic.LE34.Out inverted Signal: Negated Latched Output (Q NOT)

www.eaton.com 767

Page 768: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE35.Gate Out Signal: Output of the logic gateLogic.LE35.Timer Out Signal: Timer OutputLogic.LE35.Out Signal: Latched Output (Q)Logic.LE35.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE36.Gate Out Signal: Output of the logic gateLogic.LE36.Timer Out Signal: Timer OutputLogic.LE36.Out Signal: Latched Output (Q)Logic.LE36.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE37.Gate Out Signal: Output of the logic gateLogic.LE37.Timer Out Signal: Timer OutputLogic.LE37.Out Signal: Latched Output (Q)Logic.LE37.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE38.Gate Out Signal: Output of the logic gateLogic.LE38.Timer Out Signal: Timer OutputLogic.LE38.Out Signal: Latched Output (Q)Logic.LE38.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE39.Gate Out Signal: Output of the logic gateLogic.LE39.Timer Out Signal: Timer OutputLogic.LE39.Out Signal: Latched Output (Q)Logic.LE39.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE40.Gate Out Signal: Output of the logic gateLogic.LE40.Timer Out Signal: Timer OutputLogic.LE40.Out Signal: Latched Output (Q)Logic.LE40.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE41.Gate Out Signal: Output of the logic gateLogic.LE41.Timer Out Signal: Timer OutputLogic.LE41.Out Signal: Latched Output (Q)Logic.LE41.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE42.Gate Out Signal: Output of the logic gateLogic.LE42.Timer Out Signal: Timer OutputLogic.LE42.Out Signal: Latched Output (Q)Logic.LE42.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE43.Gate Out Signal: Output of the logic gateLogic.LE43.Timer Out Signal: Timer OutputLogic.LE43.Out Signal: Latched Output (Q)Logic.LE43.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE44.Gate Out Signal: Output of the logic gateLogic.LE44.Timer Out Signal: Timer OutputLogic.LE44.Out Signal: Latched Output (Q)

768 www.eaton.com

Page 769: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE44.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE45.Gate Out Signal: Output of the logic gateLogic.LE45.Timer Out Signal: Timer OutputLogic.LE45.Out Signal: Latched Output (Q)Logic.LE45.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE46.Gate Out Signal: Output of the logic gateLogic.LE46.Timer Out Signal: Timer OutputLogic.LE46.Out Signal: Latched Output (Q)Logic.LE46.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE47.Gate Out Signal: Output of the logic gateLogic.LE47.Timer Out Signal: Timer OutputLogic.LE47.Out Signal: Latched Output (Q)Logic.LE47.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE48.Gate Out Signal: Output of the logic gateLogic.LE48.Timer Out Signal: Timer OutputLogic.LE48.Out Signal: Latched Output (Q)Logic.LE48.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE49.Gate Out Signal: Output of the logic gateLogic.LE49.Timer Out Signal: Timer OutputLogic.LE49.Out Signal: Latched Output (Q)Logic.LE49.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE50.Gate Out Signal: Output of the logic gateLogic.LE50.Timer Out Signal: Timer OutputLogic.LE50.Out Signal: Latched Output (Q)Logic.LE50.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE51.Gate Out Signal: Output of the logic gateLogic.LE51.Timer Out Signal: Timer OutputLogic.LE51.Out Signal: Latched Output (Q)Logic.LE51.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE52.Gate Out Signal: Output of the logic gateLogic.LE52.Timer Out Signal: Timer OutputLogic.LE52.Out Signal: Latched Output (Q)Logic.LE52.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE53.Gate Out Signal: Output of the logic gateLogic.LE53.Timer Out Signal: Timer OutputLogic.LE53.Out Signal: Latched Output (Q)Logic.LE53.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE54.Gate Out Signal: Output of the logic gateLogic.LE54.Timer Out Signal: Timer Output

www.eaton.com 769

Page 770: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE54.Out Signal: Latched Output (Q)Logic.LE54.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE55.Gate Out Signal: Output of the logic gateLogic.LE55.Timer Out Signal: Timer OutputLogic.LE55.Out Signal: Latched Output (Q)Logic.LE55.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE56.Gate Out Signal: Output of the logic gateLogic.LE56.Timer Out Signal: Timer OutputLogic.LE56.Out Signal: Latched Output (Q)Logic.LE56.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE57.Gate Out Signal: Output of the logic gateLogic.LE57.Timer Out Signal: Timer OutputLogic.LE57.Out Signal: Latched Output (Q)Logic.LE57.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE58.Gate Out Signal: Output of the logic gateLogic.LE58.Timer Out Signal: Timer OutputLogic.LE58.Out Signal: Latched Output (Q)Logic.LE58.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE59.Gate Out Signal: Output of the logic gateLogic.LE59.Timer Out Signal: Timer OutputLogic.LE59.Out Signal: Latched Output (Q)Logic.LE59.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE60.Gate Out Signal: Output of the logic gateLogic.LE60.Timer Out Signal: Timer OutputLogic.LE60.Out Signal: Latched Output (Q)Logic.LE60.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE61.Gate Out Signal: Output of the logic gateLogic.LE61.Timer Out Signal: Timer OutputLogic.LE61.Out Signal: Latched Output (Q)Logic.LE61.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE62.Gate Out Signal: Output of the logic gateLogic.LE62.Timer Out Signal: Timer OutputLogic.LE62.Out Signal: Latched Output (Q)Logic.LE62.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE63.Gate Out Signal: Output of the logic gateLogic.LE63.Timer Out Signal: Timer OutputLogic.LE63.Out Signal: Latched Output (Q)Logic.LE63.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE64.Gate Out Signal: Output of the logic gate

770 www.eaton.com

Page 771: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Name Description

Logic.LE64.Timer Out Signal: Timer OutputLogic.LE64.Out Signal: Latched Output (Q)Logic.LE64.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE65.Gate Out Signal: Output of the logic gateLogic.LE65.Timer Out Signal: Timer OutputLogic.LE65.Out Signal: Latched Output (Q)Logic.LE65.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE66.Gate Out Signal: Output of the logic gateLogic.LE66.Timer Out Signal: Timer OutputLogic.LE66.Out Signal: Latched Output (Q)Logic.LE66.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE67.Gate Out Signal: Output of the logic gateLogic.LE67.Timer Out Signal: Timer OutputLogic.LE67.Out Signal: Latched Output (Q)Logic.LE67.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE68.Gate Out Signal: Output of the logic gateLogic.LE68.Timer Out Signal: Timer OutputLogic.LE68.Out Signal: Latched Output (Q)Logic.LE68.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE69.Gate Out Signal: Output of the logic gateLogic.LE69.Timer Out Signal: Timer OutputLogic.LE69.Out Signal: Latched Output (Q)Logic.LE69.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE70.Gate Out Signal: Output of the logic gateLogic.LE70.Timer Out Signal: Timer OutputLogic.LE70.Out Signal: Latched Output (Q)Logic.LE70.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE71.Gate Out Signal: Output of the logic gateLogic.LE71.Timer Out Signal: Timer OutputLogic.LE71.Out Signal: Latched Output (Q)Logic.LE71.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE72.Gate Out Signal: Output of the logic gateLogic.LE72.Timer Out Signal: Timer OutputLogic.LE72.Out Signal: Latched Output (Q)Logic.LE72.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE73.Gate Out Signal: Output of the logic gateLogic.LE73.Timer Out Signal: Timer OutputLogic.LE73.Out Signal: Latched Output (Q)Logic.LE73.Out inverted Signal: Negated Latched Output (Q NOT)

www.eaton.com 771

Page 772: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Name Description

Logic.LE74.Gate Out Signal: Output of the logic gateLogic.LE74.Timer Out Signal: Timer OutputLogic.LE74.Out Signal: Latched Output (Q)Logic.LE74.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE75.Gate Out Signal: Output of the logic gateLogic.LE75.Timer Out Signal: Timer OutputLogic.LE75.Out Signal: Latched Output (Q)Logic.LE75.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE76.Gate Out Signal: Output of the logic gateLogic.LE76.Timer Out Signal: Timer OutputLogic.LE76.Out Signal: Latched Output (Q)Logic.LE76.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE77.Gate Out Signal: Output of the logic gateLogic.LE77.Timer Out Signal: Timer OutputLogic.LE77.Out Signal: Latched Output (Q)Logic.LE77.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE78.Gate Out Signal: Output of the logic gateLogic.LE78.Timer Out Signal: Timer OutputLogic.LE78.Out Signal: Latched Output (Q)Logic.LE78.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE79.Gate Out Signal: Output of the logic gateLogic.LE79.Timer Out Signal: Timer OutputLogic.LE79.Out Signal: Latched Output (Q)Logic.LE79.Out inverted Signal: Negated Latched Output (Q NOT)Logic.LE80.Gate Out Signal: Output of the logic gateLogic.LE80.Timer Out Signal: Timer OutputLogic.LE80.Out Signal: Latched Output (Q)Logic.LE80.Out inverted Signal: Negated Latched Output (Q NOT)

772 www.eaton.com

Page 773: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Notes:

www.eaton.com 773

Page 774: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Notes:

774 www.eaton.com

Page 775: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

EDR-5000 IM02602007E

Notes:

www.eaton.com 775

Page 776: EDR-5000 EATON DISTRIBUTION RELAYes.eaton.com/protectiverelays/Documentation/EDR5000/IM02602007E... · EDR-5000 EATON DISTRIBUTION RELAY Instruction Manual for Installing, Operating,

IM02602007E EDR-5000

Instruction Leaflet IM02602007EEffective 11/30/10

EDR-5000

This instruction leaflet is published solely for information purposesand should not be considered all-inclusive. If further information isrequired, you should consult an authorized Eaton sales representative.The sale of the product shown in this literature is subject to theterms and conditions outlined in appropriate Eaton selling policiesor other contractual agreement between the parties. This literatureis not intended to and does not enlarge or add to any such contract.The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton.NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS, AND DESCRIPTIONS CONTAINED HEREIN. In no event will Eaton be responsible to the purchaser or User in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, costof capital, loss of power, additional expenses in the use of existingpower facilities, or claims against the purchaser or User by its customers resulting from the use of the information, recommendations and description contained herein.

Eaton CorporationElectrical Group1000 Cherrington ParkwayMoon Township, PA 15108United States877-ETN-CARE (877-386-2273)Eaton.com© 2010 Eaton CorporationAll Rights ReservedPrinted in USAPublication No. IM02602007E/66A2416

PowerChain Management is a registeredtrademark of Eaton Corporation.All other trademarks are property of theirrespective owners.

776 www.eaton.com