BHMM ENERGY SERVICES 2745 S. Hoffman Road Indianapolis, IN 46241-3624(317)247-9300
Report of Eddy Current InspectionManufacturer: York
Model: YK-S2-R2-J2DHSerial: GBCM13330 #2
Location: INDIANA INTERNATIONAL AIRPORT 2500 S. HIGH SCHOOL ROAD INDIANAPOLIS, IN 46201
Inspected: December 23, 2011-January 2, 2012
Inspected By: ROBERT J. KIRKHAM, LEVEL III
Reviewed By:TECHNICAL MANAGER, LEVEL III
Report of Eddy Current InspectionManufacturer: York
Model: YK-S2-R2-J2DHSerial: GBCM13330 #2
Location: INDIANA INTERNATIONAL AIRPORT 2500 S. HIGH SCHOOL ROAD INDIANAPOLIS, IN 46201
Inspected: December 23, 2011-January 2, 2012
Inspected By: ROBERT J. KIRKHAM, LEVEL III
Reviewed By:TECHNICAL MANAGER, LEVEL III
Table of Contents
Section A . . . . . . . . . . . . . . .Inspection Report
Part I . . . . . . . . . . .Vessel InformationPart II . . . . . . . . . . .Summary of InspectionPart III. . . . . . . . . . .Defect SummaryPart IV. . . . . . . . . . .RecommendationsPart V. . . . . . . . . . .Data SheetsPart VI. . . . . . . . . . .Tube Chart LayoutPart VII. . . . . . . . . . .Tube Strip Charts
Section B . . . . . . . . . . . . . . .Calibration Settingsand GraphsCalibration Procedures
Section C . . . . . . . . . . . . . . .Explanation ofAbbreviations
Copyright (c) 2009, TAI Services, Inc.
S/N GBCM13330 #2
Vessel Information
Manufacturer Model Style Serial Number Type
York YK-S2-R2-J2DH Open Drive GBCM13330 #2 Centrifugal
CondenserTestEnd
Tube Count
Tube Type
Tube Material
OD
*NWT/Under Fins
*NWT/Bell/Land
#/Type Support
Tube Numbering
Row Numbering
Tube Length +- 2
Opposite Inlet/Outlet
1527
Skip Fin IE
Copper
.750
.028
.052
3 Mild Steel
Left to Right
Top to Bottom
168 Inches
EvaporatorTestEnd
Tube Count
Tube Type
Tube Material
OD
*NWT/Under Fins
*NWT/Bell/Land
#/Type Support
Tube Numbering
Row Numbering
Tube Length +- 2
Opposite Inlet/Outlet
1494
Skip Fin IE
Copper
.750
.028
.042
3 Mild Steel
Left to Right
Top to Bottom
168 Inches
Sub-CoolerTestEnd
Tube Count
Tube Type
Tube Material
OD
*NWT/Under Fins
*NWT/Bell/Land
#/Type Support
Tube Numbering
Row Numbering
Tube Length +- 2
Opposite Inlet/Outlet
140
Skip Fin IE
Copper
.750
.028
.052
3 Mild Steel
Top to Bottom
Left to Right
168 Inches
Analyst: ROBERT J. KIRKHAM, LEVEL III
* Nominal Wall Thickness
S/N GBCM13330 #2
Vessel Bay Length Information
Condenser (Length = 168 inches)S = Intermediate Support
Opp. Test End Test End
Bay 4
Bay 4
42.00"
42.00"
S3
Bay 3
Bay 3
42.00"
42.00"
S2
Bay 2
Bay 2
42.00"
42.00"
S1
Bay 1
Bay 1
42.00"
42.00"
Evaporator (Length = 168 inches)S = Intermediate Support
Opp. Test End Test End
Bay 4
Bay 4
42.00"
42.00"
S3
Bay 3
Bay 3
42.00"
42.00"
S2
Bay 2
Bay 2
42.00"
42.00"
S1
Bay 1
Bay 1
42.00"
42.00"
S/N GBCM13330 #2
Sub-Cooler (Length = 168 inches)S = Intermediate Support
Opp. Test End Test End
Bay 4
Bay 4
42.00"
42.00"
S3
Bay 3
Bay 3
42.00"
42.00"
S2
Bay 2
Bay 2
42.00"
42.00"
S1
Bay 1
Bay 1
42.00"
42.00"
S/N GBCM13330 #2
Defect Summary/Comparison
Comparison of Tests Performed12/27/2011 9/27/2006
Condenser Defects
ID PIT 40% - 59% PREVIOUSLY PLUGGED ID PIT 60% - 79% 9/27/2006
Location Model Serial Number
INDIANA INTERNATIONAL AIRPORT YK-S2-R2-J2DH GBCM13330 #2
Note: The Graph will indicate a Comparison Analysis when the unit has been previously tested by TAI Services.
S/N GBCM13330 #2Defect Summary/Comparison - Page 2
Evaporator Defects
MISSED EXP, NOMINAL 9/27/2006
Location Model Serial Number
INDIANA INTERNATIONAL AIRPORT YK-S2-R2-J2DH GBCM13330 #2
Note: The Graph will indicate a Comparison Analysis when the unit has been previously tested by TAI Services.
S/N GBCM13330 #2Defect Summary/Comparison - Page 3
Sub-Cooler Defects
PREVIOUSLY PLUGGED ID PIT 40% - 59% 9/28/2006
Location Model Serial Number
INDIANA INTERNATIONAL AIRPORT YK-S2-R2-J2DH GBCM13330 #2
Note: The Graph will indicate a Comparison Analysis when the unit has been previously tested by TAI Services.
S/N GBCM13330 #2
Summary of InspectionAn eddy current tube inspection was performed as part of a preventive maintenance programwith the following results.
Evaporator: 1494 Tubes
Significant/Measurable IndicationsNumber of
Tubes Marked
Percent of Bundle
MISSED EXP, NOMINAL 1 .07
Totals 1 .07
Condenser: 1527 Tubes
Significant/Measurable IndicationsNumber of
Tubes Marked
Percent of Bundle
ID PIT 40% - 59%* 1 .07
PREVIOUSLY PLUGGED 21 1.38
Totals 22 1.45
* REQUIRES ACTION
NOTE: Although not marked, all tubes gave indications of ID Pits of less than 40%. These defects were not marked to keep the tube chart neat and legible and to better illustrate any major defect patterns that may have existed.
Sub-Cooler: 140 Tubes
Significant/Measurable IndicationsNumber of
Tubes Marked
Percent of Bundle
PREVIOUSLY PLUGGED 1 .71
Totals 1 .71
S/N GBCM13330 #2
Summary of Inspection - page 2
NOTE: Although not marked, all tubes gave indications of ID Pits of less than 40%. These defects were not marked to keep the tube chart neat and legible and to better illustrate any major defect patterns that may have existed.
S/N GBCM13330 #2
Recommendations
The tubes in this machine were tested for normal wear patterns using accepted test methods for eddy current inspections. The possibility does exist that tubes could contain defects and/or leaks which are not detectable, such as those at or near the tube end.The following suggested repair actions are based on accepted industry standards. After removing sample tubes to confirm the inspection results, a determination of corrective action should be made by the repair agency and end user. Only these parties have knowledge of the critical applications and long-term use of the equipment. If plugging is selected over replacement, both efficiency and capacity should be considered.EVAPORATOR:The tube marked as Missed Expanded showed no loss at the intermediate support and require no corrective action. CONDENSER:Tubes indicating ID Pits of 40% or more should be isolated from the system at this time. ID Pits of less than 40% require no immediate corrective action. However, this type damage is usually progressive and should be monitored. ID Pitting can be caused by biological or chemical attack.We recommend the cause of this damage be identified and neutralized if active.Tubes marked as Previously Plugged, had been plugged prior to this inspection.SUBCOOLER:Tubes marked as Previously Plugged, had been plugged prior to this inspection.
RE-INSPECTION RECOMMENDATIONS:We recommend that a follow-up inspection be performed on these vessels as follows:Condenser: 23 December 2014Evaporator: 23 December 2014Sub-Cooler: 23 December 2014A copy of this report should be retained in your files to be used for comparison at that time.If you should have any questions concerning this report, or if we may be of further assistance, please feel free to call upon us.
S/N GBCM13330 #2
Data SheetLocation Model Serial Number Date
INDIANA INTERNATIONAL AIRPORT
2500 S. HIGH SCHOOL ROAD
INDIANAPOLIS, IN 46201
YK-S2-R2-J2DH GBCM13330 #2 December 23, 2011
Row Tube Description Area Action Req.
SET UP CALIBRATE & STARTEDCONDENSER 1/2/2012 09:09 am
3 4 ID PIT 40% - 59% B02
8 9 PREVIOUSLY PLUGGED TE
22 10 PREVIOUSLY PLUGGED TE
24 15 PREVIOUSLY PLUGGED TE
24 16 PREVIOUSLY PLUGGED TE
24 27 PREVIOUSLY PLUGGED TE
24 28 PREVIOUSLY PLUGGED TE
10 30 PREVIOUSLY PLUGGED TE
24 38 PREVIOUSLY PLUGGED TE
25 13 PREVIOUSLY PLUGGED TE
26 4 PREVIOUSLY PLUGGED TE
27 32 PREVIOUSLY PLUGGED TE
27 39 PREVIOUSLY PLUGGED TE
27 40 PREVIOUSLY PLUGGED TE
27 41 PREVIOUSLY PLUGGED TE
27 43 PREVIOUSLY PLUGGED TE
28 16 PREVIOUSLY PLUGGED TE
28 18 PREVIOUSLY PLUGGED TE
28 19 PREVIOUSLY PLUGGED TE
S/N GBCM13330 #2
Data Sheets - Page 2
Row Tube Description Area Action Req.
28 21 PREVIOUSLY PLUGGED TE
28 24 PREVIOUSLY PLUGGED TE
31 7 PREVIOUSLY PLUGGED TE
CALIBRATION CHECK & COMPLETEDCONDENSER 1/2/2012 12:57 pm
SET UP CALIBRATE & STARTEDEVAPORATOR 12/23/2011 07:49 am
8 33 MISSED EXP, NOMINAL S01
CALIBRATION CHECK & COMPLETEDEVAPORATOR 12/23/2011 11:41 am
SET UP CALIBRATE & STARTEDSUB-COOLER 1/2/2012 12:59 pm
2 4 PREVIOUSLY PLUGGED TE
CALIBRATION CHECK & COMPLETEDSUB-COOLER 1/2/2012 01:40 pm
Condenser SectionS/N GBCM13330 #2
Opposite Inlet/Outlet
Top of Vessel
Row 1,Tube 1 -
P2
Row 5,Tube 1 -
PP
Row 10,Tube 1 - PP
Row 15,Tube 1 -
Row 20,Tube 1 -
PP
PP PP PP PP PPRow 25,Tube 1 - PP
PPPP PP PP PP PP
PP PP PP PP PP
Row 30,Tube 1 -PP
Row 35,Tube 1 -
P2 = ID PIT 40% - 59% REQUIRES ACTIONPP = PREVIOUSLY PLUGGED
Evaporator SectionS/N GBCM13330 #2
Opposite Inlet/Outlet
Top of Vessel
Row 1,Tube 1 -
Row 5,Tube 1 -
E1
Row 10,Tube 1 -
Row 15,Tube 1 -
Row 20,Tube 1 -
Row 25,Tube 1 -
E1 = MISSED EXP, NOMINAL
Sub-Cooler SectionS/N GBCM13330 #2
Opposite Inlet/Outlet
Top of Vessel
Row 1-Tube 1
PP
PP = PREVIOUSLY PLUGGED
S/N GBCM13330 #2Test Instrument UsedHighline Automation, EC14
Calibration Page
Tube Type Material Nom Wall Thick End Wall Thick OD Test Type Probe Diameter
Skip Fin IE Copper .028 .052 .750 CROSS/DIFF
Condenser Sub-Cooler
Note: Defects are compared to machined standards. Actual Defect Geometry may differ.
S/N GBCM13330 #2Test Instrument UsedHighline Automation, EC14
Calibration Page
Tube Type Material Nom Wall Thick End Wall Thick OD Test Type Probe Diameter
Skip Fin IE Copper .028 .042 .750 CROSS/DIFF
Evaporator
Note: Defects are compared to machined standards. Actual Defect Geometry may differ.
Explanation of Abbreviations
Abbreviation Explanation ABN IND Abnormal Indication B Bay FB Freeze Bulge FBH Flat Bottom Hole FM Foreign Material ID Internal Diameter ID CORROSION Internal Diameter, Corrosion ID DEPOSIT Internal Diameter, Deposit ID PIT Internal Diameter, Pit IDML Internal Diameter, Metal Loss IE Internally Enhanced OD Outside Diameter ODML Outside Diameter, Metal Loss ODML@S Outside Diameter Metal Loss at Support OD DEPOSIT Outside Diameter, Deposit PLF Possible Longitudinal Flaw PRF Possible Radial Flaw PSC Possible Stress Corrosion S Support WAS Wear at Support > Greater Than < Less Than OTE Opposite Test End TE Test End