7
D0 D0 AI DI P MS FS T PP TH THERMOMETER TEMPERATURE GAUGE TEMPERATURE SENSOR PRESSURE SENSOR/TRANSMITTER PNEUMATIC CONTROL ELECTRICAL CONTROL WIRING FLOW SWITCH/SENSOR ANALOG OUTPUT DIGITAL INPUT ANALOG INPUT DIGITAL OUTPUT T MAGNETIC STARTER THERMOSTAT PRESSURE REDUCING VALVE TEMPERATURE CONTROL VALVE AIR VENT VALVE-AUTOMATIC AIR VENT VALVE-MANUAL STRAINER PGA U AVM AVA PRESSURE GAUGE PETE'S PLUG UNION CONNECTION CKV GLV GV PRV TCV BV GLOBE VALVE CHECK VALVE GATE VALVE BUTTERFLY VALVE UNLESS NOTED OTHERWISE WEATHER OR WATER PROOF TYPICAL VENT THRU ROOF WEIGHT WATER PRESSURE DROP WT WP WPD VTR TYP UNO STANDARD STEEL STAINLESS STEEL THERMOMETER TOTAL STATIC PRESSURE STL TSP TH STD SS POUND PER SQUARE INCH GAUGE RETURN FAN RF ROUGH IN ONLY SUPPLY FAN SALVAGE TO BE RE-INSTALLED REVOLUTION PER MINUTE RELOCATE (S) SF RPM RIO (R) PLUMBING POINT OF CONNECTION POUND PER SQUARE INCH RELOCATED PSI (R) PSIG POC PLBG SD CD G FS W X X X X SD STORM DRAIN 3-WAY CONTROL VALVE 2-WAY CONTROL VALVE BC CD BALL VALVE BALANCING VALVE BALANCING COCK CONDENSATE DRAIN G V HWR CW HW FS HOT WATER RETURN GAS VENT COLD WATER FIRE SPRINKLER HOT WATER FLEXIBLE CONNECTION FIRE SPRINKLER HEAD ACCESS PANEL/ACCESS DOOR VENT RISE - VENT THRU ROOF SANITARY OR WASTE (E) PIPE TO BE REMOVED (E) PIPE TO BE REMAIN AP/AD VR-VTR W DN UP DIRECTION OF FLOW ALL SERVICES ALL SERVICES X (E) (N) FP EXISTING NEW SYMBOLS 1 1 M-1 ACU 1 NORTH ARROW (REFERENCE) POINT OF DEMOLITION EQUIPMENT IDENTIFICATION POINT OF CONNECTION KEYED NOTE DETAIL OR SECTION SHEET NUMBER ABB'R SERVICE NATIONAL FIRE PROTECTION ASSOCIATION NEW NORMALLY CLOSED PRESSURE GAUGE NORMALLY OPEN NFPA PG NO NC (N) FEET PER MINUTE FIRE SMOKE DETECTOR HEATER HOT WATER MANUFACTURER HW MFR HTR FSD FPM EXTERNAL STATIC PRESSURE EXISTING EXHAUST FAN FLEXIBLE CONNECTION FIRE SPRINKLER ESP FC F EF (E) CEILING CUBIC FEET PER MINUTE DOWN CONNECT TO EXISTING DISPOSE DN (D) CTE CLG CFM BRAKE HORSEPOWER/BOILER HORSEPOWER AIR HANDLING UNIT AHU ACCESS PANEL CAP FOR FUTURE BOTTOM OF PIPE CUBIC FEET PER HOUR CFF CFH BOP BHP AP ABOVE FINISH FLOOR AIR CONDITIONING UNIT AFF ACU REFER TO SMACNA SEISMIC GUIDELINES AND STANDARDS FOR DUCT PIPE SUPPORT AND EQUIPMENT SEISMIC BRACING. PROTECT THE PUBLIC FROM INJURY DURING PROGRESS OF WORK BY POSTING WARNING SIGNS, GUARD LIGHTS AND BARRICADES. ALL WORK SHALL BE IN COMPLIANCE WITH THE LATEST APPLICABLE LOCAL AND STATE CODES AND REGULATIONS: x CALIFORNIA BUILDING CODE 2016 x CALIFORNIA MECHANICAL CODE 2016 x CALIFORNIA PLUMBING CODE 2016 x CALIFORNIA FIRE CODE 2016 x CALIFORNIA ELECTRICAL CODE 2016 ALL PIPING SHOWN ON PLANS ARE DIAGRAMMATIC AND SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION. CERTAIN VERTICAL AND HORIZONTAL DIMENSIONS ARE SHOWN IN DUCTS AND PIPES TO INDICATE THEIR GENERAL POSITION IN RELATIONSHIP TO THE SYSTEMS WITHIN THE SPACE AVAILABLE FOR SYSTEM INSTALLATION. PROVIDE ADDITIONAL PIPING OFFSETS AS REQUIRED, AND TO COORDINATE WITH INSTALLATION REQUIREMENTS OF OTHER SYSTEMS AT NO ADDITIONAL COST TO THE OWNER. ALL DIMENSIONS ARE IN INCHES OR OTHERWISE NOTED. CONTRACTOR SHALL ASSUME SOLE RESPONSIBILITY FOR SAFETY OF ALL PERSONS ON OR ABOUT THE CONSTRUCTION SITE, IN ACCORDANCE WITH APPLICABLE LAWS AND CODES. GUARD ALL HAZARDS IN ACCORDANCE WITH THE SAFETY PROVISIONS OF THE LATEST MANUAL OF ACCIDENT PREVENTION PUBLISHED BY THE ASSOCIATED GENERAL CONTRACTORS OF AMERICA AND OSHA. SEAL AIR AND WATER TIGHT ALL PIPE PENETRATIONS THROUGH WALL. SEALANT SHALL BE 3M BRAND PRODUCTS. BRACE ALL PIPES AND EQUIPMENT TO WITHSTAND FORCES AS REQUIRED BY THE STATE AND LOCAL CODES. WHERE EXISTING CONSTRUCTION IS CUT, DAMAGED, OR REMODELED, PATCH WITH MATERIALS TO MATCH IN KIND, QUALITY, AND PERFORMANCE. COORDINATE WORK WITH THE OWNER AND ALL OTHER TRADES. THE EXISTING MECHANICAL AND ELECTRICAL SYSTEMS SHALL BE MAINTAINED IN OPERATION DURING THE DEMOLITION AND INSTALLATION OF NEW WORK. WHEN A SYSTEM SHUTDOWN IS NECESSARY, OBTAIN A WRITTEN APPROVAL FROM THE OWNER PRIOR TO SHUTTING DOWN OF ANY MECHANICAL ELECTRICAL SYSTEMS. THE CONTRACTOR SHALL PROVIDE DUST BARRIER PLASTIC COVERS, SCREEN AND TENTING AT ALL TIMES TO CONTAIN DUST AND DEBRIS WITHIN THE DESIGNATED WORK AREA. LOCATING AND INSTALLATION OF DUST PROTECTION COVERS AND TENTING TO BE APPROVED BY THE OWNER PRIOR TO INSTALLING. CONTRACTOR SHALL CLEAN WORK AREA AND REMOVE DEBRIS AT THE END OF EACH WORKING DAY. DISPOSAL OF DEBRIS AND EXCESS MATERIAL SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS. ANY ERRORS, OMISSIONS OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE CONSTRUCTION DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT OR ENGINEER AND OWNER BEFORE PROCEEDING WITH THE WORK. PENETRATIONS THROUGH EXISTING CONCRETE WALL, FLOOR OR ROOF SHALL BE VERIFIED FOR STRUCTURAL REINFORCEMENTS. X-RAY ARE REQUIRED TO LOCATE REINFORCEMENT PRIOR TO CONCRETE CORE DRILLING OR CUTTING. OBTAIN OWNER'S WRITTEN APPROVAL PRIOR TO CORE DRILLING AND CUTTING. CONTRACTOR SHALL BE RESPONSIBLE FOR CORRECTION OF WORK AT HIS OWN EXPENSE FOR WORK INSTALLED IN CONFLICT WITH CONSTRUCTION DOCUMENTS. CONTRACTOR SHALL LEAVE PREMISES AND ALL AFFECTED AREAS CLEAN AND IN ORDERLY MANNER READY FOR MOVE-IN OR FACILITY OPERATION. PROVIDE ADEQUATE CLEARANCE AND ACCESS TO EQUIPMENT FOR SERVICE AND MAINTENANCE. EQUIPMENT CLEARANCES SHALL MEET THE REQUIREMENT OF THE MANUFACTURER. INSULATE ALL HOT AND COLD PIPING. PROVIDE SILICATE INSERTS AT SUPPORT POINTS. PROVIDE ALUMINUM JACKETING FOR OUTDOOR INSTALLATION. GENERAL: THIS SCOPE OF WORK IS AN OUTLINE OF WORK INVOLVE FOR THIS PROJECT AND IS NOT INTENDED TO DESCRIBE THE COMPLETE SCOPE OF WORK. THE DETAILED REQUIREMENTS ARE INDICATED ON EACH DRAWING AND SPECIFICATION. 1. REMOVE AND DISPOSE EXISTING PLUMBING FIXTURES AS INDICATED. PRESSURE TEST ALL PLUMBING PER CPC 2016. 6. 7. FLUSH AND DISINFECT ALL WATER PIPING AND EQUIPMENT PER CPC 2016. P1.00 LEGEND, SYMBOLS, GENERAL NOTES, SCOPE OF WORK & DRAWING INDEX P2.11 FIRST FLOOR PLAN - PLUMBING DEMOLITION P1.01 SPECIFICATIONS, PLUMBING FIXTURE SCHEDULE AND DETAILS 3. PROVIDE NEW JANITOR SINK AS INDICATED. EXTEND EXISTING PLUMBING UTILITIES AS REQUIRED. 4. PROVIDE NEW SHOWERS. EXTEND AND MODIFY EXISTING PLUMBING UTILITIES AS REQUIRED. MODIFY EXISTING PLUMBING AS NECESSARY. EXPLORATORY WORK TO SEARCH FOR PIPING, PLUMBING OR DUCT FOR CONNECTIONS TO EXISTING BUILDING SYSTEM INCLUDING POINT OF CONNECTIONS UNDER FLOOR SLAB, IN WALLS AND CEILING SHALL BE INCLUDED AT NO COST TO THE OWNER. CUTTING, PATCHING AND RESTORATION OF FLOORS, WALLS, CEILING AND FINISH SHALL BE INCLUDED IN THIS WORK AT NO COST TO THE OWNER. RESTORATION OF WALL OR FLOOR FINISH SHALL MATCH EXISTING. 19. ALL PLUMBING PIPING MATERIAL, PLUMBING FIXTURE, VALVE, FIITINGS AND ACCESSORIES SHALL BE 'LEAD-FREE' IN ACCORDANCE WITH CALIFORNIA REGULATION AB1953. PROVIDE SUBMITTAL FROM MANUFACTURER'S FOR COMPLIANCE. 20. 18. 17. 16. 15. 14. 13. 11. 10. 9. 8. 6. 5. 4. 3. 2. 1. P2.21 FIRST FLOOR PLAN - PLUMBING P2.22 SECOND FLOOR PLAN - PLUMBING 2. PROVIDE NEW PLUMBING FIXTURES AS INDICATED. EXTEND AND MODIFY EXISTING PLUMBING UTILITIES AS NECESSARY. P2.12 SECOND FLOOR PLAN - PLUMBING DEMOLITION P3.01 DETAILS - PLUMBING 7. SHOWER UNIT SH0-1 VERIFY DIMENSIONS OF OWNER FURNISHED EQUIPMENT TO ENSURE PROPER COORDINATION WITH CONSTRUCTION DOCUMENTS. NOTIFY ARCHITECT/ENGINEER OF ANY DISCREPANCIES FOUND. NO ALLOWANCE SHALL BE MADE FOR ANY EXPENSE TO WHICH THE CONTRACTOR MAY INCUR DUE TO FAILURE OR NEGLECT ON HIS PART TO MAKE SUCH VERIFICATION. 12. FP2.21 FIRST FLOOR PLAN - FIRE PROTECTION FP2.22 SECOND FLOOR PLAN - FIRE PROTECTION REVISIONS SHEET NUMBER SHEET TITLE N&T JOB # ISSUE DATE 729 Heinz Avenue Berkeley, CA 94710 tel 510.542.2200 fax 510.542.2201 SEAL APPROVALS 1901 HEARST ST. BERKELEY CA 94704 21603.00 12/19/18 # DATE DESCRIPTION EDDIE PADILLA 274 Devonshire Street 5. PROVIDE NEW HI/LO DRINKING FOUNTAIN WITH COOLER AS INDICATED. EXTEND AND MODITY EXISTING PLUMBING UTILITIES AS NECESSARY.

EDDIE PADILLA - Berkeley, California · notify architect/engineer of any discrepancies found. no allowance shall be made for any expense to which the contractor may incur due to failure

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EDDIE PADILLA - Berkeley, California · notify architect/engineer of any discrepancies found. no allowance shall be made for any expense to which the contractor may incur due to failure

D0

D0

AI

DI

P

MS

FS

T

PP

TH THERMOMETER

TEMPERATURE GAUGE

TEMPERATURE SENSOR

PRESSURE SENSOR/TRANSMITTER

PNEUMATIC CONTROL

ELECTRICAL CONTROL WIRING

FLOW SWITCH/SENSOR

ANALOG OUTPUT

DIGITAL INPUT

ANALOG INPUT

DIGITAL OUTPUT

T

MAGNETIC STARTER

THERMOSTAT

PRESSURE REDUCING VALVE

TEMPERATURE CONTROL VALVE

AIR VENT VALVE-AUTOMATIC

AIR VENT VALVE-MANUAL

STRAINER

PGA

U

AVM

AVA

PRESSURE GAUGE

PETE'S PLUG

UNION CONNECTION

CKV

GLV

GV

PRV

TCV

BV

GLOBE VALVE

CHECK VALVE

GATE VALVE

BUTTERFLY VALVE

UNLESS NOTED OTHERWISE

WEATHER OR WATER PROOF

TYPICAL

VENT THRU ROOF

WEIGHT

WATER PRESSURE DROP

WT

WP

WPD

VTR

TYP

UNO

STANDARD

STEEL

STAINLESS STEEL

THERMOMETER

TOTAL STATIC PRESSURE

STL

TSP

TH

STD

SS

POUND PER SQUARE INCH GAUGE

RETURN FANRF

ROUGH IN ONLY

SUPPLY FAN

SALVAGE TO BE RE-INSTALLED

REVOLUTION PER MINUTE

RELOCATE

(S)

SF

RPM

RIO

(R)

PLUMBING

POINT OF CONNECTION

POUND PER SQUARE INCH

RELOCATED

PSI

(R)

PSIG

POC

PLBG

SD

CD

G

FS

W

X X X X

SD STORM DRAIN

3-WAY CONTROL VALVE

2-WAY CONTROL VALVE

BC

CD

BALL VALVE

BALANCING VALVE

BALANCING COCK

CONDENSATE DRAIN

G

V

HWR

CW

HW

FS

HOT WATER RETURN

GAS

VENT

COLD WATER

FIRE SPRINKLER

HOT WATER

FLEXIBLE CONNECTION

FIRE SPRINKLER HEAD

ACCESS PANEL/ACCESS DOOR

VENT RISE - VENT THRU ROOF

SANITARY OR WASTE

(E) PIPE TO BE REMOVED

(E) PIPE TO BE REMAIN

AP/AD

VR-VTR

W

DN

UP

DIRECTION OF FLOW

ALL SERVICES

ALL SERVICES

X

(E)

(N)

FP

EXISTING

NEW

SYMBOLS

1

1

M-1

ACU

1

NORTH ARROW (REFERENCE)

POINT OF DEMOLITION

EQUIPMENT IDENTIFICATION

POINT OF CONNECTION

KEYED NOTE

DETAIL OR SECTION

SHEET NUMBER

ABB'R SERVICE

NATIONAL FIRE PROTECTION ASSOCIATION

NEW

NORMALLY CLOSED

PRESSURE GAUGE

NORMALLY OPEN

NFPA

PG

NO

NC

(N)

FEET PER MINUTE

FIRE SMOKE DETECTOR

HEATER

HOT WATER

MANUFACTURER

HW

MFR

HTR

FSD

FPM

EXTERNAL STATIC PRESSURE

EXISTING

EXHAUST FAN

FLEXIBLE CONNECTION

FIRE SPRINKLER

ESP

FC

F

EF

(E)

CEILING

CUBIC FEET PER MINUTE

DOWN

CONNECT TO EXISTING

DISPOSE

DN

(D)

CTE

CLG

CFM

BRAKE HORSEPOWER/BOILER HORSEPOWER

AIR HANDLING UNITAHU

ACCESS PANEL

CAP FOR FUTURE

BOTTOM OF PIPE

CUBIC FEET PER HOUR

CFF

CFH

BOP

BHP

AP

ABOVE FINISH FLOOR

AIR CONDITIONING UNIT

AFF

ACU

REFER TO SMACNA SEISMIC GUIDELINES AND STANDARDS FOR DUCT PIPE SUPPORT AND

EQUIPMENT SEISMIC BRACING.

PROTECT THE PUBLIC FROM INJURY DURING PROGRESS OF WORK BY POSTING WARNING

SIGNS, GUARD LIGHTS AND BARRICADES.

ALL WORK SHALL BE IN COMPLIANCE WITH THE LATEST APPLICABLE LOCAL AND

STATE CODES AND REGULATIONS:

CALIFORNIA BUILDING CODE 2016

CALIFORNIA MECHANICAL CODE 2016

CALIFORNIA PLUMBING CODE 2016

CALIFORNIA FIRE CODE 2016

CALIFORNIA ELECTRICAL CODE 2016

ALL PIPING SHOWN ON PLANS ARE DIAGRAMMATIC AND SHALL NOT BE SCALED TO

DETERMINE EXACT LOCATION. CERTAIN VERTICAL AND HORIZONTAL DIMENSIONS ARE

SHOWN IN DUCTS AND PIPES TO INDICATE THEIR GENERAL POSITION IN RELATIONSHIP TO

THE SYSTEMS WITHIN THE SPACE AVAILABLE FOR SYSTEM INSTALLATION. PROVIDE

ADDITIONAL PIPING OFFSETS AS REQUIRED, AND TO COORDINATE WITH INSTALLATION

REQUIREMENTS OF OTHER SYSTEMS AT NO ADDITIONAL COST TO THE OWNER. ALL

DIMENSIONS ARE IN INCHES OR OTHERWISE NOTED.

CONTRACTOR SHALL ASSUME SOLE RESPONSIBILITY FOR SAFETY OF ALL PERSONS ON OR

ABOUT THE CONSTRUCTION SITE, IN ACCORDANCE WITH APPLICABLE LAWS AND CODES.

GUARD ALL HAZARDS IN ACCORDANCE WITH THE SAFETY PROVISIONS OF THE LATEST

MANUAL OF ACCIDENT PREVENTION PUBLISHED BY THE ASSOCIATED GENERAL

CONTRACTORS OF AMERICA AND OSHA.

SEAL AIR AND WATER TIGHT ALL PIPE PENETRATIONS THROUGH WALL. SEALANT SHALL BE

3M BRAND PRODUCTS. BRACE ALL PIPES AND EQUIPMENT TO WITHSTAND FORCES AS

REQUIRED BY THE STATE AND LOCAL CODES.

WHERE EXISTING CONSTRUCTION IS CUT, DAMAGED, OR REMODELED, PATCH WITH

MATERIALS TO MATCH IN KIND, QUALITY, AND PERFORMANCE.

COORDINATE WORK WITH THE OWNER AND ALL OTHER TRADES.

THE EXISTING MECHANICAL AND ELECTRICAL SYSTEMS SHALL BE MAINTAINED IN

OPERATION DURING THE DEMOLITION AND INSTALLATION OF NEW WORK. WHEN A SYSTEM

SHUTDOWN IS NECESSARY, OBTAIN A WRITTEN APPROVAL FROM THE OWNER PRIOR TO

SHUTTING DOWN OF ANY MECHANICAL ELECTRICAL SYSTEMS.

THE CONTRACTOR SHALL PROVIDE DUST BARRIER PLASTIC COVERS, SCREEN AND

TENTING AT ALL TIMES TO CONTAIN DUST AND DEBRIS WITHIN THE DESIGNATED WORK

AREA. LOCATING AND INSTALLATION OF DUST PROTECTION COVERS AND TENTING TO BE

APPROVED BY THE OWNER PRIOR TO INSTALLING. CONTRACTOR SHALL CLEAN WORK AREA

AND REMOVE DEBRIS AT THE END OF EACH WORKING DAY. DISPOSAL OF DEBRIS AND

EXCESS MATERIAL SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.

VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS.

ANY ERRORS, OMISSIONS OR CONFLICTS FOUND IN THE VARIOUS PARTS OF THE

CONSTRUCTION DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT

OR ENGINEER AND OWNER BEFORE PROCEEDING WITH THE WORK.

PENETRATIONS THROUGH EXISTING CONCRETE WALL, FLOOR OR ROOF SHALL BE VERIFIED

FOR STRUCTURAL REINFORCEMENTS. X-RAY ARE REQUIRED TO LOCATE REINFORCEMENT

PRIOR TO CONCRETE CORE DRILLING OR CUTTING. OBTAIN OWNER'S WRITTEN APPROVAL

PRIOR TO CORE DRILLING AND CUTTING.

CONTRACTOR SHALL BE RESPONSIBLE FOR CORRECTION OF WORK AT HIS OWN EXPENSE

FOR WORK INSTALLED IN CONFLICT WITH CONSTRUCTION DOCUMENTS.

CONTRACTOR SHALL LEAVE PREMISES AND ALL AFFECTED AREAS CLEAN AND IN ORDERLY

MANNER READY FOR MOVE-IN OR FACILITY OPERATION.

PROVIDE ADEQUATE CLEARANCE AND ACCESS TO EQUIPMENT FOR SERVICE AND

MAINTENANCE. EQUIPMENT CLEARANCES SHALL MEET THE REQUIREMENT OF THE

MANUFACTURER.

INSULATE ALL HOT AND COLD PIPING. PROVIDE SILICATE INSERTS AT SUPPORT POINTS.

PROVIDE ALUMINUM JACKETING FOR OUTDOOR INSTALLATION.

GENERAL: THIS SCOPE OF WORK IS AN OUTLINE OF WORK INVOLVE FOR THIS PROJECT AND IS

NOT INTENDED TO DESCRIBE THE COMPLETE SCOPE OF WORK. THE DETAILED REQUIREMENTS

ARE INDICATED ON EACH DRAWING AND SPECIFICATION.

1. REMOVE AND DISPOSE EXISTING PLUMBING FIXTURES AS INDICATED.

PRESSURE TEST ALL PLUMBING PER CPC 2016.6.

7. FLUSH AND DISINFECT ALL WATER PIPING AND EQUIPMENT PER CPC 2016.

P1.00 LEGEND, SYMBOLS, GENERAL NOTES, SCOPE OF WORK & DRAWING INDEX

P2.11 FIRST FLOOR PLAN - PLUMBING DEMOLITION

P1.01 SPECIFICATIONS, PLUMBING FIXTURE SCHEDULE AND DETAILS

3. PROVIDE NEW JANITOR SINK AS INDICATED. EXTEND EXISTING PLUMBING UTILITIES AS

REQUIRED.

4. PROVIDE NEW SHOWERS. EXTEND AND MODIFY EXISTING PLUMBING UTILITIES AS REQUIRED.

MODIFY EXISTING PLUMBING AS NECESSARY.

EXPLORATORY WORK TO SEARCH FOR PIPING, PLUMBING OR DUCT FOR CONNECTIONS

TO EXISTING BUILDING SYSTEM INCLUDING POINT OF CONNECTIONS UNDER FLOOR SLAB,

IN WALLS AND CEILING SHALL BE INCLUDED AT NO COST TO THE OWNER. CUTTING,

PATCHING AND RESTORATION OF FLOORS, WALLS, CEILING AND FINISH SHALL BE

INCLUDED IN THIS WORK AT NO COST TO THE OWNER. RESTORATION OF WALL OR FLOOR

FINISH SHALL MATCH EXISTING.

19.

ALL PLUMBING PIPING MATERIAL, PLUMBING FIXTURE, VALVE, FIITINGS AND ACCESSORIES

SHALL BE 'LEAD-FREE' IN ACCORDANCE WITH CALIFORNIA REGULATION AB1953. PROVIDE

SUBMITTAL FROM MANUFACTURER'S FOR COMPLIANCE.

20.

18.

17.

16.

15.

14.

13.

11.

10.

9.

8.

6.

5.

4.

3.

2.

1.

P2.21 FIRST FLOOR PLAN - PLUMBING

P2.22 SECOND FLOOR PLAN - PLUMBING

2. PROVIDE NEW PLUMBING FIXTURES AS INDICATED. EXTEND AND MODIFY EXISTING

PLUMBING UTILITIES AS NECESSARY.

P2.12 SECOND FLOOR PLAN - PLUMBING DEMOLITION

P3.01 DETAILS - PLUMBING

7.

SHOWER UNITSH0-1

VERIFY DIMENSIONS OF OWNER FURNISHED EQUIPMENT TO ENSURE PROPER

COORDINATION WITH CONSTRUCTION DOCUMENTS. NOTIFY ARCHITECT/ENGINEER OF ANY

DISCREPANCIES FOUND. NO ALLOWANCE SHALL BE MADE FOR ANY EXPENSE TO WHICH

THE CONTRACTOR MAY INCUR DUE TO FAILURE OR NEGLECT ON HIS PART TO MAKE SUCH

VERIFICATION.

12.

FP2.21 FIRST FLOOR PLAN - FIRE PROTECTION

FP2.22 SECOND FLOOR PLAN - FIRE PROTECTION

REVISIONS

SHEET NUMBER

SHEET TITLE

N&T JOB #

ISSUE DATE

729 Heinz AvenueBerkeley, CA 94710

tel 510.542.2200fax 510.542.2201

SEAL

APPROVALS

1901 HEARST ST.

BERKELEY CA 94704

21603.00

12/19/18

# DATE DESCRIPTION

EDDIEPADILLA

274 Devonshire Street

5. PROVIDE NEW HI/LO DRINKING FOUNTAIN WITH COOLER AS INDICATED. EXTEND AND MODITY

EXISTING PLUMBING UTILITIES AS NECESSARY.

Page 2: EDDIE PADILLA - Berkeley, California · notify architect/engineer of any discrepancies found. no allowance shall be made for any expense to which the contractor may incur due to failure

DISINFECTION PROCEDURE:

A. POST SUITABLE WARNING SIGNS AT EACH OUTLET: 'WARNING - DO NOT USE - WATER SYSTEM BEING

CHLORINATED'.

B. INJECT DISINFECTANT SOLUTION INTO THE SYSTEM THROUGH THE SERVICE COCK BY MEANS OF A

PUMP, OR OTHER PRESSURE DEVICE, AT A SLOW CONTINUOUS RATE, SIMULTANEOUS WITH A

REDUCED FLOW FROM THE WATER MAIN, UNTIL THE ORTHOTOLIDIN TEST FOR RESIDUAL CHLORINE

AT EACH OUTLET SHOWS A CONCENTRATION OF AT LEAST 50PPM, BUT NOT MORE THAN 100 PPM.

C. CLOSE ALL OUTLETS AND VALVES, INCLUDING THE SERVICE VALVE AT THE MAIN AND THE INJECTION

COCK. RETAIN THE CHLORINATED WATER IN THE SYSTEM FOR 24 HOURS.

D. AFTER 24 HOUR HOLDING PERIOD, THE RESIDUAL CHLORINE CONCENTRATION SHALL BE NOT LESS

THE 50 PPM AS SHOWN BY THE ORTHOTOLIDIN TEST.

E. DRAIN AND FLUSH ENTIRE DOMESTIC WATER SYSTEM UNTIL ORTHOLIDIN TEST SHOW BACKGROUND

RESIDUAL CHLORINE CONCENTRATION AT ANY OUTLET.

F. ENVIRONMENTAL, HEALTH AND SAFETY (EH&S) WILL DETERMINE WHETHER SAMPLES OF WATER MUST

BE COLLECTED AND ANALYZED FOR THE DETERMINATION OF BACTERIOLOGICAL QUALITY.

G. STANDARDS NECESSARY FOR APPROVAL:

a. THE WATER SYSTEM SHALL BE UNIFORMLY CHLORINATED UNDER THE SUPERVISION OF

ENVIRONMENTAL, HEALTH AND SAFETY (EH&S) AS OUTLINED IN THE 'DISINFECTION

PROCEDURE'.

b. THE RESULT OF WATER SAMPLE ANALYSIS SHALL BE NEGATIVE FOR THE COLIFORM

ORGANISM.

c. IF THE TEST FOR THE BACTERIOLOGICAL QUALITY OF THE WATER IN THE SYSTEM DOES

NOT MEET THE STANDARDS, REPEAT THE DISINFECTION PROCEDURE UNTIL THE SPECIFIED

STANDARDS ARE MET.

I. FINAL APPROVAL: ENVIRONMENTAL, HEALTH AND SAFETY (EH&S) WILL GIVE WRITTEN APPROVAL TO

THE UNIVERSITY FOR ACCEPTANCE AND USE OF THE WATER SYSTEM AFTER THE ABOVE

PROCEDURES HAVE BEEN SUCCESSFULLY COMPLETED AND THE STANDARDS MET.

PLUMBING FIXTURE CARRIERS OR WALL SUPPORTS SHALL BE ADJUSTABLE J. R. SMITH OR EQUAL. REFER TO

ARCHITECTURAL DRAWINGS FOR PLUMBING FIXTURE LOCATION AND MOUNTING HEIGHT.

PLUMBING FIXTURES SPECIFICATIONS

REFER TO ARCHITECTURAL DRAWINGS FOR ALL PLUMBING FIXTURE LOCATION AND MOUNTING HEIGHT.

ROUGH - IN

ALL WATER CLOSETS SHALL USE A MAXIMUM OF 1.28 GALLONS PER FLUSH.1.

2.

VSS

WATER CLOSET

LAV-1LAVATORY

WC-1

2"

4" 2"

DESCRIPTION FIXTURE TAG

TWCW HW

WALL HUNG, ADA ACCESSIBLE

WHERE INDICATED.

WALL MOUNTED, ADA ACCESSIBLE

WHERE INDICATED.

1/2"1/2" -

1" --

REMARKS

4. REFER TO ARCHITECTURAL DRAWING FOR PLUMBING FIXTURE LOCATION AND MOUNTING HEIGHT.

1.

PLUMBING FIXTURE SCHEDULE

1 1/2"

WATER HAMMER ARRESTOR (HA-1) : JAY R. SMITH, 5220 SERIES, 1" CONNECTION, PISTON TYPE. WITH EPDM

PSIG. UNIT TO COMPLY WITH ANSI 1010 WATER HAMMER ARRESTOR. PROVIDE 12X12 STAINLESS STEEL ACCESS

PANEL.

WATER CLOSET: WC-1

FURNISH AMERICAN STANDARD "AFWALL FLOWISE" NO. 2856.128 WALL-MOUNT, ELONGATED, WHITE, VITREOUS

CHINA, TOP SPUD, 1.28 GPF, EVERCLEAN SURFACE. FLUSH VALVE SHALL BE 1" HARDWIRED SELECTRONIC TOP

SPUD, 'SELECTRONIC' SENSOR ACTIVATED FLUSHOMETER WITH OVERRIDE BUTTON, NON-HOLD OPEN INTEGRAL

SOLENOID OPERATOR, WITH NO VISIBLE FASTENERS, BACK-CHECK ANGLE VALVE, VANDAL RESISTANT STOP

CAP, VACUUM BREAKER. PROVIDE NEW CARRIER SUPPORTS AND ANCHORS AS RECOMMENDED BY FIXTURE

MANUFACTURER. FURNISH TOILET SEAT AND COVER, WHITE COLOR. PROVIDE FLUSH VALVE WITH FLUSH LEVER

ON THE WIDE SIDE FOR ACCESSIBLE (ADA) ACCESS. PROVIDE POWER KIT WITH TRANSFORMER.

URINALUR-1 2"WALL MOUNTED, ADA ACCESSIBLE

WHERE INDICATED.1" --1 1/2"

4.

7.

8.

9.

3.

URINAL: UR-1

PROVIDE TOTO NO. UT105UG, WALL-MOUNT, WHITE, VITREOUS CHINA WITH 'CeFiONtect' CERAMIN GLAZE, ADA

COMPLIANT, MEETS ANSI 0.125 GPF, HIGH EFFICIENCY FLUSH REQUIREMENTS, SIPHON JET FLUSH ACTION. FLUSH

VALVE CHROME FINISHED FLUSHOMETER, HARDWIRED 'SELECTRONIC' SENSOR ACTIVATED FLUSHOMETER WITH

OVERRIDE BUTTON, WITH NO VISIBLE FASTENERS, BACK-CHECK ANGLE VALVE, VANDAL RESISTANT STOP CAP,

VACUUM BREAKER, ANGLE STOP WITH BACKFLOW PREVENTER, HIGH BACK PRESSURE VACUUM BREAKER. PROVIDE

FIXTURE CARRIER OR WALL SUPPORT AS RECOMMENDED BY THE MANUFACTURER. PROVIDE TRAP PRIMER TAIL

PIECE 'TP' VBF-72 FOR FLOOR DRAIN. PROVIDE WATER SUPPLY PLUMBING TO FLOOR DRAIN.

ALL LAVATORY FAUCETS SHALL BE FITTED WITH AN APPROVED FLOW CONTROL DEVICE ALLOWING A MAXIMUM OF 0.5 GPM. PUBLIC3.

ALL URINALS SHALL USE A MAXIMUM OF 0.125 GALLONS PER FLUSH.

FLOOR DRAIN FD-1 : ZURN Z415S-ZB-P, 5"X5" DRAIN, DURA-COATED CAST IRON BODY WITH BOTTOM OUTLET,

COMBINATION INVERTIBLE MEMBRANE CLAMP AND ADJUSTABLE COLLAR WITH SEEPAGE SLOTS, POLISHED

NICKLE BRONZE, LIGHT DUTY, INVERTER STRAINER WITH TRAP PRIMER CONNECTION. PROVIDE TRAP PRIMER

WITH SLOAN VBF-72-A WITH VACUUM BREAKER FROM CLOSIEST WATER CLOSET FLUSHOMETER.

5.

FLOOR DRAINFD-1 3"PROVIDE TRAP PRIMER.

1/2" --1 1/2"

PROVIDE CLEANOUTS WITH BRASS CAPS AND SCREWS SAME SIZE AS PIPE AT THE ENDS OF BRANCHES ON SOIL

AND WASTE PIPING, AND IN SUCH OTHER PORTIONS OF THE PIPING WHERE RUN IS OVER 50'-0". BRASS CLEANOUTS

SHALL BE SOLID NUT CONSTRUCTION

10.

JANITOR'S SINKS-1 2 - 1/2"

11.

1/2"

DRINKING FOUNTAINDF-1 2 1/2"1 1/2" -

-

-

SHOWER SHO-1: PROVIDE SHOWER HEAD KOHLER K-72425 WITH BRASS THERMOSTATIC VALVE TRIM SET

K-T10940 WITH BLADE HANDLE AND ACCESSORIES, AND SHOWER COLUMN K-45904. SHOWER SHALL BE

RESTRICTED TO 2.0 GPM.

12.

SINK, ADA COMPLIANT (S-2): PROVIDE COUNTER TOP 18-GAUGE, SEAMLESS FORMED SINGLE COMPARTMENT,

STAINLESS STEEL SINK, UNDER-MOUNT ELKAY 'ELUHAD281645', 31"X22"X4 1/5" DEEP, SATIN DECK FINISH, LUSTER

BASIN FINISH WITH UNDERCOATING, OFF-CENTERED REAR CONNECTION AND ONE CENTERED FAUCET HOLE,

ADA COMPLIANT AND SHALL MEET ASME A112.19.3/CSA B45.4, ICC/ANSI A117.1. PROVIDE KOHLER 'PURIST' K-7507,

ADA COMPLIANT, ONE-PIECE, SELF CONTAINED CERAMIC DISC VALVE ALLOW BOTH VOLUME AND TEMPERATURE

CONTROL, TEMPERATURE MEMORY, HIGH-TEMPERATURE LIMIT SETTING. METAL LEVER OPERATION HANDLE,

DECK MOUNTED, INTEGRAL VACUUM BREAKER, 8" SWING SPOUT REACH WITH ROTATING SPOUT, 1.8 GPM

MAXIMUM FLOW RATE. FAUCET SHALL MEET THE FOLLOWING CODES AND STANDARDS: ASME A112.18.1/CSA

B125.1, ACC/ANSI A117, NSF 61 AND CALIFORNIA AB1953 'LEAD-FREE' REQUIREMENTS. PROVIDE CHROME FINISH,

1-1/2" TAILPIECE, BRASS CRAFT NO. 0010 1-1/2" P-TRAP, BRASS CRAFT NO. R1512A CHROME FLEXIBLE SUPPLIES,

TRUEBRO HANDI-LAV GUARD INSULATION KIT.

13.

BAR SINKS-2 2 - 1/2"1/2" -

JANITOR'S SINK S-1:

.FLOOR MOUNTED MOP SINK 'FLORWELL' SERVICE SINK ENAMELED CAST IRON, 3" OUTLET, CORNER MODEL WITH

7745.811 REMOVABLE VINYL RIM GUARD, 28"X28"X13" DEEP BOWL, 7721.038 FLAT GRID DRAIN MEETS OR

EXCEEDS THE FOLLOWING SPECIFICATIONS ASME A1112.19.1 FOR CAST IRON PLUMBING FIXTURES. PROVIDE

AMERICAN STANDARD MODEL EXPOSED YOKE WALL-MOUNT UTILITY FAUCET WITH TOP BRACE 6" CAST BRASS

SPOUT WITH VACUUM BREAKER, CERAMIC DISC VALVE, INTEGRAL SUPPLY STOPS, OFFSET SHANKS WITH

INTEGRAL CHECK VALVES, VANDAL-RESISTANT, METAL LEVER HANDLES, BUCKET HOOK, 3/4" THREADED HOSE

END, 1/2" NPT FEMALE INLETS, ADJUSTABLE CENTERS-TO-CENTERS: 6" - 10".

LAVATORY: LAV-1

PROVIDE AMERICAN STANDARD DECORUM 9024.011EC, CENTER HOLE WITH RIGHT SOAP DISPENSER HOLE, WALL-HUNG

LAVATORY, VITREOUS CHINA 20" X 18" WITH RIGHT HAND BOBNICK B8263.18 SOAP DISPENSER WITH STARTER KIT SOAP

REFILL AND BATTERY PACK. PROVIDE SERIN SENSOR-OPERATED FAUCET, ADA COMPLIANT, INFRARED SENSOR

OPERATED ELECTRONIC, 24VAC HARDWIRED AC POWERED, 0.5 GPM, CHROME FINISH, 120 VAC/24 VAC TRANSFORMER,

VANDAL-RESISTANT, SOLID BRASS CONSTRUCTION. 'LEAD-FREE' CSA AB1953-2006, CAL GREEN WITH THERMAL

CONTROLLER /MIXING #2605XTMV-1070 WITH STAINLESS STEEL FLEXIBLE HOSES, DISCHARGE ON DEMAND UP TO 60

SECONDS WHILE ACTIVATED. PROVIDE TAILPIECE, BRASS CRAFT NO. 0010 1-1/4" P-TRAP, BRASS CRAFT NO. R1512A

CHROME FLEXIBLE SUPPLIES, TRUEBRO HANDI-LAV GUARD INSULATION KIT. PROVIDE NEW CONCEALED FIXTURE

SUPPORT ARMS OR WALL BRACKETS AS RECOMMENDED BY THE FIXTURE MANUFACTURER. PROVIDE POWER KIT WITH

TRANSFORMER.

14. SINK S-3: DROP-IN SINK LAB FIXTURE 16-GA STAINLESS STEEL TYPE 316, POLISHED FINISH, FULLY COATED

UNDERSIDE BACK-RIGHT DRAIN CENTER. FURNISH (1)28"x16"X12"DEEP SINK 'JUST' SLXD-2131-16-GR . FAUCET

SHALL BE ZURN FAUCET MODEL Z826C4-XL, DECK MOUNT, COMBINATION HOT AND COLD WATER, WITH 8"

RIGIS/SWING SPOUT, LABORATORY SERRATED NOZZLE, VANDAL PROOF 4" WRISTBLADE FOR HANDLE WITH HOT

AND COLD SUPPLY, LOW COMPRESSION OPERATING CARTRIDGE, TEFLON SEAL RATED AT 150 PSI WORKING

PRESSURE, ATMOSPHERIC VACUUM BREAKER, CHROME PLATE FINISH. PROVIDE 'GLECO TRAP' PACKAGE MODEL

GT64 FOR SOLID REMOVAL.

PLUMBING FIXTURES SPECIFICATIONS

DRINKING FOUNTAIN: (ADA ACCESSIBLE) DF-1

PROVIDE ELKAY MODEL LZSTLDDWS FOUNTAINS WITH INTEGRAL BOTTLE FILLING STATION. UNIT SHALL BE

STAINLESS STEEL CONSTRUCTION WITH PLASTIC ABS ALCOVE, UNIT SHALL HAVE SENSOR-ACTIVATION WITH AN

AUTO 20-SECOND SHUT-OFF TIMER. BOTTLE FILLER SHALL PROVIDE 1.5 GPM FLOW RATE WITH LAMINAR FLOW,

INCLUDE THE 'WATERSENTRY PLUS 3000-GALLON' CAPACITY FILTER, CERTIFIED TO NSF/ANSI 42 AND 53, WITH

VISUAL MONITOR TO INDICATE WHEN REPLACEMENT IS NECESSARY. UNIT SHALL INCLUDE INTEGRATED SILVER

ION ANTI-MICROBIAL PROTECTION IN KEY AREAS. UNIT SHALL MEET ADA GUIDELINES. UNIT SHALL BE LEAD-FREE

DESIGN WHICH IS CERTIFIED TO NSF/ANSI 61 AND 372 AND MEETS FEDERAL AND STATE LOW-LEAD

REQUIREMENTS. UNIT SHALL BE CERTIFIED TO UL399 AND CAN/CSA 22.2 NO. 120. PROVIDE P-TRAP, WATER

STOPS, IN-WALL SUPPORTS MOUNTING PLATE ASSEMBLY AND HARDWARES. INSTALL PER MANUFACTURER'S

REQUIREMENTS. MODIFY EXISTING PLUMBING AND EXTEND TO THE NEW LOCATION. VERIFY SIZE AND LOCATION

OF POINT OF CONNECTION. TO EXISTING.

14.

WATER CLOSET: WC-2(ADA)

FURNISH AMERICAN STANDARD MADERA 16 1/2" "FLOWISE" NO. 3461.001, 1.28 GPF FLOOR-MOUNT, ELONGATED,

WHITE, VITREOUS CHINA, TOP SPUD, 1.28 GPF, EVERCLEAN SURFACE. FLUSH VALVE SHALL BE 1" HARD-WIRED

SELECTRONIC, 120 VAC PK00.HAC POWER SUPPLY TOP SPUD, SENSOR ACTIVATED FLUSHOMETER WITH

OVERRIDE BUTTON, NON-HOLD OPEN INTEGRAL SOLENOID OPERATOR, WITH NO VISIBLE FASTENERS,

BACK-CHECK ANGLE VALVE, VANDAL RESISTANT STOP CAP, VACUUM BREAKER. PROVIDE NEW CARRIER

SUPPORTS AND ANCHORS AS RECOMMENDED BY FIXTURE MANUFACTURER. FURNISH TOILET SEAT AND COVER,

WHITE COLOR. PROVIDE FLUSH VALVE WITH FLUSH LEVER ON THE WIDE SIDE FOR ACCESSIBLE (ADA) ACCESS.

PROVIDE POWER KIT WITH TRANSFORMER.

2.

REVISIONS

SHEET NUMBER

SHEET TITLE

N&T JOB #

ISSUE DATE

729 Heinz AvenueBerkeley, CA 94710

tel 510.542.2200fax 510.542.2201

SEAL

APPROVALS

1901 HEARST ST.

BERKELEY CA 94704

21603.00

12/19/18

# DATE DESCRIPTION

EDDIEPADILLA

274 Devonshire Street

SHOWER DRAIN FD-2 : ZURN Z415B-HD, 2" DRAIN, DURA-COATED CAST IRON BODY WITH BOTTOM OUTLET,

COMBINATION INVERTIBLE MEMBRANE CLAMP AND ADJUSTABLE COLLAR WITH SEEPAGE SLOTS, POLISHED

NICKLE BRONZE, HEAVY DUTY, INVERTER STRAINER WITH TRAP PRIMER CONNECTION. PROVIDE TRAP PRIMER

WITH SLOAN VBF-72-A WITH VACUUM BREAKER FROM CLOSIEST WATER CLOSET FLUSHOMETER.

6.

Page 3: EDDIE PADILLA - Berkeley, California · notify architect/engineer of any discrepancies found. no allowance shall be made for any expense to which the contractor may incur due to failure

1(E)LAV

(E)LAV

(E)LAV

(E)LAV

(E)WC

1

1

1

2

(E)WC

2

(E)WC

2

(E)WC

2

(E)WC

2

(E)UR3

5(E)SINK

5(E)SINK 5(E)SINK

5(E)SINK

(E)WC 2

(E)WC2

(E)LAV 1

(E)LAV1

6(E)JAN

SINK

WORKSHOP

111

STOR.

112

MECH. RM.

113

ART

SHOP

114

HALL

115

STOR.

117

ELECT.

118

STOR.

122

HALL

123

STOR.

124

125

126

REC.

127

TRASH

128

KITCHEN

129

(N) COFFEE BAR

131

DINING

ROOM

132

MULTI-PURPOSEROOM

136

STOR

138

LOUNGE

144

WOMEN

161

HALL 142

GAME ROOM B

101GAME ROOM A

102

HEALTH

ROOM

103A

TOILET105

HEALTH

OFFICE 104

HALL

106

STOR.

107

STOR.

108

ELEV

EQUIP

109

(N) MEETING RM

103B

FRONT

DESK154

ADVISORY

COUNCIL

OFFICE

155

ENTRY

143

HALL

146

ADMIN

OFC

153

DIRECTOR

OFC

147

COPY

148STOR.

149

STAFF

LOUNGE152

TOILET 151

STOR

141

STAGE

139

MTG RM

156

MEN

157

ELEV

000

OFFICE 3

116 C

5 (E)SINK

(E)LAV (TO REMAIN)

(E)DF1

5 (E)SINK

1

A

D

5

7

B

C

3 6

42

E

F

C.5

1

P2.11

FIRST FLOOR PLAN - PLUMBING DEMOLITIONscale: 1/8" = 1'-0"

1

2

6

3

4

5

DEMOLITION KEYED NOTES:

REMOVE AND DISPOSE EXISTING (E) JANITOR SINK AND ASSOCIATED

PLUMBING, SUPPORTS, ANCHORS. MODIFY PLUMBING FOR SANITARY

WASTE & VENT, HOT AND COLD WATER FOR THE NEW FLOOR MOUNTED

JANITOR SINK.

REMOVE AND DISPOSE EXISTING (E)URINAL AND ASSOCIATED

PLUMBING, SUPPORTS AND ANCHORS.

REMOVE AND DISPOSE EXISTING (E) COUNTER SINK AND ASSOCIATED ,

PLUMBING, SUPPORTS, ANCHORS. CAP PIPE BRANCHES AT BRANCH

MAIN.

REMOVE AND DISPOSE EXISTING (E) LAVATORY AND ASSOCIATED

PLUMBING, SUPPORTS, ANCHORS. MODIFY PLUMBING FOR SANITARY

WASTE & VENT, HOT AND COLD WATER FOR THE NEW LAVATORY.

REMOVE AND DISPOSE EXISTING (E) WATER CLOSET AND ASSOCIATED

PLUMBING, SUPPORTS, ANCHORS. MODIFY PLUMBING FOR SANITARY

WASTE & VENT, HOT AND COLD WATER FOR THE NEW WATER CLOSET.

REMOVE AND DISPOSE EXISTING (E) FLOOR DRAIN. MODIFY PLUMBING

FOR SANITARY WASTE & VENT FOR THE NEW FLOOR DRAIN.

REVISIONS

SHEET NUMBER

SHEET TITLE

N&T JOB #

ISSUE DATE

729 Heinz AvenueBerkeley, CA 94710

tel 510.542.2200fax 510.542.2201

SEAL

APPROVALS

1901 HEARST ST.

BERKELEY CA 94704

21603.00

12/19/18

# DATE DESCRIPTION

EDDIEPADILLA

274 Devonshire Street

7 REMOVE AND DISPOSE EXISTING (E) DRINKING FOUNTAIN AND

ASSOCIATED PLUMBING, SUPPORTS AND ANCHORS.

Page 4: EDDIE PADILLA - Berkeley, California · notify architect/engineer of any discrepancies found. no allowance shall be made for any expense to which the contractor may incur due to failure

OPEN TO BELOW

1

A

D

5

7

B

C

3 6

42

E

F

1

1

2

2

4 POC. CONNECT TO

EXISTING IN

MECHANICAL ROOM

POC. CONNECT TO

EXISTING IN THE

KITCHEN.

EXISTING GAS METER AND

PRESSURE REGULATOR

TO REMAIN.

4

4

4

4

4 4

4

5

ELEV

000

LIBRARY

202

WOMEN

203

SHW

204

JAN

205

MEN

206

SHW

207

HALL

208

STOR.

209

CLASSROOM C

210

CLASSROOM B

211

CLASSROOM A

212

HALL

201

1

P2.12

SECOND FLOOR PLAN -PLUMBING DEMOLITIONscale: 1/8" = 1'-0"

DEMOLITION KEYED NOTES:REMOVE AND DISPOSE EXISTING (E) LAVATORY AND ASSOCIATED

PLUMBING, SUPPORTS, ANCHORS. MODIFY PLUMBING FOR SANITARY

WASTE & VENT, HOT AND COLD WATER FOR THE NEW LAVATORY.

REMOVE AND DISPOSE EXISTING (E) WATER CLOSET AND ASSOCIATED

PLUMBING, SUPPORTS, ANCHORS. MODIFY PLUMBING FOR SANITARY

WASTE & VENT, HOT AND COLD WATER FOR THE NEW WATER CLOSET.

REMOVE AND DISPOSE EXISTING (E) FLOOR DRAIN. MODIFY PLUMBING

FOR SANITARY WASTE & VENT FOR THE NEW FLOOR DRAIN.3

2

1

REMOVE AND DISPOSE EXISTING GAS PIPING ON ROOF INCLUDING

ASSOCIATED VALVES, PIPE SUPPORT AND SUPPORT ANCHORS.

REROUTE GAS PIPING IN THE BUILDING CEILING SPACE AS SHOWN ON

P2.21. VERIFY EXACT PIPE SIZE AND LOCATION AT POINT OF

CONNECTION (POC).

4

REMOVE AND DISPOSE EXISTING (E) DRINKING FOUNTAIN AND

ASSOCIATED PLUMBING, SUPPORTS, ANCHORS. MODIFY SUPPORT AND

PLUMBING FOR SANITARY WASTE & VENT, HOT AND COLD WATER FOR

THE NEW DRINKING FOUNTAIN.

5

REVISIONS

SHEET NUMBER

SHEET TITLE

N&T JOB #

ISSUE DATE

729 Heinz AvenueBerkeley, CA 94710

tel 510.542.2200fax 510.542.2201

SEAL

APPROVALS

1901 HEARST ST.

BERKELEY CA 94704

21603.00

12/19/18

# DATE DESCRIPTION

EDDIEPADILLA

274 Devonshire Street

Page 5: EDDIE PADILLA - Berkeley, California · notify architect/engineer of any discrepancies found. no allowance shall be made for any expense to which the contractor may incur due to failure

2

7

2

2

3

3

3

3

6

3

3

5

3

2

2

2

6

6

2

3

32

10

10

10

10

10

10

10

10

10

UP

1

1

A A

D

5

7

7

B B

C

3 6

42

2

E

F

C.5

UP

UP

11S-3 11S-3

1

7

12

1

WORKSHOP

111

STOR.

112

MECH. RM.

113

ART

SHOP

114

HALL

115

ADMIN

116 A

STOR.

117

ELECT.

118

MANAGERS OFC

119

STOR.

122

HALL

123STOR.

124

FREEZER

125

REF.

126

REC.

127

TRASH

128

KITCHEN

129

(N) COFFEE BAR

131

DINING

ROOM

132

STOR.

133

STOR.

134STOR.

135

STOR.

137

MULTI-PURPOSEROOM

136

STOR138

LOUNGE

144

WOMEN

161

HALL 142

GAME ROOM B

101GAME ROOM A

102

HEALTH

ROOM

103A

TOILET105

HEALTH

OFFICE 104

HALL

106STOR.

107

STOR.

108

ELEV

EQUIP

109

(N) MEETING RM

103B

FRONT

DESK

154

ADVISORY

COUNCIL

OFFICE

155

ENTRY

143

HALL

146

ADMIN

OFC

153

DIRECTOR

OFC

147

COPY

148STOR.

149

STAFF

LOUNGE152

TOILET151

STOR

141

STAGE

139

MTG RM 156

MEN

157

ELEV

000

OFFICE 2

116 B

OFFICE 3

116 C

JAN2

1

P2.21

FIRST FLOOR PLAN - PLUMBINGscale: 1/8" = 1'-0"

CONSTRUCTION KEYED NOTES:EXISTING PLUMBING TO REMAIN.

PROVIDE NEW FLOOR DRAIN. MODIFY AND EXTEND EXISTING PLUMBING

AS REQUIRED FOR COLD WATER, SANITARY WASTE DRAIN AND VENTS.

PROVIDE TRAP PRIMER. VERIFY EXISTING PIPING CONNECTION

CONDITION, LOCATION AND SIZES. PROVIDE SUPPORT AND ANCHORS.

SEE DRAWING P3.00 FOR SCHEDULED REQUIREMENTS AND PIPING

CONNECTIONS.

PROVIDE NEW BAR SINK S-1. MODIFY AND EXTEND EXISTING PLUMBING

AS REQUIRED FOR HOT & COLD WATER, SANITARY WASTE DRAIN AND

VENTS. VERIFY EXISTING PIPING CONNECTION CONDITION, LOCATION

AND SIZES. PROVIDE SUPPORT AND ANCHORS. SEE DRAWING P3.01 FOR

SCHEDULED REQUIREMENTS AND PIPING CONNECTIONS.

PROVIDE NEW SHOWER AND DRAIN. MODIFY AND EXTEND EXISTING

PLUMBING AS REQUIRED FOR HOT AND COLD WATER, SANITARY WASTE

DRAIN AND VENTS. VERIFY EXISTING PIPING CONNECTION CONDITION,

LOCATION AND SIZES. PROVIDE SUPPORT AND ANCHORS. SEE DRAWING

P1.01 FOR SCHEDULED REQUIREMENTS AND PIPING CONNECTIONS.

PROVIDE NEW WALL MOUNTED LAVATORY. MODIFY AND EXTEND

EXISTING PLUMBING AS REQUIRED FOR HOT AND COLD WATER,

SANITARY WASTE DRAIN AND VENTS. VERIFY EXISTING PIPING

CONNECTION CONDITION, LOCATION AND SIZES. PROVIDE SUPPORT

AND ANCHORS. SEE DRAWING P3.0 FOR SCHEDULED REQUIREMENTS

AND PIPING CONNECTIONS.

PROVIDE NEW WALL MOUNTED URINAL. MODIFY AND EXTEND EXISTING

PLUMBING AS REQUIRED FOR COLD WATER, SANITARY WASTE DRAIN

AND VENTS. VERIFY EXISTING PIPING CONNECTION CONDITION,

LOCATION AND SIZES. PROVIDE SUPPORT AND ANCHORS. SEE DRAWING

P3.00 FOR SCHEDULED REQUIREMENTS AND PIPING CONNECTIONS.

PROVIDE NEW WALL MOUNTED WATER CLOSET RESTROOM. MODIFY

AND EXTEND EXISTING PLUMBING AS REQUIRED FOR COLD WATER,

SANITARY WASTE DRAIN AND VENTS. VERIFY EXISTING PIPING

CONNECTION CONDITION, LOCATION AND SIZES. PROVIDE SUPPORT

AND ANCHORS. SEE DRAWING P3.00 FOR SCHEDULED REQUIREMENTS

AND PIPING CONNECTIONS.

REPLACE EXISTING FLOOR DRAIN WITH ZURN DECK RECEPTOR MODEL

Z127. MODIFY EXISTING PLUMBING AS NECESSARY.

PROVIDE NEW ADA COMPLIANT HI-LO DRINKING FOUNTAIN COMPLETE

WITH WALL BRACKET AND SUPPORTS. MODIFY AND EXTEND EXISTING

PLUMBING AS REQUIRED FOR COLD WATER, SANITARY WASTE DRAIN

AND VENTS. VERIFY EXISTING PIPING CONNECTION CONDITIONS,

LOCATION AND SIZES. SEE DRAWING P3.0 FOR SCHEDULED

REQUIREMENTS AND PIPING CONNECTIONS. REFER TO ARCHITECTURAL

DRAWING FOR ADA LAVATORY FOR EXACT LOCATION AND MOUNTING

HEIGHT. ADJUST PIPING AND SUPPORT ACCORDINGLY.

REMOVE GAS PIPING DISTRIBUTION ON ROOF. REROUTE EXISTING GAS

UNDER THE ROOF EAVE AROUND THE BUILDINGSTRUCTURE.

PROVIDE NEW DROP-IN SINK S-3. MODIFY AND EXTEND EXISTING

PLUMBING AS REQUIRED FOR HOT & COLD WATER, SANITARY WASTE

DRAIN AND VENTS. VERIFY EXISTING PIPING CONNECTION CONDITION,

LOCATION AND SIZES. PROVIDE SUPPORT AND ANCHORS. SEE DRAWING

P3.01 FOR SCHEDULED REQUIREMENTS AND PIPING CONNECTIONS.

PROVIDE 'GLECO TRAP' PACKAGE MODEL GT64 FOR SOLID REMOVAL.

_______1

EXISTING HOSE BIBB IN TRASH ENCLOSURE TO REMAIN.

REVISIONS

SHEET NUMBER

SHEET TITLE

N&T JOB #

ISSUE DATE

729 Heinz AvenueBerkeley, CA 94710

tel 510.542.2200fax 510.542.2201

SEAL

APPROVALS

1901 HEARST ST.

BERKELEY CA 94704

21603.00

12/19/18

# DATE DESCRIPTION

EDDIEPADILLA

274 Devonshire Street

Page 6: EDDIE PADILLA - Berkeley, California · notify architect/engineer of any discrepancies found. no allowance shall be made for any expense to which the contractor may incur due to failure

SHO-1

3

WC-1

ADA

LAV-1

ADA

LAV-1

ADA

2

4

4

2

3

(E)JAN

SINK1

7

OPEN TO BELOW

4

2"FD 9

2"FD-2 9

2"FD-2

9

2"FD 9

2"WCO

2"W, 1"CW

(E)4"W AND

(4) VTR

2"V

AP

1" SHUTOFF

VALVE

2"FCO

2"FCO 2"W

2"W

2"W

2"W

1 1/2"V

1 1/2"V

1 1/2"V

1 1/2"V

2"W

1

P2.22

SECOND FLOOR PARTIAL PLAN - PLUMBINGscale: 1/4" = 1'-0"

CONSTRUCTION KEYED NOTES:EXISTING PLUMBING TO REMAIN.

PROVIDE NEW WALL MOUNTED LAVATORY. MODIFY AND EXTEND

EXISTING PLUMBING AS REQUIRED FOR HOT AND COLD WATER,

SANITARY WASTE DRAIN AND VENTS. VERIFY EXISTING PIPING

CONNECTION CONDITION, LOCATION AND SIZES. PROVIDE SUPPORT

AND ANCHORS. SEE DRAWING P3.0 FOR SCHEDULED REQUIREMENTS

AND PIPING CONNECTIONS.

PROVIDE NEW WALL MOUNTED WATER CLOSET RESTROOM. MODIFY

AND EXTEND EXISTING PLUMBING AS REQUIRED FOR COLD WATER,

SANITARY WASTE DRAIN AND VENTS. VERIFY EXISTING PIPING

CONNECTION CONDITION, LOCATION AND SIZES. PROVIDE SUPPORT

AND ANCHORS. SEE DRAWING P3.00 FOR SCHEDULED REQUIREMENTS

AND PIPING CONNECTIONS.

PROVIDE NEW SHOWER AND DRAIN. MODIFY AND EXTEND EXISTING

PLUMBING AS REQUIRED FOR HOT AND COLD WATER, SANITARY WASTE

DRAIN AND VENTS. VERIFY EXISTING PIPING CONNECTION CONDITION,

LOCATION AND SIZES. PROVIDE SUPPORT AND ANCHORS. SEE DRAWING

P1.01 FOR SCHEDULED REQUIREMENTS AND PIPING CONNECTIONS.

PROVIDE NEW FLOOR MOUNTED JANITOR SERVICE SINK. MODIFY AND

EXTEND EXISTING PLUMBING AS REQUIRED FOR HOT AND COLD WATER,

SANITARY WASTE DRAIN AND VENTS. VERIFY EXISTING PIPING

CONNECTION CONDITION, LOCATION AND SIZES. PROVIDE SUPPORT

AND ANCHORS. SEE DRAWING P3.0 FOR SCHEDULED REQUIREMENTS

AND PIPING CONNECTIONS.

EXISTING JANITOR SINK TO REMAIN.

REMOVE AND DISPOSE EXISTING DRINKING FOUNTAIN. PROVIDE NEW

ADA COMPLIANT HI-LO DRINKING FOUNTAIN COMPLETE WITH WALL

BRACKET AND SUPPORTS. MODIFY AND EXTEND EXISTING PLUMBING

AS REQUIRED FOR COLD WATER, SANITARY WASTE DRAIN AND VENTS.

VERIFY EXISTING PIPING CONNECTION CONDITIONS, LOCATION AND

SIZES. SEE DRAWING P3.0 FOR SCHEDULED REQUIREMENTS AND PIPING

CONNECTIONS. REFER TO ARCHITECTURAL DRAWING FOR ADA

LAVATORY FOR EXACT LOCATION AND MOUNTING HEIGHT. ADJUST

PIPING AND SUPPORT ACCORDINGLY.

PROVIDE NEW WALL MOUNTED URINAL RESTROOM. MODIFY AND

EXTEND EXISTING PLUMBING AS REQUIRED FOR COLD WATER,

SANITARY WASTE DRAIN AND VENTS. VERIFY EXISTING PIPING

CONNECTION CONDITION, LOCATION AND SIZES. PROVIDE SUPPORT

AND ANCHORS. SEE DRAWING P3.00 FOR SCHEDULED REQUIREMENTS

AND PIPING CONNECTIONS.

PROVIDE NEW FLOOR DRAIN. MODIFY AND EXTEND EXISTING PLUMBING

AS REQUIRED FOR SANITARY WASTE DRAIN AND VENTS. PROVIDE 3/8"

TRAP PRIMER. CONNECT TO NEAREST WATER CLOSET FLUSH VALVE

WITH SLOAN VBF-72-A BREAKER TRAP PRIMER. PROVIDE SUPPORT AND

ANCHORS. SEE DRAWING P1.01 FOR SCHEDULED REQUIREMENTS AND

PIPING CONNECTIONS.

REVISIONS

SHEET NUMBER

SHEET TITLE

N&T JOB #

ISSUE DATE

729 Heinz AvenueBerkeley, CA 94710

tel 510.542.2200fax 510.542.2201

SEAL

APPROVALS

1901 HEARST ST.

BERKELEY CA 94704

21603.00

12/19/18

# DATE DESCRIPTION

EDDIEPADILLA

274 Devonshire Street

Page 7: EDDIE PADILLA - Berkeley, California · notify architect/engineer of any discrepancies found. no allowance shall be made for any expense to which the contractor may incur due to failure

LAV-12

WC-1

WC-1( ADA)

DF-1

UR-1

LAV-12

3

WC-1

WC-1

3

3

8

LAV-1 2

LAV-1 2

WC-13

WC-13

5

WC-1

ADA3

7

3"W

2"WCO

4"VTR

2"WCO

3"FCO

3"W

4"WCO

2 1/2"V2 1/2"V

2"CW, 3/4"HW2"CW, 3/4"HW

2"CW, 4"W, 2 12"V

2"CW, 4"W, 2 12"V

3"FD3"FD

3"3"2"V 2"V 44

HA-1 9

AP

HB-110HB-1 10

1/2"CW, 1/2"HW (TYP)

3"FCO

1

P3.01

FIRST FLOOR MAIN RESTROOM PLAN - PLUMBINGscale: 1/4" = 1'-0"

CONSTRUCTION KEYED NOTES:EXISTING PLUMBING TO REMAIN.

PROVIDE NEW FLOOR DRAIN. MODIFY AND EXTEND EXISTING PLUMBING

AS REQUIRED SANITARY WASTE DRAIN AND VENTS. PROVIDE TRAP

PRIMERSANITARY WASTE DRAIN AND VENTS. PROVIDE 3/8" TRAP

PRIMER. CONNECT TO NEAREST WATER CLOSET FLUSH VALVE WITH

SLOAN VBF-72-A BREAKER TRAP PRIMER.PROVIDE SUPPORT AND

ANCHORS. SEE DRAWING P1.01 FOR SCHEDULED REQUIREMENTS AND

PIPING CONNECTIONS.

PROVIDE NEW WALL MOUNTED LAVATORY. MODIFY AND EXTEND

EXISTING PLUMBING AS REQUIRED FOR HOT AND COLD WATER,

SANITARY WASTE DRAIN AND VENTS. VERIFY EXISTING PIPING

CONNECTION CONDITION, LOCATION AND SIZES. PROVIDE SUPPORT

AND ANCHORS. SEE DRAWING P1.01 FOR SCHEDULED REQUIREMENTS

AND PIPING CONNECTIONS.

PROVIDE NEW WALL MOUNTED URINAL. MODIFY AND EXTEND EXISTING

PLUMBING AS REQUIRED FOR COLD WATER, SANITARY WASTE DRAIN

AND VENTS. VERIFY EXISTING PIPING CONNECTION CONDITION,

LOCATION AND SIZES. PROVIDE SUPPORT AND ANCHORS. SEE DRAWING

P1.01 FOR SCHEDULED REQUIREMENTS AND PIPING CONNECTIONS.

PROVIDE NEW WALL MOUNTED WATER CLOSET RESTROOM. MODIFY

AND EXTEND EXISTING PLUMBING AS REQUIRED FOR COLD WATER,

SANITARY WASTE DRAIN AND VENTS. VERIFY EXISTING PIPING

CONNECTION CONDITION, LOCATION AND SIZES. PROVIDE SUPPORT

AND ANCHORS. SEE DRAWING P1.01 FOR SCHEDULED REQUIREMENTS

AND PIPING CONNECTIONS. PROVIDE NARROW WATER CLOSET

CARRIER ZURN ZN1201-ND4. VERIFY PIPE CHASE SPACE.

PROVIDE NEW ADA COMPLIANT HI-LO DRINKING FOUNTAIN COMPLETE

WITH WALL BRACKET AND SUPPORTS. MODIFY AND EXTEND EXISTING

PLUMBING AS REQUIRED FOR COLD WATER, SANITARY WASTE DRAIN

AND VENTS. VERIFY EXISTING PIPING CONNECTION CONDITIONS,

LOCATION AND SIZES. SEE DRAWING P1.01 FOR SCHEDULED

REQUIREMENTS AND PIPING CONNECTIONS. REFER TO ARCHITECTURAL

DRAWING FOR ADA LAVATORY FOR EXACT LOCATION AND MOUNTING

HEIGHT. ADJUST PIPING AND SUPPORT ACCORDINGLY.

PROVIDE WATER HAMMER ARRESTORS(HA-1). PROVIDE

12"X12" STAINLESS STEEL ACCESS PANEL(AP). SEE

ARCHITECTURAL DRAWINGS FOR DETAILS.

PROVIDE NEW WALL & FLOOR CLEANOUTS WITH ACCESS

PANEL. SEE DRAWING P1.01 FOR SCHEDULED

REQUIREMENTS.

PROVIDE NEW SHUTOFF VALVES FOR CW AND HW.

PROVIDE NEW 12"X12" ACCESS PANEL(AP). SHUTOFF

VALVES.

PROVIDE HOSE BIBB IN RECESS BOX. PROVIDE 12"X12"

STAINLESS STEEL ACCESS PANEL(AP).

REVISIONS

SHEET NUMBER

SHEET TITLE

N&T JOB #

ISSUE DATE

729 Heinz AvenueBerkeley, CA 94710

tel 510.542.2200fax 510.542.2201

SEAL

APPROVALS

1901 HEARST ST.

BERKELEY CA 94704

21603.00

12/19/18

# DATE DESCRIPTION

EDDIEPADILLA

274 Devonshire Street