7
1 EcoAir Valve LIT-12013449 April 2021 Product Bulletin Overview The EcoAir Valve is a powerful, ultra-low pressure drop valve designed with airflow sensing and debris-proof technology. This valve provides safety, reliability, and energy efficiency for critical environment HVAC design. The EcoAir Valve can be used in tandem with Venturi Valves in healthcare and laboratory spaces. The valve uses the EcoAir Valve Module (EVM) to enable compatibility with all controllers independent of their protocol. The unique blade design results in high turn-down ratios with more resolute control at the near closed position. The design also protects sensors from getting blocked and does not require an access panel to clean the valve. The valve provides accurate airflow measurement within the specified ± 5%. Features and benefits Feature Benefit Fast-acting actuator The ACT-FA-9001 smart actuator provides performance data and enhances efficiency. Air fins Unique air fin design delivers accuracy across a wide pressure range, instantly delivering the right amount of airflow. Robust gasket guard Protects the pressure sensing mechanism, ensuring precise airflow control. Debris-proof technology The access port and the internal components of the valve do not require cleaning. No straight duct requirement Provides duct design and valve installation flexibility in all orientations.

EcoAir Valve Product Bulletin - Johnson Controls

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

1

EcoAir ValveLIT-12013449

April 2021Product Bulletin

OverviewThe EcoAir Valve is a powerful, ultra-low pressure drop valve designed with airflow sensing and debris-proof technology. This valve provides safety, reliability, and energy efficiency for critical environment HVAC design.

The EcoAir Valve can be used in tandem with Venturi Valves in healthcare and laboratory spaces. The valve uses the EcoAir Valve Module (EVM) to enable compatibility with all controllers independent of their protocol.

The unique blade design results in high turn-down ratios with more resolute control at the near closed position. The design also protects sensors from getting blocked and does not require an access panel to clean the valve. The valve provides accurate airflow measurement within the specified ± 5%.

Features and benefits

Feature BenefitFast-acting actuator The ACT-FA-9001 smart actuator provides performance data and enhances efficiency.Air fins Unique air fin design delivers accuracy across a wide pressure range, instantly delivering the right

amount of airflow.Robust gasket guard Protects the pressure sensing mechanism, ensuring precise airflow control.Debris-proof technology The access port and the internal components of the valve do not require cleaning.No straight duct requirement Provides duct design and valve installation flexibility in all orientations.

LIT-120134492

Table 1: EcoAir Valve maximum flow rate at in. W.C. duct static pressure

Notes: • Maximum flow rate accuracy is ± 5% or 10 cfm. Use the greater value. • 8 in. valve flow setpoints below 30 cfm: Move the valve to full closed shut-off position.• 10 in. valve flow setpoints below 100 cfm: Move the valve to full closed shut-off position. • 12 in. valve flow setpoints below 150 cfm: Move the valve to full closed shut-off position.• 14 in. valve flow setpoints below 200 cfm: Move the valve to full closed shut-off position.• EcoAir valves come with a shut off gasket.• All product specifications and data are subject to change without notice to improve reliability, function or design, or

otherwise.

Unit Valve sizes Max CFM at 100% open duct static pressure (in. W.C.)

Diameter Gang Min 0.05 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2

CFM

8in 1 30 200 280 400 490 575 650 720 780 840 900 945 1000 1040 1090 1130 1180 1220 1260 1300 1340 1980

10in

1 100 530 770 1100 1345 1565 1745 1905 2035 2180 2315 2435 2560 2580 2670 2770

TBD

2 200 1060 1540 2200 2690 3130 3490 3810 4070 4360 4630 4870 5120 5160 5340 5540

3 300 1590 2310 3300 4035 4695 5235 5715 6105 6540 6945 7305 7680 7740 8010 8310

4 400 2120 3080 4400 5380 6260 6980 7620 8140 8720 9260 9740 10240 10320 10680 11080

6 600 3180 4620 6600 8070 9390 10470 11430 12210 13080 13890 14610 15360 15480 16020 16620

12in

1 150 800 1160 1650 2030 2380 2700 2950 3150 3430 3590 3800

TBD

2 300 1600 2320 3300 4060 4760 5400 5900 6300 6860 7180 7600

3 450 2400 3480 4950 6090 7140 8100 8850 9450 10290 10770 11400

4 600 3200 4640 6600 8120 9520 10800 11800 12600 13720 14360 15200

6 900 4800 6960 9900 12180 14280 16200 17700 18900 20580 21540 22800

14in

1 200 1280 1880 2630 3200 3800 4250 4650

TBD

2 400 2560 3760 5260 6400 7600 8500 9300

3 600 3840 5640 7890 9600 11400 12750 13950

4 800 5120 7520 10520 12800 15200 17000 18600

6 1200 7680 11280 15780 19200 22800 25500 27900

m3/hr

8in 1 51 340 476 680 833 977 1104 1223 1325 1427 1529 1606 1699 1767 1852 1920 2005 2073 2141 2209 2277 3364

10in

1 170 900 1308 1869 2285 2659 2965 3237 3457 3704 3933 4137 4349 4383 4536 4706

TBD

2 340 1801 2616 3738 4570 5318 5930 6473 6915 7408 7866 8274 8699 8767 9073 9413

3 510 2701 3925 5607 6856 7977 8894 9710 10372 11112 11800 12411 13048 13150 13609 14119

4 680 3602 5233 7476 9141 10636 11859 12946 13830 14815 15733 16548 17398 17534 18145 18825

6 1019 5403 7849 11213 13711 15954 17789 19420 20745 22223 23599 24823 26097 26301 27218 28238

12in

1 255 1359 1971 2803 3449 4044 4587 5012 5352 5828 6099 6456

TBD

2 510 2718 3942 5607 6898 8087 9175 10024 10704 11655 12199 12912

3 765 4078 5913 8410 10347 12131 13762 15036 16056 17483 18298 19369

4 1019 5437 7883 11213 13796 16175 18349 20048 21408 23310 24398 25825

6 1529 8155 11825 16820 20694 24262 27524 30072 32111 34966 36597 38737

14in

1 340 2175 3194 4468 5437 6456 7221 7900

TBD

2 680 4349 6388 8937 10874 12912 14442 15801

3 1019 6524 9582 13405 16310 19369 21662 23701

4 1359 8699 12777 17874 21747 25825 28883 31602

6 2039 13048 19165 26810 32621 38737 43325 47402

LIT-120134493

Unit size Weight Weight Valve diameter Valve length (A)

Valve height (B)

Collar width (C)

Collar height (D)Aluminium SS316

lb kg lb kg in. mm in. mm in. mm in. mm in. mm8in 1 20 9 25 11 7.88 200 23 584 13 330 N/A10in 1 25 11 30 14 9.74 247 26 660 16 406 N/A

2 50 23 60 27 N/A N/A 30 762 16 406 22.63 575 11.44 2913 75 34 90 41 N/A N/A 30 762 16 406 33.75 857 11.44 2914 110 50 120 54 N/A N/A 30 762 32 813 22.63 575 22.88 5816 150 68 180 82 N/A N/A 30 762 32 813 33.75 857 22.88 581

12in 1 30 14 40 18 11.68 297 26.8 681 18 457 N/A2 60 27 80 36 N/A N/A 30.8 782 20.5 521 26.75 679 13.5 3433 90 41 120 54 N/A N/A 30.8 782 20.5 521 40 1016 13.5 3434 120 54 160 73 N/A N/A 30.8 782 34 864 26.75 679 27 6866 180 82 240 109 N/A N/A 30.8 782 34 864 40 1016 27 686

14in 1 40 18 50 23 13.62 346 30 762 20 508 N/A2 80 36 100 45 N/A N/A 34 864 23.5 597 32.15 817 16 4063 120 54 150 68 N/A N/A 34 864 23.5 597 48.3 1227 16 4064 160 73 200 91 N/A N/A 34 864 39 991 32.15 817 32 8136 200 91 300 136 N/A N/A 34 864 39 991 48.3 1227 32 813

Note: All product specifications and data are subject to change without notice to improve reliability, function or design, or otherwise.

Table 3: Dimensions and weights

Notes: • Turn down ratios are based on the cut-off cfm range for each valve size.• All product specifications and data are subject to change without notice to improve reliability, function or design, or

otherwise.

Table 2: EcoAir Valve turn down ratios at in. W.C. duct static pressure

Diameter Turn down ratios at in. W.C. duct static pressure0.05 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2

8in 7 9 13 16 19 22 24 26 28 30 32 33 35 36 38 39 41 42 43 45 6610in 5 8 11 13 16 17 19 20 22 23 24 26 26 27 28 TBD12in 5 8 11 14 16 18 20 21 23 24 25 TBD14in 6 9 13 16 19 21 23 TBD

LIT-120134494

C

D

A

Figure 1: Dual ganged valve

C

D

A

Figure 2: Triple ganged valve

LIT-120134495

C

A

D

Figure 3: Quad ganged valve

C

D

A

Figure 4: Hexa ganged valve

LIT-120134496

Feature Code letter or number and description

Product code number example:TEN10ANFA

Brand TE = Triatek EcoAir TEGanged N = Not ganged

2 = Dual3 = Triple4 = Quad6 = HexaF = Flanged

N

Size 08 = 8 in.10 = 10 in.12 = 12 in.14 = 14 in.

10

Material A = AluminiumS = 316 Stainless steel

A

Insulation N = No insulationI = Insulated

N

Actuator FA = Fast acting FA

Technical specificationsElectrical Input power 24 VAC ± 20% 50 Hz/60 Hz

Analog inputs 0 V to 10 V cfm select signal

Analog outputs 0 cfm to 10 V cfm feedback signal4 mA to 20 mA actuator control

Network COM ports 9600 baud RS485

Performance Accuracy ± 5% or ± 10 cfm whichever is greater

Speed of response < = 5 seconds

Operating pressure 0.1 in. W.G - 5 in. W.G. differential pressure across valve

Failure modes Fail to close, fail to open

Operating temperature 0°F to 122°F (-17.78°C to 50°C)

Storage temperature -22°F to 122°F (-30°C to 50°C)

Humidity 0% to 90%

Construction Valve housing Aluminum 14 gauge or 316 stainless steel 18 gauge

Shaft SS316

Shaft bearings PTFE

Seal Neoprene

Air fins Polypropylene

Table 4: Ordering guide

This product is covered by a limited warranty. Contact your representative/branch for more details.

Software terms

Product warranty

Contact informationContact your local branch office: www.johnsoncontrols.com/locationsContact Johnson Controls: www.johnsoncontrols.com/contact-us

Use of the software that is in (or constitutes) this product, or access to the cloud, or hosted services applicable to this product, if any, is subject to applicable end-user license, open-source software information and other terms set forth at www.johnsoncontrols.com/techterms. Your use of this product constitutes an agreement to such terms.

North American Emissions Compliance

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of theFCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipmentis operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, ifnot installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.Operation of this equipment in a residential area may cause harmful interference, in which case users will be required tocorrect the interference at their own expense.

United States

CanadaThis Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.

Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada