TRAINING
COOLING TOWERS WATER TREATMENTS
1Dr. Ing. Carlo Lebrun 1Dr.Ing. Carlo LebrunCooling Tower Water Treatments
COOLING TOWERS
Source: Wikipedia
Cooling Tower Water Treatments 2Dr.Ing. Carlo Lebrun
PROCESS DIAGRAM & WATER MATERIAL BALANCE
Cooling Tower Water Treatments 3Dr.Ing. Carlo Lebrun
Drawing source: Wikipedia
KEY OPERATING PARAMETERS
- Cooling tower inlet water temperature- Cooling tower outlet water temperature
Water flow rate- Water flow rate
- Inlet air temperatureInlet air temperature- Air Humidity (higher humidity reduce cooling)- Air flow rate- Exhaust air temperature
Electrical readings of pumps and fans motors- Electrical readings of pumps and fans motors
- Cycles of Concentration (COC)
Cooling Tower Water Treatments 4Dr.Ing. Carlo Lebrun
Cycles of Concentration (COC)
CYCLES OF CONCENTRATION (COC)
A measure of cooling tower operation efficiency also referred to as “cycles”
Compares 1 TDS (total dissolved solids mg/l)1 - TDS (total dissolved solids – mg/l)or2 - conductivity (microSiemens – uS) y ( )in the makeup water and in the blowdown water.
C l t TDS / k TDSCycles = system TDS / makeup TDSe.g. TDS 2,150 mg/l / 390 mg/l = 5.5 COC
5Dr.Ing. Carlo LebrunCooling Tower Water Treatments
COMMON WATER COOLERS TERMINOLOGY
-Drift: Water droplets that are carried out of the cooling tower with theDrift: Water droplets that are carried out of the cooling tower with the exhaust air. Drift droplets have the same concentration of impurities as the water entering the tower.
-Plume: The stream of saturated exhaust air leaving the cooling tower. The plume is visible when water vapor it contains condenses in contact with cooler ambient aircooler ambient air.
- Blow-down: portion of circulating water flow that is removed. N Hi h TDS ( l di l d lid ) i i l i l iNote: Higher TDS (total dissolved solids) concentration in solution results in greater potential cooling tower efficiency. However the higher the TDS concentration, the greater the risk of scale, biological growth and corrosion.
Cooling Tower Water Treatments 6Dr.Ing. Carlo Lebrun
WHAT IS IN THE WATER?
- Suspended Solids
- Dissolved Solids (= dissolved salts)
Od i d- Odour causing compounds
- Biological ContaminantsBiological ContaminantsAlgaeFungiProtozoansBacteriaVirus
Cooling Tower Water Treatments 7Dr.Ing. Carlo Lebrun
Virus
COOLING TOWER WATER TREATMENT
C l d C li T t t t t h i lCommonly used Cooling Towers water treatment chemicals are:
- Sodium Hypochlorite
- Biocide
Bi di t- Biodispersant
- Scale/Corrosion inhibitorScale/Corrosion inhibitor
- Sulphuric acid
Cooling Tower Water Treatments 8Dr.Ing. Carlo Lebrun
EXAMPLE OF PROJECT DATA
Cooling Tower Water Treatments 9Dr.Ing. Carlo Lebrun
TYPICAL INJECTION VALUES
-Sodium Hypochlorite keep total free chloride in system/blowdown waterSodium Hypochlorite keep total free chloride in system/blowdown water between 0.5 and 1.0 ppm (practically = mg/L)
-Biocide as per vendor recommendation,Biocide as per vendor recommendation, and change periodically
- Biodispersant as per vendor recommendationp pand change periodically
- Scale/Corrosion inhibitor as per vendor recommendation
- Sulphuric acid keep pH in system/blowdown water between 7 and 7.5
Cooling Tower Water Treatments 10Dr.Ing. Carlo Lebrun
COOLING TOWER WATER TREATMENT
Commonly used Cooling Towers water treatment chemicals are:
- Sodium Hypochlorite
- Biocide
- Biodispersantp
- Scale/Corrosion inhibitor
- Sulphuric acid
Cooling Tower Water Treatments 11Dr.Ing. Carlo Lebrun
USE OF SODIUM HYPOCLORITE
- disinfection of stagnant water (biocide)
- limit fouling of pipes & equipment due to biological factors
NOTENOTE: it is an “oxidising” biocide which promotes corrosion, and environmental contamination (air & water)environmental contamination (air & water). Quantity should be limited.
Cooling Tower Water Treatments 12Dr.Ing. Carlo Lebrun
COOLING TOWER WATER TREATMENT
Commonly used Cooling Towers water treatment chemicals are:
- Sodium Hypochlorite
Biocide- Biocide
- Biodispersantp
- Scale/Corrosion inhibitor
- Sulphuric acid
Cooling Tower Water Treatments 13Dr.Ing. Carlo Lebrun
USE OF BIOCIDE
A id f li f i & i t d t bi l i l- Avoid fouling of pipes & equipment due to biological factors
NOTE 1: same purpose of sodium hypchlorite, but less corrosive and contaminant. Normally a non-oxidising biocide.
NOTE 2: effectiveness may vary in time as some bacteria may develop resistance (periodical checks required)
NOTE 3: effectiveness may be increased by correct water operating temperature:pcold water below 25°C and hot water above 55°C do not allow Legionella to grow
Cooling Tower Water Treatments 14Dr.Ing. Carlo Lebrun
USE OF BIOCIDE (Legionella)
A very important reason for using biocides in cooling towers is to prevent the growth of Legionella, including species that cause legionellosis or Legionnaires' disease most notably L pneumophilaLegionnaires disease, most notably L. pneumophila.Various Legionella species are the cause of Legionnaires' disease in humans and transmission is via inhalation of mist droplets containing the bacteria.
Legionella can spread through the air up to 6 kilometres from a large contaminated cooling tower.
Periodical inspection of cooling tower are necessary to early detect any infection.
Cooling Tower Water Treatments 15Dr.Ing. Carlo Lebrun
BIOLOGICAL AGENTS
AlgaeAlgae• food for bacteria• deposits may induce corrosion• deposits can reduce heat exchange deposits can reduce heat exchange• deposits can foul piping
FungiFungi• deposits can reduce heat exchange
BacteriaBacteria• some bacteria may cause health hazards (legionella)• sulphate reducing bacteria can produce hydrogen sulphide (corrosive!)
16Dr.Ing. Carlo LebrunCooling Tower Water Treatments
COOLING TOWER WATER TREATMENT
Commonly used Cooling Towers water treatment chemicals are:
- Sodium Hypochlorite
- Biocide- Biocide
- Biodispersantp
- Scale/Corrosion inhibitor
- Sulphuric acid
Cooling Tower Water Treatments 17Dr.Ing. Carlo Lebrun
USE OF BIODISPERSANT
- cooperate with biocide to avoidcooperate with biocide, to avoid accumulations/concentrations of biological residues
- limit fouling of pipes & equipment due to biological factors
Cooling Tower Water Treatments 18Dr.Ing. Carlo Lebrun
…
Cooling Tower Water Treatments 19Dr.Ing. Carlo Lebrun
COOLING TOWER WATER TREATMENT
Commonly used Cooling Towers water treatment chemicals are:
- Sodium Hypochlorite
- Biocide- Biocide
- Biodispersant
- Scale/Corrosion inhibitor
- Sulphuric acid
Cooling Tower Water Treatments 20Dr.Ing. Carlo Lebrun
USE OF SCALE/CORROSION INHIBITOR
- Scale & Deposit On Heat Transfer Surface
- Corrosion in pipes & equipment
Cooling Tower Water Treatments 21Dr.Ing. Carlo Lebrun
SCALING
Cooling Tower Water Treatments 22Dr.Ing. Carlo Lebrun
POSSIBLE SCALE CAUSING SALTS
Calcium Carbonate Magnesium SilicateCalcium Sulphate pZinc PhosphateCalcium Phosphate Calcium FluorideIron Oxide Iron CarbonateSilica Aluminium Hydroxide
Example reaction: C ++ + 2(HCO ) ¯ > C CO ( i it t ) + H O + COCa++ + 2(HCO3) ---> CaCO3 (precipitate) + H2O + CO2
Reaction is helped by concentration, high pH, high temperature
Cooling Tower Water Treatments 23Dr.Ing. Carlo Lebrun
COST INCREASES DUE TO SCALING & FOULING
Reduced heat transfer efficiency and/or greater energy y g gylosses
Production losses
Reduced pipe diameters (greater pumping energy)
Increased maintenance cost
Cooling Tower Water Treatments 24Dr.Ing. Carlo Lebrun
COST INCREASES DUE TO CORROSION
Loss of Metal and alloys
Replacement of product time and energyReplacement of product, time and energy
Loss of manpower due to shutdowns.AccidentsAccidents
Loss of Efficiency
Cooling Tower Water Treatments 25Dr.Ing. Carlo Lebrun
COOLING TOWER WATER TREATMENT
Commonly used Cooling Towers water treatment chemicals are:
- Sodium Hypochlorite
- Biocide- Biocide
- Biodispersant
- Scale/Corrosion inhibitor
- Sulphuric acid
Cooling Tower Water Treatments 26Dr.Ing. Carlo Lebrun
USE OF SULPHURIC ACID
- adjust pH level before discharge to effluent
- reduce scaling: acid treatment reduces [CO3] ions
Cooling Tower Water Treatments 27Dr.Ing. Carlo Lebrun
HOW TO VERIFY THE COORECT RESULT OF CHEMICALS INJECTION?OF CHEMICALS INJECTION?
Cooling Tower Water Treatments 28Dr.Ing. Carlo Lebrun
FEEDBACK ON WATER QUALITY
1 - feedback through lab analysis 2 - corrosion and scaling probes g p3 - equipment inspection are essential to evaluate the effectiveness ofare essential to evaluate the effectiveness of treatment and adjust chemicals injection to the correct quality and quantitythe correct quality and quantity.
F (d il kl t ) t b t dFrequency (daily, weekly, etc.) to be tuned on site real needs.
29Dr.Ing. Carlo LebrunCooling Tower Water Treatments
PERIODICAL TESTS OF WATER QUALITY
- Chemicals Residual Analysis- Corrosion Coupon Monitor
Fouling Depositor- Fouling Depositor- Microbiological Count Test- Hardness (both total and Calcium )Hardness (both total and Calcium )- Total Dissolved solids (TDS) - Total Suspended Solids (TSS)- pH- Chloride
Silica- Silica- Iron- Other …
30Dr.Ing. Carlo LebrunCooling Tower Water Treatments
Other …