Upload
others
View
0
Download
0
Embed Size (px)
Citation preview
AquFlow®
ECCATM
Electric Capacity ControlSeries 1000 & 2000
INSTALLATION, OPERATION ANDMAINTENANCE MANUAL
Aq
uF
low
Pu
mp
s.
i
Table of Contents
Warranty ........................................................................................................................................... iiGeneral Description ......................................................................................................................... 1
Description of Electonic Circuitry ..................................................................................................... 1Power Supply/Driver Card .......................................................................................................... 1
Installation Instructions ..................................................................................................................... 1Electrical Connections ............................................................................................................... 3Signal Inputs ............................................................................................................................... 3
Specifications ................................................................................................................................... 2
Startup Instructions .......................................................................................................................... 3
Calibration of the Circuit Board - Series 1000Equipment Required................................................................................................................... 4Input Amplifier ............................................................................................................................. 4Checking Motor Limits ................................................................................................................ 4Setting Ratio Control .................................................................................................................. 4Returning to Service ................................................................................................................... 4
DisassemblyRemoval of P.C. Card................................................................................................................. 4Removal of Synchronous Motor ................................................................................................. 5Removal of Actuator Housing from Pump Series 1000 .............................................................. 5Removal of Actuator Housing from Pump Series 2000 .............................................................. 6
ReassemblyInstalling Actuator Housing on Pump Series 1000...................................................................... 7Installing Actuator Housing on Pump Series 2000...................................................................... 7Installation of the Synchronous Motor ......................................................................................... 7Re-Synchronozation Equipment Needed ................................................................................... 8
Returning to Service ......................................................................................................................... 9
Outdoor Installations ........................................................................................................................ 9
DrawingsHookup Diagram - Electronic Capacity Control .......................................................................... 10Board Layout - Power Supply Driver .......................................................................................... 11Board Layout - Input Buffer/Motor Logic ..................................................................................... 12Electrical Schematic - Input Buffer/Motor Logic ......................................................................... 13Electrical Schematic - Power Supply & Drive Card ................................................................... 14Test Cable - Synchronization - Local Control ............................................................................. 15Test Cable Hookup Schematic ................................................................................................... 15Series 1000/2000 Motor Coupling Installation ............................................................................. 16ECCATM Cross Section & Parts List - Series 1000 All Plungers ................................................. 17ECCATM Cross Section & Parts List - Series 2000 All Plungers ................................................. 18
Troubleshooting Sequence ............................................................................................................... 19Replacement Part Numbers ............................................................................................................ 20
Parts Ordering Instructions.................................................................................................................21
ii
WARRANTY
AquFlow warrants its products against defects in workmanship or material under specified use andservice for a period of two years from date of shipment. The obligation and liability of AquFlow islimited to repairing or replacing (at its option) such allegedly defective units as are returned freight prepaid to NPA’s plant.No liability is assumed for warranties of merchantability or fitness for a particular purpose except as specified, or forreinstallation costs. Liability for consequential damages (including personal injury) is hereby excluded; liability in anyevent being limited to the original purchase price of the goods involved.
Defects shall not include failure by errosion, abrasion, chemical action, material compatibility, or operation of productsoutside of the recommended performance envelope. The component materials set forth in the proposal and/or thespecifications of an order are recommended by AquFlow for the particular application. But suchrecommendations shall not be construed as a warranty or guarantee against wear and/or corrosion, and suchrecommendations are subject in all cases to verification and acceptance by the purchaser. When repairs or replacementsare made under our warranty, incoming freight costs must be paid by the purchaser.
NIKKISO Pumps America, Inc. will not be responsible for work performed by others. AquFlowreserves the right to void applicable warranties if work performed by others is determined by AquFlow to be improper.
Read this instruction completely before installing,operating or servicing AquFlow® ECCATM Electric Capacity Controllers!
Always keep safety considerations foremost! Use proper tools, protective clothing andeye protection when working, and install the equipment with a view toward assuring safeoperation. Be extremely careful when working in the presence of hazardous substances!
NIKKISO HYDROFLO® ECCATM
page 1
n this instruction manual, the Note, CAUTIONand WARNING notations have the followingmeanings:
Note: This heading is used if a special featureor operating requirement is being pointed out.
CAUTION: This heading is used to denote whenfailure to follow the operating instructions asprescribed herein can lead to pump or systemdamage.
WARNING: This heading is used to denote whenfailure to follow the operating insructions asprescribed herein could result in PERSONALINJURY!
GENERAL DESCRIPTIONThe electric capacity control actuator can befurnished in place of the standard manualmicrometer adjustment. The actuator adjustspump capacity from an electronic signal ormanually by means of an override handwheel.Local capacity indication is read directly from anindicating scale on the actuator, or remotely byuse of the electronic retransmission signal (4-20MADC) feature. Control is achieved through theuse of down sized state of the art electronics andsynchronous motor technology in a singlecompact enclosure.
Synchronous Motor
The use of this type of motor permits rapidresponse and precision positioning in a smallpackage. Since this kind of motor is magneticallydetented, overshoot is eliminated, a probleminherent in shaded pole or gear motors.
Electronics
The operation of the electric capacity controlactuator is controlled by two electronic circuitcards. The top one serving as the input and logicsection and the bottom serving as the powersupply and motor driven section. These circuitsaccept an input signal from a process instrumentand commands the synchronous motor to driveto a corresponding position. Closed looppositioning is accomplished through use of afeedback slide wire.
Description of Electronic Circuitry
Input Buffer/Motor Logic 170071. Input Buffer Amplifier: The input voltage signal
is converted from 1-5 VDC to a 0-10 VDC signalusing a high impedance amplifier, U4A. Thisvoltage is applied to the ratio control which isused to scale the signal to the appropriate value.The resultant voltage is the positive input to theerror amplifier, U4B, which compares it to theactual capacity control position as representedby the negative feedback potentiometer whichis gear driven by the actuator motor.
2. Error Amplifier and Motor Logic: The errordeveloped at U4B is applied to twocomparators, U5A & U5D, which have slightlydifferent set points. Any error in excess of thesepre-selected values will cause the motor logic,U6A or U6B, to respond with either an up (+) ordown (-) signal. The signal then enters the motordrive Section which provides currentamplification through transistors Q3 or Q4.
3. Feedback Buffer: The previously mentionedfeedback potentiometer picks off a voltage from+5 VDC to -1.2 VDC, depending upon itsposition as the motor rotates. This voltage isapplied to the feedback buffer amplifier forcomparison with the input signal. At the sametime, this signal is applied to the electroniclimiting circuitry U5B and U5C. Thesecomparators are set (via high and lowpotentiometer) to limit actuator travel in theevent of an overdriven or underdriven input.
Power Supply/Driver Card 17006Power Supply
The transformer output is rectified by a full wavebridge, filtered and routed to a pre-regulator stage.This darlington pair is controlled by zener CR3referenced to the output of the primary regulator,U1. The 5 volt reference U2 is tied to U1 through adropping diode CR2 and held 1.2 VDC above thesupply return in order to permit live zero voltagefeedback potentiometer operation without offset.
Motor Driven
The current amplified up and down signal entersthe motor driver selection at pin two of the opticallyisolated triac drivers U7 and U8. these optoisolators
page 2
SPECIFICATIONS
Input voltage: 120 VAC 50/60 hz single phasePower consumption: 44 va maximumLine protection: Fuse type, 3 amp Bussman PCC3Line voltage variations: ±10% of nominalLine frequency variations: ±2% 50/60 hzAmbient temperatures: 0-40°C (32-104°F)Relative humidity: 5-96% (witout condensation)Altitude: 3300 feet (1000 meters)Motor type: AC synchronous (impedance protected)Response time: Series 1000 8 seconds 0-100% Series 2000 16 seconds
200 8 secondsSeries977/997 8 seconds
Turndown ration: better than 20:1Repeatability: ±1%Drive connection: Direct on Series 900, 1000, 2000 and HydromyteInput signal voltage: 1-5 VDC, 3 meg ohm impedance current: 4-20 MADC, 250 ohm impedanceOutput signal voltage: 1-5 VDC across a 250 ohm resistorCurrent: 4-20 MADC into 500 ohms maximum
Adjustments: High limit factory setLow limit factory setSpan factory setZero factory setGain field adjustable, 4-20 retransmissionOffset field adjustableRatio field adjustable 100%
Field connections: AC powerProcess signal in-captive wire typePosition signal out-captive wire typeMotor disable-MTA . 100” 2 Pin
Enclosure type: NEMA 4 standardNEMA 7 optional (class 1, div. 1, group C and D)
Indicator type: Local - mechanicalRemote - 4-20 MADC into 500 ohm or1-5 VDC across 250 ohm
Actuator control: Electronic comparator with synchronous motor andmechanical manual override
Actuator limits: Electronic - no limit switches
ACTUATOR MODEL SELECTIONACTUATOR MODEL OF PUMP SERIES OF PUMPMODEL NO. WHERE USED WHERE USED
17100-1100 100017100-2100 200017100-3100 300017100-4100 AqFlow 400017100-5100 977/99717100-5100 200
page 3
trigger triacs CR4 or CR5 which are directly coupledto the directional windings of the capacity adjustingmotor.
INSTALLATION INSTRUCTIONSThe electric capacity control has been factory testedand calibrated on the pump prior to shipment. Nofurther field adjustments or calibrations to the factorysettings should be necessary prior to placing unitinto service.
Note: To maintain correct alignment andsupport, it is recommended that the pump/actuator combination remain bolted to its factorysupplied base plate for Series 200, 977, 997,1000 and 2000 pumps.
CAUTION: Do not adjust capacity handwheelbeyond the limits of the indicating scale ordamage to the pump and actuator may result.
Electrical Connections1. Unscrew end cover to expose with connection
points. Refer to drawing on page 12 for hookupdiagram.
2. Power and signal wires SHOULD BE RUNSEPARATELY. Use shielded cable for signal line.The electric capacity control requires a powersource of 120 VAC 50/60 hz single phase. Thebranch circuit should be protected by a fuse orcircuit breaker and contain a disconnect switch.The circuit boards are protected by a selfcontained fuse.
3. The black wire should be the phase side of theline and connect to terminal “L”; the neutral orwhite wire to terminal “N”. Equipment groundingis effected by connecting a green wire to one ofthe screws in the housing, the other end of thiswire is returned to protective ground at thesource of supply.
Note: Appropriate conduit hubs must be used,and all covers must be in place and tight toprevent liquid entry and maintain NEMA integrity.
Signal Inputs1. The electric capacity control accepts a voltage
signal of 1-5 VDC. If the controlling signal is acurrent signal, the 249 ohm resistor (R133) willtransform it into the voltage required. It may beleft in place when a voltage signal is used, but
the transmitter must be low impedance output.Better practice is to remove the resistorcompletely.
2. The 249 ohm resistor is the correct value for 4-20 MADC input. This resistor (R133) is locatedadjacent to J1 and in back of TB1 on the inputbuffer/motor logic card (17007). If a highimpedance voltage source is used, the resistorcan be removed by carefully clipping the leadat the resistor body (R133).
3. Connections have been provided that allows theactuator to be disabled. A N.O. dry contactconnected to J1 (when closed) will disable themotor drive circuit while allowing the remainingcircuitry to be fully activated. This permits theactuator to be set and then disabled, while stilltransmitting a positioner signal (4-20 MADC). Italso permits manual override while the unit ispowered up. Connections to J1 are made viaan MTA two pin connector on .100” Centers.
START UP INSTRUCTIONS1. Apply power to the actuator and inject a 4 MADC
signal at B1 to bring the actuator to zero percentcapacity. Place a mark on the slotted coupling(3409 drawing 17017, 17018). Inject a 20 MADCsignal and count the number of turns. For Series1000, 977, 997 and 200, there should be tenturns for 100% output. For Series 2000, thereshould be twenty turns for 100% output. Anydifferences can be corrected by adjusting theratio potentiometer R130 on input buffer board17007.
The electronic limiting feature built into theactuator circuitry permits only a few degrees ofpositioner rotation past 100%, likewise, a fewdegrees below zero percent. This is to preventmechanical jamming of the actuator. Whenadjusting the actuator by means of the overridehandrail, it is important to maintain indicatortravel within the limits of the indicating scale, ordamage to the actuator can occur. The manualoverride should be used in conjunction with theactuator disable feature or with power removedfrom the actuator. See section 3, under “SIGNALINPUTS” for the actuator disable feature.
2. The ratio control potentiometer is used to adjustthe full scale output of the pump for a full scaleinput signal. If it is desirable to have less than100% pump output for a 100% input signal, theratio control pot should be turned in a
page 4
counterclockwise direction from its normallymidscale position. If 100% output is required forless than 100% input signal, the pot should beadjusted in a clockwise direction. Smalladjustments are in order because of the highgain system employed. (Any change in the ratiocontrol from the factory setting will require re-calibration of the pump).
3. Remote indication or closed loop operation canbe accomplished using the 4-20 MADCretransmission feature located at TB3. “COM”is the low or negative side and “OT” is the highor positive side. Apply 4 MADC to the input,(allow actuator to position itself) and adjust thegain pot to 20 MADC output. Since the offsetand gain pots interact with each other, severaladjustments from 4 to 20 MADC may be requiredto complete the calibration. The input and outputsignals are isolated from phase and ground butnot from each other. The maximum load thatcan be connected across TB3 is 500 ohms.
CALIBRATION OF THE CIRCUIT BOARD -Series 1000
Note: The P.C. Cards are tested, calibrated andmatched to each actuator motor and pump atthe factory, and are ready to be placed intoservice as received. The following instructionsare included as an aid in troubleshooting in theunlikely event of a malfunction.
Equipment Required1. 120 VAC supply.
2. Adjustable DC voltage source capable ofsimulating 1-5 VDC or a current source capableof 25 MADC.
3. A digital voltmeter reading .01 volts minimum.
4. Miscellaneous jumpers.
Extent of Calibration: This procedure covers thesetting of the zero and the span potentiometer,checking the high and low limit potentiometer, andsetting the ratio control. This procedure assumesthat the input signal range is 1 to 5 VDC, or 4-20MADC.
Preliminary: Connect (but do not turn on) the ACpower to terminal L&N (TB2) on power supply board17006. Safety ground can be connected at thehousing or under the screw head of a standoff.Connect adjustable DC voltage supply to terminalC-and V1 + (TB1) on input board 17007.
Input Amplifier1. Apply line power to board. Read voltage from
TP2 & to C-.
2. Connect a jumper (across the zero pot) fromR102 (inside leg) to C. Apply 5 VDC to input andadjust span pot for 12.5 VDC at TP2.
3. Remove jumper across zero pot. Apply 1 volt toinput and adjust zero pot for 0.0 V at TP2.
4. Apply 5 VDC to input and adjust span pot for 10VDC. All voltages are ±0.1 VDC.
5. Repeat steps 3 and 4 as required.
Motor Limits: The high and low potentiometers onthe input board are factory set for each actuator/pump combination and require no furtheradjustment.
Checking Motor Limits1. Input 0.98 VDC. Read voltage from test point h
(+) to common.
2. Input 0.94 VDC. Observe that voltage goes onhigh.
3. Input 2 VDC then 0.98 VDC. Observe thatvoltage goes on high.
4. Input 5.08 VDC. Read voltage from test point g(+) to common. Observe that voltage is high.
5. Input 5.13 VDC. Observe that voltage goes low.
6. Input 4 VDC then 5.08 VDC. Observe thatvoltage goes high. This procedure is for checkingproper operation of motor limits only.
Note: The above voltages are typical and willvary with pump/actuator combination.
Setting Ratio Control1. Input desired voltage for full scale operation.
2. Adjust ratio potentiometer for desired pumpoutput, turn clockwise to increase output,counterclockwise to decrease output.
Returning to Service1. Remove power and disconnect all test
equipment and jumpers.
2. Reconnect power and input/output signal cablesif other sources were used for calibration check.
3. Replace all covers securely to maintain NEMAintegrity.
page 5
DISASSEMBLYRemoval of P.C. Cards1. Remove and lock out power and signal to
actuator and pump.
2. If possible set pump to 0% capacity usingmanual override hand wheel and capacity scale.
3. Remove cover from actuator.
4. Disconnect incoming power and signal lines andoutgoing signal line if used.
5. Remove feedback potentiometer cable from P2on card 17007.
6. Remove motor control cable from P1 on bottomcard 17006.
7. Remove the three screws (3417) retaining themotor logic card to standoffs (3548). Drawings17018 & 17017 (depending on Series of pump).
8. Remove the three standoffs (3548) retainingpower supply to standoffs (3547).
9. Unplug phase shift network leads from the wireson the underside of the power supply card.
10. Remove P.C. Cards as a pair and place them ina safe location. Care must be taken to preventbreakage of interconnect cables.
Removal of Synchronous Motor1. Remove the three standoffs (3547) attached to
the motor plate (3402). It is recommended toidentify these standoffs soles on the motor platefor reassembly later on. These standoffs are twoinches long and should not be confused withstandoffs (3458) which are one and one halfinches long. Clip off and discard any tie wrapsretaining interconnect wiring to these standoffs(3547).
2. Remove the Zerust anticorrosion pad thenremove the four flathead screws (3416) retainingthe motor plate (3407) to the four motor standoffs(3415). Carefully remove the motor plateassembly and inspect all components forbreakage or wear. Replace worn or brokenpotentiometer and drive gears. It may benecessary to loosen (not remove) the potbracket screws on the lower side of the motorplate (3407) to allow removal of motor plateassembly from actuator housing.
3. Remove the four motor standoffs (3415)retaining the motor in place. The motor is placedinside the actuator housing with the connector
at the three o’clock position relative to the conduitentry holes. During reassembly the motor mustbe installed in this same position.
4. Carefully remove the motor and inspect for wearor breakage of the drive components. The motorshaft must turn freely, but will exhibit a detentedor slightly “rough feeling” when turned by hand.The motor must be replaced if the shaft is hardto turn or “frozen”. Check the motor coupling(3431) for breakage or wear. If the coupling isusable be sure the set screws (3432) are tight,securing the coupling to the motor shaft.
The motor shaft is flatted and one of the two setscrews must engage this flat. It is also advisableto use “retaining” grade Loctite to aid in securingthe motor coupling (3431) to the motor shaft. Toavoid damage to the motor apply Loctite to theI.D. of the coupling (3431) at the large end beforesliding it over the motor shaft. See drawing17124-1 for coupling replacement procedure.
5. Check the motor gear (3437) for wear orbreakage. If the gear must be replaced be sureit is oriented with the teeth facing outward (awayfrom the motor). Care should be taken to assurethe spacer under the motor gear is in placebefore installing the new gear. Reassemble theoverride coupling (3409) to the motor shaftabove the motor gear (3437). If any drivecomponents appear worn (beyond use) orbroken, contact NIKKISO Pumps America, inc.or your local factory representative forreplacement parts. See “replacement partnumbers”.
Removal of Actuator Housing from PumpSeries 1000Most serviceable parts are contained within theactuator housing, and are accessible withoutremoving the housing from the pump. Theseinstructions are provided for your convenience inthe unlikely event the housing must be removed.
1. Remove support stud (3425). In mostapplications this will be a length of “all thread”with accompanying lock washers and nuts.
2. Remove the four screws (3418) retaining thecapacity plate (3414) to the actuator housing(3402). This plate has been factory sealed andmay require some gentle persuasion to break itfree. Set the plate in a safe area.
3. Reach inside the housing, using a flat object(three quarter inch wide machinist scale) and
page 6
turn the actuator (3404) until the slotted end ofthe indicator pin (3413) is accessible throughthe capacity plate opening. This pin has beenfactory installed using low shear grade Loctite,use the correct size screwdriver and removethe indicator pin and set it in a safe place.
4. Loosen, but do not remove, the four clamp ringscrews (3442). This releases clamp ringpressure, permitting the actuators to beunscrewed from the mounting adapter (3401).
5. Turning counterclockwise, unscrew the actuatorhousing from the mounting adapter (3401).COUNT THE NUMBER OF TURNS AS YOUGO. This information will be necessary forreassembly of the actuator to the pump.
6. Inspect the indicator ring (3412) and pin (3413)for wear or damage. Replace as necessary,
7. Inspect the actuator coupling (3404) for wear ordamage. The actuator must turn freely insidethe housing. End movement between housingand actuator is a normal condition though radialmovement should be negligible to nonexistent.If excess radial movement is detected, housing(3402) and/or actuator (3404) should bereplaced.
8. To replace a worn or damaged actuator (3404),set the housing (3402) on end and reach insidewith a pair of snap ring pliers and remove snapring (3433). This will allow the actuator to beremoved from the housing. When replacing theactuator (3404), apply a thin film of moly greaseto its minor diameter before inserting it into thehousing, and retain it in place using a new snapring (3433). Electric capacity controldisassembly instructions stop at this point.Further disassembly of the pump is coveredunder separate print. Contact NIKKISO PumpsAmerica, Inc. for this information.
Removal of Actuator Housing from PumpSeries 2000Most serviceable parts are contained within theactuator housing, and are accessible withoutremoving the housing from the pump. Theseinstructions are provided for your convenience inthe unlikely event the housing must be removed.
1. Remove the support stud (3425). In mostapplications this will be a length of “all thread”with accompanying lockwashers and nuts.
2. Remove the four screws (3418) retaining thecapacity plate (3414) to the actuator housing
(3402). This plate has been factory sealed andmay require some gentle persuasion to break itfree. Set the plate in a safe area.
3. Loosen, but do not remove, the two adaptorhousing set screws (3429) on adaptor housing(3428). Grasp the actuator housing (3402) firmlyand in a clockwise direction, turn the adapterhousing (3428) six to eight turns to completelyseparate actuator housing (3402) from adaptorhousing (3428).
4. Inspect capacity indicator and indicator pin forwear or damage. Replace as necessary.
5. To remove the capacity indicator and pin, turnthe indicator until the pin is in the vertical position.Support the threaded adjuster (4633) andcarefully drive the pin out using an appropriatesized drift (punch). To install a new indicator andpin, support the adjuster and align one of theholes in the indicator over the hole in the adjustershaft with the raised section if the indicator facingaway from the pump housing. Place the pinthrough the hole in the indicator and hold it inplace over the hole in the adjuster (4633).
Carefully drive the pin through the hole in theadjuster until there is an equal amount ofexposed pin on either side of the adjuster shaft.Care should be taken not to deform the indicatorduring installation or binding may occur.
6. Inspect the actuator coupling (3404) for wearand damage. Actuator must turn freely insidethe housing. End movement between thehousing and the actuator is a normal conditionthough radial movement should be negligible tononexistent. If excess movement is detected,housing (3402) and actuator (3404) should bereplaced.
7. To replace a worn or damaged actuator (3404)set the housing (3402) on end and reach insidewith a pair of snap ring pliers and remove snapring (3433). This will allow the actuator to beremoved from the housing. When replacing theactuator (3404), apply a thin film of moly greaseto the minor diameter before inserting it into thehousing, and retain it in place using a new snapring (3433). Electric capacity controldisassembly instructions stop at this point.Further disassembly of the pump is coveredunder separate print. Contact NIKKISO PumpsAmerica, Inc. for this information.
page 7
REASSEMBLY
Installing Actuator Housing on Pump Series10001. Side the capacity indicating ring (3412) over the
actuator (3404) with the raised end toward thehousing (3402).
2. Align the housing (3402) with the pump adaptor(3401). Turning clockwise, start and then screwthe housing onto the adaptor using the samenumber of turns required for removal bringingthe flatted surface by the conduit entry holesparallel to the base plate (plate the pump ismounted to).
3. Tighten the four clamp ring screws (3442).Check for any radial movement of the housing.If movement is detected, loosen the clampscrew and turn the housing (3402) one turnclockwise and retighten the four clamp ringscrews.
4. Turn actuator (3404) to align a slot with thethreaded hole in the control spool assembly(3439). Slide the indicating ring (3412) in place,and insert the indicator pin (3413) through oneof the two holes in the ring, down through theslot, and into the threaded hole of the controlspool (3439). Turning clockwise, screw theindicator pin (3413) through the control spooland down through the hole in the opposite sideof the indicating ring (3412). Ends of the pin maynot protrude past the raised section of theindicator ring.
5. Remove old sealant from the capacity plate(3414) and its mating surface on the housing.Apply a film of clear RTV (silicone) to the matingsurface on the housing and secure the capacityplate in place over the RTV using the four screws(3418).
6. Install the stud (3425) with its hardware into thebottom side of the housing (3402). It may benecessary to loosen the clamp ring screws(3442) to allow slight housing repositioning wheninstalling this stud. Retighten the clamp ringscrews first then secure the stud (3425). Thisstud is intended for support only. Care shouldbe taken when tightening the jam nuts to preventthe introduction of lateral forces that might causemisalignment between the pump and theactuator housing.
Installing Actuator Housing on Pump Series20001. Apply a thin film of moly grease to the threaded
end of adaptor (3428). Align housing (3402),actuator (3404), capacity indicator (3412) andhousing adaptor (3428). In a counterclockwisedirection, screw the housing adaptor (3402) untilintimate contact is made between these twoparts. Bring the flat surface of the conduit entryholes in the housing (3402) parallel to the baseplate (plate the pump is mounted on). Hold theactuator housing in this position and install thestud (3425) with its hardware into the bottomside of the housing (3402). Tighten the two setscrews (3429) first, then secure the stud. It isimportant to seat the two set screws (3429) inthe groove (undercut) portion of the adjusterhousing (3436). Stud (3425) is intended forsupport only, and care should be taken whentightening the jam nuts to prevent the introductionof lateral forces that might cause misalignmentbetween the pump and the housing (3402).
2. Remove old sealant from the capacity plate(3414) and its mating surface on the housing.Apply a film of clear RTV (silicone) to the matingsurface on the housing and secure the capacityplate in place over the RTV using the four screws(3418).
Installation of the Synchronous MotorThe motor assembly must be complete with coupling(3431), spacer, gear (3437), and override coupling(3409). Connector with red, black and white wiresis also considered part of the motor assembly andmust be in place.
1. Insert the motor into the housing engaging thecoupling (3431) with actuator (3404). The motormust sit squarely in its mount with no movementother than rotational.
2. Orient the motor so the connector is at the threeo’clock position relative to the conduit entry hole(conduit holes at the twelve o’clock position).Secure the motor in place using the fourstandoffs (3415). If new standoffs are beingused, it is recommended to apply a thin film ofgrease to the male threads before installation.
3. The motor plate should be a built up assemblyof (3407), phase shift network consisting of2.5UF capacitor and a 500 ohm resistor, and afeedback pot assembly. Locate this motor plateassembly over the four motor standoffs (3415)
page 8
with the feedback pot at the bottom (sideopposite conduit entry holes). The two feedbackpot bracket screws (6-32 x 1/2) should be looseat this time to allow full disengagement of thetwo gears (3437) and (3438).
4. Install the three standoffs (3547) in the holesidentified during disassembly.
5. This step is for Series 1000 pumps only. Turnthe motor shaft counterclockwise (via slot onthe override coupling 3409) until it reaches itsmechanical stop. Then turn the shaft 1/4 turnclockwise. This is 0% capacity of the pump.
6. This step is for Series 2000 pumps only. Turnthe motor shaft clockwise (via slot on overridecoupling 3409) until it reaches mechanical stop.Place a mark on the coupling at the twelveo’clock position. Now, turn the couplingcounterclockwise one and one half turns. Thisis the 100% capacity. Now turn the couplingcounterclockwise twenty turns. This is 0%capacity.
7. The pump and the actuator are now ready to besynchronized.
Re-Synchronization Equipment NeededA. 1-5 VDC or 4-20 MADC source.B. 115 VAC power cord set.C. Test cable with plug, Hydroflo part number
17120-1.
1. Connect feedback pot cable to P2 on inputbuffer/motor logic card 17007.
2. Connect (do not apply power) 115 VAC cord setto TB2 on power supply/drive card 17006.
3. Connect voltage or current source TB1 on inputbuffer/motor logic card 17007.
4. Connect test cable plug (NIKKISO Hydroflo® partnumber 17120-1) to P1 on power supply/drivercard 17006.
5. Place these two cards on an insulated surfacesuch as cardboard, plastic, etc. Do not allowthe two cards to touch each other or any metallicsurface.
6. Connect 115 VAC light bulbs with pig tails (anywattage) to the test cable wires. The white wirefrom P1 is common or neutral to both lights, theblack is hot to one light, and the red is hot to theother light. See test cable schematic drawing17121-1. Do not connect the phase shift networkwires at this time.
7. Apply a 4 MADC or 1 VDC input signal to TB1.Make sure that negative, common or low isconnected to “C” on TB1.
8. Apply 115 VAC power to the card set. One ofthe two light should come on. If none of the lightscome on, check the following:
A. Power is present at TB1 of 7006.
B. Power supply fuse open or broken lead.
C. That J1 is NOT jumpered.
D. Light bulbs are operational.
E. Feedback pot is already at 0% position. (Thiscan be checked by rotating the pot gear oneturn clockwise or counterclockwise).
F. Interconnect wiring for breaks ormisconnections.
9. Turn the feedback pot gear clockwise until bothlights go out.
10. Remove 115 VAC power first, then remove theinput signal.
11. Carefully engage the feedback pot gear to themotor gear and tighten both 6-32 x 1/2” screws.On Series 2000 pumps, care must be taken tomaintain equal distance from standoffs to potgear. (Gear centered between both standoffs.)Actuator and pump are now synchronized.Remove power, feedback pot and test cableconnections from both cards.
12. Replace the Zerust vapor capsule. If a newcapsule is being used, do not forget to date it.This capsule should be replaced on a yearlybasis.
13. Position the power supply card over the threestandoffs (3547) oriented with TB2 atapproximately the five o’clock position. Be sureall three black fiber washers are in place on theunderside of the power supply card and overthe mounting holes securing it in place with thethree shorter standoffs (3548).
14. Connect the motor leads red, black and whiteto P1 on the bottom card, feedback pot leadsgray, brown and yellow to P2 on the top card,and the phase shift network leads to the redwires on the underside of the bottom card.These wires should be tied back and clear of allmoving parts, override shaft area and the conduitentry holes.
15. Reconnect 115 VAC power and signal lines toP.C. Cards. Apply a 4 MADC signal and then
page 9
apply 115 VAC power. Place a mark on theoverride coupling (3409). Inject a 20 MADCsignal and count the turns from 4 MADC to 20MADC. There should be ten turns for Series 900,1000 and Hydromyte, and twenty turns for Series2000. Any differences can be adjusted out usingthe ratio pot R130. Before making the finaladjustment to the ratio pot, high limit must bechecked. Apply 20 MADC and very carefullyadjust the ratio pot clockwise (extremely smalladjustments are in order) and note the amountof rotation past one hundred percent. Therecommended allowable is one-eight turn. If thecoupling rotates more tan one-eight (1/8) turnpast one hundred percent, adjust the ratio potcounterclockwise (decreasing capacity) enoughto bring the coupling (3409) one turncounterclockwise from one hundred percent.Adjust the high limit pot (R128) counterclockwiseone turn. Readjust the ratio pot (R130) clockwiseand check maximum rotation past one hundredpercent. Repeat this procedure using smallincremental adjustments until the actuator fallswithin stated operating parameters. After initialadjustment, increments of one half turn or lessshould be used on “HI” pot (R128). Adjust theratio pot (R130) for the one hundred percentposition. Inject a 4 MADC signal to bring theactuator to zero percent capacity. Remove theinput signal altogether and note the amount ofrotation below zero. There should be no morethan one-eight (1/8) turn. If more than one-eight(1/8) turn or jamming occurs, inject 6 MADC andthen adjust the low pot (R129) clockwiseapproximately one half turn. Inject 4 MADC tobring the actuator to zero capacity and thenremove the signal altogether and again observecounterclockwise rotation below zero. Repeatthis procedure using small incrementaladjustments until actuator falls within statedoperating parameters. This concludes theresynchronization procedure.
RETURNING TO SERVICE1. Reconnect wiring to actuator and pump motor
making sure all conduit and hubs are liquid tight.Do not apply power at this time.
2. Connect suction and discharge piping.
3. Adjust oil level as required and replace oil cover.
4. Open any suction and discharge valves andcheck supply vessel for minimum fluid level.
5. Inject a 4 MADC signal and apply 115 VAC powerto the actuator and start the pump motor.
6. Gradually increase input signal to 20 MADCwhile checking for leaks and correct pump/actuator performance (noisy orientation,overcurrent, jamming, etc.). If pump is installedoutdoors in temperatures below 40°F,intermittent actuator stalling may occur. This willnot cause any damage or an out of synccondition. To obtain maximum pump/actuatorperformance, it is recommended that ambienttemperatures above 40°F be maintained.
7. Inject a 4 MADC signal to bring the actuator to0% capacity. Remove power from the pumpmotor, correct any leaks as necessary andrecheck the oil level in the pump (refer to thepump manual for the correct oil grade and level).Be sure all covers are on tight. This is importantto maintain NEMA integrity and prevent liquidentry, which may cause damage to the pumpand the actuator.
8. Adjust capacity decal (3440) to line up withcapacity indicator ring (3412) while the pump isat zero percent capacity position. Replace thescale if it is damaged or hard to read.
9. Pump is ready for service.
OUTDOOR INSTALLATIONSSpecial consideration must be given when the pumpand actuator are used in outdoor service. Avoidlocating the pump and actuator in an area whereflooding or direct water runoff can occur.
Although the pump and actuator are designed foroutdoor service, condensation will form within theactuator housing as temperatures fluctuate,especially in sub-tropical or humid environments.
In all outdoor installations, a space heater shouldbe installed in the actuator enclosure, or the unitshould be heat traced such that a temperature of55-70°F can be maintained.
Properly sized space heaters are available fromNIKKISO Hydroflo®. Consult the factory or your localrepresentative for additional information.
page 10
TB1
- 4-2
0maD
C In
put S
igna
lTB
2 - 1
-60/
50-1
20 P
ower
Inpu
tTB
3 - 4
-20m
aDC
/1-5
VD
C R
etra
nsm
issi
on
Not
es:
1.R
ecom
men
ded
wire
siz
e 16
AW
G a
mx.
2.In
put a
nd re
trans
mis
sion
sig
nal m
ust b
ein
sep
erat
e co
ndui
t fro
m p
ower
inpu
t.3.
Ref
eren
ce b
oard
layo
ut d
raw
ings
-To
p ca
rd -
Inpu
t buf
fer/m
otor
logi
cB
-170
07Bo
ttom
car
d - P
ower
sup
ply/
driv
erB
-170
064.
Con
duit
conn
ectio
n si
ze -
1/2”
- 14
NPT
5.R
emov
e Pl
astic
Plu
g an
d re
plac
e w
ithm
etal
lic to
mai
ntai
n N
MEA
enc
losu
rein
tegr
ity.
End
Vie
w
Hook-Up DiagramElectronic Capactiy Control (Local)
page 11
Top
of A
ctua
tor
Board LayoutPower Supply/Driver
Des
Des
crip
tion
CA,
C5
Cap
acito
r - .0
1UF
500V
C2C
apac
itor E
lec.
470
UF
80V
C3,
C4,
C6
Cap
acito
r .1U
F 50
VC7
Cap
acito
r .01
UF
100V
CR1
Dio
de B
ridge
Rec
tifie
r 1 A
MP
600
PR
VCR
2D
iode
Zen
er 1
3VCR
3D
iode
Zen
er 4
.7V
CR
4, C
R5
Tria
c 80
0V @
8 A
MP
F1Fu
se 3
Am
pP1
Plug
hea
der 4
pos
ition
Q1
Tran
sist
or 2
N22
22A
Q2
Tran
sist
or 2
N30
54R
100,
R10
3R
esis
tor 3
0 O
hms
1/2
wat
t C.C
.R
101,
R10
2R
esis
tor 5
60 O
hms
1/2
Wat
t C.C
.R
104,
R10
5R
esis
tor 3
.9K
Ohm
s 1/
2 W
att C
.C.
R10
6R
esis
tor 1
6.5K
Ohm
s 1/
4 W
att H
.F.
T1Tr
ansf
orm
er 1
20 x
30
100M
ATB
2Te
rmin
al B
lock
2 p
ositi
on ri
ght a
ngle
V1Va
risto
rU1
Volta
ge R
egul
ator
+24
vol
t an7
824
U2Vo
ltage
Reg
ulat
or +
5 vo
lt EC
G 9
77U3
Volta
ge R
efer
ence
1.2
V LM
385Z
1.2
U7,
U8
Tria
c dr
iver
opt
oiso
lato
r MO
C 3
083
page 12
Top
of A
ctua
tor
Ran
geR
ES
Board LayoutInput Buffer/Motor Logic
Des
Des
crip
tion
C10
0C
apac
itor,
.01U
F 10
0V C
eram
icC
101,
103
Cap
acito
r .1
UF
50V
Cer
amic
C10
2C
apac
itor 1
0UF
16V
TA
NT
CR
1D
iode
IN 4
003
P2
Jum
per
Plu
g H
eade
r 4
Pos
ition
Loc
king
Q3,
Q4
Tran
sist
or 2
N22
22A
Q5
Tran
sist
or 2
N24
84Q
6Tr
ansi
stor
2N
2270
R10
0, R
101
Res
isto
r 5.
6K 1
/4W
C.C
. 5%
R10
2R
esis
tor
5.76
K 1
/4W
M.F
. 1%
R10
3R
esis
tor
3.3M
1/4
W C
.C.
5%R
104
Res
isto
r 24
9K 1
/4W
M.F
. 1%
R10
5R
esis
tor
11K
1/4
W M
.F.
1%R
106
Res
isto
r 49
9K 1
/4W
M.F
. 1%
R10
7R
esis
tor
453K
1/4
W M
.F.
1%R
108
Res
isto
r 10
0K 1
/4W
M.F
. 1%
R10
9R
esis
tor
200K
1/4
W M
.F.
1%R
110,
R11
3R
esis
tor
17.4
K 1
/4W
M.F
. 1%
R11
1, R
112
Res
isto
r 20
0 O
HM
S 1
/4W
M.F
. 1%
R11
4R
esis
tor
24.9
K 1
/4W
M.F
. 1%
R11
5, R
116
Res
isto
r 1M
, 1/
4W M
.F.
1%R
117,
R13
3R
esis
tor
249
OH
M 1
/4W
M.F
. 1%
R11
8R
esis
tor
10K
OH
M 1
/4W
M.F
. 1%
R11
9, R
120
Res
isto
r 20
K O
HM
1/4
W M
.F.
1%R
121
Res
isto
r 4.
22K
OH
M 1
/4W
M.F
. 1%
R12
2R
esis
tor
46.4
K O
HM
1/4
W M
.F.
1%R
123
Res
isto
r 3.
01K
OH
M 1
/4W
M.F
. 1%
R12
4R
esis
tor
158K
1/4
W M
.F.
1%R
125
Res
isto
r 49
.9K
1/4
W M
.F.
1%R
126,
R12
7P
oten
tiom
eter
2K
1/2
W M
ulti-
turn
R12
8, R
129
Pot
entio
met
er 1
0K 1
/2W
Mul
ti-tu
rnR
130
Pot
entio
met
er 1
00K
1/2
W S
ingl
e Tu
rnR
131,
R13
2P
oten
tiom
eter
5K
1/2
W M
ulti-
turn
RN
1R
esis
tor
netw
ork
3.9K
OH
MR
N2,
RN
3R
esis
tor
Net
wor
k 10
K O
HM
TB1,
TB
3Te
rmin
al b
lock
2 p
ositi
on r
ight
ang
leTP
2Tu
rret
term
inal
U4
I.C. L
H32
4NU
5I.C
. LH
339N
U6
I.C. C
D40
82B
CN
U7
I.C. L
H35
8NJ1
Jum
per,
shor
ting
page 13
Electrical SchematicInput Buffer/Motor Logic
Not
es:
1. R
ange
resi
stor
sol
dere
d to
boa
rd.
f
or 1
- 5V
DC
rem
ove
249
OH
M2.
U4C
not
use
d
page 14
Electrical SchematicPower Supply & Drive Card
Not
es:
1. R
esis
tor -
Ser
ies
1000
, 200
0 - 5
00 O
HM
S, 2
5 W
atts
S
erie
s 30
00 -
200
OH
MS
, 25
Wat
ts2.
Cap
acito
r - S
erie
s 10
00, 2
000
- 2.5
OU
F, 2
80 V
AC
S
erie
s 30
00 -
4.0U
F, 2
80VA
C3.
Pha
se s
hift
netw
ork
is m
ount
ed s
eper
ate
from
P.C
. Car
d4.
º D
irect
ly w
ired
to s
chem
atic
170
01
page 15
Item Qty Description1 1 4 Pin Connector2 1 4 Pin Dust Cover3 12” 22 AWG Black4 12” 22 AWG Red5 12” 22 AWG White
Black
Red
White
Test Cable - SychronizationLocal Control
Customer Supplied
P/N 17120-1
Test Cable Hook-up Schematic
Wire nut
Ligh
ts w
ith p
igta
ils10
0 W
atts
@ 1
15 V
AC
RedBlack
White
page 16
Series 1000/2000 Motor CouplingInstallation
To a
void
dam
age
to m
otor
appl
y lo
ctite
to I.
D. o
fco
uplin
g ‘O
NLY
’
.010
± .0
05 g
ap
page 17
Not
es:
1. L
ocal
con
trol s
how
n.2.
Rem
ote
cont
rol d
elet
e th
e fo
llow
ing
i
tem
s: 3
417,
342
0, 3
527,
354
7, 3
548
3. P
ump
mod
el &
ser
ial n
umbe
r req
uire
d
to
acc
urat
ely
spec
ify p
arts
whi
ch
va
ry b
y si
ze.
4. A
ll inf
orm
atio
n co
ntai
ned
here
in
su
bjec
t to
chan
ge w
ithou
t not
ice.
Item
Qty
Des
crip
tion
3431
1C
oupl
ing,
mot
or34
322
Set
scr
ew, c
oupl
ing
3433
1S
nap
ring,
act
uato
r34
371
Gea
r, m
otor
3439
1C
ontro
l spo
ol a
ssem
bly
3440
1D
ecal
, cap
acity
3527
1P
C b
oard
ass
y.,
pow
er s
uppl
y/dr
iver
3533
1S
nap
ring
3547
3St
ando
ff, P
c bo
ard
3548
3St
ando
ff, P
C b
oard
3441
1C
lam
p rin
g34
424
Scr
ew, c
lam
p rin
g34
431
Stop
col
lar
Item
Qty
Des
crip
tion
2601
Ref
Hou
sing
Pum
p26
23R
efO
-rin
g, c
ontro
l spo
ol a
ssem
bly
2641
Ref
Scr
ew,
cont
rol s
pool
3401
1A
dapt
er,
hous
ing
3402
1H
ousi
ng34
031
Cov
er,
hous
ing
3404
1Ac
tuat
or34
051
Sha
ft, o
verri
de34
061
Kno
b, o
verri
de34
071
Pla
te, m
otor
3408
1M
otor
3409
1C
oupl
ing
3411
1Sp
ring,
ove
rride
3412
1In
dica
tor,
capa
city
Item
Qty
Des
crip
tion
3413
1P
in,
indi
cato
r34
141
Pla
te, c
apac
ity34
154
Stan
doff,
mot
or p
late
3416
4S
crew
, mot
or p
late
3417
3S
crew
, PC
boa
rd34
184
Scr
ew, c
apac
ity p
late
3420
1P
C b
oard
ass
y. in
put b
uffe
r/m
otor
log
ic.
retra
nsm
issi
on34
22R
efS
et s
crew
, kno
b34
232
Set
scr
ew, c
oupl
ing
3424
1P
in, o
verri
de34
25A/
RB
olt
3426
1O
-rin
g, h
ousi
ng34
271
Sea
l, sh
aft o
verri
de
Electronic Capacity Control ActuatorCross Section & Parts List - Series 1000, all plungers
page 18
Electronic Capacity ActuatorCross Section & Parts List - Series 2000 all plungers
Not
es:
1. L
ocal
con
trol s
how
n.2.
Rem
ote
cont
rol d
elet
e th
e fo
llow
ing
i
tem
s: 3
417,
342
0, 3
527,
354
7, 3
548
3. P
ump
mod
el &
ser
ial n
umbe
r req
uire
d
to
acc
urat
ely
spec
ify p
arts
whi
ch
va
ry b
y si
ze.
4. A
ll inf
orm
atio
n co
ntai
ned
here
in
su
bjec
t to
chan
ge w
ithou
t not
ice.
Item
Qty
Des
crip
tion
3431
1C
oupl
ing,
mot
or34
322
Set
scr
ew, c
oupl
ing
3433
1S
nap
ring,
act
uato
r34
341
Dec
al, c
apac
ity34
351
Gea
r, m
otor
3527
1P
C B
oard
ass
y.,
pow
er s
uppl
y/dr
iver
3533
1S
nap
ring
3547
3St
ando
ff, P
C b
oard
3548
3St
ando
ff, P
C b
oard
3436
1A
djus
ter
hous
ing
3443
1A
djus
ter
4636
1O
-rin
g, a
djus
ter
Item
Qty
Des
crip
tion
3402
1H
ousi
ng34
031
Cov
er,
hous
ing
3404
1Ac
tuat
or34
051
Sha
ft, o
verri
de34
061
Kno
b, o
verri
de34
071
Pla
te, m
otor
3408
1M
otor
3409
1C
oupl
ing
3410
1G
er,
pote
ntio
met
er34
111
Sprin
g, o
verri
de34
121
Indi
cato
r, ca
paci
ty34
131
Pin
, in
dica
tor
3414
1P
late
, cap
acity
3415
4St
ando
ff, m
otor
pla
te
Item
Qty
Des
crip
tion
3416
4S
crew
, mot
or p
late
3417
3S
crew
, PC
boa
rd34
184
Scr
ew, c
apac
ity p
late
3420
1P
C b
oard
ass
y. in
put b
uffe
r/m
otor
log
ic.
retra
nsm
issi
on34
22R
efS
et s
crew
, kno
b34
232
Set
scr
ew, c
oupl
ing
3424
1P
in, o
verri
de34
25A/
RB
olt
3426
1O
-rin
g, h
ousi
ng34
271
Sea
l, sh
aft o
verri
de34
281
Sea
l, sh
aft o
verri
de34
292
Set
scr
ew,
adap
ter
hous
ing
page 19
TROUBLESHOOTING SEQUENCE
SYMPTOM PROBABLE CAUSES RECOMMENDED ACTION
1. Actuator does not Power not present at control Check for power at TB2 “N” and “L” for 115 VAC.respond to input. cards.
Process signal (4-20 MADC/ Check for correct signal at TB1 on top card1-5 VDC) not present at 17007. Connect dvm across “C” and “V1” atTB1. controller. Actuator responds to 4-20 MADC
signal which is converted to 1-5 VDC at TB1.
Process signal connected to Check input/output connections. Refer tosignal output instead of signal hookup diagram.input.
Phase shift network not Check phase shift network connections onconnected or defective. underside of power supply card.
Check phase shift network for shorted or opencomponents. Set OHM meter to Rx10K scale.Needle deflection should rise to approximately1/2 scale and return to 1000K OHMS. If meterdoes not return to 1000K OHMS or does notmove at all, phase shift network is defective.
2. Actuator power supply Shorted motor, phase shift Remove connector from P1 and checkfuse F-1 clears after network or power supply resistance between RED and BLACK wire.application of power. transformer. Reading should be approximately 450-500
ohms; across black or red to white 225-250ohms, and 1000k ohms from any three to theframe. If motor is shorted, contact NIKKISOHydroflo® for a replacement motor.
Check both phase shift network leads for ashort circuit to ground (Casing).
Check power supply transformer for a shortedor open primary/secondary. Resistance at theprimary should be approximately 300 ohms andat the secondary 50 ohms. If the transformer isshorted or open replace entire card set. CallNIKKISO Hydroflo® for replacement parts.
3. Actuator exhibits poor Plus and minus process CHECK CONNECTIONS!response and controls signal wires are switched. Minus (com, lo-), side of process MUST beonly half the output of connected to terminal “C” of TB1, high sidethe pump. to terminal V1.
4. Manual override feature Power still applied to Remove power to actuator.is hard to turn or “feels actuator. orrough”. Does not stay Disable actuator motor via J1. See page 5,positioned. section3, under “SIGNAL INPUTS”.
5. Pump does not respond Drive coupling loose or Tighten or replace drive coupling. See page __to manual override or the broken. under ‘REMOVAL OFautomatic positioner. SYNCHRONOUS MOTOR”.(Positioner turns butactuator coupling 3404does not). Series 900,1000, 2000 and Hydromyte.
Note: The two red wires onthe underside of the powersupply connect to thephase shift network.Disconnect these leads atthe wires for access to thenetwork connectors.
Replacement Part NumbersItem Description Part No. Direct Drive Series3401 adapter, housing 17093-1 10003402 actuator housing 17083-1 all3403 cover housing 17086-1 all3404 actuator 17103-1 all3405 shaft, override 17074-1 all3406 knob, override 17065-0001 all3407 plate motor 17071-1 all
capacitor 2.5Mf 17014-0401 allresistor 500 ohm 17021-0103 allpot bracket 17088-1 allpotentiometer 5k with cable 17123-1 allscrew, rh (4-40 x 1/4”) 07430-2104 allscrew, rh (6-32 x 1/2”) 07430-2208 all terminal qd f 02F6-18279 all terminal qd m 02F8-18278 all vapor capsules 17111-1 all
3408 motor, ac syn 90 oz/in 17109-1 allmotor cable assembly 17122 all
3409 coupling 17087-1 all3410 gear potentiometer 17097-1004 20003411 spring, override 17070-1 all3412 capacity indicator 17090-1 all3413 drive pin, indicator 17102-1 1000
drive pin, indicator 07750-41528 20003414 plate capacity 17092-1 all3415 standoff 17042-1 all3416 screw, motor plate (10-32 x 1/2”) 07460-2408 all3417 screw, pcb (6-32 x 3/8”) 07430-2206 all3418 screw, capacity plate (8-32 x 3/8”) 07410-3306 all3420 pcb set, power supply/input buffer 17108-1 all3422 set screw knob (10-32 x 3/8”) 07310-4406 all3423 set screw, coupling (8-32 x 1/4”) 07310-4304 all3424 pin override 12530-0207 all3425 stud a/r all3426 o-ring housing 12020-1125 all3427 seal, shaft override 15036-1005 all3428 adapter, housing 17091-1 20003429 set screw (3/8-16 x 1/2”) 07310-4908 20003431 coupling motor 17104-1 all3432 set crews motor (8-32 x 3/16”) 07310-4303 all3433 snap ring, actuator 07900-4100 all3434 decal capacity scale 12135-0 20003435 gear motor 17091-1001 20003437 gear, motor 17097-1002 10003438 gera, potentiometer 17097-1003 10003440 decal capacity scale 12544-0 10003441 clamp ring 17049-1 10003442 screw, clamp ring (10-32 x 1/2”) 07100-4408 10003533 snap ring 17075-1101 all3547 standoff 2” 17024-31250 all
washer #8 fiber, non-metallic 07800-10200 all3548 standoff 1-1/2” 17024-31203 all
page 20
page 21
PARTS ORDERING INSTRUCTIONS
Always have the complete NIKKISO Hydroflo®
pump model and serial number available whencontacting NIKKISO Pumps America, Inc. for partsor service. This information can be found on thenameplate mounted on the side of the pump.
Because of the complicated solid-state circuitrycontained in the control unit, we do notrecommend field servicing unless the necessarytools and test equipment are available.
Should it be necessary to send the pump andelectric capacity control to the factory for repair orservice, thoroughly flush the pump liquid end ofall process fluid, drain all hydraulic oil, pack securelyfor shipment, and call factory for a returnauthorization number. A material safety data sheet(MSDS) and a signed Return Goods Authorizationform will be required. Equipment received withoutreturn authorization number will not be accepted.
Direct all inquiries and orders to your localrepresentative or directly to:
AquFlow1642 McGaw Ave
Irvine, CA 92614Telephone: (949) 757-1753
Fax: (949) 757-1687Website: www.aquflow.comE-mail: [email protected]
AquFlow®
CHEMICAL METERING PUMP
MODEL CJ4T 11314-04014
SERIAL 1234567
CAPACITY 25.7 GPH
PRESSURE 425 PSIG
AquFlow Pumpwww.aquflowpumps.com
2001 NPA AquFlow Pumps
1642 McGaw Ave • Irvine, CA 92620Phone (949) 757-1753 • Fax (949) 757-1687
email: [email protected] http://www.aquflowpumps.com
Printed in U.S.A. 11/01
Bulletin 24200.60