Upload
leliem
View
217
Download
0
Embed Size (px)
Citation preview
Ja mes Goerl M etro Protec tion Sys tems , Inc . jg oe r l@m etroprotec t ionsys tem s .com
WHO, WHERE, WHY, HOW, & WHEN ?? A GUIDE TO FIRE SUPPRESSION SUB-SYSTEMS AND THE LATEST CODE REQUIREMENTS
BUILDING SUB-SYSTEMS
Different Types of Sub Systems that Exist in NYC • How do they work to suppress fires? • What are the code requirements for Servicing? • Who is permitted to perform inspections & service on these systems?
• What is the inspection/testing frequency for these systems?
• Questions
Agenda
• Chapter 9 - Covers all Building Fire Systems – Design, Installation, Operation, and Maintenance, including Inspections and Testing of Fire Protection Devices, equipment, and Systems, and other fire protection measures for the control and extinguishment of fire.
• Recognizes NFPA Standards as Reference Standards
• Kitchen Hood Extinguishing Systems – NFPA 17 or NFPA 17A
• Water Based Fire Protection Systems – NFPA 25 (Preaction)
• Halon 1301 Systems – NFPA 12A
• Clean Agent Fire Suppression Systems – NFPA 2001
• Fire Alarm Systems (Related to Sub-Systems) – NFPA 72
• Foam Water Sprinkler and Spray Systems – NFPA 16
• Watermist Systems – NFPA 750
NYC Fire Code – 2008 Edition
Key Aspects of Code FDNY Now Provides Certificate of Approval
• No longer is MEA Required (Department of Buildings Approvals of Equipment) FDNY to issue Approvals for Pre-Engineered Non Water Systems, including Systems for Commercial Cooking
• Prefabricated Hoods and Grease Filters installed in Connection with commercial cooking systems
• Fire Department Siamese Connections, standpipe system hose outlets, and pressure reducing valves
• Fire Alarm System Control Panels Out of Service Systems – Now Covered by Specific Requirements for Action / Notification
• Impairment Coordinator – Assigned by Building Owner • Tag / Disc Required • Notification to FDNY Borough Communications Office
NYC Fire Code – 2008 Edition
Systems must be in compliance with UL 300 – Wet chemical systems only – can no longer install dry chemical for Kitchen Systems
• Inspections once a month – Trained and Knowledgeable Person to Access that the system is in good working order
• Quarterly Cleaning of Exhaust System - Hood, Filters, Grease Removal devices, Ducts, Fans, Pollution Control Devices, etc. • Cleaning Technician must possess W-64 - Commercial
Kitchen Exhaust System Cleaning Technician Certificate of Fitness
• Semi-Annual Testing conducted by Master Fire Suppression Piping Contractor - Must have Factory Certification for the specific brand of system that is being serviced
Kitchen Hood Extinguishing Systems (FC 904.11)
Preaction Systems – Used for Special Hazard / Mission Critical Hazards
• Sprinkler Valve Assembly keeps water from sprinkler pipe until a “PRE” condition takes place – Smoke detection, Thermal detection, Flame detection, Manual Release Station
• Building Fire Alarm System is activated
• Sprinkler Valve Opens to Fill Piping with Water – System reverts to Conventional Wet Sprinkler System
Water Based Fire Protection Systems (FC 903)
Preaction Sprinkler and Dry Pipe Systems (Cold Storage Areas)
• Inspections once a month – Trained and Knowledgeable Person to Access that the system is in good working order – Inspector must possess S-12 - Certificate of Fitness for Citywide Sprinkler Systems (or Operating Engineer Q-01 & Q-99 with S-12 Certificate of Fitness)
• Quarterly Testing conducted by Master Fire Suppression Piping Contractor or S-12 Certificate of Fitness Holder - Certificate of Fitness for Citywide Sprinkler Systems (or Operating Engineer Q-01 & Q-99 with S-12 Certificate of Fitness)
• Tamper / Low Air / Waterflow
• Annual System Valve Test conducted by Master Fire Suppression Piping Contractor
Also –
• Fire Alarm components associated with water based fire protection system require semi-annual cleaning (smoke detectors) and annual smoke entry / sensitivity testing
• Fire Alarm Technician must possess S-98 - Fire Alarm Systems Inspection, Testing, and Service Technician Certificate of Fitness (Cleaning Technician Only may possess S-78 C of F)
Water Based Fire Protection Systems (FC 903)
Standpipe Systems
• Inspections once a month – Trained and Knowledgeable Person to Access that the system is in good working order – Inspector must possess S-13 - Certificate of Fitness for Citywide Standpipe Systems (or Operating Engineer Q-01 & Q-99 with S-13 Certificate of Fitness)
• Quarterly Testing conducted by Master Fire Suppression Piping Contractor or S-13 Certificate of Fitness Holder - Certificate of Fitness for Citywide Standpipe Systems (or Operating Engineer Q-01 & Q-99 with S-13 Certificate of Fitness)
• Waterflow
• Tamper Valves
• Annual System Flow Test conducted by Master Fire Suppression Piping Contractor
Water Based Fire Protection Systems (FC 903)
New FDNY Requirements for Preaction New Installations
Bulletin # 08-01-12 (replaces EUIB 08-02-11)
** Elimination of Preaction System Audible Devices – A sufficient Quantity of Building Fire Alarm Audio/Visual devices should be installed
** Require a control panel listed for releasing service (not a relay from Building Fire Alarm System to trip solenoid)
** Building fire alarm system smoke detector shall be installed at preaction control panel where installed in an area not continuously occupied
** ALARM, SUPERVISORY, & TROUBLE SIGNALS to Bldg. FA
Remote alarm indicator (Graphic Display or an Approved Map typically used with an Addressable System)
** Fuse Cut-Out or General Service Disconnect Switch with Power Source Local to Protected Space
Solid # 10 – Building Steel to Control Panel – No Bonding of Neutral
Local disconnect switch for air compressor
All sub-system components installed in EMT / Conduit with THHN or 1500 FDNY Approved Cabling
**Preaction Panel located OUTSIDE of preaction protected space unless part of cabinet system – FirePac, PrePac, TotalPac
** HVAC Shutdown – Required when HVAC Units are installed on a raised floor, cooling underfloor cables
HVAC Shutdown – Not Required with stand-alone unit in preaction space where no raised floor exists
** Where panel is located in a concealed space, some means of identification (light / audible) indicating its location, shall be installed
Preaction protected space shall be clearly identified with placard, which also lists the location of the preaction valve and control panel
** Underfloor smoke detection for raised floor areas for preaction
Cross zoning of smoke detectors for Preaction Systems is prohibited
Tamper Valves / Air Supply – all electrically supervised – NO CHAINS
New FDNY Requirements for Preaction New Installations
Halon • First true clean agent fire suppression • Fast suppression • Minimal damage • SAFE for occupied spaces • Ozone Depleting Gas
• Molecular structure similar to Freon
NYC Suppression Systems (Halon 1301) Require Monthly Visual Inspections conducted by a Trained and Knowledgeable person to access whether the system is in good working order. (FC 904.9.1)
A Licensed Master Fire Suppression Piping Contractor shall inspect, test service, and otherwise maintain such systems on a semi-annual basis.
Halon 1301 – Fire Suppression Systems – (FC 904.9)
No Longer Installed Domestically
Halon 1301 will remove the air from the protected space • NO! – Halon is safe
to breathe • Protects all of the
token booths in the NYC Transit system
Halon 1301 systems have been banned • NO! – Can
continue in service – replacement at the discretion of client
Misunderstandings about Halon 1301
Clean Agent Systems– Used for Special Hazard / Mission Critical Hazards
• Gaseous Fire Suppression Systems designed to fill an enclosure with a gas that will suppress the fire without causing damage to people, the equipment in the protected space, and the business continuity
• Various agents used are environmentally friendly – non-ozone depleting, safe on people, effective on fires with limited or no damage
Clean Agent Fire Suppression Systems (FC 904.10)
A variety of different gases each with their own strengths and weaknesses
HFC-227ea (DuPont - FM-200® )
FK-5-1-12 (3MTM NovecTM 1230 Fire Protection Fluid or SapphireTM)
HFC-125 (Fike - Ecaro 25)
HFC-23 (DuPont FE-13)
IG-55 (Ginge-Kerr - Argonite®)
IG-541 (Ansul - Inergen®)
Clean Agent Fire Suppression Systems (FC 904.10)
Principles of Fire Suppression
• Heat Absorption (Like a Sponge Soaking up Liquid) at a Molecular Level
• FM-200 • Novec 1230 • Ecaro 25 • FE-13
• Lowering Oxygen – Reducing oxygen in protected space to a level lower than required for the propogation of flame
• Inergen • Argonite
Clean Agent Fire Suppression Systems (FC 904.10)
NYC Suppression Systems (Clean Agent) Require Monthly Visual Inspections conducted by a Trained and Knowledgeable person to access whether the system is in good working order. (FC 904.10.1)
A Licensed Master Fire Suppression Piping Contractor shall inspect, test service, and otherwise maintain such systems.
Clean Agent Fire Suppression Systems (FC 904.10)
Fuse Cut-Out or General Service Disconnect Switch with Power Source Local to Protected Space
Solid # 10 – Building Steel to Control Panel – No Bonding of Neutral
Clean Agent Panel located INSIDE of Clean Agent protected space
HVAC Shutdown / Damper Closures – Always Required for Clean Agent Systems to prevent loss of agent, except stand-alone unit in clean agent space where no raised floor exists
FDNY Requirements for Clean Agent Systems – New Installations
Audio Visual Indication (FC 904.10.4) for First Alarm, 2nd Alarm & Discharge
Abort Station – (FC 904.10.5) (If Installed) NYC Sequence – 90 second investigative time delay
Audio Indication during Investigative Timer – Reverts back to First Alarm Indication
Manual Pull Station Overrides the Abort Time Delay
EPO – Not a requirement for Clean Agent Systems – recommended via a Pressure Operated Switch
FDNY Requirements for Clean Agent Systems – New Installations
Installed in accordance with NYC Electrical Code
Smoke Detector spacing in accordance with NFPA-72 – air changes per hour
6 air changes/Hour – 900 sq. ft
30 air changes/Hour – 250 sq. ft.
60 air changes/Hour – 125 sq. ft.
Detectors > 3’ from air registers
Beam depths - 12’ ceilings w/ 1’ beams – detectors located at bottom of beam
Beam depths - >12’ ceilings w >1’ beams – detectors located in each beam pocket
FDNY Requirements for Clean Agent Systems – New Installations
Warning & Instruction Signs – (FC 904.10.4.1) Clean Agent protected space shall be clearly identified with warning placards and appropriate audio/visual indications
FDNY Requirements for Clean Agent Systems
Underfloor Protection – Installation of Smoke Detectors in Areas with cabling and other combustibles
Graphic Annunciator or Approved Indicator
FDNY Requirements for Clean Agent Systems
Purge for Clean Agent Systems – Not required for MAIN ONLY systems (FC 904.10.7)
When required, purge must be sized for air exchange of 6 air changes per hour, to outside of protected space
Purge Key to be provided outside of Clean Agent protected Space to Open purge damper and turn-on purge fan
Pressure Relief Venting – Inert Gas Systems shall be provided with suitable pressure relief venting for the flooded area that discharges outdoors
FDNY Requirements for Clean Agent Systems – New Installations
NFPA-2001 – 2004 – Pipe Pressure Test – 6.7.2.2.12 – The piping system shall be pneumatically tested in a closed circuit for a period of 10 minutes at 360 psi. At the end of 10 minutes, the pressure drop shall not exceed 20 percent of the test pressure.
NFPA-2001 – 2004 – Pipe Puff Test – 6.7.2.2.13 – A flow test using nitrogen or an inert gas shall be performed on the piping network to verify that flow is continuous and that the piping and nozzles are unrestricted.
NFPA-2001 – 2004 – Review Enclosure Integrity– 6.7.2.3 – All total flooding systems shall have the enclosure examined and tested to locate and effectively seal any significant air leaks that could result in the failure of the enclosure to hold the specified agent for the specified time.
FDNY Requirements for Clean Agent Systems – New Installations
Door Closures / Door Sweeps / Rubber Gasketing
Clean Agent System components are easily accessible
FDNY Requirements for Clean Agent Systems – New Installations
Fire Stopping of Penetrations
Integrity of the Hazard
FDNY Requirements for Clean Agent Systems New Installations
Carbon Dioxide Systems – Suppress Fire by Removing Oxygen • Ansul / Tyco • Kidde Fire Systems • Chemetron
Existing total flooding carbon dioxide fire extinguishing systems installed to protect normally occupied areas prior to the effective date of this code (July 2008) may be continued in service until July 1, 2013, after which they will be removed from service, and a replacement fire extinguishing system shall be installed.
Carbon Dioxide Fire Suppression Systems (FC 904.8)
NYC Suppression Systems (Carbon Dioxide) Require Monthly Visual Inspections conducted by a Trained and Knowledgeable person to access whether the system is in good working order. (FC 904.8.1)
A Licensed Master Fire Suppression Piping Contractor shall inspect, test service, and otherwise maintain such systems on a Semi-Annual basis.
Carbon Dioxide Fire Suppression Systems (FC 904.8)
Water Based Foam Systems – Low Expansion or High Expansion • Ansul / Tyco • Fire Flex • National Foam
Foam Water Fire Suppression Systems (FC 904.7)
NYC Suppression Systems (Foam) Require Monthly Visual Inspections conducted by a Trained and Knowledgeable person to access whether the system is in good working order. (FC 904.7.1) A Licensed Master Fire Suppression Piping Contractor shall inspect, test service, and otherwise maintain such systems on an Annual basis.
New Systems create fog like environment to suppress fire • Marioff (UTC) • Secureplex • Victaulic (Vortex) • Fike
Watermist Fire Suppression Systems (FC 904.12)
NYC Suppression Systems (Watermist) Require Monthly Visual Inspections conducted by a Trained and Knowledgeable person to access whether the system is in good working order. (FC 904.12.1)
A Licensed Master Fire Suppression Piping Contractor shall inspect, test service, and otherwise maintain such systems on an Annual basis.
Watermist Fire Suppression Systems (FC 904.12)
•Approved by U.S. EPA for unoccupied & normally unoccupied areas.
•Safe for personnel at normal design parameters with evacuation time delays.
•Non-Corrosive - extensive tests have been run on a wide variety of structural and specialized materials used in electronics and aviation.
•Significant installation and maintenance savings…does not require pressure vessels, manifolds, nozzles or pipe work.
•Weight and space reductions up to 90% over conventional systems.
Aerosol Technology – Site Specific FDNY Approval
Non-Permeable Membrane
Exit Ports
Insulating Medium
Aerosol Forming Compound
Cooling Element
Oxidation Element
Initiator Element
Upon activation, an aerosol of ultra-fine particles (≤ 2 micron) is dispersed under low pressure (< 50 psi )
Aerosol Technology
Inspections / Service Summary
SYSTEM MONTHLY INSPECTION REQUIRED
QUALIFICATIONS FOR MONTHLY
TESTING FREQUENCY
QUALIFICATIONS FDNY TESTING
KITCHEN YES TRAINED & KNOWLEDGABLE
SEMI-ANNUAL W-64 / FACTORY CERTIFIED
TECHNICIAN
INITIAL INSTALL
PREACTION YES S-12 QUARTERLY S-12 / MFSPC ANNUAL TRIP 5 YR. FDNY
HALON YES TRAINED & KNOWLEDGABLE
SEMI-ANNUAL MFSPC INITIAL INSTALL
CLEAN AGENT
YES TRAINED & KNOWLEDGABLE
SEMI-ANNUAL MFSPC INITIAL INSTALL
WATER -FOAM
YES TRAINED & KNOWLEDGABLE
QUARTERLY MFSPC INITIAL INSTALL
CARBON DIOXIDE
YES TRAINED & KNOWLEDGABLE
SEMI-ANNUAL MFSPC INITIAL INSTALL
WATERMIST YES TRAINED & KNOWLEDGABLE
QUARTERLY MFSPC INITIAL INSTALL
FDNY Website for Listings of Authorized Smoke Detector Service Companies Company Principal – S-97 Technicians – S-98 & S-78 Sprinkler Testing – MFSPC or MP Technicians / Inspectors – S-12 & S-13 All Inspections on All Sub-systems to be Recorded in Fire Alarm Log book with Appropriate Certificate of Fitness #