Pizzeria Restaurant May 14, 2002
PHONE 847.398.0250 TOLL-FREE 800.XDX.0250 FAX 800.XDX.9656 3176 NORTH KENNICOTT AVE ARLINGTON HTS, ILLINOIS 60004
WWW.XDXUSA.COM
Type: Walk-In Freezer Walk-In Cooler Customer: Pizzeria Chain Restaurant Equipment Specification: Freezer:
• Bohn Evaporator LET0901F, Serial No. D94K01464, 9,000 BTU’s • Copeland Compressor AH55RT-169-P2 • XSTREAM® B Valve, Low Temp, R404 Cooler: • Bohn Evaporator ADT090AJ, Serial No. D95C08340, 9,000 BTU’s • Copeland Compressor REY3-0175-TFC-950, Serial No, 96D06612 • XSTREAM® B Valve, Med Temp, R22
Protocol:
• Temp/RH: o Temp Tale Temperature/RH sensors were used to monitor temperature/RH o 14,148 points monitored
• Power (freezer only):
o E Server was used to monitor: kWh, kW, KVA, PF, Volts AB, Volts AC, Volts BC, Amps A, Amps B, Amps C, kW Average, kW Minimum, and kW Maximum
o 56,000 points monitored
PHONE 847.398.0250 TOLL-FREE 800.XDX.0250 FAX 800.XDX.9656 3176 NORTH KENNICOTT AVE ARLINGTON HTS, ILLINOIS 60004
WWW.XDXUSA.COM
FREEZER BENEFITS
Conventional Freezer Operation 4 Defrosts a Day
XDX® Freezer Operation 2 Defrosts a Day with Lower Average Temperatures
PHONE 847.398.0250 TOLL-FREE 800.XDX.0250 FAX 800.XDX.9656 3176 NORTH KENNICOTT AVE ARLINGTON HTS, ILLINOIS 60004
WWW.XDXUSA.COM
XDX® maintains 78% colder average temperature & reaches 22% lower temperature in freezer
-12
-10
-8
-6
-4
-2
0
-20.27
-22.77-22.22
-23.88
Conventional XDX® Conventional XDX®
PHONE 847.398.0250 TOLL-FREE 800.XDX.0250 FAX 800.XDX.9656 3176 NORTH KENNICOTT AVE ARLINGTON HTS, ILLINOIS 60004
WWW.XDXUSA.COM
Freezer Total Defrost Duration
XDX® Decreased Defrost Time by 64% 24 Hour Sample
Conventional Operation: 374 minutes/24 hours XDX® Operation: 132 minutes/24 hours
374
132
0
50
100
150
200
250
300
350
400
Conventional XDX6.2 hours 2.2 hours
PHONE 847.398.0250 TOLL-FREE 800.XDX.0250 FAX 800.XDX.9656 3176 NORTH KENNICOTT AVE ARLINGTON HTS, ILLINOIS 60004
WWW.XDXUSA.COM
81/Minutes
Freezer Pull-Down XDX® Decreased Pull-Down Time by 42%
Single Defrost Pull-Down
81
47
0
10
20
30
40
50
60
70
80
90
Conventional XDX
81 Minutes
47 Minutes
PHONE 847.398.0250 TOLL-FREE 800.XDX.0250 FAX 800.XDX.9656 3176 NORTH KENNICOTT AVE ARLINGTON HTS, ILLINOIS 60004
WWW.XDXUSA.COM
Freezer Run-time Decreased 25% with XDX®
-20-19-18-17-16-15-14-13-12-11-10-9-8-7-6-5-4-3-2-10
1-hr sample of supply air for a walk-in freezer during conventional operation-1k30
Series1
1 hr sample of supply air for a walk-in freezer during XDX operation-1l16
-20-19-18-17-16-15-14-13-12-11-10
-9-8-7-6-5-4-3-2-10
12:00
:26 A
M
12:02
:26 A
M
12:04
:26 A
M
12:06
:26 A
M
12:08
:26 A
M
12:10
:26 A
M
12:12
:26 A
M
12:14
:26 A
M
12:16
:26 A
M
12:18
:26 A
M
12:20
:26 A
M
12:22
:26 A
M
12:24
:26 A
M
12:26
:26 A
M
12:28
:26 A
M
12:30
:26 A
M
12:32
:26 A
M
12:34
:26 A
M
12:36
:26 A
M
12:38
:26 A
M
12:40
:26 A
M
12:42
:26 A
M
12:44
:26 A
M
12:46
:26 A
M
12:48
:26 A
M
12:50
:26 A
M
12:52
:26 A
M
12:54
:26 A
M
12:56
:26 A
M
12:58
:26 A
M
Series1
Freezer Conventional Operation - 4-minute Run Cycle
XDX® Freezer Operation - 3-Minute Run Cycle
12:25:39
12:32:39
12:28:39
12:08:39
12:37:39
12:04:39 AM
12:50:39
12:22:39
12:18:39
12:41:39
12:15:39
12:34:39
12:56:39
12:04:39
AM 39 AM
12:03.26
12:09:26
12:16:26
12:22:26
12:34:26
12:44.26
12:50:26
12:56:26
12:30:26
12:19:26
12:39:26
12:47:26
12:53.26
12:06:26
12:12:26
12:11:39
12:04:39
AM 39 AM
12:54:39
12:04:39
AM 39 AM
12:47:39
12:04:39
AM 39 AM
12:44:39
12:04:39
AM 39 AM
PHONE 847.398.0250 TOLL-FREE 800.XDX.0250 FAX 800.XDX.9656 3176 NORTH KENNICOTT AVE ARLINGTON HTS, ILLINOIS 60004
WWW.XDXUSA.COM
COOLER BENEFITS
XDX® Maintains an Average Temperature of 3.27°C vs.
Conventional Operation which Averaged 5.11°C
XDX and Conventional Box temperature for a walk-in cooler during a 24 hr sample
25272931333537394143454749515355
12:0
1:58
12:4
9:58
1:37
:58
2:25
:58
3:13
:58
4:01
:58
4:49
:58
5:37
:58
6:25
:58
7:13
:58
8:01
:58
8:49
:58
9:37
:58
10:2
5:58
11:1
3:58
12:0
1:58
12:4
9:58
1:37
:58
2:25
:58
3:13
:58
4:01
:58
4:49
:58
5:37
:58
6:25
:58
7:13
:58
8:01
:58
8:49
:58
9:37
:58
10:2
5:58
11:1
3:58
Time
Tem
p
XDX BOXConv Box
XDX and Conventional Box temperature for a walk-in cooler during a 24 hr sample
PHONE 847.398.0250 TOLL-FREE 800.XDX.0250 FAX 800.XDX.9656 3176 NORTH KENNICOTT AVE ARLINGTON HTS, ILLINOIS 60004
WWW.XDXUSA.COM
Conventional Maximum Cooler Case Temperature 7°C
XDX® Maximum Cooler Case Temperature 4.72°C
3839404142434445
Conventional XDX
7
4.72
Conventional XDX
PHONE 847.398.0250 TOLL-FREE 800.XDX.0250 FAX 800.XDX.9656 3176 NORTH KENNICOTT AVE ARLINGTON HTS, ILLINOIS 60004
WWW.XDXUSA.COM
Conventional Cooler Operated 423 Minutes over 5°C
XDX® Never Operated over 5°C 24-Hour Sample
423
0
0
100
200
300
400
500
Conventional XDX7.05 Hours 0.0 Hours
Conventional XDX
PHONE 847.398.0250 TOLL-FREE 800.XDX.0250 FAX 800.XDX.9656 3176 NORTH KENNICOTT AVE ARLINGTON HTS, ILLINOIS 60004
WWW.XDXUSA.COM
Conventional and XDX KWH comparison during a 24 hr period on the walk-in freezer-1L16
02468
101214161820222426283032343638404244
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47
24 hr duration
KW
H Kwh ConvKwh XDX
kWh Comparison Conventional vs. XDX®
Power Consumption Decreased 17.7%
Conventional and XDX KWH comparison during a 24 hr period
PHONE 847.398.0250 TOLL-FREE 800.XDX.0250 FAX 800.XDX.9656 3176 NORTH KENNICOTT AVE ARLINGTON HTS, ILLINOIS 60004
WWW.XDXUSA.COM
XDX® Energy Savings Benefit
3,394.60 kWh Annually 2,640.00 kWh Freezer 754.60 kWh Walk-In Cooler 3,394.60 x .074¢ $251.20 Reduction in kW during demand .5 kW @ $5.56 $ 66.72 $ 317.92 (US) Future Replacement Current 1 ¾ hp Change Out 1 hp = $ 75.00 reduction $392.92(US)
PHONE 847.398.0250 TOLL-FREE 800.XDX.0250 FAX 800.XDX.9656 3176 NORTH KENNICOTT AVE ARLINGTON HTS, ILLINOIS 60004
WWW.XDXUSA.COM
FREEZER Conventional Operation:
• Defrosted four times a day, thirty-five minutes each • System operated at an average temperature of –20.2°C • Conventional system reached lowest temperature of -22.7°C • System defrost duration in a 24-hour period is 6.2 hours • System pull-down after defrost took 81 minutes • Operated with an average 4-minute run-time cycle
XDX® Benefits: • Decrease to two defrosts a day, thirty-five minutes each, a 50% decrease • XDX® system maintains 78% colder average temperature, averaging
-22.2°C • System reaches 22% lower temperature of -23.8°F • XDX® defrost duration in a 24-hour period is 2.2 hours, a reduction of
64% • System pull-down after defrost is 47 minutes, a 42% decrease • Operates with a 25% decrease in run-time, averaging 3-minutes per cycle
COOLER Conventional Operation:
• System operated at an average temperature of 5.11°C • Conventional system operated over 5°C over 7 hours • Defrosted 3 times a day, 40 minutes each
XDX® Benefits: • XDX® maintains an average temperature of 3.27°C • System never operated over 5°C • Decreate to two defrosts a day, forty minutes each, a 33% decrease
XDX® ENERGY BENEFITS
• Overall kWh reduction of 17.7% • $317.92 (US) annual savings in kWh