Easy. Safe. Simple.Access for Maintenance
to Cooling Towers
Paul DaviesRepresenting
Clint LewisRepresenting
• Types of Cooling Towers typically offered in the HVAC Industry
• Overview of Cooling Tower components requiring access for maintenance.
• Design obligations and standards surrounding hygiene, access and maintenance of Cooling Towers.
• Access options that meet requirements.
• Questions
Introduction
Types of Mechanical Draft Cooling Towers (airflow)
• Forced Draft Equipment
› One or more fans are located
at the air inlet to force air into
the tower
• Induced Draft Equipment
› One or more fans are located
in the air outlet to induce air
flow through the air inlets
Types of Fluid Paths in Cooling Towers
• Crossflow - Air flows horizontally through the cooling tower and interfaces perpendicularly with the falling hot water
• Counterflow - Air enters at the base of the cooling tower, flows upward and interfaces counter-currently with the falling hot water
Water
Air
Water
Air
Induced Draft COUNTERFLOW Equipment Principle of OPERATION
Induced Draft CROSSFLOW Equipment Principle of OPERATION
Dual Air InletSeries 3000
Single Air InletSeries 1500
Common Components requiring regular access for maintenance
DRIVE SYSTEM Crossflow and Counter
Flow
COLD WATER BASIN Crossflow and Counter
Flow
BELT DRIVE SYSTEM
Common Components requiring regular access for maintenance
BASIN SWEEPERS
Common Components requiring regular access for maintenance
PVC FILL Crossflow and Counter
Flow
PVC ELIMINATORSCounterflow
Common Components requiring regular access for maintenance
SPRAY SYSTEM Crossflow and Counter
Flow
AIR INLET LOUVRES Crossflow and Counter
Flow
Design Obligations
Australian Standard 3666(Air-Handling & Water Systems of Buildings– Microbial Control)
Clause 4.1.1 - Access for maintenance:
“Easy and safe access for cleaning, inspection and maintenance shall be available to and about all plant, equipment and components covered in this Section”.
Clause 4.1.5 - Cooling towers:
“Cooling towers shall be fabricated from corrosion resistant materials, and shall be designed for ease of maintenance, particularly for cleaning of fill, water distribution system, basin and sumps.”
Design Obligations
Australian Standard - AS1657Fixed platforms, walkways, stairways and ladders –
Design, construction and installation
• AS1657 is the Australian Standard that all designers, builders and suppliers of Access Solutions MUST design, select, construct and install to.
• The standard outlines all of the design clearances, tolerances and material types for compliant access solutions.
Design Obligations
SAA HB 32 - 1992
Clause 6.2 - Access for maintenance:
In Summary –• All cooling tower installations should allow for access to items
such as , Water Distribution, Pipework Headers, Heat Exchange Fill Media etc.
• Cooling Tower installations should be provided with appropriate FIXED access ladders, internal/external walkways, handrails, toeguards and platforms all in accordance with AS1657.
Design Obligations
Queensland Government Workplace Health and Safety Supplement No.2 to the
PLANT ADVISORY STANDARDClause 3 -Design and installation of cooling water systems
• “Easy and safe access should be available to cooling water systems. The design of the system should facilitate regular maintenance and cleaning.”
Clause 5.3 -Who else has workplace health and safety obligations in relation to microbial control in cooling systems of buildings?
• Designers – to ensure the plant is designed properly.• Installers – to ensure the plant is installed safe and without risk• Employers – To ensure health and safety is not affected by the way the
person conducts the person’s undertaking.
Access Considerations
PIER HEIGHTS• Piers allow for all pipework to be under the towers to allow
“freedom” to move around the plant• Piers also allow for a flooded suction to Condenser pumps
Access Considerations
EXTENTS OF EXTERNAL WALKWAYS REQUIRED• Low Level – Basin Access• Mid Level – Fill and CIS Access• High Level – Water Distribution Access (Spray System)
Access Considerations
EXTENTS OF INTERNAL WALKWAYS REQUIRED
• Low Level – Basin Access• High Level – Drive access
Site Examples(180 Anne St)
Site Examples(Sunshine Coast Uni Hospital)
Site Examples(Canelands)
Site Examples(K1)
Site Examples(Orion Shopping Centre)
Presented by: Clint LewisApplications Engineer, Baltimore Aircoil AustraliaTel: +(61) 02-4340-9004 Mob: +61 417-066-149Email: [email protected] | Web: www.baltimoreaircoil.com.au