EARTHING DESIGNE

Embed Size (px)

Citation preview

  • 8/19/2019 EARTHING DESIGNE

    1/17

    EARTHING AND

    CONSIDERATIONS FOR ITS

    DESIGNPresenter : Dr. J. K. Arora

     An earthing system is the total set of measures usedto connect an electrically conductive part of the

    power system to earth.

    • A well-designed earthing system ensures correct operation

    of protective devices on occurrence of earth faults orlightening strikes, safety of equipment and personnel and

     prevents build-up of electrostatic charges or occurrence of

    dangerous induced voltages on equipments and structures.

  • 8/19/2019 EARTHING DESIGNE

    2/17

    ROLES OF EARTHING SYSTEM

    i) Correct operation of the electric network, leading

    to good power quality through:• Low zero sequence impedance for return of

    unbalanced fraction of three-phase ac

    • Rapid and unambiguous identification of fault

    conditions for efficient relay and fuse coordination

    ii) To ensure electrical safety for exposed humans

    and animals by:

    • Fast identification of faults, leading to reducedfault duration

    • Limiting touch and step voltages and resulting

    body currents to safe values

  • 8/19/2019 EARTHING DESIGNE

    3/17

    iii) To protect against lightning by:

    • Limiting potential differences across electrical

    insulation on stricken equipment• Providing low-impedance paths for dissipation

    of stroke current energy

    iv) Providing low-impedance paths for dissipation

    of stroke current energy

    EARTH ELECTRODEA conductor or group of bare conductors in

    intimate contact with, and providing an electrical

    connection to earth

    Simple Electrode or combination of simple electrodes

  • 8/19/2019 EARTHING DESIGNE

    4/17

     

    Figure 1. Current dissipation through soil fromlong vertical rod electrode

  • 8/19/2019 EARTHING DESIGNE

    5/17

    IMPORTANT PARAMETERS

    Efficacy of an earth electrode determined from

    i) earth resistance of the electrodeii) the dangerous voltages namely maximum value of

    step voltage and touch voltage

    iii) transferred potential

    Earth resistance - A function of i) Soil resistivity, ii)electrode geometry defined by shape, dimensions

    and layout of earth conductors forming the

    electrode, iii) its depth of burial, and pattern of

    current dissipation in earth around the electrodeDangerous voltages depend on aforementioned factors

    and magnitude of current that flows between grid

    electrode and the surrounding soil

  • 8/19/2019 EARTHING DESIGNE

    6/17

    Earth Electrodes & Earth Resistance

    • Metallic rods buried vertically into earth orhorizontal bars or strips or a combination of both

    • Earth resistance not due to conductors but due to

    flow of current across the soil• Current flow between earth electrode near fault

    to ground electrodes towards sources of current

    • Current flow assumed to be flowing acrosshemispheres of increasing surface areas

    • Resistivity of conductor a few micro-ohm-m,that of soil a few ohm-m to hundreds of ohm-m

  • 8/19/2019 EARTHING DESIGNE

    7/17

    • Resistance of conductors of ground electrode is

    negligible

    • Resistivity of mass of soil important; at a distancewhich is about 5-10 times the extent of electrode, cross-

    sectional area of current path is so large that additional

    resistance of soil beyond it is very small

    • Size of electrode is important; ground resistanceinversely related to size. Same material concentrated in

    a small volume has larger ground resistance than when

    spread over a larger area

    • If soil is rocky or sandy, good option to encase the

    conductors in cement concrete for good contact w soil

  • 8/19/2019 EARTHING DESIGNE

    8/17

    PRINCIPAL DESIGN DATAi) resistivity of the soil, ii) size and shape of the

    area over which grid electrode is to beinstalled, iii) magnitude of single line to earth

    fault current and grid current.

    Besides these, the other data needed is i)material of earth conductors and type of joints,

    ii) duration of fault current, iii) special

    considerations of corrosion and minimum size

    of earth conductors if any, iv) shock duration,

    v) resistivity of gravel layer and its depth, and

    vi) type of fencing/boundary wall.

  • 8/19/2019 EARTHING DESIGNE

    9/17

    RESISTIVITY OF SOIL

    • Soil resistivity measurement is Wenner four-

     probe method• Dependent on moisture content of soil, seasonal

    variation near surface, but constant in deeper soil

    • Earth formed from layers of different materials• Soil modification may work mostly for simple

    electrodes. For a grid laid in concrete slab of say

    1:3 cement:sand ratio (av. Resistivity 150 Ω-m) ,

    grid at most acts like a plate electrode

    • Based on interpretation of measurements,

    uniform or two-layer soil model may be adopted

  • 8/19/2019 EARTHING DESIGNE

    10/17

    i) Earth resistance R G (Ω) of the electrode in

    uniform soil of resistivity ρ Ω-m, for a grid electrode

    of area = A m2 is approximated by Laurent’s formula

    above

    ii) Increase in length of horizontally buried earthconductors by placing them closely has little affect

    on earth resistance

    iii) ‘ A’ is whole of contiguous area of gridiv) Substations with low resistances are not an

    indication of safe design, nor is a substation with a

    high resistance necessarily an indication of an unsafe

    desi n

    A4R 

    G

  • 8/19/2019 EARTHING DESIGNE

    11/17

    EARTH FAULT CURRENT AND

    GRID CURRENT

    • Only faults that cause fault current to flow intoearth to be considered

    • It determines magnitudes of EPR, step voltage

    and touch voltage• For a single line to earth fault

    )]XXX( j)R R R R 3/[( 021021f I0 = E

    If = 3 I0

    Standardized values of current such as 65 kA, or 40 kA, or

    31.5 kAbased on three-phase current breaking capacity of

    circuit breakers

  • 8/19/2019 EARTHING DESIGNE

    12/17

    Electrode Conductor • must be able to carry the current which is to flow into

    soil for the required duration of time• inefficient joint will have its own resistance causing

    heating and damage at the joint

    • Corrosion is dependant on presence of moisture andsalts in the soil; is a function of soil resistivity

    • Use of Mild Steel avoids galvanic action with other

    underground utilities, which are mostly of steel

    • Area of MS conductor in mm2, tf seconds, and I amps3

    f c10tKIA

  • 8/19/2019 EARTHING DESIGNE

    13/17

    Table II. Corrosion allowance for steel earth conductors

    S.

     No.

    Resisti

    vity

    (Ω– m)

    Class (corrosive)

    of soil%

    Thickness

    mil mm

    1 Up to

    25

    Corrosive &

    Severely Corrosive

    30 180 4.5

    0

    2 > 25 <

    100

    Mildly &

    Moderately

    Corrosive

    15 90 2.2

    5

    3 > 100 Very Mildly

    Corrosive

    10 30 0.7

    5

  • 8/19/2019 EARTHING DESIGNE

    14/17

    DURATION OF FAULT CURRENT AND

    SHOCK DURATION

    • fault duration tf for should be the maximum possiblefault clearing time including back up

    • 1 second for stations using solid state or digital relaysand 3-second for stations using electromagnetic relays

    • operating time of protective relays and circuit breaker isused as shock duration ts for personnel safety againstshock 

    • ts

    taken 0.5 s for stations using digital relays and 1 s forstations using electromagnetic relays

    • appropriate value applicable keeping in view the relayand circuit breaker operating times to br chosen

  • 8/19/2019 EARTHING DESIGNE

    15/17

    RESISTIVITY OF GRAVEL LAYER AND

    ITS DEPTH

    • Gravel of resistivity s & thickness hs spread overareas of swyd for several reasons; one of which isincrease in earth resistance of foot and themaximum permissible values of E

    step

    and Etouch• Resistance modification factor is

    • Instead of gravel concrete slab

    09.0h2

    )1(09.0

    Cs

    s

    s

    At some stations a slab of cement concrete is being tried

     below gravel to prevent growth of weeds/grass. Resistivity

    of gravel is important to calculate Cs.

    Alternate

    expressions for Cs available

  • 8/19/2019 EARTHING DESIGNE

    16/17

    FENCING/BOUNDARY WALL

    Touch voltage maximum near fence. Conductor spacing

    may have to be reduced to make it safe

    Touch voltage maximum between fence and a point 1

    meter away outside itin area without gravel

    Alternately, boundary wall topped with fence may be

    considered

    SOFTWARE IN EARTHING DESIGNMany formulas currently in use obtained empirically from

    computer simulation results

    Several limitations on use of formulas

    When the conductors are unequally spaced or when thesoil model is two-la er or more use of software mandator 

  • 8/19/2019 EARTHING DESIGNE

    17/17

    132 kVSystem bus

    132/33 kV transformers 132/33 kV transformers

    33 kV lines

    33 kV substation

    11 kV line

    System generator 

    Three-phase fault level on 132 kV bus is 31.5 kASingle line to earth fault on 33 kV bus at the distrib. s/s,

    fault current = 1819 A. This current returns to the grid

    station through earth, the grid current is thus 1819 A.

    SLG fault on 11 kV bus at the distrib. s/s, fault current= 4617 A. No current returns to the grid station through

    earth and the grid current is zero

    SLG fault on 11 kV line very near to the distrib. s/s,

    fault current = 2616.4 A. grid current = 2616.4 A