Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
www.cobon.co.krISO9001 : 2008
ISO14001 : 2004TUV compliant
RoHs
EARTH LEAKAGE DETECTION MODULECURRENT SENSOR MODULE
Cobontech Co., Ltd.
The Cobontech Co., Ltd. is specialized in the fields of earth leakage detection module and current sensor module since its establishment. We use our skill to develop customized solutions and products. We stand for superior quality and reliable technology in Korean market and lead the market for earth leakage detection module selling more than 10 million modules per a year. Our products can be used mainly in earth leakage circuit breaker, electronic toilet seat (Bidet), electric vehicle charging system, solar energy, electric water heater and various electric devices. We can deal with every conceivable application area to prevent electric shock and fire thanks to our high technical skills and know-how. Our products are modular type and provide benefits lowering development time and costs for customers. The modules developed in slim and small size can used in limited space of customer’s product. Our researchers at laboratory always engage in close and partnership based interaction with our customers in order to realize customer demands and requirements in the best possible manner.
COBONTECH is a company specialized in earth-leakage detection modules.
Always grappling to develop more integrated and sensitive, much smaller, broader functioned solutions.
CUSTOMERS
02 l Cobontech Co., Ltd.
APPLICATION
Earth leakage circuit breaker (ELCB, RCD)
Electronic cleansing toilet seat
Electric Induction EV charging station High-speed railway
Solar Energy Panel
Electric water heater
www.cobon.co.kr l 03
EARTH LEAKAGE DETECTION MODULECURRENT SENSOR MODULE
04 l Cobontech Co., Ltd.
●●● B or B+ Current Sensor Module
B or B+ Current Sensor Module of RCCB, RCBO, ELCB
•Nominal current measurement: from ± 0.01A DC, AC •Excellent linearity: 15 ppm •High resolution •Very low offset drift •Overall accuracy at IPN @ +25°C: ≤±0.1 % •Wide frequency bandwidth up to 100 kHz (- 3 dB) •RoHS Compliant
Main characteristics
•DC, AC pulse currents' measurements with galvanic isolation •Nano Crystal Fluxgate technology •Electrostatic shield between primary and secondary circuit •Bipolar Power supply ±15 Volt •Operating temperature range from -20 to +85°C •Wire Connector Type•Current output
Feature
Rated residual current (IΔn) 30, 100, 300, 500 mA
Operating time (ms) Instantaneous, Short time delayed, Selective
Peak withstand current Surge Current Proof 3KA (8/20 µs)
Standard IEC / EN 61009-1, IEC / EN 62423
Technical Data
SELF Exiter & Fluxgate Detector
FluxgateController
Saturation Detector
B-TYPE RCCB Module(CF0.1AD(05~35))
●●● Earth Leakage Detection Module
A-COB detects AC and Half-wave, ±6mA DC leakage current.
DETECTING CURRENT WAVEFORM
AC
Pulse
DC + AC
•A type Earth leakage circuit breaker •Electric Vehicle Charging Station•Phase control industrial equipment
APPLICATIONCHARACTERISTICS SYMBOL
VALUEUNIT
MIN TYP MAX
Supply Voltage Vs 12 16 20 V
Operating Current IΔn 18 22 28 mA
Operating Time Ot 30 mS
Supply Current Is 0.3 mA
Power Dissipation Pd 1 3 6 mW
Operating Junction Temperature Tj -30 ~ +85 ℃
Storage Temperature Tstg -45 ~ +90 ℃
APPLICATION
MODEL Working Voltage
Trip OperatingApplication
CircuitTrip Current [mA] Time [mS]SPEC MIN TYP MAX
A-COB 15 100~240 Vac
30 18 22 28 30 FIG1
RATINGS & MODELS
DETECTING CURRENT
A-TYPE RCCB Module (A-COB)
Over-current Detector Module for RCCB (I-COB)
INSTANTANEOUS OPERATION CURRENT TABLE
OPERATING TIME
RATED CURRENTB-TYPE C-TYPE D-TYPE
250% ~ 500% 500% ~ 100% 1000% ~ 2000%
16AF 40 ~ 80 A 80~ 160 A 160 ~ 320 A
20AF 50 ~ 100 A 100 ~ 200 A 200 ~ 400 A
32AF 80 ~ 160 A 160 ~ 320 A 320 ~ 640 A
TYPE ≤ 250% ≤ 500% ≤ 1000% ≤ 2000%
B ≥ 0.1 ≤ 0.1 ≤ 0.1 ≤ 0.1
C ≥ 0.1 ≥ 0.1 ≤ 0.1 ≤ 0.1
D ≥ 0.1 ≥ 0.1 ≥ 0.1 ≤ 0.1
Instantaneous COB is operated instantaneously by an amount(%) of overload of circuit breaker.
www.cobon.co.kr l 05
06 l Cobontech Co., Ltd.
CHARACTERISTICS SYMBOLVALUE
UNITMIN TYP MAX
Supply Voltage Ve 14.7 25 Vac
Operating Time To 100 mS
Supply Current Is 2 mA
Power Dissipation Pd 150 250 350 mW
Operating Junction Temperature Tj -35 ~ +80 ℃
Storage Temperature Tstg -45 ~ +90 ℃
ABSOLUTE RATINGS / RELIABILITY ITEMS
Open-Phase Detector COB (PO-COB)
The open-phase detector COB (PO-COB) is a product to be operated if it is open-phasing does not work and to verify the safe connection of the power supply.
•Low Power Consumption (Pd=5mW, 220V)•Input High Frequency Noise Filter•Internal Blanking Circuit•High Gain Differential Amplifier•Minimum 100㎂ Output Current to Trigger SCR•Extremely Minimized External Part Counts•Built-in thyristor (MCR100-8)•High noise immunity, Large surge margin•5P HIC package by FR4
●●● Earth Leakage Detection Module
CHARACTERISTICS SYMBOLVALUE
UNITMIN TYP MAX
Supply Voltage Ve 12 20 Vac
Trip Voltage Vt 12 13.5 15 mV
Operating Time To 30 mS
Supply Current Is 2 mA
Power Dissipation Pd 150 250 350 mW
Operating Junction Temperature Tj -35 ~ +80 ℃
Storage Temperature Tstg -45 ~ +90 ℃
ABSOLUTE RATINGS / RELIABILITY ITEMS
MODEL Working Voltage
Trip OperatingApplication
CircuitTrip Current [mA] Time [mS]SPEC MIN TYP MAX
Ior-COB 220VacIor 30 22 25
28 30Ioc 90 70 75
RATINGS & MODELS
C Earth Leakage Detector COB (Ior-COB)
C earth leakage detector COB (Ior-COB) prevents an earth leakage breaking module from operating through the capacitive leakage current (Ioc).
•Low Power Consumption (Pd=5mW, 220V)•Input High Frequency Noise Filter•Internal Blanking Circuit•High Gain Differential Amplifier•Minimum 100㎂ Output Current to Trigger SCR•Extremely Minimized External Part Counts•Built-in thyristor (MCR100-8)•High noise immunity, Large surge margin•5P HIC package by FR4
Resistive leakage current [Ior] : Leakage current that flows because of an earth faultCapacitive leakage current [Ioc] : Leakage current that flows at all times through self-capacity without an earth faultCombined leakage current [Io] : Ior+ Ioc combined currentAs the existing earth leakage breaker is operated by the (Io) value of a composite leakage current, the breaker is often automatically cut off because of the Ioc that flows through the LED lamp, computer power, inverter, etc.There is no automatic trip in an C earth leakage detector COB (Ior-COB) as it has been designed to not operate in less than three times the Ioc current.Operating current of C earth leakage detector COB (Ior-COB) : Ior = 25mA / Ioc = 3 X Ior = 75mA
www.cobon.co.kr l 07
●●● Earth Leakage Detection Module
CHARACTERISTICS SYMBOLVALUE
UNITMIN TYP MAX
Supply Voltage Ve 12 20 Vac
Trip Voltage Vt 12 13.5 15 mV
Operating Time To 30 mS
Supply Current Is 2 mA
Power Dissipation Pd 150 250 350 mW
Operating Junction Temperature Tj -35 ~ +80 ℃
Storage Temperature Tstg -45 ~ +90 ℃
ABSOLUTE RATINGS / RELIABILITY ITEMS
MODEL Working Voltage
Trip OperatingApplication
CircuitTrip Current [mA] Time [mS]SPEC MIN TYP MAX
NS-COB15220Vac
15 9 11 1330 FIG1
NS-COB30 30 20 23 26
RATINGS & MODELS
Single Phase COB (NS-COB)
Single-phase COB (NS-COB) is a product specialized for a single-phase earth leakage breaker (residential).
•Low Power Consumption (Pd=5mW, 220V)•Input High Frequency Noise Filter•Internal Blanking Circuit•High Gain Differential Amplifier•Minimum 100㎂ Output Current to Trigger SCR•Extremely Minimized External Part Counts•Built-in thyristor (MCR100-8)•High noise immunity, Large surge margin•5P HIC package by CEM-1
CHARACTERISTICS SYMBOLVALUE
UNITMIN TYP MAX
Supply Voltage Ve 12 20 Vac
Trip Voltage Vt 12 13.5 15 mV
Operating Time To 30 mS
Supply Current Is 2 mA
Power Dissipation Pd 150 250 350 mW
Operating Junction Temperature Tj -35 ~ +80 ℃
Storage Temperature Tstg -45 ~ +90 ℃
ABSOLUTE RATINGS / RELIABILITY ITEMS
MODEL Working Voltage
Trip OperatingApplication
CircuitTrip Current [mA] Time [mS]SPEC MIN TYP MAX
MFS-COB 30220 ~
460Vac
30 20 23 2630 FIG1MFS-COB 100 100 60 75 90
MFS-COB 300 300 180 225 270
RATINGS & MODELS
Three-Phase COB (MFS-COB)
Three-Phase COB (MFS-COB) is a product specialized for three-phase earth leakage breaker (industrial).
•Low Power Consumption (Pd=5mW, 220V)•Input High Frequency Noise Filter•Internal Blanking Circuit•High Gain Differential Amplifier•Minimum 100㎂ Output Current to Trigger SCR•Extremely Minimized External Part Counts•Built-in thyristor (MCR100-8)•High noise immunity, Large surge margin•5P HIC package by CEM-1
08 l Cobontech Co., Ltd.
●●● Earth Leakage Detection Module
CHARACTERISTICS SYMBOLVALUE
UNITMIN TYP MAX
Supply Voltage Ve 12 20 Vac
Trip Voltage Vt 12 13.5 15 mV
Operating Time To 100 mS
Supply Current Is 2 mA
Power Dissipation Pd 150 250 350 mW
Operating Junction Temperature Tj -35 ~ +80 ℃
Storage Temperature Tstg -45 ~ +90 ℃
ABSOLUTE RATINGS / RELIABILITY ITEMS
MODEL Working Voltage
Trip OperatingApplication
CircuitTrip Current [mA] Time [mS]SPEC MIN TYP MAX
Overvoltage 220V 300 280 300 320 > 1 FIG1
RATINGS & MODELS
Overvoltage Breaking COB (OV-COB)
The overvoltage breaking COB (OV-COB) is a product to automatically cut off the power supply in case the applied voltage is more than 300V.
•Low Power Consumption (Pd=5mW, 220V)•Internal Blanking Circuit•Minimum 100㎂ Output Current to Trigger SCR•Extremely Minimized External Part Counts•Built-in thyristor (MCR100-8)•High noise immunity, Large surge margin•5P HIC package by FR4
Classification Delaying time Remarks
The maximum breaking time 1.0 sec Variable
The minimum off time 0.03 sec Variable
CHARACTERISTICS SYMBOLVALUE
UNITMIN TYP MAX
Supply Voltage Ve 12 20 Vac
Trip Voltage Vt 12 13.5 15 mV
Operating Time To 2 mS
Supply Current Is 150 250 350 mA
Power Dissipation Pd 150 250 350 mW
Operating Junction Temperature Tj -35 ~ +80 ℃
Storage Temperature Tstg -45 ~ +90 ℃
ABSOLUTE RATINGS / RELIABILITY ITEMS
RATINGS & MODELS
Delay COB
Delay COB is used to protect a system when installing a quick breaker and an SPD.
•Low Power Consumption (Pd=5mW, 220V)•Input High Frequency Noise Filter•Internal Blanking Circuit•High Gain Differential Amplifier•Minimum 100㎂ Output Current to Trigger SCR•Extremely Minimized External Part Counts•Built-in thyristor (MCR100-8)•High noise immunity, Large surge margin•5P HIC package by FR4
www.cobon.co.kr l 09
●●● Earth Leakage Detection Module
RING-COB (RC6PN)
Integrated earth leakage breaking module (integration of HIC, ZCT, and manual component)Patent registration : integrated earth leakage breaking device and its manufacturing method (Patent No. 10-0549396)
•Low Power Consumption•Input EMC improved Noise Filter•Input Rectifier Circuit•Internal Blanking Circuit•High Gain Differential Amplifier•Minimum 100㎂ Output Current to Trigger SCR•Extremely Minimized External Part Counts•High noise immunity, Large surge margin
A bidet module is a sensor-integrated earth leakage detection module to block moisture with urethane molding by converging the core component for earth leakage detection and the coil sensor part. This guarantees safety by being mainly applied to bidets. It is recommended to be applied to streetlights, coastal areas with high salinity, etc.
CASE MOLDING
Flame Retardant – Polypropylene POLYURETHANE EPOXY A/B NABAKEM
CHARACTERISTICS SYMBOLVALUE
UNITMIN TYP MAX
Supply Voltage Vac -90% AC INPUT 110% Vac
Trip Voltage IΔn 7.5 11.5 15 mV
Operating Time Ot 30 mS
Supply Current Is 2 mA
Power Dissipation Pd 800 mW
Operating Junction Temperature Tj -35 ~ +80 ℃
Storage Temperature Tstg -45 ~ +90 ℃
ABSOLUTE RATINGS / RELIABILITY ITEMS
CASE & MOLDING
12±0.2
3.9±0.2
7.1±0.2
18±
0.2
11.4±0.2 8±2
8±2Ø6±0.2R9±0.2
1.5±0.5
1.5±
0.5
0.8±
0.1
1.9±
0.2
5.6±
0.2
3±0.
2
10 l Cobontech Co., Ltd.
RCCB TESTER (COBON-1701)
Output current
Classification Specification
Voltage AC110V, AC220V, AC380V, AC460V, AC480V
Range 80%, 85%, 100%, 110%
Output voltage
Classification Specification
DISPLAY type FND type
DISPLAY TIME, R-LOAD current, C-LOAD current
DISPLAY
RCCB TESTER (COBON-1901)
Classification Specification
System Constant-current system
Type R-LOAD current, C-LOAD current, R-LOAD + C-LOAD current
Phase angle 0°, 180°
Range0.5A 0.002A ~ 0.5A
5A 0.02A ~ 5A
Frequency 50Hz, 60Hz
Classification Specification
System Constant-current system
Type R-LOAD current,C-LOAD current,R-LOAD + C-LOAD current
Phase angle 0°, 180°
Range0.1A 0.002A ~ 0.1A
1A 0.02A ~ 1A
Frequency 50Hz, 60Hz
Output current
Classification Specification
Voltage AC110V, AC220V, AC380V, AC460V, AC480V
Range 80%, 85%, 100%, 110%
Output voltage
Classification Specification
DISPLAY type FND type
DISPLAY TIME, R-LOAD current, C-LOAD current
DISPLAY
Power supply input : AC220V/60Hz
Power supply input : AC220V/60Hz
www.cobon.co.kr l 11
CF01AD (05~35)
Nominal primary current (IPN) 1.0A A r.m.s.
Measuring range @ ±15V (±5%) 2.0A A peak
Max. measuring resistance @ IP max & ±15V (±5%) 4450 Ω
Min. measuring resistance @ IPN & ±15V (±5%) 1000 Ω
Turn number 500 Turn
Secondary current at IPN 1/500 A
Accuracy at IPN @ +25°C ≤±0.1 %
Offset current @ +25°C ≤±100 uA
Linearity ≤±0.05 %
Bandwidth @ -3dB ≤100 kHz
Max. no-load consumption current @ ±15V (±5%) ≤20 mA
Secondary resistance @ +85°C ≤30 Ω
Dielectric strength Primary/Secondary @ 50Hz, 1min 3 kV
Supply voltage @ ±20% ±15V V dc
Mass 0.019 kg
Operating temperature -20 ~ +85 °C
Storage temperature -25 ~ +125 °C
●●● Current Sensor Module
•Nominal current measurement: from 0.1A DC, AC •Excellent linearity: 15 ppm •High resolution •Very low offset drift •Overall accuracy at IPN @ +25°C: ≤±0.1 % •Wide frequency bandwidth up to 100 kHz (- 3 dB) •RoHS Compliant
Main characteristics
•DC, AC pulse currents' measurements with galvanic isolation •Nano Crystal Fluxgate technology •Electrostatic shield between primary and secondary circuit •Bipolar Power supply ±15 Volt •Operating temperature range from -20 to +85°C •Wire Connector Type•Current output •Really quick response time (<100 ns)
Features
•�Typical applications: ELCB, RCB, ACB, Photovoltaics, Electric Vehicle, Rapid Transit Railway•�Feedback element in precision current regulated devices (power supplies…)•�Precise and high stability inverters•�Medical equipment•�Energy measurement•�Power analyzers
Standard compliance
•Current overload capability •Additional output indicating the transducer state
Remarks
12 l Cobontech Co., Ltd.
CF10AD (05~35)
Nominal primary current (IPN) 10A A r.m.s.
Measuring range @ ±15V (±5%) 20A A peak
Max. measuring resistance @ IP max & ±15V (±5%) 445 Ω
Min. measuring resistance @ IPN & ±15V (±5%) 10 Ω
Turn number 1000 Turn
Secondary current at IPN 1/1000 A
Accuracy at IPN @ +25°C ≤±0.1 %
Offset current @ +25°C ≤±100 uA
Linearity ≤±0.05 %
Bandwidth @ -3dB ≤100 kHz
Max. no-load consumption current @ ±15V (±5%) ≤20 mA
Secondary resistance @ +85°C ≤150 Ω
Dielectric strength Primary/Secondary @ 50Hz, 1min 3 kV
Supply voltage @ ±20% ±15V V dc
Voltage drop ≤3 V
Mass 0.019 kg
Operating temperature -20 ~ +85 °C
Storage temperature -25 ~ +125 °C
●●● Current Sensor Module
•Nominal current measurement: from 1.0A DC, AC •Excellent linearity: 15 ppm •High resolution •Very low offset drift •Overall accuracy at IPN @ +25°C: ≤±0.1 % •Wide frequency bandwidth up to 100 kHz (- 3 dB) •RoHS Compliant
Main characteristics
•DC, AC pulse currents' measurements with galvanic isolation •Nano Crystal Fluxgate technology •Electrostatic shield between primary and secondary circuit •Bipolar Power supply ±15 Volt •Operating temperature range from -20 to +85°C •Wire Connector Type•Current output •Really quick response time (<100 ns)
Features
•�Typical applications: ELCB, RCB, ACB, Photovoltaics, Electric Vehicle, Rapid Transit Railway•Feedback element in precision current regulated devices (power supplies…)•Precise and high stability inverters•Medical equipment•Energy measurement•Power analyzers
Standard compliance
•Current overload capability •Additional output indicating the transducer state
Remarks
www.cobon.co.kr l 13
CF100AD (05~35)
Nominal primary current (IPN) 100A A r.m.s.
Measuring range @ ±5V (±5%) ±120 A peak
Max. measuring resistance @ IP max & ±5V (±5%) 20 Ω
Min. measuring resistance @ IPN & ±5V (±5%) 1 Ω
Turn number 1500 Turn
Secondary current at IPN 100/1500 A
Accuracy at IPN @ +25°C ≤±0.1 %
Accuracy at IPN @ -5 ~ +85°C ≤±0.2 %
Accuracy at IPN @ -20 ~ +85°C ≤±0.5 %
Offset current @ +25°C ≤±100 uA
Linearity ≤±0.05 %
Bandwidth @ -3dB ≤300 kHz
Max. no-load consumption current @ ±5V (±5%) ≤20 mA
Secondary resistance @ +85°C ≤100 Ω
Dielectric strength Primary/Secondary @ 50Hz, 1min 3 kV
Supply voltage @ ±5% ±15V V dc
Voltage drop ≤3 V
Mass 0.039 kg
Operating temperature -20 ~ +85 °C
Storage temperature -25 ~ +125 °C
●●● Current Sensor Module
•Nominal current measurement: from 1.0A DC, AC •Excellent linearity: 15 ppm •High resolution •Very low offset drift •Overall accuracy at IPN @ +25°C: ≤±0.1 % •Wide frequency bandwidth up to 100 kHz (- 3 dB) •RoHS Compliant
Main characteristics
•DC, AC pulse currents' measurements with galvanic isolation •Nano Crystal Fluxgate technology •Electrostatic shield between primary and secondary circuit •Bipolar Power supply ±15 Volt •Operating temperature range from -20 to +85°C •Wire Connector Type•Current output •Really quick response time (<100 ns)
Features
•�Typical applications: ELCB, RCB, ACB, Photovoltaics, Electric Vehicle, Rapid Transit Railway•Feedback element in precision current regulated devices (power supplies…)•Precise and high stability inverters•Medical equipment•Energy measurement•Power analyzers
Standard compliance
•Current overload capability •Additional output indicating the transducer state
Remarks
14 l Cobontech Co., Ltd.
Arc Current Sensor Module
ARC10A
RCCBELB
9.996A
0.004A
L1 L2 L1 L2
ZCT
CT2CT1
CT2CT1
5V
50A
5V
100mA
5V
50A
5V
100mA
No arc signal
AC wave
Arc signal
5V
50A
5V
100mA
CT current detection
ZCT Signal of Earth leakage
Signal Amp
Signal Amp
Full Wave Rectification
Full Wave Rectification
Waveform shaping (DC)
Waveform shaping (DC)
OUTPUT (0~5V)
Wave OutAC detection
OUTPUT (0~5V)
CIRCUIT DIAGRAM
CHARACTERISTICS Arc Sensor Module
Normal primary current(IPN) Ar.m.s(A eff.) 50A
Output Voltage Vdc 0 ~ 5V
Wide frequency bandwidth (- 3 dB) 200 kHz
Bipolar Power supply ±12 Volt
Operating temperature range -45 to +85°C
CHARACTERISTICS
www.cobon.co.kr l 15
Lighting Surge Sensor Module
CIRCUIT DIAGRAM
SPD
100KA
t 100KA
5V
5V
50A
5V
100mA
No arc signal
50A
5V
CT Surge Detect Signal Amp Peak Hold Waveform
shaping(DC)OUTPUT(0~5V)
CT CurrentDetect Signal Amp Full Wave
RectificationWaveform
shaping (DC)OUTPUT (0~5V)
CHARACTERISTICS
CHARACTERISTICS Surge Sensor Module Current Sensor Module
Normal primary current(IPN) Ar.m.s(A eff.) 0.1 ~ 100KA 0.01 ~ 100mA
Output Voltage Vdc 0 ~ 5V 0 ~ 5V
Wide frequency bandwidth (- 3 dB) 200 kHz 200 kHz
Pulse Time 1 ~ 1000uSec 1 ~ 10mSec
Bipolar Power supply ±15 Volt ±12 Volt
Operating temperature range -45 to +85°C -45 to +85°C
28578, 501, Techno S Tower, 530, Jikji-daero, Heungdeok-gu, Cheongju-si, Chungcheongbuk-do, KoreaTel. 82-43-838-9747 / Fax. 82-31-629-5572e-mail. [email protected] / www.cobon.co.kr
ISO9001 : 2008ISO14001 : 2004
TUV compliant
RoHs