27
Earth Electrode Design Dr Hendri Geldenhuys PrEng Eskom Distribution Technology

Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Earth Electrode Design

Dr Hendri Geldenhuys PrEng

Eskom Distribution Technology

Page 2: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

SWER in the Karoo (Semi Desert )

Will the Soil conductivity be good enough?

The only way to tell is to measure

The best conducting soil in SA is in the most

dry places!

This is because the salt is not washed out by

the rain.

The most difficult place is where there are a

lot of rain…

Do not guess.. Measure !

Page 3: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

SWER LOAD CURRENT

REMOTELY EARTHED FENCE

V < 32 V

Touch Potential

Page 4: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Deep Drilled Vertical Electrode

32 V V =32V

Page 5: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Deep Drilled Vertical Electrode

100 V V =32V

Page 6: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

INSULATION COVERING OR TUBE RATED 1000V

1m DEPTH

1.5m VERTICAL ROD

AS PER DESIGN

GROUND LEVEL

0.2m MAX.

CONDUIT PIPE FOR FIRE AND MECHANICAL PROTECTION

2

50mm COPPER (MIN.)

Insulation of the Earth Down Lead

32 V

20.5 V

Page 7: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Transformer Earth Electrode Resistance

Table 1: The design resistance required for various transformer sizes. This is based on

a Ground Potential rise of 32V.

Transformer Earth return current SWER Required

resistance

Design resistance

5 kVA 0.26 A 122.2 ohm 30.0 ohm

15 kVA 0.79 A 40.7 ohm 30.0 ohm

25 kVA 1.31 A 24.4 ohm 24.0 ohm

50 kVA 2.62 A 12.2 ohm 12.0 ohm

200 kVA 10.5 A 3.1 ohm 3.0 ohm

400 kVA 20.9 A 1.5 ohm 1.5 ohm

Based on Earth Potential Rise < 32 V

Page 8: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Insulated Vertical Rod Electrode

Table 1: The design resistance required for various transformer sizes. This is based on

a Ground Potential rise of 100V.

Transformer Earth return current SWER Required

resistance

Design resistance

5 kVA 0.26 A 382.0 ohm 30.0 ohm

15 kVA 0.79 A 127.3 ohm 30.0 ohm

25 kVA 1.31 A 76.4 ohm 30.0 ohm

50 kVA 2.62 A 38.2 ohm 30.0 ohm

200 kVA 10.5 A 9.6 ohm 9.0 ohm

400 kVA 20.9 A 4.8 ohm 4.5 ohm

Based on Earth Potential Rise < 100V

Page 9: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Notes

1) The main (low resistance) SWER earth electrodes (ME 1 and ME 2) are located outside the

village to overcome the step and touch potential problems.

2) There are two main earth electrodes (ME) per village to give some redundancy.

3) The transformer pole earth (TE) is simply a butt wrapped wire around the bottom of the pole.

It must be small to avoid step and touch potential problems in the town.

4) A clearance of 2m to any conductors in the vicinity (such as fences) should be maintained

around a transformer pole (earth) to avoid step and touch potential problems.

SWER Feeder line Village

25A

25kV

A

3.6A

10W

3.6A

Dis

trib

uti

on

tran

sform

er

50kV

A

16kV

A

10W

The earthing practise and under running neutral conductor for a village.

TE ME 2 TE TE ME 1

2 m clearance

Earth Safety in a Village.

Page 10: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Dis

trib

uti

on

tran

sform

er

50kV

A

3.2

A

3.2

A

Dis

trib

uti

on

tran

sform

er

32kV

A

15W

15W

Village A

22kV supply

Isolating Transformer

500kVA

25A

25A

10W 10W

Distrib

utio

n

transfo

rmer

25kV

A

3.6A 3.6A Dis

trib

uti

on

tran

sform

er

50

kV

A

2W

Distrib

utio

n

transfo

rmer

16kV

A

Village D

22kV supply

Isolating Transformer

200kVA

10A

10A

9W 9W

Distrib

utio

n

transfo

rmer

25kV

A

5A 5A Dis

trib

uti

on

tran

sform

er

10

0k

VA

2W

Vil

lage

B

Vil

lage

C

SWER Scheme Layout

Page 11: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Double Down Earth Conductor

Page 12: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Customer Transformer Installation

Page 13: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Double Crimp on Earth Connections

Page 14: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Drilling a Vertical Electrode Hole

Page 15: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Trench Electrode for Isolation Transformer

Page 16: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Trench depth

Important points to avoid thermal runaway on SWER electrodes and to

ensure safety around SWER electrodes: 1) Electrode size must comply with safety criteria of 32V for trench and 100V for vertical

20% insulated electrodes (voltage rise at transfomer nominal current)

2) Double down conductors and double clamp connection to the earth conductors including

an underground interconnection. (Redundancy)

3) Vertical rod electrodes should be installed at the beginning and end of trench electrodes

to create the high current density/ stress area away from the point where the down

conductor is connected to the earth electrode. For the same reason it is recommended

that the down conductor to be connected 1m away from the extremities of the earth

electode.

Connection 1m away from

electrode extremity

Page 17: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

End

Page 18: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Earth Resistivity and

Electrode Resistance

Measurement

Dr Hendri Geldenhuys PrEng

Eskom Distribution Technology

Page 19: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Earth Resistivity Meter

Page 20: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Soil-Resistivity Measurement

Resistivity Meter

C1 P1 P2 C2

12.4 ohm

a a a

d

Page 21: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Resistivity Tests

Page 22: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Resistivity Measurement- Calculation

Electrode

Separation

[m]

Resistance

[Ohm] Factor Resistivity

1 R1 a x 2.Pi a x 2.Pi x R1

2 R2 a x 2.Pi a x 2.Pi x R2

5 R5 a x 2.Pi a x 2.Pi x R5

10 R10 a x 2.Pi a x 2.Pi x R10

20 R20 a x 2.Pi a x 2.Pi x R20

50 R50 a x 2.Pi a x 2.Pi x R50

Page 23: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Resistivity At Askham: Kalahari Desert

Askham Resistivity

10

100

1000

10000

1 10 100

Electrode Separation [ m ]

Re

sis

tiv

ity

[ O

hm

.m ]

Page 24: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Burkina Faso Resistivity

Page 25: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Electrode Resistance Measurement

Resistivity Meter

C1 P1 P2 C2

2.50 ohm

66% 33%

Electrode Under Test L

Test Electrode Position

Page 26: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

Electrode Resistance Measurement

Test Electrode Position Resistance

.2L

.4L

.6L

.8L

Page 27: Earth Electrode Design - piesa · Table 1: The design resistance required for various transformer sizes. This is based on a Ground Potential rise of 100V. Transformer Earth return

End