9
DESIGNING A "NEAR OPTIMUM" COOLING-WATER SYSTEH Ralph A. Crozier, Jr. E. I. du Pont de Nemours & Co. \?1lmington, Delaware Reprinted by special permission from CHEMICAL ENGINEERING April Zl Copyright (c) 1980, by McGraw-Hill, Inc. New York, N.Y. 100ZO. ABSTRACT the quantity of water being circulated. Reducing the flow (raising the coolant outlet temperature cif Cooling water is expensive to circulate. heat exchangers) significantly reduces cooling- 'Reducing its flow --ie, hiking exchanger outlet tower, pump and piping investment, and operating temperatures --can cut tower, pump and piping cost, and only moderately increases the heat-ex- investment as much as one-third and operating cost changer investment. The overriding conclusion to. almost in half. be drawn is that cooling water is very expensive, and its conservation can result in significant Heat-exchanger-network optimization has been savings. accomplished in large integrated plants, such as Three System Interactions petroleum refineries. In many of the chemical process industries, however, a plant contains sever- What are the system interactions and their al individual processes, and network optimization, relationships? When can they be ignored, and except on a limited basis, is not feasible. must they be considered? So far, no one has developed similar procedures From Fig. 1, it can be seen that there are for designing and optimizing a cooling-water once- three coolant interactions: (1) between the through-exchanger system.* This article attempts m temperature of the heat exchanger and the inlettem- fill the void by presenting a design basis that will perature of the cooling tower, (Z) between the inT produce a "near optimum" system. let temperature of the exchanger and the outlet perature of the cooling tower, and (3) between tO$Il A cooling-water system consists of four major coolant flowrate and the size of connecting piping components: heat exchangers, cooling towers, cir- and circulating pumps. . culation piping and pumps. To optimize such a sys- tem, one must define the system interactions and First Interaction - In the Fig. 1 system, cool- apply these relationships to the simultaneous design ing water enters the shell side of the exchanger of the aforementioned equipment. This article de- a fixed temperature of T l and exits at a variablel velops criteria that for most applications allow temperature of TZ; the process fluid passes one to ignore system interactions, and still design the tube side at fixed inlet and a "near optimum" system. of tl and t2' respectively. The cooling tower dis- Sipates heat to the ambient air through Cooling-water systems have long been designed t ion (evaporat ion) and sens::'ble heat ing. ' by "rules of thumb" that call for fixing the cool- ant temperature-rise across all heat exchangers Cooling-tower investment and operating cost are (usually ZO°F) and setting the coolant inlet temper- reduced by returning the water to the tower as hot ature to the heat exchanger at the site's wet-bulb as possible, because the hotter water, the , temperature plus 8°F. These rules produce a work- larger the temperature difference (thermal driving able cooling system; but, by taking the same coolant force) between it and the ambient air; hence. less rise across all exchangers, regardless of the indi- heat-transfer area (tower packing) is : vidual process outlet-temperatures, this cannot re- Additionally, as the effluent air temperature is i sult in an optimized design. raised, so is the moisture content of the exiting: air; hence, less air flow is necessary. The design method presented in this article re- places the "rules of thumb" with criteria that are Upping the temperature of thp. water to the easy to apply and that take into account the effect tower also cuts the quantity of water circu-: that the individual exchanger process outlet-temper- lated through the tower. From Eq. (1), it can be: atures have on cooling-system economics. seen that for a fixed heat load and tower outlet temperature (Tout), the quantity of cooling water: Economic analyses of actual process have shown reqUired to satisfy the heat balance is inversely' that cooling-system investment can be reduced by one proportional to the tower inlet temperature (Tin): and cooling-system operating cost by one hali, \'T=QT/[C(Tin-Tout)] (1) 1f the proposed design criteria are used instead of the "rules of thumb." It has been found that the controlling economic factor for a cooling system is 563 ESL-IE-81-04-97 Proceedings from the Third Industrial Energy Technology Conference Houston, TX, April 26-29, 1981

EArt-Designing a 'Near Optimum' Cooling-Water System

  • Upload
    moly69x

  • View
    216

  • Download
    0

Embed Size (px)

DESCRIPTION

cooling tower

Citation preview

Page 1: EArt-Designing a 'Near Optimum' Cooling-Water System

DESIGNING A "NEAR OPTIMUM" COOLING-WATER SYSTEH

Ralph A. Crozier, Jr. E. I. du Pont de Nemours & Co.

\?1lmington, Delaware

Reprinted by special permission from CHEMICAL ENGINEERING April Zl Copyright (c) 1980, by McGraw-Hill, Inc. New York, N.Y. 100ZO.

ABSTRACT the quantity of water being circulated. Reducing the flow (raising the coolant outlet temperature cif

Cooling water is expensive to circulate. heat exchangers) significantly reduces cooling­'Reducing its flow --ie, hiking exchanger outlet tower, pump and piping investment, and operating temperatures --can cut tower, pump and piping cost, and only moderately increases the heat-ex­investment as much as one-third and operating cost changer investment. The overriding conclusion to. almost in half. be drawn is that cooling water is very expensive,

and its conservation can result in significant Heat-exchanger-network optimization has been savings.

accomplished in large integrated plants, such as Three System Interactionspetroleum refineries. In many of the chemical process industries, however, a plant contains sever­

What are the system interactions and theiral individual processes, and network optimization, relationships? When can they be ignored, and whe~except on a limited basis, is not feasible. must they be considered?

So far, no one has developed similar procedures From Fig. 1, it can be seen that there arefor designing and optimizing a cooling-water once­ three coolant interactions: (1) between the outl~tthrough-exchanger system.* This article attempts m temperature of the heat exchanger and the inlettem­fill the void by presenting a design basis that will perature of the cooling tower, (Z) between the inTproduce a "near optimum" system.

let temperature of the exchanger and the outlet t~m­perature of the cooling tower, and (3) between tO$IlA cooling-water system consists of four major coolant flowrate and the size of connecting pipingcomponents: heat exchangers, cooling towers, cir ­ and circulating pumps. .

culation piping and pumps. To optimize such a sys­tem, one must define the system interactions and

First Interaction - In the Fig. 1 system, cool­apply these relationships to the simultaneous design ing water enters the shell side of the exchanger ~tof the aforementioned equipment. This article de­a fixed temperature of Tl and exits at a variablelvelops criteria that for most applications allow temperature of TZ; the process fluid passes throu~h one to ignore system interactions, and still design the tube side at fixed inlet and outlettemperatur~ a "near optimum" system. of tl and t2' respectively. The cooling tower dis­Sipates heat to the ambient air through humidific~­Cooling-water systems have long been designed t ion (evaporat ion) and sens::'ble heat ing. ' by "rules of thumb" that call for fixing the cool­

ant temperature-rise across all heat exchangers Cooling-tower investment and operating cost are(usually ZO°F) and setting the coolant inlet temper­

reduced by returning the water to the tower as hotature to the heat exchanger at the site's wet-bulb as possible, because the hotter th~ water, the ,temperature plus 8°F. These rules produce a work­larger the temperature difference (thermal drivingable cooling system; but, by taking the same coolant force) between it and the ambient air; hence. lessrise across all exchangers, regardless of the indi­heat-transfer area (tower packing) is requir~d. :vidual process outlet-temperatures, this cannot re­Additionally, as the effluent air temperature is isult in an optimized design. raised, so is the moisture content of the exiting: air; hence, less air flow is necessary.The design method presented in this article re­

places the "rules of thumb" with criteria that are Upping the temperature of thp. water to the easy to apply and that take into account the effect tower also cuts do,~ the quantity of water circu-:that the individual exchanger process outlet-temper­

lated through the tower. From Eq. (1), it can be:atures have on cooling-system economics. seen that for a fixed heat load and tower outlet temperature (Tout), the quantity of cooling water:Economic analyses of actual process have shown reqUired to satisfy the heat balance is inversely'that cooling-system investment can be reduced by one proportional to the tower inlet temperature (Tin):

~hird, and cooling-system operating cost by one hali, \'T=QT/[C(Tin-Tout)] (1)1f the proposed design criteria are used instead of

the "rules of thumb." It has been found that the controlling economic factor for a cooling system is

563

ESL-IE-81-04-97

Proceedings from the Third Industrial Energy Technology Conference Houston, TX, April 26-29, 1981

Page 2: EArt-Designing a 'Near Optimum' Cooling-Water System

Boosting the tower inlet temperature means increas­ing the coolant temperature rise across the individ­ual exchangers; hence, to reduce cooling-tower in­vestment and ope~ating cost, one must widen the coo~

ant temperature rise across th:e individual exchangers.

A significant discovery has been that in most instances exchanger "lrea is relatively insensitive to incremental changes in coolant outlet temperatuIE. To understand this, one must recognize that a well designed exchanger must have adequate heat-transfer area, but it must also have sufficient fluid-flow area to satisfy the shell-and-tube pressure-drop re­strictions.

Because coolant flowrate is inversely propor­tional to coolant temperature rise, a small coolant temperature rise produces a large increase in cool­ant flow. This means that the exchanger diameter must be increased, if the pressure-drop (maximum velocity) restriction is to be satisfied.

If the heat-transfer equation Q=UA(LMTD) were solved for the small coolant temperature-rise geome­try, it would show that the area needed for heat transfer is less than required by the pressure-drop limitation. In other words, for small coolant tem­perature rises, the exchanger's heat-transfer area would be excessive if determined by fluid-flow con­siderat ions.

If the coolant outlet temperature is sequen~

tially increased and the required exchanger area is calculated for the different coolant temperature rises, a plot similar to that in Fig. 2 would be gen­erated. Notice that the required exchanger area initially lessens, reaches a maximum, and then gains as the coolant temperature rise is increased.

The required exchanger area, as depicted in Fig. 2, passes through three distinct design regions. In the first (80°F to 115°F), the required area is controlled by fluid-flow phenomena. In the second (115°F to 158°F), the fluid-flow and heat transfer considerations are the same order of magnitude; that is, neither requirement is controlling. In the third (above 158°F), the heat-transfer requirement becomes controlling (reduced LMTD). Therefore, to minimize exchanger area, the design should be in the second (transition) region.

Fig. 2 was developed on the basis of full tube bundle. At low coolant temperatures, the better de­sign would be to have the tube bundle partially fill ­ed, so as to maintain a constant tubeside velocity. In the transition region, however, the shell velocity was kept at a constant rate by reducing the baffle spacing as the coolant flow decreased.

Second Interaction -- The tower outlet temper­ature (approach plus wet bulb) is the variable with which the cooling-tower designer has the least lati ­tude, yet it is the most significant determinant of cooling-tower investment and operating cost. The tower outlet temperature is the "Achilles heel" of this study and the reason why only a "near optimum," rather than a truly optimized, cooling system is attained.

T,

Exchanger Pip;ng Tower design ----design--- design

Typical systam demonstrates thr.. interactions Fig. 1

T2

~175r--"'--"""'---,-----,---, ~' 150 Process outlet temoer.turl 158"F .. ~ 125

i v Tutlnidl8 I hllHranshr I limitillg~100

~ ~

O·UA(LMTD)S75 I I 1,500 ; vj 50 J I 1.250 i

A I :,. .cll5 I I 1.000]

o AA" AAAO=-_---:::::­ __~:.....;:......,...,--.....l.::_-.....J750 g.a:

10 100 120 140 'SO lao

Coollnt outlet temperature, ~

Exchanger overall coefficient and araa fall into three distinct design regions Fig. 2

Specifying the coolant outlet temperature is difficult because it is bound on the lower side by the wet-bulb temperature and on the upper side by the minimum process outlet temperature. To minimize cooling-tower investment and operating cost. one needs to maximize the approach to wet-bulb tempera­ture. However, to minimize heat-exchanger invest­ment, one needs to maximize the approach to the min~

mum process outlet temperature. Therefore, the tow­er outlet temperature has to be a compromise between these two boundaries.

The importance of the cooling-tower and heat-ex­changer designers' discussing the temperature limi­tations imposed on each before any calculations are started cannot be overemphasized. Usually, the 101.1­

est cooling temperature is required for a refrigera­tion system or a steam turbine condenser. Consider­able savings can be realized if alternative coolin? methods are provided for these services, rAth~r than penalizing the entire cooling system for one, or both, of them.

Many cooling towers are designed by a rule of thumb that sets the tower outlet temperature equal to the site wet-bulb temperature plus 8°F. This can re­sult in significant cooling-tower investment and op­erating cost penalties if process requirements do not demand cooling water at a temperature that low. As previously stated, cooling-tower investment and oper­ating cost are minimized by maximizing the approach to wet-bulb temperature.

564

ESL-IE-81-04-97

Proceedings from the Third Industrial Energy Technology Conference Houston, TX, April 26-29, 1981

Page 3: EArt-Designing a 'Near Optimum' Cooling-Water System

Third Interaction--Via Eq. (1), it can be shown that the system flowrate decreases as the tower in­let temperature is hiked. Therefore, as the coolant rise across the individual exchangers is increased, the supply and return piping, as well as the circu­lating pumps, can be reduced in size.

In summary, the investment and operating cost of the tower, pumps and piping will be reduced when the cooling-tower inlet temperature is increased. The exchanger investment mayor may not be reduced as the coolant temperature rise is increased, depending on the relationship of the coolant outlet temperature and the exchanger design region (Fig. 2).

If the exchanger's optimum coolant outlet tem­perature is in the transition region, its area will be minimized, and system interactions can be ignore~

If the exchanger's coolant outlet temperature is not in the transition region, however, system interac­tions must be considered.

It has been empirically determined that if the exchanger LMTD is greater than 30°F when the coolant outlet temperature is set at the process outlet tem­perature or some maximum temperature (scaling limit~

tion) , the exchanger is in the transition region. If the LMTD is less than 30°F, the exchanger is in the heat-transfer-limiting region and the exchanger area will be very sensitive to coolant temperature changes. Therefore, if the LMTD is less than 30°F, system interactions must be considered; and a com­promise between higher exchanger investment and lower cooling-tower investment must be determined.

Constraints on Outlet Temperature

Two temperature constraints limit the exchanger coolant outlet temperature. First, the wood fill of the conventionally designed cooling tower limits the maximum water temperature to 150°F. Second, the temperature from individual exchangers is set by pre­cess outlet temperatures or by tube fouling or mate­rial of construction.

Waterside deposits of suspended solids, mineral salts, biological growths, and corrosion products interfere with heat transfer. In the design calcu­lations for sizing heat exchangers, the magnitude of the interference is the fouling factor. Attempts to quantitatively relate the factor to specific fouling conditions have been only partially successful; therefore, the numerical value assigned to different degrees of fouling by specific deposits has been based largely on experience.

Because there is no theoretical basis for select­ing fouling factors at different coolant temperatures, the same factor was used at all temperatures in this study. To analyze the effect of this assumption on the conclusions, a cooling system for which the fouling factor was arbitrarily doubled was evaluated. It was found that the cooling tower, pump and piping investment and operating cost savings far outweighed the higher exchanger investment and operating cost. Therefore, the conclusions reached in the increased­fouling-factor evaluation were the same as those ob­tained by assuming a constant fouling fac tor. For simplification, only the latter evaluation is

presented here.

Basis of the Economic Evaluations

The investment and operating cost for the cool­ing- system components were calculated as follows:, heat exchangers, by a method similar to that describ­ed by Woods, Anderson and Norman [lJ; cooling-tower pumps, by a proprietary correlation developed for, electrically driven, vertical turbine water pumps; operating at 880, 1,200 and 1,800 rpm; piping, by a proprietary correlation based on material and man­hours per linear foot (1- to l2-in. dia., "Cast Iron Pressure Pipe--Cement Lines," and 14- to 96-in. dia., "Concrete Pressure Pipe, American Water Works Assn., Spec. C-30l Prestressed"); and cooling t.owers, by t.wo booklets of The Marley Co. [2,3J.

Economic evaluations are based on cost plus re­t.urn on invest.ment. Using cost plus return, one can combine t.he investment and operating cost fact.ors into a single variable.

Cost plus return is the total cost of owning and operating a cooling syst.em for one year. Tot~l

investment (allocated, permanent, working capital; etc.) is included as a cost--that is, as an interest penalty. Operating cost (depreciation, maintenan¢e, electrical, etc.) is added to the interest penalty. This total is defined as cost plus return:

CT=C+ {xI/[(l-a)(l-i)J} (2)

In Eq. (2), C= annual operating cost; x = re-, quired net return on investment; I = total invest· ment; a = state and local taxes; and i = federal income tax.

Hereafter, cost means cost plus 10% net return on investment. The lowest-cost alternative proposal is the economic choice. All investment and operat­ing costs represent the January 1976 Engineering , News Record Construction Cost Index of 215 (1967 = 100).

COMPONENT DESIGN CRITERIA

Heat-exchanger criteria are divided into two, categories: LMTD greater and less than 30°F. Codl­ing tower criteria are similarly divided: inlet temperature greater and less than 110°F.

Exchanger LMTD greater than 30°F

Fig. 3a shows system cost as a function of tre coolant temperature rise for an exchanger whose p~o­cess outlet temperature is 195°F. Two concepts ih Fig. 3a are worth discussing:

1. Because this exchanger's LMTD is large, its area is relatively insensitive to changes in the coolant temperature rise. This phenomenon can be explained by a simple example.

It was shown previously that the area and ov~r­all heat-transfer coefficient of an exchanger in the transition region are fairly constant; hence, the required area is only a function of the L~ITD (Fig 2).

565

ESL-IE-81-04-97

Proceedings from the Third Industrial Energy Technology Conference Houston, TX, April 26-29, 1981

Page 4: EArt-Designing a 'Near Optimum' Cooling-Water System

Assume two extremes, a large and a small LMTD. If the LMTD is large, narrowing it from 150°F to 140°F augments the exchanger area by 7%. On the other hand, if the L~ITD is small, lessening it from 50°F to 40°F boosts the exchanger area by 20%. Hence, as the LMTD is reduced, the exchanger area becomes more sensitive to the coolant outlet temper­ature.

2. Recall that as the coolant outlet tempera­ture is raised, the coolant flow is reduced. Assume coolant investment to be $50/gpm (Fig. 3a). Hiking the coolant temperature rise from 20°F to 60°F re­duces the coolant flow by 660 gpm, with a resultant lowering of the coolant investment by $33,000. The~­fore, a significant investment saving can be real­ized for exchangers in this category if the coolant outlet temperature i~ raised to 150°F.

As can be seen in Fig. 3a, the system cost could be further reduced by increasing the coolant outlet temperature above 150°F. However, there are practi­cal reasons for not going this high, although this limit is arbitrary and should be evaluated for a particular site.

The evaluation should consider: for the heat exchanger, such effects ~s (1) the use of exotic tube materials of construction, and (2) increased fouling stemming from the lower coolant velocity; for the cooling tower, such effects as (1) increased blowdown to remove mineral salts, and (2) costlier water treatment because of the higher temperatures.

Fig. 3b shows system cost as a function of cool­ant temperature rise for an exchanger whose process outlet temperature is 115°F. Again, the coolant cost drops as the coolant temperature rise increases. In this case, however, the effect of the L~ITD on ex­changer area is becoming evident. At a coolant out­let temperature of 125°F, multiple exchangers in series are required because of a temperature cross (coolant outlet temperature exceeds the process out­let temperature). Although the system cost for two exchangers in series is less, the savings are margin­al and one exchanger is preferred, with the coolant outlet and process outlet temperatures set equal to one another.

An economic evaluation of Fig. 3b at three dif­ferent coolant outlet temperatures provides the first insight into the effect of coolant flowrate on system economics. It also establishes the basis for the practice of setting the process and coolant outlet temperatures equal to each other.

In Table I, the three cases represent three dif­ferent coolant outlet temperatures: (1) 15°F coolant temperature rise, (2) equal to process outlet temper­ature, and (3) 5°F higher than the process outlet temperature.

Using Case 3 as the basis, the incremental in­vestment penalties for Cases 1 and 2 are $33,700 and $6,100, respectively. The incremental cost penalties for Cases 1 and 2 are $15,OOO/yr and $3,000/yr, respectively.

From this analysis, one can see that by consid­ering the system cost, a temperature cross is eco­nomically justified. But before deliberately design­ing a heat exchanger for a cross, one must realize that an error in the predicted outlet temperature of either stream will result in a thermodynamically unstable exchanger.

In summary, the design criteria for heat ex­changers that have an ~ITD greater than 30°F (cal­culated at the coolant outlet temperature specified by the criteria) are:

Single-pass geometries-- The coolant outlet temperature should be set at the process inlet tem­perature minus 10°F, or at 150°F if the process llliet temperature is greater than 160°F.

Multiple-pass geometries-- The coolant outlet temperature should be set at the process outlet tem­perature, or at l50°F if the process outlet tempera­ture is greater than 150°F.

Exchanger LMTD Less Than 30°F

Fig. 3c shows cost as a function of the coolant temperature rise for a process outlet temperature of 115°F and an LMTD of less than 30°F (calculated at a coolant outlet temperature of 1l5°F). Once again the coolant cost decreases as the coolant temperature rise increases; however, in this example, the higher cost of the heat exchanger as the coolant outlet tem­perature is raised has a significant effect on sy~em

economics.

This example differs from the previous two in yet another respect. For the first time, the opti­mum coolant outlet temperature depends on coolant economics. In the previous examples, coolant costs so predominated that an incremental increase or de­crease in the coolant cost did not change the design criteria. In this case, however, if the coolant cost increases incrementally, one wants to reduce the quantity of coolant; therefore, the optimum coolant outlet temperature increases (or if the coolant cost decreases, the optimum coolant outlet temperature be­comes lower).

In Fig. 3c, the total cost curve has a minimum that is a function of both the heat exchanger and coolant economics. Therefore, for an exchanger with an ~ITD less than 30°F, the exchanger and coolant interaction precludes setting the coolant outlet te~

perature a priori by using the design criteria. For an exchanger in this category, the optimum coolant outlet temperature must be found by constructing a graph similar to Fig. 3c.

Such a graph is generated by (1) using plant coolant cost data, or estimating the coolant econom­ics via a Fig. 4a or 4b type graph; (2) determining the area requirements of the exchanger at different coolant temperature rises; (3) calculating the ex­changer and coolant cost at the different temperature levels; (4) plotting the exchanger and coolant cost; and (5), at a given coolant temperature rise, sum­ming the individual costs to obtain the system cost. The optimum coolant outlet temperature is that at

566

ESL-IE-81-04-97

Proceedings from the Third Industrial Energy Technology Conference Houston, TX, April 26-29, 1981

Page 5: EArt-Designing a 'Near Optimum' Cooling-Water System

which the total system cost is minimized. In Fig. 3c, this coolant outlet temperature happens to coin­cide with the design criteria temperature of 115°F.

The Step 1 graphical estimate of coolant eco­nomics is made as follows: Using Fig. 4a and assum­ing a tower having a 20°F range and a 91°F outlet temperature, one arrives at a total cost of $255,000/ yr, or $3l.25/h (8,000 h/yr). For the tower, duty of 100 million Btu/h, one then calculates, using Eq. (2), a tower flowrate of 600,000 gal/h. Dividing $3l.25/h by 600,000 gal/h, one obtains a coolant operating cost of 5.2¢/1,000 gal, which can be used to calculate the coolant economics at this tempera­ture level.

Coolan t Piping and Pumps

The connecting piping (cooling tower to heat e~

changer) in the Fig. 5 cooling system is composed of large underground distribution headers and smaller takeoffs from central distribution points to indivi~

ual heat exchangers. It was originally thought that these two piping configurations (one of straight runs, the other of many fittings and valves) would have different optimum design velocities. It was found, however, that the optimum velocities coincida

From Fig. 6, it can be seen that the cost is in­sensitive to coolant velocity changes, and that the optimum velocity falls between 5 and 10 ft/s. (The cost-pIus-return calculation of the Fig. 6 pipe and pump cost was based on the Fig. 5 cooling-system pip­ing configuration.)

The insensitivity of system cost to the coolant velocity is the result of counterbalancing cost factors. Two extremes are possible in piping system design: (1) large pipe diameters (small friction losses) and small pumps with low horsepower require­ments, or (2) smaller pipe diameters (large friction losses) and large pumps with high horsepower require­ments.

In the first, the piping investment is high, and the pump investment and operating cost low. In the second, the reverse is true. ~hen these two extremes are evaluated on a cost-pIus-return basis, the total system costs are the same. This analysis will be true for all liquid piping systems that do not re­quire exotic materials of construction.

The skill in designing coolant piping systems is in balancing flows through the various loops. To adequately analyze the flow distribution problem, one is forced to computer simulations of the piping sys­tems (the cooling-water supply and return headers, and the piping to and from heat exchangers), choosing by trial and error the pipe diameter that matches the loop and system pressure drop. Such a piping config­uration forms a series of parallel flow loops, in which, by definition, the pressure drops must be the same.

The system pressure-drop requirement can be sat~

isfied by increasing or decreasing the flowrate in the individual loops. If the piping in a particular loop is oversized, the flow through it will be excessive. To reduce the flow, a control valve must

70 ....t dt.rtv: 10 rnill'on ItWh Matllrial of conatruction: 304 ftIIifll .... tt~

60 Proens.tempernur. inlet: 340.;0 F PToc:nI-hmperature OCJn.t: 195"F CooIM1t·umper.tunl inlet: go-F

~ SO

:ac: .......Total COlt :I~, T~

£.. 30

'if Coolant Cott .. '

CfmCM,ature limit

I I I

u 20

I I

10

0 20 ~ 60 80

Coolant rise across exchanger, -F

L HighLMTD

70 He,t duty: 10 millien 8tu/h Mltllriaj of construction: 304 .t.inlllSs ItHI

60 PrQCHI-ttmper.ture inl't; 2600 F PToeus-ttmpcratur. outl.t: 115" F Cool.lnt-tllmperltur. inlet: W FSO

:>­

~ 40

~ ... 30

S· u 20

, ,10 -' I

Two uenang.", in s,ries' :

0 20 40 60 60 CooI.nt rise across exchanger. -F

b. Im,rmed;." LMTD

100 He,t duty: 10 million Btuth Mattr~1 of conttruc:tion: 304 ft.linltu nftll p,.ocess-tlimper.tur. inl.t: 140~ F

80 Procen.·tt1moef.tl.Hf outlet: 115'" F Cooiant·temperatu,.. inlet: 9tf F

~ ';3 60c: ~, 0

-5 ... 40

B u

20

0 20 ~ 60 Coolant rise across exchanger, ·F

Co Low LMTD

Imp.ct of coolant temperature rise on IotaI system cost at three different LMTDs Fig. 3

supply the pressure drop needed to achieve bala ced pressure distirbution. This means excessive wear and control-valve maintenance. Therefore, aproperly designed cooling piping system will specify the cor­rect pipe diameter for each loop that will balaqce the pressures without the need to resort to acortrol valve.

Cooling-Tower Design

As previously mentioned, a cooling tower dis­sipates process heat to the atmosphere by humidif~

the ambienr air and, to a lesser degree, by s,ensibly

567

ESL-IE-81-04-97

Proceedings from the Third Industrial Energy Technology Conference Houston, TX, April 26-29, 1981

Page 6: EArt-Designing a 'Near Optimum' Cooling-Water System

heating the incoming air. Therefore, cooling-tower design depends very much on the ambient wet-bulb tem­perature. The tower outlet temperature (exchanger inlet temperature) is calculated from the site wet­bulb temperature and an assumed approach to it (typically 8°F):

T2 = wet-bulb temperature + approach to wet-bulb temperature (3)

Eq. (3) is the first step in designing any coo~ ing system. Often, the approach to wet-bulb temper­ature is set arbitrarily, and this can result in con­siderable investment and operating cost penalties.

To analyze the magnitude of these cost differen­tials, consider the following example:

W = Q/[500 C(T - T. )J (4)gpm out 1n

Here, Q = 300 X 106 Btu/h; C = 1 Btu/(lb)(OF); Tin = 105°F and 125°F; and T = 85°F (80°F wet bulb + 5°F approach) and 95°F (80Q~twet bulb + 15°F approach).

Using Fig. 4b and 6, and subtracting, one can find the tower cost (Table II). There are several things in this example that should be particularly noted.

Although the tower heat duty in all four cases is the same and each represents a valid design, the cooling-system costs vary significantly. One can see that, for a fixed tower outlet temperature, boosting the tower inlet temperature materially reduces cool­ing-tower cost. At a fixed tower inlet temperature mayor may not lower cooling system cost.

At a 125°F tower inlet temperature, varying the tower outlet temperature has a minor effect on the quantity of water circulated. At 105°F, however, the effect is quite significant.

Therefore, even though cooling-tower cost can be reduced by raising the tower outlet temperature, for low tower inlet temperatures, the increase in piping cost can exceed the reduction in cooling-tower cost. Above a tower inlet temperature of 110°F, the inter­action between the tower inlet and outlet tempera­tures and the quantity of water circulated has mini­mal effect on system cost.

Tower outlet temperatures are usually chosen arbitrarily because of lack of communication between the cooling-tower and heat-exchanger designers. Be­fore heat exchangers can be sized, the coolant inlet temperature must be known. The cooling-tower design­er will usually calculate the tower outlet tempera­ture based on either refrigeration or turbine con­denser requirements because these exchangers take the lowest-temoerature coolant. The tower designer then gives this' coolant outlet temperature (exchanger in­let temperature) to the exchanger designer, who or­dinarily does not question the low coolant tempera­ture (although it may not be needed) because it ma'es the job easier.

A better procedure would be for the tower and exchanger designers to simultaneously develop the optimum approach to wet-bulb temperature by: (1)

assuming a reasonable approach to the wet-bulb tem­perature based on both the minimum refrigeration and process outlet temperatures, (2) following the heat­exchanger guidelines to establish the coolant outlet temperatures, (3) calculating the tower inlet tem­perature based on these outlet temperatures, (4) us­ing Fig. 4a or 4b to ascertain whether the assumed approach is the optimum, and (5) considering putting the low-temperature-coolant users on a separate cool­ing-tower cell, if the approach assumed is not optimum.

The advantages of this procedure are that it is quick, does not require heat-exchanger or cooling­tower sizing, and makes both the exchanger and tower designers aware of the system limitations.

Fig. 4a and 4b are for cooling-tower heat illties of 100 million and 300 million Btu/h for a site wet­bulb temperature of 80°F. The tower range (tower inlet minus outlet temperature) is plotted against total tower cost. Note that for a fixed tower outlet temperature total cost decreases as the range widem. Increasing the range requires higher coolant temper­ature rises across the individual heat exchangers. Also notice that for a tower inlet temperature above 110°F, the different approach to wet-bulb (or tower outlet) temperature for a particular tower inlet ­temperature has little effect on the total cost.

In summary, if, after the application of the heat-exchanger guidelines, the tower inlet tempera­ture is less than 110°F, the cooling-tower and heat­exchanger interactions are important and the apprmch to wet-bulb temperature must be found by trial and error. On the other hand, if the tower inlet tem­perature is greater than 110°F, system interactions can be ignored, and a first approximation to the tower outlet temperature should be the site wet-bulb temperature plus 10°F.

APPLYING THE GUIDELINES

It has been shown that cooling-system optimiza­tion requires reducing the coolant flowrate through the system. How the application of the proposed de­sign guidelines to a cooling system can result in considerable investment and operating cost savings will now be illustrated (Table III).

To simplify the analysis, a cooling system com­posed of five heat exchangers will be considered. Each exchanger has a heat duty of 18 million Btu/h, water as the shell-side coolant, and ethylene glycol as the orocess fluid. This cooling system is evalu­ated under two different circumstances: (1) at a fixed coolant temoerature rise of 20°F, or a 10°F approach to the p~ocess outlet temperature if a 20°F coolant rise results in a temperature cross, and (2) by means of the design guidelines that have been presented.

First Application Example

The first exchanger in this application example has a process outlet temperature greater than 150°F. Therefore, the design guidelines call for a coolant outlet temperature of 150°F. A check of the LMTD at the specified temperature levels reveals that the

568

ESL-IE-81-04-97

Proceedings from the Third Industrial Energy Technology Conference Houston, TX, April 26-29, 1981

Page 7: EArt-Designing a 'Near Optimum' Cooling-Water System

...

I.S 1:

1

.~,.., ~ g l:l8 , - ... ~ ~

'9•,a:

~ o~8ggl8 - £ilS.""'l"'.'1(3 _ ..... N ,...,

&i ~ e 2~ ... ~ iw.=

Water treatment economics for higher coolant outlet temperature

Tower inl.t ~mp.ratu~. OF 120 140

Circulation nJ'tB, gpm To~r outlet temperature, OF TOlNer inlet temperature, OF Makeup rate, gpm Slowdown, gpm Concentration cycles InYe'S1JT'l8n t, S/gpm Suspended-solids

removal, S/gpm 16

10,000 90

120 400 100

4 50

30

6,000 90

140 450 150

3 64

TOlM!r investment­Wastewater treatment

of blowdown Suspended-solids removal

135,000 180,000

120,000 160,000

InYeStment cost, S 500,000 384,000

15,000 20,000

Inerem.nt.1 investment, $

.116,000

Net incremental investment, $ -81,000

Incremental

",,.,".

LMTD is greater than 30°F; therefore, system inter­actions can be ignored and the exchanger coolant out­let temperature set at 150°F.

The next three exchangers have process outlet temperatures less than 150°F; therefore, the design guidelines require that the coolant outlet tempera­tures of these exchangers be set at their process outlet temperatures. A check of the LMTDs at the specified temperatures shows that they are greater than 30°F for these three exchangers. Again, system interactions can be ignored, and the coolant outlet temperatures of the second, third and fourth ex­changers can be set at 113°F, 131°F and 113°F, respectively.

The process outlet temperature of the fifth ex­changer is 104°F. If this exchanger's coolant ouUet II

c: temperature is set at 104°F, a check at this temper­ "ii ature shows that the LMTD is less than 30°F. This 11

il,means that, for the fifth exchanger, system inter­ ;,actions are important and must be considered. The .~

cooling-tower inlet temperature, based on the first -0

four exchangers, is calculated to be 121°F; there­ '0 c:

fore, as a first approximation, the tower outlet tem­ .;:o

perature (exchanger inlet temperature) should be set ()

at the site wet-bulb temperature plus 10°F. i-Q.

"'

"'

Finding the optimum outlet temperature of the coolant from the fifth exchanger requires generating a graph similar to Fig. 3c. The procedure is: (l)ffi­sume a coolant outlet temperature for the fifth ex­changer; (2) calculate the tower inlet temperature for the five exchangers; (3) determine the coolant cost from Fig. 4a, using the calculated inlet temper­ature of site wet-bulb temperature plus 10°F; (4) divide the total coolant cost by the tower heat duty and multiply this result by the heat duty of the fifth exchanger; (5) calculate the required heat-ex­changer area, using the assumed cooling-tower temper­atures; (6) plot the exchanger and coolant costs; (7) repeat Steps 1 through 6 at two different coolant outlet temperatures.

The coolant outlet temperature at which the sy~

tern cost is lowest should be chosen. In this exam­ple, the optimum coolant outlet temperature is l22~.

For a 122°F coolant outlet temperature, an 18°F cross occurs. This requires multiple shells in series; therefore, the coolant outlet temoerature was set at 104°F. For an exchanger in this ~ategory, one shoilld consider going to a single-pass tube geometry or to a spiral exchanger, so that true countercurrent flow will be achieved and the temperature cross eliminat­ed. By eliminating the temperature cross, the cool­ant outlet temperature of 122°F can be specified.

Wider approach temperatu re cuts tower cost

ea.. l Case 2

Tower inlet temperature, of 105 105 Tower outlet temperature, OF 85 95 Coolant flowrate, gpm Cost of tOlIVer, pumps and

piping (from Fig. 4B), S/yr COSt of pumps and piping.

Ifrom Fig. 61, Slyr

COst of tOlNer. S/yr

30,000 60,000

Table II

Case 3 Case 4

125 125 85 95

15,000 20,000

700,000 810,000 500,000 430,000

340,000 560,000 220,000 270.000

360,000 250,000 280,000 160,000

Opef'ating cost, $/yr Tower costt 150,000 90,000 Water for makeup

at 1O€ /1,000 gal 20,000 22,500 Chemicals 48,000 54,000

Net incremental oPe'fating cost, S/vr

·Coolln~to....,..rInclucMil pumps and piping. tO~,...tin; CO$t i. tJlk.n .. $0.03/1.000 g.el ot c.~itY.

cost, S/yr -<30,000

2,500 6,000

·51,500

569

ESL-IE-81-04-97

Proceedings from the Third Industrial Energy Technology Conference Houston, TX, April 26-29, 1981

Page 8: EArt-Designing a 'Near Optimum' Cooling-Water System

This example shows why the cooling-tower outlet temperature is the "Achilles heel" of this study. To be rigorous, the fifth heat exchanger should be resized, using the optimum coolant outlet tempera­ture calculated but with the coolant inlet tempera­ture reduced by 4°F. If exchanger-area requirements are greatly reduced by the lower coolant inlet tem­perature, the tower and exchanger interaction is significant, and the foregoing Steps 1 through 6 should be repeated at the lower coolant inlet tem­perature.

Recalculating this exchanger for three differ­ent coolant outlet temperatures is, however, time­consuming and may not be necessary. Because the four exchangers with the LMTD greater than 30°F will be unaffected by a slight reduction in coolant inlet temperature, what is really being sought is how sig­nificant is the cost of the fifth exchanger to the total system cost.

Through engineering judgment and application of the proposed guidelines, one can design a partially, nearly or wholly optimized cooling system, depending on how much effort one is willing to put out.

1. If one applies the guidelines only to ex­changers that have an LMTD greater than 30°F, a par­tial optimization will be attained.

2. If one is willing to generate curves simiVn to Fig. 3c for exchangers with an LMTD less than 30°F, a nearly optimum design will be gained.

3. If one is willing to recalculate the ex­changers with an LMTD of less than 30°F at differ­ent coolant inlet temperatures, then a wholly opti­mized system will be designed.

Inspection of Fig. 4a shows, however, that the last procedure is not necessary if the calculated tower inlet temperature is greater than 110°F, or if the exchangers that require the low-temperature cool­ant do not contribute significantly to the system heat duty. If the calculated tower inlet temperarure is less than 110°F, the last procedure is necessary.

Returning to the example (Table III), if one used the fixed coolant temperature-rise case as the economic basis, it can be seen that the guideline de­si~a would reduce the total coolant flowrate by 49% (14,400 gpm vs. 7,300 gpm), the operating cost by43% (S90,000/yr), and the total investment by 27% ($364,000). This example again demonstrates that a higher exchanger investment can reduce cooling-sys~m

investment and operating cost.

It is important to maintain a water velocity that mlnlmlzes the deposition of suspended solids. In the initial design of an exchanger, it is desir­able to select the baffle spacing or number of tube passes to get a water velocity above 5 ft/s. This velocity should never be less than 2 ft/s. One should recognize that raising the coolant temper&ure for an existing exchanger results in a lower coolant velocity, which, if below 2 ft/s, intensifies the tendency for suspended solids to deposit. Besides increasing the fouling factor, the sludge deposits accelerate the pitting of tube surfaces.

Water-Treatment Costs

It is usually at about this point that skeptics ask, "\';hat about the higher water-treatment cost?" The following answers this question:

Water-treatment economics--Water-treatment re­quirements do rise if the cooling-tower inlet tempe~ ature is increased. The actual cost of water treat­ment at any operating temperature is related to the quality of the makeup water and its particular treat­ment requirements. Obsiously, waters having high concentrations of sludge or dissolved mineral salts will require more treatment. Usually, the magnftude of the increased treatment cost will be minimal for the same source of makeup water.

Mineral salts--The commonly present mineralsa14 calcium carbonate, has a limited and inverse solubil­ity (less soluble at higher temperatures), and thus requires more treatment to prevent scale deposits as the water temperature is raised. Increased addition of sulfuric acid should resolve most problems. How­ever, if the volume of blowdown to control the con­centration of mineral salts resulting from increased evaporation in the cooling tower must be augmented, the added cost of waste-water treatment for the ~ea~

er volume of blowdown could represent an appreciable water-treatment cost increase.

Suspended solids--The tendency of suspended sol­ids (turbidity) in the cooling water to deposit on tube surfaces increases as the coolant temperature is raised. Such deposition can be prevented by the use of a sludge dispersant.

Biological growth--Organic growth speeds up as the coolant-water temperature increases. The resul~

ing slime deposits that develop on tube surfaces can reduce heat transfer and tend to collect more of the suspended solids than might otherwise deposit from a cooling-temperature increase alone. This type of fouling can be controlled by addition of free chlo­rine or a nonoxidizing biocide.

Accounting for Water-Treatment Costs

Table IV compares system cost between a cooling tower receiving water at temperatures of 120°F and 140°F. Using the 120°F temperature case as the eco­nomic basis, it can be shown that the tower invest­ment is reduced by $116,000 by going to 140°F, but the water-treatment investment is boosted $35,000 ($15,000 for water-treatment facilities and $20,000 for augmented blowdown facilities).

Therefore, at the 140°F cooling-tower return­water remoerature, the net investment is reduced by $81,000.. Additionally, an operating cost savings of $60,OOO/yr can also be realized. However, this $60.000/yr savings is reduced by the increase in water-treatment chemicals and makeup-water cost of S8,SOO/yr. Therefore, the net-operating-cost re­duction is $Sl,SOO/yr.

570

ESL-IE-81-04-97

Proceedings from the Third Industrial Energy Technology Conference Houston, TX, April 26-29, 1981

Page 9: EArt-Designing a 'Near Optimum' Cooling-Water System

References

1. Woods, D. R., Anderson, J. J., and Norman, S. L., Evaluation of Capital Cost Data: Heat Exchangers, Can. J. of Chern. Eng., Vol. 54, December 1976.

2. The Marley Co., "Managing lo/aste Heat with the ~Iater Cooling Tower," 1970.

3. The Marley Co., "Cooling Tower Fundamentals and Application Principles," 1969.

600 ,.--,---.,.--,---.....,----.,,---...,

~ 500 4O.000'ilPff\ ii g '5 400

§ 20.000 gpm 0. 300E ~ 0. '0

10.000 ggmii 200 ~

0.'1· il:

;~ 100 4 6 8 10 12

Pipe velocity, ftls 14 16

Pump end piping cost is reletively insensitive to coolent velocity Fig. 6

,, , , ' , ' " "i

To......routlet

350 L TO\Nef duty: 100 million 8tu/h>­ To......, wet·bulb tlmperlltUr,: 8O·F

~ ~

:II ~

~ 300

'".,; c '0. '6. '0

ii 0. 250 E ~ 0.

5' ~.I:'

..S ~

200 t,moer.turt, -F

~ u <;

5 u

150 10 20 30 40 50

Cooling-tower range, -F

900 b. Tower dutY: 300 million: Bluth

>- TOMr ......l·bulb temperatur,: aO-F'tJ c ::l 800, ~ '".,; ~ 700

:§­0. '0

ii Q. 600 E, 0.

i 500

0> " :a ~

° u 400 c <3

300 10 20 30 40 50

,, , , ,' ,f/

Tower outlet t,mperature, ~F

Cooling-to'Ner range, -F

Coolent economics may be estimeted from tower-range reletionship Fig. 4

c 0 ';;.. :; u ] !: a ~ :>

} 5 u 0­E :> 0­..,; l.. 0­'0.

2 ~

~.. .D ~.. ~.. t ~ c 0';; :! :>

'" ;;:: c: 0 u

E t: ~ b",5 I 0' 8

r-~ I

~nT '"d

~ , r ° c~j , >~

, ~~ --.:lH '"!'._ u 0

:§.lE5. .,;

" J,

~ iH £g ~~~

-<x1­ 1';;" i N .~.e d G:~

J' '-­ £.§

j '"

" d

§ ~ , ~.§

" j.JL rt><>­d

J • -i><r £)

" ~

L lp f e •• E ~ s ~2

~i £~ ... .

o§i I----.J &82 1 ~

Ii:

Economic .dvanlage of a temperature cross

Proceu inlat: 250 OF

Process outlet: 115°F

C_l Cao2 No Croa.

Water outlet temperature, OF 105 115

Corrected LMTO, OF 63 54 Exchanger area. ft2 1,600 1.650 Incremental exchanger

investmen t. $ ..sao ,500 Coolant flow, gpm 1.330 820 Incremental coolant

investment. $ 34.500 6.600 Net inYe1tment

penaltY. S 33,700 6,100 Coolant operating

COst, S/yr 32,000 20,000 Net C$erating COSt

penalty. S/vr 15,000 3,000

'" ~~

r

Table t

C_3 CrOll

120 i: 39 1,680

0 700

0 , 0

17,000

0

571

ESL-IE-81-04-97

Proceedings from the Third Industrial Energy Technology Conference Houston, TX, April 26-29, 1981