GRID GRID Generation Telecom Transmission Distribution Markets Telecom Oil and Gas e-terragridcom TPI Integrated teleprotection TELECOM

e TerragridcomTPI

Embed Size (px)

DESCRIPTION

telemetry

Citation preview

Page 1: e TerragridcomTPI

GRIDGRID

Generation

Telecom

Transmission Distribution Markets Telecom Oil and Gas

e-terragridcom TPIIntegrated teleprotection

Telecom

Page 2: e TerragridcomTPI

Generation Transmission Distribution Markets Telecom Oil and Gas

e-terragridcom TPI is an integrated teleprotection module for e-terragridcom T390 power line carrier

customers’ critical applications must have dependable access to electricity.

Reliable and independent communication between protection relays is paramount in ensuring security of service, protecting the power grid, and maintaining protection scheme operability.

The e-terragridcom TPI provides an integrated Teleprotection to Power line carrier, that remains a 100% Power Utility controlled communication network.

As an alternative to full digital communication solutions, Alstom Grid offers an innovative product for significant improvements in communication reliability in the electrical network.

With its dual path communication channels, the e-terragridcom TPI can deliver maximised performance according to customer requirements, drawing the benefits of an optical digital link in parallel with the Plc link.

Communication interface redundancy and connectivity

To improve security and reliability of Teleprotection commands, the e-terragridcom TPI offers the option of digital paths concurrently to Plc thus, improving the Probability of missing commands (Pmc) and Transfer Time (T0).

Furthermore, in response to key requests from customers, logical operations can now be applied to commands sent simultaneously on all available communication links.

At the reception side, an “oR” function can be applied on the commands received on a different path to trip the corresponding output The output is activated by the first received command from either link.

●● In terms of Pmc, reliability is improved by the fact that the 2 links operate in parallel

●● Transfer time (T0) is the best of the two links

Communication link options

The e-terragridcom TPI can be equipped with an optical SFP module for “inter or intrasubstation“ communications, allowing direct connection of the e-terragridcom TPIs or to a multiplexer compatible with Ieee c37.94 without converter or other intermediate equipment.

Also, e-terragridcom TPI connectivity can be expanded with the addition of electrical communication interfaces over V11/ X21, G703-1 64 Kbits/s and G703-6 2 mBits/s.

Modular architecture

The Plc T390 modular architecture can include up to two e-terragridcom TPI modules.

●● The 1U height e-terragridcom TPI module offers the largest number of inputs and outputs for an integrated Teleprotection.

●● each e-terragridcom TPI module is equipped with eight Inputs and 14 Heavy Duty outputs. They are freely programmable through the Human machine Interface (HmI) as main output, copy, or alarm. capacity to activate directly some circuit trip coils.

●● The e-terragridcom TPI module supports up to four commands in analogue mode, or six with priority scheme.

●● In digital mode, eight commands are supported, to cover more protection requirements, but which can also be applied to alarms and position information.

●● modular●● Integrated●● communication redundancy●● optimized bandwidth●● manageable

Customer Benefits

Enhance your grid security without trade-offs

Optical Interfaceas per IEEE C37.94

Transmission Line

SNMP Compliant Network Management Software e-terrasentinel

LMUCoupling Box

LMUCoupling Box

Electrical Interfaceas per V11 / G703 or E1

Multi-plexer

Multi-plexer

Max 40 ou 80W (option)

TelecomNetwork

Optional concurent digital communication path forteleprotection command

Circuit plug andcoupling capacitor

Circuit plug andcoupling capacitor

e-terragridcom T390Power Line Carrier

e-terragridcom T390Power Line Carrier

Integrated Teleprotection Modulee-terragridcom TPI

e-terragridcom DXC or e-terragridcom e-DXC

Telecom e-terragridcom TPI

Page 3: e TerragridcomTPI

Generation Transmission Distribution Markets Telecom Oil and Gas

1 TPi in QAM

●● command in the e-terragridcom T390 digital band (QAm separated or adjacent mode)

●● 4 independent commands or 6 with priority scheme

●● 4 / 8 / 16 KHz per band●● Functioning in superimposed mode 16 kHz

1 TPi in Speech band silent mode or dual tone per channel (up to 2)

●● Analogue modulation (separated or adjacent)●● 4 commands or 6 with priority scheme●● Silent mode (no bandwidth use) in speech

band or dual tone (1800 Hz band) (RF band allocation by HmI)

●● 2 / 2.5 / 4 KHz per band

Teleprotection configuration and maintenance

The Teleprotection module is fully configurable through the graphical HmI of the Plc by the mean of an allocation matrix.

The HmI automatically recognises the e-terragridcom TPI module(s) and the Plc, which creates time and cost savings, since additional interfaces and specialised test and commissioning tools are unnecessary.

All facilities of the graphical HmI T1, such as remote configuration using the PLC’s IP address are available to the e-terragridcom TPI module. This includes compatibility with network management system compliant with SNmP protocol.

To cope with cyber security concerns, e-terragridcom T390 is the first PLC equipment to offer AeS encryption and this feature is also available with e-terragridcom TPI module to ensure secure information exchange between the HmI and the e-terragridcom T390.

Bandwidth optimisation

To benefit from the maximum ratio between transmission speed and bandwidth, the e-terragridcom TPI can transmit Teleprotection signals within the Plc digital communication stream. Since e-terragridcom TPI command signals cut the digital transmission a Fast Recovery Time algorithm allows resynchronisation of the Digital communication link after tripping commands that can be as low as 200ms.

The e-terragridcom TPI module can also work with analogue channels of 2; 2.5 or 4 kHz . Two possibilities are offered :

●● Dedicated band to Teleprotection command for best transfer time and security

●● ”Silent mode “ over the speech channel. At Idle state the teleprotection does not require any bandwidth. When a trip command is activated, only the channel dedicated to voice transmission can be cut depending on activation or non-activation of the boost facility

The e-terragridcom TPI architecture is already prepared for support of future hardware developments and, similarly, the firmware is “Ethernet-ready” (Teleprotection applications using IEC 61850). The firmware also incorporates future options to comply with a large range of customer constraints.

Future-Proofed Design

4 or 8 or 16 kHz

Pilote-terragridcomTPIQAMTX Band

Signalling Signalling

4 or 5 or 8 kHz

PilotPilot e-terragridcomTPI

Spee

ch T

X Ba

nd

Spee

ch R

X Ba

nd

Telephone Telephone PABX

Data RS232 Data V11 Data Ethernet

Protection Relay

Intertripping commands

Additional AmplifierUp to 80W (Optional)

ExternalTeleprotection

AmplifierUp to 40W

Processing Unit

Optional Service UnitUp to 9

Integrated TeleprotectionModule with Dual

Communication Path(Optional)

2nd IntegratedTeleprotection Module

(Optional)

LAN

Multiplexer

Digital Medium

Power Line Medium

Telecom Network

Telecom e-terragridcom TPI

Page 4: e TerragridcomTPI

Generation Transmission Distribution Markets Telecom Oil and Gas

Telecom

For further informationplease contact:

Alstom Grid Inc.10865 Willows Rd. Ne, RedmondWA 98052-2502, USATel: +1 (425) 822 6800e-mail: [email protected]

Alstom Grid Worldwide Contact Centerwww.alstom.com/grid/contactcentre/Tel: +44 (0) 1785 250 070www.alstom.com

© A

lSTo

m 2

011.

All

right

s res

erve

d. In

form

atio

n co

ntai

ned

in th

is do

cum

ent i

s ind

icat

ive

only.

No

repr

esen

tatio

n or

war

rant

y is

give

n or

shou

ld b

e re

lied

on th

at it

is co

mpl

ete

or co

rrec

t or w

ill a

pply

to a

ny p

artic

ular

pro

ject

. Thi

s will

de

pend

on

the

tech

nica

l and

com

mer

cial

circ

umst

ance

s. It

is p

rovi

ded

with

out l

iabi

lity

and

is su

bjec

t to

chan

ge w

ithou

t not

ice. R

epro

duct

ion,

use

or d

isclo

sure

to th

ird p

artie

s, w

ithou

t exp

ress

writ

ten

auth

ority

, is

stric

tly p

rohi

bite

d.

GRIDGRID

Features●● Teleprotection module for Digital Power

line carrier e-terragridcom T390●● modular architecture upgradable by the

customer●● Transmission up to four independent

commands over e-terragridcom T390 (up to six with priority)

●● Transmission up to eight independent commands over Digital link

●● command can be send simultaneously on both communication medium if available for better reliability and transfer time

●● Commands configurable as blocking, permissive or direct tripping

●● optimised communication through Power line carrier e-terragridcom T390

●● compliant with digital Plc e-terragridcom T390 communication (TP in QAm)

Communication Interfaces●● overhead line through Power line

carrier e-terragridcom T390●● Redundant communication interface as

an option ( to be chosen among )●● 64 Kbit/s with G703.1●● 2 mbit/s with G703.6●● From 32 to 256 Kbit/s with V11 / V35

(RS422 – X24 protocol)●● optical interface for direct link or Ieee

c37.94 to e-terragridcom DXc or any other multiplexer with compatible interface or●› Direct single mode up to 250 km●› Communication on single or dual fibre

Human Machine Interface●● Integrated test tools●● command forcing with loop-back

function offering transfer time measurement

●● Real transfer time and BeR measurement on the digital link

●● cross-connection matrix for Input , output and communication path●› Input and output logical combinations with

”logical command” capacity

Inputs ans Outputs●● 8 Inputs – command acquisition

by voltage (24 to 250VDc) with optoelectronic decoupling

●● 14 Heavy Duty outputs (8 N/o and 6 N/o-N/c) - up to 290VDc, 100W, Breaking capacity up to 8A* ) * at 100 VDc

Performance - 4 commands mode●● Permissive Transfer Time (T0) (including

Plcs treatment time):●› TP over Speech: T0 ≤ 12 ms●› TP in QAM: T0 ≤ 12 ms●› TP digital 64 Kbps: T0 ≤ 6.5 ms

●● Probability of unwanted command (Puc):●› Analogue mode: Puc up to 10-9●› Digital mode: Puc ≤ 6E E-30

●● Probability of missing command (Pmc):●› Analogue mode: Up to 10-6●› Digital mode: Pmc ≤ 1E E-35

Operating Conditions●● Power supply voltage

●› 48VDc -30% to +25%●● operating temperature

●› -30°c / +55°c as per Iec 60068-2-1 and -2

●● max relative humidity ●› 95% at 40°c

as per Iec 60068-2-3●● Storage Temperature

●› -45°c < T < +70°c as per Iec 60870-2-1 and -2

●● mechanical Test ●› Iec 60255-21-1 and -2

Applicable Standard●● Iec recommendations

●› General: follows Iec 60834-1●› emc as per cISP22 (2006)●› Iec 61000-6-4●› Iec 61000-6-2

●● european recommendations●› eN 60950

●● Ieee Standard●› c37.90.1 /.2 / .3●› c37.94 compatible

Physical Dimension (mm)●● 483 (W) * 43,6 (1U) (H) * 297 (D)

Technical data

Telecom e-terragridcom TPI