e Man Ri Ters e 14

Embed Size (px)

Citation preview

  • 8/21/2019 e Man Ri Ters e 14

    1/96

    Driver Operating Manual

    E-MAN-RI-TERSIntegral-to-valve electronic drivers

    for pressure proportionals with integral transducer

  • 8/21/2019 e Man Ri Ters e 14

    2/96

  • 8/21/2019 e Man Ri Ters e 14

    3/96

    Contents

    E-MAN-RI-TERS/E-14 3Driver Operating Manual

    Contents

    1 General ...............................................................................................................................7

    1.1

    About this user manual ....................................................................................................7

    1.2 Documentation ................................................................................................................71.2.1 Related documentations .............................................................................................71.2.2 Atos Download Area ...................................................................................................71.2.3 Trademarks ................................................................................................................8

    1.3 About proportional electrohydraulics ................................................................................91.3.1 Electrohydraulics: hydraulics plus electronics..............................................................91.3.2 Control loops ..............................................................................................................91.3.3 Digital proportional controls ...................................................................................... 101.3.4 Digital electronic drivers............................................................................................ 111.3.5 Fieldbus systems...................................................................................................... 111.3.6 Axis motion controllers ............................................................................................. 12

    1.4

    About E-SW programming software ............................................................................... 13

    1.4.1 Registration and Access level ................................................................................... 131.4.2 Dvd contents ............................................................................................................ 131.4.3 Installation Manager Desktop ................................................................................... 141.4.4 Communication USB adapters and Cables ............................................................... 151.4.5 Minimum PC requirements for E-SW ........................................................................ 15

    1.5 Safety prescriptions ....................................................................................................... 161.5.1 General warning ....................................................................................................... 161.5.2 Personnel selection and qualification ........................................................................ 161.5.3 Electrical installation warning .................................................................................... 161.5.4 Electromagnetic compatibility ................................................................................... 171.5.5 Electrostatic discharge protection ............................................................................. 17

    1.5.6

    Repair and Troubleshooting...................................................................................... 17

    2 About E-RI-TER(AER)S drivers ........................................................................................ 18

    2.1 Model Code ................................................................................................................... 18

    2.2 Electrical Features......................................................................................................... 19

    3 Getting started.................................................................................................................. 20

    3.1 Programming tools installation ....................................................................................... 20

    3.2

    Driver installation ........................................................................................................... 20

    3.3 Driver configuration ....................................................................................................... 20

    4 Valve Installation .............................................................................................................. 21

    4.1 General prescriptions .................................................................................................... 21

    4.2 Mounting ....................................................................................................................... 22

    5 Driver Electrical connections .......................................................................................... 23

    5.1 General prescriptions .................................................................................................... 23

    5.2 Main connection ............................................................................................................ 245.2.1 Power supply (pin A,B - pin 1,2)................................................................................ 255.2.2 Reference input signal (pin D,E - pin 4,5) .................................................................. 255.2.3 Monitor output signal (pin F,C - pin 6,5) .................................................................... 255.2.4 Enable input signal (pin 3,2) - only for /Z option ........................................................ 255.2.5 Fault output (pin 11, 2) - only for /Z option................................................................. 26

    5.2.6

    Double Power (pin 9, 10) - only for /Z option ............................................................. 26

    5.3 Remote transducer connection (AERS drivers) .............................................................. 26

    5.4 Communication connection............................................................................................ 27

  • 8/21/2019 e Man Ri Ters e 14

    4/96

    Contents

    4 E-MAN-RI-TERS/E-14Driver Operating Manual

    5.4.1 Fieldbus communication connector........................................................................... 275.4.2 Hardware Node assignment ..................................................................................... 27

    6 Driver parameters operation............................................................................................ 28

    6.1 Parameters operation scheme ....................................................................................... 28

    6.2 Driver parameters ......................................................................................................... 28

    6.2.1

    Actual Parameters (non-permanent memory) ........................................................... 286.2.2 Driver Preset/User/Emergency Parameters (permanent memory)........................... 28

    6.2.3 Store Driver Parameters ........................................................................................... 296.2.4 Restore Driver Parameters ....................................................................................... 29

    6.3 E-SW parameters.......................................................................................................... 296.3.1 E-SW Actual Parameters (non-permanent memory) ............................................... 296.3.2 E-SW Setting Files (permanent memory) ............................................................... 30

    7 Software Graphic Interface .............................................................................................. 31

    7.1 Main window ................................................................................................................. 31

    7.2 Extended Diagnostic window ......................................................................................... 32

    7.3 Oscilloscope window ..................................................................................................... 32

    7.4 Error parameters ........................................................................................................... 337.4.1 Missing parameters (OFF-LINE mode) ..................................................................... 337.4.2 Communication error s (ON-LINE mode) ................................................................... 33

    8 Main Window Communication area .............................................................................. 34

    8.1 ON-LINE/OFF-LINE mode ............................................................................................. 34

    8.2 Communication Error .................................................................................................... 35

    8.3 Communication Settings................................................................................................ 35

    9 Main Window Diagnos tic area ...................................................................................... 36

    9.1 Working signals ............................................................................................................. 36

    9.1.1

    Reference Type........................................................................................................ 36

    9.1.2 Reference Actual...................................................................................................... 379.1.3 Reference Demanded .............................................................................................. 379.1.4 Feedback ................................................................................................................. 379.1.5 PID Out .................................................................................................................... 37

    9.2 Driver status and warnings ............................................................................................ 389.2.1 Driver status ............................................................................................................. 389.2.2 Alarm ....................................................................................................................... 389.2.3

    Last Error

    ................................................................................................................. 39

    9.3

    Driver Memories ............................................................................................................ 40

    9.3.1 Requested ............................................................................................................... 409.3.2 Loaded..................................................................................................................... 40

    9.3.3

    Store User Parameters ............................................................................................. 409.3.4 Driver Restart ........................................................................................................... 40

    10 Main Window - Menu area [Information] ......................................................................... 41

    10.1 Valve Information .......................................................................................................... 41

    10.2 Driver Information.......................................................................................................... 41

    10.3 User Information............................................................................................................ 42

    10.4 Hydraulic Configuration ................................................................................................. 42

    11 Main Window Menu area [Settings] .............................................................................. 43

    11.1 Pressure - Reference .................................................................................................... 44

    11.2

    Pressure - Feedback (AERS drivers) [level 2] ................................................................ 49

    11.3 Pressure(Force) - Regulation - Bias............................................................................... 51

    11.4 Pressure - Regulation - Scale ........................................................................................ 54

  • 8/21/2019 e Man Ri Ters e 14

    5/96

    Contents

    E-MAN-RI-TERS/E-14 5Driver Operating Manual

    11.5 Pressure - Ramps ......................................................................................................... 56

    11.6 Pressure - Linearization [level 2] .................................................................................... 58

    11.7 Pressure - PID [level 2] .................................................................................................. 60

    11.8 Others Monitor Output ................................................................................................ 62

    11.9

    Others Diagnostics [level 2] ........................................................................................ 63

    11.10

    Others Filter [level 2] .................................................................................................. 66

    11.11 Fieldbus (BC/BP) - Driver communication ...................................................................... 68

    11.12 Fieldbus - State Machine [level 2] .................................................................................. 70

    11.13 Wizard........................................................................................................................... 71

    12 Main Window - Menu area [Sett ing Files Manager]......................................................... 74

    12.1 Save (store into pc) ....................................................................................................... 74

    12.2 Load (restore from pc) ................................................................................................... 75

    13 Main Window - Menu area [E-SW Configuration] ............................................................ 76

    13.1 Graphic Interface Access Level .................................................................................. 76

    13.2

    Communication ............................................................................................................. 77

    13.2.1 Serial communication (E-SW-PS) ............................................................................. 7713.2.2 CANopen communication (E-SW-BC) ....................................................................... 7813.2.3 PROFIBUS DP communication (E-SW-BP) .............................................................. 79

    14 Main Window - Menu area [About] .................................................................................. 80

    14.1 Contact Us .................................................................................................................... 8014.1.1 Atos spa ................................................................................................................... 8014.1.2 Support .................................................................................................................... 81

    14.2 E-SW software .............................................................................................................. 8114.2.1 Activation info ........................................................................................................... 8114.2.2 Installation info ......................................................................................................... 81

    15 Extended Diagnostic Window.......................................................................................... 82

    15.1 Working Signals ............................................................................................................ 82

    15.2 Driver Status ................................................................................................................. 82

    15.3 Detailed Error s .............................................................................................................. 8315.3.1 Fault Acknowledge ................................................................................................... 8315.3.2 Analog Error s External Reference.......................................................................... 8315.3.3 Analog Error s Feedbacks ...................................................................................... 8415.3.4 PID Out Error s.......................................................................................................... 8415.3.5 Temperature Error s .................................................................................................. 84

    15.4 True/false conditions ..................................................................................................... 85

    15.4.1

    Digital OUT .............................................................................................................. 85

    15.4.2

    Digital IN .................................................................................................................. 85

    15.4.3

    Working Conditions .................................................................................................. 85

    15.5 Driver Memories ............................................................................................................ 8615.5.1 Adjust Name............................................................................................................. 8615.5.2 Last Store................................................................................................................. 8615.5.3 Restore User and Preset Parameters ....................................................................... 86

    16 Oscilloscope Window ...................................................................................................... 87

    16.1 Acquisition and Trigger Configuration ............................................................................ 8816.1.1 Acquisition - Sample Time ........................................................................................ 8816.1.2 Acquisition - Period .................................................................................................. 8816.1.3 Trigger Configuration Type .................................................................................... 8816.1.4

    Acquisition process data ........................................................................................... 89

    16.1.5 Trigger Configuration - Signal ................................................................................... 8916.1.6 Trigger Configuration - Level .................................................................................... 89

  • 8/21/2019 e Man Ri Ters e 14

    6/96

    Contents

    6 E-MAN-RI-TERS/E-14Driver Operating Manual

    16.1.7 Trigger Configuration - Edge .................................................................................... 8916.1.8 Trigger Configuration - Pre-trigger ............................................................................ 8916.1.9 Trigger Configuration - Holding Time ........................................................................ 89

    16.2 Cursors ......................................................................................................................... 9016.2.1 ON/OFF Cursor ........................................................................................................ 9016.2.2 Position .................................................................................................................... 9016.2.3

    Plot Lock .................................................................................................................. 90

    16.2.4

    Delta ..................................................................................................................... 90

    16.2.5 Y Position................................................................................................................. 90

    16.3 Legend.......................................................................................................................... 9116.3.1 ON/OFF Legend....................................................................................................... 91

    16.4 Scale and Grid .............................................................................................................. 9216.4.1 Scale and Grid Configuration.................................................................................... 92

    16.5 Panel Config ................................................................................................................. 93

    17 Firmware version availab le parameters ....................................................................... 94

  • 8/21/2019 e Man Ri Ters e 14

    7/96

    1 General

    E-MAN-RI-TERS/E-14 7Driver Operating Manual

    1 General

    1.1 About this user manual

    This manual describes the required operations to install and configure Atos proportional control valves withAtos E-SW programming for PC.

    This manual must be used for pressure relief/reducing proportional valves with integral (TERS) or remote

    (AERS) pressure transducer (see1.3.3) Atos software E-SW-** version 6.0 or greater is required (see1.4).

    Before installing or operating the driver for the first time, read this manual.

    The purpose of this manual is not to cover all the details or variations of Atos drivers and software, and it

    does not provide complete details for all possible working conditions; if any further information or technical

    support are required, please contact the Technical Sales Support of Atos Electronic Division

    ([email protected]).

    The manual contains important safety instructions (see1.5), whose knowledge is required to:

    avoid hazards and dangers

    minimize service and downtime

    increase the working and reliability of the driver

    In addition please follow up all the running regulations of the country/community where the drivers will be

    used.

    A basic skill in using personal computers and Windowsoperating system is required.

    1.2 Documentation

    Additional information about valves, electronic drivers and Atos software can be found into the AtosCatalog on-line or in the Atos Download Area(see1.2.2).

    1.2.1 Related documentations

    QUICKSTART-PS Software instruction manual - installation of Serial E-SW-PS and E-SW-PS/S

    QUICKSTART-BC Software instruction manual - installation of CANopen E-SW-BC and E-SW-BC/S

    QUICKSTART-BP Software instruction manual - installation of PROFIBUS DP E-SW-BP and E-SW-BP/S

    F*** Proportional pressure valves and cartridges - technical tables

    TT242-1 Installation and commissioning for proportional valves

    G205 Integral driver for proportional valves with integral or remote pressure transducer -

    technical table

    G465 Pressure transducers with amplified analog output signal - technical table

    G500 Programming software for digital drivers - technical table

    G510 Fieldbus Features of digital drivers - technical table

    E-MAN-S-BC Operating manual for Atos CANopen drivers

    E-MAN-S-BP Operating manual for Atos PROFIBUS DP drivers

    1.2.2 Atos Download AreaLatest releases of manuals, programming software and USB adapter drivers are available on Atos internet

    Download Area (www.download.atos.com).

    mailto:[email protected]:[email protected]:[email protected]://www.download.atos.com/http://www.download.atos.com/http://www.download.atos.com/http://www.download.atos.com/mailto:[email protected]
  • 8/21/2019 e Man Ri Ters e 14

    8/96

    1 General

    8 E-MAN-RI-TERS/E-14Driver Operating Manual

    To access Atos Download Area it is required to apply online registration : Atos support service will send

    an e-mail containing the required Username and Password.

    During registration to Atos Download Area, fill-in the serial number printed on E-SW Dvd to receive also the

    software Activation Code and the Access Password to modify the software graphic interface level.

    An automatic e-mail service will inform all users of registered software whenever new software or

    technical documentation updates are available.

    Updated software and USB drivers can be easily installed following the instruction contained in theinfo.txt files available in the downloading section.

    1.2.3 Trademarks

    All Atos trademarks and are distinctive sign of Atos rights, know-how, and in general intellectual

    properties. Partial or full-unauthorized reproduction of this manual, images, logos, or casting through

    internet, may be object of punishment by local law.

    Upon delivery, all installed software is copyright-protected. The software may only be reproduced with our

    written consent or in accordance with the license agreement.

    Windowsis a registered trademark of Microsoft Corporation

    Pentiumis a registered trademark of Intel Corporation

    http://en.wikipedia.org/wiki/Sign_%28semiotics%29http://en.wikipedia.org/wiki/Sign_%28semiotics%29
  • 8/21/2019 e Man Ri Ters e 14

    9/96

    1 General

    E-MAN-RI-TERS/E-14 9Driver Operating Manual

    1.3 About proportional electrohydraulics

    1.3.1 Electrohydraulics : hydraulics plus electronics

    Atos is a leading manufacturer of electrohydraulic components & systems: the advanced technology that

    integrates hydraulics and electronics to improve performances and flexibility of the modern machinery.

    Electrohydraulic proportional controls modulate hydraulic parameters according to the electronic reference

    signals; they are the ideal interface between hydraulic and electronic systems to perform fast, smooth and

    accurate motions required by todays modern machines and plants.

    Operating principle

    The core of electrohydraulic controls is the proportional valve that modulates pressure or flow according to

    the electronic input signal (standard: external analog signal 10 VDC).

    The force of the solenoid is proportional to the reference signal, thus properly moving the spool against areturn spring to modulate hydraulic parameters

    When electrical failure occurs, the spring

    restores the neutral position according to the

    valve configuration.

    Proportional valves are available with

    different neutral position to achieve the

    required fail-safe configuration.

    The wide range of Atos proportional valves is

    available with or without integral feedback

    transducer.

    The sketch at side shows a proportional

    directional valve with spool feedback

    transducer.

    1.3.2 Control loops

    Open loop con trols

    Control is provided through the modulation ofcurrent supplied to valve solenoid without the

    effective result of the regulating loop being

    verified.

    R reference inputD digital driverV proportional valveM valves main stageT valves transducerL main stage transducerO actuator

    Closed loop controls

    Feedback transducers continuously verify the

    effective result of regulation thus the closed

    loop control compensates environmental

    disturbances.

  • 8/21/2019 e Man Ri Ters e 14

    10/96

    1 General

    10 E-MAN-RI-TERS/E-14Driver Operating Manual

    1.3.3 Digital proportional controls

    Atos offers today one of the most advanced lines of proportional valves which allow performances close to

    servovalves still maintaining the typical benefits of proportional electrohydraulics: less sensitivity, low

    filtration requirements, intrinsic stability, easier servicing and lower cost.

    The wide range of Atos proportional electrohydraulics is available in different executions to match the

    specific application requirements and to allow simple upgrade of machine performances:

    ZO-A

    Open loop proportional valves to control direction/flow, pressure or flow with

    pressure compensation; separate electronic drivers are required.

    ZO-AES

    As ZO-A execution plus digital integral electronic driver, factory preset to

    ensure fine functionality, valve-to-valve interchangeability and easier set-up.

    ZO-TES; ZO-LES

    Closed loop proportional valves to control direction/flow or flow with pressure

    compensation.

    Digital integral electronic driver (factory preset) and integral spool position

    transducers (1 for ZO-TES, 2 for ZO-LES) assure valve-to-valve

    interchangeability, easier set-up and high response dynamics.

    SP/SF/SL options add pressure/force control with alternated control selection

    logic.

    ZO-TERS; ZO-AERS

    Closed loop proportional valves to control maximum relieved or reduced

    pressure.

    Digital integral electronic driver (factory preset) and integral pressure

    transducer (ZO-TERS) assure valve-to-valve interchangeability, easier set-up

    and high response dynamics; valves with remote pressure transducer (ZO-

    AERS) allow more precise regulation and application flexibility.

    ZO-PES

    Variable displacement pumps with digital integral electronic driver, control inclosed loop flow and pressure; a dedicated algorithm selects which control

    (flow/pressure) is active time by time.

    Digital integral electronic driver (factory preset) and integral pump

    displacement/pressure transducers assure pump-to-pump interchangeability,

    easier set-up and high response dynamics.

    ZA-**

    Ex-proof executions equipped with specific solenoids certified to ATEX

    94/9/CE and IECEX, available with and without integral ex-proof driver andtransducer.

  • 8/21/2019 e Man Ri Ters e 14

    11/96

    1 General

    E-MAN-RI-TERS/E-14 11Driver Operating Manual

    1.3.4 Digital electronic drivers

    Atos electronics include analog or digital drivers both in separate or integral-to-valve format.

    They supply proportional valve solenoid with current to align the valve regulation and the reference signal

    thus obtaining an ideal interface between hydraulic and electronic systems of modern machine and plants.

    Digital electronics add variable plus to

    proportional electrohydraulics:

    better performances: hysteresis, response

    time, linearity

    software setting of hydraulic parameters:

    scale, bias, ramp, non-linearity

    diagnostics and computer assisted

    maintenance

    high immunity to electromagnetic noise

    easy interfacing to fieldbus systems

    1.3.5 Fieldbus systems

    Atos digital electronics allow to integrate hydraulic components into machines equipped with the digital

    communication system commonly known as fieldbus( i.e. CANopen, PROFIBUS DP, etc).

    Up to now the connection and the control of hydraulic valves were mainly done by point-to-point analog

    connections with expensive wiring and starting-up costs.

    Thanks to the fieldbus systems it is possible to interface reference, monitor and diagnostic signals with

    proportional valves by means of cheap 2-wire cables.

    Atos digital electronics is available as standard with Serial communication interface to a notebook or

    desktop PC (driver with PS execution):

    option BC allows integration into CANopen fieldbus systems

    option BP allows integration into PROFIBUS DP fieldbus systems

  • 8/21/2019 e Man Ri Ters e 14

    12/96

    1 General

    12 E-MAN-RI-TERS/E-14Driver Operating Manual

    1.3.6 Axis motion controllers

    Atos digital axis motion controllers are the up to date solution for the motion control in modern machines

    and systems: they can be easily configured and PC programmed to best manage position, speed or force

    of any electrohydraulic axis, in closed-loop by a digital proportional.

    They improve motion performances, simplify the automation architecture and may be interfaced to the

    machine control unit via fieldbus network.

    controller type Z-RI-TEZ Z-ME-KZ Z-BM-HZ1 (HZ2)

    integral axis controller

    including integral driver

    for closed-loop control ofany linear/rotative

    actuator

    Eurocard axis

    controller for flexible

    general purposemotion control of up 2

    synchronized axis

    multiple axis controller

    modular DIN-rail

    assembly with highperformance

    computation capabilities

    valve driver function

    nr. of controlled axis 1 1 1 (2)

    internal programmable cycles simple complete extended

    Graphic programming software

    position control

    synchronism ()

    position transducer interface

    analog - SSI - encoder 1 1 1 (2)

    pressure-force/position control option option option

    pressure transducer interface 1/2 2 1/2 (2/4)

    performance parameters settings

    valve parameter settings factory preset

    communication interfaceserial - CANopen - PROFIBUS DP

    ethernet interface

    digital input/output up to 2 9 (input) / 8 output 12 (24) + modules

    auxiliary analog up to 2 6 (input) / 3 (output) 1 + modules

    A B

    P T

    PV

    PV

    DRIVER

    VS

    A B

    P T

    V1S1

    Z-RICONTROLLER

    A B

    P T

    Z-ME-KZ

    V1

    S1

    VS

    DRIVER DRIVER

    VS

    VS

  • 8/21/2019 e Man Ri Ters e 14

    13/96

    1 General

    E-MAN-RI-TERS/E-14 13Driver Operating Manual

    1.4 About E-SW programming sof tware

    E-SW-** programming software is the entry door to the Atos digital technology whilst E-SW-**/S is an

    extended software version for all Atos electrohydraulics with alternated flow/pressure(force) controls.

    Both are supplied in Dvd format and they can be easily installed on a desktop or notebook.

    The software automatically recognizes the connected valve model and adapts the displayed parameters.

    The graphic interface is organized in pages and levels related to

    different specific functional groups and it allows to:

    simply access all the functional parameters of Atos digital

    proportional valves and drivers

    numerically adapt the factory preset parameters to the

    application requirements

    verify the actual working conditions

    identify and quickly solve fault conditions

    store the customized setting into the valve/driver and into the

    PC

    Different software versions are available depending on the selected driver communication interface:

    E-SW-PS for Serial interface (PS drivers) (E-SW-PS/S for alternated controls)

    E-SW-BC for CANopen interface (BC drivers) (E-SW-BC/S for alternated controls)

    E-SW-BP for PROFIBUS DP interface (BP drivers) (E-SW-BP/S for alternated controls)

    1.4.1 Registration and Access level

    On first supply of E-SW software, it is required to apply for the registration in the Atos Download Area

    (see1.2.2); once registration is completed, the Activation Code and Access Password will be sent by email.

    The software has different available levels of graphical interface, those must be used according to the user

    experience and skill to deal with digital proportionals technology.

    The software remains active for 10 days at basic level1 from the installation date and then it stops until the

    user inputs his password.

    Select the proper password to activate one of the available graphic interface level:

    Level 1: user with low experience in proportional valve settings can handle basic parameters

    Level 2: free access to all standard parameters

    A further access password will be available only upon attending a dedicated training in Atos and upon

    submitting a detailed description of the application requirements [email protected]:Level 3: free access to all the driver parameters to specially customize the valve behavior

    All parameter/page with no Level indication are available at Level1 (see13 for access level selection)

    1.4.2 Dvd contents

    Drivers and fieldbus operating manuals

    Installer of E-SW-** software and E-A-*-USB adapters

    Configuration files for fieldbus masters: CANopen (*.EDS) or PROFIBUS DP (*.GSD)

    DVT Atos Master Catalog of standard electrohydraulic components ( over 300 pages of specific

    information in 7 different languages; it also includes an interactive version of the KT Master Catalog

    including overviews and complete Technical information for an easy and useful consultation of Atos

    production)

    mailto:[email protected]:[email protected]:[email protected]:[email protected]
  • 8/21/2019 e Man Ri Ters e 14

    14/96

    1 General

    14 E-MAN-RI-TERS/E-14Driver Operating Manual

    1.4.3 Installation Manager Desktop

    Insert E-SW-** Dvd into PC Dvd-reader.

    Automatically a dedicated graphic interface will

    start and it will guide user trough the available

    contents:

    To open the graphic interface when auto-start function of Dvd-reader is not active:

    - open Windows Explorer

    - enter Dvd main directory

    - start AtosE-SW.exe program

    For a complete description of these installation procedures, please refer to the relevant softwareinstruction manual QUICKSTART-PS, QUICKSTART-BC or QUICKSTART-BP.

    To install Atos software, the user must have administrator rights on the system.

    Click on the relevant button to start the desired operation:

    RegistrationOn-line register purchased software (or send registration by fax see

    1.4.1).

    E-SW InstallationStarts E-SW software and USB adapters installation (see QUICKSTART-**

    manual for further details)

    DocumentationAccess one of the available valve/driver operating manuals, DVT Atos

    Master Catalog and fieldbus configuration file (only for BC or BP option)

    Contact Us Access the Atos Technical Support and Download Area

  • 8/21/2019 e Man Ri Ters e 14

    15/96

    1 General

    E-MAN-RI-TERS/E-14 15Driver Operating Manual

    1.4.4 Communication USB adapters and Cables

    Proper cables and USB adapter must be used to

    connect the PC software to the specific driver and

    communication protocol (see also G500 technical

    table).

    USB adapters and cables are notdelivered with the software, they must be

    ordered separately.

    E-SW-PS or E-SW-PS/S software for serial communication required communication items:Valve type Driver USB Adapter Cable

    ZO-A open loop without integral driver

    ZA-A ex-proof (only with E-BM-AS-PS)

    E-MI-AS-IR E-A-PS-USB/IR None

    E-BM-AS-PS E-A-PS-USB/DB9 E-C-PS-DB9/RJ45

    ZO-*ES-PS valve integral driver E-RI-*-PS E-A-PS-USB/DB9 E-C-PS-DB9/M12

    ZA-**-PS ex-proof valve integral driver E-RA-*-PS E-A-PS-USB/DB9 E-C-PS-DB9/M8

    E-SW-BC or E-SW-BC/S software for CANopen communication required communication items:Valve type Driver USB Adapter Cable

    ZO-**-BC valve integral driver E-RI-*-BC E-A-BC-USB/DB9E-C-BC-DB9/M12

    E-TRM-BC-DB9/DB9

    ZA-**-BC ex-proof valve integral driver E-RA-*-BC E-A-BC-USB/DB9E-C-BC-DB9/RAE-TRM-BC-DB9/DB9

    For E-SW-BP or E-SW-BP/S software for PROFIBUS DP communication required items:

    Valve type Driver USB Adapter Cable

    ZO-AES-BP valve integral driver E-RI-*-BP E-A-BP-USB/DB9

    E-C-BP-DB9/M12

    E-TRM-BP-DB9/DB9

    ZA-AES-BP ex-proof valve integral driver E-RA-*-BP E-A-BP-USB/DB9E-C-BP-DB9/RAE-TRM-BP-DB9/DB9

    1.4.5 Minimum PC requi rements for E-SW

    Pentium processor 1GHz or equivalent

    Windows XP SP3

    SVGA 16 Bit colour depth in 1024x768 or higher

    512 MB RAM

    Dvd-Reader USB port

    Serial RS232 port (only for PS drivers is not required USB adapter)

    http://en.wikipedia.org/wiki/Registered_trademark_symbolhttp://en.wikipedia.org/wiki/Registered_trademark_symbolhttp://en.wikipedia.org/wiki/Registered_trademark_symbolhttp://en.wikipedia.org/wiki/Registered_trademark_symbol
  • 8/21/2019 e Man Ri Ters e 14

    16/96

    1 General

    16 E-MAN-RI-TERS/E-14Driver Operating Manual

    1.5 Safety prescript ions

    1.5.1 General warning

    all information and instructions reported in this manual and in the supplementary documentation

    (see1.2.1), must always be observed to avoid damage and injury

    during the store/restore operations of the driver permanent memory (see6.1):

    - current to valve solenoid is switched off (operate store/restore with no active valve regulation in the

    system)

    - do not turn off power supply (driver parameter lose may occur)

    drivers faults may compromise safety or change operating conditions, shut down the driverimmediately and notify qualified personnel

    all of the relevant local and plant/machine specific regulations must be always observed

    Hazardous situations may occur whenever the driver:

    is not properly transported and stored

    is altered or modified

    is not installed, commissioned and operated by qualified persons

    is not used properly

    1.5.2 Personnel selection and qualification

    Qualified personnel, in the sense of this document, are:

    persons properly trained and authorized to install, start-up and operate the digital driver in accordance

    with the established safety prescriptions and procedures

    persons who, based on their technical/standards knowledge and training, are able to evaluate their

    tasks, to recognize potential hazards and to carry out the correct safety measures

    1.5.3 Electrical installation warning

    Following recommendations on electrical installation must be always observed:

    Switch-off power supply before connecting or disconnecting the driver Do not use electrical signals of the driver (e.g. reference, feedback and enable signals) for safety

    purpose

    Take care when switch-on/off the driver because it could produce uncontrolled movements of the

    actuators operated by the driver

    Always shield analog signal wirings

    Use low-capacitance cables and do not use intermediate connections

    Do not wire any power cables close to control electronics or command/feedback wirings

    Protect the driver and other control electronics from electromagnetic noises

    Maintain a proper distance from antenna lines, RF devices and radio equipment

  • 8/21/2019 e Man Ri Ters e 14

    17/96

    1 General

    E-MAN-RI-TERS/E-14 17Driver Operating Manual

    1.5.4 Electromagnetic compatibil ity

    Atos electronic drivers and proportional valves have been tested according to EMC directives:

    EN 61000-6-4 (Emission) and EN 61000-6-2 (Immunity)

    The electromagnetic compatibility of the driver is valid only if wirings are realized according to therecommended electric connections (refer also to sections4 and5).

    Electromagnetic fields of machine environment may be different from test conditions: always verifythe device functionality once installed.

    1.5.5 Electrostatic discharge protection

    Electrostatic discharge (ESD) can damage electronic components of the driver; to prevent damage observe

    the following recommendations:

    Discharge static voltage from your body before

    handling the valve/driver

    Work in a safe environment (do not use any device or

    surface that can generate or hold static charge)

    Avoid to touch any exposed pins or electronic

    components

    1.5.6 Repair and Troubleshooting

    Repair and troubleshooting requires specialized skills: these activities must be performed only by Atos or

    authorized service centers.

    Please contact the Technical Sales Support of Atos Electronic Division ([email protected])to receive

    indications on how to proceed (please always indicate the driver code and serial number printed on drivers

    label).

    mailto:[email protected]:[email protected]:[email protected]:[email protected]
  • 8/21/2019 e Man Ri Ters e 14

    18/96

    2 About E-RI-TER(AER)S drivers

    18 E-MAN-RI-TERS/E-14Driver Operating Manual

    2 About E-RI-TER(AER)S drivers

    These integral digital drivers

    supply and control, in closedloop, the regulated pressure of

    direct and pilot operated

    proportional valves according to

    the electronic reference input

    signal.

    E-RI-TERS execution operates

    direct and pilot operated

    relief/reducing control valves

    with one integral pressure

    transducer.

    E-RI-AERS execution operates

    direct and pilot operated

    relief/reducing control valves

    with one remote pressure

    transducer.

    The dynamic response of pressure control can be adapted to different systems characteristics, by setting

    the internal PID parameters.

    Digital communication interface allows to set the driver parameters with the Atos E-SW-** software or, for

    -BC and -BP fieldbus execution, directly by the machine control unit.

    2.1 Model Code

  • 8/21/2019 e Man Ri Ters e 14

    19/96

    2 About E-RI-TER(AER)S drivers

    E-MAN-RI-TERS/E-14 19Driver Operating Manual

    2.2 Electrical Features

    Functional parameters are factory preset for best performances

    Standard 7 pin main connector e for power supply, analog input reference and monitor signals

    /Z option 12 pin main connector for additional double power supply, enable and fault signals

    /I option for current reference and monitor signals

    M8 - 4 pin connector for remote pressure transducer (only AERS execution)

    /C option for current interface with remote pressure transducer

    M12 - 5 pin connector for communication interface, at choice: serial -PS or fieldbus -BC and BP

    IP67 protection degree

    CE mark to EMC directive

  • 8/21/2019 e Man Ri Ters e 14

    20/96

    3 Getting started

    20 E-MAN-RI-TERS/E-14Driver Operating Manual

    3 Getting started

    This section contains a brief review of the main operations required to install and configure the drivers:

    3.1 Programming tools installation

    Registration (only for first s upply)

    Register the E-SW-** programming software onwww.download.atos.comto obtain the password for the

    software activation; software can be operated at access level 1 (see1.4.1)without activation code for

    10 days from the installation date and then it stops working until the user inputs the activation code.

    Cables, Adapter and Terminator

    Verify the proper cables, USB adapter and terminator to be used: they depend on driver to be

    programmed and on PC characteristics (see1.4.4).

    Software installation

    Install the E-SW-** software and insert the activation code received upon registration.

    For a complete description of these installation procedures, please refer to the relevant software

    instruction manual QUICKSTART-PS, QUICKSTART-BC or QUICKSTART-BP

    3.2 Driver installation

    Wire the driver to main control unit (see5.2)

    Wire the driver to the required remote pressure(force) transducers (see5.3) Apply power supply to the driver

    3.3 Driver configuration

    Connect the required cables and adapter to the driver

    Start E-SW software and activate the communication with the driver (see6)

    Check and configure the driver input reference range (see9.1 and11.1)

    Check and configure the driver remote transducer range (only AERS) (see9.1 and11.2)

    Apply hydraulic power and complete the driver setting whenever required:Bias and scale (see11.3 and11.4)

    Ramps (see11.5)

    Linearization (see11.6)

    PID parameters (see11.7)

    Save the parameters changes into the driver permanent memory (see9.3.3)

    To speed up the configuration process you can use parameter setting previously saved into thepersonal computer (see12)

    http://www.download.atos.com/http://www.download.atos.com/http://www.download.atos.com/http://www.download.atos.com/
  • 8/21/2019 e Man Ri Ters e 14

    21/96

    4 Valve Installation

    E-MAN-RI-TERS/E-14 21Driver Operating Manual

    4 Valve Installation

    4.1 General prescriptions

    The following instructions are general indications and procedures for the correct installation andcommissioning of proportional valves in modern electrohydraulic systems.

    Hydraulic fluid

    The hydraulic fluid is used to transmit power and to provide components lubrication in hydraulic systems.

    To extend system reliability select high quality fluid with high viscosity index, with antifoaming and

    antioxidant additives according to the international standards: DIN 51524 and 51535

    Oil viscosity rating depends on the installed pumps/motors characteristics and on the working temperature.

    Use lower viscosities with low system pressure to limit pressure drops and higher viscosities for high

    system pressure to limit internal leakage:

    High viscosities can cause air-emulsion in the oil and therefore cavitation and noise problems in

    continuous operation; start-up problems may also at ambient temperature with pumps that require

    viscosities higher than 290 365 cSt.

    Low viscosities decreased system efficiency and affect the dynamic lubrication.

    HLP mineral oil according to DIN 51524 - part 2 are recommended (viscosity range: 15 100 mm2/sec at

    40C).

    Oil must be periodically controlled and normally changed every 2000 hours (see Circuit cleaning, filling and

    flushing)

    Fluid temperature cond itioning

    A high-performance system must be properly conditioned to maintain the fluid temperature within specific

    range (generically between 40 and 50C) thus obtaining a constant fluid viscosity during the operation.

    The machine working cycle should start once the recommended temperature has been reached.

    Fluid temperatures higher that 60C, require components with Viton seals (option /PE).

    Fluid temperature must not exceed 80C.

    Fluid filtration

    An efficient fluid filtration prevents breakdowns of the system by protecting the components from solid

    particle contamination that may affect hydraulic fluid. Cleanliness class must be equal or better than ISO

    18/15, NAS 1632 class 9, by fitting in line filters of 10m and 10=75.In line pressure filters must be mounted, if possible, immediately before the proportional valve and should

    be of high pressure type; clogging electrical indicator without by-pass valve are recommended.

    Additional warnings have to be considered: make sure that the filters are properly sized to ensure

    efficiency; one of the main sources of contamination is air exchange into the tank: proper breather filters on

    the power unit tank have to be always provided; filter the fluid when filling the power unit tank (new fluids

    are always contaminated) through filtration Group GL-15 or similar (see technical table S150 on

    www.scoda.it).

    During system working operation the frequent cleaning or replacing of filters cartridges are required.

    Circuit cleaning, filling and flushingPower unit tank has to be accurately cleaned before filling it by removing all the contaminants and any

    extraneous object; piping has to be cold bended and pickled.

    http://www.scoda.it/http://www.scoda.it/http://www.scoda.it/
  • 8/21/2019 e Man Ri Ters e 14

    22/96

    4 Valve Installation

    22 E-MAN-RI-TERS/E-14Driver Operating Manual

    Once assembled, an accurate washing of the whole circuit (flushing) has to be performed to eliminate the

    contaminants:

    replace proportional valves with appropriate by-pass plates or with on-off valves

    by-pass the actuator user ports by means flexible pipes

    shutoff the accumulators from the other parts of the circuit

    replace filters cartridge after flushing procedures

    Hydraulic connections

    The flexible hoses on pressure line must be shielded and secured by using proper restrain devices to

    prevent damages of machine, system and injuries to the operator.

    The proportional valve must be installed as close as possible to the actuator to ensure the maximum

    stiffness of the circuit and the best dynamic performances.

    Hydraulic return and drains lines

    Return lines must be connected to the tank with low counterpressures in order to not affect the components

    regulation: return lines from proportional valve to tank must be properly sized to limit counterpressures tomax 5 bar.

    High flow regulation may require drain connections to realize separate piping to the tank and to maintain

    proper components functionality: external drain connection port is available as standard on servocylinders

    rod side, piloted directional valves and pressure reducing valves (use option /Y valves when drain port is

    not available as standard).

    Pilot ing pressures

    Standard configuration of piloted valves is with piloting line internally connected to line pressure.

    use option /E valve with external pilot connection when line pressure is less than 30 bar

    For directional control valve or throttle cartridge: use option /G valve with integral pressure reducing valve when line pressure is greater than 100 bar

    Air bleeds

    The air in the hydraulic circuits affects the hydraulic stiffness and it causes malfunctioning: air bleeds are

    provided for both proportional valves and servocylinders (cylinder rod side); in addition proper air bleed

    valves should be also installed in the hydraulic system points where the air could remains trapped.

    Additional warn ings at fir st start -up or af ter maintenance of the system

    Unscrew all the air bleeds to allow the complete removal of air

    Untight piping connections

    Use a check valve on the main return line to tank maintain to avoid the self emptying of the pipes

    following a long service stop

    4.2 Mounting

    Once removed valve packaging take care to protect valve port, connectors and cables

    Do not pull valve integral transducer cables

    Removed valve ports plastic protection before mounting the valve into the system

    Do not touch any electric components when handling the valve

    Tighten valves to the manifold without exceeding the recommended max torque (see tab.T242-1)

  • 8/21/2019 e Man Ri Ters e 14

    23/96

    5 Driver Electrical connections

    E-MAN-RI-TERS/E-14 23Driver Operating Manual

    5 Driver Electrical connections

    5.1 General prescript ions

    Switch-off power supply before any wirings operation

    During the system start-up, check the immunity of the reference signals from interferences and electrical

    noise

    Use recommended cable size: at least 1 mm2

    for power supply and 0.14 mm2for other signals

    It is recommended to use current signals options for distance longer than 20m (/I option for reference/

    and monitor signals, and /C option for remote transducer signal)

    Cable shielding and earthing

    Use Shielded wirings to avoid electromagnetic noise: it is an essential part of the EMC protection from thenoises that could otherwise bring disturbance through the signal and power supply connections.

    To avoid any interference, the driver cables must be separated from system power cables (connected to

    transformers, electrical motors, drivers, etc.) and must be correctly shielded (see below scheme):

    Connect cable shield at PLC/machine side and leave the other end (driver side) open to prevent ground

    loops

    If possible, connect shields to a protected earth (a noise-free connection with a different path from

    safety earth and power supply ground); it is just designed to connect command signals ground, cables

    shields and all other noise sensitive devices

    If protected earthis not available, use the power supply ground

    Verify that all the ground/earth points are equipotential otherwise position and dimension of the

    connections must be checked

    Earth connection of the drivers is available on the main connector; take care to the correct earthing also

    the valve

    In case of high noise levels, use additional shields and filters to allow the correct working of the

    electronic driver

  • 8/21/2019 e Man Ri Ters e 14

    24/96

    5 Driver Electrical connections

    24 E-MAN-RI-TERS/E-14Driver Operating Manual

    5.2 Main connection

    Main connector is the driver interface to the machine control unit: wire to it the driver power supply and the

    input/output signals (analog or on-off) for reference and diagnostic functions.

    Standard 7pin Main Connector

    Pin SIGNAL TECHNICAL SPECIFICATIONS NOTES

    A V+ Power supply 24 VDC for solenoid power stage Input - power supply

    B V0 Power supply 0 VDC for solenoid power stage Gnd - power supply

    C AGND Ground : signal zero for analog reference and monitor signals Input - on/off signal

    D INPUT +Pressure reference analog input: 10 VDC maximum range (420 mA for /I option)differential INPUT + and INPUT -

    Input - analog signal

    E INPUT -

    F MONITOR Pressure monitor analog output: 10 VDCmaximum range (4 20 mA for /I option) Output - analog signal

    G EARTH Internally connected to driver housing

    /Z opt ion 12pin Main Connector

    Pin SIGNAL TECHNICAL SPECIFICATIONS NOTES

    1 V+ Power supply 24 VDC for solenoid power stage Input - power supply2 V0 Power supply 0 VDC for solenoid power stage Gnd - power supply

    3 ENABLE Enable (24 VDC) or disable (0 VDC) the driver Input - on/off signal

    4 INPUT +Pressure reference analog input: 10 VDCmaximum range (4 20 mA for /I option)common mode INPUT + referred to AGND

    Input - analog signal

    5 AGND Ground : signal zero for analog reference and monitor signals Gnd - analog signal

    6 MONITOR Pressure monitor analog output: 10 VDCmaximum range (4 20 mA for /I option) Output - analog signal

    7 NC Do not connect -

    8 NC Do not connect -

    9 VL+ Power supply 24 VDC for drivers digital circuits Input - power supply

    10 VL0 Power supply 0 VDC for drivers digital circuits Gnd - power supply

    11 FAULT Driver status output: Fault (0 VDC) or normal working (24 VDC) Output - on/off signal

    PE EARTH Internally connected to driver housing

  • 8/21/2019 e Man Ri Ters e 14

    25/96

    5 Driver Electrical connections

    E-MAN-RI-TERS/E-14 25Driver Operating Manual

    5.2.1 Power supply (pin A,B - pin 1,2)

    The power supply +24 VDC(maximum range 20 32 VDC) must be appropriately stabilized or rectified and

    filtered (maximum ripple 10% VPP) and must grant at least 50W for each connected driver:

    apply at least a 10000 F/40 V capacitance near the driver in case of single phase rectifiers

    apply at least a 4700 F/40 V capacitance near the driver in case of three phase rectifiers

    2,5A safety fuse is required in series to each driver power supply.

    A minimum time of 270 to 590 ms has to be considered between the driver energizing with the 24VDCpower supply and when the valve is ready to operate. During this time the current to the valve

    coils is switched to zero.

    5.2.2 Reference input signal (pin D,E - pin 4,5)

    The driver is designed to receive one analog reference input (pin D,E differential mode input); the reference

    is referred to the common mode signal zero (pin 5).

    The inputs range and polarity are software selectable within the 10 VDCmaximum range; default setting is 0 10 VDC.

    Option /I

    The reference input signal is software selectable within 20 mA maximum range; default range is

    4 20 mA and allows cable break detection (see9 and15.3).

    Option /Z

    The reference input signal is available in common mode (pin 4 referred to pin 5) instead of the standard

    differential mode

    Do not use power supply ground (V0) as reference for input signals: the absorbed current of thedrivers power stage can affect analog signal quality.

    Small values of input range settings can be more affected by electrical noise.

    Drivers with fieldbus interface (-BC or -BP) can be software set to receive reference values directlyby the machine control unit (fieldbus master).

    In this case the analog reference input signals can be used for start-up and maintenance operations;

    if not used always connect references to AGND (pin5).

    5.2.3 Monitor output signal (pin F,C - pin 6,5)

    The driver generates one analog output signal to monitor the actual pressure measured on the system by

    the transducer integral to valve (TERS execution) or remote to valve (AERS execution); the monitor output

    signal (pin F/6 referred to pin C/5) can be software set to show other signals available in the driver (e.g.

    analog or fieldbus reference).

    The output polarity is software selectable within 10 VDCmaximum range (see11.8).Option /I

    The maximum range of monitor output signal is 4 20 mA

    Do not use power supply ground (V0) as reference for input signals: the absorbed current of thedrivers power stage can affect analog signal quality.

    5.2.4 Enable input signal (pin 3,2) - only for /Z opt ion

    To enable the driver, supply a +24 VDCon pin 3 referred to pin 2: when the Enable signal is set to zero the

    valve functioning is disabled but the driver current output stage is still active (see15.4.2, to verify this

    condition with the E-SW software). This condition is useful to maintain active the serial/fieldbus

    communication and the other driver functions when the hydraulic regulation of the valve must be disabled.

  • 8/21/2019 e Man Ri Ters e 14

    26/96

    5 Driver Electrical connections

    26 E-MAN-RI-TERS/E-14Driver Operating Manual

    5.2.5 Fault output (pin 11, 2) - only for /Z opt ion

    Fault output signal indicates fault conditions of the driver (solenoid short circuits/not connected, reference

    signal cable broken for 4 20 mA input, valve pressure transducers cable broken, etc; fault presence

    corresponds to 0 VDC, normal working corresponds to 24 VDC(pin 11 referred to pin2); see15

    Fault status is not affected by the status of the Enable input signal.

    5.2.6 Double Power (pin 9, 10) - only for /Z option

    Separate power supply for the solenoid and for the digital electronic circuits (pin 9,10).

    Cutting solenoid power supply (pin 1,2) allows to interrupt the valve functioning but keeping energized the

    digital electronics thus avoiding fault conditions of the machine fieldbus controller.

    Pin 2 and 10 (zero Volt) are connected together inside the electronics; see 9.1 for power suppliesrequirements.

    5.3 Remote transducer connection (AERS drivers)

    Remote pressure transducer installed into the systems must be directly connected to AERS driver using

    the dedicated M8 connector.

    The input range and polarity are software selectable within the 10 VDCmaximum range; default setting is

    0 +10 VDC(see11.2).

    Option /C

    The transducer input range is software selectable within 20 mA maximum range; default range is

    4 20 mA and allows cable break detection (see15.3).

    Proper selection and installation of the remote transducer is essential to obtain the bestperformances from pressure control system.

    Small values of input range settings can be more affected by electrical noise.

    Refer to technical table G465 for Atos E-ATR-7 pressure transducer characteristics.

    PIN standard vers ion /C opt ion (Ri = 316 )

    1 TR1 remote transducer signal (0 +10 VDC) TR1 remote transducer signal (4 20 mA)

    2 AGND signal zero for power supply and signal NC reserved (do not connect)

    3 VT remote transducer power supply +24 VDC VT remote transducer power supply +24 VDC

    4 TR2 2nd remote transducer (0 +10 VDC) - only for /SF option NC reserved (do not connect)

    See table G465 for the pressure transducer characteristics and connections

  • 8/21/2019 e Man Ri Ters e 14

    27/96

    5 Driver Electrical connections

    E-MAN-RI-TERS/E-14 27Driver Operating Manual

    5.4 Communication connection

    Proper communication cables and USB adapter (see1.4.4)must be used to connect the driver to the PC

    where E-SW software is installed (see QUICKSTART-** manuals for installation details).

    5.4.1 Fieldbus communication connector

    When the driver is connected to the main machine fieldbus network (see 1.3.5), always verify proper

    wirings as described by the relevant standardization (see E-MAN-BC or E-MAN-BP manuals for further

    details).

    No master device must be active in a PROFIBUS DP fieldbus when using E-SW software tocommunicated with connected valve/drivers.

    5.4.2 Hardware Node assignment

    Driver node, unique identification in the fieldbus, can be set manually using a dip switch.

    Remove the driver rear cover positioned on the programming connector side and set the node number

    using the dip switch (binary coded).

    Switch Switch on value Default

    8ON = software setting

    OFF = dip switch addressingON

    7 26= 64 ON

    6 25= 32

    OFF

    5 24= 16

    4 23= 8

    3 22= 4

    2 21= 2

    1 2 = 1

    As default (switch 8 = on) the driver use the node setting stored into the driver permanent memory (tomodify see11.11,E-MAN-BC / CANopen manual or E-MAN-BP / PROFIBUS DP manual)

    For BC use node settings between 1 and 127

    For BP use node settings between 1 and 125 (avoid node 1 that is normally used by the master)

  • 8/21/2019 e Man Ri Ters e 14

    28/96

    6 Driver parameters operation

    28 E-MAN-RI-TERS/E-14Driver Operating Manual

    6 Driver parameters operation

    To operate correctly E-RI-TER(AER)S drivers with the E-SW-** programming software you must always

    consider how the driver and the software parameters are managed:

    6.1 Parameters operation scheme

    Driver Store operations (see6.2.3):

    1) Store User Parameters

    Driver Restore operations (see6.2.4):

    2) Restore User Parameters

    3) Restore Preset Parameters

    Passing from OFF-LINE to ON-LINE (see6.3.1):

    4) Upload Parameters5) Download Parameters

    PC Setting File operations (see12):

    6) Save setting file

    7) Load setting file

    6.2 Driver parameters

    Two types of parameters are present into the driver (permanent and non-permanent) and store/restore

    operations allow to define how they must be used:

    6.2.1 Actual Parameters (non-permanent memory)

    The driver functionality and regulation depend on its Actual Parameters that:

    are automatically loaded at each power-on from the permanent memory of the driver

    are lost when the driver is turned-off (non-permanent parameters)

    can be displayed and modified using the E-SW software

    6.2.2 Driver Preset/User/Emergency Parameters (permanent memory)

    When the driver is turned-on, one of the following parameter sets is copied from this section to the Actual

    Parameters (non-permanent memory) to define the driver functionalities:

    PresetThis parameters set allows to start-up the driver with the factory setting

    defined by Atos

    User

    This parameters set allows to start-up of the driver with the customized

    values defined and stored by the user using E-SW software (as default

    User Parameters and Preset Parameters are the same)

    EmergencyThis parameters set allow to start-up the driver when Preset Parameters

    and User Parameters contain corrupted data

  • 8/21/2019 e Man Ri Ters e 14

    29/96

    6 Driver parameters operation

    E-MAN-RI-TERS/E-14 29Driver Operating Manual

    If permanent memory is corrupted, the driver try to load alternative set:

    Preset are loaded automatically in case of invalid User parameters

    Emergency are loaded automatically in case of invalid Preset parameters

    When invalid parameters are detected at power-on or driver restart (see9.3.4)the driver goes into

    Fault condition; please contact Atos Technical Sales [email protected].

    6.2.3 Store Driver Parameters

    Store User This operation allows to store the driver Actual Parameters (non-

    permanent) into the User Parameters (permanent) set;

    At power-on the drive will automatically load the User Parameter settings

    During the store/restore operations of the driver permanent memory:- power supply must be not turned off (driver parameter lose may occur) and the driver must be

    disabled or in hydraulic null regulation

    - current to valve solenoid is switched off, is best to operate store/restore with no active valve

    regulation in the system

    6.2.4 Restore Driv er Parameters

    Two operations are available to select which parameters set has to be loaded into Actual parameters at

    the next driver power-on:

    Restore Preset

    Preset Parameters will be load at next driver power-on Restore User User Parameters will be load at next driver power-on

    During the restoring operations of the driver permanent memory: power supply must be not turned-off(driver parameter lose may occur) and the driver must be disabled or in null hydraulic regulation

    6.3 E-SW parameters

    6.3.1 E-SW Actual Parameters (non-permanent memory)

    The Actual Parameters of E-SW programming software is the set of parameters displayed in the software

    graphic interface.

    The Actual Parameters values, depend on the communication status between the software and the driver:

    ON-LINE

    (communication active)

    Actual Parameters of both software and driver are linked (every

    change in the software is applied in the driver and vice versa)

    OFF-LINE

    (communication not active)Actual Parameters of the software are not linked to the driver (theycan be changed but this is not applied to the driver)

    mailto:[email protected]:[email protected]:[email protected]:[email protected]
  • 8/21/2019 e Man Ri Ters e 14

    30/96

    6 Driver parameters operation

    30 E-MAN-RI-TERS/E-14Driver Operating Manual

    When passing from off-line to on-line mode, it is possible to select which Actual Parameters have to be

    maintained between the software and the driver:

    Upload Actual Parameters of the driver are maintained and are copied into

    the software

    Download Actual Parameters of the software are maintained and are copied

    into the driver

    To perform Download operation the Actual Parameters of the driver and the software must becompatible: if Driver Code parameter (see10.2) is not the same a message will display an error

    condition.

    During Download operation the valve/driver goes into a Disable state; after it check if thedownloaded parameter are valid. If the parameter are invalid the driver remain in Disable state and

    return Invalid Download error (see9.2.3).

    6.3.2 E-SW Setting Files (permanent memory)

    E-SW and driver Actual Parameters can be stored or restored from the PC hard-disk as a Setting File

    (see12): in any time it will be possible to restore these data into the Actual Parameter of the software and

    of the driver.

    Setting File can be used efficiently as a starting point when executing repetitive installation of thesame driver.

  • 8/21/2019 e Man Ri Ters e 14

    31/96

    7 Software Graphic Interface

    E-MAN-RI-TERS/E-14 31Driver Operating Manual

    7 Software Graphic Interface

    E-SW-** software allows to verify, modify and store/restore the parameters of E-RI-TER(AER)S drivers.

    The software can work directly with the parameters of a connected driver (ON-Line mode) or with

    parameters stored in the PC (OFF-Line mode).

    The Main window of the software, displayed at start-up, allows to handle all basic settings and diagnostic

    operations on the driver, and allow to open the Extended Diagnostic window (see 15)for a more complete

    analysis of the driver working conditions.

    To open or switch between different windows, press the relevant button,

    always available in the upper-right corner of each window.

    To open the online help, press F1 or the relevant button, always available

    in the upper-left corner of each window.

    7.1 Main window

    The Main window allows to completely operate Atos valves and drivers by :

    simply access and numerically set all the functional parameters

    verify the actual working conditions

    identify and quickly solve fault conditions

    adapt the factory preset parameters to the application requirements

    store the customized setting into the valve

    archive the customized setting into the PC

    Access but ton

    Refer to the following sections for detailed description on the three areas in which this window is divided:

    Communication area, Diagnostic area and Menu area.

    The windows graphic interface is automatically adapted at start-up to the connected valve/drivermodel and firmware version (see 17), to the selected access level (see also 13.1) and to the selected

    language: actual setting of the graphic interface is always displayed in the windows title .

  • 8/21/2019 e Man Ri Ters e 14

    32/96

    7 Software Graphic Interface

    32 E-MAN-RI-TERS/E-14Driver Operating Manual

    7.2 Extended Diagnostic window

    This window allows to verify detailed information on the actual working condition of

    the valve/driver and to completely operate with the parameters stored into the driver -

    see15 for detailed description.

    Access but ton

    7.3 Oscilloscope window

    This window allows to verify the time dependant behavior of the valve/driver; it isequivalent to a standard oscilloscope - see16 for detailed description.

    Oscilloscope function is available for driver with Serial (PS) or PROFIBUS(BP) communication interface

    Access but ton

  • 8/21/2019 e Man Ri Ters e 14

    33/96

    7 Software Graphic Interface

    E-MAN-RI-TERS/E-14 33Driver Operating Manual

    7.4 Error parameters

    The Atos software implements an errors detection system in order to identify missing parameters or

    eventual communication errors.

    7.4.1 Miss ing parameters (OFF-LINE mode)

    If corrupted file or an incomplete settings file (see 12.2) with missing

    parameters is loaded, the indicator shows a missing parameter value.

    Write the missing value into the indicator and save the Setting File on the PC hard disk.

    The symbol is displayed for missing parameters errors.

    If a Setting File missing parameter values is downloaded into the driver, the missing parameter it willoverwrite by the values present into the driver.

    7.4.2 Communication errors (ON-LINE mode)

    The indicator shows a communication error.

    Check the communication parameters (see8.2).

  • 8/21/2019 e Man Ri Ters e 14

    34/96

    8 Main Window Communication area

    34 E-MAN-RI-TERS/E-14Driver Operating Manual

    8 Main Window Communication area

    In the bottom area of the Main window, it is possible to verify and change the status of communication

    between the E-SW-** software and the E-RI-TER(AER)S-** drivers (see13.2).

    8.1 ON-LINE/OFF-LINE mode

    The indicator allows the user to verify the actual status of the communication between the E-SW

    software and the connected driver (see6):

    ON-LINE

    (communication active)

    Actual Parameters of both software and driver are linked (every

    change in the software is applied in the driver and vice versa)

    In this status the OFF-LINE button allows to disconnect the driver

    from E-SW and to pass in OFF-LINE mode.

    At start-up the E-SW software always tries to pass in ON-LINEmode if a valve/driver is properly connected.

    Always use this communication mode to completely operate

    and verify the connected driver.

    OFF-LINE

    (communication not active)

    Actual Parameters of the software are not linked to the driver (they can

    be changed but this is not applied to the driver)

    In this status theON-LINE button allows to connect the driver from

    E-SW and to switch in ON-LINE mode.

  • 8/21/2019 e Man Ri Ters e 14

    35/96

    8 Main Window Communication area

    E-MAN-RI-TERS/E-14 35Driver Operating Manual

    Switching from OFF-LINE mode to ON-LINE modea message will ask which parameters must bemaintained: the software or driver parameters value.

    Press Download button to pass in ON-LINE mode

    maintaining as valid the software Actual

    parameters.

    Press Upload button to pass in ON-LINE mode

    maintaining as valid the driver Actual parameters.

    ON-LINE, OFF-LINE and Downloadbuttons can be used to copy the same parameters into multiplepump/drivers, for example:

    Connect the pump to be copied and start the E-SW software (ON-LINE mode is

    automatically achieved)

    Press OFF-LINE button and connect communication cable to the second pump

    Press ON-LINE and select Download button

    8.2 Communication Error

    The indicator allows the user to verify possible error in the communication with the valve/driver.

    Displayed Error Cause/Troubleshoot ing

    Selected communication interface

    not available!

    Verify the correct connection and/or installation of the required

    USB adapter (see QUICKSTART-** instruction manual)

    Timeout - the driver not respond! Verify the correct power supply to the driver (see5.2.1)and the

    correct communication wirings (see QUICKSTART-** instructionmanual)

    While switching from OFF-LINE mode to ON-LINE, verify the

    correct configuration for the program communication (see13.2)

    While ON-LINE mode, specific environment condition may not

    allow the selected communication speed, try with lower speed

    (see13.2)

    Parameter value not allowed! Parameter value is not accepted due to incompatibility with the

    actual setting of other valve/driver parameters (try different set)

    Wrong Data from the driver (CRC)!

    Wrong Data to the driver (CRC)!

    Verify the correct communication wirings (see QUICKSTART-**instruction manual) and try with lower speed (see13.2)

    Selected Node is not Atos!

    Selected Node not exists!

    Verify the actual setting of the fieldbus node ( this error is

    available only for BP (PROFIBUS DP) communication

    Only the last communication is displayed, double-click on the indicator to view the list of all occurredmessages

    8.3 Communication Settings

    The indicator allows the user to verify the actual communication setting of the E-SW program (see13.2for specific description of these settings).

  • 8/21/2019 e Man Ri Ters e 14

    36/96

    9 Main Window Diagnostic area

    36 E-MAN-RI-TERS/E-14Driver Operating Manual

    9 Main Window Diagnost ic area

    In the upper area of the Main window, it is

    possible to verify actual working conditions (driver

    status, alarms, reference and actual signals, etc)thus simplifying tuning and maintenance

    operations.

    It is always possible to switch on/off the

    visualization of this area using the dedicated

    button available in the upper-right corner of the

    Main window:

    Show Diagnostic area

    Hide Diagnostic area

    In ON-LINE mode displayed information are updated automatically.

    In OFF-LINE mode displayed information remain frozen to the last status before disconnection

    9.1 Working signals

    This part of the Diagnostic area is dedicated to:

    set and/or verify the reference signal used to control the proportional valve

    verify the valve response to the commands (Feedback and PID out signals)

    9.1.1 Reference Type

    The control allows the user to select the source for the reference signal:

    External Analog input signal (default selection) is used as reference signal; see11.1 to

    modify the default input signal range

    Internal Reference signal value is directly set by E-SW software (see 9.1.2); use this

    setting to simply tuning or maintenance operations, and to evaluate the effect of

    noise level on the analog reference signal.

    Fieldbus Reference signal value is set by machine central unit using the fieldbus

    communication (this selection is available only for BC and BP driver executions)

  • 8/21/2019 e Man Ri Ters e 14

    37/96

    9 Main Window Diagnostic area

    E-MAN-RI-TERS/E-14 37Driver Operating Manual

    9.1.2 Reference Actual

    The indicator allows the user to read the value of the reference signal

    that actually selected (see9.1.1):Min -100%

    Max 100%

    External: the numerical value is in % of the maximum valve regulation and corresponds to the external

    analog reference signal as defined by the range setting of the analog input signal (see 11.1)

    Internal: the indicator becomes a control and allows to set the desired % of valve regulation

    Whenever the driver power supply is switched off, the internal reference value is reset to 0%

    Fieldbus: the numerical value is in % of the maximum valve regulation

    9.1.3 Reference Demanded

    The indicator allows the user to verify the % of the demanded valve

    regulation once the actual reference signal has been elaborated by

    Bias/Scale (see 11.3 and 11.4), Ramps (see 11.5) and Linearization

    functions (see11.6).

    Min -100%

    Max 100%

    9.1.4 Feedback

    The indicator allows the user to verify the % of the real valve

    regulation as readout by the relevant integral/remote transducer.Min 0%

    Max 200%

    Feedback values exceeding +100% can be displayed during dynamic conditions; in static workingconditions, reference and feedback must correspond

    9.1.5 PID Out

    This indicator allows the user to verify the % output of the closed loop

    control action.

    Min -200%

    Max 200%

    Control actions that reach the maximum/minimum output limits (see11.7), are possible indication ofanomalous working conditions (see9.2.1).

  • 8/21/2019 e Man Ri Ters e 14

    38/96

    9 Main Window Diagnostic area

    38 E-MAN-RI-TERS/E-14Driver Operating Manual

    9.2 Driver status and warnings

    This part of the Diagnostic area shows the actual valve/driver working conditions:

    9.2.1 Driver status

    The indicator displays in which status the driver is controlling the valve:

    Active the driver is working normally

    Disable the driver is disabled and no current is supplied to the solenoid.

    Use enable pin (see 5.2.4)or fieldbus communication (see11.12) to

    enable/disable the driver

    Fault The driver is disabled due to the presence of fault conditions; no current is

    supplied to the solenoid

    To identify and solve the fault conditions use the Last Error description (see 9.2.1) or the moredetailed information of the Extended Diagnostic window (see15).

    9.2.2 Alarm

    The indicator allows the user to verify the presence of alarm conditions that has to be verified.

    Alarm conditions always correspond also to the presence of a 0V on the digital output fault pin of the

    main connector (see5.2.5)To identify and solve the alarm conditions use the Last Error description or the more detailedinformation of the Extended Diagnostic window (see15).

    As default the driver automatically returns to Active state when no error is present (see15.3.1 Fault

    Acknowledge)

  • 8/21/2019 e Man Ri Ters e 14

    39/96

    9 Main Window Diagnostic area

    E-MAN-RI-TERS/E-14 39Driver Operating Manual

    9.2.3 Last Error

    The indicator allows the user to identify which is the last fault/alarm condition that has occurred and

    indicator to verify if the error is still present.

    In case of multiple fault/alarm conditions, the worst condition is displayed first (following list -descending order); when driver is restarted (see9.3.4)or power off/on Last Error is set to No Error.

    Error reactions within brackets are software settable (see11.9)

    Error React ion Cause/Troubleshoot ing

    Invalid parameters Fault status + Alarm Requested parameters are not valid (see9.3)

    Invalid Download Fault status + Alarm Downloaded parameter are not valid (see 6.3)

    restart the driver to reset fault, without making

    any store operation. If a store operation has

    been perform, use restore preset function.Electronics High Temp (Fault status) + Alarm Internal temperature too high, verify correct

    installation and working conditions (ambient

    and fluid temperature)

    Pressure reference Fault status + Alarm Pressure(Force) analog input signal exceeds

    admissible range: verify the correct wirings and

    voltage/current signal (see 11.1 to verify

    admissible range settings high/low limits)

    Pressure transducer Fault status + Alarm Pressure(Force) signal from remote

    transducers exceeds admissible range: verify

    the correct wirings and voltage/current signal(see11.2 to verify admissible range settings

    high/low limits)

    Pressure control (Fault status) + (Alarm) Monitoring function of pressure(force) closed

    loop has detected anomalous conditions (see

    15.3): verify pressure regulation settings,

    remote transducer offset (see11.2) or P and T

    line pressure values

    Electronics Low Temp (Fault status) + Alarm Internal temperature too low, verify correct

    installation and working conditions (ambient

    temperature)

  • 8/21/2019 e Man Ri Ters e 14

    40/96

    9 Main Window Diagnostic area

    40 E-MAN-RI-TERS/E-14Driver Operating Manual

    9.3 Driver Memories

    This part of the Diagnostic area allow the user to verify/set which of the permanent parameter set stored

    into the driver memory has been loaded at power-on into driver Actual Parameters (see6).

    9.3.1 Requested

    The indicator allows the user to verify which parameter set will be loaded at next power-on: use

    store/restore operations (see9.3.3 and15.5.3)to change these settings.

    9.3.2 Loaded

    The indicator allows the user to verify which parameter set has been loaded at last power-on.

    If Requested and Loaded indicators contain different value after power-on, Last error displaysInvalid parameters message and the driver is disabled (see9.2.3):

    [Loaded = Preset and Requested = User] Atos factory parameters have been loaded andUser contains invalid data.

    [Loaded = Emergency and Requested = User or Preset] both driver parameters contain

    invalid parameters, please contact Atos service for troubleshooting

    9.3.3 Store User Parameters

    This button allows the user to store the driver Actual parameters into the User parameters

    permanent memory (see6.1).

    During parameters storing operations, power supply to the valve solenoid is switched-off: do not usethis function during system normal working.

    Never switch-off the drivers power supply during storing operations: permanent parameters storedinto the driver may result invalid!

    9.3.4 Driv er Restart

    This button allows the user to obtain the same effect of switching off/on the driver power supply: digital

    electronic is restarted and Requested parameter set is loaded.

    During driver restart operations, power supply to the valve