Upload
vophuc
View
212
Download
0
Embed Size (px)
Citation preview
1
DynatelDynatelTMTM APICS IIIAPICS III
Pair IdentificationPair Identification
Hookups, Procedures & TechniquesHookups, Procedures & Techniques
Menu Enter
StartTone
ShoeTest
SelfTest
On
Off
PowerCO BattRS-232Auxiliary Loop
Connector 1 Connector 2 Connector 3 Connector 4
Dynatel
1-25 26-50 51-75 76-100
TM
InOut
3121 APICS Automatic Pair Identification and Cable Status System
3M Telecom SystemsAPICS 3121 Ver 1.27Volt. CO 0.0 vcc
3322 APICS SCT Identification / Transfer Set
DynatelTM
Data
Ring/B
Tip/A
Talk
On
Reset
Off
F3F2F1Cancel
TraceTone
PairTrans. Xpndr Shift
Scan LTB Shoe Select
View+
View-
Vol+
Vol-
CurrentVoltage Ohms
CoilDet.
Opens DC Test
LightBuzzTalk
Menu SelfTest
87
0
9
654
1 2 3
512345 6789 12345 6789 12345 6789 12345 6789 12345 6789 100T
R
T
R
T
R12345 6789 12345 6789 12345 6789 12345 6789 12345 6789
T
R500 0 00
6 9870 000
2 3 41
3121 CO Unit
3322 Field UnitPrepared By:Roger C. ValenciaU.S. & International Technical Service Engineer3M Test & Measurement Systems3M Austin CenterAustin, TX, USA - October 2000
2
Central Office
Remote Office
Or
X-Connect
Hookup(APICS III 3121 CO Unit)
Ground Clip
RED Reference Clip (not connected)
APICS III 3121 CO Unit
Front Tap Shoes
3M Terminal Blocks
3
Pair ID Hookup & ProcedureSCAN Mode
.
CO MDFor
X-Connect Box
3121 CO Unit
FrontTap Shoe
Ground Clip
Bridge Clip
Ground Clip
3322 CO Unit
Red Clipto
-48 to 52VDCCO Battery
(Reference Voltage)
Procedure:
1. With the Field unit ON and the GROUND clip connected to the cable shield, connect the BRIDGE clip to any pair you wish to identify within the 100-pair group under test, then press the SCAN key. The pair number, color code and status of the pair will then be displayed on the screen. The LCD elements for the particular pair will also light up on the screen.
2. If SPECIAL(any service other than POTS) or UNBAL (unbalanced which means one side of the pair is grounded) is detected, the unit will pause. This is to allow the operator to decide if he wants to go ahead and identify the special or unbalanced circuit or just leave it alone. To force the unit to identify the pair, press the SCAN key twice. See examples on the following pages.
Pair to be identified - also serves as a communication link between the CO & Field unit. There must be continuity to at least one of the conductors.
Very important: Cable Shield/Ground serves as the communication return path for both the CO and Field units. The cable shield must havecontinuity (no opens) from the CO to the field. If the cable shield is open use a any known good pair within the 100-pair group under test, instead.
Note: The “SCAN” Mode can be used to identify both active and inactive pairs.
Note: It is possible not to connect the RED clip to the CO battery, the system should work normally. Only in this case, the reference voltage of -48VDC will be provided internally.
4
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
SCANSPARE R SLATET WHITE 0 0 5
OPEN
CHK CLIP
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
0 1 3SCANFAULTSPARE
SCAN Mode Display Examples
Fig. 1: NORMAL SCAN Mode Display
Connect the Bridge Clip to any pair and press SCAN key. Pair #5 is identified as shown by the numeric display at bottom right-hand corner of the LCD screen and the corresponding LTB elements also light up. The color code of the pair (WHITE/SLATE) is also displayed.
Ground Clip
Bridge Clip
APICS3322 or 3122
Fig. 2: OPEN (one conductor only)
Connect the Bridge Clip to any pair and press the SCAN key. The unit emits a HI-LO tone which indicates a condition that is not normal. The pair is identified to be Pair #13 with an OPEN fault. A single lighted LTB element also confirms the OPEN.
5
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
SCANSEND ERR
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
SCANFAULTSHORT
SPARE 0 3 7
Fig. 3: OPEN (both conductors)
Connect the Bridge Clip to any pair and press SCAN key. The unit emits 3 successive LO tones which means no communication link has been established between the CO and Field units. A SEND ERR(or) message is also displayed. In this situation, the pair cannot be identified. The OPEN fault must be cleared first before pair ID can be achieved.
Ground Clip
Bridge Clip
APICS3322 or 3122
Fig. 4: SHORT
Connect the Bridge Clip to any pair and press the SCAN key. A HI-LO tone is emitted which indicates an abnormal condition. The pair is identified to be Pair #37 with a fault, a SHORT.
SCAN Mode Display Examples
6
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
SCAN 0 0 8R GREENT RED
REVERSESPARE
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
SCAN 0 2 2CROSS FAULTSPARE
Fig. 5: REVERSE
Connect the Bridge Clip to any pair and press SCAN key. A HI-LO tone is emitted which indicates an abnormal condition (conductors REVERSED). The pair is identified to be Pair #8.
Ground Clip
Bridge Clip
APICS3322 or 3122
Fig. 6: CROSS
Connect the Bridge Clip to any pair and press the SCAN key. A HI-LO tone is emitted which indicates an abnormal condition. Pair #22 is identified and is crossed (fault) to pair #25 as indicated by the LTB elements.
SCAN Mode Display Examples
7
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
SCANSPARE FAULTSPLIT 0 1 5
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
SCAN 0 0 4WORKINGR BROWNT WHITE
Fig. 7: SPLIT
Connect the Bridge Clip to any pair and press SCAN key. A HI-LO tone is emitted which indicates an abnormal condition. The pair is identified to be Pair #15 and is SPLIT to Pair #12 as indicated by the lighted LTB elements.
Ground Clip
Bridge Clip
APICS3322 or 3122
Fig. 8: WORKING (active, non-busy)
Connect the Bridge Clip to any pair and press the SCAN key. A single HI tone is emitted indicating a normal condition. The pair is identified to be Pair #4 and its color code (WHITE/BROWN) is also displayed.
SCAN Mode Display Examples
8
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
SCANUNBAL
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
SCAN 0 4 5FAULTSPARE
Fig. 9: GROUND
Connect the Bridge Clip to any pair and press SCAN key. The unit emits single LO tone, displays an UNBAL(anced) condition of the pair and then goes into a pause to allow the operator to further investigate the pair. The UNBAL(anced) condition means that one side of the pair is grounded and it can either be a normal characteristic to the pair or it can be a fault.
Note: The GROUND can be verified by using the LTB mode and to force the unit to identify pair, follow instructions in Fig. 9a.
Ground Clip
Bridge Clip
APICS3322 or 3122
Fig. 9a: GROUND
Press the SCAN key, twice. A successive HI-LO-HI tone is emitted indicating a possible fault condition. Pair #45 is identified but then one LTB element did not light up.
Note: In SCAN mode, the LTB element of a GROUNDED conductor will not light up. Also, in a #5 Xbar office, it is normal for all the TIP[A] conductors of non-busy pairs to be GROUNDED. This is the reason why this condition requires further investigation, to determine if the GROUNDis normal to the pair or it can be a fault.
SCAN Mode Display Examples
9
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
SCANSPECIAL
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
SCAN 0 0 8R GREENT RED
SPECIAL
Fig. 10: SPECIAL (non-POTS)
Connect the Bridge Clip to any pair and press SCAN key. The unit emits a single LO tone and displays a SPECIAL (non-POTS) classification of the pair.
Note: SPECIAL circuits are more sensitive and require more careful handling than regular POTS lines. This is the reason why the unit goes into a pause to allow the operator to decide whether to go ahead with the pair ID or not. If the decision is to go ahead and identify the pair, then follow instructions in Fig. 10a.
Ground Clip
Bridge Clip
APICS3322 or 3122
Fig. 10a: SPECIAL (non-POTS)
Press the SCAN key, twice to force the unit to identify the pair. The unit emits a single HI tone to indicate a clean (non-faulted) pair. The pair is identified to be Pair #8 which is also confirmed by the lighted LTB elements.
SCAN Mode Display Examples
10
Pair ID Hookup & ProcedureLTB ModeMDF
orX-Connect Box
3121 CO Unit
FrontTap Shoe
Ground Clip
Bridge Clip
Pair to be identified
Ground Clip
3322 CO Unit
Red Clipto
-48 to 52VDCCO Battery
(Reference Voltage)
Ground conductors to identify
Procedure:
1. With the Field unit ON, connect the BRIDGE clip to any pair within the 100-pair group being worked on, the GROUND clip to the cable shield then press the LTB key. Wait for the Field unit to emit the scanning tones (2 short beeps in succession).
2. Take any pair you wish to identify and ground each conductor one at a time or both at the same time. The LCD elements corresponding to that pair should light up on the LTB screen. See examples on the following pages.
Communication link between the CO & Field unit (any pair within the 100 pair group) is required and there must be continuity to at least one of the conductors
Note: In the “LTB” Mode, the pair or conductors to be identified must be grounded to identify therefore use this mode on inactive pairs, only.
Very important: Cable Shield/Ground serves as the communication return path for both the CO and Field units. The cable shield must havecontinuity (no opens) from the CO to the field. If the cable shield is open use a any known good pair within the 100-pair group under test, instead.
Note: It is possible not to connect the RED clip to the CO battery, the system should work normally. Only in this case, the reference voltage of -48VDC will be provided internally.
11
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
LTBSENDING
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
LTBSENDING
LTB Mode Display Examples
Fig. 1: GROUNDED Conductors
If the operator is “not” grounding any pair, any LTB element that lights up upon pressing the LTB key is GROUNDED at some point along the cable length. In this case, RING[B] (Pair #6), TIP[A] (Pair #14) and both conductors of Pair #23 are all GROUNDED.
Fig. 2: NORMAL LTB Display
If both conductors of a pair are “GROUNDED” by the operator, the corresponding LTB elements should light up. In this case, Pair #23 is identified.
Ground Clip
Ground Clip
Bridge Clip
Bridge Clip
APICS3322 or 3122
APICS3322 or 3122
12
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
LTBSENDING
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
LTBSENDING
Fig. 3: OPEN (One conductor only)
If both conductors of a pair are “GROUNDED” by the operator and only one LTB element lights up, then one side is OPEN. In this case, TIP[A] of Pair #6 is OPEN.
Fig. 4: OPEN (Both conductors)
If both conductors of a pair are “GROUNDED” by the operator, and no LTB element lights up, both conductors of the pair are OPEN. In this case, the OPEN fault must be cleared first before the pair can be identified.
Ground Clip
Bridge Clip
APICS3322 or 3122
LTB Mode Display Examples
13
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
LTBSENDING
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
LTBSENDING
LTB Mode
Fig. 5: CROSS
If both conductors of a pair are “GROUNDED” by the operator and other additional LTB elements light up with the LTB elements of the pair. a CROSS (fault) exists between the pairs. In this case Pair #23 is identified but CROSSED to Pair #14 as shown above.
Fig. 6: SPLIT
If both conductors of a pair are “GROUNDED” by the operator, and the LTB elements light up, as shown above, the pairs are SPLIT. In this case, Pair #23 and #25 are SPLIT.
Ground Clip
Bridge Clip
APICS3322 or 3122
14
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
LTBSENDING
Fig. 7: SHORT
When only one conductor of a pair is “GROUNDED” by the operator and the two corresponding LTB elements to the pair light up, then the pair is SHORTED.
Ground Clip
Bridge Clip
APICS3322 or 3122
LTB Mode Display Examples
15
Pair ID Hookup & ProceduresSELECT ModeMDF
orX-Connect Box
3121 CO Unit
FrontTap Shoe
Ground Clip
Bridge Clip
Pair to be identified (with the ID tone)
Ground Clip
3322 CO Unit
Red Clipto
-48 to 52VDCCO Battery
(Reference Voltage}
Procedure:
1. With the Field unit ON, connect the Bridge clip to any pair within the 100-pair group being worked on and the GROUND clip to the cable shield. Enter the pair number you wish to identify using the numeric keys and then press the SELECT key. The Field unit will then send a command to the CO unit to place the interrupted ID tone on the pair number selected.
2. Take the TONE probe and locate the pair where the interrupted ID tone is on. You may activate the XPANDER to minimize tone bleed to the other pairs. Adjust the VOLUME level, accordingly. See examples on the following page.
Tone Probe
Note: The “SELECT” Mode uses “ Interrupted ID Tone” to identify a pair. It can be used for both active and inactive pairs.
Communication link between the CO & Field unit (any pair within the 100 pair group) is required and there must be continuity to at least one of the conductors.
Very important: Cable Shield/Ground serves as the communication return path for both the CO and Field units. The cable shield must havecontinuity (no opens) from the CO to the field. If the cable shield is open use a any known good pair within the 100-pair group under test, instead.
Note: It is possible not to connect the RED clip to the CO battery, the system should work normally. Only in this case, the reference voltage of 48VDC will be provided internally.
16
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
SELECT 0 2 6R BLUET WHITEPROBING
Press the appropriate numeric key to enter the pair number to identified. The number will then be displayed on the screen. Next step is to press the SELECT button. The field unit will now talk to the CO unit to send tone on pair #26. The LTB elements of Pair #26 will then light up and displays the pair color code to confirm that it was selected and that tone is already on it. The TONE Probe is then used to locate the tone. The pair with the strongest tone should be Pair #26.
To improve selectivity and minimize tone spreading or bleeding, press theXpander key. An X should appear under the function display box (see Fig. 11a).
Fig. 11: Normal indication
Fig. 11a: Normal indication with Xpander activated
SELECT ( Tone ) Mode Examples
51 2 3 4 5 6 7 8 9 60 1 2 3 4 5 6 7 8 9 70 1 2 3 4 5 6 7 8 9 80 1 2 3 4 5 6 7 8 9 90 1 2 3 4 5 6 7 8 9 100
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 20 1 2 3 4 5 6 7 8 9 30 1 2 3 4 5 6 7 8 9 40 1 2 3 4 5 6 7 8 9 50T
R
T
R
T
R
T
R
SELECT 0 2 6R BLUET WHITEPROBING
GroundClip Bridge
Clip
StrongTone
WeakTones
(induced)
ToneProbe
Pair #26
APICS3322 or 3122
Note:
In SELECT mode, there will be no warning message on SPECIALS (non-POTS) lines.
17
APICS IIIAPICS III
Pair Identification Pair Identification TechniquesTechniques
Menu Enter
StartTone
ShoeTest
SelfTest
On
Off
PowerCO BattRS-232Auxiliary Loop
Connector 1 Connector 2 Connector 3 Connector 4
Dynatel
1-25 26-50 51-75 76-100
TM
InOut
3121 APICS Automatic Pair Identification and Cable Status System
3M Telecom SystemsAPICS 3121 Ver 1.27Volt. CO 0.0 vcc
3322 APICS SCT Identification / Transfer Set
DynatelTM
Data
Ring/B
Tip/A
Talk
On
Reset
Off
F3F2F1Cancel
TraceTone
PairTrans. Xpndr Shift
Scan LTB Shoe Select
View+
View-
Vol+
Vol-
CurrentVoltage Ohms
CoilDet.
Opens DC Test
LightBuzzTalk
Menu SelfTest
87
0
9
654
1 2 3
512345 6789 12345 6789 12345 6789 12345 6789 12345 6789 100T
R
T
R
T
R12345 6789 12345 6789 12345 6789 12345 6789 12345 6789
T
R500 0 00
6 9870 000
2 3 41
3121 CO Unit
3322 Field Unit
18
Table Of ContentsTable Of Contents
Pages
1. How to put ID tone on any preferred pair within the 100-pair group
under test at the MDF - 19 to 24
2. APICS III Pair ID Hookup - When the cable shield is OPEN - 25
3. How to Pair ID randomly spliced or transposed pairs - 26
4. APICS III Pair ID Hookup - Multiple CO Units and/or Field Units - 27
19
How To Put “ID Tone” On Any Preferred Pair How To Put “ID Tone” On Any Preferred Pair Within The 100Within The 100--pair Group Under Test At The MDFpair Group Under Test At The MDF
1. Turn the 3121 CO unit ON. The unit will do a quick self test, and then displays the following:
On
Off
3M Telecom SystemsAPICS 3121 Ver 1.30CO Batt -48.0vdcUnit # 1
SELF Test * LOCAL *I n i t i a l i z i n g systemCopyright3M Canada Inc. 1992
SELF Test * LOCAL *I n i t i a l i z i n g system
Self Test Passed
2. Connect the “Battery” cable (“Black” clip to Ground and “Red” to the negative (-) terminal of the CO battery, if possible).
3. Connect the “Front Tap Shoe” between the CO unit and the 100-pair group to be identified at the MDF (Fig. 2).
Fig. 1: CO Unit Screens
Fig. 2: CO unit hookup at the MDF
Field Side
Shield/GroundBlack Clip
Front Tap Shoe
CO MDF
3121 CO Unit
CO Battery
(-48VDC to -52VDC)
System Ground
1
2 2
3 100-pair group under test
Note: It is possible not to connect the RED clip to the CO battery, the system should work normally. Only in this case, the reference voltage of -48VDC will be provided internally.
20
4. Press the ON/Reset key to turn the Field unit ON. The Field unit should display the
following:
12345 678910 12345 678920 12345 678930 12345 678940 12345 678950
512345 678960 12345 678970 12345 678980 12345 678990 12345 6789100
OnReset
T
RT
R 3M Model 3322 APICS/SCTF159T READY
T
RT
R
Fig. 3: 3322 Field unit screen
How To Put “ID Tone” On Any Preferred Pair How To Put “ID Tone” On Any Preferred Pair Within The 100Within The 100--pair Group Under Test At The MDFpair Group Under Test At The MDF
((con’tcon’t))
21
5. Connect the Field unit’s “Ground” clip to the MDF system Ground (see Fig.4).
6. Connect the “Bridge” clip directly or through a jumper wire to any selected pair among the 100-pair group
under test at the MDF. (ex: pair #33).
3322 Field Unit
Bridge Clip
selected pair (ex: pair #33)
Field Side
Fig. 4: Field unit hookup at the MDF
Ground Clip
5
4
Shield/Ground
CO battery
-48VDC to 52VDC
How To Put “ID Tone” On Any Preferred Pair How To Put “ID Tone” On Any Preferred Pair Within The 100Within The 100--pair Group Under Test At The MDFpair Group Under Test At The MDF
((con’tcon’t))
Note: It is possible not to connect the RED clip to the CO battery, the system should work normally. Only in this case, the reference voltage of -48VDC will be provided internally.
22
7. Using the blue numeric keys, enter the selected pair number (ex: Pair # 33)
where the “ID Tone” will be put into and then press the <Select> key.
The Field unit then sends a command to the CO unit to put ID tone on
pair #33. The screen should display the following:
3Ohms
3
Ohms
12345 678910 12345 678920 12345 678930 12345 678940 12345 678950
512345 678960 12345 678970 12345 678980 12345 678990 12345 6789100
3 3
T
RT
R 3M Model 3322 APICS/SCTF159T READY
T
RT
R
How To Put “ID Tone” On Any Preferred Pair How To Put “ID Tone” On Any Preferred Pair Within The 100Within The 100--pair Group Under Test At The MDFpair Group Under Test At The MDF
((con’tcon’t))
Select
Fig. 5: 3322 Field unit screen
12345 678910 12345 678920 12345 678930 12345 678940 12345 678950
512345 678960 12345 678970 12345 678980 12345 678990 12345 6789100
0 3 3
T
RT
RPROBING
SELECT
T
RT
R
23
8. To verify that the “ID Tone” is already on the selected pair (pair #33), plug the Tone Probe into the Field unit.
Place the tone probe close to the selected pair or the Bridge clip (Fig. 7). The ID Tone should be heard from the
internal speaker. Adjust the volume level if necessary.
9. Once the ID tone is verified on the selected pair (Pair #33), turn the 3322 Field unit OFF, disconnect it from the
pair and proceed to the far-end of the cable.
Field Side
ID Tone
ID Toneselected pair (Pair #33)
9
Fig. 6: 3322 Field unit hookup at the MDF
How To Put “ID Tone” On Any Preferred Pair How To Put “ID Tone” On Any Preferred Pair Within The 100Within The 100--pair Group Under Test At The MDFpair Group Under Test At The MDF
((con’tcon’t))
Note: It is possible not to connect the RED clip to the CO battery, the system should work normally. Only in this case, the reference voltage of -48VDC will be provided internally.
CO battery
-48VDC to 52VDC
24
10. Once out in the field, turn the Field unit ON, connect the GROUND cable to the cable shield, plug the tone PROBE into its jack and press the SELECT key to activate the tone PROBING process.
11. With the tone PROBE, look for the ID Tone on a pair. The ID tone should be on Pair #33. This should identify the 100 pair group under test. Note: As you close in to the pair with the ID tone, you may want to activate the Xpander by pressing the Xpander key. The Xpander function is used to minimize tone bleeding to other pairs.
12. Once the 100 pair group under test is identified, proceed to the normal Pair ID process using SCAN, LTB or SELECT Modes as the case maybe.
100 pair group under test
Pair #33
Probe
3121 CO Unit
CO Batt MDF Ground Cable Shield
Fig. 7 Field unit hookup at the far-end of cable
ID Tone
How To Put “ID Tone” On Any Preferred Pair How To Put “ID Tone” On Any Preferred Pair Within The 100Within The 100--pair Group Under Test At The MDFpair Group Under Test At The MDF
((con’tcon’t))
Note: It is possible not to connect the RED clip to the CO battery, the system should work normally. Only in this case, the reference voltage of -48VDC will be provided internally.
25
Pair ID Hookup When The Cable Shield Is OpenPair ID Hookup When The Cable Shield Is Open
OPEN
Cable Shield
Pair to be identified
Vacant pair to serve as control return path
CO BatteryBlack (Ground) Clip
Black (Ground) Clip
3121 CO Unit
3322 Field Unit
Bridge Clip
Bridge wire
Control pair
Front Tap Shoe
Note:
1. If the cable shield is suspected to be open, connect the black (Ground) clips of both units to a spare pair that has continuity from the CO MDF to the far-end of the cable.
Note: It is possible not to connect the RED clip to the CO battery, the system should work normally. Only in this case, the reference voltage of -48VDC will be provided internally.
26
How To Identify RandomlyHow To Identify Randomly--Spliced Or Transposed PairsSpliced Or Transposed Pairs
CO 3121 Multiple
Setup
CO Unit #1
CO Unit #2
Field Unit Single or Multiple Setup
ID # 1 (CO unit #1)Pair 006
ID #2 (CO unit #2)Pair 008 = Pair 108
ID #1 (CO unit #1)Pair 008
ID #2 (CO unit #2)Pair 006 = Pair 106
Field Unit Display(SCAN Mode)
Pairs 1 to 100
Pairs 101 to 200
CO Battery
MDF Ground
Shield Ground
Note:
1. To assign numbers to the CO units, turn them ON. On each unit, press the UP or DOWN arrow to select a number from 0 to 9.
2. On the Field Units, pay attention to the CO Unit ID number displayed on the screen as the pairs are being identified. See illustration above.
Note: It is possible not to connect the RED clip to the CO battery, the system should work normally. Only in this case, the reference voltage of -48VDC will be provided internally.
27
APICS III Pair ID HookupMultiple CO Units and/or Field UnitsCO
MDF
Front Tap Shoe
Front Tap Shoe
COBattery
GroundClip
SystemGround
Cable Shield
Pairs 1 to 100
Pairs 101 to 200
Bridge Clip
Bridge Clip
Bridge Clip
Bridge Clip
Field end of cable
Field end of cable
Notes:1. To assign a number to the CO units - turn the units ON and press the UP or Down Arrow keys to the desired unit number (0 to 9).2. Use “SCAN Mode” only on Pair ID Multiple Setups.
3121CO Unit
#1
3121CO Unit
#2
3. Pay attention to the CO unit ID number that is displayed on the Field unit screen when a pair is being identified. Example: A number 005 with ID #2 on the screen is actually pair #105 on the100-pair group that is connected to CO unit #2.
Note: It is possible not to connect the RED clip to the CO battery, the system should work normally. Only in this case, the reference voltage of -48VDC will be provided internally.