Page 1: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

R-410A50Hz

www.skmaircon.comfacebook.com/skmaircon @skmaircon

Ducted Mini Split System

Range 1.5 TR to 5 TR( 6 kW to 18 kW)

RX+DDP

Page 2: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

2

SKM Ducted Mini Split UnitsRX/DDP - R-410A

Contents

Legend The following legends are used throughout this manual:

IntroductionThe Ducted Mini Split system from SKM consists of RX (a high efficiency- TOP discharge Air Cooled Condensing Unit); matching with DDP (a low noise, ceiling suspended indoor fan coil unit). This split systems are ideally suited for apartments, houses, offices, shops, small residences, and in small commercial establishments.

SKM ducted mini split system are available in different models covering 1.5 TR to 5 TR (6 kW to 18 kW) at nominal AHRI condition, which make them ideally suited for a very small foot print for space saving and a pleasant exterior appearance.

SKM ducted mini split system are designed in accordance with ESMA, ESTIDAMA & MEW regulations.

SKM ducted mini split units are suitable to operate in a wide range of ambient temperature. (Minimum outdoor operating ambient in cooling mode is 55°F (13°C), maximum is 125°F (52°C).

SKM ducted mini split units are internally wired and all that required to be done on site is ducting, refrigerant piping, power supply and suitable room thermostat installation and field wiring, which reduces the installation work and consequently keeps to a minimum cost.

SKM provides qualified service and stock of replacement parts in all major cities of the G.C.C. countries, Egypt, Jordan, and Pakistan. See back cover for details or call SKM.

SKM Air Conditioning LLC

You name it.....We cool it

Introduction .........................................2Legend................................................2Nomenclature .....................................3Features & Specification................. 4-5Combination Ratings ...................... 6-7Electrical Data ....................................8Options ...............................................8Fan Performance ................................9

Recommended Line Sizes................10Typical Refrigeration Piping ..............11Typical Wiring Diagram.....................12Dimensional Data ....................... 13-14Outdoor Unit Clearanceand Spacing......................................15Guide Specification...........................16

AFR ...... Air Flow Ratecfm ....... Cubic feet per minutedB ........ DecibelsEADB ....Entering Air Dry BulbEAWB ....Entering Air Wet BulbET ......... Evaporating TemperatureHz ........ HertzkW ........ Kilowattskg ......... KilogramskPa ...... Kilo PascalsLADB .... Leaving Air Dry BulbPSI........Pounds Per Square InchCOP......Coefficient of Performance

EER.....Energy Efficiency RatioLAWB ... Leaving Air Wet Bulblbs .........Pounds weight (British units)l/s ..........Liters per secondMbh ...... 1000 BtuhOD ........ Outside DiameterPh ......... PhasePa ......... PascalsSC ........ Sensible CapacityTC .........Total CapacityTR ........ Tons of refrigeration = 12 MBHV ........... Volts

SKM reserves the right to change, in part or in whole the specifications of its Air Conditioning Equipment at any time in order to add the latest technology. Therefore, the enclosed information may change without any prior notice.

Page 3: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

3

SKM Ducted Mini Split UnitsRX/DDP - R-410A

Nomenclature

Ducted Mini Split Nomenclature Outdoor

R X 18 P S1 V C 00

Remote Air Cooled Condenser

Direct Expansion

Nominal Capacity in1824303642485460

RefrigerantP : R410A

SKM Code

Application

Air Discharge

Power Supply

C : Cooling

V : Vertical Discharge

Y: 380-415V/3Ph/50HzS1: 220-240V/1Ph/50Hz

FCU DD P 24 4 P C 00

Fan Coil Unit

Series Name

Ceiling suspended with Plenum

Number of Rows

SKM Code

Application

Refrigerant

C : Cooling

P : R410A

Ducted Mini Split Nomenclature Indoor

DD : Direct Driven

Unit Size1824303642485460

Page 4: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

4

SKM Ducted Mini Split UnitsRX/DDP - R-410A

Outdoor Unit - RX

• Design - Outdoor condensing units are ideal for rooftop or ground installation. Units have a pleasant exterior appearance and have a very small footprint for space saving installation.

• High efficiency Coils - inner groove tubes; mechanically bonded to hi-efficiency aluminium fins to match for a maximum efficiency.

• Hermetic Scroll Compressor - High efficiency hermetically sealed scroll type compressor located on engineered mounts for safe, quiet and vibration free operation.Compresssors are selected for reliability, power efficiency & provided with crankcase heater.

• Cabinet Construction - Heavy gauge zinc clad steel, latest technology electrostatic powder baked finish to ensure a long lasting, durable cabinet.

• Fan Motor – Condenser fan is propeller type with aluminium alloy blades and directly driven by electric motors.

• Brass Service Valves – Factory installed service valve with sweat connections to provide quick and accurate installation for start-up and servicing.

• Ease of Service and Installation – Designed to make servicing easier for the contractor, access panels are provided for all controls and the compressor from the side of the unit.

• Compressor Short Cycling Protection – To protect the compressor against rapid short cycling.• High and Low Pressure Protection - To protect the compressor against high discharge pressure and low suction pressure, and

to guarantee safe operation of compressor.• Filter Drier - Filter drier is factory supplied ( Field installed) for all sizes.

Notes: 1. Capacity ratings are based on AHRI Standard 210/240. Evaporator entering air conditions of 80/67ºF (27/19.5ºC) dry bulb/wet bulb and condenser entering air temperature of 95ºF (35ºC) dry bulb. 2. Evaporator entering air conditions of 84.2°F/66.2°F (29.0°C/19.0°C) dry bulb/wet bulb and condenser entering air temperature of 114.8°F(46°C) dry bulb, (Net Capacity).3. Evaporator entering air conditions of 80/67ºF (27/19.5ºC) dry bulb/wet bulb and condenser entering air temperature of 118.4ºF (48ºC) dry bulb.

Specification (Outdoor Unit RX)

MBh 17.6 21.4 25.2 33.0 38.1 44.1 55.7 62.1kW 5.2 6.3 7.4 9.7 11.2 12.9 16.3 18.2

12.6 12.7 12.9 13.2 12.5 12.9 13.2 12.8MBh 14.2 17.3 20.4 27.0 31.0 35.6 45.3 51.0kW 4.2 5.1 6.0 7.9 9.1 10.4 13.3 14.9

8.3 8.3 8.4 8.4 8.2 8.3 8.6 8.6MBh 15.1 18.3 21.5 27.9 32.7 37.7 47.4 53.3kW 4.4 5.4 6.3 8.2 9.6 11.0 13.9 15.6

8.4 8.4 8.5 8.3 8.2 8.5 8.7 8.8V/Ph/Hz

1 1 1 1 1 1 1 1

11.11 11.11 13.7 16.4 16.4 16.4 16.4 16.41.03 1.03 1.27 1.52 1.52 1.52 1.52 1.52

450/1 450/1 450/1 450/1 550/1 550/1 550/1 550/12570 2570 2570 2610 2610 4210 4210 42101213 1213 1213 1232 1232 1987 1987 1987

Size 0.11 0.11 0.11 0.11 0.11 0.28 0.28 0.284.2/ 1.9 4.3/ 1.97 5 / 2.28 8.5/ 3.84 8.6/ 3.88 8.7 / 3.95 9.1/ 4.41 9.3 / 4.24190 / 86 190 / 86 195 / 89 262 / 119 262 / 119 268 / 122 277 / 126 293 / 133

25 25 25 30 30 30 30 3025 25 25 30 30 30 30 30

32.9 32.9 32.9 32.9 32.9 32.9 32.9 32.93/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8"3/4" 3/4" 3/4" 7/8" 7/8" 7/8" 7/8" 7/8"

MBh 17.6 21.4 25.2 33.0 38.1 44.1 55.7 62.1kW 5.2 6.3 7.4 9.7 11.2 12.9 16.3 18.2

12.6 12.7 12.9 13.2 12.5 12.9 13.2 12.8MBh 14.2 17.3 20.4 27.0 31.0 35.6 45.3 51.0kW 4.2 5.1 6.0 7.9 9.1 10.4 13.3 14.9

8.3 8.3 8.4 8.4 8.2 8.3 8.6 8.6MBh 15.1 18.3 21.5 27.9 32.7 37.7 47.4 53.3kW 4.4 5.4 6.3 8.2 9.6 11.0 13.9 15.6

8.4 8.4 8.5 8.3 8.2 8.5 8.7 8.8686 680 777 1041 1296 1497 1761 1943324 321 367 479 612 707 831 917

Type1.7 1.7 2.0 2.7 3.0 3.5 4.7 5.30.15 0.15 0.19 0.25 0.28 0.33 0.43 0.50

Type Code 7-7 7-7 7-7 9-7 7-7 7-7 9-7 9-7

Quantity 1 1 1 1 2 2 2 2Type Size 150 150 150 150 150 150 150 150

Quantity 1 1 1 1 2 2 2 23/8 3/8 3/8 3/8 3/8 3/8 3/8 3/810 10 10 10 10 10 10 103/4 3/4 3/4 7/8 7/8 7/8 7/8 7/819 19 19 29 29 29 29 2960 63 70 86 91 114 141 14827 28.6 31.8 39.1 41.4 51.8 64.1 67.3

inchmm

Machine Weightlbs.Kg.

-

ft2

-#

#

Copper Tubes mechanically bonded to Hi-effeciency wavy corrugated Aluminium Fins

Double Inlet Double Width Centrifugal Forward Curve Direct Drive

220-240V/1Ph/50-60Hz,3 Speed Electric Motor with Permanent Split Capacitor

Conn

ectio

n Siz

es

Liquid Ø

Suction Ø

Motor

m2

-

Coil

42 48 54 60

Model RX

220-240/1/50Hz 380-415/3/50HzHermetic Scroll

HI-X tube 3/8'' OD

Propeller,Direct Drive

EER

Matched Outdoor Units RX18 24

Totally enclosed, Class-F Insulation, 6-Pole, IP54 Protected

Model DDP18 24 30 36

Refrigerant Operating Charge (R-410A)

Cooling Capacity (1) Cooling @ 95°F/35°C

Cooling Capacity (2) Cooling @ 114.8°F/46°C

EER

EER

EER

Air Flow

Pack valves Connections

42

CompressorType Qty.

Coil Face Area

Operating Weight ApproximateDimensions (inches)

30

lbs /

LengthHeightLiquidSuction

kWlbs / kg

kgWidth

Cooling Capacity (2) Cooling @ 114.8°F/46°C

Cooling Capacity (3) Cooling @ 118.4°F/48°C

EER

4818 24 30 36 42 54 60

-Watts

inchmm

Fan

Cooling @ 95°F/35°CCooling Capacity (1)

Power Supply

Type

Cond

ense

r

48 54 60

Nominal Air Flow Ratecfml/s

Cooling Capacity (3) Cooling @ 118.4°F/48°C

EER

36

Face Area

Motor

Type

TypeCode/Qty

ftm

cfml/s

Fan

Table 1

Design Features: (Air Cooled units up to 5 Tons of Refrigeration)

Page 5: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

5

SKM Ducted Mini Split UnitsRX/DDP - R-410A

Indoor Unit - DDP

• High efficiency coil with high efficiency wavy corrugated fins.

• High efficiency, low power consumption PSC electric motor.

• High efficiency forward curved fan for quiet operation.

• Heavy gauge galvanized casing and fan housing. Hot dip is standard.

• Insulated heavy gauge drain pan.

• Isolating grommet for an additional vibration isolation.

• Easy wiring / electrical and piping connections.

• Evaporator coils equipped with copper tubes and aluminium fins which give high capacity sensible and latent cooling capabilities.

• Equipped with expansion valve special type for R410A application .

Notes: 1. Capacity ratings are based on AHRI Standard 210/240. Evaporator entering air conditions of 80/67ºF (27/19.5ºC) dry bulb/wet bulb and condenser entering air temperature of 95ºF (35ºC) dry bulb. 2. Evaporator entering air conditions of 84.2°F/66.2°F (29.0°C/19.0°C) dry bulb/wet bulb and condenser entering air temperature of 114.8°F(46°C) dry bulb, (Net Capacity).3. Evaporator entering air conditions of 80/67ºF (27/19.5ºC) dry bulb/wet bulb and condenser entering air temperature of 118.4ºF (48ºC) dry bulb.

MBh 17.6 21.4 25.2 33.0 38.1 44.1 55.7 62.1kW 5.2 6.3 7.4 9.7 11.2 12.9 16.3 18.2

12.6 12.7 12.9 13.2 12.5 12.9 13.2 12.8MBh 14.2 17.3 20.4 27.0 31.0 35.6 45.3 51.0kW 4.2 5.1 6.0 7.9 9.1 10.4 13.3 14.9

8.3 8.3 8.4 8.4 8.2 8.3 8.6 8.6MBh 15.1 18.3 21.5 27.9 32.7 37.7 47.4 53.3kW 4.4 5.4 6.3 8.2 9.6 11.0 13.9 15.6

8.4 8.4 8.5 8.3 8.2 8.5 8.7 8.8V/Ph/Hz

1 1 1 1 1 1 1 1

11.11 11.11 13.7 16.4 16.4 16.4 16.4 16.41.03 1.03 1.27 1.52 1.52 1.52 1.52 1.52

450/1 450/1 450/1 450/1 550/1 550/1 550/1 550/12570 2570 2570 2610 2610 4210 4210 42101213 1213 1213 1232 1232 1987 1987 1987

Size 0.11 0.11 0.11 0.11 0.11 0.28 0.28 0.284.2/ 1.9 4.3/ 1.97 5 / 2.28 8.5/ 3.84 8.6/ 3.88 8.7 / 3.95 9.1/ 4.41 9.3 / 4.24190 / 86 190 / 86 195 / 89 262 / 119 262 / 119 268 / 122 277 / 126 293 / 133

25 25 25 30 30 30 30 3025 25 25 30 30 30 30 30

32.9 32.9 32.9 32.9 32.9 32.9 32.9 32.93/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8"3/4" 3/4" 3/4" 7/8" 7/8" 7/8" 7/8" 7/8"

MBh 17.6 21.4 25.2 33.0 38.1 44.1 55.7 62.1kW 5.2 6.3 7.4 9.7 11.2 12.9 16.3 18.2

12.6 12.7 12.9 13.2 12.5 12.9 13.2 12.8MBh 14.2 17.3 20.4 27.0 31.0 35.6 45.3 51.0kW 4.2 5.1 6.0 7.9 9.1 10.4 13.3 14.9

8.3 8.3 8.4 8.4 8.2 8.3 8.6 8.6MBh 15.1 18.3 21.5 27.9 32.7 37.7 47.4 53.3kW 4.4 5.4 6.3 8.2 9.6 11.0 13.9 15.6

8.4 8.4 8.5 8.3 8.2 8.5 8.7 8.8686 680 777 1041 1296 1497 1761 1943324 321 367 479 612 707 831 917

Type1.7 1.7 2.0 2.7 3.0 3.5 4.7 5.30.15 0.15 0.19 0.25 0.28 0.33 0.43 0.50

Type Code 7-7 7-7 7-7 9-7 7-7 7-7 9-7 9-7

Quantity 1 1 1 1 2 2 2 2Type Size 150 150 150 150 150 150 150 150

Quantity 1 1 1 1 2 2 2 23/8 3/8 3/8 3/8 3/8 3/8 3/8 3/810 10 10 10 10 10 10 103/4 3/4 3/4 7/8 7/8 7/8 7/8 7/819 19 19 29 29 29 29 2960 63 70 86 91 114 141 14827 28.6 31.8 39.1 41.4 51.8 64.1 67.3

inchmm

Machine Weightlbs.Kg.

-

ft2

-#

#

Copper Tubes mechanically bonded to Hi-effeciency wavy corrugated Aluminium Fins

Double Inlet Double Width Centrifugal Forward Curve Direct Drive

220-240V/1Ph/50-60Hz,3 Speed Electric Motor with Permanent Split Capacitor

Conn

ectio

n Siz

es

Liquid Ø

Suction Ø

Motor

m2

-

Coil

42 48 54 60

Model RX

220-240/1/50Hz 380-415/3/50HzHermetic Scroll

HI-X tube 3/8'' OD

Propeller,Direct Drive

EER

Matched Outdoor Units RX18 24

Totally enclosed, Class-F Insulation, 6-Pole, IP54 Protected

Model DDP18 24 30 36

Refrigerant Operating Charge (R-410A)

Cooling Capacity (1) Cooling @ 95°F/35°C

Cooling Capacity (2) Cooling @ 114.8°F/46°C

EER

EER

EER

Air Flow

Pack valves Connections

42

CompressorType Qty.

Coil Face Area

Operating Weight ApproximateDimensions (inches)

30

lbs /

LengthHeightLiquidSuction

kWlbs / kg

kgWidth

Cooling Capacity (2) Cooling @ 114.8°F/46°C

Cooling Capacity (3) Cooling @ 118.4°F/48°C

EER

4818 24 30 36 42 54 60

-Watts

inchmm

Fan

Cooling @ 95°F/35°CCooling Capacity (1)

Power Supply

Type

Cond

ense

r

48 54 60

Nominal Air Flow Ratecfml/s

Cooling Capacity (3) Cooling @ 118.4°F/48°C

EER

36

Face Area

Motor

Type

TypeCode/Qty

ftm

cfml/s

Fan

Specification (Indoor Unit DDP Matched with Outdoor Unit RX)

Design Features

Table 2

Page 6: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

6

SKM Ducted Mini Split UnitsRX/DDP - R-410A

Combination Ratings - DDP with RX Units

PI* PI* PI* PI* PI*

MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW

686 17.6 5.2 14.4 4.2 0.9 16.6 4.9 14 4.1 1.1 15.5 4.5 13.6 4 1.3 15.1 4.4 13.5 4 1.3 14.9 4.4 13.4 3.9 1.4

624 17.4 5.1 13.7 4 0.9 16.4 4.8 13.3 3.9 1.1 15.3 4.5 12.9 3.8 1.3 14.9 4.4 12.8 3.7 1.3 14.7 4.3 12.7 3.7 1.4

532 17.1 5 12.6 3.7 0.9 16.1 4.7 12.2 3.6 1.1 15 4.4 11.8 3.5 1.3 14.6 4.3 11.7 3.4 1.3 14.4 4.2 11.6 3.4 1.4

680 21.4 6.3 15.7 4.6 1.2 20 5.9 15.2 4.5 1.4 18.7 5.5 14.7 4.3 1.6 18.3 5.4 14.6 4.3 1.7 18.1 5.3 14.5 4.2 1.8

618 21.2 6.2 15 4.4 1.2 19.9 5.8 14.5 4.3 1.4 18.6 5.4 14 4.1 1.6 18.1 5.3 13.9 4.1 1.7 17.9 5.2 13.8 4 1.8

527 20.5 6 13.9 4.1 1.2 19.5 5.7 13.5 4 1.4 18.3 5.4 13 3.8 1.6 17.8 5.2 12.8 3.8 1.7 17.6 5.2 12.8 3.7 1.8

777 25.2 7.4 18.3 5.4 1.4 23.7 6.9 17.7 5.2 1.7 22.1 6.5 17.1 5 1.9 21.5 6.3 16.9 5 2 21.3 6.2 16.8 4.9 2.1

706 24.8 7.3 17.5 5.1 1.4 23.5 6.9 17 5 1.7 21.9 6.4 16.4 4.8 1.9 21.3 6.2 16.1 4.7 2 21 6.2 16 4.7 2.1

602 24.1 7 16.2 4.7 1.4 22.9 6.7 15.7 4.6 1.7 21.6 6.3 15.2 4.5 1.9 21 6.2 14.9 4.4 2 20.7 6.1 14.8 4.4 2.1

1041 33 9.7 24.2 7.1 2 30.9 9.1 23.4 6.9 2.3 28.7 8.4 22.6 6.6 2.7 27.9 8.2 22.3 6.5 2.9 27.6 8.1 22.2 6.5 2.9

922 32.6 9.6 22.9 6.7 2 30.6 9 22.1 6.5 2.3 28.4 8.3 21.3 6.2 2.7 27.6 8.1 21 6.2 2.9 27.2 8 20.9 6.1 2.9

786 31.6 9.3 21.2 6.2 2 30 8.8 20.5 6 2.3 28 8.2 19.8 5.8 2.7 27.2 8 19.5 5.7 2.9 26.8 7.9 19.3 5.7 2.9

1296 38.1 11.2 29.2 8.5 2.3 35.8 10.5 28.3 8.3 2.7 33.6 9.8 27.5 8.1 3.1 32.7 9.6 27.2 8 3.2 32.4 9.5 27.1 7.9 3.3

1178 37.8 11.1 27.9 8.2 2.3 35.5 10.4 27 7.9 2.7 33.2 9.7 26.1 7.7 3.1 32.4 9.5 25.8 7.6 3.2 32 9.4 25.7 7.5 3.3

1005 37.3 10.9 25.9 7.6 2.3 35 10.3 25 7.3 2.7 32.7 9.6 24.1 7.1 3.1 31.8 9.3 23.8 7 3.2 31.4 9.2 23.7 6.9 3.3

1497 44.1 12.9 33.4 9.8 2.4 41.6 12.2 32.4 9.5 2.8 38.8 11.4 31.4 9.2 3.3 37.7 11.1 31 9.1 3.4 37.2 10.9 30.9 9.1 3.5

1361 43.8 12.8 31.9 9.4 2.4 41.2 12.1 30.9 9.1 2.8 38.4 11.3 29.9 8.8 3.3 37.3 10.9 29.5 8.7 3.4 36.9 10.8 29.4 8.6 3.5

1160 42.7 12.5 29.5 8.7 2.4 40.6 11.9 28.7 8.4 2.8 37.8 11.1 27.7 8.1 3.3 36.7 10.8 27.3 8 3.4 36.3 10.6 27.1 7.9 3.5

1761 55.7 16.3 41 12 3.2 52.2 15.3 39.7 11.6 3.7 48.7 14.3 38.4 11.3 4.3 47.4 13.9 37.9 11.1 4.5 46.8 13.7 37.7 11.1 4.6

1601 55.3 16.2 39.3 11.5 3.2 51.8 15.2 38 11.1 3.7 48.2 14.1 36.6 10.7 4.3 46.9 13.7 36.1 10.6 4.5 46.3 13.6 35.9 10.5 4.6

1365 53.7 15.7 36.4 10.7 3.2 51 14.9 35.3 10.3 3.7 47.5 13.9 33.9 9.9 4.3 46.1 13.5 33.4 9.8 4.5 45.5 13.3 33.2 9.7 4.6

1943 62.1 18.2 45.6 13.4 3.8 58.3 17.1 44.2 12.9 4.4 54.6 16 42.8 12.5 4.9 53.3 15.6 42.3 12.4 5.1 52.7 15.4 42.1 12.3 5.2

1766 61.7 18.1 43.7 12.8 3.8 57.8 16.9 42.2 12.4 4.4 54 15.8 40.8 12 4.9 52.7 15.4 40.3 11.8 5.1 52.1 15.3 40 11.7 5.2

1506 59.9 17.6 40.4 11.9 3.8 56.9 16.7 39.2 11.5 4.4 53.2 15.6 37.8 11.1 4.9 51.8 15.2 37.2 10.9 5.1 51.2 15 37 10.8 5.2

118.4°F (48°C) 120°F (48.9°C)

Total Capacity (TC) Sensible Capacity (SC) Sensible Capacity (SC)Sensible Capacity (SC) Total Capacity (TC) Sensible Capacity (SC) Total Capacity (TC) Sensible Capacity (SC)

RX42+

DDP42

RX48+

DDP48

RX54+

DDP54

RX60+

DDP60

Total Capacity (TC)CFM

RX18+

DDP18

RX24+

DDP24

RX30+

DDP30

RX36+

DDP36

Total Capacity (TC)

RX+

DDP

Entering Air Temperature DB/WB-80/67°F (26.6/19.4°C)

95°F (35°C) 105°F (40.6°C) 114.8°F (46°C)

Table 3Notes:

1. Shaded areas represent matched cooling capacities based as per ARI standards 210/240 - 80/67°F (26.6/19.4°C) DB/WB temperature of air entering the indoor coil and 95°F outside air dry bulb. Capacities at other ambient temperatures as shown. 2. For matched conditions,at entering condition other than shown;consult SKM. 3. Direct interpolation is permissible but extrapolation is prohibited. 4. Combination ratings are based on indoor and outdoor units at the same elevation and connected by 25 ft. (7.6 m) of refrigerant tubing.For tubing in excess of 25 feet,slight capacity reduction will occur. Do not exceed 120 feet tubing length without checking with SKM.

5. Matching systems will operate satisfactorily at desert conditions of 125°F (51.7°C) air entering outdoor unit and 80/67°F (26.6/19.4°C) DB/WB air entering the indoor coil. 6. Cooling capacities listed do not include a deduction for fan motor heat. 7. TC - total cooling capacity in Mbh (1000 Btuh) SC - sensible cooling capacity in Mbh (1000 Btuh) PI - Power input in kW (compressor only) To convert Mbh to kW,divide by 3.413. To convert cfm to L/s,divide by 2.12. * Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical data page (7) should be referred for the same.

Page 7: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

7

SKM Ducted Mini Split UnitsRX/DDP - R-410A

Combination Ratings - DDP with RX UnitsAFR

PI* PI* PI* PI* PI*

MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW

686 16.3 4.8 14.4 4.2 0.9 15.4 4.5 14.1 4.1 1.1 14.4 4.2 13.7 4 1.3 14 4.1 13.6 4 1.3 13.8 4.1 13.5 4 1.4

624 16.1 4.7 13.7 4 0.9 15.2 4.5 13.4 3.9 1.1 14.2 4.2 13 3.8 1.3 13.9 4.1 12.9 3.8 1.3 13.7 4 12.8 3.7 1.4

532 15.7 4.6 12.6 3.7 0.9 14.9 4.4 12.3 3.6 1.1 13.9 4.1 11.9 3.5 1.3 13.5 4 11.8 3.4 1.3 13.4 3.9 11.7 3.4 1.4

680 19.7 5.8 15.8 4.6 1.2 18.6 5.4 15.3 4.5 1.4 17.4 5.1 14.8 4.3 1.6 16.9 5 14.6 4.3 1.7 16.7 4.9 14.6 4.3 1.8

618 19.5 5.7 15.1 4.4 1.2 18.4 5.4 14.6 4.3 1.4 17.2 5 14.1 4.1 1.6 16.7 4.9 13.9 4.1 1.7 16.5 4.8 13.8 4.1 1.8

527 19.1 5.6 14 4.1 1.2 18.1 5.3 13.6 4 1.4 16.9 4.9 13.1 3.8 1.6 16.4 4.8 12.9 3.8 1.7 16.2 4.7 12.8 3.7 1.8

777 23.2 6.8 18.3 5.4 1.4 21.9 6.4 17.8 5.2 1.6 20.5 6 17.2 5.1 1.9 19.9 5.8 17 5 2 19.7 5.8 16.9 5 2

706 23 6.7 17.6 5.1 1.4 21.7 6.4 17 5 1.6 20.2 5.9 16.4 4.8 1.9 19.7 5.8 16.2 4.7 2 19.5 5.7 16.1 4.7 2

602 22.4 6.6 16.3 4.8 1.4 21.4 6.3 15.8 4.6 1.6 19.9 5.8 15.2 4.5 1.9 19.3 5.7 15 4.4 2 19.1 5.6 14.9 4.4 2

1041 30.7 9 24.4 7.2 2 28.8 8.4 23.6 6.9 2.3 26.8 7.9 22.8 6.7 2.7 26 7.6 22.5 6.6 2.9 25.7 7.5 22.4 6.6 2.9

922 30.4 8.9 23.1 6.8 2 28.5 8.3 22.3 6.5 2.3 26.4 7.7 21.5 6.3 2.7 25.7 7.5 21.2 6.2 2.9 25.3 7.4 21 6.2 2.9

786 29.7 8.7 21.5 6.3 2 28.1 8.2 20.8 6.1 2.3 26 7.6 19.9 5.8 2.7 25.2 7.4 19.6 5.7 2.9 24.8 7.3 19.4 5.7 2.9

1296 35.6 10.4 29.4 8.6 2.3 33.5 9.8 28.6 8.4 2.6 31.4 9.2 27.7 8.1 3 30.6 9 27.4 8 3.2 30.3 8.9 27.3 8 3.3

1178 35.2 10.3 28.1 8.2 2.3 33.1 9.7 27.2 8 2.6 31 9.1 26.4 7.7 3 30.2 8.9 26 7.6 3.2 29.9 8.8 25.9 7.6 3.3

1005 34.7 10.2 26.1 7.6 2.3 32.5 9.5 25.2 7.4 2.6 30.4 8.9 24.3 7.1 3 29.6 8.7 24 7 3.2 29.2 8.6 23.8 7 3.2

1497 40.7 11.9 33.5 9.8 2.4 38.4 11.2 32.6 9.5 2.8 36 10.5 31.6 9.3 3.3 35.1 10.3 31.2 9.2 3.4 34.7 10.2 31.1 9.1 3.5

1361 40.4 11.8 32 9.4 2.4 37.9 11.1 31 9.1 2.8 35.5 10.4 30.1 8.8 3.3 34.6 10.2 29.7 8.7 3.4 34.2 10 29.5 8.7 3.5

1160 39.8 11.7 29.8 8.7 2.4 37.3 10.9 28.7 8.4 2.8 34.8 10.2 27.7 8.1 3.3 33.9 9.9 27.4 8 3.4 33.5 9.8 27.2 8 3.5

1761 51.6 15.1 41.3 12.1 3.2 48.5 14.2 40 11.7 3.7 45.3 13.3 38.7 11.3 4.3 44.1 12.9 38.2 11.2 4.5 43.6 12.8 38 11.1 4.6

1601 51.2 15 39.5 11.6 3.2 48 14.1 38.1 11.2 3.7 44.7 13.1 36.8 10.8 4.3 43.6 12.8 36.4 10.7 4.5 43 12.6 36.1 10.6 4.6

1365 50.2 14.7 36.7 10.8 3.2 47.3 13.8 35.5 10.4 3.7 43.9 12.9 34.1 10 4.3 42.7 12.5 33.6 9.8 4.5 42.2 12.4 33.3 9.8 4.6

1943 57.6 16.9 45.9 13.4 3.8 54.1 15.9 44.5 13 4.3 50.6 14.8 43.1 12.6 4.9 49.4 14.5 42.6 12.5 5.1 48.8 14.3 42.3 12.4 5.2

1766 57.1 16.7 43.9 12.9 3.8 53.6 15.7 42.4 12.4 4.3 50 14.7 41 12 4.9 48.7 14.3 40.5 11.9 5.1 48.2 14.1 40.2 11.8 5.2

1506 56 16.4 40.9 12 3.8 52.7 15.5 39.4 11.6 4.3 49 14.4 37.9 11.1 4.9 47.7 14 37.3 10.9 5.2 47.1 13.8 37.1 10.9 5.2

118.4°F (48°C) 120°F (48.9°C)

Total Capacity Sensible Capacity Sensible CapacitySensible Capacity Total Capacity Sensible Capacity Total Capacity Sensible Capacity

RX42+

DDP42

RX48+

DDP48

RX54+

DDP54

RX60+

DDP60

Total Capacitycfm

RX18+

DDP18

RX24+

DDP24

RX30+

DDP30

RX36+

DDP36

Total Capacity

RX+

DDP

Entering Air Temperature 76/63°F (24.4/17.2°C)

95°F (35°C) 105°F (40.6°C) 114.8°F (46°C)

Table 4Notes:

1. The capacity ratings are based on 76/63°F (24.4/17.2°C) DB/WB temperature of air entering the indoor coil.

2. For matched conditions,at entering condition other than shown;consult SKM.

3. Direct interpolation is permissible but extrapolation is prohibited.

4. Combination ratings are based on indoor and outdoor units at the same elevation and connected by 25 ft. (7.6 m) of refrigeranttubing.For tubing in excess of 25 feet,slight capacity reduction will occur. Do not exceed 120 feet tubing length without checking with SKM.

5. Cooling capacities listed do not include a deduction for fan motor heat.

6. TC - total cooling capacity in Mbh (1000 Btuh).SC - sensible cooling capacity in Mbh (1000 Btuh).PI - Power input in kW (compressor only).

To convert Mbh to kW,divide by 3.413.

To convert cfm to L/s,divide by 2.12.

* Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical data page (7) should be referred for the same.

Page 8: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

8

SKM Ducted Mini Split UnitsRX/DDP - R-410A

Electrical Data - RX & DDP

Model RX 18 24 30 36 42 48 54 60

8 10 12 17 20 7 9 11

44 52 60 82 97 43 52 64

0.9 0.9 0.9 0.9 2.5 1.1 1.1 1.1

MFA 25 25 32 50 50 20 25 32

MCA 13 15 18 24 30 12 15 17

Unit Size DDP 18 24 30 36 42 48 54 60

Type

Motor Size Watts 150 150 150 150 150 150 150 150

Quantity # 1 1 1 1 2 2 2 2

High 1.3 1.3 1.4 1.3 2.8 2.8 2.6 2.8

Maximum Amps Speed Medium 0.9 0.9 1.1 1.1 2.2 2.2 2.2 2.2

Low 0.8 0.8 0.8 0.8 1.6 1.6 1.6 1.8

230V/1Ph/50Hz, 3 Speed Electric Motor with Permanent Split Capacitor

Electrical

Power Supply 230V/1Ph/50Hz 400V/3Ph/50Hz

Comp. RLA

LRA

Condenser motor FLA

Table 5

Table 6

ThermostatThermostat is wall mounted decorative type, with large LCD and backlight. Buttons are provided for power on/off, fan speed selection, cooling or heating mode selection, set point adjustment and sleep mode selection. Indoor temperature and set point are displayed simultaneously. Apart from that, display provides fan mode (high, medium, low or auto) and operating mode (cool or heat).

Note: Optional remote control and remote sensor are available on request.

Options

Page 9: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

9

SKM Ducted Mini Split UnitsRX/DDP - R-410A

inwg 0.1 0.2 0.3 0.4Pa 25 50 75 100cfm 680 660 636 604l/s 321 312 300 285

cfm 777 753 730 704l/s 367 355 345 332

cfm 1041 983 906 817l/s 491 464 428 386

cfm 1296 1276 1223 1156l/s 612 602 577 546

cfm 1497 1476 1429 1368l/s 706 696 674 645

cfm 1882 1761 1618 1456l/s 888 831 763 687

cfm 2150 1943 1759 1562l/s 1015 917 830 737

cfm 514 498 478 449l/s 243 235 225 212

cfm 601 587 571 549l/s 284 277 270 259

cfm 724 728 706 661l/s 341 344 333 312

cfm 1016 982 937 875l/s 480 463 442 413

cfm 1224 1194 1155 1104l/s 578 563 545 521

cfm 1444 1422 1354 1251l/s 681 671 639 590

cfm 1680 1626 1532 1404l/s 933 869 795 711

cfm 396 381 355 321l/s 187 180 167 152

cfm 482 463 442 419l/s 228 219 209 198

cfm 464 467 474 445l/s 219 220 224 210

cfm 773 738 684 618l/s 365 348 323 291

cfm 951 912 870 822l/s 449 431 411 388

cfm 988 1014 987 889l/s 466 478 466 419

cfm 1150 1168 1117 990l/s 831 804 761 705

Low

24 & 18

30

36

42

48

54

60

54

60

Medium

24 & 18

30

36

42

48

54

60

Speed DDP

4 RowsExternal Static Pressure

High

24 & 18

30

36

42

48

Fan Performance

Table 7

Page 10: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

10

SKM Ducted Mini Split UnitsRX/DDP - R-410A

Recommended Suction and Liquid Line Sizes

Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid18 5/8 3/8 5/8 3/8 3/4 3/8 3/4 3/8 3/4 3/824 5/8 3/8 3/4 3/8 3/4 3/8 3/4 3/8 3/4 3/830 5/8 3/8 5/8 3/8 3/4 3/8 3/4 3/8 3/4 3/836 5/8 3/8 3/4 3/8 3/4 3/8 7/8 1/2 7/8 1/242 3/4 3/8 3/4 3/8 7/8 1/2 7/8 1/2 7/8 1/248 3/4 3/8 7/8 1/2 7/8 1/2 1 1/8 1/2 1 1/8 1/254 3/4 3/8 7/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/260 7/8 1/2 7/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2

RX(Condensing Unit)

Recommended Suction And Liquid Line Sizes For Various Length of Run to Evaporator Side- Ft. (m)

25 (7.6) 50 (15.2) 75 (22.9) 100 (30.5) 120 (36.6)

Notes :

1. Pipe diameters are based on equivalent length of copper tubing sizes. 2. Pipe sizes are based on 2ºF (1.1ºC) or less temperature losses for liquid and suction line in equivalent pipe length. 3. If the condensing unit is below the evaporating unit, the maximum lift should not exceed to 66 feet. 4. Do not exceed 120 feet piping length without checking with SKM. 5. These sizes are for guidance only. For detailed proper piping, refer to recognized piping references like ASHRAE Guide and Data Book. The recommended or required suction and liquid line sizes do not necessarily correspond with the refrigerant connections

available on the outdoor or indoor unit. Necessary transformation may be required and it’s field performed.

Table 8

2

5

34

6

1

Page 11: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

11

SKM Ducted Mini Split UnitsRX/DDP - R-410A

2

5

34

6

1

1

6

4

3

5 2

Typical Refrigeration Piping - RX+DDP

Legend:

1. Outdoor Unit (RX-)2. DDP Fan Coil Unit3. Liquid Line4. Suction Line5. Metering Device 6. Packed Valves

Refrigerant PipingCorrect design and size of refrigerant piping

is necessary for proper operation. The refrigerant piping generally should be designed to accomplish the following:

a. To ensure proper refrigerant feed to the evaporator.

b. To provide practical refrigerant line sizes without excessive pressure drop.

c. To maintain uniform return of lubricating oil to the compressor.

d. To prevent refrigerant from entering the compressor and causing compressor damage due to “slugging”.

RX (OUT DOOR UNIT)

RX (OUT DOOR UNIT)

Page 12: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

12

SKM Ducted Mini Split UnitsRX/DDP - R-410A

Typical Wiring Diagram - RX & DDP

EFAN

MOTOR1

FMFH FLN

(IF APPLICABLE)FAN

MOTOR2

FMN FH FL E

MOTOR BODYEART HING

UN

ITSI

DE

FIELD WIRING (BY OTHERS)

220~2 40 V/1 PH/50 HZ

CONNE CTIONCUSTOMER

JN. BOX FOR

FROM OUTDOOR UNITFIELD CONNECT IONS

1

2

**

L N E

FMN FHL H

OUTDOOR UNIT MODEL (RXV - 020XP, 025XP, 030XP, 035XP & 0 40XP) INDOOR UNIT(D CYP)

CFL

(BY OTHE RS / OPTION)T HERMOSTAT WIT H 3SPEED SWITCH

FIEL

DSI

DEU

NIT

SIDE

CONDENSER FAN

3~

COMPRESSOR

MOTOR

MOTOR

3~

MOTOR

MOTOR

FM

MOTORFAN

1

EFM

MOTORFAN

FH FLN N FH

FIELD WIRING (BY OTHERS)

2

EARTHINGMOTOR BODY

FL E

CONTACTOR

220-

240 V

T2

L2

T3

L3

T1

L1CY CLE TIMER

TO IND OOR UNIT

ANTI SHORTHPS

2

1LPS

(3 80~41 5V / 3PH / 50H Z)**

L3L2 NL1

HEATERCRANKCASE

(AUX. CONTACT)

G rd

GROUNDING LUG

FROM OUTDOOR UNITFIELD CONNECTIONS

JN. BOX FOR

CONNECTIONCUSTOME R

2

**

1

22 0~ 240V/1PH /5 0HZ

L N E

IND OOR UNIT(DCY P)

(BY OTH ERS / OPT ION)

FM

THERMOSTAT WITH 3SPEED SWITCH

NL FH HFL C

FIEL

DSI

DE

TO INDOOR UNIT

OUTDOOR UNIT MODEL (RXV - 045XP, 050XP, 060XP & 070XP)

RUN

CAPA

CITO

R

COMPRESSOR

S

RC

FIELD SUPPLY

FAN MOTOR

EQUIP. GRND.

S

CAPA

CITO

R

R

C

G

L2L1

220~

240V

C1

T2T1

CONTACTOR

NL

(AUX. CONTACT)

CYCLE TIMERANTI SHORT

C

CRANKCASEHEATER

220~240V/1PH/50HZ**

1

0

M

LPS HPS

T ypic al Wiring Diagram - R X V & DC Y P

E

FANMOTOR

1FMFH FLN

(IF APPLICABLE)FAN

MOTOR2

FMN FH FL E

MOTOR BODYEART HING

UN

ITSI

DE

FIELD WIRING (BY OTHERS)

220~2 40 V/1 PH/50 HZ

CONNE CTIONCUSTOMER

JN. BOX FOR

FROM OUTDOOR UNITFIELD CONNECT IONS

1

2

**

L N E

FMN FHL H

OUTDOOR UNIT MODEL (RXV - 020XP, 025XP, 030XP, 035XP & 0 40XP) INDOOR UNIT(D CYP)

CFL

(BY OTHE RS / OPTION)T HERMOSTAT WIT H 3SPEED SWITCH

FIEL

DSI

DEU

NIT

SIDE

CONDENSER FAN

3~

COMPRESSOR

MOTOR

MOTOR

3~

MOTOR

MOTOR

FM

MOTORFAN

1

EFM

MOTORFAN

FH FLN N FH

FIELD WIRING (BY OTHERS)

2

EARTHINGMOTOR BODY

FL E

CONTACTOR

220-

240 V

T2

L2

T3

L3

T1

L1CY CLE TIMER

TO IND OOR UNIT

ANTI SHORTHPS

2

1LPS

(3 80~41 5V / 3PH / 50H Z)**

L3L2 NL1

HEATERCRANKCASE

(AUX. CONTACT)

G rd

GROUNDING LUG

FROM OUTDOOR UNITFIELD CONNECTIONS

JN. BOX FOR

CONNECTIONCUSTOME R

2

**

1

22 0~ 240V/1PH /5 0HZ

L N E

IND OOR UNIT(DCY P)

(BY OTH ERS / OPT ION)

FM

THERMOSTAT WITH 3SPEED SWITCH

NL FH HFL C

FIEL

DSI

DE

TO INDOOR UNIT

OUTDOOR UNIT MODEL (RXV - 045XP, 050XP, 060XP & 070XP)

RUN

CAPA

CITO

R

COMPRESSOR

S

RC

FIELD SUPPLY

FAN MOTOR

EQUIP. GRND.

S

CAPA

CITO

R

R

C

G

L2L1

220~

240V

C1

T2T1

CONTACTOR

NL

(AUX. CONTACT)

CYCLE TIMERANTI SHORT

C

CRANKCASEHEATER

220~240V/1PH/50HZ**

1

0

M

LPS HPS

T ypic al Wiring Diagram - R X V & DC Y P

E

FANMOTOR

1

FMFH FLN

(IF APPLICABLE)FAN

MOTOR2

FMN FH FL E

MOTOR BODYEART HING

UN

ITSI

DE

FIELD WIRING (BY OTHERS)

220~2 40 V/1 PH/50 HZ

CONNE CTIONCUSTOMER

JN. BOX FOR

FROM OUTDOOR UNITFIELD CONNECT IONS

1

2

**

L N E

FMN FHL H

OUTDOOR UNIT MODEL (RXV - 020XP, 025XP, 030XP, 035XP & 0 40XP) INDOOR UNIT(D CYP)

CFL

(BY OTHE RS / OPTION)T HERMOSTAT WIT H 3SPEED SWITCH

FIEL

DSI

DEU

NIT

SIDE

CONDENSER FAN

3~

COMPRESSOR

MOTOR

MOTOR

3~

MOTOR

MOTOR

FM

MOTORFAN

1

EFM

MOTORFAN

FH FLN N FH

FIELD WIRING (BY OTHERS)

2

EARTHINGMOTOR BODY

FL E

CONTACTOR

220-

240 V

T2

L2

T3

L3

T1

L1CY CLE TIMER

TO IND OOR UNIT

ANTI SHORTHPS

2

1LPS

(3 80~41 5V / 3PH / 50H Z)**

L3L2 NL1

HEATERCRANKCASE

(AUX. CONTACT)

G rd

GROUNDING LUG

FROM OUTDOOR UNITFIELD CONNECTIONS

JN. BOX FOR

CONNECTIONCUSTOME R

2

**

1

22 0~ 240V/1PH /5 0HZ

L N E

IND OOR UNIT(DCY P)

(BY OTH ERS / OPT ION)FM

THERMOSTAT WITH 3SPEED SWITCH

NL FH HFL C

FIEL

DSI

DE

TO INDOOR UNIT

OUTDOOR UNIT MODEL (RXV - 045XP, 050XP, 060XP & 070XP)

RUN

CAPA

CITO

R

COMPRESSOR

S

RC

FIELD SUPPLY

FAN MOTOR

EQUIP. GRND.

S

CAPA

CITO

R

R

C

G

L2L1

220~

240V

C1

T2T1

CONTACTOR

NL

(AUX. CONTACT)

CYCLE TIMERANTI SHORT

C

CRANKCASEHEATER

220~240V/1PH/50HZ**

1

0

M

LPS HPS

T ypic al Wiring Diagram - R X V & DC Y P

E

FANMOTOR

1

FMFH FLN

(IF APPLICABLE)FAN

MOTOR2

FMN FH FL E

MOTOR BODYEART HING

UN

ITSI

DE

FIELD WIRING (BY OTHERS)

220~2 40 V/1 PH/50 HZ

CONNE CTIONCUSTOMER

JN. BOX FOR

FROM OUTDOOR UNITFIELD CONNECT IONS

1

2

**

L N E

FMN FHL H

OUTDOOR UNIT MODEL (RXV - 020XP, 025XP, 030XP, 035XP & 0 40XP) INDOOR UNIT(D CYP)

CFL

(BY OTHE RS / OPTION)T HERMOSTAT WIT H 3SPEED SWITCH

FIEL

DSI

DEU

NIT

SIDE

CONDENSER FAN

3~

COMPRESSOR

MOTOR

MOTOR

3~

MOTOR

MOTOR

FM

MOTORFAN

1

EFM

MOTORFAN

FH FLN N FH

FIELD WIRING (BY OTHERS)

2

EARTHINGMOTOR BODY

FL E

CONTACTOR

220-

240 V

T2

L2

T3

L3

T1

L1CY CLE TIMER

TO IND OOR UNIT

ANTI SHORTHPS

2

1LPS

(3 80~41 5V / 3PH / 50H Z)**

L3L2 NL1

HEATERCRANKCASE

(AUX. CONTACT)

G rd

GROUNDING LUG

FROM OUTDOOR UNITFIELD CONNECTIONS

JN. BOX FOR

CONNECTIONCUSTOME R

2

**

1

22 0~ 240V/1PH /5 0HZ

L N E

IND OOR UNIT(DCY P)

(BY OTH ERS / OPT ION)FM

THERMOSTAT WITH 3SPEED SWITCH

NL FH HFL C

FIEL

DSI

DE

TO INDOOR UNIT

OUTDOOR UNIT MODEL (RXV - 045XP, 050XP, 060XP & 070XP)

RUN

CAPA

CITO

R

COMPRESSOR

S

RC

FIELD SUPPLY

FAN MOTOR

EQUIP. GRND.

S

CAPA

CITO

R

R

C

G

L2L1

220~

240V

C1

T2T1

CONTACTOR

NL

(AUX. CONTACT)

CYCLE TIMERANTI SHORT

C

CRANKCASEHEATER

220~240V/1PH/50HZ**

1

0

M

LPS HPS

T ypic al Wiring Diagram - R X V & DC Y P

OUTDOOR UNIT RX18, 24, 30, 36 & 42

OUTDOOR UNIT RX48, 54 and 60

INDOOR UNIT DDP

INDOOR UNIT DDP

Page 13: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

13

SKM Ducted Mini Split UnitsRX/DDP - R-410A

Model: RX Models: 36, 42, 48, 54 & 60

Dimensional Data OUTDOOR UNITS - RX Models: 18, 24 & 30MODELS: RXV- 020XP, 025PXP, 030XP

ACCESS

CABLE ENTRY HOLE Ø25MM(WITH RUBBER GROMMET)

30[762]

2[51]

2 [50]

32 [813

]

32.9

[835

].9 [22]

SUCTION Ø

LIQUID Ø

2

1.8[45]

2 [50] 0.75

[19]

30[762]

0.79

[20]

30[762]

3

1

30 [762

]

26.1

[662

]

4

4. CONDENSER COIL

1. CONDENSER FAN

3. CONTROL PANEL

2. COMPRESSOR

L E G E N D

MODELS: RXV- 036XP, 040XP, 045XP, 050XP, 060XP

.9 [22]

25[635]

32.9

[835

]32 [813

]

LIQUIDØ

SUCTIONØ

2

3

(WITH RUBBER GROMMET)CABLE ENTRY HOLE Ø25MM

25[635]

1

2 [50]

MOUNTING HOLES

25[635]

2[51]

25 [635

]21

.1[5

35]

4.7

[19]

2 [50]

Ø3/8[9.5] x 4 NOS.

.8 [20]

ACCESS

MODELS: RXV- 020XP, 025PXP, 030XP

ACCESS

CABLE ENTRY HOLE Ø25MM(WITH RUBBER GROMMET)

30[762]

2[51]

2 [50]

32 [813

]

32.9

[835

].9 [22]

SUCTION Ø

LIQUID Ø

2

1.8[45]

2 [50] 0.75

[19]

30[762]

0.79

[20]

30[762]

3

1

30 [762

]

26.1

[662

]

4

4. CONDENSER COIL

1. CONDENSER FAN

3. CONTROL PANEL

2. COMPRESSOR

L E G E N D

MODELS: RXV- 036XP, 040XP, 045XP, 050XP, 060XP

.9 [22]

25[635]

32.9

[835

]32 [813

]

LIQUIDØ

SUCTIONØ

2

3

(WITH RUBBER GROMMET)CABLE ENTRY HOLE Ø25MM

25[635]

1

2 [50]

MOUNTING HOLES

25[635]

2[51]

25 [635

]21

.1[5

35]

4.7

[19]

2 [50]

Ø3/8[9.5] x 4 NOS.

.8 [20]

ACCESS

Page 14: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

14

SKM Ducted Mini Split UnitsRX/DDP - R-410A

DDP INDOOR UNITS

DDPUNIT

MODEL

18/24

A B C E F

INCH MMINCH MMINCH MMINCH MMMMINCH

33 838 21.5 546 11.68 297 15 381

3811564825.59403730

64825.59403742

3811595237.512454936

38115110543.513975554

110543.513975560

125749.51549611

LEGEND

1 INSULATED R.A.PLENUM

SUPPLY FAN2

FAN MO TOR3

COOLING COIL4

6 FILTER

5 ACCESS PANEL

18 457

40616

MMINCH

G

12

12

12

14.5

305

305

305

368

D

INCH

12

MM

305

14.5 368

14.5 36851

45

45

39

27

27

23

1295

1143

1143

991

686

686

584

29711.68

11.68 297

29711.68

30311.93

11.93 303

11.93 303

44017.32

17.32 440

17.32 440

16 406

18 457

16 406

18 457

18 457

103/8

MMINCH INCH MM INCH INCHMM MM3R 4R 3R 4R

LIQUIDØ SUCTION Ø

3/8 10

3/8 1010 3/8

3/8 1010 3/8

3/8 1010 3/8

1/2 13 13

1/2 13

1/2 13 13

13

5/8 16 5/8 16

5/8 16 165/8

5/8 16 165/8

5/8 16 227/8

7/8 22 227/8

1 1/8 29

1 1/8 29 1 1/8 29

291 1/8

1/2

1/2

1/2

CONNECTION SIZES

(DUCT ED)REAR RETURN-OPTIONAL

REMOVALFILTER

C0.75[19]

0.75[19]

L

F

REMOVALFILTER

5

6

G E

DRAINØ3/4

2[51]

1[25]

1

2

TERMINALCONNECTION

A 8.5[216]

3

4

I

J1 [25]

I

1.5[38]

B

L

MK

C0.75[19]

0.75[19]

2[51]

1

2

TERMINALCONNECTION

A 8.5[216]

3

4

I

1.5[38]

B

L

MK

F

6

E

LIQUID

SUCTIO N

Dx

A

FREE RETURN-STANDARD

K L M

66326.12 76029.93 200.79

559

MM

22

INCH

703

MM

27.68

INCH INCH

2.64

MM

67

DIMENSIONS FOR

3R / 4R

3R / 4R

J I

MMINCH MMINCH

2098.22 2329.13

2098.22 2329.13

26310.34 2329.13

2098.22 2329.13

2098.22 2329.13

26310.34 2329.13

26310.34 2329.13

4-5/8 ØMTG.HOLES

GROMMETSW IT H RUBBER

[16]

[19]DRAINØ3/4[19]

UNIT SIZES 18 - 36 UNITSIZES 42 - 60

1/2 13 13 1 1/8 29 1 1/8 291/226310.34 2329.1311.93 303 17.32 440 18 45714.5 368141055.521596724 57 1448

H NNNN

H

MM

N

MMINCH INCH

-- 1766.93

2278.94

2278.94

1515.9

1897.4

1897.4

2278.93

26510.4345414.87

37814.87

30111.9

30111.9

2258.9

--

--

LIQUID

SUCTION

DDPUNIT

MODEL

18/243042

365460

ALL DIMENSIONS ARE IN INCHES [MM]

Dimensional Data

Page 15: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

15

SKM Ducted Mini Split UnitsRX/DDP - R-410A

Outdoor Unit Clearance & Spacing

No obstacle

MULTIPLE UNITS

45[1143]

SINGLE UNIT

AIR OUT

30 [762

]14 [356

]

30[762]

30[762]

30 [762

]14 [356

]

AIR IN

AIR IN

SPACING FOR AI RFLOW

SPACING FORSERVICE

30 [762

]14 [356

]

30[762]

30[762]

SPACING FOR AI RFLOW

SPACING FORSERVICE

SUCTION

AIR IN

LIQUID

POWERSOURCE

CONTROLPANEL

CONTROL CIRCUIT

ALL DIMENSIONS ARE IN INCHES[MM]

Page 16: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

16

SKM Ducted Mini Split UnitsRX/DDP - R-410A

Ducted mini split Air Conditioning system shall composed of a compact design indoor fan coil unit and floor or Rooftop mounted outside air cooled condensing unit, rated with AHRI standards 210/240.

CONDENSING UNIT: The condensing unit shall be composed of compressor, condenser, coil, condenser fan and motor.

CONDENSER COIL The condenser coil shall be air cooled constructed of high efficiency inner grooved copper tube mechanically expanded into hi-efficiency aluminum fins and tested against leakage by high pressure under water.

COMPRESSOR • Compressor shall be hermetic scroll type, refrigerant gas cooled, furnished with internal high temperature motor overload protection device. • Compressor have an internal pressure relief assembly to protect against excessive pressure differential.

CONDENSER FANFor top discharge air delivery, the fan shall be equipped with statically and dynamically balanced alloy blades, and inherent corrosion resistant shaft. Complete fan assembly is mounted downward on the strong and acrylic coated fan guard.

MOTORThe motor shall be totally enclosed air over (TEAO), six pole.

CONTROLSCondensing unit shall be provided with a control panel enclosure comprising all electrical control devices except for the field supplied room thermostat and shall include the following components as minimum: • Compressor and condenser fan motor contactor• Anti recycling time delay relay• Terminal for external connections.

INDOOR UNIT: The indoor unit/air handler shall be composed of evaporator coil, fan motor assembly and the metering device.

EVAPORATOR COILEvaporator coil shall be constructed of high efficiency copper tubes, mechanically bonded to aluminium fins. The coil consists of headers of seamless copper and flow control distributor.

EVAPORATOR FANFan shall be double inlet, double width, direct driven with centrifugal type wheel. Fan wheel shall be with multi forward curved blades. Fan shall be statically and dynamically balanced. Fan housing and wheel shall be made of galvanized steel sheet.

MOTORMotor shall be single phase, 3 speed permanent split capacitor type, suitable for 220-240V/1Ph/50-60Hz.Highly efficient with integral thermal protection. Motor shall have high power factor and shall be with permanent lubricated sleeve bearings.

METERING DEVICEIndoor unit shall be equipped with special type thermostatic expansion valve for R410A refrigerant.

CASINGThe unit casing shall be made of zinc coated galvanized steel sheets conforming to JIS-G3302 and ASTM-A525 that shall be phospatized and then electro statically dry powder coated of approx 60 microns to provide an extremely tough, scratch resistance, and excellent anti corrosive protection.

GUIDE SPECIFICATIONS

Page 17: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

17

SKM Ducted Mini Split UnitsRX/DDP - R-410A

NOTES

Page 18: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

18

SKM Ducted Mini Split UnitsRX/DDP - R-410A

NOTES

Page 19: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

19

SKM Ducted Mini Split UnitsRX/DDP - R-410A

NOTES

Page 20: Ducted Mini Split System - S.K.M Air Conditioning LLC · 2 SKM Ducted Mini Split Units RX/DD R-410A Contents Legend The following legends are used throughout this manual: Introduction

20

SKM Ducted Mini Split UnitsRX/DDP - R-410A

REGIONAL OFFICES

For SKM Distributors visit:

www.skmaircon.com

Email: [email protected]

Spare Parts DivisionEmail: [email protected]

Service Centre

HEAD OFFICEP.O Box: 6004Sharjah, United Arab EmiratesTel: +971 6 514 3333Fax: +971 6 514 3300Email: [email protected] Email: [email protected]

KuwaitDasmanP.O Box: 1215-PC 15463Tel: +965 2 2492200Fax: +965 2 2494400Email: [email protected]

SKM Air Conditioning Factory Eastern provinceAD Dammam2nd industrial cityAbqiq main road Hail StreetTel: +966 3 8123332 / 4 / 5Fax: +966 3 8123337 / +966 3 8123092Email: [email protected]

Saudi Arabia(Production Facility)

Algeria

Aissat Idir ( EX-ENMA) CityBldg1, Flat 2, Dar El Beida AlgiersTel: +213 21 508197Fax: +213 21 508197Email: [email protected]

Abu DhabiP.O Box: 27788Tel: +971 2 6445223Fax: +971 2 6445145Email: [email protected]

United Arab Emirates

DubaiP.O Box: 98822Tel: +971 4 2940900Fax: +971 4 2940029Email: [email protected]

124/2016