J-107
TCN Series
SENSORS
CONTROLLERS
MOTION DEVICES
SOFTWARE
(J)TemperatureControllers
(K)SSRs
(L)PowerControllers
(M)Counters
(N)Timers
(O)Digital Panel Meters
(P)Indicators
(Q)Converters
(R)Digital Display Units
(S)SensorControllers
(T)SwitchingMode PowerSupplies
(U)Recorders
(V)HMIs
(W)Panel PC
(X)Field NetworkDevices
FeaturesDual Display, PID Control Temperature Controller
Realizesidealtemp.controllingwithnewlydevelopedPIDcontrolalgorithmand100mshighspeedsamplingBuilt-in relay output or SSR drive output selectable : Enables to phase control and cycle control with SSR drive output (SSRP function)DramaticallyincreasedvisibilityusingwidedisplaypartEnhancedconvenienceofwiringandmaintenancebyconnectorplugtype(TCN4S- -P)
Mountingspacesavingwithcompactdesign:Approx.38%reducedsizecomparedwithexistingmodel(depth-based)
Ordering Information
SpecificationsSeries TCN4S TCN4M TCN4H TCN4L Powersupply
ACpower 100-240VACᜠ50/60HzAC/DCpower 24VACᜠ50/60Hz,24-48VDCᜡ
Allowablevoltagerange 90to110%ofratedvoltagePowerconsumption
ACpower Max.5VA(100-240VAC50/60Hz)AC/DCpower Max.5VA(24VAC50/60Hz),max.3W(24-48VDC)
Displaymethod 7-segment(PV:red,SV:green),Otherdisplay(green,red)LEDCharactersize
PV(W×H) 7.0×15.0mm 9.5×20.0mm 7.0×14.6mm 11.0×22.0mmSV(W×H) 5.0×9.5mm 7.5×15.0mm 6.0×12.0mm 7.0×14.0mm
Inputtype RTD DPt100Ω,Cu50Ω(allowablelineresistancemax.5Ωperawire)Thermocouple K(CA),J(IC),L(IC),T(CC),R(PR),S(PR)
Displayaccuracy※1
RTD Atroomtemperature(23 ±5):(PV±0.5%or±1, select the higherone)±1-digitOutofroomtemperaturerange:(PV±0.5%or±2, select the higherone)±1-digitForTCN4S- -P,add±1byaccuracystandard.Thermocouple
Controloutput
Relay 250VACᜠ3A,30VDCᜡ3A,1aSSR 12VDCᜡ±2V20mAMax.
Alarmoutput AL1,AL2Relayoutput:250VAC1A1aControlmethod ON/OFFcontrol,P,PI,PD,PIDcontrolHysteresis 1to100/ (0.1to50.0/)variableProportionalband(P) 0.1to999.9/Integraltime(I) 0to9999secDerivativetime(D) 0to9999secControlperiod(T) 0.5to120.0secManualreset 0.0to100.0%Samplingperiod 100ms※1: Atroomtemperature(23±5)
ThermocoupleR(PR),S(PR),below200: (PV±0.5%or±3, select the higherone)±1-digit ThermocoupleR(PR),S(PR),over200:(PV±0.5%or±2, select the higherone)±1-digit ThermocoupleL(IC),RTDCu50Ω:(PV±0.5%or±2, select the higherone)±1-digit
Outofroomtemperaturerange ThermocoupleR(PR),S(PR),below200: (PV±1.0%or±6, select the higherone)±1-digit ThermocoupleR(PR),S(PR),over200:(PV±0.5%or±5, select the higherone±1-digit ThermocoupleL(IC),RTDCu50Ω:(PV±0.5%or±3, select the higherone)±1-digitForTCN4S- -P,add±1byaccuracystandard.
Settingtype
Item
Digit
Size
Auxiliaryoutput
Powersupply
Controloutput
Wiringmethod No-mark BoltwiringmethodP Connectorplugconnectionmethod※1
R Relaycontactoutput+SSRdriveoutput※2
2 24VAC50/60Hz,24-48VDC4 100-240VAC50/60Hz
2 Alarm1+Alarm2output
S DINW48×H48mmM DINW72×H72mmH DINW48×H96mmL DINW96×H96mm
4 9999(4-digit)
CN Dualdisplaytype,setbytouchswitch
T Temperaturecontroller
CNT S 2 P4 R4
1: OnlyforTCN4Smodel. 2:IncaseoftheACvoltagemodel,SSRdriveoutputmethod(standardON/OFFcontrol,cyclecontrol,phasecontrol)isavailabletoselect.
Please read “Safety Considerations” in the instruction manual before using.
J-108
TCN Series
Specifications
Connections
TCN4S
TCN4M
※ TCN4Serieshasselectablecontroloutput;Relayoutput,andSSRdriveoutput.AC/DCvoltagetypedoesnothaveSSRPfunction.
※2: Theweightincludespackaging.Theweightinparenthesisisforunitonly.※Environmentresistanceisratedatnofreezingorcondensation.
※1:PowersupplyACpower:100-240VAC5VA50/60HzAC/DCpower:24VAC5VA50/60Hz,24-48VDC3W
Series TCN4S TCN4M TCN4H TCN4L Dielectricstrength
ACPower 2,000VAC50/60Hzfor1min(betweeninputterminalandpowerterminal)AC/DCpower 1,000VAC50/60Hzfor1min(betweeninputterminalandpowerterminal)
Vibration 0.75mmamplitudeatfrequencyof5to55HzineachX,Y,Zdirectionfor2hours
Relaylifecycle
Mechanical OUT:over5,000,000times,AL1/2:Over5,000,000times
Electrical OUT:over200,000times(250VAC3Aresistiveload)AL1/2:over300,000times(250VAC1Aresistiveload)
Insulationresistance Over100MΩ(at500VDCmegger)Noiseimmunity ±2kVR-phase,S-phasethesquarewavenoise(pulsewidth:1us)bythenoisesimulatorMemoryretention Approx.10years(whenusingnon-volatilesemiconductormemorytype)
Environ-ment
Ambienttemperature -10to50,storage:-20to60Ambienthumidity 35to85%RH,storage:35to85%RH
Insulationtype Double insulationorreinforced insulation(mark: ,dielectricstrengthbetweenthemeasuring inputpartandthepowerpart:ACpower2kV,AC/DCPower1kV)
Approval
Weight※2 Approx.147g(approx.100g)
Approx.203g(approx.133g)
Approx.194g(approx.124g)
Approx.275g(approx.179g)
13
19
14
20
15
21
16
22
17
23
18
24
SSROUT:12VDC±2V20Max.
※1SOURCE:100-240VAC5VA50/60,24VAC5VA50/60,24-48VDC3W
B' RTD TC
SENSOR
AL1OUT:250VAC1A1a
AL2OUT:250VAC1A1a
RelayOUT:250VAC3A1a30VDC3A1a
B
A
1
7
2
8
3
9
4
10
5
11
6
12
1 7
2 8
3 94 10
5 116 12
SSROUT:12VDC±2V20mAMax. SSROUT:
12VDC±2V20mAMax.
※1 ※1SOURCE:100-240VAC5VA50/60,24VAC5VA50/60,24-48VDC3W
SOURCE:100-240VAC5VA50/60,24VAC5VA50/60,24-48VDC3W
B' RTD TC
SENSOR
AL1OUT:250VAC1A1a
AL2OUT:250VAC1A1a
RelayOUT:250VAC3A1a30VDC3A1a
B
A
TCN4H/L1
7
2
8
3
9
4
5
6
10
11
12
13
14
15
16
17
18
SSROUT:12VDC±2V20Max.
※1
SOURCE:100-240VAC5VA50/60,24VAC5VA50/60,24-48VDC3W
B' RTD TC
SENSOR
AL1OUT:250VAC1A1a
AL2OUT:250VAC1A1a
RelayOUT:250VAC3A1a30VDC3A1a
B
A
TCN4S- -PAL1OUT250VAC1A1aAL2OUT250VAC1A1a
B'
RTD
B
A
RelayOUT250VAC3A1a30VDC3A1a
TC
<Crimpterminal>
a
bc
Terminalnumber a b c1to8 6 Max.1.7 Max.3.79to11 6to8 Max.2.1 Max.4.212to14 6to8 Max.1.5 Max.3.5
(unit:mm)※Usecrimpterminalsorteminalsofsizespecifiedbelow.
a b
<Round>
a b
<Forked>a Min.3.0 Min.3.0b Max.5.8 Max.5.8
J-109
Dual Display, PID Control
SENSORS
CONTROLLERS
MOTION DEVICES
SOFTWARE
(J)TemperatureControllers
(K)SSRs
(L)PowerControllers
(M)Counters
(N)Timers
(O)Digital Panel Meters
(P)Indicators
(Q)Converters
(R)Digital Display Units
(S)SensorControllers
(T)SwitchingMode PowerSupplies
(U)Recorders
(V)HMIs
(W)Panel PC
(X)Field NetworkDevices
Dimensions (unit:mm)
TCN4S
TCN4M
TCN4L
Bracket
45
64.5648 TCN4S- -P
48
44.8
561.7
11.56
64.5
67.5
672 TCN4H
96
48
91.5
64.56
91.5
64.5696
TCN4SSeries TCN4M,TCN4H,TCN4LSeries
46
23.9
12
37.5
40.5
3.3
4 Panel cut-out
SizeSeries
A B C D
TCN4S Min.65 Min.65 45 0.60 45 0.6
0
TCN4M Min.90 Min.90 68 0.70 68 0.7
0
TCN4H Min.65 Min.115 45 0.60 92 0.8
0
TCN4L Min.115 Min.115 92 0.80 92 0.8
0
A
C
D
B
31
55
56
20
1521
545
16
48.6
44.9 36
J-110
TCN Series
4. Auto tuning indicator: ATindicatorflashesbyevery1secduringoperatingautotuning.5. key:Usedwhenenteringintoparametersettinggroup,returningtoRUNmode,movingparameter,andsavingsettingvalues.
6. Adjustment: Usedwhenenteringintosetvaluechangemode,digitmovinganddigitup/down.7. Digital input key:Press + keysfor3sectooperatethesetfunction(RUN/STOP,alarmoutputreset,autotuning)indigitalinputkey[DI-K].
8. Temperature unit (/) indicator:Itshowscurrenttemperatureunit.
Unit Description
SV Setting
Parameter Reset
1
2345 6
7
8
Youcansetthetemperaturetocontrolwith keys.SettingrangeiswithinSVlowerlimitvalue[L-SV]toSVhigherlimitvalue[H-SV].E.g.)Incaseofchangingsettemperaturefrom210ºCto250ºC
1. Present value (PV) display (red) RUNmode:Currentlymeasuredvalue(PV)display. Parametersettingmode:Parameterdisplay.
2. Setting value (SV) display (green) RUNmode:Settingtemperaturevalue(SV)display. Parametersettingmode:Parametersettingvaluedisplay.
3. Control/Alarm output display indicator OUT:ItturnsONwhenthecontroloutputisON. ※DuringSSRdriveoutputtypeinCYCLE/PHASEcontrol,thisindicator
turnsONwhenMVisover3.0%.(onlyACvoltagetype) AL1/AL2:ItturnsONwhenthealarmoutputisON.
Terminal cover (sold separately)
Dimensions (unit:mm)
RSA-COVER(48×48mm)
RMA-COVER(72×72mm)
RHA-COVER(48×96mm)
RLA-COVER(96×96mm)
70
68.5
3
64
13
91.5
86
4
13
47.2
91.5
86
3
13
9448.4
9.8
41.5
18 22
22.5
ChangeSVby , , keys
Pressanykeyamong , , , once.
①RUNmode
②SVsettingmode ③CompletesSVsetting
④CheckSV
Resetallparametersasfactorydefault.Holdthefront + + keysfor5sec,toenterparameterreset[INIT]parameter.Select'YES'andallparametersareresetasfactorydefault.Select‘NO’andprevioussettingsaremaintained.Ifsettingparameterlock[LOC]orprocessingauto-tuning,parameterresetisunavailable.
J-111
Dual Display, PID Control
SENSORS
CONTROLLERS
MOTION DEVICES
SOFTWARE
(J)TemperatureControllers
(K)SSRs
(L)PowerControllers
(M)Counters
(N)Timers
(O)Digital Panel Meters
(P)Indicators
(Q)Converters
(R)Digital Display Units
(S)SensorControllers
(T)SwitchingMode PowerSupplies
(U)Recorders
(V)HMIs
(W)Panel PC
(X)Field NetworkDevices
Parameter Group
※Press keyover3secinanysettinggroup,itsavesthesetvalueandreturnstoRUNmode.(Press keyonceinSVsetting,itreturnstoRUNmode).※Ifnokeyenteredfor30sec,itreturnstoRUNmodeautomaticallyandthesetvalueofparameterisnotbesaved.※Press keyagainwithin1secafterreturningtoRUNmode,itadvancesofthefirstparameterofprevioussettinggroup.※Press keytomovenextparameter.※ Thisparametermightnotbedisplayeddependingonotherparametersettings.※ Setparameteras'Parametergroup2→Parametergroup1→Settingofsetvalue'orderconsideringparameterrelationofeachsettinggroup.
※1:ItisnotdisplayedforAC/DCpowermodel(TCN4 -22R).
Run mode
SV setting Parameter group 1 Parameter group 2
AL1alarmtemperature
AL2alarmtemperature
Inputsensor
Temperatureunit
Inputcorrection
Inputdigitalfilter
SVlow-limitvalue
SVhigh-limitvalue
ControloutputoperationControltype
Controloutputtype
SSRdriveoutputmethod※1
Controlcycle
AL1alarmoperationmode
AL2alarmoperationmode
Alarmoutputhysteresis
LBAmonitoringtime
LBAdetectionband
Digitalinputkey
ControloutputMVincaseof
inputbreakerrorParameter
lock
Autotuning
Proportionalband
Integraltime
Derivativetime
Manualreset
Hysteresis
Pressanykeyamong, , ,
PAR1
IN-Tㅑㅑ MAvF
PAR2
AL1 UNIT IN-Bㅑㅑ
L-SV H-SV O-FTC-MD
OUT SSrM T AL-1
AL-2AHYSLBaTLBaㅑㅑB
DI-K ErMV LOC
AL2
AT
P
I
D
REST
HYS
2sec
3sec 3sec
4sec
J-112
TCN Series
※1:S :Pressanykeyamong , , .※2:Aftercheckingorchangingsettingvalueineachparameter,press keytosave
andmovetonextparametersetting.※3:Itisdisplayedwhencontroltypeparameter[C-MD]ofparametergroup2isset PID.※Press keyfor3sectoreturnRUNmodeatanyparameter.※ Thisparametermightnotbedisplayeddependingonotherparametersettings.
※1:S :Pressanykeyamong , , .※2:Aftercheckingorchangingsettingvalueineachparameter,press keytosave
andmovetonextparametersetting.※3:Itisdisplayedwhencontroltypeparameter[C-MD]ofparametergroup2isset PID.※Press keyfor3sectoreturnRUNmodeatanyparameter.※ Thisparametermightnotbedisplayeddependingonotherparametersettings.
Settingrange:Deviationalarm(-F.StoF.S),Absolutevaluealarm(temperaturerange)※ Incasealarmoperationmode[AL-2]ofParametergroup2isAM)_/SBa /BA ,noparametersisdisplayed.
Settingrange:0.1to999.9/
Settingrange:0to9999sec※IntegraloperationisOFFwhensetvalueis"0".
Settingrange:0to9999sec※DerivativeoperationisOFFwhensetvalueis"0".
Settingrange:0.0to100.0%※ItisdisplayedinP,PDcontrol.
Settingrange KCaH, JIcH,LIcH,TCcH,RPR,SRP,DPtH,CUsH:1to100/ KCaL, JIcL,LIcL,TCcL,DPtL,CUsL:0.1to50.0/※Itisdisplayedwhencontroltype[C-MD]ofparametergroup2issetONOF.
※FrontATindicatorflashesduringautotuningoperation.
Settingrange KCaH, JIcH,LIcH,TCcH,RPR,SRP,DPtH,CUsH:-999to999/ KCaL, JIcL,LIcL,TCcL,DPtL,CUsL:-199.9to999.9/
Settingrange:0.1to120.0sec※ Setinputdigitalfiltertimeforaverageinputvalueaffectedcontrol,anddisplayvalue.
※ Ifchangingtemperatureunit,SV, IN-B, H-SV, L-SV,AL1, AL2, LBaT, LBaB, AHYSparametervaluesareinitialized.
Settingrange:Referto'Inputsensorandtemperaturerange'.
※ Ifchanginginputsensor,SV, IN-B, H-SV, L-SV,AL1, AL2, LBaT, LBaB, AHYSparametervaluesareinitialized.
Parameter Group 1
Parameter Group 2
Settingrange:Deviationalarm(-F.StoF.S),Absolutevaluealarm(temperaturerange)※ Incasealarmoperationmode[AL-1]ofParametergroup2isAM)_/SBa /BA ,noparametersisdisplayed.
AL1alarmtemperature
AL2alarmtemperature
Auto-tuning
Proportionalband
Integraltime
Derivationtime
Manualreset
Hysteresis
Run mode
※3
PAR1
AL1
AL2
AT
P
I
D
REST
HYS
1250
1250
OFF ON
01)0
0000
0000
05)0
002
S
S
S
S
S
S
S
※1S
※2
2sec 3sec
Inputsensor
Temperatureunit
Inputcorrection
Inputdigitalfilter
PAR2
IN-T KCaH KCaL CUsL
UNIT ?C ?F
IN-B 0000
MAvF 00)1
※1S
S
S
S
※2
4sec
3sec
Run mode
J-113
Dual Display, PID Control
SENSORS
CONTROLLERS
MOTION DEVICES
SOFTWARE
(J)TemperatureControllers
(K)SSRs
(L)PowerControllers
(M)Counters
(N)Timers
(O)Digital Panel Meters
(P)Indicators
(Q)Converters
(R)Digital Display Units
(S)SensorControllers
(T)SwitchingMode PowerSupplies
(U)Recorders
(V)HMIs
(W)Panel PC
(X)Field NetworkDevices
※Whenchangingcontroloutputoperation,ErMVisinitialized.
※ Whenchangingcontroltype,ErMVisinitialized(controloutputMVisbelow100%)andDI-T turnsOFFautomatically.
※Itisdisplayedwhenselectingcontroloutput[OUT]asSSR.ItisnotdisplayedforAC/DCpowermodel(TCN4 -22R).
Settingrange:0.5to120.0secIncaseofRelayoutput[RLY]ofcontroloutput[OUT]itissetas20.0secIncaseofSSRdriveoutput[SSR]ofthat,itissetas2.0sec※TisnotdisplayedwhenSSRdriveoutput[SSrM]methodissetasCYCL, PHAS.
Settingrange:0to9999sec※'0'isset,loopbreakalarmfunctionisOFF.※LBaTisdisplayedwhenAL1,AL2alarmoperationmode[AL-1,AL-2]issetasLBa.
Settingrange:0to999(0.0to999.9)/※'0'isset,loopbreakalarmfunctionisOFF.※ LBaBisdisplayedwhenAL1,AL2alarmoperationmode[AL-1,AL-2]issetasLBa andLBaTisnot'0'.
Settingrange:0.0to100.0%※Only0.0,100%aredisplayedwhencontroltype[C-MD]issetasONOF.※WhenchangingPIDcontroltoON/OFFcontrol,ifMVisbelow100.0%,itisinitializedas0.0%.
Settingrange:Withintheratedtemperaturerangebyinputsensor[L-SV ≤(H-SV-1-digit)]※ When changing SV low-limit value, if SV<L-SV, SV is initialized as L-SV.※ Incaseofchanginginputsensortype[IN-T],itchangesautomaticallyasmin.valueofthechangedinputsensor.
Settingrange:Withintheratedtemperaturerangebyinputsensor[H-SV ≥(L-SV+1-digit)]※ When changing SV high-limit value, if SV>H-SV, SV is initialized as H-SV.※ Incaseofchanginginputsensortype[IN-T],itchangesautomaticallyasmax.valueofthechangedinputsensor.
Formoredetails,referto' Alarm'in Functions.※Black:Flashes,Gray:Fixed※ WhenchangingAL1,AL2alarmoperationmode,AL1,AL2alarmtemperaturevalueareinitialized.
Press + keysfor3secanditexecutesthesetfunction.Formoreinformation,referto' Digitalinputkey'in Functions.※Whencontroltype[C-MD]isONOF,ATisnotdisplayed.
LOC1:Locksparametergroup2LOC2:Locksparameter1,2groupLOC3:Locksparameter1,2groupandSVsetting※ Parametersettingvaluesarestillpossibletocheckwhenparameterlockisset.
Referto' Alarmoutputhysteresis'in Functions.※ AHYSisnotdisplayedwhenAL1,AL2alarmoperationmode[AL-1,AL-2]issetasAM)_,SBa ,LBa .
SVlow-limitvalue
SVhigh-limitvalue
Controloutputoperation
Controltype
Controloutputtype
SSRdriveoutputmethod
Controlcycle
AL1alarmoperationmode
AL2alarmoperationmode
Alarmoutputhysteresis
LBAmonitoringtime
LBAdetectionband
Digitalinputkey
ControloutputMVincaseofinputbreakerror
Parameterlock
L-SV
H-SV
O-FT
C-MD
OUT
SSrM
AL-1
AL-2
DI-K
LBaB
LBaT
AHYS
T
ErMV
LOC
STND
AM!A
AM@A
STOP
0002
0000
001
02)0
AlRE AT OFF
00)0
OFF LOC1 LOC2 LOC3
CYCL PHAS
-050
1200
HEAT
PID
RLY
COOL
ONOF
SSR
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
J-114
TCN Series
Factory Default
Input Sensor and Temperature RangeInputsensor Display Temperaturerange() Temperaturerange()
Thermocouple
K(CA)KCaH -50to1200 -58to2192KCaL -50.0to999.9 -58.0to999.9
J(IC)JIcH -30to800 -22to1472JIcL -30.0to800.0 -22.0to999.9
L(IC)LIcH -40to800 -40to1472LIcL -40.0to800.0 -40to999.9
T(CC)TCcH -50to400 -58to752TCcL -50.0to400.0 -58.0to752.0
R(PR) R PR 0to1700 32to3092S(PR) S PR 0to1700 32to3092
RTDDPt100Ω
DPtH -100to400 -148to752DPtL -100.0to400.0 -148.0to752.0
Cu50ΩCUsH -50to200 -58to392CUsL -50.0to200.0 -58.0to392.0
Mounting TCN4S (48×48mm) Series Other Series
※Mounttheproductonthepanel,fastenbracketbypushingwithtoolsasshownabove.
Parameter group 1
Parameter group 2
SV setting
Parameter Factorydefault Parameter Factorydefault Parameter Factorydefault Parameter Factorydefault
IN-T KCaH H-SV 1200 T 02)0 LBaB 0002
UNIT ?C O-FT HEAT AL-1 AMiA DI-K STOP
IN-B 0000 C-MD PID LA-2 Am@A ErMV 00)0
MAvF 00)1 OUT RLY AHYS 001 LOC OFF
L-SV -050 SSrM STND LBaT 0000
Parameter Factorydefault Parameter Factorydefault Parameter Factorydefault Parameter Factorydefault
AL1 1250 AT OFF I 0000 REST 05)0
AL2 1250 P 01)0 D 0000 HYS 002
Parameter Factorydefault
- 0
※ TheAC/DCvoltagemodelsdonothaveSSRdriveoutputmethod[SSrM].Incaseofcontroloutput[OUT],ifsetas SSR,itsupportsonlyON/OFFoutput.
J-115
Dual Display, PID Control
SENSORS
CONTROLLERS
MOTION DEVICES
SOFTWARE
(J)TemperatureControllers
(K)SSRs
(L)PowerControllers
(M)Counters
(N)Timers
(O)Digital Panel Meters
(P)Indicators
(Q)Converters
(R)Digital Display Units
(S)SensorControllers
(T)SwitchingMode PowerSupplies
(U)Recorders
(V)HMIs
(W)Panel PC
(X)Field NetworkDevices
Functions
Alarm operation
Alarm [AL-1 / AL-2]Alarm
operationAlarmoption
AM!A
Sensor break alarmThefunctionthatalarmoutputwillbeONwhensensorisnotconnectedorwhensensor'sdisconnectionisdetectedduringtemperaturecontrolling.Youcancheckwhetherthesensorisconnectedwithbuzzerorotherunitsusingalarmoutputcontact.Itisselectablebetweenstandardalarm[SBaA],oralarmlatch[SBaB].
Alarm optionMode Name DescriptionAM .A Standardalarm Ifitisanalarmcondition,alarmoutputisON.Ifitisaclearalarmcondition,alarmoutputisOFF.AM .B Alarmlatch Ifitisanalarmcondition,alarmoutputisONandmaintainsONstatus.
AM .C Standbysequence1Firstalarmconditionisignoredandfromsecondalarmcondition,standardalarmoperates.Whenpowerissuppliedanditisanalarmcondition,thisfirstalarmconditionisignoredandfromthesecondalarmcondition,standardalarmoperates.
AM .DAlarmlatchandstandbysequence1
Ifitisanalarmcondition,itoperatesbothalarmlatchandstandbysequence.Whenpowerissuppliedanditisanalarmcondition,thisfirstalarmconditionisignoredandfromthesecondalarmcondition,alarmlatchoperates.
AM .E Standbysequence2Firstalarmconditionisignoredandfromsecondalarmcondition,standardalarmoperates.Whenre-appliedstandbysequenceandifitisalarmcondition,alarmoutputdoesnotturnON.Afterclearingalarmcondition,standardalarmoperates.
AM .FAlarmlatchandstandbysequence2
Basicoperationissameasalarmlatchandstandbysequence1.ItoperatesnotonlybypowerON/OFF,butalsoalarmsettingvalue,oralarmoptionchanging.Whenre-appliedstandbysequenceandifitisalarmcondition,alarmoutputdoesnotturnON.Afterclearingalarmcondition,alarmlatchoperates.
※Conditionofre-appliedstandbysequenceforstandbysequence1,alarmlatchandstandbysequence1:PowerONConditionofre-appliedstandbysequenceforstandbysequence2,alarmlatchandstandbysequence2:PowerON,changingsettemperature,alarmtemperature[AL1,AL2]oralarmoperation[AL-1,AL-2],switchingSTOPmodetoRUNmode.
Setbothalarmoperationandalarmoptionbycombining.Alarmoutputsaretwoandeachoneoperatesindividually.Whenthecurrenttemperatureisoutofalarmrange,alarmclearsautomatically.Ifalarmoptionisalarmlatchoralarmlatchandstandbysequence1/2,pressdigitalinputkey( + 3sec,digitalinputkey[DI-K]ofparametergroup2setasAlRE),orturnOFFthepowerandturnONtoclearalarm.
Mode Name Alarmoperation Description
AM)_ - - Noalarmoutput
AM!
Deviationhigh-limitalarm
SV100
PV110
OFF ONH
PV90
SV100
OFF ONHIfdeviationbetweenPVandSVashigh-limitishigherthansetvalueofdeviationtemperature,thealarmoutputwillbeON.
Highdeviation:Setas10 Highdeviation:Setas-10
AM@
Deviationlow-limitalarm
PV90
SV100
OFFON H
SV100
PV110
OFFON HIfdeviationbetweenPVandSVaslow-limitishigherthansetvalueofdeviationtemperature,thealarmoutputwillbeON.
Lowerdeviation:Setas10 Lowerdeviation:Setas-10
AM#
Deviationhigh/low-limitalarm
PV90
PV110
SV100
OFFON ONH HIfdeviationbetweenPVandSVashigh/low-limitishigherthansetvalueofdeviationtemperature,thealarmoutputwillbeON.
High/Lowerdeviation:Setas10
AM$
Deviationhigh/low-limitreversealarm
PV90
PV110
SV100
OFFON ONH HIfdeviationbetweenPVandSVashigh/low-limitishigherthansetvalueofdeviationtemperature,thealarmoutputwillbeOFF.
High/Lowerdeviation:Setas10
AM%
Absolutevaluehighlimitalarm
PV90
SV100
OFF ONH
SV100
PV110
OFF ONH
IfPVishigherthantheabsolutevalue,theoutputwillbeON.
Absolute-valueAlarm:Setas90
Absolute-valueAlarm:Setas110
AM^
Absolutevaluelowlimitalarm
PV90
SV100
OFFON H
SV100
PV110
OFFON H
IfPVislowerthantheabsolutevalue,theoutputwillbeON.
Absolute-valueAlarm:Setas90
Absolute-valueAlarm:Setas110
SBa SensorbreakAlarm - ItwillbeONwhenitdetectssensordisconnection.LBa LoopbreakAlarm - ItwillbeONwhenitdetectsloopbreak.
※ H:Alarmoutputhysteresis[AHYS]
J-116
TCN Series
Loop break alarm (LBA) Itcheckscontrolloopandoutputsalarmbytemperaturechangeofthesubject.Forheatingcontrol(coolingcontrol),whencontroloutputMVis100%(0%forcoolingcontrol)andPVisnotincreasedoverthanLBAdetectionband[LBaB]duringLBAmonitoringtime[LBaT],orwhencontroloutputMVis0%(100%forcoolingcontrol)andPVisnotdecreasedbelowthanLBAdetectionband[LBaB]duringLBAmonitoringtime[LBaT],alarmoutputturnsON.
Startcontrolto① WhencontroloutputMVis0%andPVisnotdecreasedbelowthanLBAdetectionband[LBaB]duringLBAmonitoringtime[LBaT]
① to ② ThestatusofchangingcontroloutputMV(LBAmonitoringtimeisreset.)
② to ③ WhencontroloutputMVis0%andPVisnotdecreasedbelowthanLBAdetectionband[LBaB]duringLBAmonitoringtime[LBa]loopbreakalarm(LBA)turnsONafterLBAmonitoringtime.
③ to ④ ControloutputMVis0%andloopbreakalarm(LBA)turnsandmaintainsON.
④ to ⑥ ThestatusofchangingcontroloutputMV(LBAmonitoringtimeisreset.)
⑥ to ⑦ WhencontroloutputMVis100%andPVisnotincreasedoverthanLBAdetectionband[LBaT]duringLBAmonitoringtime[LBaT],loopbreakalarm(LBA)turnsONafterLBAmonitoringtime.
⑦ to ⑧ WhencontroloutputMVis100%andPVisincreasedoverthanLBAdetectionband[LBaB]duringLBAmonitoringtime[LBaT]loopbreakalarm(LBA)turnsOFFafterLBAmonitoringtime.
⑧ to ⑨ ThestatusofchangingcontroloutputMV(LBAmonitoringtimeisreset.)
※Whenexecutingauto-tuning,LBAdetectionband[LBaB]andLBAmonitoringtimeareautomaticallysetbasedonautotuningvalue.WhenAL1,AL2alarmoperation[AL-1,AL-2]issetasloopbreakalarm(LBA)[LBa ],LBAdetectionband[LBaB]andLBAmonitoringtime[LBaT]parameterisdisplayed.
Temperature
SV
LBAmonitoring time
PV
LBA detectionband
LBA detectionband
LBA detectionband
LBA detectionband
LBAinvalid
LBAinvalid
LBAinvalid
LBAmonitoring time
LBAmonitoring time
LBAmonitoring time
LBAmonitoring time
Controloutput
MV
100%
Time
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨
0%Loop breakalarm (LBA)
SSRdriveoutput(12VDC)
INPUT LOAD
Load
Power100-240VAC50/60Hz
Temperature controller(TCN4Series) SSR Module
※Whenselectingphaseorcyclecontrolmode,the power supply for load and temperature controller must be the same.※ IncaseofselectingPIDcontroltypeandphase[PHAS]/cycle[CYCL]controloutputmodes,controlcycle[T]isnotallowedtoset.
※ ForAC/DCpowermodel(TCN4 -22R),thisparameterisnotdisplayedanditisavailableonlystandardcontrolbyrelayorSSR.
SSRPfunctionisselectableoneofstandardON/OFFcontrol,cyclecontrol,phasecontrolbyutilizingstandardSSRdriveoutput.
Realizinghighaccuracyandcosteffectivetemperaturecontrolaslinearoutput(cyclecontrolandphasecontrol).SelectoneofstandardON/OFFcontrol[STND],cyclecontrol[CYCL],phasecontrol[PHAS]at[SSrM]parameterofparametergroup2.Forcyclecontrol,connectzerocrossturn-onSSRorrandomturn-onSSR.Forphasecontrol,connectrandomturn-onSSR.
SSR drive output function (SSRP function) [SSrM]
J-117
Dual Display, PID Control
SENSORS
CONTROLLERS
MOTION DEVICES
SOFTWARE
(J)TemperatureControllers
(K)SSRs
(L)PowerControllers
(M)Counters
(N)Timers
(O)Digital Panel Meters
(P)Indicators
(Q)Converters
(R)Digital Display Units
(S)SensorControllers
(T)SwitchingMode PowerSupplies
(U)Recorders
(V)HMIs
(W)Panel PC
(X)Field NetworkDevices
Standard ON/OFF control mode [STND]
Cycle control mode [CYCL]
Phase control mode [PHAS]
AmodetocontroltheloadinthesamewayasRelayoutputtype.(ON:outputlevel100%,OFF:outputlevel0%)
AmodetocontroltheloadbyrepeatingoutputON/OFFaccordingtotherateofoutputwithinsettingcycle.HavingimprovedON/OFFnoisefeaturebyZeroCrosstype.
AmodetocontroltheloadbycontrollingthephasewithinAChalfcycle.Serialcontrolisavailable.RANDOMTurn-ontypeSSRmustbeusedforthismode.
Heatingoperation
Controloutput
ON OFF
SVTemperature
Hysteresis[HYS]
Auto tuning [AT] Hysteresis [HYS]Autotuningmeasuresthecontrolsubject'sthermalcharacteristicsandthermalresponserate,andthendeterminesthenecessaryPIDtimeconstant.(Whencontroltype[C-MD]issetasPID,itisdisplayed.)
Iferror[OPEN]occursduringautotuning,itstopsthisoperationautomatically.
Tostopautotuning,changethesetasOFF.(ItmaintainsP,I,Dvaluesofbeforeautotuning.)
IncaseofON/OFFcontrol,setbetweenONandOFFintervalsashysteresis.(Whencontroltype[C-MD]issetasONOF,itisdisplayed.)
Ifhysteresisistoosmall,itmaycausecontroloutputhunting(takeoff,chattering)byexternalnoise,etc.
Manual reset [REST]WhenselectingP/PDcontrolmode,certaintemperaturedifferenceexistsevenafterPVreachesstablestatusbecauseheater'srisingandfallingtimeisinconsistentduetothermalcharacteristicsofcontrolledobjects,suchasheatcapacity,heatercapacity.Thistemperaturedifferenceiscalledoffsetandmanualreset[REST]functionistoset/correctoffset.WhenPVandSVareequal,resetvalueis50.0%.Aftercontrolisstable,PVislowerthanSV,resetvalueisover50.0%orPVishigherthanSV,resetvalueisbelow50.0%.
Manualreset[REST]bycontrolresult
Temperature unit selection [UNIT]Afunctiontoselectdisplaytemperatureunit.UnitdisplayindicatorwillbeONwhenconvertingtemperatureunit.
Input correction [IN-B]Controlleritselfdoesnothaveerrorsbuttheremaybeerrorbyexternalinputtemperaturesensor.E.g.)Ifactualtemperatureis80butcontrollerdisplays
78,setinputcorrectionvalue[IN-B]as002 andcontrollerdisplays80.
※ Astheresultofinputcorrection,ifcurrenttemperaturevalue(PV)isovereachtemperaturerangeofinputsensor,itdisplaysHHHHorLLLL.
Input digital filter [MAvF]Ifcurrenttemperature(PV)isfluctuatingrepeatedlybyrapidchangeofinputsignal,itreflectstoMVandstablecontrolisimpossible.Therefore,digitalfilterfunctionstabilizescurrenttemperaturevalue.Forexample,setinputdigitalfiltervalueas0.4sec,anditappliesdigitalfiltertoinputvaluesduring0.4secanddisplaysthisvalues.Currenttemperaturemaybedifferentbyactualinputvalue.
SV High/Low limit [H-SV/L-SV] ItsetsSVhigh/lowlimitLimitrangeofusingtemperaturewithintemperaturerangeforeachsensor,usercanset/changesettemperature(SV)withinSVhighlimit[H-SV]toSVlowlimit[L-SV].(※L-SV>H-SVcannotbeset.)
Whenchanginginputtype[IN-T],SVhighlimit[H-
SV]andSVlowlimit[L-SV]ofusingtemperaturewillbeinitializedasmax./min.valueofsensortemperaturerangeautomatically.
50Cycle 50Cycle50% 80%
AC
OUT
ON ONOFF OFF
AC
OUT
10%
AC
OUT50%
SV
PV
Offset
Setbelow50.0asresetvalue
Setover50.0asresetvalue
Offset
※ ManualresetfunctionisapplicableonlytoP/PDcontrolmode.
J-118
TCN Series
Display Description Troubleshooting
OPEN
Flashesifinputsensorisdisconnectedorsensorisnotconnected.
Checkinputsensorstate.
HHHHFlashesifmeasuredsensorinputishigherthantemperaturerange.
Wheninputiswithintheratedtemperaturerange,thisdisplaydisappears.
LLLLFlashesifmeasuredsensorinputislowerthantemperaturerange.
Display Description
OFF Lockoff
LOC1 Lockparametergroup2
LOC2 Lockparametergroup1,2
LOC3 Lockparametergroup1,2,SVsetting
Cool / Heat function [O-FT]
Parameter lock [LOC] Error
Control output MV when input sensor line is broken [ErMV]
Control method selection [C-MD] ItisselectablePID,ON/OFFcontrol.IncaseofON/OFF[ONOF]mode,Hysteresis[HYS]parameterisdisplayed.
IncaseofPID[PID]mode,Proportionalband[P],Integraltime[I],andDerivativetime[T]parametersaredisplayed.
AfunctiontopreventchangingSVandparametersofeachsettinggroup.Parametersettingvaluesarestillpossibletocheckwhenparameterlockisset.
Generallytherearetwowaystocontroltemperature,one(heat-function)istoheatwhenPVisgettingdown(heater).Theother(cool-function)istocoolwhenPVisgettinghigher(freezer).ThesefunctionsareoperatingoppositelywhenitisON/OFFcontrolorproportionalcontrol.ButinthiscasePIDtimeconstantwillbedifferentduetoPIDtimeconstantwillbedecidedaccordingtocontrolsystemwhenitisPIDcontrol.Cool-function[COOL]andheat-function[HEAT]mustbesetcorrectlyaccordingtotheapplication,ifsetasoppositefunction,itmaycauseafire.(Ifsetcool-function[COOL]atheater,itwillbemaintainedONanditmaycauseafire.)
Avoidchangingheat-functiontocool-functionorcool-functiontoheat-functionwhentheunitisoperating.
Itisimpossibletooperatebothfunctionatonceinthisunit.Therefore,onlyonefunctionshouldbeselectedonly.
Wheninputsensorlineisbrokenorsettingvalueerroroccurs,thisfunctionistosetcontroloutput.YoucansetON/OFFsettingforON/OFFcontrol,MVsettingforPIDcontrol.
Alarm output hysteresis [AHYS] ItdisplaysalarmoutputONandOFFintervalandhysteresisisappliedtobothAL1OUTandAL2OUT.•KCaH, JIcH, LIcH, TCcH, RPR, SPR, DPtH,CUsH
:1to100•KCaL, JIcL, LIcL, TCcL,DPtL,CUsL:0.1to50.0E.g.)AL1alarmoperation[AL-1]:AM#A,AL1alarmoperation[AL1]:10, Alarmoutputhysteresis[AHYS]:4
210
190
Temperature
SV200
ONOFF
AL1OUT
210 206 190 194
:4
:4PV
Time
Digital input key ( + 3 sec) [DI-K]
Control output type selection [OUT] It isselectableoutput type;relayoutput [RLY],SSRdriveoutput[SSR].
Parameter OperationOFF OFF Itdoesnotusedigitalinputkeyfunction.
RUN/STOP STOP
Pausescontroloutput.Auxiliaryoutput(exceptloopbreakalarm,sensorbreakalarm)exceptControloutputoperatesassetting.Holdthedigitalinputkeysfor3sectorestart.
RUN RUN
t t tt
STOP STOP RUN
Digitalinputkey(t:over3sec)
Clearalarm AlRE
Clearsalarmoutputbyforce.(onlywhenalarmoptionisalarmlatch,oralarmlatchandstandbysequence1/2.)ThisfunctionisappliedwhenpresentvalueisoutofalarmoperationrangebutalarmoutputisON.Alarmoperatesnormallyrightafterclearingalarm.
Auto-tuning AT
Starts/Stopsauto-tuning.Thisfunctionissameasauto-tuning[AT]ofparametergroup1.(Youcanstartauto-tuning[AT]ofparametergroup1andstopitbydigitalinputkey.)※ ThisparameterATappearsonlywhencontrolmethod[C-MD]parametergroup2issetasPID.Whencontrolmethod[C-MD]parametergroup2issetasONOF,thisparameterischangedasOFF.
J-119
Dual Display, PID Control
SENSORS
CONTROLLERS
MOTION DEVICES
SOFTWARE
(J)TemperatureControllers
(K)SSRs
(L)PowerControllers
(M)Counters
(N)Timers
(O)Digital Panel Meters
(P)Indicators
(Q)Converters
(R)Digital Display Units
(S)SensorControllers
(T)SwitchingMode PowerSupplies
(U)Recorders
(V)HMIs
(W)Panel PC
(X)Field NetworkDevices
Output connections Application of relay output type
KeepAlengthaslongaspossiblewhenwiringthetemperaturecontrollerandtheload.IfwirelengthofAisshort,counterelectromotiveforcewhichoccursfromacoilofmagnetswitch&powerrelaymayflowinpowerlineoftheunit,anditmaycausemalfunction.IfwirelengthofAisshort,pleaseconnectmylarcondensers104(630V)onthebothendsof" "(magnetcoil)toprotectelectromotiveforce.
Voltageoutputterminal
TCNSeries SSR
Loadpower
Power
+
-
INPUT
LOAD
※ SSRshouldbeselectedbythecapacityofload,otherwise,itmayshort-circuitandresultinafire.IndirectheatedshouldbeusedwithSSRforefficientworking.
※ Pleaseuseacoolingplateoritmaycausethecapabilitydeterioration,breakdownofSSRforalongusage.
※ Referto‘SSRdriveoutputfunction’forphase/cyclecontrolconnections.
Application of SSR drive output method
When the load (Heater etc) is not operatedPleasecheckoperationoftheOUTindicatorlocatedinfrontpaneloftheunit.IftheOUTindicatordoesnotoperate,pleasechecktheparameterofallprogrammedmode.Ifindicatorisoperating,pleasechecktheoutput(Relay,SSRdrivevoltage)afterseparatingoutputlinefromtheunit.
When it displays OPEN during operationThisisawarningthatexternalsensorisopen.Pleaseturnoffthepowerandcheckthewirestateofthesensor.Ifsensorisnotopendisconnectsensorlinefromtheunitandshorttheinput+,-terminal.Turnonthepoweroftheunitandcheckthecontrollerdisplaysroomtemperature.Ifthisunitcannotdisplayroomtemperature,thisunitisbroken.Pleaseremovethisunitandcontactourservicecenter.(Whentheinputmodeisthermocouple,itisavailabletodisplayroomtemperature.)
Proper Usage Simple "error" diagnosis Cautions during use
TCNSeries A
Relaycontactterminal
Heater
PowerCondenser
0.1630V
MagnetorRelaycontact
Followinstructionsin'Cautionsduringuse'.Otherwise,Itmaycauseunexpectedaccidents. Checkthepolarityoftheterminalsbeforewiringthetemperaturesensor.ForRTDtemperaturesensor,wireitas3-wiretype,usingcablesinsamethicknessandlength.Forthermocouple(CT)temperaturesensor,usethedesignatedcompensationwireforextendingwire. Keepawayfromhighvoltagelinesorpowerlinestopreventinductivenoise.Incaseinstallingpowerlineandinputsignallineclosely,uselinefilterorvaristoratpowerlineandshieldedwireatinputsignalline.Donotuseneartheequipmentwhichgeneratesstrongmagneticforceorhighfrequencynoise. Installapowerswitchorcircuitbreakerintheeasilyaccessibleplaceforsupplyingordisconnectingthepower. Donotusetheunitforotherpurpose(e.g.voltmeter,ammeter),buttemperaturecontroller. Whenchangingtheinputsensor,turnoffthepowerfirstbeforechanging.Afterchangingtheinputsensor,modifythevalueofthecorrespondingparameter. 24VAC,24-48VDCpowersupplyshouldbeinsulatedandlimitedvoltage/currentorClass2,SELVpowersupplydevice. Makearequiredspacearoundtheunitforradiationofheat.Foraccuratetemperaturemeasurement,warmuptheunitover20minafterturningonthepower. Makesurethatpowersupplyvoltagereachestotheratedvoltagewithin2secaftersupplyingpower. Donotwiretoterminalswhicharenotused. Thisunitmaybeusedinthefollowingenvironments.①Indoors(intheenvironmentconditionratedin'Specifications')②Altitudemax.2,000m③Pollutiondegree2④InstallationcategoryII