Delta Temperature ControllerDT Series
www.delta.com.tw/ia
Automation for a Changing World
1
FeaturesMany Sizes Available:
Quality Assurance:
Supports Various Sensors:
Various Output Modes:
Stable Control:
Current Transformer (CT):
■ From 48x24mm to 96x96mm, all panel sizes comply with international standards.
■ All temperature controllers adopt an isolated switching power supply.■ 100 ~ 240VAC input power supply, applicable in all countries of the world.■ CE, UL and C-Tick certified
■ Built-in various sensor input modes: Thermocouple, platinum RTD or linear voltage/current.
■ Relay, voltage pulse, linear voltage, and linear current
■ Built-in PID control function, with accurate auto-tuning (AT).■ PID parameters are automatically calculated, which enhances the stability of the system and accuracy of control.
■ CT can enable the off-line alarm and can detect if the current is overloaded.
+-
+A
BB -
+
-V
+
-
+
-
+
-VNO NC
COM
PV PV
Thermocouple(TC)
Relay Voltage pulse(For driving SSR)
Linear current(mA)
Linear voltage(V)
Platinum RTD(RTD)
Linear current(mA)
Linear voltage(V)
(Before AT) (After AT)
2
Programmable Control:
Communication:
Safety:
Dual Output Control:
■ Max. 8 patterns available, with 8 steps in each pattern. No master controller is required for planning many kinds of temperature control curves.
■ RS-485 communication interface, supporting Modbus ASCII/RTU communication
■ The key-locking function and communication protection prevents malfunction.
■ Able to execute heating and cooling controls at the same time, allowing the system to reach the set temperature quickly.
100°70°50°30°
Ramp Soak
35 3 8
53
Minute
HMI
Modbus RTU
Modbus ASCII
PLC
Steam Heating
Cooling Water
PID
Sensor
3
DT3Products
Remote Control
Various Control Modes
The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation, fast response, easy modularization, plus user-friendly and user-defined function keys. With Self-Tuning and FUZZY temperature control functions, controllers can be installed in open space and confined space applications and are capable of presenting a smooth temperature control curve. In addition, the innovative design enables customers to replace the module with new functions to attain the ultimate in extension flexibility.
Sets DT3 temperature via analog output of host controller
► Self Tuning► FUZZY► Auto - tuning► ON/OFF► Manual
Hotplate
0~20mA, 4~20mA0~5V, 0~10V
Analog signal mA/V
Control output
Temperature signal input
Remote control via analog signal or communication protocols
Next Generation Temperature Controller
Self-tuning Control Fuzzy Control
Temperature
Temperature
Time Time
4
Extension Ability
Large 3-color LCD Display
Heater Disconnection Detection
Retransmission Output
User-defined Function Keys
Point-to-Point Control (Proportional Output mA/V)
Dual Output Control
Modular design of functional devices lets users replace the module as needed for application flexibility
The 1st 3-color LCD temperature controller in Taiwan.
Measurable up to 100A
► Menu► Auto - tuning► Control modes selection► RUN/STOP Mode► Program hold
Sets the Present Value by point-to-point control.
►Preset temperature is rapidly attained using two sets of outputs for heating and cooling control.►This function is used to automatically calculate two sets of PID parameters, one for heating and one for cooling.
Power
Output 2 (Cooling Control)
Output 1 (Heating Control)
Present Value Transmission mA/V
Inject
Current Transfer
5
Input power supply AC 80 to 260 V, 50/60Hz, DC 24 V ±10%
Input sensors Platinum RTD: Pt100, JPt100
Analog input: 0 to 5 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA, 0 to 50 mV
Display accuracy 0 or 1 digit to the right of the decimal point
Ambient humidity 35 to 80% RH (non-condensing)
Display method LCD. Present temperature: red, Set temperature: green
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
Control modes PID, PID programmable, Fuzzy, Self-tuning, manual, ON/OFF
Ambient temperature 0 ~ +50℃
Sampling rate Analog input: 0.1s, Thermocouple or platinum RTD: 0.1s
SV0
9
11
10
12
1
7
8
6
5
4
3
2
The DT3 offers 3 alarm outputs, and each alarm output has 12 alarm modes to choose from in the initial setting mode. When the target temperature exceeds or falls below the set point, the alarm output is enabled.
Alarm mode Alarm output operationNo alarm
Offline alarm: The alarm will be enabled when the input sensor is not correct or offline.
Ct1 alarm: The alarm will be enabled when the CT1 value falls below AL-L or exceeds AL-H.
Timing alarm
Ct2 alarm: The alarm will be enabled when the CT2 value falls below AL-L or exceeds AL-H.
Alarm output will be enabled when the temperature reaches upper or lower limit: The alarm will be enabled when the PV exceeds SV + AL-H or falls below SV AL-L.
Upper limit hysteresis alarm: The alarm will be enabled when the PV exceeds SV + AL-H. The alarm will be disabled when the PV falls below SV + AL-L.
Lower limit hysteresis alarm: The alarm will be enabled when the PV below SV AL-H. The alarm will be disabled when the PV exceeds SV AL-L.
Alarm output will be enabled when the temperature reaches the absolute value of the lower limit: The alarm will be enabled when the PV falls below AL-L.
Alarm output will be enabled when the temperature reaches the absolute value of the upper limit: The alarm will be enabled when the PV exceeds AL-H.
Alarm output will be enabled when the temperature reaches the absolute value of the upper or lower limit: The alarm will be enabled when the PV exceeds AL-H or falls below AL-L.
Alarm output will be enabled when the temperature reaches the lower limit: The alarm will be enabled when the PV falls below SV AL-L.
Alarm output will be enabled when the temperature reaches the upper limit: The alarm will be enabled when the PV exceeds SV + AL-H.
Specifications
Alarm Outputs
SV-(AL-L)
AL-L
SV-(AL-H)
AL-H
SV
ON
ON
OFF
OFF
AL-L
AL-L
AL-H
AL-H
ON
ON
OFF
OFF
AL-L
ON
OFF
AL-H
ON
OFF
AL-L AL-H
ON
OFF
SV-(AL-L) SV
ON
OFF
SV-(AL-H)SV
ON
OFF
6
1000H
1001H
1003H
1002H
1005H
1006H
1007H
1008H
1009H
100AH
100BH
1012H
1013H
1016H
102BH
102CH
102DH
1815H
1816H
102AH
Present value (PV)
Set value (SV)
Lower limit of temp. range
Upper limit of temp. range
Control mode
Heating/cooling control
1 heating/cooling control cyclest
nd2 heating/cooling control cycle
Proportional band (PB)
Ti value
Td value
Read/write Output 1 volume
Read/write Output 2 volume
Regulated temp. value
Read/write key status
Panel lockup status
CT value
Programmable control Run or StopProgrammable control Run or Pause
Read/write LED status
Measuring unit: 0.1 scale. The following values read mean error occurs.8002H: Temperature not yet acquired8003H: Not connected to sensor8004H: Incorrect sensor Measuring unit: 0.1 scale.
Cannot fall below the default value
Cannot exceed the default value
0: PID, 1: ON/OFF, 2: Manual, 3: PID programmable
0: Heating, 1: Cooling, 2: Heating/cooling, 3: Cooling/heating
0 ~ 99 sec. 0: 0.5 sec.
0 ~ 99 sec. 0: 0.5 sec.
0.1 ~ 999.9
0 ~ 9999
0 ~ 9999
Unit: 0.1%, only valid in manual control mode
Unit: 0.1%, only valid in manual control mode
-99.9 ~ +99.9, Unit: 0.1
b0: Set, b1: Select, b2: Up, b3: Down, 0: Press it
0: Normal, 1: Fully locked, 11: SV adjustable
Unit: 0.1A
0: Run (default), 1: Stop
0: Run (default), 1: Pause
b0:ALM3,b1:ALM2,b2:F,b3:C,b4:ALM1,b5:OUT2,b6:OUT1,b7:AT
Address DefinitionContent
DT3 supports baudrate 2,400 to 38,400 bps, MODBUS ASCII/RTU protocol, function code 03H and reads maximum 8 words from the register.
RS-485 Communication
7
RegulationMode
OperationMode
Initial SettingMode
Parameters Operation
Regulation Mode Operation Mode Initial Setting Mode
Auto-tuning (Set in PID control and RUN mode) Press Self-tuning switch (set when in PID control and the TUNE parameter = ST) Select the nth (n = 0 ~ 5) PID. When n = 6, PID is auto-selected.
Adjust Output 1 hysteresis (when in ON/OFF control)
Set up upper limit of Alarm 1
Control cycle for Output 1 (except in ON/OFF control)
Ratio of Output 1 against Output 2 when in dual output control(set when in PID and dual output control)
Set up upper limit of Alarm 2
Set up rising slope (when CRTS = SLOP)
Record highest temperature of Alarm 3
Set up input filter factor Record highest temperature of Alarm 1
Adjust input compensation Record highest temperature of Alarm 2
Set up input filter range Record lowest temperature of Alarm 1
Adjust input gain Record lowest temperature of Alarm 2
Adjust upper limit compensation for analog Output 1*
Record lowest temperature of Alarm 3
Set up deadband (when in dual output)
Set up lower limit of Alarm 3
Control cycle for Output 2 (except in ON/OFF control)
Adjust Output 2 hysteresis(when in ON/OFF control)
Set up lower limit of Alarm 1
Set up upper limit of Alarm 2
Set up lower limit of Alarm 3
Set up Fuzzy gain value Set up the position of decimal point
Set up PID control offset Set up start step (when in programmable control)
Set up Fuzzy Deadband Lock the keys
Use to set up target temperature Press
Set up input type
Press Set up temperature unit (not displayed when in analog input)
Set up upper temperature limit
Set up upper temperature limit
Select control modes
Set up waiting temperature (when in programmable control)
Set up waiting time (when in programmable control)
Set up start slope (when in programmable control)
Select pattern to be edited
Select AT or ST
Select heating, cooling or dual output heating and cooling
Set up reverse alarm output
Set up Remote type
Select auxiliary function
Set up Alarm 1 mode
Set up Alarm 1 options Set up Alarm 1 delay
Select SV control modes
Control loop RUN or STOP
Set up start pattern (when in PID programmable control and )
Press SET for less than 3 sec. Press SET for less than 3 sec.
Press SET Press SET
8
Select the pattern number to be edited Select number Press to select OFF
Adjust upper limit compensation for analog Output 2*
Adjust upper limit compensation for Retransmission*
Adjust Remote gain
Set up EVENT1 function
Set up EVENT2 function
Set up EVENT3 function
*1 scale = 1μA; 1scale = 1mVPID mode: Any of the 6 PID groups can be selected. When n = 6, the program will automatically select the PID group that is the closest to the target temperature.
Patterns and steps: Edit in parameter. Take editing pattern 0 for example:
Adjust lower limit compensation for analog Output 1*
Select the nth PID (n = 0 ~ 5)
Exit pattern and step editing and switch to to continue the setup process
Adjust lower limit compensation for analog Output 2*
Adjust lower limit compensation for Retransmission*
Adjust Remote compensation
Display and adjust Output 2 volume
Set up lower limit percentage for Output 1
Set up lower limit percentage for Output 2
Display current measured at CT2
Press to return to auto-tuning
Press to return to set up target temperature
Press to return to set up input type
Display and adjust Output 1 volume
Set up the 0th PID temperature value Press
Edit temperature for Step 0 Select actual number of steps when the program is executing
Set up additional cycles (0 ~ 99) for the pattern execution
Set up link pattern. OFF refers to the program end. Press to return to select the pattern number to be edited
Edit time for Step 0(time unit: hr, min)
Set up the 0th PID integral deviation Press to return to PID deviation
Set up the 5 PID integral deviation Press to return to PID deviation
Set up the 0th proportional band value
Set up the 0th Ti value
Set up the 0th Td value
Set up Step 0 ~ 15 in order
Edit temperature for Step 15 Edit time for Step 15 Press to set up actual step numbers
Press Press
Press 0 ~ 5 PID
Set up upper limit percentage for Output 1
Set up upper limit percentage for Output 2
Display current measured at CT1
Select ASCII or RTU format
Set up baudrate
Set up stop bit
Enable/disable communication write-in
Set up the 5 PID temperature value Press
Set up the 5 proportional band value
Set up the 5 Ti value
Set up the 5 Td value
Set up communication address
Set up data length
Set up parity bit
Regulation Mode Operation Mode Initial Setting Mode
th
th
th
th
th
th
9
DTA is designed for practical applications, offering the 3 most frequently adopted output types in the market. DTA has many user-friendly functions built-in and a handy transmission structure, ensuring fast and stable data transmission.
Optional functions: RS-485 communication interface (MODBUS ASCII/RTU, 2,400 ~ 38,400bps), CT (current transformer)
Power supply
Power consumption
Control methods
Sampling rate
Communication protocol
Shock resistance
Storage temperature
Ambient humidity
Communication
Vibration resistance
Ambient temperature
Altitude
Waterproof degree
Display scale
Output types
Input temperature sensors
100 ~ 240VAC, 50/60Hz
5VA Max.
PID, ON/OFF, Manual
0.5 second
MODBUS protocol, ASCII/RTU format (optional)
Max. 300m/s² , 3 times in each of 3 axes, 6 directions
- 20℃~+ 65℃
35 ~ 85% RH (non-condensing)
RS-485 digital communication, 2,400 ~ 38,400bps (optional)
10 ~ 55Hz, 10m/s² for 10 mins in X, Y, Z direction
0℃~ 50℃
< 2,000m
IP56
Thermocouple: K, J, T, E, N, R, S, B, U, L, TXK
Voltage range
Display
85 ~ 110% rated voltage
0.1% full scale
Relay: 250VAC, 5A, SPDT (DTA4848: SPST)
Voltage pulse: 14VDC, Max. output current: 40mA
Current: DC 4 ~ 20mA (Load resistance: < 600W)
2-line 7-segment LED display, PV: red; SV: green
Platinum RTD: Pt100, JPt100
Electrical Specifications
Products
Standard Type
10
Power supply
Power consumption
Control methods
Sampling rate
Communication protocol
Shock resistance
Storage temperature
Ambient humidity
Communication
Vibration resistance
Ambient temperature
Altitude
Waterproof degree
Display scale
Output types
Input temperature sensors
100 ~ 240VAC, 50/60Hz
< 5VA
PID, programmable PID, ON/OFF, Manual
Analog input: 0.15 second, Thermocouple or platinum RTD: 0.4 second
MODBUS protocol, ASCII/RTU format
Max. 300m/s², 3 times in each of 3 axes, 6 directions
- 20℃~+ 65℃
35 ~ 85% RH (non-condensing)
RS-485 digital communication, 2,400 ~ 38,400bps
10 ~ 55Hz, 10m/s² for 10 mins in X, Y, Z direction
0℃~ 50℃
< 2,000m
IP56
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
Voltage range
Display
85 ~ 110% rated voltage
1 digit after decimal point, or no decimal point
Relay: SPDT (DTB4848/4824: SPST), Max. load: 250VAC, Resistive load: 5A
Voltage pulse: 14VDC, Max. output current: 40mA
Current: DC 4 ~ 20mA (Load resistance: < 600WΩ)
Analog voltage: 0 ~ 10V
2-line 7-segment LED display, 4 digits available, PV: red, SV: green
Analog input: 0 ~ 5V, 0 ~ 10V, 0 ~ 20mA, 4 ~ 20mA, 0 ~ 50mVPlatinum RTD: Pt100, JPt100
Electrical Specifications
Advanced TypeCompared to the DTA, DTB has an added linear voltage output and adopts dual-loop output control, able to execute heating and cooling controls at the same time in a temperature control system.
DTB series has a built-in RS-485 communication interface (MODBUS ASCII/RTU, 2,400 ~ 38,400bps). The programmable PID control function allows the DTB to set up 64 sets of temperature and control times.
Optional functions:■ CT (current transformer), output by alarm.■ EVENT function, switching between 2 SVs by using PLC or switches.■ Valve models are able to adjust the openness of valves depending on the SV.
11
DTC features a modular and wire-saving structure, and is able to monitor many temperature points by parallel and modular extension. The user is able to set up the suitable output method according to actual demand. The built-in password protection prevents unauthorized operation or malicious damage from staff.
DTC series has a built-in RS-485 communication interface (MODBUS ASCII/RTU, 2,400 ~ 38,400bps). The programmable PID control function allows the DTC to set up 64 sets of temperature and control times. DTC also supports 3 levels of password protection, synchronous communication protocol and auto ID setup.
Electrical Specifications
Products
Modular Type
Power supply
Power consumption
Control methods
Sampling rate
Communication protocol
Shock resistance
Storage temperature
Ambient humidity
Communication
Vibration resistance
Ambient temperature
Altitude
Output types
Input temperature sensors
3W + 3W x number of DTC2000 controllers connected in parallel (Max. 7)
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
PID, programmable PID, ON/OFF, Manual
Analog input: 0.15 second, Thermocouple or platinum RTD: 0.4 second
MODBUS protocol, ASCII/RTU format
Max. 300m/s², 3 times in each of 3 axes, 6 directions
- 20℃~+ 65℃
35 ~ 85% RH (non-condensing)
RS-485 digital communication, 2,400 ~ 38,400bps
10 ~ 55Hz, 10m/s2 for 10 mins in X, Y, Z direction
0℃~ 50℃
< 2,000m
Platinum RTD: Pt100, JPt100
Voltage range 90 ~ 110% rated voltage
24VDC, isolated switching power supply
Voltage pulse: 12VDC, Max. output current: 40mA
Relay: SPST, Max. load: 250VAC, Resistive load: 3A
Current: DC 4 ~ 20mA (Load resistance: < 500WΩ)
Analog voltage: 0 ~ 10V (Load resistance: > 1,000WΩ)
Linear current: 0 ~ 5V, 0 ~ 10V, 0 ~ 20mA, 4 ~ 20mA, 0 ~ 50mV
12
DTD series offers PID, programmable PID, ON/OFF and Manual control modes and supports 1 alarm output with 8 alarm modes, which reduces cost but enhances functions.
The programmable PID control function allows the DTD to set up 8 sets of temperature and control times.
Economical Type
Electrical SpecificationsPower supply
Power consumption
Control methods
Sampling rate
Shock resistance
Storage temperature
Ambient humidity
Vibration resistance
Ambient temperature
Altitude
Waterproof degree
Display scale
Output types
Input temperature sensors
100 ~ 240VAC, 50/60Hz
6VA Max.
PID, programmable PID, ON/OFF, Manual
0.4 second (analog input and sensor input)
Max. 300m/s², 3 times in each of 3 axes, 6 directions
- 20℃~+ 65℃
35 ~ 85% RH (non-condensing)
10 ~ 55Hz, 10m/s2 for 10 mins in X, Y, Z direction
0℃~ 50℃
< 2,000m
IP56
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
Voltage range
Display
85 ~ 110% rated voltage
K2, J2, T2, Pt100-2, JPt100, Cu50: 0.1°, Others: 1°
Relay: 250VAC, 5A, SPST
Voltage pulse: 14VDC, Max. output current: 40mA
7-segment LED display, PV: red, SV: green
Current: 0 ~ 20mA, 4 ~ 20mA Voltage: 0 ~ 5V, 0 ~ 10V, 0 ~ 70mV
Platinum RTD: Pt100, JPt100 Copper resistance: Cu50
13
DTE series is a multi-channel modular type temperature controller. The DTE10T supports 8 thermocouple inputs and the DTE10P supports 6 platinum RTD inputs. The DTE series is installed on DIN rail, and each channel operates independently. DTE series offers many optional output modules (relay, voltage pulse, current and linear current). The built-in RS-485 2-wire communication allows transmission of up to 115,200bps.
The programmable PID control function allows the DTE to set up 64 sets of temperature and control times. Maximum 7 DTC2000 controllers are extendable to DTE, and DTE supports the same synchronous communication protocol and auto ID setup which DTC supports.
Electrical Specifications
Multi-Channel Modular Type
Products
Power supply
Power consumption
Control methods
Sampling rate
Communication protocol
Shock resistance
Storage temperature
Ambient humidity
Communication
Vibration resistance
Ambient temperature
Altitude
Output types
Input temperature sensors
Max. 10W + 3W + 3W x number of DTC2000 controllers connected in parallel (Max. 7)
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
PID, programmable PID, ON/OFF, Manual
Thermocouple or platinum RTD: 1.0 second/all inputs
MODBUS protocol, ASCII/RTU format
Max. 300m/s², 3 times in each of 3 axes, 6 directions
- 20℃~+ 65℃
35 ~ 85% RH (non-condensing)
RS-485 digital communication, 2,400 ~ 115,200bps
10 ~ 55Hz, 10m/s² for 10 mins in X, Y, Z direction
0℃~ 50℃
< 2,000m
Platinum RTD: Pt100, JPt100 Copper resistance: Cu50
Voltage range 90 ~ 110% rated voltage
24VDC, isolated switching power supply
Voltage pulse: 24VDC, Max. output current: 40mA
Relay: SPST, Max. load: 250VAC, Resistive load: 3A
Current: DC 4~20mA (Load resistance: < 500WΩ)
Analog voltage: 0 ~ 10V (Load resistance: > 1,000Ω)
14
DTV series is designed for electronic valve applications. It is user-friendly and easy to use. DTV has built-in MODBUS communication, which allows handier data collection.
DTV also features:■ Auto/manual mode switching by a single key.■ "Left" key makes the parameter setting faster.■ Real-time output percentage display, for the user to check the openness of the valve.■ 2 alarm outputs, 17 alarm modes.■ RS-485 communication interface for DTV to monitor and collect data from other temperature controllers on the network.
Valve Type
Electrical SpecificationsPower supply
Power consumption
Control methods
Communication
Vibration resistance
Storage temperature
Ambient humidity
Communication protocol
Shock resistance
Ambient temperature
Altitude
Waterproof degree
Display scale
Output types
Sampling rate
Input temperature sensors
100 ~ 240VAC, 50/60Hz
< 5VA
PID, programmable PID, ON/OFF, Manual
RS-485 digital communication, 2,400 ~ 38,400bps
10 ~ 55Hz, 10m/s² for 10 mins in X, Y, Z direction
- 20℃~+ 65℃
35 ~ 85% RH (non-condensing)
MODBUS protocol, ASCII/RTU format
Max. 300m/s², 3 times in each of 3 axes, 6 directions
0℃~ 50℃
< 2,000m
IP56
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
Voltage range
Display
85 ~ 110% rated voltage
1 digit after decimal point, or no decimal point
Relay: SPST
Max. load: 250VAC, Resistive load: 5A
Analog input: 0.15 second, Thermocouple or platinum RTD: 0.4 second
2-line 7-segment LED display, 4-bit or 2-bit valve openness display available PV: red, SV & openness of valve: green
Analog input: 0 ~ 5V, 0 ~ 10V, 0 ~ 20mA, 4 ~ 20mA, 0 ~ 50mA
Platinum RTD: Pt100, JPt100
15
Accessories Information
1
D
5
1
3
3 -
- 72
T
64
Series Name
Series Name
Accessories
Panel size (W x H)
Panel size (W x H)
Option 1
Output
Output 1 options
Power supply
Output 2 options
Optional function 1
Optional function 2
Optional function 3
Communication (optional)
CT (optional)
DT3:Delta DT3 Series Temperature Controller
DTA:Delta A Series Temperature Controller
DT3:Delta DT Series Temperature Controller
20:4848:1/16 DIN W48 x H48 mm 30:7272:W72 x H72mm
4848:1/16 DIN W48 x H48 mm4896:1/8 DIN W48 x H96 mm9696:1/4 DIN W96 x H96 mm
R:Relay, SPST (4848: SPST), 250VAC, 5AV:Voltage pulse, 14V +10% ~ -20% (Max. 40mA)C:Current, 4~20mA
7272: W72 x H72 mm9648: W96 x H48 mm
1:RS-485 communication
T:With CT (only DTA7272R0)
20ESTD : DT320 EXTENSION without RS-485 & EV3
20ECOM : DT320 EXTENSION include RS-485
20EEV3 : DT320 EXTENSION include EVENT3
30ESTD : DT330 EXTENSION without RS-485 & EV3
30ECOM : DT330 EXTENSION include RS-485
40ESTD : DT340/DT360 EXTENSION without RS-485 & EV3
40ECOM : DT340/360 EXTENSION include RS-485
40EEV3 : DT340/360 EXTENSION include EVENT3
R: Relay Output
V: DC Voltage Pulse Output
C: DC Current Output
L: DC Linear Voltage Output
: Event Input EVENT
: CT InputCTI
: 30A CTCT30A
: 100A CTCT100A
: RetransmissionRETRANS
: Remote set pointREMOTE
A: AC 80 to 260VD: DC 24 V
R: Relay, 250 VAC, 5AV: Voltage pulse, 12V +10 to 20%C: DC current, 4 to 20m A L: Linear voltage, 0 to 10 VDC
40:4896:1/8 DIN W48 x H96 mm60:9696:1/4 DIN W96 x H96 mm
R: Relay, 250 VAC, 5AV: Voltage pulse, 12V +10 to 20%C: DC current, 4 to 20 mA L: Linear voltage, 0 to 10 VDC
0: None, 1: Event input 3, 2: RS-485 communication
0: None, 1: Event input 2, 2: CT input 2, 3:Retransmission output
0:N/A
□:N/A
0: None, 1: Event input 1, 2: CT input 1, 3: Remote setup input
Ordering Information
Ordering Information
1 53 72 64 8
1
1 3
1
1
5
5
3
7
6
7
2
2 4
2
6
4
8
16
4848:1/16 DIN W48 x H48 mm4896:1/8 DIN W48 x H96 mm
Series Name
Series Name
Series Name
Series Name
Series Name
Controller type
Panel size (W x H)
Panel size (W x H)
Panel size (W x H)
Optional function
Optional function
Output 1 options
Number of auxiliary outputs
Output
Output 2 options
Output
Output
Controller type
0 Optional function 0:N/A
1:Main unit 2:Accessory
4896:1/8 DIN W48 x H96 mm9696:1/4 DIN W96 x H96 mm
:4-channel TC (main unit, accessory):4-channel PT (main unit, accessory):4 channels of voltage pulse output:4 channels of linear current output
:4 channels of relay output:4 channels of linear voltage output:4 digital inputs & 4 digital outputs:4 channels of current transformers:Display & setup module
0T0P0V0C
0R0L0DCTDS
Optional function
DTB:Delta B Series Temperature Controller
DTC:Delta C Series Temperature Controller
DTD:Delta D Series Temperature Controller
DTE:Delta E Series Temperature Controller
DTV:Delta V Series Temperature Controller
4824:1/32 DIN W48 x H24 mm4848:1/16 DIN W48 x H48 mm
12
:Main unit:Extension unit
R:Relay, SPST, 250VAC, 5AV:Voltage pulse, 14V +10% ~ -20% (Max. 40mA)
00:Standard function01:With CT input
R:Relay, SPDT (4824/4848: SPST), 250VAC, 5AV:Voltage pulse: 14V +10% ~ -20%
RVCL
:Relay, SPST, 250VAC, 3A:Voltage pulse, 12V +10% ~ -20%:Current, 4 ~ 20mA:Linear voltage, 0 ~ 10V
R:Relay, SPDT (4824/4848: SPST), 250VAC, 5AV:Voltage pulse: 14V +10% ~ -20%C:DC current: 4 ~ 20mAL:Linear voltage: 0 ~ 5V, 0 ~ 10VDC
0 :Standard 2 outputs, no auxiliary output
R:Relay, SPDT, 250VAC, 5A
□:Without CT, without EVENT inputT:With CT, without EVENT input
E:Without CT, with EVENT inputV:Valve contro
4896 :1/8 DIN W48 x H96 mm9696 :1/4 DIN W96 x H96 mm
7272:W72 x H72 mm
*DTB4824 has no optional function and no extra alarm output. Output 2 can be set to alarm output.*DTB4848 has only 1 optional alarm output. Output 2 can be set to the 2 alarm output.*DTB9696 has optional valve control function. Model name: DTB9696RRV.
nd1
1
1
1
1
5
5
5
5 0
3
3
3
3
2
72
2
2
2
64
4
4
4
3
1
1
1
2
2
3
3
4
4
3
2
1 3
7
5
2
5
4
3
2 4
6
5
5
1
17
Dimensions4824
4848
7272
9648
48.0 mm
24.0
mm
3.4 mm 99.8 mm
21.8
5 m
m
44.75 mm
72.0 mm
72.0
mm
74.0
mm
13.80 mm 79.20 mm
67.8
0 m
m
SET
DTA9648
96.0
48.0
12.3 79.2
91.0
44.0
48.0 mm
48.0
mm
9.5 mm 80.0 mm
44.7
5 m
m
18
4896
DTC
9696
DTE
48.0 mm 12.8 mm 79.2 mm
91.0
mm
95.7
mm
98.2
mm
44.0 mm
SET
SET
96.0 mm
96.0
mm
98.0
mm
15.8 mm 79.2 mm
90.8
mm
900.
Delta_DT_C_EN_20130118
Industrial Automation HeadquartersDelta Electronics, Inc. Taoyuan Technology CenterNo.18, Xinglong Rd., Taoyuan City, Taoyuan County 33068, TaiwanTEL: 886-3-362-6301 / FAX: 886-3-371-6301
AsiaDelta Electronics (Jiangsu) Ltd.Wujiang Plant 31688 Jiangxing East Road, Wujiang Economic Development ZoneWujiang City, Jiang Su Province, People's Republic of China (Post code: 215200)TEL: 86-512-6340-3008 / FAX: 86-769-6340-7290
Delta Greentech (China) Co., Ltd.238 Min-Xia Road, Pudong District, ShangHai, P.R.C.Post code : 201209TEL: 86-21-58635678 / FAX: 86-21-58630003 Delta Electronics (Japan), Inc.Tokyo Office 2-1-14 Minato-ku Shibadaimon, Tokyo 105-0012, JapanTEL: 81-3-5733-1111 / FAX: 81-3-5733-1211
Delta Electronics (Korea), Inc.1511, Byucksan Digital Valley 6-cha, Gasan-dong, Geumcheon-gu, Seoul, Korea, 153-704TEL: 82-2-515-5303 / FAX: 82-2-515-5302
Delta Electronics Int’l (S) Pte Ltd4 Kaki Bukit Ave 1, #05-05, Singapore 417939TEL: 65-6747-5155 / FAX: 65-6744-9228
Delta Electronics (India) Pvt. Ltd.Plot No 43 Sector 35, HSIIDC Gurgaon, PIN 122001, Haryana, India TEL : 91-124-4874900 / FAX : 91-124-4874945
AmericasDelta Products Corporation (USA)Raleigh OfficeP.O. Box 12173,5101 Davis Drive, Research Triangle Park, NC 27709, U.S.A.TEL: 1-919-767-3800 / FAX: 1-919-767-8080
Delta Greentech (Brasil) S.ASao Paulo OfficeRua Itapeva, 26 - 3° andar Edificio Itapeva One-Bela Vista01332-000-São Paulo-SP-BrazilTEL: +55 11 3568-3855 / FAX: +55 11 3568-3865
EuropeDeltronics (The Netherlands) B.V.Eindhoven OfficeDe Witbogt 15, 5652 AG Eindhoven, The Netherlands TEL: 31-40-2592850 / FAX: 31-40-2592851
*We reserve the right to change the information in this catalogue without prior notice.