Delta Temperature ControllerDT Series

www.delta.com.tw/ia

Automation for a Changing World

Page 2: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

1

FeaturesMany Sizes Available:

Quality Assurance:

Supports Various Sensors:

Various Output Modes:

Stable Control:

Current Transformer (CT):

■ From 48x24mm to 96x96mm, all panel sizes comply with international standards.

■ All temperature controllers adopt an isolated switching power supply.■ 100 ~ 240VAC input power supply, applicable in all countries of the world.■ CE, UL and C-Tick certified

■ Built-in various sensor input modes: Thermocouple, platinum RTD or linear voltage/current.

■ Relay, voltage pulse, linear voltage, and linear current

■ Built-in PID control function, with accurate auto-tuning (AT).■ PID parameters are automatically calculated, which enhances the stability of the system and accuracy of control.

■ CT can enable the off-line alarm and can detect if the current is overloaded.

+-

+A

BB -

+

-V

+

-

+

-

+

-VNO NC

COM

PV PV

Thermocouple(TC)

Relay Voltage pulse(For driving SSR)

Linear current(mA)

Linear voltage(V)

Platinum RTD(RTD)

Linear current(mA)

Linear voltage(V)

(Before AT) (After AT)

Page 3: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

2

Programmable Control:

Communication:

Safety:

Dual Output Control:

■ Max. 8 patterns available, with 8 steps in each pattern. No master controller is required for planning many kinds of temperature control curves.

■ RS-485 communication interface, supporting Modbus ASCII/RTU communication

■ The key-locking function and communication protection prevents malfunction.

■ Able to execute heating and cooling controls at the same time, allowing the system to reach the set temperature quickly.

100°70°50°30°

Ramp Soak

35 3 8

53

Minute

HMI

Modbus RTU

Modbus ASCII

PLC

Steam Heating

Cooling Water

PID

Sensor

Page 4: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

3

DT3Products

Remote Control

Various Control Modes

The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation, fast response, easy modularization, plus user-friendly and user-defined function keys. With Self-Tuning and FUZZY temperature control functions, controllers can be installed in open space and confined space applications and are capable of presenting a smooth temperature control curve. In addition, the innovative design enables customers to replace the module with new functions to attain the ultimate in extension flexibility.

Sets DT3 temperature via analog output of host controller

► Self Tuning► FUZZY► Auto - tuning► ON/OFF► Manual

Hotplate

0~20mA, 4~20mA0~5V, 0~10V

Analog signal mA/V

Control output

Temperature signal input

Remote control via analog signal or communication protocols

Next Generation Temperature Controller

Self-tuning Control Fuzzy Control

Temperature

Temperature

Time Time

Page 5: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

4

Extension Ability

Large 3-color LCD Display

Heater Disconnection Detection

Retransmission Output

User-defined Function Keys

Point-to-Point Control (Proportional Output mA/V)

Dual Output Control

Modular design of functional devices lets users replace the module as needed for application flexibility

The 1st 3-color LCD temperature controller in Taiwan.

Measurable up to 100A

► Menu► Auto - tuning► Control modes selection► RUN/STOP Mode► Program hold

Sets the Present Value by point-to-point control.

►Preset temperature is rapidly attained using two sets of outputs for heating and cooling control.►This function is used to automatically calculate two sets of PID parameters, one for heating and one for cooling.

Power

Output 2 (Cooling Control)

Output 1 (Heating Control)

Present Value Transmission mA/V

Inject

Current Transfer

Page 6: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

5

Input power supply AC 80 to 260 V, 50/60Hz, DC 24 V ±10%

Input sensors Platinum RTD: Pt100, JPt100

Analog input: 0 to 5 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA, 0 to 50 mV

Display accuracy 0 or 1 digit to the right of the decimal point

Ambient humidity 35 to 80% RH (non-condensing)

Display method LCD. Present temperature: red, Set temperature: green

Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK

Control modes PID, PID programmable, Fuzzy, Self-tuning, manual, ON/OFF

Ambient temperature 0 ~ +50℃

Sampling rate Analog input: 0.1s, Thermocouple or platinum RTD: 0.1s

SV0

9

11

10

12

1

7

8

6

5

4

3

2

The DT3 offers 3 alarm outputs, and each alarm output has 12 alarm modes to choose from in the initial setting mode. When the target temperature exceeds or falls below the set point, the alarm output is enabled.

Alarm mode Alarm output operationNo alarm

Offline alarm: The alarm will be enabled when the input sensor is not correct or offline.

Ct1 alarm: The alarm will be enabled when the CT1 value falls below AL-L or exceeds AL-H.

Timing alarm

Ct2 alarm: The alarm will be enabled when the CT2 value falls below AL-L or exceeds AL-H.

Alarm output will be enabled when the temperature reaches upper or lower limit: The alarm will be enabled when the PV exceeds SV + AL-H or falls below SV AL-L.

Upper limit hysteresis alarm: The alarm will be enabled when the PV exceeds SV + AL-H. The alarm will be disabled when the PV falls below SV + AL-L.

Lower limit hysteresis alarm: The alarm will be enabled when the PV below SV AL-H. The alarm will be disabled when the PV exceeds SV AL-L.

Alarm output will be enabled when the temperature reaches the absolute value of the lower limit: The alarm will be enabled when the PV falls below AL-L.

Alarm output will be enabled when the temperature reaches the absolute value of the upper limit: The alarm will be enabled when the PV exceeds AL-H.

Alarm output will be enabled when the temperature reaches the absolute value of the upper or lower limit: The alarm will be enabled when the PV exceeds AL-H or falls below AL-L.

Alarm output will be enabled when the temperature reaches the lower limit: The alarm will be enabled when the PV falls below SV AL-L.

Alarm output will be enabled when the temperature reaches the upper limit: The alarm will be enabled when the PV exceeds SV + AL-H.

Specifications

Alarm Outputs

SV-(AL-L)

AL-L

SV-(AL-H)

AL-H

SV

ON

ON

OFF

OFF

AL-L

AL-L

AL-H

AL-H

ON

ON

OFF

OFF

AL-L

ON

OFF

AL-H

ON

OFF

AL-L AL-H

ON

OFF

SV-(AL-L) SV

ON

OFF

SV-(AL-H)SV

ON

OFF

Page 7: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

6

1000H

1001H

1003H

1002H

1005H

1006H

1007H

1008H

1009H

100AH

100BH

1012H

1013H

1016H

102BH

102CH

102DH

1815H

1816H

102AH

Present value (PV)

Set value (SV)

Lower limit of temp. range

Upper limit of temp. range

Control mode

Heating/cooling control

1 heating/cooling control cyclest

nd2 heating/cooling control cycle

Proportional band (PB)

Ti value

Td value

Read/write Output 1 volume

Read/write Output 2 volume

Regulated temp. value

Read/write key status

Panel lockup status

CT value

Programmable control Run or StopProgrammable control Run or Pause

Read/write LED status

Measuring unit: 0.1 scale. The following values read mean error occurs.8002H: Temperature not yet acquired8003H: Not connected to sensor8004H: Incorrect sensor Measuring unit: 0.1 scale.

Cannot fall below the default value

Cannot exceed the default value

0: PID, 1: ON/OFF, 2: Manual, 3: PID programmable

0: Heating, 1: Cooling, 2: Heating/cooling, 3: Cooling/heating

0 ~ 99 sec. 0: 0.5 sec.

0 ~ 99 sec. 0: 0.5 sec.

0.1 ~ 999.9

0 ~ 9999

0 ~ 9999

Unit: 0.1%, only valid in manual control mode

Unit: 0.1%, only valid in manual control mode

-99.9 ~ +99.9, Unit: 0.1

b0: Set, b1: Select, b2: Up, b3: Down, 0: Press it

0: Normal, 1: Fully locked, 11: SV adjustable

Unit: 0.1A

0: Run (default), 1: Stop

0: Run (default), 1: Pause

b0:ALM3,b1:ALM2,b2:F,b3:C,b4:ALM1,b5:OUT2,b6:OUT1,b7:AT

Address DefinitionContent

DT3 supports baudrate 2,400 to 38,400 bps, MODBUS ASCII/RTU protocol, function code 03H and reads maximum 8 words from the register.

RS-485 Communication

Page 8: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

7

RegulationMode

OperationMode

Initial SettingMode

Parameters Operation

Regulation Mode Operation Mode Initial Setting Mode

Auto-tuning (Set in PID control and RUN mode) Press Self-tuning switch (set when in PID control and the TUNE parameter = ST) Select the nth (n = 0 ~ 5) PID. When n = 6, PID is auto-selected.

Adjust Output 1 hysteresis (when in ON/OFF control)

Set up upper limit of Alarm 1

Control cycle for Output 1 (except in ON/OFF control)

Ratio of Output 1 against Output 2 when in dual output control(set when in PID and dual output control)

Set up upper limit of Alarm 2

Set up rising slope (when CRTS = SLOP)

Record highest temperature of Alarm 3

Set up input filter factor Record highest temperature of Alarm 1

Adjust input compensation Record highest temperature of Alarm 2

Set up input filter range Record lowest temperature of Alarm 1

Adjust input gain Record lowest temperature of Alarm 2

Adjust upper limit compensation for analog Output 1*

Record lowest temperature of Alarm 3

Set up deadband (when in dual output)

Set up lower limit of Alarm 3

Control cycle for Output 2 (except in ON/OFF control)

Adjust Output 2 hysteresis(when in ON/OFF control)

Set up lower limit of Alarm 1

Set up upper limit of Alarm 2

Set up lower limit of Alarm 3

Set up Fuzzy gain value Set up the position of decimal point

Set up PID control offset Set up start step (when in programmable control)

Set up Fuzzy Deadband Lock the keys

Use to set up target temperature Press

Set up input type

Press Set up temperature unit (not displayed when in analog input)

Set up upper temperature limit

Set up upper temperature limit

Select control modes

Set up waiting temperature (when in programmable control)

Set up waiting time (when in programmable control)

Set up start slope (when in programmable control)

Select pattern to be edited

Select AT or ST

Select heating, cooling or dual output heating and cooling

Set up reverse alarm output

Set up Remote type

Select auxiliary function

Set up Alarm 1 mode

Set up Alarm 1 options Set up Alarm 1 delay

Select SV control modes

Control loop RUN or STOP

Set up start pattern (when in PID programmable control and )

Press SET for less than 3 sec. Press SET for less than 3 sec.

Press SET Press SET

Page 9: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

8

Select the pattern number to be edited Select number Press to select OFF

Adjust upper limit compensation for analog Output 2*

Adjust upper limit compensation for Retransmission*

Adjust Remote gain

Set up EVENT1 function

Set up EVENT2 function

Set up EVENT3 function

*1 scale = 1μA; 1scale = 1mVPID mode: Any of the 6 PID groups can be selected. When n = 6, the program will automatically select the PID group that is the closest to the target temperature.

Patterns and steps: Edit in parameter. Take editing pattern 0 for example:

Adjust lower limit compensation for analog Output 1*

Select the nth PID (n = 0 ~ 5)

Exit pattern and step editing and switch to to continue the setup process

Adjust lower limit compensation for analog Output 2*

Adjust lower limit compensation for Retransmission*

Adjust Remote compensation

Display and adjust Output 2 volume

Set up lower limit percentage for Output 1

Set up lower limit percentage for Output 2

Display current measured at CT2

Press to return to auto-tuning

Press to return to set up target temperature

Press to return to set up input type

Display and adjust Output 1 volume

Set up the 0th PID temperature value Press

Edit temperature for Step 0 Select actual number of steps when the program is executing

Set up additional cycles (0 ~ 99) for the pattern execution

Set up link pattern. OFF refers to the program end. Press to return to select the pattern number to be edited

Edit time for Step 0(time unit: hr, min)

Set up the 0th PID integral deviation Press to return to PID deviation

Set up the 5 PID integral deviation Press to return to PID deviation

Set up the 0th proportional band value

Set up the 0th Ti value

Set up the 0th Td value

Set up Step 0 ~ 15 in order

Edit temperature for Step 15 Edit time for Step 15 Press to set up actual step numbers

Press Press

Press 0 ~ 5 PID

Set up upper limit percentage for Output 1

Set up upper limit percentage for Output 2

Display current measured at CT1

Select ASCII or RTU format

Set up baudrate

Set up stop bit

Enable/disable communication write-in

Set up the 5 PID temperature value Press

Set up the 5 proportional band value

Set up the 5 Ti value

Set up the 5 Td value

Set up communication address

Set up data length

Set up parity bit

Regulation Mode Operation Mode Initial Setting Mode

th

th

th

th

th

th

Page 10: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

9

DTA is designed for practical applications, offering the 3 most frequently adopted output types in the market. DTA has many user-friendly functions built-in and a handy transmission structure, ensuring fast and stable data transmission.

Optional functions: RS-485 communication interface (MODBUS ASCII/RTU, 2,400 ~ 38,400bps), CT (current transformer)

Power supply

Power consumption

Control methods

Sampling rate

Communication protocol

Shock resistance

Storage temperature

Ambient humidity

Communication

Vibration resistance

Ambient temperature

Altitude

Waterproof degree

Display scale

Output types

Input temperature sensors

100 ~ 240VAC, 50/60Hz

5VA Max.

PID, ON/OFF, Manual

0.5 second

MODBUS protocol, ASCII/RTU format (optional)

Max. 300m/s² , 3 times in each of 3 axes, 6 directions

- 20℃~+ 65℃

35 ~ 85% RH (non-condensing)

RS-485 digital communication, 2,400 ~ 38,400bps (optional)

10 ~ 55Hz, 10m/s² for 10 mins in X, Y, Z direction

0℃~ 50℃

< 2,000m

IP56

Thermocouple: K, J, T, E, N, R, S, B, U, L, TXK

Voltage range

Display

85 ~ 110% rated voltage

0.1% full scale

Relay: 250VAC, 5A, SPDT (DTA4848: SPST)

Voltage pulse: 14VDC, Max. output current: 40mA

Current: DC 4 ~ 20mA (Load resistance: < 600W)

2-line 7-segment LED display, PV: red; SV: green

Platinum RTD: Pt100, JPt100

Electrical Specifications

Products

Standard Type

Page 11: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

10

Power supply

Power consumption

Control methods

Sampling rate

Communication protocol

Shock resistance

Storage temperature

Ambient humidity

Communication

Vibration resistance

Ambient temperature

Altitude

Waterproof degree

Display scale

Output types

Input temperature sensors

100 ~ 240VAC, 50/60Hz

< 5VA

PID, programmable PID, ON/OFF, Manual

Analog input: 0.15 second, Thermocouple or platinum RTD: 0.4 second

MODBUS protocol, ASCII/RTU format

Max. 300m/s², 3 times in each of 3 axes, 6 directions

- 20℃~+ 65℃

35 ~ 85% RH (non-condensing)

RS-485 digital communication, 2,400 ~ 38,400bps

10 ~ 55Hz, 10m/s² for 10 mins in X, Y, Z direction

0℃~ 50℃

< 2,000m

IP56

Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK

Voltage range

Display

85 ~ 110% rated voltage

1 digit after decimal point, or no decimal point

Relay: SPDT (DTB4848/4824: SPST), Max. load: 250VAC, Resistive load: 5A

Voltage pulse: 14VDC, Max. output current: 40mA

Current: DC 4 ~ 20mA (Load resistance: < 600WΩ)

Analog voltage: 0 ~ 10V

2-line 7-segment LED display, 4 digits available, PV: red, SV: green

Analog input: 0 ~ 5V, 0 ~ 10V, 0 ~ 20mA, 4 ~ 20mA, 0 ~ 50mVPlatinum RTD: Pt100, JPt100

Electrical Specifications

Advanced TypeCompared to the DTA, DTB has an added linear voltage output and adopts dual-loop output control, able to execute heating and cooling controls at the same time in a temperature control system.

DTB series has a built-in RS-485 communication interface (MODBUS ASCII/RTU, 2,400 ~ 38,400bps). The programmable PID control function allows the DTB to set up 64 sets of temperature and control times.

Optional functions:■ CT (current transformer), output by alarm.■ EVENT function, switching between 2 SVs by using PLC or switches.■ Valve models are able to adjust the openness of valves depending on the SV.

Page 12: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

11

DTC features a modular and wire-saving structure, and is able to monitor many temperature points by parallel and modular extension. The user is able to set up the suitable output method according to actual demand. The built-in password protection prevents unauthorized operation or malicious damage from staff.

DTC series has a built-in RS-485 communication interface (MODBUS ASCII/RTU, 2,400 ~ 38,400bps). The programmable PID control function allows the DTC to set up 64 sets of temperature and control times. DTC also supports 3 levels of password protection, synchronous communication protocol and auto ID setup.

Electrical Specifications

Products

Modular Type

Power supply

Power consumption

Control methods

Sampling rate

Communication protocol

Shock resistance

Storage temperature

Ambient humidity

Communication

Vibration resistance

Ambient temperature

Altitude

Output types

Input temperature sensors

3W + 3W x number of DTC2000 controllers connected in parallel (Max. 7)

Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK

PID, programmable PID, ON/OFF, Manual

Analog input: 0.15 second, Thermocouple or platinum RTD: 0.4 second

MODBUS protocol, ASCII/RTU format

Max. 300m/s², 3 times in each of 3 axes, 6 directions

- 20℃~+ 65℃

35 ~ 85% RH (non-condensing)

RS-485 digital communication, 2,400 ~ 38,400bps

10 ~ 55Hz, 10m/s2 for 10 mins in X, Y, Z direction

0℃~ 50℃

< 2,000m

Platinum RTD: Pt100, JPt100

Voltage range 90 ~ 110% rated voltage

24VDC, isolated switching power supply

Voltage pulse: 12VDC, Max. output current: 40mA

Relay: SPST, Max. load: 250VAC, Resistive load: 3A

Current: DC 4 ~ 20mA (Load resistance: < 500WΩ)

Analog voltage: 0 ~ 10V (Load resistance: > 1,000WΩ)

Linear current: 0 ~ 5V, 0 ~ 10V, 0 ~ 20mA, 4 ~ 20mA, 0 ~ 50mV

Page 13: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

12

DTD series offers PID, programmable PID, ON/OFF and Manual control modes and supports 1 alarm output with 8 alarm modes, which reduces cost but enhances functions.

The programmable PID control function allows the DTD to set up 8 sets of temperature and control times.

Economical Type

Electrical SpecificationsPower supply

Power consumption

Control methods

Sampling rate

Shock resistance

Storage temperature

Ambient humidity

Vibration resistance

Ambient temperature

Altitude

Waterproof degree

Display scale

Output types

Input temperature sensors

100 ~ 240VAC, 50/60Hz

6VA Max.

PID, programmable PID, ON/OFF, Manual

0.4 second (analog input and sensor input)

Max. 300m/s², 3 times in each of 3 axes, 6 directions

- 20℃~+ 65℃

35 ~ 85% RH (non-condensing)

10 ~ 55Hz, 10m/s2 for 10 mins in X, Y, Z direction

0℃~ 50℃

< 2,000m

IP56

Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK

Voltage range

Display

85 ~ 110% rated voltage

K2, J2, T2, Pt100-2, JPt100, Cu50: 0.1°, Others: 1°

Relay: 250VAC, 5A, SPST

Voltage pulse: 14VDC, Max. output current: 40mA

7-segment LED display, PV: red, SV: green

Current: 0 ~ 20mA, 4 ~ 20mA Voltage: 0 ~ 5V, 0 ~ 10V, 0 ~ 70mV

Platinum RTD: Pt100, JPt100 Copper resistance: Cu50

Page 14: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

13

DTE series is a multi-channel modular type temperature controller. The DTE10T supports 8 thermocouple inputs and the DTE10P supports 6 platinum RTD inputs. The DTE series is installed on DIN rail, and each channel operates independently. DTE series offers many optional output modules (relay, voltage pulse, current and linear current). The built-in RS-485 2-wire communication allows transmission of up to 115,200bps.

The programmable PID control function allows the DTE to set up 64 sets of temperature and control times. Maximum 7 DTC2000 controllers are extendable to DTE, and DTE supports the same synchronous communication protocol and auto ID setup which DTC supports.

Electrical Specifications

Multi-Channel Modular Type

Products

Power supply

Power consumption

Control methods

Sampling rate

Communication protocol

Shock resistance

Storage temperature

Ambient humidity

Communication

Vibration resistance

Ambient temperature

Altitude

Output types

Input temperature sensors

Max. 10W + 3W + 3W x number of DTC2000 controllers connected in parallel (Max. 7)

Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK

PID, programmable PID, ON/OFF, Manual

Thermocouple or platinum RTD: 1.0 second/all inputs

MODBUS protocol, ASCII/RTU format

Max. 300m/s², 3 times in each of 3 axes, 6 directions

- 20℃~+ 65℃

35 ~ 85% RH (non-condensing)

RS-485 digital communication, 2,400 ~ 115,200bps

10 ~ 55Hz, 10m/s² for 10 mins in X, Y, Z direction

0℃~ 50℃

< 2,000m

Platinum RTD: Pt100, JPt100 Copper resistance: Cu50

Voltage range 90 ~ 110% rated voltage

24VDC, isolated switching power supply

Voltage pulse: 24VDC, Max. output current: 40mA

Relay: SPST, Max. load: 250VAC, Resistive load: 3A

Current: DC 4~20mA (Load resistance: < 500WΩ)

Analog voltage: 0 ~ 10V (Load resistance: > 1,000Ω)

Page 15: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

14

DTV series is designed for electronic valve applications. It is user-friendly and easy to use. DTV has built-in MODBUS communication, which allows handier data collection.

DTV also features:■ Auto/manual mode switching by a single key.■ "Left" key makes the parameter setting faster.■ Real-time output percentage display, for the user to check the openness of the valve.■ 2 alarm outputs, 17 alarm modes.■ RS-485 communication interface for DTV to monitor and collect data from other temperature controllers on the network.

Valve Type

Electrical SpecificationsPower supply

Power consumption

Control methods

Communication

Vibration resistance

Storage temperature

Ambient humidity

Communication protocol

Shock resistance

Ambient temperature

Altitude

Waterproof degree

Display scale

Output types

Sampling rate

Input temperature sensors

100 ~ 240VAC, 50/60Hz

< 5VA

PID, programmable PID, ON/OFF, Manual

RS-485 digital communication, 2,400 ~ 38,400bps

10 ~ 55Hz, 10m/s² for 10 mins in X, Y, Z direction

- 20℃~+ 65℃

35 ~ 85% RH (non-condensing)

MODBUS protocol, ASCII/RTU format

Max. 300m/s², 3 times in each of 3 axes, 6 directions

0℃~ 50℃

< 2,000m

IP56

Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK

Voltage range

Display

85 ~ 110% rated voltage

1 digit after decimal point, or no decimal point

Relay: SPST

Max. load: 250VAC, Resistive load: 5A

Analog input: 0.15 second, Thermocouple or platinum RTD: 0.4 second

2-line 7-segment LED display, 4-bit or 2-bit valve openness display available PV: red, SV & openness of valve: green

Analog input: 0 ~ 5V, 0 ~ 10V, 0 ~ 20mA, 4 ~ 20mA, 0 ~ 50mA

Platinum RTD: Pt100, JPt100

Page 16: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

15

Accessories Information

1

D

5

1

3

3 -

- 72

T

64

Series Name

Series Name

Accessories

Panel size (W x H)

Panel size (W x H)

Option 1

Output

Output 1 options

Power supply

Output 2 options

Optional function 1

Optional function 2

Optional function 3

Communication (optional)

CT (optional)

DT3:Delta DT3 Series Temperature Controller

DTA:Delta A Series Temperature Controller

DT3:Delta DT Series Temperature Controller

20:4848:1/16 DIN W48 x H48 mm 30:7272:W72 x H72mm

4848:1/16 DIN W48 x H48 mm4896:1/8 DIN W48 x H96 mm9696:1/4 DIN W96 x H96 mm

R:Relay, SPST (4848: SPST), 250VAC, 5AV:Voltage pulse, 14V +10% ~ -20% (Max. 40mA)C:Current, 4~20mA

7272: W72 x H72 mm9648: W96 x H48 mm

1:RS-485 communication

T:With CT (only DTA7272R0)

20ESTD : DT320 EXTENSION without RS-485 & EV3

20ECOM : DT320 EXTENSION include RS-485

20EEV3 : DT320 EXTENSION include EVENT3

30ESTD : DT330 EXTENSION without RS-485 & EV3

30ECOM : DT330 EXTENSION include RS-485

40ESTD : DT340/DT360 EXTENSION without RS-485 & EV3

40ECOM : DT340/360 EXTENSION include RS-485

40EEV3 : DT340/360 EXTENSION include EVENT3

R: Relay Output

V: DC Voltage Pulse Output

C: DC Current Output

L: DC Linear Voltage Output

: Event Input EVENT

: CT InputCTI

: 30A CTCT30A

: 100A CTCT100A

: RetransmissionRETRANS

: Remote set pointREMOTE

A: AC 80 to 260VD: DC 24 V

R: Relay, 250 VAC, 5AV: Voltage pulse, 12V +10 to 20%C: DC current, 4 to 20m A L: Linear voltage, 0 to 10 VDC

40:4896:1/8 DIN W48 x H96 mm60:9696:1/4 DIN W96 x H96 mm

R: Relay, 250 VAC, 5AV: Voltage pulse, 12V +10 to 20%C: DC current, 4 to 20 mA L: Linear voltage, 0 to 10 VDC

0: None, 1: Event input 3, 2: RS-485 communication

0: None, 1: Event input 2, 2: CT input 2, 3:Retransmission output

0:N/A

□:N/A

0: None, 1: Event input 1, 2: CT input 1, 3: Remote setup input

Ordering Information

Ordering Information

1 53 72 64 8

1

1 3

1

1

5

5

3

7

6

7

2

2 4

2

6

4

8

Page 17: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

16

4848:1/16 DIN W48 x H48 mm4896:1/8 DIN W48 x H96 mm

Series Name

Series Name

Series Name

Series Name

Series Name

Controller type

Panel size (W x H)

Panel size (W x H)

Panel size (W x H)

Optional function

Optional function

Output 1 options

Number of auxiliary outputs

Output

Output 2 options

Output

Output

Controller type

0 Optional function 0:N/A

1:Main unit 2:Accessory

4896:1/8 DIN W48 x H96 mm9696:1/4 DIN W96 x H96 mm

:4-channel TC (main unit, accessory):4-channel PT (main unit, accessory):4 channels of voltage pulse output:4 channels of linear current output

:4 channels of relay output:4 channels of linear voltage output:4 digital inputs & 4 digital outputs:4 channels of current transformers:Display & setup module

0T0P0V0C

0R0L0DCTDS

Optional function

DTB:Delta B Series Temperature Controller

DTC:Delta C Series Temperature Controller

DTD:Delta D Series Temperature Controller

DTE:Delta E Series Temperature Controller

DTV:Delta V Series Temperature Controller

4824:1/32 DIN W48 x H24 mm4848:1/16 DIN W48 x H48 mm

12

:Main unit:Extension unit

R:Relay, SPST, 250VAC, 5AV:Voltage pulse, 14V +10% ~ -20% (Max. 40mA)

00:Standard function01:With CT input

R:Relay, SPDT (4824/4848: SPST), 250VAC, 5AV:Voltage pulse: 14V +10% ~ -20%

RVCL

:Relay, SPST, 250VAC, 3A:Voltage pulse, 12V +10% ~ -20%:Current, 4 ~ 20mA:Linear voltage, 0 ~ 10V

R:Relay, SPDT (4824/4848: SPST), 250VAC, 5AV:Voltage pulse: 14V +10% ~ -20%C:DC current: 4 ~ 20mAL:Linear voltage: 0 ~ 5V, 0 ~ 10VDC

0 :Standard 2 outputs, no auxiliary output

R:Relay, SPDT, 250VAC, 5A

□:Without CT, without EVENT inputT:With CT, without EVENT input

E:Without CT, with EVENT inputV:Valve contro

4896 :1/8 DIN W48 x H96 mm9696 :1/4 DIN W96 x H96 mm

7272:W72 x H72 mm

*DTB4824 has no optional function and no extra alarm output. Output 2 can be set to alarm output.*DTB4848 has only 1 optional alarm output. Output 2 can be set to the 2 alarm output.*DTB9696 has optional valve control function. Model name: DTB9696RRV.

nd1

1

1

1

1

5

5

5

5 0

3

3

3

3

2

72

2

2

2

64

4

4

4

3

1

1

1

2

2

3

3

4

4

3

2

1 3

7

5

2

5

4

3

2 4

6

5

5

1

Page 18: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

17

Dimensions4824

4848

7272

9648

48.0 mm

24.0

mm

3.4 mm 99.8 mm

21.8

5 m

m

44.75 mm

72.0 mm

72.0

mm

74.0

mm

13.80 mm 79.20 mm

67.8

0 m

m

SET

DTA9648

96.0

48.0

12.3 79.2

91.0

44.0

48.0 mm

48.0

mm

9.5 mm 80.0 mm

44.7

5 m

m

Page 19: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

18

4896

DTC

9696

DTE

48.0 mm 12.8 mm 79.2 mm

91.0

mm

95.7

mm

98.2

mm

44.0 mm

SET

SET

96.0 mm

96.0

mm

98.0

mm

15.8 mm 79.2 mm

90.8

mm

900.

Page 20: DT Series - F. Wilson Electric · 2013-06-20 · The Delta temperature controller DT3 series is designed with upgraded hardware and higher specifications as well as smart operation,

Delta_DT_C_EN_20130118

Industrial Automation HeadquartersDelta Electronics, Inc. Taoyuan Technology CenterNo.18, Xinglong Rd., Taoyuan City, Taoyuan County 33068, TaiwanTEL: 886-3-362-6301 / FAX: 886-3-371-6301

AsiaDelta Electronics (Jiangsu) Ltd.Wujiang Plant 31688 Jiangxing East Road, Wujiang Economic Development ZoneWujiang City, Jiang Su Province, People's Republic of China (Post code: 215200)TEL: 86-512-6340-3008 / FAX: 86-769-6340-7290

Delta Greentech (China) Co., Ltd.238 Min-Xia Road, Pudong District, ShangHai, P.R.C.Post code : 201209TEL: 86-21-58635678 / FAX: 86-21-58630003 Delta Electronics (Japan), Inc.Tokyo Office 2-1-14 Minato-ku Shibadaimon, Tokyo 105-0012, JapanTEL: 81-3-5733-1111 / FAX: 81-3-5733-1211

Delta Electronics (Korea), Inc.1511, Byucksan Digital Valley 6-cha, Gasan-dong, Geumcheon-gu, Seoul, Korea, 153-704TEL: 82-2-515-5303 / FAX: 82-2-515-5302

Delta Electronics Int’l (S) Pte Ltd4 Kaki Bukit Ave 1, #05-05, Singapore 417939TEL: 65-6747-5155 / FAX: 65-6744-9228

Delta Electronics (India) Pvt. Ltd.Plot No 43 Sector 35, HSIIDC Gurgaon, PIN 122001, Haryana, India TEL : 91-124-4874900 / FAX : 91-124-4874945

AmericasDelta Products Corporation (USA)Raleigh OfficeP.O. Box 12173,5101 Davis Drive, Research Triangle Park, NC 27709, U.S.A.TEL: 1-919-767-3800 / FAX: 1-919-767-8080

Delta Greentech (Brasil) S.ASao Paulo OfficeRua Itapeva, 26 - 3° andar Edificio Itapeva One-Bela Vista01332-000-São Paulo-SP-BrazilTEL: +55 11 3568-3855 / FAX: +55 11 3568-3865

EuropeDeltronics (The Netherlands) B.V.Eindhoven OfficeDe Witbogt 15, 5652 AG Eindhoven, The Netherlands TEL: 31-40-2592850 / FAX: 31-40-2592851

*We reserve the right to change the information in this catalogue without prior notice.