1014-M00-ILS-003 OTE Doc. Number: B2 14-02-2012 RE - APPROVEDFOR DESIGN MC PKS KP HH HH KP PKS MC RE - APPROVED FOR DESIGN 26-12-2011 B1 03-10-2011 PKS Approved Engr Checked Prepared Description Rev Date CHARTER HIRE OF FPSO FOR D1 FIELD FGS I/O LIST BUMI ARMADA ENGINEERING 21010-BAE-70000-IN-RL-0003 Page Revision: BAE Doc. Number: CHARTER HIRE OF FPSO FOR D1 FIELD B2 1/11 A0 ISSUED FOR REVIEW HH SVS PVT B0 06-12-2011 APPROVED FOR DESIGN PKS RM HH MC

(DT-0581) 21010-BAE-70000-IN-RL-0003_revB2

Embed Size (px)

DESCRIPTION

dcs wiring

Citation preview

  • 5/25/2018 (DT-0581) 21010-BAE-70000-IN-RL-0003_revB2

    1/11

    1014-M00-ILS-003OTE Doc. Number:

    B2 14-02-2012 RE - APPROVED FOR DESIGN MC PKS KP HH

    HHKPPKSMCRE - APPROVED FOR DESIGN26-12-2011B1

    03-10-2011 PKS

    ApprovedEngrCheckedPreparedDescriptionRev Date

    CHARTER HIRE OF FPSO FOR D1 FIELD

    FGS I/O LIST

    BUMI ARMADA

    ENGINEERING

    21010-BAE-70000-IN-RL-0003

    Page

    Revision:

    BAE Doc. Number:CHARTER HIRE OF FPSO FOR D1 FIELD

    B2

    1/11

    A0 ISSUED FOR REVIEW HHSVSPVT

    B0 06-12-2011 APPROVED FOR DESIGN PKS RM HHMC

  • 5/25/2018 (DT-0581) 21010-BAE-70000-IN-RL-0003_revB2

    2/11

    -

    --

    -

    -

    -

    5

    -

    -

    132

    3

    -

    22

    DIGITAL OUTPUTS ( DO NON I.S )

    8

    4

    -

    -

    -

    M00

    1014-M00-ILS-003OTE Doc. Number:

    1. THIS I/O LIST CONTAINS HARDWIRED SIGNALS.

    2. FIRE AND GAS IO LIST IS GENERATED WITH THE FOLLOWING REFERRENCE DOCUMENTS

    a) FIRE AND GAS CAUSE AND EFFECT MATRIX DOC.NO - 21010-BAE-70000-IN-RL-0007, REV A0

    b) FIRE AND GAS LOCATION PLAN DOC.NO

    i . 21 010 -BAE -700 00- IN -DW -0 03 1, R EV A 0i i. 2 10 10 -B AE-7 00 00 -IN-DW-0 03 2, R EV A 0i ii . 2 10 10 -B AE-7 00 00 -IN-DW-0 03 3, REV A 0

    iv. 2 10 10 -B AE-7 00 20 -IN-DW-0 03 1, REV B 0v . 2 10 10 -B AE-7 00 30 -IN-DW-0 03 1, R EV B 0v i. 2 10 10 -B AE-7 00 50 -IN-DW-0 03 1, REV B 0v ii . 2 10 10 -B AE-7 00 60 -IN-DW-0 03 1, R EV B 1viii. 21010-BAE-70070-IN-DW-0031, REV B1ix. 2 10 10 -B AE-7 00 90 -IN-DW-0 03 1, REV B 1

    M90

    230

    4

    -

    46

    -

    -

    M30

    2/11

    B2

    CHARTER HIRE OF FPSO FOR D1 FIELD

    FGS I/O LIST

    BAE Doc. Number:

    Revision:

    Page

    21010-BAE-70000-IN-RL-0003

    NOTES:

    S.NO

    ANALOG INPUTS ( AI NON I.S.)

    ANALOG OUTPUTS ( AO NON I.S.)

    1

    4

    I/O TYPE

    ANALOG OUTPUTS ( AO - I.S.)

    7

    2

    5

    8

    ANALOG INPUTS ( AI - I.S.)

    19

    DIGITAL INPUTS ( DI I.S )

    DIGITAL OUTPUTS ( DO I.S )

    3

    6

    M10

    -

    -

    -

    -

    -

    3

    -

    -

    25

    -

    M20

    -

    8

    -

    -

    1

    -

    - -

    -

    1

    -

    -

    -

    3

    -

    M55M50

    -

    3

    -

    -

    -

    1

    -

    -

    11

    -

    -

    -

    -

    -

    -

    1

    -

    -

    -

    10

    -

    M70M60

    -

    45

    -

    -

    9

    -

    30

    -

    FGSI/O

    DIGITAL INPUTS ( DI NON I.S )

    18

    BUMI ARMADA

    ENGINEERING

    I/O COUNT

    48

  • 5/25/2018 (DT-0581) 21010-BAE-70000-IN-RL-0003_revB2

    3/11

    Rev

    BUMI ARMADA

    ENGINEERING

    I/ODestination

    1014-M00-ILS-003OTE Doc. Number:

    Function Tag RemarksTag NoModule

    21010-BAE-70000-IN-RL-0003

    Page

    Revision:

    BAE Doc. Number:

    FGS I/O LIST

    CHARTER HIRE OF FPSO FOR D1 FIELDB2

    3/11

    I.S /Non I.S

    Instrument Service Instrument Type F&G Loc. PlanDwg No.

    I/O Type SystemI/OSource Signal Type Disp. Range Units AlarmLoLo

    AlarmLo

    AlarmHi

    AlarmHiHi

    SetPointOperating principle

    M00-

    B2 -- -FLD -FGSI.S 2W 4-20mAFGS AIFlow element produce water overboard00-FI-8100 Flow Indicator BAE-55570-MA-DW-

    0005- Newly Added- ----

    M00

    IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-064FGSN.I.S 3w 4-20mAFGS AIForward Fire Water Pump Room Portside AirIntake

    00-GD-4540-064 Gas Detector 21010-BAE-70000-IN-DW-0031

    - 20 60---

    M00

    IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-065FGSN.I.S 3w 4-20mAFGS AIForward Fire Water Pump Room Portside AirIntake

    00-GD-4540-065 Gas Detector 21010-BAE-70000-IN-DW-0031

    - 20 60---

    M00Air Intake IR Point Type

    B1 %LEL0 60FLD GAH,GAHH-4540-066FGSN.I.S 3w 4-20mAFGS AIForward Fire Water Pump Room Starboard side00-GD-4540-066 Gas Detector 21010-BAE-70000-IN-

    DW-0032- 20 60---

    M00Air Intake IR Point Type

    B1 %LEL0 60FLD GAH,GAHH-4540-067FGSN.I.S 3w 4-20mAFGS AIForward Fire Water Pump Room Starboard side00-GD-4540-067 Gas Detector 21010-BAE-70000-IN-

    DW-0032- 20 60---

    M00-

    B2 -- -FLD -FGSN.I.S VFCFGS DIHelideck Area MAC00-MAC-4540-009 Manual Alarm Call Point HOLD - NEWLY ADDED- ----

    M00-

    B2 -- -FLD -FGSN.I.S VFCFGS DIHelideck Area MAC00-MAC-4540-010 Manual Alarm Call Point HOLD - NEWLY ADDED- ----

    M00-

    B2 -- -FLD NAFGSN.I.S VFCFGS DIZone A Deluge Valve Open00-PSH-8100 Pressure Switch 55570-MA-DW-0005 - Newly AddedNA NANANANA

    M00-

    B2 -- -FLD NAFGSN.I.S VFCFGS DIZone B Deluge Valve Open00-PSH-8102 Pressure Switch 55570-MA-DW-0003 - Newly AddedNA NANANANA

    M00-

    B2 -- -FLD NAFGSN.I.S VFCFGS DIZone C Deluge Valve Open00-PSH-8103 Pressure Switch 55570-MA-DW-0003 - Newly AddedNA NANANANA

    M00-

    B2 -- -FLD NAFGSN.I.S VFCFGS DIAFT Foam Deluge Valve Pressure00-PSH-8310 Pressure Switch - Newly AddedNA NANANANA

    M00-

    B2 mATBA TBAFLD -FGSI.S 2W 4-20mAFGS AIE/R Jockey Pump Discharge Pressure00-PT-8130 Pressure Transmitter - Newly Added- ----

    M00Transmitter Piezo-Electric

    B2 -- -FLD NAFGSI.S 2w 4-20mAFGS AIAFT Firewater On Deck Ring Main Pressure00-PZT-8101 Pressure Transmitter BAE-55570-MA-DW-

    0003- Newly AddedNA NANANANA

    M00-

    B2 -- -FLD NAFGSI.S 2w 4-20mAFGS AIFire Water Main Ring Pressure00-PZT-8102 Pressure Transmitter 55570-MA-DW-0003 - Newly AddedNA NANANANA

    M00Photo Electric/Ionisation

    B2 -- -FLD -FGSN.I.S 2W 4-20mAFGS AIForward Fire Water Pump Room No100-SD-4540-014 Smoke Detector HOLD - DELETED- ----

    M00Photo Electric/Ionisation

    B2 -- -FLD -FGSN.I.S 2W 4-20mAFGS AIForward Fire Water Pump Room No100-SD-4540-015 Smoke Detector HOLD - DELETED- ----

    M00Photo Electric/Ionisation

    B2 -- -FLD -FGSN.I.S 2W 4-20mAFGS AIForward Fire Water Pump Room No200-SD-4540-016 Smoke Detector HOLD - DELETED- ----

    M00Photo Electric/Ionisation

    B2 -- -FLD -FGSN.I.S 2W 4-20mAFGS AIForward Fire Water Pump Room No200-SD-4540-017 Smoke Detector HOLD - DELETED- ----

    M00-

    B2 -- -LCP NAFGSN.I.S VFCFGS DIE/R AFT Fire Pump Common Alarm

    00-XA-8110Alarm

    - Newly AddedNA NANANANA

    M00-

    B2 -- -FWD FW LCP NAFGSN.I.S VFCFGS DIFWD Port Fire pump Common Alarm

    00-XA-8120Common Alarm

    - Newly AddedNA NANANANA

    M00-

    B2 -- -FLD NAFGSN.I.S VFCFGS DIFWD Stbd Fire Pump Common Alarm

    00-XA-8125Alarm

    - Newly AddedNA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S VFCFLD DOE/R AFT Fire Pump Remote Start

    00-XC-8110Command

    - Newly AddedNA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S VFCFLD DOCAAP E/R AFT Fire Pump Running00-XC-8111 Command - Newly

    Added,Tag.NoChanged

    NA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S VFCFWD FW LCP DOFWD Port Fire Pump Remote Start00-XC-8120 Command 70000-IN-RL-0007 - Newly AddedNA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S VFCFLD DOCAAP FWD Port Fire Pump Running00-XC-8121 Command - Newly

    Added,Tag.Nochanged

    NA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S VFCFLD DOFWD Stbd Fire Pump Remote Start00-XC-8125 Command - Newly AddedNA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S VFCFLD DOCAAP Forward Stbd Fire Pump Running00-XC-8126 Command - Newly

    Added,Tag.Nochanged

    NA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S VFCMCC- EngineRoom

    DOFire Jockey Pump remote Start/Stop00-XC-8130 Command 52980-MA-DW-0004 - Newly AddedNA NANANANA

  • 5/25/2018 (DT-0581) 21010-BAE-70000-IN-RL-0003_revB2

    4/11

    Rev

    BUMI ARMADA

    ENGINEERING

    I/ODestination

    1014-M00-ILS-003OTE Doc. Number:

    Function Tag RemarksTag NoModule

    21010-BAE-70000-IN-RL-0003

    Page

    Revision:

    BAE Doc. Number:

    FGS I/O LIST

    CHARTER HIRE OF FPSO FOR D1 FIELDB2

    4/11

    I.S /Non I.S

    Instrument Service Instrument Type F&G Loc. PlanDwg No.

    I/O Type SystemI/OSource Signal Type Disp. Range Units AlarmLoLo

    AlarmLo

    AlarmHi

    AlarmHiHi

    SetPointOperating principle

    M00-

    B2 -- -FLD NAFGSN.I.S VFCFGS DIConfirm Fire00-XE-4510 Status - Newly AddedNA NANANANA

    M00-

    B2 -- -FLD NAFGSN.I.S VFCFGS DIConfirm Gas00-XE-4520 Status - Newly AddedNA NANANANA

    M00-

    B2 -- -MCC- EngineRoom

    NAFGSN.I.S VFCFGS DIE/R AFT Fire Pump Local/ Remote Status00-XE-8110 Status - Newly AddedNA NANANANA

    M00-

    B2 -- -MCC- EngineRoom

    NAFGSN.I.S VFCFGS DIFWD Port Fire Pump Local/ Remote Status00-XE-8120 Status - Newly AddedNA NANANANA

    M00-

    B2 -- -MCC- EngineRoom

    NAFGSN.I.S VFCFGS DIFWD Stbd Fire Pump Local/ Remote Status00-XE-8125 Status - Newly AddedNA NANANANA

    M00-

    B2 -- -MCC- EngineRoom

    NAFGSN.I.S VFCFGS DIJockey Pump Local/Remote Status00-XE-8130 Status 52980-MA-DW-0004 - Signal Type ChangeNA NANANANA

    M00-

    B2 -- -MCC- EngineRoom

    NAFGSN.I.S VFCFGS DIE/R AFT Fire Pump Running Indication00-XI-8110 Indication - Newly AddedNA NANANANA

    M00-

    B2 -- -MCC- EngineRoom

    NAFGSN.I.S VFCFGS DICAAP E/R AFT Fire Pump Running Ind.00-XI-8110A Indication - Newly AddedNA NANANANA

    M00-

    B2 -- -MCC- EngineRoom

    NAFGSN.I.S VFCFGS DIFWD Port Fire Pump Running Indication00-XI-8120 Indication - Newly AddedNA NANANANA

    M00-

    B2 -- -MCC- EngineRoom

    NAFGSN.I.S VFCFGS DICAAP FWD Port Fire Pump Running Ind.00-XI-8120A Indication - Newly AddedNA NANANANA

    M00-

    B2 -- -MCC- EngineRoom

    NAFGSN.I.S VFCFGS DIFWD Stbd Fire Pump Running Indication00-XI-8125 Indication - Newly AddedNA NANANANA

    M00-

    B2 -- -FLD NAFGSN.I.S VFCFGS DICAAP Forward Stbd Fire Pump Running Ind.00-XI-8126 Indication - Newly

    Added,Tag.Nochanged

    NA NANANANA

    M00-

    B2 -- -MCC- EngineRoom

    NAFGSN.I.S VFCFGS DIJockey Pump Running indication00-XI-8130 Status 52980-MA-DW-0004 - Newly AddedNA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S VFCFLD DOE/R AFT Fire Pump Unit Tripped00-XS-8110 Command - Newly AddedNA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S VFCFLD DOE/R AFT Fire Pump Start Inhibit00-XS-8111 Command - Newly AddedNA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S VFCFWD FW LCP DOFWD Port Fire Pump Unit Tripped00-XS-8120 Command - - Newly AddedNA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S VFCAFT FW LCP DOFWD Port Fire pump Start Inhibit00-XS-8121 Command 70000-IN-RL-0007 - FWP LCPNA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S VFCFWD FW LCP DOFWD Stbd Fire Pump Unit Tripped00-XS-8125 Command - - Newly AddedNA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S VFCFWD FW LCP DOFWD Stbd Fire Pump Start Inhibit00-XS-8126 Command - - Newly AddedNA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S VFCFLD DOFire Jockey Pump Unit Tripped00-XS-8130 Command - Newly AddedNA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S 24V DCFLD DOFWD Foam Deluge Valve Open Zone A00-XV-8100 Command - Newly AddedNA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S 24V DCFLD DOAFT Foam Deluge Valve Open Zone B00-XV-8102 Command - Newly AddedNA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S 24V DCFLD DOFWD Foam Deluge Valve Open Zone A00-XV-8103 Command - Newly AddedNA NANANANA

    M00-

    B2 -- -FGS NAFGSN.I.S 24V DCFLD DOAFT Foam Deluge Valve Open00-XV-8310 Command - Newly AddedNA NANANANA

    M10Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-031FGSN.I.S 3w 4-20mAFGS AISlug Suppression System Flame Detector10-FD-4540-031 Flame Detector HOLD - 16 20---

    M10Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-032FGSN.I.S 3w 4-20mAFGS AISlug Suppression System Flame Detector10-FD-4540-032 Flame Detector HOLD - 16 20---

    M10Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-033FGSN.I.S 3w 4-20mAFGS AITurret Head - Main Deck Flame Detector10-FD-4540-033 Flame Detector HOLD - 16 20---

    M10Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-034FGSN.I.S 3w 4-20mAFGS AITurret Head - Main Deck Flame Detector10-FD-4540-034 Flame Detector HOLD - 16 20---

  • 5/25/2018 (DT-0581) 21010-BAE-70000-IN-RL-0003_revB2

    5/11

    Rev

    BUMI ARMADA

    ENGINEERING

    I/ODestination

    1014-M00-ILS-003OTE Doc. Number:

    Function Tag RemarksTag NoModule

    21010-BAE-70000-IN-RL-0003

    Page

    Revision:

    BAE Doc. Number:

    FGS I/O LIST

    CHARTER HIRE OF FPSO FOR D1 FIELDB2

    5/11

    I.S /Non I.S

    Instrument Service Instrument Type F&G Loc. PlanDwg No.

    I/O Type SystemI/OSource Signal Type Disp. Range Units AlarmLoLo

    AlarmLo

    AlarmHi

    AlarmHiHi

    SetPointOperating principle

    M10Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-035FGSN.I.S 3w 4-20mAFGS AITurret Head - 01 Level Deck Flame Detector10-FD-4540-035 Flame Detector HOLD - 16 20---

    M10Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-036FGSN.I.S 3w 4-20mAFGS AITurret Head - 01 Level Deck Flame Detector10-FD-4540-036 Flame Detector HOLD - 16 20---

    M10IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-031FGSN.I.S 3w 4-20mAFGS AITurret Head - Swivel Stack Gas Detector10-GD-4540-031 Gas Detector HOLD - 20 60---

    M10IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-032FGSN.I.S 3w 4-20mAFGS AITurret Head - Swivel Stack Gas Detector10-GD-4540-032 Gas Detector HOLD - 20 60---

    M10IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-033FGSN.I.S 3w 4-20mAFGS AITurret Head - Main Deck Gas Detector10-GD-4540-033 Gas Detector HOLD - 20 60---

    M10IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-034FGSN.I.S 3w 4-20mAFGS AITurret Head - Main Deck Gas Detector10-GD-4540-034 Gas Detector HOLD - 20 60---

    M10IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-035FGSN.I.S 3w 4-20mAFGS AITurret Head - 01 Level Deck Gas Detector10-GD-4540-035 Gas Detector HOLD - 20 60---

    M10IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-036FGSN.I.S 3w 4-20mAFGS AITurret Head - 01 Level Deck Gas Detector10-GD-4540-036 Gas Detector HOLD - 20 60---

    M10IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-060FGSN.I.S 3w 4-20mAFGS AISlug Suppression System Gas Detector10-GD-4540-060 Gas detector HOLD - 20 60---

    M10IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-061FGSN.I.S 3w 4-20mAFGS AISlug Suppression System Gas Detector10-GD-4540-061 Gas detector HOLD - 20 60---

    M10IR Point Type

    B2 %LEL0 60FLD GAH,GAHH-4540-062FGSN.I.S 3w 4-20mAFGS AIBosun Store10-GD-4540-062 Gas detector 21010-BAE-70000-IN-

    DW-0033- Description changed20 60---

    M10IR Point Type

    B2 %LEL0 60FLD GAH,GAHH-4540-063FGSN.I.S 3w 4-20mAFGS AIBosun store10-GD-4540-063 Gas detector 21010-BAE-70000-IN-

    DW-0033- Description changed20 60---

    M10-

    B0 -- -FLD -FGSN.I.S VFCFGS DITurret Head - 01 Level Deck MAC10-MAC-4540-001A Manual Alarm Call Point HOLD - - ----

    M10-

    B0 -- -FLD -FGSN.I.S VFCFGS DITurret Head - Main Deck10-MAC-4540-001B Manual Alarm Call Point HOLD - - ----

    M10-

    B0 -- -FLD -FGSN.I.S VFCFGS DITurret Head - Swivel Stack10-MAC-4540-001C Manual Alarm Call Point HOLD - - ----

    M10Photo Electric/Ionisation

    B2 -- -FLD -FGSN.I.S 2W 4-20mAFGS AIBosun store10-SD-4540-031 Smoke Detector 21010-BAE-70000-IN-

    DW-0033- Description changed- ----

    M10Photo Electric/Ionisation

    B2 -- -FLD -FGSN.I.S 2W 4-20mAFGS AIBosun store10-SD-4540-032 Smoke Detector 21010-BAE-70000-IN-

    DW-0033- Description changed- ----

    M10Photo Electric/Ionisation

    B2 -- -FLD -FGSN.I.S 2W 4-20mAFGS AIBosun store10-SD-4540-033 Smoke Detector 21010-BAE-70000-IN-

    DW-0033- Description changed- ----

    M20Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-001FGSN.I.S 3w 4-20mAFGS AIFlare KOD Flame Detector20-FD-4540-001 Flame Detector 21010-BAE-70020-IN-

    DW-0003- 16 20---

    M20Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-002FGSN.I.S 3w 4-20mAFGS AIFlare KOD Flame Detector20-FD-4540-002 Flame Detector 21010-BAE-70020-IN-

    DW-0003- 16 20---

    M20Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-003FGSN.I.S 3w 4-20mAFGS AIFlare KOD Flame Detector20-FD-4540-003 Flame Detector 21010-BAE-70020-IN-

    DW-0003- 16 20---

    M20IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-001FGSN.I.S 3w 4-20mAFGS AIFlare KOD GasDetector20-GD-4540-001 Gas Detector 21010-BAE-70020-IN-DW-0003

    - 20 60---

    M20IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-002FGSN.I.S 3w 4-20mAFGS AIFlare KOD Gas Detector

    20-GD-4540-002Gas Detector

    21010-BAE-70020-IN-DW-0003

    - 20 60---

    M20IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-003FGSN.I.S 3w 4-20mAFGS AIFlare KOD Gas Detector

    20-GD-4540-003Gas Detector

    21010-BAE-70020-IN-DW-0003

    - 20 60---

    M20IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-004FGSN.I.S 3w 4-20mAFGS AIFlare KOD Gas Detector

    20-GD-4540-004Gas Detector

    21010-BAE-70020-IN-DW-0003

    - 20 60---

    M20IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-005FGSN.I.S 3w 4-20mAFGS AIFlare KOD Gas Detector

    20-GD-4540-005Gas Detector

    21010-BAE-70020-IN-DW-0003

    - 20 60---

    M20-

    A0 -- -FLD -FGSN.I.S VFCFGS DIFlare KOD MAC20-MAC-4540-001 Manual Alarm Call Point 21010-BAE-70020-IN-

    DW-0003- - ----

    M30Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-004FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system Flame Detector30-FD-4540-004 Flame Detector 21010-BAE-70030-IN-

    DW-0003- 16 20---

    M30Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-005FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system Flame Detector30-FD-4540-005 Flame Detector 21010-BAE-70030-IN-

    DW-0003- 16 20---

  • 5/25/2018 (DT-0581) 21010-BAE-70000-IN-RL-0003_revB2

    6/11

    Rev

    BUMI ARMADA

    ENGINEERING

    I/ODestination

    1014-M00-ILS-003OTE Doc. Number:

    Function Tag RemarksTag NoModule

    21010-BAE-70000-IN-RL-0003

    Page

    Revision:

    BAE Doc. Number:

    FGS I/O LIST

    CHARTER HIRE OF FPSO FOR D1 FIELDB2

    6/11

    I.S /Non I.S

    Instrument Service Instrument Type F&G Loc. PlanDwg No.

    I/O Type SystemI/OSource Signal Type Disp. Range Units AlarmLoLo

    AlarmLo

    AlarmHi

    AlarmHiHi

    SetPointOperating principle

    M30Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-006FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system Flame Detector30-FD-4540-006 Flame Detector 21010-BAE-70030-IN-

    DW-0003- 16 20---

    M30Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-007FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system Flame Detector30-FD-4540-007 Flame Detector 21010-BAE-70030-IN-

    DW-0003- 16 20---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-006FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system GasDetector30-GD-4540-006 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-007FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system Gas Detector30-GD-4540-007 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-008FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system Gas Detector30-GD-4540-008 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-009FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system Gas Detector30-GD-4540-009 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-010FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system Gas Detector30-GD-4540-010 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-011FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system Gas Detector30-GD-4540-011 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-012FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system Gas Detector30-GD-4540-012 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-013FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system Gas Detector30-GD-4540-013 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-014FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system Gas Detector30-GD-4540-014 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-015FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system GasDetector30-GD-4540-015 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-016FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system GasDetector30-GD-4540-016 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-017FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system GasDetector30-GD-4540-017 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-018FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system GasDetector30-GD-4540-018 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-019FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system GasDetector30-GD-4540-019 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-020FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system GasDetector30-GD-4540-020 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-021FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system GasDetector30-GD-4540-021 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-022FGSN.I.S 3w 4-20mAFGS AICSU/PW/Fuel Gas system GasDetector30-GD-4540-022 Gas Detector 21010-BAE-70030-IN-

    DW-0003- 20 60---

    M30IR Point Type

    B2 FLD GAH,GAHH-4540-022FGSN.I.S 3w 4-20mAFGS AIFuel Gas skid GasDetector30-GD-4540-048 Gas Detector 21010-BAE-70030-IN-

    DW-0003- NEWLY ADDED15 45---

    M30IR Point Type

    B2 FLD GAH,GAHH-4540-022FGSN.I.S 3w 4-20mAFGS AIFuel Gas skid GasDetector30-GD-4540-049 Gas Detector 21010-BAE-70030-IN-

    DW-0003- NEWLY ADDED15 45---

    M30IR Point Type

    B2 FLD GAH,GAHH-4540-022FGSN.I.S 3w 4-20mAFGS AIFuel Gas skid GasDetector30-GD-4540-050 Gas Detector 21010-BAE-70030-IN-DW-0003

    - NEWLY ADDED15 45---

    M30IR Point Type

    B2 FLD GAH,GAHH-4540-022FGSN.I.S 3w 4-20mAFGS AIFuel Gas skid GasDetector

    30-GD-4540-051Gas Detector

    21010-BAE-70030-IN-DW-0003

    - NEWLY ADDED15 45---

    M30-

    A0 -- -FLD -FGSN.I.S VFCFGS DICSU/PW/Fuel Gas system MAC

    30-MAC-4540-002Manual Alarm Call Point

    21010-BAE-70030-IN-DW-0003

    - - ----

    M30-

    A0 -- -FLD -FGSN.I.S VFCFGS DICSU/PW/Fuel Gas system MAC

    30-MAC-4540-003Manual Alarm Call Point

    21010-BAE-70030-IN-DW-0003

    - - ----

    M30-

    A0 -- -FLD -FGSN.I.S VFCFGS DICSU/PW/Fuel Gas system MAC

    30-MAC-4540-004Manual Alarm Call Point

    21010-BAE-70030-IN-DW-0003

    - - ----

    M50Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-008FGSN.I.S 3w 4-20mAFGS AISea Water Injection system Flame Detector50-FD-4540-008 Flame Detector 21010-BAE-70050-IN-

    DW-0003- 16 20---

    M50Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-009FGSN.I.S 3w 4-20mAFGS AISea Water Injection system Flame Detector50-FD-4540-009 Flame Detector 21010-BAE-70050-IN-

    DW-0003- 16 20---

    M50Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-010FGSN.I.S 3w 4-20mAFGS AISea Water Injection system Flame Detector50-FD-4540-010 Flame Detector 21010-BAE-70050-IN-

    DW-0003- 16 20---

  • 5/25/2018 (DT-0581) 21010-BAE-70000-IN-RL-0003_revB2

    7/11

    Rev

    BUMI ARMADA

    ENGINEERING

    I/ODestination

    1014-M00-ILS-003OTE Doc. Number:

    Function Tag RemarksTag NoModule

    21010-BAE-70000-IN-RL-0003

    Page

    Revision:

    BAE Doc. Number:

    FGS I/O LIST

    CHARTER HIRE OF FPSO FOR D1 FIELDB2

    7/11

    I.S /Non I.S

    Instrument Service Instrument Type F&G Loc. PlanDwg No.

    I/O Type SystemI/OSource Signal Type Disp. Range Units AlarmLoLo

    AlarmLo

    AlarmHi

    AlarmHiHi

    SetPointOperating principle

    M50-

    A0 -- -FLD -FGSN.I.S VFCFGS DISea water Injection System MAC50-MAC-4540-005 Manual Alarm Call Point 21010-BAE-70050-IN-

    DW-0003- - ----

    M55Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-011FGSN.I.S 3w 4-20mAFGS AIFiscal Metering system Flame Detector55-FD-4540-011 Flame Detector 21010-BAE-70055-IN-

    DW-0003- 16 20---

    M55Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-012FGSN.I.S 3w 4-20mAFGS AIFiscal Metering system Flame Detector55-FD-4540-012 Flame Detector 21010-BAE-70055-IN-

    DW-0003- 16 20---

    M55Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-013FGSN.I.S 3w 4-20mAFGS AIFiscal Metering system Flame Detector55-FD-4540-013 Flame Detector 21010-BAE-70055-IN-

    DW-0003- 16 20---

    M55-

    A0 -- -FLD -FGSN.I.S VFCFGS DIFiscal Metering system MAC55-MAC-4540-006 Manual Alarm Call Point 21010-BAE-70055-IN-

    DW-0003- - ----

    M60IR Point Type

    B0 %LEL0 45FLD GAH,GAHH-4530-001FGSN.I.S 3w 4-20mAFGS AITransformer Room Gas Detector60-GD-4530-001 Gas Detector 21010-BAE-70060-IN-

    DW-0003- 15 45---

    M60IR Point Type

    B0 %LEL0 45FLD GAH,GAHH-4530-002FGSN.I.S 3w 4-20mAFGS AITransformer Room Gas Detector60-GD-4530-002 Gas Detector 21010-BAE-70060-IN-

    DW-0003- 15 45---

    M60IR Point Type

    B0 %LEL0 45FLD GAH,GAHH-4530-003FGSN.I.S 3w 4-20mAFGS AIBattery Room Gas Detector60-GD-4530-003 Gas Detector 21010-BAE-70060-IN-

    DW-0003- 15 45---

    M60IR Point Type

    B0 %LEL0 45FLD GAH,GAHH-4530-004FGSN.I.S 3w 4-20mAFGS AISwitchgear Room Gas Detector60-GD-4530-004 Gas Detector 21010-BAE-70060-IN-

    DW-0003- 15 45---

    M60IR Point Type

    B0 %LEL0 45FLD GAH,GAHH-4530-005FGSN.I.S 3w 4-20mAFGS AISwitchgear Room Gas Detector60-GD-4530-005 Gas Detector 21010-BAE-70060-IN-

    DW-0003- 15 45---

    M60IR Point Type

    B0 %LEL0 45FLD GAH,GAHH-4530-006FGSN.I.S 3w 4-20mAFGS AIC&I Room Gas Detector60-GD-4530-006 Gas Detector 21010-BAE-70060-IN-

    DW-0003- 15 45---

    M60IR Point Type

    B0 %LEL0 45FLD GAH,GAHH-4530-101FGSN.I.S 3w 4-20mAFGS AIE-House Air intake Gas Detector60-GD-4530-101 Gas Detector 21010-BAE-70060-IN-

    DW-0003- 15 45---

    M60IR Point Type

    B0 %LEL0 45FLD GAH,GAHH-4530-102FGSN.I.S 3w 4-20mAFGS AIE-House Air intake Gas Detector60-GD-4530-102 Gas Detector 21010-BAE-70060-IN-

    DW-0003- 15 45---

    M60IR Point Type

    B0 %LEL0 45FLD GAH,GAHH-4530-103FGSN.I.S 3w 4-20mAFGS AIE-House Air intake Gas Detector60-GD-4530-103 Gas Detector 21010-BAE-70060-IN-

    DW-0003- 15 45---

    M60IR Point Type

    B0 %LEL0 45FLD GAH,GAHH-4530-104FGSN.I.S 3w 4-20mAFGS AIE-House Air intake Gas Detector60-GD-4530-104 Gas Detector 21010-BAE-70060-IN-

    DW-0003- 15 45---

    M60IR Point Type

    B0 %LEL0 45FLD GAH,GAHH-4530-105FGSN.I.S 3w 4-20mAFGS AIE-House Air intake Gas Detector60-GD-4530-105 Gas Detector 21010-BAE-70060-IN-

    DW-0003- 15 45---

    M60IR Point Type

    B0 %LEL0 45FLD GAH,GAHH-4530-106FGSN.I.S 3w 4-20mAFGS AIE-House Air intake Gas Detector60-GD-4530-106 Gas Detector 21010-BAE-70060-IN-

    DW-0003- 15 45---

    M60IR Point Type

    B0 %LEL0 45FLD GAH,GAHH-4530-107FGSN.I.S 3w 4-20mAFGS AIE-House Air intake Gas Detector60-GD-4530-107 Gas Detector 21010-BAE-70060-IN-

    DW-0003- 15 45---

    M60IR Point Type

    B0 %LEL0 45FLD GAH,GAHH-4530-108FGSN.I.S 3w 4-20mAFGS AIE-House Air intake Gas Detector60-GD-4530-108 Gas Detector 21010-BAE-70060-IN-

    DW-0003- 15 45---

    M60IR Point Type

    B0 %LEL0 45FLD GAH,GAHH-4530-109FGSN.I.S 3w 4-20mAFGS AIE-House Air intake Gas Detector60-GD-4530-109 Gas Detector 21010-BAE-70060-IN-

    DW-0003- 15 45---

    M60IR Point Type

    B1 %LEL0 60FLD GAH,GAHH-4530-026FGSN.I.S 3w 4-20mAFGS AIStore-1 Air Intake Gas Detector60-GD-4540-026 Gas Detector 21010-BAE-70060-IN-

    DW-0003- 20 60---

    M60IR Point Type

    B1 %LEL0 60FLD GAH,GAHH-4530-027FGSN.I.S 3w 4-20mAFGS AIStore-1 Air Intake Gas Detector60-GD-4540-027 Gas Detector 21010-BAE-70060-IN-DW-0003

    - 20 60---

    M60IR Point Type

    B1 %LEL0 60FLD GAH,GAHH-4530-028FGSN.I.S 3w 4-20mAFGS AIStore-2 Air Intake Gas Detector

    60-GD-4540-028Gas Detector

    21010-BAE-70060-IN-DW-0003

    - 20 60---

    M60IR Point Type

    B1 %LEL0 60FLD GAH,GAHH-4530-029FGSN.I.S 3w 4-20mAFGS AIStore-2 Air Intake Gas Detector

    60-GD-4540-029Gas Detector

    21010-BAE-70060-IN-DW-0003

    - 20 60---

    M60Point Type

    A0 TBATBA TBAFLD -FGSN.I.S VFCFGS DISwitch Gear Room Heat Detector

    60-HD-4530-001Heat Detector

    21010-BAE-70060-IN-DW-0003

    - - ----

    M60Point Type

    A0 TBATBA TBAFLD -FGSN.I.S VFCFGS DIControl & Instrument Room Heat Detector

    60-HD-4530-002Heat Detector

    21010-BAE-70060-IN-DW-0003

    - - ----

    M60Point Type

    A0 TBATBA TBAFLD -FGSN.I.S VFCFGS DIStore 1 Heat Detector60-HD-4540-001 Heat Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Point Type

    A0 TBATBA TBAFLD -FGSN.I.S VFCFGS DIStore 1 Heat Detector60-HD-4540-002 Heat Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Point Type

    A0 TBATBA TBAFLD -FGSN.I.S VFCFGS DIStore 2 Heat Detector60-HD-4540-003 Heat Detector 21010-BAE-70060-IN-

    DW-0003- - ----

  • 5/25/2018 (DT-0581) 21010-BAE-70000-IN-RL-0003_revB2

    8/11

    Rev

    BUMI ARMADA

    ENGINEERING

    I/ODestination

    1014-M00-ILS-003OTE Doc. Number:

    Function Tag RemarksTag NoModule

    21010-BAE-70000-IN-RL-0003

    Page

    Revision:

    BAE Doc. Number:

    FGS I/O LIST

    CHARTER HIRE OF FPSO FOR D1 FIELDB2

    8/11

    I.S /Non I.S

    Instrument Service Instrument Type F&G Loc. PlanDwg No.

    I/O Type SystemI/OSource Signal Type Disp. Range Units AlarmLoLo

    AlarmLo

    AlarmHi

    AlarmHiHi

    SetPointOperating principle

    M60Catalytic

    A0 TBATBA TBAFLD -FGSN.I.S 3w 4-20mAFGS AIBattery Room Hydrogen gas Detecor60-HYD-4530-001 Hydrogen Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Catalytic

    A0 TBATBA TBAFLD -FGSN.I.S 3w 4-20mAFGS AIBattery Room Hydrogen gas Detecor60-HYD-4530-002 Hydrogen Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60-

    A0 -- -FLD -FGSN.I.S VFCFGS DITransformer Room MAC60-MAC-4530-001 Manual Alarm Call Point 21010-BAE-70060-IN-

    DW-0003- - ----

    M60-

    A0 -- -FLD -FGSN.I.S VFCFGS DIBattery Room MAC60-MAC-4530-002 Manual Alarm Call Point 21010-BAE-70060-IN-

    DW-0003- - ----

    M60-

    A0 -- -FLD -FGSN.I.S VFCFGS DISwitchgear Room MAC60-MAC-4530-003 Manual Alarm Call Point 21010-BAE-70060-IN-

    DW-0003- - ----

    M60-

    A0 -- -FLD -FGSN.I.S VFCFGS DIC&I Room MAC60-MAC-4530-004 Manual Alarm Call Point 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AIBattery room (Ceiling) Smoke Detector60-SD-4530-0006 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AITransformer room (Ceiling) Smoke Detector60-SD-4530-001 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AITransformer room (Ceiling) Smoke Detector60-SD-4530-002 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AITransformer room (Ceiling) Smoke Detector60-SD-4530-003 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AITransformer room (Ceiling) Smoke Detector60-SD-4530-004 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AIBattery room (Ceiling) Smoke Detector60-SD-4530-005 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AISwitch Gear Room (Ceiling) Smoke Detector60-SD-4530-007 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AISwitch Gear Room (Ceiling) Smoke Detector60-SD-4530-008 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AISwitch Gear Room (Ceiling) Smoke Detector60-SD-4530-009 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AISwitch Gear Room (Ceiling) Smoke Detector60-SD-4530-010 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AIC&I Room (Ceiling) Smoke Detector60-SD-4530-011 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AIC&I Room (Ceiling) Smoke Detector60-SD-4530-012 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AIBattery room (Ceiling) Smoke Detector60-SD-4530-013 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60

    Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AISwitch Gear Room (False Floor) SmokeDetecotor

    60-SD-4530-021 Smoke Detector 21010-BAE-70060-IN-DW-0003

    - - ----

    M60

    Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AISwitch Gear Room (False Floor) SmokeDetecotor

    60-SD-4530-022 Smoke Detector 21010-BAE-70060-IN-DW-0003

    - - ----

    M60

    Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AISwitch Gear Room (False Floor) SmokeDetecotor

    60-SD-4530-023Smoke Detector

    21010-BAE-70060-IN-DW-0003

    - - ----

    M60

    Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AISwitch Gear Room (False Floor) SmokeDetecotor

    60-SD-4530-024 Smoke Detector 21010-BAE-70060-IN-DW-0003

    - - ----

    M60

    Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AISwitch Gear Room (False Floor) SmokeDetecotor

    60-SD-4530-025 Smoke Detector 21010-BAE-70060-IN-DW-0003

    - - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AIInstrument (False Floor) Smoke Detecotor60-SD-4530-026 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AIInstrument (False Floor) Smoke Detecotor60-SD-4530-027 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AIInstrument (False Floor) Smoke Detecotor60-SD-4530-028 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AIStore 1 (Ceiling) Smoke Detector

    60-SD-4540-001Smoke Detector

    21010-BAE-70060-IN-DW-0003

    - - ----

  • 5/25/2018 (DT-0581) 21010-BAE-70000-IN-RL-0003_revB2

    9/11

    Rev

    BUMI ARMADA

    ENGINEERING

    I/ODestination

    1014-M00-ILS-003OTE Doc. Number:

    Function Tag RemarksTag NoModule

    21010-BAE-70000-IN-RL-0003

    Page

    Revision:

    BAE Doc. Number:

    FGS I/O LIST

    CHARTER HIRE OF FPSO FOR D1 FIELDB2

    9/11

    I.S /Non I.S

    Instrument Service Instrument Type F&G Loc. PlanDwg No.

    I/O Type SystemI/OSource Signal Type Disp. Range Units AlarmLoLo

    AlarmLo

    AlarmHi

    AlarmHiHi

    SetPointOperating principle

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AIStore 1 (Ceiling) Smoke Detector60-SD-4540-002 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60Photo Electric/Ionisation

    A0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AIStore 2 (Ceiling) Smoke Detector60-SD-4540-003 Smoke Detector 21010-BAE-70060-IN-

    DW-0003- - ----

    M60-

    B1 -- -FGS NAFGSN.I.S 24V DCESD DOFlash Helideck Handing Lights60-XI-3004 Helideck NA - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCEMG.GEN DOInhibit Emergency Generator Start60-XS-0011 Command NA - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCEMG.GEN DOTrip Emergency Generator Start60-XS-0012 Command - - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCPAGA-A DOGeneral Alarm to PAGA A60-XS-4104A PAGA Interface - - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCPAGA-B DOGeneral Alarm to PAGA B60-XS-4104B PAGA Interface - - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCPAGA-A DOConfirm Frie/Gas Alram to PAGA system A60-XS-4105A PAGA Interface - - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCPAGA-A DOConfirm Frie/Gas Alram to PAGA system B60-XS-4105B PAGA Interface - - NA NANANANA

    M60

    -

    B1 -- -FGS NAFGSN.I.S VFCSWBD 7720 DOTrip Essential Feeder to E-House at EmergencySWB

    60-XS-5143 Shunt Trip 70000-IN-RL-0007 - NA NANANANA

    M60Inergen System -

    B1 -- -FGS NAFGSN.I.S VFCInergen Sys. DOInitiate inertgas Release Battery Room60-XS-7522 Inergen Interface - - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCBatt Charger DOTrip UPS Batt. Charger A&B60-XS-7525 Battery Panel Interface - - NA NANANANA

    M60Damper -

    B1 -- -FGS NAFGSN.I.S VFCE-Hse HVAC DOTrip Transformer Rm Ventilation Fan & Close Fire60-XS-7610 HVAC Interface - - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCInergen Sys. DORelease Transformer Room Inergen System60-XS-7612 Inergen Interface - - NA NANANANA

    M60Damper -

    B1 -- -FGS NAFGSN.I.S VFCE-Hse HVAC DOTrip Battery Rm Ventilation Fan & Close Fire60-XS-7620 HVAC Interface - - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCE-Hse HVAC DOE-House HVAC 1&2 Close Fire Damper60-XS-7630 HVAC Interface - - NA NANANANA

    M60release -

    B1 -- -FGS NAFGSN.I.S VFCE-Hse HVAC DOE-House switchgear & instrument Room inert gas60-XS-7632 HVAC Interface - - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCFWD FW LCP DOEngineroom Firewater Pump start60-XS-8100 FW Pump Interface - - NA NANANANA

    M60

    -

    B1 -- -FGS NAFGSN.I.S VFCFwd FW Rm DOTrip FWD FWP Room Vent Fan & Close FireDamper

    60-XS-8111 Interface Signal - - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCLab HVAC DOStore-1 HVAC System Trip

    60-XS-9711Interface Signal

    - - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCStore HVAC DOStore-1 Fire Dampers CLose Trip

    60-XS-9712Interface Signal

    - - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCLab HVAC DOStore-2 HVAC System Trip

    60-XS-9721Interface Signal

    - - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCStore HVAC DOStore-2 Fire Dampers CLose Trip60-XS-9722 Interface Signal - - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCESD DOWorkshop HVAC system Trip60-XS-9731 ESD Interface - - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCESD DOWorkshop Fire Dampers close60-XS-9732 ESD Interface - - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCFLD DOFW Deluge to Zone A Module 10,20 Open60-XY-8100 Deluge Valve SOV 55570-MA-DW-0003 - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCFLD DOFW Deluge to Zone c Modules 55,90, Open60-XY-8102 Deluge Valve SOV 55570-MA-DW-0003 - NA NANANANA

    M60-

    B1 -- -FGS NAFGSN.I.S VFCFLD DOFW Deluge to Zone-B M30 Open60-XY-8103 Deluge Valve SOV 55570-MA-DW-0005 - NA NANANANA

  • 5/25/2018 (DT-0581) 21010-BAE-70000-IN-RL-0003_revB2

    10/11

    Rev

    BUMI ARMADA

    ENGINEERING

    I/ODestination

    1014-M00-ILS-003OTE Doc. Number:

    Function Tag RemarksTag NoModule

    21010-BAE-70000-IN-RL-0003

    Page

    Revision:

    BAE Doc. Number:

    FGS I/O LIST

    CHARTER HIRE OF FPSO FOR D1 FIELDB2

    10/11

    I.S /Non I.S

    Instrument Service Instrument Type F&G Loc. PlanDwg No.

    I/O Type SystemI/OSource Signal Type Disp. Range Units AlarmLoLo

    AlarmLo

    AlarmHi

    AlarmHiHi

    SetPointOperating principle

    M60-

    B1 -- -FGS NAFGSN.I.S VFCESD DOFPSO ESD Level-160-XZ-0001 ESD Interface NA - NA NANANANA

    M60-

    B0 -- -LCP NAFGSN.I.S 24V DCFGS DOConfirmed Fire at Topside60-XZ-0001A ESD Interface - - - ----

    M60-

    B1 -- -FGS NAFGSN.I.S VFCESD DOFPSO ESD Level-160-XZ-0002 ESD Interface NA - NA NANANANA

    M60-

    B0 -- -LCP NAFGSN.I.S 24V DCFGS DOConfirmed Gas at Topside60-XZ-0002A ESD Interface - - - ----

    M70Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-014FGSN.I.S 3w 4-20mAFGS AIPower Gen/N2&Air System FlameDetector70-FD-4540-014 Flame Detector 21010-BAE-70070-IN-

    DW-0003- 16 20---

    M70Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-015FGSN.I.S 3w 4-20mAFGS AIPower Gen/N2&Air System Flame Detector70-FD-4540-015 Flame Detector 21010-BAE-70070-IN-

    DW-0003- 16 20---

    M70Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-016FGSN.I.S 3w 4-20mAFGS AIPower Gen/N2&Air System Flame Detector70-FD-4540-016 Flame Detector 21010-BAE-70070-IN-

    DW-0003- 16 20---

    M70Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-017FGSN.I.S 3w 4-20mAFGS AIPower Gen/N2&Air System Flame Detector70-FD-4540-017 Flame Detector 21010-BAE-70070-IN-

    DW-0003- 16 20---

    M70IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-023FGSN.I.S 3w 4-20mAFGS AIPower Gen/N2&Air System GasDetector70-GD-4530-023 Gas Detector 21010-BAE-70070-IN-

    DW-0003- 20 60---

    M70IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-023FGSN.I.S 3w 4-20mAFGS AIPower Gen/N2&Air System GasDetector70-GD-4530-024 Gas Detector 21010-BAE-70070-IN-

    DW-0003- 20 60---

    M70IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-024FGSN.I.S 3w 4-20mAFGS AIPower Gen/N2&Air System Gas Detector70-GD-4530-025 Gas Detector 21010-BAE-70070-IN-

    DW-0003- 20 60---

    M70

    IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-041FGSN.I.S 3w 4-20mAFGS AIAi rCompressor package Gas Detector (AirIntake)

    70-GD-4540-041 Gas Detector 21010-BAE-70070-IN-DW-0003

    - 20 60---

    M70

    IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-042FGSN.I.S 3w 4-20mAFGS AIAir Compressor package Gas Detector (AirIntake)

    70-GD-4540-042 Gas Detector 21010-BAE-70070-IN-DW-0003

    - 20 60---

    M70

    IR Point Type

    B0 %LEL0 60FLD GAH,GAHH-4540-043FGSN.I.S 3w 4-20mAFGS AIAir Compressor package Gas Detector (AirIntake)

    70-GD-4540-043 Gas Detector 21010-BAE-70070-IN-DW-0003

    - 20 60---

    M70-

    A0 -- -FLD -FGSN.I.S VFCFGS DIPower Gen/N2&Air System MAC70-MAC-4540-007 Manual Alarm Call Point 21010-BAE-70070-IN-

    DW-0003- - ----

    M90Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-018FGSN.I.S 3w 4-20mAFGS AILaydown/chemical injection FlameDetector90-FD-4540-018 Flame Detector 21010-BAE-70090-IN-

    DW-0003- 16 20---

    M90Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-019FGSN.I.S 3w 4-20mAFGS AILaydown/chemical injection Flame Detector90-FD-4540-019 Flame Detector 21010-BAE-70090-IN-

    DW-0003- 16 20---

    M90Multi Spectrum IR

    B0 mA0 20FLD FAH,FAHH-4540-020FGSN.I.S 3w 4-20mAFGS AILaydown/chemical injection Flame Detector90-FD-4540-020 Flame Detector 21010-BAE-70090-IN-

    DW-0003- 16 20---

    M90IR Point Type

    B1 %LEL0 60FLD GAH,GAHH-4540-044FGSN.I.S 3w 4-20mAFGS AIE&I workshop Air Intake Gas Detector90-GD-4540-044 Gas Detector 21010-BAE-70090-IN-

    DW-0003- 20 60---

    M90IR Point Type

    B1 %LEL0 60FLD GAH,GAHH-4540-045FGSN.I.S 3w 4-20mAFGS AIE&I workshop Air Intake Gas Detector90-GD-4540-045 Gas Detector 21010-BAE-70090-IN-

    DW-0003- 20 60---

    M90IR Point Type

    B1 %LEL0 60FLD GAH,GAHH-4540-046FGSN.I.S 3w 4-20mAFGS AIWorkshop Air Intake Gas Detector90-GD-4540-046 Gas Detector 21010-BAE-70090-IN-

    DW-0003- 20 60---

    M90IR Point Type

    B1 %LEL0 60FLD GAH,GAHH-4540-047FGSN.I.S 3w 4-20mAFGS AIWorkshop Air Intake Gas Detector90-GD-4540-047 Gas Detector 21010-BAE-70090-IN-

    DW-0003- 20 60---

    M90Point Type

    B0 -- -FLD -FGSN.I.S VFCFGS DIE&I Work shop Heat Detector90-HD-4540-004 Heat Detector 21010-BAE-70090-IN-

    DW-0003- - ----

    M90Point Type

    B0 -- -FLD -FGSN.I.S VFCFGS DIE&I Work shop Heat Detector90-HD-4540-005 Heat Detector 21010-BAE-70090-IN-

    DW-0003- - ----

    M90Point Type

    B0 -- -FLD -FGSN.I.S VFCFGS DIWork shop Heat Detector90-HD-4540-006 Heat Detector 21010-BAE-70090-IN-

    DW-0003- - ----

    M90Point Type

    B0 -- -FLD -FGSN.I.S VFCFGS DIWork shop Heat Detector90-HD-4540-007 Heat Detector 21010-BAE-70090-IN-

    DW-0003- - ----

    M90-

    A0 -- -FLD -FGSN.I.S VFCFGS DILaydown /Chemical Injection MAC90-MAC-4540-008 Manual Alarm Call Point 21010-BAE-70090-IN-

    DW-0003- - ----

    M90Photo Electric/Ionisation

    B0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AIE&I Workshop Smoke Detector90-SD-4540-004 Smoke Detector 21010-BAE-70090-IN-

    DW-0003- - ----

  • 5/25/2018 (DT-0581) 21010-BAE-70000-IN-RL-0003_revB2

    11/11

    Rev

    BUMI ARMADA

    ENGINEERING

    I/ODestination

    1014-M00-ILS-003OTE Doc. Number:

    Function Tag RemarksTag NoModule

    21010-BAE-70000-IN-RL-0003

    Page

    Revision:

    BAE Doc. Number:

    FGS I/O LIST

    CHARTER HIRE OF FPSO FOR D1 FIELDB2

    11/11

    I.S /Non I.S

    Instrument Service Instrument Type F&G Loc. PlanDwg No.

    I/O Type SystemI/OSource Signal Type Disp. Range Units AlarmLoLo

    AlarmLo

    AlarmHi

    AlarmHiHi

    SetPointOperating principle

    M90Photo Electric/Ionisation

    B0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AIE&I Workshop Smoke Detector90-SD-4540-005 Smoke Detector 21010-BAE-70090-IN-

    DW-0003- - ----

    M90Photo Electric/Ionisation

    B0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AIWorkshop Smoke Detector90-SD-4540-006 Smoke Detector 21010-BAE-70090-IN-

    DW-0003- - ----

    M90Photo Electric/Ionisation

    B0 -- -E-House -FGSN.I.S 2W 4-20mAFGS AIWorkshop Smoke Detector90-SD-4540-007 Smoke Detector 21010-BAE-70090-IN-

    DW-0003- - ----