DSE9470 Configuration Suite PC Software Manual ISSUE DEEP SEA ELECTRONICS PLC DSE9470 Configuration Suite PC Software Manual Document Number 057-159 Author: Fady Atallah

Dse9470 Software Manual

Embed Size (px)

DESCRIPTION

DSE sofware manual

Citation preview

Page 1: Dse9470 Software Manual

DSE9470 Configuration Suite PC Software Manual ISSUE

DEEP SEA ELECTRONICS PLC DSE9470 Configuration Suite PC Software

Manual

Document Number 057-159

Author: Fady Atallah

Page 2: Dse9470 Software Manual

DSE9470 Configuration Suite PC Software Manual

2

DEEP SEA ELECTRONICS PLC Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel: +44 (0) 1723 890099 Sales Fax: +44 (0) 1723 893303 E-mail : [email protected] Website : www.deepseaplc.com

DSE9470 Configuration Suite PC Software Manual © Deep Sea Electronics Plc All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents Act 1988. Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to Deep Sea Electronics Plc at the address above. The DSE logo is a UK registered trademarks of Deep Sea Electronics PLC. Any reference to trademarked product names used within this publication is owned by their respective companies. Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice. Amendments List Issue Comments Minimum

Module version required

Minimum Configuration Suite

Version required

1 Initial release 1 Typeface: The typeface used in this document is Arial. Care should be taken not to mistake the upper case letter I with the numeral 1. The numeral 1 has a top serif to avoid this confusion.

NOTE: Highlights an essential element of a procedure to ensure correctness.

CAUTION!: Indicates a procedure or practice which, if not strictly observed, could result in damage or destruction of equipment.

WARNING!: Indicates a procedure or practice which could result in injury to personnel or loss of life if not followed correctly.

Deep Sea Electronics Plc owns the copyright to this manual, which cannot be copied, reproduced or disclosed to a third party without prior written permission.

SAE Society of Automotive Engineers (USA)

Page 3: Dse9470 Software Manual

DSE9470 Configuration Suite PC Software Manual

3

TABLE OF CONTENTS

1 BIBLIOGRAPHY .......................................................................................... 3

2 DESCRIPTION ............................................................................................. 3

3 INSTALLATION AND USING THE DSE CONFIGURATION SUITE SOFTWARE ....................................................................................................... 4

4 EDIT CONFIG............................................................................................... 4

4.1 SCREEN LAYOUT .............................................................................................................................. 4

4.2 CHARGER .......................................................................................................................................... 5

4.2.1 CHARGER SETTINGS................................................................................................................ 5

4.2.2 TIMERS ....................................................................................................................................... 5

4.3 BATTERY............................................................................................................................................ 6

4.3.1 BATTERY TEMPERATURE SENSOR........................................................................................ 6

4.3.2 OVER CURRENT ALARM .......................................................................................................... 7

4.3.3 OVER VOLTAGE ALARM ........................................................................................................... 7

4.4 MAINS ................................................................................................................................................. 8

4.4.1 MAINS VOLTAGE ALARMS ....................................................................................................... 8

4.5 COMMUNICATIONS ........................................................................................................................... 9

4.5.1 RS485 PORT............................................................................................................................... 9

1 BIBLIOGRAPHY This document refers to and is referred to by the following DSE publications which can be obtained from the DSE website www.deepseaplc.com: DSE PART DESCRIPTION 053-049 DSE9000 Series Battery Charger Installation Instructions 057-085 DSE9000 Series Battery Charger Operator Manual

2 DESCRIPTION This manual covers the operation of the DSE Configuration Suite for DSE9470 battery charger. Separate manuals cover the remaining DSE modules supported by the software.

The DSE Configuration Suite allows the DSE9470 to be connected to a PC via USB ‘A –USB B’ cable. Once connected the various operating parameters within the charger can be viewed or edited as required by the engineer. This software allows easy controlled access to these values and also has diagnostic monitoring facilities. The DSE Configuration Suite should only be used by competent, qualified personnel, as changes to the operation of the module may have safety implications on the panel to which it is fitted. The information contained in this manual should be read in conjunction with the information contained in the appropriate module documentation. This manual only details which settings are available and how they may be used. A separate manual deals with the operation of the charger (See section entitled Bibliography elsewhere in this document).

Page 4: Dse9470 Software Manual

Edit Configuration

4

3 INSTALLATION AND USING THE DSE CONFIGURATION SUITE

SOFTWARE For information in regards to installing and using the DSE Configuration Suite Software please refer to DSE publication: 057-151 DSE Configuration Suite PC Software Installation & Operation Manual which can be found on our website: www.deepseaplc.com

4 EDIT CONFIG This menu allows module configuration, to change the function of Inputs, Outputs and LED’s, system timers and level settings to suit a particular application. 4.1 SCREEN LAYOUT

The type of configuration file being edited

Close this configuration file

Move to the Previous or Next configuration page

The coloured shading shows the currently selected page.

Click + or – to show or hide the sub settings within each sections.

Click to select the subsection to view / edit

Page 5: Dse9470 Software Manual

Edit Configuration - Charger

5

4.2 CHARGER 4.2.1 CHARGER SETTINGS

4.2.2 TIMERS

Timer Description Bulk Charge Run-On This is the duration after the bulk charge is over (determined by the battery charger)

for which the charger will continue in bulk charge mode before automatically switching to float mode.

Free entry boxes to allow the user to give the configuration file a description. Typically this is used to enter the job number, customer name, engineers name etc.

Click and drag to change the setting. Timers increment in steps of 1 second up to one minute, then in steps of 30 seconds up to 30 minutes, then in steps of 30 minutes thereafter (where allowed by the limits of the timer).

Page 6: Dse9470 Software Manual

Edit Configuration - Battery

6

4.3 BATTERY 4.3.1 BATTERY TEMPERATURE SENSOR

Over Temperature Alarms Trip If the battery temperature exceeds the Trip value setting

AND Remains higher for the “Trip Delay” time duration : The onboard status LED 2 will light continuously and the NC relay output will change to open position.

Trip Delay

Return If the battery temperature falls below the return value setting AND Remains lower for the “Return Delay” time duration : The onboard status LED 2 will turn back off and the NC relay output will return to close position.

Return Delay

Temperature Compensation Voltage Reduction /°C

The amount by which the voltage is decreased for each degree Celsius of temperature rise. This is normally specified by the battery manufacturer.

Enable or disable the external Battery Temperature Sensor (PT1000). The relevant values below will appear greyed out if the option is disabled.

Type the value or click the up and down arrows to change the settings

Click and drag to change the settings

Page 7: Dse9470 Software Manual

Edit Configuration - Battery

7

4.3.2 OVER CURRENT ALARM

Over Current Alarm Trip If the current drawn by the battery exceeds the trip value setting,

AND Remains higher for the “Trip Delay” time duration : The onboard status LED 1 will start flashing and the NC relay output will change to open position.

Trip Delay

Return If the current drawn by the battery falls below the return value setting AND Remains lower for the “Return Delay” time duration : The onboard status LED 1 will switch off and the NC relay output will return to close position.

Return Delay

4.3.3 OVER VOLTAGE ALARM

Over Voltage Alarm Trip If the battery voltage exceeds the trip value setting

AND Remains higher for the “Trip Delay” time duration : The onboard status LED 1 will light continuously and the NC relay output will change to open position.

Trip Delay

Return If the battery voltage falls below the return value setting AND Remains lower for the “Return Delay” time duration : The onboard status LED 1 will switch off and the NC relay output will return to close position.

Return Delay

Enable or disable the alarms. The relevant values below will appear greyed out if the option is disabled.

Type the value or click the up and down arrows to change the settings

Click and drag to change the settings

Enable or disable the alarms. The relevant values below will appear greyed out if the option is disabled.

Type the value or click the up and down arrows to change the settings

Click and drag to change the settings

Page 8: Dse9470 Software Manual

Edit Configuration - Mains

8

4.4 MAINS 4.4.1 MAINS VOLTAGE ALARMS

Mains Over Voltage Alarms Trip If the Mains voltage exceeds the trip value setting

AND Remains higher for the “Trip Delay” time duration : The onboard status LED 1 will start flashing

Trip Delay

Return If the Mains voltage falls below the return value setting AND Remains inactive for the “Return Delay” time duration : The onboard status LED 1 will switch off

Return Delay

Mains Under Voltage Alarms Trip If the Mains voltage falls below the trip value setting

AND Remains active for the “Trip Delay” time duration : The onboard status LED 1 will start flashing

Trip Delay

Return If the Mains voltage exceeds the return value setting AND Remains inactive for the “Return Delay” time duration : The onboard status LED 1 will switch off

Return Delay

Enable or disable the alarms. The relevant values below will appear greyed out if the option is disabled.

Type the value or click the up and down arrows to change the settings

Click and drag to change the settings

Page 9: Dse9470 Software Manual

Edit Configuration - Communications

9

4.5 COMMUNICATIONS

4.5.1 RS485 PORT

RS485 Port Basic Slave ID Baud Rate

The Modbus Slave address and RS485 baud rate. This is used when connecting the RS485 port to a Modbus Master device.

Advanced Master Inactivity Timeout

Modbus timer to enable the charger to detect when the Modbus Master is no longer communicating.

Click to edit the RS485 settings

Page 10: Dse9470 Software Manual

This page is intentionally blank

10