Upload
levgrigoryev7396
View
102
Download
1
Embed Size (px)
Citation preview
Design Standards
M O D U L E
J A N U A R Y 2 0 0 5
FIRE PROTECTION /L I F E S A F E T Y
14
14 - Fire Protection / Life Safety Renaissance Hotel
Fire Protection / Life Safety
Table of Contents
Subject ................................................................................... Page A. General Requirements............................................................. 1 B. Definitions ................................................................................ 1 C. Codes, References and Standards.......................................... 2 D. Systems Testing ...................................................................... 2 E. Submittals ................................................................................ 3 F. Automatic Sprinkler / Standpipe System.................................. 4 G. Fire Alarm and Communications.............................................. 6 H. Mechanical Smoke Control .................................................... 8 I. Kitchen Hood and Duct Fire Suppression................................ 9 J. Emergency Electrical Systems .............................................. 9 K. Central Control Station (Fire Command Room)..................... 10 L. Emergency Egress................................................................. 10 M. Example Diagrams................................................................. 11
Module Organization • This Module is a part of an integrated series of 17 Modules. • Coordination with information from other Modules is required. • The reference symbol <XX> is used to indicate a Module reference that
includes additional information.
Marriott Confidential and Proprietary Information The contents of the Design Standards are confidential and proprietary to Marriott International, Inc. and may not be reproduced, disclosed, distributed or used without the express permission of an authorized representative of Marriott.
Copyright, Marriott International, Inc., unpublished material. All rights Reserved
14 - B January 2005 Design Standards - Copyright, Marriott International, Inc.
Renaissance Hotel Fire Protection / Life Safety - 14
Fire Protection / Life Safety
A. General Requirements 1. Application:
• Marriott's Fire Protection and Life Safety Design Standards apply to all Marriott International Brands and owned, managed and franchised properties.
• The Marriott Fire Protection and Life Safety Design Standards include design standards, performance criteria, reference standards and life safety process verification that defines a comprehensive fire protection program. Coordinate requirements with Modules 10, 15A, 15B and 15C.
• Application of these standards to a specific project requires a design analysis to define project requirements and establish a project's unique standards compliance program. For example, a project's qualification as either a low-rise or high-rise building will significantly affect the elements of a project's fire protection and life safety program.
• When a Marriott property is integrated with or interconnected with another building, the building shall provide protection equal to the fire protection and life safety standards required for the Marriott property, as defined by Marriott’s Fire Protection Department on a case-by-case evaluation.
2. Systems: Provide the following functional systems in compliance with the listed Performance Criteria: • Sprinkler / Standpipe System • Fire Alarm and Communications • Mechanical Smoke Control • Kitchen Hood and Duct Fire Suppression • Standby Power, Emergency Power and Lighting • Central Control Station (Fire Command Room) • Emergency Egress
B. Definitions 1. Low-Rise Building: A building that does not qualify as a
High-Rise Building as defined below. 2. High-Rise Building: A building conforming to one or both of
the following configurations: • Stories: More than 6 stories (required by Marriott's Fire
Protection Department). • Height: More than 23 m (75 ft.) in height to the floor of
the highest occupiable story in compliance with NFPA 101.
Design Standards - Copyright, Marriott International, Inc. January 2005 14 - 1
14 - Fire Protection / Life Safety Renaissance Hotel
• Exception: Buildings more than 6 stories and less than 23 m (75 ft.) high (as defined above) may be designed as a Low-Rise Building except must be provided with guestroom corridor and public area smoke exhaust and stairwell pressurization.
3. Back of House (BOH): Includes areas such as employee spaces, employee restrooms, laundry, offices, work areas, kitchen, storage areas, shops, etc.
C. Codes, References and Standards 1. Application: Current edition and associated references
are the basis for Marriott's Fire Protection / Life Safety Design Standards and are applicable to all Marriott managed, owned and franchised properties.
2. National Fire Protection Association (NFPA) Standards: Comply with the following: • NFPA 101: Life Safety Code (except no “horizontal
exits”) • NFPA 13: Standards for the Installation of Sprinkler
Systems • NFPA 14: Standpipe Systems • NFPA 17: Wet Chemical Extinguishing Systems • NFPA 20: Centrifugal Fire Pumps • NFPA 70: National Electric Code • NFPA 72: National Fire Alarm Code • NFPA 92A, 92B: Smoke Control Systems • NFPA 96: Ventilation and Fire Protection of
Commercial Cooking Operations • NFPA 110: Emergency and Standby Power Systems
3. Underwriters Laboratories (UL) Listing: Provide UL listed materials, appliances and equipment.
4. Governing Regulations: Follow governing laws, codes, and regulations that are more stringent. Refer regulation conflicts with Marriott's Design Standards to Marriott for resolution.
5. Americans with Disabilities Act (ADA): Comply with Life Safety requirements. See the Design Standards for general accessibility requirements.
D. Systems Testing 1. Application: Before a property is opened to the public,
the fire protection and life safety systems shall be fully operational, contractor tested and approval obtained from Marriott's Fire Protection Department. In order to obtain Marriott's approval, the fire protection and life safety systems shall be operated by the contractor under simulated emergency conditions in the presence of Marriott Fire Protection personnel and the contractor shall demonstrate compliance with Marriott's standards.
14 - 2 January 2005 Design Standards - Copyright, Marriott International, Inc.
Renaissance Hotel Fire Protection / Life Safety - 14
2. Automatic Sprinkler / Standpipe System (Paragraph F.): • Contractor shall flush and pressure test system prior to
Marriott's observation of the test of water flow and tamper switches.
• Fire pump shall be tested and certified by the manufacturer.
3. Fire Alarm and Communications (Paragraph G.): • Contractor shall pretest and operate system without
trouble lights exhibited. • Contractor shall demonstrate compliance by activating all
devices to set-off alarms and verifying that proper point address or zone indications appear on alarm panel.
4. Mechanical Smoke Control (Paragraph H.): • Prior to testing smoke control systems, HVAC systems
shall be contractor tested and balanced. • Public area, atrium and guestroom corridor smoke
exhaust, and stairwell pressurization systems shall be operational and tested to clear "cold smoke" so that exit signs are visible within 10 minutes of activation.
5. Kitchen Hood and Duct Fire Suppression (Paragraph I.): • Contractor shall pretest all coordinated components by
activation of kitchen hood and duct flow switch or control unit.
• Contractor shall demonstrate compliance by operating initiating devices, activating coordinated alarms, gas, electric and hood supply air fan shut-downs.
6. Emergency Electrical Systems (Paragraph J.): • Diesel generator shall be operational and tested to
automatically activate upon loss of normal incoming power and to provide standby and emergency service to operate emergency lighting and specified systems.
• Battery standby power and UPS systems providing emergency power and lighting shall be fully operational.
7. Central Control Station (Fire Command Room) – (K.): Panels, indicators, controls and systems shall be operational, tested and approved.
8. Emergency Egress (Paragraph L.): Facilities for emergency egress shall be operational and unobstructed.
E. Submittals 1. General: Prior to installation of systems, submit the following
for review and approval to: Marriott Corporate Fire Protection: • Floor plans with exiting and occupant load diagrams. • Fire alarm system diagrams, shop drawings and
equipment product sheets. • Automatic sprinkler / standpipe system shop drawings,
hydraulic calculations and equipment product sheets.
Design Standards - Copyright, Marriott International, Inc. January 2005 14 - 3
14 - Fire Protection / Life Safety Renaissance Hotel
Zurich Services Corporation: • Automatic sprinkler / standpipe system shop drawings,
hydraulic calculations and equipment product sheets. • Set of construction (contract) drawings.
2. Mailing Addresses: • Marriott International, Inc.; Marriott Corporate Fire
Protection, Dept. 52/924.36; 10400 Fernwood Road; Bethesda, MD 20817
• Zurich Services Corporation; Risk Engineering Department; 1818 Market Street, 21ST Floor; Philadelphia, PA 19103; Attn: Mr. Richard Gallagher, Sr. Risk Engineering Consultant
F. Automatic Sprinkler / Standpipe System 1. Design Requirements:
• Standards: NFPA 13 (not NFPA 13R), 14 and 20. • Water Source: Perform flow-test(s) and document.
Provide dependable source of water quantity and pressure from municipal water main or from on-site cistern or tank(s) if municipal water is not available.
• Safety Factor: Provide a 10% hydraulic safety factor. • Pressure Reducing Valves: Design system within
maximum pressure of 175 psi without use of pressure reducing valves.
• Low-Rise Buildings: Provide control valves, flow and tamper switches at each connection monitored on the fire alarm system. Locate inspector's test assembly at remote end of zone (not in guestrooms) with discharge piped to exterior drain. See example detail at end of this Module.
• High Rise Buildings: Connect guestroom floor sprinkler piping to 2 risers at each floor with a control valve and flow and tamper switches at each connection. See example "looped" riser and inspector test drain assembly detail at end of this Module. At guestroom and non-guestroom levels, locate inspector test assembly at remote end of zone, hardpiped to exterior similar to low-rise building.
2. System Application: Equip Marriott properties with complete hydraulically designed combination / automatic sprinkler / standpipe system zoned by floor. • Building Footprint: Sprinkler building areas within
building “footprint”. • Parking Garages / Decks: Provide sprinkler protection,
unless greater than 50% of perimeter is open to exterior air and not under hotel footprint.
14 - 4 January 2005 Design Standards - Copyright, Marriott International, Inc.
Renaissance Hotel Fire Protection / Life Safety - 14
• Utility Spaces: Provide complete sprinkler protection in electrical, mechanical, telephone and computer rooms.
• Loading Docks and Truck Bays: Provide sprinkler protection. If subject to freezing, provide dry-pipe system.
• Freezer and Cooler Boxes: Protect with dry-type heads off of area wet sprinkler system.
• Guestroom Bathrooms: Sprinklers are not required if bathroom is less than 5.10 m2 (55 sq. ft.). Regardless of bathroom area, sprinklers are required when combustible tubs or shower or tub surrounds (plastic / fiberglass) enclosures are used.
• Closets and Pantries: Sprinklers are not required in clothes closets, linen closets and pantries within hotel guestrooms where the area of the space does not exceed 2.2 m2 (24 sq. ft.). Closets and pantries with washer, dryer, water heater, mechanical or electrical equipment require sprinklers.
• Building Exception: Sprinkler / standpipe system may not be required in existing buildings of 2 stories or less where all guestrooms exit directly to exterior (no enclosed corridors).
3. Wet-Pipe Sprinkler: Provide wet-pipe sprinklers for habitable spaces such as guestrooms, guestroom corridors, restaurants, ballrooms / meeting rooms, public and back-of-house areas.
4. Dry-Pipe Sprinklers: Provide dry-pipe sprinklers in attic and unheated areas to avoid the possibility of freezing. • Dry type heads from the wet system may be used in
small unheated areas. • Wet sprinkler piping covered with attic insulation, pipe
insulation or heat tape is not considered “freeze protected” and is unacceptable.
• Use galvanized steel pipe. • Design for dry valve trip test that provides water to the
remote inspector test assembly within 60 seconds. • Provide system with valve, trim, tank mounted
compressor, control and test valves, gauges, pressure and high / low air pressure switches and approved drains.
5. Sprinkler Heads: Fast-response 68° to 74° C (155° to 165° F), recessed, semi-recessed and concealed throughout, except where listed for a particular application as follows:
Design Standards - Copyright, Marriott International, Inc. January 2005 14 - 5
14 - Fire Protection / Life Safety Renaissance Hotel
Room / Space Head Type Temp. Rating
Attic Systems Standard Response - ventilatedStandard Response - unventilated
100° C (212° F) 141° C (286° F)
Dry-pipe Systems Standard Response - ventilated (unoccupied spaces) Standard Response - unventilated
100° C (212° F) 141° C (286° F)
Mechanical / Electrical Quick Response 68° to 74° C (155 to 165° F)
Balcony (combustible) Dry-side wall, corrosion – resistant / Quick Response 100° C (212° F)
Porches Dry-side wall, corrosion – resistant / Quick Response 100° C (212° F)
Elevator Machinery Standard Response 100° C (212° F) Swimming Pools (Indoor)
Corrosion-resistant / Quick Response
68° to 74° C (155° to 165° F)
Sauna / Steam Rooms Laundry Dryer Plenum
Corrosion-resistant / Quick Response 141° C (286° F)
Walk-in Coolers / Freezers Dry pendent Quick Response 74° C (165° F)
6. Sprinkler Coordination:
• Install sprinkler heads with the manufacturer’s minimum allowable projection from the wall or ceiling.
• Coordinate locations of sprinkler heads at guestrooms and public areas with the interior designer to avoid location conflicts and minimize appearance impact.
• In corridor ceilings, generally, position heads along centerline of corridor width.
• In ceilings with acoustical tiles, position heads in center of tiles.
G. Fire Alarm and Communications 1. Requirements: Equip entire building with a central fire
alarm system. See the Fire Alarm System Sequence Matrix in this Module. Coordinate with <15C>. • Standard: NFPA 72. • System: Provide fully point addressable, analog
system (all alarm initiating and supervisory devices individually addressable) in all buildings.
• Campus Style Sites: Provide point addressable networking that reports to the continuously attended property location.
• Testing: Provide the following at the Fire Alarm Control Panel (FACP). + Disconnect switches to disable notification, audible
appliances, visual strobes, and auxiliary function points for testing purposes.
+ Alarm sensitivity testing at FACP.
14 - 6 January 2005 Design Standards - Copyright, Marriott International, Inc.
Renaissance Hotel Fire Protection / Life Safety - 14
2. Smoke Sensors (Detectors): • Guestrooms, Suite Rooms and other Sleeping Units:
Provide smoke sensors with sounder bases to meet the following: + Photoelectric type sensor. + Sounder Base: Provide minimum audible alarm of 85
dBA at 10 feet; minimum of 75 dBA “at the pillow”. + Activation of room smoke sensor to immediately and
automatically sound an alarm within the room of incident.
+ System smoke sensor normal and emergency power is provided by the FACP.
+ In suites and other mixed sleeping spaces, provide smoke sensors in each separate sleeping room, in living rooms convertible to sleeping and in areas providing access to the corridor doorway. Multiple sensor sounder bases located within the same suite or unit shall activate at the same time.
• Public Areas, Corridor and Back of House Areas: Provide system smoke sensors where: + Required by governing code. + Smoke exhaust is required in compliance with the
other requirements of this Module. • Duct Smoke Sensors: Provide duct smoke sensors as
required by the Life Safety Code. Provide remote test switch and indicator light accessible from floor level.
3. Carbon Monoxide Detectors: Install CO detectors with sounders connected to the FACP. • General: Provide in rooms and areas containing fuel
burning appliances and equipment. • Fireplaces: Provide detector in guestrooms and public
spaces containing gas or wood burning fireplaces. 4. Manual Pull Stations: At Front Desk only, unless required
in other locations by applicable codes. 5. Firefighter Communication Systems: Comply with
governing code requirements. 6. Alarm Notification Appliances: Provide audible notification
appliances (speakers, mini-horns, horns, or sounder bases of system connected smoke sensors) and visual notification strobe lights in locations according to the following: • Guestroom, Suite Rooms and Other Sleeping Spaces:
Provide audible appliances in each sleeping room. In properties with separate multiple sleeping spaces such as suites and apartments, provide in each sleeping room.
• In ADA Accessible and Hearing Accessible designated Guestrooms, Suites, or Apartments: provide audible alarm and visual alarm strobe(s).
Design Standards - Copyright, Marriott International, Inc. January 2005 14 - 7
14 - Fire Protection / Life Safety Renaissance Hotel
+ Arrange strobe(s) to flash in each room or area and bathroom when smoke sensor(s) in room(s) or unit(s) activate.
+ Arrange strobe(s) to flash in each room or area and bathroom when the building fire alarm notification alarms activate.
Low Rise Buildings: • Guestrooms, Sleeping Rooms: Provide smoke sensor
with sounder base. • Accessible Guestrooms / Sleeping Rooms: Provide
smoke sensor with sounder base and visual stobe(s). Additionally provide a strobe in the bathroom.
• Public Areas, Corridors & Back of House (BOH): Provide mini horns and visual strobes.
High Rise Buildings: • Guestrooms, Sleeping Rooms: Speaker only. • Accessible Guestrooms / Sleeping Rooms: Speaker
and strobe(s). Additionally, provide strobe in bathroom(s).
• Public Areas, Corridors & BOH: Speaker and strobe. 7. Emergency Message Appliances:
• Low-Rise Buildings: Alert tone (three-pulse temporal pattern).
• High-Rise Buildings: Pre-recorded, alert and automatic voice message with manual voice communication override.
8. Annunciator: Provide point address to indicate floor, device and type of alarm. Provide annunciator(s) in area(s) monitored 24 hours by property Associates (Security, AYS, PABX room, Front Desk) in a location(s) approved by Marriott and governing authority.
H. Mechanical Smoke Control <15A> 1. Standard: NFPA 92A and 92B. 2. Building Configuration:
• Low-Rise Buildings: Mechanical smoke control may be required by Marriott Fire Protection Department, if judged that fire department access is limited or exiting is not adequate.
• High-Rise Buildings: Mechanical smoke control is required.
• Atrium: Consult Marriott Fire Protection Department for atrium smoke control requirements.
3. Application: • Public Areas: Provide mechanical smoke exhaust in
lobby, atriums, restaurants, pre-function areas, ballrooms and meeting rooms. Activate by area smoke detectors.
14 - 8 January 2005 Design Standards - Copyright, Marriott International, Inc.
Renaissance Hotel Fire Protection / Life Safety - 14
• Guest Corridors. Provide mechanical smoke exhaust. Activate by area smoke sensors and by floor water flow switches (independent of each other).
• Stairwell Pressurization: Mechanically pressurize stairwell in compliance with NFPA 101 <15A>. See “Fire Alarm System Sequence Matrix” at end of this Module for sequence of operation.
• Manual Override: Include manual override controls at the Central Control Station (Fire Command Room) or designated area.
I. Kitchen Hood and Duct Fire Suppression 1. Application: Provide fire suppression system for kitchen
hoods and duct in food production kitchens <10> <15A> <15B> <15C>.
2. Suppression System: Provide the following: • Sprinkler / Water Mist System: Sub-zone off kitchen area
sprinkler main with separate annunciated flow and control valve tamper switches. (See NFPA 13, Section 3-9). + Provide the following type heads in locations of food
production kitchen hoods and ducts: Hood / Duct Locations Head Type Temp. Rating $ Cooking Surfaces / Appliances
Grinnell EA-1 163° C (325° F)
$ Plenums / Collars Grinnell EA-1 260° C (500° F) $ Exhaust Ducts Grinnell EA-1 260° C (500° F)
+ Exception: Where sprinkler / water mist head is not approved by governing authority, provide Ansul “Piranha” dual agent suppression system. Verify with Marriott Fire Protection.
3. Other Functions: Provide kitchen hood and duct system flow switch or control units of Ansul fire suppression system to perform these functions: • Send fire alarm signal to FACP. • Disconnect gas and all electric for cooking appliances
and lighting under the hood(s). (Manual reset is required).
• Shut-off kitchen hood make-up air handler.
J. Emergency Electrical Systems <15C> 1. Standards: NFPA 110, NFPA 70 and NEC 70 2. Requirements: Emergency electrical systems are required
for standby power to emergency power and lighting, and to maintain property operation in the event of loss of normal incoming electrical service. <15C>
Design Standards - Copyright, Marriott International, Inc. January 2005 14 - 9
14 - Fire Protection / Life Safety Renaissance Hotel
K. Central Control Station (Fire Command Room) 1. High-Rise Buildings: Provide at a location approved by
the governing authority. <15C>
L. Emergency Egress 1. Standards: Comply with NFPA 101, The Life Safety
Code except “horizontal exits” are not permitted. 2. Guestroom Areas Corridors: <7B> A minimum of 2
remote exits; maximum 15.24 m (50 ft.) travel distance at dead-end corridors.
3. Ballrooms and Meeting Rooms (public assembly spaces): <6> • Exit Load: 0.65 m2 (7 sq. ft.) per occupant. • Dead-End Corridors: 6.10 m (20 ft.) maximum. • Ballrooms and Meeting Rooms with areas of 32.5 m2
(350 sq. ft.) and larger require two or more remote exits. Doors in operable partitions are not considered exits.
• Provide door hold-open(s) with automatic release devices.
• Provide panic hardware on assembly occupancy doors where occupant loads are greater than 100 persons.
4. Restaurant, Lounges and Board Rooms: • Exit Load: 1.4 m2 (15 sq. ft.) per occupant. • Occupant loads greater than 50 persons, room
requires two or more remote exits. • Egress paths through Kitchen do not qualify as an
exit. 5. Multi-Use Exits: Avoid sharing stairs and exit corridors
with other properties (office, retail, residence, etc.). If unavoidable, submit and obtain approval from Marriott of alternate facilities that safeguard the property operational and security integrity. See “Multi-Use Buildings” in the Design Standards for general requirements.
6. Exit Path: Provide normal and emergency lighting and minimum 3 ft. (0.9 m) wide, hard surfaced walkway leading to a public way.
7. Exit Discharge: One half of all exits shall discharge directly to exterior of building.
8. Stairwell Doors: Doors shall not be locked from either side.
14 - 10 January 2005 Design Standards - Copyright, Marriott International, Inc.
Renaissance Hotel Fire Protection / Life Safety - 14
M. Example Diagrams 1. General: The following schematic diagrams are provided to
illustrate the systems described in this Module. • Isometric of Typical Zoned Low-Rise Sprinkler System • Isometric of Typical "Looped" High-Rise Guestroom
Tower Sprinkler System • Typical "Looped" High-Rise Guestroom Tower Sprinkler
Riser Diagram • Fire Alarm System Sequence Matrix
Design Standards - Copyright, Marriott International, Inc. January 2005 14 - 11
14 - Fire Protection / Life Safety Renaissance Hotel
14 - 12 January 2005 Design Standards - Copyright, Marriott International, Inc.
Renaissance Hotel Fire Protection / Life Safety - 14
Design Standards - Copyright, Marriott International, Inc. January 2005 14 - 13
14 - Fire Protection / Life Safety Renaissance Hotel
14 - 14 January 2005 Design Standards - Copyright, Marriott International, Inc.
R
enai
ssan
ce H
otel
Fi
re P
rote
ctio
n / L
ife S
afet
y - 1
4
Fire
Ala
rm S
yste
m S
eque
nce
Mat
rix
Not
es: R
efer
ence
num
bers
are
sho
wn
in p
aren
thes
is (1
) for
not
es /
nota
tions
indi
cate
d be
low
and
in h
eadi
ngs
to th
e rig
ht.
System Smoke Sensors (1)
System Heat Detectors (7)
Eshaft / machine rom heat detectors
levator o
s
(2) & (7)
Guestroom System Smoke Sensors (3)
Manual Pull Stations
Waterflow Switches
Dry Sprinkler Pressure Switches
Kitchen Hood & Duct Fire Suppression
Low / High Air Supply Switche
Duct Smoke Sensors
Sprinkler Valve Tamper Switches
Fire Pump Signals (8)
Emergency Generator Signals (8)
Carbon Monoxide Signals
FAC
P: D
ispl
ay a
n au
dibl
e / v
isua
l ala
rm.
X X
X X
X X
X X
X X
X X
X X
Rem
ote
Ann
unci
ator
: Dis
play
an
audi
ble
/ vis
ual a
larm
. X
X X
X X
X X
X X
X X
X X
X A
udib
le /
Visu
al A
larm
s: A
ctiv
ate
audi
ble
/ vis
ual s
trobe
app
lianc
es o
n af
fect
ed fl
oor.
(5)
X
X
X
XX
X
Fire
Doo
r: R
elea
se m
agne
tic d
oor h
olde
rs o
n af
fect
ed fl
oor.
X X
X
X
Stai
rwel
l Pre
ssur
izat
ion:
Act
ivat
e pr
essu
rizat
ion.
X
X
X
X X
Sm
oke
Exha
ust:
Act
ivat
e ex
haus
t sys
tem
in a
ffect
ed z
ones
. X
X
(4)
(4)
G
uest
room
Aud
ible
Ala
rms:
Act
ivat
e al
arm
s in
room
s on
affe
cted
flo
or.
(5)
X
XX
XX
X
AD
A G
uest
room
s A
udib
le /
Visu
al S
igna
ls: A
ctiv
ate
both
sig
nals
in
AD
A a
nd h
earin
g-im
paire
d gu
estro
oms
on a
ffect
ed fl
oor.
(5)
X
XX
XX
X
Gue
stro
om L
ocal
Aud
ible
Ala
rms:
Act
ivat
e au
dibl
e al
arm
s on
ly in
ro
oms
cont
aini
ng a
larm
.
X
X(6
)
AD
A G
uest
room
Loc
al A
udib
le /
Visu
al S
igna
ls: A
ctiv
ate
both
si
gnal
s on
ly in
hea
ring-
impa
ired
and
ADA
gues
troom
con
tain
ing
alar
m.
XX
(6)
Air
Han
dler
s: S
hut d
own
asso
ciat
ed a
ir ha
ndle
rs.
X
K
itche
n G
as /
Elec
tric
: Shu
t dow
n as
soci
ated
kitc
hen
gas
& e
lect
ric.
X
Gen
eral
Not
es:
(1)
Sys
tem
sm
oke
sens
ors
not l
ocat
ed in
gue
stro
oms.
•
All
fire
alar
m s
yste
m d
evic
es to
be
poin
t add
ress
able
. (2
) P
rovi
de a
ssoc
iate
d el
evat
or re
call
and
shun
t trip
func
tions
in c
ompl
ianc
e w
ith A
SM
E A
-17.
1,
Ele
vato
r Cod
e.
• O
n ca
mpu
s st
yle
prop
ertie
s, p
rovi
de p
oint
add
ress
able
net
wor
king
re
porti
ng to
con
tinuo
usly
atte
nded
pro
perty
loca
tion.
(3
) G
uest
room
Sm
oke
Sen
sors
: Pro
vide
pho
toel
ectri
c ty
pe, w
ith s
ound
er b
ase
(min
imum
ratin
gs o
f 85
dBA
, with
75
dBA
"at t
he p
illow
").
At s
uite
s, m
ultip
le s
enso
rs s
hall
activ
ate
at th
e sa
me
time.
•
Spr
inkl
er s
yste
m w
ater
flow
and
tam
per s
witc
h al
arm
s ar
e an
nunc
iate
d on
the
FAC
P.
(4)
Wat
erflo
w a
larm
s sh
all n
ot a
ctiv
ate
smok
e co
ntro
l exh
aust
fans
whe
re s
mok
e co
ntro
l zon
es a
nd
fire
sprin
kler
zon
es d
o no
t cor
resp
ond.
(5)
Fire
ala
rms
shal
l act
ivat
e on
ly o
n flo
or o
f ala
rm.
Gov
erni
ng a
utho
rity
may
requ
ire a
dditi
onal
zo
ning
.
(6)
Car
bon
Mon
oxid
e de
tect
ors
in g
uest
room
s sh
all a
ctiv
ate
an a
larm
in th
e gu
estro
om o
f inc
iden
t an
d at
the
fire
alar
m c
ontro
l pan
el.
(7
) W
e re
com
men
d no
t usi
ng h
eat d
etec
tors
sin
ce fi
re s
prin
kler
s ar
e al
so a
ctiv
ated
by
heat
.
(8)
Run
and
faul
t sig
nals
. 14
- 15
Ja
nuar
y 20
05
Des
ign
Sta
ndar
ds -
Cop
yrig
ht, M
arrio
tt In
tern
atio
nal,
Inc.