  • 8/2/2019 Ds 824 Controller Datasheet

    1/3

    The DS-824 is an advanced low voltage version of the

    DS-8. It is primarily designed for hydronic and low volt-

    age guer, downspout, and roof ice melng applica-

    ons. It can also be used on exisng buildings where

    retrong high voltage wiring would be to dicult.

    The 24VAC/VDC supply means less expensive wiring, norequirement for conduit, and lower installaon costs.

    The unit is housed in a two gang PVC enclosure. The

    overall dimensions of the DS-824 are 4(120) x 7(178)

    x 2(70). The unit weighs 2 pounds. The user may

    access all electronics by removing the four front cover

    screws. The remote precipitaon sensor includes 10 feet

    (3 m) of interconnect cable. A weatherproof LED indica-

    tor on the base of the unit provides a method of check-

    ing power and trigger status when the unit is mounted

    in a hard to reach locaon. Steady OFF indicates no

    power to the unit. Steady ON indicates power is being

    supplied but no snow or rain trigger is acve. A blink-

    ing LED indicates the DS-824 is triggered and connected

    equipment has been acvated.

    The DS-824 can be powered from a 22-28VAC/VDC

    source. Peak power consumpon is 15 VA at startup,

    8.5 VA steady state triggered, 5 VA steady state untrig-

    gered. Power input is polarity protected for a DC supply.

    The unit provides a single 24VAC/30A or 24VDC/20A

    normally open load contact set. This contact set is paral-

    leled with a low power contact set to provide remote

    control and acvaon monitoring. Operaonal tempera-

    ture range is -40C to +85C.

    CONTROLS & MONITORING

    THE DS824 RAIN/SNOWSENSOR CONTROLLER

    Designed for Low Voltage Hydronic

    and Baery Powered Systems

    Automac Acvaon means Lower De-icing Costs

    Reliable Rain and Snow Detecon

    24VAC/VDC Operaon, Only 20 VA Required

    Full 30A @ 24VAC Control

    Replaceable Remote Precipitaon Sensor

    8 Dierent Funcons, 1 Part Number

    Adjustable Temperature Trigger Point

    Exclusive Adjustable Sensivity Control

    Selectable Low Temperature Cuto

    Smart Manual On Operates for One Delay O Cycle

    High Power, Low Price!

    (866) 635-8123

    www.thermaltechusa.com

  • 8/2/2019 Ds 824 Controller Datasheet

    2/3

    The table on the next page outlines the operang

    modes for the DS-824. Trigger Temperature (TT) is

    adjustable from 34F-44F using an on-board control.

    When ambient air temperature (AT) is below this trigger

    point precipitaon is assumed to be snow or freezing

    rain. When above the trigger point, precipitaon is as-

    sumed to be rain.

    Delay O refers to the internal drying cycle mer of

    the DS-824. The mer is used to allow the DS-824 to dry

    the heated surface through evaporaon once precipita-

    on has stopped. The drying cycle reduces the chance

    that moisture le behind by the melng process will

    refreeze into ice. This mer is restarted by each precipi-

    taon detecon. Therefore, the DS-824 will connue to

    operate as long as precipitaon and trigger temperature

    is detected, then for the Delay O me once rain or

    snow stops. It is assumed that, when operang as asensor, the DS-824 is supplying an acvaon signal to an

    external control system. All sensor modes provide a

    minimum 2 minute closure, reducing cycling of the ex-

    ternal controller. The Delay O cycle has been extended

    for hydronic applicaons and is determined by the Long

    Delay (LD) switch seng, DEL switch seng and the DEL

    adjustment. Delay O is 30-90 minutes in non-LD con-

    troller mode and 2-6 hours in LD controller mode.

    An environmentally sealed control switch is provided.

    The Manual On funcon acvates the controlled

    equipment for tesng and special operaonal condi-ons. The Automac posion allows the DS-824 to

    handle all detecons and control. The Standby/Reset

    posion disables triggering and can also be used to clear

    the delay o mer (see next page) from true or test

    acvaon. If the switch is placed in Manual On for less

    than 2 seconds, then switched back to Automac the

    controller will execute one delay o cycle. This allows a

    controlled manual acvaon of the snow melt system

    without the fear of forgeng and leaving the system

    in Manual On for an extended and potenally very

    expensive period of me. Standby/Reset can sll be

    used to clear this delay o cycle. Remote control and

    monitor up to 1000 feet away is also available when the

    oponal CS-1 C/M cable listed is installed. The DS-824

    is also compable with the DP-7B, DP-7EX, and CDP-2

    remote control/status panels.

    The Low Temperature Cuto (LTC) opon is typically

    used on de-icing or snow melng systems with limited

    output capacity. If selected, the sensor will not trigger if

    precipitaon is detected below 15F. However, if the de-

    icing system has been acvated, precipitaon connues,

    and the ambient temperature drops below 15F, LTC will

    be ignored. This assures that water le behind on thesurface during the heang cycle will not immediately

    refreeze into ice as a result of deacvang the de-icing

    system.

    The DS-824 also features a new innovaon, a Trigger

    Sensivity Adjustment. Previous units have always

    detected and triggered on the rst drop of rain, the rst

    ake of snow. While this has always provided a highly

    reliable detecon it may create nuisance triggers in

    some installaons. Snow blowing o a roof or falling

    from a tree could cause the system to acvate for adelay cycle when its not needed, increasing operat-

    ing costs. The sensivity adjustment allows seng

    the number of seconds the precipitaon grid must

    see connuous rain or snow before the sensor is trig-

    gered and ranges from 3 seconds to 4 minutes. A higher

    sensivity seng assures quick detecon no maer the

    condions. A lower sensivity seng will allow a few

    stray drips of rain or akes of snow to be ignored but a

    heavier downfall will trigger the system.

    CONTROLS & MONITORING

    (866) 635-8123

    www.thermaltechusa.com

  • 8/2/2019 Ds 824 Controller Datasheet

    3/3

    CONTROLS & MONITORING

    DS824 SPECIFICATIONSDimensions 4"(120) x 7"(178) x 2"(70)

    Weight 2 Lbs. (0.9 Kg)

    Operang Temperature -40F to +185F (-40C to +85C)

    Enclosure Rang NEMA 3R

    Supply Power 22-28VAC/VDC 15VA maximum, 5VA typical

    Trigger Temperature 34F-44F (1.1C-6.6C) Field Selectable

    Delay O (Sensor) 2 Minutes

    Delay O (Controller) 30-90 Minutes/2-6 Hours Field Selectable

    Load Contact Capacity 30A @ 24 VAC/100,000 operaons minimum at full load

    Monitor Contact Capacity 24 VDC/VAC 400mA 10W total

    FUNCTION

    AMBIENT

    TEMP AT

    DELAY OFF

    LD OFF

    DELAY

    OFF

    LD ON SUGGESTED APPLICATION

    Snow sensor w\o LTC AT < TT 2 Min 2 Min Snow and ice alert, Sensor for external deice/snow melt con-

    troller (unlimited heat)

    Snow sensor w\LTC TT>AT>15F 2 Min 2 Min Sensor for external deice/snow melt controller (limited heat)

    Snow controller w\o

    LTC

    AT < TT 30-90 Min 2-6 Hrs Stand-alone controller for electric/hydronic snow melng

    Snow controller w\LTC TT>AT>15F 30-90 Min 2-6 Hrs Stand-alone controller for electric/hydronic snow melng

    Precipitaon sensor Not Used 2 Min 2 Min Snow, ice, and rain alert, Ku band rain and snow diversion

    Precipitaon controller Not Used 30-90 Min 2-6 Hrs Snow, ice, and rain alert, Ku band rain and snow diversion

    Rain sensor AT>TT 2 Min 2 Min Rain alert, Ku band rain diversion

    Rain controller AT>TT 30-90 Min 2-6 Hrs Ku band rain diversion, intake and exhaust fan control