    Rev Approved CPECC Owner Description Date Prepared Checked

    Issued for Approval 6/26/2007 ARS SN ShS LiuXG

    Issued for Construction 8/17/2007 ARS SN ShS LiuXG

    Document No: DS-55-E-PM5504

    KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS) PROJECT

    DATA SHEET FOR MOTOR PM-5504 A/BDocument Title:

    DATA SHEET FOR MOTOR PM-5504 A/B

    Class: IIRev: 0 Sheet 1 of 2

    CONTRACTOROWNER

    Date:17/08/2007

  • 7/27/2019 DS-55-E-PM5504 Rev-0 (Jockey Fire Water Pumps)

    2/2

    1 MOTOR APPLICATION

    2 Project Kandhkot Field Gas Compression Station Project Project Number PAK0053 Client CPECC Tag Number PM-5504 A/B

    4 Location Kandhkot, Sindh Number Required 2

    5 Service Jockey Fire Water Pump

    6 MOTOR DETAILS

    7 Company Requirements

    8 Rated output 3 * kW Manufacturer 9 Supply 415 Volts 3 Ph 50 Hz Frame number

    10 System neutral earthing: Solid x Resistive Full load speed

    11 Synchronous speed rpm Full load torque N

    12 Enclosure rating (IEC60529) Motor:IP 55 Locked rotor torque N

    13 Terminal Box/Cable Entry Size:IP 56 Pull-out torque N

    14 Duty rating S1 Current N/L 1/2 3/4 F/L Am

    15 Insulation class F Efficiency N/L 1/2 3/4 F/L16 Temperature rise limit Class B Power factor N/L 1/2 3/4 F/L

    17 Starting torque designation Locked rotor current (7.6 x IFLC) Am

    18 Winding protection Yes No x Cooling method IC

    19 Anticondensation Heater Yes No x Motor cool down time m

    20 Max. stalled time hot cold s

    21 Starting power factor

    22 Const. type & mounting arrgt IM

    23 ENVIRONMENTAL DETAILS

    24 Design ambient temperature (Min/Max) 6/53 C Motor explosion protection

    25 Area classification: Hazardous Non-hazardous x Certifying body

    26 Hazardous protection type Certificate No.

    27 Gas Group: Temperature Class:28 MECHANICAL DETAILS

    29 Bearing type: DE: NDE:

    30 Drive system: Direct x V-belt Geared Bearing manufacturer

    31 Load moment of inertia kg.m Lubrication system

    32 Slide rails required Yes No x Shaft end float

    33 Required to have reversing duty:Yes No x Rotor moment of inertia kg

    34 Maximum noise level at one metre dB

    35 Motor weight

    36 Shipping dimensions L x W x H

    37 Run direction from DE CW CCW

    38 CABLE DETAILS

    39 Main power cable TBA40 Cable entry direction Vertical Terminal box location (viewed from drive end)

    41 Anti-condensation heater # NA Size of screwed entry X M

    42 Thermistor/RTD cable NA

    43

    44 NOTES

    45 Vendor to provide detail.

    46 * Vendor Shall Confirm Motor Rating.

    47 TBA To Be Advised

    48 1 Vendor to provide details on the right hand side of Data Sheet.

    49 2 Vendor shall provide a routine test certificate for each motor.