  • 8/2/2019 Ds 2b Controller Datasheet

    1/3

    The DS-2B is the base model of the DS series. It is pri-

    marily designed for small satellite antenna/broadcast

    tower de-icing, pavement snow melng applicaons,

    and used as a sensor for larger control systems. The unit

    may also be used as a stand-alone rain diversion con-

    troller for Ku band satellite applicaons.

    The unit is housed in a two gang PVC enclosure. The

    overall dimensions of the DS-2B are 4(120) x 7(178)

    x 2(70). The unit weighs 2 pounds. The user may

    access all electronics by removing the four front cover

    screws.

    The DS-2B can be powered from either a 100-120 VAC

    or 200-240 VAC 50/60Hz source. Peak power consump-

    on is 15 was. Voltage selecon is performed by in-

    stalling provided jumpers onto the printed circuit board.

    The unit provides a single 240VAC @ 30A normally openload contact set. This contact set is paralleled with a low

    power contact set to provide remote acvaon moni-

    toring. Operaonal temperature range is -40C to +85C.

    An environmentally sealed control switch is provided.

    The Manual On funcon acvates the controlled

    equipment for tesng and special operaonal condi-

    ons. The Automac posion allows the DS-2B to

    handle all detecons and control. The Standby/Reset

    posion disables triggering and can also be used to clear

    the delay o mer from true or test acvaon. Remote

    control and monitor up to 1000 feet away is also avail-

    able when the oponal C/M cable listed is installed. The

    DS-2B is also compable with the DP-7B, DP-7EX, and

    CDP-2 remote control/status panels.

    A new feature has been added to the DS-2B. If the

    switch is placed in Manual On for less than 2 seconds,

    then switched back to Automac the controller will

    execute one delay o cycle. The delay o cycle is de-

    termined by the DEL switch seng and the DEL adjust-

    ment, i.e., 2 minutes in sensor mode, 30-90 minutesin controller mode. This can be used to clear surfaces

    with a frost or hail buildup without the danger of leav-

    ing the system in a connuous Manual On condion.

    Standby/Reset can sll be used to clear this delay o

    cycle.

    CONTROLS & MONITORING

    THE DS2B RAIN/SNOWSENSOR CONTROLLER

    Automac Acvaon means Lower De-icing Costs

    Reliable Rain and Snow Detecon

    Full 30A @ 240VAC Control

    Field Strap for 100-120/200-240 VAC Operaon

    Replaceable Precipitaon Sensor

    Easy Installaon, Full Access to Electronics

    8 Dierent Funcons, 1 Part Number

    Adjustable Temperature Trigger Point

    Adjustable Delay O Cycle

    Selectable Low Temperature Cuto

    Smart Manual On Operates for One Delay O Cycle

    High Power, Low Price!

    (866) 635-8123

    www.thermaltechusa.com

  • 8/2/2019 Ds 2b Controller Datasheet

    2/3

    The table below outlines the operang modes for the

    DS-2B. Trigger Temperature (TT) is adjustable from

    34F-44F using an on-board control. When ambient air

    temperature (AT) is below this trigger point precipitaonis assumed to be snow or freezing rain. When above the

    trigger point, precipitaon is assumed to be rain.

    Delay O refers to the internal drying cycle mer of

    the DS-2B. The mer is used to allow the DS-2B to dry

    the heated surface through evaporaon once precipita-

    on has stopped. The drying cycle reduces the chance

    that moisture le behind by the melng process will

    refreeze into ice. This mer is restarted by each precipi-

    taon detecon. Therefore, the DS-2B will connue to

    operate as long as precipitaon and trigger temperature

    is detected, then for the Delay O me once rain or

    snow stops. It is assumed that, when operang as a

    sensor, the DS-2B is supplying an acvaon signal to an

    external control system. All sensor modes provide a

    minimum 2 minute closure to reducing cycling of the ex-

    ternal controller. When in a controller mode the Delay

    O me can be adjusted from 30-90 minutes. Properadjustment assures drying without excessive runme.

    The Low Temperature Cuto (LTC) opon is typically

    used on de-icing or snow melng systems with limited

    output capacity. If selected, the sensor will not trigger if

    precipitaon is detected below 15oF. However, if the de-

    icing system has been acvated, precipitaon connues,

    and the ambient temperature drops below 15oF, LTC will

    be ignored. This assures that water le behind on the

    surface during the heang cycle will not immediately

    refreeze into ice as a result of deacvang the de-icing

    system.

    CONTROLS & MONITORING

    FUNCTION

    AMBIENT

    TEMP AT DELAY OFF APPLICATION

    Snow sensor w\o LTC AT < TT 2 Min Snow and ice alert, Sensor for external deice/snow melt controller

    (unlimited heat)

    Snow sensor w\LTC TT>AT>15F 2 Min Sensor for external deice/snow melt controller (limited heat)

    Snow controller w\o LTC AT < TT 30-90 Min Stand-alone controller for satellite antenna/tower de-icing and

    electric/hydronic snow melng

    Snow controller w\LTC TT>AT>15F 30-90 Min Stand-alone controller for satellite antenna/tower de-icing and

    electric/hydronic snow melng

    Precipitaon sensor Not Used 2 Min Snow, ice, and rain alert, Ku band rain and snow diversion

    Precipitaon controller Not Used 30-90 Min Snow, ice, and rain alert, Ku band rain and snow diversion

    Rain sensor AT>TT 2 Min Rain alert, Ku band rain diversion

    Rain controller AT>TT 30-90 Min Ku band rain diversion

    (866) 635-8123

    www.thermaltechusa.com

  • 8/2/2019 Ds 2b Controller Datasheet

    3/3

    DS2B SPECIFICATIONSDimensions 4(120) x 7(178) x 2(70)Weight 2 Lbs. (0.9 Kg)

    Operang Temperature -40F to +185F (-40C to +85C)

    Enclosure Rang NEMA 3R

    Supply Power 100-120VAC/200-240VAC Field Selectable

    15W maximum

    Trigger Temperature 34F-44F (1.1C-6.6C) Field Selectable

    Delay O (Sensor) 2 Minutes

    Delay O (Controller) 30-90 Minutes Field Selectable

    Load Contact Capacity 30A @ 240 VAC/100,000 operaons mini-

    mum at full load

    Monitor Contact Capacity 24 VDC/VAC 400mA 10W total