Upload
michael-yoanito-oliviano
View
224
Download
0
Embed Size (px)
Citation preview
8/17/2019 Dry Van Manual
1/234
TRITON
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES
FOR STEEL DRY CARGO and OPEN TOP
CONTAINERS
Revision / May-06
Revision / Feb-07
DVMAN1 FEB07 CVR.doc
8/17/2019 Dry Van Manual
2/234
1
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES FOR
STEEL DRY CARGO and OPEN TOP CONTAINERS
FEB – 07 REVISIONS
EXTERIOR PANELS
Text, page 2 RevisedEP 1-17.xls Revised
EP 1-20.xls RevisedEP 1-22a.xls Added
EP 1-31a.xls AddedEP 1-34.xls RevisedEP 1-35.xls RevisedEP 1-36.xls RevisedEP 1-43a.xls AddedEP 1-50a.xls Added
EP 1-56.xls Revised
8/17/2019 Dry Van Manual
3/234
2
FEB – 07 REVISIONS
FRAME
FR 2-08a.xls AddedFR 2-09.xls DroppedFR 2-11.xls RevisedFR 2-14.xls Revised
FR 2-14a.xls Added
DOORS AND GASKETS
DG-03.xls Revised
DG-03a.xls AddedDG-03b.xls AddedDG-04.xls Revised
DG-10.xls RevisedDG-11.xls RevisedDG-12.xls Revised
DG-13.xls Revised
DG-14.xls RevisedDG-24.xls Revised
8/17/2019 Dry Van Manual
4/234
3
FEB – 07 REVISIONS
UNDERSTRUCTURE
US-03a.xls AddedUS-04a.xls AddedUS-04b.xls AddedUS-04c.xls Added
US-05.xls RevisedUS-06.xls RevisedUS-07.xls RevisedUS-08.xls RevisedUS-08a.xls Added
US-09.xls RevisedUS-09a.xls Added
US-11.xls RevisedUS-11a.xls AddedUS-11b.xls Added
INTERIOR WALLS
Text, page 2 RevisedIW 5-13.xls RevisedIW 5-17a.xls AddedIW 5-17b.xls Added
IW 5-17c.xls Added
8/17/2019 Dry Van Manual
5/234
4
FEB – 07 REVISIONS
FLOOR
FL 6-06.xls RevisedFL 6-07.xls RevisedFL 6-13.xls DroppedFL 6-16a.xls Added
FL 6-16b.xls AddedFL 6-17.xls RevisedFL 6-18.xls RevisedFL 6-18a.xls AddedFL 6-18b.xls Added
FL 6-21.xls RevisedFL 6-22.xls Revised
FL 6-24a.xls AddedFL 6-25.xls Revised
8/17/2019 Dry Van Manual
6/234
5
FEB – 07 REVISIONS
OPEN TOPS
OT 7-01.xls RevisedOT 7-02.xls RevisedOT 7-03.xls Revised
OT 7-04.xls RevisedOT 7-05.xls RevisedOT 7-06a.xls AddedOT 7-07a.xls AddedOT 7-07b.xls Added
OT 7-15.xls Revised
DV MAN1 REV LIST.doc
8/17/2019 Dry Van Manual
7/234
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES FOR
STEEL DRY CARGO and OPEN TOP CONTAINERS
TABLE OF CONTENTS
1. INTRODUCTION
2. LOCAL PORT STANDARDS
3. REPAIR COST ALLOCATION
4. PREEXISTING CONDITIONS
5. IMPROPER or NON-CONFORMING REPAIRS
6. CATEGORIES OF IMPROPER REPAIRS
7. TRITON DEPOT REPAIRS
8. EXTERIOR PANELS
9. FRAME
10. DOORS AND GASKETS
11. UNDERSTRUCTURE
8/17/2019 Dry Van Manual
8/234
12. INTERIOR WALLS
13. FLOOR
14. OPEN TOPS
DVMAN2 TOC.doc
8/17/2019 Dry Van Manual
9/234
1
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES FOR
STEEL DRY CARGO and OPEN TOP CONTAINERS
1. INTRODUCTION
The Institute of International Container Lessors (IICL) hasissued criteria for the inspection and repair of containers.Triton requires that all Triton depots and surveyors follow theIICL guidelines. However, in some areas the IICL has notfully defined the criteria, and it has been left to the containerowners to establish their own standards. These areas arecommonly referred to as gray areas, and manuals such asthis one are called gray area manuals.
In addition, there are areas where field practice or specialcircumstances have resulted in standard interpretationsand/or accepted modifications to the IICL standards.
The photos and text within this manual describe Triton’spolicies and procedures for these undefined and discretionaryareas. This manual will also describe actual fieldinterpretations of the IICL manuals. As a practical matter,improper repairs (repairs not conforming to IICLrecommended repair methods or workmanship standards)make up the vast majority of gray areas, so this manualfocuses on Triton’s improper repair policies.
The intention of this manual is to provide guidance andtraining for Triton maintenance and repair personnel,surveyors acting on behalf of Triton, and Triton depotoperators and estimators.
8/17/2019 Dry Van Manual
10/234
2
This manual does not supplant the IICL Guide for ContainerEquipment Inspection, the IICL Repair Manual for SteelFreight Containers, nor any other IICL manual. Instead, itcomplements the IICL manuals by clarifying and interpreting
IICL criteria such that they may be consistently andunambiguously applied in actual field practice.
Should the IICL standards be revised subsequent to thepublication of this manual such that the revised IICLstandards contradict those in this manual, the revised IICLstandards shall apply.
Triton has attempted to be fair, reasonable, and practical in
addressing the areas discussed within this manual. Inparticular, effort has been made to avoid requiring repairsthat are not necessary for the operation of the container.Conversely, though, some repairs have been required tomeet the general condition and cosmetic expectations ofshippers and carriers.
This manual does not create any new standards, but merelydocuments existing industry practices. Certain local
differences may exist that require inspection or repairtechniques that are not covered in this manual or in the IICLpublications. In these situations, the decision of the TritonMaintenance and Repair representative will override all other
criteria.
8/17/2019 Dry Van Manual
11/234
3
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES FOR
STEEL DRY CARGO and OPEN TOP CONTAINERS
2. LOCAL PORT STANDARDS
Both Triton and the IICL endeavor to write standards thatminimize the lessees’ off-hire repair costs while, at the same
time, result in a container repaired to a standard that meetsboth carriers’ and shippers’ quality requirements at on-hire.As a result, standards are written to a level that is, on aworldwide average, acceptable for general cargo.
There are ports, though, where shippers have local on-hirestandards that exceed IICL and Triton standards. These localstandards usually apply to cosmetic or interior cleanliness andcondition requirements. To avoid having to increase
worldwide standards to meet the needs of a few aboveaverage standard ports and, thereby, increase worldwide off-hire repair costs; it is understood that the off-hire damageinspection and repair standards in these ports will be revisedupward to meet the on-hire standards.
In all cases, the fundamental IICL principle applies that,unless there is a prior agreement to the contrary between theowner and user of the container, the criteria are to be
applied equally at off-hire and on-hire. As stated in theGuide for Container Equipment Inspection / Fifth Edition /IICL-5 , “The recommendations and definitions of terms mustbe applied consistently, both at on-hire and off-hireinterchanges.” DVMAN3 INT LPS.doc
8/17/2019 Dry Van Manual
12/234
1
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES FOR
STEEL DRY CARGO and OPEN TOP CONTAINERS
3. REPAIR COST ALLOCATION
Damage repair costs are allocated between Triton and thelessee based on the IICL general definitions of Wear & Tearand Damage.
As a general guide, Wear & Tear is any repairworthycondition that is a result of the normal deterioration of thecontainer when used in the manner for which it wasdesigned and that could not have been reasonably avoidedby the user. Wear & Tear costs are allocated to Triton’saccount.
Customer damage is any repairworthy condition resultingfrom using the container in a manner for which it was notdesigned and that could have reasonably been avoided bythe lessee. Damage costs are allocated to either thelessee’s account or to the DPP account.
8/17/2019 Dry Van Manual
13/234
2
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES FOR
STEEL DRY CARGO and OPEN TOP CONTAINERS
4. PREEXISTING CONDITIONS
At off-hire, the lessee bears the responsibility for allrepairworthy damage and improper repairs with thefollowing exceptions:
If the lessee is able to produce an on-hire survey reportindicating that the condition was on the container at thetime of lease (i.e. a preexisting condition), the repair costwill be allocated to Triton’s account.
In cases of shorter leases (e.g. less than one year), if thecondition visually appears to be older than the length of thelease, the repair cost will be allocated to Triton’s account
even in the absence of an on-hire survey report.
DVMAN4 ALL PREX.DOC
8/17/2019 Dry Van Manual
14/234
1
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES FORSTEEL DRY CARGO and OPEN TOP CONTAINERS
5. IMPROPER or NON-CONFORMINGREPAIRS
Repairs that do not conform to the technical or workmanshipstandards of the IICL Repair Manual for Steel FreightContainers are commonly called improper repairs (IRs).
With rare exceptions, leasing company depot repair methodsconform to IICL standards. Non–leasing company repairfacilities, such as shipping line in-service depots, often make
repairs that do not conform.
At off-hire, a decision must be made as to if these improperrepairs can be left in place or must be reworked to IICLstandards. The IICL leaves this decision to the equipmentowner. Generally, Triton’s standards for reworking IRs canbe grouped into five categories as are described in the nextsection.
8/17/2019 Dry Van Manual
15/234
2
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES FORSTEEL DRY CARGO and OPEN TOP CONTAINERS
6. CATEGORIES OF IMPROPER REPAIRS
1. IRs that do not meet measurable IICL inspection standards.
Example: panel straightening that does not return thepanel to within the IICL 35mm dent inspectionstandard.
Triton always requires correction of this category ofIRs.
2. IRs that do not meet measurable IICL repair standards.
Example: rail inserts less than 150 mm in length.
With very few exceptions, Triton requires correction ofthis category of IRs.
3. IRs that do not meet IICL workmanshipstandards and compromise thecargoworthiness of the container.
Example: Unsound welding of a structural component.
8/17/2019 Dry Van Manual
16/234
3
Triton always requires correction of this category ofIRs.
4. IRs that do not meet IICL workmanship
standards but do not compromise thecargoworthiness of the container.
Example: Rough panel straightening that does notreturn the original corrugation profile.
Triton seldom requires rework of this category of IRs.
5. IRs that do not meet IICL workmanship
standards and do not compromise thecargoworthiness of the container, but that areunacceptable for lease out in the off-hire port.
Example: Unpainted interior panel straightening orpatching.
Triton requires rework to the extent necessary to meetport on-hire standards.
8/17/2019 Dry Van Manual
17/234
4
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES FORSTEEL DRY CARGO and OPEN TOP CONTAINERS
7. TRITON DEPOT REPAIRS
Although Triton does not require the correction of certain
improper repairs made by the lessee while the container wason lease, Triton’s depots are required to meet all IICL repairstandards, including workmanship standards, when makingoff-hire repairs.
DVMAN5 IR DPT.doc
8/17/2019 Dry Van Manual
18/234
1
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES forSTEEL DRY CARGO and OPEN TOP CONTAINERS
8. EXTERIOR PANELS
Background
Improper in-service straightening is the most common panelimproper repair problem. The IICL workmanship standardfor panel straightening requires that the panel be returned,as near as is possible, to the original profile. Theacceptability of the straightening workmanship is based onthe extent to which the corrugation bend radii and flatsbetween the bend radii have been returned to their originalpositions and profiles. In addition, both sides of the repair
must be properly surface prepared and painted.
In-service panel repairs quite often do not meet the IICLworkmanship standards: the panels are hammered backwithin the inspection criteria without efforts being made torestore the corrugation profiles, and the surface preparationand painting is substandard or omitted entirely.
Triton Standards
The IICL leaves the decision to correct improper repairs tothe equipment owner. Triton’s standards can besummarized as follows:
8/17/2019 Dry Van Manual
19/234
2
• All repairs must be within IICL dimensional inspectioncriteria.
• Improper in-service panel straightening or substandard
painting does not require correction.
• Patches or welds that were not painted at the time ofrepair require surface preparation and painting.
•
Except for severe paint color mismatches, cosmeticpainting is not required.
• Cosmetic touch-up of corrosion and preventative
maintenance painting is not required.
• Corrosion is repaired only if it fails a hammer test.
• All ISO markings and the Triton side logo must belegible.
The photos on the following pages demonstrate thestandards addressed above and explain other Triton
standards relative to exterior panel repairs.
Ports with On-hire Standards Exceeding
IICL and Triton Standards
In certain ports, carriers and shippers have local standardsfor exterior panel condition that exceed IICL and Tritonstandards, and containers not meeting these standards willbe rejected for on-hire. In these cases, it is understood thatthe local port standard overrides the IICL and Tritonstandards, and the local off-hire damage inspection andrepair standards will be raised to match the local on-hirestandards.
8/17/2019 Dry Van Manual
20/234
3
In all cases, the fundamental IICL principle applies that,unless there is a prior agreement to the contrary between
the owner and user of the container, the criteria are to beapplied equally at off-hire and on-hire. As stated in theGuide for Container Equipment Inspection / Fifth Edition /
IICL-5 , “The recommendations and definitions of terms mustbe applied consistently, both at on-hire and off-hireinterchanges.”
DVMAN FEB07 SEC1 EP.doc
8/17/2019 Dry Van Manual
21/234
EP 1-1.xls
Condition: Improper straightening.
Action: No action.
8/17/2019 Dry Van Manual
22/234
EP 1 - 2.xls
Condition: Improper straightening.
Action: No action.
Note: The paint color used on this repair is acceptable as it is
a near brown shade.
8/17/2019 Dry Van Manual
23/234
EP 1-3.xls
Condition: Improper straightening.
Action: No action.
8/17/2019 Dry Van Manual
24/234
EP 1-4.xls
Condition: Improper straightening.
Action: No action.
8/17/2019 Dry Van Manual
25/234
EP 1-5.xls
Condition: Improper straightening.
Action: No action.
8/17/2019 Dry Van Manual
26/234
EP 1-6.xls
Condition: Improper straightening.
Action: No action.
8/17/2019 Dry Van Manual
27/234
EP 1-7.xls
Condition: Improper straightening.
Action: No action.
8/17/2019 Dry Van Manual
28/234
EP 1-8.xls
Condition: Improper straightening.
Action: No action.
8/17/2019 Dry Van Manual
29/234
EP 1-9.xls
Condition: Improper straightening.
Action: No action.
8/17/2019 Dry Van Manual
30/234
EP 1-10.xls
Condition: Poor straightening.
Action: No action.
8/17/2019 Dry Van Manual
31/234
EP 1-11.xls
Condition: Improper panel straightening.
Action: No action.
Condition: Unpainted straightening
Action: No action.
8/17/2019 Dry Van Manual
32/234
EP 1-12.xls
Condition: Improper straightening.
Action: No action.
8/17/2019 Dry Van Manual
33/234
EP 1-13.xls
Condition: Poor straightening.
Action: No action.
8/17/2019 Dry Van Manual
34/234
EP 1-14.xls
Condition: Improper straightening.
Action: No action.
Note: Correction is required if the poor straightening affects
the door handle operation or prevents the handle from being
secured and latched in the retainer.
8/17/2019 Dry Van Manual
35/234
EP 1-15.xls
Condition: Unpainted weld.
Action: Clean and paint.
8/17/2019 Dry Van Manual
36/234
EP 1-16.xls
Condition: Welding without straightening.
Action: No action.
Condition: Unpainted weld.
Action: Clean and paint.
8/17/2019 Dry Van Manual
37/234
EP 1-17.xls
C-33
Condition: Welded panel in excess of 200mm in length.
Action: No action.
8/17/2019 Dry Van Manual
38/234
EP 1-18.xls
Condition: Poor welding workmanship.
Action: No action.
Condition: Improper paint color on repair.
Action: No action. This is considered to be a shade of brown.
8/17/2019 Dry Van Manual
39/234
EP 1-19.xls
Condition: Poor welding workmanship.
Action: No action.
8/17/2019 Dry Van Manual
40/234
EP 1-20.xls
Condition: Poor welding workmanship.
Action: No action.
Condition: Improper straightening.
Action: No action.
Note: Repair if necessary to meet local port on-hire
standards.
8/17/2019 Dry Van Manual
41/234
EP 1-21.xl
Condition: Poor welding workmanship.
Action: No action.
8/17/2019 Dry Van Manual
42/234
EP 1-22.xls
Condition: Poor welding workmanship.
Action: No action.
Condition: Unpainted weld.
Action: Clean and paint.
8/17/2019 Dry Van Manual
43/234
EP 1-22a.xls
C-03
Condition: Exterior sharp edges on weld repair.
Action: No action.
Condition: Repair painted with non-Triton color.
Action: Any shade of brown, near brown, or earth tone color
is acceptable for in-service repairs. The color shown in this
photo is clearly red, and, therefore, is repair worthy.
8/17/2019 Dry Van Manual
44/234
EP 1-23.xls
Condition: Poor welding workmanship.
Action: No action.
8/17/2019 Dry Van Manual
45/234
EP 1-24.xls
Condition: Poor welding workmanship.
Action: No action.
Condition: Unpainted weld.
Action: Clean and paint.
8/17/2019 Dry Van Manual
46/234
EP 1-25.xls
Condition: Poor welding workmanship.
Action: No action.
Note: Correction is required if the poor straightening affects
the door handle operation or prevents the handle from being
secured and latched in the retainer.
8/17/2019 Dry Van Manual
47/234
EP 1-26.xls
Condition: Patch weld with spatter and weld wire.
Action: No action.
8/17/2019 Dry Van Manual
48/234
EP 1-27.xls
Condition: Welding with porosity.
Action: No action.
Note: Action is required if the patch is not light tight.
8/17/2019 Dry Van Manual
49/234
EP 1-28.xls
Condition: Small patches fitted into the inboard or outboard
panel corrugations.
Action: No action.
Note: There are no IICL minimum patch size limits
provided the 13mm (1/2 in) overlap requirement is met.
8/17/2019 Dry Van Manual
50/234
EP 1-29.xls
Condition: Cut, fold, and weld roof corrugation end repair.
Action: No action.
Note: Cut, fold, and weld roof corrugation repairs should
only be done in locations where proper pressed corrugation
material is not available.
8/17/2019 Dry Van Manual
51/234
EP 1-30.xls
Condition: Cut, fold, and weld roof corrugation repair
showing good quality workmanship prior to painting.
Action: Paint.
Note: Cut, fold, and weld roof corrugation repairs shouldonly be done in locations where proper pressed corrugation
material is not available.
8/17/2019 Dry Van Manual
52/234
EP 1-31.xls
Condition: Examples of proper roof panel corrugation endpieces.
8/17/2019 Dry Van Manual
53/234
EP 1-31a.xls
C-01
Condition: Mismatched side panel corrugations (steep angle
corrugated panel used to replace a shallow angle type side
panel).
Action: No action.
8/17/2019 Dry Van Manual
54/234
EP 1-32.xls
Condition: Small areas of panel corrosion.
Action: No action.
Note: Corroded areas should be hammer tested with a Triton
approved corrosion inspection hammer and technique. If the
tested area does not hole or dimple severely, no repair is
necessary.
8/17/2019 Dry Van Manual
55/234
EP 1-33.xls
Condition:Old patch repair with coating failure.
Action: No action.
Note: Corroded areas should be hammer tested with a Triton
approved corrosion inspection hammer and technique. If thetested area does not hole or dimple severely, no repair is
necessary.
8/17/2019 Dry Van Manual
56/234
EP 1-34.xls
Condition:Old patch repair with coating failure.
Action: No action.
Note: Corroded areas should be hammer tested with a Triton
approved corrosion inspection hammer and technique. If the
tested area does not hole or dimple severely, no repair is
necessary.
Note: Clean and paint if necessary to meet local port
on-hire standards.
8/17/2019 Dry Van Manual
57/234
EP 1-35.xls
Condition:Old patch repair with coating failure.
Action: No action.
Note: Corroded areas should be hammer tested with a Triton
approved corrosion inspection hammer and technique. If the
tested area does not hole or dimple severely, no repair is
necessary.
Note: Clean and paint if necessary to meet local port
on-hire standards.
8/17/2019 Dry Van Manual
58/234
EP 1-36.xls
Condition:Old patch with signs of coating failure.
Action: No action.
Note: Corroded areas should be hammer tested with a
Triton approved corrosion inspection hammer and technique.
If the tested area does not hole or dimple severely, no repair
is necessary.
Note: Clean and paint if necessary to meet local port
on-hire standards.
8/17/2019 Dry Van Manual
59/234
EP 1-37.xls
Condition: Corroded side panel.
Action: No action.
Note: Corroded areas should be hammer tested with a Triton
approved corrosion inspection hammer and technique. If thetested area does not hole or dimple severely, no repair is
necessary.
8/17/2019 Dry Van Manual
60/234
EP 1-38.xls
Condition: Paint on container exterior.
Action: No action.
Note: Foreign materials on the outside of the container are
repairworthy only if they attack the paint or make the ISO
markings illegible.
Note: When repair is required to make the ISO markings
legible, the removal of the foreign materials is limited to
what is required to make the markings legible.
8/17/2019 Dry Van Manual
61/234
EP 1-39.xls
Condition: Foreign material on exterior.
Action: No action.
Note: Foreign materials on the outside of the container are
repairworthy only if they attack the paint or make the ISO
markings illegible.
Note: When repair is required to make the ISO markings
legible, the removal of the foreign materials is limited to
what is required to make the markings legible.
8/17/2019 Dry Van Manual
62/234
EP 1-40.xls
Condition: Foreign material on the container exterior.
Action: No action.
Note: Foreign materials on the outside of the container are
repairworthy only if they attack the paint or make the ISO
markings illegible.
Note: When repair is required to make the ISO markings
legible, the removal of the foreign materials is limited to
what is required to make the markings legible.
8/17/2019 Dry Van Manual
63/234
EP 1-41.xls
Condition: Paint on container exterior making ISO markings
illegible.
Action: Remove paint and replace affected decals.
Cost Allocation: Customer's account.
Note: When repair is required to make the ISO markings
legible, the removal of the foreign materials is limited to
what is required to make the markings legible.
8/17/2019 Dry Van Manual
64/234
EP 1-42.xls
Condition: Paint on container exterior.
Action: Replace illegible decals.
Cost Allocation: Customer's account.
Note: Exterior foreign material spillage so severe that it
makes the container unleaseable must be repaired even if the
foreign material is not attacking the paint, and has notrendered the markings illegible.
8/17/2019 Dry Van Manual
65/234
EP 1-43.xls
Condition: Repair painted with non-Triton color.
Action: No action.
Note: Any shade of brown, near brown, or earth tone color is
acceptable for in-service repairs. Only colors sharply
contrasting with Triton brown (e.g. red, green, blue, yellow,
etc.) need to be repainted.
8/17/2019 Dry Van Manual
66/234
EP 1-43a.xls
C-02
Condition: Non-brown repair color.
Action: Repaint with Triton brown.
Note: Any shade of brown, near brown, or earth tone is
acceptable for in-service repairs. The color shown in this photois clearly orange, and is, therefore, repair worthy.
8/17/2019 Dry Van Manual
67/234
EP 1-44.xls
Condition: Repair painted with non-Triton color.
Action: Repaint.
Note: Any non-brown color that sharply contrasts with Triton's
brown must be repainted.
8/17/2019 Dry Van Manual
68/234
EP 1-44a.xls
Condition: Decals loose at edges.
Action: No action.
Note: No action is required unless decals are missing or
illegible. Do not remove or peel off decals that are loose at the
edges.
8/17/2019 Dry Van Manual
69/234
EP 1-45.xls
Condition: Damaged ISO decals.
Action: No action.
Note: No action is required unless decals are illegible.
Note: Repairworthy damage to decals on a standing
corrugation are to be estimated to Triton's account. Damages
on decals in the recessed corrugation should be estimated to
the customer's account.
8/17/2019 Dry Van Manual
70/234
EP 1-46.xls
Condition: Damaged Triton side logo.
Action: No action.
Note: In this example, the logo is still legible.
8/17/2019 Dry Van Manual
71/234
EP 1-47.xls
Condition: Missing letters on Triton
side logo.
Action: Repair required.
Cost Allocation: If there is no sign ofimpact, damage, or repair, allocate to
Triton's account.
8/17/2019 Dry Van Manual
72/234
EP 1-48.xls
Condition: Missing letters on Triton side logo.
Action: Repair required.
Cost Allocation: Customer's account.
Note: When a logo is made illegible by the
repair of an IICL dent or marks removal, thelogo must be replaced as part of the repair.
8/17/2019 Dry Van Manual
73/234
EP 1-49.xls
Condition: Partially missing Triton side logo.
Action: No action.
Note: In this example the logo is still legible.
8/17/2019 Dry Van Manual
74/234
EP 1-50.xls
Condition: Missing Triton door logo.
Action: No action.
8/17/2019 Dry Van Manual
75/234
EP 1-50a.xls
C-04
Condition: Hand sprayed decals.
Action: Replace decals.
Note: Decals that are properly painted using a stencil of the
correct size and that are clearly legible are acceptable.
Cost Allocation: Triton account.
Note: In the absence of damage, decal replacementcosts are for Triton's account.
8/17/2019 Dry Van Manual
76/234
EP 1-51.xls
Condition: Prefix and unit numbers replaced by painting
instead of decals.
Action: No action.
Note: Prefix, unit numbers, and Triton side logos can be
replaced by painting provided they are the proper size and
legible.
8/17/2019 Dry Van Manual
77/234
EP 1-52.xls
Condition: Missing zebra stripe on high cube unit.
Action: Replacement required.
Note: If more than 1/2 of the length of the zebra stripe is
missing, it should be replaced.
Cost Allocation: In the absence of damage allocate to
Triton's account.
8/17/2019 Dry Van Manual
78/234
EP 1-53.xls
Condition: Illegible ISO markings.
Action: Replacement required.
Cost Allocation: In the absence of damage, allocate to
Triton's account.
8/17/2019 Dry Van Manual
79/234
EP 1-54.xls
Condition: Missing or illegible Triton prefix or serial number.
Action: Repair required.
Cost Allocation: In the absence of damage, allocate to
Triton's account.
8/17/2019 Dry Van Manual
80/234
EP 1 - 55.xls
Condition: Gouged side panel.
Action: No action.
Note: There is no IICL criteria for loss of material thickness
and the IICL gouge criteria only applies to flooring.
8/17/2019 Dry Van Manual
81/234
EP 1-56.xls
Condition: Ventilator cracked at upper or lower rivet point.
Action: No action.
Note: Cracks in ventilators are acceptable provided they
are limited to the attachment flange area.
8/17/2019 Dry Van Manual
82/234
EP 1-57.xls
Condition: Cracked ventilator at perforated area over baffles.
Action: Replace.
Note: Vent must be replaced because it is cracked in the
baffle area.
Cost Allocation: Customer account.
8/17/2019 Dry Van Manual
83/234
1
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES for
STEEL DRY CARGO and OPEN TOP CONTAINERS
9. FRAME
Triton Standards
As the frame components are critical to the structuralintegrity of the container, Triton fully adheres to all IICLinspection repair standards and requires improper framerepairs to be reworked to those standards.
In some areas, the IICL repair standards are incomplete orunclearly specified. The photos on the following pages
specify Triton’s requirements in those areas.
DVMAN SEC2 FR.doc
8/17/2019 Dry Van Manual
84/234
FR 2-01.xls
Condition: Gouged top rail
Action: Gouged rails should be measured to determine
whether the gouge exceeds the IICL damage criteria for toprail dents.
Note: Except for flooring, there is no IICL damage criteria for
material thickness loss or gouging at the point of impact.
8/17/2019 Dry Van Manual
85/234
FR 2-02.xls
Condition: Gouged corner post
Action: Corner post gouges should be measured to determine
if they exceed either the IICL dent criteria or the
IICL ISO + 5 mm criterion. If either criterion is exceeded,
repair by insert.
Note: Except for flooring, there is no IICL damage criteria for
material thickness loss or gouging at the point of impact.
8/17/2019 Dry Van Manual
86/234
FR 2-03.xls
Condition: Corner post gouge.
Action: No action unless gouge depth exceeds the IICL
corner post dent criteria.
Note: Except for flooring, there is no IICL damage criteria for
material thickness loss or gouging at the point of impact.
8/17/2019 Dry Van Manual
87/234
Condition: Corner post insert that extends through more than
half of the cross sectional profile.
Action: No action.
FR 2-04.xls
Note: IICL repair standards allow corner post inserts to extend
through more than half of the cross sectional profile provided
that the insert does not include more than one radius and
comes no closer than 10mm to the adjacent radii.
8/17/2019 Dry Van Manual
88/234
FR 2-05.xls
Condition: Corroded top side rail.
Action: No action unless the rail fails the corrosion hammer
test.
Note: Corroded areas should be hammer tested with a Tritonapproved corrosion inspection hammer and technique. If the
tested area does not hole or dimple severely, no repair is
necessary. Corroded areas are not repaired for either
cosmetic or preventative maintenace reasons; repairs are
made only in areas that fail a corrosion hammer test.
8/17/2019 Dry Van Manual
89/234
FR 2-06.xls
Condition: Top side rail insert ending at corner casting less
than 300mm (12") in length.
Action: Replace insert to correct length.
Note: Inserts and sections in structural components must
fully meet the dimension requirements of the IICL repair
standards. Being close is not good enough.
8/17/2019 Dry Van Manual
90/234
FR 2-07.xls
Condition: Torn rain gutter with burr.
Action: Grind to remove burr.
Note: Gouged or cut rain gutters do not require repair unless
there are burrs or sharp edges. Burrs and sharp
edges are removed by grinding.
8/17/2019 Dry Van Manual
91/234
FR 2-08.xls
Condition: Gouged rain gutter.
Action: No action.
Note: Gouged or cut rain gutters do not require repair unless there
are burrs or sharp edges. Burrs and sharp
edges are removed by grinding.
8/17/2019 Dry Van Manual
92/234
FR 2-08a.xls
C-05
Condition: Cut header flange.
Action: Repair.
Note: Repair header flanges only when they are cut. In the
absence of a cut, do not repair header flanges because they
are bent even if the bend exceeds the IICL header dent
criteria.
8/17/2019 Dry Van Manual
93/234
FR 2-10.xls
Condition: Bent and torn bottom side rail top flange.
Action: Insert.
Note: A torn, cut, or cracked flange requires repair. If the
damage does not extend beyond the panel-to-rail weld, the
damage can be ground smooth. Otherwise, an insert is
required.
8/17/2019 Dry Van Manual
94/234
FR 2-11.xls
C-38
Condition: Bent and cracked bottom rail flange.
Action: Straighten and weld.
8/17/2019 Dry Van Manual
95/234
FR 2-12.xls
Condition: Bottom side rail flange torn and gouged.
Action: If at least 50% of the bottom flange width remains,
grind smooth. Otherwise, insert.
8/17/2019 Dry Van Manual
96/234
FR 2-13.xls
Condition: Fitting and welding with bad workmanship.
Action: Replace insert.
Note: Fitting and welding on structural components must be to a
workmanship standard that ensures structural strength. This is
critical in the highly stresses areas near the corner castings.
8/17/2019 Dry Van Manual
97/234
FR 2-14.xls
C-39
Condition: Rear sill insert with flange shorter than original
profile.
Action: Replace insert and install doubler if originally fitted.
Note: Insert and section materials for structural components
must match or exceed the thicknesses and dimensions of the
original components. This is critical in the highly stressed
areas near the corner castings.
Note: It is recommended good practice to weld both sides of
any repair adjacent to the corner castings.
8/17/2019 Dry Van Manual
98/234
FR 2-14a.xls
C-15
Condition: Improper repair due to the full cross-sectional cut
of the inner rear corner post.
Action: No action.
Note: The correction of improper repairs that would require
replacement or major rework in the areas of the corner
castings and corner posts should be discussed with the Triton
M&R Manager, as consideration must be given to the relative
structural strengths of the rework versus the non-conforming
repair.
8/17/2019 Dry Van Manual
99/234
FR 2-15.xls
Condition: Damaged corner casting aperature.
Action: Replace casting
Note: Damages to the corner casting that 1) alters the
aperature size or shape such that a twist lock cannot enter the
corner casting or 2) reduces the amount of material in the
bearing area of the twist lock or 3) cracks the corner casting or
4) affects the integrity of the casting welds must be repaired by
replacement of the corner casting.
8/17/2019 Dry Van Manual
100/234
FR 2-16.xls
Condition: Damaged corner casting.
Action: No action.
Note: Damage to the corner casting that 1) alters the
aperature size or shape such that a twist lock cannot enter
the corner casting or 2) reduces the amount of material in the
bearing area of the twist lock or 3) cracks the corner casting or
4) affects the integrity of the casting welds must be repaired by
replacement of the corner casting.
8/17/2019 Dry Van Manual
101/234
1
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES forSTEEL DRY CARGO and OPEN TOP CONTAINERS
10. DOORS AND GASKETS
Triton Standards
The IICL door and gasket standards are clear in theirrequirements that the door gaskets be light-tight with theupper horizontal gasket fully in place and seated on theheader, and the door gear must be fully functional.
There are, though, certain gasket seating surface conditions,gasket improper repairs, and door gear damage conditionsthat require clarification. The photos on the following pages
specify Triton’s standards in these areas.
Ports with On-hire Standards Exceeding
IICL and Triton Standards
In certain ports, carriers and shippers have local standardsfor door gasket condition that exceed IICL and Triton
standards, and containers not meeting these standards willbe rejected for on-hire. In these cases, it is understood thatthe local port standard overrides the IICL and Tritonstandards, and the local damage inspection and repair off-hire standards will be raised to match the local on-hirestandards.
8/17/2019 Dry Van Manual
102/234
2
In all cases, the fundamental IICL principle applies that,unless there is a prior agreement to the contrary betweenthe owner and user of the container, the criteria are to beapplied equally at off-hire and on-hire. As stated in the
Guide for Container Equipment Inspection / Fifth Edition /IICL-5 , “The recommendations and definitions of terms mustbe applied consistently, both at on-hire and off-hireinterchanges.”
DVMAN SEC3 DG.doc
8/17/2019 Dry Van Manual
103/234
DG - 01.xls
Condition: Rear header corrosion.
Action: Repair by removing corrosion and repainting.
Note: Corrosion on the rear header is repairworthy if the
following conditions exist:
* The corrosion is visible above the upper horizontal sealing
edge of the gasket lip.
* The corrosion is serious enough that the upper horizontal
sealing edge of the gasket is raised off of the header.
8/17/2019 Dry Van Manual
104/234
DG - 02.xls
Condition: Rear header corrosion.
Action: Repair by removing corrosion and repainting.
Note: Corrosion on the rear header is repairworthy if the
following conditions exist:
* The corrosion is visible above the upper horizontal sealing
edge of the gasket lip.
* The corrosion is serious enough that the upper horizontal
sealing edge of the gasket is raised off of the header.
8/17/2019 Dry Van Manual
105/234
DG-03.xls
C-40
Condition: Rear header corrosion.
Action: Repair.
Note: This condition is repair worthy because the corrosion
extends above the upper horizontal edge of the gasket such
that it will raise the gasket sealing edge off of the header.
8/17/2019 Dry Van Manual
106/234
DG-03a.xls
C-06
Condition: Corroded door header.
Action: No action.
Note: Do not repair corroded door headers unless the
corrosion prevents the door upper lap gasket from seating on
the header.
8/17/2019 Dry Van Manual
107/234
DG-03b.xls
C-07
Condition: Corroded door header.
Action: No action.
Note: Do not repair corroded door headers unless the
corrosion prevents the door upper lap gasket from seating onthe header.
8/17/2019 Dry Van Manual
108/234
DG - 04.xls
Condition: Rear sill corrosion.
Action: No action.
Note: Corrosion in this area is not likely to affect the water
tight integrity of the container.
8/17/2019 Dry Van Manual
109/234
DG - 05.xls
Condition: Corrosion on vertical door edge.
Action: No action
Note: No action is required as corrosion at the
vertical edge is unlikely to affect the water tightintegrity of the gasket.
8/17/2019 Dry Van Manual
110/234
DG - 06.xls
Condition: Tape on exterior gaskets.
Action: Remove tape.
Note: Tape on the exterior doors orventilators should be considered a customer
marking and requires removal.
8/17/2019 Dry Van Manual
111/234
DG - 07.xls
Condition: Gasket folded under at door edge.
Action: Perform light check.
Note: If the gasket does not leak light, no action is
required.
8/17/2019 Dry Van Manual
112/234
DG - 08.xls
Condition: Damaged top gasket.
Action: Perform light check.
Note: No action is required provided that the gasket is light
tight. In some regions, this type of gasket damage is
repairworthy even if it is light tight because the damage has
exposed an area where water may possibly leak into the
container.
8/17/2019 Dry Van Manual
113/234
DG - 09.xls
Condition: Damaged top gasket.
Action: Perform light check.
Note: No action is required provided that the gasket is light
tight. In some regions, this type of gasket damage is
repairworthy even if it is light tight because the damage has
exposed an area where water may possibly leak into the
container.
8/17/2019 Dry Van Manual
114/234
DG-10.xls
C-41
Condition: Damaged top gasket.
Action: Perform light check.
Note: No action is required provided that the gasket is light
tight. In some regions, this type of gasket damage is repair
worthy even if it is light tight, because the damage has
exposed an area where water may possibly leak into the
container.
Condition: Corroded header.
Action: Repair.
Note: This corrosion raises the upper horizontal sealing edge
of the gasket off of the header.
Cost Allocation: Triton account.
8/17/2019 Dry Van Manual
115/234
DG-11.xls
C-43
Condition: Damaged top gasket.
Action: Repair.
Note: Even if this gasket is light tight, the IICL states that all
horizontal outer lips of top gaskets must be seated with no
missing pieces.
Reference the IICL Supplement on Container Inspection and
Repair: Gray Areas / Second Edition: "Horizontal top
gaskets: These gaskets are considered to be watertight if
they do not leak light AND the outer lips of the gaskets are
fully in place and seated against the header. Cuts, splits and
cracks are acceptable on the outer lips, but pieces may not be
missing."
8/17/2019 Dry Van Manual
116/234
DG - 12.xls
Condition: Improper door gasket repair.
Action: No action.
Note: This gasket repair is considered improper because the
wrong material was used for the gasket patch and because of
the overlapping sections on the ends.
No action is required if the repair is light tight.
8/17/2019 Dry Van Manual
117/234
DG-13.xls
C-42
Condition: Overlapping patch on top gasket.
Action: No action.
8/17/2019 Dry Van Manual
118/234
DG-14.xls
C-44
Condition: Improper overlapping patch on top gasket.
Action: No action.
8/17/2019 Dry Van Manual
119/234
DG - 15.xls
Condition: Damaged lower gasket.
Action: Perform light check.
Note: No action is required provided that the gasket is light
tight.
8/17/2019 Dry Van Manual
120/234
DG - 16.xls
Condition: Damaged lower gasket.
Action: Perform light check.
Note: No action is required provided that the gasket is light
tight.
8/17/2019 Dry Van Manual
121/234
DG - 17.xls
Condition: Damaged lower door gasket.
Action: Perform light check.
Note: No action is required provided that the gasket is light
tight. In some regions, this type of gasket damage is
repairworthy even if it is light tight because the damage has
exposed an area where water may possibly leak into the
container.
8/17/2019 Dry Van Manual
122/234
DG-18.xls
Comments: Damaged gasket.
Action: Perform light check.
Note: No action is required provided that the gasket is light
tight. In some regions, this type of gasket damage is
repairworthy even if it is light tight, because the damage has
exposed an area where water may possibly leak into the
container.
8/17/2019 Dry Van Manual
123/234
DG - 19.xls
Condition: Improper door gasket repair.
Action: No action.
Note: This gasket repair is considered to be improper
because the insert used was the wrong profile. No action is
required if the gasket is light tight.
8/17/2019 Dry Van Manual
124/234
DG - 20.xls
Condition: Welded overlapping patch under door bracket.
Action: No action.
Note: In this case a repair is only required if the locking gear
operation is affected.
8/17/2019 Dry Van Manual
125/234
DG - 21.xls
Condition: Welded door bracket.
Action: No action.
Note: In this case a repair is only required if the locking gear
operation is affected.
8/17/2019 Dry Van Manual
126/234
DG - 22.xls
Condition: Welded door bracket.
Action: No action.
Note:In this case a repair is only required if the locking gearoperation is affected.
Condition: Unpainted repair.
Action: Clean and paint.
Cost Allocation: Customer's account.
8/17/2019 Dry Van Manual
127/234
DG - 23.xls
Condition: Bent door locking rod.
Action: No action.
Note: Damaged door locking gear requires no action, even if
the lock rod is contacting the door panel, provided that the
door operation is not affected.
8/17/2019 Dry Van Manual
128/234
DG - 24.xls
C-45
Condition: Bent door handle.
Action: Repair.
Note: Bent door handles only require repair if the door
handle cannot be secured in the handle retainer with the
retainer catch closed and the cam keeper fully engaged, or if
the handle is bent out of the ISO tolerances. In this case, the
cam keeper is not engaged and the retainer catch cannot be
closed, so repair is required.
Cost Allocation: Customer's account.
8/17/2019 Dry Van Manual
129/234
8/17/2019 Dry Van Manual
130/234
DG - 25.xls
Condition: Bent / distorted door handle keeper.
Action: Repair.
Note: Bent door handle retainers or retainer catches only
require repair if the door handle cannot be secured in the
handle retainer with the retainer catch closed. In this case, the
retainer catch cannot be closed so repair is required.
Cost Allocation: Customer's account.
8/17/2019 Dry Van Manual
131/234
DG - 26.xls
Condition: Bent / distorted locking bar bracket.
Action: No action.
Note: Repair or replacement of a damaged locking bar
bracket is only required if the damage affects the door gear
operation.
8/17/2019 Dry Van Manual
132/234
DG - 27.xls
Condition: Missing locking bar bracket bushing.
Action: No action.
Note: Repair or replacement of locking bar bushings is only
required if the missing or damaged piece affects the door gear
operation.
8/17/2019 Dry Van Manual
133/234
DG - 28.xls
Condition: Cracked hinge blade.
Action: Replace hinge.
Note: Cracked hinge blades should be replaced. Welding
cracked hinge blades is not allowed.
Cost Allocation: Customer's account.
8/17/2019 Dry Van Manual
134/234
DG - 29.xls
Condition: Welded hinge blade.
Action:Replace hinge.
Note: Cracked hinge blades should be replaced. Welding
cracked hinge blades is not allowed.
Cost Allocation: Customer's account.
8/17/2019 Dry Van Manual
135/234
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES for
STEEL DRY CARGO and OPEN TOP CONTAINERS
11. UNDERSTRUCTURE
Triton Standards
As the understructure components are critical to thestructural integrity of the container, Triton fully adheres toall IICL inspection and repair standards and requires thatimproper frame repairs be reworked to those standards.
In some areas, the IICL repair standards are incomplete orunclearly specified, additional repair methods have been
introduced to the industry, or alternative measurementmethods have been adopted. The photos on the followingpages specify Triton’s requirements in those areas.
DVMAN SEC4 US.doc
8/17/2019 Dry Van Manual
136/234
US - 01.xls
Condition: Underside corrosion.
Action: No action.
Note: Corroded areas should be hammer tested with a Triton
approved corrosion inspection hammer and technique. If the
tested area does not hole or dimple severely, no repair is
necessary.
8/17/2019 Dry Van Manual
137/234
US - 02.xls
Condition: Underside corrosion.
Action: No action.
Note: Corroded areas should be hammer tested with a
Triton approved corrosion inspection hammer and technique.
If the tested area does not hole or dimple severely, no repair
is necessary.
8/17/2019 Dry Van Manual
138/234
US - 03.xls
Condition: Contamination on understructure from spill in
container.
Action:Steam clean and reinspect affected area.
Note: After steam cleaning and reinspection, if it is
determined that the contamination has attacked the
undercoating, all affected areas must be steam cleaned,
blasted and recoated.
Cost Allocation: Customer's account.
8/17/2019 Dry Van Manual
139/234
US-03a.xls
C-30b
Condition: Bent flat bar center rail.
Action: No action unless light leaks.
Note: If light leaks, caulk.
8/17/2019 Dry Van Manual
140/234
US - 04.xls
Condition: Crossmember insert without leaving 13mm of
original web intact.
Action: No action.
Note: The IICL suggests that it is good practice to leave
13mm intact, if possible. This is not a requirement.
8/17/2019 Dry Van Manual
141/234
US-04a.xls
C-27
Condition: Sequential crossmember inserts.
Action: No action.
Note: In general, there are no limitations on sequential
inserts, but in the specific case of sequential inserts used atthe center of crossmembers to repair downward crossmember
bowing (not shown here), they are not allowed. Experience
has shown that inserts used in this manner fail by fracture of
the vertical web welds.
8/17/2019 Dry Van Manual
142/234
US-04b.xls
C-29
Condition: Sequential inserts at crossmember centers.
Welds still sound.
Action: No action.
Note: Sequential inserts used at the center of crossmembers
to repair downward crossmember bowing are not allowed, as
experience has shown that inserts used in this manner fail by
fracture of the vertical web welds. For pre-existing inserts of
this type, repair is not required unless there are signs of weld
fracture.
8/17/2019 Dry Van Manual
143/234
US-04c.xls
C-28
Condition: Failed crossmember inserts.
Action: If crossmembers show signs of residual bowing,
replace crossmembers. Otherwise, reweld, or extend inserts
depending on quality of fit attainable.
Note: In general, there are no limitations on sequential
inserts, but in the specific case of sequential inserts used at
the center of crossmembers to repair downward crossmember
bowing, they are not allowed. Experience has shown that
inserts used in this manner fail by vertical fracture of the
transverse web welds.
8/17/2019 Dry Van Manual
144/234
US-05.xls
C-53
Condition: Angle stitch welded to crossmember web to
facilitate floorboard re-securing after board section.
Action: No action.
Note: Triton accepts this in-service repair provided it meets
the following criteria:
1. Reinforcement angle must be one piece and of same
thickness or thicker than the original crossmember.
2. Reinforcement angle must be stitch welded to the
crossmember web. Stitch welding must be minimum 25mm
length welds with a pitch of no greater than 100mm.
3. Repairs must be coated with primer and undercoating.
Note: This repair is not an acceptable Triton depot off-hire
repair.
8/17/2019 Dry Van Manual
145/234
US - 06.xls
Condition: Angle applied to front of crossmember to facilitate
floorboard resecuring after floor board section.
Action: Repair to meet requirements below.
Note: This is a Triton approved in-service repair provided it
meets the following criteria:
1. Reinforcement angle must be one piece and of samethickness or thicker than the original crossmember.
2. Reinforcement angle must be stitch welded to the
crossmember web. Stitch welding must be minimum 25mm
length welds with a pitch of no greater than 100mm.
3. Repairs must be coated with primer and undercoating.
Note: This is not an approved Triton depot repair.
8/17/2019 Dry Van Manual
146/234
US - 07.xls
Condition: Flat plates applied to front of crossmember tofacilitate floorboard resecuring after floor board section.
Action: Repair.
Note: The correct repair in this case would be to weld a
reinforcement angle to the front of the crossmember. This is a
Triton approved in-service repair provided it meets the
following criteria:
* Reinforcement angle must be one piece and of same
thickness or thicker than the original crossmember.
* Reinforcement angle must be stitch welded to the
crossmember web. Stitch welding must be minimum 25mm
length welds with a pitch of no greater than 100mm.
* Repairs must be coated with primer and undercoating.
Note: This is not an approved Triton depot repair.
8/17/2019 Dry Van Manual
147/234
US - 08.xls
Condition: Flat plates applied to front of crossmember to
facilitate floorboard resecuring after floor board section.
Action: Repair.
Note: The correct repair in this case would be to weld a
reinforcement angle to the front of the crossmember. This is a
Triton approved in-service repair provided it meets the
following criteria:
* Reinforcement angle must be one piece and of same
thickness or thicker than the original crossmember.
* Reinforcement angle must be stitch welded to the
crossmember web. Stitch welding must be minimum 25mm
length welds with a pitch of no greater than 100mm.
* Repairs must be coated with primer and undercoating.
Note: This is not an approved Triton depot repair.
8/17/2019 Dry Van Manual
148/234
US - 08a.xls
Condition: In-service floor repair without undercoating the
wood panels.
Action: No action.
Note: Undercoating can be omitted from wood panels,
but it must be applied to steel components.
Triton depot repairs must include coating on both steel and
wood components.
8/17/2019 Dry Van Manual
149/234
US-09.xls
C-46
Condition: Broken, cracked, or partially missing plastic floor
angle.
Action: Perform light check.
Note: No action is required provided the area is light tight. If
light leaks, caulk.
Cost Allocation: Triton account.
8/17/2019 Dry Van Manual
150/234
US-09a.xls
C-13
Condition: Loose base gasket.
Action: If light is leaking, caulk.
8/17/2019 Dry Van Manual
151/234
US - 10.xls
Condition: Crossmembers bent below bottom side rail.
Action: Measure crossmember deflection.
Note: Crossmembers that are bowed more than 13mm
require replacement.
8/17/2019 Dry Van Manual
152/234
US-11.xls
C-47
Condition: Improper welding repair.
Action: Replacement required.
Note: This is an example of an improper repair of bowed
crossmembers by cutting through the full crossmember profile,
restraightening, and rewelding. Experience has shown that this
type of repair fails due to cracking of the vertical welds. Bowed
crossmembers that cannot be straightened by mechanical
means should be estimated for replacement.
Cost Allocation: Customer's account.
8/17/2019 Dry Van Manual
153/234
US-11a.xls
C-30
Condition: Crossmember bow repair with failed welds.
Action: Replace crossmembers.
Note: Repairing bowed crossmembers by V-notching and
rewelding the crossmembers is unacceptable as it leads to the
type of failure shown above.
8/17/2019 Dry Van Manual
154/234
US-11b.xls
C-32
Condition: Damage to flatrack heavy structural
members.
Action: Repair by straightening in combination with
flange and web inserts
Note: The majority of depot repair facilities do not
have the capability to make this type of repair. Repair
only in facilities that have the fixturing to straighten
and position heavy sections and the expertise to do
cutting and structural welding of thick sections.
8/17/2019 Dry Van Manual
155/234
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES forSTEEL DRY CARGO and OPEN TOP CONTAINERS
12. INTERIOR WALLS
Background
Improper in-service straightening is the most common
problem affecting the interior wall condition of containers.The IICL workmanship standard for panel straighteningrequires that the panel be returned, as near as is possible,to the original profile. The acceptability of the straighteningworkmanship is based on the extent to which thecorrugation bend radii and flats between the bend radii havebeen returned to their original positions and profiles. Inaddition, both sides of the repair must be properly surfaceprepared and painted.
In-service panel repairs quite often do not meet the IICLworkmanship standards: the panels are hammered backwithin the inspection criteria without efforts made to restorethe corrugation profiles, and the surface preparation andpainting is substandard or omitted entirely.
Triton Standards
The IICL leaves the decision to correct improper repairs tothe equipment owner. Triton’s standards for improper repaircorrection and other standards related to the containerinterior can be summarized as follows:
8/17/2019 Dry Van Manual
156/234
•
All repairs must be within IICL dimension inspectioncriteria.
• Improper in-service panel straightening, substandardpainting, or unpainted straightening does not requirecorrection.
•
Patches or welds that were not painted at the time ofrepair require surface preparation and painting.
• In-service repairs can be painted with any color paint.
•
Cosmetic painting is not required.
•
Touch-up of corrosion and preventative maintenancepainting is not required.
•
Corrosion is repaired only if it fails a hammer test.
•
Non-original lashing rings and bars may be left in placeprovided they 1) do not intrude into the cube or 2) arelocated on the inner faces of the headers and do notprotrude beyond the inner vertical faces of the corner
castings or 3) are located between the upper cornercasting and the corner post above the lower face of theupper corner casting.
The photos on the following pages demonstrate thestandards addressed above and explain other Tritonstandards relative to interior panel condition.
Ports with On-hire Standards ExceedingIICL and Triton Standards
In certain ports, carriers and shippers have local standardsfor interior wall condition and cleanliness that exceed IICLand Triton standards, and containers not meeting thesestandards will be rejected for on-hire. In these cases, it isunderstood that the local port standard overrides the IICL
8/17/2019 Dry Van Manual
157/234
and Triton standards, and the local off-hire standard will beraised to match the local on-hire standard.
DVMAN FEB07 SEC5 IW.doc
8/17/2019 Dry Van Manual
158/234
IW 5-01.xls
Condition: Unpainted hammer marks on interior panel.
Action: No action.
Note: Painting required if necessary to meet local port
on-hire standards.
8/17/2019 Dry Van Manual
159/234
IW 5-02.xls
Condition: Bad straightening.
Action: No action.
Condition: Interior straightening not painted.
Action: No action.
Note: Painting required if necessary to meet local port
on-hire standards.
8/17/2019 Dry Van Manual
160/234
IW 5-03.xls
Condition: Corroded patch on interior.
Action: No action.
Note: Painting required if necessary to meet local port
on-hire standards.
8/17/2019 Dry Van Manual
161/234
IW 5-04.xls
Condition:Corrosion on interior of patch.
Action: No action.
Note: Painting required if necessary to meet local port
on-hire standards.
8/17/2019 Dry Van Manual
162/234
IW 5-05.xls
Condition: Poor straightening and welding workmanship.
Action: No action.
Note: Panel weld repairs can exceed the IICL limit of 200 mm.
8/17/2019 Dry Van Manual
163/234
IW 5-06.xls
Condition: Poor straightening and welding workmanship.
Action: No action.
8/17/2019 Dry Van Manual
164/234
IW 5-07.xls
Condition: Straightening and welding with bad workmanship.
Action: No action.
Note: Roof weld repairs can exceed the IICL limit of 200 mm.
8/17/2019 Dry Van Manual
165/234
IW 5-08.xls
Condition: Unpainted weld and weld smoke.
Action: Clean and paint.
Condition: Poor quality weld.
Action: No action.
8/17/2019 Dry Van Manual
166/234
IW 5-09.xls
Condition: Unpainted weld and weld smoke.
Action: Clean and paint.
8/17/2019 Dry Van Manual
167/234
IW 5-10.xls
Condition: Interior touch-up with non-Triton paint color.
Action: No action.
Note: Any color paint is acceptable on the interior walls.
8/17/2019 Dry Van Manual
168/234
IW 5-11.xls
Condition: Weld smoke on interior wall.
Action: Remove.
Condition: Incorrect interior paint color.
Action: No action.
Note: There is no limitation on interior repair paint color.
8/17/2019 Dry Van Manual
169/234
IW 5-12.xls
Condition: Dried, non-sticky glue on interior panels.
Action: No action.
Note: Removal is required if not acceptable for on-hire.
8/17/2019 Dry Van Manual
170/234
IW 5-13.xls
C-48
Condition: Exterior panel dent blocking access to cargo
lashing ring.
Action: No action.
8/17/2019 Dry Van Manual
171/234
IW 5-14.xls
Condition: Non-original lashing ring.
Action: No action.
Note: Non-original lashing rings and bars that intrude into the
container's interior cube must be removed. Non-original
lashing rings welded to the headers can be left in place
provided they do not extend beyond the plane of the inward
vertical faces of the corner castings.
8/17/2019 Dry Van Manual
172/234
IW 5-15.xls
Condition: Non-original lashing rings on top side rail.
Action: Remove.
Note: Non-original lashing rings and bars that intrude into the
container's interior cube must be removed. Non-original
lashing rings welded to the headers can be left in place
provided they do not extend beyond the plane of the inward
vertical faces of the corner castings.
8/17/2019 Dry Van Manual
173/234
IW 5-16.xls
Condition: Non- original lashing rod.
Action: Remove.
Note: Non-original lashing rings and bars that intrude into the
container's interior cube must be removed. Non-original
lashing rings welded to the headers can be left in place
provided they do not extend beyond the plane of the inward
vertical faces of the corner castings.
8/17/2019 Dry Van Manual
174/234
IW 5-17.xls
Condition: Non-original lashing bar.
Action: No action.
Note: Non-original lashing rings and bars that intrude into the
container's interior cube must be removed. Non-originallashing rings welded to the headers can be left in place
provided they do not extend beyond the plane of the inward
vertical faces of the corner castings.
Condition: Unpainted lashing bar welds.
Action: Clean and Paint.
8/17/2019 Dry Van Manual
175/234
IW 5-17a.xls
C-18
Condition: Non-standard, but factory original lashing bars.
Action: No action.
Note: Certain container designs have factory lashing bars
positioned horizontally between the upper corner casting innerfaces and the corner posts. Triton will accept customer in-
service installed lashing bars in the same location.
8/17/2019 Dry Van Manual
176/234
IW 5-17b.xls
C-16
Condition: Interior wall scratches.
Action: Repair.
Cost Allocation: Customer's account due to the extent of
scratching on the recessed corrugations.
Note: Off-hire repair worthiness of interior scratching is
guided by the IICL inspection criteria adjusted upward if
necessary to meet local on-hire standards.
8/17/2019 Dry Van Manual
177/234
IW 5-17c.xls
C-17
Condition: Interior wall scratches.
Action: Repair.
Cost Allocation: Customer's account due to the extent of
scratching on the recessed corrugations.
Note: Off-hire repair worthiness of interior scratching is guided
by the IICL inspection criteria adjusted upward if necessary to
meet local on-hire standards.
8/17/2019 Dry Van Manual
178/234
IW 5-18.xls
Condition: Chemical attack of interior paint.
Action: If the entire interior paint system or large areas are
affected, repair by compete or partial interior refurbishment.
Touch-up painting or wire brushing and painting is not
acceptable for chemical attack repair.
Note: No action is required for minor, isolated areas of
chemical paint attack.
8/17/2019 Dry Van Manual
179/234
IW 5-19.xls
Condition: Minor, isolated areas of chemical paint attack.
Action: No action.
8/17/2019 Dry Van Manual
180/234
IW 5-20.xls
Condition: Large area of chemical attack on interior paint.
Action: Partial interior refurbishment.
8/17/2019 Dry Van Manual
181/234
IW 5-21.xls
Condition: Chemical attack of ceiling paint.
Action: Refurbish ceiling.
Note: Painting over or grinding and painting chemically
contaminated paint will not stop further attack. All paint on
the contaminated surfaces must be removed by abrasive
blasting.
8/17/2019 Dry Van Manual
182/234
IW 5-22.xls
Condition: Chemical attack of container interior.
Action: Complete interior refurbishment and possible
floor replacement.
8/17/2019 Dry Van Manual
183/234
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES forSTEEL DRY CARGO and OPEN TOP CONTAINERS
13. FLOOR
Triton Standards
There are various areas relative to allocating floor repairs todamage or wear & tear and the acceptability of alternativerepair methods that require clarification. The photos on thefollowing pages specify Triton’s standards in those areas.
Ports with On-hire Standards ExceedingIICL and Triton Standards
In certain ports, carriers and shippers have local standardsfor floor condition and cleanliness that exceed IICL andTriton standards, and containers not meeting thesestandards will be rejected for on-hire. In these cases, it is
understood that the local port standard overrides the IICLand Triton standards, and the local off-hire damageinspection and repair standards will be raised to match thelocal on-hire standard.
8/17/2019 Dry Van Manual
184/234
In all cases, the fundamental IICL principle applies that,unless there is a prior agreement to the contrary betweenthe owner and user of the container, the criteria are to beapplied equally at off-hire and on-hire. As stated in the
Guide for Container Equipment Inspection / Fifth Edition /IICL-5 , “The recommendations and definitions of terms mustbe applied consistently, both at on-hire and off-hireinterchanges.”
DVMAN SEC6 FL.doc
8/17/2019 Dry Van Manual
185/234
FL 6-01.xls
Condition: Non-repairworthy gouge on board that has loose
splintered areas.
Action: Remove splinters and sand rough edges to preventcargo from getting caught on flooring.
Note: This repair is only required on the interior face of the
floor board. Gouges on the underside of the floor board are
not repairworthy unless they exceed the IICL gouge criteria.
8/17/2019 Dry Van Manual
186/234
FL 6-02.xls
Condition: Surface delamination of floor.
Action: Section only if exceeds the IICL floor gouge criteria.
Condition: Rough edges and splinters due to surface
delamination.
Action: Grind smooth.
8/17/2019 Dry Van Manual
187/234
FL 6-03.xls
Condition: Gouged and splintered flooring.
Action: Apply the IICL gouge criteria to determine if repair is
required.
Note: Inspectors should not pull top veneers from the flooring
to check for delamination unless the floor is clearly and
obviously delaminated.
8/17/2019 Dry Van Manual
188/234
FL 6-04.xls
Condition: Gouged subfloor.
Action: No action provided the IICL gouge criteria is not
exceeded.
Note: Subfloor gouges should not be confused with breakage
due to impact on the top of the board.
8/17/2019 Dry Van Manual
189/234
8/17/2019 Dry Van Manual
190/234
FL 6-07.xls
C-58
Condition: Finger cracking on underside of floor.
Action: No action unless the damage meets the requirements
of IICL technical bulletin IICL TB 003, 1 May 2005. "Not all
cases of finger cracking will be repair worthy. Finger cracking
will be repair worthy only when accompanied by one or more ofthe following conditions:
* Visible sign of impact on the opposite side
* Damage to adjacent components, i.e., crossmembers, sills,
floor rails, hat sections
* Visible bowing of the opposite side of the floor
* Hollow sound when hammer tested"
8/17/2019 Dry Van Manual
191/234
FL 6-08.xls
Condition: Surface delamination of flooring.
Action: Replace flooring.
Cost Allocation: Charge to Triton account.
Note: Surface delamination of flooring is caused by improper
gluing of the original floor panels. Lack of glue adhesion is
indicated by the brown layer of glue without embedded wood
fibers.
8/17/2019 Dry Van Manual
192/234
FL 6-09.xls
Condition: Damaged and delaminated floorboard.
Action: Replace floorboard.
Note: Even though there are signs of damage, the severe
surface delamination of the flooring indicates that the flooring
was defective. Allocate repair costs to Triton.
8/17/2019 Dry Van Manual
193/234
FL 6-10.xls
Condition: Top veneers of floor delaminated at threshold.
Action: Add floor screws in areas where veneer protrudes
above the sill.
8/17/2019 Dry Van Manual
194/234
FL 6-11.xls
Condition: Sagging of flooring between crossmembers.
Action: Replace flooring.
Cost Allocation: Allocate costs based on the guidance given
in the IICL manual: Supplement on Container Inspection and
Repair: Gray Areas / Second Edition.
Note: Sagging of the floor between crossmembers is caused
by interior delamination of the plywood. Delamination can be
caused by shear failure due to overloading or shear failure due
to gluing or material problems in the original floor construction.
Refer to the IICL gray area manual for guidance.
8/17/2019 Dry Van Manual
195/234
FL 6-16.xls
Condition: Factory coated floor with coating scraped and
worn off.
Action: No action.
Note: It is not necessary to recoat the floor when the original
factory coating is worn off. Floor section repairs to coated
floors need not be coated.
8/17/2019 Dry Van Manual
196/234
FL 6-16a.xls
C-08
Condition: Floor hole greater than 13mm in diameter.
Action: Repair by installing a dowel.
Note: The IICL now accepts floor dowel repairs up to 25 mm
in diameter.
8/17/2019 Dry Van Manual
197/234
FL 6-16b.xls
C-12
Condition: Large diameter holes drilled in floor.
Action: Repair subject to the note, below.
Note: Large floor holes up to 25 mm in diameter may be
repaired with dowels with the following dimensional limitations:
1) The minimum distance between the dowel and any floor
panel edge, screw, or another dowel is 50mm, and 2) A
maximum of three dowel repairs is allowed in any area of the
floor that is transversely between the floor center support and
the side rails and longitudinally between crossmembers or
crossmember and sill.
8/17/2019 Dry Van Manual
198/234
FL 6-17.xls
C-59
Condition: Drilled hole in floor that cannot be repaired
with a 13 mm diameter dowel.
Action: Repair with a dowel up to 25mm diameter.
Note: The IICL repair standard has been revised to allow
dowel repairs up to 25mm.
8/17/2019 Dry Van Manual
199/234
FL 6-18.xls
C-60
Condition: In-service dowel repair with unacceptable
workmanship.
Action: Repair with dowel if repair can be done within the IICL
25mm diameter limit. Otherwise, section floor.
8/17/2019 Dry Van Manual
200/234
FL 6-18a.xls
C-11
Condition: In-service floor dowel repair.
Action: No action.
Note: In-service floor dowel repairs must meet the IICL repair
standards. Although the repair shown above is not smoothly
finished and completely flush with the floor surface, it is of
acceptable quality.
8/17/2019 Dry Van Manual
201/234
FL 6-18b.xls
C-10
Condition: Floor dowel repair with unacceptable
workmanship.
Action: Rework to meet IICL repair standards.
Note: Insert floor only if dowels cannot be reworked to IICL
standards.
8/17/2019 Dry Van Manual
202/234
FL 6-19.xls
Condition: Nail on interior surface of flooring.
Action: Remove.
Note: It is acceptable to leave nails in place only when the
nail head is flush with the surface.
8/17/2019 Dry Van Manual
203/234
FL 6-20.xls
Condition: Nails protruding from bottom of floor.
Action: No action.
8/17/2019 Dry Van Manual
204/234
FL 6-21.xls
Condition: Nail holes in floor boards.
Action: Repair is required only if the nail holes leak light.
Note: If nail holes leak light, repair by filling with hard putty.
Drilled holes up to 5 mm can be filled with hard putty. Drilled
holes greater than 5 mm up to 25 mm must be repaired with a
dowel.
8/17/2019 Dry Van Manual
205/234
FL 6-22.xls
Condition: Nail holes filled with putty.
Action: No action.
Note: Nail holes should not be repaired unless they leak light.
Note: As a general guideline, hard putty installed while the
container was in-service should be left in place at off-hire
provided it is applied smoothly and flush with the floor, does
not pass entirely through the floor, and does not appear to be
hiding a broken floor condition. Conversely, soft putty should
always be removed and followed by floor inspection applying
the IICL gouged and/or broken floor criteria.
8/17/2019 Dry Van Manual
206/234
FL 6-23.xls
Condition: Burned floor boards
Action: No action provided the burned area does not exceed
the IICL gouge criteria.
Note: Clean away the charred wood and apply the IICL gouge
criteria.
8/17/2019 Dry Van Manual
207/234
FL 6-24.xls
Condition: Corroded floor screws causing stains on floor.
Action: No action.
8/17/2019 Dry Van Manual
208/234
FL 6-24a.xls
C-09
Condition: Floor repair with screws at panel edges.
Action: No action unless floor panels are loose.
Note: If floor panels are loose, resecure by adding screws.
8/17/2019 Dry Van Manual
209/234
FL 6-25.xls
Condition: Oil leaking through the floor onto the
undercarriage.
Action: No action.
Note: Oil on the undercarriage indicates that oil was spilled onthe interior floor, but it does not drive the decision to either
clean or replace the flooring. This decision is driven by the
IICL cleanliness standards applied to the interior surface
condition of the floor.
8/17/2019 Dry Van Manual
210/234
TRITON CONTAINER INTERNATIONAL INC.
INSPECTION & REPAIR GUIDELINES forSTEEL DRY CARGO and OPEN TOP CONTAINERS
14. OPEN TOPS
Triton Standards
There are various tarp and roof bow repair standards thatrequire clarification. The photos on the following pagesspecify Triton’s requirements in those areas.
Ports with On-hire Standards ExceedingIICL and Triton Standards
In certain ports, carriers and shippers have local standardsfor tarp condition that exceed IICL and Triton standards, andcontainers not meeting these standards will be rejected foron-hire. In these cases, it is understood that the local portstandard overrides the IICL and Triton standards, and the
local off-hire damage inspection and repair standards will beraised to match the local on-hire standard.
In all cases, the fundamental IICL principle applies that,unless there is a prior agreement to the contrary between
8/17/2019 Dry Van Manual
211/234
the owner and user of the container, the criteria are to beapplied equally at off-hire and on-hire. As stated in theGuide for Container Equipment Inspection / Fifth Edition /
IICL-5 , “The recommendations and definitions of terms must
be applied consistently, both at on-hire and off-hireinterchanges.”
DVMAN SEC7 OT.doc
8/17/2019 Dry Van Manual
212/234
OT 7-01.xls
C-50
Condition: Non-original roof bows.
Action: Repair.
Note: Non-original roof bows are acceptable provided: 1) they
fit into the original retainers, 2) they are galvanized or painted,
3) they do not have sharp edges contacting the tarp, 4) they
have zero or positive camber, and 5) they are flush with the top
side rail at the retainers.
8/17/2019 Dry Van Manual
213/234
OT 7-02.xls
C-55
Condition: Non-original roof bow.
Action: Repair.
Note: Non-original roof bows are acceptable provided: 1) they
fit into the original retainers, 2) they are galvanized or painted,
3) they do not have sharp edges contacting the tarp, 4) they
have zero or positive camber, and 5) they are flush with the top
side rail at the retainers.
8/17/2019 Dry Van Manual
214/234
OT 7-03.xls
C-56
Condition: Non-original roof bow.
Action: No action.
Note: Non-original roof bows are acceptable provided: 1) they
fit into the original retainers, 2) they are galvanized or painted,
3) they do not have sharp edges contacting the tarp, 4) they
have zero or positive camber, and 5) they are flush with the
top side rail at the retainers.
8/17/2019 Dry Van Manual
215/234
OT 7-04.xls
Condition: Non-original roof bow.
Action: No action (assuming the flat bar is welded to the
tube on the backside).
Note: Non-original roof bows are acceptable provided: 1) they
fit into the original retainers, 2) they are galvanized or painted,
3) they do not have sharp edges contacting the tarp, 4) they
have zero or positive camber, and 5) they are flush with the top
side rails at the retainers.
Note: In two piece roof bow designs such as the one shown
above, the pieces must be welded together.
8/17/2019 Dry Van Manual
216/234
OT 7-05.xls
C-52
Condition: Non-original roof bow.
Action: Replace.
Note: Non-original row bows of this type fail by bending in the
flat bar area adjacent to the retainer. For this reason, it isrequired that the flat bar have a minimum thickness of 6mm
and extend no farther than 25mm beyond the retainer. The flat
bar must be welded into the tube.
Note: In addition, non-original roof bows are acceptable
provided: 1) they fit into the original retainers, 2) they are
galvanized or painted, 3) they do not have sharp edges
contacting the tarp, 4) they have zero or positive camber, and
5) they are flush with the top side rail at the retainers.
8/17/2019 Dry Van Manual
217/234
OT 7-06.xls
Condition: Roof bow with full section repair.
Action: No action.
Note: If rough, the welds should be ground smooth where they
contact the tarp.
8/17/2019 Dry Van Manual
218/234
OT 7-06a.xls