DriveSize Users Manual

Embed Size (px)

Citation preview

  • 8/12/2019 DriveSize Users Manual

    1/59

    Drive PC tools

    User manualDriveSize

  • 8/12/2019 DriveSize Users Manual

    2/59

  • 8/12/2019 DriveSize Users Manual

    3/59

    3

    User manual

    DriveSize

    3AXD00000000073 Rev 1ENEFFECTIVE: 2014-03-03

    2014 ABB Oy. All Rights Reserved

  • 8/12/2019 DriveSize Users Manual

    4/59

    4

  • 8/12/2019 DriveSize Users Manual

    5/59

    5

    Table of contents

    Introduction to the manual 9

    What this chapter contains ................................................................................................. 9

    Applicability ........................................................................................................................ 9

    Compatibility ....................................................................................................................... 9

    Purpose of the manual........................................................................................................ 9

    Target audience.................................................................................................................. 9

    Terms and abbreviations .................................................................................................. 10

    Overview of DriveSize 11

    What this chapter contains ............................................................................................... 11

    DriveSize installation instructions ..................................................................................... 11Program structure ............................................................................................................. 11

    DriveSize functions ........................................................................................................... 12

    DriveSize Help .................................................................................................................. 12

    Dimensioning 13

    What this chapter contains ............................................................................................... 13

    Starting a new project ....................................................................................................... 13

    Selecting a product series ......................................................................................... 14

    Changing project data ............................................................................................ 15Selecting ambient conditions.................................................................................. 15

    Input data ......................................................................................................................... 16

    The main dimensioning window ........................................................................................ 16

    Toolbar ...................................................................................................................... 17

    System configuration ................................................................................................. 18

    Network and transformer data ................................................................................... 19

    Motor input data ........................................................................................................ 20

    Selecting the load type and duty cycle ................................................................... 20

    Entering motor speeds and loads ........................................................................... 21

    One-time overload at start ...................................................................................... 23

    Changing motor specifications ............................................................................... 24

    Motor selection in general and User selection ........................................................ 25

    Additional derating requirements ............................................................................... 25

    Reinforced insulation.............................................................................................. 25

    Terminal boxes ...................................................................................................... 25

    Inverter input data...................................................................................................... 26

    Entering inverter load ............................................................................................. 26

    Changing inverter specifications ............................................................................ 27

    Inverter selection in general and User selection ..................................................... 27Selecting liquid cooled inverter ............................................................................... 28

  • 8/12/2019 DriveSize Users Manual

    6/59

  • 8/12/2019 DriveSize Users Manual

    7/59

    7

    Printing the dimensioning results ...................................................................................... 56

    Efficiency Report .............................................................................................................. 57

    Network check report ........................................................................................................ 57

    Product and service inquiries ..................................................................................... 58

    Product training ......................................................................................................... 58Providing feedback on ABB Drives manuals .............................................................. 58

    Document library on the Internet................................................................................ 58

  • 8/12/2019 DriveSize Users Manual

    8/59

    8

  • 8/12/2019 DriveSize Users Manual

    9/59

    9

    Introduction to the manual

    What this chapter contains

    This chapter gives basic information on the manual.

    Applicabili ty

    This manual applies to DriveSize (version 3.9 or later).

    Note:Version-specific installation instructions for DriveSize are given in the readme file.The file contains also hardware and system requirements. Read the readme file carefullybefore installing the software.

    Compatibility

    DriveSize is compatible with ABB low voltage AC drives and ABB low voltage motorssuitable for the use with the drives. The software is also compatible with the ABB DC

    drives and ABB direct-on-line motors if the software includes the appropriate additionalcomponents. These components have their own manuals.

    Purpose of the manual

    This manual instructs you to use DriveSize for selecting motors and drives.

    Target audience

    To use this manual you must have basic knowledge of: Terminology of AC drives

    ABB product names Load torque, power and speed requirements.

    1

  • 8/12/2019 DriveSize Users Manual

    10/59

    10 Introduction to the manual

    Terms and abbreviations

    The table below lists the terms and abbreviations which have a special meaning in theDriveSize software and this manual.

    Term/Abbreviation Description

    Base speed Maximum speed of the driven machinery at nominal load

    torque. Also maximum speed of constant torque range

    (and minimum speed of constant power range).

    Base power Motor shaft power, typically, nominal load of the

    machinery on the motor shaft. Also used as the reference

    value for loads of the duty cycle.

    Drive Frequency converter for controlling AC motors

    DSU Diode supply unit

    Generating The operating mode of the IGBT supply unit whenconverting power from the drive back to the AC supply.

    Generator bridge The bridge of the thyristor supply unit in the regenerative

    mode (converts power from the drive back to the AC

    supply).

    IC International Cooling

    IP International Protection

    ISU IGBT supply unit

    LC Liquid cooling

    Line-up Consists of the supply unit and inverters which have a

    common DC bus.

    Motor bridge The bridge of the thyristor supply unit or diode supply unit

    in the rectifying mode (converts power from the AC

    supply to the DC link of the drive).

    Motoring The operating mode of the IGBT supply unit when

    converting power from the AC supply into the drive DC

    link.

    Overload Defines the maximum required power for short durations.

    The power is overload in percent x base power. The

    overload in percent is normally positive, but a negativevalue means the overload has a different sign than the

    base power.

    One-time at start overload This overload type is allowed once, for instance, at start.

    Before the next start, it is assumed that the drive has

    cooled down to the ambient temperature.

    TempRiseClass Temperature rise class of the motor.

    TSU Thyristor supply unit

  • 8/12/2019 DriveSize Users Manual

    11/59

    11

    Overview of DriveSize

    What this chapter contains

    This chapter tells you how to install and start the DriveSize program. It also provides

    general information about using DriveSize.

    DriveSize installation instructions

    Note:Version-specific installation instructions for DriveSize are given in the readme file.

    The file contains also hardware and system requirements. Read the readme file carefullybefore installing the software.

    Program structure

    DriveSize consists of a user interface with dimensioning functions and of productdatabases. The databases contain catalog motors and drives and the units/modules of

    the drives. Dimensioning of customer-specific motors is based on ABB Sophi, which hasbeen developed by ABB Oy / Machines. The DriveSize installation package includes ABB

    Sophi.

    The program follows the common user interface guidelines of Microsoft Windows.

    When you select first one of the AC drive product series, the associated productdatabase opens. The dimensioning cases are called projects. You can save the selectionresults for the project into their own project file (XML file). You can then generatetechnical reports in the MS Excel format and you can attach the reports to the project and

    drive documentation.

    2

  • 8/12/2019 DriveSize Users Manual

    12/59

    12 Overview of DriveSize

    DriveSize functions

    DriveSize offers several functions for dimensioning the drive. All of the functions areavailable on the main menu bar or toolbar. This manual also describes other ways to

    access these functions.

    DriveSize contains the following items for dimensioning: Ambient conditions (There are separate functions for the conditions of drives and

    motors.)

    Motor temperature rise class

    Motor load types available:

    Constant power

    Constant torque

    Constant torque and power

    Squared torque (Pump/fan)

    Overload types available:

    One-time at start

    Simple cyclic

    Multiform cyclic

    Supply unit power factor

    Network harmonics calculation

    Harmonics for any inverter or supply unit

    Combined harmonics

    Thermal loss calculations for motor, inverter and supply unit

    Supply-unit-specific total mass flow and dissipated losses for liquid cooled multidrives

    Results in numerical form

    Results in graphical form (load, motor, inverter)

    Selecting an alternative inverter, a motor and a line supply unit

    Selecting metric units or US units

    Generating reports in Excel format for saving or printing

    Saving and retrieving dimensioning cases

    Saved information is in XML format and can be used with other software.

    DriveSize Help

    The DriveSize HTML help includes information on using the program and dimensioning adrive. You can access the DriveSize Help through the Helpmenu or by pressing F1. TheDriveSize Help is context sensitive and when F1 is pressed, the help automatically opensa help window associated with the active function of the program.

  • 8/12/2019 DriveSize Users Manual

    13/59

    13

    Dimensioning

    What this chapter contains

    This chapter describes how to make dimensioning or retrieve a previously saved project

    file.

    Starting a new project

    You can make a complete drive system design with DriveSize in many ways. The

    following list is an overview of the tasks you can perform with DriveSize. Later on you willlearn shortcuts to perform the same tasks more quickly.

    Double click a product family or select one and click Openin the New projectselection (See Figure 1: New project8.6cm).

    You may enter project information. Select Project Infoon the Filemenu. (See Figure2: Project information).

    If ambient conditions deviate from normal selectAmbient Condit ionson the Datamenu and set new ones. (See Figure 3: Ambient conditions).

    If the network data, voltages and frequency deviate from your previous settingschange them from main window (See Figure 4: The main dimensioning window). InSystem configuration, highlight a network/transformer. (See Figure 5: Network data

    and Transformer load definition).

    In System configuration, highlight the motor and enter load definitions (See Figure

    6: Motor load and specifications data). Let DriveSize to select the motor. If you wish tochange the motor, use the User selection functions.

    Let DriveSize to select the drive or inverter once the motor/motors are known.MultiDrive systems normally contain many inverters and motors and DriveSize is able

    with one shot select all. You can also select manually the drive or inverter.

    3

  • 8/12/2019 DriveSize Users Manual

    14/59

    14 Dimensioning

    For a multidrives, the dimensioning of line supply unit is done when the inverters andmotors have been defined.

    Note:The supply unit type has also effect on the motors.

    In System configuration, use a toolbar icon or a menu command or press Ctrl+Dto

    control the dimensioning for a selected unit. You can make dimensioning one by one(Ctrl+D) or dimension all units at same time (Ctrl+A).

    Selecting a product series

    When you start DriveSize without a project file, the Welcomewindow opens. If you are

    starting a new project, you must select a product series first. Figure 1: New project8.6cmshows the Welcomewindow.

    Figure 1: New project8.6 cm

    Use Project Info on the Filemenu andAmb ient Condit ionson the Datamenu if you

    wish to change the defaults. You can change this information later with menu commands.

  • 8/12/2019 DriveSize Users Manual

    15/59

    15

    Changing project data

    Figure 2: Project informationshows the Project informationwindow. Enter new project

    data in the specified text box. DriveSize saves this information when you save yourproject and includes it in your reports. Click OKto accept the project information. Click

    Cancelto discard the changes.

    Figure 2: Project information

    Selecting ambient condi tions

    Figure 3: Ambient conditionsshows theAmbient conditions window. Type new data tothe appropriate text box to change the ambient conditions. The practical range for altitudeis between 1000 m and 4000 m.

    Note: The dependency of the altitude to the loadability varies with different components.The practical range of ambient temperature is mostly from 30 C to 50 C. This alsovaries with the component. For example, a temperature up to 55C is accepted for

    ACS880 single drives and marine drives but Ex motors are not selected at all if theambient temperature exceeds 40C.

    Click OKto accept the project information. Click Cancelto discard the changes.

    Figure 3: Ambient conditions

  • 8/12/2019 DriveSize Users Manual

    16/59

    16 Dimensioning

    Input data

    Motors, inverters, line supply units, transformers and the network have different datainput displays. When you click an item in the System configurationfield, the input data

    display changes depending on the item you select.

    The main dimensioning window

    After opening or creating a project the main window opens. Figure 4: The maindimensioning window shows its main parts.

    Figure 4: The main dimensioning window

    The main window contains a title bar, a menu bar, a toolbar, the System configurationfield, the input data field and a field which displays the data that you selected. Each field

    has a specific usage and functions.

    The main dimensioning windows title bar displays the name of the project.

    The menu bar contains the DriveSize menus. Each menu contains a group of selections,

    each of which performs a specific function. Click on a menu to open it. You can also opena menu with key combinations. Press theAlt key plus the letter that is underlined in themenus title. To choose a menu selection, press the appropriate letter, or use the cursor

    keys to highlight it and press ENTER.

    You can also access many of DriveSize's functions from the keyboard by using keycombinations. These combinations are called shortcut keys. The shortcut key for acommand appears to the right of the command on the menus.

  • 8/12/2019 DriveSize Users Manual

    17/59

    17

    Toolbar

    The toolbar provides quick access to common commands in DriveSize. Toolbar buttons

    perform a function just like a menu selection. To perform the function of a certain button,click the button on the toolbar.

    Tip:When you move the cursor over the button, the help text for that button appearsbelow it.

    Table 1: Toolbar icons

    Icon Action Menu equivalent

    Opens a new project. New... command under the Filemenu.

    Opens a project. Open... command under the Filemenu.

    Saves the project. Save... command under the Filemenu.

    Shows the Printdialog. Print... command under the Filemenu.

    Shows theAmbient Condi tions

    view.

    Ambient Condi tions command under the Data

    menu.

    Shows the Overload Definitions

    view.

    Overload Definiti ons command under the

    Data menu.

    Shows the Network Checkview. Network Check... command under the Tools

    menu.

    Dimensions the selected item. Make Dimensioning command under the

    Toolsmenu.

    Shows the dimensioning Results

    view.

    Dimensioning Result... command under the

    Resultmenu.

    Shows the Graphview. Graphs... command under theResult menu.

    Shows the Selected Unitview. List of Selected... command under the Result

    menu.

    Shows the User Selectionview. User Selection command under the Toolsmenu.

  • 8/12/2019 DriveSize Users Manual

    18/59

  • 8/12/2019 DriveSize Users Manual

    19/59

    19

    Network and transformer data

    The primary voltage does not have effect on motor and drive choices but if you select a

    value that is too high it prevents you from selecting a transformer. The default systemfrequency is 50 Hz but it changes to 60 Hz if valid. The default system frequency has a

    direct effect on possible secondary voltage levels as well as on the motor databases. Thelogic of DriveSize assumes that in the 60 Hz countries the standard motors are 60 Hzmotors. This limitation is not valid with the AC Drives.

    Short-circuit power is essential when network harmonics are calculated. DriveSize has apractical upper limit for short-circuit power.

    Figure 5: Network data and Transformer load definitionshows the Network dataandTransformer loaddialog.

    DriveSize calculates the transformer load power from the motor base powers and

    efficiencies and power factors. You can allow DriveSize to use these values, but inspecial cases you can use your own values.

    The software includes Oil immersedand Vacuum Cast Coil Drytypes of transformers.

    Figure 5: Network data and Transformer load definition

  • 8/12/2019 DriveSize Users Manual

    20/59

  • 8/12/2019 DriveSize Users Manual

    21/59

    21

    Entering motor speeds and loads

    The Motor speedand Motor loadinput fields vary with different load types.

    DriveSize does not accept gear information. If a gear is involved, convert the values tomotor speed manually or use an Excel sheet.

    DriveSize does not consider dynamic torque when it accelerates inertias up and down.When remarkable dynamic torque exists, include it as short term overloads.

    Base speed

    Base speed is the minimum mechanical speed of a motor where the base power isrequired.

    Note: Use exact values for base speed. Use 1456 (not1500) because the rated speedsof motors are also exact.

    Base power

    Base power is the mechanical power of a motor. This is used as the base value for alloverloads. Note that motor thermal dimensioning is based on worst 10 min RMS by

    default. For motor selection there is an option to skip RMS computing. Select Skip RMS-

    computing of overloadsfrom Toolsmenus Options. You can use a round number like10 kW, 50 kW or 100 kW and type in overloads based on the base value you select. Basepower is normally positive but negative values are acceptable.

    Fill in the required load that is on the shaft notthe rated power of the motor. Specify thereal required shaft power of the loading machine. In VSD applications, the motors arealways slightly derated.

    Base overload

    Base overload defines the maximum required power together with base power for theoverload time. The power is overload in percent x base power. Overload in percent is

    normally positive but a negative value means that the overload has a different sign thanthe base power.

    Min speed

    If the minimum speed is too low, DriveSize selects for the motors and drives a size that islarger than necessary. In DriveSize, the minimum speed is not exactly the minimumspeed of the motor but a speed that is used without interruptions of, for example,

    30 minutes. DriveSize assumes that the duty cycle continues without stopping and

    DriveSize selects the motor and drive accordingly. If the minimum speed is critical, youcan see it from the results/graphs. The default minimum speed is 300 rpm or 400 rpm.

    Max speed

    A maximum speed that is too high can have a negative impact on the motor size. If themaximum speed is much higher than the base speed and the overload in percent is high,

    the absolute maximum torque of the motor can be a limiting factor.

  • 8/12/2019 DriveSize Users Manual

    22/59

    22 Dimensioning

    Overload at max speed

    Due to the reasons stated above, the overload in percent at maximum speed can be

    given a different normally lower - value than the overload in percent at base speed. Thisis valid for constant power load types.

    Figure 6: Motor load and specifications data

  • 8/12/2019 DriveSize Users Manual

    23/59

    23

    One-time overload at start

    Figure 7: Motor input datashows where you select the values forOne-time overload at

    start.OL[%]

    The starting torque is OL% x base torque. The base torque is calculated from the basepower and base speed. The valid range for OL% is from 1% to 1000%.

    OL timeis the duration of the starting overload in seconds.

    OL max speedtells DriveSize at which speed the overload ceases. Use low values. Ifthe OL maximum speed is equal to the base speed and OL% is high, the power limit of

    the inverter can force DriveSize to select a larger drive.

    Figure 7: Motor input data

  • 8/12/2019 DriveSize Users Manual

    24/59

    24 Dimensioning

    Changing motor specifications

    You can adjust the specifications for the motor such as the number of motors, the

    preferred motor type, frame material, IP class, IC class, temperature rise class and so on.

    Click the item to change a selection.

    The first item in the Specificationslist is the name. To display Namein Systemconfiguration, go to Tools -> Options-> Unit name. DriveSize displayes the type codes

    of motors.Table 3: Options for Motor Specifications

    Specification Options

    Name Any text or string

    Motors per inverter 1...100 per inverter unit. > 1 = MultiMotor Case, a factor DriveSize considers

    when it selects an inverter. The load is given for one motor. One inverter feeds

    several motors connected in parallel.

    Motor type IEC 34 catalogHXR, AMI Motors

    NEMA catalog

    Marine motors

    Water cooled

    PM motors

    Flameproof

    Non-sparking

    Dust ignition protection

    User defined

    SynRM (reluctance with ACS850 and ACS880 single drive)

    Note that all motors are not available for all drives.

    FrameMaterial Not Specified, Aluminium, Cast iron, Steel. You can limit the motor families.

    Family Limits the search to one family only, such as M3BP.

    Pole number Pole number can beAut omaticor one of the following: 2,4,6,8,10 or 12

    Efficiency Not Specified, IE1, IE2, IE3, IE4. You can limit the motor efficiency class.

    Design Read more about Design from the motor user manuals.

    Connection Currently ignored.

    IP Class IP55, This does not impact the selection

    IC Class IC411 self ventilated= cooling fan on motor shaft; means lower loadability at

    partial speeds

    IC416 forced venti lated= separate cooling fan. Select this option for constant

    torque cases where the minimum speed is very low.

    For large motors there are other selections available.

    Max speed rule Standard= Standard maximum speeds is used.

    Metal fan= The higher speed limit of the metallic fan is used.

    Separate fan= Higher maximum speed is available when force ventilated.

    Temp rise B, Fornot specified. Not specifiedmeans that DriveSize will use the

    temperature class given in motor catalogues.

    Tmax margin 43%, 30% or 20%.Motor catalogues give rough maximum torque values andsome margin has to be provided. The margin from actual overload torque to

  • 8/12/2019 DriveSize Users Manual

    25/59

    25

    Tmax must be 43%, 30% or 20%.

    Motor selection in general and User selection

    DriveSize usually selects the most suitable motor from the technical point of viewconsidering specification. However, sometimes you may want to select another motor. In

    these cases, you can choose an optional motor from the User selection list. Figure 20:User selection view for motorshows the alternative selections.

    Addit ional derating requirements

    Terminal box mounting and possible special winding insulation have an effect on thetemperature rise of the motor. DriveSize does not take these extra deratings into account.It is assumed that standard insulation and a top-mounted terminal box are used. If not,some extra margin must be reserved. The necessity of derating can also be a sum of

    these both items.

    Reinforced insulation

    Reinforced insulation is recommended when motor voltage is higher than 500 V. Aboutthree per cents (3%) additional derating of the continuous loadability curve is required

    when reinforced windings are used. Reserve at least 3% margin in DriveSize for this

    purpose.

    Terminal boxes

    Terminal boxes are mounted either on the top of the motor or on the left or right side.Availability of the terminal box mounting options depends on the type of the motor and

    the motor frame size. Three per cents (3%) additional derating is needed for thecontinuous loadability curve when the terminal box is mounted on the side of the motor oron the ND end of the motor. As standard, terminal boxes are mounted on the top of the

    motor and extra margin is unnecessary. Reserve at least 3% margin in DriveSize for this

    purpose.

    Note: Check the availability of force ventilation and accessories from the motor

    manufacturer.

  • 8/12/2019 DriveSize Users Manual

    26/59

    26 Dimensioning

    Inverter input data

    This section describes how to enter the drive/inverter data. Figure 8: Inverter input data

    shows the inverter input data.

    Entering inverter loadThe load of the inverter consists of the motor currents and frequencies. DriveSize

    calculates the load currents based on the selected motor characteristics (power factor,

    efficiency, pole pairs), shaft loads, shaft speeds and motor voltage.

    You can change the inverter load value by entering new currents. In this case, DriveSize

    uses the currents you have given manually instead of the calculated currents. The rest ofthe data that DriveSize uses in calculation is based on the motor. If you have not selectedthe motor characteristics, DriveSize uses the default values of the software.

    Figure 8: Inverter input data

  • 8/12/2019 DriveSize Users Manual

    27/59

    27

    Table 4: Abbreviations used for inverter load

    Abbreviation Meaning

    I continuous (A) Continuous (base) current required from the

    inverter. If you enter this value manually and if themotor is not known, DriveSize assumes that the

    frequency range is wide.

    I maximum (A) Maximum current required. If you enter this value

    manually and if the motor is not known, DriveSize

    assumes that the frequency range is wide.

    I max start (A) Maximum current at start for the inverter.

    Changing inverter specifications

    You can adjust some specifications for the inverter, such as the inverter amount, type, IPclass and pulse number towards network.

    Table 5: Options for inverter specifications (ACS800 SD)

    Specification Options

    Name Any text or string

    No.of drives Number of parallel connected inverter and motor combinations.

    Type Auto selection includes ACS800 and ACS800 regenerative drives

    for all the constructions but modules and marine. You can limit the

    type with the following options: ACS800, ACS880, ACS800

    regenerative, ACS 800 low harmonic, ACS850, ACS810.

    Construction Wall-mounted only, Free standing only, Cabinet drives only,

    Marine drives only, Drive modules only

    Cooling Air, Liquid.

    Note: Liquid cooling is available only for the Cabinetconstruction.

    IP Class IP00, IP21, IP22, IP42, IP54, IP54R, IP55. Depends on Type and

    Construction specifications.

    Pulse 6 or 12. When the 12-pulse option is selected, the transformer must

    be of a three-winding type.

    Glycol concentration 0%, 30%, 50%. For liquid cooled units only.

    Liquidtemperature

    25C45C. For liquid cooled units only.

    Inverter selection in general and User selection

    DriveSize usually selects the most suitable inverter/drive from the technical point of viewconsidering specification. However, sometimes you may want to select another inverter.

    In these cases, you can choose an optional inverter from the User selection list. Figure

    20: User selection view for motorshows this screen for motors but similar screen isavailable for inverters and drives too.

  • 8/12/2019 DriveSize Users Manual

    28/59

    28 Dimensioning

    Selecting l iquid cooled inverter

    When you select the liquid cooled drive option in the Coolingspecification, two new

    specifications Glycol concentration and Liquid temperature appear. For a multidrive,

    select liquid cooling for the supply unit first. The cooling method of the supply unitdetermines also cooling for all the inverters connected to that line-up.

  • 8/12/2019 DriveSize Users Manual

    29/59

    29

    Line supply unit input data

    This section describes the line supply unit data input (see Figure 9: Line supply unit input

    data)

    Figure 9: Line supply unit input data

    Entering line supply unit load

    If you have selected the inverters, DriveSize calculates the supply unit motoring and

    regeneration powers. Change the power and cycle time values. The view has also fieldsfor regenerative powers when the supply unit type is TSU or ISU.

    Table 6: Abbreviations used to describe the supply unit load

    Abbreviation Meaning

    Pcont (kW) Continuous power for the supply unit.

    Pmax (kW) Maximum power for the supply unit.

    Changing line supply unit specifications

    The default supply unit is a 6-pulse DSU cabinet but other types and pulse numbers andIP classes are available. For the thyristor supply units, two additional parameters are

  • 8/12/2019 DriveSize Users Manual

    30/59

    30 Dimensioning

    available: the braking voltage and motor voltage. These parameters are mutually

    exclusive.

    Selecting liquid cooled supply unit

    When you select the liquid cooled (LC) supply option in the Coolingspecification, two

    new specifications Glycol concentration and Liquid temperature appear. Thesespecifications determine also all the inverters connected to that supply unit. The coolingmethod of line supply unit is valid also for all the inverters connected to that line supplyunit.

    Table 7: Options for Line Supply Unit Specifications

    Specification Options

    Name Any text or number string

    Type DSU cabinet, DSU module, TSU cabinet, TSU module, ISU cabinet, ISU

    module, LC DSU cabinet

    IP Class IP00, IP21, IP22, IP42, IP54

    Cooling Air, Liquid.

    This option determines also the cooling method for all the inverters

    connected to that line-up.

    Pulse 6-pulse, 12-pulse, 18-pulse, 24-pulse (DSU, TSU). When the 12-pulse

    option is selected, the transformer must be of a three-winding type.

    Braking Voltage (%) 85, 90, 100 (TSU)

    A lower braking voltage means that prior to braking, the DC voltage is

    reduced.

    Note:A lower DC voltage means that there is less available motor voltageand therefore the maximum torque a motor produces is also lower. This

    setting has to be understood so that TSU makes a lower than nominal DC

    voltage and the motor voltages are also lower. In this case, TSU can quickly

    change from motoring to regenerating.

    Motor Voltage (V) 380, 400, 415, 500, 525, 660, 690, 830 for 50 Hz and 380, 440, 460, 480,

    575, 600, 660, 690 for 60 Hz.

    Glycol concentration 0%, 30%, 50%. For liquid cooled units only. The supply unit determines also

    glycol concentration for all the inverters connected to that line-up.

    Liquid

    temperature

    25 C 45 C. For liquid cooled units only. The supply unit determines also

    liquid temperature for all the inverters connected to that line-up.

  • 8/12/2019 DriveSize Users Manual

    31/59

  • 8/12/2019 DriveSize Users Manual

    32/59

  • 8/12/2019 DriveSize Users Manual

    33/59

    33

    Automatic t rack

    The program always keeps the dimensioning status valid. If you change some input data,

    which can have effect on the dimensioning of other units, then those dimensions willbecome not valid.

    Table 9: DriveSize dimension updating

    Changed data Dimensioning not valid for

    Motor ambient conditions All motors, inverters and line supply units

    Drive ambient conditions All inverters and line supply units

    Network voltage All motors, inverters and line supply units

    Network frequency All motors, inverters and line supply units

    Supply unit load Only the line supply unit whose load you changed

    Line supply unit type, motor voltage or braking

    voltage

    All motors, inverters and line supply units in that

    line-up

    Line supply unit IP class Only line supply unit whose IP class you changed

    Inverter load Only the inverter and line supply unit where the

    inverter is connected

    Inverter IP class Only that inverter and line supply unit where the

    inverter is connected

    Motor load Only that motor and inverter where the motor is

    connected. Also that line supply unit in that line-up

    Motor number, type, IC class or TempRiseClass Only that motor and inverter where the motor is

    connected. Also that incoming unit in that line-up

    Inserting motor and inverter Only the line-ups line supply unit

    Deleting or pasting motor and inverter Only the line-ups line supply unit

    Dimensioning motor The inverter where the motor is connected. Also

    that line supply unit in that line-up

    Dimensioning inverter Only the line-ups line supply unit

  • 8/12/2019 DriveSize Users Manual

    34/59

    34 Dimensioning

    Opening a saved project

    When you open a previously saved project, a window shows all of the available projects

    in the selected path. When you highlight a file, you can view the project information in the

    Project infofield before opening the project. Figure 11: Opening project viewshows theOpenfile window.

    Figure 11: Opening project view

    Opening a project fi le

    To open a project file, highlight it or type its name in the File Nametext box and click OK.You can also open a project file by double-clicking its name in the file list. By changingthe List of f ile Typesoption, you can open projects which are based on different

    products.

    Changing the Drive or the Director ies path

    To change the DirectoriesorDrivepath, double-click the path in the list on the right

    hand side of the window. If you are using a keyboard, you can press the spacebar tohighlight the path.

  • 8/12/2019 DriveSize Users Manual

    35/59

    35

    Special features

    What this chapter contains

    This chapter describes the special features of DriveSize, such as making more

    sophisticated load definitions. This section also describes how to use special motors andhow to create your motor database.

    Motor load

    Enter the motor load data in the main dimensioning window. If the project is morecomplicated, start from Overload definitions. See

    4

  • 8/12/2019 DriveSize Users Manual

    36/59

  • 8/12/2019 DriveSize Users Manual

    37/59

  • 8/12/2019 DriveSize Users Manual

    38/59

    38 Special features

    Figure 13: Line supply unit load

    DriveSize fills in the time fields with defaults but you must check and, if necessary, modifythe times and power values. DriveSize does not know the mutual timings of differentinverters.

  • 8/12/2019 DriveSize Users Manual

    39/59

    39

    Customer-specific motors

    Some motors are called customer-specific because they are not picked from any list but

    the rated power and frequency are computed from load requirements. When youdimension a customer-specific motor like HXR, AMA or AMI, ABB Sophi automaticallyselects the number of poles and the field weakening point (Fwp frequency). After theautomatic selection you can alter the value of field weakening frequency between the

    given limits. The minimum and maximum limits for field weakening are shown in theselected motor data. Additionally, there is also a value for the recommended maximum(Rec). Before you change the value ofFwp frequency,select the pole number. When

    the value of the pole number is changed, the Fwp frequencyreturns toAutomat ic .Figure 14: Drop-down list of field weakening frequencyshows the drop-down list for acustomer-specific motor.

    ABB Sophi automatically starts when the program cannot find any standard motor andthe Motor typeis Auto selection or if you have selected HXR, AMA & AMI motors as themotor type.

    Figure 14: Drop-down list of field weakening frequency

  • 8/12/2019 DriveSize Users Manual

    40/59

    40 Special features

    Existing motors

    You can define an existing motor in the Existing Motordialog. It automatically opens

    when you select the Existing motor type. Figure 15: Existing Motor dialog boxshows

    the dialog for an existing motor. The loadability curves of the ABB standard motors areused for existing motors. DriveSize assumes that the existing motor is already installed

    and driving the load. The loadability of an existing motor is not checked, but the graphsshow if it is undersized according to the rules for standard motors.

    Figure 15: Existing Motor dialog box

    User motorsYou can make dimensioning for motors from your own motor list. This section describes

    how you can import your own motor database into DriveSize.

    The format of the motor list is an Excel worksheet with specified column headers and one

    row for the information of one motor. The motor list is expected to start on the firstworksheet in the book and the upper right corner is cell A1. Before you can use the motorlist, import it to a UserMotor database in DriveSize. The import is always a full import and

    all previously existing user motors are removed when you import a new list.

    User motors are used independently from supply frequency but the motor voltage mustmatch the supply voltage. The rating value conversion from one voltage to another is not

    done for user motors (You can make the conversion yourself in Excel.) Different voltagesmust have separate rows in the database.

    Creating a user motors fi le

    Enter the motor data and loadability curves in UserMotors.xls. By default, you can findthis file in your working directory in

    C:\\ProgramFiles\DriveWare\DriveSize\VsdSize20\system. You can change the file name

    but not the extension.

  • 8/12/2019 DriveSize Users Manual

    41/59

    41

    Importing from a file

    To import new data to the database, select File -> User motors -> Import from fi le. This

    action overwrites the existing UserMotor database.

    Figure 16: Import Database window

    The import function validates the information in the Excel sheet before updating thedatabase. The validation rules are: Correct column headers

    Correct data types (text, numeric)

    All numeric values must be > 0

    Text values must fit into a maximum length

    The frequency column must be between 8400 (Hz) so that also values other than50 Hz or 60 Hz are accepted.

    The voltage must be known by DriveSize

    In case of import errors, the program tells you which values are not accepted and the

    import is cancelled.

    The import date is stored in the Generaltable and it is visible in theAbout box.

    If there is at least one motor imported to the database, a new item is added to the Motortype list: User definedin the motor specification grid.

    When you select User defined, DriveSize updates the Familylist with all families fromthe Database. The other specification items are: Family: Not specified, + rest of list from the database

    Pole number: Automatic, 2, 4, 6, 8, 10, 12

    Design: Not specified, Basic, High-Output

    Connection: Not specified, Y, D

    IC class: IC411, IC416

    IM class: IM10001,

    Max speed rule: Standard

    Temp r ise: Not specified, B, F

    Motor Tmax Margin: 20%, 30%, 43%

  • 8/12/2019 DriveSize Users Manual

    42/59

  • 8/12/2019 DriveSize Users Manual

    43/59

    43

  • 8/12/2019 DriveSize Users Manual

    44/59

    44 Results

    Results

    What this chapter contains

    This chapter describes how to interpret DriveSizes Resultsshown on screen.

    Dimensioning results

    DriveSize always try to select some unit. The selection may not be optimal but it providesa result quickly. When you change the input data, you get another result. DriveSize

    computes the selections quickly but you make the f inal decision. Figure 17: Main

    dimensioning window shows an example of the motor results.

    Figure 17: Main dimensioning windowYou can read the dimensioning results in the main dimensioning window, but you can findmore detailed information in the dimensioning Resultview where results appearnumerically or in the Graphview where results appear graphically. If you are not satisfied

    with the software dimensioning result, make your own selection. This is possible in theUser Selectionview. All the individual sections dimensioned for the project can be seen

    in the List o f Selectedview.

  • 8/12/2019 DriveSize Users Manual

    45/59

    45

    Result view

    The Resultview shows the results in a numeric form for the item you have highlighted.

    The view is similar for motors, inverters and incoming units. The Specifications datashows the user requirements. The Catalogue datadisplays the unit and selectioncalculations in different points and shows how the unit meets the requirements. TheSelection datahas columns forRequired, Resultand Margin values. The required data

    is calculated from the user load demands. The result data is based on selected unit(motor, drive etc). The margin indicates the percentage of capacity still available(difference between the input requirements and the resulting data of the component).

    Figure 18: Result view for motors

    Table 11: Selection data for motors

    Point Meaning

    Torque (Nm)

    min, base, max

    Calculated torque at the user-defined speed: Minimum, base, maximum speed.

    Power (kW)

    min, base, max

    Calculated power at the user-defined speed: Minimum, base, maximum speed.

    Overload (Nm)

    min, base, max

    Calculated overload torque at the user-defined speed: Minimum, base,

    maximum speed for the user-defined time.

  • 8/12/2019 DriveSize Users Manual

    46/59

    46 Results

    Table 12: Selection data for inverters

    Point Meaning

    Icont (A),

    Imax (A) or

    Imax start (A)

    Calculated current load for an inverter in two situations:

    Continuous load and maximum load for the user-defined time

    Maximum load at start is shown in case the load type is One time at start

    overload

    Temperature Temperature margin in percent for the IGBT module. There is also an

    additional temperature margin for other components like a choke when liquidcooled.

    Table 13: Selection data for diode or thyristor supply units

    Point Meaning

    Power (kW)

    mot cont,

    mot max,

    gen cont,

    gen max

    Calculated power load for an incoming unit for motoring and generating bridgesin two situations:

    Continuous load

    Maximum load for the user-defined time

    DC-current (A)

    cont motoring,

    max motoring,

    cont generating

    max generating

    Calculated DC bus current with minimum voltage and power for motoring and

    generating bridges in two situations:

    Continuous load

    Maximum load for the user-defined time

    Temperature

    mot temp,

    gen temp

    Temperature margin in percent for motoring and generating bridges. There isalso an additional temperature margin for other components like a choke when

    liquid cooled.

    Table 14: Selection data for IGBT supply units

    Point Meaning

    Power (kW)

    mot cont,

    mot max

    Calculated power load for an incoming unit in two situations:

    Continuous load

    Maximum load for the user-defined time

    AC-current (A)

    cont motoring,

    max motoring

    Calculated current with minimum voltage and power:

    Continuous load

    Maximum load for the user-defined time

    Temperature

    mot temp

    Temperature margin in percent for a supply unit. There is also an additional

    temperature margin for other components like an LCL filter when liquid cooled.

    Table 15: Liquid flow sums of line-up (ACS800 LC multidrives)

    Point Meaning

    Total flow (l/min) Calculated total mass flow for this line-up. The liquid flow of line supply unit is

    shown in the catalogue data table of the LSU result sheet.

    Heat loss (kW) Calculated loss power for that line-up.

  • 8/12/2019 DriveSize Users Manual

    47/59

    47

    You can see in the selection data the required load margin for the selected unit. Whenthe margins are positive, the unit meets the requirements.

    Note:A large margin causes over-dimensioning. If the margin is negative, the unit cannot

    meet the requirements. When the motor type is ACS800, where a thermal model is used,the margin of continuous current can be negative when the ambient temperature is below

    40 C.

    Efficiency report

    Click the Efficiency Reportbutton in Motor data view to see the efficiencies and lossesin a printable form (See Figure 18: Result view for motors). This view is available only for

    single drives.

  • 8/12/2019 DriveSize Users Manual

    48/59

    48 Results

    Graph view

    The Graphview helps you to check how well the unit f its the requirements. The graphs

    display load and motor torques, load and motor powers and load and inverter currents.

    Figure 19: Graphs for motorshows the graph for load and motor torques as a function ofspeed.

    Figure 19: Graphs for motor

    In the view, a legend explains the curves. Each curve has its own color.

    Table 16: Curves in the Load / Motor torque graph

    Curve Meaning

    max. loadability Motor maximum capability as a function of speed

    max. load User-defined maximum load (overload)

    cont. loadability Motor continuous loadability thermal limit

    cont. load User-defined continuous load

    Table 17: Curves in the inverter graph

    Curve Meaning

    max. loadability Inverter maximum capability

    max. load User- defined maximum

    cont. loadability Inverter continuous loadability

    cont. load User-defined continuous load

  • 8/12/2019 DriveSize Users Manual

    49/59

    49

    User selection view

    In the User selectionview, you can view and even select a smaller or larger unit instead

    of your current selection (made by the software or by your own previous selection). The

    selected unit has number 0 and its row is highlighted. Smaller units have a negativemark. Larger units have a positive mark. The table includes some catalogue values andcalculated margins to help with the new selection process. In some cases when theoverloads are decisive there are no smaller units in the list.

    Figure 20: User selection view for motorshows the alternative selections. The view isavailable for ABB standard motors, inverters and supply units.

    Figure 20: User selection view for motor

    Table 18: Items in User selection view, motor table

    Item Meaning

    # Identity number

    PU Production unit

    Type designation The motors type designation

    Power (kW) Rated power

    Efficiency class Motor efficiency class

    Poles Pole number

    Speed (rpm) Nominal speed

    In (A) Nominal current

    Tn (Nm) Nominal torque

    Tmax/Tn Maximum torque / Nominal torque

    Tcont margin Calculated continuous load margin. The smallest margin over the complete speed

    range.

    Tmax margin Calculated maximum load margin. The smallest margin over the complete speedrange.

  • 8/12/2019 DriveSize Users Manual

    50/59

    50 Results

    Im (A) Calculated continuous load current

    Immax (A) Calculated maximum load current

    Table 19: Items in the User selection view, inverter table

    Item Meaning

    # Identity number

    Type designation Inverters type designation

    Apparent power (kVA) Inverters apparent power

    Power (kW) Inverters nominal motor power

    Icont (A) Nominal continuous loadability current

    Margin Calculated margin for your continuous load

    Imax (A) Nominal maximum loadability current

    Margin Calculated margin for maximum load

    Select ion method Selection criterion

    Temp. margin Calculated temperature margin

    Table 20: Items in the User selection view, line supply unit table

    Item Meaning

    # Identity number

    Type designation Line supply units type designation

    Apparent power (kVA) Line supply units apparent power

    Power fwd margin Calculated power margin for motoring load. Minimum of continuous and

    maximum load.

    Current fwd margin Calculated current margin for motoring load with required power and minimum

    voltage. Minimum of continuous and maximum load.

    Power rev margin Calculated power margin for generating load. Minimum of continuous and

    maximum load.

    Current rev margin Calculated current margin for generating load with required power and

    minimum voltage. Minimum of continuous and maximum load.

    To select a different unit, click the row in which you wish the unit to be listed. To verify

    your selection, click OK. Your selection is highlighted. If you click Cancel, the selection isdiscarded.

  • 8/12/2019 DriveSize Users Manual

    51/59

    51

    List of selected

    List of selecteddisplays the selected units. The list contains: Type designation, Unit

    name andDimension status. Dimension status shows whether you or the softwaremade the dimensioning. Figure 21: List of selected

    shows an example of this view.

    Figure 21: List of selected

  • 8/12/2019 DriveSize Users Manual

    52/59

    52 Network Check

    Network Check

    What this chapter contains

    This chapter describes how to compute the effects of drives on a network. Harmonics

    calculation is based on discrete Fourier transformation and tabulation.

    Network Check view

    With Network Checkyou can calculate: the network harmonics and power factor for an individual drive

    the network harmonics and power factor for a line supply unit

    combined harmonics for several units.

    Both the voltage and the current harmonics are calculated. DC voltage calculations

    provide DC link voltage. Figure 22: Network Check viewshows an example.

    Tip:Compute the combined harmonics, not harmonics for individual drives because theparallel drives will smoothen and, in some cases, compensate each other. Combine ISUand DSU drives.

    6

  • 8/12/2019 DriveSize Users Manual

    53/59

  • 8/12/2019 DriveSize Users Manual

    54/59

    54 Network Check

    Cable length Length of the cable

    Table 22: Supply Unit items

    Items Meaning

    Lac (H) AC choke inductance

    Ldc (H) DC link inductance

    Cdc (mF) DC link capacitance

    Pdc (kW) DC power; the default value is base power plus the losses in the motor and

    inverter.

    Table 23: Result items

    Items Meaning

    cos 1 Fundamental power factor, main wave power factor

    Tot power factor Calculated total power factor with the harmonics included

    Udc (V) Calculated DC voltage

    Table 24: Harmonic items

    Items Meaning

    Voltage THD (%) Voltage total harmonic distortion

    Current THD (%) Current total harmonic distortion

    N Harmonic order number

    f (Hz) Harmonic frequency

    Current (A) Harmonic current

    In/I1 Harmonic proportional current to base current

    Voltage (V) Harmonic voltage

    Un/U1 Harmonic proportional voltage to base voltage

    Calculating harmonics

    To calculate the harmonics, highlight the transformer and click Network check in the

    toolbar. The Network Check view opens. If necessary, adjust the Pdc and other settings.Click Calculate. If you have not given the network data in the main dimensioning window,fill in the network voltage and frequency with deviations.

    Note: The network data you fill in Network Checkdoes not have effect on the network

    data in the main dimensioning window.

    To view the harmonics output as a table or a graph, select the TableorGraphradiobutton in Show Mode. When you select the graph view, you can choose between thevoltage and current harmonics.

  • 8/12/2019 DriveSize Users Manual

    55/59

  • 8/12/2019 DriveSize Users Manual

    56/59

    56 Printing and saving results with Excel format

    Printing and saving results withExcel format

    What this chapter contains

    This chapter gives information on the printing functions. The printed results are meant tobe used as appendixes for offer or request for offer or just for documentation purposes.

    Instead of printing we encourage you to save the results on Excel format and if you wish,

    convert them into PDF format. This is one way to avoid consumption of printers andpaper.

    Printing the dimensioning results

    You can use the printing functions for two purposes:

    exporting the project information to Excel, which can be used as shopping lists for

    motors and drives. To do this, select Preview. printing on paper. To do this, select Print.

    In the Printdialog, define what information you wish to move to Excel.

    7

  • 8/12/2019 DriveSize Users Manual

    57/59

    57

    DriveSize uses Microsoft Office Excel 97 English version or later for printing. Figure 23:Print dialog shows the Printdialog.

    Figure 23: Print dialog

    Many DriveSize views have a Reportbutton. Click Reportto print the view data in Excel.

    Efficiency Report

    Click the Efficiency Reportbutton in Motor dataview to see the efficiencies and lossesin a printable form. Note that printAll Data Sheetsdoes not contain the Efficiency Reportsheet. This sheet is available for single drives.

    Network check report

    Click the Reportbutton in the Network Checkview to see the printable result sheet ofthe harmonics.

  • 8/12/2019 DriveSize Users Manual

    58/59

    58 Printing and saving results with Excel format

    Further information

    Product and service inquiries

    Address any inquiries about the product to your local ABB representative, quoting thetype designation and serial number of the unit in question. A listing of ABB sales, supportand service contacts can be found by navigating to www.abb.com/drivesand selecting

    Sales, Support and Service network.

    Product training

    For information on ABB product training, navigate to www.abb.com/drivesand selectTraining courses.

    Providing feedback on ABB Drives manuals

    Your comments on our manuals are welcome. Go to www.abb.com/drivesand selectDocument Library Manuals feedback form (LV AC drives).

    Document library on the Internet

    You can find manuals and other product documents in PDF format on the Internet. Go towww.abb.com/drivesand select Document Library. You can browse the library or enterselection criteria, for example a document code, in the search field.

  • 8/12/2019 DriveSize Users Manual

    59/59