0.1 Details & Drawings DWG. # PROJ. # DWN. SCALE DATE CH'D. #301D - 30721 Simpson Road, Abbotsford, BC PH. 604-575-8220 www.apexbuildingsciences.com Apex SEAL 5653 SK 3" = 1'-0" Mar. 14 / 2017 BC Victoria Community Hall 2026 E 43rd Avenue, Vancouver, BC DRAWINGS & DETAILS Issued for Tender

DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

0.1

Details & DrawingsDWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

DRAWINGS&

DETAILS

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

NEW ASPHALT SHINGLES

NEW ROOFING UNDERLAYMENT PER

VBBL; LAP MIN. 12" OVER ICE & WATER

PROTECTION MEMBRANE

NEW ICE & EAVE

PROTECTION MEMBRANE

M

I

N

.

1

1

/

2

"

NEW 26 Ga. PRE - FINISHED

METAL DRIP EDGE FLASHING;

MIN. 4" UP ROOF SHEATHING

NEW ICE & WATER

PROTECTION STARTER

STRIP BELOW METAL

FLASHING

NEW GUTTERS

& DOWNSPOUT

EXISTING

WOOD FASCIA

- PAINT

EXISTING SIDING (STUCCO)

EXISTING SHEATHING

MEMBRANE

W1

NEW ICE & WATER PROTECTION MEMBRANE;

MEMBRANE MIN. 12" UP ROOF FROM THE

INSIDE FACE OF THE EXTERIOR WALL

E

X

I

S

T

I

N

G

R

O

O

F

R

A

F

T

E

R

NOTES:

1. INSTALL NEW ICE AND WATER SHIELD MEMBRANE AT ALL EAVES AS PER RCABC STANDARDS.

2. ALL EAVES MUST HAVE SOLID DECKING TO RECEIVE NEW ICE & WATER SHIELD MEMBRANE. IF SOLID

DECKING IS MISSING AT EAVES THEN INSTALL NEW WOOD DECKING; SIZE TO MATCH EXISTING.

SLOPED ROOF

Sloped Roof Eave

EXISTING ROOF DECKING /

SHEATHING

SLOPED ROOF

2"

NEW ASPHALT SHINGLES

NEW 26 Ga. PRE-FINISHED METAL FLASHING;

MIN. 6" VERTICAL AND SLOPED LEGS

MIN

. 4"

M

I

N

.

6

"

RO

OF

IN

G U

ND

ER

LA

YM

EN

T M

IN

. 8" U

P W

ALL

Sloped Roof at Dormer

- Head Wall

~

EXISTING ROOF DECKING /

SHEATHING

R1

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

LAP & SEAL NEW AIR BARRIER SHEATHING

MEMBRANE OVER NEW ROOFING

UNDERLAYMENT

NEW FIBER CEMENT PANEL SIDING; COLOUR &

PROFILE TO MATCH EXIST. STUCCO CLADDING

NEW ROOFING UNDERLAYMENT;

MIN. 8" UP WALL SHEATHING

W2

NEW 1/2" X 2" PRESSURE TREATED PLYWOOD

STRAPPING AT 8" o.c.

~

1

HATCHED AREA TO

BE CUT OUT

TRIM

2

0

°

KICK-OUT MUST BE

20-DEGREE ANGLE TO

THE VERTICAL SLOPE

2

FOLD LAYOUT

3

BREADPANNED CORNER FOLD

DOTTED AREA

SHOWS THE FOLD

LAYOUT

FOLD UP MUST BE EQUAL IN

HEIGHT TO THE UPSTAND OF

THE FLASHING

4

HIDDEN SEAM

BREADPAN FOLD TO

BE TURN BEHIND THE

UPSTAND

5

ANGLE TRIM

KICK-OUT CAN BE ANGLE

TRIMMED AND A DRIP EDGE

FORMED AT THE OUTLET

NOTES:

1. PREPARE MOCK-UP FOR CONSULTANT'S

APPROVAL.

2. FLASHING DIMENSIONS ARE SUBJECT

TO VERIFICATION OF SPECIFIC SITE

CONDITIONS.

6

"

6"

Roof Diverter Flashing - Fabrication

Sequence

2.1

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

Issued for Tender

Page 2: DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

EXISTING ROOF

& EAVE FRAMING

EXISTING

INSULATION

~

1.1

INSTALL NEW ICE AND WATER SHIELD MEMBRANE AT ALL EAVES AS PER RCABC STANDARDS.

ALL EAVES MUST HAVE SOLID DECKING TO RECEIVE NEW ICE & WATER SHIELD MEMBRANE. IF SOLID

DECKING IS MISSING AT EAVES THEN INSTALL NEW WOOD DECKING; SIZE TO MATCH EXISTING.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

EXISTING ROOF

DECKING /

SHEATHING

NEW ROOFING

UNDERLAYMENT

NOTE:-

1. INSTALL NEW ICE AND WATER SHIELD ON ALL EAVES, GABLES AND VALLEYS AS PER RCABC STANDARDS.

NEW ASPHALT

SHINGLE

R1

MIN

. 8"

SLOPED ROOF

TOP OF ROOF

1.10

NEW FIBER CEMENT PANEL; COLOUR & PROFILE TO

MATCH EXIST. STUCCO CLADDING

Sloped Roof at Dormer

- Side Wall

NEW PRE-FINISHED 26 Ga. MIN. 6" X 6" METAL

STEP FLASHING

NEW ASPHALT SHINGLES

NEW ROOFING FELT; MIN. 8" UP WALL

LAP & SEAL NEW AIR BARRIER SHEATHING MEMBRANE

OVER NEW ROOFING UNDERLAYMENT

2"

SLOPED ROOF

NOTE:

1. IF EXISTING SHEATHING MEMBRANE IS DAMAGED AND / OR DETERIORATED; REPLACE IT WITH NEW

SHEATHING MEMBRANE.

EXISTING ROOF DECKING

/ SHEATHING

W2

NEW 1/2" X 2" PRESSURE TREATED PLYWOOD

STRAPPING AT 8" o.c.

~

3

FASCIA

(IF APPLICABLE)

DIVERTER

FLASHING AT

FASCIA EDGE

AS SHOWN -

SEE NOTE 1

~

R

O

O

F

S

L

O

P

E

ROOFING FELT

~

R

O

O

F

S

L

O

P

E

R

O

O

F

S

L

O

P

E

CLADDING

NOTES:

1. A DIVERTER FLASHING IS INSTALLED AS

THE FIRST PIECE OF FLASHING AT THE

END OF THE ROOF WHERE IT INTERSECTS

THE WALL. DIVERTER FLASHING OUTLET

TO EXTEND A MIN. 1" LOWER THAN THE

EDGE OF ROOF MATERIAL AND LEAD

WATER INTO THE GUTTER.

2. THIS DETAIL SHOWS THE INSTALLATION

OF THE DIVERTER AND STEP FLASHING.

THE PURPOSE OF THE STEP FLASHING

AND DIVERTER IS TO SHED THE WATER

OFF THE ROOF AND KEEP IT AWAY FROM

THE VERTICAL WALL BENEATH.

3. ALL JOINTS MUST BE FOLDED.

SOLDERING IS ALLOWED.

URETHANE SEALANT - BETWEEN

CLADDING & FLASHING AND

FASCIA & CLADDING

1

2

Roof Diverter Flashing - Installation

Sequence

NEW ASPHALT

SHINGLES

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

0.2

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

ROOFS

1.1 Sloped Roof Eave

1.2 Sloped Roof Gable

1.3 Ridge Vent Detail

1.4 Roof Penetration

1.5 Sloped Roof at Chimney - Side

1.6 Cricket at Chimney

1.7 Chimney at Sloped Roof - 3D View

1.8 Roof Overhang at Exterior Wall

1.9 Sloped Roof at Dormer - Head Wall

1.10 Sloped Roof at Dormer - Side Wall

1.11 Valley Detail

FLASHINGS

2.1 Roof Diverter - Fabrication Sequence

2.2 Roof Diverter - Installation Sequence

B. DETAILS

GENERAL

0.1 Details & Drawings

0.2 Drawing Index

0.3 Construction Assemblies

A. DRAWINGS

1 of 2 Site Plan

2 of 2 Roof Plan

Drawing & Detail Index

R1

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

Issued for Tender

Page 3: DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

0.3

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

EXTERIOR WALL TYPES

EXISTING EXTERIOR WALL

EXISTING SIDING (STUCCO)

EXISTING SHEATHING PAPER

EXISTING SHEATHING

EXISTING STUDS

EXISTING INSULATION

EXISTING POLY. VAPOUR BARRIER

EXISTING INTERIOR FINISH

W1

Construction Assemblies - 1 of 1

R1

NEW FIBRE GLASS LAMINATED ROOF SHINGLES - PER

CURRENT VBBL

NEW ROOFING UNDERLAYMENT - PER CURRENT VBBL

EXISTING ROOF DECKING / SHEATHING

EXISTING ROOF FRAMING

EXISTING INSULATION

EXISTING VAPOUR BARRIER

EXISTING INTERIOR FINISH

NOTE:- INSTALL ICE & EAVE PROTECTION MEMBRANE

PER DETAILS & RCABC STANDARDS

SLOPED ROOF (MAIN)

EXISTING EXTERIOR WALL - NEW FIBER CEMENT PANEL SIDING

NEW FIBER CEMENT PANEL SIDING

NEW 1/2" X 2" EXTERIOR GRADE PLYWOOD STRAPPING AT 8" O.C.

NEW SHEATHING MEMBRANE (TYVEK COMMERCIAL OR PRE -

APPROVED EQUAL)

EXISTING SHEATHING

EXISTING STUDS

EXISTING INSULATION

EXISTING POLY. VAPOUR BARRIER

EXISTING INTERIOR FINISH

W2

ROOF TYPES

R2

NEW FIBRE GLASS LAMINATED ROOF SHINGLES - PER

CURRENT VBBL

NEW ROOFING UNDERLAYMENT - PER CURRENT VBBL

EXISTING ROOF DECKING / SHEATHING

EXISTING ROOF FRAMING

SLOPED ROOF (OVERHANG)

Ridge Vent Detail

SLOPED

ROOF

1.3

DIMENSION OF GAP IN

SHEATHING AS PER RIDGE VENT

MANUFACTURER'S

RECOMMENDATIONS

NEW RIDGE CAP

ASPHALT SHINGLES

NEW CONTINUOUS RIDGE

VENT - SEE NOTE 1 & 2

CREATE SPACE IN EXIST. ROOF

DECKING / SHEATHING AT RIDGE

FOR REQUIRED VENTILATION

1. CONTINUOUS RIDGE VENT TO BE USED ON ALL SLOPED ROOFS, WHERE POSSIBLE.

2. INSTALLATION OF RIDGE VENT IS TO BE PER MANUFACTURER'S WRITTEN INSTRUCTIONS.

EXIST. ROOF DECKING /

SHEATHING

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

SEAL

5513

SK

Nov. 4/ 2014

BC

The Fairmont

19528 Fraser Highway, Surrey, BC

3" = 1'-0"

Issued for Tender

Page 4: DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

M

I

N

.

1

2

"

NEW ASPHALT SHINGLES

NEW ROOFING UNDERLAYMENT PER

VBBL; LAP MIN. 12" OVER ICE & WATER

PROTECTION MEMBRANE

NEW ICE & EAVE

PROTECTION MEMBRANE

M

I

N

.

1

1

/

2

"

NEW 26 Ga. PRE - FINISHED

METAL DRIP EDGE FLASHING;

MIN. 4" UP ROOF SHEATHING

NEW ICE & WATER

PROTECTION STARTER

STRIP BELOW METAL

FLASHING

NEW GUTTERS

& DOWNSPOUT

EXISTING

WOOD FASCIA

- PAINT

EXISTING SIDING (STUCCO)

EXISTING SHEATHING

MEMBRANE

W1

EXISTING ROOF

& EAVE FRAMING

EXISTING

INSULATION

~

1.1

12"

NEW ICE & WATER PROTECTION MEMBRANE;

MEMBRANE MIN. 12" UP ROOF FROM THE

INSIDE FACE OF THE EXTERIOR WALL

E

X

I

S

T

I

N

G

R

O

O

F

R

A

F

T

E

R

NOTES:

1. INSTALL NEW ICE AND WATER SHIELD MEMBRANE AT ALL EAVES AS PER RCABC STANDARDS.

2. ALL EAVES MUST HAVE SOLID DECKING TO RECEIVE NEW ICE & WATER SHIELD MEMBRANE. IF SOLID

DECKING IS MISSING AT EAVES THEN INSTALL NEW WOOD DECKING; SIZE TO MATCH EXISTING.

R1

SLOPED ROOF

Sloped Roof Eave

EXISTING ROOF DECKING /

SHEATHING

SLOPED ROOF

2"

NEW ASPHALT SHINGLES

NEW 26 Ga. PRE-FINISHED METAL FLASHING;

MIN. 6" VERTICAL AND SLOPED LEGS

MIN

. 4

"

M

I

N

.

6

"

RO

OF

IN

G U

ND

ER

LA

YM

EN

T M

IN

. 8

" U

P W

AL

L

Sloped Roof at Dormer

- Head Wall

~

EXISTING ROOF DECKING /

SHEATHING

R1

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

1.9

LAP & SEAL NEW AIR BARRIER SHEATHING

MEMBRANE OVER NEW ROOFING

UNDERLAYMENT

NEW FIBER CEMENT PANEL SIDING; COLOUR &

PROFILE TO MATCH EXIST. STUCCO CLADDING

NEW ROOFING UNDERLAYMENT;

MIN. 8" UP WALL SHEATHING

W2

MIN

. 8

"

SLOPED ROOF

NEW FIBER CEMENT PANEL; COLOUR & PROFILE TO

MATCH EXIST. STUCCO CLADDING

Sloped Roof at Dormer

- Side Wall

NEW PRE-FINISHED 26 Ga. MIN. 6" X 6" METAL

STEP FLASHING

NEW ASPHALT SHINGLES

NEW ROOFING FELT; MIN. 8" UP WALL

LAP & SEAL NEW AIR BARRIER SHEATHING MEMBRANE

OVER NEW ROOFING UNDERLAYMENT

2"

SLOPED ROOF

NOTE:

1. IF EXISTING SHEATHING MEMBRANE IS DAMAGED AND / OR DETERIORATED; REPLACE IT WITH NEW

SHEATHING MEMBRANE.

W2

NEW 1/2" X 2" PRESSURE TREATED PLYWOOD

STRAPPING AT 8" o.c.

NEW 1/2" X 2" PRESSURE TREATED PLYWOOD

STRAPPING AT 8" o.c.

~

~

1

HATCHED AREA TO

BE CUT OUT

TRIM

2

0

°

KICK-OUT MUST BE

20-DEGREE ANGLE TO

THE VERTICAL SLOPE

2

FOLD LAYOUT

3

BREADPANNED CORNER FOLD

DOTTED AREA

SHOWS THE FOLD

LAYOUT

FOLD UP MUST BE EQUAL IN

HEIGHT TO THE UPSTAND OF

THE FLASHING

4

HIDDEN SEAM

BREADPAN FOLD TO

BE TURN BEHIND THE

UPSTAND

5

ANGLE TRIM

KICK-OUT CAN BE ANGLE

TRIMMED AND A DRIP EDGE

FORMED AT THE OUTLET

NOTES:

1. PREPARE MOCK-UP FOR CONSULTANT'S

APPROVAL.

2. FLASHING DIMENSIONS ARE SUBJECT

TO VERIFICATION OF SPECIFIC SITE

CONDITIONS.

6

"

6"

Roof Diverter Flashing - Fabrication

Sequence

FASCIA

(IF APPLICABLE)

DIVERTER

FLASHING AT

FASCIA EDGE

AS SHOWN -

SEE NOTE 1

R

O

O

F

S

L

O

P

E

CLADDING

URETHANE SEALANT - BETWEEN

CLADDING & FLASHING

FASCIA & CLADDING

1

Roof Diverter Flashing - Installation

2.1

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

R1

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

Issued for Tender

Page 5: DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

1.2

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

SLOPED

ROOF

EXISTING SIDING (STUCCO)

MIN. 1 1/2"

EXISTING ROOF

DECKING /

SHEATHING

EXISTING SHEATHING MEMBRANE

NEW ROOFING

UNDERLAYMENT

NOTE:-

1. INSTALL NEW ICE AND WATER SHIELD ON ALL EAVES, GABLES AND VALLEYS AS PER RCABC STANDARDS.

Sloped Roof Gable

NEW ASPHALT

SHINGLE

R1

EXISTING WOOD FASCIA - PAINT

TOP OF ROOF

1.10

NEW FIBER CEMENT PANEL; COLOUR & PROFILE TO

NEW PRE-FINISHED 26 Ga. MIN. 6" X 6" METAL

NEW ROOFING FELT; MIN. 8" UP WALL

LAP & SEAL NEW AIR BARRIER SHEATHING MEMBRANE

1. IF EXISTING SHEATHING MEMBRANE IS DAMAGED AND / OR DETERIORATED; REPLACE IT WITH NEW

EXISTING ROOF DECKING

/ SHEATHING

NEW 1/2" X 2" PRESSURE TREATED PLYWOOD

R

O

O

F

S

L

O

P

E

ROOFING FELT

~

STEP FLASHING

EXTENDS UP

AT LEAST 6"

R

O

O

F

S

L

O

P

E

NOTES:

1. A DIVERTER FLASHING IS INSTALLED AS

THE FIRST PIECE OF FLASHING AT THE

END OF THE ROOF WHERE IT INTERSECTS

THE WALL. DIVERTER FLASHING OUTLET

TO EXTEND A MIN. 1" LOWER THAN THE

EDGE OF ROOF MATERIAL AND LEAD

WATER INTO THE GUTTER.

2. THIS DETAIL SHOWS THE INSTALLATION

OF THE DIVERTER AND STEP FLASHING.

THE PURPOSE OF THE STEP FLASHING

AND DIVERTER IS TO SHED THE WATER

OFF THE ROOF AND KEEP IT AWAY FROM

THE VERTICAL WALL BENEATH.

3. ALL JOINTS MUST BE FOLDED. NO

SOLDERING IS ALLOWED.

Roof Diverter Flashing - Installation

2.2

NEW ASPHALT

SHINGLES

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

Valey Detail

NEW 26 Ga. METAL VALLEY

FLASHING; MIN. 12" UP ROOF

SHEATHING EACH SIDE

M

I

N

.

2

4

"

M

I

N

.

1

2

"M

I

N

.

1

2

"

M

I

N

.

2

4

"

SLOPED ROOF

SLOPED ROOF

NEW ICE & EAVE PROTECTION MEMBRANE PER

BC BUILDING CODE 2012; MEMBRANE MIN. 24"

UP ROOF SHEATHING EACH SIDE

M

I

N

.

2

"

NEW ASPHALT SHINGLES

NEW ROOFING FELT LAPS OVER ICE & EAVE

PROTECTION MEMBRANE & METAL FLASHING

EXISTING ROOF DECKING / SHEATHING

R1

DWG. #

SEAL

5653

3" = 1'-0"

Mar. 14 / 2017

BC

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

Issued for Tender

Page 6: DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

Ridge Vent Detail

SLOPED

ROOF

1.3

DIMENSION OF GAP IN

SHEATHING AS PER RIDGE VENT

MANUFACTURER'S

RECOMMENDATIONS

NEW RIDGE CAP

ASPHALT SHINGLES

NEW CONTINUOUS RIDGE

VENT - SEE NOTE 1 & 2

NEW ASPHALT

SHINGLE

NEW ROOFING

FELT

CREATE SPACE IN EXIST. ROOF

DECKING / SHEATHING AT RIDGE

FOR REQUIRED VENTILATION

THROUGH RIDGE VENT

NOTES:

1. CONTINUOUS RIDGE VENT TO BE USED ON ALL SLOPED ROOFS, WHERE POSSIBLE.

2. INSTALLATION OF RIDGE VENT IS TO BE PER MANUFACTURER'S WRITTEN INSTRUCTIONS.

EXIST. ROOF DECKING /

SHEATHING

1.11

NEW ICE & EAVE PROTECTION MEMBRANE PER

BC BUILDING CODE 2012; MEMBRANE MIN. 24"

NEW ROOFING FELT LAPS OVER ICE & EAVE

PROTECTION MEMBRANE & METAL FLASHING

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

Issued for Tender

Page 7: DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

1.4

Roof Penetration

ROOFING UNDERLAYMENT

STARTER STRIP

ROOFING UNDERLAYMENT

LAPS OVER ROOF

PENETRATION FLANGE &

ROOFING UNDERLAYMENT

STARTER STRIP

EXISTING ROOF

DECKING / SHEATHING

NEW ASPHALT SHINGLES

NEW ROOFING

UNDERLAYMENT

EXISTING ROOF

PENETRATION

NEW ROOF PENETRATION

FLASHING (WITH GOOSE

NECK) - PROFILE MAY VARY

R1

R1

SLOPED ROOF

SLOPED ROOF

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

1"

Issued for Tender

Page 8: DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

1.5

Sloped Roof at Chimney - SideDWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

SEALANT; MIN. 6% SLOPE

MIN

. 8"

EXISTING ROOF DECKING /

SHEATHING

NEW ROOFING UNDERLAYMENT;

MIN. 8" UP BRICK WALL

NEW ASPHALT SHINGLES

NEW 26 Ga. PRE-FINISHED METAL CAP

FLASHING OVERLAPPING ROOFING

UNDERLAYMENT & STEP FLASHING

NEW 6" x 6" - 26 Ga. METAL

STEP FLASHING

1"

2" C

LE

AR 6"

3"

6"

CHIMNEY

ENCLOSURE

CUT A REGLET 3/4" X 3/4" TO

ACCOMMODATE THE INSTALLATION

OF METAL FLASHING

6%

EXISTING BRICK CLADDING AT

CHIMNEY WALL

R1

Issued for Tender

Page 9: DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

1.6

Cricket at Chimney

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

CONTINUOUS SEALANT

MIN

. 8"EXISTING ROOF DECKING

/ SHEATHING

NEW ROOFING UNDERLAYMENT;

MIN. 8" UP BRICK WALL

NEW ASPHALT SHINGLES

NEW 26 Ga. PRE-FINISHED METAL

FLASHING OVERLAPPING ROOFING

UNDERLAYMENT & METAL FLASHING

NEW 26 Ga. PRE-FINISHEDE

METAL (SADDLE) FLASHING

1"

2" C

LE

AR

6"

3"

CHIMNEY

ENCLOSURE

CUT A REGLET 3/4" X 3/4" TO ACCOMMODATE

THE INSTALLATION OF METAL FLASHING

6%

EXISTING BRICK CLADDING AT CHIMNEY WALL

~

NEW CRICKET (SADDLE)

FRAMING NOTE:- BUILD

UP TO MIN. 6" PAST

CHIMNEY ENCLOSURE

BOTH SIDES

R1

Issued for Tender

Page 10: DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

1.7

Chimney at Sloped Roof - 3D View

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

EXISTING BRICK

CLADDING

NEW 26 Ga. PRE -

FINISHED METAL

CAP FLASHING

OVERLAPPING

ROOFING

UNDERLAYMENT &

METAL FLASHING

NEW 26 Ga. PRE -

FINISHED METAL

BASE LASHING

OVERLAPPING

ASPHALT SHINGLE

NEW ASPHALT

SHINGLES

NEW ROOFING

UNDERLAYMENT

EXISTING ROOF

DECKING /

SHEATHING

NEW 26 Ga.

PRE-FINISHED METAL

BASE FLASHING

NEW 26 Ga.

PRE-FINISHED

METAL CAP

FLASHING

NEW 26 Ga.

PRE-FINISHED METAL

SIDE FLASHING

NEW 6" x 6" - 26

Ga. METAL STEP

FLASHING

NEW 26 Ga.

METAL BACK CAP

FLASHING

NEW 26 Ga.

METAL (SADDLE)

FLASHING

NEW ASPHALT

SHINGLES

3/4" X 3/4" REGLET

CONTINUOUS

SEALANT

Issued for Tender

Page 11: DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

2"

ASPHALT SHINGLE ROOFING

NEW 26 Ga. PRE-FINISHED METAL FLASHING;

MIN. 6" VERTICAL AND SLOPED LEGS

MIN

. 4"

6

"

M

I

N

.

RO

OF

IN

G U

ND

ER

LA

YM

EN

T M

IN

. 8" U

P W

ALL

Roof Overhang at Exterior Wall

~

EXISTING ROOF DECKING /

SHEATHING

R2

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

1.8

NOTE:

1. IF EXISTING SHEATHING PAPER IS DAMAGED OR DETERIORATED, REPLACE WITH NEW

SHEATHING MEMBRANE.

NEW ROOFING UNDERLAYMENT;

MIN. 8" UP WALL

CUT

LINE

MIN

. 1"

SAW CUT EXIST. STUCCO CLADDING, WIRE MESH,

ETC. MIN. 10" UP VERTICAL WALLS

EXISTING CLADDING (STUCCO)

NEW 3/8" ROD AND CAULK

NEW PRE-FINISHED 26 Ga. METAL

FLASHING - SEE DETAIL 'A'

SAVE EXISTING SHEATHING MEMBRANE MIN. 6";

LAP & SEAL EXIST. SHEATHING MEMBRANE OVER

NEW ROOFING FELT- SEE NOTE 1

NEW BUG SCREEN

NEW FIBER CEMENT PLANK; 7 1/4" WIDTH; COLOUR &

PROFILE TO MATCH EXIST. STUCCO CLADDING

NEW 1/2" X 2" PRESSURE TREATED PLYWOOD

STRAPPING AT 8" o.c.

~

W1

W1

SIM.

Issued for Tender

Page 12: DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

SLOPED ROOF

2"

NEW ASPHALT SHINGLES

NEW 26 Ga. PRE-FINISHED METAL FLASHING;

MIN. 6" VERTICAL AND SLOPED LEGS

MIN

. 4"

M

I

N

.

6

"

RO

OF

IN

G U

ND

ER

LA

YM

EN

T M

IN

. 8" U

P W

ALL

Sloped Roof at Dormer

- Head Wall

~

EXISTING ROOF DECKING /

SHEATHING

R1

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

1.9

LAP & SEAL NEW AIR BARRIER SHEATHING

MEMBRANE OVER NEW ROOFING

UNDERLAYMENT

NEW FIBER CEMENT PANEL SIDING; COLOUR &

PROFILE TO MATCH EXIST. STUCCO CLADDING

NEW ROOFING UNDERLAYMENT;

MIN. 8" UP WALL SHEATHING

W2

NEW 1/2" X 2" PRESSURE TREATED PLYWOOD

STRAPPING AT 8" o.c.

~

1

HATCHED AREA TO

BE CUT OUT

TRIM

2

0

°

KICK-OUT MUST BE

20-DEGREE ANGLE TO

THE VERTICAL SLOPE

2

FOLD LAYOUT

3

BREADPANNED CORNER FOLD

DOTTED AREA

SHOWS THE FOLD

LAYOUT

FOLD UP MUST BE EQUAL IN

HEIGHT TO THE UPSTAND OF

THE FLASHING

4

HIDDEN SEAM

BREADPAN FOLD TO

BE TURN BEHIND THE

UPSTAND

5

ANGLE TRIM

KICK-OUT CAN BE ANGLE

TRIMMED AND A DRIP EDGE

FORMED AT THE OUTLET

NOTES:

1. PREPARE MOCK-UP FOR CONSULTANT'S

APPROVAL.

2. FLASHING DIMENSIONS ARE SUBJECT

TO VERIFICATION OF SPECIFIC SITE

CONDITIONS.

6

"

6"

Roof Diverter Flashing - Fabrication

Sequence

2.1

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

Issued for Tender

Page 13: DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

MIN

. 8"

SLOPED ROOF

TOP OF ROOF

1.10

NEW FIBER CEMENT PANEL; COLOUR & PROFILE TO

MATCH EXIST. STUCCO CLADDING

Sloped Roof at Dormer

- Side Wall

NEW PRE-FINISHED 26 Ga. MIN. 6" X 6" METAL

STEP FLASHING

NEW ASPHALT SHINGLES

NEW ROOFING FELT; MIN. 8" UP WALL

LAP & SEAL NEW AIR BARRIER SHEATHING MEMBRANE

OVER NEW ROOFING UNDERLAYMENT

2"

SLOPED ROOF

NOTE:

1. IF EXISTING SHEATHING MEMBRANE IS DAMAGED AND / OR DETERIORATED; REPLACE IT WITH NEW

SHEATHING MEMBRANE.

EXISTING ROOF DECKING

/ SHEATHING

W2

NEW 1/2" X 2" PRESSURE TREATED PLYWOOD

STRAPPING AT 8" o.c.

~

3

FASCIA

(IF APPLICABLE)

DIVERTER

FLASHING AT

FASCIA EDGE

AS SHOWN -

SEE NOTE 1

~

R

O

O

F

S

L

O

P

E

ROOFING FELT

~

R

O

O

F

S

L

O

P

E

CLADDING

NOTES:

1. A DIVERTER FLASHING IS INSTALLED AS

THE FIRST PIECE OF FLASHING AT THE

END OF THE ROOF WHERE IT INTERSECTS

THE WALL. DIVERTER FLASHING OUTLET

TO EXTEND A MIN. 1" LOWER THAN THE

EDGE OF ROOF MATERIAL AND LEAD

WATER INTO THE GUTTER.

2. THIS DETAIL SHOWS THE INSTALLATION

OF THE DIVERTER AND STEP FLASHING.

THE PURPOSE OF THE STEP FLASHING

AND DIVERTER IS TO SHED THE WATER

OFF THE ROOF AND KEEP IT AWAY FROM

THE VERTICAL WALL BENEATH.

3. ALL JOINTS MUST BE FOLDED.

SOLDERING IS ALLOWED.

URETHANE SEALANT - BETWEEN

CLADDING & FLASHING AND

FASCIA & CLADDING

1

2

Roof Diverter Flashing - Installation

Sequence

NEW ASPHALT

SHINGLES

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

Mar. 14 / 2017

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

R1

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

Issued for Tender

Page 14: DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

STEP FLASHING

EXTENDS UP

AT LEAST 6"

1. A DIVERTER FLASHING IS INSTALLED AS

THE FIRST PIECE OF FLASHING AT THE

END OF THE ROOF WHERE IT INTERSECTS

THE WALL. DIVERTER FLASHING OUTLET

TO EXTEND A MIN. 1" LOWER THAN THE

EDGE OF ROOF MATERIAL AND LEAD

2. THIS DETAIL SHOWS THE INSTALLATION

OF THE DIVERTER AND STEP FLASHING.

THE PURPOSE OF THE STEP FLASHING

AND DIVERTER IS TO SHED THE WATER

OFF THE ROOF AND KEEP IT AWAY FROM

2.2

1.11

Valey Detail

NEW 26 Ga. METAL VALLEY

FLASHING; MIN. 12" UP ROOF

SHEATHING EACH SIDE

M

I

N

.

2

4

"

M

I

N

.

1

2

"M

I

N

.

1

2

"

M

I

N

.

2

4

"

SLOPED ROOF

SLOPED ROOF

NEW ICE & EAVE PROTECTION MEMBRANE PER

BC BUILDING CODE 2012; MEMBRANE MIN. 24"

UP ROOF SHEATHING EACH SIDE

M

I

N

.

2

"

NEW ASPHALT SHINGLES

NEW ROOFING FELT LAPS OVER ICE & EAVE

PROTECTION MEMBRANE & METAL FLASHING

EXISTING ROOF DECKING / SHEATHING

R1

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

Issued for Tender

Page 15: DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

1

HATCHED AREA TO

BE CUT OUT

TRIM

2

0

°

KICK-OUT MUST BE

20-DEGREE ANGLE TO

THE VERTICAL SLOPE

2

FOLD LAYOUT

3

BREADPANNED CORNER FOLD

DOTTED AREA

SHOWS THE FOLD

LAYOUT

FOLD UP MUST BE EQUAL IN

HEIGHT TO THE UPSTAND OF

THE FLASHING

4

HIDDEN SEAM

BREADPAN FOLD TO

BE TURN BEHIND THE

UPSTAND

5

ANGLE TRIM

KICK-OUT CAN BE ANGLE

TRIMMED AND A DRIP EDGE

FORMED AT THE OUTLET

NOTES:

1. PREPARE MOCK-UP FOR CONSULTANT'S

APPROVAL.

2. FLASHING DIMENSIONS ARE SUBJECT

TO VERIFICATION OF SPECIFIC SITE

CONDITIONS.

6

"

6"

Roof Diverter Flashing - Fabrication

Sequence

2.1

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

Issued for Tender

Page 16: DRAWINGS DETAILS - Vancouver · ROOFING UNDERLAYMENT MIN. 8" UP WALL MIN. 6" Sloped Roof at Dormer - Head Wall ~ EXISTING ROOF DECKING / SHEATHING R1 DWG. # PROJ. # DWN. SCALE DATE

3

FASCIA

(IF APPLICABLE)

DIVERTER

FLASHING AT

FASCIA EDGE

AS SHOWN -

SEE NOTE 1

~

R

O

O

F

S

L

O

P

E

ROOFING FELT

~

STEP FLASHING

EXTENDS UP

AT LEAST 6"

R

O

O

F

S

L

O

P

E

R

O

O

F

S

L

O

P

E

CLADDING

NOTES:

1. A DIVERTER FLASHING IS INSTALLED AS

THE FIRST PIECE OF FLASHING AT THE

END OF THE ROOF WHERE IT INTERSECTS

THE WALL. DIVERTER FLASHING OUTLET

TO EXTEND A MIN. 1" LOWER THAN THE

EDGE OF ROOF MATERIAL AND LEAD

WATER INTO THE GUTTER.

2. THIS DETAIL SHOWS THE INSTALLATION

OF THE DIVERTER AND STEP FLASHING.

THE PURPOSE OF THE STEP FLASHING

AND DIVERTER IS TO SHED THE WATER

OFF THE ROOF AND KEEP IT AWAY FROM

THE VERTICAL WALL BENEATH.

3. ALL JOINTS MUST BE FOLDED. NO

SOLDERING IS ALLOWED.

URETHANE SEALANT - BETWEEN

CLADDING & FLASHING AND

FASCIA & CLADDING

1

2

Roof Diverter Flashing - Installation

Sequence

2.2

NEW ASPHALT

SHINGLES

DWG. #

PROJ. #

DWN.

SCALE

DATE

CH'D.

#301D - 30721 Simpson Road, Abbotsford, BC

PH. 604-575-8220

www.apexbuildingsciences.com

Apex

SEAL

5653

SK

3" = 1'-0"

Mar. 14 / 2017

BC

Victoria Community Hall

2026 E 43rd Avenue, Vancouver, BC

Issued for Tender