Upload
others
View
20
Download
2
Embed Size (px)
Citation preview
J J
P
J
DRAWING REFERENCE SYMBOLSDESCRIPTIONSYMBOL
12. DEMOLITION NOTES
A. MAINTAIN CONTINUITY OF ALL CIRCUITS AFFECTED BY DEMOLITION. INTEGRITY TO OTHER AREAS SHALLNOT BE DAMAGED.
B. CLEAN, RELAMP AND REPAIR EXISTING LIGHTING FIXTURES THAT ARE TO BE RELOCATED.
C. COORDINATE WITH ARCHITECT TO MATCH NEW LIGHTING FIXTURES WITH EXISTING LIGHTING FIXTURES.
D. REMOVE ALL UNUSED WIRING BACK TO PANEL AND/OR EXISTING TO REMAIN FIXTURE, RECEPTACLE, ETC.AS APPLICABLE.
E. DEMOLISH ALL RECEPTACLES, OUTLETS, FIRE ALARM DEVICES, SWITCHES, ETC. THAT ARE IN PARTITIONSAND/OR COLUMNS TO BE DEMOLISHED. REMOVE ALL WIRING BACK TO NEAREST REMAINING DEVICE.
F. ALL RECEPTACLES, LIGHT FIXTURES, EXIT SIGNS, OUTLETS, ETC. SHOWN ON PLAN ARE NEW, UNLESSOTHERWISE NOTED. "E" INDICATES EXISTING TO REMAIN, "R" INDICATES RELOCATED AND "X" INDICATESTO BE DEMOLISHED.
G. PATCH OVER AND PAINT TO MATCH EXISTING, ALL RECEPTACLES, FIRE ALARM DEVICES, OUTLETS,SWITCHES, ETC. THAT ARE TO BE DEMOLISHED OR RELOCATED.
H. REMOVE ALL OBSOLETE INACTIVE OR OTHERWISE UNUSED DATA, VOICE, SECURITY AND AUDIO-VISUALCABLING IN RACEWAYS AND ABOVE CEILINGS PER NEC 800.3.C.
I. REFER TO THE MECHANICAL DOCUMENTS FOR MECHANICAL EQUIPMENT SCHEDULED FOR DEMOLITION.U.N.O., MECHANICAL EQUIPMENT SCHEDULED FOR DEMOLITION SHALL ALSO INCLUDE ELECTRICALEQUIPMENT, CONDUIT, AND CONDUCTORS SERVING THAT MECHANICAL EQUIPMENT TO BE REMOVED ANDDEMOLISHED BACK TO THE EXISTING SOURCE OVERCURRENT DEVICE.
J. WHERE ELECTRICAL CIRCUITS OR DEVICES ARE SCHEDULED TO BE DEMOLISHED OR DISCONNECTED ANDABANDONED IN PLACE, THE CONTRACTOR SHALL OBTAIN WRITTEN AUTHORIZATION FROM THE END USERAND THE END USER'S TENANTS PRIOR TO DEMOLISHING OR DISCONNECTING EXISTING ELECTRICALEQUIPMENT FROM THE SOURCE.
K. WITHIN 2 WEEKS AFTER AWARD OF CONTRACT, AND PRIOR TO THE START OF WORK, PROVIDE OWNER/ENDUSER WITH SCHEDULE OF SHUTDOWN S OF ELECTRICAL FEEDER CIRCUITS AND EQUIPMENT FOROWNER/END USER REVIEW AND APPROVAL. INDICATE ESTIMATED DURATIONS OF SCHEDULED EQUIPMENTDOWNTIME FOR EACH FEEDER CIRCUIT AND ELECTRICAL EQUIPMENT.
13. SUBSTITUTION OF EQUIPMENT OR MATERIALS IS ACCEPTABLE IF EQUIVALENT TO THE ITEM SPECIFIED.UNIDENTIFIED FIELD CHANGES REQUIRED TO ACCOMMODATE THE SUBSTITUTED EQUIPMENT OR MATERIALS SHALLBE THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR.
14. ELECTRICAL DISTRIBUTION EQUIPMENT INSTALLATION.
A. MOUNT ALL SURFACE MOUNTED PANEL BOARDS, SAFETY SWITCHES, AUTOMATIC TRANSFER SWITCHES,STARTERS ETC. ON A STEEL FRAME OF 12 GAUGE, HOT-DIPPED, GALVANIZED STEEL
CHANNEL WITH A CROSS-SECTION DIMENSION OF AT LEAST 1-1/2 INCHES BY 1-1/2 INCHES. 1. DESIGN FRAME TO DISTRIBUTION WEIGHT EVENLY. 2. SECURE TO FLOOR AND CEILING SLAB AT DRYWALL PARTITIONS, PARTITIONS ARE NOT TO SUPPORT
CHANNELS. 3. SECURE TO FLOOR AND WALL AT MASONRY PARTITIONS.
P. ALL CONDUITS AND CABLES LOCATED OUTSIDE OF TENANT SPACE THAT ARE PART OF THISCONSTRUCTION SHALL BE LABELED AT THE TERMINATION (SOURCE) AND JUST OUTSIDE OF THETENANT SPACE. THIS LABELING SHALL INDICATE SOURCE.
Q. ALL JUNCTION BOXES ABOVE CEILINGS SHALL BE MARKED WITH PANEL & CIRCUIT DESIGNATION FORCIRCUITS CONTAINED WITHIN.
4. WIRING DEVICES
A. ALL WIRING DEVICES SHALL BE PROVIDED AS LOCATED IN THE ARCHITECTURAL PLANS AND ASIDENTIFIED IN THE SYMBOL LIST.
B. ALL OUTLET BOXES SHALL BE GALVANIZED STEEL, AT LEAST 1 - 1/2 INCH DEEP AND OF SUFFICIENT SIZE TOACCOMMODATE THE WIRING DEVICES AND/OR WIRING TO BE INSTALLED.
C. OUTLET BOXES FOR WIRING DEVICES IN FINISHED WALLS SHALL BE ONE PIECE STANDARD GANG TYPE OFSIZE TO ACCOMMODATE NUMBER OF DEVICES NOTED. BOXES SHALL HAVE PLASTIC COVERS TO BRINGBOX OPENING FLUSH WITH FINISHED WALL OR NOT MORE THAN 1/4 INCH IN BACK OF SAME.
D. WIRING DEVICES OF THE SAME OR SIMILAR TYPE SHOWN ADJACENT TO EACH OTHER ON THE DRAWINGSSHALL BE INSTALLED IN A MULTI-GANGED OUTLET BOX AND UNDER A COMMON COVERPLATE. REFER TOALL APPLICABLE NOTES.
E. PROVIDE THE FOLLOWING TYPE OF DEVICES FOR THE PROJECT:NOTE: FINAL SELECTION OF DEVICE AND COVERPLATE COLOR SHALL BE BY ARCHITECT.
1) DUPLEX RECEPTACLES 2P, 3W, 20A, 125V; P&S CAT. NO. 26352.
2) ISOLATED GROUND DUPLEX RECEPTACLES 2P, 3W, 20A, 125V; P&S CAT. NO. IG26362 (ORANGE).
3) DUPLEX RECEPTACLES 2P, 3W, 20A, 125V; GROUND FAULT CIRCUIT INTERRUPTER; P&S CAT. NO.2091-S.
4) FLUSH FLOOR POKE-THRU WITH DUPLEX RECEPTACLE 2P, 3W, 20A, 125V AND SPACE FOR (4)CATEGORY 5 JACKS: WIREMOLD RC3 SERIES.
5) FLUSH FLOOR POKE-THRU WITH DOUBLE DUPLEX RECEPTACLE 2P, 3W, 20A, 125A AND SPACE FOR(4) CATEGORY 5 JACKS: WIREMOLD RC4 SERIES.
6) FLUSH FLOOR BOX WITH FLIP LID AND RECESSED DEVICES; WALKER 6AT OR 8AT SERIES WITHDEVICES AS NOTED ON PLANS.
7) SINGLE-WAY FLUSH TUMBLER SWITCH (20A); P&S CAT. NO. 2621.
8) THREE-WAY FLUSH TUMBLER SWITCH (20A); P&S CAT. NO. 2623.
9) ALL COVER PLATES FOR DEVICES LISTED ABOVE SHALL BE THERMOPLASTIC UON.
5. CONDUCTOR INSTALLATION
A. HOMERUNS TO THE PANELBOARD MAY BE RUN TOGETHER IN ONE CONDUIT, PROVIDED ALL CONNECTIONSARE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL ELECTRICAL CODEREQUIREMENTS AND THE MAXIMUM UNBALANCED CURRENT IN NEUTRAL DOES NOT EXCEED THECAPACITY OF THE WIRE. NO MORE THAN THREE SINGLE PHASE CIRCUITS SERVED FROM DIFFERENTPHASES OR ONE THREE PHASE CIRCUIT SHALL BE INSTALLED IN ONE RACEWAY.
B. CONDUCTORS SHALL BE CONTINUOUS (SPLICE FREE) FROM TERMINATION TO TERMINATION. PROVIDEPULLBOXES WHERE SPLICES ARE ABSOLUTELY NECESSARY; SPLICE IN READILY ACCESSIBLE PULL,JUNCTION OR OUTLET BOX.
6. MODIFICATIONS TO EXISTING PANELBOARDS
A. PROVIDE NEW CIRCUIT BREAKERS AND/OR FUSED SWITCHES AS REQUIRED. NEW EQUIPMENT SHALLMATCH EXISTING INSTALLED EQUIPMENT AND SHALL BE OF THE SAME MANUFACTURER AND TYPE ASSIMILAR EXISTING EQUIPMENT. INTERRUPT RATING OF EQUIPMENT SHALL BE THE SAME AS THAT OFEXISTING EQUIPMENT. PROVIDE NEW TYPED PANELBOARD DIRECTORY TO REFLECT CHANGES MADE TOPANELBOARD AND THE EXISTING TO REMAIN CIRCUITS. THE DIRECTORY SHALL INDICATE DEVICE SERVEDAND SPECIFIC LOCATION OF DEVICE(S). SPECIFIC LOCATION SHALL INDICATE ROOM NUMBER AND TYPE OFROOM (i.e. RECEPTACLES-OFFICES 514, 515 & 516). THE CONTRACTOR SHALL INSURE THAT COMPLIANCEWITH NEC 408.4 IS MET CLEARLY ON ALL PLANELBOARD DIRECTORIES.
7. NEW PANELBOARDS
A. ALL PANELBOARDS SHALL BE BOLT-ON TYPE CIRCUIT BREAKER WITH COPPER BUS AND FULL NEUTRALUON.
B. IN PANELBOARDS, "EQUIPPED SPACE" OR "SPACE" UNDER THIS CONTRACT IS DEFINED TO INCLUDE ALLNECESSARY BUS, DEVICE SUPPORTS AND CONNECTIONS FOR INSERTION OF A FUTURE DEVICE.
C. PROVIDE NEW TYPED PANEL DIRECTORIES FOR ALL PANELS AFFECTED BY THIS WORK. THE DIRECTORYSHALL INDICATE DEVICE SERVED AND SPECIFIC LOCATION OF DEVICE(S). SPECIFIC LOCATION SHALLINDICATE ROOM NUMBER AND TYPE OF ROOM (i.e. RECEPTACLES-OFFICES 514, 515 & 516). THECONTRACTOR SHALL INSURE THAT COMPLIANCE WITH NEC 408.4 IS MET CLEARLY ON ALL PLANELBOARDDIRECTORIES.
D. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
8. INTERRUPTION OF ELECTRICAL POWER
A. COORDINATE ALL WORK REQUIRING INTERRUPTION OF ELECTRICAL POWER WITH THE BUILDING OWNERAND SHALL OBTAIN WRITTEN PERMISSION FROM THE BUILDING OWNER PRIOR TO SHUTTING DOWN POWERTO ANY ELECTRICAL EQUIPMENT. THE CONTRACTOR SHALL ALSO PROVIDE NOTICE TO ALL OTHER TRADESOF ALL SCHEDULED INTERRUPTIONS OF POWER.
9. SITE VISIT
A. PRIOR TO SUBMITTING THE CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH ALLEXISTING CONDITIONS. NOTIFY THE ARCHITECT AND/OR ENGINEER IN ADVANCE OF ANY CONDITION THATEXISTS THAT WOULD PREVENT THE WORK HEREIN SPECIFIED OR SHOWN ON THE DRAWINGS FROM BEINGPERFORMED. FAILURE TO SURVEY THE SITE PRIOR TO BID AND START OF CONSTRUCTION WILL NOTRELIEVE THE CONTRACTOR OF THE RESPONSIBILITY TO INSTALL DESIGN WITHIN THE CONFINES OFEXISTING CONDITIONS.
10. GUARANTEE
A. LEAVE THE ENTIRE ELECTRICAL SYSTEM INSTALLED UNDER THIS CONTRACT IN PROPER WORKING ORDERAND SHALL, WITHOUT CHARGE, REPLACE ANY WORK OR MATERIALS WHICH DEVELOP DEFECTS, EXCEPTFROM ORDINARY WEAR AND TEAR, WITHIN ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE.BENEFICIAL USE SHALL NOT BE CONSTRUED AS FINAL ACCEPTANCE.
B. DURING THE ONE YEAR GUARANTEE PERIOD, PROVIDE PROPER REPAIR AND ADJUSTMENTS OF ALLELECTRICAL SYSTEMS AND EQUIPMENT, APPARATUS, DEVICES, ETC., INSTALLED AND DO ALL WORKNECESSARY TO ENSURE EFFICIENT AND PROPER FUNCTIONING.
C. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR, AND SHALL INCUR FINANCIAL REPONSIBILITYFOR ANY DAMAGES CAUSED BY, OR RESULTING FROM, DEFECTS IN HIS WORK.
D. DEMONSTRATE OPERABILITY OF ALL SYSTEMS IN THIS DESIGN TO THE SATISFACTION OF THE TENANT,DESIGN TEAM, CM/PM & BUILDING ENGINEER AS NECESSARY AND REQUESTED.
11. RECORD DRAWINGS
A. MAINTAIN AT THE SITE, FOR THE OWNER, ONE COPY OF ALL DRAWINGS, ADDENDA, APPROVED SHOPDRAWINGS, REVISIONS AND OTHER MODIFICATIONS, IN GOOD ORDER AND MARKED TO RECORD ALLCHANGES MADE DURING CONSTRUCTION. THE SET OF DRAWINGS AND OTHER INFORMATION SHALL BEDELIVERED TO THE OWNER UPON COMPLETION OF WORK.
1. SCOPE
A. THE WORK TO BE DONE SHALL INCLUDE THE FURNISHING OF ALL LABOR, MATERIALS, APPLIANCES,EQUIPMENT, TOOLS, TRANSPORTATION, SUPERINTENDENTS AND SERVICES REQUIRED TO CONSTRUCT,INSTALL AND MODIFY COMPLETE AND OPERATIVE, THE ELECTRICAL SYSTEMS AS HEREIN SPECIFIED ANDAS SHOWN ON THESE DRAWINGS. COORDINATE WORK TO BE PERFORMED OR INSTALLED BY OTHERSAFFECTING ELECTRICAL WORK AND PROVIDE AND INSTALL ALL NECESSARY ANCHORS, SLEEVES,HANGERS, ETC. FOR ATTACHING OR CONNECTING ELECTRICAL WORK TO RELATED WORK OF OTHERTRADES.
2. GENERAL CONDITIONS
A. ALL ELECTRICAL WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH THE NATIONAL ELECTRICALCODE AND ALL OTHER LOCAL CODES AND AUTHORITIES HAVING JURISDICTION.
B. DRAWINGS, WHICH CONSTITUTE A PART OF THIS CONTRACT, INDICATE THE GENERAL ARRANGEMENT OFCIRCUITS AND OUTLETS, LOCATIONS OF SWITCHES, PANELBOARDS, CONDUIT AND OTHER WORK. ALLITEMS NOT SPECIFICALLY MENTIONED HEREIN, WHICH ARE NECESSARY TO MAKE A COMPLETE WORKINGINSTALLATION, SHALL BE INCLUDED AT NO EXTRA COST.
C. IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO EXAMINE THE ARCHITECTURAL, STRUCTURAL,MECHANICAL AND PLUMBING DRAWINGS TO FAMILIARIZE HIMSELF WITH ALL ASPECTS OF THOSE DESIGNSAFFECTING HIS WORK. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH ALL OTHERTRADES.
D. ALL ELECTRICAL MATERIALS SHALL BE NEW, EXCEPT WHERE SPECIFICALLY NOTED AS EXISTING TO BEREUSED, AND SHALL BE LISTED BY THE UNDERWRITERS' LABORATORIES, INC. (UL). DEFECTIVEEQUIPMENT OR EQUIPMENT DAMAGED IN THE COURSE OF INSTALLATION OR TEST SHALL BE REPLACED ORREPAIRED IN A MANNER MEETING THE APPROVAL OF THE ARCHITECT AND ENGINEER. WHEREAPPLICABLE, ALL EQUIPMENT SHALL BE IN ACCORDANCE WITH NEMA STANDARDS.
E. ALL WORK SHALL BE SUBJECT TO THE APPROVAL OF THE OWNER OR HIS AUTHORIZED REPRESENTATIVEAND SHALL BE PERFORMED IN ACCORDANCE WITH ALL BUILDING RULES AND REGULATIONS AS PROVIDEDBY THE BUILDING OWNER.
F. ALL WORK SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER.
G. WHERE CONDUITS, WIREWAYS, AND OTHER ELECTRICAL RACEWAYS PASS THROUGH FIRE RATEDPARTITIONS OR SLABS, INSTALL A UL LISTED FIRE STOP OF ROCKWOOL FIBER OR SILICON FOAM SEALANTTO PROVIDE AN EFFECTIVE BARRIER AGAINST THE SPREAD OF FIRE AND SMOKE. APPROVEDMANUFACTURERS ARE HILTI & 3M.
H. ALL CERTIFICATES OF APPROVAL SHALL BE IN TRIPLICATE, DELIVERED TO THE ENGINEER, AND BECOMETHE PROPERTY OF THE OWNER.
I. VERIFY ALL EQUIPMENT REQUIREMENTS BEFORE INSTALLING CONDUIT OR CONDUCTORS FROM POWERSOURCE TO EQUIPMENT TERMINATION.
J. X-RAY SLAB IN AREA OF PENETRATION PRIOR TO CORE DRILLING AND COORDINATE WITH EQUIPMENT INCEILING SPACE BELOW TO CHECK FOR OBSTRUCTIONS. IN ADDITION, REVIEW SLAB PENETRATIONS WITHSTRUCTURAL ENGINEER RETAINED BY THE CONTRACTOR IN ORDER TO INSURE THAT THE STRUCTURE'SINTEGRITY IS MAINTAINED. THE CONTRACTOR SHALL COORDINATE WITH THE BUILDING OWNER FOR ANYADDITIONAL REQUIREMENTS OR IF GROUND PENETRATING RADAR (GPR) IS AN ACCEPTABLE ALTERNATETO X-RAY.
K. ENGINEER'S CONSTRUCTION PHASE SERVICES ARE INTENDED TO BENEFIT THE CLIENT ONLY. SERVICESRENDERED BY ENGINEER DO NOT RELIEVE CONTRACTOR FROM OBLIGATIONS UNDER THE CONSTRUCTIONDOCUMENTS. ENGINEER DOES NOT HAVE AUTHORITY TO SUPERVISE, DIRECT OR CONTROL CONTRACTOR,AND IS NOT RESPONSIBLE FOR MEANS, METHODS, TECHNIQUES, SEQUENCES, OR PROCEDURES OFCONSTRUCTION OR FOR SAFETY PROGRAMS OR PRECAUTIONS DURING CONSTRUCTION. NOR ISENGINEER RESPONSIBLE FOR CONTRACTOR'S FAILURE TO PERFORM THE WORK IN ACCORDANCE WITHTHE CONSTRUCTION DOCUMENTS OR APPLICABLE LAWS OR CODES.
L. ENGINEER WILL CONSIDER CONTRACTOR SUBSTITUTIONS IF THEY ARE CLEARLY DELINEATED AS SUCH.ENGINEER CANNOT BE RESPONSIBLE FOR IDENTIFYING ALL SUBSTITUTIONS OR DEVIATIONS FROM THECONTRACT DOCUMENTS, UNLESS SPECIFICALLY NOTED AS SUCH IN WRITING. CONTRACTOR SHALL MAKESURE THAT SUBSTITUTED EQUIPMENT MEETS ELECTRICAL REQUIREMENTS AS WELL PHYSICALREQUIREMENTS OF SPECIFIED EQUIPMENT.
3. WIRING METHODS
A. ALL CONDUCTORS SHALL BE COPPER, CONFORMING TO THE LATEST REQUIREMENTS OF THE NATIONALELECTRICAL CODE, STRANDED FOR NO. 8 AWG AND LARGER, SOLID FOR NO. 10 AWG AND SMALLER. THEUSE OF ALUMINUM CONDUCTORS FOR ANY PURPOSE SHALL NOT BE ACCEPTABLE.
B. ALL NEW LUGS & CONNECTORS SHALL RATED FOR 75 DEGREE CENTRIGRADE. WHERE EXISTINGEQUIPMENT IS REUSED AND REFED, REPLACE ANY EXISTING 60 DEGREE CENTRIGRADE LUGS WITH NEW 75DEGREE CENTIGRADE LUGS.
C. MINIMUM SIZE CONDUCTOR SHALL BE NO. 12 AWG.
D. CONDUCTORS SHALL BE THERMOPLASTIC TYPE THHN/THWN-2. ALL WIRE AMPACITIES SHALL BE LIMITEDTO THE 75 DEGREES CENTIGRADE COLUMN OF TABLE 310-16 OF THE NEC.
E. ALL CONDUCTORS SHALL BE COLOR CODED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. ALLFLEXIBLE CABLE, MC CABLE, SHALL BE COLOR CODED ON THE EXTERIOR OF THE METAL CLADDING.
F. GROUNDING OF THE ENTIRE ELECTRICAL SYSTEM SHALL BE IN ACCORDANCE WITH THE NATIONALELECTRICAL CODE AND AS INDICATED ON DRAWINGS.
G. ALL WIRING SHALL BE INSTALLED IN CONDUIT (E.M.T. OR FLEXIBLE METAL CONDUIT). MINIMUM CONDUITSIZE SHALL BE 3/4 INCH. ALL CONDUIT AND WIRING SHALL BE CONCEALED IN CEILINGS AND/OR WALLSUNLESS SPECIFICALLY NOTED OTHERWISE. CHANNEL EXISTING WALLS WHERE REQUIRED. WHEREWIRING RUNS ARE EXPOSED DUE TO THE LACK OF A NEW FINISHED CEILING, E.M.T. SHALL BE USED.INSTALL ALL CONDUITS IN RUNS WHICH ARE PARALLEL AND PERPENDICULAR WITH BUILDING LINES.
H. TYPE MC CABLE MAY BE USED IN LIEU OF EMT IN CONCEALED SPACES WHERE PERMITTED BY CODES ANDBUILDING OWNER.
I. ALL VOICE, DATA, SECURITY, AV AND TV OUTLETS SHALL BE PROVIDED WITH PLASTER RING AND NYLONPULL STRING UP TO CEILING PLENUM ABOVE, IN HOLLOW SLAB TO CEILING WALLS. IN WALLS THAT ARESLAB TO SLAB OR INSULATED, PROVIDE A 1900 BOX WITH A SINGLE GANG PLASTER RING, EXTEND A 1-INCHCONDUIT UP TO CEILING PLENUM FROM 1900 BOX AND INSTALL A NYLON PULL STRING.
J. PROVIDE MINIMUM NO. 10 AWG CONDUCTOR SIZE IN BRANCH CIRCUIT RUNS OVER 75 FEET AND N0. 8 AWGIN BRANCH CIRCUIT OVER 120 FEET IN LENGTH FOR 120V CIRCUITS.
K. ALL RACEWAYS SHALL BE CONCEALED. WHERE RACEWAYS CANNOT BE CONCEALED, IT SHALL BEINSTALLED AT ARCHITECT'S DIRECTION.
L. PROVIDE ACCESS PANELS WHERE REQUIRED FOR PROPER ACCESS TO JUNCTION BOXES, PULL BOXES,TAP BOXES, ETC. WHERE EXISTING JUNCTION BOXES ARE LOCATED ABOVE NEW DRYWALL CEILING AREASTHESE SHALL BE RELOCATED TO ABOVE ACCESSIBLE CEILING FOR CODE REQUIRED ACCESS. ACCESSPANELS ARE ALLOWED, ONLY IF APPROVED BY THE ARCHITECT. FOR BID PURPOSES, ASSUME JUNCTIONBOX RELOCATION MUST OCCUR. SEE ARCHITECTURAL PLANS FOR SPECIFICATIONS OF ACCESS PANELS.
M. ALL CONNECTORS AND/OR COUPLERS SHALL BE STEEL. CAST FITTINGS ARE NOT ACCEPTABLE.
N. DERATE CONDUCTORS PER NATIONAL ELECTRICAL CODE AND PROVIDE ONE NEUTRAL CONDUCTOR FOREACH THREE PHASE CONDUCTORS IF MORE THAN THREE PHASE CONDUCTORS ARE INSTALLED IN ASINGLE PIPE.
O. PROVIDE AND INSTALL TYPE, HCF OR MCIG CABLE FOR ALL BRANCH CIRCUIT WIRING SERVING ISOLATEDGROUND TYPE RECEPTACLES (IG). THE CONTRACTOR SHALL ENSURE THAT THE ISOLATED GROUNDCONDUCTOR IS A MINIMUM NO. 12 AWG COPPER CONDUCTOR AND THAT A SEPARATE EQUIPMENT GROUNDPATH IS PROVIDED (UL LISTED). THE ISOLATED GROUND AND EQUIPMENT GROUND MAY NOT BECOMBINED.
260500 GENERAL REQUIREMENTS AND WORK RESULTS FOR ELECTRICALSYSTEMS
260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS260529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS260533 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS260544 SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND
CABLING260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS260570 PROTECTIVE DEVICE SHORT CIRCUIT, COORDINATION, AND ARC
FLASH STUDY260800 ELECTRICAL COMISSIONING262200 LOW-VOLTAGE DRY TYPE TRANSFORMERS262413 SWITCHBOARDS262416 PANELBOARDS262510 TRACK BUSWAY SYSTEM262813 FUSES262816 ENCLOSED SWITCHES AND CIRCUIT BREAKERS264313 SURGE PROTECTION FOR LOW-VOLTAGE ELECTRICAL POWER
CIRCUITS269000 ELECTRICAL TESTING269500 SUBMITTAL AND DOCUMENTATION REQUIREMENTS FOR
ELECTRICAL SYSTEMS
WALL MOUNTED DUPLEX RECEPTACLE, NEMA 5-20R, 2P-3W-20A-125V
VOICE OUTLET
DATA OUTLET
SPECIAL RECEPTACLE - ALPHANUMERICS INDICATE- NEMA CONFIGURATION
WALL MOUNTED DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, 2P-3W-20A-125V
COMBINATION DATA/ VOICE OUTLET.
WALL MOUNTED GROUND FAULT INTERRUPTER RECEPTACLE 2P-3W-20A-125V
FLOOR BOX WITH FLIP LID AND RECESSED RECEPTACLES AND OUTLETS.
WALL MOUNTED SIMPLEX RECEPTACLE, NEMA 5-20R, 2P-3W-20A-125V
AC-1 MECHANICAL HVAC UNIT
3 4
ARL:
K:\21
5\215
0490
1\E-C
OVER
Plott
edBy
:Sha
wnSe
greti|
4/10/0
8|9:1
8PM
ELECTRICAL ABBREVIATIONS
ISOMETRIC VIEW
FRONT VIEW
SIDE VIEW
BUSWAY
"B" BUSWAY
FRONT VIEW
"B" BUSWAY
RAC
K
RACK DETAILS
STACKED XFMR DETAILSCALE : NONE
02
E-501
T
T
ARL:
K:\21
5\215
0490
1\E-D
etails
Plott
edBy
:Sha
wnSe
greti|
4/10/0
8|9:1
8PM
1-7
PP3
PP6XFMR PP5
PP4
XFMR
PP1
PP2
XFMR
T11
2.5K
01-EXISTING ELECTRICAL POWER PLAN - LOWER LEVELSCALE: 1/8"=1'-0"
GENERAL NOTES1. PLAN REFLECTS GENERAL EXISTING ELECTRICAL PLAN CONDITIONS FOR INFORMATIONAL PURPOSES.
2. EXISTING UNDERFLOOR RECEPTACLES THROUGHOUT THE COMPUTER ROOM SHALL BE DEMOLISHED AND CORRESPONDINGBRANCH CIRCUIT CONDUITS AND CONDUCTORS SHALL BE REMOVED BACK TO THE PANELBOARD THAT SERVES THERECEPTACLES.
3. EXISTING WALL MOUNTED WIREMOLD RACEWAY AND RECEPTACLES THROUGHOUT THE COMPUTER ROOM SHALL BEDEMOLISHED AND CORRESPONDING BRANCH CIRCUIT CONDUITS AND CONDUCTORS SHALL BE REMOVED BACK TO THEPANELBOARD THAT SERVES THE RECEPTACLES.
KEYED NOTES# #1. ELEC. EQUIPMENT DUPS; FOR XFMRS, PANELS PP (1,2,3,4,5,6) AND THE EQUIPMENT'S CORRESPONDING FEEDER CIRCUITS AND
BRANCH CIRCUITS SHALL BE RELOCATED TO AREA INDICATED IN .
2. AREA FOR NEW AND RELOCATED ELEC. EQUIPMENT, WHERE RECEPTACLES ARE MADE INACCESSIBLE FROM EQUIPMENTRELOCATION. REMOVE RECEPT + WIRING BACK TO NEAREST JB AND BLANK OFF BACK BOX.
3. EXISTING RACKS SHALL BE RE-FED FROM NEW OVERHEAD BUSWAY. DEMOLISHED BRANCH CKT'S MADE OBSOLETE.
4. EXISTING COMPUTER EQUIPMENT RACK, SCHEDULED FOR DEMOLITION. COORDINATE DEMOLITION WITH THE END USER, CO NOTDEMOLISH UNTIL AFTER THE END USER HAS REMOVED EQUIPMENT AND RE-ROUTED CONNECTIONS.
5. COMPUTER ROOM WHERE EXISTING WALL AND BELOW FLOOR DEVICES ARE SCHEDULED TO BE DEMOLISHED BACK TOPANELBOARD(S) SERVING THOSE DEVICES.
6. REGARDLESS OF ACTUAL QUANTITY OF EXISTING WIRING DEVICES , PROVIDE FOR DEMOLITION OF ALL BELOW RAISED FLOORAND WALL MOUNTED DEVICES THROUGHOUT THE COMPUTER ROOM.
2
3
2
19'-1/11"
6'-1"
13
4 5
65
5
5
5
ARL:
K:\21
5\215
0490
1\E-P
LANP
Plott
edBy
:Sha
wnSe
greti|
4/10/0
8|9:1
8PM
1-7
T
T T
DUPS
LUA1
01-NEW WORK ELECTRICAL PLAN - LOWER LEVELSCALE: 1/8"=1'-0"
KEYED NOTES1. NEW POWERBAR BUSWAY MOUNTED ABOVE COMPUTER EQUIPMENT RACKS, WITH PLUG-INS. REFER TO DETAILS
FOR ADDITIONAL INFORMATION. AT A MINIMUM, PROVIDE BUSWAY IN LENGTH SHOWN ON PLAN VIEW, BUT OFSUFFICIENT LENGTH TO PROVIDE QUANTITY AND SIZES OF SPECIFIED PLUG-INS.
2. NEW SPACE RESERVED FOR FUTURE FULLY REDUNANT POWERBAR BUSWAY.3. END CABLE TAP BOX FOR POWERBAR EQUIPMENT.4. ELEC. EQUIPMENT MOUNTED FREE STANDING USING STEEL CHANNELING ATTACHED TO THE STRUCTURE OR SLAB
ON GRADE.5. EXISTING CRAC UNIT SCHEDULED FOR DEMOLITION. EXTEND EXISTING CONDUIT AND CONDUCTORS FROM
EXISTING LOCATION TO SCHEDULED RELOCATION. RELOCATE LOCAL DISCONNECTING MEANS WITH UNITRELOCATION.
6. NEW IN-ROW COOLING UNIT.7. EXISTING SURFACE WALL MOUNTED PLUGMOLD, HATCHED PLUGMOLD SCHEDULED TO BE DEMOLISHED. ANY
BRANCH CIRCUITS MADE AVAILABLE THROUGH DEMOLITION SHALL BE MARKED 'SPARE.' COMMUNICATIONSWIRING MADE OBSOLETE THROUGH DEMOLITION SHALL BE REMOVED IN ITS ENTIRETY BACK TO THE TELECOMCIRCUIT(S) SOURCE.
8. 112.5 KVA FLOOR MOUNTED XFMR WITH ONE 75 XFMR MOUNTED ABOVE FLOOR MOUNTED TRANSFORMERUSING UNI-STRUT AND STEEL CHANNELING AS NECESSARY TO MOUNT SECOND XFMR ABOVE FLOOR MOUNTEDUNIT, REFER TO ELEC. DETAILS.
9. ALPHANUMERIC DESIGNATION IS PROVIDED PER RACK, FOR EACH CONTRACTOR SHALL PROVIDE BUSWAY PLUG INWITH CIRCUIT BREAKERS, WIRING DEVICES, FEATURES AND RATINGS SPECIFIED IN THE POWER BAR PLUG-INSCHEDULE.
10. 112.5 KVA FLOOR MOUNTED XFMR WITH ONE 75 XFMR MOUNTED ABOVE FLOOR MOUNTED TRANSFORMERUSING UNI-STRUT AND STEEL CHANNELING AS NECESSARY TO MOUNT SECOND XFMR ABOVE FLOOR MOUNTEDUNIT, REFER TO ELEC. DETAILS.
11. RELOCATED EMERGENCY POWER OFF SWTICHES FOR UPS EQUIPMENT AND HVAC EQUIPMENT. CONNECT TO EPOCIRCUIT OF UPS AND HVAC EQUIPMENT. PROVIDE CONDUIT AND CONDUCTORS MATCHING EXISTING AND PERCODE.
12. REFER TO DETAIL 02 FOR ALTERNATE EATON IFS EQUIPMENT LAYOUT.13. EXISTING COMPUTER RACK SCHEDULED TO BE PROVIDED WITH NEW PLUG-IN AND CORD, REFER TO SCHEDULES.14. IN-ROW COOLER HOMERUN CONNECTED TO NEW PANEL PAC, ROUTE CONDUIT BELOW RAISED FLOOR TO PANEL.15. HATCHED AREA INDICATES APPROXIMATE LOCATION OF SCHEDULE BUSWAY PLUG-IN. COORDINATE SPECIFIC
LOCATION OF EACH PLUG-IN IN FIELD WITH END USER.16. AREA OF ELECTRICAL EQUIPMENT SCHEDULED TO BE ABANDONED, DEMOLISHED, AND/OR RELOCATED. PROVIDE
NEW JUNCTION BOX IN THIS AREA AND EXTEND 600A DUPS PNL FEEDER TO NEW LOCATION OF DUPS.17. PULL BOXES LOCATED BELOW THE FINISHED CEILING, AND ABOVE DOOR FOR CONNECTING TO DATA CENTER
AREA. PROVIDE 20" HIGH x 42" WIDE AND DEPTH AS NECESSARY TO FACILITATE BENDING/PULLING OFCONDUCTORS. PROVIDE SLEEVES AS NECESSARY THROUGH WALL ABOVE DOOR. PROVIDE SLEEVES WITH BENDS ASNECESSARY THROUGH WALL TO FACILITATE PULLING OF CONDUCTORS.
18. NEW CRAC UNIT. RELOCATE EXISTING BRANCH CIRCUIT CONDUIT & CONDUCTORS FROM DEMOLISHED CRAH-1AND 2 UNIT, PROVIDE ADDITIONAL NEW CONDUIT AND CONDUCTORS MATCHING EXISTING AND PER CODE ASNECESSARY TO FACILITATE RELOCATION OF CRAH UNIT CIRCUIT TO SERVE NEW UNIT. PROVIDE NEW LOCAL30AF/3P/FSS FOR CONNECTION TO UNIT.
19. EXISTING SWITCH ROOM SHALL NOT HAVE CONDUITS UNDER THIS SCOPE PASS THROUGH OR BE ROUTEDTHROUGH THE AREA.
20. ROUTING PATH FOR DUPS FEEDER TO PANEL DUPS WITH PULL BOXES, ROUTING MAY BE BELOW THE 9'0" FINISHEDCEILING WHERE NECESSARY THE BOTTOM OF CONDUIT ASSEMBLIES SHALL NOT BE LOWER THAN 8" BELOW THEFINISHED CEILING.
21. EXISTING BRANCH CIRCUITS SERVED FROM PANELS SCHEDULED TO BE RELOCATED MAY BE ROUTED ABOVE ORBELOW THE CEILING WITHIN THE GENERAL ROUTING PATH OF THE FEEDER CONDUIT PATHS SHOWN.
22. ROUTING PATH FOR BUSWAY FEEDERS TO TRACK BUSWAYS OVER RACKS, WITH PULL BOXES, ROUTING MAY BEBELOW THE 9'0" FINISHED CEILING WHERE NECESSARY THE BOTTOM OF CONDUIT ASSEMBLIES SHALL NOT BELOWER THAN THE TOP OF DOOR FRAMES. ROUTE CONDUITS AROUND EXISTING VERTICAL PIPING RUNS, ORMOUNT SUFFICIENTLY INBOARD OF ROOM WALLS TO ALLOW EXISTING PIPING SCHEDULED TO REMAIN, ASCURRENTLY INSTALLED.
23. DASHED LINE AROUND DATA CENTER AND NEW STORAGE ROOM INDICATES AREA WHERE EQUIPMENT SERVED BYBRANCH CIRCUITS SCHEDULED TO BE RELOCATED BY THIS SCOPE, SHALL HAVE CONDUIT AND CONDUCTORSDEMOLISHED AT A MINIMUM TO WITHIN THE AREA INDICATED. OTHER BRANCH CIRCUITS THAT SERVICEEQUIPMENT AND DEVICES OUTSIDE OF THE DASHED LINE MAY HAVE THEIR CONDUITS AND CONDUCTORS RE-USEDFROM THE PREVIOUS EQUIPMENT LOCATION AT THE CONTRACTOR'S OPTION.
24. MOUNT XFMR ABOVE FINISHED RAISED FLOOR WITH DEDICATED LEVERS AND FLOOR STANDS AS NECESSARY TOSUPPORT 2 TIMES THE WEIGHT OF THE XFMR.
25. RELOCATE EXISTING 480V 3 Ø BRANCH CKT SERVING EXISTING CRAC UNIT SCHEDULED FOR DEMOLITION TORELOCATED CRAC UNITS IN DATA CENTER.
26. PROVIDE NEW CEILING MOUNTED MULTICRITERIA AREA SMOKE DETECTOR FOR DATA CENTER. CONNECT TOEXISTING FIRE ALARM SYSTEM CONTROL PANEL WITH CONDUIT AND CONDUCTORS AS NECESSARY, PROVIDEADDRESSABLE CONTACT AT EACH AHU AND IN -ROW COOLER FOR MECHANICAL UNIT SHUT DOWN UPONDETECTION OF SMOKE WITHIN ROOM. PROVIDE NEW AND ADDITIONAL FIRE ALARM SYSTEM HARDWARE, PANELS,AND SYSTEM PROGRAMMING AS NECESSARY TO FACILITATE THIS SYSTEM FUNCTION.
27. NEW NEMA '1' ENCLOSED C/B FOR SERVING XFMR FOR PNL PAC, WALL MOUNTED ADJACENT TO PANEL DP.28. SIMPLEX RECEPTACLE LOCATE WALL MOUNTED BELOW RAISED FLOOR FOR CONNECTION TO CONDENSATE PUMP.29. EXISTING CRAC SCHEDULED TO REMAIN.30. 60AF/3P/NFSS
TYP. OF 4
TYP. OF 4
TYP. OF 4
LUA4 LUA2
TYP. OF 7
3'-7"
CRAH-1 (D) CRAH-2 (D)5
5
HOT ISLE
COLD ISLE
COLD ISLE
HOT ISLE
HOT ISLE
COLD ISLE
HOT ISLE
3'-6"
9"
7
7
E3E4E5E7E8E9E10E11E12
J3J4J5J6J7J8J9J10J11J129 TYP.
OF WALL ABOVE HEATING UNITS
DUPS
MTS
BUSWAY A-E(3-12)
BUSWAY A-J(3-12)
02-ALTERNATE EQUIPMENT LAYOUT- LOWER LEVELSCALE: 1/8"=1'-0"
BUSWAY A-K(16-27)K16K17K18K19K20K21K22K23K24K25K26K27K36K37K38K40K41K42K43K44K45
6 TYP.
29
LUA1& XFMR
LUA(3,4)& XFMR
LUA2& XFMR
400AC/B& XFMR
BUSWAY A-K(36-45)
7
T75 PAC
14 TYP. OF 8
1/3/5
7/9/1113/15/1719/21/232/4/68/10/1214/16/18
15
16J
PB
PB
PBPB
19
TYP. OF 2
7
24
18
SSS
SSS
SSS
S
S
S
S
S
S
S
SS
S
S
S
S
S
MTS
FRONT OF MTS, W/ PB OVERHEAD
CLEARANCE AREA
PB
26 TYP.
DPT P1 P2
27
28 PAC-42
29
11
7
PAC-40
18
25/27/29
30
SWITCH FRONT
LUA3
PAC-38
ARL:
K:\21
5\215
0490
1\E-P
LANP
New
Work
Plott
edBy
:Sha
wnSe
greti|
4/10/0
8|9:1
8PM
HOT ISLE
4
KEYED NOTES1. EXISTING LIGHT FIXTURE, SCHEDULED FOR RELOCATION. PROVIDE CONDUIT AND CONDUCTORS MATCHING
EXISTING LIGHTING BRANCH CIRCUIT SIZES, AS WELL AS JUNCTION BOXES, ETC. AND EXTEND LIGHTING BRANCHCIRCUIT TO FACILITATE LIGHT FIXTURE RELOCATION.
2. SOLID FIXTURE INDICATES NEW LOCATION FOR RELOCATED EXISTING LIGHT FIXTURE.
3. AREA OF WORK FOR ELECTRICAL LIGHT FIXTURE PLANS. AREAS OUTSIDE OF THE AREA OF WORK SHALL BE EXISTINGTO REMAIN.
4. EXISTING LIGHT FIXTURE, 3-T8 LAMP FIXTURE SCHEDULE TO BE DEMOLISHED. PROVIDE CONDUIT ANDCONDUCTORS MATCHING EXISTING LIGHTING BRANCH CIRCUIT SIZES, AS WELL AS JUNCTION BOXES, ETC. ANDEXTEND LIGHTING BRANCH CIRCUIT TO FACILITATE NEW FIXTURE INSTALLATION.
5. NEW SURFACE WALL MOUNTED LED FIXTURE. PROVIDE HYDREL #4762-LED-40K-MVOLT-VCNP-CM-LP-WH.CONNECT TO EXISTING BRANCH CIRCUIT SERVING AREA. MOUNT 24" BELOW ACOUSTICAL CEILING TILE TO CENTERLINE OF LIGHT FIXTURE.
TYP. OF 8
01-ELECTRICAL LIGHTING PLAN - LOWER LEVELSCALE: 1/8"=1'-0"
GENERAL NOTES1. EXISTING INTERIOR ARCHITECTURE SHALL REMAIN UNCHANGED FOR THIS PROJECT, EXISTING FIRE ALARM DEVICES,
EMERGENCY LIGHTS, AND EXIT SIGNS SHALL REMAIN AS PREVIOUSLY PERMITTED AND INSTALLED.
2TYP. OF 2
1TYP. OF 2J JJJJJJ
J
5TYP. OF 8
3
ARL:
K:\21
5\215
0490
1\E-P
LANL
Plott
edBy
:Sha
wnSe
greti|
4/10/0
8|9:1
8PM
01-EXISTING ONE-LINE DIAGRAMSCALE: NONE
UPS A BATTERY A
BATTERY B
600A
GEN
300 KW GENERATOR480/277V. 3Ø
600AAUTOMATICTRANSFERSWITCH
UPS SERVICE BY-PASS PANEL
600A
200A 200A 250A 250A
UPS DIST.PANEL
175A175A
125A
ROOM 1T1112.5KVA208/120V.
75KVA208/120V.
T2ROOM 2
112.5KVA208/120V.
T3ROOM 3
225A 350A
PP6 PP5 PP3 PP4
3 SETS - 3 #3/0 & 1 #4 GND., IN 2"C.
3 SETS - 3 #3/0 & 1 #4 GND., IN 2"C.
3 SETS - 3 #3/0 &1 #4 GND., IN 2"C.
UPGRADE TO1000 KVA
J
PP7 PP10
150A100A
100A
P5
100A
350A
PP1 PP2
600AMLO
160 KVA
APC #SL160K6
UPS B160 KVA
APC #SL160K6
250A
PP9PP8
T4112.5 KVA208/120V
30AF/3P/FSS
30AF/3P/FSS
CR
AC
,LIE
BE
RT
#1
CR
AC
,LIE
BE
RT
#2
ATS-UPS
DOUBLE TAPPED
GENERAL NOTES1. EXISTING RISER REFLECTS GENERAL EXISTING ELECTRICAL CONDITIONS FOR INFORMATIONAL PURPOSES.
KEYED NOTES1. EXISTING PANELBOARD SCHEDULED TO BE MADE OBSOLETE
THROUGH ADDITION OF NEW BUSWAY SYSTEM OVEREXISTING COMPUTER RACKS.
2. PANELBOARDS PP9 AND PP10, SERVING EXISTING IBMTENANT SPACE, MAY BE REMOVED WITH WRITTENAPPROVAL FROM END USER AND IBM (INTERNATIONALBUSINESS MACHINES CORPORATION) TENANT.
3. PRIOR TO EXCUTING WORK ON ANY UPSTREAM FEEDERCIRCUITS, DOWNSTREAM CIRCUITS SERVED BYPANELBOARD P4, OR PANELBOARD P4 ITSELF, COORDINATEWITH THE END USER AND THE IBM TENANT PRIOR, PROVIDEWRITTEN DESCRIPTION OF ELEC. WORK REQUIRED UPONEITHER PANEL P4 OR BRANCH CIRCUITS SERVED FROM P4AND OBTAIN WRITTEN APPROVAL FROM END USER ANDTENANT PRIOR TO PROCEEDING WITH WORK. INCLUDEAGREED UPON WORK THE DATE, TIME, AND DURATION OFWORK REQUIRED RELATED TO P4 OR BRANCH CIRCUITSCONNECTED TO P4.
4. PANELBOARD SCHEDULED TO BE MADE OBSOLETETHROUGH THE INSTALLATION OF NEW BUSWAY OVEREXISTING COMPUTER RACK ROWS. PANELBOARD ANDCORRESPONDING EXISTING ELECTRICAL SERVICE SHALL NOTBE INTERRUPTED OR SHUT OFF UNTIL AFTER THECOMPLETION OF THE INSTALLATION AND TESTING OF NEWBUSWAYS SERVING THE EXISTING COMPUTER RACKS.
5. PANELBOARD SHALL BE DISCONNECTED FROM FEEDER ANDBRANCH CIRCUITS, AND SHALL BE ABANDONED IN PLACE.MAINTAIN GROUNDING SYSTEM CONNECTIONS.
6. TRANSFORMER SHALL BE DISCONNECTED FROM FEEDERSOURCE, AND SHALL BE ABANDONED IN PLACE. MAINTAINGROUNDING SYSTEM CONNECTIONS.
7. EQUIPMENT SCHEDULED FOR RELOCATION.
8. PROVIDE ALTERNATE PRICE TO ABANDON IN PLACE.
ARL:
K:\21
5\215
0490
1\E-R
ISER
Plott
edBy
:Sha
wnSe
greti|
4/10/0
8|9:1
8PM
01-NEW WORK ONE-LINE DIAGRAMSCALE: NONE
UPS A BATTERY A
BATTERY B
600A
GEN
300 KW GENERATOR480/277V. 3Ø
600AAUTOMATICTRANSFERSWITCH
UPS SERVICE BY-PASS PANEL
600A
200A 200A 250A 250A
UPS DIST.PANEL
175A125A
125A
ROOM 1NEW T175KVA208/120V.
75KVA208/120V.
T2ROOM 2
112.5KVA208/120V.
T3ROOM 3
225A 400A
3 SETS - 3 #3/0 & 1 #4 GND., IN 2"C.
3 SETS - 3 #3/0 & 1 #4 GND., IN 2"C.
3 SETS - 3 #3/0 &1 #4 GND., IN 2"C.
1000 KVA
J
PP10
100A100A
225A'LUA1'
600AMLO
160 KVA
APC #SL160K6
UPS B160 KVA
APC #SL160K6
250A
PP9
30AF/3P/FSS
ATS-UPS
DOUBLE TAPPED
NEW POWERBAR 120/208V, 3Ø, 4W,22KAIC, 400A, 150% NETURAL
PLUG-IN TRACK BUSWAY, REFERTO PLANS, SCHEDULES, AND
DETAILS FOR LENGTHS, PLUG-INSINFORMATION, TYP. OF 4
KEYED NOTES1. NEW FEEDER, PROVIDE 3#3/0 AWG, 1#350 KCMIL NETURAL
AND #2 GND in 2.5" C. PROVIDE #2 FOR FUTURE EXPANSIONOF FEEDER TO BUSWAY TAP BOX OF A MATCHING SET OFCONDUCTORS AND CONDUIT FOR INCREASE OF BUSWAYTOTAL CAPACITY TO 400A.
2. DASHED LINE WHERE THE EXISTING DASHED EQUIPMENTWITHIN, WITH THE EXCEPTION OF FEEDER CONDUIT, WIRE,THREE NEW PANELBOARDS, AND POWER BAR BUSWAYS,SHALL BE RELOCATED FROM ROOM 054 TO ROOM O57.
3. PROVIDE NEW JUNCTION BOX AND SPLICE EXISTING 600AMP CONDUCTORS SERVING PANEL DUPS. MATCHEXISTING CONDUIT AND CONDUCTOR SIZES AND PROVIDEPER CODE, FOR PRICING PURPOSES INCLUDE TWO 3" C. EA.W/ 4#400 KCMIL CU AND #1 G. EXTEND TO NEW DOUBLETHROW SWITCH AND CONTINUE TO NEW LOCATION FORDUPS.
4. PROVIDE NEW PANELBOARD.5. PROVIDE NEW PANELBOARD WITH MAINS RATINGS,
FEATURES, AND BRANCH DEVICES AS SCHEDULED, EXCEPTPROVIDE 400A FEED THROUGH LUGS WITH A MININUM OF2 LUGS PER PHASE AND 2 PER NETURAL SIZED TO ACCEPTUP TO #4/0 AWG CU.
6. RECONNECT EXISTING FEED THROUGH LUGS ON EXISTINGPANEL TO MAIN LUGS ON NEW PANEL BOARD, IN NEWLOCATION INDICATED ON THE PLANS. MATCH EXISTINGCONDUIT AND CONDUCTOR SIZES. FOR PRICING PURPOSES,PROVIDE 4" C. WITH 5#600 KCMIL CU AND #2 G.
7. MAX CONDUCTOR LENGTH OF 25'.8. MAX CONDUCTOR LENGTH OF 10'.9. EXISTING PANELBOARD SCHEDULED TO BE MADE OBSOLETE
THROUGH ADDITION OF NEW BUSWAY SYSTEM OVEREXISTING COMPUTER RACKS.
10. PANELBOARDS PP9 AND PP10, SERVING EXISTING IBMTENANT SPACE, MAY BE DISCONNECTED FROM UPS SOURCEONCE WRITTEN APPROVAL FROM END USER AND IBMTENANT IS OBTAINED. PROVIDE ALTERNATE PRICE TO NOTINSTALL NEW FEEDER, BUT INSTEAD DISCONNECT ANDABANDON IN PLACE.
11. NEW FEEDER PROVIDE TWO 2.5" C. EA. W/ 3#3/0, 1#350KCMIL, AND #2 G.
12. MATCH CONDUIT AND CONDUCTORS SERVING RELOCATEDPANELBOARD. FOR PRICING PURPOSES PROVIDE 5#3/0AWG AND #2 GND in 3" C.
13. PROVIDE NEW 175A CIRCUIT BREAKER IN EXISTING PANELDUPS. MATCH EXISTING MANUFACTURER AND RATINGS.
14. REMOVE EXISTING 175A C/B AND REPLACE WITH NEW 125AC/B. MATCH EXISTING MANUFACTURER AND RATINGS.
15. REFER TO ALTERNATIVE DESIGN FOR EATON IFS EQUIPMENTFOR SWITCHBOARD ENCLOSED EQUIPMENT. PROVIDEALTERNATE PRICE FOR IFS EQUIPMENT WITH ESTIMATE FORDOWN TIME OF EXISTING DATA CENTER DURINGCONSTRUCTION.
16. 600A, 277/480V, 3Ø, 4W MANUALLY OPERATED DOUBLE THROWSWITCH, SECOND SOURCE LUGS FOR FUTURE UPS SYSTEMOUTPUT.
17. NEW FEEDER PROVIDE 4#600 KCMIL, 2#350 KCML CU NEUTRAL, #2 G.IN 4" C.
18. NEW FEEDER PROVIDE 4#600 KCMIL, 2#350 KCML CU NEUTRAL, #1/0G. IN 4" C.
19. NEW FEEDER PROVIDE TWO 2.5" C. EA. W/ 3#3/0, 1#350 KCMIL, AND#1/0 G.
200A
J
COPPER TRANSFORMER SCHEDULE
COPPER FEEDER SCHEDULE
175A
125A
175A
125A
75 KVA480V:120/208VK-4 RATED
225A
DUPS:600A MLO277/480V42 KAIC
112.5 KVA480V:120/208VK-4 RATED
200A 200A
75 KVA480V:120/208VK-4 RATED
225A
112.5 KVA480V:120/208VK-4 RATED
400A
NEW EATON IFS 277/480 V, 3Ø, 4W 600A MLO, 42 KAIC PNL DUPS, W/ TWO 112.5KVA AND TWO 75 KVA 480V:120/208 V XFMRS. PROVIDE FOUR 42 POLE,PANELS WITH CIRCUIT BREAKERS AND ACCESSORIES AS SCHEDULED
PANEL'LUA1'
225A FTL, TYP OF 3
PANEL'LUA4'
PANEL'LUA3'
PANEL'LUA2'
400A FEEDER C/B.
600A, 277/480V, 3Ø,4W MANUALLY
OPERATED DOUBLETHROW SWITCH
BUSWAY A-E(3-12)
BUSWAY A-K(16-27)
BUSWAY A-K(36-45)
NEW XFMR112.5 KVA208/120V.K-4
K-4 K-4 K-4
02-ALTERNATIVE EQUIPMENT DESIGNSCALE: NONE
200AF/3P/F150 A
BUSWAY A-J(3-12)
175A
208V, 3P, 400ANEMA '1' ENCLOSED
C/B
200AF/3P/F175 A
NEW PNL 'PAC'
BUSWAY A-J(3-12)
BUSWAY A-K(36-45)
BUSWAY A-K(16-27)
BUSWAY A-E(3-12)
PP10 PP9
GENERAL NOTES1. EQUIPMENT SHOWN AS DASHED IS
EXISTING.2. EQUIPMENT SHOWN IN SOLID LINE SHALL BE
PROVIDED AS NEW.3. PANELBOARDS SCEDHEUDL
NOTES:1. REFER TO DETAIL 01 FOR FEEDER REQUIREMENTS AND OTHER CONNECTIONS TO EQUIPMENT.
65 KAIC
30AF/3P/FSS
30AF/3P/FSS
CR
AC
,LIE
BE
RT
#1
CR
AC
,LIE
BE
RT
#2
PANELNEW
200AF/3P/F200 A
'LUA2'PANELNEW
'LUA3'PANELNEW
'LUA4'PANELNEW
TRACK BUSWAYEND CABLE TAPBOX., TYP. OF 4
ARL:
K:\21
5\215
0490
1\E-R
ISER
NEW
WOR
K
Plott
edBy
:Sha
wnSe
greti|
4/10/0
8|9:1
8PM
EXISTING PANELBOARD SCHEDULE PP1VOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 350A 400A 10000 SURFACETYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ -R RECEPTACLES E EXISTING -M MECH EQUIP O OTHER -
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 EIXISTING BRANCH CKT 20A 1 A 1 20A EXISTING BRANCH CKT 23 | 20A 1 B 1 20A | 45 | 20A 1 C 1 20A | 67 | 20A 1 A 1 20A | 89 | 20A 1 B 1 20A | 1011 | 20A 1 C 1 20A | 1213 | 20A 1 A 1 20A | 1415 | 20A 1 B 1 20A | 1617 | 20A 1 C 1 20A | 1819 | 20A 1 A 1 20A | 2021 | 20A 1 B 1 20A | 2223 | 20A 1 C 1 20A | 2425 | 20A 1 A 1 20A | 2627 | 20A 2 B 1 20A | 2829 | C 1 20A | 3031 | 20A 2 A 2 30A | 3233 | B | 3435 | 20A 1 C 1 20A | 3637 | 20A 3 A 1 20A | 3839 | B 1 20A | 4041 V C 1 20A V 42
EXISTING PANELBOARD SCHEDULE PP2VOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 - 350A 10000 SURFACETYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ -R RECEPTACLES E EXISTING -M MECH EQUIP O OTHER -
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 EIXISTING BRANCH CKT 20A 1 A 1 30A EXISTING BRANCH CKT 23 | 20A 1 B 1 20A | 45 | 20A 1 C 1 20A | 67 | 20A 1 A 1 20A | 89 | 20A 1 B 1 20A | 1011 | 20A 1 C 1 20A | 1213 V 20A 1 A 1 20A | 1415 SPACE B 1 20A | 1617 EIXISTING BRANCH CKT 30A 1 C 1 20A | 1819 | 30A 1 A 1 20A | 2021 | 30A 1 B 1 20A | 2223 | 30A 1 C 1 20A | 2425 | 30A 1 A 1 20A | 2627 | 30A 1 B 1 20A | 2829 | 30A 2 C 2 30A | 3031 | A | 3233 | 30A 2 B 2 30A | 3435 | C V 3637 | 20A 1 A 1 30A SPACE 3839 | 20A 1 B 1 | 4041 V 20A 1 C 1 20A V 42
EXISTING PANELBOARD SCHEDULE PP3VOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 - 350A 10000 SURFACETYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ FED FROM PP4R RECEPTACLES E EXISTING -M MECH EQUIP O OTHER -
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 EXISTING BRANCH CKT 30A 2 A 2 30A EXISTING BRANCH CKT 23 | B | 45 | 30A 2 C 2 30A | 67 | A | 89 | 30A 2 B 2 30A | 1011 | C | 1213 | 30A 2 A 2 30A | 1415 V B V 1617 SPACE C SPACE 1819 EXISTING PANEL PP10 150A 3 A 3 60A EXISTING BRANCH CKT 2021 SIX POLE SPACES B | 2223 | C | 2425 | A 3 60A | 2627 | B | 2829 V C | 3031 EXISTING PANEL PP7 100A 3 A 3 60A | 3233 ROOM 59 B | 3435 C | 3637 EXISTING PANEL P4 100A 3 A 3 60A | 3839 ROOM 58 B | 4041 C V 42
EXISTING PANELBOARD SCHEDULE PP4VOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 350A - 10000 SURFACE - - -TYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ -R RECEPTACLES E EXISTING -M MECH EQUIP O OTHER -
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 EXISTING BRANCH CKT 20A 1 A 1 20A EXISTING BRANCH CKT 23 | 20A 1 B 1 20A | 45 | 20A 1 C 1 30A | 67 | 20A 1 A 1 30A | 89 | 30A 2 B 1 30A | 1011 | C 1 30A | 1213 | 30A 2 A 1 20A | 1415 | B 1 20A | 1617 | 30A 2 C 2 30A | 1819 | A | 2021 | 20A 2 B 2 30A | 2223 | C | 2425 | 20A 1 A 2 30A | 2627 | 20A 1 B | 2829 | 30A 2 C 2 30A | 3031 | A | 3233 | 30A 2 B 1 20A | 3435 | C 1 20A | 3637 | 30A 3 A 1 20A | 3839 | B 1 20A | 4041 V C 1 20A V 42
EXISTING PANELBOARD SCHEDULE PP5VOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 - 225A 10000 SURFACE - - -TYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ FED FROM PP6R RECEPTACLES E EXISTING -M MECH EQUIP O OTHER -
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 EIXISTING BRANCH CKT 20A 1 A 1 20A EXISTING BRANCH CKT 23 | 20A 1 B 1 20A | 45 | 20A 1 C 1 20A | 67 | 20A 1 A 1 20A | 89 | 20A 1 B 1 20A | 1011 | 20A 1 C 1 20A | 1213 | 30A 3 A 3 30A | 1415 | B | 1617 | C | 1819 | 30A 3 A 3 30A | 2021 | B | 2223 | C | 2425 | 30A 3 A 3 30A | 2627 | B | 2829 | C | 3031 | 20A 1 A 2 60A | 3233 | 20A 1 B | 3435 | 30A 2 C 2 60A | 3637 | A V 3839 | 30A 2 B 1 20A SPACE 4041 V C 1 20A SPACE 42
EXISTING PANELBOARD SCHEDULE PP6VOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 225A - 10000 SURFACE - - -TYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ -R RECEPTACLES E EXISTING -M MECH EQUIP O OTHER -
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 EIXISTING BRANCH CKT 30A 2 A 1 20A EXISTING BRANCH CKT 23 | B 1 20A | 45 | 30A 2 C 1 20A | 67 | A 1 20A | 89 | 30A 2 B 1 20A | 1011 | C 1 20A | 1213 | 30A 2 A 1 20A | 1415 | B 1 20A | 1617 | 30A 2 C 1 20A | 1819 | A 1 20A | 2021 | 20A 1 B 1 20A | 2223 | 20A 1 C 1 20A | 2425 | 20A 1 A 1 20A | 2627 | 20A 1 B 1 20A | 2829 | 20A 1 C 1 20A | 3031 | 20A 1 A 1 20A | 3233 | 20A 1 B 1 20A | 3435 | 20A 1 C 1 20A | 3637 | 100A 3 A 3 30A | 3839 | B | 4041 V C V 42
GENERAL NOTES1. WHERE EXISTING PANELS ARE SHOWN TO BE RELOCATED OR RELOCATED AND REPLACED WITH NEW PANELBOARDS, ALL EXISTING BRANCH
CIRCUITS SHALL BE RELOCATED FROM THE CURRENT PANELBOARD SOURCE LOCATION AND RE-FED/RECONNECTED TO THE SAME PANELBAORDDESIGNATION, POLE LOCATION, AND CIRCUIT BREAKER UNLESS NOTED OTHERWISE. FOR EACH BRANCH CIRCUIT AFFECTED BY THE PANELBOARDRELOCATION, THE CONTRACTOR SHALL PROVIDE ADDITIONAL CONDUIT AND CONDUCTORS MATCHING EXISTING AND SHALL BE PROVIDED PERCODE.
1.1. FOR PRICING PURPOSES, CIRCUITS SCHEDULED TO BE RELOCATED THAT ARE PROTECTED WITH 15A OR 20A C/B, THE CONTRACTOR SHALLPROVIDE RELOCATION OF A #12 AWG PHASE CONDUCTOR PER POLE, AND A #12 NEUTRAL & #12 GND W/ 3/4" C.. FOR CIRCUITS PROTECTEDBY 25A OR 30A, USE #10 AWG PER Ø, NETURAL, AND GND., WITH 3/4"C. FOR CIRCUITS 35A TO 40A USE #8 AWG PER Ø AND NEUTRAL WITH#10 AWG GND IN 3/4" C., CIRCUITS 45A TO 50A USE #6 AWG PER Ø AND NETURAL WITH #10 AWG GND IN 1" C.. CIRCUITS 60A TO 70A SHALLUSE #4 AWG PER Ø AND NEUTRAL, WITH #8 AWG GND IN 1" C.. FOR LARGER CIRCUITS REFER TO THE RISER DIAGRAM. INCLUDE WITH EACHCIRCUIT RELOCATED FOR PRICING PURPOSES A MINIMUM OF 150' OF CONDUCTOR AND EMT CONDUIT LENGTH REQUIRED AT A MINIMUMTO BE INSTALLED AS NEW IN ORDER TO FACILITATE RELOCATION OF BRANCH CIRCUITS.
2. DEVICES SHOWN ON EXISTING REPLACEMENT PANEL BOARDS, THAT ARE SCHEDULED TO BE RELOCATED, ARE PROVIDED FOR ESTIMATINGPURPOSES. PRIOR TO RELEASE OF REPLACEMENT PANELBOARDS SCHEDULED TO BE RELOCATED, THE CONTRACTOR SHALL FIELD VERIFY EACHEXISTING PANEL BOARDS'S BRANCH DEVICE AMPERE RATING & QUANTITY OF POLES PER DEVICE. ALSO, THE CONTRACTOR SHALL FIELD VERIFYTHE POLE LOCATION OF EACH DEVICE WITHIN EACH EXISTING PANEL BOARD FOR RELOCATION. THE CONTRACTOR SHALL INCLUDE FIELD VERIFIEDINFORMATION OF EXISTING TO BE RELOCATED, AND EXISTING TO BE RELOCATED AND REPLACED WITHIN PANEL BOARD SUBMITTALINFORMATION TO CONFIRM DEVICE QUANTITIES, POLES, AND POLE LOCATIONS AS THE EXISTING CONDITIONS IN THE FIELD.
ARL:
K:\21
5\215
0490
1\E-S
ched
ules
Plott
edBy
:Sha
wnSe
greti|
4/10/0
8|9:1
8PM
EXISTING PANELBOARD SCHEDULE PP7VOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 - 250A 10000 SURFACETYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ -R RECEPTACLES E EXISTING -M MECH EQUIP O OTHER -
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) P TRIP SERVED
1 EIXISTING BRANCH CKT 30A 3 A 3 60A EXISTING BRANCH CKT 23 | B | 45 | C | 67 | 60A 3 A 3 60A | 89 | B | 1011 | C | 1213 | 30A 3 A 3 30A | 1415 | B | 1617 | C | 1819 | 30A 3 A 3 30A | 2021 | B | 2223 | C | 2425 | 30A 3 A 1 20A | 2627 | B 1 20A | 2829 | C 2 20A | 3031 | 60A 3 A | 3233 | B 1 30A | 3435 | C 2 20A | 3637 | 50A 3 A | 3839 | B 2 30A | 4041 V C V 42
EXISTING PANELBOARD SCHEDULE PP8VOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 150A - 10000 SURFACETYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ -R RECEPTACLES E EXISTING -M MECH EQUIP O OTHER -
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 EIXISTING BRANCH CKT 30A 3 A 2 30A EXISTING BRANCH CKT 23 | B | 45 | C 2 30A | 67 | 30A 2 A | 89 | B 2 30A | 1011 | 30A 2 C | 1213 | A 2 30A | 1415 | 30A 2 B | 1617 | C 2 30A | 1819 | 20A 1 A | 2021 | 20A 1 B 1 20A | 2223 | 20A 1 C 1 20A | 2425 | 20A 2 A 1 20A | 2627 | B 1 20A | 2829 | 20A 2 C 2 30A | 3031 | A | 3233 | 20A 1 B 1 20A | 3435 | 20A 1 C 1 20A | 3637 | 50A 3 A 3 50A | 3839 | B | 4041 V C V 42
EXISTING PANELBOARD SCHEDULE PP9VOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 - 250A 10000 SURFACETYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ -R RECEPTACLES E EXISTING -M MECH EQUIP O OTHER -
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 EIXISTING BRANCH CKT 20A 2 A 2 20A EXISTING BRANCH CKT 23 | B 45 | 30A 2 C 1 20A SPACE 67 | A 1 20A | 89 | 30A 2 B 1 20A | 1011 | C 1 20A | 1213 | 20A 2 A 1 20A | 1415 | B 1 20A | 1617 | 20A 2 C 1 20A | 1819 | A 1 20A | 2021 | 20A 2 B 1 20A | 2223 V C 1 20A | 2425 SPACE A 1 20A | 2627 | B 1 20A | 2829 V C 1 20A | 3031 EIXISTING BRANCH CKT 30A 3 A 1 20A | 3233 | B 1 20A V 3435 | C 2 60A EXISTING BRANCH CKT 3637 | 30A 3 A | 3839 | B 2 60A | 4041 V C V 42
EXISTING PANELBOARD SCHEDULE PP10VOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 - 225A 10000 SURFACETYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ -R RECEPTACLES E EXISTING -M MECH EQUIP O OTHER -
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 EIXISTING BRANCH CKT 20A 2 A 3 20A EXISTING BRANCH CKT 23 | B | 45 | 20A 2 C | 67 | A 2 20A | 89 | 20A 2 B | 1011 | C 2 20A | 1213 | 30A 2 A | 1415 | B 3 30A | 1617 | 30A 2 C | 1819 | A | 2021 | 30A 3 B 3 30A | 2223 | C | 2425 | A | 2627 | 30A 3 B 3 30A | 2829 | C | 3031 V A | 3233 SPACE 20A 1 B 3 30A | 3435 | 20A 1 C | 3637 | 20A 1 A | 3839 V 20A 1 B 2 20A | 4041 EIXISTING BRANCH CKT 20A 1 C V 42
VOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF120 208 3 4 125A - 10000 SURFACE
TYPE LEGEND REMARKSL LIGHTING K KITCHEN EQ -R RECEPTACLES E EXISTING -M MECH EQUIP O OTHER -
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 EIXISTING BRANCH CKT 20A 1 A 1 20A EXISTING BRANCH CKT 23 | 20A 1 B 1 20A | 45 | 20A 1 C 2 30A | 67 | 30A 2 A | 89 | B 3 30A | 1011 | 20A 2 C | 1213 | A | 1415 | 20A 1 B 1 30A | 1617 | 20A 1 C 1 20A | 1819 | 20A 3 A 1 20A | 2021 | B 1 20A | 2223 V C 1 20A V 24
EXISTING PANELBOARD SCHEDULE P5VOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 400A 400A 10000 SURFACETYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ -R RECEPTACLES E EXISTING -M MECH EQUIP O OTHER -
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 EIXISTING BRANCH CKT 20A 1 A 3 100A EXISTING BRANCH CKT 23 | 60A 3 B | 45 | C | 67 | A 3 30A | 89 | 60A 3 B | 1011 | C | 1213 | A 1 20A | 1415 | 60A 2 B 1 20A | 1617 | C 1 20A | 1819 | 20A 1 A 1 20A | 2021 | 20A 1 B 1 20A | 2223 | 20A 1 C 3 60A | 2425 | 30A 3 A | 2627 | B | 2829 | C 3 30A | 3031 | 30A 3 A | 3233 | B | 3435 | C 3 30A | 3637 | 30A 3 A | 3839 | B | 4041 V C 1 20A V 42
GENERAL NOTES1. WHERE EXISTING PANELS ARE SHOWN TO BE RELOCATED OR RELOCATED AND REPLACED WITH NEW PANELBOARDS, ALL EXISTING BRANCH
CIRCUITS SHALL BE RELOCATED FROM THE CURRENT PANELBOARD SOURCE LOCATION AND RE-FED/RECONNECTED TO THE SAME PANELBAORDDESIGNATION, POLE LOCATION, AND CIRCUIT BREAKER UNLESS NOTED OTHERWISE. FOR EACH BRANCH CIRCUIT AFFECTED BY THE PANELBOARDRELOCATION, THE CONTRACTOR SHALL PROVIDE ADDITIONAL CONDUIT AND CONDUCTORS MATCHING EXISTING AND SHALL BE PROVIDED PERCODE.
1.1. FOR PRICING PURPOSES, CIRCUITS SCHEDULED TO BE RELOCATED THAT ARE PROTECTED WITH 15A OR 20A C/B, THE CONTRACTOR SHALLPROVIDE RELOCATION OF A #12 AWG PHASE CONDUCTOR PER POLE, AND A #12 NEUTRAL & #12 GND W/ 3/4" C.. FOR CIRCUITS PROTECTEDBY 25A OR 30A, USE #10 AWG PER Ø, NETURAL, AND GND., WITH 3/4"C. FOR CIRCUITS 35A TO 40A USE #8 AWG PER Ø AND NEUTRAL WITH#10 AWG GND IN 3/4" C., CIRCUITS 45A TO 50A USE #6 AWG PER Ø AND NETURAL WITH #10 AWG GND IN 1" C.. CIRCUITS 60A TO 70A SHALLUSE #4 AWG PER Ø AND NEUTRAL, WITH #8 AWG GND IN 1" C.. FOR LARGER CIRCUITS REFER TO THE RISER DIAGRAM. INCLUDE WITH EACHCIRCUIT RELOCATED FOR PRICING PURPOSES A MINIMUM OF 150' OF CONDUCTOR AND EMT CONDUIT LENGTH REQUIRED AT A MINIMUMTO BE INSTALLED AS NEW IN ORDER TO FACILITATE RELOCATION OF BRANCH CIRCUITS.
2. DEVICES SHOWN ON EXISTING REPLACEMENT PANEL BOARDS, THAT ARE SCHEDULED TO BE RELOCATED, ARE PROVIDED FOR ESTIMATINGPURPOSES. PRIOR TO RELEASE OF REPLACEMENT PANELBOARDS SCHEDULED TO BE RELOCATED, THE CONTRACTOR SHALL FIELD VERIFY EACHEXISTING PANEL BOARDS'S BRANCH DEVICE AMPERE RATING & QUANTITY OF POLES PER DEVICE. ALSO, THE CONTRACTOR SHALL FIELD VERIFYTHE POLE LOCATION OF EACH DEVICE WITHIN EACH EXISTING PANEL BOARD FOR RELOCATION. THE CONTRACTOR SHALL INCLUDE FIELD VERIFIEDINFORMATION OF EXISTING TO BE RELOCATED, AND EXISTING TO BE RELOCATED AND REPLACED WITHIN PANEL BOARD SUBMITTALINFORMATION TO CONFIRM DEVICE QUANTITIES, POLES, AND POLE LOCATIONS AS THE EXISTING CONDITIONS IN THE FIELD.
ARL:
K:\21
5\215
0490
1\E-S
ched
ules
Plott
edBy
:Sha
wnSe
greti|
4/10/0
8|9:1
8PM
EXISTING PANELBOARD SCHEDULE DUPSVOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
277 208 3 4 - 600A 22000 SURFACETYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ FED FROM UPSR RECEPTACLES E EXISTING -M MECH EQUIP O OTHER -
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 SPACE A SPACE 23 | B | 45 | C | 67 | A | 89 | B | 1011 V C | 1213 EXISTING 112.5 KVA 175A 3 A | 1415 PP1/2 B | 1617 C V 1819 EXISTING 112.5 KVA 175A 3 A 3 125A EXISTING 75 KVA 2021 PP3/4 B PP5/6 2223 C 24
EXISTING PANELBOARD SCHEDULE DP MECHVOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
277 480 3 4 600A - 14 KAIC SURFACETYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ -R RECEPTACLES E EXISTING -M MECH EQUIP O OTHER -
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 EXISTING PANEL P1 250A 3 A 3 250A EXISTING CH ATS 23 B 45 C 67 EXISTING PNL P3 70A 3 A 3 50A EXISTING PUMP P1 89 B 1011 C 1213 EXISTING PUMP P2 50A 3 A 3 50A EXISTING PUMP P3 1415 B 1617 C 1819 EXISTING ELEVATOR 50A 3 A 3 50A EXISTING AHU 1 2021 B 2223 C 2425 EXISTING BRANCH CKT 50A 3 A 3 50A EXISTING PUMP P4 2627 B 2829 C 3031 EXISTING BRANCH CKT 50A 3 A 3 80A EXISTING PUMP P8 3233 B 3435 C 3637 EXISTING BRANCH CKT 80A 3 A 3 80A EXISTING BRANCH CKT 3839 B 4041 C 4243 EXISTING BRANCH CKT 80A 3 A 3 50A EXISTING BRANCH CKT 4445 B 4647 C 48
NEW PANELBOARD SCHEDULE LUA2VOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 225A - 10000 SURFACETYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ PROVIDE FEED THROUGH LUGS WITH LUGS SIZES NECESSARY TOR RECEPTACLES E EXISTING FEED THROUGH TO TRACK BUSWAY (W/ 150% NETURAL FTL)M MECH EQUIP O OTHER PROVIDE 150% NETURAL BUS, PROVIDE GND BUS.
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 SPARE 20A 1 A 1 20A SPARE 23 | 20A 1 B 1 20A | 45 | 20A 1 C 1 20A | 67 | 20A 1 A 1 20A | 89 V 20A 1 B 1 20A V 1011 SPACE 20A 1 C 1 20A SPACE 1213 | 20A 1 A 1 20A | 1415 | 20A 1 B 1 20A | 1617 | 20A 1 C 1 20A | 1819 | 20A 1 A 1 20A | 2021 | 20A 1 B 1 20A | 2223 | 20A 1 C 1 20A | 2425 | 20A 1 A 1 20A | 2627 | 20A 1 B 1 20A | 2829 | 20A 1 C 1 20A | 3031 | 20A 1 A 1 20A | 3233 | 20A 1 B 1 20A | 3435 | 20A 1 C 1 20A | 3637 | 20A 1 A 1 20A | 3839 | 20A 1 B 1 20A | 4041 V 20A 1 C 1 20A V 42
NEW PANELBOARD SCHEDULE LUA4VOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 - 400A 10000 SURFACETYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ PROVIDE FTL (MIN TWO #4/0 LUGS/PH , TWO #350 KCMIL NEUT.) FOR CONNECTION TOR RECEPTACLES E EXISTING POWER BAR BUSWAY FEEDER AND PP9'S AND LOCAL FUSED SWITCHES. PROVIDE GND BUS.M MECH EQUIP O OTHER PROVIDE 150% NEUTRAL BUS
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 SPARE 20A 1 A 1 20A SPARE 23 | 20A 1 B 1 20A | 45 | 20A 1 C 1 20A | 67 | 20A 1 A 1 20A | 89 V 20A 1 B 1 20A V 1011 SPACE 20A 1 C 1 20A SPACE 1213 | 20A 1 A 1 20A | 1415 | 20A 1 B 1 20A | 1617 V 20A 1 C 1 20A | 1819 EXISTING PANEL FEEDER 150A 3 A 1 20A | 2021 SIX POLE SPACES B 1 20A | 2223 | C 1 20A | 2425 | A 1 20A | 2627 | B 1 20A | 2829 V C 1 20A | 3031 SPARE 100A 3 A 1 20A | 3233 B 1 20A | 3435 C 1 20A | 3637 EXISTING PANEL P4 100A 3 A 1 20A | 3839 ROOM 58 B 1 20A | 4041 C 1 20A V 42
NEW PANELBOARD SCHEDULE LUA3VOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 400A - 10000 SURFACE - - -TYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ [PROVIDE 150% NEUTRAL BUS, PROVIDE GND BUSR RECEPTACLES E EXISTING PROVIDE FEED THROUGH LUGSM MECH EQUIP O OTHER
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 SPARE 20A 1 A 1 20A SPARE 23 | 20A 1 B 1 20A | 45 | 20A 1 C 1 20A | 67 | 20A 1 A 1 20A | 89 | 20A 1 B 1 20A V 1011 | 20A 1 C 1 20A SPACE 1213 | 100A 3 A 1 20A | 1415 | B 1 20A | 1617 V C 1 20A | 1819 SPACE 20A 1 A 1 20A | 2021 | 20A 1 B 1 20A | 2223 | 20A 1 C 1 20A | 2425 | 20A 1 A 1 20A | 2627 | 20A 1 B 1 20A | 2829 | 20A 1 C 1 20A | 3031 | 20A 1 A 1 20A | 3233 | 20A 1 B 1 20A | 3435 | 20A 1 C 1 20A | 3637 | 20A 1 A 1 20A | 3839 | 20A 1 B 1 20A | 4041 V 20A 1 C 1 20A V 42
NEW PANELBOARD SCHEDULE PACVOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 225A - 10000 SURFACE - - -TYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ PROVIDE NEUTRAL BUS, GROUND BUS, AND FTL. PROVIDE MULTIPLE EMTR RECEPTACLES E EXISTING CONDUITS FROM PANEL TO BELOW RAISED FLOOR WIREWAY, WITH LIQUIDM MECH EQUIP O OTHER TIGHT PLENUM RATED CABLE FOR CONNECTION TO IN-ROW COOLERS
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 NEW IN ROW AC UNIT M 3#12 1/2" 15A 3 913 A 913 3 15A 1/2" 3#12 M NEW IN ROW AC UNIT 23 (PDLK) 913 B 913 (PDLK) 45 913 C 913 67 NEW IN ROW AC UNIT M 3#12 1/2" 15A 3 913 A 913 3 15A 1/2" 3#12 M NEW IN ROW AC UNIT 89 (PDLK) 913 B 913 (PDLK) 1011 913 C 913 1213 NEW IN ROW AC UNIT M 3#12 1/2" 15A 3 913 A 913 3 15A 1/2" 3#12 M NEW IN ROW AC UNIT 1415 (PDLK) 913 B 913 (PDLK) 1617 913 C 913 1819 NEW IN ROW AC UNIT M 3#12 1/2" 15A 3 913 A 913 3 15A M FUTURE IN ROW AC UNIT 2021 (PDLK) 913 B 913 (PDLK) 2223 913 C 913 SPARE C/B DEVICE 2425 HUMDIFIER M 4#3 1" 60A 3 5008 A 913 3 15A M FUTURE IN ROW AC UNIT 2627 #8 G. 5008 B 913 (PDLK) 2829 5008 C 913 SPARE C/B DEVICE 3031 SPACE 20A 1 A 1 20A SPARE 3233 | 20A 1 B 1 20A | 3435 | 20A 1 C 1 20A V 3637 | 20A 1 A 588 1 20A 1/2" 2#12 M HUMDIFER BLOWER 3839 | 20A 1 B 900 1 20A 1/2" 2#12 R RECEPT CKT 4041 V 20A 1 C 300 1 20A 1/2" 2#12 M CONDENSATE PUMPS 42
PP B C TOTALCONNECTED LOAD (VA) 13810 14122 13522 41453
LOAD SUBLOADS (VA) CONN SIZING SIZING NOTESTYPE (VA) PNL PNL PNL LD(VA) FACTOR LOAD (VA) * 1ST 10KVA @ 100%, REMAINING @ 50%LIGHTING 0 - - - 0 125% 0 ** SIZE. FAC. IN ACCORDANCE TO NEC 220-20RECEPTACLES 900 - - - 900 * 900 (PDLK) - PROVIDE PADLOCKING HASP HARDWAREMECH EQUIP 40553 - - - 40553 125% 50692KITCHEN EQ 0 - - - 0 100% 0 **# OF KITCH EQ 0 - - - 0EXISTING 0 - - - 0 125% 0OTHER 0 - - - 0 100% 0
CONNECTED TOTAL (VA) 41453 51592 SIZING TOTAL (VA)CONNECTED AMPACITY (A) 115.06 143.20 SIZING AMPACITY (A)
DEMAND TOTAL (VA) 51592DEMAND AMPACITY (A) 143.20
GENERAL NOTES1. WHERE EXISTING PANELS ARE SHOWN TO BE RELOCATED OR RELOCATED AND REPLACED WITH NEW PANELBOARDS, ALL EXISTING BRANCH
CIRCUITS SHALL BE RELOCATED FROM THE CURRENT PANELBOARD SOURCE LOCATION AND RE-FED/RECONNECTED TO THE SAME PANELBAORDDESIGNATION, POLE LOCATION, AND CIRCUIT BREAKER UNLESS NOTED OTHERWISE. FOR EACH BRANCH CIRCUIT AFFECTED BY THE PANELBOARDRELOCATION, THE CONTRACTOR SHALL PROVIDE ADDITIONAL CONDUIT AND CONDUCTORS MATCHING EXISTING AND SHALL BE PROVIDED PERCODE.
1.1. FOR PRICING PURPOSES, CIRCUITS SCHEDULED TO BE RELOCATED THAT ARE PROTECTED WITH 15A OR 20A C/B, THE CONTRACTOR SHALLPROVIDE RELOCATION OF A #12 AWG PHASE CONDUCTOR PER POLE, AND A #12 NEUTRAL & #12 GND W/ 3/4" C.. FOR CIRCUITS PROTECTEDBY 25A OR 30A, USE #10 AWG PER Ø, NETURAL, AND GND., WITH 3/4"C. FOR CIRCUITS 35A TO 40A USE #8 AWG PER Ø AND NEUTRAL WITH#10 AWG GND IN 3/4" C., CIRCUITS 45A TO 50A USE #6 AWG PER Ø AND NETURAL WITH #10 AWG GND IN 1" C.. CIRCUITS 60A TO 70A SHALLUSE #4 AWG PER Ø AND NEUTRAL, WITH #8 AWG GND IN 1" C.. FOR LARGER CIRCUITS REFER TO THE RISER DIAGRAM. INCLUDE WITH EACHCIRCUIT RELOCATED FOR PRICING PURPOSES A MINIMUM OF 150' OF CONDUCTOR AND EMT CONDUIT LENGTH REQUIRED AT A MINIMUMTO BE INSTALLED AS NEW IN ORDER TO FACILITATE RELOCATION OF BRANCH CIRCUITS.
2. DEVICES SHOWN ON EXISTING REPLACEMENT PANEL BOARDS, THAT ARE SCHEDULED TO BE RELOCATED, ARE PROVIDED FOR ESTIMATINGPURPOSES. PRIOR TO RELEASE OF REPLACEMENT PANELBOARDS SCHEDULED TO BE RELOCATED, THE CONTRACTOR SHALL FIELD VERIFY EACHEXISTING PANEL BOARDS'S BRANCH DEVICE AMPERE RATING & QUANTITY OF POLES PER DEVICE. ALSO, THE CONTRACTOR SHALL FIELD VERIFYTHE POLE LOCATION OF EACH DEVICE WITHIN EACH EXISTING PANEL BOARD FOR RELOCATION. THE CONTRACTOR SHALL INCLUDE FIELD VERIFIEDINFORMATION OF EXISTING TO BE RELOCATED, AND EXISTING TO BE RELOCATED AND REPLACED WITHIN PANEL BOARD SUBMITTALINFORMATION TO CONFIRM DEVICE QUANTITIES, POLES, AND POLE LOCATIONS AS THE EXISTING CONDITIONS IN THE FIELD.
ARL:
K:\21
5\215
0490
1\E-S
ched
ules
Plott
edBy
:Sha
wnSe
greti|
4/10/0
8|9:1
8PM
POWER BAR BUSWAY SCHEDULE OF PLUG-INSVOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 - 400A 22000 SURFACEREMARKS
1. PROVIDE SCHEDULED PLUG-INS WITH MINIMUM OF 15' OF CORD FOR CONNECTION TO RACKEQUIPMENT2. DEVICES SHALL BE RATED 10 KAIC.3. FOR 2 POLE PLUG-INS, PROVIDE ROTATION FOR EACH PLUG-IN UNIT CONNECTION TO BUSWAY A-B,B-C, C-A.
RACK
ALPH
ANUM
ERIC
ALDE
SIGN
ATIO
NWIRING DIVICE CONNECTION
CORD
LENG
TH
WIR
E
QUAN
TITY
OFW
IRIN
GDE
VICE
CONN
ECTI
ONS
PER
RACK
QUAN
TITY
OFDE
DICA
TED
C/B
AND
BRAN
CHCI
RCUI
TSPE
RPL
UG-IN
EA. C/BDEVICE
POW
ERBA
RPL
UG-IN
MOD
ULE
QUAN
TITY
-WID
TH(IN
CHES
)
POW
ERBA
RPL
UG-IN
MOD
ULE
QUAN
TITY
-WID
TH(IN
CHES
)
EA. C/BDEVICE
QUAN
TITY
OFDE
DICA
TED
C/B
AND
BRAN
CHCI
RCUI
TSPE
RPL
UG-IN
QUAN
TITY
OFW
IRIN
GDE
VICE
CONN
ECTI
ONS
PER
RACK
WIR
E
CORD
LENG
TH
WIRING DIVICE CONNECTION
RACK
ALPH
ANUM
ERIC
ALDE
SIGN
ATIO
NREQUIREMENT
TRIP P P TRIP
REQUIREMENT
E3 IEC60309 208V, 3 PH 15' 3#6 2 2 60A 3 1-12" 2-12" 3 60A 2 4 3#6 15' K16E4 IEC60309 208V, 3 PH 15' 3#6 2 2 60A 3 1-12" 2-12" 3 60A 2 4 3#6 15' IEC60309 208V, 3 PH K18E5 IEC60309 208V, 3 PH 15' 3#6 2 2 60A 3 1-12" 2-12" 3 60A 2 4 3#6 15' IEC60309 208V, 3 PH K19E7 NEMA L15-30R 15' 5#10 2 2 30A 3 1-12" 2-12" 3 60A 2 4 3#6 15' IEC60309 208V, 3 PH K20E8 NEMA L15-30R 15' 5#10 2 2 30A 3 1-12" 2-12" 3 60A 2 4 3#6 15' IEC60309 208V, 3 PH K21E9 NEMA L15-30R 15' 5#10 2 2 30A 3 1-12" 2-12" 3 60A 2 4 3#6 15' IEC60309 208V, 3 PH K22
E10 NEMA L6-30R 15' 3#10 4 2 30A 2 2-12" 2-12" 3 60A 2 4 3#6 15' IEC60309 208V, 3 PH K23E11 NEMA L15-30R 15' 5#10 2 2 30A 3 1-12" 1-12" 3 30A 2 2 5#10 15' NEMA L15-30R K24E12 IEC60309 208V, 3 PH 15' 3#6 2 2 60A 3 1-12" 2-12" 3 30A 2 4 5#10 15' NEMA L15-30R K25J3 FUTURE RACK 2-12" 3 30A 2 4 5#10 15' NEMA L15-30R K26J4 IEC60309 208V, 3 PH 15' 3#6 2 2 60A 3 1-12" 2-12" 2 30A 2 4 3#10 15' NEMA L6-30R K27J5 IEC60309 208V, 3 PH 15' 3#6 2 2 60A 3 1-12" 2-12" 3 60A 2 4 3#6 15' IEC60309 208V, 3 PH K36J6 IEC60309 208V, 3 PH 15' 3#6 2 2 60A 3 1-12" 2-12" 3 60A 2 4 3#6 15' IEC60309 208V, 3 PH K37J7 IEC60309 208V, 3 PH 15' 3#6 2 2 60A 3 1-12" 2-12" 3 60A 2 4 3#6 15' IEC60309 208V, 3 PH K38J8 IEC60309 208V, 3 PH 15' 3#6 2 2 60A 3 1-12" 2-12" 2 30A 2 4 3#10 15' NEMA L6-30R K40J9 IEC60309 208V, 3 PH 15' 3#6 2 2 60A 3 1-12" 2-12" 2 30A 2 4 3#10 15' NEMA L6-30R K41
J10 IEC60309 208V, 3 PH 15' 3#6 2 2 60A 3 1-12" 2-12" 2 30A 2 4 3#10 15' NEMA L6-30R K42J11 IEC60309 208V, 3 PH 15' 3#6 2 2 60A 3 1-12" FUTURE RACK K43J12 FUTURE RACK FUTURE RACK K44
FUTURE RACK K45
NEWPANELBOARD SCHEDULE LUA1VOLTAGE PHASE WIRE MCB (A) MLO (A) AIC MOUNTING MANUFAC. MDL # DWG REF
120 208 3 4 225A 10000 SURFACETYPE LEGEND REMARKS
L LIGHTING K KITCHEN EQ PROVIDE FEED THROUGH LUGS WITH LUGS SIZES NECESSARY TOR RECEPTACLES E EXISTING FEED THROUGH TO TRACK BUSWAY (W/ 150% NETURAL FTL)M MECH EQUIP O OTHER PROVIDE 150% NETURAL BUS, PROVIDE GND BUS.
CKT.
# ITEM
TYPE
WIR
E
COND
UIT CKT. BRK LOAD
PHAS
E LOAD CKT. BRK
COND
UIT
WIR
E
TYPE ITEM
CKT.
#
SERVED TRIP P (VA) (VA) P TRIP SERVED
1 SPARE 20A 1 A 1 20A SPARE 23 | 20A 1 B 1 20A | 45 | 20A 1 C 1 20A | 67 | 20A 1 A 1 20A | 89 V 20A 1 B 1 20A V 1011 SPACE 20A 1 C 1 20A SPACE 1213 | 20A 1 A 1 20A | 1415 | 20A 1 B 1 20A | 1617 | 20A 1 C 1 20A | 1819 | 20A 1 A 1 20A | 2021 | 20A 1 B 1 20A | 2223 | 20A 1 C 1 20A | 2425 | 20A 1 A 1 20A | 2627 | 20A 1 B 1 20A | 2829 | 20A 1 C 1 20A | 3031 | 20A 1 A 1 20A | 3233 | 20A 1 B 1 20A | 3435 | 20A 1 C 1 20A | 3637 | 20A 1 A 1 20A | 3839 | 20A 1 B 1 20A | 4041 V 20A 1 C 1 20A V 42
NOTES:1. PROVIDE CONNECTION REQUIRED RECEPTACLE AT THE END OF EACH CORD LENGT.2. IEC60309 CONNECTION MAY ALSO BE HUBBELL #HBL460C9W.
GENERAL NOTES1. WHERE EXISTING PANELS ARE SHOWN TO BE RELOCATED OR RELOCATED AND REPLACED WITH NEW PANELBOARDS, ALL EXISTING BRANCH
CIRCUITS SHALL BE RELOCATED FROM THE CURRENT PANELBOARD SOURCE LOCATION AND RE-FED/RECONNECTED TO THE SAME PANELBAORDDESIGNATION, POLE LOCATION, AND CIRCUIT BREAKER UNLESS NOTED OTHERWISE. FOR EACH BRANCH CIRCUIT AFFECTED BY THE PANELBOARDRELOCATION, THE CONTRACTOR SHALL PROVIDE ADDITIONAL CONDUIT AND CONDUCTORS MATCHING EXISTING AND SHALL BE PROVIDED PERCODE.
1.1. FOR PRICING PURPOSES, CIRCUITS SCHEDULED TO BE RELOCATED THAT ARE PROTECTED WITH 15A OR 20A C/B, THE CONTRACTOR SHALLPROVIDE RELOCATION OF A #12 AWG PHASE CONDUCTOR PER POLE, AND A #12 NEUTRAL & #12 GND W/ 3/4" C.. FOR CIRCUITS PROTECTEDBY 25A OR 30A, USE #10 AWG PER Ø, NETURAL, AND GND., WITH 3/4"C. FOR CIRCUITS 35A TO 40A USE #8 AWG PER Ø AND NEUTRAL WITH#10 AWG GND IN 3/4" C., CIRCUITS 45A TO 50A USE #6 AWG PER Ø AND NETURAL WITH #10 AWG GND IN 1" C.. CIRCUITS 60A TO 70A SHALLUSE #4 AWG PER Ø AND NEUTRAL, WITH #8 AWG GND IN 1" C.. FOR LARGER CIRCUITS REFER TO THE RISER DIAGRAM. INCLUDE WITH EACHCIRCUIT RELOCATED FOR PRICING PURPOSES A MINIMUM OF 150' OF CONDUCTOR AND EMT CONDUIT LENGTH REQUIRED AT A MINIMUMTO BE INSTALLED AS NEW IN ORDER TO FACILITATE RELOCATION OF BRANCH CIRCUITS.
2. DEVICES SHOWN ON EXISTING REPLACEMENT PANEL BOARDS, THAT ARE SCHEDULED TO BE RELOCATED, ARE PROVIDED FOR ESTIMATINGPURPOSES. PRIOR TO RELEASE OF REPLACEMENT PANELBOARDS SCHEDULED TO BE RELOCATED, THE CONTRACTOR SHALL FIELD VERIFY EACHEXISTING PANEL BOARDS'S BRANCH DEVICE AMPERE RATING & QUANTITY OF POLES PER DEVICE. ALSO, THE CONTRACTOR SHALL FIELD VERIFYTHE POLE LOCATION OF EACH DEVICE WITHIN EACH EXISTING PANEL BOARD FOR RELOCATION. THE CONTRACTOR SHALL INCLUDE FIELD VERIFIEDINFORMATION OF EXISTING TO BE RELOCATED, AND EXISTING TO BE RELOCATED AND REPLACED WITHIN PANEL BOARD SUBMITTALINFORMATION TO CONFIRM DEVICE QUANTITIES, POLES, AND POLE LOCATIONS AS THE EXISTING CONDITIONS IN THE FIELD.
ARL:
K:\21
5\215
0490
1\E-S
ched
ules
Plott
edBy
:Sha
wnSe
greti|
4/10/0
8|9:1
8PM
E-0.pdfE-0
E-1E-1
E-2E-2
E-3E-3
E-4E-4
E-5E-5
E-6E-6
E-7E-7
E-8E-8
E-9E-9
E-10E-10