PROJECT:
TITLE:
DRAWN BY: SOPREMA TECHNICAL SUPPORT, GGALLOWAY
NO.: DATE:REVISION:
DATE: 1.12.2017
SCALE: NTS
DRAWING NUMBER:
US.WSBS.03.14bUSAGE OF THIS DETAIL IS GOVERNED BY THE TERMS OF SERVICE FOR SOPREMA DETAILS.
PLEASE CONSULT THESE TERMS OF SERVICE PRIOR TO UTILIZING THIS DRAWING.
US CORPORATE ADDRESS310 QUADRAL DRIVE
WADSWORTH, OHIO 44281www.soprema.usTel:330.334.0066
W L L A M G R A N T A L L W A Y
DRAWING MUST BE VIEWED IN ADOBE READER TO ENABLE CUSTOM LAYERING
NOTES:1. SOPREMA DETAIL DRAWINGS: REFER TO SOPREMA AND OTHER RELATED PUBLISHED DOCUMENTATION, PRODUCT DATA SHEETS (PDS) AND SAFETY DATA SHEETS (SDS) FOR ADDITIONAL
INFORMATION. ALL DETAIL DRAWINGS AND RELATED INSTALLATION GUIDELINES ARE PROVIDED BY SOPREMA FOR THE SOLE PURPOSE OF ISSUING A SOPREMA WARRANTY. ACCORDINGLY, THEDETAIL DRAWINGS ARE NOT OFFERED, AND SHOULD NOT BE CONSIDERED, AS A SUBSTITUTE FOR PROFESSIONAL DESIGN SERVICES.
2. HOT WORK: THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING APPROPRIATE CONDITIONS TO UTILIZE HEAT-WELDING EQUIPMENT. REFER TO THE NRCA CERTA RECOMMENDATIONS, LOCALCODES AND BUILDING OWNER'S REQUIREMENTS FOR HOT WORK OPERATIONS.
3. PRIMER: WHERE NOT SHOWN OR INDICATED ON DETAIL DRAWINGS, REFER TO MATERIAL PRODUCT DATA SHEETS FOR PRIMER APPLICATION REQUIREMENTS4. FOR 90° TRANSITIONS, FLASHING PLIES MUST MEET THE FOLLOWING REQUIREMENTS: HEAT WELD OR SELF-ADHERED POLYESTER REINFORCED FLASHING BASE PLY AND FULLY REINFORCED
LIQUID APPLIED FLASHING CAP SHEET.5. SOPREMA RECOMMENDS 8 INCH VERTICAL FLASHING HEIGHTS BEYOND OVERBURDEN. FLASHING DETAILS SHOWN INCLUDE MINIMUM DIMENSIONS TO MEET WARRANTY REQUIREMENTS.
CONTACT SOPREMA FOR ADDITIONAL REQUIREMENTS.6. DO NOT APPLY ALSAN RS LIQUID APPLIED SYSTEMS OVER SBS MODIFIED BITUMEN MATERIALS ADHERED USING COLPLY OR COPLY MODIFIED ADHESIVES OR CEMENTS. HOT AIR WELD, TORCH
APPLY, OR ADHERE THE SBS MODIFIED BITUMEN MEMBRANE AND FLASHINGS WITH COLPLY EF IN ALL AREAS WHERE ALSAN RS WILL BE APPLIED.
CANT
WEATHERPROOF MEMBRANE
ROOF EDGE SYSTEM
EXTEND REINFORCING FABRIC AMINIMUM OF 8" ONTO CAP SHEET
ALSAN RS
CAP SHEETCAP SHEET
BASE PLYBASE PLY
2 PLY SBS MEMBRANE,NON-INSULATED,
PARAPET WALL WITH LIQUID FLASHING
BASE SHEET/ANCHOR SHEET
BASE SHEET/ANCHOR SHEET
BARRIER BOARD
DECKDECKDECKDECK
BARRIER BOARD
DECKDECK
BARRIER BOARD
DECKDECK
BARRIER BOARD
DECK
BARRIER BOARD
DECKDECK
BARRIER BOARD
BASE SHEET/ANCHOR SHEETBASE SHEET/ANCHOR SHEET
FASTEN AT 8" O.C.IN BOTH DIRECTIONS
FASTEN AT 8" O.C.IN BOTH DIRECTIONS
ALSAN RS
EXTEND ALSAN RS A MAXIMUM OF1/4" BEYOND REINFORCING FABRIC
EXTEND REINFORCING FABRIC AMINIMUM OF 4" BEYOND OVERBURDEN
EXTEND REINFORCING FABRIC AMINIMUM OF 8" ONTO CAP SHEET
EXTEND ALSAN RS A MAXIMUM OF1/4" BEYOND REINFORCING FABRIC
EXTEND REINFORCING FABRIC AMINIMUM OF 4" BEYOND OVERBURDEN
STRIP-IN ALL TRANSITIONS USING REINFORCEDLIQUID-APPLIED FLASHING MINIMUM2" VERTICALLY AND 2" DIAGONALLY
REINFORCING FABRICREINFORCING FABRIC
ALSAN RS
POLYESTER REINFOREDFLASHING BASE PLY
STRIP-IN ALL TRANSITIONS USINGSBS FLASHING MINIMUM
3" VERTICALLY AND 3" HORIZONTALLY
EXTEND REINFORCING FABRIC AMINIMUM OF 8" ONTO CAP SHEET
EXTEND ALSAN RS A MAXIMUM OF1/4" BEYOND REINFORCING FABRIC
EXTEND REINFORCING FABRIC AMINIMUM OF 4" BEYOND OVERBURDEN
REINFORCING FABRIC
ALSAN RS
POLYESTER REINFOREDFLASHING BASE PLY
STRIP-IN ALL TRANSITIONS USINGSBS FLASHING MINIMUM
3" VERTICALLY AND 3" HORIZONTALLY
EXTEND REINFORCING FABRIC AMINIMUM OF 8" ONTO CAP SHEET
EXTEND ALSAN RS A MAXIMUM OF1/4" BEYOND REINFORCING FABRIC
EXTEND REINFORCING FABRIC AMINIMUM OF 4" BEYOND OVERBURDEN
REINFORCING FABRIC
ALSAN RS
STRIP-IN ALL TRANSITIONS USING REINFORCEDLIQUID-APPLIED FLASHING MINIMUM
2" VERTICALLY AND 2" HORIZONTALLY
OVERBURDEN NOT SHOWNFOR CLARITY, REFER TOWATERPROOFINGOVDERBURDEN DETAILS
OVERBURDEN NOT SHOWNFOR CLARITY, REFER TOWATERPROOFINGOVDERBURDEN DETAILS