FOR BID/ PERMIT - MARCH 21, 2016
GALLAGHER STUDENT CENTER RENOVATION XAVIER UNIVERSITY
3800 VICTORY PARKWAY, CINCINNATI, OH 445207
1538 Alexandria Pike, Suite 11 Ft. Thomas, KY 41075 Tel: 859 442
8050 Fax: 859 442 8058 VICINITY MAP
CAMPUS MAP
NUMBER SHEET
A001 ARCHITECTURAL GENERAL NOTES, SYMBOLS & TYP DETAILS AD101
ARCHITECTURAL LEVEL 1 DEMOLITION PLAN
A101 LEVEL 1 ARCHITECTURAL FLOOR PLAN A102 LEVEL 1 REFLECTED
CEILING PLANS A103 INTERIOR ELEVATIONS A104 ARCHITECTURAL DETAILS
A105 ARCHITECTURAL DETAILS A106 THIRD FLOOR SHADE DETAILS A111 DOOR
SCHEDULE AND DETAILS
I101 INTERIOR FINISH SCHEDULE AND DETAILS I102 FOR REFERENCE -
STUDENT LOUNGE FURNITURE LAYOUT
FD101 FIRE PROTECTION- DEMOLITION- FIRST FLOOR F101 FIRE
PROTECTION- NEW- FIRST FLOOR
MD101 MECHANICAL- DEMOLITION- FIRST FLOOR M-101 MECHANICAL
DUCTWORK- NEW- FIRST FLOOR M-501 MECHANICAL DETAILS
E-001 ELECTRIC LEGEND E-501 ELECTRIC- DETAILS ED101 ELECTRIC-
DEMOLITION- FIRST FLOOR
EL101 ELECTRIC LIGHTING- NEW- FIRST FLOOR EL601 ELECTRIC LUMINAIRE
SCHEDULE
EP101 ELECTRIC POWER- NEW- FIRST FLOOR EP601 ELECTIRC- SINGLE LINE
DIAGRAM EP602 ELECTRIC PANEL SCHEDULES
DRAWING LIST
R1
TRAVEL DISTANCE 70'-0"
CONTRACTOR TO VERIFY ALL EXISTING RATED WALLS WITHIN SCOPE OF WORK
MEET RATED WALL REQUIREMENTS PER RATED WALLS SHOWN IN THE LIFE
SAFETY DRAWINGS. EXTEND EXISTING PARTITIONS AS REQUIRED TO
UNDERSIDE OF FLOOR/ROOF STRUCTURE ABOVE AND SEAL ALL PENETRATIONS
AS REQUIRED AT RATED WALLS.
2 HR FIRE RATED BARRIER ASSEMBLY (FIRE DAMPERS REQUIRED)
1 HR RATED PARTITION
Xavier University - Gallagher Center Student Center
Renovation
Building Code: All of the following references are to the Ohio
Building Code 2011(OBC) Ohio Mechanical Code 2011 (OMC)
Project Description: Partial Renovation on the First Level of the
existing building. Renovation of the existing campus Bookstore.
This area will be divided into approximate half. With one half of
the space to remain as the Bookstore with minimal renovation work,
finish replacement and finish refurbishment. The remaining half
will be renovated as a Student Lounge.
Note: No work affecting existing means of egress features. No
change to existing fire extinguishers and location. No work at
exterior, except minimal electrical work. No work at building
structure. No work at existing toilet rooms. No change to existing
atrium life safety design or smoke evac system. New work at Atrium
corridor wall will match existing design of 1-hour rating achieved
through rated walls and deluge sprinklers on either side of
borrowed lites meeting building code requirements.
Building Occupancy Classification: Mixed Use (Original Construction
2002): A-1, A-2, A-3, B, M, S-1, U
Construction Type: 2A
Accessibility: Barrier-free design
Lower Level Area: 29,445s.f.
Level One Area: 15,480s.f.
Level Two Area: 15,000s.f.
Level Three Area: 15,865s.f.
R EG
I T EC
EXPIRATION DATE 12/31/2017
ISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2 T 513.241.4474 F
513.241.0081
Drawn By
Checked By
Project Number
Client Number
3/ 21
/2 01
6 7:
51 :0
9 PM
45207
No. Description Date
MONITOR/ TV
TYPE A7 ONE LAYER OF 5/8" GYPSUM WALLBOARD ON EACH SIDE OF 3-5/8"
20 GA. METAL STUDS @ 16" O.C. WITH NO SOUND ATTENUATION BLANKETS IN
STUD SPACE. EXTEND STUDS AND BOARD TO 6" ABOVE CEILING. BRACE TOP
OF WALL AS REQUIRED, BUT NOT LESS THAN 8'-0" O.C.
TYPE F2 1 HOUR RATED WALL UL# U419 PROVIDE TYPE "X" GYPSUM
WALLBOARD FOR 1 HR UL RATING ON EACH SIDE OF 6" 20 GA. METAL STUDS
@ 16" O.C. WITH 6" SOUND ATTENUATION BLANKETS IN STUD SPACE. EXTEND
STUDS, BOARD, AND BLANKETS FULL HEIGHT TO DECK ABOVE.
TYPE F1 1 HOUR RATED WALL UL# U419 PROVIDE TYPE "X" GYPSUM
WALLBOARD FOR 1 HR UL RATING ON EACH SIDE OF 3 5/8" 20 GA. METAL
STUDS @ 16" O.C. WITH 3" SOUND ATTENUATION BLANKETS IN STUD SPACE.
EXTEND STUDS, BOARD, AND BLANKETS FULL HEIGHT TO DECK ABOVE.
TYPE A1 (U.N.O.) ONE LAYER OF 5/8" GYPSUM WALLBOARD ON EACH SIDE OF
3-5/8" 20 GA. METAL STUDS @ 16" O.C. WITH 3" SOUND ATTENUATION
BLANKETS IN STUD SPACE. EXTEND STUDS, BOARD, AND BLANKETS FULL
HEIGHT TO DECK ABOVE.
NOTES: 1. TYPICAL PARTITION TYPE IS WALL TYPE "A1" UNLESS NOTED
OTHERWISE ON PLAN. 2. BUILD PARTITIONS IN ACCORDANCE WITH PARTITION
SCHEDULE AND DESIGN REFERENCED. REFERENCES ARE TO THE LATEST
EDITION
OF GYPSUM ASSOCIATION (GA) FIRE RESISTANCE DESIGN MANUAL, OR TO
UNDERWRITERS LABORATORY (UL) FIRE RESISTANCE DIRECTORY.
3. ALL WALLBOARD IS TO BE TYPE "X" UNLESS NOTED OTHERWISE. 4. NO
EXISTING FIREPROOFING IS TO BE REMOVED FROM EXISTING BUILDING
STRUCTURE FOR ANY NEW INSTALLATION FOR ANY REASON.
REPAIR ANY FIREPROOFING DAMAGED BY CONSTRUCTION TO MATCH EXISTING
SYSTEM. 5. FLOOR TO FLOOR HEIGHT IS TO BE VERIFIED IN THE FIELD BY
THE CONTRACTOR. 6. ALL INTERIOR METAL STUD PARTITIONS ARE TO HAVE A
2 1/2" DEEP TOP TRACK FOR DEFLECTION COMPENSATION. DO NOT
SCREW-
ATTACH STEEL VERTICAL STUDS OR GYPSUM WALLBOARD TO TOP DEFLECTION
TRACK. UNLESS NOTED, THE CONNECTION AT THE TOP OF THE PARTITION TO
THE STRUCTURE ABOVE MUST ALLOW FOR 1" MINIMUM VERTICAL MOVEMENT,
EITHER UP OR DOWN. AT FIRE RATED METAL STUD PARTITIONS, THE TOP
CONNECTION MUST BE A FIRE STOP CONNECTION THAT ALLOWS 1" MINIMUM
VERTICAL MOVEMENT, EITHER UP OR DOWN. HOLD GYPSUM WALL BOARD AND
STEEL STUDS 1" FROM THE BOTTOM OF THE STRUCTURE ABOVE. DO NOT
SCREW-ATTACH STEEL VERTICAL STUDS OR GYPSUM WALL BOARD TO THE TOP
TRACK. INSTALL BRIDGING 12" MINIMUM FROM THE TOP OF THE
STUDS.
7. PARTITION TYPES INDICATED ARE CONTINUOUS TO A CORNER OR AN
INTERSECTING PARTITION, UNLESS INDICATED OTHERWISE. WHERE
PARTITIONS OF DIFFERENT THICKNESS MEET, MAINTAIN A FLUSH SURFACE ON
THE SIDE WHERE FACES ARE STRAIGHT AND CONTINUOUS, UNLESS NOTED
OTHERWISE.
8. METAL STUD GAUGES SCHEDULED ARE THE MINIMUM REQUIRED, AND MAY BE
INCREASED BY SPECIFICATIONS TO ACCOMMODATE LOADS, FINISHES, OR
UNBRACED CEILING HEIGHT LIMITS. DO NOT CONSIDER CEILING SYSTEM(S)
AS A PARTITION BRACING ELEMENT.
9. SOUND ATTENUATION BATT (SAB) IS TO BE PLACED IN ALL PARTITIONS
WHICH ENCLOSE A ROOM UNLESS NOTED OTHERWISE. 10. WOOD AND PLYWOOD
BLOCKING TO BE FIRE RETARDANT TREATED (FRT). 11. EDGES OF GYPSUM
WALL BOARD (GWB) LEFT EXPOSED TO VIEW, OR ABUTTING DISSIMILAR
MATERIAL, IS TO BE FINISHED WITH METAL
"L" BEAD TRIM AND COMPOUND UNLESS NOTED OTHERWISE. 12. SCHEDULING
OF A PARTITION DESIGN WHICH CARRIES A FIRE RATING DOES NOT IMPLY A
FIRE SEPARATION FUNCTION FOR THAT
PARTITION. LOCATIONS OF FIRE AND SMOKE PARTITIONS ARE INDICATED ON
THE LIFE SAFETY PLAN. 13. 1PARTITION SCHEDULE IS BASED ON THE USE
OF GYPSUM WALL BOARD (GWB), BUT FACING BOARD MAY VARY, DEPENDENT ON
FINAL
FINISH SCHEDULED FOR THAT PARTITION: USE CEMENTITIOUS BACKER BOARD
(CBB) WHERE CERAMIC TILE SCHEDULED IN "WET" AREAS; USE MOISTURE
RESISTANT BOARD (MR) WHERE CERAMIC TILE SCHEDULED IN "DRY" AREAS;
USE GYPSUM LATH (BLUE BOARD) WHERE VENEER PLASTER IS SCHEDULED. SEE
FINISH SCHEDULE AND SPECIFICATIONS FOR PARTICULARS. AT ALL PLUMBING
FIXTURES INSTALL 4X8 (MR) MOISTURE RESISTANT BOARD CENTERED ON
FIXTURE.
14. ALL FIRE RATED WALL AND FLOOR PENETRATION MUST COMPLY WITH
ASTM-E814 15. ALL DOOR OPENINGS SHALL BE 4" FROM A PERPENDICULAR
PARTITION TO OUTSIDE FACE OF FRAME, UNLESS NOTED OR DETAILED
OTHERWISE. 16. ALL PARTITIONS, INCL. STUDS, BOARD, SOUND
ATTENUATION BLANKETS, ETC. TO EXTEND FROM TOP OF FLOOR SLAB TO
UNDERSIDE
OF CONCRETE SLAB ABOVE UNLESS OTHERWISE NOTED. 17. CONTRACTOR IS TO
CLOSE OFF ANY VOIDS LEFT AS A RESULT OF ANY REMOVALS AND NEW
CONSTRUCTION, AS WELL AS INFILL ANY
EXISTING VOIDS IN NEWLY DESIGNATED FIRE RATED PARTITIONS. ALL
PATCHES SHALL MATCH AND ALIGN WITH SURROUNDING MATERIALS AND SHALL
BE IN ACCORDANCE WITH OHIO BASIC BUILDING CODE.
18. REFER TO ARCHITECTURAL FLOOR PLANS FOR PARTITION TYPE
DESIGNATIONS. 19. CONTRACTOR SHALL SEAL PARTITION WALLS AROUND ALL
M.E.P. PENETRATIONS OR OPENINGS, RESULTING FROM M.E.P.
INSTALLATIONS INCLUDING BUT NOT LIMITED TO THE SLAB, ABOVE AND
BELOW CEILINGS.
TYPE WD WOOD ACOUSTICAL PLANK SYSTEM ON FURRING STRIP ATTACHED WITH
MOUNTING CLIPS. WC-1 INSTALL PER MANUFACTURER'S INSTRUCTIONS.
TYPE GL BACK PAINTED GLASS. PAINT PER FINISH SCHEDULE. SEE
DETAILS.
TYPE C1 ONE LAYER OF 5/8" GYPSUM WALLBOARD ON ROOM SIDE OF 2 1/2"
20 GA. METAL STUDS @ 16" O.C. WITH NO SOUND ATTENUATION BLANKET IN
STUD SPACE. EXTEND STUDS AND BOARD FULL HEIGHT TO DECK ABOVE.
ATTACH TO STRUCTURE ABOVE W/ VERTICAL SLIP CONNECTIONS. SEE
PARTITION NOTES THIS DWG.
TYPE B7 ONE LAYER OF 5/8" GYPSUM WALLBOARD ON EACH SIDE OF 6" 20
GA. METAL STUDS @ 16" O.C. WITH NO SOUND ATTENUATION BLANKETS IN
STUD SPACE. EXTEND STUDS AND BOARD TO 6" ABOVE CEILING. BRACE TOP
OF WALL AS REQUIRED, BUT NOT LESS THAN 8'-0" O.C.
A.D. AC.T. ACOUS. A/C
ASPHALT CONCRETE
ANCHOR BOLT
ANGLE
CER.T. CER.
DF. D.F.
DIAG. DIA.
DIM. DISP.
DWR.
DIV.
CLO.
DOUGLAS FIR DRINKING FOUNTAIN DIAMETER DIAGONAL DIMENSION DISPOSAL
DIVISION DOWN DOOR OPENING DOOR DOWN SPOUT DRAIN TILE
DISHWASHER
DRAWER
DETAIL
BENCH MARK or BEAM
APPROXIMATE ARCHITECT ASPHALT
CLOSURE CLEAR CLOSET CAULKING CEILING JOIST
UNIT
CEILING
CERAMIC TILE CERAMIC CEMENT
CATCH BASIN CARPET CABINET
BUILT-UP ROOFING BETWEEN BRONZE
EXISTING EACH
EACH END EXHAUST FAN EXPANSION JOINT ELECTRICAL ELEVATION EDGE
NAIL
(E)
ADJUSTABLEADJ.
LP
LC
LF
E.C. ELECTRICAL CONTRACTOR
C.HK. COAT HOOK
FACE NAIL
FACE OF MASONRY FACE OF FINISH
F.O.S. F.R.T.W.
FTG. FUT.
HARDWARE HARDWOOD
INTERIOR INVERT
HOT WATER
HDR. HEADER
FH.M.S.
F.HORN
EXPANSION EXPANSION BOLT EXPOSURE EXTERIOR
FLAT HEAD MACHINE SCREW
FINISH
CABINET
FIRE ALARM FACE BRICK FIREBOARD FIRE BELL FURNISHED BY OTHERS
FACE
APPROVAL)
REFLECTED CEILING
ROUND HEAD WOOD SCREW
MAT.
METAL
OFF.
O.F.S.
PLUMBING CONTRACTORP.C.
SOLID CORE
SQUARE
DRAWINGS
TOE NAIL TOOL JOINT
SUSP.
VINYL COMPOSITION TILE
SANITARY NAPKIN DISPENSER
1
ROOM NAME W/ ROOM NUMBER, AREA & OCCUPANCY
BUILDING SECTION NUMBER W/ SHEET NUMBER
WALL SECTION NUMBER W/ SHEET NUMBER
DOOR NUMBER
WALL TAG
WINDOW TAG
NORTH ARROW
BLOCKING = 2x8 FIRE RETARDANT TREATED WOOD, (FRTW). USE SPRUCE PINE
FIR NO. 2, TREATED W/ DRICON
WHERE BLOCKING ATTACHES TO THE OPEN SIDE OF WALL STUD, PROVIDE 20
GA. TRACK x 7 1/4" LONG. SCREW TO STUD W/ 4 - NO.10-16 SCREWS EA.
SIDE.
SCREW THROUGH STUD OR TRACK INTO THE END OF THE WOOD BLOCKING W/ 4
- NO. 9-18 x 1 1/2" CUT THREAD WOOD SCREWS. SCREWS SHALL HAVE A
PROTECTIVE COATING. AN ACCEPTABLE FASTERNER IS BUILDEX 9- 18 x 1
1/2" HWH TRUGRIP COATED W/ CLIMASEAL.
TYP. 3/4" MAX.
BLOCKING = 8" DEEP x 14 GA. TRACK W/ 1 1/4" FLANGES CLIP & BEND
FLANGES EA. END. CONNECT EA. END W/ 4 - NO.10-16 SCREWS
WHERE BLOCKING ATTACHES TO OPEN SIDE OF WALL STUD, PROVIDE 20 GA.
TRACK x 8" LONG. SCREW TO STUD W/ 4 - NO.10-16 SCREWS EA.
SIDE
WHERE BLOCKING ATTACHES TO OPEN SIDE OF WALL STUD, PROVIDE 20 GA.
TRACK x 8" LONG. SCREW TO STUD W/ 4 - NO.10-16 SCREWS EA. SIDE
BLOCKING = 8" DEEP x 14 GA.
TRACK W/ 1 1/4" FLANGES
12 GA.CLIP ANGLE 2"x2"x7 1/2" TALL W/ 4 - NO. 10-16 SCREWS IN EA.
LAG.
WALL BLOCKING TYPE 1
WALL BLOCKING TYPE 2
WALL BLOCKING TYPE 3
OPTION B - PLAN VIEW
OPTION A - PLAN VIEW
OPTION A - ELEVATION VIEW OPTION B - (SIMILAR)
BLOCKING = 18 GA. x 8" MIN. TALL SHEET STEEL. SCREW TO STUDS W/ 4 -
NO. 10-16 SCREWS @ EA. END. PROVIDE ONE ADDITIONAL SCREW EA. END
FOR EACH 2" ADDITIONAL HEIGHT INCREASE IN THE BLOCKING PLATE. IF
BLOCKING PLATE IS CONTINUOUS @ A WALL STUD, PROVIDE 2 ROWS OF
SCREWS.
OF PLATE TYP.
PLAN VIEW
ELEVATION VIEW
PLAN VIEW
ELEVATION VIEW
NOTES:
WALL BLOCKING TYPE 1: TO BE USED FOR WALL MOUNTED ITEMS THAT WEIGH
50 POUNDS OR LESS AND THAT ARE NOT INTENDED FOR HUMAN SUPPORT.
EXAMPLES OF WALL MOUNTED ITEMS THAT ARE INTENDED FOR HUMAN SUPPORT
ARE HANDRAILS AND GRAB BARS. THESE CANNOT HAVE WALL BLOCKING TYPE
1.
WALL BLOCKING TYPE 2 OR 3: TO BE USED FOR ALL OTHER WALL MOUNTED
ITEMS NOT MEETING THE REQUIREMENTS FOR WALL BLOCKING TYPE 1.
THE CONTRACTOR MUST COORDINATE WITH ALL TRADES TO DETERMINE WHICH
TYPE OF WALL BLOCKING IS REQUIRED FOR EACH WALL MOUNTED ITEM. ALL
ANCHORS SHALL EXTEND THROUGH THE WALL FINISH INTO THE BLOCKING.
AVOID THE USE OF PLASTIC TYPE ANCHOR DEVISES. MANUFACTURERS OF THE
WALL MOUNTED ITEMS MUST PROVIDE THE PULLOUT AND SHEAR FORCES AT THE
ANCHORS DUE TO THE WEIGHT OF THE ITEM AS WELL AS THE LOADS THAT ARE
REQUIRED TO BE SUPPORTED BY THE ITEM AS MANDATED BY THE GOVERNING
AUTHORITY. ANCHORS MUST HAVE ADEQUATE STRENGTH TO SUPPORT THESE
FORCES. CONTRACTOR HAS THE OPTION TO USE A PROPRIETARY BLOCKING
SYSTEM WHICH MUST BE SUBMITTED TO THE ARCHITECT FOR APPROVAL.
FILL MATERIAL (DEPTH TO BE MIN. 1/2")
METAL PIPE OR CONDUIT
1/ 2" 1/2" MIN. PROJECTION
TO A MAX. 2"
PIPE SLEEVE
THIS DETAIL IS DIAGRAMMATIC ONLY, MFR. OF FIRESTOP MATERIALS SHALL
PROVIDE FINAL DESIGN AND APPLICABLE U.L. DESIGN NUMBERS.
SE E
PL AN
1HR PARTITION - SEE FLOOR PLAN & PARTITION TYPE SCHEDULE FOR
REQUIREMENTS
PROVIDE FIRE SEALANT @JOINT AND OVER ENTIRE CLOSURE PLATE (TYP.
BOTH SIDES)
TEST REF.: SIMILAR TO JMI/PHV 60-01
DEFLECTIONI TRACK - ATTACH TO CLOSURE PLATE
1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH APPLICABLE LOCAL,
STATE AND FEDERAL AUTHORITIES, CODES, RULES AND REGULATIONS.
2. THESE DOCUMENTS SHOW THE MINIMUM CONSTRUCTION REQUIREMENTS AND
THE MINIMUM QUALITY OF WORK EXPECTED. MORE STRINGENT REQUIREMENTS
STIPULATED WITHIN RELEVANT MANUFACTURER’S INSTALLATION INSTRUCTIONS
WILL SUPERSEDE.
3. ANY UNFORESEEN OR UNCLEAR CONDITIONS SHALL BE REPORTED TO THE
ARCHITECT PRIOR TO PROCEEDING WITH WORK.
4. ANY CONFLICTS WITHIN THE DRAWINGS, BETWEEN THE DRAWINGS AND THE
SPECIFICATIONS, OR BETWEEN THE DRAWINGS AND THE ACTUAL CONDITIONS
AT THE SITE, ARE TO BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
ARCHITECT. THE CONTRACTOR SHALL NOT PROCEED WITH WORK UNTIL WRITTEN
CLARIFICATION FROM THE ARCHITECT IS RECEIVED.
5. UNLESS OTHERWISE NOTED, ALL MATERIALS AND EQUIPMENT ARE TO BE
INSTALLED PER THE APPLICABLE PROVISIONS OF THESE DOCUMENTS AND THE
MANUFACTURER’S INSTRUCTIONS.
6. ALL MATERIALS USED ARE REQUIRED TO BE NEW UNLESS OTHERWISE NOTED
AND/OR OF A QUALITY TO MEET OR EXCEED ALL APPLICABLE INDUSTRY
STANDARDS. WHERE SPECIFIED PRODUCTS OR MANUFACTURERS ARE NOT NOTED,
THE CONTRACTOR IS REQUIRED TO NOTIFY THE ARCHITECT TO OBTAIN A
MINIMUM STANDARD OF QUALITY.
7. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL MEANS, METHODS AND
TECHNIQUES FOR CONSTRUCTION.
8. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR JOB-SITE SAFETY
INCLUDING BUT NOT LIMITED TO THE ADHERENCE TO OSHA
REGULATIONS.
9. ALL ELECTRICAL AND MECHANICAL WORK SHALL BE PERFORMED BY
PERSONNEL LICENSED IN THE STATE WHERE THIS PROJECT IS
LOCATED.
10. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF
EXISTING ITEMS TO REMAIN DURING DEMOLITION AND CONSTRUCTION.
11. REMOVE ALL DEBRIS PROPERLY FROM THE SITE. LOAD DEBRIS DIRECTLY
ONTO TRUCKS OR INTO DUMPSTERS FOR REMOVAL. DISPOSE OF DEBRIS
LEGALLY. DO NOT BURN DEBRIS ON THE SITE. DO NOT ALLOW DEBRIS TO
ENTER SEWERS. DO NOT ALLOW PILED DEBRIS TO ENDANGER STRUCTURES,
BLOCK EXISTS OR ROADWAYS. COMBUSTIBLE WASTE WHICH COULD CREATE A
FIRE HAZARD SHALL NOT BE PERMITTED TO ACCUMULATE IN OR AROUND THE
CONSTRUCTION SITE.
12. DO NOT SCALE DRAWINGS. DIMENSIONS SHALL GOVERN. ALL PLAN
DIMENSIONS ARE TAKEN TO FINISH FACE OF CONSTRUCTION.
13. LAYOUT AND VERIFY ALL PARTITION LOCATIONS PRIOR TO CONSTRUCTION
FOR CLEARANCES AND DIMENSIONS. NOTIFY ARCHITECT OF ANY
DISCREPANCIES.
14. WITHIN ALL METAL STUD PARTITIONS, THE GENERAL CONTRACTOR IS TO
PROVIDE BLOCKING FOR ALL WALL MOUNTED EQUIPMENT AND ACCESSORIES
INCLUDING BUT NOT LIMITED TO: MECHANICAL, ELECTRICAL AND PLUMBING
DEVICES, FURNITURE, CASEWORK, MILLWORK AND ALL OTHER WALL MOUNTED
ACCESSORIES AND ITEMS. THE LOCATIONS, MOUNTING HEIGHTS AND BLOCKING
REQUIREMENTS SHOWN HEREON ARE GIVEN FOR INFORMATIONAL PURPOSES ONLY
AND IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO VERIFY
THIS INFORMATION WITH THE ASSOCIATED SUB-CONTRACTORS,
MANUFACTURERS, OR EQUIPMENT SUPPLIERS. SEE TYPICAL BLOCKING DETAILS
IN METAL STUD WALLS INCLUDED IN THESE DOCUMENTS FOR BLOCKING AND
ANCHORING REQUIREMENTS.
15. ALL CONCEALED WOOD SHALL BE FIRE RETARDANT TREATED. 16. THE
GENERAL CONTRACTOR SHALL COORDINATE WITH ALL OTHER DISCIPLINES
INCLUDING BUT NOT
LIMITED TO MECHANICAL, ELECTRICAL AND PLUMBING, TO DETERMINE THE
SIZE AND LOCATION OF ALL PENETRATIONS IN NEW CONSTRUCTION.
COORDINATE AND PROVIDE ALL OPENINGS. SEAL CONSTRUCTION TIGHT TO ALL
PENETRATIONS AND CAULK.
17. ALL PENETRATIONS THROUGH FIRE RATED CONSTRUCTION MUST BE FIRE
SAFED IN ACCORDANCE WITH THE SPECIFICATIONS.
18. PROVIDE CONTROL JOINTS IN GYPSUM WALLBOARD INTERIOR PARTITIONS
AT 30 FEET ON CENTER MAXIMUM. WHERE POSSIBLE, LOCATE AT CORNERS
ABOVE OPENINGS. VERIFY LOCATIONS WITH ARCHITECT. SEE THE ASSOCIATED
TYPICAL DETAILS INCLUDED IN THESE DOCUMENTS.
19. FURNISH AND INSTALL SEALANT AT ALL FIXTURES AND CHANGES IN
MATERIAL, AND AS REQUIRED BY THE APPLICABLE HEALTH
DEPARTMENT.
20. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL
EQUIPMENT INSTALLATION AND VERIFYING ALL REQUIRED ROUGH OPENINGS,
AND ROUGH-IN DIMENSIONS WITH THE EQUIPMENT MANUFACTURER, OWNER AND
ARCHITECT PRIOR TO CONSTRUCTION.
21. THE GENERAL CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND
FIELD CONDITIONS PRIOR TO DEMOLITION AND CONSTRUCTION. IF PROVIDED,
THE GENERAL CONTRACTOR SHALL CAREFULLY EXAMINE EXISTING BUILDING
DOCUMENTS. THE CONTRACTOR SHALL BRING ANY DISCREPANCIES TO THE
IMMEDIATE ATTENTION OF THE ARCHITECT.
22. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF
EXISTING ITEMS TO REMAIN DURING DEMOLITION AND CONSTRUCTION.
23. MAINTAIN EXIT EGRESS PATHS TO EXISTING EXIT DOORS DURING
CONSTRUCTION. 24. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE
PROTECTION OF ALL CONSTRUCTION ROUTES
BEYOND THE AREAS OF WORK AND THE ROUTES MUST BE RETURNED TO THEIR
ORIGINAL CONDITION AT THE END OF THE PROJECT.
25. MAINTAIN THE BUILDING IN A WEATHER TIGHT CONDITION AT ALL
TIMES. 26. ALL DEMOLITION AND CONSTRUCTION ACTIVITIES SHALL BE
COORDINATED WITH THE OWNER TO MINIMIZE
DISRUPTIONS OF NORMAL FUNCTIONS OF THE OWNER'S OCCUPIED AREAS. 27.
IF CONSTRUCTION NOISE IS ANTICIPATED, SUBMIT A WRITTEN REQUEST TO
THE OWNER FOR THE
SCHEDULED TIME OF THE CONSTRUCTION ACTIVITIES. NO WORK SHALL BE
DONE WITHOUT THE WRITTEN APPROVAL OF THE OWNER. THE OWNER RESERVES
THE RIGHT TO DISCONTINUE NOISY CONSTRUCTION AT ANY TIME.
28. ALL EXISTING SERVICES AND UTILITIES SHALL BE MAINTAINED TO
ADJACENT AREAS THAT ARE IN OPERATION AND SERVED BY THEM. COORDINATE
ALL DISRUPTIONS OR DISCONTINUATIONS OF UTILITIES AND SERVICES WITH
OWNER. NO SHUT DOWN OF EXISTING SERVICES IS ALLOWED TO OCCUR UNTIL
RECEIVING THE OWNER'S WRITTEN APPROVAL OF THE SHUT DOWN SCHEDULE.
PROVIDE TEMPORARY SERVICES AND/OR UTILITIES DURING INTERRUPTIONS AS
REQUIRED AND APPROVED BY THE OWNER.
29. THE GENERAL CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO
PREVENT DAMAGE TO OWNER'S OCCUPIED AREAS ADJACENT TO NEW
CONSTRUCTION OR OCCUPIED AREAS WHERE VARIOUS SYSTEM CONNECTIONS OR
EXTENSIONS ARE REQUIRED. IN THESE AREAS, THE GENERAL CONTRACTOR IS
RESPONSIBLE FOR DAMAGE CAUSED BY LACK OF SUFFICIENT PROTECTION FROM
THE WEATHER AND FROM THE RESULTS OF ALL CONSTRUCTION ACTIVITY
INCLUDING BUT NOT LIMITED TO DUST AND WATER.
30. TEMPORARY BARRICADES WHERE INDICATED ON THE DOCUMENTS ARE SHOWN
IN THEIR APPROXIMATE LOCATIONS. THE GENERAL CONTRACTOR MUST
COORDINATE SPECIFIC LOCATIONS WITH THE OWNER IN CONJUNCTION WITH
THE CONSTRUCTION PHASING. TEMPORARY BARRICADES MUST BE CONSTRUCTED
IN ACCORDANCE WITH OSHA REQUIREMENTS AND OWNER'S INTERIM LIFE
SAFETY MEASURES.
31. DURING CONSTRUCTION, ISOLATE ALL HVAC SYSTEMS IN AREAS WHERE
THE WORK IS BEING PERFORMED. COMPLETE ALL CRITICAL BARRIERS TO SEAL
THE WORK AREA FROM THE REST OF THE FACILITY. MAINTAIN NEGATIVE AIR
PRESSURE WITHIN THE WORK SITE USING HEPA EQUIPPED AIR FILTRATION
UNITS. PROMPTLY SEAL ANY HOLES/PENETRATIONS BETWEEN THE WORK AREA
AND THE REST OF THE FACILITY. CONTAIN CONSTRUCTION WASTE IN COVERED
CONTAINERS BEFORE TRANSPORTING IT.
32. THE GENERAL CONTRACTOR SHALL RECEIVE WRITTEN APPROVAL FROM THE
OWNER BEFORE USING OPEN FLAMES, WELDING RODS AND TORCHES. THE
GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL MEANS AND METHODS TO
PROHIBIT THE MIGRATION OF SMOKE AND OTHER PRODUCTS OF COMBUSTION
INTO OCCUPIED AREAS OF THE EXISTING BUILDING AND FOR OBTAINING ALL
REQUIRED PERMITS RELATED TO HOT WORK.
33. PROVIDE FIRE PROTECTION IN ACCORDANCE WITH THE REQUIREMENTS OF
THE GOVERNING AUTHORITY. 34. IT IS THE GENERAL CONTRACTORS
RESPONSIBILITY TO PATCH ALL SPRAY-ON FIRE PROTECTION AT
REMOVALS, AT ANY EXISTING LOCATIONS WHICH ARE VOID OF PROTECTION
WITHIN THE AREA OF WORK AND AT NEW CONSTRUCTION WHICH DISTURBS
EXISTING FIRE PROTECTION. FIREPROOFING MUST BE CONTINUOUS AND
UNOBSTRUCTED.
35. DO NOT OVERLOAD THE EXISTING BUILDING STRUCTURE. MAINTAIN THE
STRUCTURAL INTEGRITY OF ALL STRUCTURAL FRAMING MEMBERS AND SYSTEMS
AT ALL TIMES.
36. ALL OPENINGS IN EXISTING WALLS, CEILINGS AND FLOORS, WHICH ARE
THE RESULT OF REMOVALS AND OTHER NEW CONSTRUCTION ACTIVITY, SHALL
BE PATCHED WITH NEW MATERIALS THAT MATCH THE EXISTING MATERIALS. IF
THE PATCH IS TO BE MADE IN FIRE RATED CONSTRUCTION, THE PATCH MUST
ACHIEVE THE REQUIRED FIRE RATING. THE PATCH SHALL BE FINISHED TO A
LIKE NEW CONDITION TO MATCH THE EXISTING FINISH.
37. ALL EXISTING OPENINGS IN CEILINGS, FLOORS AND WALLS DISCOVERED
IN THE EXISTING STRUCTURE SHALL BE PATCHED WITH NEW MATERIALS THAT
MATCH THE EXISTING MATERIALS. IF THE PATCH IS TO BE MADE IN FIRE
RATED CONSTRUCTION, THE PATCH MUST ACHIEVE THE REQUIRED FIRE
RATING. THE PATCH SHALL BE FINISHED TO A LIKE NEW CONDITION TO
MATCH THE EXISTING FINISH.
38. WHERE EXISTING SURFACES ARE TO BE REFINISHED OR ARE TO SERVE AS
SUBSTRATE FOR THE ATTACHMENT OR APPLICATION OF NEW MATERIALS OR
CONSTRUCTION, PREPARE OR ALTER THE EXISTING SURFACES AS NECESSARY
TO PROPERLY ACCOMMODATE THE NEW MATERIALS.
39. FIELD VERIFY SIZES AND DIMENSIONS OF ALL EXISTING UTILITIES
THAT IMPACT THE NEW WORK. DETERMINE THE SIZE AND LOCATION THE
PENETRATIONS FROM THE EXISTING UTILITIES WITHIN THE NEW WORK. SEAL
TIGHT TO ALL PENETRATIONS AND CAULK.
40. PENETRATIONS THROUGH EXISTING FIRE RATED CONSTRUCTION MUST BE
PROPERLY CLOSED AND FIRE SAFED TO ACHIEVE THE PROPER FIRE RATING BY
THE END OF CONSTRUCTION OPERATIONS FOR EACH DAY.
41. UNLESS OTHERWISE NOTED, THE GENERAL CONTRACTOR IS RESPONSIBLE
FOR VERIFYING ALL EXISTING SALVAGED STOCK BEFORE ORDERING NEW
MATERIAL.
42. ROOM IDENTIFICATION SIGNAGE IS REQUIRED TO MEET THE
REQUIREMENTS FOR CHARACTER HEIGHT AND PROPORTION, FINISH AND
CONTRAST, FRONT, BRAILLE AND PICTOGRAM TYPES AS INDICATED IN THESE
DOCUMENTS. ROOM IDENTIFICATION SIGNAGE SHALL BE MOUNTED AT 60"
ABOVE THE FINISHED FLOOR TO THE SIGN CENTERLINE AND SHALL BE
MOUNTED TO THE WALL AT THE LATCH SIDE OF THE DOOR.
1-HOUR RATED SHAFT WALL. 4" STEEL STUDS @ 16" O.C.
1 LAYERS OF 5/8" GYPSUM BOARD
1" GYPSUM LINER PANEL
FASTENER 24" O.C. MAX. SHEAR AND WITHDRAWAL RESISTANCE AS REQUIRED
BY SPECIFIC DESIGN CONDITIONS (TYP.)
USG STEEL J-RUNNER
SEALANT
FASTENER 24" O.C. MAX. SHEAR AND WITHDRAWAL RESISTANCE AS REQUIRED
BY SPECIFIC DESIGN CONDITIONS (TYP.)
1/2" TYPE S PAN HEAD SCREW AT 12" O.C. (ATTACH BOTH SIDES OF C-H
STUD AND J-RUNNER AT TOP AND BOTTOM OF STUD)
DUCTWORK
1-HOUR RATED WALL. SEE PARTITION TYPES.
1-HOUR RATED PARTITION BEYOND
R EG
I T EC
EXPIRATION DATE 12/31/2017
ISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2 T 513.241.4474 F
513.241.0081
Drawn By
Checked By
Project Number
Client Number
3/ 21
/2 01
6 7:
48 :5
6 PM
DETAILS
45207
GENERAL NOTESPARTITION TYPES
WALL BLOCKING DETAILS
1 1/2" = 1'-0"A001 A WALL PENETRATION - 1 HR & 2HR RATED
PARTITION
1 1/2" = 1'-0"A001 B TYP. RATED WALL PARALLEL TO ROOF DECK - 1HR
RATED TYPICAL MOUNTING HEIGHTS
No. Description Date
HATCHED AREA - INTERIOR DEMOLITION AREA • REMOVE ALL INTERIOR
FINISHES, INCLUDING BUT NOT LIMITED TO: INTERIOR
PARTITIONS, CEILINGS, FLOOR FINISHES, EQUIPMENT, RUBBER OR WOOD
BASE, CASEWORK AND ITEMS MOUNTED ON WALLS AND CEILINGS REMAINING
ETC.
• SALVAGE 2X4 LIGHTS TO BE REINSTALLED IN NEW WORK. ANY LIGHTS THAT
ARE NOT USED ARE TO BE RETURNED TO OWNER. COORDINATE WITH CEILING
PLAN AND ELECTRICAL DRAWINGS.
• SALVAGE UNDAMAGED FULL ACOUSTICAL CEILING TILES THIS AREA. AT NEW
WORK, USE THIS STOCK TO REPLACE DAMAGED CEILING TILES IN ROOM 109
AND AT MODIFIED CEILING WORK. RETURN REMAINING ATTIC STOCK TO
OWNER.
• COORDINATE THE REMOVAL OF MECHANICAL, ELECTRICAL, SECURITY AND
PLUMBING ITEMS WITH MEPT DRAINING.
• PROTECT ITEMS TO REMAIN DURING DEMOLITION AND NEW WORK. • SEE
GENERAL NOTES AND KEYNOTES FOR ITEMS TO BE SALVAGED AND
ADDITIONAL
SCOPE.
HATCHED AREA - LIMITED DEMOLITION • NO WORK AT FLOORING • CEILING
SYSTEM, MINI-BLINDS AND DEVICES TO REMAIN. COORDINATE WITH
NEW
WORK. • COORDINATE THE REMOVAL OF MECHANICAL, ELECTRICAL, SECURITY
AND
PLUMBING ITEMS WITH MEPT DRAINING. • PROTECT ITEMS TO REMAIN DURING
DEMOLITION AND NEW WORK. • SEE GENERAL NOTES AND KEYNOTES FOR ITEMS
TO BE SALVAGED AND ADDITIONAL
SCOPE.
DOOR AND FRAME TO REMAIN. PROTECT ITEMS TO REMAIN DURING DEMOLITION
AND NEW WORK.
DOOR AND FRAME TO BE REMOVED.
PARTITIONS AND CASEWORK TO REMAIN. PROTECT ITEMS TO REMAIN DURING
DEMOLITION AND NEW WORK.
PARTITIONS AND CASEWORK TO BE REMOVED.
DEMOLITION PLAN LEGEND
NO WORK THIS AREA
1. NO WORK THIS AREA. 2. RELOCATE TV AND SUPPORT. SEE NEW WORK. 3.
SALVAGE SLAT WALL AND STANDARDS. RETURN TO TENANT. 4. SALVAGE 2X4
LIGHTS TO BE REINSTALLED IN NEW WORK. ANY LIGHTS THAT ARE NOT USED
ARE TO BE
RETURNED TO OWNER. COORDINATE WITH CEILING PLAN AND ELECTRICAL
DRAWINGS. 5. SALVAGE TRACK LIGHTING AND PENDANTS. RETURN TO OWNER.
6. SALVAGE UNDAMAGED FULL ACOUSTICAL CEILING TILES THIS AREA. AT
NEW WORK, USE THIS STOCK TO
REPLACE DAMAGED CEILING TILES IN ROOM 109 AND AT MODIFIED CEILING
WORK. RETURN REMAINING ATTIC STOCK TO OWNER.
7. RELOCATE TRACK LIGHTING. MODIFY AS REQUIRED. SEE ELECTRICAL
DRAWINGS. 8. REMOVE MINI-BLINDS. 9. MINI-BLINDS TO REMAIN. 10.
OWNER TO REMOVE ANTI-THEFT SECURITY TOWER. CONTRACTOR TO REMOVE
WIRE MOLDING AND ANY
ASSOCIATED POWER. 11. CHECK-OUT DESK/ CASEWORK AND SLAT WALL TO
REMAIN. 12. DELAMINATE THE WALLCOVERING, AS INDICATED, TO BE
REINSTALLED IN NEW WORK. 13. RELOCATE THERMOSTAT. SEE ELECTRICAL
DRAWINGS. 14. RELOCATE FIRE STROBE. SEE ELECTRICAL DRAWINGS. 15.
REMOVE HARDWARE AS REQUIRED FOR NEW WORK. 16. REMOVE BOARD. 17.
SALVAGE POOL CUE RACKS AND RETURN TO OWNER. 18. REMOVE PHONE. 19.
SALVAGE CROWN MOLDING AND CHAIR RAIL TO BE REINSTALLED IN NEW WORK.
20. REMOVE CEILING MOUNTED TV AND SUPPORT. 21. SEE ARCHITECTURAL
DRAWINGS FOR LOCATION AND SCOPE OF NEW WORK.
DEMOLITION PLAN KEYNOTES A. ALL DEMOLISHED MATERIAL, EXCEPT
MATERIAL THAT IS LISTED OR MARKED BY THE ARCHITECT
OR THE OWNER FOR RETENTION, SHALL BECOME THE PROPERTY OF THE
CONTRACTOR AND IT SHALL BE DISPOSED OF. NO DEBRIS RESULTING FROM
WORK SHALL BE LEFT IN THE CONSTRUCTION ROUTES BEYOND THE AREAS OF
WORK.
B. REMOVAL OF A PARTICULAR ITEM IS TO INCLUDE ALL RELATED ITEMS,
SUCH AS REMOVAL OF WALLS WOULD INCLUDE ASSOCIATED DOORS, HARDWARE,
ELECTRICAL, PLUMBING, MECHANICAL, ETC. REFER TO DEMOLITION DRAWINGS
FOR MORE INFORMATION. FOR ALL REMOVALS, THE GENERAL CONTRACTOR
SHALL COORDINATE WITH ALL OTHER DISCIPLINES INCLUDING BUT NOT
LIMITED TO MECHANICAL, ELECTRICAL AND PLUMBING.
C. WHERE CEILINGS ARE SHOWN TO BE REMOVED, ALL UNUSED SUSPENDED
EQUIPMENT, WIRES, ANGLES, ETC. SHALL BE REMOVED. SEE DEMOLITION
DRAWINGS FOR ADDITIONAL INFORMATION. EXISTING LIGHTS MAY BE
MAINTAINED AS TEMPORARY CONSTRUCTION LIGHTING.
D. THE CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT FOR ITEMS NOT
DEMOLISHED OR REMOVED AS REQUIRED UNTIL PERMANENT SUPPORT IS
PROVIDED IN THE FINAL CONSTRUCTION.
E. SALVAGE ANY SECURITY SYSTEM DEVICES AND RETURN TO OWNER.
COORDINATE WITH ELECTRICAL AND TECHNOLOGY DRAWINGS.
F. COORDINATE WITH ELECTRICAL DRAWINGS FOR NEW LOCATIONS AND
RE-LOCATIONS OF THE ELECTRICAL DEVICES.
DEMOLITION PLAN GENERAL NOTES
R EG
I T EC
EXPIRATION DATE 12/31/2017
ISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2 T 513.241.4474 F
513.241.0081
Drawn By
Checked By
Project Number
Client Number
3/ 21
/2 01
6 7:
50 :4
5 PM
45207
LEGEND
12'-0" +/-
C1
WD
7
A105
5
2 2
1. ALIGN WITH EXISTING WALL 2. ALIGN 3. WALL PROTECTION PANEL.
TYPICAL ALL WALL THIS ROOM. SEE MATERIAL AND
FINISH SCHEDULE AND NOTES. 4. CARD READER. SEE DOOR SCHEDULE AND
ELECTRICAL DRAWINGS. 5. PROJECTION SCREEN ABOVE. 6. 1-HOUR
PROTECTION TO BE CONTINUOUS TO STRUCTURE. WHEN RATED
PARTITION, CANNOT EXTEND VERTICALLY TO THE STRUCTURE DUE TO THE
DUCT MAIN INTERFERENCE, PROVIDE A 1-HOUR RATED HORIZONTAL
TRANSITION. SEE SHEET A001 FOR DETAILS.
7. ADA-COMPLIANT ENTRY SIGNAGE FOR "STUDENT LOUNGE" MATCHING
BUILDING STANDARDS. COORDINATE WITH OWNER
8. ADA-COMPLIANT ROOM SIGNAGE. MATCH BUILDING STANDARDS. COORDINATE
WITH OWNER.
FLOOR PLAN KEYNOTES A. SEE A001 FOR PROJECT NOTES. B. PATCH AND
REPAIR AREAS DISTURBED BY DEMOLITION. SEE SHEET A001 NOTES. C.
PATCH, REPAIR AND PAINT DAMAGED COLUMN FURRING IN ALL AREAS OF
WORK,
INCLUDING AREAS TO RECEIVED FINISH MATERIAL. D. COORDINATE WITH
OWNER ON SIGNAGE INSTALLATION REQUIREMENTS.
FLOOR PLAN GENERAL NOTES
NO WORK THIS AREA
R EG
I T EC
EXPIRATION DATE 12/31/2017
ISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2 T 513.241.4474 F
513.241.0081
Drawn By
Checked By
Project Number
Client Number
3/ 21
/2 01
6 7:
49 :1
4 PM
45207
No. Description Date
3"
CEILING PLAN KEYNOTES 1. ALIGN 2. PATCH AND REPAIR CEILING TO
MATCH
EXISTING. 3. METAL CEILING TRANSITION TRIM AND DRYWALL
SOFFIT, WALL TYPE C1. SEE DETAIL A105. 4. PAINTED DRYWALL SOFFIT.
PAINT TO MATCH
BOOKSTORE ENTRY SOFFIT. 5. MODIFY EXISTING CEILING GRID FOR NEW
WORK.
INSTALL SALVAGED ACOUSTICAL CEILING TILES AND CEILING TRIM AND NEW
TRIM, AS REQUIRED. REPLACE DAMAGED CEILING TILES WITH SALVAGED
CEILING TILES.
6. CEILING RECESSED POWERED PROJECTION SCREEN - SEE ELECTRICAL
DRAWINGS.
7. CEILING MOUNTED POWERED PROJECTION SCREEN - SEE DETAIL SHEET
A105 AND ELECTRICAL DRAWINGS.
8. LCD PROJECTOR AND SUPPORT,OFOI. COORDINATE WITH OWNER AND THEIR
VENDOR FOR FINAL LOCATION. COORDINATE WITH ELECTRICAL DRAWINGS FOR
POWER AND DATA REQUIREMENTS.
9. RELOCATED TV AND SUPPORT PIPE, OFCI. COORDINATE WITH TENANT ON
FINAL LOCATION. MATCH EXISTING DETAILING AND MANUFACTURER'S
REQUIREMENTS. COORDINATE WITH ELECTRICAL DRAWINGS.
10. POWERED ROLLER SHADE CLOTH AND ALUMINUM POCKET CEILING TRIM.
SEE DETAIL AND COORDINATE WITH ELECTRICAL DRAWINGS.
11. VERTICAL TRANSITION EXTRUDED PAINTED ALUMINUM CEILING TRIM. SEE
DETAIL SHEET A105. BASIS OF DESIGN: ARMSTRONG AXIOM TRANSITIONS
TRIM - CEILING TO CEILING STRAIGHT TRANSITION. COLOR TO MATCH MAIN
CEILING.
12. EXISTING CEILING ASSEMBLIES TO REMAIN. PATCH AND PAINT AS
REQUIRED.
13. DRYWALL SOFFIT, WALL TYPE C1 UNLESS NOTED OTHERWISE. TYPICAL.
SEE DETAILS ON SHEET A105.
2' X 4' LIGHT FIXTURE
2' X 2' LIGHT FIXTURE
RECESSED DOWNLIGHT
SUPPLY - SEE MECH. DWGS.
EXHAUST - SEE MECH. DWGS.
SPRINKLER - SEE MECH. DWGS.
RECESSED CONTINUOUS WALL WASH
LINEAR DIFFUSER
GYPSUM BOARD
EXIT SIGN
CJ GYPSUM WALL BOARD CEILING CONTROL JOINT
LIGHT COVE
NO WORK THIS AREA
A. SEE DRAWING SHEET A001 FOR GENERAL INFORMATION AND PROJECT
ABBREVIATIONS
B. COORDINATE WITH HVAC, PLUMBING, ELECTRICAL AND FIRE SUPPRESSION
DOCUMENTS FOR ALL LIGHT FIXTURES, SPRINKLERS, POWER, HVAC, AND
MEDICAL GAS OUTLET LOCATION AND TYPES. COORDINATE WITH
ARCHITECTURAL RCP FOR LOCATION AND ALIGNMENTS OF FIXTURES
C. WHERE FIXTURES (INCLUDING SPRINKLERS, DIFFUSERS, SMOKE
DETECTORS, CAN LIGHTS, ETC.) ARE SHOWN ON PLANS AS ALIGNED; ALIGN
FIXTURES IN CENTER OF TILE OR CENTER OF AREA AS GRAPHICALLY SHOWN
ON THE CEILING PLAN. NOTIFY ARCHITECT IF THERE ARE ANY
DISCREPANCIES.
D. PROVIDE ACCESS PANELS IN HARD CEILINGS AS REQUIRED.
E. LOCATE SPRINKLER HEADS, SMOKE DETECTORS, CAN LIGHTS AND ALL
OTHER FIXTURES IN ACOUSTICAL CEILING SYSTEM IN FIELD SO THAT THEY
ARE CENTERED IN TILE UNO. REFER TO SKETCH BELOW.
2x4 ACT 2x2 ACT OR 4x4 ACT
ACCEPTABLE
R EG
I T EC
EXPIRATION DATE 12/31/2017
ISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2 T 513.241.4474 F
513.241.0081
Drawn By
Checked By
Project Number
Client Number
3/ 21
/2 01
6 7:
49 :4
1 PM
45207
1/8" = 1'-0"A102 2 REFLECTED CEILING PLAN - CLOUDS AND SOFFIT
LOCATIONS
3/16" = 1'-0"A102 1 LEVEL 1 - Ceiling Plan- OVERALL
No. Description Date
WALLCOVERING
ALIGN WITH EXISTING
EXISTING WALLCOVERING , REINSTALLED
HARDWOOD TRIM ON HM BORROWED LITE FRAME. SEE DETAILS SHEET
A104.
3
A104
10'-0" CEILING
10'-8" POCKET
9'-4" CLOUD
PROJECTION SCREEN
LINEAR PLANK AND ACOUTICAL FELT SYSTEM - FULL HEIGHT FROM FLOOR TO
TOP OF SOFFIT. SEE TYPICAL DETAIL 1/A105
START PATTERN WITH A FULL WIDTH BOARD
2
A105
5
R EG
I T EC
EXPIRATION DATE 12/31/2017
ISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2 T 513.241.4474 F
513.241.0081
Drawn By
Checked By
Project Number
Client Number
3/ 21
/2 01
6 7:
49 :4
8 PM
45207
1/2" = 1'-0"A103 1 ELEVATION - GLASS COLUMN
1/2" = 1'-0"A103 2 ENLARGED PLAN - TYPICAL GLASS COLUMN
1/2" = 1'-0"A103 3 ENLARGED PLAN - PARTIAL GLASS COLUMN
3/8" = 1'-0"A103 5 ELEVATION- ENTRY
3/8" = 1'-0"A103 4 ELEVATION- BORROWED LITE
3/8" = 1'-0"A103 6 ELEVATION - STAGE WALL
No. Description Date
LINE OF FINISHED FLOOR, COORDINATE WITH FINISH TYPE AND
THICKNESS
8"
1/4" ALUMN J CHANNEL WITH GASKET GLAZING. J NOSING CHANNEL AT TOP
EDGE OF GLASS.
BACK PAINTED GLASS. SEE FINISH SCHEDULE.
EXISTING COLUMN FURRING.
ANODIZED ALUMN EDGE PROTECTION TRIM FROM TOP OF BASE TO CEILING,
ALL OUTSIDE CORNERS. BASIS OF DESIGN: SCHLUTER-INDEC 7/16"
SECTION DETAIL PLAN DETAILA B PLAN DETAILC
ANODIZED ALUMN EDGE PROTECTION TRIM FROM TOP OF BASE TO CEILING,
ALL INSIDE CORNERS. BASIS OF DESIGN: SCHLUTER-JOLLY 1/2"
8" COLUMN WOOD BASE.
4" TYPICAL WOOD BASE.
ANODIZED ALUMN EDGE PROTECTION TRIM FROM TOP OF BASE TO CEILING,
ALL OUTSIDE CORNERS. BASIS OF DESIGN: SCHLUTER-INDEC 7/16"
BACK PAINTED GLASS AND J CHANNEL BELOW. SEE FINISH SCHEDULE.
4 3/4"4 3/4"
W10 W16
W1 - SOLID OAK BASE ADHERED AND FASTENED TO EXISTING WALL ALIGN
WITH EXISTING. W2 - RUBBER BASE, HARDWOOD CHAIR RAIL MOULDING AND
HARDWOOD PICTURE RAIL MOULDING. W3 - 3/16" CLEAR SAFETY GLASS W4 -
3/16" TRANSOM GLASS W5 - 3/4" VENEER PLYWOOD W6 - HARDWOOD TRIM,
UNLESS NOTED OTHERWISE. W7 - ALIGN W8 - PAINTED HM FIRE RATED
FRAMING W9 - HARDWOOD BASE W10 - HARDWOOD BASE CAP W11 - 1/2" W X
1/4" D WOOD REVEAL W12 - REINSTALLED EXISTINGTEXTILE WALLCOVERING
(BELOW PICTURE RAIL) W13 - LINE OF EXISTING WOOD BASE W14 - LINE OF
NEW WOOD BASE AT NEW TRIM. W15 - PROVIDE BLOCKING AS REQUIRED. W16
- TYPICAL 4" WOOD BASE. SEE DETAIL 3/A103.
A. THE DESIGN INTENTION IS TO MATCH THE EXISTING CORRIDOR AND
BOOKSTORE B. WOODWORK AND TRIM APPEARANCE. MATCH EXISTING PROFILES,
SIZES, MOUNTING
HEIGHTS, TYPES AND STAINS. NEW CONSTRUCTION TO ALIGN IN HEIGHT AND
FACE OF TRIM THAT MEET ARE TO BE FLUSH.
C. HARDWOOD - MATCH EXISTING: CONFIRM EXISTING IS TRUE QUARTER OAK
WITH FLAKE STAINED TO MATCH VENEER OR HARD MAPLE STAINED TO MATCH
THE VENEER. PROVIDE SAMPLE FOR REVIEW AND APPROVAL, PRIOR TO
FABRICATION.
D. VENEER - MATCH EXISTING: CONFIRM EXISTING IS QUARTERED HEAVY
FIGURED EUCALYPTUS WITH CUSTOM STAIN, AWI FINISH TR2 CATALYZED
LACQUER 45 SHEEN; PARCEL/ FLICH: 4496; SUBSTRATE PER MANUFACTURER'S
RECOMMENDATION. MEET ALL CODES AND REGULATIONS. PROVIDE SAMPLE FOR
REVIEW AND APPROVAL, PRIOR TO FABRICATION.
E. ATTACH WOOD TRIM TO HM FRAMING WITH STAGGERED SCREWS,
COUNTERSINK AND PLUG. PROVIDE NEOPRENE OR SILICON GLAZING GASKETS
AS REQUIRED.
F. MITER WOOD CORNERS. G. ALL CORNER CONDITIONS TO BE HARDWOOD. DO
NOT PROVIDE VENEER TRIM. H. CHAIR RAIL - MATCH EXISTING. I. PICTURE
RAIL - MATCH EXISTING.
GENERAL NOTES - WOOD TRIM
MATCH EXISTING PROFILE
R EG
I T EC
EXPIRATION DATE 12/31/2017
ISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2 T 513.241.4474 F
513.241.0081
Drawn By
Checked By
Project Number
Client Number
3/ 21
/2 01
6 7:
49 :5
5 PM
45207
3" = 1'-0"A104 4 PLAN DETAIL - BORROW LITE TRIM
3" = 1'-0"A104 2 TYPICAL WOOD BASE
ENTRY PLAN - 1 1/2" = 1'-0" No. Description Date
3" = 1'-0"A104 3 SECTION - BORROW LITE W/ WOOD TRIM
ANGLE MOLDING
5/8" GYP. BD., PAINTED
4" UPTURN WD PANEL
STUD AND TRACK
3 3/4"
5/8" GYP. BD., PAINTED
STUD AND TRACK
3 3/4"
ANGLE MOLDING
4" AXIOM PERIMETER TRIM
STUD AND TRACK
5/8" GYP BD
5"X5" 2-SIDED PT ALUM PERMITER POCKET AND SUPPORT SYSTEM. BOD IS
AXIOM AXP255, WITH 3" CLOSURE CLIP PAINTED TO MATCH ADJACENT
CEILING
POWERED ROLLER SHADE CLOTH
BLOCKING AT CLIPS
LINEAR PLANK
STRUCTURE ABOVE.
ARMSTRONG AXIOM
ASSEMBLY EXTENDS FROM TOP OF FLOOR SLAB TO UNDERSIDE
OF DECK ABOVE. BRACE AS REQUIRED
TO SECURE TO STRUCTURE ABOVE
UNDERSIDE OF STRUCTURE ABOVE;V.I.F.
5/8" TYPE "X" GYPSUM BOARD OVER 3-5/8" METAL STUDS. PAINT AS
INDICATED ON RCP.
10'-10"+/- A.F.F.
10'-0" A.F.F.
LINEAR PLANK SYSTEM AND ACOUTICAL FELT BEYOND - PLANKS RUNNING
PERPENDICULAR TO FLOOR. WALL IS TO BE COMPOSED OF FULL WIDTH PLANKS
WITH STAGGERED JOINTS USING THE LONGEST LENGTHS POSSIBLE.
LINEAR PLAN SYSTEM AND ACOUTICAL FELT - PLANKS RUNNING PARALLEL TO
FLOOR
TRIM TOP PLANK AS REQUIRED TO FIT.
PROJECTION SCREEN, BEYOND
2" WOOD FACIA BY CEILING MANUFACTURER, SET BEHIND MAIN PLANK
WALL ANGLE & SCREWS
3"
LED COVE LIGHT FIXTURE. SEE ELECTRICAL DRAWINGS
LINEAR PLAN SYSTEM AND ACOUTICAL FELT - PLANKS RUNNING PARALLEL TO
FLOOR
LINEAR PLANK SYSTEM AND ACOUTICAL FELT - PLANKS RUNNING
PERPENDICULAR TO FLOOR. WALL IS TO BE COMPOSED OF FULL WIDTH PLANKS
WITH STAGGERED JOINTS USING THE LONGEST LENGTHS POSSIBLE.
4" +/-
2"
TOP OF FRAME 9'-11" +/-
5/8" GYP BD
5"X5" 2-SIDED PT ALUM PERMITER POCKET AND SUPPORT SYSTEM. BOD IS
AXIOM AXP255, WITH 3" CLOSURE CLIP PAINTED TO MATCH ADJACENT
CEILING.
POWERED ROLLER SHADE CLOTH
ACOUSTICAL CLG SYSTEM
45 DEGREE METAL STUD BRACING AT 16" C/C - SECURE TO UNDERSIDE OF
EXIST. STRUCTURE ABOVE.
ELECTRICALLY OPERATED PROJECTOR SCREEN
FRONT OF PROJECTOR SCREEN
SECURE TO UNDERSIDE OF EXIST. STRUCTURE
ABOVE.
PAINT EXPOSED HOUSING TO MATCH CEILING
SUSPENDED ACOUSTICAL CEILING REFL. CEILING PLANS
VIBRATION ISOLATION HANGERS AS REQ'D - CONTINUOUS FULL LENGTH OF
PROJECTOR CASE PLUS TWO FEET
PROVIDE 18 GA. METAL STUD FRAMING ANCHORED TO UNDERSIDE OF
STRUCTURE ABOVE - 16" C/C FULL LENGTH OF PROJECTOR CASE PLUS
TWO FEET
ONE AT EACH CORNER
SIZE
SYSTEM; SECURE TO STRUCTURE ABOVE
AXIOM PERIMETER TRANSITION TRIM SYSTEM, REFER TO
REFLECTED CEILING PLAN. MECHANICALLY FASTEN TRIM TO
CEILING GRID SYSTEM
LIGHT GAUGE METAL FRAMING 16" O.C. BRACE TO STRUCTURE ABOVE
5/8" PAINTED GWB
1'-0"
R EG
I T EC
EXPIRATION DATE 12/31/2017
ISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2 T 513.241.4474 F
513.241.0081
Drawn By
Checked By
Project Number
Client Number
3/ 21
/2 01
6 7:
50 :1
0 PM
45207
3" = 1'-0"A105 11 SECTION DETAIL - AT ACOUSTIC CEILING TILE
1 1/2" = 1'-0"A105 5 SECTION DETAIL - HIGH CLG WINDOW SHADE
DETAIL
3" = 1'-0"A105 1 SECTION DETAIL - TYICAL WOOD WALL
1 1/2" = 1'-0"A105 7 SECTION DETAIL - WOOD WALL TOP
3" = 1'-0"A105 2 PLAN DETAIL - WOOD WALL
1 1/2" = 1'-0"A105 6 SECTION DETAIL - MAIN CLG WINDOW SHADE
DETAIL
No. Description Date
1 1/2" = 1'-0"A105 4 SECTION - TYPICAL CEILING TRANSITION
1 1/2" = 1'-0"A105 8 SECTION - SOFFIT AT FEATURE WALL
V.I.F.
15'-4"
V.I.F.
4'-5"
V.I.F.
6'-6"
V.I.F.
4'-5"
WALL MOUNTED POWERED SHADE BRACKETS AND ANGLES ATTACHED TO CURTAIN
WALL PER MANUFACTURERE'S INSTALLATION REQUIREMENTS. STANDARD SQUARE
FASCIA PAINTED TO MATCH CURTAIN WALL. SINGLE SHADE - SEE FINISH
NOTES.
SHADECLOTH IS CENTERED ON MULLIONS
A106
2
Sim
A106
R EG
I T EC
EXPIRATION DATE 12/31/2017
ISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2 T 513.241.4474 F
513.241.0081
Drawn By
Checked By
Project Number
Client Number
3/ 21
/2 01
6 7:
50 :1
8 PM
45207
3/8" = 1'-0"A106 1 PARTIAL FLOOR PLAN - LEVEL 3
No. Description Date
LINE INDICATION OF FINISHED CEILING
CONTROL JOINT. PROVIDE CONTROL JOINTS SPACED 30'-0" O.C. MAXIMUM AT
CLOSEST DOOR JAMB LOCATION WITHIN MAXIMUM ALLOWED SPACING.
FRAME AS SCHEDULED
DOOR AS SCHEDULED
JAMB ANCHER (S)
SECURE JAMB STUDS TO STUDS STRUCTURE ABOVE
COORDINATE STUD SIZE WITH SPECS AND PARTITION SCHEDULE
TYPICAL CEILING HEIGHT AS INDICATED ON CEILNG PLAN
CRIPPLE STUD AT CONTROL JOINT LOCATIONS. REFER TO
SPECIFICATIONS.
FLAT STRAP
DOOR TYPE-F
* - MATCH EXISTING
WOOD TRIM APPLIED TO SURFACE. PROFILE TO MATCH EXST BOOKSTORE
DOORS.
INTERIOR FLUSH DOOR
FRAME TYPE-1
PATTERN
WITH TRANSOM MATCH EXISING BOOKSTORE FRAME. COORDINATE WITH WOOD
TRIM
REQUIREMENTS.
WITH TRANSOM MATCH EXISING BOOKSTORE FRAME. COORDINATE WITH WOOD
TRIM
REQUIREMENTS. 1'
-1 1
GLASS AREA APPROX = 2,130SI
HOLLOW METAL FRAME - CAULK FRAME PERIMETER BOTH SIDES
METAL STUD HEADER
5/8" GYPSUM WALLBOARD (TYPE "X" WHERE SCHEDULED) ON METAL STUDS.
CONTINUE STUDS, GWB, AND SOUND ATTENUATION BATTS (WHERE SCHEDULED)
TO DECK U.N.O.
1/2" 1/2"
5/ 8"
HOLLOW METAL FRAME - CAULK FRAME PERIMETER BOTH SIDES. ANCHORS AS
SPECIFIED.
METAL STUD TO HEADER
5/8" 2"
1/ 2"
1/ 2"
2" 1
5/8" GYPSUM WALLBOARD (TYPE "X" WHERE SCHEDULED) ON METAL
STUDS.
GENERAL NOTES SEE FINISH AND MATERIAL SCHEDULE. HARDWARE FINISH TO
MATCH EXISTING BOOKSTORE HARDWARE FINISH. MATCH EXISTING BUILDING
DOOR HARDWARE TYPES AND MANUFACTURERS FOR LIKE APPLICATIONS.
HARDWARE SET 1 (INTERIOR STORAGE) 3 HEAVY DUTY HINGES 1 STOREROOM
LOCKSET (SCHLAGE: D 80 PD) 1 WALL STOP 1 CYLINDER RIGID VINYL WALL
PROTECTION, BOTH SIDES DOOR (SEE MATERIAL AND FINISH SCHEDULE)
RIGID VINYL DOOR EDGE PROTECTION (SEE MATERIAL AND FINISH
SCHEDULE)
HARDWARE SET 2 (INTERIOR PAIR, STEERAGE WITH ONE INACTIVE LEAF) 3
HEAVY DUTY HINGES 1 STOREROOM LOCKSET (SCHLAGE: D 80 PD) 2 FLUSH
BOLTS 1 DUSTPROOF STRIKE 2 OVERHEAD STOPS 1 CYLINDER RIGID VINYL
WALL PROTECTION, BOTH SIDES DOOR (SEE MATERIAL AND FINISH SCHEDULE)
RIGID VINYL DOOR EDGE PROTECTION (SEE MATERIAL AND FINISH
SCHEDULE)
HARDWARE SET 3 (INTERIOR PAIR – ENTRY, RATED) 3 EXTRA HEAVY DUTY
HINGES 1 SET AUTO FLUSH BOLTS 1 EA DUSTPROOF STRIKE 2 EA CLOSERS 1
COORDINATOR WITH FILLER AND BRACKETS 1 SET SMOKE GASKETS/ SEALS 1
ASTRAGAL 1 CLASSROOM LOCKSET (SCHLAGE: D70 PD) 1 CYLINDER 1
ELCTRIFIED WALL MAGNETIC HOLD OPENS - SEE ELECTRICAL SPECIFICATIONS
POWER -- SEE ELECTRICAL DRAWINGS NOTE: MATCH EXISTING BOOKSTORE
HARDWARE. DOORS TO RELEASE WITH ACTIVATION OF FIRE ALARM, SMOKE
EVAC SYSTEM OR SMOKE DETECTORS.
HARDWARE SET 4 (EXISTING INTERIOR STAIR) REMOVE ALARM / SOUNDER.
NOTE: PROVIDE FREE ACCESS IN AND OUT OF DOOR.
HARDWARE SET 5 (EXISTING EXTERIOR STAIR) REPLACE EXTERIOR GASKETS.
CARD READER - MATCH EXISTING BUILDING SYSTEM. MOUNT TO BE ADA
COMPLIANT. POWER SUPPLY - SEE ELECTRICAL DRAWINGS. NOTE: MODIFY
EXISTING DOOR TO PROVIDE ACCESS CONTROL FOR STUDENT/ STAFF ONLY
ENTRY FROM THE EXTERIOR INTO THE STAIR. COORDINATE WITH ELECTRICAL
DRAWINGS AND OWNER. DOOR MUST ALWAYS ALLOW FREE OUT.
HARDWARE SETS
W AL
L TY
R EG
I T EC
EXPIRATION DATE 12/31/2017
ISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2 T 513.241.4474 F
513.241.0081
Drawn By
Checked By
Project Number
Client Number
3/ 21
/2 01
6 7:
50 :2
7 PM
45207
NUMBER ROOM DOOR FRAME DETAIL FIRE
RATING HARDWARE COMMENTSTO ROOM NAME WIDTH HEIGHT MATERIAL TYPE
THK. TYPE MATERIAL HEAD JAMB
110 STUDENT LOUNGE 6' - 0" 7' - 0" WD FP 0' - 2" 2 HM * * 3/4-HR 3
*SEE DETAILS; PAINT FRAME TO MATCH WD TRIM; DOOR IS COMPONENT OF
ATRIUM LIFE SAFETY CLOSURE SYSTEM; PROVIDE ASTRGAL
110A STOR 6' - 0" 7' - 0" WD F 0' - 2" 1 HM 1 2 2 DOOR PROTECTION
PANEL 110B STOR 6' - 0" 7' - 0" WD F 0' - 2" 1 HM 1 2 2 DOOR
PROTECTION PANEL 110C STOR 4' - 0" 7' - 0" WD F 0' - 2" 1 HM 1 2 1
DOOR PROTECTION PANEL ST1-Ca STAIR C 3' - 0" 7' - 0" EXST EXST 0' -
2" EXST HM 1-HR 4 MODIFY EXISTING RATED HARDWARE ST1-Cb STAIR C 3'
- 0" 7' - 0" EXST EXST 0' - 2" EXST HM 1-HR 5 MODIFY EXISTING
HARDWARE
1/2" = 1'-0"A111 B DOOR TYPICAL CONTROL JOINT DETAIL
1/2" = 1'-0"A111 A DOOR TYPICAL TYPICAL DETAIL
1/2" = 1'-0"A111 C DOOR AND FRAME TYPES
3" = 1'-0"A111 1 DOOR HEAD DETAIL - #1
3" = 1'-0"A111 2 DOOR JAMB DETAIL - #2
BORROWED LITES
3" = 1'-0"A111 7 BORROWED LIGHT SILL @ FLOOR
3" = 1'-0"A111 4 BORROWED LIGHT JAMB
110C - HM / FRAME TYPE 3/ FIRE RATING = 3/4-HOUR / SEE BORROWED
LITE DETAILS THIS SHEET. REMARK: PROVIDE RATED HM FRAME. GLASS FIRE
PROTECTION PROVIDED BY DELUGE SPRINKLERS - SEE FIRE PROTECTION
DRAWINGS. PROVIDE GLASS STOPS AND GASKETS TO MEET CODE LOAD AND
RATING REQUIREMENTS.
No. Description Date
-
-
VP-2
Align
Align
Align
NOTE: EXTENT OF BOOKSTORE FINISH WORK IS TO BE DETERMINED BY
FOLLETT CORPORATE.
WORK WILL BE DONE BY TENANT, WITH THE EXCEPTION OF ALTERNATE #A01
DEMOLITION - IF IT IS ACCEPTED.
ENTRANCE ALCOVE NOTES 10, 11
NOTE 12
3'-1 1/2"
5'-3 3/4"
TC-1 TEXTILE COMPOSITE FLOORING MANUF.: KINETEX STYLE: UMBRA (1819)
COLOR: 1766 ECLIPSED SIZE: 18" X 36" BACKING: POLYESTER FELT
CUSHION INSTALLATION:ASHLAR - DIRECTION FROM ENTRANCE TO SOUTH
WINDOW REP: ERIN RINK:
[email protected]
TC-2 TEXTILE COMPOSITE FLOORING MANUF. KINETEX STYLE: PROPEL (
1817) COLOR: 1708 OUTPACE SIZE: 18" X 36" BACKING: POLYESTER FELT
CUSHION INSTALLATION:ASHLAR - DIRECTION FOLLOWING STRIPE DIRECTION
REP: ERIN RINK:
[email protected]
VP-1 VINYL PLANK RESILIENT FLOORING MANUF.: CENTIVA STYLE: EVENT
COLOR: WP-3315-E TG MAHOGONY -
SUBMIT SAMPLE FOR FINAL APPROVAL SIZE: 4" X 36" SURF. TEXT.: (TG)
STANDARD (SE) SQ. EDGE REP: MARY SIEWE:
[email protected]
VP-2 VINYL PLANK RESILIENT FLOORING MANUF.: CENTIVA STYLE: CONTOUR
COLOR: CP-3201-C-TK GRAPPA NOCE SIZE: 4" X 36" SURF. TEXT.: (NG)
NATURAL GRAIN EDGE: SQUARE EDGE (SE) REP: MARY SIEWE:
[email protected]
B-1 4" RUBBER BASE MANUF.: JOHNSONITE COLOR: #48 GRAY SIZE: 4"
COVED BASE REP: ROD SEABOLT:
[email protected]
GL-1 BACK PAINTED GLASS COLUMN PANELS MANUF.: SEE SPECIFICATIONS
COLOR: SHERWIN WILLIAMS SW6537 LUXE BLUE SIZE: 1/4" TEMPERED
INSTALLATION:SEE DRAWINGS & SPECIFICATIONS
WB-1 WOOD BASE DETAIL.: SEE SHEET A104 FINISH: TO MATCH VP-1 -
SUBMIT SAMPLE FOR APPROVAL SIZE: 4" HT x 3/4" - SEE DETAIL
2/A104
WP-1 .060 WALL PROTECTION SHEET MANUF.: INPRO COLOR: TAUPE 0113
SIZE: 4'-0" HT - SET ON TOP OF 4" BASE INSTALLATION:SEE DRAWINGS
REP: CHRIS WALSH:
[email protected]
WP-2 DOOR PROTECTION SHEET MANUF.: INPRO COLOR: 0545 CROWN
CHERRY
SUBMIT SAMPLE FOR FINAL APPROVAL SIZE: 4'-0" HT - SET ON TOP OF
BASED THICKNESS: .060 INSTALLATION:SEE DRAWINGS REP: CHRIS WALSH:
[email protected]
ACT-1 ACOUSTICAL CEILING TILE MANUF.: ARMSTRONG STYLE: CALLA SQUARE
TEGULAR SIZE: 24" X 24" IN 9/16" PRELUDE SYPRAFINE GRID COLOR:
STONE
*SEE NOTES 14, 15
ACT-2 ACOUSTICAL CEILING TILE MANUF.: ARMSTRONG STYLE: ULTIMA 1942
BEVELED TEGULAR EDGE SIZE: 24" X 24" IN 9/16" PRELUDE SUPRAFINE
GRID COLOR: WHITE TILES IN WHITE GRID AND TRIM
WC-1 WOOD PLANK CEILING MANUF.: ARMSTRONG STYLE: WOODWORKS PLANK
SIZE: 4" PLANK - NATURAL VARIATIONS COLOR: DARK CHERRY (W1) REP:
MONTY GILLESPIE:
[email protected]
P-1 WALL PAINT MANUF.: SHERWIN WILLIAMS COLOR: SW7043 WORLDLY GRAY
FINISH: EGGSHELL
AX-1 METAL CEILING FACIA TRIM MANUF.: ARMSTRONG STYLE: AXION SIZE:
4" HEIGHT COLOR:WHITE/ GREY MATCH CEILING COLOR
SCH-1 VERTICAL METAL TRIM MANUF.: SCHLUTER FINISH: NATURAL ANODIZED
ALUM. SIZE: SEE DRAWINGS
P-2 WALL PAINT TO MATCH EXISTING ATRIUM VINYL WALLCOVERING
B-2 WOOD BASE STAIN TO MATCH EXISTING WOOD BASE IN ATRIUM
CORRIDOR
C-1 CARPET TO MATCH EXISTING CARPET IN ATRIUM CORRIDOR XAVIER STOCK
NOTED TO BE AVAILABLE SEE XAVIER FACILITIES
WB-2 WOOD BASE DETAIL.: SEE SHEET A104 FINISH: TO MATCH VP-1 -
SUBMIT SAMPLE FOR APPROVAL SIZE: 8" HT x 3/4" - SEE DETAIL
1/A104
ST
R EG
I T EC
EXPIRATION DATE 12/31/2017
ISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2 T 513.241.4474 F
513.241.0081
Drawn By
Checked By
Project Number
Client Number
3/ 21
/2 01
6 7:
51 :1
8 PM
45207
FINISH SCHEDULE
FINISH NOTES 1. ALL FINISHES TO BE INSTALLED PER MANUFACTURER'S
DIRECTIONS.
2. ALL ACCESS PANEL DOORS, GRILLES, ETC. TO BE PAINTED TO MATCH
WALL COLOR.
3. ALL HOLLOW METAL DOOR FRAMES TO BE PAINTED TO MATCH WALL COLOR.
SEE SPECIFICATIONS FOR PAINT FINISH.
4. REFER TO SPECIFICATIONS SECTION 09260 FOR DRYWALL LEVEL
INFORMATION.
5. PROVIDE DETAILED SEAM LAYOUT SHOP DRAWINGS FOR ALL FLOORING
PATTERNS.
6. STANDARD WALL COLOR THROUGHOUT TO BE CODE "P-1", UNLESS NOTED
OTHERWISE.
7. SEE ELEVATIONS SHEET FOR EAST STAGE WALL DETAILS.
8. STANDARD HT. FOR WALL PROTECTION IN ALL STORAGE ROOMS TO 4'-4" -
4'-0" WP-1 WALL PROTECTION SHEET ABOVE THE 4" RESILIENT BASE.
9. NOTIFY ARCHITECT OF ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD
CONDITIONS.
10. CARPET IN NEW ALCOVE TO MATCH BOOKSTORE ALCOVE CARPET AND TO BE
PULLED FROM EXISTING CAMPUS STOCK.
11. DRYWALL CEILING IN NEW ALCOVE TO BE PAINTED TO MATCH CEILING IN
BOOKSTORE ALCOVE.
12. REMOVE EXISTING VINYL WALLCOVERING FROM SIDE WALL TO NEW
ENTRANCE. PAINT TO MATCH VWC.
13. BOOKSTORE FINISH REPLACEMENT / PATCHING TO BE DETERMINED BY
FOLLETT CORPORATE.
14. ALL CEILINGS NOTED ACT-1 ARE ARMSTRONG TILE COLOR STONE.
PRELUDE GRID AND AXIOM TRIM FOR THESE CEILINGS ARE TO MATCH THE
TILE COLOR STONE.
15. BEFORE CEILING INSTALLATION, A TECHNICAL REVIEW BETWEEN THE
CONTRACTOR AND THE MANUFACTURER IS REQUIRED.
16. BASIS OF DESIGN FOR SHADES ARE MECHOSHADE SATIN WEAVE 1-2%
OPEN, DIAMONWEAVE, SERIES 3000, 3200, 3300 - THERMOVEIL. THIS
APPLIES ALSO TO THE THIRD FLOOR LOUNGE WINDOWS DETAILED ON SHEET
A1.08.
17. ALL FINISHES ARE PENDING PER FINAL APPROVAL OF SUBMITTED
SAMPLES.
18. PROVIDE SCHLUTER SCHIENE ALUMINUM FINISH TRANSITION STRIPES
BETWEEN TC-1/TC-2 TEXITLE COMPOSITE FLOORING TILES AND VP-1/VP-2
VINYL PLANK FLOORING.
19. WB-2 BASE TO BE PROVIDED AT THE 4 CENTRAL COLUMNS WITH
BACK-PAINTED GLASS CLADDING ONLY. SEE DETAIL 2/A103.
110 STUDENT CENTER
EAST WALL
SOUTH WALL
ACT-1
ACT-1
ACT-1
NOTES 10, 11, 12
No. Description Date
R EG
I T EC
EXPIRATION DATE 12/31/2017
ISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2 T 513.241.4474 F
513.241.0081
Drawn By
Checked By
Project Number
Client Number
3/ 21
/2 01
6 7:
51 :2
6 PM
45207
No. Description Date
1 2 3
F03
F03
F01
F01
F01
ISSUANCESISSUANCESISSUANCESISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2
T 513.241.4474 F 513.241.0081
ProjectProjectProjectProject NumberNumberNumberNumber
ClientClientClientClient NumberNumberNumberNumber
WWW.KLHENGRS.COM
41075 800-354-9783 859-442-8050
3 /1
8 /2
45207
EXISTING FCA
KEYED NOTES
F03 EXISTING TO BE REMOVED AND RELOCATED FOR NEW CEILING.
No. Description Date
1 2 3
N
A.F.F.?
F01
F01
F04N
N
F04
F02
N
N
N
N
N
N
ISSUANCESISSUANCESISSUANCESISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2
T 513.241.4474 F 513.241.0081
ProjectProjectProjectProject NumberNumberNumberNumber
ClientClientClientClient NumberNumberNumberNumber
WWW.KLHENGRS.COM
41075 800-354-9783 859-442-8050
3 /1
8 /2
45207
KEYED NOTES
F04 PROVIDE WATER CURTAIN AT GLASS ENTRY.
GENERAL NOTES A. COVERS SHALL BE CHROME / ALUMINUM IN THE STUDENT
LOUNGE.
COORDINATE WITH ARCHITECT PRIOR TO PURCHASING.
No. Description Date
1 2 "
S A
10"ø SA
10"ø SA
= EXISTING WORK TO BE DEMOLISHED BY CONTRACTOR
= NEW WORK BY CONTRACTOR
= EXISTING WORK TO REMAIN
ISSUANCESISSUANCESISSUANCESISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2
T 513.241.4474 F 513.241.0081
ProjectProjectProjectProject NumberNumberNumberNumber
ClientClientClientClient NumberNumberNumberNumber
WWW.KLHENGRS.COM
41075 800-354-9783 859-442-8050
3 /1
8 /2
45207
KEYED NOTES
M02 REMOVE EXISTING JOHNSON CONTROL THERMOSTAT AND REMOVE WIRE BACK
TO VAV CONTROLLER.
No. Description Date
350 CFM
350 CFM
280 CFM
245 CFM
255 CFM
255 CFM
255 CFM
255 CFM
255 CFM
350 CFM
350 CFM
14"x12" SA
1 8 "
S A
210 CFM
220 CFM
220 CFM
220 CFM
220 CFM
220 CFM
220 CFM
220 CFM
62"x16" SA
10"ø SA
= EXISTING WORK TO BE DEMOLISHED BY CONTRACTOR
= NEW WORK BY CONTRACTOR
= EXISTING WORK TO REMAIN
ISSUANCESISSUANCESISSUANCESISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2
T 513.241.4474 F 513.241.0081
ProjectProjectProjectProject NumberNumberNumberNumber
ClientClientClientClient NumberNumberNumberNumber
WWW.KLHENGRS.COM
41075 800-354-9783 859-442-8050
3 /1
8 /2
45207
KEYED NOTES
M01 CONNECT NEW DUCTWORK TO EXISTING MAIN. CUT & PATCH AS
NECESSARY.
M03 INSTALL NEW SIEMENS THERMOSTAT AND INSTALL NEW WIRE BACK TO VAV
CONTROLLER.
M04 RELOCATE EXISTING LINEAR DIFFUSER TO NEW LOCATION SHOWN AND
BALANCE TO CFM INDICATED. PROVIDE NEW FLEX DUCT FROM MAIN TO
EXISTING LINEAR DIFFUSER
GENERAL NOTES A. ALL DIFFUSERS SHALL BE PAINTED MATCH THE CEILING
COLORS. COORDINATE
WITH ARCHITECTURAL PLANS.
No. Description Date
RECOMMENDATIONS AND PER CEILING FINISH.
PROVIDE GRID CLIPS PER MFG'R REQUIREMENTS.
PROVIDE FRAMING FOR DRYWALL
DUCTWORK
AND SHEET METAL SCREWS AT FLEX CONNECTION TO
DUCT. THEN PROVIDE STRAPPING AROUND
INSULATION.
1. MAXIMUM LENGTH OF INSUL. FLEX DUCT
EQUALS 5 FEET. FLEX NOT PERMITTED IN
INACCESSIBLE CEILINGS
HVAC CONTRACTOR
3. SCOOP
DAMPER
DRYWALL APPLICATIONS ONLY.
SYSTEMS THAT PENETRATE 1-HR FIRE
BARRIERS. REFER TO ARCHITECTURAL
SCALE:
24 (0.020 IN.)
22 (0.025 IN.)
20 (0.032 IN.)
18 (0.040 IN.)
16 (0.051 IN.)
1" X 16 GA. MIN (DUCTS OVER 2 SQ. FT.) MAX. 700
LBS. 1" X 18 GA. MIN (DUCTS UNDER 2 SQ. FT.) MAX.
420 LBS. FOR DUCTS OVER 49" WIDE, TURN METAL
STRAP UNDER BOTTOM OF DUCT AND FASTEN
NOT TO SCALE
BEAM CLAMP (MAX.
WEIGHT 500 LBS.)
AGENCIES HAVING
18 GAUGE ON WIDER BRANCHES
2. MAIN DUCT
BLADE, BRACKET & LOCKING
GALVANIZED OPERATOR PAD
TAKEOFFS
STRAIGHT INLET DIAMETER
TERMINAL DEVICE TAKEOFF
ACCESSIBLE CEILING.
MAXIMUM LENGTH OF 24" TO HARD DUCT
CONNECTION TO VAV BOX
CLEARANCE. PROVIDE ABOVE ACCESSIBLE
4. GALVANIZED THREADED ROD (CONNECT TO
STRUCTURE WITH DOUBLE NUT)
6. SHEET METAL DUCT INTO VAV BOX, MINIMUM
LENGTH OF 3 TIMES INLET DUCT DIAMETER
KEYED NOTES:
SYSTEMS THAT PENETRATE 1-HR FIRE
BARRIERS. REFER TO ARCHITECTURAL
6. SHEET METAL PLENUM
7. 1/2" ACOUSTICAL LINING
TYP, BOTH SIDES
10. VOLUME ADJUSTER
11. BAND CLAMP
BETWEEN SUPPORT BRACING
ADJUSTABLE MANUAL DAMPER. LOCATE
ACCESS PANEL BELOW DAMPER.
14. MANUAL VOLUME DAMPER
2. 1" WIDE BAND AND CLAMP.
3. SHEET METAL SCREW
4. INSULATED FLEX. DUCT
CEILINGS ONLY.
STRAPPING AROUND INSULATION
WINDOWS, ADJUST PATTERN CONTROLLER
TO DIRECT AIRFLOW HORIZONTALLY
ACTUATOR AND WIRING FOR VAV BOXES. TEMPERATURE CONTROLS CONTRACTOR
SHALL
FIELD OR FACTORY MOUNT CONTROLLER AT THEIR EXPENSE. VAV BOX
MANUFACTURER
SHALL FURNISH FLOW RING, ROUND DAMPER SHAFT FOR DIRECT MOUNTING
OF
ACTUATOR, AND CONTROL ENCLOSURE. TEMPERATURE CONTROLS CONTRACTOR
SHALL
PROVIDE TRANSFORMERS WITH CONNECTION TO LINE VOLTAGE JUNCTION BOX
ABOVE
CEILING PROVIDED BY ELECTRICAL CONTRACTOR IN VARIOUS LOCATIONS.
PROVIDE ROOM
TEMPERATURE SENSOR(S) WITH ROOM TEMPERATURE SETPOINT ADJUSTMENT
CAPABILITY (+/-
3 DEG. F., ADJUSTABLE THRU BAS) AND OVERRIDE FEATURE (2 HOURS,
ADJUSTABLE THRU
BAS).
2. ON A CALL FOR HEAT, VAV DAMPER SHALL MODULATE DOWN TO MINIMUM
SETPOINT POSITION
(15% adj.). ON A CALL FOR COOLING, CONTROL VALVE SHALL CLOSE AND
DAMPER SHALL
MODULATE OPEN TO SATISFY ROOM TEMPERATURE. PROVIDE SUPPLY AIR
TEMPERATURE
SENSOR TIED TO BAS.
3. CONTROL AND MONITORING POINTS SHALL INCLUDE BUT NOT BE LIMITED
TO THE FOLLOWING:
a. DAMPER POSITION (AO)
c. ZONE OCCUPANCY TEMPERATURE OVERRIDE (AI)
d. ACTUAL CFM (AI)
AI SPACE HUMIDITY
SYSTEM STATUS SIZE MAX CFM MIN CFM HMIN CFM EAT
VAV-14 NEW 14 1680 840 252 55
VAV-11 EXISTING 14 1590 795 795 55
FP-102 EXISTING 14 1520 760 1164 55
FP-101 EXISTING 14 1680 840 1180 55
HVAC VENTILATION SCHEDULE
ROOMNUM ROOMNAME SYSTEM ZONE AREA CLNGHT AIR CHGS OA CHGS PEOPLE
DES PEOPLE RED OA PER OA SQFT REQ SUP ACT SUP REQ OA ACT OA ACT RET
ACT EXH CRITICAL PRESSURE PCT OPERABLE NATURAL VENTILATION
109 BOOKSTORE 1 1 2121 0 0 0 20 20 7.5 0.06 1645 1680 329 336 1680
0 0.2059 E 0.0000
110 STUDENT CENTER 1 2 1761 0 0 0 20 20 7.5 0.06 1500 1530 300 306
1530 0 0.2091 E 0.0000
110A STOR 1 2 50 0 0 0 0 0 0 0.12 20 20 4 4 20 0 0.4 E 0.0000
110B STOR 1 2 66 0 0 0 0 0 0 0.12 20 20 4 4 20 0 0.5 E 0.0000
110C STUDENT CENTER 1 3 473 0 0 0 10 10 7.5 0.06 1490 1520 298 304
1520 0 0.0848 E 0.0000
110D STUDENT CENTER 1 4 475 0 0 0 15 15 7.5 0.06 1645 1680 329 336
1680 0 0.1047 E 0.0000
111 STOR 1 2 64 0 0 0 0 0 0 0.12 20 20 4 4 20 0 0.5 E 0.0000
1-C STAIR C 1 262 0 0 0 0 0 0 0 90 90 18 18 90 0 0 E 0.0000
HVAC PROJECT INFO / CODE SCHEDULE
LOCATION STATE TSQFT VENTILATION CODE BUILDING CODE MECHANICAL CODE
PLUMBING CODE FIRE CODE ELECTRIC CODE ENERGY CODE TOA TEX
CINCINNATI,OH OHIO 5272 2009 IMC IBC 2009 IMC 2009 IPC 2009 IFC
2009 NEC 2011
ASHRAE 90.1
HVAC ACCESSORIES
24. SHAFT GROUNDING BRUSHES
C i n c i n n a t i , O H 4 5 2 0 2
T 513.241.4474 F 513.241.0081
WWW.KLHENGRS.COM
M-501
KTW
CJS
MECHANICAL -
DETAILS
2010 NFPA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE
2009 INTERNATIONAL ENERGY CONSERVATION CODE
PROVIDE (1) 1" CONDUIT TO ABOVE ACCESSIBLE CEILING CAVITY UNLESS
NOTED OTHERWISE
COMMUNICATIONS OUTLET - VOICE/DATA/MISC. (PROVIDE 4"X4" OUTLET BOX
WITH 1-GANG RING)
COMMUNICATION/INFORMATION TECHNOLOGY
COORDINATE WITH SYSTEM INSTALLERS PRIOR TO INSTALLATION FOR
LOCATIONS, HEIGHTS, CONDUIT TERMINATIONS, ETC.
PR
PROVIDE (1) 1" CONDUIT TO ABOVE ACCESSIBLE CEILING CAVITY UNLESS
NOTED OTHERWISE
PROXIMITY READER/AUTHENTICATION DEVICE
SHADED LUMINAIRES DENOTE THOSE CONNECTED TO EMERGENCY POWER
SOURCE
(UNSWITCHED LUMINAIRES ARE EGRESS LIGHTS THAT OPERATE 24/7)
PROVIDE ALL REQUIRED ACCESSORIES (FITTINGS, END CAPS, POWER FEEDS,
ETC.)
TRACK LIGHTING IN LENGTH SHOWN AND WITH NUMBER OF LUMINAIRE HEADS
AS INDICATED
DECORATIVE LUMINAIRE / CHANDELIER
SINGLE / DOUBLE SIDED EXIT SIGN
CONNECT AHEAD OF SWITCHING & CONFIGURE ARROWS TO INDICATE
DIRECTION OF EGRESS TRAVEL
A,B,C
DUPLEX RECEPTACLE
DUPLEX RECEPTACLE - AT COUNTER HEIGHT OR SPECIAL HEIGHT - VERIFY IN
FIELD
DETERMINE EXACT NEMA CONFIGURATION IN FIELD CASE-BY-CASE
SPECIAL PURPOSE RECEPTACLE
CEILING DUPLEX RECEPTACLE
SHOWN AT SAME LOCATION ON DWGS. OF E & CT, THEY ARE THE SAME
DIV. 26 MULTI-SERVICE FLOOR OUTLET
FLOOR OUTLET - POWER AND / OR TECHNOLOGY (SEE SPECIFICATIONS FOR
TYPE DESIGNATION) - WHERETYPE
INDICATES CONNECTION TO EQUIPMENT
CIRCUIT BREAKER (CENTER) - FUSED SWITCH IN SWITCHGEAR OR
DISTRIBUTION BOARD (RIGHT)
ENCLOSED CIRCUIT BREAKER IN NEMA 1 ENCLOSURE UNLESS OTHERWISE NOTED
(LEFT)
T
TRANSFORMER
M
200A MCB
TRIANGLE SYMBOL (RIGHT) WITHIN PANELBOARD = PROVIDE WITH
FEED-THROUGH OR SUB-FEED LUGS
RECESSED OR SURFACE MOUNTED PANELBOARD AS INDICATED ON PLANS
1,3
(FULLY CONCEALED IN FINISHED AREAS, CONCEALED TO OVERHEAD STRUCTURE
IN UNFIN. AREAS)
CABLING/RACEWAY, CEILING OR WALL. SEE SPECS. FOR APPLICABLE
CONDUIT/RACEWAY REQ'TS.
S.C.
GFI / GFCI
DRAWINGS, DO NOT FEED DOWNSTREAM OUTLETS FROM LOAD SIDE TERMINALS
OF GFI RECEPTS.)
GROUND FAULT CIRCUIT INTERRUPTER DEVICE (UNLESS SPECIFICALLY NOTED
OTHERWISE ON
VM
DOUBLE DUPLEX ("QUAD") RECEPTACLE
MOUNTED AT COUNTER HEIGHT OR SPECIAL HEIGHT VERIFY IN FIELD
DOUBLE DUPLEX ("QUAD") RECEPTACLE
DOWNSTREAM OUTLETS FROM LOAD SIDE TERMINALS UNLESS SPECIFICALLY
NOTED OTHERWISE ON DWGS.
DUPLEX GFCI RECEPTACLE - COUNTER HEIGHT OR SPECIAL HEIGHT - VERIFY
IN FIELD - DO NOT FEED
FOR EACH SPD RECEPT. BRANCH CCT. PHASE CONDUCTOR - DO NOT SHARE
NEUTRALS)
DOUBLE-DUPLEX ("QUAD") RECEPTACLE - SURGE PROTECTIVE DEVICE
(PROVIDE DEDICATED NEUTRAL
FOR EACH SPD RECEPT. BRANCH CCT. PHASE CONDUCTOR - DO NOT SHARE
NEUTRALS)
DUPLEX RECEPTACLE - SURGE PROTECTIVE DEVICE (PROVIDE DEDICATED
NEUTRAL
SPECIAL PURPOSE RECEPTACLE (MOUNT AT, ON OR WITHIN COMMUNICATION
RACK/CABINET)
FIELD COORDINATE WITH EQUIPMENT INSTALLER AND DETERMINE NEMA
CONFIGURATION IN FIELD
CONDUIT UP OR DOWN
TYPE
WALL-MOUNTED OCCUPANCY SENSOR SWITCH. TYPE "IR"=INFRARED, TYPE
"US"=ULTRASONIC,
TYPE "DT"=DUAL TECH., "V"=VACANCY SENSOR, #= NUMBER OF CCTS. THAT
MAY BE CONTROLLED
(PROVIDE CONCEALED HEAVY-DUTY BLOCKING/ANCHORING IN WALL)
FIRE ALARM SYSTEM ELECTRO-MAGNETIC DOOR HOLDER
F
FIRE ALARM SYSTEM STROBE-ONLY UNIT
F
FIRE ALARM SYSTEM SPEAKER/STROBE UNIT
F
400
300
NON-FUSED HEAVY DUTY DISCONNECT SWITCH (LEFT) AND FUSED HEAVY DUTY
DISCONNECT SWITCH (RIGHT)
FLUSHNEMA 3R
200%N
PROVIDE ISOLATED GROUND BAR (LEFT) - PROVIDE 200% SIZED NEUTRAL
(RIGHT)
PROVIDE NEMA 3R OR OTHER INDICATED ENCLOSURE (LEFT) - PROVIDE FLUSH
ENCLOSURE (RIGHT)
SWITCHBOARD / DISTRIBUTION PANEL
PLAN-VIEW LINE TYPES
WORK SHOWN BOLD-CONTINUOUS INDICATES NEW WORK
(UNLESS INDICATED OTHERWISE)
WORK SHOWN FADED INDICATES EXISTING WORK TO REMAIN OR NEW WORK BY
OTHERS AS APPLICABLE
(UNLESS INDICATED OTHERWISE)
(UNLESS INDICATED OTHERWISE)
TAG
S
FIRE ALARM SYSTEM SMOKE DETECTOR - PHOTOELECTRIC TYPE | TAG "IZ" =
IONIZATION TYPE
TAG "SB" = AUDIO SOUNDER BASE
FIRE ALARM SYSTEM WALL MOUNTED DEVICES
EL
INDICATES AN EGRESS LIGHTING LUMINAIRE WIRED AHEAD OF ALL SWITCHING
AND INTENDED
TO PROVIDE REQUIRED EGRESS ILLUMINATION
THERMOSTAT
T
FP
RECEPTACLE TO BE USED FOR A FLAT PANEL DISPLAY.
VERIFY EXACT LOCATION AND HEIGHT OF RECEPTACLE WITH C.T.C. PRIOR TO
ROUGH-IN.
HOME RUN WITH CIRCUIT NUMBER(S)
C i n c i n n a t i , O H 4 5 2 0 2
T 513.241.4474 F 513.241.0081
WWW.KLHENGRS.COM
E-001
DTJ
AK
DIMENSION FROM DOOR FRAME OR WALL.
B. CONDUIT/CABLES SHALL BE ROUTED WHEREVER
NECESSARY TO KEEP DEVICES ALIGNED.
C. ALL DEVICES MOUNTED AT SAME HEIGHT TO BE
ALIGNED HORIZONTALLY.
AFTER INSTALLATION.
CENTER OF GROUP. PROVIDE SINGLE
FACEPLATE FOR GROUPS OF DEVICES WHERE
APPLICABLE.
EXIT
F
FIRE
RELAY PACK(S)
A. THIS DETAIL IS SCHEMATIC IN NATURE INTENDED TO INDICATE HOW
LOCAL SWITCHING
SHALL INTERACT WITH RELATED OCCUPANCY SENSORS. THERE MAY ALSO BE
OTHER
LIGHTING CONTROL ELEMENTS AS SHOWN ON PLAN OR IN DETAILS THAT APPLY
TO A
PARTICULAR AREA.
GENERAL NOTES:
NONE
265113.00-10
A. PROVIDE INDIVIDUAL ROOM LIGHTING CONTROLLER EQUAL TO STRAND,
ALTMAN, ACUITY BRANDS NLIGHT, COOPER FIFTH LIGHT, OR LUTRON
ECOSYSTEM WITH DMX AND 0-10V CONTROL CAPABILITY.
A.1. LIGHTING CONTROLLER SHALL BE EASILY PROGRAMMABLE BY OWNER
AFTER INSTALLATION. PROVIDE PROGRAMMABLE CONTROL STATION(S) IN
LOCATION(S) SHOWN AND AS SPECIFIED ABOVE . CONTROL STATIONS
SHALL BE PROVIDED WITH FIELD MODIFIABLE LABELS. COORDINATE FINAL
PRESETS WITH OWNER / ENGINEER PRIOR TO INSTALLATION.
A.2. PROVIDE MODULES TO CONTROL EACH ZONE (AS INDICATED ON
DRAWINGS) SEPARATELY. COORDINATE DIMMING / CONTROL REQUIREMENTS
WITH LUMINAIRE SCHED.
A.3. PROVIDE OCCUPANCY 100% DUAL TECHNOLOGY OCCUPANCY SENSOR
COVERAGE.
A.4. A NETWORKED / ADDRESSABLE SYSTEM IS ACCEPTABLE IF NECESSARY
FOR EASE OF COMMISSIONING.
A.5. PROVIDE SUBMITTALS THAT INCLUDE DETAILED ZONE LAYOUTS, CONTROL
DIAGRAMS, AND OCCUPANCY SENSOR PLACEMENT AND COVERAGES.
A.6. PROVIDE (1) DMX INPUT (LOCATED IN FIELD BY OWNER) FOR PORTABLE
DMX CONTROLLER OVERRIDE (CONTROLLER BY OTHERS).
PROVIDE LIST / MAP OF FINAL DMX CHANNELS TO THE OWNER FOR FUTURE
PROGRAMMING.
GENERAL
OWNER. COORDINATE A MEETING WITH THE OWNER
TO DETERMINE FINAL PROGRAMMING
OWNER. COORDINATE A MEETING WITH THE OWNER
TO DETERMINE FINAL PROGRAMMING
OWNER. COORDINATE A MEETING WITH THE OWNER
TO DETERMINE FINAL PROGRAMMING
OWNER. COORDINATE A MEETING WITH THE OWNER
TO DETERMINE FINAL PROGRAMMING
OWNER. COORDINATE A MEETING WITH THE OWNER
TO DETERMINE FINAL PROGRAMMING
(PORTABLE CONTROLLER). SEE NOTES BELLOW.
"Switching" Line
On/Off Control
A. PROVIDE EMERGENCY LIGHTING CONTROL UNIT THAT IS UL
OR ETL LISTED TO UL STANDARD 924. PROVIDE CONTACTS
RATED AT LEAST 20 AMPERES UP TO AT LEAST 277 VOLTS.
BASIS OF DESIGN FOR THIS DETAIL IS WATTSTOPPER
ELCU-200. MODIFY IF REQUIRED FOR OTHER
MANUFACTURERS.
ELCU-200 SERIES. LC&D, DOUGLAS LIGHTING AND LVS
CONTROLS ARE CONSIDERED EQUIVALENT.
NONE
265100.00-04
CS
C i n c i n n a t i , O H 4 5 2 0 2
T 513.241.4474 F 513.241.0081
WWW.KLHENGRS.COM
E-501
DTJ
AK
E10
ISSUANCESISSUANCESISSUANCESISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2
T 513.241.4474 F 513.241.0081
ProjectProjectProjectProject NumberNumberNumberNumber
ClientClientClientClient NumberNumberNumberNumber
WWW.KLHENGRS.COM
41075 800-354-9783 859-442-8050
3 /1
8 /2
45207
KEYED NOTES
No. Description Date
A
B
C
D
CECECECE
VE
VE
VE
VE
VE
ISSUANCESISSUANCESISSUANCESISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2
T 513.241.4474 F 513.241.0081
ProjectProjectProjectProject NumberNumberNumberNumber
ClientClientClientClient NumberNumberNumberNumber
WWW.KLHENGRS.COM
41075 800-354-9783 859-442-8050
3 /1
8 /2
45207
KEYED NOTES
E02 PROVIDE KEYED SWITCH FOR AUTHORIZED PERSONNEL TO TURN OFF "EL"
EGRESS LIGHTING IN THIS ROOM. PROVIDE UL924 LISTED EMERGENCY
LIGHTING CONTROL UNIT FOR SWITCH BYPASS WHEN POWER IS LOST TO FORCE
EGRESS LIGHTING TO 100% ON. SEE ELCU DETAIL.
E03 PROVIDE PROGRAMMABLE CONTROL STATION FOR CONTROL OF NORMAL
LIGHTING IN THIS ROOM. SEE DETAIL.
E05 MOUNT TYPE PS3 LUMINAIRES ABOVE WOOD CLOUD AS SHOWN TO
ILLUMINATE CEILING AROUND CLOUD. SEE ARCHITECTURAL DRAWINGS FOR
LUMINAIRE LOCAITON AND MOUNTING. TYPICAL.
E06 MOUNT TYPE PS3 LUMINAIRES TO SIDE OF WALL FURRING TO ILLUMINATE
SIDE WALLS. COORDINATE EXACT MOUNTING LOCATION IN FIELD WITH
ARCHITECT PRIOR TO ROUGH IN.
E09 PROVIDE NEW CORRIDOR LUMINAIRE TO MATCH EXISTING LUMINAIRES.
CONNECT TO EXISTING CORRIDOR CIRCUIT AND CONTROLS. EXISTING
CORRIDOR CIRCUIT IS SL2-3.
GENERAL NOTES A. ALL EGRESS LIGHTING AND EXIT SIGNS SHALL BE WIRED
AHEAD OF
SWITCHING.
ISSUANCESISSUANCESISSUANCESISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2
T 513.241.4474 F 513.241.0081
ProjectProjectProjectProject NumberNumberNumberNumber
ClientClientClientClient NumberNumberNumberNumber
WWW.KLHENGRS.COM
41075 800-354-9783 859-442-8050
3 /1
8 /2
45207
SCHEDULE SHALL APPLY IN ADDITION TO CATALOG SERIES.
B. LAMP, BALLAST AND TRANSFORMER INFORMATION IN SPECIFICATION SHALL
APPLY IN ADDITION TO INFORMATION IN LUMINAIRE SCHEDULE.
C. REFER TO DRAWINGS FOR MOUNTING TYPE, NUMBER OF FACES AND ARROWS
OF EXIT SIGNS.
D. ALL COMPACT FLUORESCENT LUMINAIRES WITH T-5 LAMPS AND SMALLER TO
HAVE END-OF-LIFE CIRCUIT CUTOUT FEATURE EQUAL TO OSRAM-SYLVANIA
"QUICK-SENSE".
E. ALL 3 AND 4 LAMP PARABOLIC FLUORESCENT TROFFERS SHALL HAVE 2
BALLAST COMPARTMENTS.
F. ALL RECESSED TROFFER HOUSINGS CONSTRUCTED WITHOUT ROLLED EDGES
SHALL BE POST PAINTED.
G. ALL RECESSED TROFFER DOOR FRAMES SHALL BE SECURED WITH SPRING
LATCHES.
H. VERIFY LUMINAIRE, LAMP AND VOLTAGE COMPATIBILITY.
I. LAMP QUANTITY REFERS TO NUMBER OF LAMPS IN CROSS SECTION, UNLESS
OTHERWISE NOTED.
J. LENS DIMENSION REFERS TO OVERALL THICKNESS, MAXIMUM PENETRATION
OF PRISM TO BE .080".
K. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING EACH
LUMINAIRE LOCATION WITH THE ARCHITECTURAL REFLECTED CEILING PLANS
AND FOR VERIFYING AND PROVIDING THE MOUNTING SYSTEM REQUIRED FOR
EACH LUMINAIRE. THE CONTRACTOR ALSO PROVIDE PLASTER FRAMES, WALL
BRACKETS, SUPPORTS, OR OTHER APPURTENANCES AS REQUIRED FOR PROPER
INSTALLATION.
L. CLEAN WHITE COTTON GLOVES SHALL BE WORN WHEN HANDLING THE
LUMINAIRES' EXPOSED REFLECTIVE SURFACES. THE CONTRACTOR SHALL CLEAN
ALL SURFACES, INCLUDING DUST, FINGERPRINTS, PAINT, ETC. WITH A
CLEAN DRY CHEESECLOTH AFTER ALL INTERIOR WORK HAS BEEN COMPLETED.
PLASTIC SHIPPING BAGS SHALL REMAIN ON THE LUMINAIRES UNTIL WORK IS
COMPLETED.
M. ALL LUMINAIRES HAVE A STATIC AIR FUNCTION, UNLESS OTHERWISE
NOTED.
N. ALL LUMINAIRES ARE NON-IC, UNLESS OTHERWISE NOTED.
O. ALL LUMINAIRES ARE U.L. DAMP LISTED, UNLESS OTHERWISE
NOTED.
P. MOUNTING HEIGHTS INDICATED ARE TO THE BOTTOM OF THE LUMINAIRE,
UNLESS OTHERWISE NOTED.
Electric Luminaire Schedule
Ballast / Driver Qty Ballast / Driver Finish Comments Fixture Load
Voltage
A3Z LED PRISMATIC LITHONIA 2TL4 DAYBRITE SPS COLUMBIA LLT24
WILLIAMS 50G METALUX 24GR
4'x2'x3-3/4" RECESSED STEEL 0.125" MINIMUM PATTERN 12 PRISMATIC
ACRYLIC LENS
1 65W LED, 3500K, 80 CRI
6400 NOMINAL LUMENS
1 ELECTRONIC INTEGRAL DRIVER, MVOLT
WHITE FLAT STEEL DOOR FRAME, FIELD REPLACABLE LED MODULE AND
DRIVER
65 VA 277 V
CE EXISTING - PRISMATIC TROFFER
EXISTING - RELOCATED FROM DEMOLITION RECESSED 3 T8 32W ELECTRONIC
RELOCATE FROM DEMOLITION - SEE DEMOLITION SHEET
96 VA 277 V
CHLORIDE CXL LITHONIA LQM DUAL-LITE LX SURELITES LPX WILLIAMS
EXIT
12"x8"x2" UNIVERSAL, REFER TO PLAN
THERMOPLASTIC STENCIL FACE 1 0W LED, WITH SIGN
0 NO BALLAST WHITE RED LETTERS, AC ONLY 1 VA 277 V
PS1 DECORATIVE PENDANT
TBD BY ARCHITECT 1 LED 1 ELECTRONIC, INTEGRAL DRIVER, 0-10V
DIMMABLE
50 VA 277 V
OPTOLUM FINELINE LP LITHONIA LED LINEAR WAC LIGHTING OR EQUAL
1"x1/2" - CONTINUOUS LENGTH
SURFACE STEEL OPAL 1 3.8W /FT LED, 3500K, 80+CRI
330 LUMENS / FT 1 INTEGRAL ELECTRONIC, MVOLT, 0-10V DIMMING
WHITE PROVIDE CONTINUOUS LENGTHS AS SHOWN ON DRAWINGS (2' LENGTHS
HAVE BEEN DRAWN FOR SCHEMATIC PURPOSES ONLY). PROVIDE ALL NECESSARY
POWER SUPPLIES AND ACCESSORIES FOR A FULLY OPERABLE SYSTEM.
8 VA 277 V
CSL LIGHTING MR16 (PER EXISTING DRAWINGS) OR EQUAL
ALUMINUM 1 35W MR16 GU10 1 TRANSFORMER LUMINAIRE SHALL MATCH THE
EXISTING LUMINAIRES IN SIMILAR LOCATIONS
35 VA 277 V
PS5 ADJUSTABLE COVE LIGHT
1.5"x1.5" - CONTINUOUS LENGTH
SURFACE STEEL FROSTED 1 4W /FT LED, 3500K, 80+CRI
330 LUMENS / FT 1 INTEGRAL ELECTRONIC, MVOLT, 0-10V DIMMING
WHITE AIM IN FIELD WITH ARCHITECT, PROVIDE CONTINUOUS LENGTHS AS
SHOWN ON DRAWINGS (2' LENGTHS HAVE BEEN DRAWN FOR SCHEMATIC
PURPOSES ONLY). PROVIDE ALL NECESSARY POWER SUPPLIES AND
ACCESSORIES FOR A FULLY OPERABLE SYSTEM.
8 VA 277 V
PS24 LINEAR FLUSH AXIS LIGHTING BEAM 4 A-LIGHT PRUDENTIAL MARK
ARCHITECTURAL LIGHTING FOCAL POINT FINELITE
4'x4"x4-7/8" RECESSED FLUSH STEEL SPOTLESS LENS 1 45W LED, 3500K,
80+CRI
4000 LUMEN 1 INTEGRAL ELECTRONIC, MVOLT, 0-10V DIMMING
WHITE VERIFY WIDTH WITH ARCHITECTURAL CEILING SLOTS 45 VA 277
V
VE EXISTING - TRACK EXISTING - RELOCATED FROM DEMOLITION 1 PAR 30
INC NA RELOCATE FROM DEMOLITION - SEE DEMOLITION SHEET
75 VA 120 V
VS THEATRICAL TRACK LIGHTING
SURFACE 1 50W LED RGBA IQ38
1 INTEGRAL ELECTRONIC, DMX CONTROLLED
PROVIDE CUSTOM COLOR TO MATCH CEILING - COORDINATE WITH
ARCHITECTURAL DRAWINGS AND GET OWNER APPROVAL
PROVIDE BLACK DMX ENABLED TRACK, MOUNT TRACK TO HIGH CEILING
BETWEEN CLOUDS TO CONCEAL, PROVIDE ALL NECESSARY COMPONENTS FOR A
FULLY OPERABLE SYSTEM
50 VA 120 V
Z1 LED DOWNLIGHT PATHWAY 6VLFLX PORTFOLIO LD610 JUNO IC922LEDG3
LITEFRAME LF6LED5
6" DIAx15"x7-1/2" RECESSED ALUMINUM SEMI-SPECULAR REFLECTOR, MEDIUM
DOWNLIGHT OPTIC
1 25W LED, 3500K, 80 CRI
2000 LUMEN 1 ELECTRONIC, INTEGRAL DRIVER, 0-10V DIMMABLE
SELF TRIM REMOTE PHOSPHOR LENS, FIELD REPLACABLE LED MODULE AND
DRIVER
25 VA 277 V
Interior Lighting Compliance Certificate
Project Type: Alterations
Section 2: Interior Lighting and Power Calculation Floor Area (sq.
ft.) 6,386
Watts per sq. ft. 1.2
Allowed Watts 7,663
Complies Yes
Section 3: Interior Lighting Fixture Schedule Type Lamp Type
Ballast / Driver Lamp Qty Count Load Total Load
A3Z 65W LED, 3500K, 80 CRI ELECTRONIC INTEGRAL DRIVER, MVOLT 1 3 65
VA 195 VA
CE T8 32W ELECTRONIC 3 11 96 VA 1056 VA
EXISTING 2X4 T8 32W ELECTRONIC 3 19 96 VA 1824 VA
PS1 LED ELECTRONIC, INTEGRAL DRIVER, 0-10V DIMMABLE 1 4 50 VA 200
VA
PS3 3.8W /FT LED, 3500K, 80+CRI INTEGRAL ELECTRONIC, MVOLT, 0-10V
DIMMING 1 20 8 VA 152 VA
PS4 35W MR16 TRANSFORMER 1 1 35 VA 35 VA
PS5 4W /FT LED, 3500K, 80+CRI INTEGRAL ELECTRONIC, MVOLT, 0-10V
DIMMING 1 79 8 VA 632 VA
PS24 45W LED, 3500K, 80+CRI INTEGRAL ELECTRONIC, MVOLT, 0-10V
DIMMING 1 21 45 VA 945 VA
Z1 25W LED, 3500K, 80 CRI ELECTRONIC, INTEGRAL DRIVER, 0-10V
DIMMABLE 1 52 25 VA 1300 VA
6339 VA
- 1SR5-A
E04
USB
USB
E04
UP TO SR5-A ISSUANCESISSUANCESISSUANCESISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2
T 513.241.4474 F 513.241.0081
ProjectProjectProjectProject NumberNumberNumberNumber
ClientClientClientClient NumberNumberNumberNumber
WWW.KLHENGRS.COM
41075 800-354-9783 859-442-8050
3 /1
8 /2
45207
KEYED NOTES
E01 COORDINATE EXACT TECHNOLOGY POWER AND PATHWAY LOCATIONS AND
REQUIREMENTS WITH OWNER / TECHNOLOGY CONTRACTOR PRIOR TO ROUGH
IN.
E04 PROVIDE DARK BROWN (TO MATCH BASEBOARD) USB RECEPTACLES
INSTALLED HORIZONTALLY IN THE BASEBOARD. COORDINATE EXACT LOCATION
IN FIELD WITH ARCHITECT PRIOR TO ROUGH IN.
E07 PROVIDE POWER AND CONTROL FOR SHADES. COORDINATE EXACT
REQUIREMENTS WITH SHADE MANUFACTURER PRIOR TO ROUGH IN.
E08 COORDINATE CONTROL SWITCH WALLS IN FIELD WITH OWNER PRIOR TO
ROUGH IN. LAYOUT ALL CONTROLS IN A NEAT CLEAN LAYOUT.
1/8" = 1'-0"EP101
No. Description Date
C i n c i n n a t i , O H 4 5 2 0 2
T 513.241.4474 F 513.241.0081
WWW.KLHENGRS.COM
EP601
DTJ
AK
ELECTRIC -
ISSUANCESISSUANCESISSUANCESISSUANCES
t h i n k c h a m p l i n . c o m
C i n c i n n a t i , O H 4 5 2 0 2
T 513.241.4474 F 513.241.0081
ProjectProjectProjectProject NumberNumberNumberNumber
ClientClientClientClient NumberNumberNumberNumber
WWW.KLHENGRS.COM
41075 800-354-9783 859-442-8050
3 /1
8 /2
45207
PANEL SCHEDULE LEGEND
(EX) = EXISTING CIRCUIT TO REMAIN (#) = NEW CIRCUIT TO EXISTING
CIRCUIT BREAKER (G) = PROVIDE GROUND-FAULT CIRCUIT INTERRUPTER
(GFCI) CIRCUIT BREAKER (GE) = PROVIDE GROUND-FAULT EQUIPMENT
PROTECTION (GFEP) CIRCUIT BREAKER (ST) = PROVIDE SHUNT TRIP CIRCUIT
BREAKER (A) = PROVIDE ARC FAULT CIRCUIT INTERRUPTER (AFCI) CIRCUIT
BREAKER (L) = PROVIDE LOCK-ON DEVICE (LT) = PROVIDE
LOCK-OUT/TAG-OUT DEVICE (->) = CONNECT BRANCH CIRCUIT, WHICH WAS
DISCONNECTED FROM ANOTHER
SOURCE AS PART OF SELECTIVE DEMOLITION, TO POLE SPACE(S) AND
BREAKER INDICATED, DETERMINE EXACT POLE ASSIGNMENT(S) BASED ON
EXISTING COLOR-CODING OF THE BRANCH CIRCUIT CONDUCTOR
INSULATION
PANEL SCHEDULE GENERAL NOTES A. PROVIDE HACR RATED BREAKERS ON ALL
MOTOR LOADS. B. PROVIDE LOCKING TYPE BREAKER FOR ALL LIFE SAFETY
AND NIGHT LIGHTING
BRANCH CIRCUITS. C. UNLESS INDICATED OTHERWISE ON PLANS OR
SCHEDULES, PROVIDE NEW BRANCH
OVERCURRENT PROTECTIVE DEVICE (OPD) BREAKER OR FUSED SWITCH, WITH
FUSE, AS APPLICABLE) IN CASES WHERE NEW CIRCUITS OR FEEDERS ARE
SHOWN CONNECTED TO EXISTING POWER DISTRIBUTION EQUIPMENT. PROVIDE
OPD MANUFACTURED BY THE SAME MANUFACTURER AS THE EXISTING EQUIPMENT
IN WHICH IT WILL BE INSTALLED. PROVIDE A.I.C. RATINGS THAT MEET OR
EXCEED THE RATINGS OF THE EXISTING EQUIPMENT AND OPD's.
Total Estimated Demand Amps: 47 A
Total Estimated Demand: 39157 VA
Total Connected Load: 39.0 kVA
Panel Totals
Kitchen Equipment 0 VA 0.00% 0 VA Existing Load Demand
Motor 0 VA 0.00% 0 VA 100.00%
Misc 0 VA 0.00% 0 VA Existing Load Demand Factor
Receptacle 0 VA 0.00% 0 VA 38542 VA
Lighting 492 VA 125.00% 615 VA Existing Connected Load
Load Classification Connected Load Demand Factor Estimated Demand
Existing Loads
Total Connected Load: 9.3 kVA 15.8 kVA 14.0 kVA
29 30
27 28
25 26
23 24
21 22
19 20
17 2.0 kVA 18
15 (EX) B LEVEL/ XMFR AISLE LTG. 20 A 1 2.0 kVA 2.0 kVA 16
13 2.0 kVA
14
11 (EX) EM LIGHTING LEVEL THREE 20 A 1 2.6 kVA 12
9 (EX) EM LIGHTING LEVEL TWO 20 A 1 2.2 kVA 1.5 kVA 1 20 A (EX)
10
7 (#) EMERGENCY LIGHTING 20 A 1 0.5 kVA 1.5 kVA 1 20 A (EX) 8
5 (EX) EM LIGHTING LOWER LEVEL 20 A 1 3.3 kVA 6.0 kVA 6
3 (EX) THEATRE EM LIGHTING 20 A 1 2.2 kVA 5.9 kVA 4
1 (EX) EXIT LIGHTS 20 A 1 0.4 kVA 4.9 kVA
3 60 A (EX) TEM
2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit
Description CKT
Notes: Existing Square D
Supply From: Voltage: 480V 3PH Phase: 3 Wire: 4 Location:
Panel Name: E
Total Estimated Demand: 16810 VA
Total Connected Load: 16.8 kVA
Panel Totals
Kitchen Equipment 0 VA 0.00% 0 VA Existing Load Demand
Motor 0 VA 0.00% 0 VA 100.00%
Misc 0 VA 0.00% 0 VA Existing Load Demand Factor
Receptacle 0 VA 0.00% 0 VA 16810 VA
Lighting 0 VA 0.00% 0 VA Existing Connected Load
Load Classification Connected Load Demand Factor Estimated Demand
Existing Loads
Total Connected Load: 4.9 kVA 5.9 kVA 6.0 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 (EX) SPARE TOWARDS GENERATOR 20 A 1 0.5 kVA 24
21 (EX) GENERATOR HEAT STRIP 20 A 1 0.4 kVA 22
19 (EX) GENERATOR BATTERY CHARGER 20 A 1 0.2 kVA 20
17 0.5 kVA 1 20 A (EX) CLOCK TOWER PANEL 18
15 (EX) ACCESS CONTROL - 1ST 20 A 1 0.5 kVA 0.5 kVA 1 20 A (EX) PUB
16
13 (EX) ELEVATOR CAB LIGHTING 20 A 1 0.5 kVA 0.5 kVA 1 20 A (EX)
PUB 14
11 (EX) FACP 20 A 1 0.5 kVA 0.5 kVA 1 20 A (EX) ACCESS CONTROL
12
9 (EX) FACP 20 A 1 0.5 kVA 10
7 (EX) THEATRE EGRESS 20 A 1 0.3 kVA 0.0 kVA 1 20 A (EX)
RECEPTACLES 8
5 (EX) ORCHESTRA PIT SUMP / WHEELCHAIR... 20 A 1 1.1 kVA 2.9 kVA
6
3 (EX) AHU-1 SUMP 20 A 1 1.1 kVA 2.9 kVA 4
1 (EX) ELEVATOR SUMP 20 A 1 0.5 kVA 2.9 kVA
3 30 A (EX) EMERGENCY DIMMERS
2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit
Description CKT
Notes: Existing Square D
Supply From: TEM Voltage: 208V 3PH Phase: 3 Wire: 4 Location:
Panel Name: EM
Total Estimated Demand: 28118 VA
Total Connected Load: 26.9 kVA
Panel Totals
Kitchen Equipment 0 VA 0.00% 0 VA Existing Load Demand
Motor 0 VA 0.00% 0 VA 100.00%
Misc 0 VA 0.00% 0 VA Existing Load Demand Factor
Receptacle 0 VA 0.00% 0 VA 21745 VA
Lighting 4938 VA 125.00% 6173 VA Existing Connected Load
Load Classification Connected Load Demand Factor Estimated Demand
Existing Loads
Total Connected Load: 13.2 kVA 7.7 kVA 6.0 kVA
29 2.1 kVA 30
27 2.5 kVA 28
26
7 (#) BOOKSTORE LIGHTING 20 A 1 2.5 kVA 8
5 (EX) OFFICE LIGHTING 20 A 1 1.3 kVA 2.6 kVA 1 20 A STUDENT LOUNGE
110 LIGHTING 6
3 (EX) ATRIUM LIGHTING 20 A 1 2.5 kVA 2.7 kVA 1 20 A (EX) ATRIUM
COVE 4
1 (EX) BOOKSTORE LIGHTING 20 A 1 3.1 kVA 2.6 kVA 1 20 A (EX) ATRIUM
COVE 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit
Description CKT
Notes: Existing Square D
Supply From: Voltage: 480V 3PH Phase: 3 Wire: 4 Location:
Panel Name: SL-2
Total Estimated Demand: 9555 VA
Total Connected Load: 9.6 kVA
Panel Totals
Kitchen Equipment 0 VA 0.00% 0 VA Existing Load Demand
Motor 0 VA 0.00% 0 VA 100.00%
Misc 0 VA 0.00% 0 VA Existing Load Demand Factor
Receptacle 0 VA 0.00% 0 VA 9555 VA
Lighting 0 VA 0.00% 0 VA Existing Connected Load
Load Classification Connected Load Demand Factor Estimated Demand
Existing Loads
Total Connected Load: 5.0 kVA 2.5 kVA 2.1 kVA
41 (EX) ENERGY MGMT. / HVAC SYSTEM 20 A 1 0.0 kVA 0.0 kVA 1 20 A
(EX) ICE CREAM MACHINE 42
39 (EX) PHONE BOARD 20 A 1 0.0 kVA 0.0 kVA 1 20 A (EX) CONTROL
BOOTH / VICTOR PERK 40
37 (EX) CONTROL KEEPER / LIGHT SYSTEM 20 A 1 0.0 kVA 0.0 kVA 1 20 A
(EX) CONTROL BOOTH / TRACK LIGHTING 38
35 (EX) CAP. MACHINE 20 A 1 0.0 kVA 0.0 kVA 1 20 A (EX) SOUND
SYSTEM 36
33 (EX) CAP. MACHINE 30 A 1 0.0 kVA 0.0 kVA 1 20 A (EX) SECURITY
SYSTEM 34
31 (EX) GAS VALVE FIREPLACE 20 A 1 0.0 kVA 0.0 kVA 1 20 A (EX)
32
29 (EX) VENDING RECEPTACLES 20 A 1 0.0 kVA 0.0 kVA 30
27 (EX) MARQUIS SIGN 20 A 1 0.0 kVA 0.0 kVA 2 20 A (EX)
CYBERCAFE
28
25 (EX) COFFEE MACHINE 20 A 1 0.0 kVA 0.0 kVA 1 20 A (EX) 26
23 (EX) COFFEE MACHINE 20 A 1 0.0 kVA 0.0 kVA 1 20 A (EX)
UNDERCOUNTER RECEPTACLES 24
21 (EX) BIG FRIDGE (COFFEE SHOP) 20 A 1 0.0 kVA 0.0 kVA 1 20 A (EX)
UNDERCOUNTER RECEPTACLES 22
19 (EX) SIGNAL PROCESSOR 20 A 1 0.0 kVA 0.0 kVA 20
17 (EX) INFO COUNTER LIGHTING 20 A 1 0.5 kVA 0.0 kVA 2 20 A (EX)
VICTORY PERK
18
15 (EX) ATRIUM WALL SCONCES 20 A 1 0.6 kVA 0.4 kVA 1 20 A (EX)
CYBERCAFE 16
13 (EX) DETAIL 114 LIGHTING 20 A 1 0.7 kVA 0.7 kVA 1 20 A (EX)
RECEPTACLES 14
11 (EX) OFFICE - WELCOME DESK... 20 A 1 1.1 kVA 0.5 kVA 1 20 A
(EX)RECEPTACLES 12
9 (EX) OFFICE RECEPTACLES 20 A 1 1.1 kVA 0.0 kVA 1 20 A (EX)
VENDING RECEPTACLES 10
7 (EX) OFFICE RECEPTACLES 20 A 1 1.1 kVA 0.5 kVA 1 20 A (EX)
COFFEE/ COOLERS 8
5 (#) Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A (#) Spare 6
3 (#) Spare 20 A 1 0.0 kVA 0.5 kVA 1 20 A (EX) ATRIUM RECEPTACLES
4
1 (EX) BOOKSTORE RECEPTACLES 20 A 1 1.1 kVA 0.9 kVA 1 20 A (EX)
ATRIUM RECEPTACLES 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit
Description CKT
Notes: Existing Square D
Supply From: TSR-2 Voltage: 208V 3PH Phase: 3 Wire: 4
Location:
Panel Name: SR-2
Total Estimated Demand: 22.9 kVA
Total Connected Load: 21.3 kVA
Panel Totals
Load Classification Connected Load Demand Factor Estimated Demand
Additional Notes:
Total Connected Load: 7.9 kVA 7.0 kVA 6.4 kVA
41 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 42
39 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 40
37 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 38
35 Spare 20 A 1 0.0 kVA