7
SYMBOL L1 a INDICATES DIRECTION OF ARROW LIGHTING FIXTURE, POLE MOUNTED EMERGENCY WALL PACK SURFACE METAL RACEWAY W/RECEPTACLE @ X" O.C. (X) EXIT LIGHT, LIGHTING FIXTURE, CEILING MOUNTED AS INDICATED IN LUMINAIRE SCHEDULE FIXTURE, WALL MOUNT LIGHTING FIXTURE, EMERGENCY STRIP, SURFACE OR PENDANT LIGHTING FIXTURE, RECESSED DESCRIPTION INDICATES SWITCHING INDICATES CIRCUITING INDICATES TYPE PER LUMINAIRE SCHEDULE LIGHTING FIXTURE, SURFACE P1-2 "P1-2" "L1" "a" GFCI= CLASS A, GROUND FAULT CIRCUIT INTERRUPTER DUPLEX RECEPTACLE GFCI P1-4= CIRCUIT NUMBER (TYP) WP P1-4 WP= WEATHERPROOF POWER CONDUIT & WIRE TAG CONTROL CONDUIT & WIRE TAG SIGNAL CONDUIT & WIRE TAG TELEPHONE CONDUIT & WIRE TAG MECHANICAL EQUIP. DESIGNATION INSTRUMENT DESIGNATION SCALE SECTION SECTION LETTER PSL-101 P-01 FAULT CURRENT TAG (AIC) KEY NOTE DETAIL SCALE REFERENCE SYMBOLS CONDUIT CONCEALED IN WALL, CEILING, EXISTING CONDUIT ROUTED UNDERGROUND WITH INTEGRAL & BYPASS CONTACTORS SOLID STATE STARTER, REDUCED VOLTAGE CKT. BKR, RATING/NO. OF POLES WITH THERMAL PULL OUT SWITCH/PLUG-RECEPTACLE CONNECTION TERMINAL AT REMOTE DEVICE OR PANEL DEVICE TERMINAL TERMINAL IN CONTROL PANEL PANELBOARD WP = WEATHER PROOF SWITCH K = KEY OPERATED SWITCH P = SWITCH AND PILOT LAMP (FOR USE WITH THERMALLY M = MOTOR RATED SWITCH T = SWITCH WITH TIMER 3 = THREE WAY SWITCH 4 = FOUR WAY SWITCH SOLID STATE OVERLOAD CONDUCTORS CONNECTED THERMAL OVERLOAD RELAY SS OL PHASE FAIL RELAY & FUSE CONDUCTORS NOT CONNECTED PHOTO ELECTRIC CELL RUN TIME METER SPECIAL PURPOSE RECEPTACLE SMOKE DETECTOR 2 = DOUBLE POLE SWITCH SINGLE POLE SWITCH DATA OUTLET TELEPHONE OUTLET THERMOSTAT DOUBLE DUPLEX RECEPTACLES FUSE VARIABLE FREQUENCY DRIVE SSS XXA VFD HANDHOLE WITH DESIGNATION MAGNETIC CIRCUIT BREAKER TRIP MANUAL OR AUTOMATIC TRANSFER SWITCH POWER CAPACITOR JUNCTION BOX 2P 30A HH1 OVERHEAD ELECTRICAL CONDUIT FLEXIBLE CONDUIT TURNED UP OR TOWARD CONDUIT TURNED DOWN OR AWAY CONDUIT CAPPED ELECTRICAL HEAT TRACE CABLE OE E CONDUIT EXPOSED SYMBOL DESCRIPTION PUSHBUTTON SWITCH, MOMENTARY ON FT = FLOW TRANSMITTER SI = SPEED INDICATOR PT = PRESSURE TRANSMITTER LT = LEVEL TRANSMITTER POTENTIOMETER PRESSURE SWITCH, NORMALLY CLOSED LEVEL SWITCH, CLOSES ON RISING LEVEL TS, TEMP. SWITCH, CLOSES ON FALLING TEMP FLOW SWITCH, NORMALLY CLOSED T, THERMOSTAT LIMIT SWITCH, NORMALLY OPEN GENERATOR, PLAN VIEW SHOWN TO SCALE F 200AS R R R 200/100 100AF FVNR 2 60A DISCONNECT SWITCH, FUSED W = 200=SWITCH RATING, 100=FUSE RATING LIGHTED PUSHBUTTON SELECTOR SWITCH: HAND/OFF/AUTO HAND/OFF/REMOTE RUN/OFF HOA = HOR = RO = INDICATING LIGHT: UTILITY WATT HOUR METER BLUE AMBER A = B = RED GREEN R = G = WHITE (60A) INDICATES AMPERAGE RATING FULL VOLTAGE NON-REVERSING STARTER/NEMA SIZE BP=BYPASS CONTACTOR IC=ISOLATION CONTACTOR DISCONNECT SWITCH, NON FUSED MS=MOTOR STARTER CONTACT SOLENOID VALVE 150W 3 - + SCHEMATIC PLAN SYMBOL MOTOR, NUMBER INDICATES HORSEPOWER TRANSFORMER, PLAN VIEW SHOWN TO SCALE ELECTRIC HEATER WINDING, WATTAGE INDICATED CURRENT TRANSFORMER, NUMBER INDICATES NUMBER OF C.T.'S. PLAN VIEW SHOWN TO SCALE BATTERY DESCRIPTION GROUND ROD IN GROUND ROD BOX CB - GRS - HH - HOA - DO - EF - EXIST - GND - GIL - DF - DI - CP - CPT - CV - DB - CT - BC - C - BH - BIL - BP - ALT - AO - AT - ATS - AF - AFF - AI - AIL - A,AMP - AL - ABBREVIATIONS MOTOR CONTROL CENTER ISOLATION CONTACTOR KILOWATT HOUR LOCAL CONTROL PANEL MAIN CONTROL PANEL OPERATOR INTERFACE TERMINAL PHASE FAILURE RELAY PRESSURE SWITCH SURGE ARRESTOR RUN TIME METER STAINLESS STEEL SOLENOID VALVE WEATHER PROOF MOTOR OPERATED VALVE PUSH BUTTON - LIGHTED POTENTIAL TRANSFORMER POLY VINYL CHLORIDE CONDUIT RED INDICATING LIGHT TIME DELAY ON ENERGIZATION TIME DELAY ON DE-ENERGIZATION TELEPHONE NETWORK INTERFACE VARIABLE FREQUENCY DRIVE WHITE INDICATING LIGHT PT - CIRCUIT BREAKER AC DIGITAL OUTPUT POINT GREEN INDICATING LIGHT GALVANIZED RIGID STEEL CONDUIT HAND HOLE HAND-OFF-AUTO EXISTING EXHAUST FAN GROUND CONTROL POWER TRANSFORMER CURRENT TRANSFORMER AC DIGITAL INPUT POINT DEMAND FACTOR CONTROL PANEL CHECK VALVE DIRECT BURIED TDOD - UTP - WIL - WP - XFMR - VFD - TNI - UNSHIELDED TWISTED PAIR TRANSFORMER PVC - SA - RTM - SS - SV - T - TC - TDOE - RIL - THERMOSTAT TIME CLOCK ANALOG OUTPUT POINT AUTOMATIC TRANSFER SWITCH BATTERY CHARGER BLUE INDICATING LIGHT BYPASS CONTACTOR BLOCK HEATER CONDUIT ALTERNATOR AMPERE TRIP ABOVE FINISHED FLOOR ANALOG INPUT POINT AMBER INDICATING LIGHT AMPERE FRAME AMPERE ALARM MCC - N - MCP - MFGR - MOV - OIT - PBL - PB - PS - PFR - PUSH BUTTON NEUTRAL MANUFACTURER IC - kWH - L - LCP - LINE MCP, LCP, FACP OVERTEMPERATURE CUTOUT INTERCOM STATION LOCAL EQUIPMENT CONTROL PANEL - HORN XXXX GENERAL NOTES DOOR SWITCH PVC COATED - GALVANIZED RIGID STEEL PGRS - EXTRA-HARD USAGE FLEXIBLE CORD SHUNT TRIP BREAKER ST - P1 MOTORIZED LOUVER EXHAUST FAN C1 S1 T1 R1 SHEET WHERE SECTION IS TAKEN FROM SHEET ON WHICH DETAIL APPEARS SHEET ON WHICH SECTION APPEARS A XXX A XXX 1 XXX DETAIL NUMBER SECTION LETTER DETAIL AREA CONDUIT HOME RUN 3/4"C, 2#12 & 1#12 GND. UNLESS SHOWN OTHERWISE. (EXAMPLE SHOWN: TO PANEL P1, CIRCUIT 1) P1 COMBINATION DATA/TELEPHONE OUTLET S J UNDER FLOOR, IN FLOOR SLAB, OR ROUTED UNDERGROUND DETAIL NUMBER FIGURE OR PHOTO 2 E9 DIRECTION TAKEN IF PHOTO, ARROW DENOTES IS TAKEN FROM SHEET WHERE DETAIL HEAT DETECTOR P1-1 CONDUIT HOME RUN - SEE CONDUIT AND WIRE SCHEDULE DMS DIGITAL METERING SYSTEM G1 GROUNDING ELECTRODE SYSTEM CONDUIT & WIRE TAG L1 a P1-2 PROTECTED MOTORS) S X XXA (XXA INDICATES CURRENT RATING) (XXA INDICATES CURRENT RATING) FVNR=FULL VOLTAGE NON-REVERSING SURGE PROTECTION DEVICE SPD- SHIELDED TWISTED PAIR STP - UH - UNIT HEATER VB = VIBRATION TRANSMITTER TT = TEMPERATURE TRANSMITTER DRAWING LIST SHEET NO. SHEET TITLE TYPICAL TYP - SEAL OFF SPARE CONDUIT & WIRE TAG HUMIDISTAT OCCUPANCY SENSOR UNIT HEATER F PUSH TO TEST PTT - TIMED CONTACT, CONTACT ACTION IS RETARTED AFTER COIL IS ENERGIZED - NOTC TIMED CONTACT, CONTACT ACTION IS RETARTED AFTER COIL IS ENERGIZED - NCTO TIMED CONTACT, CONTACT ACTION IS RETARTED AFTER COIL IS DEENERGIZED - NOTO TIMED CONTACT, CONTACT ACTION IS RETARTED AFTER COIL IS DEENERGIZED - NCTC TDR = TIME DELAY RELAY CR = CONTROL RELAY TR = TIMER RELAY FI = FLOW INDICATOR 1 XXX S T M TS TS TS TS TS XX D OT H CP I PE T LS ZS FS PS PB SV 10 M M ONE INCH AT FULL SIZE IF NOT ONE INCH SCALE ACCORDINGLY ENGR RECORD PLOT DATE: PROJECT TITLE DESCRIPTION SHEET ACAD FILE NAME COMPUTER GENERATED DRAWING NO MANUAL REVISIONS ALLOWED BY APPROVED DRAWN CHECKED DESIGNED PROJECT ENG DATE SCALE PROJECT NUMBER DWG NUMBER REV REVISIONS DRWN CHKD APVL ENGR PROJ APVL REV DATE 1875 N. LAKEWOOD DRIVE, SUITE #201 COEUR D'ALENE, IDAHO 83814 (208) 676-8001 (208) 676-0100 ITD GENERATOR REPLACEMENT ELECTRICAL LEGEND E1 18180 18180.DWG 1 A 2/3/2010 ALH 05/01/2018 ALH 05/01/2018 RCD N.T.S. 0 05/10/2018 ISSUED FOR BID ALH ST CR H HOA XX RTM PFR G XX 1. ALL EQUIPMENT SHOWN IN BOLD LINEWEIGHT SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR UNLESS OTHERWISE NOTED. EXISTING ELECTRICAL EQUIPMENT, BACKGROUND AND/OR WORK/EQUIPMENT THAT IS TO BE PROVIDED BY OTHERS IS SHOWN IN LIGHTER LINEWEIGHTS. 2. SOME LEGEND SYMBOLS OR ABBREVIATIONS ON THIS SHEET ARE NOT USED ON THE FOLLOWING DRAWINGS. 3. WHERE EQUIPMENT PART NUMBERS ARE SHOWN ON THESE PLANS, THEY SHALL SUPERCEDE THE REQUIREMENTS OF THE SPECIFICATIONS. 4. "GENERAL NOTES" APPLY TO ALL DRAWINGS. "SHEET NOTES" APPLY TO ALL OF THE SHEETS WHICH THEY OCCUR. "KEY NOTES" APPLY WHERE CALLED OUT. 5. CONTRACTOR SHALL KEEP A FULL-SIZE DRAWING SET ON SITE AND NOTE ALL DEVIATIONS TO THE CONSTRUCTION DRAWINGS AS WELL AS NOTE LOCATIONS OF CONDUIT RUNS (OR OTHER ITEMS) WHICH ARE NOT SHOWN ON THE CONSTRUCTION DRAWINGS. THESE DRAWINGS SHALL BE TRANSCRIBED UPON COMPLETION OF THE PROJECT ONTO A CLEAN SET AND BECOME THE PROJECTS RECORD DRAWINGS. THEY SHALL BE TURNED OVER TO THE OWNER PRIOR TO FINAL PAYMENT. HAND OFF AUTO XX R ELECTRICAL LEGEND ELECTRICAL ONE-LINE DIAGRAM DEMOLITION PLAN ELECTRICAL ONE-LINE DIAGRAM ELECTRICAL SCHEDULES ELECTRICAL DETAILS PHOTO DETAILS PHOTO DETAILS E1 E2 E3 E4 E5 E6 E7 DETAIL NUMBER SHEET WHERE SECTION IS TAKEN FROM

DRAWING LIST SYMBOL DESCRIPTION SYMBOL DESCRIPTION … · project eng date scale project number dwg number rev revisions drwn chkdapvl engrproj rev date apvl 1875 n. lakewood drive,

  • Upload
    others

  • View
    12

  • Download
    0

Embed Size (px)

Citation preview

Page 1: DRAWING LIST SYMBOL DESCRIPTION SYMBOL DESCRIPTION … · project eng date scale project number dwg number rev revisions drwn chkdapvl engrproj rev date apvl 1875 n. lakewood drive,

SYMBOL

L1

a

INDICATES DIRECTION OF ARROW

LIGHTING FIXTURE, POLE MOUNTED

EMERGENCY WALL PACK

SURFACE METAL RACEWAY W/RECEPTACLE @ X" O.C.

(X)

EXIT LIGHT,

LIGHTING FIXTURE, CEILING MOUNTED

AS INDICATED IN LUMINAIRE SCHEDULE

FIXTURE, WALL MOUNT

LIGHTING FIXTURE, EMERGENCY

STRIP, SURFACE OR PENDANT

LIGHTING FIXTURE, RECESSED

DESCRIPTION

INDICATES SWITCHING

INDICATES CIRCUITING

INDICATES TYPE PER LUMINAIRE SCHEDULE

LIGHTING FIXTURE, SURFACE

P1-2

"P1-2"

"L1"

"a"

GFCI= CLASS A, GROUND FAULT CIRCUIT INTERRUPTER

DUPLEX RECEPTACLE

GFCI

P1-4= CIRCUIT NUMBER (TYP)

WP

P1-4

WP= WEATHERPROOF

POWER CONDUIT & WIRE TAG

CONTROL CONDUIT & WIRE TAG

SIGNAL CONDUIT & WIRE TAG

TELEPHONE CONDUIT & WIRE TAG

MECHANICAL EQUIP. DESIGNATION

INSTRUMENT DESIGNATION

SCALE

SECTION

SECTION LETTER

PSL-101

P-01

FAULT CURRENT TAG (AIC)

KEY NOTE

DETAIL

SCALE

REFERENCE SYMBOLS

CONDUIT CONCEALED IN WALL, CEILING,

EXISTING CONDUIT ROUTED UNDERGROUND

WITH INTEGRAL & BYPASS CONTACTORS

SOLID STATE STARTER, REDUCED VOLTAGE

CKT. BKR, RATING/NO. OF POLES WITH THERMAL

PULL OUT SWITCH/PLUG-RECEPTACLE CONNECTION

TERMINAL AT REMOTE DEVICE OR PANEL

DEVICE TERMINAL

TERMINAL IN CONTROL PANEL

PANELBOARD

WP = WEATHER PROOF SWITCH

K = KEY OPERATED SWITCH

P = SWITCH AND PILOT LAMP

(FOR USE WITH THERMALLY

M = MOTOR RATED SWITCH

T = SWITCH WITH TIMER

3 = THREE WAY SWITCH

4 = FOUR WAY SWITCH

SOLID STATE OVERLOAD

CONDUCTORS CONNECTED

THERMAL OVERLOAD RELAY

SS

OL

PHASE FAIL RELAY & FUSE

CONDUCTORS NOT CONNECTED

PHOTO ELECTRIC CELL

RUN TIME METER

SPECIAL PURPOSE RECEPTACLE

SMOKE DETECTOR

2 = DOUBLE POLE SWITCH

SINGLE POLE SWITCH

DATA OUTLET

TELEPHONE OUTLET

THERMOSTAT

DOUBLE DUPLEX RECEPTACLES

FUSE

VARIABLE FREQUENCY DRIVE

SSS

XXA

VFD

HANDHOLE WITH DESIGNATION

MAGNETIC CIRCUIT BREAKER TRIP

MANUAL OR AUTOMATIC TRANSFER SWITCH

POWER CAPACITOR

JUNCTION BOX

2P

30A

HH1

OVERHEAD ELECTRICAL

CONDUIT FLEXIBLE

CONDUIT TURNED UP OR TOWARD

CONDUIT TURNED DOWN OR AWAY

CONDUIT CAPPED

ELECTRICAL HEAT TRACE CABLE

OE

E

CONDUIT EXPOSED

SYMBOL DESCRIPTION

PUSHBUTTON SWITCH, MOMENTARY ON

FT = FLOW TRANSMITTER

SI = SPEED INDICATOR

PT = PRESSURE TRANSMITTER

LT = LEVEL TRANSMITTER

POTENTIOMETER

PRESSURE SWITCH, NORMALLY CLOSED

LEVEL SWITCH, CLOSES ON RISING LEVEL

TS, TEMP. SWITCH, CLOSES ON FALLING TEMP

FLOW SWITCH, NORMALLY CLOSED

T, THERMOSTAT

LIMIT SWITCH, NORMALLY OPEN

GENERATOR, PLAN VIEW SHOWN TO SCALE

F

200AS

R

R

R

200/100

100AF

FVNR 2

60A

DISCONNECT SWITCH, FUSED

W =

200=SWITCH RATING, 100=FUSE RATING

LIGHTED PUSHBUTTON

SELECTOR SWITCH:

HAND/OFF/AUTO

HAND/OFF/REMOTE

RUN/OFF

HOA =

HOR =

RO =

INDICATING LIGHT:

UTILITY WATT HOUR METER

BLUE

AMBERA =

B =

RED

GREEN

R =

G = WHITE

(60A) INDICATES AMPERAGE RATING

FULL VOLTAGE NON-REVERSING STARTER/NEMA SIZE

BP=BYPASS CONTACTOR

IC=ISOLATION CONTACTOR

DISCONNECT SWITCH, NON FUSED

MS=MOTOR STARTER CONTACT

SOLENOID VALVE

150W

3

- +

SCHEMATIC PLAN

SYMBOL

MOTOR, NUMBER INDICATES HORSEPOWER

TRANSFORMER, PLAN VIEW SHOWN TO SCALE

ELECTRIC HEATER WINDING, WATTAGE INDICATED

CURRENT TRANSFORMER, NUMBER INDICATES NUMBER

OF C.T.'S. PLAN VIEW SHOWN TO SCALE

BATTERY

DESCRIPTION

GROUND ROD IN GROUND ROD BOX

CB -

GRS -

HH -

HOA -

DO -

EF -

EXIST -

GND -

GIL -

DF -

DI -

CP -

CPT -

CV -

DB -

CT -

BC -

C -

BH -

BIL -

BP -

ALT -

AO -

AT -

ATS -

AF -

AFF -

AI -

AIL -

A,AMP -

AL -

ABBREVIATIONS

MOTOR CONTROL CENTER

ISOLATION CONTACTOR

KILOWATT HOUR

LOCAL CONTROL PANEL

MAIN CONTROL PANEL

OPERATOR INTERFACE TERMINAL

PHASE FAILURE RELAY

PRESSURE SWITCH

SURGE ARRESTOR

RUN TIME METER

STAINLESS STEEL

SOLENOID VALVE

WEATHER PROOF

MOTOR OPERATED VALVE

PUSH BUTTON - LIGHTED

POTENTIAL TRANSFORMER

POLY VINYL CHLORIDE CONDUIT

RED INDICATING LIGHT

TIME DELAY ON ENERGIZATION

TIME DELAY ON DE-ENERGIZATION

TELEPHONE NETWORK INTERFACE

VARIABLE FREQUENCY DRIVE

WHITE INDICATING LIGHT

PT -

CIRCUIT BREAKER

AC DIGITAL OUTPUT POINT

GREEN INDICATING LIGHT

GALVANIZED RIGID STEEL CONDUIT

HAND HOLE

HAND-OFF-AUTO

EXISTING

EXHAUST FAN

GROUND

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

AC DIGITAL INPUT POINT

DEMAND FACTOR

CONTROL PANEL

CHECK VALVE

DIRECT BURIED

TDOD -

UTP -

WIL -

WP -

XFMR -

VFD -

TNI -

UNSHIELDED TWISTED PAIR

TRANSFORMER

PVC -

SA -

RTM -

SS -

SV -

T -

TC -

TDOE -

RIL -

THERMOSTAT

TIME CLOCK

ANALOG OUTPUT POINT

AUTOMATIC TRANSFER SWITCH

BATTERY CHARGER

BLUE INDICATING LIGHT

BYPASS CONTACTOR

BLOCK HEATER

CONDUIT

ALTERNATOR

AMPERE TRIP

ABOVE FINISHED FLOOR

ANALOG INPUT POINT

AMBER INDICATING LIGHT

AMPERE FRAME

AMPERE

ALARMMCC -

N -

MCP -

MFGR -

MOV -

OIT -

PBL -

PB -

PS -

PFR -

PUSH BUTTON

NEUTRAL

MANUFACTURER

IC -

kWH -

L -

LCP -

LINE

MCP, LCP, FACP

OVERTEMPERATURE CUTOUT

INTERCOM STATION

LOCAL EQUIPMENT CONTROL PANEL -

HORN

XXXX

GENERAL NOTES

DOOR SWITCH

PVC COATED - GALVANIZED RIGID STEELPGRS -

EXTRA-HARD USAGE FLEXIBLE CORD

SHUNT TRIP BREAKERST -

P1

MOTORIZED LOUVER

EXHAUST FAN

C1

S1

T1

R1

SHEET WHERE

SECTION IS TAKEN

FROM

SHEET ON

WHICH

DETAIL

APPEARS

SHEET ON WHICH SECTION

APPEARS

A

XXX

A

XXX

1

XXX

DETAIL NUMBER

SECTION LETTER

DETAIL AREA

CONDUIT HOME RUN 3/4"C, 2#12 & 1#12 GND. UNLESS

SHOWN OTHERWISE. (EXAMPLE SHOWN: TO PANEL P1,

CIRCUIT 1)

P1

COMBINATION DATA/TELEPHONE OUTLET

S

J

UNDER FLOOR, IN FLOOR SLAB, OR

ROUTED UNDERGROUND

DETAIL NUMBER

FIGURE OR PHOTO

2

E9

DIRECTION TAKEN

IF PHOTO, ARROW DENOTES

IS TAKEN FROM

SHEET WHERE DETAIL

HEAT DETECTOR

P1-1

CONDUIT HOME RUN - SEE CONDUIT AND WIRE

SCHEDULE

DMS

DIGITAL METERING SYSTEM

G1

GROUNDING ELECTRODE SYSTEM CONDUIT

& WIRE TAG

L1

a

P1-2

PROTECTED MOTORS)

SX

XXA

(XXA INDICATES CURRENT RATING)

(XXA INDICATES CURRENT RATING)

FVNR=FULL VOLTAGE NON-REVERSING

SURGE PROTECTION DEVICESPD-

SHIELDED TWISTED PAIRSTP -

UH - UNIT HEATER

VB = VIBRATION TRANSMITTER

TT = TEMPERATURE TRANSMITTER

DRAWING LIST

SHEET NO. SHEET TITLE

TYPICALTYP -

SEAL OFF

SPARE CONDUIT & WIRE TAG

HUMIDISTAT

OCCUPANCY SENSOR

UNIT HEATERF

PUSH TO TESTPTT -

TIMED CONTACT, CONTACT ACTION IS RETARTED

AFTER COIL IS ENERGIZED - NOTC

TIMED CONTACT, CONTACT ACTION IS RETARTED

AFTER COIL IS ENERGIZED - NCTO

TIMED CONTACT, CONTACT ACTION IS RETARTED

AFTER COIL IS DEENERGIZED - NOTO

TIMED CONTACT, CONTACT ACTION IS RETARTED

AFTER COIL IS DEENERGIZED - NCTC

TDR = TIME DELAY RELAY

CR = CONTROL RELAY

TR = TIMER RELAY

FI = FLOW INDICATOR

1

XXX

S

T

M

TS

TS

TS

TS

TS

XX

D

OT

HCP

I

PE

T

LS

ZS

FS

PS

PB

SV

10

M

M

ONE INCH

AT FULL SIZE

IF NOT ONE INCH

SCALE ACCORDINGLY

ENGR RECORD

PLOT DATE:

PROJECT

TITLE

DESCRIPTION

SHEET

ACAD FILE NAME

COMPUTER GENERATED DRAWING NO MANUAL REVISIONS ALLOWED

BY

APPROVED

DRAWN

CHECKED

DESIGNED

PROJECT ENG

DATE

SCALE

PROJECT NUMBER

DWG NUMBER REV

REVISIONS

DRWN

CHKDAPVL

ENGR PROJ

APVLREV DATE

1875 N. LAKEWOOD DRIVE, SUITE #201

COEUR D'ALENE, IDAHO 83814

(208) 676-8001 (208) 676-0100

ITD GENERATOR REPLACEMENT

ELECTRICAL LEGEND

E1

18180

18180.DWG

1

A

2/3/2010

ALH 05/01/2018

ALH 05/01/2018

RCD

N.T.S.0

05/10/2018 ISSUED FOR BID

ALH

ST

CR

H

HOA

XX

RTM

PFR

G

XX

1. ALL EQUIPMENT SHOWN IN BOLD LINEWEIGHT SHALL BE PROVIDED AND INSTALLED BY THE

CONTRACTOR UNLESS OTHERWISE NOTED. EXISTING ELECTRICAL EQUIPMENT, BACKGROUND

AND/OR WORK/EQUIPMENT THAT IS TO BE PROVIDED BY OTHERS IS SHOWN IN LIGHTER

LINEWEIGHTS.

2. SOME LEGEND SYMBOLS OR ABBREVIATIONS ON THIS SHEET ARE NOT USED ON THE FOLLOWING

DRAWINGS.

3. WHERE EQUIPMENT PART NUMBERS ARE SHOWN ON THESE PLANS, THEY SHALL SUPERCEDE THE

REQUIREMENTS OF THE SPECIFICATIONS.

4. "GENERAL NOTES" APPLY TO ALL DRAWINGS. "SHEET NOTES" APPLY TO ALL OF THE SHEETS WHICH

THEY OCCUR. "KEY NOTES" APPLY WHERE CALLED OUT.

5. CONTRACTOR SHALL KEEP A FULL-SIZE DRAWING SET ON SITE AND NOTE ALL DEVIATIONS TO THE

CONSTRUCTION DRAWINGS AS WELL AS NOTE LOCATIONS OF CONDUIT RUNS (OR OTHER ITEMS)

WHICH ARE NOT SHOWN ON THE CONSTRUCTION DRAWINGS. THESE DRAWINGS SHALL BE

TRANSCRIBED UPON COMPLETION OF THE PROJECT ONTO A CLEAN SET AND BECOME THE PROJECTS

RECORD DRAWINGS. THEY SHALL BE TURNED OVER TO THE OWNER PRIOR TO FINAL PAYMENT.

HAND

OFF

AUTO

XX

R

ELECTRICAL LEGEND

ELECTRICAL ONE-LINE DIAGRAM DEMOLITION PLAN

ELECTRICAL ONE-LINE DIAGRAM

ELECTRICAL SCHEDULES

ELECTRICAL DETAILS

PHOTO DETAILS

PHOTO DETAILS

E1

E2

E3

E4

E5

E6

E7

DETAIL NUMBER

SHEET WHERE

SECTION IS TAKEN

FROM

AutoCAD SHX Text
M
AutoCAD SHX Text
OC
Page 2: DRAWING LIST SYMBOL DESCRIPTION SYMBOL DESCRIPTION … · project eng date scale project number dwg number rev revisions drwn chkdapvl engrproj rev date apvl 1875 n. lakewood drive,

ONE INCH

AT FULL SIZE

IF NOT ONE INCH

SCALE ACCORDINGLY

ENGR RECORD

PLOT DATE:

PROJECT

TITLE

DESCRIPTION

SHEET

ACAD FILE NAME

COMPUTER GENERATED DRAWING NO MANUAL REVISIONS ALLOWED

BY

APPROVED

DRAWN

CHECKED

DESIGNED

PROJECT ENG

DATE

SCALE

PROJECT NUMBER

DWG NUMBER REV

REVISIONS

DRWN

CHKDAPVL

ENGR PROJ

APVLREV DATE

1875 N. LAKEWOOD DRIVE, SUITE #201

COEUR D'ALENE, IDAHO 83814

(208) 676-8001 (208) 676-0100

ITD GENERATOR REPLACEMENT

ONE-LINE DIAGRAM

DEMOLITION PLAN

E2

18180

18180.DWG

1

A

2/3/2010

ALH 05/01/2018

ALH 05/01/2018

RCD

N.T.S.0

05/10/2018 ISSUED FOR BID

ALH

ST

ONE-LINE DIAGRAM

SHEET NOTES

A. "GENERAL NOTES" APPLY TO ALL DRAWINGS.

"SHEET NOTES" APPLY TO ALL OF THE SHEET

ON WHICH THEY OCCUR. "KEY NOTES" APPLY

ONLY WHERE CALLED OUT.

B. ALL EQUIPMENT SHOWN IN BOLD LINEWEIGHT

SHALL BE PROVIDED AND INSTALLED BY THE

CONTRACTOR UNLESS OTHERWISE NOTED.

EXISTING ELECTRICAL EQUIPMENT,

BACKGROUND AND/OR WORK/EQUIPMENT

THAT IS TO BE PROVIDED OTHERS IS SHOWN

IN LIGHTER LINEWEIGHTS.

C. DISTRIBUTION ONE-LINE DIAGRAM IS ONLY

PARTIAL AND DOES NOT REFLECT THE ENTIRE

SITE POWER DISTRIBUTION SYSTEM. ONLY

ELEMENTS MODIFIED IN THIS PROJECT ARE

SHOWN.

D. PROTECT ALL EQUIPMENT SHOWN FOR

REMOVAL/DEMOLITION AND FURNISH TO

OWNER.

KEY NOTES

1. DEMO EXISTING EQUIPMENT AS SHOWN AND

FURNISH TO OWNER. PRESERVE AND PROTECT

CONDUIT, CONDUCTORS, AND

APPURTENANCES FOR USE WHERE

APPLICABLE AS SHOWN ON SHEET E3.

2. DEMO EXISTING EXHAUST, ENCLOSURE/FRAME,

AND DUCTWORK FOR GENERATOR, AUTOMATIC

TRANSFER SWITCH AND DAY TANK SYSTEM

FOR INSTALLATION OF NEW GENERATOR, ATS,

AND DAY TANK IN EXISTING LOCATION.

3. INTERCEPT EXISTING FUEL SYSTEM

CONNECTIONS, PRESERVE, AND PROTECT FOR

CONNECTION TO NEW DAY TANK SHOWN ON

SHEET E3.

4. VERIFY AND REPLACE CIRCUIT 2 CONDUCTORS

FOR NEW FUEL TANK SYSTEM SHOWN ON E03.

REPLACE CIRCUIT 4, 20A/1P SIEMENS BL

CIRCUIT BREAKER WITH 30A/1P SIEMENS BL

BREAKER AND CONDUCTORS TO ATS FOR

BLOCK HEATER AND BATTERY CHARGER

CIRCUIT. INTERCEPT BLOCK HEATER

RECEPTACLE CIRCUIT FROM PANELBOARD EM1

TO ADJACENT GENERATOR WALL, REMOVE,

AND EXTEND AS NECESSARY TO NEW

GENERATOR.

5. PRESERVE AND PROTECT CONDUIT. REMOVE

AND FURNISH TO OWNER ALL CONDUCTORS.

6. INTERCEPT CONDUIT AND CONDUCTORS

ABOVE PANEL-EM1 TO FIRE ALARM CONTROL

PANEL. PULL CONDUCTORS BACK AND EXTEND

CONDUIT TO NEW JUNCTION BOX LOCATED

ABOVE PANEL-EM1. SEE SHEET E3 NOTE 5 FOR

MORE DETAILS.

3P-800A

(800AF)

3P-200A

(200AF)

3P-100A

(100AF)

3P-200A

(200AF)

3P-200A

(200AF)

ELEVATOR

(E)

PANEL AD2

(E)

(E)

(E)

3P-200A

SPARE

3P-100A

SPARE

(E) MAIN SWITCHBOARD

120/208V, 3PH, 4W

3P-200A

(200AF)

3P-200A

(200AF)

3P-400A

(400AF)

3P-200A

3P-200A

(200AF)

(200AF)

3 #1/0 + 1 #6 GND - 1 1/2"C

4 #250MCM + 1 #4 GND - 3"C

4 #250MCM + 1 #4 GND - 3"C

4 #250MCM + 1 #4 GND - 3"C

PANEL AD3

PANEL AD4

3P-800A

(800AF)

3P-800A

(800AF)

(1) SET, 4 #750MCM -

4"C + 1 SPARE CONDUIT

(E)

(E)

4 #250MCM + 1 #4 GND - 3"C

4 #250MCM + 1 #4 GND - 3"C

PANEL AD6

PANEL AD7

(E)

PANEL M

(E)

PANEL AD1

CHILLER - CH-1

(DIV 15)

3 #350MCM + 1 #2 GND CU - 3"C

(1) SET, 4 #250MCM + 1 #1 GND - 3"C

4 #250MCM + 1 #4 GND - 3"C

TO UTILITY

NG

80

0A

B

US

80

0A

B

US

20

00

A B

US

3P-200A

(200AF)

3P-200A

(200AF)

3P-200A

(200AF)

3P-200A

(200AF)

PANEL EM1

(E)

PANEL EM2

(E)

(E)

(E)

3P-100A

(100AF)

3P-200A

(125AF)

(E) EMERGENCY SWITCHBOARD

120/208V, 3PH, 4W

4 #250MCM + 1 #4 GND - 3"C

4 #250MCM + 1 #4 GND - 3"C

4 #250MCM + 1 #4 GND - 3"C

PANEL EM3

PANEL UPS

80

0A

B

US

4 #250MCM + 1 #4 GND - 3"C

3P-800A

(800AF)

3P-200A

(200AF)

3P-100A

SPARE

3P-100A

SPARE

(E)

4 #1/0 + 1 #6 GND - 2"C

PANEL CR

(E) UPS

(E)

4 #250MCM + 1 #4 GND - 3"C

PANEL EM5 (ISP)

4 #1/0 + 1 #6 GND - 2"C

AC UNIT, RM B115

(E)

PANEL UPS

4 #1/0 + 1 #6 GND -

2"C

(E) ATS

4P-600A, 3P, 4W

N

L

E

(E) ENGINE GENERATOR

3P-600A

DIESEL, 200KW

120/208V 3PH

NG

(2

) S

ET

, 4

#

75

0M

CM

- 3

1

/2

"C

(2) SET, 4 #750MCM - 3 1/2"C

(2) SETS, 3 #350 MCM +

1 #1/0 GND CU - 2 1/2"

LS

(E) DAY TANK

LS

BH

BC

WALL RECEPTACLE

BATTERY

CHARGER

(E) DAY TANK CONTROLLER

22

4

2

3

1

4

4

5

PARTIAL SITE PLAN - EXISTING

6

ATS

DAY TANK

BYPASS

Page 3: DRAWING LIST SYMBOL DESCRIPTION SYMBOL DESCRIPTION … · project eng date scale project number dwg number rev revisions drwn chkdapvl engrproj rev date apvl 1875 n. lakewood drive,

ONE INCH

AT FULL SIZE

IF NOT ONE INCH

SCALE ACCORDINGLY

ENGR RECORD

PLOT DATE:

PROJECT

TITLE

DESCRIPTION

SHEET

ACAD FILE NAME

COMPUTER GENERATED DRAWING NO MANUAL REVISIONS ALLOWED

BY

APPROVED

DRAWN

CHECKED

DESIGNED

PROJECT ENG

DATE

SCALE

PROJECT NUMBER

DWG NUMBER REV

REVISIONS

DRWN

CHKDAPVL

ENGR PROJ

APVLREV DATE

1875 N. LAKEWOOD DRIVE, SUITE #201

COEUR D'ALENE, IDAHO 83814

(208) 676-8001 (208) 676-0100

ITD GENERATOR REPLACEMENT

ONE-LINE DIAGRAM

E3

18180

18180.DWG

1

A

2/3/2010

ALH 05/01/2018

ALH 05/01/2018

RCD

N.T.S.0

05/10/2018 ISSUED FOR BID

ALH

ST

P-01

ONE-LINE DIAGRAM

3P-800A

(800AF)

3P-200A

(200AF)

3P-100A

(100AF)

3P-200A

(200AF)

3P-200A

(200AF)

ELEVATOR

(E)

PANEL AD2

(E)

(E)

(E)

3P-200A

SPARE

3P-100A

SPARE

(E) MAIN SWITCHBOARD

120/208V, 3PH, 4W

3P-200A

(200AF)

3P-200A

(200AF)

3P-400A

(400AF)

3P-200A

3P-200A

(200AF)

(200AF)

3 #1/0 + 1 #6 GND - 1 1/2"C

4 #250MCM + 1 #4 GND - 3"C

4 #250MCM + 1 #4 GND - 3"C

4 #250MCM + 1 #4 GND - 3"C

PANEL AD3

PANEL AD4

3P-800A

(800AF)

3P-800A

(800AF)

(1) SET, 4 #750MCM - 4"C + 1 SPARE CONDUIT

(E)

(E)

4 #250MCM + 1 #4 GND - 3"C

4 #250MCM + 1 #4 GND - 3"C

PANEL AD6

PANEL AD7

(E)

PANEL M

(E)

PANEL AD1

CHILLER - CH-1

(DIV 15)

3 #350MCM + 1 #2 GND CU - 3"C

(1) SET, 4 #250MCM + 1 #1 GND - 3"C

4 #250MCM + 1 #4 GND - 3"C

TO UTILITY

NG

80

0A

B

US

80

0A

B

US

20

00

A B

US

3P-200A

(200AF)

3P-200A

(200AF)

3P-200A

(200AF)

3P-200A

(200AF)

PANEL EM1

(E)

PANEL EM2

(E)

(E)

(E)

3P-100A

(100AF)

3P-200A

(125AF)

(E) EMERGENCY SWITCHBOARD

120/208V, 3PH, 4W

4 #250MCM + 1 #4 GND - 3"C

4 #250MCM + 1 #4 GND - 3"C

4 #250MCM + 1 #4 GND - 3"C

PANEL EM3

PANEL UPS

80

0A

B

US

4 #250MCM + 1 #4 GND - 3"C

3P-800A

(800AF)

3P-200A

(200AF)

3P-100A

SPARE

3P-100A

SPARE

(E)

4 #1/0 + 1 #6 GND - 2"C

PANEL CR

(E) UPS

(E)

4 #250MCM + 1 #4 GND - 3"C

PANEL EM5 (ISP)

4 #1/0 + 1 #6 GND - 2"C

AC UNIT, RM B115

(E)

PANEL UPS

4 #1/0 + 1 #6 GND - 2"C

(2

) S

ET

, 4

#

75

0M

CM

- 3

1

/2

"C

(2) SET, 4 #750MCM - 3 1/2"C

LS

(E) DAY TANK

LS

(E) DAY TANK CONTROLLER

1

2

6

4

SHEET NOTES

A. "GENERAL NOTES" APPLY TO ALL DRAWINGS.

"SHEET NOTES" APPLY TO ALL OF THE SHEET

ON WHICH THEY OCCUR. "KEY NOTES" APPLY

ONLY WHERE CALLED OUT.

B. ALL EQUIPMENT SHOWN IN BOLD LINEWEIGHT

SHALL BE PROVIDED AND INSTALLED BY THE

CONTRACTOR UNLESS OTHERWISE NOTED.

EXISTING ELECTRICAL EQUIPMENT,

BACKGROUND AND/OR WORK/EQUIPMENT

THAT IS TO BE PROVIDED OTHERS IS SHOWN

IN LIGHTER LINEWEIGHTS.

C. DISTRIBUTION ONE-LINE DIAGRAM IS ONLY

PARTIAL AND DOES NOT REFLECT THE ENTIRE

SITE POWER DISTRIBUTION SYSTEM. ONLY

ELEMENTS MODIFIED IN THIS PROJECT ARE

SHOWN.

KEY NOTES

1. GENERATOR MAIN CIRCUIT BREAKER SHALL

BE SIZED BY THE MANUFACTURER BASED ON

THE OUTPUT RATING OF THE GENERATOR.

THE CIRCUIT BREAKER LONG-TIME PICKUP

SETTING SHALL BE ADJUSTED DOWN TO

PROTECT THE 600A RATED FEEDER

CONDUCTORS AND TRANSFER SWITCH.

CIRCUIT BREAKER AND ENCLOSURE SHALL

MEET THE REQUIREMENTS OF NFPA 70,

ARTICLE 240.6 (C).

2. 24HR DAY TANK SYSTEM SHALL BE

CONTROLLED VIA GENERATOR /ATS SYSTEM.

RE-USE EXISTING CONDUITS AS APPLICABLE

FOR INSTALLATION OF NEW ATS AND DAY

TANK SYSTEM.

3. BOND NEW ATS, GENERATOR, AND DAY TANK

SYSTEM TO EXISTING SYSTEM GROUNDING

ELECTRODE SYSTEM.

4. TO/FROM PANEL EM1. PANEL EM1 CIRCUIT 2

(DAY TANK) AND CIRCUIT 4 (BLOCK

HEATER/BATTERY CHARGER).

APPROXIMATELY 125' IN ADJACENT

ELECTRICAL ROOM.

5. FIELD VERIFY AND RELOCATE PANEL-EM1

CIRCUIT 14, FIRE ALARM CONTROL PANEL, TO

PANEL-UPS CIRCUIT 18. INSTALL 20A/1P

SIEMENS BL BREAKER. INSTALL CONDUIT AND

CONDUCTORS FROM JUNCTION BOX WITH DIN

RAIL AND TERMINAL BLOCKS LOCATED ABOVE

PANEL-EM1, THROUGH CONCRETE DIVIDING

WALL, TO PANEL-UPS. UTILIZE 3/4" RGS, (2) #12

AWG, (1) #12 AWG GND, BUSHINGS,

APPURTENANCES, AND GROUTING FOR

REROUTING. APPROXIMATELY 75' IN

ADJACENT GENERATOR ROOM, B105

6. FIELD ROUTE CONDUITS, SURFACE MOUNT OR

STAINLESS STEEL UNI-STRUT RACKING,

TO/FROM THE TERMINATION POINTS.

N

G

BC

CP

600A/3P

CP

- +

H

NG

200KW, 208/120V, 3Ø, 4W

STANDBY DIESEL GENERATOR

3

C-02

AUTOMATIC TRANSFER SWITCH

800A, 208/120V, 3Ø, 4W

C-01

P-03

P-00

P-02

4

4

P04

1

1

5

5

Page 4: DRAWING LIST SYMBOL DESCRIPTION SYMBOL DESCRIPTION … · project eng date scale project number dwg number rev revisions drwn chkdapvl engrproj rev date apvl 1875 n. lakewood drive,

ONE INCH

AT FULL SIZE

IF NOT ONE INCH

SCALE ACCORDINGLY

ENGR RECORD

PLOT DATE:

PROJECT

TITLE

DESCRIPTION

SHEET

ACAD FILE NAME

COMPUTER GENERATED DRAWING NO MANUAL REVISIONS ALLOWED

BY

APPROVED

DRAWN

CHECKED

DESIGNED

PROJECT ENG

DATE

SCALE

PROJECT NUMBER

DWG NUMBER REV

REVISIONS

DRWN

CHKDAPVL

ENGR PROJ

APVLREV DATE

1875 N. LAKEWOOD DRIVE, SUITE #201

COEUR D'ALENE, IDAHO 83814

(208) 676-8001 (208) 676-0100

ITD GENERATOR REPLACEMENT

ELECTRICAL SCHEDULES

E4

18180

18180.DWG

1

A

2/3/2010

ALH 05/01/2018

ALH 05/01/2018

RCD

N.T.S.0

05/10/2018 ISSUED FOR BID

ALH

ST

Page 5: DRAWING LIST SYMBOL DESCRIPTION SYMBOL DESCRIPTION … · project eng date scale project number dwg number rev revisions drwn chkdapvl engrproj rev date apvl 1875 n. lakewood drive,

ONE INCH

AT FULL SIZE

IF NOT ONE INCH

SCALE ACCORDINGLY

ENGR RECORD

PLOT DATE:

PROJECT

TITLE

DESCRIPTION

SHEET

ACAD FILE NAME

COMPUTER GENERATED DRAWING NO MANUAL REVISIONS ALLOWED

BY

APPROVED

DRAWN

CHECKED

DESIGNED

PROJECT ENG

DATE

SCALE

PROJECT NUMBER

DWG NUMBER REV

REVISIONS

DRWN

CHKDAPVL

ENGR PROJ

APVLREV DATE

1875 N. LAKEWOOD DRIVE, SUITE #201

COEUR D'ALENE, IDAHO 83814

(208) 676-8001 (208) 676-0100

ITD GENERATOR REPLACEMENT

ELECTRICAL DETAILS

E5

18180

18180.DWG

1

A

2/3/2010

ALH 05/01/2018

ALH 05/01/2018

RCD

N.T.S.0

05/10/2018 ISSUED FOR BID

ALH

ST

6"

5" 6"

3"

#4 REBAR 12"O.C. TYP.

5/8" COMPACTED GRAVEL

COMPACTED EARTH

REBAR

CONCRETE PAD EDGE

5/8" MIN ANCHOR BOLTS PER

MANUFACTURER TYP

TO GENERATOR GROUND BUS

GENERATOR PAD SECTION

PAD TO EXTEND 6" MINIMUM EDGE OF

GENERATOR EQUIPMENT ON ALL SIDES

N Ø Ø Ø

SERVICE

BONDING JUMPER

GENERATOR

BREAKER

G

ISOLATE NEUTRAL FROM GROUND AT

GENERATOR

G

N

SERVICE

ENTRANCE

RATED MAIN

DISCONNECT

TRANSFER

SWITCH

GROUND

ELECTRODE

SYSTEM

GROUND

GENERATOR

CASE

4 WIRE CABLE

W/GROUND

WHERE INSTALLING ON CONCRETE

IN LIEU OF COMPACTED GRAVEL,

CONCRETE WILL SUFFICE.

4"

INSULATOR

5/8"Ø LOCKWASHER,

TYPICAL

5/8"Ø - 11" x 1" HEX

HEAD CAP SCREW, TYPICAL

MINIMUM 12" x 3" COPPER GROUND

BAR WITH HOLES FOR (6) 2-HOLE

LUGS. PROVIDE QUANTITY OF HOLES

TO MATCH PROJECT REQUIREMENTS

WITH 50 50% SPARE HOLES.

ANCHOR BOLT, TYPICAL

1/4"

STAINLESS STEEL WALL

MOUNTING BRACKET

BOLT SIZE DEPENDS ON LUG

SIZE

COPPER (ELECTRO-TIN

PLATED) GROUND BAR

METAL TIE WIRE

STAMPED BRASS LABEL

WITH NAME OF CONNECTION

LUG

CABLE (INSULATED OR BARE,

AS REQUIRED BY

SPECIFICATIONS)

TWO 1/2" STAINLESS

STEEL BOLTS, NUTS,

AND WASHERS

#4/0 CU

1" PCV 18" BELOW

GRADE

TO GROUND GRID

BOLTED TWO-HOLE

BRONZE CONNECTOR

BURNDY #YGHA28-2N

OR APPROVED EQUAL

MAIN GROUND LOOP OR GROUND TAP CONDUCTOR

SIZE AS SHOWN ON PLAN DRAWINGS

MAIN GROUND LOOP CONDUCTOR SIZE AS SHOWN ON

PLAN DRAWINGS

30"

(MIN)

"TEE"

TOP OF GRADE

"CROSS (BUTTED)" "CROSS (PASS THRU)" "SPLICE (HORIZONTAL)" "SPLICE (VERTICAL)"

SCALE:

SPECIAL SYSTEMS

GROUNDING AND INTERSYSTEM

BONDING BUS BAR

NTS

--

1

SCALE:

STRUCTURE GROUND (TYP)

NTS

--

2

SCALE:

EXOTHERMIC GROUND

TAP CONNECTION (TYP)

NTS

--

3

SCALE:

GENERATOR DETAIL - TYPICAL

NTS

--

4

SCALE:

GENERATOR PAD PLAN

NTS

--

5

AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
5
AutoCAD SHX Text
2
Page 6: DRAWING LIST SYMBOL DESCRIPTION SYMBOL DESCRIPTION … · project eng date scale project number dwg number rev revisions drwn chkdapvl engrproj rev date apvl 1875 n. lakewood drive,

ONE INCH

AT FULL SIZE

IF NOT ONE INCH

SCALE ACCORDINGLY

ENGR RECORD

PLOT DATE:

PROJECT

TITLE

DESCRIPTION

SHEET

ACAD FILE NAME

COMPUTER GENERATED DRAWING NO MANUAL REVISIONS ALLOWED

BY

APPROVED

DRAWN

CHECKED

DESIGNED

PROJECT ENG

DATE

SCALE

PROJECT NUMBER

DWG NUMBER REV

REVISIONS

DRWN

CHKDAPVL

ENGR PROJ

APVLREV DATE

1875 N. LAKEWOOD DRIVE, SUITE #201

COEUR D'ALENE, IDAHO 83814

(208) 676-8001 (208) 676-0100

ITD GENERATOR REPLACEMENT

PHOTO DETAILS

E6

18180

18180.DWG

1

A

2/3/2010

ALH 05/01/2018

ALH 05/01/2018

RCD

N.T.S.0

05/10/2018 ISSUED FOR BID

ALH

ST

KEY NOTES

1. UTILITY SERVICE (PRIMARY) AND FEEDER

(SECONDARY) CONDUIT AND CONDUCTORS.

2. GENERATOR CONDUIT AND CONDUCTORS.

3. REMOVE AND REPLACE EMERGENCY

GENERATOR SHUTDOWN SWITCH WITH

LIKE-TYPE/STYLE EMERGENCY SWITCH AS

SHOWN ON SHEET E7, DETAIL 1.

4. CONDUIT AND CONDUCTORS FOR

CONTROL/SIGNAL AS REQUIRED BY

GENERATOR, UPS, AND DAY TANK.

5. ATS DIMENSIONS 39"Wx59.5"Lx18"D.

6. GENERATOR DIMENSIONS 118"Lx42"Wx72"H.

1

2

4

BLOCK HEATER

RECEPTACLE

BATTERY

CHARGER

75"

136"

3

2

5

SCALE:

EXISTING ATS

NTS

--

1

6

SCALE:

EXISTING

STANDBY GENERATOR

NTS

--

2

SCALE:

EMERGENCY

GENERATOR HATCH

NTS

--

3

SCALE:

EMERGENCY

GENERATOR SWITCH

NTS

--

4

Page 7: DRAWING LIST SYMBOL DESCRIPTION SYMBOL DESCRIPTION … · project eng date scale project number dwg number rev revisions drwn chkdapvl engrproj rev date apvl 1875 n. lakewood drive,

ONE INCH

AT FULL SIZE

IF NOT ONE INCH

SCALE ACCORDINGLY

ENGR RECORD

PLOT DATE:

PROJECT

TITLE

DESCRIPTION

SHEET

ACAD FILE NAME

COMPUTER GENERATED DRAWING NO MANUAL REVISIONS ALLOWED

BY

APPROVED

DRAWN

CHECKED

DESIGNED

PROJECT ENG

DATE

SCALE

PROJECT NUMBER

DWG NUMBER REV

REVISIONS

DRWN

CHKDAPVL

ENGR PROJ

APVLREV DATE

1875 N. LAKEWOOD DRIVE, SUITE #201

COEUR D'ALENE, IDAHO 83814

(208) 676-8001 (208) 676-0100

ITD GENERATOR REPLACEMENT

PHOTO DETAILS

E7

18180

18180.DWG

1

A

2/3/2010

ALH 05/01/2018

ALH 05/01/2018

RCD

N.T.S.0

05/10/2018 ISSUED FOR BID

ALH

ST

KEY NOTES

1. SUCTION/DISCHARGE LINES FOR DIESEL FUEL

SYSTEM MAIN TANK.

2. EXISTING UNI-STRUT AND CONDUIT RACK

EQUIPMENT INTERFERES WITH HATCH

OPENING. ALL EXISTING UNI-STRUT AND

CONDUITS, AS APPLICABLE, SHALL BE

REMOVED FOR INSTALLATION OF NEW

GENERATOR. REPLACEMENT OF UNI-STRUT

SHALL MATCH EXISTING AS NECESSARY FOR

OVERHEAD CONDUIT RUNS FROM

PANELBOARD/ATS/GENERATOR.

BATTERY

CHARGER

2

1

2

HATCH

HINGES

(TYP. 4)

SCALE:

EMERGENCY GENERATOR

SWITCH REFERENCE

NTS

--

1

SCALE:

FUEL SUPPLY PUMP & TANK

NTS

--

2

SCALE:

EXHAUST OUTLET & HATCH

NTS

--

3

SCALE:

BATTERY CHARGER CIRCUIT

NTS

--

4