2
24590-G04B-F00006 Rev 49 (Revised 7/25/2017) Ref: 24590-WTP-3DP-G04B-00046 Drawing Change Notice Page 1 of 2 CHANGE DOCUMENT NO. 24590-BOF-M0N-DEP- 00001 JOB NO. 24590 TITLE FOR CHANGE NOTICE Updating Corrosion Allowance for DEP Evaporator Reboiler and DEP Evaporator Primary Condenser Data Sheets DOCUMENT NUMBER REV DOCUMENT NUMBER REV 24590-BOF-MBD-DEP-00001 1 24590-BOF-MED-DEP-00004 1 PART OF DESIGN CHANGE PACKAGE (DCP)? Yes No Justification for no DCP: Impacted SSC has not been turned over to the Plant Management organization. JUSTIFICATION FOR CHANGE The purpose of this DCN is to align with the corrosion evaluations (24590-BOF-N1D-DEP-00007, Rev. 0 and 24590-BOF-N1D-DEP-00009, Rev.1) for DEP Evaporator Reboiler (24590-BOF-MBD-DEP-00001, Rev.1) and DEP Evaporator Primary Condenser (24590-BOF-MED-DEP-00004, Rev.1). The tubesides (including heads) must have a corrosion allowance of 0.04 inch and the tubes (heat transfer surface) must have 0.0 inch. MARGIN ANALYSIS Is the drawing a line list or equipment datasheet AND is the change associated with a Q SCC? Yes No Supersedes Change Document Yes No ECN Needed Yes No REQUIREMENTS REVIEW Client Approval Required Yes No Interface Resolution Required * Yes No Address any “yes” answers in the description DESCRIPTION OF CHANGE The affected mechanical data sheets are being updated as follows: ` 1) 24590-BOF-MBD-DEP-00001, Rev.1 Before After (See this DCN) Issued by RPP-WTP PDC I -- --- Mechani ca l Design Data Shell Side Tube Side Design Pressure (Max/Min) psig 50 Full vacuum 50 Full vacuum Design Temperature (Max/ Min ) OF 300 40 175 40 Corrosion/Erosi on Allowance inch 0.04 o.o Shell ID inch Dimensions 33 (H (T-T) x D) ft. 12 4 :'. "H x 2' 9"D (Ref. 1) (Ref. 1) 8 Total Number of Tubes / 222 / Tube OD / Length Tube Thickness (Nominal) / (Minimum) 0.065" I 0.060" (Nominal) 1.5" / 8.0' (Ref. 1) (Ref. 2) (Ref. 2) Tube Pitch / Layout I Clearance 1.875" / Triangular / 0.375" No. of Tube Passes 2 (Ref. 2) (Ref. 2) Mechanical Design Data I This DCN I Shell Side I I Tube Side Design Pressure (Max/Min) psig 50 Full vacuum I 50 Full vacuum Design Temperature (Max/Min) OF 300 40 "'-...... ,t. ....... -v V ~-~-, 40 Corrosion/Erosion Allowance inch 0.04 y 0.04 (0 .0 for tubes) ) Dimension~ A_A )._ ' / Shell ID inch 33 (H (T-T) x D) ft. 12 4 :'."H x 2' 9"D (Ref 1) (Ref. 1) 8 Total Number of Tubes / 222 / Tube OD / Length Tube Thickness (Nominal) / (Minimum) 0. 065" I 0.060" (Nominal) 1.5" / 8.0' (Ref. 1) (Ref. 2) (Ref. 2) Tube Pitch / Layout I Clearance 1.875" / Triangular / 0.375" No. of Tube Passes 2 /Ref. 2) /Ref. 2)

Drawing Change Notice CHANGE DOCUMENT NO. 24590-BOF … bof...24590-BOF-M0N-DEP-00001 JOB NO. TITLE FOR CHANGE NOTICE 24590 Updating Corrosion Allowance for DEP Evaporator Reboiler

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

  • 24590-G04B-F00006 Rev 49 (Revised 7/25/2017) Ref: 24590-WTP-3DP-G04B-00046

    Drawing Change Notice Page 1 of 2

    CHANGE DOCUMENT NO. 24590-BOF-M0N-DEP-00001

    JOB NO.

    24590

    TITLE FOR CHANGE NOTICE

    Updating Corrosion Allowance for DEP Evaporator Reboiler and DEP Evaporator Primary Condenser Data Sheets

    DOCUMENT NUMBER REV DOCUMENT NUMBER REV

    24590-BOF-MBD-DEP-00001 1 24590-BOF-MED-DEP-00004 1

    PART OF DESIGN CHANGE PACKAGE (DCP)? Yes No

    Justification for no DCP: Impacted SSC has not been turned over to the Plant Management organization.

    JUSTIFICATION FOR CHANGE

    The purpose of this DCN is to align with the corrosion evaluations (24590-BOF-N1D-DEP-00007, Rev. 0 and 24590-BOF-N1D-DEP-00009, Rev.1) for DEP Evaporator Reboiler (24590-BOF-MBD-DEP-00001, Rev.1) and DEP Evaporator Primary Condenser (24590-BOF-MED-DEP-00004, Rev.1). The tubesides (including heads) must have a corrosion allowance of 0.04 inch and the tubes (heat transfer surface) must have 0.0 inch.

    MARGIN ANALYSIS

    Is the drawing a line list or equipment datasheet AND is the change associated with a Q SCC? Yes No

    Supersedes Change Document Yes No

    ECN Needed Yes No

    REQUIREMENTS REVIEW

    Client Approval Required Yes No Interface Resolution Required * Yes No

    Address any “yes” answers in the description

    DESCRIPTION OF CHANGE

    The affected mechanical data sheets are being updated as follows: `

    1) 24590-BOF-MBD-DEP-00001, Rev.1

    Before

    After (See this DCN)

    Issued byRPP-WTP PDC

    I

    • ~

    -- • ~ • ~ • ~

    • ~ • ~

    ---Mechanical Design Data

    Shell Side Tube Side Design Pressure (Max/Min) psig 50 Full vacuum 50 Full vacuum Design Temperature (Max/Min) OF 300 40 175 40 Corrosion/Erosion Allowance inch 0.04 o.o Shell ID inch

    Dimensions 33 (H (T-T) x D) ft. 12 4 :'. "H x 2' 9"D (Ref. 1) (Ref. 1)

    8

    Total Number of Tubes / 222 / Tube OD / Length Tube Thickness (Nominal) / (Minimum)

    0.065" I 0.060" (Nominal) 1.5" / 8.0'

    (Ref. 1) (Ref. 2) (Ref. 2) Tube Pitch / Layout I Clearance

    1.875" / Triangular / 0.375" No. of Tube Passes

    2 (Ref. 2) (Ref. 2)

    Mechanical Design Data I This DCN I Shell Side I I Tube Side

    Design Pressure (Max/Min) psig 50 Full vacuum I 50 Full vacuum Design Temperature (Max/Min) OF 300 40 "'-......,t. ....... -v V ~-~-, 40 Corrosion/Erosion Allowance inch 0.04 y 0.04 (0.0 for tubes) )

    Dimension~ A_A )._ ' / Shell ID inch 33 (H (T-T) x D) ft. 12 4 :'."H x 2 ' 9"D (Ref 1) (Ref. 1)

    8

    Total Number of Tubes / 222 / Tube OD / Length Tube Thickness (Nominal) / (Minimum)

    0.065" I 0.060" (Nominal) 1.5" / 8.0'

    (Ref. 1) (Ref. 2) (Ref. 2) Tube Pitch / Layout I Clearance

    1.875" / Triangular / 0.375" No. of Tube Passes

    2 /Ref. 2) /Ref. 2)

    smurdockAEA-Rectangle

  • Page 2 of i

    • SJ Drawing Change Notice CHANGE DOCUMENT NO. 24590-BOF-M0N-DEP-00001 TITLE FOR CHANGE NOTICE JOB NO.

    24590 Updating Corrosion Allowance for DEP Evaporator Reboiler and DEP Evaporator Primary Condenser Data Sheets

    DESCRIPTION OF CHANGE

    2) 24590-BOF-MED-DEP-00004, Rev.1

    Design Pressure (Max/Min)

    Design Temperature (Max/Min) Corrosion/Erosion Allowance

    Shell ID (Ref. 1)

    Total Number ofTubes / Tube Thickness (Nominal)/ (Minimum) (Ref. 1 ) (Ref. 2) Tube Pitch / Layout I Clearance (Ref.2)

    After (See this DCN}

    Design Pressure (Max/Min)

    Design Temperature (Max/Min) Corrosion/Erosion Allowance

    Shell ID (Ref. 1)

    Total Number of Tubes/ Tube Thickness (Nominal)/ (Minimum) (Ref. 1) (Ref. 2) Tube Pitch / Layout I Clearance (Ref. 2)

    ORIGINATOR

    Thang Thawn - Mechanical Systems

    Originator ..... " By Thang E Thawn - tethawn 0fg Name Bedltel

    Placed Oct 03, 2017

    Approval(s)*

    Youssef Mohammad-Zadeh - WTP-Reston Mechanical EGS

    Date (inserted by final approver):

    psig Of

    inch

    inch

    psig Of

    inch

    inch

    24590-G04B-F00006 Rev 49 (Revised 7/25/2017)

    r ec amen esum M b . ID. D ata Shell Side Tube Side

    50 I Full vacuum 100 Full vacuum 175 I 40 165 40

    0,04 o.o Dimensions 7 1 7 3/411H X 3'D X

    36 (H x D x L (F-F)) ft. (Ref. 1) (Note 8) 18'3"L

    406 I Tube OD / Length

    0.065" I 0.060" (Nominal) 1.011 / 16' (Ref.2)

    1,375 /Triangular/ 0.375" No. of Tube Passes 6 (Ref.2)

    MecbanicalDesignData I Th' DCN I Shell Side I IS I ............ Tube Side

    50 I Full vacuum 100 ~ Full vacuum 175 I 40 ~- - _ ....... 40 r ·-- , '( '( I '( ' 0,04 r 0.04 (0.0 for tubes) ~

    Dimen,.icrr., -~-~ 7 1 7 3/4 11H x 3 1D x

    36 (H x D x L (f -f )) ft. 18'3"L (Ref. 1) (Note 8)

    406 / Tube OD / Length

    0.06511 / 0.06011 (Nominal) 1.011 / 16' CRef.2)

    1.375 / Triangular / 0.375" No. of Tube Passes

    6 (Ref.2)

    CHECKER

    Erica Poberezny- Mechanical Systems

    Org Name BKhtel Nabortal, Inc

    Placed. Oct 03. 2017

    Ref: 24590-WTP-3DP-G04B-00046