NYC Department of Education Building Condition Assessment Survey 2019-2020 M496 Architectural Inspection Inspection Type Last Edited Time In InspectionId DOE EARLY CHILDHOOD OFFICE @ 110 WILLIAM STREET -, 110 WILLIAM STREET, BROOKLYN, NY, 10038 School: 1892 2019-12-06 08:59AM 2020-08-24 04:43PM ARCHITECTURAL - SENIOR 1919 2019-12-06 08:55AM 2019-12-09 06:32AM ARCHITECTURAL - ASSOCIATE Asset Data Question Answer Was the Building Fully Accessible for Inspection? No Mechanical Rooms on other floors require prior permission from the building owner for access. Comments on Inaccessible Inspection Principal(s) Information Principal Name Elizabeth Kot - Director of Central and Field Facilities Principal Organization Department of Education Early Childhood Office Meeting with Principal? Yes Principal Feedback The Director commented that most Windows have Air Infiltration. Custodian Was not present Fireman Was not present Building Square Footage 85,000 Comments on the Area (Square Feet) None Comments on the Stories (Floors) plus Basements 3 Floors - 14 (partial), 15 and 16 Comments on the Year Built 1957 Comments on the Student Population 0 Comments on the Staff Population 328 Comments on the Number of Classrooms 0 Weather Fair Facade Photo Corner of William Street and John Street - Northeast View Main Entrance Photo Facade A - William Street Page 1 of 9 Print Date: 9/11/2020 Mobile Validity Version 2.0 (P)

DOE EARLY CHILDHOOD OFFICE @ 110 WILLIAM STREET -, …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M496 InspectionId Inspection

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: DOE EARLY CHILDHOOD OFFICE @ 110 WILLIAM STREET -, …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M496 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M496Architectural Inspection

Inspection Type Last EditedTime InInspectionId

DOE EARLY CHILDHOOD OFFICE @ 110 WILLIAM STREET -, 110 WILLIAM STREET, BROOKLYN, NY, 10038School:

1892 2019-12-06 08:59AM 2020-08-24 04:43PMARCHITECTURAL - SENIOR

1919 2019-12-06 08:55AM 2019-12-09 06:32AMARCHITECTURAL - ASSOCIATE

Asset DataQuestion Answer

Was the Building Fully Accessible for Inspection? No

Mechanical Rooms on other floors require prior permission from

the building owner for access.

Comments on Inaccessible Inspection

Principal(s) Information

Principal Name Elizabeth Kot - Director of Central and Field Facilities

Principal Organization Department of Education Early Childhood Office

Meeting with Principal? Yes

Principal Feedback The Director commented that most Windows have Air Infiltration.

Custodian Was not present

Fireman Was not present

Building Square Footage 85,000

Comments on the Area (Square Feet) None

Comments on the Stories (Floors) plus Basements 3 Floors - 14 (partial), 15 and 16

Comments on the Year Built 1957

Comments on the Student Population 0

Comments on the Staff Population 328

Comments on the Number of Classrooms 0

Weather Fair

Facade Photo

Corner of William Street and John Street - Northeast View

Main Entrance Photo

Facade A - William Street

Page 1 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 2: DOE EARLY CHILDHOOD OFFICE @ 110 WILLIAM STREET -, …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M496 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M496Architectural InspectionRoof Photo Not taken

Have any Systems/Major Building Components been upgraded? Systems: Renovation for Dept. of Education use

Years: 2019

Have there been any New Building Additions? No New Construction

Tandem No Tandem

Leased Space? Yes

Year Leased 2018

Inspection Type Partial Inspection

Priority ConditionExist

Last Year?

Priority

Category

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Structural Engineer Required

Structural

Condition Type

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Accessibility

Accessibility Status Question Response

Is the Primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? Yes

Are All floors of the building accessible through compliant means? Yes

Accessible classrooms exists on each floor? Yes

Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes

If the following spaces exist, are they ALL accessible? Art Room, Auditorium,

Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

Yes

Physical Breakdown Structure Exists Complies Required DeficiencyAudio

Induction

System

Fire

Alarm

Strobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

YesExterior Entrances & Exits

NoNoExterior H/C Lifts

NoNoExterior Ramps and Railings

Interior Routes

NoNoCorridor and Lobby H/C Lifts

YesYesInterior Corridor Doors And

Hardware

YesInterior Corridors & Lobbies

YesYesInterior Elevators

YesInterior Lobby Doors And Hardware

NoInterior Ramps

Rooms & Spaces

NoArt Rooms

NoAuditorium

NoCafeteria

NoClassrooms

NoComputer Rooms

NoGymnasium

NoLibrary

NoMain Office

NoMulti-purpose Room

NoNurse's Office

NoPool

Page 2 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 3: DOE EARLY CHILDHOOD OFFICE @ 110 WILLIAM STREET -, …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M496 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M496Architectural Inspection

Physical Breakdown Structure Exists Complies Required DeficiencyAudio

Induction

System

Fire

Alarm

Strobe

NoScience Lab

NoToilet Rooms (boys)

NoToilet Rooms (girls)

Toilet Rooms (staff)

Yes YesFloors 15th and 16th

Building Template

Inspection

Question Response

Architectural

ATHLETIC FIELDS Does not exist

EXTERIOR Inspected

Does not existAREAWAY

Does not existAWNINGS AND CANOPIES

Not requiredCHIMNEY

Does not existCOPING

Does not existCORNICE

InspectedDOORS

InspectedDOOR HARDWARE

Condition 3- Fair

No deficiencies recordedDeficiency

InspectedDOORS AND FRAMES

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existLINTELS

InspectedTRANSOM/SIDE LIGHT

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existEXTERIOR SOFFITS

InspectedEXTERIOR WALLS

OtherMaterial Type(s)

24,000Replacement Quantity

Replacement Uom S.F.

Instance on All Facades Inspected

Page 3 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 4: DOE EARLY CHILDHOOD OFFICE @ 110 WILLIAM STREET -, …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M496 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M496Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

2- Between Good and FairInstance Condition

Instance Quantity 24,000

Instance Quantity Uom S.F.

No deficiencies recordedDeficiency

Does not existLOADING DOCK

Does not existLOUVER

Does not existPARAPETS

Does not existPLAZA DECK

Not requiredROOF

Does not existSTAIRS/RAMPS: EXTERIOR

InspectedWINDOWS

6,000Replacement Quantity

Replacement Uom S.F.

Does not existEXTERIOR GUARDS

Does not existLINTELS

InspectedWINDOWS

Material Type(s) Aluminum

Instance on Aluminum - Other:Facade D, E and G (Non-Original) Inspected

4- Between Fair and PoorInstance Condition

Instance Quantity 1,700

Instance Quantity Uom S.F.

Installation Year 1995

Source of Installation Year Inspector Estimate

ALUMINUM - OTHER:AIR/WATER INFILTRATIONDeficiency

Roof Plan Reference

Elevation

Elevation Reference Facade D and E

250Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE TRIM, SILLS OR WEATHERSTRIPPING

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

16th Floor near Stair D

Page 4 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 5: DOE EARLY CHILDHOOD OFFICE @ 110 WILLIAM STREET -, …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M496 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M496Architectural Inspection

Question Response

EXTERIOR

WINDOWS

WINDOWS

Deficiency Photo 2

16th Floor near Stair D

Violations No violations recorded

ALUMINUM - OTHER:DETERIORATEDDeficiency

Roof Plan Reference

Elevation

Elevation Reference Facade B and C

200Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE WINDOW

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

15th Floor

Violations No violations recorded

Instance on Aluminum - Double Hung:Facade A-C and H-J (Original) Inspected

3- FairInstance Condition

Instance Quantity 4,300

Instance Quantity Uom S.F.

Installation Year 1957

Source of Installation Year Inspector Estimate

ALUMINUM - DOUBLE HUNG:BROKEN PANEDeficiency

Page 5 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 6: DOE EARLY CHILDHOOD OFFICE @ 110 WILLIAM STREET -, …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M496 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M496Architectural Inspection

Question Response

EXTERIOR

WINDOWS

WINDOWS

Roof Plan Reference

Elevation

Elevation Reference Facade H

10Deficiency Quantity

Quantity Uom S.F.

Potential Action MAINTENANCE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

15th Floor near Open Stairs

Violations No violations recorded

INTERIOR Inspected

Does not existAUDITORIUM

Does not existCAFETERIA

InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES

InspectedCeiling

Condition 1- Good

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

METAL:DAMAGED LOUVERDeficiency

Electrical Equipment Room at 15th Floor near Elevator LobbyDeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 6 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 7: DOE EARLY CHILDHOOD OFFICE @ 110 WILLIAM STREET -, …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M496 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M496Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Door(s)

Deficiency Photo 1

Electrical Equipment Room at 15th Floor near Elevator Lobby

Violations No violations recorded

InspectedFloor Finish

Condition 2- Between Good and Fair

CONCRETE:CRACKSDeficiency

16th Floor corridorDeficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

16th Floor corridor

Violations No violations recorded

Does not existSpecialties

InspectedWalls

Condition 1- Good

No deficiencies recordedDeficiency

Does not existGYMNASIUM

InspectedINTERIOR DOOR HARDWARE

Condition 1- Good

No deficiencies recordedDeficiency

Does not existINTERIOR GUARDS

Does not existKITCHEN

Does not existLIBRARY

Does not existLOCKER ROOM

Does not existMULTI-PURPOSE ROOM

Does not existPOOLS

Does not existSCIENCE DEMO ROOM

Does not existSCIENCE LAB

Does not existSCIENCE PREP ROOM

Does not existSHOWER ROOM

Does not existSTAIRS/RAMPS: INTERIOR

InspectedSTRUCTURAL

InspectedCOLUMNS/BEAMS/BEARING WALLS

Condition 3- Fair

Page 7 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 8: DOE EARLY CHILDHOOD OFFICE @ 110 WILLIAM STREET -, …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M496 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M496Architectural Inspection

Question Response

INTERIOR

STRUCTURAL

COLUMNS/BEAMS/BEARING WALLS

STEEL COLUMNS/BEAMS:DETERIORATED CONCRETE

FIREPROOFING

Deficiency

15th and 16th FloorDeficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

IDF Room 1637 shown, also MDF Room 1536

Violations No violations recorded

InspectedFLOOR STRUCTURE

Condition 3- Fair

CONCRETE:CRACKS/SPALLED/REINFORCEMENT

EXPOSED

Deficiency

15th and 16th FloorDeficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Electrical Closet 1582 shown, also MDF Room 1536

Violations No violations recorded

Not requiredFOUNDATION WALLS

Not requiredROOF STRUCTURE

Does not existVAULTS-BUNKERS

InspectedTOILET ROOMS - STAFF

InspectedCeiling

Condition 1- Good

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 1- Good

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 1- Good

No deficiencies recordedDeficiency

InspectedStalls

Page 8 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 9: DOE EARLY CHILDHOOD OFFICE @ 110 WILLIAM STREET -, …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M496 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M496Architectural Inspection

Question Response

INTERIOR

TOILET ROOMS - STAFF

Stalls

Condition 1- Good

No deficiencies recordedDeficiency

InspectedWalls

Condition 1- Good

No deficiencies recordedDeficiency

Does not existTOILET ROOMS - STUDENTS

LIFE SAFETY Inspected

Does not existF.D. HOLDING AREA

Does not existSTEEL STAIRS

SITE Not required

Page 9 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)