NYC Department of Education
Building Condition Assessment Survey 2019-2020
M496Architectural Inspection
Inspection Type Last EditedTime InInspectionId
DOE EARLY CHILDHOOD OFFICE @ 110 WILLIAM STREET -, 110 WILLIAM STREET, BROOKLYN, NY, 10038School:
1892 2019-12-06 08:59AM 2020-08-24 04:43PMARCHITECTURAL - SENIOR
1919 2019-12-06 08:55AM 2019-12-09 06:32AMARCHITECTURAL - ASSOCIATE
Asset DataQuestion Answer
Was the Building Fully Accessible for Inspection? No
Mechanical Rooms on other floors require prior permission from
the building owner for access.
Comments on Inaccessible Inspection
Principal(s) Information
Principal Name Elizabeth Kot - Director of Central and Field Facilities
Principal Organization Department of Education Early Childhood Office
Meeting with Principal? Yes
Principal Feedback The Director commented that most Windows have Air Infiltration.
Custodian Was not present
Fireman Was not present
Building Square Footage 85,000
Comments on the Area (Square Feet) None
Comments on the Stories (Floors) plus Basements 3 Floors - 14 (partial), 15 and 16
Comments on the Year Built 1957
Comments on the Student Population 0
Comments on the Staff Population 328
Comments on the Number of Classrooms 0
Weather Fair
Facade Photo
Corner of William Street and John Street - Northeast View
Main Entrance Photo
Facade A - William Street
Page 1 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M496Architectural InspectionRoof Photo Not taken
Have any Systems/Major Building Components been upgraded? Systems: Renovation for Dept. of Education use
Years: 2019
Have there been any New Building Additions? No New Construction
Tandem No Tandem
Leased Space? Yes
Year Leased 2018
Inspection Type Partial Inspection
Priority ConditionExist
Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Structural Engineer Required
Structural
Condition Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Accessibility
Accessibility Status Question Response
Is the Primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are All floors of the building accessible through compliant means? Yes
Accessible classrooms exists on each floor? Yes
Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes
If the following spaces exist, are they ALL accessible? Art Room, Auditorium,
Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
Physical Breakdown Structure Exists Complies Required DeficiencyAudio
Induction
System
Fire
Alarm
Strobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
YesExterior Entrances & Exits
NoNoExterior H/C Lifts
NoNoExterior Ramps and Railings
Interior Routes
NoNoCorridor and Lobby H/C Lifts
YesYesInterior Corridor Doors And
Hardware
YesInterior Corridors & Lobbies
YesYesInterior Elevators
YesInterior Lobby Doors And Hardware
NoInterior Ramps
Rooms & Spaces
NoArt Rooms
NoAuditorium
NoCafeteria
NoClassrooms
NoComputer Rooms
NoGymnasium
NoLibrary
NoMain Office
NoMulti-purpose Room
NoNurse's Office
NoPool
Page 2 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M496Architectural Inspection
Physical Breakdown Structure Exists Complies Required DeficiencyAudio
Induction
System
Fire
Alarm
Strobe
NoScience Lab
NoToilet Rooms (boys)
NoToilet Rooms (girls)
Toilet Rooms (staff)
Yes YesFloors 15th and 16th
Building Template
Inspection
Question Response
Architectural
ATHLETIC FIELDS Does not exist
EXTERIOR Inspected
Does not existAREAWAY
Does not existAWNINGS AND CANOPIES
Not requiredCHIMNEY
Does not existCOPING
Does not existCORNICE
InspectedDOORS
InspectedDOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedDOORS AND FRAMES
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existLINTELS
InspectedTRANSOM/SIDE LIGHT
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existEXTERIOR SOFFITS
InspectedEXTERIOR WALLS
OtherMaterial Type(s)
24,000Replacement Quantity
Replacement Uom S.F.
Instance on All Facades Inspected
Page 3 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M496Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
2- Between Good and FairInstance Condition
Instance Quantity 24,000
Instance Quantity Uom S.F.
No deficiencies recordedDeficiency
Does not existLOADING DOCK
Does not existLOUVER
Does not existPARAPETS
Does not existPLAZA DECK
Not requiredROOF
Does not existSTAIRS/RAMPS: EXTERIOR
InspectedWINDOWS
6,000Replacement Quantity
Replacement Uom S.F.
Does not existEXTERIOR GUARDS
Does not existLINTELS
InspectedWINDOWS
Material Type(s) Aluminum
Instance on Aluminum - Other:Facade D, E and G (Non-Original) Inspected
4- Between Fair and PoorInstance Condition
Instance Quantity 1,700
Instance Quantity Uom S.F.
Installation Year 1995
Source of Installation Year Inspector Estimate
ALUMINUM - OTHER:AIR/WATER INFILTRATIONDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade D and E
250Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE TRIM, SILLS OR WEATHERSTRIPPING
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
16th Floor near Stair D
Page 4 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M496Architectural Inspection
Question Response
EXTERIOR
WINDOWS
WINDOWS
Deficiency Photo 2
16th Floor near Stair D
Violations No violations recorded
ALUMINUM - OTHER:DETERIORATEDDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade B and C
200Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE WINDOW
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
15th Floor
Violations No violations recorded
Instance on Aluminum - Double Hung:Facade A-C and H-J (Original) Inspected
3- FairInstance Condition
Instance Quantity 4,300
Instance Quantity Uom S.F.
Installation Year 1957
Source of Installation Year Inspector Estimate
ALUMINUM - DOUBLE HUNG:BROKEN PANEDeficiency
Page 5 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M496Architectural Inspection
Question Response
EXTERIOR
WINDOWS
WINDOWS
Roof Plan Reference
Elevation
Elevation Reference Facade H
10Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
15th Floor near Open Stairs
Violations No violations recorded
INTERIOR Inspected
Does not existAUDITORIUM
Does not existCAFETERIA
InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedCeiling
Condition 1- Good
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
METAL:DAMAGED LOUVERDeficiency
Electrical Equipment Room at 15th Floor near Elevator LobbyDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 6 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M496Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s)
Deficiency Photo 1
Electrical Equipment Room at 15th Floor near Elevator Lobby
Violations No violations recorded
InspectedFloor Finish
Condition 2- Between Good and Fair
CONCRETE:CRACKSDeficiency
16th Floor corridorDeficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
16th Floor corridor
Violations No violations recorded
Does not existSpecialties
InspectedWalls
Condition 1- Good
No deficiencies recordedDeficiency
Does not existGYMNASIUM
InspectedINTERIOR DOOR HARDWARE
Condition 1- Good
No deficiencies recordedDeficiency
Does not existINTERIOR GUARDS
Does not existKITCHEN
Does not existLIBRARY
Does not existLOCKER ROOM
Does not existMULTI-PURPOSE ROOM
Does not existPOOLS
Does not existSCIENCE DEMO ROOM
Does not existSCIENCE LAB
Does not existSCIENCE PREP ROOM
Does not existSHOWER ROOM
Does not existSTAIRS/RAMPS: INTERIOR
InspectedSTRUCTURAL
InspectedCOLUMNS/BEAMS/BEARING WALLS
Condition 3- Fair
Page 7 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M496Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS
STEEL COLUMNS/BEAMS:DETERIORATED CONCRETE
FIREPROOFING
Deficiency
15th and 16th FloorDeficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
IDF Room 1637 shown, also MDF Room 1536
Violations No violations recorded
InspectedFLOOR STRUCTURE
Condition 3- Fair
CONCRETE:CRACKS/SPALLED/REINFORCEMENT
EXPOSED
Deficiency
15th and 16th FloorDeficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Electrical Closet 1582 shown, also MDF Room 1536
Violations No violations recorded
Not requiredFOUNDATION WALLS
Not requiredROOF STRUCTURE
Does not existVAULTS-BUNKERS
InspectedTOILET ROOMS - STAFF
InspectedCeiling
Condition 1- Good
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 1- Good
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 1- Good
No deficiencies recordedDeficiency
InspectedStalls
Page 8 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M496Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STAFF
Stalls
Condition 1- Good
No deficiencies recordedDeficiency
InspectedWalls
Condition 1- Good
No deficiencies recordedDeficiency
Does not existTOILET ROOMS - STUDENTS
LIFE SAFETY Inspected
Does not existF.D. HOLDING AREA
Does not existSTEEL STAIRS
SITE Not required
Page 9 of 9 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)