Document Number 481329 ODFD-XXX and OFD-XXX Series Installation Drawings for Out of Wall Curtain Fire Dampers Steel Stud Flange Flange Flange Factory Supplied Thermal Blanket 7 1/2 in. (191mm) or 8 1/2 in. (216mm) max. Concrete or Masonry Wall Wood Stud Damper Type A- Vertical Mount, Duct Terminates Flange Method Type A - Horizontal Mount Below Floor/Wall, Duct Terminates Flange Method Flange 7 1/2 in. (191mm) or 8 1/2 in. (216mm) max. Factory Supplied Thermal Blanket Masonry or Concrete Floor Damper Type A- Vertical Mount, Duct Terminates Single Angle Method Type A - Horizontal Mount Above Floor/Wall, Duct Terminates Single Angle Method Type A - Horizontal Mount Below Floor/Wall, Duct Terminates Single Angle Method 7 1/2 in. (191mm) or 8 1/2 in. (216mm) max. Factory Supplied Thermal Blanket Retaining Angle Alternate Retaining Angle Location Concrete or Masonry Wall Wood Stud Steel Stud Damper 7 1/2 in. (191mm) or 8 1/2 in. (216mm) max. Retaining Angle Factory Supplied Thermal Blanket Concrete or Masonry Floor Damper Retaining Angle Concrete or Masonry Floor Damper 7 1/2 in. (191mm) or 8 1/2 in. (216mm) max. Factory Supplied Thermal Blanket Approved installations for curtain fire dampers 1) Through the grille access and 2) Installation in continuing duct. The following maximum distances outside the barrier apply: • Steel stud and masonry barriers: - 8 1 2 in. (216mm) provided the width and height of the damper are both 24 in. (610mm) or less and the damper sleeve is 20 gauge - 7 1 2 in. (191mm) in all other instances • Wood stud walls: 6 1 2 in. (165mm) For access to inspect the damper and fusible link, refer to the requirements of NFPA 90A. ®

Document Number 481329 ODFD-XXX and OFD-XXX … · Document Number 481329 ODFD-XXX and OFD-XXX Series Installation Drawings for Out of Wall Curtain Fire Dampers Steel Stud Flange

  • Upload
    buithuy

  • View
    218

  • Download
    0

Embed Size (px)

Citation preview

Document Number 481329ODFD-XXX and OFD-XXX Series

Installation Drawings for Out of Wall Curtain Fire Dampers

Steel Stud

Flange

FlangeFlange

Factory SuppliedThermal Blanket

7 1/2 in. (191mm) or 8 1/2 in. (216mm)

max.

Concrete or Masonry

Wall

Wood Stud

Damper

Type A- Vertical Mount, Duct Terminates Flange Method

Type A - Horizontal Mount Below Floor/Wall, Duct Terminates Flange Method

Flange

7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.Factory Supplied

Thermal Blanket

Masonry or Concrete Floor

Damper

Type A- Vertical Mount, Duct Terminates Single Angle Method

Type A - Horizontal Mount Above Floor/Wall, Duct Terminates Single Angle Method

Type A - Horizontal Mount Below Floor/Wall, Duct Terminates Single Angle Method

7 1/2 in. (191mm) or 8 1/2 in. (216mm)

max.

Factory Supplied Thermal Blanket

Retaining Angle

Alternate Retaining

AngleLocation

Concrete or Masonry Wall

Wood Stud

Steel StudDamper

7 1/2 in. (191mm)or 8 1/2 in. (216mm) max.

Retaining Angle

Factory SuppliedThermal Blanket

Concrete or Masonry

Floor

Damper

Retaining Angle

Concrete or Masonry

Floor

Damper

7 1/2 in. (191mm) or8 1/2 in. (216mm) max.

Factory SuppliedThermal Blanket

Approved installations for curtain fire dampers 1) Through the grille access and

2) Installation in continuing duct.

The following maximum distances outside the barrier apply:

• Steel stud and masonry barriers:

- 81⁄2 in. (216mm) provided the width and height of the damper are both 24 in. (610mm) or less and the damper sleeve is 20 gauge - 71⁄2 in. (191mm) in all other instances

• Wood stud walls: 6 1⁄2 in. (165mm)

For access to inspect the damper and fusible link, refer to the requirements of NFPA 90A.

®

Type A- Vertical Mount, Thru Duct with Two Retaining Angles

Type A- Vertical Mount, Thru Duct with Single Retaining Angle

Type A - Horizontal Mount Above Floor/Wall, Thru Duct with Two Retaining Angles

Type A - Horizontal Mount Above Floor/Wall, Thru Duct with Single Retaining Angle

Type A - Horizontal Mount Below Floor/Wall, Thru Duct with Two Retaining Angles

Type A - Horizontal Mount Below Floor/Wall, Thru Duct with Single Retaining Angle

RetainingAngle

RetainingAngle

7 1/2 in. (191mm) 8 1/2 in. (216mm)

max.

Factory SuppliedThermal Blanket

Damper

Masonry or Concrete Wall

MetalStud

WoodStud

Masonry or Concrete Floor

7 1/2 in. (191mm) or8 1/2 in. (216mm) max.

RetainingAngle

Factory SuppliedThermal Blanket

Damper

RetainingAngle

7 1/2 in. (191mm) or8 1/2 in. (216mm) max.

RetainingAngle

RetainingAngle

Factory SuppliedThermal Blanket

Masonry or Concrete

Floor

Damper

Concrete or Masonry Wall

Wood Stud

7 1/2 in. (191mm) or 8 1/2 in. (216mm)

max.

Factory SuppliedThermal Blanket

Retaining Angle

Alternate Retaining Angle Location

Damper

7 1/2 in. (191mm) or8 1/2 in. (216mm) max.

Factory SuppliedThermal Blanket

Retaining Angle

Concrete or Masonry

Floor

Damper

7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.Factory Supplied

Thermal Blanket

Retaining Angle

Concrete or Masonry Floor

2

Type A cont....

Type B2

Type B2- Vertical Mount, Duct Terminates Flange Method

Type B2 - Horizontal Mount Below Floor/Wall, Duct Terminates Flange Method

Factory Supplied Thermal Blanket

7 1/2 in. (191mm) or 8 1/2 in. (216mm)

max.Damper

Wood Stud

Masonry or Concrete

Flange

SteelStud

7 1/2 in. (191mm) or8 1/2 in. (216mm) max.

Factory SuppliedThermal Blanket

Flange

Masonry or Concrete

Damper

Type B2- Vertical Mount, Thru Duct with Two Retaining Angles

Type B2 - Horizontal Mount Above Floor/Wall, Thru Duct with Two Retaining Angles

Type B2 - Horizontal Mount Below Floor/Wall, Thru Duct with Two Retaining Angles

Wood Stud

Masonry orConcrete

7 1/2 in.(191mm) or8 1/2 in. (216mm) max.

Retaining Angle

Retaining Angle

Damper

Factory SuppliedThermal Blanket

MetalStud

Damper

Masonry or Concrete

RetainingAngle

RetainingAngle

Factory SuppliedThermal Blanket

7 1/2 in. (191mm) or8 1/2 in. (216mm) max.

7 1/2 in. (191mm) or8 1/2 in. (216mm) max.

RetainingAngle

RetainingAngle

Damper

Masonry orConcrete

Factory SuppliedThermal Blanket

3

Type B2 cont....

Type B2- Vertical Mount, Thru Duct with Single Retaining Angle

Type B2 - Horizontal Mount Above Floor/Wall, Thru Duct with Single Retaining Angle

Type B2 - Horizontal Mount Below Floor/Wall, Thru Duct with Single Retaining Angle

7 1/2 in. (191mm) or8 1/2 in. (216mm) max.

Factory SuppliedThermal Blanket

Metal Stud

Damper

RetainingAngle

Alternate RetainingAngle Location

Concrete or Masonry

WoodStud

RetainingAngle

Factory SuppliedThermal Blanket

Damper

Concrete or Masonry

7 1/2 in. (191mm) or8 1/2 in. (216mm) max.

Factory SuppliedThermal Blanket

Retaining Angle

Concrete orMasonry

7 1/2 in. (191mm) or8 1/2 in. (216mm) max.

Damper

Type B2- Vertical Mount, Duct Terminates Single Angle Method

Type B2 - Horizontal Mount Above Floor/Wall, Duct Terminates Single Angle Method

Type B2 - Horizontal Mount Below Floor/Wall, Duct Terminates Single Angle Method

7 1/2 in. (191mm) or8 1/2 in, (216mm) max.

Retaining Angle

Alternate RetainingAngle Location

Concrete or Masonry

Factory SuppliedThermal Blanket

Damper

7 1/2 in. (191mm)or8 1/2 in. (216mm) max.

Retaining Angle

Factory SuppliedThermal Blanket

Concrete or Masonry

Damper

7 1/2 in. (191mm) or8 1/2 in. (216mm) max.

Factory SuppliedThermal Blanket

Damper

Concrete or Masonry

RetainingAngle

4

5

Type C2 cont....

Type C2- Vertical Mount, Thru Duct with Two Retaining Angles

Type C2 - Horizontal Mount Above Floor/Wall, Thru Duct with Two Retaining Angles

Type C2 - Horizontal Mount Below Floor/Wall, Thru Duct with Two Retaining Angles

Factory SuppliedThermal Blanket Retaining

Angle

RetainingAngle

Metal Stud

Wood Stud

Concrete or Masonry

7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.

Factory SuppliedThermal Blanket

RetainingAngle

RetainingAngle

Concrete or Masonry

Damper

7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.

RetainingAngle

RetainingAngle

Factory SuppliedThermal Blanket

Concrete or Masonry

Damper

7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.

Type C2- Vertical Mount, Duct Terminates Flange Method

Type C2 - Horizontal Mount Above Floor/Wall, Duct Terminates Flange Method

Type C2 - Horizontal Mount Below Floor/Wall, Duct Terminates Flange Method

7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.

Factory SuppliedThermal Blanket

Flange

MetalStud

Concrete orMasonry

Wood Stud

Damper

Flange

Factory SuppliedThermal Blanket

Damper

Concrete or Masonry

7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.

Flange

Factory SuppliedThermal Blanket

Damper

Concrete or Masonry

7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.

Type C2 cont....

Type C2- Vertical Mount, Thru Duct with Single Retaining Angle

Type C2 - Horizontal Mount Above Floor/Wall, Thru Duct with Single Retaining Angle

Type C2 - Horizontal Mount Below Floor/Wall, Thru Duct with Single Retaining Angle

Factory Supplied Thermal Blanket

Wood Stud

Metal Stud

Alternate RetainingAngle Location

Concrete or Masonry

7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.

Factory SuppliedThermal Blanket

Retaining Angle

Damper

Concrete or Masonry

7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.

RetainingAngle

Factory SuppliedThermal Blanket

Damper

Concrete or Masonry

7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.

481329 • ODFD OFD Installation Drawings Rev. 1, November 2015 Copyright 2015 © Greenheck Fan Corporation