Document Number 481329ODFD-XXX and OFD-XXX Series
Installation Drawings for Out of Wall Curtain Fire Dampers
Steel Stud
Flange
FlangeFlange
Factory SuppliedThermal Blanket
7 1/2 in. (191mm) or 8 1/2 in. (216mm)
max.
Concrete or Masonry
Wall
Wood Stud
Damper
Type A- Vertical Mount, Duct Terminates Flange Method
Type A - Horizontal Mount Below Floor/Wall, Duct Terminates Flange Method
Flange
7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.Factory Supplied
Thermal Blanket
Masonry or Concrete Floor
Damper
Type A- Vertical Mount, Duct Terminates Single Angle Method
Type A - Horizontal Mount Above Floor/Wall, Duct Terminates Single Angle Method
Type A - Horizontal Mount Below Floor/Wall, Duct Terminates Single Angle Method
7 1/2 in. (191mm) or 8 1/2 in. (216mm)
max.
Factory Supplied Thermal Blanket
Retaining Angle
Alternate Retaining
AngleLocation
Concrete or Masonry Wall
Wood Stud
Steel StudDamper
7 1/2 in. (191mm)or 8 1/2 in. (216mm) max.
Retaining Angle
Factory SuppliedThermal Blanket
Concrete or Masonry
Floor
Damper
Retaining Angle
Concrete or Masonry
Floor
Damper
7 1/2 in. (191mm) or8 1/2 in. (216mm) max.
Factory SuppliedThermal Blanket
Approved installations for curtain fire dampers 1) Through the grille access and
2) Installation in continuing duct.
The following maximum distances outside the barrier apply:
• Steel stud and masonry barriers:
- 81⁄2 in. (216mm) provided the width and height of the damper are both 24 in. (610mm) or less and the damper sleeve is 20 gauge - 71⁄2 in. (191mm) in all other instances
• Wood stud walls: 6 1⁄2 in. (165mm)
For access to inspect the damper and fusible link, refer to the requirements of NFPA 90A.
®
Type A- Vertical Mount, Thru Duct with Two Retaining Angles
Type A- Vertical Mount, Thru Duct with Single Retaining Angle
Type A - Horizontal Mount Above Floor/Wall, Thru Duct with Two Retaining Angles
Type A - Horizontal Mount Above Floor/Wall, Thru Duct with Single Retaining Angle
Type A - Horizontal Mount Below Floor/Wall, Thru Duct with Two Retaining Angles
Type A - Horizontal Mount Below Floor/Wall, Thru Duct with Single Retaining Angle
RetainingAngle
RetainingAngle
7 1/2 in. (191mm) 8 1/2 in. (216mm)
max.
Factory SuppliedThermal Blanket
Damper
Masonry or Concrete Wall
MetalStud
WoodStud
Masonry or Concrete Floor
7 1/2 in. (191mm) or8 1/2 in. (216mm) max.
RetainingAngle
Factory SuppliedThermal Blanket
Damper
RetainingAngle
7 1/2 in. (191mm) or8 1/2 in. (216mm) max.
RetainingAngle
RetainingAngle
Factory SuppliedThermal Blanket
Masonry or Concrete
Floor
Damper
Concrete or Masonry Wall
Wood Stud
7 1/2 in. (191mm) or 8 1/2 in. (216mm)
max.
Factory SuppliedThermal Blanket
Retaining Angle
Alternate Retaining Angle Location
Damper
7 1/2 in. (191mm) or8 1/2 in. (216mm) max.
Factory SuppliedThermal Blanket
Retaining Angle
Concrete or Masonry
Floor
Damper
7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.Factory Supplied
Thermal Blanket
Retaining Angle
Concrete or Masonry Floor
2
Type A cont....
Type B2
Type B2- Vertical Mount, Duct Terminates Flange Method
Type B2 - Horizontal Mount Below Floor/Wall, Duct Terminates Flange Method
Factory Supplied Thermal Blanket
7 1/2 in. (191mm) or 8 1/2 in. (216mm)
max.Damper
Wood Stud
Masonry or Concrete
Flange
SteelStud
7 1/2 in. (191mm) or8 1/2 in. (216mm) max.
Factory SuppliedThermal Blanket
Flange
Masonry or Concrete
Damper
Type B2- Vertical Mount, Thru Duct with Two Retaining Angles
Type B2 - Horizontal Mount Above Floor/Wall, Thru Duct with Two Retaining Angles
Type B2 - Horizontal Mount Below Floor/Wall, Thru Duct with Two Retaining Angles
Wood Stud
Masonry orConcrete
7 1/2 in.(191mm) or8 1/2 in. (216mm) max.
Retaining Angle
Retaining Angle
Damper
Factory SuppliedThermal Blanket
MetalStud
Damper
Masonry or Concrete
RetainingAngle
RetainingAngle
Factory SuppliedThermal Blanket
7 1/2 in. (191mm) or8 1/2 in. (216mm) max.
7 1/2 in. (191mm) or8 1/2 in. (216mm) max.
RetainingAngle
RetainingAngle
Damper
Masonry orConcrete
Factory SuppliedThermal Blanket
3
Type B2 cont....
Type B2- Vertical Mount, Thru Duct with Single Retaining Angle
Type B2 - Horizontal Mount Above Floor/Wall, Thru Duct with Single Retaining Angle
Type B2 - Horizontal Mount Below Floor/Wall, Thru Duct with Single Retaining Angle
7 1/2 in. (191mm) or8 1/2 in. (216mm) max.
Factory SuppliedThermal Blanket
Metal Stud
Damper
RetainingAngle
Alternate RetainingAngle Location
Concrete or Masonry
WoodStud
RetainingAngle
Factory SuppliedThermal Blanket
Damper
Concrete or Masonry
7 1/2 in. (191mm) or8 1/2 in. (216mm) max.
Factory SuppliedThermal Blanket
Retaining Angle
Concrete orMasonry
7 1/2 in. (191mm) or8 1/2 in. (216mm) max.
Damper
Type B2- Vertical Mount, Duct Terminates Single Angle Method
Type B2 - Horizontal Mount Above Floor/Wall, Duct Terminates Single Angle Method
Type B2 - Horizontal Mount Below Floor/Wall, Duct Terminates Single Angle Method
7 1/2 in. (191mm) or8 1/2 in, (216mm) max.
Retaining Angle
Alternate RetainingAngle Location
Concrete or Masonry
Factory SuppliedThermal Blanket
Damper
7 1/2 in. (191mm)or8 1/2 in. (216mm) max.
Retaining Angle
Factory SuppliedThermal Blanket
Concrete or Masonry
Damper
7 1/2 in. (191mm) or8 1/2 in. (216mm) max.
Factory SuppliedThermal Blanket
Damper
Concrete or Masonry
RetainingAngle
4
5
Type C2 cont....
Type C2- Vertical Mount, Thru Duct with Two Retaining Angles
Type C2 - Horizontal Mount Above Floor/Wall, Thru Duct with Two Retaining Angles
Type C2 - Horizontal Mount Below Floor/Wall, Thru Duct with Two Retaining Angles
Factory SuppliedThermal Blanket Retaining
Angle
RetainingAngle
Metal Stud
Wood Stud
Concrete or Masonry
7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.
Factory SuppliedThermal Blanket
RetainingAngle
RetainingAngle
Concrete or Masonry
Damper
7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.
RetainingAngle
RetainingAngle
Factory SuppliedThermal Blanket
Concrete or Masonry
Damper
7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.
Type C2- Vertical Mount, Duct Terminates Flange Method
Type C2 - Horizontal Mount Above Floor/Wall, Duct Terminates Flange Method
Type C2 - Horizontal Mount Below Floor/Wall, Duct Terminates Flange Method
7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.
Factory SuppliedThermal Blanket
Flange
MetalStud
Concrete orMasonry
Wood Stud
Damper
Flange
Factory SuppliedThermal Blanket
Damper
Concrete or Masonry
7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.
Flange
Factory SuppliedThermal Blanket
Damper
Concrete or Masonry
7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.
Type C2 cont....
Type C2- Vertical Mount, Thru Duct with Single Retaining Angle
Type C2 - Horizontal Mount Above Floor/Wall, Thru Duct with Single Retaining Angle
Type C2 - Horizontal Mount Below Floor/Wall, Thru Duct with Single Retaining Angle
Factory Supplied Thermal Blanket
Wood Stud
Metal Stud
Alternate RetainingAngle Location
Concrete or Masonry
7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.
Factory SuppliedThermal Blanket
Retaining Angle
Damper
Concrete or Masonry
7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.
RetainingAngle
Factory SuppliedThermal Blanket
Damper
Concrete or Masonry
7 1/2 in. (191mm) or 8 1/2 in. (216mm) max.