17003-2 Eau Claire Memorial 2018 00 90 00 -1
DOCUMENT 00 90 00
ADDENDUM
ADDENDUM NO. [2] Date: February 21, 2018
RE: EAU CLAIRE AREA SCHOOL DISTRICT MEMORIAL HIGH SCHOOL OFFICE & LOBBY EXPANSION 2225 KEITH ST EAU CLAIRE, WISCONSIN 54701 HSR PROJECT NO. 17003-2
FROM: HSR Associates, Inc
100 Milwaukee Street
La Crosse, WI 54603
(608) 784-1830
To: Prospective Bidders
This addendum forms a part of the Contract Documents and modifies the original Bidding Documents
dated January 2018. Acknowledge receipt of this Addendum in the space provided on the bid form.
Failure to do so may subject the Bidder to disqualification.
This Addendum consists of [2] pages, Pre-bid attendance, [1] Revised Hardware Groups and [6] 30 x
42 Drawings.
CHANGES TO GENERAL REQUIREMENTS:
1. Section 01 10 00 SUMMARY
a. 1.06, B: Add: “Submit BMS pricing directly to the District.”
CHANGES TO SPECIFICATIONS:
2. Section 08 43 13 ALUMINUM FRAMED STOREFRONT
a. 2.01, A: Add the following for the listed manufacturer’s;
A. Kawneer: 601UT 2” x 6”.
B. Tubelite: TU24650 2” x 6 ½”.
C. YKK AP: YES 60 XT 2” x 6”.
3. Section 08 71 00 FINISH HARDWARE
a. Completely revised Hardware Schedule attached hereto.
4. Section 08 80 00 GLAZING
a. 2.04, C, 3, a: Delete paragraph. Tint is listed in Item ‘C’.
b. 2.04, C, 4, b: Change “#2” to “#3”.
c. 2.04, D, 3, a: Delete paragraph. Tint is listed in Item ‘D’.
d. 2.04, D, 4, b: Change “#2” to “#3”
e. 2.04, D, 9: Change “70” to “35”.
5. Section 22 42 00 PLUMBING FIXTURES: Note the following revisions;
a. 2.01, A, 1: Water Closet manufacturer shall be Kohler only. Campus standard
b. 2.01, A, 5: Acceptable Faucet Manufacturer’s revised to: Chicago Faucet, Kohler, Sloan,
Zurn.
17003-2 Eau Claire Memorial 2018 00 90 00 -2
c. 2.01, A, 7 -Acceptable Supply and Stop Manufacturers revised to: Stops and Supplies –
Brasscraft only. Campus standard.
d. 2.01, A, 17: Electric Water Cooler manufacturer shall be Elkay only. Campus standard.
e. 2.09, A, 1: Add Model No. VRCGRNTL8WSK.
CHANGES TO DRAWINGS
6. Sheet A100R PARTIAL FIRST FLOOR REMODEL PLAN 30 x 42 attached hereto
a. Install new lockable metal floor access panel in exiting opening at Office 111. (Plan Key
Note #40).
b. .Designate existing door into Training 123 as Door 123C. This door is to be equipped
with electronic card access. See Door Schedule.
c. Patch existing floor, wall and soffit at Door 127 (Plan Key Note #41).
7. Sheet A120 ROOF PLAN
a. Omit 6 mil poly vapor barrier at roof system description’s A & B.
8. Sheet A600R DOOR SCHEDULE AND WALL TYPES 30 x 42 attached hereto
a. At the door schedule, add Remark #1 to Door #123.
b. Add existing Door #123C to Door Schedule.
c. Add a transfer grill to Door 128.
9. Sheet P101R 1st FLOOR ABOVE SLAB PLAN 30 x 42 attached hereto
a. Added Tub Filler(TF1) location in training room b. Increased hot water piping size to training room for tub filler.
10. Sheet P500R PLUMBING ISO AND DETAILS 30 x 42 attached hereto
a. Added tub filler to training room isometric b. Added note to install shutoff valves at new branch piping.
11. Sheet M010R HVAC DEMO PLAN 30 x 42 attached hereto
a. Added Demo Plan for Classroom Area E remodel.
12. Sheet M100R – FIRST FLOOR HVAC VENTILATION PLAN 30 x 42 attached hereto
a. Added plan for classroom remodel Area E.
13. Sheet E100 FIRST FLOOR PLAN – POWER AND SYSTEMS
a. 1E100; Add an access panel in the new furred wall at the corner of Office 1582. Position
it to access the existing conduit stub.
b. 2E100;
A. Add card reader, door position switch, power supply and electric strike at
exterior door 123.
B. Add card reader, door position switch, power supply and electric strike at
corridor door 123C.
14. Sheet E500 ELECTRICAL SCHEDULES
a. Light Fixture Schedules
A. Add Note 6 “Equivalent by Hubbell Lighting is acceptable.” Apply to all types.
B. Add note 7 “LED modules must be replaceable without removing fixtures.” Apply to types AA, DD, FF, OA, and OB.
END OF DOCUMENT 00 90 00
17003-2 Eau Claire Memorial 08 71 00 - 1
SECTION 08 71 00
3.04 HARDWARE SCHEDULE
EAU CLAIRE MEMORIAL HS
HARDWARE GROUP 1
EACH SINGLE ALUM DOOR TO HAVE:
DR.100A
1 EA CONTINUOUS HINGE MCK-14HD 83” CLEAR MCKINNEY
1 EA EXIT DEVICE ED5000 X K157 630 CORBIN
1 EA RIM CYLINDER MEDICO-GET THRU TRULOCK
1 EA OFFSET PULL BF156 US32D ROCKWOOD
1 EA ELECTRIC STRIKE 9400 630 HES
1 EA ES SPACER PLATE 108-630 HES
1 EA AUTO OPERATOR STANLEY MAGIC FORCE STANLEY
2 EA ACTUATORS AS REQUIRE STANLEY
1 EA CONCEALED OHS 1-336 630 RIXSON
1 EA THRESHOLD S425A36 REESE
1 EA WEATHERSTRIP/SWEEP BY ALUM DR/FR SUPPLIER
1 EA PWR SUPPLY BY ACCESS CONTROL VENDOR
1 EA DR POSITION SWITCH BY ACCESS CONTROL VENDOR
1 EA CARD READER BY ACCESS CONTROL VENDOR
HARDWARE GROUP 2
EACH SINGLE ALUM DOOR TO HAVE:
DR.100B, 100C, 100D, 100E, 100F
1 EA CONTINUOUS HINGE MCK-14HD 83” CLEAR MCKINNEY
1 EA EXIT DEVICE ED5000EO 630 CORBIN
1 EA OFFSET PULL BF156 US32D ROCKWOOD
1 EA CLOSER CPS7500 689 NORTON
1 EA DROP PLATE 7788 689 NORTON
1 EA SUPPORT BRACKET 6890 689 NORTON
1 EA BLADE SPACER 6891 689 NORTON
1 EA THRESHOLD S425A36 REESE
1 EA WEATHERSTRIP/SWEEP BY ALUM DR/FR SUPPLIER
HARDWARE GROUP 3
EACH SINGLE ALUM DOOR TO HAVE:
DR.100G
1 EA CONTINUOUS HINGE MCK-14HD 83” CLEAR MCKINNEY
1 EA PUSH/PULL COMBO BF15647 US32D ROCKWOOD
1 EA AUTO OPERATOR STANLEY MAGIC FORCE STANLEY
2 EA ACTUATORS AS REQUIRE STANLEY
1 EA CONCEALED OHS 1-336 630 RIXSON
17003-2 Eau Claire Memorial 08 71 00 - 2
HARDWARE GROUP 4
EACH SINGLE ALUM DOOR TO HAVE:
DR.100H, 100J, 100K, 100L, 100M
1 EA CONTINUOUS HINGE MCK-14HD 83” CLEAR MCKINNEY
1 EA PUSH/PULL COMBO BF15647 US32D ROCKWOOD
1 EA CLOSER CPS7500 689 NORTON
1 EA DROP PLATE 7788 689 NORTON
1 EA SUPPORT BRACKET 6890 689 NORTON
1 EA BLADE SPACER 6891 689 NORTON
HARDWARE GROUP 5
EACH PAIR OF ALUM DOORS TO HAVE:
DR.101A/B
2 EA CONTINUOUS HINGE MCK-14HD 83” CLEAR MCKINNEY
2 EA EXIT DEVICE ED5000EO 630 CORBIN
1 EA KEYED REMOVABLE MULLION 910KM 7’ CORBIN
1 EA MORTISE CYLINDER MEDICO-GET THRU TRULOCK
2 EA CLOSER CPS7500T 689 NORTON
2 EA DROP PLATE 7788 689 NORTON
2 EA SUPPORT BRACKET 6890 689 NORTON
2 EA BLADE SPACER 6891 689 NORTON
1 EA THRESHOLD S425A72 REESE
2 EA WEATHERSTRIP/SWEEP BY ALUM DR/FR SUPPLIER
HARDWARE GROUP 6
EACH SINGLE ALUM DOOR TO HAVE:
DR.101C, 101D, 101E, 101F
1 EA CONTINUOUS HINGE MCK-14HD 83” CLEAR MCKINNEY
1 EA EXIT DEVICE ED5000EO 630 CORBIN
1 EA CLOSER CPS7500 689 NORTON
1 EA DROP PLATE 7788 689 NORTON
1 EA SUPPORT BRACKET 6890 689 NORTON
1 EA BLADE SPACER 6891 689 NORTON
1 EA THRESHOLD S425A36 REESE
1 EA WEATHERSTRIP/SWEEP BY ALUM DR/FR SUPPLIER
HARDWARE GROUP 7
EACH PAIR OF DOORS TO HAVE:
DR.101G, 101H, 101J
2 EA CONTINUOUS HINGE MCK-FM300 83” 630 MCKINNEY
2 EA EXIT DEVICE ED5470B L910 M55 630 CORBIN
2 EA CLOSER PR7500 689 NORTON
2 EA MAG HOLD OPEN 998 689 RIXSON
2 EA WALL STOPS 409 US32D ROCKWOOD
2 EA SMOKE AST FINS S771D7 PEMKO
1 EA SMOKE GASKET F797B25 REESE
17003-2 Eau Claire Memorial 08 71 00 - 3
HARDWARE GROUP 8
EACH SINGLE ALUM DOOR TO HAVE:
DR.119A
1 EA CONTINUOUS HINGE MCK-14HD 93” CLEAR MCKINNEY
1 EA EXIT DEVICE ED5000 X K157 630 CORBIN
1 EA RIM CYLINDER MEDICO-GET THRU TRULOCK
1 EA OFFSET PULL BF156 US32D ROCKWOOD
1 EA ELECTRIC STRIKE 9400 630 HES
1 EA ES SPACER PLATE 108-630 HES
1 EA AUTO OPERATOR STANLEY MAGIC FORCE STANLEY
2 EA ACTUATORS AS REQUIRE STANLEY
1 EA CONCEALED OHS 1-336 630 RIXSON
1 EA THRESHOLD S425A36 REESE
1 EA WEATHERSTRIP/SWEEP BY ALUM DR/FR SUPPLIER
1 EA PWR SUPPLY BY ACCESS CONTROL VENDOR
1 EA DR POSITION SWITCH BY ACCESS CONTROL VENDOR
1 EA CARD READER BY ACCESS CONTROL VENDOR
1 EA CONTROL/BUZZER STATION BY ACCESS CONTROL VENDOR
HARDWARE GROUP 9
EACH SINGLE ALUM DOOR TO HAVE:
DR.119B, 119C, 119D
1 EA CONTINUOUS HINGE MCK-14HD 93” CLEAR MCKINNEY
1 EA EXIT DEVICE ED5000EO 630 CORBIN
1 EA OFFSET PULL BF156 US32D ROCKWOOD
1 EA ELECTRIC STRIKE 9400 630 HES
1 EA ES SPACER PLATE 108-630 HES
1 EA CLOSER CPS7500 689 NORTON
1 EA DROP PLATE 7788 689 NORTON
1 EA SUPPORT BRACKET 6890 689 NORTON
1 EA BLADE SPACER 6891 689 NORTON
1 EA THRESHOLD S425A36 REESE
1 EA WEATHERSTRIP/SWEEP BY ALUM DR/FR SUPPLIER
HARDWARE GROUP 10
EACH SINGLE ALUM DOOR TO HAVE:
DR.119E
1 EA CONTINUOUS HINGE MCK-14HD 83” CLEAR MCKINNEY
1 EA EXIT DEVICE ED5000 X K157 630 CORBIN
1 EA RIM CYLINDER MEDICO-GET THRU TRULOCK
1 EA OFFSET PULL BF156 US32D ROCKWOOD
1 EA ELECTRIC STRIKE 9400 630 HES
1 EA ES SPACER PLATE 108-630 HES
1 EA AUTO OPERATOR STANLEY MAGIC FORCE STANLEY
2 EA ACTUATORS AS REQUIRE STANLEY
1 EA CONCEALED OHS 1-336 630 RIXSON
1 EA PWR SUPPLY BY ACCESS CONTROL VENDOR
1 EA DR POSITION SWITCH BY ACCESS CONTROL VENDOR
1 EA CARD READER BY ACCESS CONTROL VENDOR
17003-2 Eau Claire Memorial 08 71 00 - 4
HARDWARE GROUP 11
EACH SINGLE ALUM DOOR TO HAVE:
DR. 119F, 119G, 119H
1 EA CONTINUOUS HINGE MCK-14HD 83” CLEAR MCKINNEY
1 EA EXIT DEVICE ED5000EO 630 CORBIN
1 EA OFFSET PULL BF156 US32D ROCKWOOD
1 EA ELECTRIC STRIKE 9400 630 HES
1 EA ES SPACER PLATE 108-630 HES
1 EA CLOSER CPS7500 689 NORTON
1 EA DROP PLATE 7788 689 NORTON
1 EA SUPPORT BRACKET 6890 689 NORTON
1 EA BLADE SPACER 6891 689 NORTON
HARDWARE GROUP 12
EACH PAIR OF DOORS TO HAVE:
DR. 103, 106
2 EA CONTINUOUS HINGE MCK-FM300 630 MCKINNEY
1 EA STOREROOM LOCK ML2057 LWA 630 CORBIN
1 EA MORTISE CYLINDER MEDICO-GET THRU TRULOCK
2 EA CLOSER CPS7500T 689 NORTON
2 EA FLUSHBOLTS 555 626 ROCKWOOD
1 EA DUST PR STRIKE 570 626 ROCKWOOD
2 EA KICKPLATE 10 X 35 B4E CS 630 ROCKWOOD
1 EA GASKET F797B25 REESE
2 EA AST FINS S771D7 REESE
HARDWARE GROUP 12.1
EACH PAIR OF DOORS TO HAVE:
DR. 107, 200
2 EA CONTINUOUS HINGE MCK-FM300 630 MCKINNEY
1 EA STOREROOM LOCK ML2057 LWA 630 CORBIN
1 EA MORTISE CYLINDER MEDICO-GET THRU TRULOCK
2 EA ELECTRO MECH CLOSER 7215MPI 689 NORTON
2 EA AUTO FLUSHBOLTS 1848 US32D ROCKWOOD
1 EA COORDINATOR 1672 SP28 ROCKWOOD
2 EA KICKPLATE 10 X 35 B4E CS 630 ROCKWOOD
1 EA GASKET F797B25 REESE
2 EA AST FINS S771D7 REESE
17003-2 Eau Claire Memorial 08 71 00 - 5
HARDWARE GROUP 13
EACH SINGLE DOOR TO HAVE:
DR. 102
3 EA BUTTS T4A3786-26D 4.5 X 4.5 MCKINNEY
1 EA CLASSRM LOCK ML2003LC LWA 630 CORBIN
1 EA MORTISE CYLINDER MEDICO-GET THRU TRULOCK
1 EA ELECTRIC STRIKE 1006 X KM 630 HES
1 EA SMART PACK 2005M3 HES
1 EA CLOSER CPS7500 689 NORTON
1 EA MAG HOLD OPEN 998 689 RIXSON
1 EA WALL STOP 409 US32D ROCKWOOD
1 EA PWR SUPPLY BY ACCESS CONTROL VENDOR
1 EA DR POSITION SWITCH BY ACCESS CONTROL VENDOR
1 EA CARD READER BY ACCESS CONTROL VENDOR
HARDWARE GROUP 14
EACH SINGLE DOOR TO HAVE:
DR. 108
1 EA CONTINUOUS HINGE MCK-FM300 630 MCKINNEY
1 EA CLASSRM LOCK ML2003LC LWA 630 CORBIN
1 EA MORTISE CYLINDER MEDICO-GET THRU TRULOCK
1 EA ELECTRO MECH CLOSER 7215MPI 689 NORTON
1 EA WALL STOP 409 US32D ROCKWOOD
1 EA SMOKE GASKET F797B19 REESE
HARDWARE GROUP 15
EACH PAIR OF DOORS TO HAVE:
DR.109A, 109B
2 EA CONTINUOUS HINGE MCK-FM300 83” 630 MCKINNEY
2 EA EXIT DEVICE ED5470B L955 M55 630 CORBIN
2 EA RIM CYLINDER MEDICO-GET THRU TRULOCK
2 EA ELECTRO MECH CLOSER 7215MPI 689 NORTON
2 EA CONCEALED OHS 1-336 630 RIXSON
2 EA SMOKE AST FINS S771D7 PEMKO
1 EA SMOKE GASKET F797B25 REESE
HARDWARE GROUP 16
EACH PAIR OF DOORS TO HAVE:
DR.105A, 105B
2 EA CONTINUOUS HINGE MCK-FM300 83” 630 MCKINNEY
2 EA EXIT DEVICE ED5470B L955 M55 630 CORBIN
2 EA RIM CYLINDER MEDICO-GET THRU TRULOCK
1 EA CLOSER PR7500 689 NORTON
1 EA ELECTRO MECH CLOSER 7215MPI 689 NORTON
1 EA MAG HOLD OPEN 998 689 RIXSON
1 EA CONCEALED OHS 1-336 630 RIXSON
1 EA WALL STOPS 409 US32D ROCKWOOD
2 EA SMOKE AST FINS S771D7 PEMKO
1 EA SMOKE GASKET F797B25 REESE
17003-2 Eau Claire Memorial 08 71 00 - 6
HARDWARE GROUP 17
EACH PAIR OF DOORS TO HAVE:
DR.110
1 EA BUTTS T4A3786-26D 4.5 X 4.5 MCKINNEY
1 EA EXIT DEVICE ED5200A L955 630 CORBIN
1 EA RIM CYLINDER MEDICO-GET THRU TRULOCK
1 EA CLOSER PR7500 689 NORTON
1 EA WALL STOPS 409 US32D ROCKWOOD
1 EA SMOKE GASKET F797B17 REESE
HARDWARE GROUP 18
EACH SINGLE DOOR TO HAVE:
DR. 111, 112, 113, 114, 117
3 EA BUTTS TA2714-26D 4.5 X 4.5 MCKINNEY
1 EA DORMITORY LOCK ML2067LC LWA 630 CORBIN
1 EA MORTISE CYLINDER MEDICO-GET THRU TRULOCK
1 EA CLOSER 7500 689 NORTON
1 EA MAG HOLD OPEN 998 689 RIXSON
1 EA KICKPLATE 10 X 34 B4E CS 630 ROCKWOOD
1 EA WALL STOP 409 US32D ROCKWOOD
1 EA GASKET F797B17 REESE
HARDWARE GROUP 19
EACH SINGLE DOOR TO HAVE:
DR. 115
3 EA BUTTS TA2714-26D 4.5 X 4.5 MCKINNEY
1 EA PRIVACY LOCK ML2030 LWA 630 CORBIN
1 EA CLOSER 7500 689 NORTON
1 EA KICKPLATE 10 X 34 B4E CS 630 ROCKWOOD
1 EA WALL STOP 409 US32D ROCKWOOD
1 EA GASKET F797B17 REESE
HARDWARE GROUP 20
EACH SINGLE DOOR TO HAVE:
DR. 118A
4 EA BUTTS T4A3786-26D 4.5 X 4.5 MCKINNEY
1 EA CLASSRM LOCK ML2003LC LWA 630 CORBIN
1 EA MORTISE CYLINDER MEDICO-GET THRU TRULOCK
1 EA ELECTRIC STRIKE 1006KM US32D HES
1 EA AUTO OPERATOR STANLEY MAGIC FORCE STANLEY
2 EA ACTUATORS AS REQUIRE STANLEY
1 EA KICKPLATE 10 X 34 B4E CS 630 ROCKWOOD
1 EA WALL STOP 409 US32D ROCKWOOD
1 EA GASKET F797B17 REESE
1 EA PWR SUPPLY BY ACCESS CONTROL VENDOR
1 EA DR POSITION SWITCH BY ACCESS CONTROL VENDOR
1 EA CARD READER BY ACCESS CONTROL VENDOR
SHARE UNLOCKING STATION ON DR 119A BY ACCESS CONTROL PROVIDER
17003-2 Eau Claire Memorial 08 71 00 - 7
HARDWARE GROUP 21
EACH SINGLE DOOR TO HAVE:
DR. 118B
4 EA BUTTS T4A3786-26D 4.5 X 4.5 MCKINNEY
1 EA DEADLATCH 4512-4-6-1-01-628 ADAMS RITE
1 EA DEADLATCH HANDLE 4569-X01 628 ADAMS RITE
1 EA MORTISE CYLINDER MEDICO-GET THRU TRULOCK
1 EA ELECTRIC STRIKE 7400 628 ADAMS RITE
1 EA PUSH/PULL BAR BF15747 US32D ROCKWOOD
1 EA CLOSER 7500 689 NORTON
1 EA KICKPLATE 10 X 34 B4E CS 630 ROCKWOOD
1 EA WALL STOP 409 US32D ROCKWOOD
1 EA GASKET F797B17 REESE
HARDWARE GROUP 22
EACH SINGLE ALUM DOOR TO HAVE:
DR. 123
1 EA CONTINUOUS HINGE MCK-14HD 83” CLEAR MCKINNEY
1 EA EXIT DEVICE ED5000 X K157 630 CORBIN
1 EA RIM CYLINDER MEDICO-GET THRU TRULOCK
1 EA OFFSET PULL BF156 US32D ROCKWOOD
1 EA ELECTRIC STRIKE 9400 630 HES
1 EA ES SPACER PLATE 108-630 HES
1 EA CLOSER CPS7500 689 NORTON
1 EA DROP PLATE 7788 689 NORTON
1 EA SUPPORT BRACKET 6890 689 NORTON
1 EA BLADE SPACER 6891 689 NORTON
1 EA THRESHOLD S425A36 REESE
1 EA RAIN DRIP R201A48 REESE
1 EA WEATHERSTRIP/SWEEP BY ALUM DR/FR SUPPLIER
1 EA PWR SUPPLY BY ACCESS CONTROL VENDOR
1 EA DR POSITION SWITCH BY ACCESS CONTROL VENDOR
1 EA CARD READER BY ACCESS CONTROL VENDOR
HARDWARE GROUP 23
EACH SINGLE DOOR TO HAVE:
DR. 123A, 124, 125, 126, 128
3 EA BUTTS TA2714-26D 4.5 X 4.5 MCKINNEY
1 EA DORMITORY LOCK ML2067LC LWA 630 CORBIN
1 EA MORTISE CYLINDER MEDICO-GET THRU TRULOCK
1 EA KICKPLATE 10 X 34 B4E CS 630 ROCKWOOD
1 EA WALL STOP 409 US32D ROCKWOOD
3 EA SILENCERS 608RWK GREY ROCKWOOD
17003-2 Eau Claire Memorial 08 71 00 - 8
HARDWARE GROUP 23.1
EACH SINGLE DOOR TO HAVE:
DR. 123C
3 EA BUTTS TA2714-26D 4.5 X 4.5 MCKINNEY
1 EA CLASSRM LOCK ML2003LC LWA 630 CORBIN
1 EA MORTISE CYLINDER MEDICO-GET THRU TRULOCK
1 EA ELECTRIC STRIKE 1006KM US32D HES
1 EA KICKPLATE 10 X 34 B4E CS 630 ROCKWOOD
1 EA WALL STOP 409 US32D ROCKWOOD
3 EA SILENCERS 608RWK GREY ROCKWOOD
HARDWARE GROUP 24
EACH SINGLE DOOR TO HAVE:
DR. 124A
3 EA BUTTS TA2714-26D 4.5 X 4.5 MCKINNEY
1 EA PRIVACY LOCK ML2030 LWA 630 CORBIN
1 EA CONCEALED OHS 1-336 630 RIXSON
1 EA KICKPLATE 10 X 34 B4E CS 630 ROCKWOOD
1 EA GASKET F797B17 REESE
HARDWARE GROUP 25
EACH SINGLE DOOR TO HAVE:
DR. 123B
3 EA BUTTS TA2714-26D 4.5 X 4.5 MCKINNEY
1 EA PASSAGE LOCK ML2010 LWA 630 CORBIN
1 EA KICKPLATE 10 X 34 B4E CS 630 ROCKWOOD
1 EA WALL STOP 409 US32D ROCKWOOD
3 EA SILENCERS 608RWK GREY ROCKWOOD
HARDWARE GROUP 26
EACH SINGLE DOOR TO HAVE:
DR. 127
3 EA BUTTS TA2714-26D 4.5 X 4.5 MCKINNEY
1 EA STOREROOM LOCK ML2057 LWA 630 CORBIN
1 EA MORTISE CYLINDER MEDICO-GET THRU TRULOCK
1 EA KICKPLATE 10 X 34 B4E CS 630 ROCKWOOD
1 EA WALL STOP 409 US32D ROCKWOOD
3 EA SILENCERS 608RWK GREY ROCKWOOD
END OF SECTION 08 71 00
RE
F.
GENERAL NOTES:
A
A
SYMBOL INDICATES WALL TYPE - SEESHEET A600 FOR WALL TYPE DETAILS.
SYMBOL INDICATES WINDOW TYPE. SEE SHEET A601 FORALUMINUM CURTAINWALL & STOREFRONT ELEVATIONS.
SEE ID SHEETS FOR FLOOR AND WALL FINISH LAYOUTS.
VERIFY EXACT SIZE AND LOCATION OF ALL MECH / PLUMB / ELEC OPENINGS.GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR FINISH AT ALLVISIBLE AREAS. ALL OPENINGS SHALL BE SEALED AFTER UTILITYINSTALLATION.
LOOSE FURNISHINGS EXCEPT AS NOTED SHALL BE PROVIDED ANDINSTALLED BY THE OWNER.
PAINT ALL EXPOSED STEEL LINTELS.
INSTALL BULLNOSE CMU AT ALL OUTSIDE CORNERS W/O TILE AND ATDOOR JAMBS AS DETAILED. NO BULLNOSE AT WINDOW JAMBS.
SEE STRUCTURAL FOR SLAB CONTROL JOINTS.
SEE 6A501& 7A501 FOR CMU WALL CONTROL JOINT DETAILS. SEESTRUCTURAL PLANS FOR CJ LOCATIONS. CJ = CONTROL JOINT
A
B
C
D
E
F
G
H
J
K
EXTEND ALL WALLS TO DECK UNLESS NOTED OTHERWISE.
L
M SEE 12A501 FOR TYPICAL HEAD FLASHING AND THROUGH-WALL FLASHINGISOMETRIC DETAIL.
SYMBOL INDICATES CONSTRUCTION NOTE THIS SHEET(NOT ALL KEY NOTES APPLY TO EACH SHEET)
REFER TO PLANS FOR FIRE RATING LOCATIONS AND ACCESSIBILITYROUTES.
LEGEND:
1 HOUR FIRE PARTITION WALL TO DECK
REMOVAL / INFILL OF EXISTING CMU WALLS TO BE 'TOOTHED' IN TOMATCH ADJACENT RUNNING BOND PATTERN. PATCH WALL TO MATCHADJACENT - TYPICAL
2 HOUR FIRE WALL
CORNER PROTECTION INTERGAL WITH GYPSUM WALL BOARD, INSTALLFLOOR TO CEILING AT ALL OUTSIDE CORNERS.
N NEW FACE BRICK IS FURNISHED BY OWNER, INSTALLED BY CONTRACTOR.
OFFICE
1XX
15XX
ROOM NAME
ARCHITECTURAL ROOM NUMBER
SCHOOL DISTRICT ROOM NUMBER
6" 12'-10" 6" 12'-10" 4" 6'-3"
6"
9'-0" 6" 10'-0" 6" 18'-9"
8"
20'-0"
3
A301
1'-0" 11'-6"
4'-8" 6'-0" 6'-0" 6'-0" 7'-4" 6'-0" 7'-4" 6'-0" 20'-0" 8'-0" 4'-8" 15'-4" 2'-4" 2'-0" 19'-6" 2'-0"
D8a
D8
D8
D8
D8
D8a
D8a
D8a D8a
D8aD8a
B3
A1A1
A1
B4a
B3
B4
B4a
B4a
B3a
B3a
B3a
B3a
B6
B3a
B3a
D7D7 D7 D7 D7
B4a
B6
3
A30014'-5 1
/2"
6"
2'-2"
5'-9"
2"4 1
/2"
6'-1"
6"
10'-6 1
/2"
5'-9"
4'-3 1
/2"
2"
1'-0"
3'-0"
14'-8"
2'-0"
6'-4"
25'-4"
6'-4"
1'-3"
27'-11"
2'-4"
14'-8"
8"
12'-0"
1'-4"
2"
1'-0"
1'-8"22'-10" 18'-8"
1'-0"2"1'-4"
1'-4"
8"
10'-0"
1'-4"
4'-0" 24'-10" 1'-0" 15'-4" 1'-0"
2"
1'-4"
1'-4"
3'-4"
2'-0"
8"
6'-0"
8"
4"
6'-4"
1'-4"
6'-4"
4"
1'-8"
8"
7'-6"
4'-0"
16'-5"
1'-0"
7'-4"
1'-0"
8'-3"
6'-4"
7'-6"
1'-0"
8'-2"
8"
6'-4"
1'-4"
6'-4"
8"
8"
2'-4"
1'-0"
2"
1
A301
12
A301
9
A302
1'-0" 12'-4" 3'-0"
5'-10"5'-4"
1'-2"
5'-4"
8"
4'-6"
6"
3'-6"
6"
4'-6"
8"
5'-4"
10"
8'-5"
10"
5'-4"
9 1/2"
6'-2 1/2"
6"
9'-0"
6"
4'-4" 5'-4"
10"
9'-5"
8"
8'-0" 1'-4" 20'-0"
2
A200
1
A200
6
A200
4
A300
VESTIBULE
1500.10
100
OFFICE
1582
111
OFFICE
1580
112
OFFICE
1578
113
OFFICE
1576
114
TOILET
1574
115
CONF.
1566
117RECEPTION
1564
118
VESTIBULE
1500.08
119
CORRIDOR
1500.06
122
CORRIDOR
1500.07
120
LOBBY
1500.09
101
CONCESSION
1598
102
STORAGE
1590
108
GYM
1525
109
1
A300
2
A300
5
A300
HALL
1568
110A
CORRIDOR
1570
110
2
A302
9
A301
10
A301
2'-0"
26'-10" 2'-0"
4" 1'-0"
2'-0" 13'-0" 1'-0"2"
1'-0"
7
A301
2"
1'-0"
5'-2"
6'-0"
14'-0"
3'-8"
1'-4"
70'-4"
31'-4"
101'-8"
8
A301
4
A301
2
A301
5
A301
6
A301
14
A301
15
A301
13
A301
6
A300
6
A302
3
A302
5
A302
1
6" 15'-0"
7
A300
18'-0"
CU
RT
AIN
WA
LL
45'-4"
7'-0"
8"
2'-0"
CURTAINWALL
24'-0" 6'-0"2'-0" 14'-4"
1'-4"
7" 28'-3" 1'-4" 15'-0" 1'-0"
2"
1'-4"
7"
6'-4"
4"
8"
4"
6'-4"
4"
8"
4"
6'-4"
7"
4
A302
3
A301
11
A301
OFFICE
1498E
116
110
109A
109B
108
102
101G
101H
101J
106
105B
107
111
112
113
114
115
117
118A
DECA
1590A
103
7
A302
CLERESTORYABOVE - SEE2A101
103
4'-8"
1'-0"
9'-4"
2
B3
B3
2
22
22
2
2
4 4 4 4 4 4
55
5
10
10
10
10
10
10
10
10
COACHES
1550
126
COACHES
1530
125
125
126
102A
12
12
12
13
13
13
13
14
14
15
15
17
17
17
8
2'-4"
10
A302
2
A303
A501
1
A501
2
A501
3
A1
A501
2
A501
4
A501
10
A501
8
1818
18 18 18
18 18
20
20
21
21
2222 2222 22222222222222
24
27
27
27
28
28
28
2929
A501
5
A
A
E
CC C C G BA501
18
TYP
B4a
B4a
A B C D
1
2
3
4
5
3
A303
29
100G
100M
101A/B
101C
101D
101E
101F
31
31
CORR.
1600.01
1600.01
CORR.
1500.05
1500.05
F
B3
32 32
32
32
B1
11
A302
3'-4"
2'-10"
28'-6 3
/4"
29'-0"
31'-1 1
/4"
6'-10"
A100R 3
34
34
34
34
17
B3
OFFSET FORBULLNOSE
22
B3B3B3B3
B4
B7
B4
12'-0"
B4a
B4a
STORAGE
1500.11
107
STORAGE
1500.12
106
2'-8"
5'-4"
B3
B4
B3
1'-7" 28'-7" 1'-10" 15'-4"
13
1314
32
32
32
32
32
32
B6
SIM
2'-8"
118B
119A
119D
1'-8"
2'-4"
1'-0"
1'-1"
12'-8"
4'-0"
6'-0"6'-4"
B3a
2
A1a
6"
12'-6 1
/2"
7 1
/2"
4'-3"
10"
7 1/2" 1'-1 1/2"
9" 22'-8" 5'-2" 3'-4" 11'-0" 1'-8"
2'-7"
4'-2"
2'-7"
9'-4"
B4a
B6
B6
FEC
FEC
FEC
FEC
FEC
16
16
GYM
1525
109
8'-0"
17'-0"
D
1'-6"
17
18
18
18
18
18
F.F.E 100'-0"
100H
100J
100K
100L
100A
100B
100C
100D
100E
100F
7 B4a
PASSAGE
1584
109
34
105APASSAGE
1592
105
119B
119C
119E
119F
119G
119H
3
A301
6
A301
B3
6'-10"
17'-8"
1
A302
B4
6
A2
COPIER
COUNTER REF. BELOWMICROWAVE ABOVE
ICE
PO
PC
OR
NS
OD
AC
OO
LE
R
HA
ND
WA
SH
CASHIER
FEC
22
D1 D1a
D1a
11
A501
4
A501
2
SIM
A501
4
SIM
A501
9
K.O.PANEL
26
10
10
8
A302
D7
B4a
B4
A1
33
5
A303
4'-8"
8'-2"
D8
D7
EXIST BLEACHERS
FIELD VERIFY
100'-0"
MIN
.
1'-6"
MIN
.
1'-6"
FLOOREXTENTS
12
39
39
39
39
39
39
39
39
39
39
39
39
27
27
27
27
FE
D1a
INFILLEXISTINGOPENING
22
4'-6"
4'-2"
40
A2
CORR
1700.02
1700.02
CORR
1400.06
1400.064'-0"
6'-0"
8"
17'-4"
4'-8"
8"
14'-2" 8"
14'-8"
8"4"3'-4"
A100R
2
TRAINING
123
OFFICE
123A
TOILET
124A
PASSAGE
127
OUTSIDE
127
123B
123A
124 OFFICIALS
124
124A
EXIST LOCKERSEXIST LOCKERS
14
2
6'-8"
8"
10'-0"
STOR
1507
123B
26'-2" 8" 8'-0"
8"
5'-3 1/2"
B3
B3
B3
B3
B3
123
A501
20
TR
EA
TM
EN
T T
AB
LE
30
"X80
"
TAPINGAREA 4'X8'
ICE30"X40"
UTILITYSINK
WP +TABLE
53" X 47"
BASECABINET
(NIC)
TR
EA
TM
EN
T T
AB
LE
30
"X80
"
CH CH
A2
123C
41
A2
ID100
4
8" 9'-0"
8" CLR
3'-0" 2'-0"
8"
8"
11"
4"
3'-4"
2'-0"
3'-5"
GB36
GB
42
VGBTPH
PTDLS
D M1
SCRH RH
1'-6"
UTILITY SINK
B3
B1
B1
B3
B3
S
VGB
GB18-30
ACCESSORY SCHEDULEABBREVIATION ITEM STD. MOUNTING HEIGHT
1'-6"W X 3'-0"H MIRROR WITH FRAMEM1 BOT. @ 3'-4" A.F.F.
PAPER TOWEL DISPENSER (OFCI)PTD BOT. @ 3'-6" A.F.F.
DBL TOILET PAPER HOLDER - CENTER 36" FROM BACK WALLTPH
1 1/2" DIA. GRAB BAR, 42" LONGGB42 CENTER @ 2'-10" A.F.F.
STOOL LIP (OFCI)
1 1/2" DIA. VERTICAL GRAB BAR - 18" LONGVGB BOT @ 3'-4" A.F.F.
ACCESSORY SCHEDULE GENERAL NOTES:
1. ALL ACCESSORIES TO BE - PROVIDED AND INSTALLED BY CONTRACTOR, UNLESS NOTED OTHERWISE2. CONFIRM EXACT LOCATION OF EACH ACCESSORY WITH OWNER PRIOR TO INSTALLATION.3. SURFACE MOUNTED ACCESSORIES SHALL BE INSTALLED OVER WALL TILE.4. OFCI = OWNER FURNISHED, CONTRACTOR INSTALLED5. PROVIDE INSULATION WRAP AT EXPOSED PIPING AT SINKS WHERE NO OTHER PROTECTION IS PROVIDED6. DIMENSIONS ARE TO FINISH FACE OF WALL TILE WHERE TILE IS INSTALLED.
LSD LIQUID SOAP DISP. (OFCI)
GB36 1 1/2" DIA. GRAB BARS, 36" LONG
CENTER @ 2'-0"
CENTER @ 2'-10" A.F.F.
BOT. @ 3'-6" A.F.F.
SHOWER CURTAIN AND RODSC TOP. @ 7'-0" A.F.F.
ROBE HOOK (DOUBLE)RH TOP. @ 5'-0" A.F.F.
ADA COMPLIANT FOLD-UP SHOWER SEATS
1 1/2" DIA. GRAB BAR - 18" LONG x 30" LONG (SEE PLAN)GB18-30 CENTER @ 2'-10" A.F.F.
18" A.F.F.FIRST FLOORPARTIAL PLAN100'-0"
MEZZ110'-10"
OWNERFURNISHED
PLASTERPANELS
(8” DEPTH) –VERIFY SIZE
OWNERFURNISHED
PLASTER PANELS(8” DEPTH) –VERIFY SIZE
OWNERFURNISHED
PLASTERPANELS
(8” DEPTH) –VERIFY SIZE
FACE BRICKVENEER
EQ 3'-10 1/2" 6'-0" 4'-7 1/2" 6'-0" 3'-10 1/2" EQ
TRACK LIGHTING -SEE ELECTRICAL
2'-0"
5'-2"
3'-8 1
/2"
3'-5 1
/2"
8'-0"
GYP BD
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREETLA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
WEB SITE: www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sh
ee
t T
itle
:
Pro
ject L
oca
tio
n:
Pro
ject T
itle
:
BIDDOCUMENTS
2/19/2018 1:55:33 PM
A100R
HSR
17003
2-5-18
PA
RT
IAL
FIR
ST
FL
OO
R R
EM
OD
EL
PL
AN
ME
MO
RI A
L H
IGH
SC
HO
OL
OF
FI C
E/ L
OB
BY
EX
PA
NS
ION
2225 K
EIT
H S
T, E
AU
CL
AIR
E, W
I 54701
EA
U C
LA
IRE
AR
EA
SC
HO
OL
DIS
TR
ICT
KEY NOTES PLAN1 4" CONCRETE FLOOR SLAB INFILL
2 INFILL EXISTING OPENING WITH MASONRY. SEE WALL TYPE/ MATCHEXISTING ADJACENT CONDITIONS. TOOTH IN NEW MASONRY ASREQUIRED
3 NOT USED
4 SOLID SURFACE WINDOW STOOL – ADHESIVE APPLIED – SEALPERIMETER
5 PAINTED EXPOSED STEEL COLUMN - SEE INTERIORS
6 CONSTRUCT SHAFT TO ACCOMODATE FUTURE WHEELCHAIR LIFT.PROVIDE MASONRY KNOCK-OUT PANEL FOR FUTURE DOOR @ FIRSTFLOOR. WHEELCHAIR LIFT AND ACCESS DOORS WILL BE FURNISHED &INSTALLED BY OTHERS. CONFIRM SHAFT SIZE & REQUIREMENTS w/OWNER PRIOR TO SHAFT CONSTRUCTION.
7 M/E/P CHASE
8 FEATURE ACCENT WALL - OWNER PROVIDED BRICK VENEER & PLASTERPANELS – SEE 3/A100 ELEVATION.
9 ROOF ACCESS VERTICAL LADDER, WITH SCUTTLE ABOVE.
10 PATCH/ REPAIR FLOOR AND WALLS AT WALL REMOVAL. TOOTH IN NEWMASONRY AS REQUIRED
11 MAINTAIN EXISTING FLOOR HATCH
12 BULKHEAD/ SOFFIT ABOVE, TYP. SEE CEILING PLANS
13 AUTO OPERATOR PUSH PADDLE CONTROL LOCATION
14 CONCRETE STOOP, TYP. SEE STRUCTURAL
15 REINSTALL RELOCATED WALL MATS
16 PAINTED EXPOSED CANOPY FRAMING ABOVE
17 DISPLAY CASE FURNISHED & INSTALLED BY OWNER. SEE ELECTRICALFOR LIGHTING/ OUTLETS. SEE SECTION 10/A301 FOR TYPICAL DISPLAYCASE SUPPORT WALL AND GYPSUM SOFFIT ABOVE.
18 FURNITURE/ CASEWORK FURNISHED AND INSTALLED BY OWNER.COORDINATE ELECTRICAL/ IT/ LIGHTING/ PLUMBING AS REQUIRED
19 ALUM RAIN WATER CONDUCTOR HEAD & OPEN FACE DOWNSPOUT
20 MOTORIZED GYM DIVIDER FOLDING WALL. NEW TRACK AND PLYWOODSURROUND INSTALLED IN EXISTING LOCATION - SEE 7A303. INSTALLPANEL CLOSET DOOR.
21 RETURN AIR DUCT - SEE MECHANICAL.
22 NEW WALL FURRING ON EXISTING WALL. SEE WALL TYPE
23 INSTALL ROOF PROTECTION PAD AT HIGH ROOF DRIP LINE
24 EXISTING RESTROOM FINISHES AND FIXTURES TO REMAIN. NEW FIRERATED DOOR
25 EQUIP PLATFORM STAIR: METAL PLATE TREADS & LANDING, STEELCHANNEL STRINGERS, STEEL PIPE HAND RAILS
26 NEW STEEL BEAMS ABOVE - SEE STRUCT
27 NEW OPENING IN EXISTING MASONRY WALL
28 RADIATOR - SEE MECHANICAL
29 INSTALLED STAINLESS STEEL COUNTERTOP OVER OWNER INSTALLEDBASE CABINETS
30 6" CONCRETE HOUSEKEEPING PAD AND AIR HANDLING UNIT - SEEMECHANICAL
31 REINSTALLED SALVAGED CASEWORK/ TV. MODIFY EXISTINGCASEWORK AND COUNTERTOP TO ACHIEVE MINIMUM OF 18” CLEARDIMENSION AT DOOR.
32 NEW CMU PIER - SEE STRUCTURAL
33 STEEL COLUMN - SEE STRUCT
34 RECESS CONCRETE SLAB 5/8” (VERIFY) FOR FLUSH INSTALLATION OFPORCELAIN TILE FLOOR
35 PREFINISH SHEET METAL WALL CAP
36 2'-0" WIDE X 3'-4" HIGH FIRE RATED STEEL ACCESS DOOR INSTALLED @86" A.F.F. TO BOTTOM. VERIFY LOCATION WITH OPERABLE PARTITIONSHOP DRAWINGS FOR ACCESS TO MOTOR.
37 INSTALL EXPANDED METAL SCREEN INFILL AT EQUIPMENT PLATFORMSTAIR REMOVAL - PAINT. (TYPICAL @ 3 LOCATIONS IN GYM)
38 TEMPORARY FIRE TREATED PLYWOOD FLOOR DECK - SEE WALLSECTION.
39 REPLACE/ PATCH VENTED FLOOR BASE AT NEW OPENING/ WALLS.
40 INSTALL NEW LOCKABLE METAL FLOOR ACCESS HATCH IN EXISTINGOPENING.
41 AT LOCKER REMOVAL, PATCH EXISTING CORRIDOR TERRAZZO FLOORWHERE CONC LOCKER BASE HAS BEEN REMOVED. INSTALL NEWTERRAZZO COVE BASE IN DOOR ALCOVE. PATCH EXISTING WALL EACHSIDE OF NEW DOOR / FRAME AND RECONSTRUCT EXISTING PLASTERSOFFIT @ 7'-4" A.F.F. PAINT WALL & SOFFIT TO MATCH EXISTINGADJACENT SURFACES.
1/8" = 1'-0"1PARTIAL FIRST FLOOR REMODEL PLAN KEY PLAN
1/4" = 1'-0"2ENLARGED TOILET
1/4" = 1'-0"3FEATURE ACCENT WALL
SEE SHEET AI0I
No. Description Date
A2 Addendum 2 2/20/18
A2
DOOR SCHEDULE REMARKS1. ELECTRONIC CARD ACCESS AND ELECTRONIC STRIKE REQUIRED.2.3.4.5.
6.7.8.
DOOR SCHEDULE GENERAL NOTES
A. SEE SPECIFICATIONS FOR DOOR HARDWARE GROUPS.B. ALL HM (HOLLOW METAL) AND IHM (INSULATED HOLLOW METAL) DOORS AND FRAMES SHALL BE PAINTED.
HM = HOLLOW METAL IHM = INSULATED HOLLOW METAL ALUM = ALUMINUM
A B
7'-0"
SEE SCHED.3'-0"
7'-0"
10"
ALUM
*WIDE STYLE DOOR
C
7'-0"
SEE SCHED.
4'-0"
2'-6"
6"
8" 6"6" 8"
C1 NO GLASS
D
SEE SCHED.
7'-0"
4'-0"
2'-6"
6"
6" 8"
C. ALL O.H. DOORS SHALL BE INSULATED
E
SEE SCHED.
7'-0"
4'-0"
2'-6"
6"
6" 2'-0"
DOOR FRAME GENERAL NOTES
A. ALL HM (HOLLOW METAL) FRAMES SHALL BE PAINTED.
HM = HOLLOW METAL ALUM=ALUMINUM
HOLLOW METAL FRAME ELEVATIONS
1
2"
SE
E S
CH
ED
2" SEE SCHED 2"
2
4"
SE
E S
CH
ED
2" SEE SCHED 2"
3
2" SEE SCHED
2"
- 2"
MAGNETIC HOLD OPEN TIED TO FIRE ALARM. SEE ELECTRICAL.POWER SUPPLY, AUTO OPERATOR W/ ACTUATORS.REMOVABLE MULLION BY DOOR HARDWARE SUPPLIER.ELECTRONIC CARD ACCESS CONTROL AND ELECTRONIC STRIKE REQUIRED.BUZZER SYSTEMWITH CONTROL AT TWO STATIONS.
MOTORIZED COILING COUNTER DOOR.TWO EQUAL LEAFS.MAIN DOOR TO BE 3'-4".
9. HEAVY DUTY CONTINUOUS HINGE
4
2" SEE SCHED
2"
EQ
2"
EQ2"
4"
4'-2"
2"
1'-10"
10"
5
2"SEE SCHED
2"
EQ
4"
EQ
4"
EQ2"
10"
1'-10"
2"
4'-2"
4"
SEE PLAN SEE PLAN
2"
3'-10"
2"
1'-10"
10"
SEE PLAN
GLT 18
GLT 18
GLT 8
GLT 8
GLT 8
GLT 8
GLT 8
GLT 8
GLT 8
GLT 8
GLT 8
GLT 8
C2 RATED OPENINGS6"X16" NV
6
2" SEE SCHED
2"
- 2"
SEE PLAN
GLT 18
GLT 18
7'-4"
MA
TC
H E
XIS
TIN
G
-
B3
8" CMU
7 5/8" 8"
PARTITIONTYPE
PARTITION WIDTH
ACTUAL NOMINAL
B1
4" CMU
MASONRY REINFORCING
3 5/8"
PARTITIONTYPE
PARTITION WIDTH
ACTUAL NOMINAL
4"
12" CMU
B4 11 5/8" 12"
PARTITIONTYPE
PARTITION WIDTH
ACTUAL NOMINAL
3 5/8" 7 5/8" 11 5/8"
B3a 7 5/8" 8"
8" CMU
1 HOUR RATED
@ B3a
D7 D8
1/2" MOLD RES. GYP BD.
FIRE TREATED 1/2"PLYWOOD
FIRE TREATED 1/2"PLYWOOD
SPRAY FOAM
PARTITIONTYPE
STUD WIDTH/ SPACING
PARTITION WIDTH
ACTUAL NOMINAL
PARTITIONTYPE
STUD WIDTH/ SPACING
PARTITION WIDTH
ACTUAL NOMINAL
16" O.C. 16" O.C.4 1/2" 5 5/8"5" 6"D1
PARTITIONTYPE
STUD WIDTH/ SPACING
PARTITION WIDTH
ACTUAL NOMINAL
16" O.C. 2 1/8" 2"
7/8" HAT CHANNEL @ 16"O.C.
7/8"
5/8"
5/8"
2 1/8"
A1
PARTITIONTYPE
PARTITION WIDTH
ACTUAL NOMINAL
1'-4"
7 5/8" 3"
1 3/4"
3 5/8"
1'-4"
GENERAL WALL TYPE NOTES:A REFER TO MASTER COLOR SCHEDULE AND INTERIOR DESIGN
SHEETS FOR ADDITIONAL WALL FINISHES.
B
NON RATED WALLS, INCLUDING BULKHEADS SHALL HAVE FRAMINGEXTENDED TO DECK ABOVE. GYP BOARD SHALL EXTEND TO DECKUNLESS NOTED OTHERWISE. COLUMN FURRING MAY STOP 4" ABOVECEILING.
C
D
E
F
AT SOUND CONTROL WALLS (INDICATED BY INSULATION, SOUND SEALNOTE OR STC RATING) APPLY CONTINUOUS BEAD OF ACOUSTICALSEALANT AT FLOOR/CEILING TRACK STUDS AND STUD AT WALL. APPLYCONTINUOUS BEAD OF ACOUSTICAL SEALANT AT PERIMETER OF GYPBOARD HOLDING EDGE OF GYP BOARD AWAY FROM ADJACENTSTRUCTURE NO MORE THAN 3/8". SEAL ALL M/E/P/FP PENETRATIONSWITH SOUND BLANKET, BACKING, ACOUSTICAL SEALANT AND FIRESTOPPING. AFTER INSTALLING ONE SIDE OF GYP BOARD, APPLYOVERSIZED 2" SOUND BLANKET OVER BACK SIDE OF ELECTRICALBOXES AND SIMILAR PENETRATIONS. WHERE WALL BOXES OCCUR ATOPPOSITE SIDES, APPLY INSULATION TO BACKSIDE OF WALL BOXES.AT FIRE RATED WALLS REQUIRING SOUND CONTROL, USE PUTTYPADS FOR REQUIRED WALL RATING. REFER TO TOP OF WALL DETAILSFOR INSTALLATION OF ADDITIONAL MATERIALS AT DECK ANDAPPLICATION OF RATED TOP OF WALL ASSEMBLIES.
INSTALL GYPSUM BOARD CONTROL JOINTS AT TOP OF ALL INTERIORTOP OF DOOR JAMBS TO TOP OF GYPSUM BOARD WALLS. OTHERCONTROL JOINTS TO BE INSTALLED PER PLAN OR AT 30'-0" O.C.MAX. REVIEW LOCATION REQUIREMENTS WITH A/E PRIOR TOSTART OF INSTALLATION OF GYPSUM BOARD ASSEMBLIES.
G WHERE FIRE RATED WALLS ARE INDICATED BY WALL TYPE, USE ULOR EQUIVALENT APPROVED RATING SYSTEM INCLUDING TOP OFWALL AND PENETRATIONS.
RATED CMU WALL TABLE:1 HOUR MINIMUM 2.8 EQUIVALENT WALL THICKNESS
2 HOUR MINIMUM 4.2 EQUIVALENT WALL THICKNESS
EXTEND STUDS, GYP BOARD AND SOUND BLANKET TO DECK ABOVEAT SOUND CONTROL WALLS (INDICATED BY BATT INSULATION, SOUNDSEAL NOTE OR STC RATING). LEVEL OF FINISH ABOVE CEILING ASNOTED IN SECTION 09 21 16
2 HOUR RATED
B6 15 5/8" 16"
PARTITIONTYPE
PARTITION WIDTH
ACTUAL NOMINAL
1'-3 5/8"
3 1/2"
1/2"1/2"
4 1/2"
1/2"1/2"
3 5/8"1/2"1/2"
5 5/8"
1/2" MOLD RES. GYP BD.
BATT INSULATION
D9
PARTITIONTYPE
STUD WIDTH/ SPACING
PARTITION WIDTH
ACTUAL NOMINAL
16" O.C. 7 1/4" 7"
5/8" MOLD RES. GYP BD.
6" BATT INSULATION
7 1/4"
5/8" 6" 5/8"
FACE BRICK
A2
PARTITIONTYPE
PARTITION WIDTH
ACTUAL NOMINAL
2'-0" 2'-0"
3 5/8"
3/8"
11 5/8"3"
1 3/4"
3 5/8"
2'-0"
3" SPRAY FOAM INSULATION
AIR SPACE
12" CMU
FACE BRICK
8" CMU
A3
PARTITIONTYPE
PARTITION WIDTH
ACTUAL NOMINAL
1'-8" 1'-8"
11 5/8" 3"
1 3/4"3 5/8"
1'-8"
FACE BRICK
3" SPRAY FOAM INSULATION
AIR SPACE
12" CMU
ADJUSTABLE MASONRYWALL TIE
5/8" MOLD RES. GYP BD.
PARTITIONTYPE
STUD WIDTH/ SPACING
PARTITION WIDTH
ACTUAL NOMINAL
4 1/4"
6" METAL STUDS
D10
PARTITIONTYPE
STUD WIDTH/ SPACING
PARTITION WIDTH
ACTUAL NOMINAL
16" O.C. 9 5/8" 10"
5/8" MOLD RES. GYP BD.
2" RIGID INSULATION W/ TAPED JOINTS FORCONTINUOUS AIR BARRIER
5/8" 6"
1/2"
2" 1/2"
6" METAL COLD FORMED FRAMING
E.P.D.M. FLASHING FULLY ADHERED
1/2" EXT PLYWD SHTG
16" CMU OR DOUBLEWYTHE
@ B4a
12" CMU
MASONRYREINFORCING
MASONRYREINFORCING
B4a 11 5/8" 12"
MASONRYREINFORCING
B7
8" CMU
15 5/8" 16"
PARTITIONTYPE
PARTITION WIDTH
ACTUAL NOMINAL
7 5/8"
MASONRYREINFORCING
BRICK
4 3/8" 3 5/8"
1'-3 5/8"
AIR SPACE
FIRE TREATED 1/2" PLYWOOD
D8a 16" O.C. 5 5/8" 6" 1 HOUR
CORNER PROTECTION INTERGAL WITH GYPSUM WALL BOARD, INSTALLFLOOR TO CEILING AT ALL OUTSIDE CORNERS.
2 HOUR RATED
FIRERESISTANCE
RATING
1 HOUR RATED
FIRERESISTANCE
RATING
FIRERESISTANCE
RATING
1'-4"
ADJUSTABLE MASONRYWALL TIE
D1a
5/8" MOLD RES. ABUSE GYP BD
5/8" GYP BD DIRECT GLUEDTO EXIST CMU WALL @ 'D1a'
A1a 1'-0" 1'-0"
1 1/2" SPRAY FOAM @ 'A1a'
6" CMU @ 'A1a'
BOTH SIDES
BOTH SIDES
D4 16" O.C. 4 1/4"
3 5/8" METAL STUD
FIRE TREATED WOOD STUD
9 5/8"
FIRE TREATED 1/2" PLYWOOD
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREETLA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
WEB SITE: www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sh
ee
t T
itle
:
Pro
ject L
oca
tio
n:
Pro
ject T
itle
:
BIDDOCUMENTS
2/19/2018 1:33:05 PM
A600R
HSR
17003
2-5-18
DO
OR
SC
HE
DU
LE
/ W
AL
L T
YP
ES
ME
MO
RI A
L H
IGH
SC
HO
OL
OF
FI C
E/ L
OB
BY
EX
PA
NS
ION
2225 K
EIT
H S
T, E
AU
CL
AIR
E, W
I 54701
EA
U C
LA
IRE
AR
EA
SC
HO
OL
DIS
TR
ICT
DOOR SCHEDULE
DOORNO.
DOOR FRAME
FIRELABEL
HDWRGROUP REMARKS
SIZE
MAT'L TYPEGLASSTYPE MAT'L ELEV DEPTH
DETAILS
W H TJAMB /HEAD SILL
100A 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 12 ALUM 1A601 7 1/2" 11A501 1 1, 3
100B 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 12 ALUM 1A601 7 1/2" 11A501 2 1
100C 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 12 ALUM 1A601 7 1/2" 11A501 2 1
100D 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 12 ALUM 1A601 7 1/2" 11A501 2 1
100E 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 12 ALUM 1A601 7 1/2" 11A501 2 1
100F 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 12 ALUM 1A601 7 1/2" 11A501 2 1
100G 3' - 0" 7' - 0" 1 3/4" ALUM A GLT-4 ALUM 2A601 6" 3 1, 3
100H 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 4 ALUM 2A601 6" 4 1
100J 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 4 ALUM 2A601 6" 4 1
100K 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 4 ALUM 2A601 6" 4 1
100L 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 4 ALUM 2A601 6" 4 1
100M 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 4 ALUM 2A601 6" 4 1
101A/B 6' - 0" 7' - 0" 1 3/4" ALUM A GLT 12 ALUM 11A601 7 1/2" 11A501 5 4, 7
101C 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 12 ALUM 11A601 7 1/2" 11A501 6
101D 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 12 ALUM 11A601 7 1/2" 11A501 6
101E 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 12 ALUM 11A601 7 1/2" 11A501 6
101F 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 12 ALUM 11A601 7 1/2" 11A501 6
101G 6' - 0" 7' - 0" 1 3/4" SCWD C2 GLT 18 HM 2 8 3/4" 4 / 15A501 SIM 90 MIN 7 2, 7
101H 6' - 0" 7' - 0" 1 3/4" SCWD C2 GLT 18 HM 2 8 3/4" 4/ 15A501 SIM 90 MIN 7 2, 7
101J 6' - 0" 7' - 0" 1 3/4" SCWD C2 GLT 18 HM 2 8 3/4" 4 / 15A501 SIM 90 MIN 7 2, 7
102 3' - 4" 7' - 0" 1 3/4" HM B HM 2 8 3/4" 15A501 13 1
102A 14' - 0" 5' - 2" 2" COILING DOOR - - - 6
103 6' - 0" 7' - 0" 1 3/4" SCWD C1 - HM 2 5 3/4" 15A501 12 7
105A 6' - 0" 7' - 0" 1 3/4" SCWD C2 GLT 18 HM 2 8 3/4" 4 / 15A501 90 MIN 16
105B 6' - 0" 7' - 0" 1 3/4" SCWD C2 GLT 18 HM 2 8 3/4" 4 / 15A501 90 MIN 16
106 6' - 0" 7' - 0" 1 3/4" SCWD B HM 2 5 3/4" 15A501 SIM 12 7, 9
107 6' - 0" 7' - 0" 1 3/4" HM B - HM 2 8 3/4" 15A501 SIM 90 MIN 12 7
108 3' - 8" 7' - 0" 1 3/4" HM B HM 2 5 3/4" 15A501 SIM 90 MIN 14
109A 6' - 0" 7' - 0" 1 3/4" SCWD C2 GLT 18 HM 2 8 3/4" 4 & 15A501 90 MIN 15 7
109B 6' - 0" 7' - 0" 1 3/4" SCWD C2 GLT 18 HM 2 8 3/4" 4 & 15A501 90 MIN 15 7
110 3' - 0" 7' - 0" 1 3/4" SCWD B GLT 18 HM 2 8 3/4" 15A501 SIM 90 MIN 17
111 3' - 0" 7' - 0" 1 3/4" SCWD B HM 3 6 3/4" 16A501 20 MIN (Type S) 18 2
112 3' - 0" 7' - 0" 1 3/4" SCWD B HM 3 6 3/4" 16A501 20 MIN (Type S) 18 2
113 3' - 0" 7' - 0" 1 3/4" SCWD B HM 3 6 3/4" 16A501 20 MIN (Type S) 18 2
114 3' - 0" 7' - 0" 1 3/4" SCWD B HM 3 6 3/4" 16A501 20 MIN (Type S) 18 2
115 3' - 0" 7' - 0" 1 3/4" SCWD B HM 2 6 3/4" 20 MIN (Type S) 19
117 3' - 0" 7' - 0" 1 3/4" SCWD B HM 3 6 3/4" 16A501 20 MIN (Type S) 18 2
118A 3' - 0" 7' - 0" 1 3/4" SCWD A GLT 8 HM 5 8 3/4" 15A501 20 1, 3, 5
118B 3' - 0" 7' - 0" 1 3/4" SCWD A GLT 8 HM 4 8 3/4" 15A501 21
119A 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 12 ALUM 9A601 6" 15A501 SIM 11A501 8 1, 3
119B 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 12 ALUM 9A601 6" 15A501 SIM 11A501 9 1
119C 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 12 ALUM 9A601 6" 15A501 SIM 11A501 9 1
119D 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 12 ALUM 9A601 6" 15A501 SIM 11A501 9 1
119E 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 8 ALUM 10A601 4 1/2" 15A501 10 1, 3
119F 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 8 ALUM 10A601 4 1/2" 15A501 11 1
119G 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 8 ALUM 10A601 4 1/2" 15A501 11 1
119H 3' - 0" 7' - 0" 1 3/4" ALUM A GLT 8 ALUM 10A601 4 1/2" 15A501 11 1
123 3' - 0" 7' - 2" 1 3/4" ALUM A GLT 12 ALUM 3 4 1/2" 20A501 11A501 SIM 22 1
123A 3' - 0" 7' - 0" 1 3/4" SCWD D GLT 4 HM 1 8 3/4" 15A501 23
123B 3' - 0" 7' - 0" 1 3/4" SCWD B HM 1 8 3/4" 15A501 25
124 3' - 0" 7' - 0" 1 3/4" SCWD B HM 1 5 3/4" 15A501 20 MIN (Type S) 23
124A 3' - 0" 7' - 0" 1 3/4" SCWD B HM 1 8 3/4" 15A501 SIM 24
125 3' - 0" 7' - 0" 1 3/4" SCWD D GLT 18 HM 1 8 3/4" 15A501 20 MIN (Type S) 23
126 3' - 0" 7' - 0" 1 3/4" SCWD D GLT 18 HM 1 8 3/4" 15A501 20 MIN (Type S) 23
127 3' - 0" 7' - 0" 1 3/4" SCWD D GLT 18 HM 1 5 3/4" 15A501 20 MIN (Type S) 26
128 3' - 0" 7' - 0" 1 3/4" SCWD B HM 6 5 3/4" 4A303 23
200 6' - 0" 7' - 0" 1 3/4" HM B HM 2 5 3/4" 15A501 SIM 90 MIN 12 7
No. Description Date
A2 Addendum 2 2/20/18
EXIST DOOR SCHEDULE
DOORNO.
HDWRGROUP REMARKS
123C 23.1 1
A2
A2
VESTIBULE
1500.10
100
OFFICE
1582
111
OFFICE
1580
112
OFFICE
1578
113
OFFICE
1576
114
TOILET
1574
115
CONF.
1566
117RECEPTION
1564
118
VESTIBULE
1500.08
119
CORRIDOR
1500.06
122
CORRIDOR
1500.07
120
LOBBY
1500.09
101
CONCESSION
1598
102
STORAGE
1590
108
GYM
1525
109
HALL
1568
110A
CORRIDOR
1570
110
OFFICE
1498E
116
DECA
1590A
103
COACHES
1550
126
COACHES
1530
125
CORR.
1600.01
1600.01
CORR.
1500.05
1500.05
STORAGE
1500.11
107
STORAGE
1500.12
106
GYM
1525
109
PASSAGE
1584
109
PASSAGE
1592
105
4"øST(15)
4"øST(30)
4"øST(70)
REROUTE STORMTO NEW WALL
4"ø XST(46)
4"øST(46)4"øST(30)
3"øCWW
4"øSAN(4)
4"øST(75)3"øCWW
3"øCWW
3"øCWW
3"øCWW
4"øSAN(4)
2"øV
4"øSAN(4)
2"øV
1 1/2"øV
4"øST(49)
S2
S1
S3
3/4"øHW(2.5)
3/4"øCW(3)
1/2"øCW(2)1/2"øHW(2)
1/2"øCW(0.5)
1/2"øHW(0.5)2"øV
1 1/2"øV
1/2"øHW(2)
1/2"øCW(2)
6"øST(138)
NEW STORM PIPING TOBE ROUTED IN TRUSS
SPACE FROM EXISTINGROOF DRAIN
NEW STORM DROP IN CHASE
5"ø XST(140)
6"øST(138)
PROVIDE WCO FOR STORM
4"øST(70)
3"CO
2"øCWV
2"øCWV
2"øCWV3"øCWW
EXTEND EXISTING HWC LOOP TO MAKESURE NEW CONCESSIONS AREA ISWITHIN 25' OF CIRCULATED MAIN
DROP IN CHASEBEHIND SINKDISCHARGE
OVERFLOW 12" AFF W/OUTLET NOZZLE
1/2"CW FORICE MAKER
2"HD1
6
5
4
3
2
1
3"FCO
4"ø OST(110)
UP TO 2"VTR
1/2"øHWC
3/4"øHW(2.5)
3/4"øCW(3)
CONNECT TO EXISTINGBRANCHES, SEE DEMO PLANFOR LOCATIONS
DROP IN CORNER,KEEP TIGHT TO WALL
XL
XWC
3/4"øSAN(0)
2"øV
1 1/2"øCW(14.5)
1"øHW(7.5)
PROVIDE WALL CLEANOUT IN DROP
1/2"øCW(0.5)
TO ICE MAKER
3"HD1
1 1/2"øV
2"øV
1 1/2"øCW(14)
1"øHW(7.5)
L1
LT1
4"FCO
4"FD1
2"SH1
WC14"WCO
1/2"øCW(2)1/2"øHW(2)
1 1/2"øCW(6.5)
4"øSAN(6)2"øV
1/2"øCW(2)
1/2"øHW(2)
1/2"øHW(0.5)1/2"øCW(0.5)
2"øV
1 1/2"øV
1 1/2"øCW(10.5)
1 1/2"øCW(8.5)
PROVIDE BALANCING VALVEAND SIGHT FLOW INDICATOR
ON HWC BRANCH
1/2"øHWC
3/4"øHW(3)
3/4"øCW(3)
TF1
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREETLA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
WEB SITE: www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sh
ee
t T
itle
:
Pro
ject L
oca
tio
n:
Pro
ject T
itle
:
2/21/2018 6:14:28 AM
P101R
JMW
17003
2/5/18
1S
T F
LO
OR
AB
OV
E S
LA
B P
LA
NS
VO
LU
ME
3 -
ME
MO
RIA
L H
I GH
SC
HO
OL
OF
FIC
E/ L
OB
BY
EX
PA
NS
ION
2225 K
EIT
H S
T, E
AU
CL
AIR
E, W
I 54701
EA
U C
LA
IRE
AR
EA
SC
HO
OL
DIS
TR
ICT
BIDDOCUMENTS
SCALE:N 1/8" = 1'-0"P101R
1 ABOVE SLAB PLAN
SCALE:N 1/8" = 1'-0"P101R
2 Training and Officials Above Slab Plumbing
AD1
No. Description Date
1 Addendum 1 2.21.2018
1 1/2"ø XCW1 1/2"ø XHW CAP AND REMOVE
EXISITING BRANCHES
1/2"øHW(2)
1/2"øCW(2)
CONNECT ANDREUSE EXISTINGBRANCH PIPING
S3
EXISTINGFIXTURES TOREMAIN
3/4"ø XHW1 1/2"ø XCW
VERIFY PRESENCE OFWATER HAMMER ARRESTOR,INSTALL IF NOT PRESENT
3/4"ø XHWC
3/4"ø XHW
1 1/2"ø XCW
1 1/2"ø XHW
1 1/2"ø XCW
3/4"ø XHWC
PROVIDE SHUTOFFS AT NEWBRANCH CONNECTIONS
4"FCO
S3
1 1/2"øV
2"ø XV
4"øSAN(2)
1 1/2"ø XV
2"øSAN(2)
3"XVTR
CAPPED SANITARY
CAPPEDSANITARY
4"ø XSAN
4"ø XSAN
4"ø XSAN
4"ø XSAN
4"ø XSAN
1/2"CW CONNECTIONTO ICE MACHINE
1 1/2"øCW(14.5)
1"øHW(7.5)
1 1/2"øCW(14.5)
2"ø XCW
PROVIDE WATER HAMMER ARRESTOR
1/2"øCW(0.5)
1"øHW(7.5)1 1/2"øCW(14)
3/4"øHW(4)
1 1/2"øCW(14)
1/2"øHW(0.5)
1/2"øCW(0.5)
1 1/2"øCW(10.5)
1/2"øHW(2)1/2"øCW(2)
1 1/2"øCW(8.5)
1 1/2"øCW(6.5)
1/2"øCW(2)
1/2"øHW(2)
WC1
SH1
L1
LT1
PROVIDE BALANCING BALLVALVE AND SIGHT FLOWINDICATOR ON NEW ANDEXISTING RETURN PIPE
3"ø XHW
1"ø XHWC
TF1
3/4"øCW(3)
3/4"øHW(3)
SHOWER VALVE FORTHERAPY TUB FILLERPROVIDE ELEVATED VACUUMBREAKER AND HOSECONNECTION FOR TUB
4"WCO
2"øV
2"ø XV
2"ø XV
WC1
LT1L1
4"FCO
4"FD1
2"SH1
4"øSAN(6)2"øSAN(2)
4"øSAN(7)
2"øSAN(1)
4"øSAN(4)
4"øSAN(13)
1 1/2"øSAN(1)
4"øSAN(14)
2"øV
2"øV
2"øV
1 1/2"øV
2"øV
3"øSAN(4)
4"øSAN(14)
4"øSAN(18)
1 1/2"øV
3"HD1
2"øV
2"øV
5"ø XSAN
2
1
24"
2
1
TYPE A SHOCK ARRESTORS
WASHING MACHINESUPPLY & DRAIN UNIT
42" A.F.F.
VENTED TRAP
FLOOR
4"OUTLET WITH BARRELL STRAINER
REMOVEABLE LINTSCREEN WITH3/8"PERFORATIONS
STAINLESS STEELFRICTION FIT FRAME
1"HIGH X 3/16" THICK BAR GRATE
6X6 OPERNING IN GRATEFOR WASHERDISCHARGE
1"HIGH X3/16"THICKBAR GRATE
4"STAINLESSSTEEL OUTLETCAST IN
4"STAINLESS STEELBARREL STRAINER WITH
1/4"PERFORATIONS
CAST IN PLACE CONCRETETRENCH BY OTHERS
4"OUTLET WITH HUSKYCOUPLING
SCH-40 PVC P-TRAP
12"MIN18"MIN
1-1/2" TRAP - 3" OPENING
2" TRAP - 4" OPENING
3" TRAP - 6" OPENING
4" TRAP - 6" OPENING
RIM 2" A.F.F. WHEN O.S. IS AT FLOOR
VENT PER D.O.C. 82.31 (9)
ROOFDRAIN WITH POLYDOME
PROVIDE PIPEHANGER ON LATERALWITHIN 18"OF DRAIN
PROVIDE 4"INTERNAL OREXTERNAL WATER DAMON OVERFLOW DRAINS
CLAMPING COLLAR FORROOF MEMBRANE,
ATTACHED BY ROOFINGCONTRACTOR
PROVIDE AND INSTALLUNDERDECK CLAMP
24"X24"SUMP PAN PLATEWELDED TO DECK
BOARD INSTALLATIONAND MEMBRANE ROOF
IF SUMP PLATE/PAN NOTPROVIDED,CLAMP ONUNDERSIDE OF CORRUGATEDDECK
ROOF DRAIN TO SEAT ON TOP OF ROOFINGINSULATION PITCHED AND CUT BY ROOFINGCONTRACTOR
SEE PLANS FORTRAP SIZE
SEE PLANS FORRECEPTOR SIZE (HUBDRAINS HAVE SAMERECEPROT SIZE ASTRAPUNLESS NOTED)
2" AIR GAP
ANGLE CUTINDIRECTWASTETERMINATION
2" MIN
FLOOR LINE: HUB DRAINMUST TERMINATE 1"ABOVEFINISH FLOOR, FLOORDRAIN/SINK RECEPTORSARE FLUSH WITH FLOOR
1/2"CW FOR ICE MAKER
S2
S1
3/4"øCW(3)1/2"øHWC
3/4"øHW(2.5)
1/2"øCW(2)
1/2"øHW(2)
1/2"øCW(0.5)
1/2"øHW(0.5)
3/4"øCW(2.5)
PIPING FOR S1 TO BE RUNDOWN CHASE BEHIND S2 ANDRUN UNDER COUNTER TO S1
PROVIDE SHUTOFFS ATNEW BRANCH
CONNECTIONS
2"HD1
3"FCO
S2
S12"øV
1 1/2"øV
3"øSAN(6)
4"ø XSAN
4"ø XSAN
4"ø XSAN
2"øSAN(3)
2"øSAN(1)
1 1/2"øSAN(2)
2"øV
2"øV
3"øSAN(4)
3"øSAN(6)
4"øSAN(4)
4"FD2
2"øV
2"VTR
4"øSAN(4)
4"ø XSAN
4"ø XSAN
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREETLA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
WEB SITE: www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sh
ee
t T
itle
:
Pro
ject L
oca
tio
n:
Pro
ject T
itle
:
2/21/2018 6:14:29 AM
P500R
JMW
17003
2/5/18
PL
UM
BIN
G IS
O &
DE
TA
ILS
VO
LU
ME
3 -
ME
MO
RIA
L H
I GH
SC
HO
OL
OF
FIC
E/ L
OB
BY
EX
PA
NS
ION
2225 K
EIT
H S
T, E
AU
CL
AIR
E, W
I 54701
EA
U C
LA
IRE
AR
EA
SC
HO
OL
DIS
TR
ICT
BIDDOCUMENTS
SCALE: NO SCALEP500R
1 Laundry Remodel Domestic Water Isometric
SCALE: NO SCALEP500R
2 Laundry Remodel Waste and Vent Isometric
SCALE: NO SCALEP500R
3 Training and Officials Domestic Water Isometric
SCALE: NO SCALEP500R
4 Training and Officials Waste and Vent Isometric
WATER PIPE SIZING CHARTMATERIAL: A = PSI/100FT
TYPE: SYSTEM:
TAG PIPE SIZE
WSFU
GPM
1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3"
TYPE L COPPER 3
FLUSH VALVE COLD WATER
- - 4 6 12.5 75 283 698
2 5 10.5 18.5 29 60 107 169
WATER PIPE SIZING CHARTMATERIAL: A = PSI/100FT
TYPE: SYSTEM:
TAG PIPE SIZE
WSFU
GPM
1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3"
TYPE L COPPER 3
FLUSH TANK HOT/COLD WATER
2 6 14 27.5 52 175 410 752
2 5 10.5 18.5 29 60 107 169
SCALE: NO SCALEP500R
5 AWC-1 LAUNDRY UNIT DETAIL
SCALE: NO SCALEP500R
6 TD-1 LAUNDRY TRENCH DRAIN DETAIL
SCALE: NO SCALEP500R
7 Open Site Drain Detail
SCALE: NO SCALEP500R
8 Roof drain detail
SCALE: NO SCALEP500R
9 Air Gap Detail
SCALE: NO SCALEP500R
10 Concessions Domestic Water Isometric
SCALE: NO SCALEP500R
11 Concessions Waste and Vent Isometric
WATER CALCULATION WORKSHEET
INFORMATION REQUIRED TO CALCULATE WATER SERVICE SIZE FOR
1. TOTAL DEMAND OF BUILDING: WSFU'S: GPM:
2. DIFFERENCE IN ELEVATION FROM MAIN OR EXTERNALPRESSURE TANK TO BUILDING CONTROL VALVE:
3. SIZE OF THE WATER METER (WHEN APPLICABLE):
4. DEVELOPED LENGTH FROM MAIN OR EXTERNAL PRESSURE TANKTO BUILDING CONTROL VALVE:
5. LOW PRESSURE AT MAIN IN STREET OR EXTERNAL PRESSURE TANK:
CALCULATED WATER SERVICE PRESSURE LOSS
6. LOW PRESSURE AT MAIN IN STREET OR EXTERNAL PRESSURE TANK:
7. WATER SERVICE (MAIN TO BLDG CTRL VALVE) DIAMETER:
MATERIAL IS:
PRESSURE LOSS/100FT:
LENGTH OF SERVICE:
PRESSURE LOSS:
SUBTOTAL:
8. DETERMINE PRESSURE GAIN/LOSS DUE TO ELEVATION
9. AVAILABLE PRESSURE BEFORE BUILDING CONTROL/PRESSUREREDUCING VALVE:
CALCULATED PRESSURE AVAILABLE FOR UNIFORM LOSS (VALUE OF "A")
10. AVAILABLE PRESSURE AFTER THE BUILDING PRESSURE REDUCINGVALVE IF APPLICABLE
11. PRESSURE LOSS OF WATER METER IF APPLICABLE
SUBTOTAL:
12. PRESSURE AT CONTROLLING FIXTURE:
13. ELEVATION DIFFERENCE AT CONTROLLING FIXTURE:
SUBTOTAL:
PRESSURE LOSS DUE TO ELEVATION DIFFERENCE:
SUBTOTAL:
14. PRESSURE LOSS DUE TO WATER TREATMENT DEVICES, INSTANTEOUSWATER HEATERS, AND BACKFLOW PREVENTERS THAT SERVE THECONTROLLING FIXTURE:
SOFT WATER HARD WATER
SUBTOTAL:
15. DISTANCE FROM BLDG CONTROL VALVE TO CONTROLLING FIXTURE
WATER DISTRIBUTION PIPING MATERIAL IS:
16. "A VALUE" - PRESSURE AVAILABLE FOR UNIFORM LOSS (PSI/100FT):
DEVELOPED LENGTH FIXTURE IN FEET: DISTANCE * 1.5(FITTINGS)
1
59
3.472
55.528
55.528
52.528
28.188
4.34
32.528
55.528
52.528
28.188
4.34
32.528
28.188 28.188
3 3
900 900
MEMORIAL HS
900 200
8
6"
250
60
60
4"
DUCTILE IRON
0.4
250
3
20SHOWER
10
0
WATER SOFTENER [12]
3
20
10
0
600 600
1
1
No. Description Date
1 Addendum 1 2.21.2018
CORRIDOR
CORR.
CORR. CORR.
VITREOUS CHINA C_URINALS BRANHAM K-4920-R VITREOUS CHINA C_URINALS BRANHAM K-4920-R
VITREOUS CHINA
LAVATORY
GREENWICH
K-2032
VITREOUS CHINA
LAVATORY
GREENWICH
K-2032
VITREOUS CHINA
LAVATORY
GREENWICH
K-2032
VITREOUS CHINA
LAVATORY
GREENWICH
K-2032
M.
DRY SHR.LK.RM. M.
L.R. L.R.
DRY
CORR.
15A
16
16E1605
1700A
1600.01
1619
1617B 1617C1617A 1615A
1617D
1611A 1609A
1615C 1605B
1607
1607B
WOMEN'S P.E.LOCKER RM.
POOL ST.
1,289 SF
633 SF
955 SF
340 SF
165 SF 281 SF249 SF 145 SF
129 SF 129 SF
66 SF 28 SF
128 SF
39 SF
VITREOUS CHINA
LAVATORY
GREENWICH
K-2032
16E
156 SF
CORR. CORR.
6' TACKBD
6' TACKBD
6' TACKBD
EQ. OFF.
STOR.
OFF. OFF.1200.03 12121200.07 1200.091218 1224
311 SF
4
M401
3
M401
4
M400
1
M401
1 1/2"ø XCHWR
1 1/2"ø XCHWS
2"øHHWS
2"øHHWR
DEMO EXISTING1-1/4" CHWS/ CHWRFROM THIS POINT
DEMO EXISTING1-1/4" CHWS/ CHWR
FROM THIS POINT
DEMO EXISTING1-1/2" HWS/ HWRFROM THIS POINT
DEMO EXISTING1-1/2" HWS/ HWRFROM THIS POINT
DEMO EXISTING 3/4"HWS/ HWR FROM
THIS POINT
DEMO EXISTINGCONVECTOR ANDRELATED PIPING
DEMO EXISTINGCONVECTOR ANDRELATED PIPING
DEMO EXISTINGCONVECTOR ANDRELATED PIPING
DEMO EXISTING CABHEATER, RELATED
DUCTWORK, PIPINGAND EXTERIOR LOUVER
DEMO EXISTING 3/4"CONDENSATECOMPLETE
DEMO EXISTING 1-1/4"CHWS/ CHWR COMPLETE
DEMO EXISTING 1"HWS/ HWR COMPLETE
24"x14"
18"x10"12"x6"
16"x10"
12"x
10"
12"x
12"DEMO EXISTING EF-34
AND ALL RELATEDDUCTWORK. CURB CAP
TO BE BY OTHERS
DEMO ALL EXISINGEXHAUST DUCT
DEMO ALL EXISINGEXHAUST DUCT
DEMO EXISTING AHU-18AND ALL RELATEDPIPING AND DUCTWORK.WALL PATCHING BYOTHERS.
DEMO EXISTING AHU-21AND ALL RELATEDPIPING AND DUCTWORK.WALL PATCHING BYOTHERS.
DEMO EXISTING AHU-19AND ALL RELATED
PIPING AND DUCTWORK.WALL OPENINGS TO BE
RE-USED
DEMO EXISTING AHU-20AND ALL RELATED
PIPING AND DUCTWORK.WALL OPENINGS TO BE
RE-USED
ALL HWS/ HWRPIPING IN THIS AREA
TO BE REMOVED
ALL HWS/ HWRPIPING IN THIS AREA
TO BE REMOVED
ALL HWS/ HWR ANDCHWS/ CHWR PIPINGIN THIS AREA TO BEREMOVED
THE STRUCTURE IN THISAREA IS BEING REVISED,
PROVIDE TEMPORARYSUPPORT FOR PIPING
DEMO EXISTINGCONVECTOR
REMOVE UNITVENTILATOR , RELATEDDUCTWORK AND PIPING
DEMO UNIT HEATER
DEMO UNIT HEATERS
DEMO EXISTINGCONVECTOR
REMOVE EXHAUST FANDUCTWORK AND LOUVER
DEMO EXHAUST FAN,RELATED DUCTWORK
AND GRILLES
DEMO EXHAUSTDUCTWORK AND
RELATED GRILLES
DEMO CONVECTORSAND RELATED PIPING
DEMO 1" CHWS/CHWRAND 2" HWS/HWR
PIPING BACK TO MAIN
EXISTING CONVECTORTO REMAIN
EXISTING 3/4" HWS/ HWRPIPING TO REMAIN
DEMO EXISTING UNIT VENTILATOR,DUCTWORK, PIPING, TRANSFERS,LOUVER, AND DRYER VENTS INEXISTING LAUNDRY ROOM
6
5
4
3
2
1
AIR HANDLER TOREMAIN IN PLACE UNTIL
NEW AIR HANDLERSSERVING GYM ARE
OPERATIONAL
ROOF HOOD TO REMAINAFTER DEMO FOR SPACE
PRESSURE RELIEF
AIR HANDLER TOREMAIN IN PLACE UNTIL
NEW AIR HANDLERSSERVING GYM ARE
OPERATIONAL
ROOF HOOD TO REMAINAFTER DEMO FOR SPACE
PRESSURE RELIEF
REMOVE RETURN DUCT FROM AIRHANDLER FOR INSTALATION OF NEW
HOT WATER PIPING SERVING THENEW MECHANICAL MEZZANINE
EXISTING CABINET UNITHEATER TO REMAIN
REMOVE DYER VENTS
DECA StoreFed by VAV79 from AHU-11existing sheet HV2.37, HV3.38, HV2.58
EXISTING CONVECTORSTO REMAIN
REMOVE THERMOSTAT
TVAV109
VAV109
REMOVE AND REPLACEGRILLES AND DIFFUSERS
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREETLA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
WEB SITE: www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sh
ee
t T
itle
:
Pro
ject L
oca
tio
n:
Pro
ject T
itle
:
2/21/2018 6:14:23 AM
M010R
TCP
17003
2/5/18
HV
AC
DE
MO
PL
AN
VO
LU
ME
3 -
ME
MO
RIA
L H
I GH
SC
HO
OL
OF
FIC
E/ L
OB
BY
EX
PA
NS
ION
2225 K
EIT
H S
T, E
AU
CL
AIR
E, W
I 54701
EA
U C
LA
IRE
AR
EA
SC
HO
OL
DIS
TR
ICT
BIDDOCUMENTS
SCALE:N 1/8" = 1'-0"M010R
1 First Floor HVAC Demo Plan
SCALE:N 1/8" = 1'-0"M010R
2 First Floor HVAC Demo Plan Training Room
HVAC Sheet IndexNo Sheet Name
M010R HVAC DEMO PLAN
M100R FIRST FLOOR HVAC VENTILATION PLAN
M101 FIRST FLOOR PIPING PLANS
M130 HVAC ROOF PLAN
M400 HVAC MECHANICAL ROOM PLAN
M401 MECHANICAL MEZZANINE SECTIONS
M500 HVAC DETAILS
M501 HVAC DETAILS
M600 HVAC SCHEDULES
DEMO EXISTING8"x8"X2" TEES
DEMO EXISTING 2"CHWS/ CHWR TO
THIS POINTDEMO 4" HWS/HWRBACK TO 6" MAIN
DEMO 6"x6"x5" TEES
No. Description Date
1 Addendum 1 2.21.2018
SCALE:N 1/8" = 1'-0"M010R
3 First Floor HVAC Demo Plan Classroom Area E
1
RE
F.
FD
FD
FD
F/S
F/SF/S
F/S F/S
F/S
FD
F/S
4
M401
3
M401
LOBBY1500.09
STORAGE1590
GYM-11525-1
GYM-21525-2
CONCESSION1598
MAINTENANCE1620
STAIR1600.05
STORAGE1500.12
VESTIBULE1500.10
OFFICE1582
OFFICE1580
OFFICE1578
OFFICE1576
CORRIDOR1570
CONF.1566
CORRIDOR1570
RECEPTION1564
CORRIDOR1500.07
VESTIBULE1500.08
CORRIDOR1500.06
COACHES1550
COACHES1530
CORRIDOR1500.06
4
M400
1
M401
VAV-1
VAV-2 VAV-3 VAV-4 VAV-5VAV-7
VAV-8VAV-6
30"øSA
26"x 10"SD1
1650
26"x 10"SD1
165026"x 10"
SD1
170026"x 10"
SD1
1650
26"x 10"SD1
170026"x 10"
SD1
1650
30"øSA
42"x 10"SD1
150042"x 10"
SD1
150042"x 10"
SD1
1500
42"x 10"SD1
150042"x 10"
SD1
150042"x 10"
SD1
150042"x 10"SD1
1500
42"x 10"SD1
1500
CUH-1
L1
12000100"x 45"
L1
10000100"x 45"
SD6
27513"x 4"
SD6
27513"x 4"
SD6
27513"x 4"
SD6
27513"x 4"
SD2
756"
SD6
27513"x 4"
SD6
27513"x 4"
SD6
27513"x 4"
SD6
33010"
SD6
33010"
HALL1568
SD6
33010"
16"øSA
10"ø
SA
10"ø
SA
10"ø
SA
12"ø
SA
10"øSA10"øSA
10"ø
SA
10"øSA8"øSA
SD3
2008"
10"ø
SA
10"ø
SA1
0"ø
SA
10"ø
SA
24"x 12"RG3
275
10"ø
RA
24"x 12"RG3
275
24"x 12"RG3
275
24"x 12"RG3
27510"ø
RA
10"ø
RA
10"ø
RA
24"x 12"RG3
275
24"x 24"RG3
825
24"x 12"RG3
130
24"x 24"RG2
500
14"ø
RA
10"ø
RA
22"x14"RA26"x14"RA32"x14"RA
18"x
12"S
A
SD4
27510"
SD4
27510"
10"ø
SA
10"øSA
26"x
13"R
A
8"x8"OA
18"x18"SA
HVLS-2
CEF-2
6"øEA
TOILET1574
34"øSA
30"ø
SA
24"ø
SA
96"x 30"RG1
8550
34"x 6"SD7
855
34"x 6"SD7
855
34"x 6"SD7
855
34"x 6"SD7
855
34"x 6"SD7
855
34"x 6"SD7
855
34"x 6"SD7
855
34"x 6"SD7
855
34"x 6"SD7
855
34"x 6"SD7
855
TAPDISCHARGE45°DOWN
TAPDISCHARGE45°DOWN
TAPDISCHARGE45°DOWN
TAPDISCHARGE45°DOWN
TAPDISCHARGE45°DOWN
40"x 72"RG1
8350
40"x 84"RG1
10350
36"ø
SA
36"øSA
NEW RELIEF LOUVER WITHWEIGHTED BACKDRAFT
DAMPER MODIFY EXISTING100"X16" OPENING FOR
NEW LOUVER
NEW RELIEF LOUVER WITHWEIGHTED BACKDRAFT
DAMPER MODIFY EXISTING100"X16" OPENING FOR
NEW LOUVER
20"ø
SA
HVLS-1
AC-1
EXPOSED DUCT TO BECLEANED AND DEGREASED
FOR PAINTING PROIR TOBEING INSTALLED
EXPOSED DUCT TO BECLEANED AND DEGREASED
FOR PAINTING PROIR TOBEING INSTALLED
EXPOSED DUCT TO BECLEANED AND DEGREASEDFOR PAINTING PROIR TOBEING INSTALLED
6
5
4
3
2
1
TFT-4
CO2
CO2
NOTE:CO2 MOUNTED IN RETURN
TVAV-1T VAV-2
T VAV-3
T VAV-4
TVAV-6
T VAV-5
T VAV-7
TVAV-8
NOTE:MOUNT GRILLE IN HIGHWALLFOR RETURN/ RELIEF
CO2
NOTE:PROVIDE TAMPER PROOFPLATE SENSOR
S
S
T AC-1
SENSOR TO MONITOR SPACETEMPERATURE
S NOTE:PROVIDE TAMPER PROOFPLATE SENSOR
S
NOTE:PROVIDE TAMPER PROOFPLATE SENSOR
CO2
NOTE:CO2 MOUNTED IN RETURN
TCUH-1
OFFICE1498E
24"x 12"RG3
550
FC-1
TFC-1
32"x14"RA
18"x18"SA
FIRE DAMPER ATFLOOR PENETRATION
24"x 24"RG2
990
8"ø
RA
8X8 UP TOGOOSENECK INTAKE
WITH MOD ABOVERETURN DUCT
26"x18"RA
18"x18"SA32"x14"RA
XCUH
XCUH
SD6
25010"
SD6
25010"
XCUH
6"x 6"EG1
100
L2
32524"x 14"
16"x 16"EG2
300 IEF-1
10"øEA10"øEA
12"x12"EA
L3
32524"x 14"
24"x 12"RG3
0
24"x 12"RG3
0
SD3
2258"
SD3
2258" SD2
1006"
SD2
756"
SD3
2258"
10"øSA6"øSA
12"øSA
6"øSA
FC-3
TFC-3
FC-2TFC-2
26"x12"RA
12"x12"OA6"øEA
MOD
10"øOA
8"øOA
10"øRA
26"x13"RA
MOD
VAV109
EXISTING 10"øVAV INCREASEMAXIMUM AIRLFOW FROM 600
TO 750CFM. BALANCEGRILLES AND VAV
T VAV109
RELOCATE THERMOSTAT TO NEW WALLXSD
2508"
XSD
506"
XSD
1606"
XSD
1206"
12
"x10
" X
SA
10
"ø X
SA
8"ø
XS
A1
2"x
8"
XS
A6
"x6
" X
SA
EXISTING VAV TO REMAIN
SD4
25010"
SD4
25010"
SD4
25010"
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREETLA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
WEB SITE: www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sh
ee
t T
itle
:
Pro
ject L
oca
tio
n:
Pro
ject T
itle
:
2/21/2018 6:14:26 AM
M100R
TCP
17003
2/5/18
FIR
ST
FL
OO
R H
VA
C V
EN
TIL
AT
ION
PL
AN
VO
LU
ME
3 -
ME
MO
RIA
L H
I GH
SC
HO
OL
OF
FIC
E/ L
OB
BY
EX
PA
NS
ION
2225 K
EIT
H S
T, E
AU
CL
AIR
E, W
I 54701
EA
U C
LA
IRE
AR
EA
SC
HO
OL
DIS
TR
ICT
BIDDOCUMENTS
SCALE:N 1/8" = 1'-0"M100R
1 Gymnasium and Offices HVAC Plan
SCALE:N 1/8" = 1'-0"M100R
2 Training Room Ventilation Plan
SCALE:N 1/8" = 1'-0"M100R
3 Classrooom Area E Remodeled HVAC Plan
1
No. Description Date
1 Addendum 1 2.21.2018