18022 Prentice School District Bid Pkg 3 00 90 00 -1
DOCUMENT 00 90 00
ADDENDUM
ADDENDUM NO. [2] Date: November 2, 2018
RE: PRENTICE SCHOOL DISTRICT ADDITION AND REMODELING BID PKG 3 1025 TOWN ST PRENTICE, WI 54556 HSR PROJECT NO. 18022
FROM: HSR Associates, Inc
100 Milwaukee Street
La Crosse, WI 54603
(608) 784-1830
To: Prospective Bidders
This addendum forms a part of the Contract Documents and modifies the original Bidding Documents
dated October 2018. Acknowledge receipt of this Addendum in the space provided on the bid form.
Failure to do so may subject the Bidder to disqualification.
This Addendum consists of [2] pages, [1] specification section, and [17] 30 x 42 drawings.
CHANGES TO BIDDING REQUIREMENTS AND CONDITIONS OF THE CONTRACT:
1. Section 00 11 33 ADVERTISEMENT FOR BIDS
a. Bid date shall change from November 6 to November 13, 2018.
GENERAL REQUIREMENTS:
2. Section 01 21 00 ALLOWANCES
a. 1.07, A: Change allowance amount for brick from $1400 to $2000 per thousand.
CHANGES TO SPECIFICATIONS:
3. Section 04 72 00 CAST STONE MASONRY
a. Section attached hereto as part of Contract Documents.
CHANGES TO DRAWINGS
4. Sheet A112R FLOOR PLAN-UNIT B 30 x 42 attached hereto.
a. Revisions clouded on Drawing.
b. 6” concrete foundation wall w/ 4” brick added at NW corner of Kitchen.
5. Sheet A200R EXTERIOR ELEVATIONS 30 x 42 attached hereto
a. Revisions clouded on Drawing.
b. Cast reveals added.
c. Cast stone corner details added.
6. Sheet A201R EXTERIOR ELEVATIONS 30 x 42 attached hereto
a. Revisions clouded on Drawing
18022 Prentice School District Bid Pkg 3 00 90 00 -2
7. Sheet A310R WALL SECTIONS 30 x 42 attached hereto
a. Revisions clouded on Drawing
b. Section 11 added showing 6 inch foundation brick ledge.
8. Sheet A311R WALL SECTIONS 30 x 42 attached hereto
a. Revisions clouded on Drawing
9. Sheet A313R WALL SECTIONS 30 x 42 attached hereto
a. Revisions clouded on Drawing
10. Sheet A314R WALL SECTIONS 30 x 42 attached hereto
a. Revisions clouded on Drawing
11. Sheet A315R WALL SECTIONS 30 x 42 attached hereto
a. Revisions clouded on Drawing
12. Sheet A500 DETAILS 30 x 42 attached hereto
a. Drawing attached as part of Contract Documents
13. Sheet A501 DETAILS 30 x 42 attached hereto
a. Drawing attached as part of Contract Documents
14. Sheet A510 DOOR-WINDOW DETAILS 30 x 42 attached hereto
a. Drawing attached as part of Contract Documents
15. Sheet A511 DOOR-WINDOW DETAILS 30 x 42 attached hereto
a. Drawing attached as part of Contract Documents
16. Sheet A512 DOOR-WINDOW DETAILS 30 x 42 attached hereto
a. Drawing attached as part of Contract Documents
17. Sheet A513 DOOR-WINDOW DETAILS 30 x 42 attached hereto
a. Drawing attached as part of Contract Documents
18. Sheet A514 MISC DETAILS 30 x 42 attached hereto
a. Drawing attached as part of Contract Documents
19. Sheet S202R FRAMING PLANS-UNIT A&E 30 x 42 attached hereto
a. Revisions clouded on Drawing
20. Sheet S810R FRAMING DETAILS 30 x 42 attached hereto
a. Revisions clouded on Drawing
END OF DOCUMENT 00 90 00
18022 Prentice Bid Pkg 3 04 72 00 - 1 CAST STONE MASONRY
SECTION 04 72 00
CAST STONE MASONRY
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Architectural cast stone, dry cast.
B. Units required are:
1. Exterior wall units, including sills, water tables, and wall panels.
1.02 RELATED REQUIREMENTS
A. Section 04 05 11 - Mortar and Masonry Grout: Mortar for setting cast stone.
B. Section 04 20 00 - Unit Masonry: Installation of cast stone in conjunction with masonry.
C. Section 07 92 00 - Joint Sealants: Sealing joints indicated to be left open for sealant.
1.03 REFERENCE STANDARDS
A. ACI 318 - Building Code Requirements for Structural Concrete and Commentary; 2014 (Errata 2016).
B. ASTM A123/A123M - Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products; 2015.
C. ASTM A185/A185M - Standard Specification for Steel Welded Wire Reinforcement, Plain, for Concrete; 2007.
D. ASTM A615/A615M - Standard Specification for Deformed and Plain Carbon-Steel Bars for Concrete Reinforcement; 2016.
E. ASTM A767/A767M - Standard Specification for Zinc-Coated (Galvanized) Steel Bars for Concrete Reinforcement; 2009 (Reapproved 2015).
F. ASTM A884/A884M - Standard Specification for Epoxy-Coated Steel Wire and Welded Wire Reinforcement; 2014.
G. ASTM A1064/A1064M - Standard Specification for Carbon-Steel Wire and Welded Wire Reinforcement, Plain and Deformed, for Concrete; 2015.
H. ASTM C33/C33M - Standard Specification for Concrete Aggregates; 2016.
I. ASTM C150/C150M - Standard Specification for Portland Cement; 2016.
J. ASTM C 173 - Standard Test Method for Air Content of Freshly Mixed Concrete by the Volume Method.
K. ASTM C 231 - Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method.
L. ASTM C 260 - Standard Specification for Air-Entrained Admixtures for Concrete.
M. ASTM C270 - Standard Specification for Mortar for Unit Masonry; 2014a.
N. ASTM C494/C494M - Standard Specification for Chemical Admixtures for Concrete; 2016.
O. ASTM C 618 – Specification for Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use as a Mineral Admixture in Concrete.
P. ASTM C642 - Standard Test Method for Density, Absorption, and Voids in Hardened Concrete; 2013.
Q. ASTM C 666 – Standard Test Method for Resistance of Concrete to Rapid Freezing and Thawing.
R. ASTM C979/C979M - Standard Specification for Pigments for Integrally Colored Concrete; 2016.
S. ASTM C 989 – Standard Specification for Ground Granulated Blast-Furnace Slag for Use in Concrete.
T. ASTM C 1194 - Standard Test Method for Compressive Strength of Architectural Cast Stone.
U. ASTM C 1195 - Standard Test Method for Absorption of Architectural Cast Stone
V. ASTM C1364 - Standard Specification for Architectural Cast Stone; 2017.
W. ASTM D 2244 – Standard Test Method for Calculation of Color Differences from Instrumentally Measured Color Coordinates.
18022 Prentice Bid Pkg 3 04 72 00 - 2 CAST STONE MASONRY
1.04 DEFINITIONS
A. Cast Stone - a refined architectural concrete building unit manufactured to simulate natural cut stone, used in unit masonry applications.
1. Dry Cast Concrete Products – manufactured from zero slump concrete.
a. Vibrant Dry Tamp (VDT) casting method: Vibratory ramming of earth moist, zero- slump concrete against a rigid mold until it is densely compacted.
b. Machine casting method: manufactured from earth moist, zero-slump concrete compacted by machinery using vibration and pressure against a mold until it becomes densely consolidated
2. Wet Cast Concrete Products – manufactured from measurable slump concrete.
a. Wet casting method: manufactured from measurable slump concrete and vibrated into a mold until it becomes densely consolidated.
1.05 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.
B. Product Data: Test results of cast stone components made previously by the manufacturer.
C. Shop Drawings: Include key plans, elevations, floor plans when appropriate, dimensions, layouts, profiles, cross sections, reinforcement, exposed faces, arrangement of joints, anchoring methods, anchors, and piece numbers.
D. Test results: Submit manufacturers test results of Cast Stone previously made by the manufacturer in the last 90 days, for the following.
1. Compressive Strength
2. Absorption
3. Air Content (wet cast only)
E. Verification Samples: (2) pieces of actual cast stone components not less than 12 inches square, illustrating range of color and texture to be anticipated in components furnished for the project.
F. Source Quality Control Test Reports.
G. Manufacturer's Qualification Data: Documentation showing compliance with specified requirements.
1.06 QUALITY ASSURANCE
A. Manufacturer Qualifications:
1. A firm with a minimum of 10 years experience producing cast stone of types required for project.
2. Current producer member of the Cast Stone Institute in good standing.
3. Manufacturer's production facility currently holds a Plant Certification from the Cast Stone Institute.
4. Adequate plant capacity to furnish quality, sizes, and quantity of cast stone required without delaying progress of the work.
5. All products must contain Portland cement.
B. Mock-Up: Provide full size cast stone components for installation in mock-up of exterior wall.
1. Approved mock-up will become standard for appearance and workmanship.
1.07 DELIVERY, STORAGE, AND HANDLING
A. Deliver cast stone components secured to shipping pallets and protected from damage and discoloration. Protect corners from damage.
B. Number each piece individually to match shop drawings and schedule.
C. Store cast stone components and installation materials in accordance with manufacturer's instructions.
D. Store cast stone components on pallets with nonstaining, waterproof covers. Ventilate under covers to prevent condensation. Prevent contact with dirt.
E. Protect cast stone components during handling and installation to prevent chipping, cracking, or other damage.
F. Store mortar materials where contamination can be avoided.
G. Schedule and coordinate production and delivery of cast stone components with unit masonry work to optimize on-site inventory and to avoid delaying the work.
18022 Prentice Bid Pkg 3 04 72 00 - 3 CAST STONE MASONRY
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. Architectural Cast Stone:
1. Any current producer member of the Cast Stone Institute.
2. Edwards Cast Stone: www.edcstone.com.
3. American Artstone: www.american-artstone.com.
4. MidCon Products: www.midconproducts.com
5. Custom Cast Stone: www.customcaststone.com
2.02 ARCHITECTURAL CAST STONE
A. Cast Stone: Architectural concrete product manufactured to simulate appearance of natural stone, complying with ASTM C1364.
1. Compressive Strength: As specified in ASTM C 1194 and C 1364; 6500 psi minimum for products at 28 days.
2. Water absorption: ASTM C 1195: 6% maximum by the cold water method, or 10% maximum by the boiling method for products at 28 days.
3. Air Content – ASTM C173 or C 231, for wet cast product shall be 4-8% for units exposed to freeze-thaw environments. Air entrainment is not required for VDT products.
4. Freeze-Thaw Resistance: Demonstrated by laboratory testing in accordance with ASTM C 1364. The CPWL shall be less than 5% after 300 cycles of freezing and thawing.
5. Linear Shrinkage – ASTM C 426: Shrinkage shall not exceed 0.065%.
6. Surface Texture: Fine grained texture, with no bugholes, air voids, or other surface blemishes visible from distance of 20 feet.
7. Color: Selected by Architect from manufacturer's full range.
B. Shapes: Provide shapes indicated on drawings.
1. Variation from Any Dimension, Including Bow, Camber, and Twist: Maximum of plus/minus 1/8 inch or length divided by 360, whichever is greater, but not more than 1/4 inch.
2. Unless otherwise indicated on drawings, provide:
a. Wash or slope of 1:12 on exterior horizontal surfaces.
b. Drips on projecting components, wherever possible.
c. Raised fillets at back of sills and at ends to be built in.
C. Reinforcement: Provide reinforcement as required to withstand handling and structural stresses; comply with ACI 318.
1. Pieces More than 12 inches Wide: Provide full length two-way reinforcement of cross-sectional area not less than 0.25 percent of unit cross-sectional area.
D. Reinforcement shall be noncorrosive where faces exposed to weather are covered with less than 1.5 in. of concrete material. All reinforcement shall have minimum coverage of twice the diameter of the bars.
E. Panels, soffits and similar stones greater than 24 in. (600 mm) in one direction shall be reinforced in that direction. Units less than 24 in. (600 mm) in both their length and width dimension shall be non-reinforced unless otherwise specified.
F. Welded wire fabric reinforcing shall not be used in dry cast products.
2.03 MATERIALS
A. Portland Cement: ASTM C150/C150M.
1. For Units: Type I or II, white or grey.
2. For Mortar: Type I or II, except Type III may be used in cold weather.
B. Coarse Aggregate: ASTM C33/C33M, except for gradation; granite, quartz, or limestone.
C. Fine Aggregate: ASTM C33/C33M, except for gradation; natural or manufactured sands.
D. Pigments: ASTM C979, inorganic iron oxides; do not use carbon black.
E. Admixtures:
1. ASTM C 260 for air entraining admixtures.
2. ASTM C 494/C 494M Types A-G for water reducing, retarding, accelerating and high range admixtures.
3. Other admixtures: integral water repellents and other chemicals, for which no ASTM Standard exists, shall be previously established as suitable for use in concrete by proven field performance or through laboratory testing.
18022 Prentice Bid Pkg 3 04 72 00 - 4 CAST STONE MASONRY
4. ASTM C 618 mineral admixtures of dark and variable colors shall not be used in surfaces intended to be exposed to view.
5. ASTM C 989 granulated blast furnace slag may be used to improve physical properties. Tests are required to verify these features.
F. Water: Potable.
G. Reinforcing:
1. ASTM A 615/A 615M. Grade 40 or 60 steel galvanized or epoxy coated when cover is less than 1.5 in.
2. Welded Wire Fabric: ASTM A 185/A where applicable for wet cast units.
3. All anchors, dowels and other anchoring devices and shims shall be standard building stone anchors commercially available in a non-corrosive material such as zinc plated, galvanized steel, brass, or stainless steel Type 302 or 304.
H. Reinforcing Bars: ASTM A615/A615M deformed bars, galvanized.
1. Galvanized in accordance with ASTM A767/A767M, Class I.
I. Steel Welded Wire Reinforcement: ASTM A1064/A1064M, galvanized or ASTM A884/A884M, epoxy coated.
J. Embedded Anchors, Dowels, and Inserts: Type 304 stainless steel, of type and size as required for conditions.
K. Shelf Angles and Similar Structural Items: Hot-dip galvanized steel per ASTM A123/A123M, of shapes and sizes as required for conditions.
L. Prefab corners as recommended by supplier.
M. Mortar: Portland cement-lime; do not use masonry cement.
N. Sealant: As specified in Section 07 92 00.
O. Flashings: Type as specified in Section 04 20 00.
P. Cleaner: Approved for intended use by cast stone manufacturer and by cleaner manufacturer for use on cast stone and adjacent masonry materials.
2.04 COLOR AND FINISH
A. Match approved sample.
B. All surfaces intended to be exposed to view shall have a fine-grained texture similar to natural stone, with no air voids in excess of 1/32 in. (0.8 mm) and the density of such voids shall be less than 3 occurrences per any 1 in.2 (25 mm2) and not obvious under direct daylight illumination at a 5 ft (1.5m) distance.
C. All exposed edges to be hand tooled to ensure a consistent quality edge.
D. Units shall exhibit a texture equal to the approved sample when viewed under direct daylight illumination at a 10 ft (3 m) distance.
1. ASTM D 2244 permissible variation in color between units of comparable age subjected to similar weathering exposure.
a. Total color difference - not greater than 6 units.
b. Total hue difference - not greater than 2 units.
E. All Cast Stone shall be hand sanded and acid washed with a 10% muriatic acid solution.
F. The occurrence of crazing or efflorescence shall not constitute a cause for rejection.
2.05 SOURCE QUALITY CONTROL
A. Production Testing:
1. Test compressive strength and absorption of specimens selected at random from plant production.
2. Test in accordance with ASTM C642 ASTM C 1194 and C 1195.
3. Samples shall be taken and tested from every 500 cubic feet of product produced.
4. New and existing mix designs shall be tested for strength, absorption and freeze thaw compliance prior to producing units.
18022 Prentice Bid Pkg 3 04 72 00 - 5 CAST STONE MASONRY
B. Job Site Testing: One (1) sample from production units shall be selected at random from the field for each 500 cubic feet delivered to the job site.
1. Three (3) field cut cube specimens from each of these samples shall have an average minimum compressive strength of not less than 85% with no single specimen testing less than 75% of design strength as allowed by ACI 318.
2. Three (3) field cut cube specimens from each of these samples shall have an average maximum cold-water absorption of 6%.
3. Field specimens shall be tested in accordance with ASTM C 1194 and C 1195.
4. Submit reports of tests by independent testing agency, showing compliance with requirements.
PART 3 EXECUTION
3.01 EXAMINATION
A. Examine construction to receive cast stone components. Notify Architect if construction is not acceptable.
B. Do not begin installation until unacceptable conditions have been corrected.
3.02 INSTALLATION
A. Install cast stone components in conjunction with masonry, complying with requirements of Section 04 20 00.
B. Mechanically anchor cast stone units indicated; set remainder in mortar.
C. Setting:
1. Drench cast stone components with clear, running water immediately before installation.
2. Set units in a full bed of mortar unless otherwise indicated.
3. Fill vertical joints with mortar.
4. Fill dowel holes and anchor slots completely with mortar or non-shrink grout.
D. Joints: Make all joints 3/8 inch, except as otherwise detailed.
1. Rake mortar joints 3/4 inch for pointing.
2. Remove excess mortar from face of stone before pointing joints.
3. Point joints with mortar in layers 3/8 inch thick and tool to a slight concave profile.
4. Leave the following joints open for sealant:
a. Head joints in top courses, including copings, parapets, cornices, sills, and steps.
b. Joints in projecting units.
c. Joints between rigidly anchored units, including soffits, panels, and column covers.
d. Joints below lugged sills and stair treads.
e. Joints below ledge and relieving angles.
f. Joints labeled "expansion joint".
E. Sealant Joints: Install sealants as specified in Section 07 92 00.
F. Installation Tolerances:
1. Variation from Plumb: Not more than 1/8 inch in 10 feet or 1/4 inch in 20 feet or more.
2. Variation from Level: Not more than 1/8 inch in 10 feet or 1/4 inch in 20 feet, or 3/8 inch maximum.
3. Variation in Joint Width: Not more than 1/8 inch in 36 inches or 1/4 of nominal joint width, whichever is less.
4. Variation in Plane Between Adjacent Surfaces (Lipping): Not more than 1/16 inch difference between planes of adjacent units or adjacent surfaces indicated to be flush with units.
G. Repairs: Repair chips and other surface damage noticeable when viewed in direct daylight at 20 feet.
1. Repair with matching touchup material provided by the manufacturer and in accordance with manufacturer's instructions.
2. Repair methods and results subject to Architect 's approval.
3.03 TOLERANCES
A. Cross section dimensions shall not deviate by more than ±1/8 in. from approved dimensions.
B. Length of units shall not deviate by more than length/ 360 or ±1/8 in., whichever is greater, not to exceed ±1/4 in. (6 mm).
1. Maximum length of any unit shall not exceed 12 times the average thickness of such unit unless otherwise agreed by the manufacturer
18022 Prentice Bid Pkg 3 04 72 00 - 6 CAST STONE MASONRY
C. Warp, bow or twist of units shall not exceed length/ 360 or ±1/8 in. (3 mm), whichever is greater.
D. Location of dowel holes, anchor slots, flashing grooves, false joints and similar features; on formed sides of unit, 1/8 in. (3 mm), on unformed sides of unit, 3/8 in. (9 mm) maximum deviation.
3.04 CLEANING
A. Clean completed exposed cast stone after mortar is thoroughly set and cured.
1. Wet surfaces with water before applying cleaner.
2. Apply cleaner to cast stone in accordance with manufacturer's instructions.
3. Remove cleaner promptly by rinsing thoroughly with clear water.
4. Do not use acidic cleaners.
END OF SECTION
D W DW REF.
REF.DN
GENERAL NOTES:
A
A
SYMBOL INDICATES WALL TYPE - SEESHEET A601 FOR WALL TYPE DETAILS.
SYMBOL INDICATES WINDOW TYPE. SEE SHEET A602 FORWINDOW FRAME ELEVATIONS.
SEE ID SHEETS FOR FLOOR AND WALL FINISH LAYOUTS.
VERIFY EXACT SIZE AND LOCATION OF ALL MECHANICAL / PLUMB AND ELEC.OPENINGS - GENERAL CONTRACTOR SHALL BE RESPONSIBLEFOR FINISH AT ALL VISIBLE AREAS. ALL OPENING SHALL BE SEALED AFTER UTILITY INSTALLATION.
LOOSE FURNISHINGS EXCEPT AS NOTED SHALL BE PROVIDED AND INSTALLED BY THE OWNER.
PAINT ALL EXPOSED STEEL LINTELS.
INSTALL BULLNOSE CMU AT ALL OUTSIDE CORNERS W/O TILE AND AT DOOR JAMBS AS DETAILED. NO BULLNOSE AT WINDOW JAMBS.
SEE STRUCTURAL FOR SLAB CONTROL JOINTS.
SEE A510 FOR WALL CONTROL JOINT DETAILS. SEE PLANS AND ELEVATIONS FOR CJ LOCATIONS. CJ = CONTROL JOINTS
A
B
C
D
E
F
G
H
J
K
EXTEND ALL WALLS TO DECK UNLESS NOTED OTHERWISE. SEE A601 FOR TOP OF WALL DETAILS.
UNLESS NOTED OTHERWISE RESTROOM FLOORS SHALL BE SLOPED A MIN. 1/16" : 12" TO FLOOR DRAINS - TO "CENTER", IF NO FLOOR DRAINS.
L
M
SEE A512 FOR TYPICAL HEAD FLASHING AND THROUGH-WALL FLASHING ISOMETRIC DETAILS.
SYMBOL INDICATES CONSTRUCTION NOTE THIS SHEET
REFER TO CODE PLANS FOR FIRE RATING LOCATIONS AND ACCESSIBILITY ROUTES.
LEGEND:
1 HOUR WALL
GEN. CONTRACTOR TO PROVIDE CONC. EQUIP. PADS/CURBS AS REQUIRED FOR MECH/ELECTRICAL EQUIP. - VERIFY SIZE/PROFILE/LOCATION WITH MECH/ELECTRICAL.
2 HOUR WALL
EXISTING STEEL COLUMNCOL
PLAN DIMENSIONS ARE FROM FACE OF WALL TO FACE OF WALL.N
P ALL DOOR FRAMES TO BE 4" FROM CORNERS UNLESS NOTED OTHERWISE.
ELECTRIC WATER COOLEREWC
FIRE EXTINGUISHER- BRACKET MOUNTEDFE
FIRE EXTINGUISHER CABINETFEC
MB- n'
TACK BOARD- 48" HIGH x 48" WIDETB
MARKER BOARD- 48" HIGH x LENGTH INDICATED ON PLAN
SLOTTED WALL BOARD- 24" HIGH x LENGTH INDICATED ON PLANSWB
TS- n' TACK STRIPS- MOUNT (1) AT 44" AFF AND (1) AT 84" AFF x LENGTH INDICATED ON PLAN
SMART BOARDSB
4
A310R
1
A310R
KITCHEN
240
DISTANCE
LEARNING
246
FOOD
STG
JAN. CLOS.
230
GIRL'S T.R.
231
BOY'S T.R.
229
HALL
244
SEG A
SEG B
SE
G A
SEG B
SE
G D
SEG B
SEG C
SEG B
A400
6
CORRIDOR
146ART
237
SEATING
232
SCHOOL
STORE
233
STG
234ART STG
235
KILN
236
CAFETERIA
239
CIRCULATION
238CORRIDOR
228
ELEC
243
FACE
242TECH CLASSROM
241
7
A310R
8
A310R
6
A310R
237
243B
B3b
229
231
146A
146B
234
243A
2
A310R3
A310R
COL
IT OFFICE
AND SHOP
245
10" 4'-0" 35'-2"
11'-11" 8'-0 1/2"
5"
5'-0"
5"
14'-2 1/2"
30
'-4
"1
0'-8
"5
"
10
A310R
100A
100B
244A
5
A310R
5
11
11
12
13
9 9 9 9
99
D7
245A
245B
BL-3
101010
260A
260B
241 242
4'-4"
6"
5'-0" 10'-4"
4
D26
WATERPROOFING AT EXISTING TUNNELLOCATIONS
24
'-2
"
24
'-4
"
B2
B2
B2
B2
A512
14
12'-7" +-
10
'-6
"
EWC EWC
244B
EXISTING STUD & GYP BD WALL
1414
3434
34 34
SEE OVERALL FLOOR PLANSHEET A110 FOR LOCATIONOF DOOR 260C.
9
A201R
239
3'-8" 16'-0" 2'-10" 25'-2" 8" 16'-0" 3'-8" 3'-8" 15'-8" 1'-4" 15'-8" 3'-8"
28
4
B4B4 B4 B4 B4 B4 B4
236
233A
233B
2"
CROSS-HATCHED AREA INDICATESLIMITS OF NEW CONCRETE. FLOORREMOVAL PART OF BID PACKAGE 4.
BL-3 BL-3
SE
G C
TYP OF 4
NEW OPENINGS IN 2HR WALL
1
INFILL EXISTING OPENINGSW/ CMU
28
11
A310R
36'-2"
14
'-0
"
2
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREET
LA CROSSE, WISCONSIN
PHONE: 608.784.1830
FAX: 608.782.5844
www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sheet T
itle
:
Pro
ject Location:
Pro
ject T
itle
:
11/2/2018 10:56:49 AM
A112R
MPL
18022
OCTOBER 19, 2018
FL
OO
R P
LA
N-
UN
IT B
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025 T
ow
n S
treet
Pre
nti
ce,W
I 54556
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
KEY NOTES PLAN1 INFILL EXISTING OPENING WITH CMU. MATCH ADJACENT FINISHES.
2 NEW FOLDING PANEL PARTITION.
3 INFILL EXISTING SLAB DEPRESSION.
4 FLOOR OPENING INFILL. SEE _____.
5 PERMANENTLY SECURE EXISTING TUNNEL ACCESS PANELS.
6 RELOCATED DOOR/ TRANSOM.
7 LINE OF CANOPY ABOVE.
8 NEW CHEM COUNTERTOP, INTEGRAL SINK, GAS VALVES ANDELECTRICAL OUTLETS. SEE CASEWORK DRAWINGS, PLUMBING ANDELECTRICAL.
9 LINE OF BULKHEAD ABOVE.
10 VENDING MACHINES (N.I.C.)
11 NEW COOLER- SEE FOOD SERVICE SHEETS.
12 NEW DISHWASHER- SEE FOOD SERVICE SHEETS.
13 MOBILE STAGE (N.I.C.)
14 INFILL FLOOR AS REQUIRED AFTER REMOVAL OF CMU WALL. PREPAREFOR NEW FLOORING.
15 12"W x 15"D LOCKERS ON 4" CONCRETE SLAB.
16 12"W x 15"D CUBBIES ON 4" CONCRETE SLAB.
17 PROVIDE 3/4" PLYWOOD PANEL- COORDINATE SIZE AND MOUNTING HTWITH ELECTRICAL.
18 STEEL COLUMN- SEE STRUCTUAL.
19 MOP SINK- SEE PLUMBING.
20 ROOF DRAIN LEADER- SEE PLUMBING AND DETAILS A512.
21 SOLID SURFACE SILL.
22 REMOVABLE RAILING.
23 DIMENSION INDICATES PRECAST PANEL OVERHANG AT FOUNDATIONBELOW. SEE DETAIL 11/A200.
24 CONCRETE STOOP- SEE STRUCTRAL.
25 4 3/4" FLOOR INFILL TO MATCH HEIGHT OF GYM FLOOR. SEE DETAIL8/A514.
26 STUD AND GYP BD COLUMN ENCLOSURE. SEE 7/A514.
27 CHAIR LIFT
28 INFILL OPENING TO MATCH EXISTING EXTERIOR WALL.
29 RAMP- 15% SLOPE
30 RAMP- 8.3% SLOPE
31 PERFORATED WINDOW BLINDS.
32 INSTALL SOUNDPROOFING FLOOR MAT AND 4 x 8 x 3/4" PLYWOOD ONEXISTING STAGE. PAINT BLACK.
33 SHADED LINES INDICATE LOCATION OF IN-FLOOR HEATING. SEE9/A514.
34 LINE OF SKYLIGHT ABOVE.
35 EXISTING SLOPED SILL TO REMAIN (NON ADA).
36 CABINET HEATER- SEE MECH SHEETS.
37 CANOPY COLUMN- SEE _____.
38 EXISTING DATA CABINET.
39 ROOM DARKENING SHADES.
40 PLAM SHELVES IN EXISTING WINDOW AND DOOR OPENINGS.
41 LINE OF AWNING ABOVE- SEE ____.
42 PAD ALL WALLS- FLOOR TO 6'-0" AFF.
43 6" STUDS CHASE AT VENT PIPE LOCATIONS- COODINATE WITHPLUMBING.
44 NEW CURTAINS AND STAGE RIGGING- SEE SPECS.
KEY PLAN
SEG B
SEG A
SEG C
SEG D
SE
G E
1/8" = 1'-0"1FLOOR PLAN- UNIT B
No. Description Date
1 ADD 1 10-25-18
2 ADD 2 11-02-18
BID
PA
CK
AG
E 3
BID PACKAGE 3ADDENDUM 2
GENERAL NOTES:SEE DETAILS A200 FOR CONTROL JOINT (CJ) AND BRICKCONTROL JOINT (BCJ) INFORMATION.
BRICK COURSING: RUNNING 1/3 BOND TYPICAL.
LEGEND:
WINDOW TAG, SEE SHEET A212 FOR FRAME ELEVATIONS
CJ THROUGH WALL CONTROL JOINT - SEE DETAILS A510
BCJ BRICK VENEER CONTROL JOINT - SEE DETAILS A510
FIELD BRICKRUNNING BOND
A
B
SEE SPECIFICATION FOR MATERIAL TYPE.D
-
ACCENT BAND BRICKROWLOCK
METAL PANEL
1 KEYNOTE TAG
BRICK SIZE: 4x4x12 (NOMINAL)C
SEE DETAIL 11/A512 FOR TYPICAL HEAD FLASHING DETAIL.E
ARCHITECTURAL CASTSTONE PANEL- SEE9/A200 FOR REVEALPROFILE
SEE WINDOW ELEVCAST STONE SILL- SEE 8/A200 FORTYPICAL PROFILE. SEE SPECFOR MINIMUM LENGTHS.
A
B
METAL PANEL - COLOR A
METAL PANEL - COLOR B
4
A311R
7 6 5 4 3 1
JOIST BRG114'-0"
JOIST BRG MEZZ126'-8"
6
A311R
1
A313R
FIRST FLOOR100'-0"
2
7
A311R
10
A311R
11
A311R1
A312
2
A312
7 7
1
1
1
2 3 3 3 3 3
3333
4444
BEJ @INSIDE
CORNER
BEJ @INSIDECORNER
B
A
3 2
CJ
CJ CJ CJ CJ CJ CJ CJ CJ CJ
6"
11 11 11
COORDINATE GROUTED CORES AND BOND BEAMS FOR AWNING ATTACHMENT
11
A200R
7.17.37.7 7.4
CD AF
JOIST BRG114'-0"
5
A311R
FIRST FLOOR100'-0"
E B1
B B
1
A311R
4
A311R
4
A311R
1
A311R
2 2 23 3 3 3 3 3 3 3
1'-10" 1'-10" 1'-10"1'-10"2'-4" 2'-4"
1
1
11
1'-10"1'-10"1'-10"1'-10"2'-4"
BCJ BCJ BCJ BCJ BCJ BCJ BCJ BCJ BCJ BCJ BCJ BCJ
11 11 11 11
13 13
11
A200R
D.1E.2
8
A311R
9
A311RBEJ @INSIDECORNER
1
4
1
CJ CJ
11
765431
JOIST BRG114'-0"
1
A311R
FIRST FLOOR100'-0"
2
11
A311R
10
A311R
2
A312
3
A312
7
A311R
B
11
1
4444
333333 2
3 3 3 3
BEJ @INSIDE
CORNER
BEJ @INSIDECORNER
1111
11
6"
1
3
BCJ BCJ BCJ BCJ BCJ BCJ BCJ BCJ BCJ BCJ BCJ
COORDINATE GROUTED CORES AND BOND BEAMS FOR AWNING ATTACHMENT
6.97.1 7.3 7.77.4
JOIST BRG114'-0"
FIRST FLOOR100'-0"
11
3
4
BEJ @INSIDE
CORNER
9
A311R
8
A311R
BCJBCJ
11
FIRST FLOOR100'-0"
1 1
3 5
/8"
5 1/2"
4 1/2" 1"
2"
1 5
/8"
5/8"DRIPEDGE
WINDOW
2"
1 5
/8"
5 5/8" 3 5/8"
9 1/4"
5/8"
3 5
/8"
BUMP-OUT
1"
1/2
"
1"
RAKE JOINT 3/4" MIN. INSTALL SEALANT AND BACKER ROD
FILL CAVITY COMPLETELY WITH CAVITY WALL INSULATION -MINIMUM 12" WIDE
SEE ELEVATIONS FOR BEJ LOCATIONS
04 21 00.A15
BACKER ROD AND SEALANT
HORIZONTAL JOINT REINFORCEMENT, DISCONTINUOUS AT MOVEMENT JOINT
5/8"
4'-1
"
1"
4'-0
"
A2
A2
4'-1"
4'-0"1"
CLOSE OFF CAVITY WITH EXTRUDEDINSULATION- TYPICALAT ALL PRECASTCORNERS
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREET
LA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sheet T
itle
:
Pro
ject Location:
Pro
ject T
itle
:
11/2/2018 10:56:56 AM
A200R
MPL
18022
OCTOBER 19, 2018
EX
TE
RIO
R E
LE
VA
TIO
NS
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025 T
ow
n S
treet
Pre
nti
ce,W
I 54556
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
KEY NOTES ELEVATION1 PREFINISHED SHEET METAL CAP FLASHING W/ 6" WIDE JOINT COVERS
SET IN SEALANT.
2 CONCRETE STOOP SLAB AT DOOR- SEE STRUCTURAL.
3 CAST STONE SILL- SEE PROFILE 8/A200.
4 METAL AWNING- SEE DETAILS ______.
5 OVERFLOW SCUPPER- SEE ROOF PLAN AND DETAIL SHEET _____.
6 SPRINKLER RISER CONNECTION.
7 LOUVER- SEE MECHANICAL.
8 CANOPY COLUMN- SEE DETAILS _____.
9 MAIN CANOPY- SEE DETAILS _____.
10 BUILDING SIGNAGE- BY OWNER.
11 ARCHITECTURAL PRECAST PANELS TO BE 2'-0" WIDE, UNLESS SHOWNOTHERWISE.
12 RUN EPDM UP PARAPET.
13 EXTERIOR LIGHTING.
14 SAWTOOTH IN BRICK AT EXISTING OPENING. MATCH ADJACENT BRICK.
15 REPAIR/ REPLACE METAL CAP FLASHING AS REQUIRED.
16 EXISTING METAL CAP FLASHING AND DRIP EDGE TO REMAIN.
17 CLEAN/ REPAIR EXISITNG BRICK.
18 Elev.
19 Elev.
20 Elev.
1/8" = 1'-0"7SEGMENT C- EAST ELEVATION
1/8" = 1'-0"5SEGMENT C- NORTH ELEVATION
1/8" = 1'-0"6SEGMENT C- SOUTH 2
1/8" = 1'-0"1SEGMENT C- WEST ELEVATION
1/8" = 1'-0"2SEGMENT C- SOUTH 1
26
5
17
1/8" = 1'-0"3SEGMENT C- EAST 1
1/8" = 1'-0"4SEGMENT C- WEST 1
ELEVATION KEY PLAN
34
No. Description Date
2 ADD 2 11-02-18
1 1/2" = 1'-0"8CAST STONE SILL PROFILES
3" = 1'-0"9CAST STONE REVEAL
1 1/2" = 1'-0"10EXPANSION JOINT DETAIL
1/2" = 1'-0"11PRECAST CORNER DETAIL
ADJUSTED REVEALS IN PRECAST
2
2
BID
PA
CK
AG
E 3
BID PACKAGE 3ADDENDUM 2
EXTG JOIST BRG111'-4"
1
A315R
FIRST FLOOR100'-0"
3
A315R
4
A315R
2
A315R
10
9
B B
8
B18
A514
8
A314R
JOIST BRG D119'-4"
3
A313R
6
A314R
9
A314R
FIRST FLOOR100'-0"
10
A314R
4
A313R
CJ
11
1
11
4
3
2
7.3
3
A312
2
A314R
JOIST BRG D119'-4"
FIRST FLOOR100'-0"
5
A313R1'-8"
CJ CJ CJ CJ CJ CJ CJ CJ CJ
BEJ @INSIDECORNER
1 1
23333
6"
123"
12"5 5
DF
JOIST BRG MEZZ126'-8"
9
A310R
MEZZANINE114'-7 1/2"
7
A501
1
7 7 7 7
A
5
D.1E.2 7
6
A312
6
A311R
1
7 7
B
A
6.97.1 7.3 7.77.4D F
10
A310R
5
A312
1
1
EXISTING EASTGYM ROOF
A12 12
2 7/8"
1'-0"
D.1 E.2
FINISH FLOOR100'-0"
1
GENERAL NOTES:SEE DETAILS A200 FOR CONTROL JOINT (CJ) AND BRICKCONTROL JOINT (BCJ) INFORMATION.
BRICK COURSING: RUNNING 1/3 BOND TYPICAL.
LEGEND:
WINDOW TAG, SEE SHEET A212 FOR FRAME ELEVATIONS
CJ THROUGH WALL CONTROL JOINT - SEE DETAILS A510
BCJ BRICK VENEER CONTROL JOINT - SEE DETAILS A510
FIELD BRICKRUNNING BOND
A
B
SEE SPECIFICATION FOR MATERIAL TYPE.D
-
ACCENT BAND BRICKROWLOCK
METAL PANEL
1 KEYNOTE TAG
BRICK SIZE: 4x4x12 (NOMINAL)C
SEE DETAIL 11/A512 FOR TYPICAL HEAD FLASHING DETAIL.E
ARCHITECTURAL CASTSTONE PANEL- SEE9/A200 FOR REVEALPROFILE
SEE WINDOW ELEVCAST STONE SILL- SEE 8/A200 FORTYPICAL PROFILE. SEE SPECFOR MINIMUM LENGTHS.
A
B
METAL PANEL - COLOR A
METAL PANEL - COLOR B
PRECAST BRG133'-2"
GYM ROOF- WEST130'-0"
3
A316
E STAGE FLOOR-WEST
104'-0"
1
A316
FIRST FLOOR100'-0"
2
A316
EXTG JOIST BRG111'-4"
FIRST FLOOR100'-0"
13
15
16 11
A310R
2
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREET
LA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sheet T
itle
:
Pro
ject Location:
Pro
ject T
itle
:
11/2/2018 10:57:03 AM
A201R
Author
18022
OCTOBER 19, 2018
EX
TE
RIO
R E
LE
VA
TIO
NS
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025 T
ow
n S
treet
Pre
nti
ce,W
I 54556
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
1/8" = 1'-0"1MAIN ENTRY EAST
1/8" = 1'-0"2SEGMENT D- EAST
1/8" = 1'-0"4SEGMENT D- NORTH
1/8" = 1'-0"5MEZZANINE- NORTH
1/8" = 1'-0"6MEZZANINE- WEST
1/8" = 1'-0"7MEZZANINE- CHORAL/ BAND SOUTH
1
4
7
ELEVATION KEY PLAN
62
5
1/8" = 1'-0"3SEGMENT D- SOUTH
3
No. Description Date
2 ADD 2 11-02-18
KEY NOTES ELEVATION1 PREFINISHED SHEET METAL CAP FLASHING W/ 6" WIDE JOINT COVERS
SET IN SEALANT.
2 CONCRETE STOOP SLAB AT DOOR- SEE STRUCTURAL.
3 CAST STONE SILL- SEE PROFILE 8/A200.
4 METAL AWNING- SEE DETAILS ______.
5 OVERFLOW SCUPPER- SEE ROOF PLAN AND DETAIL SHEET _____.
6 SPRINKLER RISER CONNECTION.
7 LOUVER- SEE MECHANICAL.
8 CANOPY COLUMN- SEE DETAILS _____.
9 MAIN CANOPY- SEE DETAILS _____.
10 BUILDING SIGNAGE- BY OWNER.
11 ARCHITECTURAL PRECAST PANELS TO BE 2'-0" WIDE, UNLESS SHOWNOTHERWISE.
12 RUN EPDM UP PARAPET.
13 EXTERIOR LIGHTING.
14 SAWTOOTH IN BRICK AT EXISTING OPENING. MATCH ADJACENT BRICK.
15 REPAIR/ REPLACE METAL CAP FLASHING AS REQUIRED.
16 EXISTING METAL CAP FLASHING AND DRIP EDGE TO REMAIN.
17 CLEAN/ REPAIR EXISITNG BRICK.
18 Elev.
19 Elev.
20 Elev.
1/8" = 1'-0"8FITNESS WEST
8
1/8" = 1'-0"9SEGMENT B- NORTH
ALTERNATE
BID
PA
CK
AG
E 3
BID PACKAGE 3ADDENDUM 2
CORRIDOR
CLASSROOM
LO
CK
ER
SG
LA
SS
FIRST FLOOR100'-0"
CORRIDOR
PLY
WO
OD
DO
OR
S
FIRST FLOOR100'-0"
LO
CK
ER
S
EXTG JOIST BRG111'-4"
FIRST FLOOR100'-0"
11 5/8"
FACE BRICKW/ 8" CMU
BACKUP
WATERPROOFING AT EXISTING TUNNEL
LOCATIONS
JOIST BRG114'-0"
B3b
LOUNGE/ WORK
101
CAFETERIA
239
FIRST FLOOR100'-0"
8" CMU INFILL
5'-4
"
EXISTINGEXTERIORWALL
EXISTINGROOF
2'-7 1
/4"
REMOVE EXISTINGGRAVEL STOP
FILL GAP WITHRIGID INSULATION
A500
1
EXTEND 2 HR WALLMIN. 30" ABOVE EXISTING ROOF
EXTG JOIST BRG111'-4"
CAFETERIA
239
FIRST FLOOR100'-0"
9'-4
"
EXISTINGEXTERIOR
WALL
EXISTING ROOF
JOIST BRG114'-0"
CORRIDOR
100
CIRCULATION
238
FIRST FLOOR100'-0"
8"
REMOVE TOP 8"OF EXISTING FOUNDATION
EXISTINGEXTERIORWALL
EXISTINGROOF
REMOVE EXISTINGGRAVEL STOP
FILL GAP WITHRIGID INSULATION
2'-7 1
/4"
A500
1
A510
6
5
A510
A510
4
EXTEND 2 HR WALLMIN. 30" ABOVE EXISTING ROOF
EXTG JOIST BRG111'-4"
CIRCULATION
238
EXISTING ROOF
JOIST BRG114'-0"
MEZZANINE114'-7 1/2"
GIRL'S T.R.
107
ART
237
MECH MEZZ
280
FIRST FLOOR100'-0"
PLAM SHELVING
EXISTINGEXTERIORWALL
EXISTINGROOF
REMOVE EXISTINGGRAVEL STOP
T.O. PARAPET128'-8"
A4
2 H
R W
ALL
2 H
R W
ALL
1 H
R W
ALL
EXTEND 2HR WALL MIN. 30" ABOVE EXISTING ROOF
1 HR WALL FROMPENTHOUSE FLOORTO PARAPET
7
JOIST BRG114'-0"
MEZZANINE114'-7 1/2"
B3
D3
A8
A500
2
A500
6
7.1
JOIST BRG114'-0"
FIRST FLOOR100'-0"
EXISTINGEXTERIORWALL
EXISTINGROOF
REMOVE EXISTINGGRAVEL STOP
FILL GAP WITHRIGID INSULATION
2'-7 1
/4"
A500
1
A510
1
A510
3
EXTEND 2HR WALL MIN. 30" ABOVE EXISTING ROOF
2
A510
EXTG JOIST BRG111'-4"
FIRST FLOOR100'-0"
FLUID APPLIED WATERPROOFING
6"
4" FACE BRICKW/ BRICK TIES
TO EXISTING WALL
AIR SPACE
1" SPRAY FOAM INSULATION
8"
4'-4
"4
"3
'-8
"4
"2
'-8
"
REMOVE EXISTINGGRAVEL STOP AS
REQUIRED TO INSTALLNEW BRICK WALL ANDMETAL CAP FLASHING
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREET
LA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sheet T
itle
:
Pro
ject Location:
Pro
ject T
itle
:
11/2/2018 10:57:08 AM
A310R
MPL
18022
OCTOBER 19, 2018
WA
LL
SE
CT
ION
S
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025 T
ow
n S
treet
Pre
nti
ce,W
I 54556
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
1/2" = 1'-0"2EXTG CORR. SECTION
1/2" = 1'-0"3EXTG CORR. SECTION
1/2" = 1'-0"1EXTG WALL SECTION
1/2" = 1'-0"4WALL SECTION
1/2" = 1'-0"6WALL SECTION
1/2" = 1'-0"7WALL SECTION
1/2" = 1'-0"8WALL SECTION
1/2" = 1'-0"10PENTHOUSE SECTION
1/2" = 1'-0"9PENTHOUSE SECTION
1/2" = 1'-0"5WALL SECTION
No. Description Date
2 ADD 2 11-02-18
BID
PA
CK
AG
E 3
1/2" = 1'-0"11WALL SECTION
2
BID PACKAGE 3ADDENDUM 2
A
JOIST BRG114'-0"
FIRST FLOOR100'-0"
2'-8
"4
'-8
"5
'-8
"4
"2
'-8
"
A3
A1
16
'-0
"4
"
A510
7
A510
9
A500
7
2" EXTRUDED RIGIDINSULATION
C
CLASSROOM CORRIDOR
D31
GRID
4" CONCRETECURB
CONCRETEPAD- SEESTRUCTURAL
D
CLASSROOMCOLLABORATE
CONCRETEPAD- SEESTRUCTURAL
D31
A511
1
2
A511
F
FIRST FLOOR100'-0"
2'-8
"4
'-8
"4
"5
'-4
"4
"3
'-0
"
16
'-0
"4
"
A3
A1
A500
7
A500
3
2" EXTRUDED RIGIDINSULATION
F
JOIST BRG114'-0"
MEZZANINE114'-7 1/2"
MECH MEZZ
280
FIRST FLOOR100'-0"
12
'-8
"2
'-8
"1
3'-4
"
A8
A3
A1
28
'-8
"
A510
12
A510
13
A500
11
A500
12
14
A510
2" EXTRUDED RIGIDINSULATION
FINISH FLOOR100'-0"
JOIST BRG114'-0"
A3
8'-0
"9
'-4
"
1'-0" 4" 4'-0"
17
'-4
"
A500
4
A510
10
A500
8
A510
12
11
A510
2" EXTRUDED RIGIDINSULATION
2'-0
"1
'-2
"1
'-6
"2
'-4
"2
'-4
"1
'-0
"1
'-0
"2
'-0
"2
'-0
"2
'-0
" +
-
AWNING-FUTURE BID PACKAGE
2
F
JOIST BRG114'-0"
FIRST FLOOR100'-0"
3'-0
"1
3'-0
"
16
'-0
"4
"
0"
6'-0
"4
"3
'-8
"4
"2
'-8
"
2 WYTHES4" BRICK AT PILASTERS
HEADERBRICKCOURSE
A3
A1
A500
5
A500
9
2" EXTRUDED RIGIDINSULATION
7 5/8"
2
A3
12
'-4
"1
'-0
"
4"
A510
15
A510
17
16
A510
2" EXTRUDED RIGIDINSULATION
IN-FLOOR HEATING-SEE MECHANICAL AND
DETAIL 5/A514
21
'-1
1"
±2
'-1
"2
'-0
"1
'-0
"1
'-0
"2
'-4
"2
'-4
"1
'-6
"1
'-2
"2
'-0
"
17
'-4
"
A2
A500
4
A500
10
2" EXTRUDED RIGIDINSULATION
IN-FLOOR HEATING-SEE MECHANICAL AND
DETAIL 5/A514
A3
16
'-0
"4
"
A1
2'-8
"6
'-4
"4
"3
'-8
"4
"2
'-8
"
2" EXTRUDED RIGIDINSULATION
IN-FLOOR HEATING-SEE MECHANICAL AND
DETAIL 5/A514
A3 2'-8
"4
'-0
"8
'-4
"1
'-0
"
16
'-0
"4
"
A1
A510
7
A510
17
2" EXTRUDED RIGIDINSULATION
16
A510
IN-FLOOR HEATING-SEE MECHANICAL AND
DETAIL 5/A514
2
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREET
LA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sheet T
itle
:
Pro
ject Location:
Pro
ject T
itle
:
11/2/2018 10:57:13 AM
A311R
MPL
18022
OCTOBER 19, 2018
WA
LL
SE
CT
ION
S
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025 T
ow
n S
treet
Pre
nti
ce,W
I 54556
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
1/2" = 1'-0"1WALL SECTION
1/2" = 1'-0"2WALL SECTION
1/2" = 1'-0"3WALL SECTION
1/2" = 1'-0"4WALL SECTION
1/2" = 1'-0"6PENTHOUSE SECTION
1/2" = 1'-0"5WALL SECTION
1/2" = 1'-0"7WALL SECTION
1/2" = 1'-0"8WALL SECTION
1/2" = 1'-0"9WALL SECTION
1/2" = 1'-0"10WALL SECTION
1/2" = 1'-0"11WALL SECTION
No. Description Date
2 ADD 2 11-02-18
BID
PA
CK
AG
E 3
BID PACKAGE 3ADDENDUM 2
F
MEZZANINE114'-7 1/2"
JOIST BRG D119'-4"
MECH MEZZ
280
VESTIBULE
145
CHOIR/ MUSIC
148
FIRST FLOOR100'-0"
A500
2
A501
6
A8
BAND
149
2'-8
"5
'-4
"
A3
A1
8'-0
"4
'-0
"9
'-4
"
21
'-4
"4
"
A501
3
A511
5
A510
9
A500
9
6
A511
2" EXTRUDED RIGIDINSULATION
OPP
E STAGE FLOOR-EAST
103'-2"
7
A313R
CORRIDOR
147
FIRST FLOOR100'-0"
5 T @ 11"
4'-7" 8'-4" 21'-0"
6 R
@ 6
.33
"
3'-2
"
CONCRETE SLABON FOAM BASE
2'-10
"
5/8" GYP BD CFMF FRAMING-SEE STRUCTURAL
CFMF FRAMING-SEE STRUCTURAL
CLIP ANGLE- ANCHOREDTO CONC- TYP BOTH SIDES
CORRIDOR
147
FIRST FLOOR100'-0"
3'-6
"3
'-2
"
REMOVABLERAILING
2'-10
"
CONCRETE SLABON FOAM BASE
5/8" GYP BD
CFMF FRAMING-SEE STRUCTURAL
8"
2'-0
"2
'-0
"1
'-0
"1
'-0
"2
'-4
"2
'-4
"1
'-6
"1
'-2
"2
'-0
"
5'-4
"1
6'-0
"
21
'-4
"
A1
1"
A501
3
A500
10
2" EXTRUDED RIGIDINSULATION
A2
4'-0
"2
'-4
"3
'-10
"
A501
8
FINISH FLOOR100'-0"
JOIST BRG D119'-4"
8'-0
"1
3'-0
"4
"
A1
21
'-4
"
A501
3
A511
5
A510
17
2" EXTRUDED RIGIDINSULATION
A3
8
A510
2
BAND
149
LG PRACTICE
153
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREET
LA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sheet T
itle
:
Pro
ject Location:
Pro
ject T
itle
:
11/2/2018 10:57:16 AM
A313R
MPL
18022
OCTOBER 19, 2018
WA
LL
SE
CT
ION
S
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025 T
ow
n S
treet
Pre
nti
ce,W
I 54556
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
1/2" = 1'-0"1WALL SECTION
1/2" = 1'-0"3WALL SECTION
1/2" = 1'-0"6STAIR/ RAMP SECTION
1/2" = 1'-0"7LANDING SECTION
1/2" = 1'-0"4WALL SECTION
1/2" = 1'-0"5WALL SECTION
1/2" = 1'-0"2WALL SECTION
No. Description Date
2 ADD 2 11-02-18
BID
PA
CK
AG
E 3
BID PACKAGE 3ADDENDUM 2
EXTG JOIST BRG111'-4"
CORRIDOR
228
FIRST FLOOR100'-0"
7'-3
"
A512
16
A512
18
17
A512
E STAGE FLOOR-EAST
103'-2"
P.E. OFFICE
250
STAGE
249
D12
FIRST FLOOR100'-0"
6'-2
"
FIRST FLOOR100'-0"
EXISTING FOUNDATION
4'-4
" ±
3'-10
"3
'-6
"
A10
9'-8
"
A501
5
A501
9
2
2" EXTRUDED INSULATION
11
'-4
"
A10a
EXISTINGEXTERIOR WALL
EXISTINGFOUNDATION
A501
5
A501
9
4'-4
" ±
3'-10
"3
'-2
"
2
2" EXTRUDED INSULATION
1'-0
" ±
1'-0
"2
'-4
"2
'-4
"1
'-6
"1
'-2
"2
'-0
"
11
'-4
"
A11a
A501
5
A501
9
2
2" EXTRUDED INSULATION
E STAGE FLOOR-EAST
103'-2"
FIRST FLOOR100'-0"
4" 2'-0"
B3b
CUT BACK EXISTINGROOF TO ALLOW FOR NEW 2 HR FIRE WALLTO EXTEND PAST
EX
IST
ING
WA
LL
MIN
.
2'-6
"
2 H
R W
ALL
2 H
R W
ALL
EXTEND 2HR WALL MIN. 30" ABOVE EXISTING ROOF
2'-8
"4
"5
'-4
"4
"4
'-8
"2
'-8
"5
'-4
"
A3
A1
4"
16
'-0
"
A501
3
A501
4
2" EXTRUDED RIGIDINSULATION
FIRST FLOOR100'-0"
4" INFILL100'-4"
A512
20
A512
19
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREET
LA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sheet T
itle
:
Pro
ject Location:
Pro
ject T
itle
:
11/2/2018 10:57:20 AM
A314R
MPL
18022
OCTOBER 19, 2018
WA
LL
SE
CT
ION
S
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025 T
ow
n S
treet
Pre
nti
ce,W
I 54556
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
1/2" = 1'-0"3ALCOVE SECTION
1/2" = 1'-0"4STAIR SECTION
1/2" = 1'-0"8GYM VEST. SECTION
1/2" = 1'-0"5STAGE SECTION
1/2" = 1'-0"6GYM VEST. SECTION
1/2" = 1'-0"9GYM VEST. SECTION
1/2" = 1'-0"10GYM VEST. SECTION
1/2" = 1'-0"1WALL SECTION
1/2" = 1'-0"2WALL SECTION
No. Description Date
2 ADD 2 11-02-18
BID
PA
CK
AG
E 3
1/2" = 1'-0"7GYM VEST. SECTION
BID PACKAGE 3ADDENDUM 2
D3
8"
±2
'-0
"2
'-4
"2
'-4
"1
'-6
"1
'-2
"2
'-0
"
12
'-0
"
A2
2
EXTG JOIST BRG111'-4"
FIRST FLOOR100'-0"
D3
2'-8
"6
'-4
"3
'-0
"
12
'-0
"
3'-0
"
EXISTINGFOUNDATION
A511
8
A511
10
A511
11
9
A511
A4
EXTG JOIST BRG111'-4"
FIRST FLOOR100'-0"
1
A514
CANOPY STRUCTUREPART OF FUTUREBID PACKAGE
CANOPY STRUCTUREPART OF FUTUREBID PACKAGE
8"
+-
1'-0
"1
'-0
"2
'-4
"2
'-4
"1
'-6
"1
'-2
"2
'-0
"
12
'-0
"
2
E STAGE FLOOR-EAST
103'-2"
FIRST FLOOR100'-0"
10
5/8
"7
'-11
3/8
"
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREET
LA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sheet T
itle
:
Pro
ject Location:
Pro
ject T
itle
:
11/2/2018 10:57:21 AM
A315R
MPL
18022
OCTOBER 19, 2018
WA
LL
SE
CT
ION
S
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025 T
ow
n S
treet
Pre
nti
ce,W
I 54556
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
1/2" = 1'-0"3WALL SECTION
1/2" = 1'-0"4WALL SECTION
1/2" = 1'-0"1MAIN ENTRY CANOPY SECTION
1/2" = 1'-0"2MAIN ENTRY WALL SECTION
No. Description Date
2 ADD 2 11-02-18
1/2" = 1'-0"5A315-5
BID
PA
CK
AG
E 3
BID PACKAGE 3ADDENDUM 1
MEZZANINE114'-7 1/2"
B3b
1/2" PLYWOOD OVER2" RIGID INSUL. (R=5/IN.)- BOTH SIDES
1/2" PLYWOOD OVER2x WOOD BLOCKING -BOTH SIDES
PREFINISHED SHEETMETAL CAP FLASHING
NON-CORROSIVE SCREWS W/NEOPRENE WASHER
1x WOOD BLOCKING
1/2" PLYWOOD
EXTEND MEMBRANE UPAND OVER PARAPET AND FASTEN TO WOODBLOCKING
FLASH PER ROOFMANUF. WARRANTYDETAIL
SEE ROOFDESCRIPTIONS ONROOF PLAN
1/2" PLYWOOD OVER2x WOOD BLOCKING -BOTH SIDES
FILL VOID W/ BATT INSUL.
2x WOOD BLOCKING
6"
CONT. CLIP
FLASH PER ROOF MANUF.WARRANTY DETAIL
2x WOO BLOCKING
1/2" PLYWOOD W/ POSITIVEDRAINGE AWAY FROMPARAPET
FILL VOID W/ RIGID INSUL.(R=5/IN.)
METAL ROOF DECK AND ANGLE - SEESTRUCT.
EXIST. BRICK ANDCMU COMPOSITEWALL
EXIST. ROOFINGSYSTEM
2"
2x WOODBLOCKING
EXIST. BAR JOIST
3/8" ANCHOR BOLT @ 48" O.C.
JOIST BRG MEZZ126'-8"
A8
SEE 1A500 FOR TYPICALCONSTRUCTION NOTES
(2) 2x8 WOODBLOCKING
3/4" x 3/4" CONT.KERF
3 5/8" METAL STUDS @ 16"O.C. ASREQUIRD INWF BEAM VOID
WF BEAM - SEESTRUCT.
1/2" GYP. BD. SHEATHING
2'-0
"
E JOIST BRGWEST
113'-4"
JOIST BRG114'-0"
MEZZANINE114'-7 1/2"
A8
CONC. SLAB ON METALDECK - SEE STRUCT.
WF BEAM - SEE STRUCT.
B3METAL DECK AND ANGLE -SEE STRUCT.
2" CMU @ BEAM BRG.
1/2" PLYWOOD OVER 1xWOOD BLOCKING
EXTEND COMPOSITE GIRTS& GYP. BD. SHEAHING TOROOF DECK
SEE ROOF PLAN FORROOF DESCRIPTION
FLASH PER ROOF MANUF.WARRANTY DETAIL
PREFINISHED SHEET METALCOUNTER FLASHING
PREFINISHED SHEET METALTHRU-WALL RECEIVERFLASHING EXTEND BACK TOGIRTS AND UP 8" - FASTEN W/TERM BAR TO GIRTS
FIRST FLOOR100'-0"
A1
RIGID INSUL. (R=5/IN.) INLIEU OF SPRAY FOAM ATFLASHING
CAVITY MORTAR CONTROL
BRICK VENTS/WEEPS @24" O.C.
S.S. FLASHING - EXTENDBEYOND VENEER FACE
GRADE - SEE CIVIL
2" RIGID INSUL. (R=5/IN.)
CONC. FDN. WALL - SEESTRUCT.
BOND BREAK - SEESTRUCT.
CONC. SLAB - SEESTRUCT.
FLEXIBLE MEMBRANEFLASHING - EXTENDOVER TOP OF S.S.FLASHING
A3
SEE 1A500 & 3A500 FORTYPICAL CONSTRUCTIONNOTES
2x8 WOOD BLOCKING
A3
VENTS/WEEPS @ 48"O.C. MAX.
STEEL PLATE, ANGLEAND CHANNEL - SEESTRUCT. - PAINTEXPOSED STEEL
S.S. FLASHING - EXTENDBEYOND VENEER FACE
CAST STONE FASTENERSDESIGNED/SUPPLIED BYMANUF.
RIGID INSUL. (R=5/IN.) INLIEU OF SPRAY FOAM ATFLASHING
INTEGRALLY COLOREDACRYLIC COATING OVER5/8" GYP. SHEATHING
CEILING SUSPENSIONSYSTEM
BACKER ROD & SEALANT@ PERIMETER
BOND BEAM - SEESTRUCT.
FLEXIBLE MEMBRANEFLASHING - EXTENDOVER TOP OF S.S. FLASHING
JOIST BRG114'-0"
A3
A1
SEE 1A500 & 3A500 FORTYPICAL CONSTRUCTIONNOTES
1 1/2"
4" FACE BRICK
3 5/8"3/8"
2'-0
"
JOIST BRG114'-0"
A3
A1
SEE 1A500 FOR TYPICALCONSTRUCTION NOTES
VENTS/WEEPS @ 48" O.C.MAX. (TOP & BOTTOM)
FILL VOID W/ RIGID INSUL.(R=5/IN.)
CAST STONE FASTENERSDESIGNED/SUPPLIED BYMANUF.
RIGID INSUL. (R=5/IN.) INLIEU OF SPRAY FOAM ATFLASHING
INSTALL BACKER ROD& SEALANT @ CASTSTONE/BRICK JOINT
2'-0
"
DRILL AND ANCHOR BLOCKINGTO CAST STONE
FIRST FLOOR100'-0"
A1
4" FACE BRICK
SEE 7A500 FOR TYPICALCONSTRUCTION NOTES
3 5/8"3/8"
BRICK VENT AT EACHSIDE OF BUMP-OUT
FIRST FLOOR100'-0"
A2
1"
VENTS/WEEPS BETWEENEACH PANEL
S.S. FLASHING - EXTENDBEYOND VENEER FACE
CAST STONE FASTENERSDESIGNED/SUPPLIED BYMANUF.
RIGID INSUL. (R=5/IN.) INLIEU OF SPRAY FOAM ATFLASHING
FLEXIBLE MEMBRANEFLASHING - EXTEND
OVER TOP OF S.S. FLASHING
SHIM TO ALLOW FORBASE FLASHING
EMBED BY CONTR.-SEE STRUCTURAL
JOIST BRG114'-0"
MEZZANINE114'-7 1/2"
A1
BOND BEAM - SEESTRUCT.
TS BEAM - SEESTRUCT.
FILL VOID W/ RIGIDINSUL. (R=5/IN.)
CEILING SUSPENSIONSYSTEM
INTEGRALLY COLOREDACRYLIC COATINGOVER 5/8" GYP. SHEATHING
BACKER ROD & SEALANT @ PERIMETER
BRICK VENTS/WEEPS@ 24" O.C.
CONC. SLAB ON METALDECK - SEE STRUCT.
FILL VOID W/ NEOPRENEDECK FILLER - INSTALL RATED TOP OF WALLSYSTEM @ RATED WALLS
JOIST BRG114'-0"
MEZZANINE114'-7 1/2"
A8
3 5/8"
1 3/4"
3 1/2"
1/2" PLYWOOD OVERDOUBLE 2x6 WOODBLOCKING
EXTEND GYP. BD.SHEATHING AND COMPOSITE GIRTS
PREFINISHED SHEETMETAL FLASHING
FLEXIBLE MEMBRANEFLASHING - FASTEN TOWALL W/ TERM BAR
1/2" PLYWOOD OVERSLOPED (1/2") 2x WOODBLOCKING
CONT. CLIP
CONT. KERF
DOUBLE 2x8 WOODBLOCKING
CAST STONE FASTENERSDESIGNED/SUPPLIED BYMANUF.
VENTS/WEEPS BETWEENEACH PANEL (TOP & BOTTOM)
FILL VOID W/ RIGID INSUL.(R=5/IN.)
CAST STONE PANEL
AIR SPACE
STEEL ANGLE, PLATE& WF BEAM - SEE STRUCT. - PAINT EXPOSED STEEL
CONC. SLAB ON METALDECK - SEE STRUCT.
SEE 8A500 FOR TYPICALCONSTRUCTION NOTES
2x WOOD BLOCKING- TOP & BOTTOM
TERMINATION BAR
FIRST FLOOR100'-0"
A4
SEE 7A500 FOR TYPICALCONSTRUCTION NOTES
S.S. FLASHING - EXTENDBEYOND FOUNDATION FACE
A3
A4
SEE 1A500, 3A500 & 8A500 FOR TYPICAL CONSTRUCTIONNOTES
2x8 WOOD BLOCKING
BACKER ROD & SEALANT BETWEENLINTEL AND METALPANEL
CAST STONE FASTENERSDESIGNED/SUPPLIED BYMANUF.
JOIST BRG D119'-4"
A1
SEE 1A500 & 3A500 FORTYPICAL CONSTRUCTIONNOTES
2x8 WOOD BLOCKING
BRICK VENTS/WEEPS @24" O.C.
2'-
0'
A1
A2
WF BEAM & STEEL PLATE- SEE STRUCT. - PAINT
EXPOSED STEEL
CAST STONE FASTENERSDESIGNED/SUPPLIED BY
MANUF.
VENTS/WEEPS BETWEENEACH PANEL
(TOP & BOTTOM)
WEEP / VENT AT 24" O.C.
CAVITY MORTAR CONTROL
FLEXIBLE MEMBRANEFLASHING- EXTEND OVER
TOP OF S.S. FLASHING
S.S. FLASHING- EXTENDBEYOND PC VENEER FACE
RIGID INSUL. (R=5/IN.) INLIEU OF SPRAY FOAM AT
FLASHING
JOIST BRG D119'-4"
A4
SEE 1A500 & 3A500 FORTYPICAL CONSTRUCTIONNOTES
2'-0
"
A4
SEE 6A500 FOR TYPICALCONSTRUCTION NOTES
METAL ROOF DECK, WF BEAM, ANGLE &PLATE - SEE STRUCT.- PAINT EXPOSED STEEL
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREET
LA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sheet T
itle
:
Pro
ject Location:
Pro
ject T
itle
:
11/2/2018 10:57:26 AM
A500
MPL/JTD
18022
OCTOBER 19, 2018
DE
TA
ILS
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025 T
ow
n S
treet
Pre
nti
ce,W
I 54556
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
1 1/2" = 1'-0"1ROOF PARAPET DETAIL
1 1/2" = 1'-0"2ROOF PARAPET DETAIL
1 1/2" = 1'-0"6ROOF/WALL/FLOOR DETAIL
1 1/2" = 1'-0"7WALL BASE DETAIL
1 1/2" = 1'-0"4ROOF PARAPET DETAIL
1 1/2" = 1'-0"8SOFFIT/WALL DETAIL
1 1/2" = 1'-0"5ROOF PARAPET DETAIL
1 1/2" = 1'-0"3ROOF PARAPET DETAIL
1 1/2" = 1'-0"9WALL BASE DETAIL
1 1/2" = 1'-0"10WALL BASE DETAIL
1 1/2" = 1'-0"11WALL/FLOOR DETAIL
1 1/2" = 1'-0"12SOFFIT/WALL DETAIL
1 1/2" = 1'-0"14WALL BASE DETAIL
1 1/2" = 1'-0"13ROOF PARAPET DETAIL
1 1/2" = 1'-0"15ROOF PAPAPET DETAIL
1 1/2" = 1'-0"16WALL/SOFFIT DETAIL
1 1/2" = 1'-0"17ROOF PARAPET DETAIL
1 1/2" = 1'-0"18WALL/ROOF DETAIL
No. Description Date
BID
PA
CK
AG
E 3
BID PACKAGE 3ADDENDUM 2
EXTG JOIST BRG111'-4"
EXTG JOIST BRG111'-4"
F
B3b
JOIST BRG D119'-4"
A1
SEE 1A500 & 3A500 FOR TYPICALCONSTRUCTION NOTES
A1
A3
A1
SEE 3A500 FOR TYPICALCONSTRUCTION NOTES
2'-8
"
CAST STONE FASTENERSDESIGNED/SUPPLIED BYMANUF.
BACKER ROD AND SEALANT
BACKER ROD AND SEALANT
A10
SEE 1A500 FOR TYPICALCONSTRUCTION NOTES
2" WIDER ATWALL TYPE A11
WEEP/VENT BETWEENEACH PANEL ANDPANEL/BRICK
FIRST FLOOR100'-0"
A10
SEE 10A500 FOR TYPICALCONSTRUCTION NOTESF
JOIST BRG D119'-4"
LOUVER- SEEMECHANICAL
SHIM
BACKER RODAND SEALANT
CONTINUOUS 2XWOOD BLOCKING
COMPOSITE 3 1/2"ZEE GIRT
SEE ROOF DESCRIPTIONON ROOF PLN
PREFINISHED SHEET METAL COUNTER FLASHING
B3
PREFINISHEDSHEET METAL SILL
7
JOIST BRG114'-0"
MEZZANINE114'-7 1/2"
A8
A1
6.9 7.1
CEILING SUSPENSIONSYSTEM
INTEGRALLY COLOREDACRYLIC COATINGOVER 5/8" GYP. SHEATHING
BACKER ROD & SEALANT @ PERIMETER
STEEL TUBE-SEE STRUCTURAL
CONTINUOUSDECK ANGLE-
MATCH ANGLE OF ROOF JOISTS
FILL VOID ANDDECK FLUTES W/
INSULATION
SEE ROOF PLAN FORROOF DESCRIPTIONS
FLASH PER ROOFMANUF. WARRANTY DETAIL
CONC. SLAB ON METALDECK - SEE STRUCT.
PREFINISHED SHEET METALCOUNTER FLASHING
PREFINISHED SHEET METALTHRU-WALL RECEIVER
FLASHING EXTEND BACK TOGIRTS AND UP 8" - FASTEN W/
TERM BAR TO GIRTS
A8
A8
PREFINISHED METAL CORNER FASTENING- BY INSTALLER
A8
A4
PREFINISHED METAL CORNER FASTENING- BY INSTALLER
METAL PARAPET BELOW
A8
A4
METAL PARAPET BELOW
PREFINISHED METAL CORNER FASTENING- BY INSTALLER
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREET
LA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sheet T
itle
:
Pro
ject Location:
Pro
ject T
itle
:
11/2/2018 10:57:29 AM
A501
MPL/JTD
18022
OCTOBER 19, 2018
DE
TA
ILS
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025 T
ow
n S
treet
Pre
nti
ce,W
I 54556
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
1 1/2" = 1'-0"1ROOF DETAIL
1 1/2" = 1'-0"2ROOF DETAIL
1 1/2" = 1'-0"3ROOF PARAPET DETAIL
1 1/2" = 1'-0"4WALL DETAIL
1 1/2" = 1'-0"5ROOF PARAPET DETAIL
1 1/2" = 1'-0"9WALL BASE DETAIL
No. Description Date
1 1/2" = 1'-0"6ROOF DETAIL
1 1/2" = 1'-0"7MEZZ. FLOOR-WALL DETAIL
1 1/2" = 1'-0"10MEZZAINE WALL DETAIL
1 1/2" = 1'-0"11MEZZAINE WALL DETAIL
1 1/2" = 1'-0"13MEZZAINE WALL DETAIL
BID
PA
CK
AG
E 3
1 1/2" = 1'-0"12MEZZAINE WALL DETAIL
FLOOR SLAB-SEE STRUCTURAL
1 1/2" = 1'-0"8WALL DETAIL
BID PACKAGE 3ADDENDUM 2
EQ. 5 3/4" EQ.
B3b
EXISTINGEXTERIORWALL
BENT METALEXPANSIONJOINT COVER
BACKER RODAND SEALANT
FILL VOID W/RIGID INSULATION
EXISTING LINTELTO REMAIN
HM FRAME-GROUT SOLID
EQ. 5 3/4" EQ
B3b
EXISTINGEXTERIORWALL
BENT METALEXPANSIONJOINT COVER
BACKER RODAND SEALANT
FILL VOID W/RIGID INSULATIONJAMB ANCHORS
HM FRAME-GROUT SOLID
EQ. 5 3/4" EQ.
B3b
1'-3"+/- 3/4"
1 1
/2"
SOLID SURFACESILL
GROUT EXISTNG CMUCORES SOLID AT SILLLOCATIONS
GROUT CMU CORESSOLID AT WINDOW
LOCATIONS
2X WOODBLOCKING
HM FRAME-GROUT SOLID B3b
EQ. 5 3/4" EQ.EXPANSIONJOINT SYSTEM
STEEL BEAM ANDPLATE- SEE STRUCT.-PAINT EXPOSED STEEL
CMU INFILL
HM FRAME-GROUT SOLID
2X CONTINUOUSWOOD BLOCKING
B3b
EQ. 5 3/4" EQ.
SAWTOOTH NEWCMU AT NEW JAMB LOCATIONS
EXISTING EXTERIORWALL
JAMBANCHOR
HM FRAME-GROUT SOLID
4" SOLID CMU
FIRST FLOOR100'-0"
B3b
EQ. 5 3/4" EQ.
A
3" 6"
A1
SEE 8A500 FOR TYPICALCONSTRUCTION NOTES
SH
OW
AW
NIN
GA
ND
FLA
SH
ING
A
3/4"7"6"3"
1 1
/2"
A1
CAST STONESILL
WEEP/ VENT AT 24" O.C.
FLEXIBLE MEMBRANEFLASHING- EXTEND OVER
TOP OF S.S. FLASHING
S.S. FLASHING- EXTENDBEYOND VENEER FACE
A
1 1/2" 3" 6" 7" +/- 3/4"
A1
CONTINUOUS 2XWOOD BLOCKING
WRAP AIR BARRIEROVER WOOD BLOCKING
CAST STONESILL BELOW
PREFINISHED ALUM STOREFRONT SYSTEM
SOLID SURFACESILL BELOW
BACKER ROD AND SEALANT
SHIM
7" 6"
A1
NOBRICK
CEILING SUSPENSIONSYSTEM
INTEGRALLY COLOREDACRYLIC COATINGOVER 5/8" GYP. SHEATHING
BACKER ROD & SEALANT @ PERIMETER
WRAP AIR BARRIEROVER WOOD BLOCKING
CONTINUOUS 2XWOOD BLOCKING
A1
D31 A2
6" 3"
FIRST FLOOR100'-0"
7" 6" 3"
3/4" 4"
EXPANSION MATERIAL
ALUM THRESHOLDSET IN SEALANT
6" 3"
A1RIGID INSUL. (R=5/IN.) INLIEU OF SPRAY FOAM ATFLASHING
CAVITY MORTAR CONTROL
WEEP / VENT AT 24" O.C.
S.S. FLASHING- EXTENDBEYOND VENEER FACE
STEEL LINTEL- SEESTRUCTURAL- PAINTEXPOSED STEEL
FLEXIBLE FLASHING MEMBRANE- EXTEND OVER
SS. FLASHHING
BOND BEAM-SEE STRUCTURAL
WRAP AIR BARRIEROVER WOOD BLOCKING
CONTINUOUS WOODBLOCKING
A1
D3
D3
D3
B3A1
6" 3"
ALUM DOOR FRAME
CLOSE OFF CAVITY WITHEXTRUDED INSULATION
WRAP AIR BARRIERAROUND WOOD BLOCKING
2X CONTINUOUSWOOD BLOCKING
SHIM
BACKER ROD AND SEALANT
JOIST BRG114'-0"
6" 3"
A3
SEE 1A500 & 3A500 FOR TYPICALCONSTRUCTION NOTES
CAVITY MORTAR CONTROL
S.S. FLASHING- EXTENDBEYOND VENEER FACE
STEEL LINTEL- SEESTRUCTURAL- PAINTEXPOSED STEEL
WEEP/VENT BETWEEN PANELS
RIGID INSUL. (R=5/IN.) INLIEU OF SPRAY FOAM ATFLASHING
VENEER LINTEL- SEESTRUCTURAL- PAINTEXPOSED STEEL
FLEXIBLE MEMBRANE FLASHING-EXTEND OVER TOP OF S.S. FLASHING
3/4" 7" 6" 4" 1/2"
A2
WRAP AIR BARRIEROVER WOOD BLOCKING
CONTINUOUS 2XWOOD BLOCKING
SHIM
BACKER ROD AND SEALANT
CAST STONE SILL BELOW
SOLID SURFACESILL BELOW
PREFINISHED ALUMSTOREFRONT SYSTEM
FIRST FLOOR100'-0"
6" 3" 1"
A1
3/4"
1 1
/2"
1 1/2"
CAST STONE SILL
FLEXIBLE FLASHING- EXTENDOVER TOP OF S.S. FLASHING
CAVITY MORTAR CONTROL
S.S. FLASHING- EXTENDBEYOND VENEER FACE
WEEP / VENT AT 24" O.C.
BACKER ROD AND SEALANTPREFINISHED ALUMSTOREFRONT SYSTEM
SOLID SURFACE SILL
WALL TYPEVARIES
SEE SCHED
SE
E S
CH
ED
4"
LINTELSEE STRUCT
MORTAR FILL HM FRAME
1 3/4" DOOR AS SCHEDULED
HM FRAME (PAINT)SEAL PERIMETER BOTH SIDES
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREET
LA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sheet T
itle
:
Pro
ject Location:
Pro
ject T
itle
:
11/2/2018 10:57:34 AM
A510
MPL/JTD
18022
OCTOBER 19, 2018
DO
OR
-WIN
DO
W D
ET
AIL
S
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025 T
ow
n S
treet
Pre
nti
ce,W
I 54556
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
1 1/2" = 1'-0"1WDO. HEAD DETAIL
1 1/2" = 1'-0"2WDO. JAMB DETAIL
1 1/2" = 1'-0"3WDO. SILL DETAIL
1 1/2" = 1'-0"4DOOR HEAD DETAIL
1 1/2" = 1'-0"5DOOR JAMB DETAIL
1 1/2" = 1'-0"6DOOR SILL DETAIL
1 1/2" = 1'-0"7WDO. HEAD DETAIL
1 1/2" = 1'-0"9WDO. SILL DETAIL
1 1/2" = 1'-0"8WDO. JAMB DETAIL
No. Description Date
1 ADD 1 10-25-18
1 1/2" = 1'-0"10DOOR HEAD DETAIL
1 1/2" = 1'-0"11DOOR JAMB DETAIL
1 1/2" = 1'-0"12DOOR SILL DETAIL
1 1/2" = 1'-0"13DOOR HEAD DETAIL
1 1/2" = 1'-0"14DOOR JAMB DETAIL
1 1/2" = 1'-0"15WDO. HEAD/ROOF DETAIL
1 1/2" = 1'-0"16WDO. JAMB DETAIL
1 1/2" = 1'-0"17WDO. SILL DETAIL
BID
PA
CK
AG
E 3
1 1/2" = 1'-0"18DOOR HEAD DETAIL
BID PACKAGE 3ADDENDUM 2
D
D31
D.1
D
OVERHEAD DOORTRACK
OVERHEAD DOOR -SEE DOOR SCHEDULE
DOOR JAMB FRAMING/DESIGN BY STUD MANUF.
HM FRAME & DOOR -SEAL PERIM. BOTH SIDES- SEE DOOR SCHEDULE.
D31
8 1/4"
A3
SEE 3A500 FOR TYPICALCONSTRUCTION NOTES
BOND BEAM LINTEL-SEE STRUCTURAL
CAVITY MORTAR CONTROL
S.S. FLASHING- EXTENDBEYOND VENEER FACE
RIGID INSUL. (R=5/IN.) INLIEU OF SPRAY FOAM ATFLASHING
VENEER LINTEL- SEESTRUCTURAL- PAINTEXPOSED STEEL
FLEXIBLE MEMBRANE FLASHING-EXTEND OVER TOP OF S.S. FLASHING
CAST STONE FASTENERSDESIGNED/SUPPLIED BYMANUF.
6" 3"
A4
A1
BELOW
6" 3" 1 1/2"
CAST STONESILL BELOW
SOLID SURFACE SILL BELOW
2X CONTINUOUSWOOD BLOCKING
WRAP AIR BARRIERAROUND WOOD BLOCKING
BACKER ROD AND SEALANT
SHIM
A3
3"6"
A1
BELOW
6" 3" 1 1/2"3/4"
STEEL COLUMN-SEE STRUCTURAL
ALUM STOREFRONTWINDOW SYSTEM
SEAM AT CENTEROF COLUMN-
SEAL JOINT AS REQUIRED
SOLID SURFACESILL BELOW
CAST STONE SILLBELOW
BREAK METAL ENCLOSURETO MATCH WINDOW FRAME
FINISH OVER WOOD BLOCKINGAS REQUIRED
D3A4
3 1/2"
1/2"
6"
RETURN GYP BDTO ALUM FRAME
RIGID INSUL. (R=5/IN.) INLIEU OF SPRAY FOAM ATFLASHING
FLEXIBLE MEMBRANE FLASHING-EXTEND OVER TOP OF S.S. FLASHING
S.S. FLASHING- EXTEND PAST VENEER FACE
WRAP AIR BARRIER AROUNDWOOD BLOCKING
STEEL LINTEL-SEE STRUCTURAL
A2D3
6" 5 1/4"
SOLID SURFACESILL BELOW
BACKER ROD AND SEALANT
ALUM STOREFRONTWINDOW SYSTEM
2X CONTINUOUS WOOD BLOCKING
WRAP AIR BARRIERAROUND WOOD BLOCKING
ALIGN WDW FRAME WITHEDGE OF EXISTING FOUNDATION
4"6"3/4"
1 1
/2"
D9
ALUM STOREFRONTWINDOW SYSTEM
SOLID SURFACEWINDOW SILL
2X WOOD BLOCKING
SEALANT ATPERIMETER
SPANDREL GLASSBELOW SILL
FIRST FLOOR100'-0"
6"
D9 ALIGN WDW FRAMEWITH EDGE OF EXISTINGFOUNDATION WALL
GROUT TOP CORE OFEXISTING CMU FOUNDATION SOLID
S.S. FLASHING- EXTENDBEYOND FACE OFFOUNDATION
OVERHEAD DOORTRACK
INSUL. OVERHEAD DOORW/ WEATHERSTIPPING -SEE DOOR SCHEDULE
1/4" BENT STEEL PLATEW/ STRAP ANCHORS @16" O.C. - PAINT
CLOSE OFF CAVITY W/2x WOOD BLOCKING
E STAGE FLOOR-WEST
104'-0"
3" 6" 3" 6"
3/4"9" +/-6"3"
1 1
/2"
EXTRUDED ALUM.WDO. SILL ANDCLIPS - SET INGROUT
SE
E F
RA
ME
ELE
V.
SEALANT AT PERIMETER BOTH SIDES
DOUBLE METAL STUD
SEE DOOR SCHEDULE FOR DOOR TYPE
SEE PLAN
CONTINUOUS LEAD LINING THROUGHOUT FRAME. OVERLAPWITH LEAD LINED WALL (WHERE SCHEDULED)
HOLLOW METAL FRAME WITH METAL STUD ANCHORS @ JAMB - PAINT
SEE SCHED
METAL RUNNER TRACK
SEE PLAN
2"
SE
E F
RA
ME
ELE
V.
SEALANT AT PERIMETER BOTH SIDES
DOUBLE METAL STUDS
SEE DOOR SCHEDULE FOR DOOR TYPE AND FRAME ELEVATIONS FOR GLASS TYPE
SEE PLAN
ALUM. STOREFRONT DOOR / WINDOW FRAME SYSTEM
4 1/2"
METAL RUNNER TRACK
SEE PLAN
METAL EDGE TRIM BOTH SIDES
SHIM
2"
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREET
LA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sheet T
itle
:
Pro
ject Location:
Pro
ject T
itle
:
11/2/2018 10:57:38 AM
A511
MPL/JTD
18022
OCTOBER 19, 2018
DO
OR
-WIN
DO
W D
ET
AIL
S
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025 T
ow
n S
treet
Pre
nti
ce,W
I 54556
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
No. Description Date
1 1/2" = 1'-0"1OH DOOR HEAD DETAIL
1 1/2" = 1'-0"2OH DOOR JAMB DETAIL
1 1/2" = 1'-0"3WDO. HEAD/ROOF DETAIL
1 1/2" = 1'-0"4WDO. JAMB DETAIL
1 1/2" = 1'-0"5WDO. HEAD DETAIL
1 1/2" = 1'-0"6WDO. MULLION DETAIL
1 1/2" = 1'-0"8WDO. HEAD DETAIL
1 1/2" = 1'-0"9WDO. JAMB DETAIL
1 1/2" = 1'-0"10WDO. MULLION/WALL DETAIL
1 1/2" = 1'-0"11WDO. SILL DETAIL
1 1/2" = 1'-0"12OH DOOR HEAD DETAIL
1 1/2" = 1'-0"13OH DOOR JAMB DETAIL
1 1/2" = 1'-0"14OH DOOR SILL DETAIL
1 1/2" = 1'-0"15WDO. HEAD DETAIL
1 1/2" = 1'-0"16WDO. JAMB DETAIL
1 1/2" = 1'-0"17WDO. SILL DETAIL
1 1/2" = 1'-0"18DOOR HEAD/JAMB DETAIL
1 1/2" = 1'-0"19DOOR HEAD/JAMB DETAIL
BID
PA
CK
AG
E 3
DETAIL 7 NOT USED
ALTERNATE ALTERNATE ALTERNATE
ALTERNATE ALTERNATE ALTERNATE
BID PACKAGE 3ADDENDUM 2
1
1111
B3b
8 3
/4"
HM DOOR AND FRAME- SEAL PERIMETER -BOTH SIDES - FILL FRAME W/ GROUT
JAMB ANCHOR
2" CMU
EXIST. 12" CMU
4"
E STAGE FLOOR-EAST
103'-2"
FINISH FLOOR100'-0"FIRST FLOOR100'-0"
4" INFILL100'-4"
FINISH FLOOR100'-0"FIRST FLOOR100'-0"
4" INFILL100'-4"
A
A1a
B3b
FIRST FLOOR100'-0"
FINISH FLOOR100'-0"FIRST FLOOR100'-0"
4" INFILL100'-4"
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREET
LA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sheet T
itle
:
Pro
ject Location:
Pro
ject T
itle
:
11/2/2018 10:57:42 AM
A512
Author
18022
OCTOBER 19, 2018
DO
OR
-WIN
DO
W D
ET
AIL
S
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025 T
ow
n S
treet
Pre
nti
ce,W
I 54556
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
No. Description Date
1 1/2" = 1'-0"1127A 143A Door Hd
1 1/2" = 1'-0"3127A 143A Dr Jm 1
1 1/2" = 1'-0"2127A 143A Dr Jm 2
1 1/2" = 1'-0"4DOOR JAMB DETAIL
1 1/2" = 1'-0"5149B 249A Dr Hd
1 1/2" = 1'-0"6149B 249B Dr Jm 2
1 1/2" = 1'-0"7DOOR JAMB DETAIL
1 1/2" = 1'-0"8149B Dr Sl
1 1/2" = 1'-0"9210 213 222 Dr Hd
1 1/2" = 1'-0"10210 213 222 Dr Sl 2
1 1/2" = 1'-0"11223 Dr Hd
1 1/2" = 1'-0"12223 Dr Sl
1 1/2" = 1'-0"13239 Dr Hd
1 1/2" = 1'-0"14DOOR JAMB DETAIL
1 1/2" = 1'-0"15239 Dr Sl
1 1/2" = 1'-0"16253 ABC Hd
1 1/2" = 1'-0"17253ABC Dr Jm
1 1/2" = 1'-0"18253ABC Sl
1 1/2" = 1'-0"19253DEF Dr Hd
1 1/2" = 1'-0"20253 DEF Dr Sl
BID PACKAGE 3ADDENDUM 2
BID
PA
CK
AG
E 3
E STAGE FLOOR-WEST
104'-0" JOIST BRG114'-0"
MEZZANINE114'-7 1/2"
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREET
LA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sheet T
itle
:
Pro
ject Location:
Pro
ject T
itle
:
11/2/2018 10:57:44 AM
A513
Author
18022
OCTOBER 19, 2018
DO
OR
-WIN
DO
W D
ET
AIL
S
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025 T
ow
n S
treet
Pre
nti
ce,W
I 54556
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
No. Description Date
1 1/2" = 1'-0"1270A Dr Hd
1 1/2" = 1'-0"2270A Dr Sl
1 1/2" = 1'-0"3280A Dr Hd
1 1/2" = 1'-0"4280A Dr Jm
1 1/2" = 1'-0"5280A Dr Sl
1 1/2" = 1'-0"6Ctr Dr hd 233B
1 1/2" = 1'-0"7Ctr Dr Jm 233B
1 1/2" = 1'-0"8Ctr Dr Sl 233B
BID PACKAGE 3ADDENDUM 2
BID
PA
CK
AG
E 3
A2
MASONRY PIER-SEE STRUCTURAL
D3
EXISTING EXTERIORWALL
SAWTOOTH IN BRICKAS REQUIRED TO MEET
NEW PRECAST
BACKER ROD AND SEALANT
EXISTING EXTERIORWALL
A2
BACKER ROD AND SEALANT
D3
1"
SEALANT
SECURE CONTINUOUSANGLE TO EXISTING BRICK
W/ ANCHOR BOLTS
GROUT SOLID
D27
D2
D2D31
D31
2'-2"
10
1/2
"
CASEWORK -SEE PLANS ANDELEVATIONS
CASEWORK -SEE PLANS ANDELEVATIONS
1'-0
"
B2c
B2cD2
1'-0 1/2"
D2
DEFLECTION BEAD
DEFLECTION BEADEXISTINGCOLUMN
D3
10 1/2"
11
1/8
"
HOLD STUDSTIGHT TOCOLUMN
TO 4" ABOVEFINISH CLG
FIRST FLOOR100'-0"
4" INFILL100'-4"
B2
BOND BREAK @PERIMETER - SEESTRUCT.
4"
D3
CONC. SLAB - SEESTRUCT.
EXIST. CONC. SLAB
VAPOR BARRIER
COMPACTED FILL
FLOOR INSULATION
RADIANT FLOORTUBING
CONCRETE SLAB
SIMILAR CONDITION AT DOOR AND WINDOW HEADS AND WINDOW SILLS
SEE STRUCTURAL FOR LINTEL - TYPICAL
FLEXIBLE MEMBRANE FLASHING
MIN
.
1 1
/2"
TURN UP FLASHING TO FORM END DAM AT EACH END OF WINDOW HEAD LINTEL AT MASONRY HEAD JOINT
CORNERS SHALL BE FOLDED INTO "BREADPAN" STYLE CORNER
PITCH
BEARING DEPTH
MATCH
PREFINISHED SHEETMETAL LINTEL FLASHINGSET IN SEALANT EXTENDTO DAYLIGHT
B3c
EXTG JOIST BRG111'-4"
2"
SUSPENDED GYP BDCEILING SYSTEM
4"
SHOWER CURTAINROD @ 7'-0" AFF
A11
A10
2"
CLOSE OFF CAVITY WITH EXTRUDEDINSULATION
1'-0
"
A4
A2PREFINISHED METAL JAMB TRIM- BY INSTALLER
BACKER ROD AND SEALANT
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREET
LA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
www.hsrassociates.com
Consultant:
Revisions:
Graphic Scale:
VARIES
Sheet T
itle
:
Pro
ject Location:
Pro
ject T
itle
:
11/2/2018 10:57:48 AM
A514
MPL/JTD
18022
OCTOBER 19, 2018
MIS
C D
ET
AIL
S
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025 T
ow
n S
treet
Pre
nti
ce,W
I 54556
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
No. Description Date
1 1/2" = 1'-0"1WALL PLAN DETAIL
1 1/2" = 1'-0"2WALL PLAN DETAIL
1 1/2" = 1'-0"4ROOF LEADER DETAIL
1 1/2" = 1'-0"6ROOF LEADER DETAIL
1 1/2" = 1'-0"7LOUNGE COLUMN
1 1/2" = 1'-0"8RAISED FLOOR DETAIL
1 1/2" = 1'-0"9IN-FLOOR HEAT DETAIL
1" = 1'-0"10HEAD FLASHING DETAIL
1 1/2" = 1'-0"11OPENING JAMB DETAIL
BID
PA
CK
AG
E 3
1 1/2" = 1'-0"12BULKHEAD DETAIL
1 1/2" = 1'-0"13SKYLIGHT DETAIL
1 1/2" = 1'-0"14CEILING DETAIL
1 1/2" = 1'-0"15BULKHEAD DETAIL
1 1/2" = 1'-0"16BULKHEAD DETAIL
1 1/2" = 1'-0"3ROOF LEADER DETAIL
1 1/2" = 1'-0"5ROOF LEADER DETAIL
1 1/2" = 1'-0"17PRECAST OFFSET DETAIL
1 1/2" = 1'-0"18MTL PANEL-PRECAST DETAIL
BID PACKAGE 3ADDENDUM 2
(e)1
8J7
W/ (
3) L
INE
S O
F B
RID
GIN
G
(e)1
6WF
40(e
)14W
F34
(e)1
4WF
30(e
)16W
F36
1'-9
" (V
.I.F
.)(5
) E
Q S
PA
AT
4'-0
" =
20'
-0"
(e)1
6WF
40
(e)1
6WF
36
(e)1
8J6
W/ (
4) L
INE
S O
F B
RID
GIN
G
(e)1
8J6
W/ (
4) L
INE
S O
F B
RID
GIN
G
12'-0
" (V
.I.F
.)4'
-0"
4'-0
"4'
-3"
4'-3
"
(e)2
2GA
ST
EE
L R
OO
F D
EC
K
(e)2
2GA
ST
EE
L R
OO
F D
EC
K
4S810R
______
3S810R
______
REINFORCE WEBS OF THESE (4) JOISTS 5'-0" FROM EACH END (SEE 10/S811) AND 18'-0" OF T&B CHORDS (CENTERED ON JOIST SPAN, SEE 11/S811).
(2) CHANNELS UNDER RTU, EXTENDING 1'-0" PAST EACH END OF RTU (OVER (4) JOISTS). SEE 4/S810.
(4) CHANNELS UNDER RTU, EXTENDING 1'-0" PAST EACH END OF RTU (OVER (2) JOISTS). SEE 4/S810.
4S810R
______
3S810R
______
REINFORCE WEBS OF THESE (4) JOISTS 6'-0" FROM EACH END (SEE 10/S811) AND 20'-0" OF T&B CHORDS (CENTERED ON JOIST SPAN, SEE 11/S811).
4'-1
"22
'-0"
4'-
1"REINFORCE 22'-0" OF THIS GIRDER (SEE
12/S811)
L13
MP1
L7L7
8"
2'-0
"
VE
RIF
Y I N
FIE
LD
22 S
PA
@ 4
'-0"
= 8
8'-0
"4"
(e)
18J7
W/ (
3) R
OW
S B
RID
GIN
G
(e)1
2WF
27 (
111'
-4")
SH
OR
E E
XIS
TIN
G F
RA
MIN
G A
S R
EQ
'D F
OR
INS
TA
LAT
ION
OF
NE
W W
ALL
AN
D M
AS
ON
RY
PIE
R
L5
W12
X30
HSS3x3x3/8BP2
HSS3x3x3/8BP2
29'-4
" (V
.I.F
.)
VERIFY w/ ARCH.
19S811
______
13
(e) 8" PRECAST PLANK
14S810R
______
14S810R
______
W16X40
W16X40
W12
X30
W12
X30
W12X30
W12
X30
W12X30W12X30
W21X73114'-0"
L12
L12
L12
L12
L12
18S811
______
TYP.
18S811
______
TYP.
14
C1 / W14x90
W18
x35
(4,2
,4)
c=1"
(12
0'-0
")
36G
8N 1
2.5K
INDICATES BEAM FRAMING OVER OR THRU HSS OR WF COLUMN
INDICATES BEAM FRAMING INTO SIDE OF HSS OR WF COLUMN
INDICATES BEAM-TO-COLUMN MOMENT FRAME CONNECTION
COLUMN MARK / COLUMN SIZE
TOP OF STEEL ELEVATION
BEAM DESIGNATION
JOIST GIRDER DESIGNATION
INDICATED LOCATION OF BEAM SPLICE
INDICATES EXISTING BEAM / JOIST FRAMING INTO SIDE OF NEW GIRDER
INDICATES BEAM / JOIST FRAMING INTO SIDE OF GIRDER
INDICATES BEAM / JOIST FRAMING OVER GIRDER
INDICATES MOMENT CONNECTION BETWEEN BEAMS ACROSS GIRDER IN SAME HORIZONTAL PLANE
STRUCTURAL STEEL LEGEND
SHOP CAMBER
FIELD APPLIED SHEAR STUDS BETWEEN BEAM ENDS AND/OR CONCENTRATED LOADS
MEMBER SIZES OR MARKS WITH A PREFIX OF "(e)" ARE EXISTING ELEMENTS
(e)W
18x3
5
ROOF FRAMING KEY NOTES
1
2
3
4
SEE 8A/S810 FOR REINFORCING AT BOUNDARY ELEMENTS OF THIS WALL SEGMENT
SEE 8B/S810 FOR REINFORCING AT BOUNDARY ELEMENTS OF THIS WALL SEGMENT
SEE 8C/S810 FOR REINFORCING AT BOUNDARY ELEMENTS OF THIS WALL SEGMENT
SHEAR TAB CONNECTION TO W24
REFER TO DETAIL 18/S810 FOR VENEER LINTEL
COLUMN (SEE PLAN) UP TO BOTTOM OF LINTEL
JOISTS SELECTED BASED ON FULL DRIFT FOR FULL LENGTH (SL = 116 PSF)
VERIFY EXISTING FRAMING CONSTRAINTS AND DIMENSIONS IN FIELD BEFORE JOIST FABRICATION
5/8" PLYWOOD OVER 10" CFMF FLOOR JOISTS AT 16" O.C.. FINAL MEZZANINE DESIGN BY CFMF SUPPLIER. 125 PSF LIVE LOAD. FINISH FLOOR ELEV = 108'-9 1/4"
HEADER BY CFMF DESIGNER CAPABLE OF TRANSFERRING WIND LOAD AROUND OPENING.
BEAM RUNS AT A SKEW (3" SKEW OVER 24'-11" COLUMN TO COLUMN LENGTH). EXTEND JOIST SEATS AS NECESSARY TO MEET MINIMUM BEARING REQUIREMENTS.
REFER TO DETAIL 16/S811 FOR VENEER LINTEL.
FOLDING PARTITION, SEE ARCHITECTURAL PLANS. STRUCTURAL BASIS OF DESIGN IS HUFCOR 630 SERIES (10 PSF WEIGHT OR LESS).
FOLDING GLASS PARTITION, SEE ARCHITECTURAL PLANS. STRUCTURAL BASIS OF DESIGN IS HUFCOR SERIES GA1 (10 PSF WEIGHT OR LESS).
MINIMIZE DEMO OF EXISTING ELEMENTS REQUIRED FOR INSTALLATION OF NEW FRAMING AND FOUNDATIONS.
STOP MOMENT FRAME BEAM AT FACE OF MASONRY WALL (LEAVE 1/2" GAP).
SEE 22/S811 FOR BEAM PASSING OVER COLUMN DETAIL.
SEE 1/S002 FOR TYPICAL BEAM TO COLUMN MOMENT CONNECTION DETAIL.
5
6
7
8
9
10
11
12
13
14
15
16
17
18
ROOF FRAMING PLAN NOTES
1. TOP OF BASE STEEL (JOIST BEARING) ELEVATION = (XXX'-X").
2. ROOF DECKING SHALL BE 1 1/2" x 20GA WIDE RIB PRIME PAINTED METAL ROOF DECK FASTENED TO SUPPORTING STRUCTURE USING 36/4 PATTERN OF ANY OF THE ATTACHMENT METHODS SHOWN IN DETAIL 1/S810 WITH #10 TEK SIDELAP FASTENERS AT 18" OC. PROVIDE DECK WITH THE FOLLOWING PROPERTIES:
THICK = 0.0358 in Ip = 0.201 in4/ft S p = 0.234 in3/ftF y = 33 KSI In = 0.222 Sn = 0.247 in3/ft
INSTALL DECK UNDER 3 OR MORE SPAN CONDITIONS.
3. ROOF DECKING SHALL BE 1 1/2" x 20GA WIDE RIB ACOUSTIC PRIME PAINTED METAL ROOF DECK FASTENED TO SUPPORTING STRUCTURE USING 36/4 PATTERN OF ANY OF THE ATTACHMENT METHODS SHOWN IN DETAIL 1/S810 WITH #10 TEK SIDELAP FASTENERS AT 18" OC. PROVIDE DECK WITH THE FOLLOWING PROPERTIES:
THICK = 0.0358 in Ip = 0.201 in4/ft S p = 0.234 in3/ftF y = 33 KSI In = 0.222 Sn = 0.247 in3/ft
INSTALL DECK UNDER 3 OR MORE SPAN CONDITIONS.
4. PROVIDE 8" HIGH BOND BEAM WITH (2) #4 CONTINUOUS AT AND ADJACENT TO JOIST BEARING ELEVATIONS UNLESS NOTED OTHERWISE. WHERE JOIST BEARING IS NOT AT COURSING, PROVIDE PARTIAL HEIGHT BLOCK GROUTED SOLID TO TOP OF BOND BEAM. WIDTH OF BOND BEAM TO MATCH WALL THICKNESS AND IS TO RUN CONTINUOUS THROUGH CONTROL JOINTS. PROVIDE CORNER BARS WHERE THEY OCCUR AND LAP ALL BOND BEAM STEPS A MINIMUM OF 24".
5. JOIST SUPPLIER TO PROVIDE CONTINUOUS TOP AND BOTTOM CHORD HORIZONTAL ANGLE BRIDGING AS REQUIRED. PROVIDE DIAGONAL X-BRIDGING WHERE INDICATED.
6. PROVIDE ANGLE FRAME SUPPORT AT ALL ROOF OPENINGS IN ACCORDANCE WITH DETAIL 3/S810.
7. REFER TO SHEET S002 FOR COLUMN SCHEDULE.
8. BRACE TOP OF NON-LOAD BEARING CMU WALLS IN ACCORDANCE WITH DETAILS 11/S810 & 12/S810.
9. ALL 8" CMU WALLS SHALL BE REINFORCED WITH (1) #5 VERTICAL (FULL WALL HEIGHT GROUTED) AT 48" O.C. UNLESS NOTED OTHERWISE ON PLAN.
Contractors are responsible for the means, methods, techniques,
sequences and procedures of construction including, but not limited to, temporary supports, shoring, forming to support imposed loads and
other similar items.
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREETLA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
www.hsrassociates.comConsultant:
Revisions:
Graphic Scale:
VARIES
She
et T
itle:
Pro
ject
Loc
atio
n:
Pro
ject
Titl
e:
project number: 1180371
11/2/2018 10:28:43 AM
S202R
raSmith
18022
OCTOBER 19, 2018
FR
AM
ING
PL
AN
S -
UN
IT A
& E
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025
To
wn
Str
eet
Pre
nti
ce,W
I 545
56
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
SCALE: 1/8" = 1'-0"S202R
2 UNIT A FRAMING PLANSCALE: 1/8" = 1'-0"S202R
1 UNIT E FRAMING PLAN - ALTERNATE ONLY
KEY PLAN
UNIT B
UNIT A
UNIT C
UNIT D
UN
IT E
No. Description DateBP3 10/19/18
3 BP3 ADD2 11/2/18
3
CL
SUPPORT
CL
SUPPORT
CL
SUPPORT
CL
SUPPORT
6"
6"
DECK LENGTH (3) S
PAN MINIMUM
3" MINIMUM LAP EACH END
*
*
*SEE PLAN FOR TYP FASTENER SPACING
ATTACH DECK TO SUPPORT AT 6" OC AT DECK END LAPS
ATTACH DECK AT 6" OC AT SUPPORT ADJACENT TO BUILDING PERIMETER/ EXPANSION JOINT
FASTENERS, TYPICAL SEE NOTES BELOW
PROVIDE #10 TEK SIDELAP FASTENERS IN ACCORDANCE WITH SDI RECOMMENDATIONS IF NOT INDICATED OTHER ON PROJECT DRAWINGS
FAST DECK TO SUPPORTING MEMBERS USING FASTENING METHOD INDICATED ON DRAWINGS AND ACCORDING TO THE FOLLOWING REQUIREMENTS:a. WELDING (DEFAULT UNO): ALL WEDS ARE TO BE 5/8" DIA PUDDLE WELDS. USE
WELDING WASHERS ON ALL DECKS EQUAL TO OR LESS THANK 24GA THICKNESS.
b. SCREWING: BUILDEX #12 TEK SCREWS OR EQUAL.c. POWDER-ACTUATED FASTENERS: HILTI X-HSN 24 AND X-ENP 19L15, RAMSET
265D, OR APPROVED EQUAL (SUBMIT MANUFACTURER'S LITERATURE FOR APPROVAL ON EQUAL PRIOR TO USING POWDER-ACTUATED PRODUCT).
d. PNEUMATICALLY-DRIVEN FASTENERS: PNUETEK PINS OR EQUAL (SUBMIT MANUFACTURER'S LITERATURE FOR APPROVAL ON EQUAL PRIOR TO USING PNEUMATICALLY-DRIVEN PRODUCT).
WELDS OR FASTENERS AT 8" OC AROUND PLATE PERIMETER
AT DECK OPENINGS BETWEEN 6" AND 15"Ø OR 4" AND 9" SQUARE, PROVIDE 16 GAUGE STEEL PLATE REINFORCEMENT AS SHOWN
NOTE:A) NO PLATE REINFORCEMENT REQUIRED AT DECK OPENINGS SMALLER THAN 6"Ø OR 4" SQUARE.B) FOR DECK OPENINGS LARGER THAN 13"Ø OR 9" SQUARE, PROVIDE STEEL FRAME PER TYPICAL FRAMING AT ROOF OPENINGS DETAIL
JOIST OR BEAM SPACING
MECH/PLUMBING CONTRACTOR)ROOF OPENING (VERIFY WITH
FRAME OPENING WITH L3 1/2X 3 1/2X5/16
L4X4X1/4X0'-4" LONG
STEEL JOIST OR BEAM
1" MAX
NOTE:GC TO VERIFY SIZE, SHAPE AND LOCATION OF ALL ROOF OPENINGS WITH APPROPRIATE TRADES PROVIDING TYPICAL FRAME AT ALL OPENINGS:1. LARGER THAN 13"Ø OR 9" SQUARE OR2. SUPPORTING IN EXCESS OF 60LBS
EQUIPMENT LOADS
ROOF DECK ROOF DECK
L2x2x1/4 STRUTS, FIELD LOCATE AND WELD BETWEEN TOP CHORD PANEL POINT AND BOTTOM CHORD
HANGER, BY OTHERS
NOTE:PRIOR TO INSTALLATION, VERIFY LOADS WITH ENGINEER IF ACTUAL DIFFER FROM THOSE POSTED ON DRAWINGS.
NOTE:REINFORCEMENT REQUIRED AT ALL HANGING LOADS BETWEEN BOTTOM CHORD PANEL POINTS AND AS NOTED ON PLAN.
L2x2x1/4 STRUTS, FIELD LOCATE AND WELD BETWEEN TOP CHORD PANEL POINT AND BOTTOM CHORD
NOTE:REINFORCE TOP CHORDS AT CONCENTRATED LOADS BETWEEN PANEL POINTS AS SHOWN.
METAL DECK
EQUIPMENT RAIL/UNIT, BY OTHERS
METAL DECK
3/16
____S810R
5
EQUIPMENT RAIL UNIT BY OTHERS
METAL ROOF DECK
PROVIDE C12X20.7 PLACED PARALLEL TO ROOF DECK SPAN BELOW EQUIPMENT RAIL/UNIT. (ONE PER SIDE) EXTEND CHANNELS BEYOND EQUIPMENT TO NEXT SUPPORT MEMBER
TOP FLANGE OF SUPPORTING MEMBER
3/16 3
TYPICALAT EACH
SUPPORT3/16 3
TYPICALAT EACHSUPPORT
BOND BEAM REINFORCEMENT TO BECONTINUOUS THRU CONTROL JOINTAT TOP OF WALL AND WHEREOTHERWISE NOTED
STOP ALL HORIZONTAL JOINTREINFORCEMENT SHORT OF CONTROL JOINT
CONTROL JOINTS TO BE PLACED:
1) MAXIMUM OF 6'-0" FROM CORNERALONG ONE OF THE TWO
ORTHOGONALWALLS
2) MAXIMUM OF 24'-0" OC INCLUDINGDISTANCE BETWEEN JOINTS AROUNDCORNER
3) AS OTHERWISE DETAILED ON ARCHITECTURAL DRAWINGS
FULL-DEPTHNEOPRENEJOINT INSERT
CONCRETESASH BLOCK
SEALANT OVER ROPEBACKUP, EACH SIDE
DISCONTINUE HORIZONTAL JOINT REINFORCEMENTAT CONTROL JOINTS
CMU WALL WITH HORIZONTAL JOINT REINFORCEMENT
COMPRESSIBLE FILLER, EACH SIDE
FILL CORE SOLID WITHGROUT, EACH SIDE
MATCH VERTICAL WALLREINFORCEMENT, SEEPLAN, EACH SIDE
3/8"
1"
1 1/2"1 1/2"
1 1/
2"
OC
@ 8
"1
1/2"
3/16 3
1/2"x6"x(FLANGE WIDTH +3") BRG PLATE CENTERED ON BEAM w/ (2) 3/4" x6" DIA HWS
GROUT (2) #5 BARS SOLID IN EACH CMU CELL (1 EA FACE) FULL HEIGHT FOR ALL CELLS WITHIN 16" WIDE AREA CENTERED ON BEAM
NOTES:1. DETAIL APPLIES AT ALL BEAMS BEARING ON WALL EXCEPT FOR
LINTELS AND WHERE OTHERWISE NOTED.2. WHERE BEAM BUTTS INTO AND BEARS ON PARALLEL WALL, PROVIDE
1/2"x12"x(FLANGE WIDTH +3", BUT NO GREATER THAN WALL WIDTH) BEARING PLATE SIMILAR TO ABOVE CHANGING 7" BEARING LENGTH TO 11".
SEE PLAN
3/4" DIAMETER x 3" LONGTHREADED STUD WELDED TO PLATE, FINGER-TIGHTEN NUT
BEAM WITH LONGSLOTTED HOLES
T/STEEL
EQ EQ
WHERE TOP OF MASONRY WALL IS ABOVE JOIST BOTTOM CHORDS, ELIMINATE THE TWO HANGERS AND LAY HORIZONTAL ACROSS JOIST BOTTOM CHORD. WHERE IT EXTENDS TO UNDERSIDE OF DECK, ELIMINATE DIAGONAL ALSO (MAINTAIN STATED CLEARANCE BY POCKETING CMU WALL AROUND HORIZONTAL)
L2X2X3/16 HORIZONTAL
L2X2X3/16 HANGER (TYP)
L2X2X3/16 DIAGONAL
NEW/EXISTING BAR JOIST
L5X3X1/4X0'-6" 9LLV) WELD TO ANGLE (TYPICAL)
NON-LOAD BEARING CMU WALL
1" MINIMUM CLEAR BETWEEN TOP OF NON-LOAD BEARING MASONRY WALLS AND BOTTOM STEEL ANGLE
35° MIN3/16 2
3/16TYP
NOTE:1. MAXIMUM SPACING OF BRACES IS TO BE MEASURED PARALLEL
TO PARTITION LENGTH2. MAXIMUM SPACING OF BRACES IS TO BE 15 FT FOR 6" CMU
WALLS AND 20 FT FOR 8" CMU WALLS3. INTERSECTION MASONRY CROSS-WALLS TIED TOGETHER SERVE
AS BRACES4. ADDITIONAL L4X3X1/4 SUBFRAMING MEMBERS AT BOTTOM OF
ROOF FRAMING MAY BE REQUIRED FOR SOME LOCATIONS
GROUT TOP COURSE SOLID. SEE ARCH FOR FILLER MATERIAL BETWEEN TOP OF WALL & DECK
NOTE: 1. MAXIMUM SPACING OF BRACES IS TO BE
MEASURED PARALLEL TO PARTITION LENGTH.
2. MAXIMUM SPACING OF BRACES IS TO BE 15 FT. FOR 6" CMU WALLS AND 20 FT. FOR 8" CMU WALLS.
3. INTERSECTING MASONRY CROSS-WALLS TIED TOGETHER SERVE AS BRACES.
4. ADDITIONAL L4x3x1/4 SUBFRAMING MEMBERS AT BOTTOM OF ROOF FRAMING MAYBE REQUIRED FOR SOME LOCATIONS.
WHERE TOP OF MASONRY WALL IS ABOVE JOIST BOTTOM CHORD, ELIMINATE L2X2'S AND WELD L5X3 DIRECTLY TO JOIST BOTTOM CHORD (MAINTAIN STATED CLEARANCE BY POCKETING CMU AROUND JOIST BOTTOM CHORD)
L2X2X3/16
NEW/EXISTING BAR JOIST
L5X3X1/4X0'-6" (LLV) TYP.
NON-LOAD BEARING CMU WALL
1" MIN CLEAR BETWEEN TOP OF WALL AND BOTTOM OF ANGLE, ROOF DECK AND/OR BAR JOIST
1
1 MAX
3/16" 2 (MIN)
3/16" 2
DECK BRG
MASONRY WALL
METAL ROOF DECK
JOIST BRIDGING, WELD TO ANGLE
L2x2x3/16x(JOIST DEPTH-5") FASTENED TO MASONRY WALL USING 1/2" DIA. (ANCHOR SIZE XXX) DROP-IN OR SLEEVE ANCHORS. PROVIDE (2) ANCHORS FOR ANGLE LENGTHS LESS THAN 1'-0", OTHERWISE PROVIDE 3 ANCHORS
L4x4x5/16 xCONT. ANCHORED TO MASONRY WALL IN POSITION SHOWN USING 1/2" DIA. x 5" HILTI SLEEVE ANCHORS OR 1/2" DIA. LOK-BOLT SPACED AT 24" OC.
SEE PLAN
PROVIDE CONT. BOND BREAKER BETWEEN WALL AND SLAB
DECK BRG
L4x4x3/8 x CONT. ATTACH TO CMU WALL USING 1/2" x 5" HILTI SLEEVE ANCHORS OR 1/2" DIA LOK-BOLT AT 24" O.C.
BOND BEAM WITH (2) #5 CONTINUOUS
CONCRETE SLAB ON STEEL FORM DECK. PROVIDE CELL CLOSURES AT END OF DECK AS REQUIRED
CMU WALL. SEE PLAN FOR REINFORCEMENT REQUIREMENTS
3/16 4
LINTEL WITH 8" BEARING (TYPICAL)
BEARING PLATE IF REQUIRED (TYPICAL)
GROUT CMU CELL BELOW LINTELBEARING SOLID DOWN TO SUPPORTOR AS NOTED OTHERWISE IN LINTEL SCHEDULE (TYPICAL)
HORIZONTAL CAULKJOINT AT BOTTOMOF LINTEL
PLACE TEFLON OR PLASTICPAD BETWEEN BOTTOM OF LINTEL AND BEARING SURFACE
CONTROL JOINT LOCATED AT END OF LINTEL CAPABLE OFTRANSFERRING LATERAL LOADSACROSS JOINT TO FULL HEIGHTPORTION OF WALL
B/ANGLE
VWA
7 5/8"
1/8"3"5"
1/4" 8 3/8"
L5X5X3/8 ANGLE SHOP WELDED TO CHANNEL; ENTIRE ASSEMBLY TO BE GALVANIZED AFTER WELDING
3/4"DIA THREADED ROD, DRILLED & EPOXIED WITH 5 1/2" EMBEDMENT
CMU LINTEL, SEE SCHEDULE
1/8" NEOPRENE WASHER FOR THERMAL BREAK
3/4"DIA SIMPSON TITEN HD ANCHOR WITH MINIMUM 5 1/2" EMBEDMENT
BRICK VENEER, SEE ARCH
C12X20.7 CHANNEL X 1'-1" TALL, WITH TOES POINTING OUT
AIR/VAPOR BARRIER MUST BE INSTALLED PRIOR TO SETTING CHANNELS
1 1/
2"
2 1/
2"8"
2 1/
2"
2 1/2" RIGID INSULATION
EQ. 4'-0" 4'-0" EQ.
VERIFY w/ ARCH.
ROUGH OPENING
(3) CHANNELS
ANGLE
CHANNEL SPACING
3-12
3-121/8" PLATE X 16" WIDE WELDED TO ANGLE
B/ANGLE
113'-4" VWA
8 3/8" 7 5/8"
3"
1/8"
5"
1/4"
L5X5X3/8 ANGLE SHOP WELDED TO CHANNEL; ENTIRE ASSEMBLY TO BE GALVANIZED AFTER WELDING
3/4"DIA THREADED ROD, DRILLED & EPOXIED WITH 5 1/2" EMBEDMENT
L2 LINTEL (SEE SCHEDULE)
1/8" NEOPRENE WASHER FOR THERMAL BREAK
3/4"DIA SIMPSON TITEN HD ANCHOR WITH MINIMUM 5 1/2" EMBEDMENT
BRICK VENEER, SEE ARCH
C12X20.7 CHANNEL X 1'-1" TALL, WITH TOES POINTING OUT
AIR/VAPOR BARRIER MUST BE INSTALLED PRIOR TO SETTING CHANNELS
1 1/
2"10
1/2
"8"
2 1/
2"
2 1/2" RIGID INSULATION
EQ. 4'-0" 4'-0" EQ.
VERIFY w/ ARCH.
ROUGH OPENING
(3) CHANNELS
ANGLE
CHANNEL SPACING
3-12
3-12
1/8" PLATE X 16" WIDE WELDED TO ANGLE (CONTINUOUS OVER POST)
W8X28
FACE SHELLS AS REQUIRED
1/2"x6" HAS AT 24" O.C.
VERTICAL BARS, SEE PLAN
3
METAL ROOF DECK
DECK BRG2 1/
2"
5"
BOND BEAM WITH (2) #5 CONTINUOUS
L4x4x5/16 x CONT. ATTACH TO CMU WALL USING 1/2" x 5" HILTI SLEEVE ANCHORS OR 1/2" DIA LOK-BOLT AT 24" O.C.
GROUT FIRST (2) CELLS SOLID WITH (1) #5 CENTERED. (THIS REINFORCING APPLIES IN BOTH DIRECTIONS AT BUILDING CORNERS).
1'-4
"
8" CMU WALL
GROUT FIRST CELL SOLID WITH (1) #5 CENTERED. (THIS REINFORCING APPLIES IN BOTH DIRECTIONS AT BUILDING CORNERS).
8"
8" CMU WALL
8B8A
GROUT FIRST (3) CELLS SOLID WITH (1) #5 CENTERED. (THIS REINFORCING APPLIES IN BOTH DIRECTIONS AT BUILDING CORNERS).
2'-0
"
8" CMU WALL
8C
OPENING
LINTEL SCHEDULEJAMB, SEE
DRILL AND ANCHOR (WITH HILTI HIT HY-200 ORPOWERS AC100 ADHESIVE) (2) #5x1'-6" DOWELS 3 1/2" INTO EXTG WALL OR SLAB. SEE LINTEL SCHEDULE FOR JAMB LENGTH.
INSTALL NEW REINFORCEMENT, SEE JAMB SCHEDULE FOR SIZE. SPLICE BARS IN 6'-0" TO 8'-0" LENGTHS.IF EXISTING VERTICAL WALL REINFORCEMENT IN GROUTED CELL IS PRESENT THIS IS NOT REQUIRED.
SAW CUT AND REMOVE CMU WALL AS REQUIRED TO PROVIDE OPENING AND LINTEL (SHORE AS REQUIRED)
IN THE AREA OF OPENING, SAW CUT AND REMOVE EXISTING FACE SHELLS AS NECESSARY TO INSTALL NEW REINFORCEMENT AND TO CLEAN OUT ALLVERTICAL CELLS
RESTORE THE FACE OF THE CMU BY INSTALLING SOAP BLOCKS AND NEW BLOCKS AS NECESSARY. SURFACE TREATMENT OF NEW BLOCK TO MATCH ORIGINAL
IF EXISTING VERTICAL WALL REINFORCEMENT INGROUTED CELL IS PRESENT, INSTALL 1'-6" LINTEL DOWELS TO MATCH SIZE AND QUANTITY OF NEW CMU LINTEL REINFORCEMENT. DRILL AND ANCHOR DOWELS WITH HILTI HIT HY-200 ADHESIVE 9" INTO EXISTING RIENFORCED CELL AND CONTACT LAP SPLICE DOWELWITH NEW CMU LINTEL REINFORCEMENT (NOT REQUIREDIF PRECAST LINTEL IS USED)
INSTALL NEW LINTEL, SEE SCHEDULE
SAWCUT AND REMOVE FACE SHELLS IN THE COURSE ABOVETHE LINTEL AS NECESSARY TO GROUT THE NEW LINTEL
CLEAN OUT ALL CELLS TO RECEIVE NEW REINFORCEMENT, REMOVE ALL DEBRIS, INSULATION, LOOSE MORTAR AND MORTAR WHICH OBSTRUCTS THE FLOW OF GROUT PRIOR TO INSTALLATION OF REINFORCEMENT
GROUT SOLID ALL CELLS CONTAINING REINFORCEMENT WITH FINE OR COURSE GROUT USING THE LOW-LIFT METHOD.GROUT TO BE CONSOLIDATED USING VIBRATORS
FINISH FLOOR
T/MASONRY OPENING
CONTRACTOR NOTES:1) SHORE EXTG STRUCTURE AS REQUIRED 2) RE-POINT ALL AFFECTED MORTAR JOINTS
ROOF JOIST, SEE PLAN
T/STEEL
VERIFY w/ ARCH.& PARTITION SUPPLIER
L2x2x1/4 BRACE FROM BOTTOM FLANGE OF BEAM TO JOIST PANEL POINT. BRACE AT EVERY JOIST, ALTERNATE SIDES OF BEAM. VERIFY LENGTH IN FIELD. AS REQUIRED PROVIDE STRUT TO TOP CHORD PANEL POINT OF EXISTING JOIST, REFERENCE 4/S810.1/4
3/16
FULL DEPTH 3/8" STIFFENER AT EACH BRACE. VERIFY SPACING IN FIELDSTEEL BEAM, SEE PLAN
Contractors are responsible for the means, methods, techniques,
sequences and procedures of construction including, but not limited to, temporary supports, shoring, forming to support imposed loads and
other similar items.
Key Plan:
HSR Project Number:
Project Date:
Drawn By:
Last Update:
HSR ASSOCIATES INC.100 MILWAUKEE STREETLA CROSSE, WISCONSIN
PHONE: 608.784.1830FAX: 608.782.5844
www.hsrassociates.comConsultant:
Revisions:
Graphic Scale:
VARIES
She
et T
itle:
Pro
ject
Loc
atio
n:
Pro
ject
Titl
e:
project number: 1180371
11/2/2018 10:28:45 AM
S810R
raSmith
18022
OCTOBER 19, 2018
FR
AM
ING
DE
TA
ILS
AD
DIT
ION
AN
D R
EM
OD
EL
ING
1025
To
wn
Str
eet
Pre
nti
ce,W
I 545
56
PR
EN
TIC
E S
CH
OO
L D
IST
RIC
T
SCALE: 12" = 1'-0"S810R
1 METAL DECK FASTENING DETAILSCALE: 1" = 1'-0"S810R
2 TYPICAL ROOF DECK OPENINGSCALE: 1" = 1'-0"S810R
3 TYPICAL FRAMING AT ROOF OPENINGSSCALE: 1" = 1'-0"S810R
4 CONCENTRATED LOAD AT JOISTSCALE: 1" = 1'-0"S810R
5 EQUIPMENT RAIL SUPPORT
SCALE: 12" = 1'-0"S810R
6
KEYED CMU CONROL JOINT (NEOPRENEINSERT, REBAR ADJACENT TO CJ)
SCALE: 1 1/2" = 1'-0"S810R
7 CMU WALL-CONTROL JOINT
SCALE: 1" = 1'-0"S810R
14 BEAM BRG DETAIL (CMU)
SCALE: 1" = 1'-0"S810R
12 NON-LOAD BEARING CMU PARALLEL TO JOISTSSCALE: 3/4" = 1'-0"S810R
11 NON-LOAD BEARING CMU PERPENDICULAR TO JOISTS
SCALE: 1 1/2" = 1'-0"S810R
17 TYPICAL ROOF DECK END WALL DETAILSCALE: 1" = 1'-0"S810R
16
TYPICAL FLOOR DECKBEARING ANGLE AT WALL
SCALE: 1/2" = 1'-0"S810R
10 LINTEL BEARING DETAIL
SCALE: 1 1/2" = 1'-0"S810R
18 SECTIONSCALE: 1 1/2" = 1'-0"S810R
19 SECTIONSCALE: 1" = 1'-0"S810R
15
TYPICAL DECKBEARING ANGLE AT WALL
SCALE: 3/4" = 1'-0"S810R
8 CMU WALL REINFORCEMENTSCALE: 1/4" = 1'-0"S810R
9 NEW OPENING IN EXISTING CMU WALL
SCALE: 3/4" = 1'-0"S810R
13 PARTITION BEAM BRACING
No. Description DateBP3 10/19/18
3 BP3 ADD2 11/2/18