Do We Really Needthe 100-meter Limit?

Igor G. Smirnov, RCDDSignamax, Inc.

Dr. Andrey B. SemenovIT Co.

Page 2: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Preface• Statistical data and calculations in this

presentation

– based on information collected by:

IT Co.

AESP East Europe

Signamax, Inc.

– from warranted installations

over a 10-year period

500,000 cabling links/channels analyzed

Page 3: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

100-meter Limit Background• Bell System Practices, SECTION 518-010-101 (1976)• Forerunner of structured cabling standards, it defined:

– Cabling topology– Telecom spaces:

Terminal Room Equipment Room Apparatus Closet Riser Closet Satellite Closet

– Cross-connections and interconnections– Administration, and…

Page 4: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Bell System Practices

…and

– Cabling distances:

“3. PLANNING

3.03 For optimum working conditions, one

closet should be provided for each 10,000

square feet of usable floor space. The cabling

should be laid out so that all cable runs between the

apparatus closet and the key equipment

are as short as possible…”

Page 5: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Bell System Practices“…Loop resistance should not exceed 50 ohms or

approximately 1000 feet of 24-gauge cable.”

ApparatusCloset

SatelliteLocation

EquipmentRoom

ApparatusCloset

2,500 ft2 2,500 ft2

10,000 ft2 10,000 ft2

SatelliteCloset

SatelliteCloset

SatelliteLocation

SatelliteLocation

SatelliteLocation

Page 6: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Bell System Practices“…Loop… should not exceed …approximately 1000 feet…”That means that technically it was possible to service an area up to 1000 ft in diameter or 500 ft x 500 ft (250,000 ft2)

AC

500 f

t

500 f

t

AC

250 ft

250 ft

250

ft

250

ft

KSU

KSU

Page 7: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Bell System Practices• AT&T Cabling Systems Engineering Group,

building its verdict on its vast research data, showed that:

– 98 % of all phone sets in commercial buildings were located no more than:

150 ft (45 m) away from switchboards dimensionally, or

300 ft (about 100 m) in terms of cable length

Page 8: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Bell System Practices• Elegant explanation was suggested by Donna

Ballast in CI&M (August 2006):200 ft: worst-case ceiling pathway from TC to WA

45 ft: drop from ceiling in TC and Work Area

33 ft: Work Area and equipment cords

10 ft: slack in the TC

10 ft: slack in the Work Area

30 ft: de-rating for TP to undercarpet cabling

328 ft (100 m)

+++++

Page 9: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

New Trends

TDMM

Bell System Practices 10BASE-T

ANSI/EIA/TIA-568

Page 10: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

100-Meter Impact• Canonic “generic cabling” principle is often used

in complete isolation of immediate networking infrastructure

• Template approach to structured cabling design does not allow to implement it in almost 100% situations

• Structured cabling component selection is done empirically

Page 11: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

100-Meter Impact• The following conceptions are absent:

– Integrated system approach to providing high efficiency of structured cabling

– Transmission media selection

– Administration subsystem architecture

– Evaluation of horizontal cable consumptionas the key element of structured cabling

Page 12: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

100-Meter Impact• 20 years ago:

– TIA-568(Commercial Building Telecommunications Cabling)

• Today:– TIA-568-C (Commercial Buildings)

– TIA-758 (Campus)

– TIA-862 (Building Automation)

– TIA-942 (Data Centers)

– TIA-1005 (Industrial)

Page 13: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Transmission Limitations

• The Shannon-Hartley noisy channel theorem

– The theorem establishes channel capacity for a

communication path, a limit for the maximum amount

of error-free digital data that can be transmitted with a

specified bandwidth in the presence of the noise

interference

Tx RxTransmission Channel

Page 14: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Transmission Limitations

• The Shannon-Hartley noisy channel theorem

where

C channel capacity, bit/s

B bandwidth of the channel, Hz

S total received signal power over the bandwidth, W or V2

N total noise or interference power over the bandwidth, W

or V2

S/N signal-to-noise ratio (SNR)

)1(log2 N

SBC

Page 15: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

1.0E-16

1.0E-15

1.0E-14

1.0E-13

1.0E-12

1.0E-11

1.0E-10

1.0E-09

1.0E-08

0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160

Permanent Link Length, m

Bit

Ero

r R

ate

10GBASE-T 10GBASE-T 10GBASE-T 10GBASE-T

1000BASE-T 1000BASE-T

100BASE-T

10BASE-T

Transmission Limitations

Cat. 5e

Cat. 6

Cat. 6ACat. 7A

Page 16: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Transmission Limitations

50

100

150

200

250

300

0.50 0.55 0.60 0.65 0.70 0.75 0.80 0.85 0.90 0.95 1.00

Nominal Velocity of Propagation (NVP)

Ch

an

ne

l Le

ng

th,

m

10BASE-T

100BASE-T

1000BASE-T

10GBASE-T

Page 17: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Segment Length Distribution• Two-point estimation

• Expansion of φ(х) into a Gram-Charlier series

XkLL

L gk

2

)( minmax

...])36(!4

)3(!3

1[2

1)( 244332

2

xxxxexx

u

2

)1()( 11*0

uux

Page 18: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Segment Length Distribution

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90

Segment length, m

Fre

que

ncy

of o

ccur

ence

45

Page 19: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Segment Length Distribution• In order to increase accuracy of calculations it is

recommended to use a “12/70” rule:

– Cabling links shorter than 12 m are not taken into consideration

– Cabling links beyond 70 m are calculated separately

– Accuracy increase – about 5 %

– Cable laying unevenness can be neglected

– Design raw error probability decrease – 5 to 7 times

Page 20: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

10GE Capabilities vs. Category

Cabling category Link length Cabling utilization

Category 5e 25 m 13 %

Category 6 55 m 60 %

Category 6A 100 m 100 %

Category 7A 155 m 100 %

Category 8 40-100 Gbit/s

Page 21: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Capabilities vs. Category

0

1

2

3

4

5

6

50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200

Link length, m

Re

lativ

e c

ost

Category 6Category 6ACategory 7AOptical Fiber

130 140 150

Page 22: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Interconnect vs. Cross-connect • Interconnection vs. cross-connection

– Link/channel configuration gives 3- to 5-time reduction in bit error rate (BER)

• 98 % of all today’s installations/applications use interconnection scheme

• Channel models– Two-connector link (typical, approx. > 98 %)

– Three-connector link (uncommon, approx. < 1 %)

– Four-connector link (rare, approx. < 0.5 %)

Page 23: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

10BASE-TToken Ring

1989

1990

1991

1992

1993

1994

1995

1996

1997

1998

1999

2000

2001

2002

2003

2004

2005

2006

2007

2008

2009

“Generic” Cabling100 Gbit/s

10 Gbit/s

1 Gbit/s

100 Mbit/s

10 Mb/s

1 Mb/s

100 kbit/s

Token Ring

ARCnet

AppleTalk

ATM

TP-PMD100BASE-TX 100BASE-T4

ATM10BASE-T

100BASE-T2Demand Priority

1000BASE-T

1000BASE-TX

ATM

10GBASE-T

Voice-Grade

Category 3

Category 5

Category 5e

Category 6

Category 6A

Category 7A

“Generic cabling” turned out to benot so generic

Statistically cabling lives 5 to 7 years

Page 24: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Application-Dependent PHY

• CONCLUSIONS:

– Cabling links:

Majority (70 %) are within 45 meters, another 25 %

do not exceed 70 meters

Majority can support all applications up to 10GE,

and 10GE with certain limitations

Page 25: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Application-Dependent PHY

• CONCLUSIONS:

– Lifespan of an average structured cabling system

does not exceed 5–7 years

Choice of transmission media can be based on the best

cable meeting the networking needs rather than administered

by the standards

– 85 % of cabling systems are characterized by only

one parameter – number of work areas/outlets

Page 26: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Application-Dependent PHY• Attempts to strike a compromise between

physical level and application limitations

– ISO/IEC 11801 and CENELEC EN 50173engineering approach Flexible approach to distance limits

Basic estimation methods provided

– Anixter Levels Program (now obsolete) 7 levels of transmission performance

Flexible approach to component selection

Application-oriented approach

Page 27: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Other Distance Issues• There are other distance-dependent issues

influencing cabling design:

– Service area size

– Equipment and patch cord lengths

– Spare cable ratio

– System redundancy options

– Prospects for cables with higher impedance

– 15-meter problem

… and others

Page 28: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Service Area Size• Six-around-one model

2a

TRTR11

TRTR22

TRTR33

TRTR44

TRTR55

TRTR66

TRTR77

Page 29: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Service Area Size• Linear programming problem

• Problem simplification

min)MG(R

0k

n

1iikii

m90VerYyXx kiki

constay )1(

constYX

yx kk

2

))((

N

i

R

k

N

jkjki lMlGlG

1 1

7/

1

)]()([)(

Page 30: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Service Area Size

0.96

0.98

1

1.02

1.04

1.06

1.08

40 44 48 52 56 60 64 68 72 76 80

Service area diameter, m

Cost

opt

imiza

tion

inde

x

70

Page 31: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Service Area Size• CONCLUSIONS:

– Service area diameter should not exceed 70–75 m

– Horizontal subsystem requires 85 % of all resources during installation (element #1 for optimization)

– Horizontal subsystem cable length does not exceed 70 m (approx. 95 %)

Page 32: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Patch Cord Length Allocation• Equipment and patch cord routes

• φk(x) requires usage of certain connecting field layout rules and cable management panels

j

j

x

x

kajk dxxNkn1

)(

Page 33: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Patch Cord Length AllocationInterconnection

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

48 72 96 120 144 168 192 216 240 264

Number of Work Areas

Patc

h co

rd le

ngth

sha

re

1.0 m (3 ft)1.5 m (5 ft)2.0 m (7 ft)3.0 m (10 ft)

Page 34: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Patch Cord Length AllocationCross-Connection

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

48 72 96 120 144 168 192 216 240

Number of Work Areas

Patc

h co

rd le

ngth

sha

re

1.0 m (3 ft)1.5 m (5 ft)2.0 m (7 ft)

Page 35: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Patch Cord Length Allocation• CONCLUSIONS:

– Patch cord length dependency on the Work Area number (N) is very complex and should be tabulated

– Four influencing variables:

1. Number of Work Areas/Telecommunications Outlets

2. Cord type

3. Number of racks/cabinets in the cross-connect

4. Connecting hardware layout

Page 36: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Patch Cord Length Allocation• CONCLUSIONS:

– Average “data” cord length –1.5 м (5 ft)

– Average “phone” cord length – 1 m (3 ft)

– Overall channel length reduction – about 5 m (17 ft)

Page 37: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Patch Cord Length Allocation• CONCLUSIONS:

Reduction in 20 m in horizontal cable length

+5-meter reduction in equipment and patch cord lengths (5 m * 1.2 (1.5) = 6–7.5 m equivalent)

=up to 28-meter reduction of channel length, which guarantees 100% application functioning(the rule of 80 m)

Page 38: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Spare Cable Ratio• Calculation of spare cable ratio can be done

with the help of Fokker-Plank equation:

• Initial and boundary conditions:

• Average cable excess:

x

fl

x

f

t

f

2

22

2

0)0,(' tf 0),( Ltf)(),0( xxf

1 01 00

]),(1[/}),()(]),(1[{t

L

t

LL

dxxtfdxxtfxLdxxtfl

Page 39: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Spare Cable Ratio

0

0.005

0.01

0.015

0.02

0.025

0.03

0.035

0 25 50 75 100 125 150 175 200 225 250 275 300

Consumed cable length (m)

Pro

ba

bili

ty 1 drop2 drops4 drops6 drops7 drops

Page 40: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Spare Cable Ratio

Standarddeviation

Cable reel length

250 m(820 ft)

305 m(1,000 ft)

500 m(1,640 ft)

1,000 m(3,280 ft)

19 m(62 ft)

11.5 % 9.8 % 9.0 % 7.6 %

17 m(56 ft)

10.0 % 8.4 % 6.9 % 5.3 %

15 m(49 ft)

9.3 % 7.9 % 6.6 % 4.9 %

Page 41: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Spare Cable Ratio• CONCLUSIONS:

– Spare cable ratio advantage for larger cable reels is insignificant – ~ 1–5 %

– Recommended spare cable ratio – 10 %

– 500-meter and 1,000-meter cable reels are impractical due to unhandiness during installation (size and weight)

Page 42: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co

Overall Conclusions• Application-dependent cabling is inevitable

• Current “generic” concept can be used only as a foundation in creating up-to-date, flexible cabling systems

• Wanted concepts and methods:

– More flexible and precise transmission media selection/categorization

– Administration subsystem architecture (equipment/patch cord) principles and guidelines

Page 43: Do We Really Need the 100-meter Limit? Igor G. Smirnov, RCDD Signamax, Inc. Dr. Andrey B. Semenov IT Co