TS400 & TS410 Intruder Alarm Control Panels Installation & Programming Instructions HOME 0 AWAY 7 8 9 5 6 4 1 2 3 1 2 3 4 5 UNSET TAMPER FINAL EXIT

D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

TS400 & TS410Intruder Alarm Control Panels

Installation & ProgrammingInstructions

HOME 0 AWAY

7 8 9

5 64

1 2 3

1 2 3 4 5

UNSET TAMPER FINAL EXIT

Page 2: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Contents

OverviewIntroduction . . . . . . . . . . . . . . . . . . . . . . . . . 3TS400 Features . . . . . . . . . . . . . . . . . . . . . . . 3TS410 Features . . . . . . . . . . . . . . . . . . . . . . . 3Specifications. . . . . . . . . . . . . . . . . . . . . . . . 3

TS400 Control Panel . . . . . . . . . . . . . . . . . 3TS410 Control Panel . . . . . . . . . . . . . . . . . 3Remote Keypad . . . . . . . . . . . . . . . . . . . . 3

Planning The InstallationGeneral . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Cable Routing . . . . . . . . . . . . . . . . . . . . . . . 4TS400 Control Panel . . . . . . . . . . . . . . . . . . . 4TS410 Control Panel . . . . . . . . . . . . . . . . . . . 4External Sounder. . . . . . . . . . . . . . . . . . . . . . 4Remote Keypad. . . . . . . . . . . . . . . . . . . . . . 4Detection Devices . . . . . . . . . . . . . . . . . . . . 5

Passive Infra-Red (PIR) . . . . . . . . . . . . . . . . 5Magnetic Contacts . . . . . . . . . . . . . . . . . 5Personal Attack (PA) Button . . . . . . . . . . . . 5Vibration Detectors . . . . . . . . . . . . . . . . . . 5Smoke/Heat Detectors . . . . . . . . . . . . . . . 5

Final Exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Auxiliary Tamper . . . . . . . . . . . . . . . . . . . . . . 5Keyswitch . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

System InstallationInstalling the TS400 Control Panel . . . . . . . . . 6Installing the TS410 Control Panel . . . . . . . . . 6Mains Connection . . . . . . . . . . . . . . . . . . . . 7Battery Connection . . . . . . . . . . . . . . . . . . . 7PCB Layout . . . . . . . . . . . . . . . . . . . . . . . . . . 8Multiple Detectors on the same Zone . . . . . 9

Door Contacts . . . . . . . . . . . . . . . . . . . . . 9Passive Infra-Red. . . . . . . . . . . . . . . . . . . . 9

Auxiliary Tamper . . . . . . . . . . . . . . . . . . . . . . 9Wiring Example. . . . . . . . . . . . . . . . . . . . . . . 10Installing a Remote Keypad . . . . . . . . . . . . . 11External Sounder Connections . . . . . . . . . . . 11Extension Loudspeakers . . . . . . . . . . . . . . . . 12ALM- Terminal . . . . . . . . . . . . . . . . . . . . . . . . 12RST- Terminal. . . . . . . . . . . . . . . . . . . . . . . . . 12

Detector Reset (DTR RST) . . . . . . . . . . . . . . 12Switched 12V (SW12V). . . . . . . . . . . . . . . . 12

Aux 12V Power . . . . . . . . . . . . . . . . . . . . . . . 12SD1(Optional) . . . . . . . . . . . . . . . . . . . . . . . . 12Initial Power-Up . . . . . . . . . . . . . . . . . . . . . . . 13

ProgrammingProgramming Menus . . . . . . . . . . . . . . . . . . 14Program Zones . . . . . . . . . . . . . . . . . . . . . . . 15

Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Access . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Keyswitch . . . . . . . . . . . . . . . . . . . . . . . . . 15Fire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15P.A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

View Event Log . . . . . . . . . . . . . . . . . . . . . . . 15Walk Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Exit Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Entry Time . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Bell Duration Time . . . . . . . . . . . . . . . . . . . . . 16Change Engineer’s Passcode . . . . . . . . . . . 16Remote Reset Number. . . . . . . . . . . . . . . . . 17System Options. . . . . . . . . . . . . . . . . . . . . . . 17

Bell Output . . . . . . . . . . . . . . . . . . . . . . . . 17Setting Mode . . . . . . . . . . . . . . . . . . . . . . 17Reset Authority . . . . . . . . . . . . . . . . . . . . . 17System Re-arms . . . . . . . . . . . . . . . . . . . . 17Keyswitch Operation. . . . . . . . . . . . . . . . . 18RST- Output . . . . . . . . . . . . . . . . . . . . . . . . 18

Returning to the Unset Mode . . . . . . . . . . . . 18Full Setting the System (AWAY) . . . . . . . . . . . 18Part-Setting the System (HOME) . . . . . . . . . . 18Unsetting the System . . . . . . . . . . . . . . . . . . 18

Testing & Fault FindingTesting the System . . . . . . . . . . . . . . . . . . . . 19Fault Finding. . . . . . . . . . . . . . . . . . . . . . . . . 19Chart 1 - Zone Faults . . . . . . . . . . . . . . . . . . 20Chart 2 - System Will Not Set. . . . . . . . . . . . . 21Chart 3 - External Sounder Faults . . . . . . . . . 22

Installation RecordsSystem Programming Record. . . . . . . . . . . . 23

2

TS400/TS410 Installation Instructions

Page 3: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Overview

IntroductionThe TS400 and TS410 are 6 zone microprocessorbased intruder alarm control panels with 5programmable zones and a dedicated Final Exitzone. The ease of operation for setting andunsetting lends itself ideally to domestic andsmaller commercial installations.

TS400 Features� 5 Programmable zones Night, Access, Fire, PA

& Keyswitch (plus common tamper)

� Dedicated Final Exit zone

� On board keypad and LED indicators

� Up to 4 remote keypads

� Facilities to connect to an SD1 Speech Dialler

� 4 event log

� Programmable output for vibration detectorsor latching PIRs

� Dual user codes

� Remote Reset facility

� 2.1 Ah battery capacity

� All data stored in Non-Volatile Memory (NVM)

TS410 Features� 5 Programmable zones Night, Access, Fire, PA

& Keyswitch (plus common tamper)

� Dedicated Final Exit zone

� Blind control panel supplied with 1 remotekeypad with the option to support up to 4.

� Facilities to connect to an SD1 Speech Dialler

� 4 event log

� Programmable output for vibration detectorsor latching PIRs

� Dual user codes

� Remote Reset facility

� 7.0 Ah battery capacity

� All data stored in Non-Volatile Memory (NVM)

Specifications

TS400 Control PanelInput Voltage: 240V ±10% 50HzCurrent: 40mA (normal) 85mA (alarm)Power Supply: 750mAStandby Battery: 2.1AhDimensions: 205 (W) x 205 (H) x 64 (D) mmMaterial: 3mm polycarbonateWeight: 1.2 KgEnvironment: 0 - 55°C

TS410 Control PanelInput Voltage: 240V ±10% 50HzCurrent: 40mA (normal) 85mA (alarm)Power Supply: 750mAStandby Battery: 7.0AhDimensions: 242 (W) x 237 (H) x 86 (D) mmMaterial: 1.2mm mild steelWeight: 2.6 KgEnvironment: 0 - 55°C

Remote KeypadCurrent: 35mA (normal) 50mA (alarm)Dimensions: 130 (W) x 130 (H) x 30 (D) mmMaterial: 3mm PolycarbonateWeight: 415gEnvironment: 0 - 55°C

3

TS400/TS410 Installation Instructions Overview

Page 4: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Planning The Installation

GeneralThe TS400 and TS410 are flexible systems, but caremust be taken in planning the installation toprovide maximum protection with minimumeffort.

Survey the household and determine where eachsecurity device is to be fitted. Wherever possible,try to conceal wiring (e.g., in the loft, under carpetsor floorboards and inside cupboards). Commit thesystem design to paper for future reference.

Cable RoutingWhen installing cables, the following should benoted:

� Ensure that all cables are kept clear of mainssupply cables, telephone cables, cablessupplying bells or sounders and any cableslikely to induce electrical noise (R.F.) into thesystem.

� Screened cable may prove necessary ifcables are run adjacent to cables which carryR.F. (electrical noise) or are switching highcurrent loads.

� The mains power supply cable to the systemmust be connected to an un-switched fusedspur that cannot be accidentally switched off.The mains cable must enter the control panelhousing via its own cable entry point.

TS400 Control PanelThe TS400 control panel should be located in aposition where it has easy access for the users toset and unset the system. It should by mounted ata level where it is easy to operate the keypad andread the indicator LEDs. The provision forconnecting to a permanent mains supply mustalso be considered.

When operating the system it should be possible tohear the exit and entry tones throughout the entry& exit route and outside the final exit door. If thecontrol panel is positioned a long way from thefinal exit door, it may be necessary to fit anextension loudspeaker.

TS410 Control PanelThe TS410 control panel is blind panel and as suchit can positioned out of view, normally in acupboard under the stairs. The provision forconnecting to a permanent mains supply mustalso be considered.

When operating the system it should be possible tohear the exit and entry tones throughout the entry& exit route and outside the final exit door. If theremote keypad is located a long way from thefinal exit door, it may be necessary to fit anextension loudspeaker.

External SounderThe external sounder should be mounted as highas possible so that it is visible and out of reach topotential intruders. A six-core cable is required forconnection to the sounder which should enterdirectly through the wall and into the sounder viathe cable entries in the back plate. However, if thecable is run over the surface to the sounder then itshould be protected (e.g., the cable may be runin aluminium conduit).

Remote KeypadIf required, up to four remote keypads may beconnected to the system to allow remoteoperation of the system. The remote keypad has 8LED indicators and an internal sounder to indicateall system tones. Remote keypads require asix-core cable for connection.

4

Planning The Installation TS400/TS410 Installation Instructions

Page 5: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Detection DevicesThere are several types of detection devicesavailable which are suitable for domesticinstallations as follows:

Passive Infra-Red (PIR)A detector which detects movement of anintruder by the change in infra-red body heat.When fitting PIRs, refer to the installation instructionssupplied with the unit. In general there are twotypes of PIR "Standard" and "Latching". Normallythe standard type is used where one detector perzone is fitted and a six-core cable is required forconnection. The latching type is used when morethan one detector is fitted to a zone, the latchfacility allows the user to identify the triggereddetector by means of the indicator LED on thedetector "latching" on. If latching detectors areused an eight-core cable is required forconnection.

Magnetic ContactsMagnetic contacts consist of an electrical switchwhich is operated by a magnet. They come in twoversions, the "Flush" type is designed to be fittedinto the top or side of the door/window. The"Sur face" type is des igned to f i t ted todoors/windows where it is not possible to use flushcontacts e.g. garage doors, UPVC windows etc.Both types of contacts require a four-core cablefor connections.

Personal Attack (PA) ButtonNormally PA buttons are located by the front dooror adjacent to the bed, and preferably out ofreach to small children. Pressing the button at anytime will generate a full alarm. Some PA buttonsauto reset and some require a key to reset them. Inboth cases the control panel must be reset. PAbuttons require a four-core cable for connections.

Vibration DetectorsVibration detectors are normally fitted to windowsor door frames. They are triggered when thedevice senses a shock attack. Vibration detectorsrequire a six-core cable for connections.

Smoke/Heat Detectors12V Smoke or heat detectors may be connectedto the system to provide additional protectionagainst fire. When activated a distinctive internalsounder tone is generated and the externalsounder is pulsed. Smoke detectors require afour-core cable for connections.

Final ExitThis is the point at which the user leaves and entersthe premises (normally the front door). Whensetting the system the user must leave theprotected area via the exit route and through theFinal Exit zone. When re-entering the premises theuser must activate the Final Exit zone to start theentry timer which allows the user time to gainaccess to the control panel to unset the system. Ifthe user enters the premises through any otherpoint and triggers a detection device a full alarmwi l l be generated. The system may beprogrammed to set after the exit timer has expiredor by the operation of the Final Exit detectiondevice.

Auxiliary TamperThe tamper protection for all zones and anyauxiliary devices such as the speech dialler mustbe wired in a continuous loop and then beconnected to the auxiliary tamper terminals.

KeyswitchAn optional keyswitch may be fitted to the systemto allow the user to set and unset (or part-set andunset) the system using a physical key rather thana four digit passcode.

5

TS400/TS410 Installation Instructions Planning The Installation

Page 6: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

System Installation

Installing the TS400 Control Panel1. Remove the screw from the top of the control

panel and lift away the front cover.

2. Ensure that there is no battery in the housing,then remove the circuit board as follows:

(a) Disconnect the yellow leads from thetransformer and remove the connectionsto the internal loudspeaker.

(b) Pull down the plastic clip at the bottom righthand corner of the circuit board and gentlylift the board forward.

(c) Repeat with the plastic clip at the bottomleft hand corner of the circuit board.

(d) The bottom of the circuit board will thenswing forward and can be removed fromthe base.

3. Hold the base in the required position andmark the centre of the keyhole. Remove thebase, then drill and plug the holes. Note:Remember to allow enough room to get thecover screw in to top of panel when mountingthe base.

4. Re-position the base and secure to the wallusing not less than 30mm x No 10 screws.

5. Re-fit the circuit board assembly by aligningthe top of the board into the 2 supports in thetop of the housing ensuring that the edges ofthe board sit between the 2 flanges, then pushthe bottom of the circuit board until it clicks intoplace.

6. Re-connect the yellow leads to the transformerand re-connect the internal loudspeaker.

Installing the TS410 Control Panel1. Open the control panel by removing the two

screws from the front cover.

2. Note the position of the cable entries asfollows:

(a) Seven 20mm cable entries for detection,alarm and remote keypad cables.

(b) A 20mm cable entry for mains (240V)below the mains input terminal block onthe left hand side of the control panel backbox.

6

System Installation TS400/TS410 Installation Instructions

+ -

Holders forspare fuses

Fusedterminal block(200mA)

Transformer

Cover clips

PCB retention clips

Printed Circuit Board(PCB)

Loudspeaker(under PCB)

Standby battery2.1 Ah max.

PCB locationflange

Figure 1 TS400 Control Panel Assembly

Page 7: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

�The mains cable must enter the controlpanel through its own cable entry andmust not be mixed with other cables.

3. Hold the control panel back box in the requiredposition (keyhole to the top) and mark thecentre of the keyhole position. Remove theback box, drill and plug the hole.

4. Screw a No 10 screw into the plugged hole.Re-position the back box and mark theremaining securing holes. Remove the backbox, drill and plug the holes.

5. Re-position the back box and pass all cablesinto the base via cable entries, grommeting asappropriate.

6. Secure the back box using not less than 30mmx No 10 screws.

�When replacing the cover, alwaysensure that the earth bonding lead isconnected to the spade connectioninside the control panel.

Mains ConnectionThe mains supply is connected to a 3 way "EuroType" fused terminal block, which is fitted with a200mA fuse. All electrical connections should becarried out by a qualified electrician and mustcomply with the current IEE regulations.

� To comply with european regulations thesupply should be fed from a readilyaccessible disconnect device, e.g.un-switched fused spur fitted.

� When making mains connections it shouldbe ensured that if the cable slips in such away as to place a strain on the conductors,the protective earthing conductor will bethe last to take the strain.

Battery ConnectionA suitable standby battery must be fitted to thesystem to allow it to function during a mains failcondition. The TS400 and TS410 are equipped witha "Battery Protection" circuit so that if a battery isaccidentally reverse connected or its voltage isbelow 4V, a tamper alarm is generated. To clearthe fault simply reconnect or replace the batteryas appropriate.

7

TS400/TS410 Installation Instructions System Installation

Fusedterminal block(200mA)

Transformer

Spade connectionfor earth lead to frontcover

Printed Circuit Board(PCB)

Standby battery7.0 Ah

Standby battery2.1 Ah

Figure 2 TS410 Control Panel Assembly

Page 8: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

PCB Layout

Bell FuseThis 1 Amp fuse protects the supply to the externalsounder/bell.

Aux FuseThis 1 Amp fuse protects the supply to devicespower from the auxiliary 12V terminals.

Speaker Volume R37Cut R37 to reduce the volume of the extensionloudspeakers.

Factory Restart PinsIf these pins are shorted during power-up allsystem programming data is restored to thefactory default values, see page 13 for defaults.

Home Inhibit LinkWhen the link is open the [ALM-] terminal activateswhen an alarm occurs during a full or part setcondition. When the link is closed the [ALM-]terminal activates only if an alarm occurs during afull set condition.

1 - 5 Indicator LEDsThese red indicator LEDs indicate the alarm statusof zone 1 - 5. Note these are not fitted on theTS410.

Unset Indicator LEDThis green indicator LED is used to indicate thestatus of the system set or unset. It also flasheswhen the mains power is removed or when theuser selects the user program mode

Tamp Indicator LEDThis red LED is used to indicate a system tamperalarm, it also flashes when the engineer programmode is selected. Note this is not fitted on theTS410.

F/E Indicator LEDThis red LED is used to indicate the status of the finalexit zone. Note this is not fitted on the TS410.

8

System Installation TS400/TS410 Installation Instructions

A.C.

AL

M-

RS

T-

TR

G-S

TB

-+

H/O

-T

MP

-A

UX

TA

MP

ER

L/S-

AU

X1

2V

+-

P.A

.Z

ON

E5

FIR

EZ

ON

E4

K'S

WZ

ON

E3

AC

CE

SS

ZO

NE

2A

CC

ES

SZ

ON

E1

F/E

XIT

Remote KeypadInterface Connector

Keypad(Not fitted on TS410)

Factory Restart Pins

Indicator LEDs

Home alarminhibit link

Cut R37 to reducevolume

(1AMP)

AUX12V

Leads totransformer

Tamper switch

Zoneconnections

Externalsounderconnections

Bell(1AM

P)

1 2 3

4 5 6

7 8 9

HOME 0 AWAY

FACTORYRESTART

VO

LU

ME

R37 HOME ALM

INHIBIT

1 2

UNSET TAMP F/E

3 4 5

EX

TE

RN

AL

BE

LL

Figure 3 TS400 & TS410 Connection Diagram

Page 9: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Multiple Detectors on the same Zone

Door ContactsWhen connecting more than one door contact toa zone, the alarm contacts must be connected inseries. The switch inside the contact is connectedbetween the two plated screws (shown in white inthe above figure).

Passive Infra-RedWhen connecting more than one PIR to a zone it isrecommended that you use "Latching" type PIRs.The latch terminal on the PIR is connected to the[RST-] output which must then be programmed asSW 12V.

Auxiliary TamperThe tamper wires for each detector must beconnected in series using a terminal strip or similarand then connect to the AUX TAMPER terminals.

9

TS400/TS410 Installation Instructions System Installation

AU

XTA

MP

ER

ZO

NE

To tamper loopfor other zones

Flush ContactFlush ContactA

UX

TA

MP

ER

ZO

NE

Surface ContactSurface Contact

Connecting severalflush contacts per zone

Connecting severalsuface contacts per zone

AU

XTA

MP

ER

AU

X1

2V

Connecting severalPIRs per zone

Program [RST-] asSW 12V

PIR

0V

+1

2V

AL

AR

M

TA

MP

ER

LA

TC

H

ZO

NE

+-

PIR

0V

+1

2V

AL

AR

M

TA

MP

ER

LA

TC

H

RS

T-

To tamper loopfor other zones

To tamper loopfor other zones

Figure 4 Connecting Multiple Detectors per Zone

AUXTAMPER

Terminal Strip (Not Supplied)

Tamper Loop

Tamper Loop

Tamper Loop

Tamper Loop

Figure 5 Auxiliary Tamper Connection

Page 10: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Wiring Example

10

System Installation TS400/TS410 Installation Instructions

ALM -

RST -

TRG -STB-

+

-

TMP -

AUX

TAMPERL/S -

+

-

ZONE 5 (P A)

H/O

AUX 12V

ZONE 4 (Fire)

ZONE 3 (K/Sw)

ZONE 2 (Access)

ZONE 1 (Access)

FINAL EXIT

PIR

+12V

0V

TAMPER

ALARM

PIR

+12V

0V

TAMPER

ALARM

Flush Contact

Surface Contact

ALARM

Supply -

Supply +

Smoke Detector

TRIGGER -

STROBE -

HOLD OFF +

HOLD OFF -

TAMPER RETURN -

External SounderR37

Note

Any unused zones must belinked out.PIRs and surface contacts canbe connected to any zone. Thisdiagram is only used torepresent a typical installationexample.

If a keyswitch is fitted, it mustbe connected to ZONE 3 andthen programmed asKEYSWITCH.

If a smoke/heat detector isfitted, it must be connected toZONE 4 and then programmedas FIRE.

If a P.A. button is fitted, it mustbe connected to ZONE 5 andthen programmed as P.A.

16 Ohm Extension loudspeaker(cut R37 to reduce volume)

TS400 / TS410

Terminal strip(not supplied)

To ZONE 1

To ZONE 2

To ZONE 3

To FINAL EXIT

To ZONE 5 (P.A.)

To AUX +12VTo AUX -12V

To ZONE 4 (Fire)

To AUX -12V

To AUX -12V

To AUX +12V

To AUX +12V

P.A. Button

Figure 6 Example Wiring Diagram

Page 11: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Installing a Remote KeypadEnsure that the mains and battery power has beendisconnected and proceed as follows:

1. Connect each core of the 6-core cable to theinterface terminals "L E D C B A" (make a note ofthe colours used for each connection).

2. Pass the yellow flying-lead behind the PCB andconnect it to the [L/S-] terminal.

3. Plug the Interface board into the interfacesocket as shown below.

4. Separate the remote keypad cover and baseby using a screwdriver to push two of the clips(top or bottom) inwards from the coverretaining slots. Then lift the cover assembly,noting that the circuit board is connected tothe under side of the cover.

5. Hold the remote keypad base in position(keyhole to the top) and mark the threesecuring holes, drill and plug the wall asrequired. Pass the 6-core cable into the basevia the cable entry points as appropriate andsecure the base to the wall.

6. Connect each core of the 6-core cable to theremote keypad terminals "L A B C D E", ensuringthat the connections through to the controlpanel are A to A, B to B, etc. If more remotekeypads are to be fitted, they may beconnected in a star or daisy chainconfiguration (providing the cable length to

the last or furthest remote keypad does notexceed 50 metres).

7. Carefully reattach the front cover assembly tothe remote keypad base ensuring that allcables are clear of the tamper switch springand the cover is securely clipped to the base.

External Sounder ConnectionsThe following terminals have been provided toallow connections to an external sounder:

H/O - This is used to provide a permanent -vehold off to external sounders, strobes etc.

H/O + This is used to provide a permanent +vehold off to external sounders, strobes etc.It is protected by a 1 Amp fuse (Bell 12V).

TMP - This is the negative tamper returnconnection from the external sounder. Ifan external sounder is not fitted this inputmust be linked to [H/O -].

STB - This is the strobe output which switches to0V on alarm. The output is rated at 500mAand should be connected to -ve strobetrigger input on the external sounder.

TRG - This is the external sounder trigger outputwhich is rated at 500mA. This output canbe programmed for SAB or SCBoperation, as follows:SAB: TRG - will switch to 0V on alarm andwill provide a maximum of 500mA.SCB: TRG - will provide a negative holdoff (500mA), which is removed on alarm.

11

TS400/TS410 Installation Instructions System Installation

Interface PCBFlying-leadconnected to L/S -

Flying-lead

L/S

Figure 7 Remote Interface Connections

TypicalExternal Sounder

ControlPanel

H/O +12V +

H/O -0V

Tamper In TMP -

STB -Tamper Out

TRG -Strobe +ve

Strobe -ve

Trigger -ve

Figure 8 External Sounder Connections

Page 12: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Extension LoudspeakersA 16Ohm extension loudspeaker can beconnected between the [L/S-] and [AUX 12V+]terminals. R37 (located in the top left hand cornerof the PCB) can be cut to reduce the volume ofthe internal sounders (alarm is always full volume).

ALM- TerminalThis terminal is switched negative (100mA) onalarm and is removed when the system is reset. Ifthe Link marked "HOME ALARM INHIBIT" on the mainPCB is closed, the [ALM-] output is disabled whenthe system is part-set (Home). Normally this outputis used to trigger a speech dialler or similar.

RST- TerminalThis terminal may be programmed as:

Detector Reset (DTR RST)When programmed as Detector Reset the outputmay be used for detectors which latch their alarmcondition, and must be de-powered to reset (e.g.,smoke detectors, vibration detectors etc.). Powerfor such detectors must be connected between[AUX 12V] and [RST-].

Switched 12V (SW12V)When programmed as Switched 12V the outputmay be connected to the latch input terminal onlatching detectors (e.g., PIRs etc.). This feature isnormally used when more than one detector isconnected to a single zone. It allows the user toidentify the alarm source by latching the indicatorLED on the detector that caused the alarmactivation. The latched LED will clear when thesystem is reset.

Aux 12V PowerThe auxiliary 12V terminals provide a permanent12V supply for detectors which require a lowvoltage supply e.g., PIRs, vibration detectors,smoke detectors etc. The output is protected by a1 Amp fuse (Aux 12V).

The maximum available current from the controlpanel power supply is 750mA. The following is atypical example showing how to calculate theavailable auxiliary current.

Control Panel = 85mA

External Sounder = 250mA

External Strobe = 115mA

Total = 450mA

Auxiliary Available = 300mA (750 - 450)

SD1(Optional)The SD1 is a customer programmable speechdialler which dials pre-programmed numbers toinform neighbours etc. of the alarm. It is capableof transmitting up to 3 messages linked to inputs A,B and C.

12

System Installation TS400/TS410 Installation Instructions

16 Ohm Loudspeaker L/S -

AUX +12V

Figure 9 Speaker Connections

ALM -

RST -

TRG -

STB-

+-

TMP -

AUX

TAMPER

L/S -

+

-

ZONE 5 (P A)

H/O

AUX 12V

ZONE 4 (Fire)

TRIG A

TRIG B

0V

+12V

TAMPER

BOX

TRIG C

Set TRIG POLARITY to -ve

Note: Only connect TRIG A (FIRE)and TRIG B (PA) if zones 4 and 5are programmed as Fire and PA.

TS400/TS410SD1

Figure 10 SD1 Connections Details

Page 13: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Initial Power-Up1. Place a small screwdriver blade between the

pins on the control panel PCB, markedFACTORY RESTART (located just below the LEDs).This will ensure the factory defaults are loadedas shown below:

Engineer Code 1234

User Code 1 5678

Zone 1 Alarm

Zone 2 Access

Zone 3 Alarm

Zone 4 Alarm

Zone 5 Alarm

Exit Time 30 Seconds

Entry Time 30 Seconds

Bell Duration 20 Minutes

Bell Output SAB (-ve applied)

Remote Reset Number 004

Setting Mode Timed Set

Reset Authority User Reset

Number Of Rearms 3

Operation Of Keyswitch Away Set (Full)

RST- Output Detector Reset

HOME Set Configuration Zone 1 Omitted

Factory Default Settings

2. Switch on the 240V mains supply, when thegreen UNSET LED is lit remove the screwdriverblade. The internal alarm will sound and theTAMPER LED will light.

3. Enter the engineer’s passcode (default 1 2 3 4),the alarm will silence. Enter the engineerspasscode again and the TAMPER LED will flash(engineer programming menu selected).

4. Connect the standby battery. If the TAMPERLED lights permanently and the internal alarmsounds when the battery is connected, then itmay be incorrectly connected or it may betotally discharged. Disconnect the batteryimmediately and reconnect or replace asappropriate.

5. Push the battery into place at the bottom of thehousing and re-fit the front cover.

� On the TS410 you MUST connect the earthbonding cable from the front cover to thespade connection point, see figure 2.

6. Fit the battery link in the external sounder andreplace cover.

7. The system is now ready for programming.

13

TS400/TS410 Installation Instructions System Installation

Page 14: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Programming

Programming MenusThere are two programming menus within the system. The engineer’s programming menu and the userprogramming menu. The figure below shows the structure of both programming menus, however theengineers programming menu is only covered in full detail within this manual. For full details on the useroptions see "User Operating Instructions".

14

Programming TS400/TS410 Installation Instructions

1 2 3 4 5

TAMPERUNSET FINAL EXIT

1 2 3 4 5

TAMPERUNSET FINAL EXIT

TamperLEDFlashes

UnsetLEDFlashes

1 1

1 2 3 4

2 2

3 4

4 6

5 7

6 0

7

8

9

0

AWAY

HOME

HOME

HOME

= Program Zones = Bell Test

Enter the engineer's passcode(default = )

= View Event Log = Walk Test

= Walk Test = Change Passcode 1

= Exit Time = Change Passcode 2

= Entry Time = Home Set Configuration

= Bell Duration = Return to unset mode

Press twice when the systemis in the unset mode to select

"Chime" zones.

= Engineer's Passcode

= Remote Reset No.

= System Options

= Return to unset mode

= Full set the system

= Part set the system

1 2 3 4 5

TAMPERUNSET FINAL EXIT

1 2 3 4 5

TAMPERUNSET FINAL EXIT

HOME5 6 7

Enter first 3 digits of passcode then(e.g., )

Engineer's Menu User Menu

Page 15: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Program ZonesThe TS400 zones may be programmed so thatthey perform different functions. The zones typesare as follows:

AlarmZones 1- 5 can be programmed as alarm zones,this type of zone will only generate a full alarmwhen activated during a set condition.

AccessZones 1 and 2 can be programmed as accesszones, this type of zone is automatically isolatedduring the entry/exit procedure to allow a walkthrough route for the user. Once the system is fullset the access zones respond as alarm zones. If anaccess zone is armed during the part set (Home)condition it will start the entry timer if activated.

KeyswitchZone 3 can be programmed as a keyswitch zone,this type of zone will set the system when active(zone open) and unset the system when healthy(zone closed). The keyswitch zone functionalitycan be further programmed to either full set(Away) or part set (Home) the system, see "SystemOptions" on page 17.

FireZone 4 can be programmed as a fire zone, thistype of zone is monitored at all times, whenactivated a distinctive internal sounder tone isgenerated and the external sounder is pulsed onand off. The internal and external sounders willoperate for 20 minutes, irrespective of the bellduration setting.

P.A.Zone 5 can be programmed as a Panic Alarm(P.A.) zone, this type of zone is monitored at alltimes, when activated a full alarm is generated.The internal and external sounders will operate for20 minutes, irrespective of the bell durationsetting.

➤ To program zones proceed as follows:

1. Ensure that the engineer’s menu is selected,then press [1] to select program zones.

2. Press keys [1] to [5] to toggle between the twooptions for each zone as shown below.

Zone LED LED On LED Off

Zone 1 Access Alarm

Zone 2 Access Alarm

Zone 3 Keyswitch Alarm

Zone 4 Fire Alarm

Zone 5 PA Alarm

3. When completed, press [0] to accept, a highpitched acceptance tone will be heard andthe system returns to the engineer’s menu.

View Event LogThe TS400 will store up to 4 alarm activation eventswithin the memory log. This option allows theevents to be viewed.

➤ To view the event log proceed as follows:

1. Ensure that the engineer’s menu is selected,then press [2] to select view event log.

2. Press [1] to view the newest event, [4] to viewthe oldest event etc.

3. When completed, press [0] to accept, a highpitched acceptance tone will be heard andthe system returns to the engineer’s menu.

Walk TestThe Walk Test option allows the engineer to test thefunction of all detection zones without causing analarm. As each zone is activated its zone indicatorLED will light and the internal sounder generates atwo-tone sound. When the zone is deactivated thesounder stops and the zone LED goes out.

➤ To perform a walk test proceed as follows:

1. Ensure that the engineer’s menu is selected,then press [3] to select walk test.

2. Activate each zone in turn by opening doorsfitted with alarm contacts and walking in frontof movement detectors.

3. When completed, press [0] to accept, a highpitched acceptance tone will be heard andthe system returns to the engineer’s menu.

15

TS400/TS410 Installation Instructions Programming

Page 16: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Exit TimeThis timer sets the delay between the user initiatingthe setting procedure and the system actuallysetting. This only applies when the system isprogrammed to set by "Timed Exit", see "SystemOptions" on page 17.

➤ To program the exit time proceed as follows:

1. Ensure that the engineer’s menu is selected,then press [4] to select Exit Time.

2. Select the required exit time by using keys [1] to[4] to light the appropriate zone LED. When theLED is lit the exit time will be as shown below:

Zone LED LED On

Zone 1 10 Seconds

Zone 2 30 Seconds

Zone 3 1 Minute

Zone 4 2 Minutes

3. When completed, press [0] to accept, a highpitched acceptance tone will be heard andthe system returns to the engineer’s menu.

Entry TimeWhen the entry procedure is initiated, the EntryTimer is started. If a valid user passcode is notentered when the timer reaches zero, a full alarmtone is generated from the internal sounders onlyand the timer is restarted. If a valid user passcodeis not entered when the timer reaches zero for thesecond time the external sounder is activated.

➤ To program the entry time proceed as follows:

1. Ensure that the engineer’s menu is selected,then press [5] to select entry time.

2. Select the required exit time by using keys [1] to[4] to light the appropriate zone LED. When theLED is lit the entry time will be as shown below:

Zone LED LED On

Zone 1 10 Seconds

Zone 2 30 Seconds

Zone 3 1 Minute

Zone 4 2 Minutes

3. When completed, press [0] to accept, a highpitched acceptance tone will be heard andthe system returns to the engineer’s menu.

Bell Duration TimeThis timer controls the duration of the externalsounder when the system is triggered into a fullalarm condition.

➤ To program the bell duration time proceed asfollows:

1. Ensure that the engineer’s menu is selected,then press [6] to select the bell duration time.

2. Select the required bell duration time by usingkeys [1] to [4] to light the appropriate zoneLED. When the LED is lit the bell duration time willbe as shown below:

Zone LED LED On

Zone 1 90 Seconds

Zone 2 3 Minutes

Zone 3 10 Minute

Zone 4 20 Minutes

Zone 5 Continuous

3. When completed, press [0] to accept, a highpitched acceptance tone will be heard andthe system returns to the engineer’s menu.

Change Engineer’s PasscodeThe factory default engineer’s passcode is set to[1] [2] [3] [4], but the installation engineer shouldchange this to their own personal 4 digit passcodeas follows:

➤ To change the engineer's passcode proceedas follows:

1. Ensure that the engineer’s menu is selected,then press [7] to select change engineer’spasscode.

2. Zone LEDs 1 to 4 will now light.

3. As the new passcode is entered each LED willgo out one by one. When all 4 digits havebeen entered, LEDs 1 to 4 will light again andthe new passcode must be re-entered forconfirmation.

4. A high pitched tone indicates the newpasscode was accepted, a low pitched toneindicates the passcode was not accepted. Ifthe passcode was not accepted repeat theprocedure again, using a different passcode.

16

Programming TS400/TS410 Installation Instructions

Page 17: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Remote Reset NumberThe "Engineer Reset" option can be overridden bythe user, operating the "Remote Reset" facility. Ifan alarm is generated the system will respond witha four digit "seed" code which the user quotes tothe alarm company. The "seed" code is thenentered into a decoder and a unique "RemoteReset" code is generated. This is passed back tothe user and, on entering the "Remote Reset"code, the system will reset.

The "Remote Reset" code is generated using analgorithm identified by a 3 digit number.Alternative algorithms may be selected but thesemust correspond to that used by the alarmcompany otherwise the "Remote Reset" code willbe incorrect. The "Remote Reset" feature may bedisabled altogether by setting the number to"000".

➤ To program the remote reset numberproceed as follows:

1. Ensure that the engineer’s menu is selected,then press [8] to select remote reset number.

2. Zone LEDs 1 to 3 will now light.

3. As the new remote reset number is enteredeach LED will go out one by one. When all 3digits have been entered, LEDs 1 to 3 will lightagain and the new number must bere-entered for confirmation.

4. A high pitched tone indicates the new numberwas excepted, a low pitched tone indicatesthe number was incorrectly entered and theprocedure must be repeated.

System OptionsThere are six system options which change thefunctionality of the alarm system. The options areas follows:

Bell OutputThe bell trigger output [TRG-] can be programmedas either:

SAB: When programmed as SAB the output willswitch to 0V on alarm.

SCB: When programmed as SCB the outputprovides a 0V hold off, which is removed on alarm.

Setting ModeThe system can be programmed to set usingether:

Timed Exit: The system will set when the exit timerhas expired.

Final Exit: The system will set when the lastdetector or door contact is activated during theexit procedure. Note: When the system is part set(HOME) the system will always set by timed exit andis silent.

Reset AuthorityThe person responsible for resetting full alarms canbe programmed as either:

User: Following a full alarm the system can bereset by the user.

Engineer: Following a full alarm the system canonly be reset by the engineer or Remote Reset (Ifenabled).

System Re-armsThe system can be programmed to re-arm afteran alarm. The re-arm options are:

1 re-arm: When an alarm occurs, the internaland external sounders are operated for the lengthof the bell duration. At the end of this time thealarm is silenced and the all zones are re-armed.Any zones that are active will be automaticallyisolated until they return to their healthy state. If analarm occurs from the same zone it will cause theinternal and external sounders to operate again,at the end of the alarm the zone is "Locked-out"and prevented from generating another alarm. Allother healthy zones will re-arm and will only be‘Locked-out’ when they have caused anotheralarm.

3 Re-arms: Operates as above, but zones areonly "Locked-out" after the system has re-armed 3times.

17

TS400/TS410 Installation Instructions Programming

Page 18: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Keyswitch OperationThe operation of the keyswitch (zone 3) can beprogrammed as either:

AWAY: When keyswitch zone is opened the exitprocedure for AWAY set will start and the system willattempt to full set. When the zone is closed thesystem will unset.

HOME: When the key switch zone is opened theexit timer will start and when the timer has expiredthe system will be part set. When the zone is closedthe system will unset.

RST- OutputThe operation of the [RST-] output can beprogrammed as either:

SW 12V: This can be connected to the "Latch"input on latching detection devices.

Detector Reset: This can be used as the 0Vconnection to detectors that require the power tobe removed to reset them (such as smokedetectors and vibration sensors).

➤ To program the system options proceed asfollows:

1. Ensure that the engineer’s menu is selected,then press [9] to select system options.

2. Press keys [1] to [6] to toggle the zone LEDs onor off. The system options will be set accordingto the status of the relevant zone LED as shownbelow:

Zone LED LED On LED Off

Zone 1 Bell output is anSAB

Bell output is anSCB

Zone 2 System is set byFinal Exit

System is set byTimed exit

Zone 3 System is resetby the Engineer

System is resetby the User

Zone 4 System re-armsthree times

System re-armsonce

Zone 5 Keyswitch =Home set

Keyswitch =Away set

Final Exit RST output isSW12V

RST output isDetector Reset

3. When completed, press [0] to accept, a highpitched acceptance tone will be heard.

Returning to the Unset ModeOnce all the engineer programming is completedthe system can be returned to the unset mode bypressing the [0] key. The user passcodes and"HOME" set conf igurat ion must also beprogrammed, see the "User Guide" for full details.

Full Setting the System (AWAY)The engineer can use his passcode to full set thesystem as follows:

1. Ensure that the engineer’s menu is selected,then press [AWAY] to full set the system.

2. The exit tone will start and the Final Exit LED willflash.

3. When the exit tone stops, the system is full set.

Part-Setting the System (HOME)The engineer can use his passcode to part set thesystem as follows:

1. Ensure that the engineer’s menu is selected,then press [HOME] to part set the system.

2. The Final Exit LED will flash (HOME set is alwayssilent and timed).

3. When the high pitched tone is heard thesystem is part set.

Unsetting the SystemThe engineer can only use his passcode to unsetthe system when the system is set or part set usingthe engineer passcode (i.e., if the system is set bythe user the engineer passcode will NOT unset thesystem).

1. Enter via the prescribed entry route.

2. The entry tone will start and the Final Exit LED willflash.

3. Enter the engineer’s passcode (e.g., 1 2 3 4 ).

4. The entry tone will stop and the unset LED willlight.

18

Programming TS400/TS410 Installation Instructions

Page 19: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Testing & Fault Finding

Testing the SystemOnce the system has been installed and fullyprogrammed it can be tested. Before performingany tests it is advisable to warn your neighbours ofany tests that involve using the external sounder.

1. Perform a WALK TEST to ensure that all zones areoperating correctly.

2. Perform a BELL TEST to ensure that the externalsounder and strobe is operating correctly (See"User Operating Instructions" for details on BELLTEST).

3. Set the alarm system. Open a door or activatea detector to create an alarm.

4. Unset the system to silence the internal andexternal sounder.

5. Ensure the correct zone LED is lit, then enter thepasscode again to clear the indications.

Installation and checks are now complete, if thereare any problems in your installation refer to thesection on Fault Finding.

Fault FindingIf you have carefully followed the installation andwiring instructions and carried out the variouschecks correctly, your security system will now befully operational.

However if the system is not operating correctlywhen you have completed the installation, or ithas developed a fault after a period of troublefree operation, the Fault Finding Charts will helpyou identify and clear the fault.

Before using the fault finding charts refer to thefollowing notes:

� When removing covers from the controlpanel, external sounder or detectors you mustremember to first enter the four digit engineercode into the control panel.

� When all tests are complete, remember toreplace all covers etc.

� A battery operated circuit tester availablefrom most hardware and DIY stores, or asimple battery bulb and length of wire, willassist in checking the continuity of circuitwiring, if necessary.

19

TS400/TS410 Installation Instructions Testing & Fault Finding

Page 20: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Chart 1 - Zone Faults

20

Testing & Fault Finding TS400/TS410 Installation Instructions

Enter 4 digitengineer code and

then press 3 to selectwalk test mode

Relevant zone LEDon and pulsed

sounder

Remove wiring fromfaulty zone and linkwith a piece of wire.

Remove link fromfaulty zone and re-fit

zone wiring.

Remove zone wiringfrom detector and

twist together

If the control panelsounder remains

silent, the fault is inthe detector

If the control panelsounder is puled,there is an open

circuit in the wiring.

No zone LED's onand sounder is off.

Relevant zone LEDstill on and pulsed

sounder.

Control Panel Faulty.

Relevant zone LEDlight's and sounder

changes to a pulsedtone.

Control panel anddetector are OK.

Enable case tamperand re-fit cover.

No change incontrol panelindecations.

Remove the wiringfrom the faulty zone.

Relevant zone ledlight and sounder

changes to a pulsedtone

Re-fit zone wiring atcontrol panel.

remove zone wiringfrom detector

No zone LEDs onand sounder is off.

Control Panel Faulty

If the control panelsounder remainssilent, there is a

short in the wiring.

Activate therelevant detector

No zone LED's onand sounder is off.

Remove controlpanel front cover

and disable the casetamper switch

If the control panelsounder is pulsed,the fault is in the

detector

Permanent ZoneFault

Detectors Fail ToOperate

Page 21: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Chart 2 - System Will Not Set

21

TS400/TS410 Installation Instructions Testing & Fault Finding

Enter 4 digitengineer code and

then press 3 to selectwalk test mode

Zone LED on andPulse Sounder.

No zone LED's onand sounder is off.

Press to exitWalk Test.

[0]

Press orto part set

or full set the system.

[HOME]

[AWAY]

Remove controlpanel cover anddisable the case

tamper.

Remove wiring fromAUX TAMPER

terminals and linkwith a piece of wire

If the Tamper LEDremains lit, fit link

between TMP- andH/O -

If Tamper LED goesout there is an open

circuit within theAUX TAMPER wiring.

If the Tamper LEDremains lit ,

disconnect thebattery.

If tamper LED goesout the tamper onthe external siren is

open.

If the Tamper LEDremains lit, thecontrol panel is

faulty.

If the Tamper LEDgoes out the

battery is faulty

Tamper LED on.See Chart 1 on ZoneFaults

Deactivate alldetectors & contacts

(e.g. close doorsetc.)

Page 22: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Chart 3 - External Sounder Faults

22

Testing & Fault Finding TS400/TS410 Installation Instructions

Check PA buttonsare not depressed.

External Sirensounds continuously.

Enter 4 digitengineer code andremove the control

panel cover.

Remove the wirefrom the TRG-

terminal..

If zone 5 LED ison, the fault is

within the PA circuit.(see chart 1)

Enter 4 digitengineer code andremove the control

panel cover.

Using a voltmetercheck this is

13 - 14V betweenH/O+ & H/O-.

Check TRG- isprogrammed for

correct type (SAB orSCB).

Remove the wirefrom the TRG-

terminal.

If there is no readingcheck the Bell Fuse

hasn't blown.

Activate therelevant detector

Place the removedwire on the H/O-

terminal. The sirenshould sound.

If voltage reads OK,the fault is likely tobe within the siren

External siren willnot trigger whenperforming a Bell

Test.

external siren soundscontiniously.

If the siren did notsound check

connections at thesiren

If the connectionsare OK the fault is

likely to be within thesiren.

External siren stops.

If the siren triggeredOK the fault is likely

to be within thecontrol panel.

Ensure that thesystem is in theunset mode.

Page 23: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

Installation Records

23

TS400/TS410 Installation Instructions Installation Records

Zone Programming

Zone Type Location Chime Home Config.

1 Alarm / Access On / Off Armed / Omitted

2 Alarm / Access On / Off Armed / Omitted

3 Alarm / Keyswitch On / Off Armed / Omitted

4 Alarm / Fire On / Off Armed / Omitted

5 Alarm / PA On / Off Armed / Omitted

Final Exit On / Off Always Armed

Timers

Exit Time 10 seconds 30 seconds 1 minute 2 minutes

Entry Time 10 seconds 30 seconds 1 minute 2 minutes

Bell Duration 90 seconds 3 minutes 10 minutes 20 minutes Continuous

System Options

Bell Output Setting Mode Reset By Re-arms Keyswitch RST Output

SCB Timed User 1 re-arm Away set Detector Reset

SAB Final Exit Engineer 3 re-arms Home set SW12V

Installer Information

Remote Reset No.

For Remote Reset Telephone:

Company Name:

Address:

Telephone No.:

Date Installed:

Page 24: D:Menvier docsTS400TS400INS s400insmcalarms.co.uk/manuals/1c3834e6f3f92ee7c1b4d693d...doors/windows where it is not possible to use flush contacts e.g. garage doors, UPVC windows etc

18014 Drg. No. 33:1939:00 Issue 01 Doc 01 April 97

Key Function Action LEDs On Off

1 Zone TypesPress [1] - [5] to toggle

LEDs on/off.Press [0] to end

12345

Z1 = AccessZ2 = AccessZ3 = KeyswitchZ4 = FireZ5 = PA

Z1 = AlarmZ2 = AlarmZ3 = AlarmZ4 = AlarmZ5 = Alarm

2 View LogPress [1] for newest eventPress [4] for oldest event

Zone LEDs that light have caused an alarm

3 Walk TestActivate detectors.

Press [0] to endWhen the zone is in alarm the panel will sound

and the relevant zone LED will light.

4 Exit TimePress [1] to [4].Press [0] to end

1234

10 seconds30 seconds1 minute2 minutes

5 Entry TimePress [1] to [4].Press [0] to end

1234

10 seconds30 seconds1 minute2 minutes

6 Bell DurationPress [1] - [5].

Press [0] to end

12345

90 seconds3 minutes10 minutes20 minutesContinuous

7Change Engineer's

PasscodeEnter new passcode

twiceZone LEDs 1 - 4 will light, as code is entered

each LED will go out one by one.

8 Remote Reset No. Enter reset number twiceZone LEDs 1 - 3 will light, as code is entered

each LED will go out one by one.

9 System OptionsPress [1] - [6] to toggle

LEDs on/offPress [0] to end

12345

F.Exit

Bell output = SABSet by Final ExitReset by Engineer3 re-armsKey = Home setRST = SW12V

Bell output = SCBSet by Timed ExitReset by User1 re-armKey = Away setRST = Det. Reset

HOME Part set the system Leave via exit route

AWAY Full set the system Leave via exit route

0 Return to unset

Engineer's Quick Reference Programming Chart

Cooper Security Ltd, Security House,Vantage Point Business Village,Mitcheldean, Gloucestershire,GL17 0SZ. England

Product Support Tel: +44 (0)1594 545556Available between;08:15 and 17:00, Monday to Thursday.08:15 and 12:45 Friday. Emergency service onlybetween 12:45 and 17:00 Friday.Product Support Fax: +44 (0)1594 545401.www.coopersecurity.co.uk