Distribution Feders

Embed Size (px)

Citation preview

  • 8/14/2019 Distribution Feders

    1/21

    UnitUnit--IIIIDistribution FeedersDistribution Feeders

    by

    N.Ramchander,Asst Professor,EEED-BVRIT.

    by

    N.Ramchander,Asst Professor,EEED-BVRIT.

  • 8/14/2019 Distribution Feders

    2/21

    CONTENTS

    CONTENTS

    8/16/2009

    Introduction Distribution System-Classification Connection Schemes of primary feeders

    Primary Distribution feeder rating Primary Distribution voltage levels

    Primary feeder loading Secondary Distribution Systems

  • 8/14/2019 Distribution Feders

    3/21

    INTRODUCTION

    INTRODUCTION

    Classical Structure of Power System

    8/16/2009

  • 8/14/2019 Distribution Feders

    4/21

    8/16/2009

  • 8/14/2019 Distribution Feders

    5/21

    8/16/2009

    Distribution System-Classification

    1. Primary distribution, which carries the load at higher thanutilization voltages from the substation (or other source) to the poin

    where the voltage is stepped down to the value at which the energy

    is utilized by the consumer.

    Primary distribution systems include three basic types:

    1. Radial systems, including duplicate and throwover systems

    2. Loop systems, including both open and closed loops

    3. Primary network systems

    2. Secondary distribution, which includes that part of the systemoperating at utilization voltages, up to the meter at the consumers

    premises.

  • 8/14/2019 Distribution Feders

    6/21

    8/16/2009

    Secondary distribution systems operate at relatively low utilizationvoltages and, like primary systems, involve considerations of servicereliability and voltage regulation. The secondary system may be of fourgeneral types:

    1. An individual transformer for each consumer; i.e., a single service

    from each transformer.

    2. A common secondary main associated with one transformer from whicha group of consumers is supplied.

    3. A continuous secondary main associated with two or moretransformers, connected to the same primary feeder, from which a groupof consumers is supplied. This is sometimes known as bankingof

    transformer secondaries.

    4. A continuous secondary main or grid fed by a number of transformers,connected to two or more primary feeders, from which a

    large group of consumers is supplied. This is known as a low-voltageorsecondarynetwork.

  • 8/14/2019 Distribution Feders

    7/21

    Factors Affecting Selection of feederFactors Affecting Selection of feeder

    The nature of the load connected

    The load density of the area served

    The growth rate of the load

    The type and cost of circuit employed The design and capacity of the substation

    involved

    The quality of the service required The continuity of the service required

    8/16/2009

  • 8/14/2019 Distribution Feders

    8/21

    Radial Systems

    8/16/2009

    Advantages:

    Simplest and lower cost

    Simple in planning, design, andoperation.

    Most widely used from ofdistribution system(99%-inINDIA)

    Disadvantages:

    it is less reliable than other two

    If any branch along this pathfails, a loss of power delivery

    results.

  • 8/14/2019 Distribution Feders

    9/21

    Loop Type Feeders

    which essentially provide a two-way primaryfeed for critical consumers.

    the supply from one direction fail, the entireload of the feeder may be carried from the

    other end this type of system may be operated with the

    loop normally open or with the loop normallyclosed.

    8/16/2009

  • 8/14/2019 Distribution Feders

    10/21

    Open Loop System

    8/16/2009

    1

  • 8/14/2019 Distribution Feders

    11/21

    In the event of a fault, the section of the primary

    on which the fault occurs can be disconnected at

    both its ends and service re-established to the

    unfaulted portions by closing the loop at the pointwhere it is normally left open, and reclosing the

    breaker at the substation (or supply source) on the

    other, unfaulted portion of the feeder.

    The disconnecting devices between sections are

    manually operated and may be relativelyinexpensive fuses, cutouts, or switches.

    8/16/2009

    1

  • 8/14/2019 Distribution Feders

    12/21

    Closed LoopSystem

    8/16/2009

    1

  • 8/14/2019 Distribution Feders

    13/21

    8/16/2009

    1

    This type of systems are used, where a greater degree

    of reliability is desired. Here, the disconnecting devices are usually the more

    expensive circuit breakers.

    The breakers are actuated by relays, which operate

    to open only the circuit breakers on each end of the

    faulted section, leaving the remaining portion of theentire feeder energized.

    when the fault is located, the disconnecting devices

    on both ends of the faulted section may be openedand the unfaulted sections reenergized by closing the

    proper circuit breakers.

  • 8/14/2019 Distribution Feders

    14/21

    Primary Network Systems

    8/16/2009

    1

  • 8/14/2019 Distribution Feders

    15/21

    8/16/2009

    1

    Primary network is a system of interconnected

    feeders supplied by a number of substations. The primary network system supplies a load fromseveral directions.

    In general losses in a primary network are lowerthan those in a comparable radial system due toload division.

    The reliability and the quality of service of theprimary network arrangement is much higher than

    radial and loop arrangements. However, it is more difficult to design and

    operate than the radial or loop type.

  • 8/14/2019 Distribution Feders

    16/21

    Tie LinesTie Lines

    8/16/2009

    1

    A tie line is a line that connects two supplysystems to provide emergency service to onesystem from another.

    Usually, a tie line provides service for area loadsits route as well as providing for emergency

    service to adjacent areas or substations.

  • 8/14/2019 Distribution Feders

    17/21

    8/16/2009

    1

  • 8/14/2019 Distribution Feders

    18/21

    Low Voltage DistributionLow Voltage DistributionSystem(LVDS)System(LVDS)

    8/16/2009

    1

    High Voltage DistributionHigh Voltage DistributionSystem(HVDS)System(HVDS)

  • 8/14/2019 Distribution Feders

    19/21

    Factors Affecting the FeederFactors Affecting the Feeder

    voltage levelvoltage level The feeder voltage level is important factor

    affecting the system design, cost and operation. Some of the design and operational aspects of

    the primary voltage levels depend upon the: Feeder length

    Feeder loading

    No of distribution S/Ss and its rating

    No of Primary lines

    No of customers effected by a specific failure

    System maintenance practice

    8/16/2009

    1

  • 8/14/2019 Distribution Feders

    20/21

    Voltage Square rule:Voltage Square rule:

    8/16/2009

    2

    For a given percentage of voltage drop, the length of feeder and

    loading are direct functions of the feeder voltage levels.

    Ex:- if feeder voltage level is doubled for the same permissibledrop, the power capacity of the feeder is four times and length

    of the feeder can be increased four times.

    thereforevoltage square factor = (VLN

    new) length ratio X load ratio

    (VLNold )

    length ratio = new length/old length

    load ratio = new feeder loading/old feeder loading

  • 8/14/2019 Distribution Feders

    21/21

    8/16/2009

    2

    g{t~ Y t|xg{t~ Y t|x