Upload
doankiet
View
219
Download
0
Embed Size (px)
Citation preview
DISTANCE PROTECTION OF TRANSMISSION LINE
1S.Padmini A.P(Sr.G)/EEE SRM University
Comparison Between Distance Relays
Comparison of distance relays
S.Padmini A.P(Sr.G)/EEE SRM University 2
Comparison of distance relays
Distance Protection of a Three-phase Line
S.Padmini A.P(Sr.G)/EEE SRM University 3
The problem of providing distance protection to a three-phase line
Continued…
S.Padmini A.P(Sr.G)/EEE SRM University 4
Presence of sequence components in various faults
Phase Faults
Phase a sequence network connection for b-c phase fault
S.Padmini A.P(Sr.G)/EEE SRM University 5
Phase a sequence network connection for b c phase fault.
Continued…
S.Padmini A.P(Sr.G)/EEE SRM University 6
Continued…
Phase a sequence network connection for b-c phase fault.
S.Padmini A.P(Sr.G)/EEE SRM University 7
Continued…
S.Padmini A.P(Sr.G)/EEE SRM University 8
Ground FaultsGround Faults
S.Padmini A.P(Sr.G)/EEE SRM University 9
Continued…
S.Padmini A.P(Sr.G)/EEE SRM University 10
Phase a sequence network connections for a-g fault.
Continued…
S.Padmini A.P(Sr.G)/EEE SRM University 11
Continued…
S.Padmini A.P(Sr.G)/EEE SRM University12
Continued…• Complete Protection of a Three‐phase Line
S.Padmini A.P(Sr.G)/EEE SRM University 13
Complete protection of a three-phase line.
Three-stepped Distance Protection
S.Padmini A.P(Sr.G)/EEE SRM University14
Continued…
Three-stepped distance protection simplified representation
S.Padmini A.P(Sr.G)/EEE SRM University15
Continued…
S.Padmini A.P(Sr.G)/EEE SRM University 16Three-stepped distance protection using mho relays.
Continued…
S.Padmini A.P(Sr.G)/EEE SRM University 17
Loss of selectivity of second zone of RA with second zone of RB .
Continued…
S.Padmini A.P(Sr.G)/EEE SRM University 18
Philosophy of the three-stepped distance protection
Trip Contact Configuration for the Three-stepped DistanceTrip Contact Configuration for the Three-stepped Distance Protection
S.Padmini A.P(Sr.G)/EEE SRM University 19
Trip contact circuit of the three-stepped distance scheme.
Impedance Seen from Relay SideImpedance Seen from Relay Side
S.Padmini A.P(Sr.G)/EEE SRM University 20
Continued…
S.Padmini A.P(Sr.G)/EEE SRM University 21
Impedance seen from the relay side.
Th t d P t ti f D bl E d F d LiThree-stepped Protection of Double-End-Fed Lines
S.Padmini A.P(Sr.G)/EEE SRM University 22
Only 60% of the line gets high speed distance protection.
Review Questionsh h d b k if f l• 1. What are the drawbacks, if any, of over-current relays?
• 2. Why are over-current relays not used for primary protection of EHV linesin spite of the fact that instantaneous over current relays exist?3 i h i i li d ll d f h k f di l i ?• 3. How is the transmission line modelled for the sake of distance relaying?
• 4. Arc resistance is a function of spark-over distance, wind velocity and time.Explain.5 Wh d b lli f l ?• 5. What do you mean by a metallic fault?
• 6. How is it different from an arcing fault?• 7. What is the effect of fault resistance on the reach of various distance
l ?relays?• Which relay is the most affected and which the least affected?• 8. What do you mean by power swing?
S.Padmini A.P(Sr.G)/EEE SRM University 23
• 9. Will an over-current relay be affected by power swing?
Review Questions• 10. How do different distance relays perform with respect to their behaviour on
load,• effect of arc resistance on the reach and response to power swing?effect of arc resistance on the reach and response to power swing?• 11. Prove that a-6 distance measuring unit fed with (Va- Vb) and (Ia - Ib) responds a
correctly to a-b-g faults as well as a-b-c faults. • 12 Why is residual current compensation required in case of ground fault distance• 12. Why is residual current compensation required in case of ground fault distance
measuring unit?• 13. Explain the need for a three-stepped distance protection of a transmission line.• 14. How many distance measuring units will be required for the complete three-• stepped protection of a transmission line section in case of (i) a singly-fed-systems
and (ii) a double-end-fed system?
S.Padmini A.P(Sr.G)/EEE SRM University 24
• 15. The impedance seen from the relay side in a distance relay is 10 ohms. Given that the CT ratio is 1000 : 1 and the PT ratio is 100,000 : 110, determine the actual impedance. Given that the line has a resistance of 1 milliohm per km and a