4
Display Vision DV1U1230L13AC Operating Manual 01/2014

Display Vision DV1U1230L13AC - Effekta · the permissible operating range. Cause: The battery is defective and must be replaced. Please ensure proper disposal. Battery capacity very

  • Upload
    others

  • View
    13

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Display Vision DV1U1230L13AC - Effekta · the permissible operating range. Cause: The battery is defective and must be replaced. Please ensure proper disposal. Battery capacity very

Display VisionDV1U1230L13AC

Operating Manual

01/2014

Page 2: Display Vision DV1U1230L13AC - Effekta · the permissible operating range. Cause: The battery is defective and must be replaced. Please ensure proper disposal. Battery capacity very

Congratulations on your purchase of one of the most technically advanced exit sign luminaire - VISION.VISION is developed and produced 100% in Germany.

1. Handling

VISION is a technical product. Please read the safety instructions (see section 6) before commissioning. The law requires that a “responsible person” has to be named for this product, who records the test results of the weekly functional and annual endurance tests “in a test book including the date”. The result of the respective test can be read over the LED status display. It has to be ensured that two adjacent VISION luminaires are not tested in the same time interval. Note: the test duration (up to 3 hours) and the recharge time (20 hours) are to be taken into consideration. We recommend scheduling the test of the adjacent luminaires to take place 2 days later.

2.

VISION is equipped with the AutoCheck function (self-diagnostics function), and automatically carries out the weekly functional and annual endurance tests. The following is checked: the switchover from mains to emergency mode, the charger, the battery voltage, the LED array and the battery capacity over the complete duration of the supply (only for the endurance test).

The AutoCheck timer is started when VISION is connected to the mains voltage for the first time. The first functional test runs exactly one week later. The 53rd test is an endurance test. This is also started automatically. You can change the start time of the AutoCheck timer by starting the functional test via the test button:

The next automatic test now runs exactly one

3.

week later.

VISION is equipped with a nickel-metal hydride battery. The battery should be charged for at least 20 hours following commissioning. The battery is then fully charged and can power the LED array for at least 3 hours in the event of a mains failure. Ensure that the VISION environmental temperature is +10°C to +40°C. Temperature differences shorten the lifetime of the battery.

4.

VISION can be operated as maintained and non-maintained luminaire.There are two jumpers on the middle of the board for this purpose. The position is marked with DS for maintained lighting (jumper centre-right) and BS for non-maintained lighting (jumper centre-left).

The image shows programming in standby circuit (BS)

Select the operating mode you need and start a manual function test. The luminaire is preset as maintained luminaire at time of delivery.

5.

The current status of the VISION lighting is shown over multi-coloured LED status display:

Mains operation: Mains voltage available. The battery is charged.

Test mode: VISION is currently running a test (AutoCheck function). Test duration of weekly function test – about 5 minutes. Test duration of annual endurance test – up to 3 hours.

Power failure:VISION is supplied by the battery (Back-up time: 3 hours)Help:Check whether there is mains voltage on the network terminal. This has to be 230V AC-50/60Hz.

Operating Manual / Display Vision

2

LED-Status display

Set operating mode

AutoCheck function

The battery

Page 3: Display Vision DV1U1230L13AC - Effekta · the permissible operating range. Cause: The battery is defective and must be replaced. Please ensure proper disposal. Battery capacity very

Battery fault:The battery cannot be charged.Help:a) Check whether the battery plug is inserted into the PCB.b) The battery voltage is outside the permissible operating range.Cause: The battery is defective and must be replaced. Please ensure proper disposal.

Battery capacity very low: The battery capacity is very low (display after functional test)Help:a) Before the first functional test, charge the battery for at least 20 hours. Run a new function test by briefly pressing the VISION test button once. The LED now flashes green (test mode).b) The battery loses capacity due to age. Replace the battery and ensure proper disposal.

Battery capacity low: This display appears following an annual endurance test.The battery capacity is too low to guarantee the back-up time of 3 hours.Help:The battery loses capacity due to age. Replace the battery and ensure proper disposal.

LED array: At least one LED has malfunctioned/has reduced light intensity.Help:The LEDs are firmly mounted to the motherboard. These cannot be replaced individually. To replace, disconnect the battery from the motherboard and replace the

6.

motherboard.

Installation and assembly work may only be carried out by a qualified electrician.

• Do not cover the product.• Do not hang or attach anything to the

product.• Only use the product when it is working

properly. In case of malfunction, do NOT touch or

continue to operate the product. Touching and continuing to operate the

product when there is a malfunction carries the risk of danger to life from electric shock, burning hazard or fire hazard!

There is a malfunction if:• visible damage appears• the product cannot be run properly (e.g.

flickering)• it smokes, steams or there are audible

crackling noises• the smell of fire arises• overheating is detected

Only operate the product again following maintenance and inspection by a qualified electrician.

7.

This product is used for marking emergency and escape routes and may:• only be operated with a voltage of 230V AC

– 50/60Hz• only be operated if it is securely mounted• only be operated in dry areas, so not

- in damp or dirt-prone areas- in areas where there is a high level of

humidity• not be exposed to strong mechanical stress

or a high level of contamination• only be operated after checking its condition

following damp or contaminated storage• not be altered or modified!

8. Care

Clean the product regularly – only with a damp, soft and lint-free cloth.

Operating Manual / Display Vision

3

Safety instructions

Intended use

Page 4: Display Vision DV1U1230L13AC - Effekta · the permissible operating range. Cause: The battery is defective and must be replaced. Please ensure proper disposal. Battery capacity very

9. Other important information

• Warranty: In the event of a warranty case, please contact your specialist dealer.

• Storage: The product has to be stored in a dry area, where it is protected from contamination and mechanical stress.

• Disposal: Do not dispose the product with household waste! Products with this symbol conform to the directive (WEEE, 2003/108) on electric and electronic equipment to be disposed via the local collection points for waste electric equipment! The battery has to be disposed separately.

10. electrician)

Switch off the mains supply or unplug the power cord before starting any work!

There is the risk of electric shock resulting in death!

Only use accessories which have been delivered with this product or are definitely described as accessories. Otherwise safe operation is not guaranteed. Risk to life and a fire hazard could arise.

Check whether there are loose parts in the product. If there are and the existence of such parts is not explicitly described, the product may not be installed or commissioned. Accessible parts may be energized by connection - danger to life!

Only use suitable mounting materials for the mounting base.Unsuitable mounting material could result in danger to life or personal injury from the product falling over.

Unpacking• Carefully take the product out of the

packaging and remove any transport protection.

• When disposing of the packaging, follow the relevant environmental regulations of your country.

• Before disposing of the packaging material, check that all parts of the product have been removed.

Installation site• The product is suitable for mounting on

walls and ceilings.• Only mount the product on a stable and even

foundation, which is secure from toppling over.

Installation steps• For this, please read the enclosed installation

manual.

Useful informationVISION is powered by a durable, nickel-metal hydride battery.To extend the battery life, disconnect the power supply of the VISION light for at least 1 hour every 2 months.

Effekta Power Systems ABSadelgatan 6213 77 MALMÖ

Tel.: +46 40-94 60 20

E-Mail: [email protected]: www.effekta.se

Operating Manual / Display Vision

Installation (only by a qualified