Digital Transmitter 2010TD-TA Series

Embed Size (px)

Citation preview

  • 8/12/2019 Digital Transmitter 2010TD-TA Series

    1/14

    Measured media: gases, vapours, liquids

    Accuracy: 0.075% (option 0.05%)

    One sided overload up to rated pressure;max. 410 bar (6000psi)

    Large turn down ratio 100 : 1

    Span and zero externally adjustable

    Transfer function configurable:linear square rooting freely programmable

    In conjunction with the LCD indicator, the transmitter can beconfigured with the external keys

    Communication protocol:PROFIBUS PA or Foundation Fieldbus orHART, 4...20mA

    Explosion protection: Intrinsic safety flameproof enclosure

    connection to Zone 0

    Surge voltage resistant acc. to IEC 61000-4Interchangeable electronics with self reconfiguration

    1 ApplicationTheMulti Vision- series is a complete series of differen-

    tial pressure, pressure and absolute pressure transmitters with an

    analogue or digital output signal for the process industry.

    The transmitter 2010TD measures differential pressure, flow rate

    or level; the transmitter 2010TA absolute pressure of aggressive

    and non-agressive media.

    The measuring ranges are:

    2010TD: from 1 kPa to 10 MPa (5 in. H2O to 1500 psi)

    2010TA: from 40 kPa to 2 MPa abs. (160 in. H2O to 300 psia)

    each for the nominal pressure ranges (safe working pressure

    SWP) 160, 250 and 410 bar (2300, 3600 and 6000 psi).

    2010TD for Differential

    Pressure, Flow Rate and Level

    2010TA for Absolute PressureSpans: 50 Pa ... 10 MPa (0.2 in. H2O...1500 psi)

    2 kPa ... 2 MPa abs. (8 in. H2O ... 300 psia)

    Multi Vision

    Digital Transmitter

    10/15-4.10 EN

    2010TDSW.TIF

  • 8/12/2019 Digital Transmitter 2010TD-TA Series

    2/14

  • 8/12/2019 Digital Transmitter 2010TD-TA Series

    3/14

    10.2003 Page 3 of 14

    2010TD for Differential Pressure, Flow Rate and Level2010TA for Absolute Pressure 10/15-4.10 EN

    Technical data

    Alarm current

    Min. alarm current: configurable from 3.5 mA to 4 mA,

    standard setting: 3.6 mA

    Max. alarm current: configurable from 20 mA to 22.5 mA,

    standard setting: 21 mAStandard setting: max. alarm current

    LoadTransmitters with 4...20 mA

    Imax = 20 ... 22.5 mA (configurable)

    Us = supply voltage

    min. power supplyy: 10.5 VDC, 14 VDC with backlit LCD-indicator

    min. load for digital communications > 250 Ohm

    Field Bus units (communication code: P / F)

    Digital signal

    Transmission technique: acc. to IEC 61158-2Power supply: 10.2 VDC ... 32 V DC

    Base current: 14 mA

    Transmission rate: 31.25 kbits/s

    PROFIBUS-PA: Version 3.0, Profile B for pressure

    transmitters; Ident No.: 04C2 HEX

    Foundation Fieldbus: FF-890 / 891 and FF-902 / 903

    Characteristic

    Linear, square root, freely programmable with 20 reference points,

    x3/2and x5/2output function

    5 Accuracy

    Reference conditions

    to DIN IEC 60 770

    Temperature: 20 C (68 F)Relative humidity: 65 %

    Atmospheric pressure: 1013mbar (1013 hPa, 14.7 psia)

    additional conditions:

    Separating diaphragm material Hastelloy C1), filll fluid silicone

    oil and linear output

    All specifications are limits and relate to the output range or cali-

    brated range. The influences marked relate to the measuring

    range (URL) and are to be multiplied by the turn down factor (ratio

    range (URL) / calibrated span). The turn down factor should be

    kept to a minimum.

    Conformity

    for 2010TD and 2010TA, dp-sensor:

    terminal based, including hysteresis and the dead band2)

    Optional2)(Order code: 5C9)

    for 2010TD, pabs-sensor:

    0.8 bar, with pabs-sensor 6 bar: 12 mbar

    (321 in.H2O, with pabs-sensor 90 psi: 4,82 in.H2O)

    Hysteresis 2)

    Reproducibility0.01 %

    Warm-up time

    < 15 s

    Rise time

    The time behaviour of this transmitter is composed of the rise time

    of the sensor and an adjustable integration time constant of the

    A/D converter. A high time constant results into a high resolution,

    e.g. required for a high span ratio, and at the same time into a high-

    er rise time for the output signal. A low time constant means a low-

    er resolution, but a shorter rise time and thus a faster reaction time

    of the transmitter. In case of the default integration time constant

    the values shown in the table below result

    .

    additional adjustable time constant 0.. .60s

    The effect appearing at the output for non-linear output (e.g.square root function) depends on the function and is to be calcu-lated accordingly.Long-term drift

    0.05% per 12 months

    Effect of position

    Ranges

    on zero approx. 3.5 mbar (1.4 in.H2O) x sin

    ( = angular deviation in degrees

    from the nominal mounting position)

    Ambient temperature effect (dp-sensor)

    Temperature coefficient (-40C...+80C)3)4)/ (-40F...+176F)3)4)

    on zero 0.04 % per 10 K (18F)

    on span 0.04 % per 10 K (18F)

    Ambient temperature effect (pabs-sensor (2010TD))

    Thermal change (-40C ... +80C)3)4) / (-40F...+176F)3)4)

    on zero 0.4 bar (160 in.H2O)

    6 mbar with 6 bar pabs-sensor

    (2.4 in.H2O with 90 psi-sensor)

    Thermal change (-20 C ... +60 C)3)4) / (-4 F...+140 F)3)4)

    on span 2 bar (803 in.H2O)

    30 mbar with 6 bar pabs-sensor

    (12 in.H2O with 90 psi-sensor)

    linear square root

    0.075% 0.15%

    linear square root

    0.05% 0.1%

    RUs 10 5V,

    Imax------------------------------- in kOhm

    linear square root

    0.05% 0.1%

    range linearsquare

    root

    freely

    program-

    mable

    function

    turn down factor

    1 : 10

    > 1 : 10

    up to

    1 : 20

    > 1 : 20

    up to

    1 : 40

    > 1: 40

    10mbar(4 in.H2O)

    ~ 2.0 s ~ 2.2 s ~ 2.6 s ~ 3.1 s ~ 2.6 s ~ 2.2 s

    60mbar(25 in.H2O)

    ~ 0.8 s ~ 1.0 s ~ 1.4 s ~ 1.9 s ~ 1.4 s ~ 1.0 s

    400mbar(160 in.H2O) ~ 0.3 s ~ 0.5 s ~ 0.9 s ~ 1.4 s ~ 0.9 s ~ 0.5 s

    http://ea410v02.pdf/http://ea410v02.pdf/
  • 8/12/2019 Digital Transmitter 2010TD-TA Series

    4/14

    Page 4 of 14 10.2003

    2010TD for Differential Pressure, Flow Rate and Level2010TA for Absolute Pressure 10/15-4.10 EN

    Technical data

    Thermal change (-40C ... +80C)3)4) / (-40 F...+176 F)3)4)

    on span 3 bar (1204 in.H2O)

    45 mbar with 6 bar pabs-sensor

    (18 in.H2O with 90 psi-sensor)

    Static pressure effect

    Effect of electro-magnetic interference 0.05%

    1) with Tantalum, Monel or Gold Plated Isolating Diaphragm, the

    factor 1.5 is to be taken into account with static pressure and

    ambient temperature effect with conformity2) additionally with turn-down factor > 10:1

    3) with range 10mbar / 100 bar:

    -20 C ... +60 C (4 in.H2O / 1450 psi: (-4 F...+140 F)4) with carbon fluoride filling liquid:

    -20 C ... +80 C (-4 F ... +176 F)

    6 General conditions

    6.1 Installation conditions

    Notes on installation

    Installation position: The transmitter can be directly flanged in any

    position. Preferably in such a position that the process flange axes

    are vertical (horizontal with barrel-type amplifier housing). Devia-

    tions from this can cause a shift in the zero, which can be correct-

    ed. The electronic housing can be rotated through 360and can

    be fixed in any position. A stop prevents the housing beeing turned

    too far.

    6.2 Ambient conditions

    Ambient temperature-40 C ... +85 C (with O-ring Viton / PTFE: -20 C ... +85 C)

    (-40 F ... +185 F) (with O-ring Viton / PTFE: -4 F ... +185 F),

    Observe approvals for explosion-protected transmitters.

    Storage temperature / transport temperature

    -50 C ... +85 C, with LCD-indicator -40 C ... +85 C

    (-58 F ... +185 F, with LCD-indicator -40 F ... +185 F)

    Humidity

    Relative humidity: 95% annual average

    Condensation, icing: admissible

    Protection class

    IP 67 acc. to EN 60 529 ( NEMA Standard Type 6);

    with Han 8U plug: IP 65 (NEMA Standard Type 4x)

    Protective varnish

    epoxy resin, greywhite, RAL 9002

    Shock resistant

    Acceleration: 50g

    Duration: 11msVibration resistance

    2g up to 1000 Hz, with amplifier housing made of stainless steel

    are valid restricted values (on request)

    Electromagnetic compatibility (EMC)

    to EN 50 082-2

    Definition: Class 3

    Radio suppression (EN 55 011): Limit class B

    Fulfills NAMUR recommendation.

    Process conditions

    Temperature limits

    -50 C ... +120 C (-58 F ... +248 F), at process connection

    to +400 C (752F) in conjunction with remote seals.

    with gaskets:

    O-rings Viton / PTFE -20 C ... +120 C

    (-4 F ... +248F)

    Pressure limits

    2010TD:Static pressure limits: from 3.5 kPa abs. (14 in.H2O abs.)

    to the nominal pressure (SWP);

    proof pressure up to 1.5-times the nominal pressure simultaleously

    on both sides of the transmitter admissible.

    2010TA:Static pressure limits: from full vacuum up to the nominal

    pressure (SWP);

    proof pressures up to 1.0-times the nominal pressure admissible.

    Overload limit

    One-sided overload up to the nominal pressure (SWP).

    Weight

    3.5 kgMaterial

    Sensor body: 316 L stainless steel

    Isolating diaphragm(s): Hastelloy C * / 316 L stainless steel *

    (1.4435) / Tantalum / Monel /gold plated

    Process flange: 316 L stainless steel (1.4404) * /

    Hastelloy C * / Monel * / PVDF

    Nuts and bolts: stainless steel (A4) *

    Plugs: as process flange material

    Fill fluid: Silicone oil / carbon fluoride

    O-rings: the whole ranges:

    Viton(FPM) (green)

    Perbunan (NBR) (black)

    EPDM * (black)

    furthermore: ranges 60mbar (24 in.H2O)PTFE * (white) :

    max. permissible SWP 250bar

    (3600 psi)

    min. permissible operating tempe-

    rature -20C (-4 F)

    range 10mbar (4 in.H2O) : FEP- coated silicone (grey)

    Amplifier housing / aluminium with epoxy resin coat /

    Housing cover: stainless steel

    * in compliance with NACE MR0175 Class II

    Measuring

    range

    10 mbar

    (4 in.H2O)

    60 mbar

    ( 24 in.H2O)

    100 bar

    (1450 psi)

    on

    zero

    up to 2 bar:

    0.05%

    up to 100 bar:

    0.05%

    up to 100 bar:

    0.1%

    > 2 bar:

    0,05% / bar

    > 100 bar:

    0.05% / 100 bar

    > 100 bar:

    0.1% / 100 bar

    on

    span

    up to 2 bar:

    0.05%

    up to 100 bar:

    0,05%

    up to 100 bar:

    01%

    > 2 bar:

    0.05% / bar

    > 100 bar:

    0.05% / 100 bar

    > 100 bar:

    0.1% / 100 bar

    0.005(measuring range

    adjusted span------------------------------------------ 0.05 ) %

    http://ea410v02.pdf/http://ea410v02.pdf/
  • 8/12/2019 Digital Transmitter 2010TD-TA Series

    5/14

    10.2003 Page 5 of 14

    2010TD for Differential Pressure, Flow Rate and Level2010TA for Absolute Pressure 10/15-4.10 EN

    Technical data

    Process connection

    Flange with fixing thread 7/16-20 UNF and 1/4-18 NPT female

    thread on both sides or

    flange connection to DIN 19 213 with thread M 10 for 6 bar (90 psi)

    and 160 bar (2300 psi) or M 12 for 250 bar (3600 psi) / 410 bar(6000 psi) and 1/4-18 NPT female thread on both sides.

    Electrical connections

    Two female threads 1/2-14 NPT or M 20 x 1.5 or one plug Han 8 U.

    (with Profibus PA: plug connector M 12 [without female mating

    plug]).

    Screw terminals for wire cross-sections up to 2.5 mm2.

    Cable connection compartment / electrical connection

    Electrical connection with plug

    barrel-type DIN-type

    7 Display and operation interface

    Operation with keys

    Retrofit / optional key unit for external adjustment of zero and spanand a write protect switch. There are no physical connections

    through the housing for the keys.

    In conjunction with an LCD indicator, the transmitter can be config-

    ured with the keys as follows:

    Zero and span with or without applied pressure, oblique sensor,

    damping, output current during faults, displayed value, pressure

    unit, linear or square rooting, temperature unit, as well as address

    with fieldbus devices.

    Operation via remote communications

    Communication protocol: PROFIBUS-PAor

    Foundation Fieldbusor

    HART

    Hardware: for HART

    :FSK modem for PC / notebook

    Handheld Terminal: STT 04 or HHT 275 or 691 HT

    LCD indicator

    2-line, 6-character 19-segment alphanumeric display with addi-

    tional bar chart display, optionally with back illumination. User-spe-

    cific displays:

    Pressure value as a physical unit or

    percentage of the output current or

    output current in mA or

    instrument temperature in freely selectable units or

    free process variable

    address (only with Fieldbus-Transmitters)

    Diagnostic messages, alarms, measuring range infringements andchanges in the configuration are also displayed.

    8 Auxiliary energy

    Transmitters with 4...20mA (communication code: H )

    Power supply: 10.5 ... 45 VDC (14 ... 45 VDC with backlit indicator), inverse polarity

    protection, explosion-protectedtransmitters, observe the approvals.

    Harmonic distortion: Maximal permissible voltage ripple of

    the power supply during the communi-

    cation:

    7 Vpp at 50Hz f 100Hz

    1 Vpp at 100Hz < f 200Hz

    0.2 Vpp at 200Hz < f 300HzField Bus units (communication code: P / F)

    Power supply: 10.2 ... 32 VDC, inverse polarityprotection, explosion-protectedtransmitters, observe the approvals.

    Pollution degree

    2 according to ANSI / ISA 82.01Overvoltage category

    II according to ANSI / ISA 82.01

    9 Certificates and ApprovalsObserve mounting conditions according to EN 60079-10; 1996ff!

    Transmitters of the type of protection Intrinsically safe

    EEx ia according to the directions 94 / 9 / EG (ATEX)

    Transmitter with 4...20 mA output signalMarking (DIN EN 50 014):II 1/2 G T 50C EEx ia IIC T6

    II 1/2 G T 95C EEx ia IIC T4

    EC-Type-Examination Certif.:ZELM 01 ATEX 0064

    (1st + 2nd add.)

    Supply and signal circuit type of protection Intrinsic Safety

    EEx ib IIB/IIC resp. EEx ia IIB/IIC

    for connection to supply units with maximum values:

    II 1/2 G T 50C EEx ia IIC T6

    II 1/2 G T 95C EEx ia IIC T4,

    for Temperature class T4:

    Ui = 30 V

    Ii = 200 mA

    Pi = 0,8 W for T4 with Ta = (-40...+85)C / (-40...+185)F

    M 0 1 4 3 1 E 2 . T I F

    Cable ent ry (e.g. v ia M 20 x 1.5)

    Outputsignal / powersupply

    Test socketsfo r 4 20 mA(not in funct ionwith f ieldbustransmitters)

    Earthing /

    potent ia lequalizingterminal

    Screw terminals for0,5. . .2,5 mm -wires

    2

    http://ea410v02.pdf/http://ea410v02.pdf/
  • 8/12/2019 Digital Transmitter 2010TD-TA Series

    6/14

    Page 6 of 14 10.2003

    2010TD for Differential Pressure, Flow Rate and Level2010TA for Absolute Pressure 10/15-4.10 EN

    Technical data

    Pi = 1,0 W for T4 with Ta = (-40...+70)C / (-40...+158)F

    for Temperature class T5, T6:

    Pi = 0.7 W for T6 with Ta = (-40...+40)C / (-40...+104)F

    effective internal capacitance,Ci 10 nF

    effective internal inductivity Li0

    Field Bus transmitters (PROFIBUS / Foundation Fieldbus)

    Marking (DIN EN 50 014):II 1/2 G T 50C EEx ia IIC T6

    II 1/2 G T 95C EEx ia IIC T4

    EC-Type-Examination Certif.:ZELM 01 ATEX 0064

    (1st + 2nd add.

    Supply and signal circuit type of protection Intrinsic Safety

    EEx ia IIB/IIC resp. EEx ib IIB/IIC

    for connection to FISCOsupply units with rectangular or

    trapezoidal characteristics with maximum values:

    II 1/2 G T 50C EEx ia resp. ib IIC T6 Ui = 17.5 V

    II 1/2 G T 95C EEx ia resp. ib IIC T4li = 360 mA

    Pi = 2.52 W

    II 1/2 G T 50C EEx ia resp. ib IIC T6Ui = 17.5 V

    II 1/2 G T 95C EEx ia resp. ib IIC T4li = 380 mA

    Pi = 5.32 W

    resp. for connection to supply unit or barrier with linear charac-

    teristics

    maximum values:

    II 1/2G EEx ia respectively ib IIC T4...T6 Ui = 24 V

    li = 250 mA

    Pi = 1.2 W

    effective internal inductance Li 10 H,

    effective internal capacitance Ci 0

    Maximum permissible ambient temperatures depending on

    the temperature class :

    Transmitters of the type of protection flameproof enclosure

    EEx d according to the directions 94 / 9 / EG (ATEX)

    Marking (DIN EN 50 014): II 1/2 G EEx d IIC T6

    EC-Type-Examination Certificate: PTB 00 ATEX 1018

    Ambient temperature range: -40 C ... 75C

    (-40 F ... 167F)

    Transmitters of category 3 for the application in "Zone 2" ac-

    cording to the directions 94 / 9 / EG (ATEX)

    Marking (DIN EN 50 014):II 3 GD 50C EEx nL IIC T6

    II 3 GD 95C EEx nL IIC T4

    EC-Type-Examination Certificate: ZELM 01 ATEX 3059Operating conditions:

    Supply and signal circuit

    (terminals signal + / -): U 45 V

    I 22.5 mA

    Ambient temperature range:

    Temperature class T4 Ta= -40 C ... 85 C

    (-40 F ... 185 F)

    Temperature class T5, T6 Ta= -40 C ... 40 C

    (-40 F ... 104 F)

    Factory Mutual (FM)

    Intrinsically safe: Class I; Division 1; Groups A, B, C, D;

    Class I; Zone 0; Group IIC; AEx ia IIC

    Degree of protection: NEMA Type 4X (indoor or outdoor)

    Permissible ambient temperature range in dependence on

    temperature class

    Explosion-Proof: Class I, Division 1, Groups A, B, C, D

    Class II / III, Division 1, Groups E, F, G

    Degree of protection: NEMA Type 4X (Indoor or outdoor)

    Canadian Standard (CSA) (pending)

    Intrinsically safe,

    Explosion-Proof: Class I, Division 1, Groups A, B, C, D

    Class II, Division 1, Groups E, F, G

    Class III

    Degree of protection: NEMA Type 4X (Indoor or outdoor)

    2010TD as a part of Overflill protectionon vessels for water pol-luting and flammable liquids.

    Flammable liquids: only when combined with Ex-Code 5A3

    Total pressure up to 40 bar / (580 psi)

    Process temperature limits:

    2010TD without remote seal -40C...+85C / (-40F...+185F)

    2010TD with remote seal and capillary tube(s)250C / (482F)

    2010TD with directly mounted remote seal 180C / (356F)

    Approval: Z-65.11-271

    Temperature class

    Ambient

    temperature

    minimum

    Ambient

    temperature

    maximum

    T4-40 C

    -40 F

    +85 C

    +185 F

    T5-40 C

    -40 F

    +40 C

    +104 F

    T6-40 C

    -40 F

    +40 C

    +104 F

    Ambient-

    temperature

    Temperature-

    classImax Pi

    -40 C +85 C

    (-40 F +185 F)0.8 W

    -40 C +70 C

    (-40 F +158 F)1 W

    T5 0.75 W

    T61)

    0.5 W1)

    1)

    not with 2010TC

    Umax= 30 V, Ci= 10.5 nF, Li= 10 H

    T4 200 mA

    -40 C +40 C

    (-40 F +104F)25 mA

    http://ea410v02.pdf/http://ea410v02.pdf/
  • 8/12/2019 Digital Transmitter 2010TD-TA Series

    7/14

    10.2003 Page 7 of 14

    2010TD for Differential Pressure, Flow Rate and Level2010TA for Absolute Pressure 10/15-4.10 EN

    Model ordering number

    Continued on next page.

    Catalog No. Code EUR Delivery

    Transmitter 2010TD for differential pressure measurement V15712- 1.702,- 4 wks

    Transmitter 2010TA for absolute pressure measurement V15713- 1.987,- 4 wks

    CommunicationHART, 4...20 mA H -

    Foundation Fieldbus F +161,- -

    PROFIBUS-PA P +161,- -

    Measuring Ranges dp / pabs

    10 mbar (1kPa / 5 inch H2O) (max. SWP 6 bar / 90 psi) A +237,- + 2 wks

    60 mbar (6kPa / 25 inch H2O) adj. to ... B - -

    400 mbar (40kPa / 160 inch H2O) adj. to ... C - -

    2.5 bar (250kPa / 1000 inch H2O) adj. to ... D - -

    20 bar (2MPa / 300 psi) adj. to ... E - -

    100 bar (10MPa / 1500 psi) adj. to ... G +102,- + 2 wks

    400 mbar abs. only adj. to ... L - + 2 wks

    2.5 bar abs. sensing diaphragm adj. to ... M - + 2 wks

    20 bar abs. made of Hastelloy C adj. to ... N - + 2 wksMeasuring Ranges pabs-sensor (second value, only with 2010TD)

    410 bar / 6000 psi (6 bar / 90 psi with range 10 mbar / 5 in.H2O [Code A]) 1 - -

    without second value (only with 2010TA) 0 - -

    Measuring sensor

    Diaphragm Fill fluid

    Hastelloy C Silicone oil A - -

    Carbon fluoride B +46,- + 2 wks

    316 L stainless steel (1.4435) Silicone oil E +64,- + 3 wks

    (not 2010TA)

    Tantalum Carbon fluoride (only with PTFE O-ring) K +423,- on req.

    (not with range 10 mbar)

    Monel Silicone oil (only with PTFE O-ring) N +130,- + 4 wks

    (not with range 10 mbar)Gold plated Silicone oil (only with PTFE O-ring) T on req. on req.

    (not with range 10 mbar)

    Process flange, HP and LP sides identical

    Material Nominal Pressure (SWP)

    316 L stainless steel (1.4404) 160 bar / 2300 psi 1 - -

    250 bar / 3600 psi 2 +76,- -

    410 bar / 6000 psi 3 +134,- -

    6 bar / 90 psi (range 10 mbar / 5 in.H2O) E - -

    Hastelloy C 160 bar / 2300 psi 7 on req. + 6 wks

    250 bar / 3600 psi 8 on req. + 6 wks

    410 bar / 6000 psi 9 on req. + 6 wks

    6 bar / 90 psi (range 10 mbar / 5 in.H2O) F on req. + 6 wks

    Monel 160 bar / 2300 psi A on req. + 8 wks250 bar / 3600 psi B on req. + 8 wks

    410 bar / 6000 psi C on req. + 8 wks

    6 bar / 90 psi (range 10 mbar / 5 in.H2O) G on req. + 8 wks

    PVDF 10 bar / 150 psi D on req. on req.

    6 bar / 90 psi (range 10 mbar / 5 in.H2O) H on req. on req.

    Process Connection Position of the thread holes for the drain / vent valves

    (scope of delivery: plugs only, no vent valves)

    7/16 UNF and 1/4-18 NPT upright A - -

    female thread side (only in conjunction with Code 395 / 396) B +16,- -

    acc. to DIN 19213 upright C - -

    (M10/M12 and 1/4-18 NPT) side (only in conjunction with Code 395 / 396) D +16,- -

    attached remote seal1) E - -

    http://ea410v02.pdf/http://ea410v02.pdf/
  • 8/12/2019 Digital Transmitter 2010TD-TA Series

    8/14

    Page 8 of 14 10.2003

    2010TD for Differential Pressure, Flow Rate and Level2010TA for Absolute Pressure 10/15-4.10 EN

    Model ordering number

    Continued from preceding page

    Catalog No. Code EUR Delivery

    Bolts Flange O-rings

    Stainless Steel Viton (Temperature Limits: -20 C +120 C) 6 + 19,- -Perbunan 7 - -

    PTFE (PN -20 C) 8 + 31,- -

    EPDM (for NACE application) 9 + 19,- -

    for vacuum proof remote seals (only in conjunction with Code 739) B - -

    Amplifier Housing

    Type Material Electrical connection

    Barrel - Type, Aluminium 1/2 NPT A3) + 15,- +2 wks

    ID Plate, Stainless Steel

    Barrel - Type, Aluminium 1/2 NPT D - -

    ID Plate Plastic One M20 x 1.5 cable gland E - -

    Plug Han 8U (with Profibus PA: plug M122)

    ) F + 53,- -

    Barrel - Type, Stainless Steel 1/2 NPT J + 349,- -

    ID Plate Plastic One M20 x 1.5 cable gland K + 349,- -DIN - Type, Aluminium 1/2 NPT L - -

    ID Plate Plastic One M20 x 1.5 cable gland M - -

    Plug Han 8U (with Profibus PA: plug M122)

    ) N + 53,- -

    Function

    square rooting 224 - -

    Conformity < 0.05 % 5C9 + 215,- -

    Amplifier housing accessories

    Local keys (not with amplifier housing Code J, K) 5C2 + 13,- -

    LCD indicator 5C4 + 106,- -

    LCD indicator, back lit (only with communication HART, 420 mA) 5C5 + 126,- -

    Transient Suppression (not with Ex-Protection "Intrinsically Safe") 5C6 + 134,- +2 wks

    Explosion Protection (acc. to ATEX)

    II 1/2 G EEx d IIC T6 (not with housing Code F or N; without cable gland) 5A1 + 33,- -

    FM Explosion Proof (only with amplifier housing code A) 5A2 + 33,- +2 wks

    II 1/2 GD EEx ia IIC T6 5A3 + 16,- -

    FM Intrinsically Safe 5A4 + 16,- -

    II 3 GD EEx nL IIC T6 (supply without cable gland) 5AC + 16,- -

    Oxygen measurement (O2)

    Free from oil and grease for measuring oxygen (Pmax= 60 bar; Tmax= 60 C) 179 + 105,- +2 wks

    (only when combined with filling liquid Carbon fluoride [measuring sensor Code B],

    material process flange [Code 1 or 7] and flange O-rings Viton [Code 6]

    Overfill protection

    for water polluting liquids; (flammable liquids: only with Ex-Code 5A3) 546 + 66,- -

    for 2010TD and 2010TD with close coupled

    or remotely coupled chemical seal(s) via capillary tube (only with range Code B, C and D)

    Mounting Bracket

    Wall mounting, stainless steel 143 + 39,- -Wall and pipe mounting, stainless steel 144 + 61,- -

    Vent / drain plugs

    Stainless Steel (2 pieces) 395 + 56,- -

    Hastelloy (2 pieces) 396 on req. +6 wks

    Flange Adapter (material: oval flange / bolts)

    Oval flange 1/2-14 NPT(stainless steel / stainless steel) 377 + 116,- -

    Tag-No.

    on Type plate (max. 30 characters) 205 - -

    Stainless Steel Tag Plate (max. 30 characters) 5C8 + 14,- -

    Operating manual (1 pcs. free of charge)

    German each Z2D + 11,- -

    English each Z2E + 11,- -1)

    2010TA: 1 remote seal, 2010TD: 2 remote seals, but with 1 remote seal please indicate the Process connection Code A, B, C or D2)

    without mating plug (female), see Data Sheet 10/63-6.443)

    for Explosion Proof acc. to FM

    http://ea410v02.pdf/http://ea410v02.pdf/
  • 8/12/2019 Digital Transmitter 2010TD-TA Series

    9/14

    10.2003 Page 9 of 14

    2010TD for Differential Pressure, Flow Rate and Level2010TA for Absolute Pressure 10/15-4.10 EN

    Model ordering number

    Continued from preceding page

    Catalog No. Code EUR Delivery

    Certificates

    Factory Certificate EN 10 204 of the instrument design 530 + 16,- -

    Acceptance Test Certificate B EN 10 204 of the conformity, hysteresis 531 + 49,- -

    Acceptance Test Certificate B EN 10 204 of the pressure testing 532 + 49,- -

    Factory Certificate EN 10 204 of process wetted parts 533 + 16,- -

    Acceptance Test Certificate B EN 10 204 of the Cleanliness Stage acc. to DIN 25410 534 + 49,- -

    Accept. Test Certificate B EN 10 204 Helium leakage test of the sensor module (only with Code 150) 535 + 49,- -

    Acceptance Test Certificate B EN 10 204 of the pressure-bearing and process wetted parts with 536 + 127,- +2 wks

    analysis certificates as material verification (minor parts with Factory Certificate acc. to "EN 10 204")

    Factory Certificate EN 10 204 of the pressure-bearing and process wetted parts 537 + 49,- -

    Measuring mechanism leak-tested with helium 150 + 63,- -

    Scope of Delivery Supplied against special order:

    1 Instructions Remote Seal, Power supply e.g. TZN 128 (Data Sheet 18-8.39 EN)1 Instrument socket with plug connector Spare Parts Transmitter 2010TD / 2010TA

    2 Plugs

    http://ea410v02.pdf/http://ea410v02.pdf/
  • 8/12/2019 Digital Transmitter 2010TD-TA Series

    10/14

    Page 10 of 14 10.2003

    2010TD for Differential Pressure, Flow Rate and Level2010TA for Absolute Pressure 10/15-4.10 EN

    Model ordering number

    Customer-specific configuration(Please add to the order)

    Output signal (please pick)

    4...20 mA linearPROFIBUS-PA square root: Zero suppression ............. %

    lin / Sq.Rt. transition point .. ..... ..... . %Foundation Fieldbus characteristic, programmable (please complete Table):

    Electrical damping

    .......... s (0...60 s)

    Output currentMax. output current .......... mA (20...22.5 mA)Min. output current .......... mA (3.5...4 mA)

    Max. alarm current .......... mA (20...22.5 mA)Min alarm current .......... mA (3.5...4 mA)

    Tag-No...........................

    Digital displayDisplayed value ..........................

    Characteristic Input (%) Output (%)

    1 0 0

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    21

    22 100 100

    http://ea410v02.pdf/http://ea410v02.pdf/
  • 8/12/2019 Digital Transmitter 2010TD-TA Series

    11/14

    10.2003 Page 11 of 14

    2010TD for Differential Pressure, Flow Rate and Level2010TA for Absolute Pressure 10/15-4.10 EN

    Dimensional drawings

    4.25(108)

    1.18

    (30)

    ~7.32(186)

    2.40(61)

    2 . 1 3 ( 5 4 )

    3 .78(96)

    1.02

    (26)

    1.625

    (41.3)

    3 . 5 4 ( 9 0 )

    ~4.61(117)

    0 . 3 5 ( 9 ) ~ 2 . 2 8 ( 5 8 )

    ~ 4 . 4 9 ( 1 1 4 )

    3

    .2

    7

    (8

    3

    )

    0 . 79 ( 20 )C l ea r ance f o rCov er rem oval

    + 0 . 9 1 ( 2 3 m m ) w i t hL C D - I n d i c a t o r

    M

    01433

    E

    4.

    T

    IF

    13

    9

    3

    1

    5

    68

    11

    7

    10

    4

    12

    2

    10 Construction

    Transmitter with barrel-type amplifier housingErrors and omissions excepted. Dimensions are in inches (mm).

    Connectionsthisside

    1 1/4-18 NPT female threadfor process connection or sealing plug.

    2 Thread for fixing screws: 7/16-20 UNF, 16mm deep. Minimum

    screw-in length is 12mm, however 15mm with PN410. With aflange according to DIN 19 213: M 10 with PN 6 and PN 160 bar,M 12 with PN 250 and PN 410 bar, minimum screw-in lengthaccording to DIN 19 213.

    3 Electrical connections:M20 x 1.5 cable gland or1/2-14 NPT female threads on both sides orone plug Han 8U.

    4 Type plate. 5 Measuring mechanism plate. 6 Threaded side-mounted entry 1/4-18 NPT for drain / vent valves. 7 Captive screw for key unit cover. 8 Housing rotation stop screw. 9 Blind plug.10 Enclosure cover.11 Tie-on plate, e.g. for tag number (optional).12 Plate, also with key legend.13 Fastener for seal wire (cover and key-board cover)

    http://ea410v02.pdf/http://ea410v02.pdf/
  • 8/12/2019 Digital Transmitter 2010TD-TA Series

    12/14

    Page 12 of 14 10.2003

    2010TD for Differential Pressure, Flow Rate and Level2010TA for Absolute Pressure 10/15-4.10 EN

    Dimensional drawings

    Transmitter with DIN-type amplifier housingErrors and omissions excepted. Dimensions are in inches (mm).

    1 1/4-18 NPT female thread

    for process connection or sealing plug.

    2 Thread for fixing screws: 7/16-20 UNF, 16mm

    deep. Minimum screw-in length is 12mm,

    however 15mm with PN410. With a flange accordingto DIN 19 213: M 10 with PN 6 and PN 160 bar,

    M 12 with PN 250 and PN 410 bar,

    minimum screw-in length according to DIN 19 213.

    3 Electrical connections:

    M20 x 1.5 cable gland sides or

    1/2-14 NPT female threads on both sides or

    one plug Han 8U.

    4 Type plate.

    5 Measuring mechanism plate.

    6 Captive screw for key unit cover

    7 Housing rotation stop screw. 8 Blind plug

    9 Enclosure cover.

    10 Tie-on plate, e.g. for tag number (optional).

    11 Plate, also with key legend.

    12 Fastener for seal wire (cover and key-board cover)

    2

    1

    5

    4

    9

    10

    3

    8

    11 67

    12

    http://ea410v02.pdf/http://ea410v02.pdf/
  • 8/12/2019 Digital Transmitter 2010TD-TA Series

    13/14

    10.2003 Page 13 of 14

    2010TD for Differential Pressure, Flow Rate and Level2010TA for Absolute Pressure 10/15-4.10 EN

    Dimensional drawings

    Errors and omissions excepted. Dimensions are in mm.

    Possible mounting with bracket (optional,Code 143/144) for barrel-type electronic housing

    1 2M01517x1.TIF

    Vertical pipe mounting Horizontal pipe mounting Vertical pipe mountingand transmitter above themounting bracket

    Horizontal pipe mountingand transmitter abovemounting bracket

    M01518x1.TIF M01519x1.TIF

    M01520x1.TIF M01521x1.TIF

    1 U-bolts for pipe mounting. Pipe: 2 (internal-).Permissible pipe-: 53 ... 64mm.Rearrange the brackets for horizontal pipe mounting.

    2 Brackets, hole-: 11mm.

    http://ea410v02.pdf/http://ea410v02.pdf/
  • 8/12/2019 Digital Transmitter 2010TD-TA Series

    14/14

    16

    14

    ABB Automation Products GmbHSchillerstrae 72

    D - 32425 Minden

    Tel. (0571) 830 - 0

    Fax (0571) 830 - 1846

    http://www.abb.com

    Technical revision reservedPrinted in the Fed. Rep. of Germany

    10 / 15 - 4.10 EN 10.2003

    ABB Automation Inc.125 East County Line Road

    Warminster PA

    18974-4995 USA

    Tel. (215) 674- 6693/6320/6777

    Facsmile (215) 674- 7184

    http://www.abb.com