    4TD Series Digital TimerInstruction Manual

    Clipsal Australia Pty Ltd

    4TD Series Digital Timers

    Industrial circuit control is a snap with 4TD Series Digital Timers.Clipsal 4TD Series Digital Timers offer exceptional control of complex electrical circuits associated with

    air conditioning, material handling, lighting, motor starting and process control.

    These double and multifunctional devices have time ranges selectable from one second to 10 hours

    and feature accuracy of 0.5%. All models are extremely compact and simply snap onto DIN rails for fast

    installation. Time delays are easy to set, even after installation, because all adjustments are made on the

    front fascia.

    Functions Terms

    ON D ON delay U Supply voltage

    ON DP ON delay with pulse control S Control input

    OFF D OFF delay R Switched output

    INT Interval timer

    INT P Interval with pulse control

    INT OFF P Interval with OFF pulse controlAPR Asymmetric pulse recycler

    AWR Asymmetric work recycler

    SPR Symmetric pulse recycler

    SWR Symmetric work recycler

    IC Inhibit controller

    MFMultifunction - includes functionsON D, OFF D, INT, ON DP, INT P, INT OFF P, SPR and IC

    Clipsal Cat No. Function Contacts4TD1 ON D + OFF D 1 CO

    4TD2 ON D + INT 1 CO

    4TD3 SPR + SWR 1 CO

    4TD4 APR + AWR 2 CO

    4TD5 MF 1 CO

    4TD6 MF 2 CO

    ContactsNumber of contacts 1 CO or 2 CO

    Contact type Single throw

    Rated voltage 250V a.c.

    Rated current 8A

    Rated breaking capacity 2000 VA (resistive load)

    Contact material AgNi.

    NOTE:Timers not suitable for switching fluorescent loads without additional Clipsal Contactor.

    Selectable Time Ranges

    1 second 10 seconds 1 minute 10 minutes 1 hour 10 hours

  • 8/11/2019 Digital Timers

    3/43 of 4 Clipsal Australia Pty Ltd

    4TD Series Digital TimerInstruction Manual

    Installation Instructions

    1. Select appropriate timer for application.

    2. Fit timer to DIN rail.

    3. Connect power supply, wire switch control input, where appropriate, load to switch terminals.

    4. Adjust TIME dial to appropriate number, set ROTARY DIAL SELECTOR switches to required setting (x1/

    x10 time; seconds, minutes or hours), set ROTARY FUNCTION SELECTOR switch to required setting.

    NOTE:Function on 4TD4 set by connecting a wire loop.Example:4TD1 (ON D) on delay. To delay switching load by eight seconds, adjust red time dial to .8 and set

    DIP switches as follows:

    10

    s

    r

    TIME FUNC

    .2.4

    .6

    .8

    TIME

    Function Diagram Description

    ON DON delay

    On application of the supply voltage, the timer starts to run.After the time t has elapsed, the relay switches ON.

    ON DPON delay with

    pulse control

    Supply voltage must remain ON. Function is controlled by the controlinput. When the control input goes ON, the timer starts to run. Afterthe time t has elapsed, the relay switches ON. When the controlinput goes OFF, the timing run is broken and the relay trips out. Thisfunction enables control of switching delays by a small current - forexample via a sensor.

    OFF DOFF delay

    Supply voltage must remain ON. Function is controlled by the controlinput. When the control input goes ON, the relay turns ON. When thecontrol input goes OFF, the timer starts to run. After the time t haselapsed, the relay switches OFF. If the control input goes back to ONbefore the time t expires, the time already elapsed is cancelled andrestarts from zero on the next cycle.

    INTInterval timer

    On application of the supply voltage, the relay immediately switchesand the timer starts to run. After the time t has elapsed, the relayswitches OFF.

    INT PInterval with

    pulse control

    Supply voltage must remain ON. Function is controlled by the controlinput. On a signal from the control input independent of duration thissignal pulse is converted to a fixed duration delay. Timing starts onthe positive going edge of control input, the timer starts to run andthe relay switches ON immediately. The relay turns OFF after thetime t has elapsed. During the timing period, changes to the controlinput are ineffective.

    INT OFF PInterval with

    OFF pulse

    control

    Supply voltage must remain ON. Function is controlled by the controlinput. When the control input goes ON, a defined pulse length isgenerated. Starting at the negative going edge of the control input,the relay switches ON and trips at the end of the timing run. Duringthe time period, changes on the control input are ineffective.

    SPRSymmetrical

    recycler, pause

    start

    On application of the supply voltage, the relay cycles pulse startbetween ON and OFF for the preset time, beginning with theON phase.

    SWRSymmetrical

    recycler, start

    On application of the supply voltage, the relay cycles pulse betweenON and OFF for the preset time, beginning with the ON phase.

  • 8/11/2019 Digital Timers

    4/4

    CLIPCOM/17619 July 2008F231/04

    Clipsal Australia Pty Ltd reserves the right to change specifications,

    modify designs and discontinue items without incurring obligationand whilst every effort is made to ensure that descriptions,specifications and other information in this catalogue are correct, nowarranty is given in respect thereof and the company shall not beliable for any error therein.

    Clipsal Australia Pty Ltd. The identified trademarks and copyrightsare the property of Clipsal Australia Pty Ltd unless otherwise noted.

    Product of Clipsal Australia Pty LtdA member of Schneider Electric

    Contact us: clipsal.com/feedback

    National Customer Care Enquiries:

    Tel 1300 2025 25

    Fax 1300 2025 56

    clipsal.com

    APRAsymmetrical

    recycler, pulse

    start

    On application of the supply voltage, the relay cycles between ONand OFF for the preset time, beginning with the OFF phase. The ONand OFF times are separately adjustable.

    AWRAsymmetrical

    recycler, pulse

    start

    On application of the supply voltage, the relay cycles between ONand OFF for the preset time, beginning with the ON phase. The ONand OFF times are separately adjustable.

    ICInhibit

    controller

    On application of the supply voltage, the relay switches ON,regardless of the state of the control input at this point in time. Afterthat, the first positive going edge of the control input starts the timer.Each subsequent positive going edge (provided that it occurs beforethe timing run is completed) resets the timer for a further period.At the end of the timing run, the relay switches OFF. The device isthen inhibited against further control inputs. Resetting can only occurby removing and reconnecting the supply.

    MFMultifunction

    Include functions: ON D, ON D P, INT, INT P, OFF P, INT OFF P,SPR, and IC.

    Technical DataDesign according to OVE-EN 60669

    Rated voltage 24V a.c./d.c.; 110 to 240 V~ a.c.

    Admissible voltage range 10%

    Time ranges selectable 1s - 10 hr

    Additional adjustment by potentiometer 5 - 100%

    Time delay range 0,05 s - 1 hr

    Accuracy 0,5%

    Reset time 100 ms

    Repeat accuracy to full scale value 0,5%

    Minimum impulse duration 50 ms

    Ambient operating temperature -25 - +55C

    Temperature coefficient 0,01 %/K

    Degree of protection IP40

    Mechanical Data

    Frame size 45mm

    Socket size 87.5mm

    Module width 17.5mm (1 CO), 35mm (2 CO)Mounting Quick fastening with 2 lock-in positions on DIN rail EN50022

    Upper and lower terminals Lift terminals

    Terminal protection Finger and hand touch safe

    Terminal capacity 1-6mm

    NOTE:Segregation requirements AS/NZS 3000 Wiring Rules