ALPS™ALPS™Advanced Line Protection SystemAdvanced Line Protection System

Page 2: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

2

Modified Fourier Calculation

ALPS Advanced Line Protection System

• High Speed Sampling

• Phaselet Calculation

• Variable Window

• Digital Mimic

Page 3: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

High Speed Sampling

ALPS Advanced Line Protection System

-20

-15

-10

-5

0

5

10

0 4 8 12 16 20 24 28 32 36 40PHSLT

# 4

16

SAMPLES

PHSLT

# 8

32

SAMPLES

EXECUTEPHASELET

CALCULATIONAND PROTECTIONALGORITHMS

PHSLT

# 1PHSLT

# 2

PHSLT

# 3

PHSLT

# 5

PHSLT

# 6

PHSLT

# 7

PHSLT

# 9

PHSLT

# 10

Page 4: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

4

Discrete Fourier Transform

ALPS Advanced Line Protection System

v t V t

VrealN

Vkk

N

VimagN

Vkk

N

peak

k

N

k

N

( ) cos( )

( ) [ cos( )]

( ) [ sin( )]

= • +

= • • • •∑

= • − • • •∑

=

=

ω φ

π

π

22

22

0

1

0

1

Page 5: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

5

Full Cycle Fourier Transform

ALPS Advanced Line Protection System

-20

-15

-10

-5

0

5

10

15

20

0 64 128 192 256 320

WINDOW 1WINDOW 2

WINDOW 3

Page 6: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

6

Phaselet Definition

ALPS Advanced Line Protection System

• Phaselets are partial sums of the products of

the waveform samples and the sine/cosine

coefficients.

• Input signals are sampled 64 times per cycle;

protection algorithms are executed 16 times

per cycle.

• Groups of phaselets may be added together

and transformed to create a phasor.

Page 7: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

7

Phaselet Calculation

ALPS Advanced Line Protection System

Phaselet al C X

Phaselet aginary S X

Where

p kk p P P

p P

k

pk p P P

p P

k k

Re

Im

:

= ∑ ⋅

= −∑ ⋅

=

= ⋅ − +

= ⋅ − +

⋅1

1

C , S Sine and Cosine Coefficients

p = phaselet index: there are N / P phaselets per cycle

P = the number of phaselets per cycle

X = kth sample of the input signal

k k

k

Page 8: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

8

-20

-15

-10

-5

0

5

10

0 4 8 12 16 20 24 28 32 36 40PHSLT

# 4

16

SAMPLES

PHSLT

# 8

32

SAMPLES

EXECUTEPHASELET

CALCULATIONAND PROTECTIONALGORITHMS

PHSLT

# 1PHSLT

# 2

PHSLT

# 3

PHSLT

# 5

PHSLT

# 6

PHSLT

# 7

PHSLT

# 9

PHSLT

# 10

Variable Window

ALPS Advanced Line Protection System

Page 9: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

9

Phasor Calculation

ALPS Advanced Line Protection System

Phasor al

Phasor aginary

T nW T n W

T n W T n W

PhasorSum al

PhasorSum aginary

n

n

RR RI

IR II

n

n

Re

Im

( , ) ( , )

( , ) ( , )

Re

Im

=

Phaselets are converted to phasors by the following:

Where:

PhaseletSum al Phaselet aln p

p nW

P

n

Re Re=

= − +

∑1

PhaseletSum aginary Phaselet aginaryn p

p nW

P

n

Im Im= ∑= − +1

n = Phasor index (N/P) W = Window size in samples

Page 10: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

10

Phasor Calculation

ALPS Advanced Line Protection System

For a one cycle window, the Fourier calculation becomes:

P h a so r a lN

P h a s e l e t a l

P h a so r a g in a ryN

P h a s e l e t a g in a ry

n p

p nN

P

n

n p

p nN

P

n

R e R e

Im Im

= ⋅ ∑

= ⋅ ∑

= − +

= − +

2

2

1

1

Page 11: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

11

Variable Window Fourier Transform

ALPS Advanced Line Protection System

PRE-FAULT

ONE CYCLE

WINDOW

VARIABLE WINDOW

-20

-15

-10

-5

0

5

10

15

0 64 128 192 256 320

Page 12: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

12

Mimic Algorithm

ALPS Advanced Line Protection System

Time Domain:

Sampled Data:

IZ t I t Rd

dtI t L( ) ( ) ( ( ))= • + •

IZkI k I k

RI k I k

L( )( ( ) ( )) ( ( ) ( ))+ = + + • + + − •δ δ δ

δ2 2

Page 13: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

13

EXAMPLES OF

ADAPTIVE PROTECTION

ALGORITHMS

ALPS Advanced Line Protection System

Page 14: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

14

Adaptive Polarizing Memory

Remote line end three phase faults:

Reverse zero voltage faults:

ZLZS3 PH

3 PH

ZS = 19 ZL

Vr = 0.05 Rated

Vr = 0

ALPS Advanced Line Protection System

Page 15: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

15

Adaptive Polarizing Memory

Extend memory time if:

• Voltage at the relay is less than 10% of rated.

AND

• Any distance measuring function is picked up.

ALPS Advanced Line Protection System

Page 16: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

16

Adaptive Polarizing Memory

ALPS Advanced Line Protection System

Reset memory if:

• Voltage at the relay is greater than 10% of rated.

AND

• Distance measuring function resets.

Page 17: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

17

Variable Reach Zone 1

Z LINE

FINAL REACH

INITIAL REACH

ALPS Advanced Line Protection System

Page 18: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

18

Variable Reach Zone 1

Zone 1 reach is set to 90 % of ZL.

WINDOW SIZE % OF SET REACH

1/16 Cycle 0 (can not operate)

1/8 Cycle 33%

3/16 Cycle 65%

1/4 Cycle 75%

5/16 Cycle 83%

1/2 Cycle 90%

> 1/2 Cycle 100%

ALPS Advanced Line Protection System

Page 19: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

19

Adaptive Reactive Unit Supervision

Reactance type distance functions require

supervision to prevent operation on normal load

flow.

The traditional approach is to use a fixed

resistive blinder, or a fixed reach mho function.

ALPS Advanced Line Protection System

Page 20: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

20

Adaptive Reactive Unit Supervision

X -

ZL min

X' - ZL max

Fixed

mho

Fixed

Blinder

Adaptive

mho

Reactance

Unit

Adaptive

Blinder

ALPS Advanced Line Protection System

Page 21: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

21

EVALUATION OF

DISTANCE RELAY

OPERATING SPEED

ALPS Advanced Line Protection System

Page 22: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

22

Modeled System

Protected Line

Parallel Line

Z1 = 6.0 ohms @ 86 degZ0 = 18.3 ohms @ 76 deg

Z1S = 1.5 ohms @ 86 degZ0S = 1.5 ohms @ 86 deg

Z1S = 1.5 ohms @ 86 degZ0S = 1.5 ohms @ 86 deg

ALPS Advanced Line Protection System

Page 23: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

23

PC Simulation Trip Times

0

5

10

15

20

0 25 50 75

% of Line

Tim

e (mS)

ALPS Advanced Line Protection System

Page 24: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

24

MPS Test Results

0

5

10

15

20

0 25 50 75

% of Line

Tim

e (mS)

ALPS Advanced Line Protection System

Page 25: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

25

The ALPS Advanced Line Protection

System gives you the protection

choices you need. Whether you’re

protecting compensated or

uncompensated lines; require single

phase tripping or three phase tripping,

with or without reclosing, its available.

ALPS Advanced Line Protection System

ALPS Advanced Line Protection System

Page 26: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

26

APPLICATION

• Distance protection for EHV lines

• Series compensated lines

• High speed tripping (half cycle)

• Single and three phase tripping

Providing complete transmission line protection,

ALPS is a multi-function digital protective relay

system intended to provide distance protection for

HV or EHV transmission lines.

ALPS Advanced Line Protection System

Page 27: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

27

Single Line Diagram

ALPS Advanced Line Protection System

Page 28: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

28

PROTECTION

• Four zones of distance protection

• Pilot protection, step distance backup

• Out of step blocking and tripping

• Phase instantaneous overcurrent

• Ground instantaneous overcurrent

• Ground time overcurrent backup

• Over and under voltage functions

ALPS Advanced Line Protection System

Page 29: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

29

CONTROL

• Optional four shot recloser

• Configurable inputs and outputs

• Fully configurable relay logic

ALPS Advanced Line Protection System

Page 30: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

30

INPUTS/OUTPUTS

All contact converter inputs and all contact outputs

(except for alarms) in ALPS are configurable by the

user.

• 8 configurable inputs, or 12 for single

phase tripping

• 15 configurable outputs, or 20 for single

phase tripping

ALPS Advanced Line Protection System

Page 31: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

31

RMS METERING

• Current (Ia, Ib, Ic, In)

• Voltage (Va, Vb, Vc)

• Watts (3 phase)

• Vars (3 phase)

• Frequency

ALPS Advanced Line Protection System

Page 32: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

32

MONITORING

• fault location provided by a single ended

• fault location algorithm

• trip circuit monitor

• self test diagnostics

• event reporting of last 100 events

• fault reports

• high resolution oscillography

ALPS Advanced Line Protection System

Page 33: Digital Mimic · ALPS is a multi-function digital protective relay system intended to provide distance protection for HV or EHV transmission lines. ALPS Advanced Line Protection System

33

USER INTERFACE

• 20 button keypad and 4 line LCD display

• RS232 serial port on front of unit

• RS232 and RS485 ports on rear of unit

• communication software

• IRIG-B input for time synchronization

ALPS Advanced Line Protection System