14
DGP01361AAA PROPRIETARY INFORMATION THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF SPIRENT COMMUNICATIONS PLC. EXCEPT AS SPECIFICALLY AUTHORISED IN WRITING BY SPIRENT COMMUNICATIONS PLC, THE HOLDER OF THIS DOCUMENT SHALL KEEP ALL INFORMATION CONTAINED HEREIN CONFIDENTIAL AND SHALL PROTECT SAME IN WHOLE OR IN PART FROM DISCLOSURE AND DISSEMINATION TO ALL THIRD PARTIES TO THE SAME DEGREE IT PROTECTS ITS OWN CONFIDENTIAL INFORMATION. © COPYRIGHT SPIRENT COMMUNICATIONS PLC 2017. N.B. Only documents bearing the Document Status ‘APPROVED SPIRENT DOCUMENTATION’ in the panel below are deemed official literature. This Issue Originated by: Approved by: Document Status: Stuart Miller James Spalding APPROVED SPIRENT DOCUMENTATION Title: Technical Writer Title: Staff Firmware Engineer Issue 1-02, Date of Issue: 15 September 2017 Page 1 of 14 SETUP GUIDELINES FOR USING SIMREMOTE WITH A GSS7000 OR GSS9000-SERIES SIGNAL GENERATOR ABSTRACT This document is a guide to configuring SimREMOTE to communicate with the Embedded Host in a GSS7000 signal generator; or the C50r SimGEN Host of a GSS9000-series signal generator RECORD OF ISSUE

DGP01361AAA SETUP GUIDELINES FOR USING SIMREMOTE …...DGP01361AAA DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017 Page 2 of 14 Issue

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: DGP01361AAA SETUP GUIDELINES FOR USING SIMREMOTE …...DGP01361AAA DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017 Page 2 of 14 Issue

DGP01361AAA

PROPRIETARY INFORMATION THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF SPIRENT COMMUNICATIONS PLC. EXCEPT AS SPECIFICALLY AUTHORISED IN WRITING BY SPIRENT COMMUNICATIONS PLC, THE HOLDER OF THIS DOCUMENT SHALL KEEP ALL INFORMATION CONTAINED HEREIN CONFIDENTIAL AND SHALL PROTECT SAME IN WHOLE OR IN PART FROM DISCLOSURE AND DISSEMINATION TO ALL THIRD PARTIES TO THE SAME DEGREE IT PROTECTS ITS OWN CONFIDENTIAL INFORMATION. © COPYRIGHT SPIRENT COMMUNICATIONS PLC 2017.

N.B. Only documents bearing the Document Status ‘APPROVED SPIRENT DOCUMENTATION’ in the panel below are deemed official literature.

This Issue Originated by:

Approved by:

Document Status:

Stuart Miller

James Spalding

APPROVED SPIRENT DOCUMENTATION

Title: Technical Writer

Title: Staff Firmware Engineer

Issue 1-02, Date of Issue: 15 September 2017 Page 1 of 14

SETUP GUIDELINES FOR USING SIMREMOTE WITH A GSS7000 OR GSS9000-SERIES SIGNAL GENERATOR

ABSTRACT

This document is a guide to configuring SimREMOTE to communicate with the Embedded Host in a GSS7000 signal generator; or the C50r SimGEN Host of a GSS9000-series signal generator

RECORD OF ISSUE

Page 2: DGP01361AAA SETUP GUIDELINES FOR USING SIMREMOTE …...DGP01361AAA DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017 Page 2 of 14 Issue

DGP01361AAA

DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017

Page 2 of 14

Issue Date Author Reason for Change

1-02 15 Sep. 17 SDM Bug 15461 - add 7000

1-01 8 Dec 2014 SDM Bug 11133 - application name and miscellaneous corrections

1-00 20 Nov. 14 BT First Issue

Page 3: DGP01361AAA SETUP GUIDELINES FOR USING SIMREMOTE …...DGP01361AAA DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017 Page 2 of 14 Issue

DGP01361AAA

DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017

Page 3 of 14

TABLE OF CONTENTS 1.1 SCOPE & APPLICABILITY ............................................................................................................ 4 1.2 REFERENCED DOCUMENTS ...................................................................................................... 4 2 INTRODUCTION ................................................................................................................................. 4 2.1 GSS7000 SIGNAL GENERATOR ................................................................................................. 5 2.2 GSS9000-SERIES SIGNAL GENERATOR ................................................................................... 6 3 DIRECT POINT TO POINT REMOTE SETUP ................................................................................... 7 3.1 SETTINGS FOR THE SIMREMOTE PC ....................................................................................... 7 3.2 SETTINGS FOR THE EMBEDDED HOST (GSS7000 SIGNAL GENERATOR) .......................... 8 3.3 SETTINGS FOR THE C50R SIMGEN HOST (GSS9000-SERIES SIGNAL GENERATOR) ........ 9 4 RUNNING A SCENARIO USING REMOTE COMMANDS ............................................................... 10 4.1 GSS7000 SIGNAL GENERATOR (EMBEDDED HOST) ............................................................ 10 4.2 GSS9000-SERIES SIGNAL GENERATOR (C50R SIMGEN HOST) .......................................... 11 5 REMOTE SETUP USING A CORPORATE LAN .............................................................................. 13

LIST OF FIGURES

Figure 1 SimREMOTE - interconnections to the GSS7000 ............................................................................... 5 Figure 2 SimREMOTE - interconnections to the C50r SimGEN Host ................................................................ 6 Figure 3 Local Area Connection Properties ....................................................................................................... 7 Figure 4 Configuring IP Settings ........................................................................................................................ 8 Figure 5 Host controller utility ............................................................................................................................. 9 Figure 6 Embedded Host rear panel Ethernet ports ........................................................................................ 10 Figure 7 TCP/IP address dialog in Socket_string_Send.exe ........................................................................... 11 Figure 8 C50r SimGEN Host Revision A rear panel Ethernet ports ................................................................. 11 Figure 9 C50r SimGEN Host Revision B rear panel Ethernet ports ................................................................. 11 Figure 10 Socket_string_send utility ................................................................................................................ 12 Figure 11 Network Port Information ................................................................................................................. 13

Page 4: DGP01361AAA SETUP GUIDELINES FOR USING SIMREMOTE …...DGP01361AAA DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017 Page 2 of 14 Issue

DGP01361AAA

DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017

Page 4 of 14

general

1.1 SCOPE & APPLICABILITY

This document describes the steps to connect a SimREMOTE PC with a simulator using a GSS7000 (which uses an Embedded Host) or a GSS9000-series signal generator with a C50r SimGEN Host.

1.2 REFERENCED DOCUMENTS

a) DGP00792AAA SimREMOTE User Manual b) DGP00686AAA SimGEN user manual c) DGP01430AAA GSS7000 user manual d) DGP01446AAA SimTEST user manual

2 INTRODUCTION The following sections describe using the signal generators with remote commands.

Page 5: DGP01361AAA SETUP GUIDELINES FOR USING SIMREMOTE …...DGP01361AAA DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017 Page 2 of 14 Issue

DGP01361AAA

DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017

Page 5 of 14

2.1 GSS7000 SIGNAL GENERATOR

Note: internally, the Embedded Host uses the local IP addresses 192.168.25.n and 192.168.26.n Spirent recommends you ensure any LAN you use, including a corporate LAN, does not use these IP Addresses The TCP/IP settings for a simulator using a GSS7000 signal generator are more complex than a Windows-only system, due to the nature of its Embedded Host; reference c) gives more details on the Embedded Host. This document lists the steps to configure the Embedded Host and SimREMOTE PC to enable remote control of the GSS7000 signal generator. Figure 1 shows the typical interconnections between a SimREMOTE PC and the Embedded Host of a GSS7000 signal generator. Notice if you want to use RS-232, you must use the USB to RS232 adapter Spirent supplies.

Figure 1 SimREMOTE - interconnections to the GSS7000

Page 6: DGP01361AAA SETUP GUIDELINES FOR USING SIMREMOTE …...DGP01361AAA DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017 Page 2 of 14 Issue

DGP01361AAA

DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017

Page 6 of 14

2.2 GSS9000-SERIES SIGNAL GENERATOR

Note: internally, the C50r SimGEN Host uses the local IP addresses 192.168.25.n and 192.168.26.n Spirent recommends you ensure any LAN you use, including a corporate LAN, does not use these IP Addresses The TCP/IP settings for a simulator using a GSS9000-series signal generator with a C50r SimGEN Host are more complex than a Windows-only system, due to the nature of the C50r SimGEN Host; reference b) gives more details on the C50r SimGEN Host. This document lists the steps to configure a C50r SimGEN Host and SimREMOTE PC to enable remote control of the GSS9000-series signal generator. Figure 2 shows the typical interconnections between a SimREMOTE PC and the C50r SimGEN Host and the use of adapters to send remote commands over IEEE-488 or RS-232.

Figure 2 SimREMOTE - interconnections to the C50r SimGEN Host

Page 7: DGP01361AAA SETUP GUIDELINES FOR USING SIMREMOTE …...DGP01361AAA DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017 Page 2 of 14 Issue

DGP01361AAA

DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017

Page 7 of 14

3 DIRECT POINT TO POINT REMOTE SETUP This section describes setting up a direct, remote connection between the SimREMOTE PC, the Embedded Host in the GSS7000, or the C50r SimGEN Host.

3.1 SETTINGS FOR THE SIMREMOTE PC

In the SimREMOTE PC:

1. Go to Start Menu->Control Panel->Network and Sharing Center.

2. Click Change adapter settings in the left-hand area to display the Local Area and Wireless connections on the SimREMOTE PC.

3. Select the Local Area Connection you will use to connect directly to the Embedded Host

(GSS7000 signal generator) or the C50r SimGEN Host (GSS9000-series signal generator), right-click and select Properties to see Figure 3:

Figure 3 Local Area Connection Properties

4. Select Internet Protocol Version 4 (TCP/IPv4), then click Properties to open the dialog in

Figure 4:

Page 8: DGP01361AAA SETUP GUIDELINES FOR USING SIMREMOTE …...DGP01361AAA DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017 Page 2 of 14 Issue

DGP01361AAA

DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017

Page 8 of 14

Figure 4 Configuring IP Settings

5. Select the option Use the following IP address:

The IP address of the SimREMOTE PC you enter should be a private, or local, address which is 192.168.x.x. The Embedded Host (GSS7000 signal generator), or the C50r SimGEN Host (GSS9000-series signal generator) must have an IP address that is compatible with the IP address of the SimREMOTE PC. This IP address must be:

• The same where the subnet mask is 255

• Different where the subnet mask is 0

6. Click OK twice to complete setting up the SimREMOTE PC.

3.2 SETTINGS FOR THE EMBEDDED HOST (GSS7000 SIGNAL GENERATOR)

On the Embedded Host:

1. Log in to the gpssim account 2. Navigate to the folder D:\posapp\software\<version>\gui\Host_control and double-click

on the file host_control.exe Notice <version> will depend on the installed version of PosApp

3. The Host controller utility opens

4. Set the IP address of the Embedded Host rear panel port REMOTE by selecting SimREMOTE IP - SimREMOTE, see Figure 5, then typing the IP Address you want to use.

Page 9: DGP01361AAA SETUP GUIDELINES FOR USING SIMREMOTE …...DGP01361AAA DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017 Page 2 of 14 Issue

DGP01361AAA

DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017

Page 9 of 14

Figure 5 Host controller utility

5. Click Set

6. To correctly configure the IP Address of this port, follow the instruction in the prompt and

shut down and restart the Embedded Host. Note: You must use “Shut down” from Windows to correctly apply the new IP settings. Do not use Windows “Restart” as this will not correctly configure the Embedded Host.

3.3 SETTINGS FOR THE C50R SIMGEN HOST (GSS9000-SERIES SIGNAL GENERATOR)

On the C50r SimGEN Host:

1. Log in to the gpssim account 2. Navigate to the folder D:\posapp\software\<version>\gui\Host_control and double-click

on the file host_control.exe Notice <version> will depend on the installed version of PosApp

3. Set the IP address of the C50r SimGEN Host rear panel port REMOTE by selecting

SimREMOTE IP - SimREMOTE, see Figure 5, then typing the IP Address you want to use. 4. Click Set

5. To correctly configure the IP Address of this port, follow the instruction in the prompt and

shut down and restart the C50r SimGEN Host. Note: You must use “Shut down” from Windows to correctly apply the new IP settings. Do not use Windows “Restart” as this will not correctly configure the C50r SimGEN Host.

Page 10: DGP01361AAA SETUP GUIDELINES FOR USING SIMREMOTE …...DGP01361AAA DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017 Page 2 of 14 Issue

DGP01361AAA

DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017

Page 10 of 14

4 RUNNING A SCENARIO USING REMOTE COMMANDS This section covers running a scenario on the GSS7000 and GSS9000-series signal generators.

4.1 GSS7000 SIGNAL GENERATOR (EMBEDDED HOST)

Use an Ethernet cable to connect the Ethernet port of your SimREMOTE PC (the Ethernet port whose IP Address you set in section 3.2) to the rear panel port REMOTE, see Figure 6, which shows the correct Ethernet port circled in red.

Figure 6 Embedded Host rear panel Ethernet ports

Check you can send remote messages:

1. On the Embedded Host, load a scenario in SimGEN, see reference b).

Notice SimGEN automatically enables Ethernet Remote messages.

2. Navigate to the Socket_string_send utility in D:\posapp\software\<version>\gui Notice <version> will depend on the installed version of PosApp

3. Open the utility so you can send Remote messages.

4. In the utility, Select Options->TCP/IP address to set the IP address of the Embedded Host, see Figure 7:

Page 11: DGP01361AAA SETUP GUIDELINES FOR USING SIMREMOTE …...DGP01361AAA DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017 Page 2 of 14 Issue

DGP01361AAA

DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017

Page 11 of 14

Figure 7 TCP/IP address dialog in Socket_string_Send.exe

5. Type the IP Address you want to use in the Hostname area

6. Click SimGEN remote control to set the Port number

7. Click OK

8. In the Socket_string_send utility send the remote command RU, which will remotely

run the scenario currently open in SimGEN, see Figure 10. Type ‘RU’ in the area next to Send, then click Send

4.2 GSS9000-SERIES SIGNAL GENERATOR (C50R SIMGEN HOST)

Use an Ethernet cable to connect the Ethernet port of your SimREMOTE PC (the Ethernet port whose IP Address you set in section 3.3) to the rear panel port REMOTE of your C50r SimGEN Host. Figure 8 and Figure 9 show the rear panel ports for Revisions A and B of the C50r SimGEN Host, with the REMOTE circled in red.

Figure 8 C50r SimGEN Host Revision A rear panel Ethernet ports

Figure 9 C50r SimGEN Host Revision B rear panel Ethernet ports

Check you can send remote messages:

Page 12: DGP01361AAA SETUP GUIDELINES FOR USING SIMREMOTE …...DGP01361AAA DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017 Page 2 of 14 Issue

DGP01361AAA

DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017

Page 12 of 14

1. On the C50r SimGEN Host, load a scenario in SimGEN, see reference b).

Notice SimGEN automatically enables Ethernet Remote messages.

2. Navigate to the Socket_string_send utility in D:\posapp\software\<version>\gui Notice <version> will depend on the installed version of PosApp

3. Open the utility so you can send Remote messages.

4. In the utility, Select Options->TCP/IP address to set the IP address of the C50r SimGEN Host, see Figure 7:

5. Type the IP Address you want to use in the Hostname area

6. Click SimGEN remote control to set the Port number

7. Click OK

8. In the Socket_string_send utility send the remote command RU, which will remotely

run the scenario currently open in SimGEN, see Figure 10. Type ‘RU’ in the area next to Send, then click Send

Figure 10 Socket_string_send utility

Reference a) details the available remote commands. As SimGEN receives the remote command and actions it, the right-hand area of the socket_string_send utility returns the status of the scenario, see Figure 10. Table 1 defines the returned status number:

Status number Description 0 No scenario loaded 1 Loading 2 Ready

Page 13: DGP01361AAA SETUP GUIDELINES FOR USING SIMREMOTE …...DGP01361AAA DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017 Page 2 of 14 Issue

DGP01361AAA

DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017

Page 13 of 14

Status number Description 3 Arming 4 Armed 5 Running

Table 1 Scenario status numbers and their meaning

You can send a “NULL” command at any time to query the status of the scenario.

5 REMOTE SETUP USING A CORPORATE LAN Notice in this section ‘Host’ refers to either the Embedded Host in a GSS7000 signal generator; or the C50r SimGEN Host used with a GSS9000-series signal generator. To set up a remote configuration for use over a corporate LAN:

1. Connect an Ethernet cable from your corporate LAN to the rear panel port REMOTE, see Figure 6, Figure 8 or Figure 9 depending on your Host. Each of these figures shows the correct Ethernet port circled in red

2. Shutdown, and reboot the Host. You must use “Shut down” from Windows, do not use Windows “Restart” as this will not correctly configure the Host

3. Once the Host has restarted and Windows has opened, navigate to

D:\posapp\software\<version>\gui\C50_control and double-click host_control.exe to open the Host controller utility, see Figure 5. Notice <version> will depend on the installed version of PosApp

4. Click Read Network Port Info to display a table of IP addresses and descriptions, Figure 11 gives

an example:

Figure 11 Network Port Information

Page 14: DGP01361AAA SETUP GUIDELINES FOR USING SIMREMOTE …...DGP01361AAA DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017 Page 2 of 14 Issue

DGP01361AAA

DGP01361AAA Setup Guidelines for SimREMOTE with a GSS9000 Issue 1-02, 15 September 2017

Page 14 of 14

5. Locate Ethernet Device-posapp_bridge1.

6. The corresponding IP address gives the IP address to use for remote control of SimGEN (using the Host rear panel port REMOTE) Now move to the SimREMOTE PC:

1. Go to the Windows start menu and open a Command Prompt window

2. At the prompt, type ‘ping’ followed by the IP address you found for posapp-bridge1, see Figure 11. This confirms you can access the Host rear panel port REMOTE over your corporate LAN.

Setting up a SimREMOTE PC to send remote commands over TCP/IP to the Embedded Host (GSS7000), or the C50r SimGEN Host (GSS9000-series signal generator), is now complete. Reference a) describes setting up SimGEN for remote control.